mibs/MIBS/carel/CAREL-ug40cdz-MIB
2023-12-05 12:25:34 +01:00

1547 lines
54 KiB
Plaintext

--
-- CAREL-ug40cdz.MIB
-- MIB generated by CAREL
-- Tuesday, 11 April 2006
--
CAREL-ug40cdz-MIB DEFINITIONS ::= BEGIN
IMPORTS
OBJECT-GROUP FROM SNMPv2-CONF
sysContact, sysName,
sysLocation FROM SNMPv2-MIB
enterprises, MODULE-IDENTITY,
OBJECT-TYPE, Integer32 FROM SNMPv2-SMI
DisplayString FROM RFC1213-MIB;
ug40cdzMIB MODULE-IDENTITY
LAST-UPDATED "200604111645Z" -- April 11, 2006 at 16:45 GMT
ORGANIZATION "CAREL SpA"
CONTACT-INFO
"
Carel SpA
Via dell'Industria, 11
35020 Brugine (PD) Italy
Tel: +39 049 9716611
E-mail: carel@carel.com
"
DESCRIPTION
"This is the MIB module for the UG40 Close Control Uniflair device."
REVISION "200604111645Z" -- April 11, 2006 at 16:45 GMT
DESCRIPTION
"This is the original version of the MIB"
::= { instruments 1 }
--
-- Node definitions
--
-- 1.3.6.1.4.1.9839
carel OBJECT IDENTIFIER ::= { enterprises 9839 }
-- 1.3.6.1.4.1.9839.1
systm OBJECT IDENTIFIER ::= { carel 1 }
-- 1.3.6.1.4.1.9839.1.1
agentRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Release of the Agent."
::= { systm 1 }
-- 1.3.6.1.4.1.9839.1.2
agentCode OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Code of the Agent. 1=WebGate"
::= { systm 2 }
-- 1.3.6.1.4.1.9839.2
instruments OBJECT IDENTIFIER ::= { carel 2 }
-- 1.3.6.1.4.1.9839.2.0
webGateInfo OBJECT IDENTIFIER ::= { instruments 0 }
-- 1.3.6.1.4.1.9839.2.0.1
agentParameters OBJECT IDENTIFIER ::= { webGateInfo 1 }
-- 1.3.6.1.4.1.9839.2.0.1.1
netSize OBJECT-TYPE
SYNTAX Integer32 (1..16)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Network size. It corresponds to the number of units connected to the WebGate. "
::= { agentParameters 1 }
-- 1.3.6.1.4.1.9839.2.0.1.2
baudRate OBJECT-TYPE
SYNTAX Integer32 (1200 | 2400 |4800 |9600 | 19200)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Baudrate of the Carel network. "
::= { agentParameters 2 }
-- 1.3.6.1.4.1.9839.2.0.2
unitTypeGroup OBJECT IDENTIFIER ::= { webGateInfo 2 }
-- 1.3.6.1.4.1.9839.2.0.2.1
unit1-Type OBJECT-TYPE
SYNTAX DisplayString
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of the unit having serial address 1. "
::= { unitTypeGroup 1 }
-- ... You will have how many unitX-Type objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.3
unitCodeGroup OBJECT IDENTIFIER ::= { webGateInfo 3 }
-- 1.3.6.1.4.1.9839.2.0.3.1
unit1-Code OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Code of the unit having serial address 1. "
::= { unitCodeGroup 1 }
-- ... You will have how many unitX-Code objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.4
unitSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 4 }
-- 1.3.6.1.4.1.9839.2.0.3.1
unit1-SoftwareRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Software release of the unit having serial address 1. "
::= { unitSoftwareReleaseGroup 1 }
-- ... You will have how many unitX-SoftwareRelease objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.5
unitMinSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 5 }
-- 1.3.6.1.4.1.9839.2.0.5.1
unit1-MinSoftwareRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Minimum software release of the unit having serial address 1. "
::= { unitMinSoftwareReleaseGroup 1 }
-- ... You will have how many unitX-MinSoftwareRelease objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.6
unitMaxSoftwareReleaseGroup OBJECT IDENTIFIER ::= { webGateInfo 6 }
-- 1.3.6.1.4.1.9839.2.0.6.1
unit1-MaxSoftwareRelease OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Maximum software release of the unit having serial address 1. "
::= { unitMaxSoftwareReleaseGroup 1 }
-- ... You will have how many unitX-MaxSoftwareRelease objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.7
unitNoAnswerCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 7 }
-- 1.3.6.1.4.1.9839.2.0.7.1
unit1-NoAnswerCounter OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "No answer counter of the unit having serial address 1. "
::= { unitNoAnswerCounterGroup 1 }
-- ... You will have how many unitX-NoAnswerCounter objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.8
unitErrorChecksumCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 8 }
-- 1.3.6.1.4.1.9839.2.0.8.1
unit1-ErrorChecksumCounter OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Error checksum counter of the unit having serial address 1. "
::= { unitErrorChecksumCounterGroup 1 }
-- ... You will have how many unitX-ErrorChecksumCounter objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.0.9
unitTimeoutCounterGroup OBJECT IDENTIFIER ::= { webGateInfo 9 }
-- 1.3.6.1.4.1.9839.2.0.9.1
unit1-TimeoutCounter OBJECT-TYPE
SYNTAX Integer32
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Timeout counter of the unit having serial address 1. "
::= { unitTimeoutCounterGroup 1 }
-- ... You will have how many unitX-TimeoutCounter objects as the value of netSize is
-- 1.3.6.1.4.1.9839.2.1
-- ug40cdzMIB OBJECT IDENTIFIER ::= { instruments 1 }
-- 1.3.6.1.4.1.9839.2.1.1
digitalObjects OBJECT IDENTIFIER ::= { ug40cdzMIB 1 }
-- 1.3.6.1.4.1.9839.2.1.1.1
systemOn OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "System On (Fan)"
::= { digitalObjects 1 }
-- 1.3.6.1.4.1.9839.2.1.1.2
compressore1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compressor 1"
::= { digitalObjects 2 }
-- 1.3.6.1.4.1.9839.2.1.1.3
compressore2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compressor 2"
::= { digitalObjects 3 }
-- 1.3.6.1.4.1.9839.2.1.1.4
compressore3 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compressor 3"
::= { digitalObjects 4 }
-- 1.3.6.1.4.1.9839.2.1.1.5
compressore4 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compressor 4"
::= { digitalObjects 5 }
-- 1.3.6.1.4.1.9839.2.1.1.6
heating1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Heating 1"
::= { digitalObjects 6 }
-- 1.3.6.1.4.1.9839.2.1.1.7
heating2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Heating 2"
::= { digitalObjects 7 }
-- 1.3.6.1.4.1.9839.2.1.1.9
hotGasCoil OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Hot Gas Coil"
::= { digitalObjects 9 }
-- 1.3.6.1.4.1.9839.2.1.1.10
dehumidification OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Dehumidification"
::= { digitalObjects 10 }
-- 1.3.6.1.4.1.9839.2.1.1.11
humidification OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Humidification"
::= { digitalObjects 11 }
-- 1.3.6.1.4.1.9839.2.1.1.12
emerg OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Main Power Loss"
::= { digitalObjects 12 }
-- 1.3.6.1.4.1.9839.2.1.1.20
alarmAccess OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Tampering Alarm"
::= { digitalObjects 20 }
-- 1.3.6.1.4.1.9839.2.1.1.21
alarmRoomHT OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Room High Temperature"
::= { digitalObjects 21 }
-- 1.3.6.1.4.1.9839.2.1.1.22
alarmRoomLT OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Room Low Temperature"
::= { digitalObjects 22 }
-- 1.3.6.1.4.1.9839.2.1.1.23
alarmRoomHH OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Room High Humidity"
::= { digitalObjects 23 }
-- 1.3.6.1.4.1.9839.2.1.1.24
alarmRoomLH OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Room Low Humidity"
::= { digitalObjects 24 }
-- 1.3.6.1.4.1.9839.2.1.1.25
alarmRoomEAP OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Room T+H Limits by External Sensors"
::= { digitalObjects 25 }
-- 1.3.6.1.4.1.9839.2.1.1.26
alarmFilter OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Clogged Filter"
::= { digitalObjects 26 }
-- 1.3.6.1.4.1.9839.2.1.1.27
alarmFlood OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Water Leakage Detected"
::= { digitalObjects 27 }
-- 1.3.6.1.4.1.9839.2.1.1.28
alarmAirFlow OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Loss of Air Flow"
::= { digitalObjects 28 }
-- 1.3.6.1.4.1.9839.2.1.1.29
alarmHeater OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Heater Overheating"
::= { digitalObjects 29 }
-- 1.3.6.1.4.1.9839.2.1.1.30
alarmHP1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Circuit 1 High Pressure"
::= { digitalObjects 30 }
-- 1.3.6.1.4.1.9839.2.1.1.31
alarmHP2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Circuit 1 High Pressure"
