3695 lines
113 KiB
Plaintext
3695 lines
113 KiB
Plaintext
-- powertek
|
|
-- MIB for 1phase Products
|
|
--
|
|
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) powertek(42610)
|
|
-- product(1) pdu(4) sps(4)
|
|
-- ==============================================================================================
|
|
---
|
|
--- Revision History
|
|
---
|
|
--- v0.10 14-Feb-2014 ChainLiu
|
|
--- v0.11 11-Mar-2014 JimmyYang
|
|
--- v0.12 01-Sep-2014 ChainLiu/
|
|
--- v0.13 24-Nov-2014 ChainLiu
|
|
--- v0.14 12-Aug-2015 ChainLiu
|
|
-- ==============================================================================================
|
|
|
|
SPSv1-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
enterprises
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
DisplayString
|
|
FROM RFC1213-MIB
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
powertek OBJECT IDENTIFIER ::= { enterprises 42610 }
|
|
product OBJECT IDENTIFIER ::= { powertek 1 }
|
|
pdu OBJECT IDENTIFIER ::= { product 4 }
|
|
sps OBJECT IDENTIFIER ::= { pdu 4 }
|
|
pduObjects OBJECT IDENTIFIER ::= { sps 1 }
|
|
pduTraps OBJECT IDENTIFIER ::= { sps 2 }
|
|
|
|
pduIdent OBJECT IDENTIFIER ::= { pduObjects 1 }
|
|
pduNetwork OBJECT IDENTIFIER ::= { pduObjects 2 }
|
|
pduSystem OBJECT IDENTIFIER ::= { pduObjects 3 }
|
|
pduSNMP OBJECT IDENTIFIER ::= { pduObjects 4 }
|
|
pduEmail OBJECT IDENTIFIER ::= { pduObjects 5 }
|
|
pduPwrMonitoring OBJECT IDENTIFIER ::= { pduObjects 6 }
|
|
pduEnvMonitoring OBJECT IDENTIFIER ::= { pduObjects 7 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduIdent
|
|
--
|
|
-- pdu Identification Group
|
|
--
|
|
-- ===========================================================================
|
|
pduIdentAgentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The firmware version of the device."
|
|
::= { pduIdent 1 }
|
|
|
|
pduIdentSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A Model of this device."
|
|
::= { pduIdent 2 }
|
|
|
|
|
|
pduNetworkTcpip OBJECT IDENTIFIER ::= { pduNetwork 1 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduNetworkTcpip
|
|
--
|
|
-- Network Configuration Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
|
|
pduNetworkTcpipDhcpControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable DHCP protocol"
|
|
::= { pduNetworkTcpip 1 }
|
|
|
|
pduNetworkTcpipIpv4 OBJECT IDENTIFIER ::= { pduNetworkTcpip 2 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduNetworkTcpipIpv4
|
|
--
|
|
-- Ip address Configuration Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduNetworkTcpipIpv4Address OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ip address that NMS can identify the managed device."
|
|
::= { pduNetworkTcpipIpv4 1}
|
|
|
|
pduNetworkTcpipIpv4Gateway OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The default gateway that allow device managed through routers."
|
|
::= { pduNetworkTcpipIpv4 2}
|
|
|
|
pduNetworkTcpipIpv4Subnet OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Internet address subnet mask"
|
|
::= { pduNetworkTcpipIpv4 3}
|
|
|
|
pduNetworkTcpipIpv4PrimaryDNS OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Internet address of Primary DNS Server"
|
|
::= { pduNetworkTcpipIpv4 4}
|
|
|
|
pduNetworkTcpipIpv4SecondaryDNS OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Internet address of Secondary DNS"
|
|
::= { pduNetworkTcpipIpv4 5}
|
|
|
|
pduNetworkTcpipIpv6 OBJECT IDENTIFIER ::= { pduNetworkTcpip 3 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduNetworkTcpipIpv6
|
|
--
|
|
-- Ip address Configuration Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduNetworkTcpipIpv6Control OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable IPv6 protocol"
|
|
::= { pduNetworkTcpipIpv6 1 }
|
|
|
|
pduNetworkTcpipIpv6AutoConfig OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
auto(1),
|
|
manual(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"IPv6 Auto-config or Maual setting"
|
|
::= { pduNetworkTcpipIpv6 2 }
|
|
|
|
pduNetworkTcpipIpv6Address OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ipv6 address that NMS can identify the managed device."
|
|
::= { pduNetworkTcpipIpv6 3}
|
|
|
|
pduNetworkTcpipIpv6Prefix OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The prefix length for ipv6 address."
|
|
::= { pduNetworkTcpipIpv6 4}
|
|
|
|
pduNetworkTcpipIpv6Router OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The default gateway that allow device managed through routers."
|
|
::= { pduNetworkTcpipIpv6 5}
|
|
|
|
pduNetworkTcpipIpv6PrimaryDNS OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Internet address of Primary DNS Server"
|
|
::= { pduNetworkTcpipIpv6 6}
|
|
|
|
pduNetworkTcpipIpv6SecondaryDNS OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Internet address of Secondary DNS"
|
|
::= { pduNetworkTcpipIpv6 7}
|
|
|
|
|
|
|
|
pduNetworkSecurity OBJECT IDENTIFIER ::= { pduNetwork 2 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduNetworkSecurity
|
|
--
|
|
-- Network Security Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduNetworkSecurityControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable Network Access Protection"
|
|
::= { pduNetworkSecurity 1 }
|
|
|
|
pduNetworkSecuritySsh OBJECT IDENTIFIER ::= { pduNetworkSecurity 2 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduNetworkSecuritySsh
|
|
--
|
|
-- SSH Security Group Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduNetworkSecuritySshControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable SSH Access Protection"
|
|
::= { pduNetworkSecuritySsh 1 }
|
|
|
|
pduNetworkSecuritySshInterval OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
oneMinute(1),
|
|
fiveMinutes(2),
|
|
tenMinutes(3),
|
|
thirtyMinutes(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Detecting Interval of SSH Access Protection"
|
|
::= { pduNetworkSecuritySsh 2 }
|
|
|
|
pduNetworkSecuritySshFailTimes OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
five(1),
|
|
ten(2),
|
|
twenty(3),
|
|
thirty(4),
|
|
hundred(5)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Unsuccessful attempts of SSH Access Protection"
|
|
::= { pduNetworkSecuritySsh 3 }
|
|
|
|
pduNetworkSecuritySshBlock OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
fiveMinutes(1),
|
|
thirtyMinutes(2),
|
|
oneHour(3),
|
|
oneDay(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Block Time of SSH Access Protection"
|
|
::= { pduNetworkSecuritySsh 4 }
|
|
|
|
pduNetworkSecuritySnmp OBJECT IDENTIFIER ::= { pduNetworkSecurity 3 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduNetworkSecuritySnmp
|
|
--
|
|
-- SNMP Security Group Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduNetworkSecuritySnmpControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable SNMP Access Protection"
|
|
::= { pduNetworkSecuritySnmp 1 }
|
|
|
|
pduNetworkSecuritySnmpInterval OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
oneMinute(1),
|
|
fiveMinutes(2),
|
|
tenMinutes(3),
|
|
thirtyMinutes(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Detecting Interval of SNMP Access Protection"
|
|
::= { pduNetworkSecuritySnmp 2 }
|
|
|
|
pduNetworkSecuritySnmpFailTimes OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
five(1),
|
|
ten(2),
|
|
twenty(3),
|
|
thirty(4),
|
|
hundred(5)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Unsuccessful attempts of SNMP Access Protection"
|
|
::= { pduNetworkSecuritySnmp 3 }
|
|
|
|
pduNetworkSecuritySnmpBlock OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
fiveMinutes(1),
|
|
thirtyMinutes(2),
|
|
oneHour(3),
|
|
oneDay(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Block Time of SNMP Access Protection"
|
|
::= { pduNetworkSecuritySnmp 4 }
|
|
|
|
pduNetworkSecurityHttp OBJECT IDENTIFIER ::= { pduNetworkSecurity 4 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduNetworkSecurityHttp
|
|
--
|
|
-- HTTP Security Group Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduNetworkSecurityHttpControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable HTTP Access Protection"
|
|
::= { pduNetworkSecurityHttp 1 }
|
|
|
|
pduNetworkSecurityHttpInterval OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
oneMinute(1),
|
|
fiveMinutes(2),
|
|
tenMinutes(3),
|
|
thirtyMinutes(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Detecting Interval of HTTP Access Protection"
|
|
::= { pduNetworkSecurityHttp 2 }
|
|
|
|
pduNetworkSecurityHttpFailTimes OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
five(1),
|
|
ten(2),
|
|
twenty(3),
|
|
thirty(4),
|
|
hundred(5)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Unsuccessful attempts of HTTP Access Protection"
|
|
::= { pduNetworkSecurityHttp 3 }
|
|
|
|
pduNetworkSecurityHttpBlock OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
fiveMinutes(1),
|
|
thirtyMinutes(2),
|
|
oneHour(3),
|
|
oneDay(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Block Time of HTTP Access Protection"
|
|
::= { pduNetworkSecurityHttp 4 }
|
|
|
|
|
|
pduNetworkService OBJECT IDENTIFIER ::= { pduNetwork 3 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduNetworkService
|
|
--
|
|
-- Network Service Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
|
|
pduNetworkServiceSsh OBJECT IDENTIFIER ::= { pduNetworkService 1 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduNetworkServiceSsh
|
|
--
|
|
-- SSH Service Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduNetworkServiceSshControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable SSH Server Service"
|
|
::= { pduNetworkServiceSsh 1 }
|
|
|
|
pduNetworkServiceSshPort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Port Number of SSH Server Service"
|
|
::= { pduNetworkServiceSsh 2 }
|
|
|
|
|
|
pduNetworkServiceSsl OBJECT IDENTIFIER ::= { pduNetworkService 2 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduNetworkServiceSsl
|
|
--
|
|
-- HTTPs Service Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduNetworkServiceSslControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable HTTPs Server Service"
|
|
::= { pduNetworkServiceSsl 1 }
|
|
|
|
pduNetworkServiceSslPort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Port Number of HTTPs Server Service"
|
|
::= { pduNetworkServiceSsl 2 }
|
|
|
|
pduNetworkServiceSslForce OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Force use HTTPs Server Service only."
