--Delta-MIB { iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) delta(2254) ups(2) upsv4(4) }
|
|
|
|
|
|
DeltaUPS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
IMPORTS
|
|
enterprises, IpAddress
|
|
FROM RFC1155-SMI
|
|
DisplayString
|
|
FROM RFC1213-MIB
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
|
|
delta OBJECT IDENTIFIER ::= { enterprises 2254 }
|
|
|
|
ups OBJECT IDENTIFIER ::= { delta 2 }
|
|
|
|
upsv4 OBJECT IDENTIFIER ::= { ups 4 }
|
|
|
|
dupsIdent OBJECT IDENTIFIER ::= { upsv4 1 }
|
|
dupsControl OBJECT IDENTIFIER ::= { upsv4 2 }
|
|
dupsConfig OBJECT IDENTIFIER ::= { upsv4 3 }
|
|
dupsInput OBJECT IDENTIFIER ::= { upsv4 4 }
|
|
dupsOutput OBJECT IDENTIFIER ::= { upsv4 5 }
|
|
dupsBypass OBJECT IDENTIFIER ::= { upsv4 6 }
|
|
dupsBattery OBJECT IDENTIFIER ::= { upsv4 7 }
|
|
dupsTest OBJECT IDENTIFIER ::= { upsv4 8 }
|
|
dupsAlarm OBJECT IDENTIFIER ::= { upsv4 9 }
|
|
dupsEnvironment OBJECT IDENTIFIER ::= { upsv4 10 }
|
|
dupsTraps OBJECT IDENTIFIER ::= { upsv4 20 }
|
|
|
|
|
|
----------------------
|
|
-- dups Ident group --
|
|
----------------------
|
|
dupsIdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..20))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the UPS manufacturer."
|
|
::= { dupsIdent 1 }
|
|
|
|
dupsIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Model designation."
|
|
::= { dupsIdent 2 }
|
|
|
|
dupsIdentUPSSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..15))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS firmware/software version(s). This variable
|
|
may or may not has the same value as
|
|
upsIdentAgentSoftwareVersion in some implementations."
|
|
::= { dupsIdent 3 }
|
|
|
|
dupsIdentAgentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..15))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS agent software version. This variable may or
|
|
may not has the same value as
|
|
upsIdentUPSSoftwareVersion in some implementations."
|
|
::= { dupsIdent 4 }
|
|
|
|
dupsIdentName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the UPS. This object should be
|
|
set by the administrator."
|
|
::= { dupsIdent 5 }
|
|
|
|
dupsAttachedDevices OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the devices attached to the
|
|
output(s) of the UPS. This object should be set by
|
|
the administrator."
|
|
::= { dupsIdent 6 }
|
|
|
|
dupsRatingOutputVA OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal output VA rating."
|
|
::= { dupsIdent 7 }
|
|
|
|
dupsRatingOutputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal output voltage rating."
|
|
::= { dupsIdent 8 }
|
|
|
|
dupsRatingOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal output frequency rating."
|
|
::= { dupsIdent 9 }
|
|
|
|
dupsRatingInputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal input voltage rating."
|
|
::= { dupsIdent 10 }
|
|
|
|
dupsRatingInputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal input frequency rating."
|
|
::= { dupsIdent 11 }
|
|
|
|
dupsRatingBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal battery voltage rating."
|
|
::= { dupsIdent 12 }
|
|
|
|
dupsLowTransferVoltUpBound OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum input line voltage upper bound allowed
|
|
before the UPS system transfers to battery backup."
|
|
::= { dupsIdent 13 }
|
|
|
|
dupsLowTransferVoltLowBound OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum input line voltage lower bound allowed
|
|
before the UPS system transfers to battery backup."
|
|
::= { dupsIdent 14 }
|
|
|
|
dupsHighTransferVoltUpBound OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum input line voltage upper bound allowed
|
|
before the UPS system transfers to battery backup."
|
|
::= { dupsIdent 15 }
|
|
|
|
dupsHighTransferVoltLowBound OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum input line voltage lower bound allowed
|
|
before the UPS system transfers to battery backup."
|
|
::= { dupsIdent 16 }
|
|
|
|
dupsLowBattTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Minutes, time from low battery to low battery shutdown."