::= { digitalObjects 31 }
-- 1.3.6.1.4.1.9839.2.1.1.32
alarmLP1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Circuit 1 Low Pressure"
::= { digitalObjects 32 }
-- 1.3.6.1.4.1.9839.2.1.1.33
alarmLP2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Circuit 2 Low Pressure"
::= { digitalObjects 33 }
-- 1.3.6.1.4.1.9839.2.1.1.34
alarmEXV1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Circuit 1 Electronic Valve Failure"
::= { digitalObjects 34 }
-- 1.3.6.1.4.1.9839.2.1.1.35
alarmEXV2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Circuit 2 Electronic Valve Failure"
::= { digitalObjects 35 }
-- 1.3.6.1.4.1.9839.2.1.1.36
alarmPSE OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Wrong Phase Sequence"
::= { digitalObjects 36 }
-- 1.3.6.1.4.1.9839.2.1.1.37
alarmSmokeFire OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: SMOKE-FIRE DETECTED"
::= { digitalObjects 37 }
-- 1.3.6.1.4.1.9839.2.1.1.38
alarmLAN OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Interrupted LAN Alarm"
::= { digitalObjects 38 }
-- 1.3.6.1.4.1.9839.2.1.1.39
alarmHUHC OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Humidifier High Current"
::= { digitalObjects 39 }
-- 1.3.6.1.4.1.9839.2.1.1.40
alarmHUPL OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Humidifier Power Loss"
::= { digitalObjects 40 }
-- 1.3.6.1.4.1.9839.2.1.1.41
alarmHUWL OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Humidifier Water Loss"
::= { digitalObjects 41 }
-- 1.3.6.1.4.1.9839.2.1.1.42
alarmCWDHT OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: CW Temperature too High for Dehumidification"
::= { digitalObjects 42 }
-- 1.3.6.1.4.1.9839.2.1.1.43
alarmCWF OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: CW Valve Failure or Water Flow too Low"
::= { digitalObjects 43 }
-- 1.3.6.1.4.1.9839.2.1.1.44
alarmCWFF OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Loss of Water Flow"
::= { digitalObjects 44 }
-- 1.3.6.1.4.1.9839.2.1.1.45
alarmCWHT OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: High Chilled Water Temperature"
::= { digitalObjects 45 }
-- 1.3.6.1.4.1.9839.2.1.1.46
alarmRTS OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Room Temp. Sensor Failed/Disconnected"
::= { digitalObjects 46 }
-- 1.3.6.1.4.1.9839.2.1.1.47
alarmHWS OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Hot Water Temp. Sensor Failed/Disconnected"
::= { digitalObjects 47 }
-- 1.3.6.1.4.1.9839.2.1.1.48
alarmCWS OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Chilled Water Temp. Sensor Failed/Disconnected"
::= { digitalObjects 48 }
-- 1.3.6.1.4.1.9839.2.1.1.49
alarmOTS OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Outdoor Temperature Sensor Failed/Disconnected"
::= { digitalObjects 49 }
-- 1.3.6.1.4.1.9839.2.1.1.50
alarmDTS OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Delivery Air Temp. Sensor Failed/Disconnected"
::= { digitalObjects 50 }
-- 1.3.6.1.4.1.9839.2.1.1.51
alarmRHS OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Room Humidity Sensor Failed/Disconnected"
::= { digitalObjects 51 }
-- 1.3.6.1.4.1.9839.2.1.1.52
alarmCWOTS OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm: Chilled Water Outlet T. Sensor Failed/Disconnected"
::= { digitalObjects 52 }
-- 1.3.6.1.4.1.9839.2.1.1.53
alarmC1Hours OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "ServiceAlarm: Compressor 1 hour counter threshold"
::= { digitalObjects 53 }
-- 1.3.6.1.4.1.9839.2.1.1.54
alarmC2Hours OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "ServiceAlarm: Compressor 2 hour counter threshold"
::= { digitalObjects 54 }
-- 1.3.6.1.4.1.9839.2.1.1.55
alarmC3Hours OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "ServiceAlarm: Compressor 3 hour counter threshold"
::= { digitalObjects 55 }
-- 1.3.6.1.4.1.9839.2.1.1.56
alarmC4Hours OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "ServiceAlarm: Compressor 4 hour counter threshold"
::= { digitalObjects 56 }
-- 1.3.6.1.4.1.9839.2.1.1.57
alarmFilterHours OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "ServiceAlarm: Air Filter hour counter threshold"
