-- C&C Power DC_SYSTEM MIB
|
||
-- Management Information Base for SNMP Network Management
|
||
--
|
||
-- Copyright 2004 C&C Power, Inc.
|
||
--
|
||
-- C&C Power shall not be liable for technical or
|
||
-- editorial errors or omissions contained herein. The information in
|
||
-- this document is provided "as is" without warranty of any kind and
|
||
-- is subject to change without notice. The warranties for C&C Power products
|
||
-- are set forth in the express limited warranty statements
|
||
-- accompanying such products. Nothing herein should be construed as
|
||
-- constituting an additional warranty.
|
||
--
|
||
-- The C&C Power Enterprise number is 18642.
|
||
-- The ASN.1 prefix to, and including the C&C Power Enterprise is:
|
||
-- 1.3.6.1.4.1.18642
|
||
--
|
||
-- MIB Version 1.0
|
||
-- *********************************************************************
|
||
-- Release History
|
||
-- Initial Release Date: August 9, 2004 (Version 1.0)
|
||
-- Author: Jeff Gear
|
||
-- Revision History
|
||
-- Date:
|
||
-- Revision:
|
||
-- *********************************************************************
|
||
|
||
CCPOWER-MIB DEFINITIONS ::= BEGIN
|
||
|
||
IMPORTS
|
||
enterprises FROM RFC1155-SMI
|
||
DisplayString FROM RFC1213-MIB
|
||
OBJECT-TYPE FROM RFC-1212
|
||
TRAP-TYPE FROM RFC-1215;
|
||
|
||
ccpower OBJECT IDENTIFIER ::= { enterprises 18642 }
|
||
dcSystem OBJECT IDENTIFIER ::= { ccpower 1 }
|
||
|
||
-- *********************************************************************
|
||
-- readWriteObjects definition
|
||
-- *********************************************************************
|
||
|
||
readWriteObjects OBJECT IDENTIFIER ::= { dcSystem 1 }
|
||
|
||
-- *********************************************************************
|
||
-- readWriteObjects.settings definition
|
||
-- *********************************************************************
|
||
|
||
settings OBJECT IDENTIFIER ::= { readWriteObjects 1 }
|
||
|
||
floatVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Rectifier DC Output Voltage.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 1 }
|
||
|
||
overloadCurrent OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Current which when exceeded will cause an alarm.
|
||
Return value is XXXX representing XXXX amps."
|
||
::= { settings 2 }
|
||
|
||
highVoltageAlarm OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when exceeded will cause an alarm.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 3 }
|
||
|
||
lowVoltageAlarm OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when exceeded will cause an alarm.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 4 }
|
||
|
||
disconnect1Voltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when exceeded will cause a specific load to disconnect.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 5 }
|
||
|
||
disconnect1Temperature OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Temperature which when exceeded will cause a specific load to disconnect.
|
||
Return value is XX representing XX <20>C."
|
||
::= { settings 6 }
|
||
|
||
disconnect1LoadShedSundayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Sunday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 7 }
|
||
|
||
disconnect1LoadShedMondayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Monday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 8 }
|
||
|
||
disconnect1LoadShedTuesdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Tuesday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 9 }
|
||
|
||
disconnect1LoadShedWednesdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Wednesday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 10 }
|
||
|
||
disconnect1LoadShedThursdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Thursday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 11 }
|
||
|
||
disconnect1LoadShedFridayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Friday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 12 }
|
||
|
||
disconnect1LoadShedSaturdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Saturday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 13 }
|
||
|
||
disconnect2Voltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when exceeded will cause a specific load to disconnect.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 14 }
|
||
|
||
disconnect2Temperature OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Temperature which when exceeded will cause a specific load to disconnect.
|
||
Return value is XX representing XX <20>C."
|
||
::= { settings 15 }
|
||
|
||
disconnect2LoadShedSundayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Sunday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 16 }
|
||
|
||
disconnect2LoadShedMondayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Monday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 17 }
|
||
|
||
disconnect2LoadShedTuesdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Tuesday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 18 }
|
||
|
||
disconnect2LoadShedWednesdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Wednesday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 19 }
|
||
|
||
disconnect2LoadShedThursdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Thursday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 20 }
|
||
|
||
disconnect2LoadShedFridayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Friday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 21 }
|
||
|
||
disconnect2LoadShedSaturdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Saturday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 22 }
|
||
|
||
disconnect3Voltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when exceeded will cause a specific load to disconnect.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 23 }
|
||
|
||
disconnect3Temperature OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Temperature which when exceeded will cause a specific load to disconnect.
