-- Last Mile Gear CTM Master MIB
|
|
-- This mib was custom edited to add Slave information
|
|
-- Mar 27, 2018 - Paul Heinrichs <pdheinrichs@gmail.com>
|
|
|
|
|
|
CTMMIBCUSTOM DEFINITIONS ::= BEGIN
|
|
IMPORTS
|
|
enterprises
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
|
|
lastmilegear OBJECT IDENTIFIER ::= { enterprises 25868 }
|
|
|
|
mibObjects OBJECT IDENTIFIER ::= { lastmilegear 1 }
|
|
|
|
version OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Version of Web GUI - Version of Web GUI Interface
|
|
currently running on CTM"
|
|
::= { mibObjects 1 }
|
|
|
|
site OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Site Name - Site name as stored on CTM"
|
|
::= { mibObjects 2 }
|
|
|
|
lastIP OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Last IP Address Login - Last IP address captured
|
|
at Login Attempt"
|
|
::= { mibObjects 3 }
|
|
|
|
lastTime OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Last Time Login - Last time of Login attempt"
|
|
::= { mibObjects 4 }
|
|
|
|
nSats OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Number Satellites in View - Number of Satellites
|
|
in view of GPS Receiver Antenna being used for
|
|
timing calculations"
|
|
::= { mibObjects 5 }
|
|
|
|
pwrP OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Primary Power - Master ?1? = Power OK,
|
|
?0? = Power Off or Low"
|
|
::= { mibObjects 6 }
|
|
|
|
pwrS OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Secondary Power - Master ?1? = Power OK,
|
|
?0? = Power Off or Low"
|
|
::= { mibObjects 7 }
|
|
|
|
cbTrip OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Circuit Breaker Trip Bit Code - Master
|
|
Breaker Tripped Code: 1=Port 1, 2=Port2, 4=Port
|
|
3, 8=Port4, 16=Port5, 32=Port6, 64=Port7, 128=Port8
|
|
Example: Code 5 means Port 3 and Port 1 Tripped"
|
|
::= { mibObjects 8 }
|
|
|
|
tempC OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Temperature"
|
|
::= { mibObjects 9 }
|
|
|
|
voltsM1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Primary Power In Voltage - In Tenths of
|
|
a Volt"
|
|
::= { mibObjects 10 }
|
|
|
|
voltsM2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Secondary Power In Voltage - In Tenths
|
|
of a Volt"
|
|
::= { mibObjects 11 }
|
|
|
|
portOnM OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Ports ON Enabled Status - Master ?1? =Sync
|
|
Enabled, ?0? = Sync Off listed in order ?Port1?,
|
|
?Port2?, ?Port3?, ?Port4?, ?Port5?, ?Port6?,
|
|
?Port7?, ?Port8?"
|
|
::= { mibObjects 12 }
|
|
|
|
portSyncM OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Ports Sync Enabled Status - Master ?1?
|
|
=Sync Enabled, ?0? = Sync Off listed in order
|
|
?Port1?, ?Port2?, ?Port3?, ?Port4?, ?Port5?,
|
|
?Port6?, ?Port7?, ?Port8?"
|
|
::= { mibObjects 13 }
|
|
|
|
portPwrM1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Power Port 1 - (in tenths of a Watt) delivered
|
|
on Port 1"
|
|
::= { mibObjects 14 }
|
|
|
|
portPwrM2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Power Port 2 - (in tenths of a Watt) delivered
|
|
on Port 2"
|
|
::= { mibObjects 15 }
|
|
|
|
portPwrM3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Power Port 3 - (in tenths of a Watt) delivered
|
|
on Port 3"
|
|
::= { mibObjects 16 }
|
|
|
|
portPwrM4 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Power Port 4 - (in tenths of a Watt) delivered
|
|
on Port 4"
|
|
::= { mibObjects 17 }
|
|
|
|
portPwrM5 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Power Port 5 - (in tenths of a Watt) delivered
|
|
on Port 5"
|
|
::= { mibObjects 18 }
|
|
|
|
portPwrM6 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Power Port 6 - (in tenths of a Watt) delivered
|
|
on Port 6"
|
|
::= { mibObjects 19 }
|
|
|
|
portPwrM7 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Power Port 7 - (in tenths of a Watt) delivered
|
|
on Port 7"
|
|
::= { mibObjects 20 }
|
|
|
|
portPwrM8 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Power Port 8 - (in tenths of a Watt) delivered
|
|
on Port 8"
|
|
::= { mibObjects 21 }
|
|
|
|
pwrSP OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Slave Primary Power - Master ?1? = Power OK,
|
|
?0? = Power Off or Low"
|
|
::= { mibObjects 23 }
|
|
|
|
pwrSS OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Slave Secondary Power - Master ?1? = Power OK,
|
|
?0? = Power Off or Low"
|
|
::= { mibObjects 24 }
|
|
|
|
voltsS1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Slave Primary Power In Voltage - In Tenths of
|
|
a Volt"
|
|
::= { mibObjects 27 }
|
|
|
|
voltsS2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Slave Secondary Power In Voltage - In Tenths
|
|
of a Volt"
|
|
::= { mibObjects 28 }
|
|
|
|
portOnS OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Slave Ports ON Enabled Status - Slave ?1? =Sync
|
|
Enabled, ?0? = Sync Off listed in order ?Port1?,
|
|
?Port2?, ?Port3?, ?Port4?, ?Port5?, ?Port6?,
|
|
?Port7?, ?Port8?"