::= { digitalObjects 57 }
-- 1.3.6.1.4.1.9839.2.1.1.58
alarmHeat1Hours OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "ServiceAlarm: Heater 1 hour counter threshold"
::= { digitalObjects 58 }
-- 1.3.6.1.4.1.9839.2.1.1.59
alarmHeat2Hours OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "ServiceAlarm: Heater 1 hour counter threshold"
::= { digitalObjects 59 }
-- 1.3.6.1.4.1.9839.2.1.1.60
alarmHumHours OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "ServiceAlarm: Humidifier hour counter threshold"
::= { digitalObjects 60 }
-- 1.3.6.1.4.1.9839.2.1.1.61
alarmUnitHours OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "ServiceAlarm: Unit hour counter threshold"
::= { digitalObjects 61 }
-- 1.3.6.1.4.1.9839.2.1.1.62
alarmDI2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm by Digital Input 2"
::= { digitalObjects 62 }
-- 1.3.6.1.4.1.9839.2.1.1.63
alarmDI4 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm by Digital Input 4"
::= { digitalObjects 63 }
-- 1.3.6.1.4.1.9839.2.1.1.64
alarmDI6 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Alarm by Digital Input 6"
::= { digitalObjects 64 }
-- 1.3.6.1.4.1.9839.2.1.1.65
alarmHum OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Humidifier General Alarm"
::= { digitalObjects 65 }
-- 1.3.6.1.4.1.9839.2.1.1.66
alarmGeneral OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "General Alarm"
::= { digitalObjects 66 }
-- 1.3.6.1.4.1.9839.2.1.1.67
alarm2ndLevel OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Standby Unit Switchover Alarm"
::= { digitalObjects 67 }
-- 1.3.6.1.4.1.9839.2.1.1.68
alarmA OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type A Alarm"
::= { digitalObjects 68 }
-- 1.3.6.1.4.1.9839.2.1.1.69
alarmB OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type B Alarm"
::= { digitalObjects 69 }
-- 1.3.6.1.4.1.9839.2.1.1.70
alarmC OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type C Alarm"
::= { digitalObjects 70 }
-- 1.3.6.1.4.1.9839.2.1.1.71
selDXCW OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "DX/CW Switch on TC Units"
::= { digitalObjects 71 }
-- 1.3.6.1.4.1.9839.2.1.1.72
selSW OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Summer/Winter Switchover"
::= { digitalObjects 72 }
-- 1.3.6.1.4.1.9839.2.1.1.75
systemOnOff OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "System On-Off"
::= { digitalObjects 75 }
-- 1.3.6.1.4.1.9839.2.1.1.76
resetAlarm OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Alarm Reset"
::= { digitalObjects 76 }
-- 1.3.6.1.4.1.9839.2.1.1.77
resetHrsFilt OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Filter Run Hours Reset"
::= { digitalObjects 77 }
-- 1.3.6.1.4.1.9839.2.1.1.78
resetHrC1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compressor 1 Run Hours Reset"
::= { digitalObjects 78 }
-- 1.3.6.1.4.1.9839.2.1.1.79
resetHrC2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compressor 2 Run Hours Reset"
::= { digitalObjects 79 }
-- 1.3.6.1.4.1.9839.2.1.1.80
resetHrC3 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compressor 3 Run Hours Reset"
::= { digitalObjects 80 }
-- 1.3.6.1.4.1.9839.2.1.1.81
resetHrC4 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compressor 4 Run Hours Reset"
::= { digitalObjects 81 }
-- 1.3.6.1.4.1.9839.2.1.1.82
resetStC1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compressor 1 Starting Counter Reset "
::= { digitalObjects 82 }
-- 1.3.6.1.4.1.9839.2.1.1.83
resetStC2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compressor 2 Starting Counter Reset "
::= { digitalObjects 83 }
-- 1.3.6.1.4.1.9839.2.1.1.84
resetStC3 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compressor 3 Starting Counter Reset "
::= { digitalObjects 84 }
-- 1.3.6.1.4.1.9839.2.1.1.85
resetStC4 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Compressor 4 Starting Counter Reset "
::= { digitalObjects 85 }
-- 1.3.6.1.4.1.9839.2.1.1.86
resetHrH1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heater 1 Run Hours Reset"
::= { digitalObjects 86 }
-- 1.3.6.1.4.1.9839.2.1.1.87
