DELL-SNMP-UPS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
-- Title: UPS MIB
|
|
-- Date: August 8th, 2013
|
|
-- Author: Eaton - R&D Communication
|
|
-- Release: 01.04.0002
|
|
-- NMC Firmware compatibility: 01.18.000x
|
|
|
|
IMPORTS
|
|
enterprises
|
|
FROM RFC1155-SMI
|
|
TimeStamp, DisplayString
|
|
FROM SNMPv2-TC
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
----
|
|
-- Path to the root
|
|
----
|
|
dell OBJECT IDENTIFIER ::= { enterprises 674 }
|
|
upsdell OBJECT IDENTIFIER ::= { dell 10902 }
|
|
hardware OBJECT IDENTIFIER ::= { upsdell 2 }
|
|
|
|
|
|
|
|
-- Groups of the MIB
|
|
productID OBJECT IDENTIFIER ::= { hardware 100 }
|
|
productStatus OBJECT IDENTIFIER ::= { hardware 110 }
|
|
physical OBJECT IDENTIFIER ::= { hardware 120 }
|
|
logical OBJECT IDENTIFIER ::= { hardware 130 }
|
|
traps OBJECT IDENTIFIER ::= { hardware 140 }
|
|
|
|
-- Groups of the Physical group
|
|
physicalIdent OBJECT IDENTIFIER ::= { physical 1 }
|
|
physicalOutput OBJECT IDENTIFIER ::= { physical 2 }
|
|
physicalRectifier OBJECT IDENTIFIER ::= { physical 3 }
|
|
physicalUPS OBJECT IDENTIFIER ::= { physical 4 }
|
|
physicalBattery OBJECT IDENTIFIER ::= { physical 5 }
|
|
physicalLoadSegment OBJECT IDENTIFIER ::= { physical 6 }
|
|
physicalEnvironment OBJECT IDENTIFIER ::= { physical 7 }
|
|
|
|
----
|
|
-- Definition of object types
|
|
----
|
|
|
|
--------------------------
|
|
-- the productID group --
|
|
--------------------------
|
|
|
|
productIDDisplayName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name of this product for display purposes."
|
|
::= { productID 1 }
|
|
|
|
productIDDescription OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A short description of this product."
|
|
::= { productID 2 }
|
|
|
|
productIDVendor OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the product manufacturer."
|
|
::= { productID 3 }
|
|
|
|
productIDVersion OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The version of this product."
|
|
::= { productID 4 }
|
|
|
|
productIDBuildNumber OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The software build number of the product populating the MIB."
|
|
::= { productID 5 }
|
|
|
|
productIDURL OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The URL of the web-based application to manage this device, should the device provide one."
|
|
::= { productID 6 }
|
|
|
|
productIDDeviceNetworkName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Operating system specific computer name if product SNMP service is hosted."
|
|
::= { productID 7 }
|
|
|
|
--------------------------
|
|
-- the productStatus group --
|
|
--------------------------
|
|
|
|
productStatusGlobalStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other(1),
|
|
unknown(2),
|
|
ok(3),
|
|
non-critical(4),
|
|
critical(5),
|
|
non-recoverable(6)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current status of the product.
|
|
This is a rollup for the entire product including any
|
|
monitored devices. The status is intended to give
|
|
initiative to an SNMP monitor to get further data when
|
|
this status is abnormal."
|
|
::= { productStatus 1 }
|
|
|
|
productStatusLastGlobalStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status before the current status which induced an initiative
|
|
to issue a global status change trap."
|
|
::= { productStatus 2 }
|
|
|
|
productStatusTimeStamp OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The last time that the SNMP table geometries changed and/or
|
|
attribute data was significantly updated. This is to be used by
|
|
management applications to trigger a refresh of data acquired
|
|
from the MIB."
|
|
::= { productStatus 3 }
|
|
|
|
productStatusGetTimeOut OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS optional
|
|
DESCRIPTION
|
|
"Suggested time out value in milliseconds for how long the SNMP getter
|
|
should wait while attempting to poll the product SNMP service."
|
|
::= { productStatus 4 }
|
|
|
|
productStatusRefreshRate OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS optional
|
|
DESCRIPTION
|
|
"Rate in seconds at which the SNMP service cached data is being updated."