|
|
::= { pduNetworkServiceSsl 3 }
|
|
|
|
pduNetworkServicePingControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable to response to PING request."
|
|
::= { pduNetworkService 3 }
|
|
|
|
|
|
pduNetworkServiceRadius OBJECT IDENTIFIER ::= { pduNetworkService 4 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduNetworkServiceRadius
|
|
--
|
|
-- RADIUS Client Service Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduNetworkServiceRadiusControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable RADIUS Client Service"
|
|
::= { pduNetworkServiceRadius 1 }
|
|
|
|
pduNetworkServiceRadiusIp OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The IP Address of RADIUS Client Service"
|
|
::= { pduNetworkServiceRadius 2 }
|
|
|
|
pduNetworkServiceRadiusPort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Port Number of RADIUS Client Service"
|
|
::= { pduNetworkServiceRadius 3 }
|
|
|
|
pduNetworkServiceRadiusSecretKey OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Secret Key of RADIUS Client Service"
|
|
::= { pduNetworkServiceRadius 4 }
|
|
|
|
pduNetworkServiceRadiusTimeout OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Timeout Interval of RADIUS Client Service in seconds"
|
|
::= { pduNetworkServiceRadius 5 }
|
|
|
|
pduNetworkServiceRadiusRetry OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Retry Times of RADIUS Client Service"
|
|
::= { pduNetworkServiceRadius 6 }
|
|
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduSystem
|
|
--
|
|
-- System Management Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduSystemName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of system."
|
|
::= { pduSystem 1 }
|
|
|
|
pduSystemContact OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The contact of system."
|
|
::= { pduSystem 2 }
|
|
|
|
pduSystemLocation OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The location of system."
|
|
::= { pduSystem 3 }
|
|
|
|
pduSystemLogInterval OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Log Interval of device"
|
|
::= { pduSystem 4 }
|
|
|
|
pduSystemWebRefresh OBJECT-TYPE
|
|
SYNTAX INTEGER (3..60)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Web Refresh Interval of device"
|
|
::= { pduSystem 5 }
|
|
|
|
pduSystemTime OBJECT IDENTIFIER ::= { pduSystem 6 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduSystemTime
|
|
--
|
|
-- Date/Time Configuration Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduSystemTimeDisplay OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date/time in agent"
|
|
::= { pduSystemTime 1 }
|
|
|
|
pduSystemTimeZone OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
gMT-1200InternationalDateLineWest(1),
|
|
gMT-1200Eniwetok-Kwajalein(2),
|
|
gMT-1100MidwayIsland-Samoa(3),
|
|
gMT-1000Hawaii(4),
|
|
gMT-0900Alaska(5),
|
|
gMT-0800PacificTime-Tijuana(6),
|
|
gMT-0700Arizona-MountainTime(7),
|
|
gMT-0700Chihuahua-LaPaz-Mazatlan(8),
|
|
gMT-0700MountainTime(9),
|
|
gMT-0600CentralAmerica(10),
|
|
gMT-0600CentralTime(11),
|
|
gMT-0600Guadalajara-MexicoCity-Monterrey(12),
|
|
gMT-0600Saskatchewan(13),
|
|
gMT-0500Bogota-Lima-Quito(14),
|
|
gMT-0500EasternTime(15),
|
|
gMT-0500Indiana(16),
|
|
gMT-0400AtlanticTime(17),
|
|
gMT-0400Caracas-LaPaz(18),
|
|
gMT-0400Santiago(19),
|
|
gMT-0330Newfoundland(20),
|
|
gMT-0300Brasilia(21),
|
|
gMT-0300BuenosAires-Georgetown(22),
|
|
gMT-0300Greenland(23),
|
|
gMT-0200Mid-Atlantic(24),
|
|
gMT-0100Azores(25),
|
|
gMT-0100CapeVerdeIs(26),
|
|
gMT-0000Casablanca-Monrovia(27),
|
|
gMT-0000GreenwichMeanTime-Dublin-Edinburgh-Lisbon-London(28),
|
|
gMT0100Amsterdam-Berlin-Bern-Rome-Stockholm-Vienna(29),
|
|
gMT0100Belgrade-Bratislava-Budapest-Ljubljana-Prague(30),
|
|
gMT0100Brussels-Copenhagen-Madrid-Paris(31),
|
|
gMT0100Sarajevo-Skopje-Warsaw-Zagreb(32),
|
|
gMT0100WestCentralAfrica(33),
|
|
gMT0200Athens-Istanbul-Minsk(34),
|
|
gMT0200Bucharest(35),
|
|
gMT0200Cairo(36),
|
|
gMT0200Harare-Pretoria(37),
|
|
gMT0200Helsinki-Kyiv-Riga-Sofia-Tallinn-Vilnius(38),
|
|
gMT0200Jerusalem(39),
|
|
gMT0300Baghdad(40),
|
|
gMT0300Kuwait-Riyadh(41),
|
|
gMT0300Moscow-StPetersburg-Volgograd(42),
|
|
gMT0300Nairobi(43),
|
|
gMT0330Tehran(44),
|
|
gMT0400AbuDhabi-Muscat(45),
|
|
gMT0400Baku-Tbilisi-Yerevan(46),
|
|
gMT0430Kabul(47),
|
|
gMT0500Ekaterinburg(48),
|
|
gMT0500Islamabad-Karachi-Tashkent(49),
|
|
gMT0530Bombay-Calcutta(50),
|
|
gMT0530Chennai-Kolkata-Mumbai-NewDelhi(51),
|
|
gMT0545Kathmandu(52),
|
|
gMT0600Almaty-Novosibirsk(53),
|
|
gMT0600Astana-Dhaka(54),
|
|
gMT0600SriJayawardenepura(55),
|
|
gMT0630Rangoon(56),
|
|
gMT0700Bangkok-Hanoi-Jakarta(57),
|
|
gMT0700Krasnoyarsk(58),
|
|
gMT0800Beijing-Chongqing-HongKong-Urumqi(59),
|
|
gMT0800Irkutsk-UlaanBataar(60),
|
|
gMT0800KualaLumpur-Singapore(61),
|
|
gMT0800Perth(62),
|
|
gMT0800Taipei(63),
|
|
gMT0900Osaka-Sapporo-Tokyo(64),
|
|
gMT0900Seoul(65),
|
|
gMT0900Yakutsk(66),
|
|
gMT0930Adelaide(67),
|
|
gMT0930Darwin(68),
|
|
gMT1000Brisbane(69),
|
|
gMT1000Canberra-Melbourne-Sydney(70),
|
|
gMT1000Guam-PortMoresby(71),
|
|
gMT1000Hobart(72),
|
|
gMT1000Vladivostok(73),
|
|
gMT1100Magadan-SolomonIs-NewCaledonia(74),
|
|
gMT1200Auckland-Wellington(75),
|
|
gMT1200Fiji-Kamchatka-MarshallIs(76),
|
|
gMT1300NukuAlofa(77)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Time Zone to use when synchronize with NTP server."
|
|
::= { pduSystemTime 2 }
|
|
|
|
pduSystemTimeFormat OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
mmddyyyy(1),
|
|
ddmmyyyy(2),
|
|
yyyymmdd(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Date Format"
|
|
::= { pduSystemTime 3 }
|
|
|
|
pduSystemTimeSetting OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
twentyFourHrFormat(1),
|
|
twelveHrFormat(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Time Setting"
|
|
::= { pduSystemTime 4 }
|
|
|
|
pduSystemTimeDayLightSaving OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the Day Light Saving when synchronize with NTP server."
|
|
::= { pduSystemTime 5 }
|
|
|
|
pduSystemTimeManual OBJECT IDENTIFIER ::= { pduSystemTime 6 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduSystemTimeManual
|
|
--
|
|
-- Manual Time Setting Configuration Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduSystemTimeManualDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (10..10))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date in agent, format is (dd/mm/yyyy)"
|
|
::= { pduSystemTimeManual 1 }
|
|
|
|
pduSystemTimeManualTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (8..8))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time in agent, format is (hh:mm:ss)"
|
|
::= { pduSystemTimeManual 2 }
|
|
|
|
pduSystemTimeNtp OBJECT IDENTIFIER ::= { pduSystemTime 7 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduSystemTimeNtp
|
|
--
|
|
-- NTP Configuration Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduSystemTimeNtpControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable or disable the agent to synchronize date/time with NTP server."