|
||
Return value is XX representing XX <20>C."
|
||
::= { settings 24 }
|
||
|
||
disconnect3LoadShedSundayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Sunday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 25 }
|
||
|
||
disconnect3LoadShedMondayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Monday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 26 }
|
||
|
||
disconnect3LoadShedTuesdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Tuesday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 27 }
|
||
|
||
disconnect3LoadShedWednesdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Wednesday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 28 }
|
||
|
||
disconnect3LoadShedThursdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Thursday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 29 }
|
||
|
||
disconnect3LoadShedFridayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Friday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 30 }
|
||
|
||
disconnect3LoadShedSaturdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Saturday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 31 }
|
||
|
||
reconnect1Voltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when reached will cause a specific load to reconnect.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 32 }
|
||
|
||
reconnect1LoadShedSundayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 33 }
|
||
|
||
reconnect1LoadShedMondayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Monday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 34 }
|
||
|
||
reconnect1LoadShedTuesdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Tuesday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 35 }
|
||
|
||
reconnect1LoadShedWednesdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Wednesday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 36 }
|
||
|
||
reconnect1LoadShedThursdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Thursday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 37 }
|
||
|
||
reconnect1LoadShedFridayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Friday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 38 }
|
||
|
||
reconnect1LoadShedSaturdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Saturday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 39 }
|
||
|
||
reconnect2Voltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when reached will cause a specific load to reconnect.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 40 }
|
||
|
||
reconnect2LoadShedSundayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Sunday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 41 }
|
||
|
||
reconnect2LoadShedMondayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Monday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 42 }
|
||
|
||
reconnect2LoadShedTuesdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Tuesday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 43 }
|
||
|
||
reconnect2LoadShedWednesdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Wednesday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 44 }
|
||
|
||
reconnect2LoadShedThursdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Thursday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 45 }
|
||
|
||
reconnect2LoadShedFridayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Friday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 46 }
|
||
|
||
reconnect2LoadShedSaturdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Saturday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 47 }
|
||
|
||
reconnect3Voltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when reached will cause a specific load to reconnect.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 48 }
|
||
|
||
reconnect3LoadShedSundayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Sunday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 49 }
|
||
|
||
reconnect3LoadShedMondayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Monday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 50 }
|
||
|
||
reconnect3LoadShedTuesdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Tuesday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 51 }
|
||
|
||
reconnect3LoadShedWednesdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Wednesday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 52 }
|
||
|
||
reconnect3LoadShedThursdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Thursday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 53 }
|
||
|
||
reconnect3LoadShedFridayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Friday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 54 }
|
||
|
||
reconnect3LoadShedSaturdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Saturday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 55 }
|
||
|
||
equalizeTime OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Number of hours the equalize voltage is to be applied.
|
||
Return value is XXX representing XX.X hours."
|
||
::= { settings 56 }
|
||
|
||
equalizeVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Equalize voltage to be applied.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 57 }
|
||
|
||
batteryResistancePercentChange OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Resistance percentange change that when reached will cause an alarm.
|
||
Return value is XXX representing XXX %."
|
||
::= { settings 58 }
|
||
|
||
batteryResistanceTestInterval OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery resistance test interval.
|
||
Return value is XX representing XX weeks."
|
||
::= { settings 59 }
|
||
|
||
loadShedTimeControl OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
enabled(1),
|
||
disabled(2)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Load shed time control enabled/disabled status.
|
||
Return value: 1 = time control enabled, 2 = time control disabled."
|
||
::= { settings 60 }
|
||
|
||
batteryFloatCurrent OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery float current.
|
||
Return value is XXX representing XXX amps."
|
||
::= { settings 61 }
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects definition
|
||
-- *********************************************************************
|
||
|
||
readOnlyObjects OBJECT IDENTIFIER ::= { dcSystem 2 }
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.rectifiers definition
|
||
-- *********************************************************************
|
||
|
||
rectifiers OBJECT IDENTIFIER ::= { readOnlyObjects 1 }
|
||
|
||
rectifierFloatVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Rectifier float voltage.