|
|
::= { productStatus 5 }
|
|
|
|
productStatusGeneratingTrapFlag OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
true(1),
|
|
false(2),
|
|
disabled(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS optional
|
|
DESCRIPTION
|
|
"Indicates if this SNMP sub-agent is capable of and/or is generating SNMP Traps.
|
|
This variable can take the following values:
|
|
1 True, this service is capable of sending traps and is the originator of SNMP
|
|
traps generated for the devices represented in this MIB and is currently generating traps.
|
|
2 False, this service not capable of sending traps and is not the originator of
|
|
any SNMP traps generated for the devices represented in this MIB.
|
|
3 Disabled, this service is capable of sending traps and is the originator of SNMP
|
|
traps for the devices represented in this MIB, but traps are currently disabled."
|
|
::= { productStatus 6 }
|
|
|
|
--------------------------
|
|
-- the Physical group --
|
|
--------------------------
|
|
|
|
-- physicalIdent group
|
|
|
|
physicalIdentFamilyName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS Family name."
|
|
::= { physicalIdent 1 }
|
|
|
|
physicalIdentSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS Serial number."
|
|
::= { physicalIdent 2 }
|
|
|
|
physicalIdentConverterType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
lineInteractive(1),
|
|
onLine(2),
|
|
onLineUnitaryParallel(3),
|
|
onLineParallelWithNS(4),
|
|
onLineHotStandbyRedundancy(5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS type."
|
|
::= { physicalIdent 3 }
|
|
|
|
physicalIdentReferenceNumber OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Technical Reference of UPS firmware."
|
|
::= { physicalIdent 4 }
|
|
|
|
-- physicalOutput group
|
|
|
|
physicalOutputInstantHeadroom OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This is the present amount of watt capacity remaining before overload."
|
|
::= { physicalOutput 1 }
|
|
|
|
physicalOutputPeakHeadroom OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Statistical value holding the lowest value that Instantaneous Headroom
|
|
Watts was ever set too since the last time this statistic was reset."
|
|
::= { physicalOutput 2 }
|
|
|
|
physicalOutputPeakHeadroomTimestamp OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Time and date stamp of the last time the Peak Headroom Watts value was updated."
|
|
::= { physicalOutput 3 }
|
|
|
|
physicalOutputPeakConsumption OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Statistical value of the maximum RMS Watts the UPS has seen since
|
|
the last time this statistic was reset."
|
|
::= { physicalOutput 4 }
|
|
|
|
physicalOutputPeakConsumptionTimestamp OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Time and date stamp of the last time the Peak Consumption Watts value was updated."
|
|
::= { physicalOutput 5 }
|
|
|
|
physicalOutputPresentConsumption OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Derived by averaging the watt second consumption over the past hour.
|
|
Use an array of 60 words to store the average watt seconds consumed over
|
|
the last minute then after you have a full hours worth of data in the 60
|
|
word array, average those values to get your Present KWH Consumption meter.
|
|
Then every minute after that update the oldest value in the array, average
|
|
again and update the meter.
|
|
Value is 0 until the minimum 1 hour of data has been accumulated."
|
|
::= { physicalOutput 6 }
|
|
|
|
physicalOutputCumulativeConsumption OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"64 bit meter value that is derived by reading the Present KWH Consumption meter
|
|
once per hour and adding it to the last value of this meter. Value accumulates
|
|
until it is reset from the LCD or via the SHUT protocol or the meter rolls over."
|
|
::= { physicalOutput 7 }
|
|
|
|
physicalOutputCumulativeConsumptionTimestamp OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Time and date stamp of last time this meter value was reset."
|
|
::= { physicalOutput 8 }
|
|
|
|
physicalOutputVA OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output VA."
|
|
::= { physicalOutput 9 }
|
|
|
|
|
|
-- physicalRectifier group
|
|
|
|
physicalRectifierPosVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"DC bus positive voltage."
|
|
::= { physicalRectifier 1 }
|
|
|
|
physicalRectifierNegVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"DC bus negative voltage."