|
|
::= { pduSystemTimeNtp 1 }
|
|
|
|
pduSystemTimeNtpServer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ip address of NTP server."
|
|
::= { pduSystemTimeNtp 2 }
|
|
|
|
pduSystemTimeNtpSyncInterval OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Sync Interval with NTP server."
|
|
::= { pduSystemTimeNtp 3 }
|
|
|
|
pduSystemTimeNtpSyncUnit OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
day(1),
|
|
month(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Unit of Sync Interval"
|
|
::= { pduSystemTimeNtp 4 }
|
|
|
|
pduSystemResetToDefault OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
nothing(1),
|
|
reset(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Reset the parameter of PDU to default."
|
|
::= { pduSystem 7 }
|
|
|
|
pduSystemReboot OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
nothing(1),
|
|
reboot(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Reboot the system of PDU."
|
|
::= { pduSystem 8 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduSNMP
|
|
--
|
|
-- SNMP Configuration Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduSnmpControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable SNMP protocol."
|
|
::= { pduSNMP 1 }
|
|
|
|
pduSnmpPort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UDP port for SNMP."
|
|
::= { pduSNMP 2}
|
|
|
|
pduSnmpVersion OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
v1(1),
|
|
v2(2),
|
|
v3(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Set SNMP version."
|
|
::= { pduSNMP 3 }
|
|
|
|
pduSnmpTrapsReceiversTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduSnmpTrapsReceiversEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of managers to send traps to. The number of
|
|
entries is given by the value of pduSnmpNumTrapReceivers"
|
|
::= { pduSNMP 4}
|
|
|
|
pduSnmpTrapsReceiversEntry OBJECT-TYPE
|
|
SYNTAX PduSnmpTrapsReceiversEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The managers to send traps to."
|
|
INDEX { trapsIndex}
|
|
::= { pduSnmpTrapsReceiversTable 1 }
|
|
|
|
PduSnmpTrapsReceiversEntry ::=
|
|
SEQUENCE {
|
|
trapsIndex
|
|
INTEGER,
|
|
trapsReceiverAddr
|
|
DisplayString,
|
|
receiverEventLevel
|
|
INTEGER,
|
|
receiverSnmpVer
|
|
INTEGER,
|
|
receiverDescription
|
|
DisplayString
|
|
}
|
|
|
|
trapsIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..15)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to a trap receiver entry."
|
|
::= { pduSnmpTrapsReceiversEntry 1 }
|
|
|
|
trapsReceiverAddr OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The IP address of the manager to send a trap to."
|
|
::= { pduSnmpTrapsReceiversEntry 2 }
|
|
|
|
receiverEventLevel OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
critical(1),
|
|
warning(2),
|
|
informational(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The severity level of traps to be received by this manager."
|
|
::= { pduSnmpTrapsReceiversEntry 3 }
|
|
|
|
receiverSnmpVer OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
v1(1),
|
|
v2(2),
|
|
v3(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The SNMP Trap version of trap receivers."
|
|
::= { pduSnmpTrapsReceiversEntry 4 }
|
|
|
|
receiverDescription OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Description of trap receivers"
|
|
::= { pduSnmpTrapsReceiversEntry 5 }
|
|
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduEmail
|
|
--
|
|
-- Email Configuration Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduEmailServer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The address of Email server."
|
|
::= { pduEmail 1 }
|
|
|
|
pduEmailPort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UDP port for Email Server."
|
|
::= { pduEmail 2}
|
|
|
|
pduEmailSenderEmail OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The sender's Email address"
|
|
::= { pduEmail 3 }
|
|
|
|
pduEmailPrefix OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The prefix string of mail subject"
|
|
::= { pduEmail 4 }
|
|
|
|
pduEmailAuthControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable SMTP Authentication."
|
|
::= { pduEmail 5 }
|
|
|
|
pduEmailAuthUsername OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The user name of SMTP Authentication"
|
|
::= { pduEmail 6 }
|
|
|
|
pduEmailAuthPassword OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The password of SMTP Authentication"
|
|
::= { pduEmail 7 }
|
|
|
|
pduEmailReceiversTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduEmailReceiversEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of managers to send email notification to."
|
|
::= { pduEmail 8}
|
|
|
|
pduEmailReceiversEntry OBJECT-TYPE
|
|
SYNTAX PduEmailReceiversEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The managers to send email notification to."
|
|
INDEX { mailRecvIndex}
|
|
::= { pduEmailReceiversTable 1 }
|
|
|
|
PduEmailReceiversEntry ::=
|
|
SEQUENCE {
|
|
mailRecvIndex
|
|
INTEGER,
|
|
mailRecvReceiverAddr
|
|
DisplayString,
|
|
mailRecvEmailType
|
|
INTEGER,
|
|
mailRecvEventLevel
|
|
INTEGER,
|
|
mailRecvDescription
|
|
DisplayString
|
|
}
|
|
|
|
mailRecvIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..15)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to a email notification receiver entry."
|
|
::= { pduEmailReceiversEntry 1 }
|
|
|
|
mailRecvReceiverAddr OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Email address of the manager to send a email notification to."
|
|
::= { pduEmailReceiversEntry 2 }
|
|
|
|
mailRecvEmailType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(1),
|
|
events(2),
|
|
status(3),
|
|
both(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Email Type of email notification receivers."
|
|
::= { pduEmailReceiversEntry 3 }
|
|
|
|
mailRecvEventLevel OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
critical(1),
|
|
warning(2),
|
|
informational(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The severity level of email notification to be received by this manager."
|
|
::= { pduEmailReceiversEntry 4 }
|
|
|
|
mailRecvDescription OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Description of email notification receivers"
|
|
::= { pduEmailReceiversEntry 5 }
|
|
|
|
pduPwrMonitoringInlet OBJECT IDENTIFIER ::= { pduPwrMonitoring 1 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringInlet
|
|
--
|
|
-- Inlet Management Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringInletNum OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of Inlet."
|
|
::= { pduPwrMonitoringInlet 1}
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringInletStatusTable
|
|
--
|
|
-- Inlet Status Group
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringInletStatusTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPwrMonitoringInletStatusEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display status of Inlet."
|
|
::= { pduPwrMonitoringInlet 2}
|
|
|
|
pduPwrMonitoringInletStatusEntry OBJECT-TYPE
|
|
SYNTAX PduPwrMonitoringInletStatusEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display status of Inlet."
|
|
INDEX { inletIndex}
|
|
::= { pduPwrMonitoringInletStatusTable 1 }
|
|
|
|
PduPwrMonitoringInletStatusEntry ::=
|
|
SEQUENCE {
|
|
inletIndex
|
|
INTEGER,
|
|
inletPowerAll
|
|
INTEGER,
|
|
inletResetFrom
|
|
DisplayString,
|
|
inletEnergy
|
|
INTEGER,
|
|
inletStatus
|
|
INTEGER,
|
|
inletCurrPhase1
|
|
INTEGER,
|
|
inletCurrPhase2
|
|
INTEGER,
|
|
inletCurrPhase3
|
|
INTEGER,
|
|
inletVoltPhase1
|
|
INTEGER,
|
|
inletVoltPhase2
|
|
INTEGER,
|
|
inletVoltPhase3
|
|
INTEGER,
|
|
inletPwrFactorPhase1
|
|
INTEGER,
|
|
inletPwrFactorPhase2
|
|
INTEGER,
|
|
inletPwrFactorPhase3
|
|
INTEGER,
|
|
inletPowerPhase1
|
|
INTEGER,
|
|
inletPowerPhase2
|
|
INTEGER,
|
|
inletPowerPhase3
|
|
INTEGER,
|
|
inletStatusPhase1
|
|
INTEGER,
|
|
inletStatusPhase2
|
|
INTEGER,
|
|
inletStatusPhase3
|
|
INTEGER
|
|
}
|
|
|
|
inletIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..3)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to Inlet status entry."
|
|
::= { pduPwrMonitoringInletStatusEntry 1 }
|
|
|
|
inletPowerAll OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1W"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The total power of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 2 }
|
|
|
|
inletResetFrom OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The reset date of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 3 }
|
|
|
|
inletEnergy OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "KWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The total energy of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 4 }
|
|
|
|
inletStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
warning(2),
|
|
critical(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Status of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 5 }
|
|
|
|
inletCurrPhase1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.01A"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase1 current of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 6 }
|
|
|
|
inletCurrPhase2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.01A"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase2 current of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 7 }
|
|
|
|
inletCurrPhase3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.01A"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase3 current of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 8 }
|
|
|
|
inletVoltPhase1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1V"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase1 voltage of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 9 }
|
|
|
|
inletVoltPhase2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1V"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase2 voltage of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 10 }
|
|
|
|
inletVoltPhase3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1V"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase3 voltage of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 11 }
|
|
|
|
inletPwrFactorPhase1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1%"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase1 power factor of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 12 }
|
|
|
|
inletPwrFactorPhase2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1%"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase2 power factor of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 13 }
|
|
|
|
inletPwrFactorPhase3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1%"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase3 power factor of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 14 }
|
|
|
|
inletPowerPhase1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1W"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase1 power of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 15 }
|
|
|
|
inletPowerPhase2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1W"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase2 power of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 16 }
|
|
|
|
inletPowerPhase3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1W"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase3 power of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 17 }
|
|
|
|
inletStatusPhase1 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
warning(2),
|
|
critical(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase1 status of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 18 }
|
|
|
|
inletStatusPhase2 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
warning(2),
|
|
critical(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase2 status of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 19 }
|
|
|
|
inletStatusPhase3 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
warning(2),
|
|
critical(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The phase3 status of inlet."