|
|
::= { mibObjects 29 }
|
|
|
|
portSyncS OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Slave Ports Sync Enabled Status - Slave ?1?
|
|
=Sync Enabled, ?0? = Sync Off listed in order
|
|
?Port1?, ?Port2?, ?Port3?, ?Port4?, ?Port5?,
|
|
?Port6?, ?Port7?, ?Port8?"
|
|
::= { mibObjects 30 }
|
|
|
|
portPwrS1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Slave Power Port 1 - (in tenths of a Watt) delivered
|
|
on Port 1"
|
|
::= { mibObjects 31 }
|
|
|
|
portPwrS2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Slave Power Port 2 - (in tenths of a Watt) delivered
|
|
on Port 2"
|
|
::= { mibObjects 32 }
|
|
|
|
portPwrS3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Slave Power Port 3 - (in tenths of a Watt) delivered
|
|
on Port 3"
|
|
::= { mibObjects 33 }
|
|
|
|
portPwrS4 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Slave Power Port 4 - (in tenths of a Watt) delivered
|
|
on Port 4"
|
|
::= { mibObjects 34 }
|
|
|
|
portPwrS5 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Slave Power Port 5 - (in tenths of a Watt) delivered
|
|
on Port 5"
|
|
::= { mibObjects 35 }
|
|
|
|
portPwrS6 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Slave Power Port 6 - (in tenths of a Watt) delivered
|
|
on Port 6"
|
|
::= { mibObjects 36 }
|
|
|
|
portPwrS7 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Slave Power Port 7 - (in tenths of a Watt) delivered
|
|
on Port 7"
|
|
::= { mibObjects 37 }
|
|
|
|
portPwrS8 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Slave Power Port 8 - (in tenths of a Watt) delivered
|
|
on Port 8"
|
|
::= { mibObjects 38 }
|
|
|
|
modeReqM OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master CTM2 Port Type Setting - Master ?00?=Type
|
|
A (Canopy) ?10?=Type B (OFDM), ?01? = Type C
|
|
(POE 802.3at), ?11? (POE 802.3at 4 Pair), ?100?=(POE
|
|
24V mode, CTM2 C Only) listed in order ?Port1?,
|
|
?Port2?, ?Port3?, ?Port4?, ?Port5?, ?Port6?,
|
|
?Port7?, ?Port8?"
|
|
::= { mibObjects 39 }
|
|
|
|
trpCntGM1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Auto Restart Count Port 1 - Number of Times
|
|
Auto Reset Feature has executed a Circuit Breaker
|
|
Restart on Port 1"
|
|
::= { mibObjects 45 }
|
|
|
|
trpCntGM2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Auto Restart Count Port 2 - Number of Times
|
|
Auto Reset Feature has executed a Circuit Breaker
|
|
Restart on Port 2"
|
|
::= { mibObjects 46 }
|
|
|
|
trpCntGM3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Auto Restart Count Port 3 - Number of Times
|
|
Auto Reset Feature has executed a Circuit Breaker
|
|
Restart on Port 3"
|
|
::= { mibObjects 47 }
|
|
|
|
trpCntGM4 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Auto Restart Count Port 4 - Number of Times
|
|
Auto Reset Feature has executed a Circuit Breaker
|
|
Restart on Port 4"
|
|
::= { mibObjects 48 }
|
|
|
|
trpCntGM5 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Auto Restart Count Port 5 - Number of Times
|
|
Auto Reset Feature has executed a Circuit Breaker
|
|
Restart on Port 5"
|
|
::= { mibObjects 49 }
|
|
|
|
trpCntGM6 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Auto Restart Count Port 6 - Number of Times
|
|
Auto Reset Feature has executed a Circuit Breaker
|
|
Restart on Port 6"
|
|
::= { mibObjects 50 }
|
|
|
|
trpCntGM7 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Auto Restart Count Port 7 - Number of Times
|
|
Auto Reset Feature has executed a Circuit Breaker
|
|
Restart on Port 7"
|
|
::= { mibObjects 51 }
|
|
|
|
trpCntGM8 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Auto Restart Count Port 8 - Number of Times
|
|
Auto Reset Feature has executed a Circuit Breaker
|
|
Restart on Port 8"
|
|
::= { mibObjects 52 }
|
|
|
|
trpCntBM1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Ckt Breaker Auto Restart Fail Count Port
|
|
1 - Number of Times Auto Reset Feature has failed
|
|
to restart (after 7 tries) a Circuit Breaker
|
|
on Port 1"
|
|
::= { mibObjects 53 }