|
|
::= { physicalRectifier 2 }
|
|
|
|
|
|
-- physicalUPS group
|
|
|
|
physicalUPSDateTime OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Real Time Clock with Date and Time."
|
|
::= { physicalUPS 1 }
|
|
|
|
physicalUPSAlarmsStatus OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"List of traps that are in active mode. This list is coded in ASCI format
|
|
and each trap number is separated by a coma (ex: 1,5,23,77). Only odd traps
|
|
are listed."
|
|
::= { physicalUPS 2 }
|
|
|
|
physicalUPSRuntimeToShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of seconds remaining until UPS will receive a ShutdownAfterDelay command.
|
|
2147483647 if no countdown is in effect."
|
|
::= { physicalUPS 3 }
|
|
|
|
physicalUPSOutpoutSwitchable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
switchable(1),
|
|
notSwitchable(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Parameter to enable or not remote UPS commands coming from all communication ports."
|
|
::= { physicalUPS 4 }
|
|
|
|
|
|
-- physicalBattery group
|
|
|
|
physicalBatteryABMStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
abmCharging(1),
|
|
abmDischarging(2),
|
|
abmFloating(3),
|
|
abmResting(4),
|
|
abmOff(5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Advanced Battery Monitoring satus."
|
|
::= { physicalBattery 1 }
|
|
|
|
physicalBatteryTestStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
donePassed(1),
|
|
doneWarning(2),
|
|
doneError(3),
|
|
aborted(4),
|
|
inProgress(5),
|
|
noTestIniated(6),
|
|
testScheduled(7)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Battery test satus."
|
|
::= { physicalBattery 2 }
|
|
|
|
physicalBatterySecondsRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Battery remaining time calculated by the autonometer."
|
|
::= { physicalBattery 3 }
|
|
|
|
|
|
-- physicalLoadSegment group
|
|
|
|
physicalLoadSegment1ShutdownAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of seconds remaining until load segment 1 will switch off.
|
|
-1 if no shutdown countdown is in effect."
|
|
::= { physicalLoadSegment 1 }
|
|
|
|
physicalLoadSegment1StartupAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of seconds remaining until load segment 1 will switch on.
|
|
-1 if no startup countdown is in effect."
|
|
::= { physicalLoadSegment 2 }
|
|
|
|
physicalLoadSegment2ShutdownAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of seconds remaining until load segment 2 will switch off.
|
|
-1 if no shutdown countdown is in effect."
|
|
::= { physicalLoadSegment 3 }
|
|
|
|
physicalLoadSegment2StartupAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of seconds remaining until load segment 2 will switch on.
|
|
-1 if no startup countdown is in effect."
|
|
::= { physicalLoadSegment 4 }
|
|
|
|
physicalLoadSegment1RuntimeToShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of seconds remaining until load segment 1 will receive a
|
|
ShutdownAfterDelay command. 2147483647 if no countdown is in effect."
|
|
::= { physicalLoadSegment 5 }
|
|
|
|
physicalLoadSegment2RuntimeToShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of seconds remaining until load segment 2 will receive a
|
|
ShutdownAfterDelay command. 2147483647 if no countdown is in effect."
|
|
::= { physicalLoadSegment 6 }
|
|
|
|
-- physicalEnvironment group
|
|
|
|
physicalEnvironmentSensorPresent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Informations, if there is Environment Measurement Probe connected."
|
|
::= { physicalEnvironment 1 }
|
|
|
|
physicalEnvironmentSensorName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..59))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"User name of EMP."
|
|
::= { physicalEnvironment 2 }
|
|
|
|
physicalEnvironmentValues OBJECT IDENTIFIER ::= { physicalEnvironment 3 }
|
|
|
|
physicalEnvironmentValuesTemperatureUnit OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
celsius(1),
|
|
fahrenheit(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Temperature unit setting."
|
|
::= { physicalEnvironmentValues 1 }
|
|
|
|
physicalEnvironmentValuesTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current temperature value in 0.1 degree Celsius."
|
|
::= { physicalEnvironmentValues 2 }
|
|
|
|
physicalEnvironmentValuesHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current humidity value in 0.1 percents."