|
|
::= { pduPwrMonitoringInletStatusEntry 20 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringInletCfgTable
|
|
--
|
|
-- Inlet Configuration Group
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringInletCfgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPwrMonitoringInletCfgEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to configure thresholds of inlet."
|
|
::= { pduPwrMonitoringInlet 3}
|
|
|
|
pduPwrMonitoringInletCfgEntry OBJECT-TYPE
|
|
SYNTAX PduPwrMonitoringInletCfgEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to configure thresholds of inlet."
|
|
INDEX { inletCfgIndex}
|
|
::= { pduPwrMonitoringInletCfgTable 1 }
|
|
|
|
PduPwrMonitoringInletCfgEntry ::=
|
|
SEQUENCE {
|
|
inletCfgIndex
|
|
INTEGER,
|
|
inletCfgLoadCritical
|
|
INTEGER,
|
|
inletCfgLoadWarning
|
|
INTEGER,
|
|
inletCfgCurrCritPhase1
|
|
INTEGER,
|
|
inletCfgCurrCritPhase2
|
|
INTEGER,
|
|
inletCfgCurrCritPhase3
|
|
INTEGER,
|
|
inletCfgCurrWarnPhase1
|
|
INTEGER,
|
|
inletCfgCurrWarnPhase2
|
|
INTEGER,
|
|
inletCfgCurrWarnPhase3
|
|
INTEGER,
|
|
inletCfgVoltCritPhase1
|
|
INTEGER,
|
|
inletCfgVoltCritPhase2
|
|
INTEGER,
|
|
inletCfgVoltCritPhase3
|
|
INTEGER,
|
|
inletCfgVoltWarnPhase1
|
|
INTEGER,
|
|
inletCfgVoltWarnPhase2
|
|
INTEGER,
|
|
inletCfgVoltWarnPhase3
|
|
INTEGER
|
|
}
|
|
|
|
inletCfgIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..3)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to inlet configuration entry."
|
|
::= { pduPwrMonitoringInletCfgEntry 1 }
|
|
|
|
inletCfgLoadCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1kW"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of inlet load."
|
|
::= { pduPwrMonitoringInletCfgEntry 2 }
|
|
|
|
inletCfgLoadWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1kW"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of inlet load."
|
|
::= { pduPwrMonitoringInletCfgEntry 3 }
|
|
|
|
inletCfgCurrCritPhase1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of pahse1 current of inlet."
|
|
::= { pduPwrMonitoringInletCfgEntry 4 }
|
|
|
|
inletCfgCurrCritPhase2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of pahse2 current of inlet."
|
|
::= { pduPwrMonitoringInletCfgEntry 5 }
|
|
|
|
inletCfgCurrCritPhase3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of pahse3 current of inlet."
|
|
::= { pduPwrMonitoringInletCfgEntry 6 }
|
|
|
|
inletCfgCurrWarnPhase1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of pahse1 current of inlet."
|
|
::= { pduPwrMonitoringInletCfgEntry 7 }
|
|
|
|
inletCfgCurrWarnPhase2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of pahse2 current of inlet."
|
|
::= { pduPwrMonitoringInletCfgEntry 8 }
|
|
|
|
inletCfgCurrWarnPhase3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of pahse3 current of inlet."
|
|
::= { pduPwrMonitoringInletCfgEntry 9 }
|
|
|
|
inletCfgVoltCritPhase1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1V"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of pahse1 voltage of inlet."
|
|
::= { pduPwrMonitoringInletCfgEntry 10 }
|
|
|
|
inletCfgVoltCritPhase2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1V"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of pahse2 voltage of inlet."
|
|
::= { pduPwrMonitoringInletCfgEntry 11 }
|
|
|
|
inletCfgVoltCritPhase3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1V"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of pahse3 voltage of inlet."
|
|
::= { pduPwrMonitoringInletCfgEntry 12 }
|
|
|
|
inletCfgVoltWarnPhase1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1V"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of pahse1 voltage of inlet."
|
|
::= { pduPwrMonitoringInletCfgEntry 13 }
|
|
|
|
inletCfgVoltWarnPhase2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1V"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of pahse2 voltage of inlet."
|
|
::= { pduPwrMonitoringInletCfgEntry 14 }
|
|
|
|
inletCfgVoltWarnPhase3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1V"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of pahse3 voltage of inlet."
|
|
::= { pduPwrMonitoringInletCfgEntry 15 }
|
|
|
|
pduPwrMonitoringOutlet OBJECT IDENTIFIER ::= { pduPwrMonitoring 2 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutlet
|
|
--
|
|
-- Outlet Management Group of the device.
|
|
--
|
|
-- ===========================================================================
|
|
|
|
pduPwrMonitoringOutletPduA OBJECT IDENTIFIER ::= { pduPwrMonitoringOutlet 1 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletPduA
|
|
--
|
|
-- Outlet of Device1 management Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletNumPduA OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of PduA Outlet."
|
|
::= { pduPwrMonitoringOutletPduA 1}
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletStatusTablePduA
|
|
--
|
|
-- Outlet of Device1 Status Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletStatusTablePduA OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPwrMonitoringOutletStatusPduAEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display status of PduA outlet."
|
|
::= { pduPwrMonitoringOutletPduA 2}
|
|
|
|
pduPwrMonitoringOutletStatusPduAEntry OBJECT-TYPE
|
|
SYNTAX PduPwrMonitoringOutletStatusPduAEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display status of PduA outlet."
|
|
INDEX { outletPduAIndex}
|
|
::= { pduPwrMonitoringOutletStatusTablePduA 1 }
|
|
|
|
PduPwrMonitoringOutletStatusPduAEntry ::=
|
|
SEQUENCE {
|
|
outletPduAIndex
|
|
INTEGER,
|
|
outletPduAState
|
|
INTEGER,
|
|
outletPduACurrent
|
|
INTEGER,
|
|
outletPduAPwrFactor
|
|
INTEGER,
|
|
outletPduAPower
|
|
INTEGER,
|
|
outletPduAEnergy
|
|
INTEGER,
|
|
outletPduAResetFrom
|
|
DisplayString,
|
|
outletPduAStatus
|
|
INTEGER
|
|
}
|
|
|
|
outletPduAIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..41)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to outlet status of PduA."
|
|
::= { pduPwrMonitoringOutletStatusPduAEntry 1 }
|
|
|
|
outletPduAState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The state of PduA outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduAEntry 2 }
|
|
|
|
outletPduACurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.01A"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current of PduA outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduAEntry 3 }
|
|
|
|
outletPduAPwrFactor OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1%"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power factor of PduA outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduAEntry 4 }
|
|
|
|
outletPduAPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1W"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power of PduA outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduAEntry 5 }
|
|
|
|
outletPduAEnergy OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "KWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The energy of PduA outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduAEntry 6 }
|
|
|
|
outletPduAResetFrom OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The reset date of PduA outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduAEntry 7 }
|
|
|
|
outletPduAStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
warning(2),
|
|
critical(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of PduA outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduAEntry 8 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletCfgTablePduA
|
|
--
|
|
-- Outlet of Device1 Configuration Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletCfgTablePduA OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPwrMonitoringOutletCfgPduAEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display configuration of PduA outlet."
|
|
::= { pduPwrMonitoringOutletPduA 3}
|
|
|
|
pduPwrMonitoringOutletCfgPduAEntry OBJECT-TYPE
|
|
SYNTAX PduPwrMonitoringOutletCfgPduAEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display configuration of PduA outlet."
|
|
INDEX { outletCfgPduAIndex}
|
|
::= { pduPwrMonitoringOutletCfgTablePduA 1 }
|
|
|
|
PduPwrMonitoringOutletCfgPduAEntry ::=
|
|
SEQUENCE {
|
|
outletCfgPduAIndex
|
|
INTEGER,
|
|
outletCfgPduAName
|
|
DisplayString,
|
|
outletCfgPduADelayOnStatus
|
|
INTEGER,
|
|
outletCfgPduADelayOnTime
|
|
INTEGER,
|
|
outletCfgPduADelayOffStatus
|
|
INTEGER,
|
|
outletCfgPduADelayOffTime
|
|
INTEGER,
|
|
outletCfgPduAReboot
|
|
INTEGER,
|
|
outletCfgPduAOverCurrCritical
|
|
INTEGER,
|
|
outletCfgPduAOverCurrWarning
|
|
INTEGER,
|
|
outletCfgPduAOverPwrCritical
|
|
INTEGER,
|
|
outletCfgPduAOverPwrWarning
|
|
INTEGER
|
|
}
|
|
|
|
outletCfgPduAIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..41)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to outlet configuration of PduA."
|
|
::= { pduPwrMonitoringOutletCfgPduAEntry 1 }
|
|
|
|
outletCfgPduAName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name for outlet of PduA."