resetHrH2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heater 2 Run Hours Reset"
::= { digitalObjects 87 }
-- 1.3.6.1.4.1.9839.2.1.1.88
resetStH1 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heater 1 Starting Counter Reset"
::= { digitalObjects 88 }
-- 1.3.6.1.4.1.9839.2.1.1.89
resetStH2 OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heater 2 Starting Counter Reset"
::= { digitalObjects 89 }
-- 1.3.6.1.4.1.9839.2.1.1.90
resetHrHU OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Humidifier Run Hours Reset"
::= { digitalObjects 90 }
-- 1.3.6.1.4.1.9839.2.1.1.91
resetStHU OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Humidifier Starting Counter Reset"
::= { digitalObjects 91 }
-- 1.3.6.1.4.1.9839.2.1.1.92
resetHrACU OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Unit Run Hours Reset"
::= { digitalObjects 92 }
-- 1.3.6.1.4.1.9839.2.1.1.95
sleepmode OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Setback Mode (Sleep Mode)"
::= { digitalObjects 95 }
-- 1.3.6.1.4.1.9839.2.1.1.96
smtest OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Sleep Mode Test"
::= { digitalObjects 96 }
-- 1.3.6.1.4.1.9839.2.1.1.97
enablemeanT OBJECT-TYPE
SYNTAX Integer32 (0..1)
UNITS "N/A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Local/Mean Usage of Values"
::= { digitalObjects 97 }
-- 1.3.6.1.4.1.9839.2.1.2
analogObjects OBJECT IDENTIFIER ::= { ug40cdzMIB 2 }
-- 1.3.6.1.4.1.9839.2.1.2.1
roomTemp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Room Temperature"
::= { analogObjects 1 }
-- 1.3.6.1.4.1.9839.2.1.2.2
outdoorTemp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Ambient Temperature"
::= { analogObjects 2 }
-- 1.3.6.1.4.1.9839.2.1.2.3
deliveryTemp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delivery Air Temperature"
::= { analogObjects 3 }
-- 1.3.6.1.4.1.9839.2.1.2.4
cwTemp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Chilled Water Temperature"
::= { analogObjects 4 }
-- 1.3.6.1.4.1.9839.2.1.2.5
hwTemp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Hot Water Temperature"
::= { analogObjects 5 }
-- 1.3.6.1.4.1.9839.2.1.2.6
roomRH OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "rH%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Room Relative Humidity"
::= { analogObjects 6 }
-- 1.3.6.1.4.1.9839.2.1.2.7
cwoTemp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Chilled Water Outlet Temperature"
::= { analogObjects 7 }
-- 1.3.6.1.4.1.9839.2.1.2.8
evapPress1 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "bar"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Circuit 1 Evaporating Pressure"
::= { analogObjects 8 }
-- 1.3.6.1.4.1.9839.2.1.2.9
evapPress2 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "bar"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Circuit 2 Evaporating Pressure"
::= { analogObjects 9 }
-- 1.3.6.1.4.1.9839.2.1.2.10
suctTemp1 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Circuit 1 Suction Temperature"
::= { analogObjects 10 }
-- 1.3.6.1.4.1.9839.2.1.2.11
suctTemp2 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Circuit 2 Suction Temperature"
::= { analogObjects 11 }
-- 1.3.6.1.4.1.9839.2.1.2.12
evapTemp1 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Circuit 1 Evap.Temperature"
::= { analogObjects 12 }
-- 1.3.6.1.4.1.9839.2.1.2.13
evapTemp2 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Circuit 2 Evap.Temperature"
::= { analogObjects 13 }
-- 1.3.6.1.4.1.9839.2.1.2.14
ssh1 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Circuit 1 Superheat"
::= { analogObjects 14 }
-- 1.3.6.1.4.1.9839.2.1.2.15
ssh2 OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Circuit 2 Superheat"
::= { analogObjects 15 }
-- 1.3.6.1.4.1.9839.2.1.2.16
coolRamp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Cooling Valve Ramp"
::= { analogObjects 16 }
-- 1.3.6.1.4.1.9839.2.1.2.17
heatRamp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Heating Valve Ramp"
::= { analogObjects 17 }
-- 1.3.6.1.4.1.9839.2.1.2.18
fanSpeed OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Evapor. Fan Speed"