|
|
::= { physicalEnvironmentValues 3 }
|
|
|
|
physicalEnvironmentValuesTemperatureLow OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Temperature low threshhold in units of degree Celsius."
|
|
::= { physicalEnvironmentValues 4 }
|
|
|
|
physicalEnvironmentValuesTemperatureHigh OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Temperature high threshhold in units of degree Celsius."
|
|
::= { physicalEnvironmentValues 5 }
|
|
|
|
physicalEnvironmentValuesTemperatureHysteresis OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Temperature hysteresis in units of degree Celsius."
|
|
::= { physicalEnvironmentValues 6 }
|
|
|
|
physicalEnvironmentValueshHumidityLow OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Humidity low threshhold in percents."
|
|
::= { physicalEnvironmentValues 7 }
|
|
|
|
physicalEnvironmentValuesHumidityHigh OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Humidity high threshhold in percents."
|
|
::= { physicalEnvironmentValues 8 }
|
|
|
|
physicalEnvironmentValuesHumidityHysteresis OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Humidity hysteresis in percents."
|
|
::= { physicalEnvironmentValues 9 }
|
|
|
|
physicalEnvironmentInputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PhysicalEnvironmentInputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The table containins dry contact inputs information."
|
|
::= { physicalEnvironment 4 }
|
|
|
|
physicalEnvironmentInputEntry OBJECT-TYPE
|
|
SYNTAX PhysicalEnvironmentInputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The description of an entry in the table."
|
|
INDEX { physicalEnvironmentInputIndex }
|
|
::= { physicalEnvironmentInputTable 1 }
|
|
|
|
|
|
PhysicalEnvironmentInputEntry ::= SEQUENCE { -- ASN.1 type definition
|
|
physicalEnvironmentInputIndex INTEGER,
|
|
physicalEnvironmentInputName DisplayString,
|
|
physicalEnvironmentInputState INTEGER,
|
|
physicalEnvironmentInputOpenedState DisplayString,
|
|
physicalEnvironmentInputClosedState DisplayString
|
|
}
|
|
|
|
physicalEnvironmentInputIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The input index, ranging from 1 to 2."
|
|
::= { physicalEnvironmentInputEntry 1 }
|
|
|
|
physicalEnvironmentInputName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..27))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The input user-friendly name."
|
|
::= { physicalEnvironmentInputEntry 2 }
|
|
|
|
physicalEnvironmentInputState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
opened(1),
|
|
closed(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Current state of input."
|
|
::= { physicalEnvironmentInputEntry 3 }
|
|
|
|
physicalEnvironmentInputOpenedState OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..21))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The input opened state user-friendly name."
|
|
::= { physicalEnvironmentInputEntry 4 }
|
|
|
|
physicalEnvironmentInputClosedState OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..21))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The input closed state user-friendly name."
|
|
::= { physicalEnvironmentInputEntry 5 }
|
|
|
|
|
|
--------------------------
|
|
-- the Logical group --
|
|
--------------------------
|
|
|
|
|
|
--------------------------
|
|
-- the Traps group --
|
|
--------------------------
|
|
|
|
-- This group defines objects and traps, so that for each trap, simple
|
|
-- get request on related objects (one or many) allow to confirm actual
|
|
-- status of the trap.
|
|
|
|
-- TRAPS NOTIFICATIONS
|
|
|
|
trapInverterOverVoltage TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Inverter AC over voltage."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "The Inverter AC Voltage has exceeded the 'Over Voltage Threshold' value."
|
|
::= 1
|
|
|
|
trapInverterOverVoltageOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Inverter AC over voltage ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "The Inverter AC Voltage is no longer over the 'Over Voltage Threshold' value."
|
|
::= 2
|
|
|
|
trapInverterUnderVoltage TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Inverter AC under voltage."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Inverter AC Voltage has fallen below the 'Under Voltage Threshold' value."
|
|
::= 3
|
|
|
|
trapInverterUnderVoltageOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Inverter AC under voltage ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Inverter AC Voltage is no longer below the 'Under Voltage Threshold' value."
|
|
::= 4
|
|
|
|
trapBypassFrequencyOutOfRange TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Bypass under or over frequency."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "UPS Bypass Frequency has gone out of Range."