|
||
Return value is XXX representing XX.X volts. Valid ranges are 24.0 to 57.0 volts."
|
||
::= { rectifiers 1 }
|
||
|
||
rectifierLoadCurrent OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Rectifier DC load current.
|
||
Return value is XXXX representing XXXX amps. Valid ranges are 0000 to 5000 amps."
|
||
::= { rectifiers 2}
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.batteries definition
|
||
-- *********************************************************************
|
||
|
||
batteries OBJECT IDENTIFIER ::= { readOnlyObjects 2 }
|
||
|
||
batteryCurrent OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery current.
|
||
Return value is XXXX representing XXXX amps. Valid ranges are 0000 to 1000 amps."
|
||
::= { batteries 1 }
|
||
|
||
batteryTemperature OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery temperature.
|
||
Return value is XX representing XX <20>C. Valid ranges are -40 to 99 <20>C."
|
||
::= { batteries 2 }
|
||
|
||
batteryResistanceReference OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Initial battery resistance.
|
||
Return value is XXXXX representing X.XXXX ohms. Valid ranges are 0.0000 to 5.0000 ohms."
|
||
::= { batteries 3 }
|
||
|
||
batteryResistanceReading OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Last battery resistance reading.
|
||
Return value is XXXXX representing X.XXXX ohms. Valid ranges are 0.0000 to 5.0000 ohms."
|
||
::= { batteries 4 }
|
||
|
||
batteryResistanceChange OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Percent change from last battery resistance reading.
|
||
Return value is XXX representing XXX %. Valid ranges are 001 to 999 %."
|
||
::= { batteries 5 }
|
||
|
||
batteryCycles1 OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Number of discharge/recharge cycles less than 1 minute.
|
||
Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles."
|
||
::= { batteries 6 }
|
||
|
||
batteryCycles1to5 OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Number of discharge/recharge cycles from 1 to 5 minutes.
|
||
Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles."
|
||
::= { batteries 7 }
|
||
|
||
batteryCycles5to15 OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Number of discharge/recharge cycles from 5 to 15 minutes.
|
||
Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles."
|
||
::= { batteries 8 }
|
||
|
||
batteryCycles15 OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Number of discharge/recharge cycles greater than 15 minutes.
|
||
Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles."
|
||
::= { batteries 9 }
|
||
|
||
batteryCycles15LastCycleDate OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Last cycle date of batteryCycles15.
|
||
Return value is MM-DD-YY, HH-MM."
|
||
::= { batteries 10 }
|
||
|
||
batteryCycles15LastDuration OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Duration of batteryCycles15 last cycle.
|
||
Return value is XXXX representing XXXX minutes."
|
||
::= { batteries 11 }
|
||
|
||
batteryTestFault OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
abort1(1),
|
||
abort2(2),
|
||
abort3(3),
|
||
none(4)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery failure has occured during battery restistance test.
|
||
Return value: 1 = Abort 1, 2 = Abort 2, 3 = Abort 3, 4 = None."
|
||
::= { batteries 12 }
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.factorySettings definition
|
||
-- *********************************************************************
|
||
|
||
factorySettings OBJECT IDENTIFIER ::= { readOnlyObjects 3 }
|
||
|
||
floatVoltagePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Float voltage factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 1 }
|
||
|
||
highVoltageAlarmPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "High voltage alarm factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 2 }
|
||
|
||
lowVoltageAlarmPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage alarm factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 3 }
|
||
|
||
disconnect1VoltagePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect voltage 1 factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 4 }
|
||
|
||
disconnect1TemperaturePreset OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect temperature 1 factory setting.
|
||
Return value is XX <20>C."