::= { analogObjects 18 }
-- 1.3.6.1.4.1.9839.2.1.2.20
coolSetP OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling Set Point"
::= { analogObjects 20 }
-- 1.3.6.1.4.1.9839.2.1.2.21
coolDiff OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling Prop.Band"
::= { analogObjects 21 }
-- 1.3.6.1.4.1.9839.2.1.2.22
cool2SetP OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Cooling 2nd Set Point"
::= { analogObjects 22 }
-- 1.3.6.1.4.1.9839.2.1.2.23
heatSetP OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heating Set point"
::= { analogObjects 23 }
-- 1.3.6.1.4.1.9839.2.1.2.24
heat2SetP OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heating 2nd Set point"
::= { analogObjects 24 }
-- 1.3.6.1.4.1.9839.2.1.2.25
heatDiff OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Heating Prop.Band"
::= { analogObjects 25 }
-- 1.3.6.1.4.1.9839.2.1.2.26
thrsHT OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "High Room Temperature Alarm Threshold"
::= { analogObjects 26 }
-- 1.3.6.1.4.1.9839.2.1.2.27
thrsLT OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Low Room Temperature Alarm Threshold"
::= { analogObjects 27 }
-- 1.3.6.1.4.1.9839.2.1.2.28
smCoolSetp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Setback Mode: Cooling Setpoint"
::= { analogObjects 28 }
-- 1.3.6.1.4.1.9839.2.1.2.29
smHeatSetp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Setback Mode: Heating Setpoint"
::= { analogObjects 29 }
-- 1.3.6.1.4.1.9839.2.1.2.30
cwDehumSetp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "CW Setpoint to Start Dehumidification"
::= { analogObjects 30 }
-- 1.3.6.1.4.1.9839.2.1.2.31
cwHtThrsh OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "CW High Temperature Alarm Threshold"
::= { analogObjects 31 }
-- 1.3.6.1.4.1.9839.2.1.2.32
cwModeSetp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "CW Setpoint to start CW Operating Mode (Only TC Units)"
::= { analogObjects 32 }
-- 1.3.6.1.4.1.9839.2.1.2.33
radcoolSpES OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Radcooler Setpoint in Energy Saving Mode"
::= { analogObjects 33 }
-- 1.3.6.1.4.1.9839.2.1.2.34
radcoolSpDX OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Radcooler Setpoint in DX Mode"
::= { analogObjects 34 }
-- 1.3.6.1.4.1.9839.2.1.2.35
delTempLimit OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C x10"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delivery Temperature Low Limit Setpoint"
::= { analogObjects 35 }
-- 1.3.6.1.4.1.9839.2.1.2.36
dtAutChgMLT OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "degrees C"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Delta Temperature for Automatic Mean/Local Changeover"
::= { analogObjects 36 }
-- 1.3.6.1.4.1.9839.2.1.3
integerObjects OBJECT IDENTIFIER ::= { ug40cdzMIB 3 }
-- 1.3.6.1.4.1.9839.2.1.3.1
filterWorkH OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "h"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Air Filter Working Houres"
::= { integerObjects 1 }
-- 1.3.6.1.4.1.9839.2.1.3.2
unitWorkH OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "h"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Unit Working Houres"
::= { integerObjects 2 }
-- 1.3.6.1.4.1.9839.2.1.3.3
compr1WorkH OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "h"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compressor 1 Run Hours"
::= { integerObjects 3 }
-- 1.3.6.1.4.1.9839.2.1.3.4
compr2WorkH OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "h"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compressor 2 Run Hours"
::= { integerObjects 4 }
-- 1.3.6.1.4.1.9839.2.1.3.5
compr3WorkH OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "h"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compressor 3 Run Hours"
::= { integerObjects 5 }
-- 1.3.6.1.4.1.9839.2.1.3.6
compr4WorkH OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "h"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Compressor 4 Run Hours"
::= { integerObjects 6 }
-- 1.3.6.1.4.1.9839.2.1.3.7