|
|
::= 5
|
|
|
|
trapBypassFrequencyOutOfRangeOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Bypass under or over frequency ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS Bypass Frequency is no longer out of Range."
|
|
::= 6
|
|
|
|
trapOnBuck TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"On Buck / Input Voltage Reducer."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "On Buck / Input Voltage Reducer."
|
|
::= 7
|
|
|
|
trapReturnFromBuck TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Return from Buck."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "The UPS has returned from Buck."
|
|
::= 8
|
|
|
|
trapOnBoost TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"On Boost / Input Voltage Booster."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "On Boost / Input Voltage Booster."
|
|
::= 9
|
|
|
|
trapReturnFromBoost TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Return from Boost."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "The UPS has returned from Boost."
|
|
::= 10
|
|
|
|
trapInputOverVoltage TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Input AC over voltage."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Input AC Voltage to the UPS has exceeded the 'Over Voltage Threshold' value."
|
|
::= 11
|
|
|
|
trapInputOverVoltageOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Input AC over voltage ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Input AC Voltage to the UPS no longer above the 'Over Voltage Threshold' value."
|
|
::= 12
|
|
|
|
trapInputUnderVoltage TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Input AC under voltage."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Input AC Voltage to the UPS has fallen below 'Input Low Voltage Threshold' value."
|
|
::= 13
|
|
|
|
trapInputUnderVoltageOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Input AC under voltage ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Input AC Voltage to the UPS is no longer below the 'Under Voltage Threshold' value."
|
|
::= 14
|
|
|
|
trapInputFrequencyOutOfRange TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Input under or over frequency."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Input Frequency to UPS has fallen out of Range."
|
|
::= 15
|
|
|
|
trapInputFrequencyOutOfRangeOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Input under or over frequency ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Input Frequency to UPS is no longer out of Range."
|
|
::= 16
|
|
|
|
trapRemoteEmergencyPowerOff TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Remote emergency power off."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Remote emergency power off."
|
|
::= 17
|
|
|
|
trapReturnFromEmergencyPowerOff TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Return from remote emergency power off."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Return from remote emergency power off."
|
|
::= 18
|
|
|
|
trapLevel1Overload TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Output Level 1 overload."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "UPS Output has exceeded the 'OverLoad Level 1 Threshold' value."
|
|
::= 19
|
|
|
|
trapLevel1OverloadOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Output Level 1 overload ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS Output is no longer above the 'Overload Level 1 threshold' value."
|
|
::= 20
|
|
|
|
trapLevel2Overload TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Level 2 overload."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "UPS Output has exceeded the 'OverLoad Level 2 Threshold' value."
|
|
::= 21
|
|
|
|
trapLevel2OverloadOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Level 2 overload ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS Output is no longer above the 'Overload Level 2 threshold' value."
|
|
::= 22
|
|
|
|
trapLevel3Overload TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Level 3 overload."
|
|
--#SEVERITY CRITICAL
|
|
--#SUMMARY "UPS Output has exceeded the 'OverLoad Level 3 Threshold' value."
|
|
::= 23
|
|
|
|
trapLevel3OverloadOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Level 3 overload ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS Output is no longer above the 'Overload Level 3 threshold' value."
|
|
::= 24
|
|
|
|
trapPosDCLinkOverVoltage TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Positive DC link over voltage."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Positive DC link voltage has exceeded the 'Over Voltage Threshold' value."
|
|
::= 25
|
|
|
|
trapPosDCLinkOverVoltageOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Positive DC link over voltage ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Positive DC link Voltage is no longer above the "Over Voltage Threshold" value."
|
|
::= 26
|
|
|
|
trapPosDCLinkUnderVoltage TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Positive DC link under voltage."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Positive DC Link Voltage has fallen below 'Low Voltage Threshold' value."
|
|
::= 27
|
|
|
|
trapPosDCLinkUnderVoltageOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Positive DC link under voltage ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Positive DC link Voltage is no longer below the 'Under Voltage Threshold' value."
|
|
::= 28
|
|
|
|
trapNegDCLinkOverVoltage TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Negative DC link over voltage."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Negative DC link Voltage has exceeded the 'Over Voltage Threshold' value."