|
|
::= { pduPwrMonitoringOutletCfgPduAEntry 2 }
|
|
|
|
outletCfgPduADelayOnStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
nodelay(1),
|
|
delay(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay On status of PduA outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduAEntry 3 }
|
|
|
|
outletCfgPduADelayOnTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay On time of PduA outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduAEntry 4 }
|
|
|
|
outletCfgPduADelayOffStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
nodelay(1),
|
|
delay(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay Off status of PduA outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduAEntry 5 }
|
|
|
|
outletCfgPduADelayOffTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay Off time of PduA outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduAEntry 6 }
|
|
|
|
outletCfgPduAReboot OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay On reboot duration of PduA outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduAEntry 7 }
|
|
|
|
outletCfgPduAOverCurrCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of current of PduA outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduAEntry 8 }
|
|
|
|
outletCfgPduAOverCurrWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of current of PduA outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduAEntry 9 }
|
|
|
|
outletCfgPduAOverPwrCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1W"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of power of PduA outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduAEntry 10 }
|
|
|
|
outletCfgPduAOverPwrWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1W"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of power of PduA outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduAEntry 11 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletCtlTablePduA
|
|
--
|
|
-- Outlet of Device1 Control Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletCtlTablePduA OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPwrMonitoringOutletCtlPduAEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display control of PduA outlet."
|
|
::= { pduPwrMonitoringOutletPduA 4}
|
|
|
|
pduPwrMonitoringOutletCtlPduAEntry OBJECT-TYPE
|
|
SYNTAX PduPwrMonitoringOutletCtlPduAEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display control of PduA outlet."
|
|
INDEX { outletCtlPduAIndex}
|
|
::= { pduPwrMonitoringOutletCtlTablePduA 1 }
|
|
|
|
PduPwrMonitoringOutletCtlPduAEntry ::=
|
|
SEQUENCE {
|
|
outletCtlPduAIndex
|
|
INTEGER,
|
|
outletCtlPduAControl
|
|
INTEGER
|
|
}
|
|
|
|
outletCtlPduAIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..41)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to outlet control of PduA."
|
|
::= { pduPwrMonitoringOutletCtlPduAEntry 1 }
|
|
|
|
outletCtlPduAControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn(1),
|
|
delayedOn(2),
|
|
immediateOff(3),
|
|
delayedOff(4),
|
|
immediateCycle(5),
|
|
delayedCycle(6)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The control-type of PduA outlet."
|
|
::= { pduPwrMonitoringOutletCtlPduAEntry 2 }
|
|
|
|
pduPwrMonitoringOutletPduB OBJECT IDENTIFIER ::= { pduPwrMonitoringOutlet 2 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletPduB
|
|
--
|
|
-- Outlet of Device2 management Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletNumPduB OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of PduB Outlet."
|
|
::= { pduPwrMonitoringOutletPduB 1}
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletStatusTablePduB
|
|
--
|
|
-- Outlet of Device2 Status Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletStatusTablePduB OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPwrMonitoringOutletStatusPduBEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display status of PduB outlet."
|
|
::= { pduPwrMonitoringOutletPduB 2}
|
|
|
|
pduPwrMonitoringOutletStatusPduBEntry OBJECT-TYPE
|
|
SYNTAX PduPwrMonitoringOutletStatusPduBEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display status of PduB outlet."
|
|
INDEX { outletPduBIndex}
|
|
::= { pduPwrMonitoringOutletStatusTablePduB 1 }
|
|
|
|
PduPwrMonitoringOutletStatusPduBEntry ::=
|
|
SEQUENCE {
|
|
outletPduBIndex
|
|
INTEGER,
|
|
outletPduBState
|
|
INTEGER,
|
|
outletPduBCurrent
|
|
INTEGER,
|
|
outletPduBPwrFactor
|
|
INTEGER,
|
|
outletPduBPower
|
|
INTEGER,
|
|
outletPduBEnergy
|
|
INTEGER,
|
|
outletPduBResetFrom
|
|
DisplayString,
|
|
outletPduBStatus
|
|
INTEGER
|
|
}
|
|
|
|
outletPduBIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..41)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to outlet status of PduB."
|
|
::= { pduPwrMonitoringOutletStatusPduBEntry 1 }
|
|
|
|
outletPduBState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The state of PduB outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduBEntry 2 }
|
|
|
|
outletPduBCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.01A"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current of PduB outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduBEntry 3 }
|
|
|
|
outletPduBPwrFactor OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1%"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power factor of PduB outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduBEntry 4 }
|
|
|
|
outletPduBPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1W"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power of PduB outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduBEntry 5 }
|
|
|
|
outletPduBEnergy OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "KWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The energy of PduB outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduBEntry 6 }
|
|
|
|
outletPduBResetFrom OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The reset date of PduB outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduBEntry 7 }
|
|
|
|
outletPduBStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
warning(2),
|
|
critical(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of PduB outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduBEntry 8 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletCfgTablePduB
|
|
--
|
|
-- Outlet of Device2 Configuration Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletCfgTablePduB OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPwrMonitoringOutletCfgPduBEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display configuration of PduB outlet."
|
|
::= { pduPwrMonitoringOutletPduB 3}
|
|
|
|
pduPwrMonitoringOutletCfgPduBEntry OBJECT-TYPE
|
|
SYNTAX PduPwrMonitoringOutletCfgPduBEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display configuration of PduB outlet."
|
|
INDEX { outletCfgPduBIndex}
|
|
::= { pduPwrMonitoringOutletCfgTablePduB 1 }
|
|
|
|
PduPwrMonitoringOutletCfgPduBEntry ::=
|
|
SEQUENCE {
|
|
outletCfgPduBIndex
|
|
INTEGER,
|
|
outletCfgPduBName
|
|
DisplayString,
|
|
outletCfgPduBDelayOnStatus
|
|
INTEGER,
|
|
outletCfgPduBDelayOnTime
|
|
INTEGER,
|
|
outletCfgPduBDelayOffStatus
|
|
INTEGER,
|
|
outletCfgPduBDelayOffTime
|
|
INTEGER,
|
|
outletCfgPduBReboot
|
|
INTEGER,
|
|
outletCfgPduBOverCurrCritical
|
|
INTEGER,
|
|
outletCfgPduBOverCurrWarning
|
|
INTEGER,
|
|
outletCfgPduBOverPwrCritical
|
|
INTEGER,
|
|
outletCfgPduBOverPwrWarning
|
|
INTEGER
|
|
}
|
|
|
|
outletCfgPduBIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..41)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to outlet configuration of PduB."
|
|
::= { pduPwrMonitoringOutletCfgPduBEntry 1 }
|
|
|
|
outletCfgPduBName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name for outlet of PduB."
|
|
::= { pduPwrMonitoringOutletCfgPduBEntry 2 }
|
|
|
|
outletCfgPduBDelayOnStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
nodelay(1),
|
|
delay(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay On status of PduB outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduBEntry 3 }
|
|
|
|
outletCfgPduBDelayOnTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay On time of PduB outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduBEntry 4 }
|
|
|
|
outletCfgPduBDelayOffStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
nodelay(1),
|
|
delay(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay Off status of PduB outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduBEntry 5 }
|
|
|
|
outletCfgPduBDelayOffTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay Off time of PduB outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduBEntry 6 }
|
|
|
|
outletCfgPduBReboot OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay On reboot duration of PduB outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduBEntry 7 }
|
|
|
|
outletCfgPduBOverCurrCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of current of PduB outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduBEntry 8 }
|
|
|
|
outletCfgPduBOverCurrWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of current of PduB outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduBEntry 9 }
|
|
|
|
outletCfgPduBOverPwrCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1W"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of power of PduB outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduBEntry 10 }
|
|
|
|
outletCfgPduBOverPwrWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1W"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of power of PduB outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduBEntry 11 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletCtlTablePduB
|
|
--
|
|
-- Outlet of Device2 Control Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletCtlTablePduB OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPwrMonitoringOutletCtlPduBEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display control of PduB outlet."
|
|
::= { pduPwrMonitoringOutletPduB 4}
|
|
|
|
pduPwrMonitoringOutletCtlPduBEntry OBJECT-TYPE
|
|
SYNTAX PduPwrMonitoringOutletCtlPduBEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display control of PduB outlet."
|
|
INDEX { outletCtlPduBIndex}
|
|
::= { pduPwrMonitoringOutletCtlTablePduB 1 }
|
|
|
|
PduPwrMonitoringOutletCtlPduBEntry ::=
|
|
SEQUENCE {
|
|
outletCtlPduBIndex
|
|
INTEGER,
|
|
outletCtlPduBControl
|
|
INTEGER
|
|
}
|
|
|
|
outletCtlPduBIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..41)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to outlet control of PduB."
|
|
::= { pduPwrMonitoringOutletCtlPduBEntry 1 }
|
|
|
|
outletCtlPduBControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn(1),
|
|
delayedOn(2),
|
|
immediateOff(3),
|
|
delayedOff(4),
|
|
immediateCycle(5),
|
|
delayedCycle(6)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The control-type of PduB outlet."
|
|
::= { pduPwrMonitoringOutletCtlPduBEntry 2 }
|
|
|
|
pduPwrMonitoringOutletPduC OBJECT IDENTIFIER ::= { pduPwrMonitoringOutlet 3 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletPduC
|
|
--
|
|
-- Outlet of Device3 management Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletNumPduC OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of PduC Outlet."