|
|
::= { dupsIdent 17 }
|
|
|
|
dupsOutletRelays OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of outlet relay. If it is 0, the function is not
|
|
available for the UPS."
|
|
::= { dupsIdent 18 }
|
|
|
|
dupsType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on-line(1),
|
|
off-line(2),
|
|
line-interactive(3),
|
|
3phase(4),
|
|
splite-phase(5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicate the UPS type."
|
|
::= { dupsIdent 19 }
|
|
|
|
------------------------
|
|
-- dups Control group --
|
|
------------------------
|
|
dupsShutdownType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
output(1),
|
|
system(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object determines the nature of the action to be
|
|
taken at the time when the countdown of the
|
|
upsShutdownAfterDelay and upsRebootWithDuration
|
|
objects reaches zero.
|
|
Setting this object to output(1) indicates that
|
|
shutdown requests should cause only the output of the
|
|
UPS to turn off. Setting this object to system(2)
|
|
indicates that shutdown requests will cause the entire
|
|
UPS system to turn off."
|
|
::= { dupsControl 1 }
|
|
|
|
dupsAutoReboot OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"In backup mode, the UPS may shutdown normally by SDA command,
|
|
dry-contact remote shutdown signal or low battery shutdown.
|
|
This command is used to determine the unit should restart or
|
|
not next time when the power restores"
|
|
::= { dupsControl 2 }
|
|
|
|
dupsShutdownAction OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
-- UNITS "Second"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the value is greater than 0 the UPS performs
|
|
shutdown action that defined by ShutdownType after
|
|
the seconds. 0, aborted."
|
|
::= { dupsControl 3 }
|
|
|
|
dupsRestartAction OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
-- UNITS "Minute"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS will restart after the indicated number of minutes.
|
|
-1, aborted."
|
|
::= { dupsControl 4 }
|
|
|
|
dupsSetOutletRelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicate which outlet relay, from 1,2,3... ."
|
|
::= { dupsControl 5 }
|
|
|
|
dupsRelayOffDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
-- UNITS "Second"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Turn the relay off after the seconds. The relay was indicated
|
|
by SetOutletRelay."
|
|
::= { dupsControl 6 }
|
|
|
|
dupsRelayOnDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
-- UNITS "Minute"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Turn the relay on after the seconds. The relay was indicated
|
|
by SetOutletRelay."
|
|
::= { dupsControl 7 }
|
|
|
|
--------------------------
|
|
-- dups Configure group --
|
|
--------------------------
|
|
dupsConfigBuzzerAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
alarm(1),
|
|
silence(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS will keep silence but will alarm again when
|
|
next power event is occurred"
|
|
::= { dupsConfig 1 }
|
|
|
|
dupsConfigBuzzerState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If it is disabled then the UPS is always muted."
|
|
::= { dupsConfig 2 }
|
|
|
|
dupsConfigSensitivity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(0),
|
|
reduced(1),
|
|
low(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The seneitivity of the UPS to utility line
|
|
abnormalities or noises."
|
|
::= { dupsConfig 3 }
|
|
|
|
dupsConfigLowVoltageTransferPoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum input line voltage allowed before the UPS
|
|
system transfers to battery backup."
|
|
::= { dupsConfig 4 }
|
|
|
|
dupsConfigHighVoltageTransferPoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum line voltage allowed before the UPS
|
|
system transfers to battery backup."
|
|
::= { dupsConfig 5 }
|
|
|
|
dupsConfigShutdownOSDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Second"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The operating system shutdown delay time when the
|
|
input power fail. -1 will disable this option."
|
|
::= { dupsConfig 6 }
|
|
|
|
dupsConfigUPSBootDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Second"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Delay the UPS startup after power restores. The power
|
|
quality may not stable when power restores, this
|
|
feature let the UPS wait a period of time to startup
|
|
the system."
|
|
::= { dupsConfig 7 }
|
|
|
|
dupsConfigExternalBatteryPack OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicate the number of external battery pack."
|
|
::= { dupsConfig 8 }
|
|
|
|
----------------------
|
|
-- dups Input group --
|
|
----------------------
|
|
dupsInputNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of input lines utilized in this device."
|
|
::= { dupsInput 1 }
|
|
|
|
dupsInputFrequency1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current input line 1 frequency to the UPS
|
|
system in 1/10 Hz."