|
|
|
|
trpCntBM2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Ckt Breaker Auto Restart Fail Count Port
|
|
2 - Number of Times Auto Reset Feature has failed
|
|
to restart (after 7 tries) a Circuit Breaker
|
|
on Port 2"
|
|
::= { mibObjects 54 }
|
|
|
|
trpCntBM3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Ckt Breaker Auto Restart Fail Count Port
|
|
3 - Number of Times Auto Reset Feature has failed
|
|
to restart (after 7 tries) a Circuit Breaker
|
|
on Port 3"
|
|
::= { mibObjects 55 }
|
|
|
|
trpCntBM4 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Ckt Breaker Auto Restart Fail Count Port
|
|
4 - Number of Times Auto Reset Feature has failed
|
|
to restart (after 7 tries) a Circuit Breaker
|
|
on Port 4"
|
|
::= { mibObjects 56 }
|
|
|
|
trpCntBM5 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Ckt Breaker Auto Restart Fail Count Port
|
|
5 - Number of Times Auto Reset Feature has failed
|
|
to restart (after 7 tries) a Circuit Breaker
|
|
on Port 5"
|
|
::= { mibObjects 57 }
|
|
|
|
trpCntBM6 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Ckt Breaker Auto Restart Fail Count Port
|
|
6 - Number of Times Auto Reset Feature has failed
|
|
to restart (after 7 tries) a Circuit Breaker
|
|
on Port 6"
|
|
::= { mibObjects 58 }
|
|
|
|
trpCntBM7 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Ckt Breaker Auto Restart Fail Count Port
|
|
7 - Number of Times Auto Reset Feature has failed
|
|
to restart (after 7 tries) a Circuit Breaker
|
|
on Port 7"
|
|
::= { mibObjects 59 }
|
|
|
|
trpCntBM8 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Master Ckt Breaker Auto Restart Fail Count Port
|
|
8 - Number of Times Auto Reset Feature has failed
|
|
to restart (after 7 tries) a Circuit Breaker
|
|
on Port 8"
|
|
::= { mibObjects 60 }
|
|
|
|
|
|
lostEthernetConnection TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "Lost Ethernet Connection"
|
|
::= 0
|
|
|
|
masterPrimayPowerLost TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "Master Primary Power Lost"
|
|
::= 1
|
|
|
|
masterSecondaryPowerLost TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "Master Secondary Power Lost"
|
|
::= 2
|
|
|
|
gpsSignalLost TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "GPS Signal Lost"
|
|
::= 3
|
|
|
|
masterTempatureError TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "Master Temperature Error"
|
|
::= 4
|
|
|
|
masterCircuitBreakerTripCode TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "Master Circuit Breaker Trip Code - Master Breaker Tripped
|
|
Code: 1=Port 1, 2=Port2, 4=Port 3, 8=Port4, 16=Port5,
|
|
32=Port6, 64=Port7, 128=Port8 Example: Code
|
|
5 means Port 3 and Port 1 Tripped"
|
|
::= 5
|
|
|
|
loginFailedAttempt TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "Login Failed Attempt"
|
|
::= 6
|
|
|
|
settingsChanged TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "CTM Settings Changed"
|
|
::= 7
|
|
|
|
masterPrimaryPowerOK TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "Master Primary Power OK"
|
|
::= 10
|
|
|
|
masterSecondaryPowerOK TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "Master Secondary Power OK"
|
|
::= 20
|
|
|
|
gpsSignalOK TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "GPS Signal OK"
|
|
::= 30
|
|
|
|
tempatureOK TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "Temperature OK"
|
|
::= 40
|
|
|
|
circuitBreakersOK TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "Circuit Breakers OK"
|
|
::= 50
|
|
|
|
masterAutoRestartCBCompletedOK TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "Master Auto Restart CB Completed OK"
|
|
::= 52
|
|
|
|
loginOK TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "Login OK"
|
|
::= 60
|
|
|
|
resetComplete TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "Reset Complete"
|
|
::= 80
|
|
|
|
ethernetConnectionRestored TRAP-TYPE
|
|
ENTERPRISE mibObjects
|
|
DESCRIPTION "Ethernet Connection Restored"
|
|
::= 99
|
|
|
|
|
|
END |