|
|
::= { pduPwrMonitoringOutletPduC 1}
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletStatusTablePduC
|
|
--
|
|
-- Outlet of Device3 Status Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletStatusTablePduC OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPwrMonitoringOutletStatusPduCEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display status of PduC outlet."
|
|
::= { pduPwrMonitoringOutletPduC 2}
|
|
|
|
pduPwrMonitoringOutletStatusPduCEntry OBJECT-TYPE
|
|
SYNTAX PduPwrMonitoringOutletStatusPduCEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display status of PduC outlet."
|
|
INDEX { outletPduCIndex}
|
|
::= { pduPwrMonitoringOutletStatusTablePduC 1 }
|
|
|
|
PduPwrMonitoringOutletStatusPduCEntry ::=
|
|
SEQUENCE {
|
|
outletPduCIndex
|
|
INTEGER,
|
|
outletPduCState
|
|
INTEGER,
|
|
outletPduCCurrent
|
|
INTEGER,
|
|
outletPduCPwrFactor
|
|
INTEGER,
|
|
outletPduCPower
|
|
INTEGER,
|
|
outletPduCEnergy
|
|
INTEGER,
|
|
outletPduCResetFrom
|
|
DisplayString,
|
|
outletPduCStatus
|
|
INTEGER
|
|
}
|
|
|
|
outletPduCIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..41)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to outlet status of PduC."
|
|
::= { pduPwrMonitoringOutletStatusPduCEntry 1 }
|
|
|
|
outletPduCState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The state of PduC outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduCEntry 2 }
|
|
|
|
outletPduCCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.01A"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current of PduC outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduCEntry 3 }
|
|
|
|
outletPduCPwrFactor OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1%"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power factor of PduC outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduCEntry 4 }
|
|
|
|
outletPduCPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1W"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power of PduC outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduCEntry 5 }
|
|
|
|
outletPduCEnergy OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "KWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The energy of PduC outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduCEntry 6 }
|
|
|
|
outletPduCResetFrom OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The reset date of PduC outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduCEntry 7 }
|
|
|
|
outletPduCStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
warning(2),
|
|
critical(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of PduC outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduCEntry 8 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletCfgTablePduC
|
|
--
|
|
-- Outlet of Device3 Configuration Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletCfgTablePduC OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPwrMonitoringOutletCfgPduCEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display configuration of PduC outlet."
|
|
::= { pduPwrMonitoringOutletPduC 3}
|
|
|
|
pduPwrMonitoringOutletCfgPduCEntry OBJECT-TYPE
|
|
SYNTAX PduPwrMonitoringOutletCfgPduCEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display configuration of PduC outlet."
|
|
INDEX { outletCfgPduCIndex}
|
|
::= { pduPwrMonitoringOutletCfgTablePduC 1 }
|
|
|
|
PduPwrMonitoringOutletCfgPduCEntry ::=
|
|
SEQUENCE {
|
|
outletCfgPduCIndex
|
|
INTEGER,
|
|
outletCfgPduCName
|
|
DisplayString,
|
|
outletCfgPduCDelayOnStatus
|
|
INTEGER,
|
|
outletCfgPduCDelayOnTime
|
|
INTEGER,
|
|
outletCfgPduCDelayOffStatus
|
|
INTEGER,
|
|
outletCfgPduCDelayOffTime
|
|
INTEGER,
|
|
outletCfgPduCReboot
|
|
INTEGER,
|
|
outletCfgPduCOverCurrCritical
|
|
INTEGER,
|
|
outletCfgPduCOverCurrWarning
|
|
INTEGER,
|
|
outletCfgPduCOverPwrCritical
|
|
INTEGER,
|
|
outletCfgPduCOverPwrWarning
|
|
INTEGER
|
|
}
|
|
|
|
outletCfgPduCIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..41)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to outlet configuration of PduC."
|
|
::= { pduPwrMonitoringOutletCfgPduCEntry 1 }
|
|
|
|
outletCfgPduCName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name for outlet of PduC."
|
|
::= { pduPwrMonitoringOutletCfgPduCEntry 2 }
|
|
|
|
outletCfgPduCDelayOnStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
nodelay(1),
|
|
delay(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay On status of PduC outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduCEntry 3 }
|
|
|
|
outletCfgPduCDelayOnTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay On time of PduC outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduCEntry 4 }
|
|
|
|
outletCfgPduCDelayOffStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
nodelay(1),
|
|
delay(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay Off status of PduC outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduCEntry 5 }
|
|
|
|
outletCfgPduCDelayOffTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay Off time of PduC outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduCEntry 6 }
|
|
|
|
outletCfgPduCReboot OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay On reboot duration of PduC outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduCEntry 7 }
|
|
|
|
outletCfgPduCOverCurrCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of current of PduC outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduCEntry 8 }
|
|
|
|
outletCfgPduCOverCurrWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of current of PduC outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduCEntry 9 }
|
|
|
|
outletCfgPduCOverPwrCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1W"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of power of PduC outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduCEntry 10 }
|
|
|
|
outletCfgPduCOverPwrWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1W"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of power of PduC outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduCEntry 11 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletCtlTablePduC
|
|
--
|
|
-- Outlet of Device3 Control Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletCtlTablePduC OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPwrMonitoringOutletCtlPduCEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display control of PduC outlet."
|
|
::= { pduPwrMonitoringOutletPduC 4}
|
|
|
|
pduPwrMonitoringOutletCtlPduCEntry OBJECT-TYPE
|
|
SYNTAX PduPwrMonitoringOutletCtlPduCEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display control of PduC outlet."
|
|
INDEX { outletCtlPduCIndex}
|
|
::= { pduPwrMonitoringOutletCtlTablePduC 1 }
|
|
|
|
PduPwrMonitoringOutletCtlPduCEntry ::=
|
|
SEQUENCE {
|
|
outletCtlPduCIndex
|
|
INTEGER,
|
|
outletCtlPduCControl
|
|
INTEGER
|
|
}
|
|
|
|
outletCtlPduCIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..41)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to outlet control of PduC."
|
|
::= { pduPwrMonitoringOutletCtlPduCEntry 1 }
|
|
|
|
outletCtlPduCControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn(1),
|
|
delayedOn(2),
|
|
immediateOff(3),
|
|
delayedOff(4),
|
|
immediateCycle(5),
|
|
delayedCycle(6)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The control-type of PduC outlet."
|
|
::= { pduPwrMonitoringOutletCtlPduCEntry 2 }
|
|
|
|
pduPwrMonitoringOutletPduD OBJECT IDENTIFIER ::= { pduPwrMonitoringOutlet 4 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletPduD
|
|
--
|
|
-- Outlet of Device4 management Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletNumPduD OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of PduD Outlet."
|
|
::= { pduPwrMonitoringOutletPduD 1}
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletStatusTablePduD
|
|
--
|
|
-- Outlet of Device3 Status Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletStatusTablePduD OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPwrMonitoringOutletStatusPduDEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display status of PduD outlet."
|
|
::= { pduPwrMonitoringOutletPduD 2}
|
|
|
|
pduPwrMonitoringOutletStatusPduDEntry OBJECT-TYPE
|
|
SYNTAX PduPwrMonitoringOutletStatusPduDEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display status of PduD outlet."
|
|
INDEX { outletPduDIndex}
|
|
::= { pduPwrMonitoringOutletStatusTablePduD 1 }
|
|
|
|
PduPwrMonitoringOutletStatusPduDEntry ::=
|
|
SEQUENCE {
|
|
outletPduDIndex
|
|
INTEGER,
|
|
outletPduDState
|
|
INTEGER,
|
|
outletPduDCurrent
|
|
INTEGER,
|
|
outletPduDPwrFactor
|
|
INTEGER,
|
|
outletPduDPower
|
|
INTEGER,
|
|
outletPduDEnergy
|
|
INTEGER,
|
|
outletPduDResetFrom
|
|
DisplayString,
|
|
outletPduDStatus
|
|
INTEGER
|
|
}
|
|
|
|
outletPduDIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..41)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to outlet status of PduD."
|
|
::= { pduPwrMonitoringOutletStatusPduDEntry 1 }
|
|
|
|
outletPduDState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The state of PduD outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduDEntry 2 }
|
|
|
|
outletPduDCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.01A"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current of PduD outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduDEntry 3 }
|
|
|
|
outletPduDPwrFactor OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1%"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power factor of PduD outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduDEntry 4 }
|
|
|
|
outletPduDPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1W"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power of PduD outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduDEntry 5 }
|
|
|
|
outletPduDEnergy OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "KWh"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The energy of PduD outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduDEntry 6 }
|
|
|
|
outletPduDResetFrom OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The reset date of PduD outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduDEntry 7 }
|
|
|
|
outletPduDStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
warning(2),
|
|
critical(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of PduD outlet."
|
|
::= { pduPwrMonitoringOutletStatusPduDEntry 8 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletCfgTablePduD
|
|
--
|
|
-- Outlet of Device4 Configuration Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletCfgTablePduD OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPwrMonitoringOutletCfgPduDEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display configuration of PduD outlet."
|
|
::= { pduPwrMonitoringOutletPduD 3}
|
|
|
|
pduPwrMonitoringOutletCfgPduDEntry OBJECT-TYPE
|
|
SYNTAX PduPwrMonitoringOutletCfgPduDEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display configuration of PduD outlet."