|
|
::= { dupsInput 2 }
|
|
|
|
dupsInputVoltage1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 1 voltage of the UPS system in 1/10 V."
|
|
::= { dupsInput 3 }
|
|
|
|
dupsInputCurrent1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 1 current to the UPS system in 1/10 A."
|
|
::= { dupsInput 4 }
|
|
|
|
dupsInputFrequency2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current input line 2 frequency to the UPS system
|
|
in 1/10 Hz."
|
|
::= { dupsInput 5 }
|
|
|
|
dupsInputVoltage2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 2 voltage of the UPS system in 1/10 V."
|
|
::= { dupsInput 6 }
|
|
|
|
dupsInputCurrent2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 2 current to the UPS system in 1/10 A."
|
|
::= { dupsInput 7 }
|
|
|
|
dupsInputFrequency3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current input line 3 frequency to the UPS system
|
|
in 1/10 Hz."
|
|
::= { dupsInput 8 }
|
|
|
|
dupsInputVoltage3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 3 voltage of the UPS system in 1/10 V."
|
|
::= { dupsInput 9 }
|
|
|
|
dupsInputCurrent3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 3 current to the UPS system in 1/10 A."
|
|
::= { dupsInput 10 }
|
|
|
|
-----------------------
|
|
-- dups Output group --
|
|
-----------------------
|
|
dupsOutputSource OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(0),
|
|
battery(1),
|
|
bypass(2),
|
|
reducing(3),
|
|
boosting(4),
|
|
manualBypass(5),
|
|
other(6),
|
|
none(7)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present source of output power. The enumeration
|
|
none(7) indicates that there is no source of output
|
|
power (and therefore no output power), for example,
|
|
the system has opened the output breaker."
|
|
::= { dupsOutput 1 }
|
|
|
|
dupsOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Hertz"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output frequency in 1/10 Hz."
|
|
::= { dupsOutput 2 }
|
|
|
|
dupsOutputNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of output lines utilized in this device."
|
|
::= { dupsOutput 3 }
|
|
|
|
dupsOutputVoltage1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 1 voltage of the UPS system in 1/10 V."
|
|
::= { dupsOutput 4 }
|
|
|
|
dupsOutputCurrent1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 1 current of the UPS system in 1/10 A."
|
|
::= { dupsOutput 5 }
|
|
|
|
dupsOutputPower1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 1 real power of the UPS system in watts."
|
|
::= { dupsOutput 6 }
|
|
|
|
dupsOutputLoad1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current UPS output line 1 load expressed in percent
|
|
of rated capacity."
|
|
::= { dupsOutput 7 }
|
|
|
|
dupsOutputVoltage2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 2 voltage of the UPS system in 1/10 V."
|
|
::= { dupsOutput 8 }
|
|
|
|
dupsOutputCurrent2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 2 current of the UPS system in 1/10 A."
|
|
::= { dupsOutput 9 }
|
|
|
|
dupsOutputPower2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 2 real power of the UPS system in watts."
|
|
::= { dupsOutput 10 }
|
|
|
|
dupsOutputLoad2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current UPS output line 2 load expressed in percent
|
|
of rated capacity."
|
|
::= { dupsOutput 11 }
|
|
|
|
dupsOutputVoltage3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 3 voltage of the UPS system in 1/10 V."
|
|
::= { dupsOutput 12 }
|
|
|
|
dupsOutputCurrent3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 3 current of the UPS system in 1/10 A."
|
|
::= { dupsOutput 13 }
|
|
|
|
dupsOutputPower3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 3 real power of the UPS system in watts."
|
|
::= { dupsOutput 14 }
|
|
|
|
dupsOutputLoad3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current UPS output line 3 load expressed in percent
|
|
of rated capacity."
|
|
::= { dupsOutput 15 }
|
|
|
|
-----------------------
|
|
-- dups Bypass group --
|
|
-----------------------
|
|
dupsBypassFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Hertz"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass frequency in 1/10 Hz."
|
|
::= { dupsBypass 1 }
|
|
|
|
dupsBypassNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of bypass lines utilized in this device."
|
|
::= { dupsBypass 2 }
|
|
|
|
dupsBypassVoltage1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 1 voltage of the UPS system in 1/10 V."
|
|
::= { dupsBypass 3 }
|
|
|
|
dupsBypassCurrent1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 1 current of the UPS system in 1/10 A."