|
||
::= { factorySettings 5 }
|
||
|
||
disconnect1LoadShedSundayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 1 load shed Sunday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 6 }
|
||
|
||
disconnect1LoadShedMondayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 1 load shed Monday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 7 }
|
||
|
||
disconnect1LoadShedTuesdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 1 load shed Tuesday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 8 }
|
||
|
||
disconnect1LoadShedWednesdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 1 load shed Wednesday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 9 }
|
||
|
||
disconnect1LoadShedThursdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 1 load shed Thursday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 10 }
|
||
|
||
disconnect1LoadShedFridayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 1 load shed Friday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 11 }
|
||
|
||
disconnect1LoadShedSaturdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 1 load shed Saturday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 12 }
|
||
|
||
reconnectVoltage1Presets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Reconnect voltage 1 factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 13 }
|
||
|
||
disconnect2VoltagePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect voltage 2 factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 14 }
|
||
|
||
disconnect2TemperaturePreset OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect temperature 2 factory setting.
|
||
Return value is XX <20>C."
|
||
::= { factorySettings 15 }
|
||
|
||
disconnect2LoadShedSundayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 2 load shed Sunday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 16 }
|
||
|
||
disconnect2LoadShedMondayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 2 load shed Monday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 17 }
|
||
|
||
disconnect2LoadShedTuesdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 2 load shed Tuesday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 18 }
|
||
|
||
disconnect2LoadShedWednesdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 2 load shed Wednesday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 19 }
|
||
|
||
disconnect2LoadShedThursdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 2 load shed Thursday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 20 }
|
||
|
||
disconnect2LoadShedFridayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 2 load shed Friday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 21 }
|
||
|
||
disconnect2LoadShedSaturdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 2 load shed Saturday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 22 }
|
||
|
||
reconnect2VoltagePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Reconnect voltage 2 factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 23 }
|
||
|
||
disconnect3VoltagePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect voltage 3 factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 24 }
|
||
|
||
disconnect3TemperaturePreset OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect temperature 3 factory setting.
|
||
Return value is XX <20>C."
|
||
::= { factorySettings 25 }
|
||
|
||
disconnect3LoadShedSundayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 3 load shed Sunday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 26 }
|
||
|
||
disconnect3LoadShedMondayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 3 load shed Monday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 27 }
|
||
|
||
disconnect3LoadShedTuesdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 3 load shed Tuesday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 28 }
|
||
|
||
disconnect3LoadShedWednesdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 3 load shed Wednesday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 29 }
|
||
|
||
disconnect3LoadShedThursdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 3 load shed Thursday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 30 }
|
||
|
||
disconnect3LoadShedFridayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 3 load shed Friday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 31 }
|
||
|
||
disconnect3LoadShedSaturdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 3 load shed Saturday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 32 }
|
||
|
||
reconnect3VoltagePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Reconnect voltage 3 factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 33 }
|
||
|
||
overloadCurrentPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Overload current factory setting range.
|
||
Return value is XXXX amps min, XXXX amps max."
|
||
::= { factorySettings 34 }
|
||
|
||
maximumCurrentPreset OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Maximum current factory setting.
|
||
Return value is XXXX amps."
|
||
::= { factorySettings 35 }
|
||
|
||
batteryFloatCurrentPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery float current factory settings.
|
||
Return value is XXX amps min, XXX amps max."
|
||
::= { factorySettings 36 }
|
||
|
||
equalizeTimePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Equalize time factory setting range.
|
||
Return value is 00.0 hours min, XX.X hours max."
|
||
::= { factorySettings 37 }
|
||
|
||
equalizeVoltagePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Equalize voltage factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 38 }
|
||
|
||
batteryResistancePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery resistance percent change factory setting range.
|
||
Return value is XXX % min, XXX % max."
|
||
::= { factorySettings 39 }
|
||
|
||
batteryTestIntervalPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery resistance test interval factory setting range.
|
||
Return value is XX weeks min, XX weeks max."