|
|
INDEX { outletCfgPduDIndex}
|
|
::= { pduPwrMonitoringOutletCfgTablePduD 1 }
|
|
|
|
PduPwrMonitoringOutletCfgPduDEntry ::=
|
|
SEQUENCE {
|
|
outletCfgPduDIndex
|
|
INTEGER,
|
|
outletCfgPduDName
|
|
DisplayString,
|
|
outletCfgPduDDelayOnStatus
|
|
INTEGER,
|
|
outletCfgPduDDelayOnTime
|
|
INTEGER,
|
|
outletCfgPduDDelayOffStatus
|
|
INTEGER,
|
|
outletCfgPduDDelayOffTime
|
|
INTEGER,
|
|
outletCfgPduDReboot
|
|
INTEGER,
|
|
outletCfgPduDOverCurrCritical
|
|
INTEGER,
|
|
outletCfgPduDOverCurrWarning
|
|
INTEGER,
|
|
outletCfgPduDOverPwrCritical
|
|
INTEGER,
|
|
outletCfgPduDOverPwrWarning
|
|
INTEGER
|
|
}
|
|
|
|
outletCfgPduDIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..41)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to outlet configuration of PduD."
|
|
::= { pduPwrMonitoringOutletCfgPduDEntry 1 }
|
|
|
|
outletCfgPduDName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name for outlet of PduD."
|
|
::= { pduPwrMonitoringOutletCfgPduDEntry 2 }
|
|
|
|
outletCfgPduDDelayOnStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
nodelay(1),
|
|
delay(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay On status of PduD outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduDEntry 3 }
|
|
|
|
outletCfgPduDDelayOnTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay On time of PduD outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduDEntry 4 }
|
|
|
|
outletCfgPduDDelayOffStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
nodelay(1),
|
|
delay(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay Off status of PduD outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduDEntry 5 }
|
|
|
|
outletCfgPduDDelayOffTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay Off time of PduD outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduDEntry 6 }
|
|
|
|
outletCfgPduDReboot OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay On reboot duration of PduD outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduDEntry 7 }
|
|
|
|
outletCfgPduDOverCurrCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of current of PduD outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduDEntry 8 }
|
|
|
|
outletCfgPduDOverCurrWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of current of PduD outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduDEntry 9 }
|
|
|
|
outletCfgPduDOverPwrCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1W"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Critical Threshold of power of PduD outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduDEntry 10 }
|
|
|
|
outletCfgPduDOverPwrWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "1W"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Warning Threshold of power of PduD outlet."
|
|
::= { pduPwrMonitoringOutletCfgPduDEntry 11 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- pduPwrMonitoringOutletCtlTablePduD
|
|
--
|
|
-- Outlet of Device4 Control Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduPwrMonitoringOutletCtlTablePduD OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPwrMonitoringOutletCtlPduDEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display control of PduD outlet."
|
|
::= { pduPwrMonitoringOutletPduD 4}
|
|
|
|
pduPwrMonitoringOutletCtlPduDEntry OBJECT-TYPE
|
|
SYNTAX PduPwrMonitoringOutletCtlPduDEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list to display control of PduD outlet."
|
|
INDEX { outletCtlPduDIndex}
|
|
::= { pduPwrMonitoringOutletCtlTablePduD 1 }
|
|
|
|
PduPwrMonitoringOutletCtlPduDEntry ::=
|
|
SEQUENCE {
|
|
outletCtlPduDIndex
|
|
INTEGER,
|
|
outletCtlPduDControl
|
|
INTEGER
|
|
}
|
|
|
|
outletCtlPduDIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..41)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to outlet control of PduD."
|
|
::= { pduPwrMonitoringOutletCtlPduDEntry 1 }
|
|
|
|
outletCtlPduDControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOn(1),
|
|
delayedOn(2),
|
|
immediateOff(3),
|
|
delayedOff(4),
|
|
immediateCycle(5),
|
|
delayedCycle(6)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The control-type of PduD outlet."
|
|
::= { pduPwrMonitoringOutletCtlPduDEntry 2 }
|
|
|
|
pduEnvMonitoringStatus OBJECT IDENTIFIER ::= { pduEnvMonitoring 1 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduEnvMonitoringStatus
|
|
--
|
|
-- Emd Status Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduEnvMonitoringTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degC"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The temperature of EMD."
|
|
::= { pduEnvMonitoringStatus 1 }
|
|
|
|
pduEnvMonitoringHumi OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1%"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The humidity of EMD."
|
|
::= { pduEnvMonitoringStatus 2 }
|
|
|
|
pduEnvMonitoringTempAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
warning(2),
|
|
critical(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The temperature status of EMD."
|
|
::= { pduEnvMonitoringStatus 3 }
|
|
|
|
pduEnvMonitoringHumiAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
warning(2),
|
|
critical(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The humidity status of EMD."
|
|
::= { pduEnvMonitoringStatus 4 }
|
|
|
|
pduEnvMonitoringCfg OBJECT IDENTIFIER ::= { pduEnvMonitoring 2 }
|
|
-- ===========================================================================
|
|
--
|
|
-- pduEnvMonitoringCfg
|
|
--
|
|
-- Emd Configuration Group.
|
|
--
|
|
-- ===========================================================================
|
|
pduEnvMonitoringControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the EMD."
|
|
::= { pduEnvMonitoringCfg 1 }
|
|
|
|
pduEnvMonitoringTempHighCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degC"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The High Critical Threshold of temperature of EMD."
|
|
::= { pduEnvMonitoringCfg 2 }
|
|
|
|
pduEnvMonitoringTempHighWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degC"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The High Warning Threshold of temperature of EMD."
|
|
::= { pduEnvMonitoringCfg 3 }
|
|
|
|
pduEnvMonitoringTempLowCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degC"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Low Critical Threshold of temperature of EMD."
|
|
::= { pduEnvMonitoringCfg 4 }
|
|
|
|
pduEnvMonitoringTempLowWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degC"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Low Warning Threshold of temperature of EMD."
|
|
::= { pduEnvMonitoringCfg 5 }
|
|
|
|
pduEnvMonitoringTempHystersis OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degC"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Hystersis of Temperature of EMD."
|
|
::= { pduEnvMonitoringCfg 6 }
|
|
|
|
pduEnvMonitoringTempOffset OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degC"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Offset of Temperature of EMD."
|
|
::= { pduEnvMonitoringCfg 7 }
|
|
|
|
pduEnvMonitoringHumiHighCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1%"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The High Crtitcal Threshold of humidity of EMD."
|
|
::= { pduEnvMonitoringCfg 8 }
|
|
|
|
pduEnvMonitoringHumiHighWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1%"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The High Warning Threshold of humidity of EMD."
|
|
::= { pduEnvMonitoringCfg 9 }
|
|
|
|
pduEnvMonitoringHumiLowCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1%"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Low Crtitcal Threshold of humidity of EMD."
|
|
::= { pduEnvMonitoringCfg 10 }
|
|
|
|
pduEnvMonitoringHumiLowWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1%"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Low Warning Threshold of humidity of EMD."
|
|
::= { pduEnvMonitoringCfg 11 }
|
|
|
|
pduEnvMonitoringHumiHystersis OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1%"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Hystersis of Humidity of EMD."
|
|
::= { pduEnvMonitoringCfg 12 }
|
|
|
|
pduEnvMonitoringHumiOffset OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1%"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Ofset of Humidity of EMD."
|
|
::= { pduEnvMonitoringCfg 13 }
|
|
|
|
-- ===========================================================================
|
|
-- pduTraps
|
|
--
|
|
-- iPoManIII Trap group
|
|
-- ===========================================================================
|
|
|
|
-- This section defines the well-known notifications sent by
|
|
-- agents.
|
|
|
|
pduSystemColdBoot TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Cold boot."
|
|
::= 1
|
|
|
|
pduSystemWarmBoot TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Warm boot."
|
|
::= 2
|
|
|
|
pduSystemRestart TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: System restart."
|
|
::= 3
|
|
|
|
pduResetToDefault TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Parameters reset to default."
|
|
::= 4
|
|
|
|
pduFirmUpgrade TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Firmware upgrade."
|
|
::= 5
|
|
|
|
pduSystemLogClear TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: System log cleared."
|
|
::= 6
|
|
|
|
pduEventlogClear TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Event log cleared."
|
|
::= 7
|
|
|
|
pduInletHistoryClear TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet history log cleared."
|
|
::= 8
|
|
|
|
pduOutletHistoryClear TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet history log cleared."
|
|
::= 9
|
|
|
|
pduSystemTimeChangeUser TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Time changed by user."
|
|
::= 10
|
|
|
|
pduSystemTimeChangeNtp TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Time synced with NTP server."
|
|
::= 11
|
|
|
|
pduSystemTimeChangeRtc TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Time changed by RTC."
|
|
::= 12
|
|
|
|
pduMailTestPass TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Test mail pass."
|
|
::= 13
|
|
|
|
pduMailTestFail TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Test mail failed."
|
|
::= 14
|
|
|
|
pduMailSentPass TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Mail sent successfully."
|
|
::= 15
|
|
|
|
pduMailSentFail TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Mail sent failed."
|
|
::= 16
|
|
|
|
pduSystemCfgChange TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Parameter changed."