|
|
::= { dupsBypass 4 }
|
|
|
|
dupsBypassPower1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 1 real power of the UPS system in watts."
|
|
::= { dupsBypass 5 }
|
|
|
|
dupsBypassVoltage2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 2 voltage of the UPS system in 1/10 V."
|
|
::= { dupsBypass 6 }
|
|
|
|
dupsBypassCurrent2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 2 current of the UPS system in 1/10 A."
|
|
::= { dupsBypass 7 }
|
|
|
|
dupsBypassPower2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 2 real power of the UPS system in watts."
|
|
::= { dupsBypass 8 }
|
|
|
|
dupsBypassVoltage3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 3 voltage of the UPS system in 1/10 V."
|
|
::= { dupsBypass 9 }
|
|
|
|
dupsBypassCurrent3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 3 current of the UPS system in 1/10 A."
|
|
::= { dupsBypass 10 }
|
|
|
|
dupsBypassPower3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 3 real power of the UPS system in watts."
|
|
::= { dupsBypass 11 }
|
|
|
|
------------------------
|
|
-- dups Battery group --
|
|
------------------------
|
|
dupsBatteryCondiction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good(0),
|
|
weak(1),
|
|
replace(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The indication of the capacity remaining in the UPS
|
|
system's batteries when AC normal."
|
|
::= { dupsBattery 1 }
|
|
|
|
dupsBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok(0),
|
|
low(1),
|
|
depleted(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The indication of the capacity remaining in the UPS
|
|
system's batteries when AC failed. A value of ok
|
|
indicates that the remaining run-time is greater than
|
|
upsConfigLowBattTime. A value of low indicates
|
|
that the remaining battery run-time is less than or
|
|
equal to upsConfigLowBattTime. A value of
|
|
depleted indicates that the UPS will be unable
|
|
to sustain the present load when and if the utility
|
|
power is lost (including the possibility that the
|
|
utility power is currently absent and the UPS is
|
|
unable to sustain the output)."
|
|
::= { dupsBattery 2 }
|
|
|
|
dupsBatteryCharge OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
floating(0),
|
|
charging(1),
|
|
resting(2),
|
|
discharging(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsBattery 3 }
|
|
|
|
dupsSecondsOnBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the unit is on battery power, the elapsed time
|
|
since the UPS last switched to battery power, or the
|
|
time since the network management subsystem was last
|
|
restarted, whichever is less. Zero shall be returned
|
|
if the unit is not on battery power."
|
|
::= { dupsBattery 4 }
|
|
|
|
dupsBatteryEstimatedTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "minutes"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Estimated time from backup to low battery shutdown."
|
|
::= { dupsBattery 5 }
|
|
|
|
dupsBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt DC"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present battery voltage
|
|
in 1/10 V."
|
|
::= { dupsBattery 6 }
|
|
|
|
dupsBatteryCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp DC"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present battery current in 1/10 A."
|
|
::= { dupsBattery 7 }
|
|
|
|
dupsBatteryCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
UNITS "percent"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An estimate of the battery charge remaining expressed
|
|
as a percent of full charge."
|
|
::= { dupsBattery 8 }
|
|
|
|
dupsTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ambient temperature at or near the UPS Battery
|
|
casing."
|
|
::= { dupsBattery 9 }
|
|
|
|
dupsLastReplaceDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The last battery replacement date. The format is YYYYMMDD."
|
|
::= { dupsBattery 10 }
|
|
|
|
dupsNextReplaceDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The next battery replacement date. The format is YYYYMMDD."
|
|
::= { dupsBattery 11 }
|
|
|
|
-------------------
|
|
-- dups Test group
|
|
-------------------
|
|
dupsTestType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
abort(0),
|
|
generalTest(1),
|
|
batteryTest(2),
|
|
testFor10sec(3),
|
|
testUntilBattlow(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Perform the UPS Test procedure."
|
|
::= { dupsTest 1 }
|
|
|
|
dupsTestResultsSummary OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTestsInitiated(0),
|
|
donePass(1),
|
|
inProgress(2),
|
|
generalTestFail(3),
|
|
batteryTestFail(4),
|
|
deepBatteryTestFail(5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The results of the current or last UPS diagnostics
|
|
test performed. The values for donePass(1),
|
|
generalTestFail(3), and batteryTestFail(4) indicate that the
|
|
test completed either successfully, with a warning, or
|
|
with an error, respectively.Tests which have not yet
|
|
concluded are indicated by inProgress(2). The value
|
|
noTestsInitiated(0) indicates that no previous test
|
|
results are available."