|
|
::= 29
|
|
|
|
trapNegDCLinkOverVoltageOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Negative DC link over voltage ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Negative DC link over voltage is no longer above the 'Over Voltage Threshold' value."
|
|
::= 30
|
|
|
|
trapNegDCLinkUnderVoltage TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Negative DC link under voltage."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Negative DC link Voltage has fallen below 'Low Voltage Threshold' value."
|
|
::= 31
|
|
|
|
trapNegDCLinkUnderVoltageOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Negative DC link under voltage ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Negative DC link Voltage is no longer below the 'Under Voltage Threshold' value."
|
|
::= 32
|
|
|
|
trapRectifierFault TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Rectifier fault."
|
|
--#SEVERITY CRITICAL
|
|
--#SUMMARY "Rectifier fault has occured."
|
|
::= 33
|
|
|
|
trapRectifierOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Rectifier ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Rectifier is functioning normally."
|
|
::= 34
|
|
|
|
trapInverterFault TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Inverter fault."
|
|
--#SEVERITY CRITICAL
|
|
--#SUMMARY "There is an Inverter fault."
|
|
::= 35
|
|
|
|
trapInverterOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Inverter ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Inverter is functioning normally."
|
|
::= 36
|
|
|
|
trapChargerFailure TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Charger failure."
|
|
--#SEVERITY CRITICAL
|
|
--#SUMMARY "Charger failure has occured."
|
|
::= 37
|
|
|
|
trapChargerOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Charger ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Charger is functioning normally."
|
|
::= 38
|
|
|
|
trapEepromFailure TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"EEPROM failure."
|
|
--#SEVERITY CRITICAL
|
|
--#SUMMARY "EEPROM failure has occured."
|
|
::= 39
|
|
|
|
trapEepromOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"EEPROM off."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "EEPROM is turned off."
|
|
::= 40
|
|
|
|
trapShutdownImminent TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Shutdown imminent."
|
|
--#SEVERITY CRITICAL
|
|
--#SUMMARY "The UPS Shutdown is imminent."
|
|
::= 41
|
|
|
|
trapShutdownImminentOver TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Shutdown imminent over."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "The imminient UPS Shutdown is no longer present."
|
|
::= 42
|
|
|
|
trapBatteryLow TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Battery low."
|
|
--#SEVERITY CRITICAL
|
|
--#SUMMARY "UPS battery remaining capacity has fallen below the 'Low Remaining Capacity Threshold' value."
|
|
::= 43
|
|
|
|
trapBatteryOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Battery ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS battery remaining capacity is no longer below the 'Under Remaining Capacity Threshold' value."
|
|
::= 44
|
|
|
|
trapOutputShortCircuit TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Output short circuit."
|
|
--#SEVERITY CRITICAL
|
|
--#SUMMARY "Output short circuit."
|
|
::= 45
|
|
|
|
trapOutputReturnFromShortCircuit TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Output return from short circuit."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Output return from short circuit."
|
|
::= 46
|
|
|
|
trapUtilityNotPresent TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Utility not present."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Utility is not present."
|
|
::= 47
|
|
|
|
trapUtilityPresent TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Utility present."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Utility is present."
|
|
::= 48
|
|
|
|
trapBatteryOverVoltage TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Battery DC over voltage."
|
|
--#SEVERITY CRITICAL
|
|
--#SUMMARY "Battery DC Voltage has exceeded the 'Over Voltage Threshold' value."
|
|
::= 49
|
|
|
|
trapBatteryOverVoltageOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Battery DC over voltage ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Battery DC Voltage is no longer above the 'Over Voltage Threshold' value."
|
|
::= 50
|
|
|
|
trapHeatsinkOvertemperature TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Heatsink overtemperature."
|
|
--#SEVERITY CRITICAL
|
|
--#SUMMARY "UPS temperature has exceeded the 'Over Temperature Threshold' value."
|
|
::= 51
|
|
|
|
trapHeatsinkOvertemperatureOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Heatsink overtemperature ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS temperature is no longer above the 'Over Temperature Threshold' value."