|
|
::= 17
|
|
|
|
pduSystemParamImport TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Import XML configuration."
|
|
::= 18
|
|
|
|
pduInletCommLost TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet communication lost."
|
|
::= 19
|
|
|
|
pduInletCommRestore TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet communication restore."
|
|
::= 20
|
|
|
|
pduOutletCommLost TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet communication lost."
|
|
::= 21
|
|
|
|
pduOutletCommRestore TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet communication restore"
|
|
::= 22
|
|
|
|
pduOutletOnUser TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet turned on by user."
|
|
::= 23
|
|
|
|
pduOutletOnSchedule TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet turned on by schedule."
|
|
::= 24
|
|
|
|
pduOutletOffUser TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet turned off by user."
|
|
::= 25
|
|
|
|
pduOutletOffSchedule TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet turned off by schedule."
|
|
::= 26
|
|
|
|
pduOutletRebootUser TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet reboot by user."
|
|
::= 27
|
|
|
|
pduOutletRebootSchedule TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet reboot by schedule."
|
|
::= 28
|
|
|
|
pduInletEnergyReset TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet energy reset."
|
|
::= 29
|
|
|
|
pduOutletEnergyReset TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet energy reset."
|
|
::= 30
|
|
|
|
pduSetUser TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Assign outlet to user."
|
|
::= 31
|
|
|
|
pduDeletUser TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Delete user."
|
|
::= 32
|
|
|
|
pduUpgradeInletSuccess TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet upgrade successfully."
|
|
::= 33
|
|
|
|
pduUpgradeInletFail TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet upgrade fail."
|
|
::= 34
|
|
|
|
pduUpgradeOutletSuccess TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet upgrade successfully."
|
|
::= 35
|
|
|
|
pduUpgradeOutletFail TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet upgrade fail."
|
|
::= 36
|
|
|
|
pduEmdTempHighWarnToNormal TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Temperature had returned from high warning to normal."
|
|
::= 101
|
|
|
|
pduEmdTempHighWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Temperature was higher than high warning set point."
|
|
::= 102
|
|
|
|
pduEmdTempLowWarnToNormal TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Temperature had returned from low warning to normal."
|
|
::= 103
|
|
|
|
pduEmdTempLowWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Temperature was lower than low warning set point."
|
|
::= 104
|
|
|
|
pduEmdTempHighCritToWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Temperature had returned from high critical to high warning."
|
|
::= 105
|
|
|
|
pduEmdTempHighCritical TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Critical: Temperature was higher than high critical set point."
|
|
::= 106
|
|
|
|
pduEmdTempLowCritToWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Temperature had returned from low critical to low warning."
|
|
::= 107
|
|
|
|
pduEmdTempLowCritical TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Critical: Temperature was lower than low critical set point."
|
|
::= 108
|
|
|
|
pduEmdHumiHighWarnToNormal TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Humidity had returned from high warning to normal."
|
|
::= 109
|
|
|
|
pduEmdHumiHighWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Humidity was higher than high warning set point."
|
|
::= 110
|
|
|
|
pduEmdHumiLowWarnToNormal TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Humidity had returned from low warning to normal."
|
|
::= 111
|
|
|
|
pduEmdHumiLowWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Humidity was lower than low warning set point."
|
|
::= 112
|
|
|
|
pduEmdHumiHighCritToWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Humidity had returned from high critical to high warning."
|
|
::= 113
|
|
|
|
pduEmdHumiHighCritical TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Critical: Humidity was higher than high critical set point."
|
|
::= 114
|
|
|
|
pduEmdHumiLowCritToWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Humidity had returned from low critical to low warning."
|
|
::= 115
|
|
|
|
pduEmdHumiLowCritical TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Critical: Humidity was lower than low critical set point."
|
|
::= 116
|
|
|
|
pduEmdAlarm1NotActive TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Alarm-1 became inactive."
|
|
::= 117
|
|
|
|
pduEmdAlarm1Active TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Alarm-1 became active."
|
|
::= 118
|
|
|
|
pduEmdAlarm2NotActive TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Alarm-2 became inactive."
|
|
::= 119
|
|
|
|
pduEmdAlarm2Active TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Alarm-2 became active."
|
|
::= 120
|
|
|
|
pduRs485Online TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: RS485 Sensor was online."
|
|
::= 121
|
|
|
|
pduRs485Offline TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: RS485 Sensor was offline."
|
|
::= 122
|
|
|
|
pduInletLoadCritToWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet load had returned from critical to warning."
|
|
::= 123
|
|
|
|
pduInletLoadCritical TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Critical: Inlet load was higher than critical set point."
|
|
::= 124
|
|
|
|
pduInletLoadWarnToNormal TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet load had returned from warning to normal."
|
|
::= 125
|
|
|
|
pduInletLoadWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Inlet load was higher than warning set point."
|
|
::= 126
|
|
|
|
pduInletCurrPhase1CritToWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet phase1 current had returned from critical to warning."
|
|
::= 127
|
|
|
|
pduInletCurrPhase1Critical TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Critical: Inlet phase1 current was higher than critical set point."
|
|
::= 128
|
|
|
|
pduInletCurrPhase1WarnToNormal TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet phase1 current had returned from warning to normal."
|
|
::= 129
|
|
|
|
pduInletCurrPhase1Warn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Inlet phase1 current was higher than warning set point."
|
|
::= 130
|
|
|
|
pduInletCurrPhase2CritToWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet phase2 current had returned from critical to warning."
|
|
::= 131
|
|
|
|
pduInletCurrPhase2Critical TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Critical: Inlet phase2 current was higher than critical set point."
|
|
::= 132
|
|
|
|
pduInletCurrPhase2WarnToNormal TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet phase2 current had returned from warning to normal."
|
|
::= 133
|
|
|
|
pduInletCurrPhase2Warn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Inlet phase2 current was higher than warning set point."
|
|
::= 134
|
|
|
|
|
|
pduInletCurrPhase3CritToWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet phase3 current had returned from critical to warning."
|
|
::= 135
|
|
|
|
pduInletCurrPhase3Critical TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Critical: Inlet phase3 current was higher than critical set point."
|
|
::= 136
|
|
|
|
pduInletCurrPhase3WarnToNormal TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet phase3 current had returned from warning to normal."
|
|
::= 137
|
|
|
|
pduInletCurrPhase3Warn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Inlet phase3 current had returned from critical to warning."
|
|
::= 138
|
|
|
|
pduInletVoltPhase1CritToWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet phase1 voltage had returned from critical to warning."
|
|
::= 139
|
|
|
|
pduInletVoltPhase1Critical TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Critical: Inlet phase1 voltage was higher than critical set point."
|
|
::= 140
|
|
|
|
pduInletVoltPhase1WarnToNormal TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet phase1 voltage had returned from warning to normal."
|
|
::= 141
|
|
|
|
pduInletVoltPhase1Warn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Inlet phase1 voltage was higher than warning set point."
|
|
::= 142
|
|
|
|
pduInletVoltPhase2CritToWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet phase2 voltage had returned from critical to warning."
|
|
::= 143
|
|
|
|
pduInletVoltPhase2Critical TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Critical: Inlet phase2 voltage was higher than critical set point."
|
|
::= 144
|
|
|
|
pduInletVoltPhase2WarnToNormal TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet phase2 voltage had returned from warning to normal."
|
|
::= 145
|
|
|
|
pduInletVoltPhase2Warn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Inlet phase2 voltage was higher than warning set point."
|
|
::= 146
|
|
|
|
pduInletVoltPhase3CritToWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet phase3 voltage had returned from critical to warning."
|
|
::= 147
|
|
|
|
pduInletVoltPhase3Critical TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Critical: Inlet phase3 voltage was higher than critical set point."
|
|
::= 148
|
|
|
|
pduInletVoltPhase3WarnToNormal TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Inlet phase3 voltage had returned from warning to normal."
|
|
::= 149
|
|
|
|
pduInletVoltPhase3Warn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Inlet phase3 voltage was higher than warning set point."
|
|
::= 150
|
|
|
|
pduOutletCurrCritToWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet current had returned from critical to warning."
|
|
::= 151
|
|
|
|
pduOutletCurrCritical TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Critical: Outlet current was higher than critical set point."
|
|
::= 152
|
|
|
|
pduOutletCurrWarnToNormal TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet current had returned from warning to normal."
|
|
::= 153
|
|
|
|
pduOutletCurrWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Outlet current was higher than warning set point."
|
|
::= 154
|
|
|
|
pduOutletPwrCritTOWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet power had returned from critical to warning."
|
|
::= 155
|
|
|
|
pduOutletPwrCritical TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Critical: Outlet power was higher than critical set point."
|
|
::= 156
|
|
|
|
pduOutletPwrWarnToNormal TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Outlet power had returned from warning to normal."
|
|
::= 157
|
|
|
|
pduOutletPwrWarn TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Warning: Outlet power was higher than warning set point."
|
|
::= 158
|
|
|
|
pduAlarm1Disabled TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Alarm-1 became disabled."
|
|
::= 159
|
|
|
|
pduAlarm2Disabled TRAP-TYPE
|
|
ENTERPRISE pduTraps
|
|
DESCRIPTION
|
|
"Informational: Alarm-2 became disabled."
|
|
::= 160
|
|
|
|
END
|