|
||
::= { factorySettings 40 }
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.alarmStatus definition
|
||
-- *********************************************************************
|
||
|
||
alarmStatus OBJECT IDENTIFIER ::= { readOnlyObjects 4 }
|
||
|
||
highVoltageAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "High voltage alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 1 }
|
||
|
||
lowVoltageAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 2 }
|
||
|
||
overloadAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Overload alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 3 }
|
||
|
||
breakerAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Breaker alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 4 }
|
||
|
||
acFailureAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "AC failure alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 5 }
|
||
|
||
fanFailureAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Fan failure alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 6 }
|
||
|
||
rectifierFailureAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Rectifier failure alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 7 }
|
||
|
||
majorAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Major alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 8 }
|
||
|
||
lowVoltageDisconnect1TemperatureAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage disconnect 1 high temperature alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 9 }
|
||
|
||
lowVoltageDisconnect2TemperatureAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage disconnect 2 high temperature alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 10 }
|
||
|
||
lowVoltageDisconnect3TemperatureAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage disconnect 3 high temperature alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 11 }
|
||
|
||
lowVoltageDisconnect1VoltageAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage disconnect 1 low voltage alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 12 }
|
||
|
||
lowVoltageDisconnect2VoltageAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage disconnect 2 low voltage alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 13 }
|
||
|
||
lowVoltageDisconnect3VoltageAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage disconnect 3 low voltage alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 14 }
|
||
|
||
batteryResistanceAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery resistance alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 15 }
|
||
|
||
batteryCurrentAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery resistance alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 16 }
|
||
|
||
batteryTestAbortCondition1AlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery test abort condition 1 alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 17 }
|
||
|
||
batteryTestAbortCondition2AlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery test abort condition 2 alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 18 }
|
||
|
||
batteryTestAbortCondition3AlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery test abort condition 3 alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 19 }
|
||
|
||
batteryDisconnectAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery disconnect alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 20 }
|
||
|
||
fuseAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Fuse alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 21 }
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.digitalSensorAlarms definition
|
||
-- *********************************************************************
|
||
|
||
digitalSensorAlarms OBJECT IDENTIFIER ::= { readOnlyObjects 5 }
|
||
|
||
breakerTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
--#SEVERITY CRITICAL
|
||
DESCRIPTION "Breaker has tripped."
|
||
::= 0
|
||
|
||
fuseTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
--#SEVERITY CRITICAL
|
||
DESCRIPTION "Fuse has opened."
|
||
::= 1
|
||
|
||
batteryDisconnectTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
--#SEVERITY CRITICAL
|
||
DESCRIPTION "Battery disconnect has operated."
|
||
::= 2
|
||
|
||
programmableTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Programmable alarm has occurred."
|
||
--#SEVERITY CRITICAL
|
||
::= 3
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.SystemAlarms definition
|
||
-- *********************************************************************
|
||
|
||
systemAlarms OBJECT IDENTIFIER ::= { readOnlyObjects 6 }
|
||
|
||
highVoltageTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Float voltage has exceeded preset value.
|
||
Return value: High voltage alarm XX.X volts."
|
||
--#SEVERITY WARNING
|
||
::= 4
|
||
|
||
lowVoltageTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Float voltage is below preset value.
|
||
Return value: Low voltage alarm XX.X volts."
|
||
--#SEVERITY WARNING
|
||
::= 5
|
||
|
||
loadOverCurrentTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load current has exceeded preset value.
|
||
Return value: Load over current alarm XXXX amps."
|
||
--#SEVERITY WARNING
|
||
::= 6
|
||
|
||
batteryFloatCurrentTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery float current has exceeded preset value.
|
||
Return value: Battery float current alarm XXXX amps."
|
||
--#SEVERITY CRITICAL
|
||
::= 7
|
||
|
||
loadDisconnect1VoltageTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 1 voltage has dropped below preset value.
|
||
Return value: Load disconnect 1 voltage XX.X volts."
|
||
--#SEVERITY CRITICAL
|
||
::= 8
|
||
|
||
loadDisconnect2VoltageTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 2 voltage has dropped below preset value.
|
||
Return value: Load disconnect 2 voltage XX.X volts."
|
||
--#SEVERITY CRITICAL
|
||
::= 9
|
||
|
||
loadDisconnect3VoltageTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 3 voltage has dropped below preset value.
|
||
Return value: Load disconnect 3 voltage XX.X volts."
|
||
--#SEVERITY CRITICAL
|
||
::= 10
|
||
|
||
loadDisconnect1TemperatureTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 1 temperature has exceeded preset value.
|
||
Return value: Load disconnect 1 temperature alarm XX <20>C."
|
||
--#SEVERITY CRITICAL
|
||
::= 11
|
||
|
||
loadDisconnect2TemperatureTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 2 temperature has exceeded preset value.