|
|
::= 52
|
|
|
|
trapBypassNotAvailable TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Bypass not available."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Bypass is not available."
|
|
::= 53
|
|
|
|
trapBypassNotAvailableOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Bypass not available ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Bypass is now available."
|
|
::= 54
|
|
|
|
trapOnManualBypass TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"On manual/ maintenance bypass."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "On manual/ maintenance bypass."
|
|
::= 55
|
|
|
|
trapUPSOnBattery TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"UPS on battery."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS on battery."
|
|
::= 57
|
|
|
|
trapUPSReturnFromBattery TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"UPS return from battery."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS return from battery."
|
|
::= 58
|
|
|
|
trapUPSOnBypass TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"UPS on bypass."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS on bypass."
|
|
::= 59
|
|
|
|
trapUPSReturnFromBypass TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"UPS return from bypass."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS return from bypass."
|
|
::= 60
|
|
|
|
trapBatteryTestInProgress TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Battery manual or automatic test in progress."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Battery manual or automatic test in progress."
|
|
::= 61
|
|
|
|
trapBatteryTestDone TRAP-TYPE
|
|
ENTERPRISE traps
|
|
VARIABLES { physicalBatteryTestStatus }
|
|
DESCRIPTION
|
|
"Battery test done."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Battery test done, battery status is: %d."
|
|
--#ARGUMENTS {0}
|
|
::= 62
|
|
|
|
trapBatteryNeedReplacement TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Battery test failed, battery needs to be replaced."
|
|
--#SEVERITY CRITICAL
|
|
--#SUMMARY "Battery test failed, battery needs to be replaced."
|
|
::= 63
|
|
|
|
trapBatteryReplacementDone TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Battery replacement done."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Battery replacement is done."
|
|
::= 64
|
|
|
|
trapFanFailure TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Fan failure."
|
|
--#SEVERITY CRITICAL
|
|
--#SUMMARY "UPS Fan has failed."
|
|
::= 65
|
|
|
|
trapFanOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Fan ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS Fan is working normally."
|
|
::= 66
|
|
|
|
trapSiteWiringFault TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Site wiring fault."
|
|
--#SEVERITY CRITICAL
|
|
--#SUMMARY "There is a fault in Site Wiring."
|
|
::= 67
|
|
|
|
trapSiteWiringOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Site wiring ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "No fault found in Site Wiring."
|
|
::= 68
|
|
|
|
trapBatteryDisconnected TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Batteries disconnected."
|
|
--#SEVERITY CRITICAL
|
|
--#SUMMARY "Batteries have been disconnected from the UPS."
|
|
::= 69
|
|
|
|
trapBatteryConnected TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Batteries connected."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Batteries have been connected to UPS."
|
|
::= 70
|
|
|
|
trapUPSOff TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"UPS off."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "UPS has been turned Off."
|
|
::= 71
|
|
|
|
trapUPSOn TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"UPS on."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "UPS has been turned On."
|
|
::= 72
|
|
|
|
trapDCLinkImbalance TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"DC link imbalance."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS has a DC link imbalance."
|
|
::= 73
|
|
|
|
trapDCLinkImbalanceOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"DC link imbalance ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS no longer has a DC link imbalance."
|
|
::= 74
|
|
|
|
trapABMOn TRAP-TYPE
|
|
ENTERPRISE traps
|
|
VARIABLES { physicalBatteryABMStatus }
|
|
DESCRIPTION
|
|
"ABM state on."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "ABM is POWERED ON, battery state is : %d"
|
|
--#ARGUMENTS {0}
|
|
::= 79
|
|
|
|
trapABMOff TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"ABM state off."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "ABM state is POWERED OFF."
|
|
::= 80
|
|
|
|
trapLoadSegment1Off TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Load segment 1 off."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Load segment 1 is Switched Off."
|
|
::= 81
|
|
|
|
trapLoadSegment1On TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Load segment 1 on."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Load segment 1 is Switched On."
|
|
::= 82
|
|
|
|
trapLoadSegment2Off TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Load segment 2 off."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Load segment 2 is Switched Off."
|
|
::= 83
|
|
|
|
trapLoadSegment2On TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Load segment 2 on."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Load segment 2 is Switched On."