heat1WorkH OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "h"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Heater 1 Run Hours"
::= { integerObjects 7 }
-- 1.3.6.1.4.1.9839.2.1.3.8
heat2WorkH OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "h"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Heater 2 Run Hours"
::= { integerObjects 8 }
-- 1.3.6.1.4.1.9839.2.1.3.9
humiWorkH OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "h"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Humidifier Run Hours"
::= { integerObjects 9 }
-- 1.3.6.1.4.1.9839.2.1.3.12
dehumPband OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "rH%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Dehumidification Prop.Band"
::= { integerObjects 12 }
-- 1.3.6.1.4.1.9839.2.1.3.13
humidPband OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "rH%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Humidification Prop.Band"
::= { integerObjects 13 }
-- 1.3.6.1.4.1.9839.2.1.3.14
hhAlarmThrsh OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "rH%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "High Humidity Alarm Threshold"
::= { integerObjects 14 }
-- 1.3.6.1.4.1.9839.2.1.3.15
lhAlarmThrsh OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "rH%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Low Humidity Alarm Threshold"
::= { integerObjects 15 }
-- 1.3.6.1.4.1.9839.2.1.3.16
dehumSetp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "rH%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Dehumidification Setpoint"
::= { integerObjects 16 }
-- 1.3.6.1.4.1.9839.2.1.3.17
smDehumSetp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "rH%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Setback Mode: Dehumidification Setpoint"
::= { integerObjects 17 }
-- 1.3.6.1.4.1.9839.2.1.3.18
humidSetp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "rH%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Humidification Setpoint"
::= { integerObjects 18 }
-- 1.3.6.1.4.1.9839.2.1.3.19
smHumidSetp OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "rH%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Setback Mode: Humidification Setpoint"
::= { integerObjects 19 }
-- 1.3.6.1.4.1.9839.2.1.3.20
pwOnDelay OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "s"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Restart Delay"
::= { integerObjects 20 }
-- 1.3.6.1.4.1.9839.2.1.3.21
regulDelay OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "s"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Regulation Start Transitory"
::= { integerObjects 21 }
-- 1.3.6.1.4.1.9839.2.1.3.22
lowPdelay OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "s"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Low Pressure Delay"
::= { integerObjects 22 }
-- 1.3.6.1.4.1.9839.2.1.3.23
thAlarmdelay OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Temp./Humid.Limits Alarm Delay"
::= { integerObjects 23 }
-- 1.3.6.1.4.1.9839.2.1.3.24
regExcTime OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Anti-Hunting Constant"
::= { integerObjects 24 }
-- 1.3.6.1.4.1.9839.2.1.3.25
stdbyTime OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "h"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Stand-by Cycle Base Time"
::= { integerObjects 25 }
-- 1.3.6.1.4.1.9839.2.1.3.27
lanUnit OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "n"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Number of LAN Units"
::= { integerObjects 27 }
-- 1.3.6.1.4.1.9839.2.1.3.28
smCycleTime OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "min"
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Sleep Mode Testing Cycle Time"
::= { integerObjects 28 }
-- 1.3.6.1.4.1.9839.2.1.3.29
exv1steps OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "n"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Circuit 1 EXV Valve Position"
::= { integerObjects 29 }
-- 1.3.6.1.4.1.9839.2.1.3.30
exv2steps OBJECT-TYPE
SYNTAX Integer32 (-32767..32767)
UNITS "n"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Circuit 2 EXV Valve Position"
::= { integerObjects 30 }
END
--
-- CAREL-ug40cdz.MIB
--