|
||
Return value: Load disconnect 2 temperature alarm XX <20>C."
|
||
--#SEVERITY CRITICAL
|
||
::= 12
|
||
|
||
loadDisconnect3TemperatureTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 3 temperature has exceeded preset value.
|
||
Return value: Load disconnect 3 temperature alarm XX <20>C."
|
||
--#SEVERITY CRITICAL
|
||
::= 13
|
||
|
||
rectifierFailureTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Rectifier failure.
|
||
Return value: Rectifier failure."
|
||
--#SEVERITY WARNING
|
||
::= 14
|
||
|
||
fanFailureTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Rectifier fan has failed.
|
||
Return value: Fan failure."
|
||
--#SEVERITY CRITICAL
|
||
::= 15
|
||
|
||
acFailureTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Rectifier has lost AC input power.
|
||
Return value: AC failure."
|
||
--#SEVERITY CRITICAL
|
||
::= 16
|
||
|
||
majorFailureTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Multiple failures of AC, rectififers, fans or a programmed alarm.
|
||
Return value: Multiple AC, fan, rectifier or optional alarm failures has occurred."
|
||
--#SEVERITY CRITICAL
|
||
::= 17
|
||
|
||
batteryResistanceTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery resistance has increased by a programmed percentage.
|
||
Return value: Battery resistance alarm X.XXXX ohms, XXX %."
|
||
--#SEVERITY WARNING
|
||
::= 18
|
||
|
||
batteryTestAbort1Trap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery failure abort 1 has occured during battery resistance test.
|
||
Return value: Battery test failure: Abort 1."
|
||
--#SEVERITY CRITICAL
|
||
::= 19
|
||
|
||
batteryTestAbort2Trap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery failure abort 2 has occured during battery resistance test.
|
||
Return value: Battery test failure: Abort 2."
|
||
--#SEVERITY CRITICAL
|
||
::= 20
|
||
|
||
batteryTestAbort3Trap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery failure abort 3 has occured during battery resistance test.
|
||
Return value: Battery test failure: Abort 3."
|
||
--#SEVERITY CRITICAL
|
||
::= 21
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.digitalSensorAlarmClears definition
|
||
-- *********************************************************************
|
||
|
||
digitalSensorAlarmClears OBJECT IDENTIFIER ::= { readOnlyObjects 7 }
|
||
|
||
breakerTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Breaker alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 100
|
||
|
||
fuseTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Fuse alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 101
|
||
|
||
batteryDisconnectTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery disconnect alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 102
|
||
|
||
programmableTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Programmable alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 103
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.SystemAlarmClears definition
|
||
-- *********************************************************************
|
||
|
||
systemAlarmClears OBJECT IDENTIFIER ::= { readOnlyObjects 8 }
|
||
|
||
highVoltageTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "High voltage alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 104
|
||
|
||
lowVoltageTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Low voltage alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 105
|
||
|
||
loadOverCurrentTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load over current alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 106
|
||
|
||
batteryFloatCurrentTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery float current alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 107
|
||
|
||
loadDisconnect1VoltageTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 1 voltage alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 108
|
||
|
||
loadDisconnect2VoltageTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 2 voltage alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 109
|
||
|
||
loadDisconnect3VoltageTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 3 voltage alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 110
|
||
|
||
loadDisconnect1TemperatureTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 1 temperature alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 111
|
||
|
||
loadDisconnect2TemperatureTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 2 temperature alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 112
|
||
|
||
loadDisconnect3TemperatureTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 3 temperature alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 113
|
||
|
||
rectifierFailureTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Rectififer failure alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 114
|
||
|
||
fanFailureTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Fan failure alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 115
|
||
|
||
acFailureTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "AC failure alarm been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 116
|
||
|
||
majorFailureTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Major failure alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 117
|
||
|
||
batteryResistanceTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery resistance alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 118
|
||
|
||
batteryTestAbort1TrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery test abort 1 alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 119
|
||
|
||
batteryTestAbort2TrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery test abort 2 alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 120
|
||
|
||
batteryTestAbort3TrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery test abort 3 alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 121
|
||
|
||
END
|
||
|
||
|