|
|
::= 84
|
|
|
|
trapInHighEfficiencyMode TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"In High Efficiency mode."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "UPS is running in High Efficiency mode."
|
|
::= 85
|
|
|
|
trapReturnFromHighEfficiencyMode TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Return from High Efficiency mode."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS is no longer running in High Efficiency mode."
|
|
::= 86
|
|
|
|
trapRectifierOverload TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Rectifier input over current."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Rectifier Input Current has exceeded the 'Input Current Threshold' value."
|
|
::= 87
|
|
|
|
trapRectifierOverloadOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Rectifier current ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Rectifier current is no longer over 'Input Current Threshold' value."
|
|
::= 88
|
|
|
|
trapInverterOverload TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Inverter output over current."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Inverter Output Current has exceeded the 'Over Load Threshold' value."
|
|
::= 89
|
|
|
|
trapInverterOverloadOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Inverter output current ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Inverter Output Current is no longer over 'Ouput Current Threshold' value."
|
|
::= 90
|
|
|
|
trapBypassVoltageOutOfRange TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Bypass AC under or over voltage."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Bypass AC Voltage has gone out of Normal Range."
|
|
::= 91
|
|
|
|
trapBypassVoltageOutOfRangeOk TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Bypass AC under or over voltage ok."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Bypass AC Voltage has returned back to Normal Range."
|
|
::= 92
|
|
|
|
trapServiceBattery TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Service battery."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "UPS battery needs to be serviced."
|
|
::= 93
|
|
|
|
trapToBypassCommand TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"UPS received command to switch on bypass."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS received command to switch on bypass."
|
|
::= 94
|
|
|
|
trapFromBypassCommand TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"UPS received command to switch on inverter."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "UPS received command to switch from bypass to inverter."
|
|
::= 95
|
|
|
|
trapCommunicationLost TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Lost communication with UPS, HID databasis is not updated."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "UMC lost communication with UPS, HID databasis is not updated."
|
|
::= 96
|
|
|
|
trapCommunicationRestored TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Communication restored with UPS, HID databasis is updated."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Communication restored with UPS."
|
|
::= 97
|
|
|
|
-- 01.04.0001 Release on 2011/07/28 : Traps 98 to 111 added for the environment sensor.
|
|
|
|
trapEnvironComFailure TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Environment Probe communication failure."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Environment Probe communication failure."
|
|
::= 98
|
|
|
|
trapEnvironComOK TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Environment Probe communication restored."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Environment Probe communication restored."
|
|
::= 99
|
|
|
|
trapEnvironTemperatureLow TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Temperature is below low threshold."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Temperature is below low threshold."
|
|
::= 100
|
|
|
|
trapEnvironTemperatureHigh TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Temperature is above high threshold."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Temperature is above high threshold."
|
|
::= 102
|
|
|
|
trapEnvironTemperatureOK TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Temperature is in normal range."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Temperature is in normal range."
|
|
::= 103
|
|
|
|
trapEnvironHumidityLow TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Humidity is below low threshold."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Humidity is below low threshold."
|
|
::= 104
|
|
|
|
trapEnvironHumidityHigh TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Humidity is above high threshold."
|
|
--#SEVERITY WARNING
|
|
--#SUMMARY "Humidity is above high threshold."
|
|
::= 106
|
|
|
|
trapEnvironHumidityOK TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Humidity is in normal range."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Humidity is in normal range."
|
|
::= 107
|
|
|
|
trapEnvironInput1Closed TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Input #1 is Closed."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Input #1 is Closed."
|
|
::= 108
|
|
|
|
trapEnvironInput1Open TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Input #1 is Open."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Input #1 is Open."
|
|
::= 109
|
|
|
|
trapEnvironInput2Closed TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Input #2 is Closed."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Input #2 is Closed."
|
|
::= 110
|
|
|
|
trapEnvironInput2Open TRAP-TYPE
|
|
ENTERPRISE traps
|
|
DESCRIPTION
|
|
"Input #2 is Open."
|
|
--#SEVERITY INFORMATIONAL
|
|
--#SUMMARY "Input #2 is Open."
|
|
::= 111
|
|
END
|