|
|
::= { dupsTest 2 }
|
|
|
|
dupsTestResultsDetail OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..255))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Additional information about upsTestResultsSummary.
|
|
If no additional information available, a zero length
|
|
string is returned."
|
|
::= { dupsTest 3 }
|
|
|
|
-----------------------
|
|
-- dups Alarm group --
|
|
-----------------------
|
|
dupsAlarmDisconnect OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS disconnect?"
|
|
::= { dupsAlarm 1 }
|
|
|
|
dupsAlarmPowerFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the input power fail?"
|
|
::= { dupsAlarm 2 }
|
|
|
|
dupsAlarmBatteryLow OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Are the UPS batteries low?"
|
|
::= { dupsAlarm 3 }
|
|
|
|
dupsAlarmLoadWarning OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS load percent over the load warning value?"
|
|
::= { dupsAlarm 4 }
|
|
|
|
dupsAlarmLoadSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS load percent over the load severity value?"
|
|
::= { dupsAlarm 5 }
|
|
|
|
dupsAlarmLoadOnBypass OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS load on bypass?"
|
|
::= { dupsAlarm 6 }
|
|
|
|
dupsAlarmUPSFault OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS general fail?"
|
|
::= { dupsAlarm 7 }
|
|
|
|
dupsAlarmBatteryGroundFault OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS battery ground fault?"
|
|
::= { dupsAlarm 8 }
|
|
|
|
dupsAlarmTestInProgress OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS test in progress?"
|
|
::= { dupsAlarm 9 }
|
|
|
|
dupsAlarmBatteryTestFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS test fail?"
|
|
::= { dupsAlarm 10 }
|
|
|
|
dupsAlarmFuseFailure OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS fuse failure?"
|
|
::= { dupsAlarm 11 }
|
|
|
|
dupsAlarmOutputOverload OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS output overload?"
|
|
::= { dupsAlarm 12 }
|
|
|
|
dupsAlarmOutputOverCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS output overcurrent?"
|
|
::= { dupsAlarm 13 }
|
|
|
|
dupsAlarmInverterAbnormal OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS inverter abnormal?"
|
|
::= { dupsAlarm 14 }
|
|
|
|
dupsAlarmRectifierAbnormal OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS rectifier abnormal?"
|
|
::= { dupsAlarm 15 }
|
|
|
|
dupsAlarmReserveAbnormal OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS reserve abnormal?"
|
|
::= { dupsAlarm 16 }
|
|
|
|
dupsAlarmLoadOnReserve OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS load on reserve?"
|
|
::= { dupsAlarm 17 }
|
|
|
|
dupsAlarmOverTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS over heat?"
|
|
::= { dupsAlarm 18 }
|
|
|
|
dupsAlarmOutputBad OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Is the UPS output abnormal?"
|
|
::= { dupsAlarm 19 }
|
|
|
|
dupsAlarmBypassBad OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Is the UPS bypass bad?"
|
|
::= { dupsAlarm 20 }
|
|
|
|
dupsAlarmUPSOff OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Is the UPS in standby mode?"
|
|
::= { dupsAlarm 21 }
|
|
|
|
dupsAlarmChargerFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS charger fail?"
|
|
::= { dupsAlarm 22 }
|
|
|
|
dupsAlarmFanFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS fan fail?"
|
|
::= { dupsAlarm 23 }
|
|
|
|
dupsAlarmEconomicMode OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates whether the UPS is in the economic mode."
|
|
::= { dupsAlarm 24 }
|
|
|
|
dupsAlarmOutputOff OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates whether the UPS output is turned off or not."
|
|
::= { dupsAlarm 25 }
|
|
|
|
dupsAlarmSmartShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates whether the Smart Shutdown is in progress."
|
|
::= { dupsAlarm 26 }
|
|
|
|
dupsAlarmEmergencyPowerOff OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS emergency power off."
|
|
::= { dupsAlarm 27 }
|
|
|
|
dupsAlarmUPSShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS shutdown."
|
|
::= { dupsAlarm 28 }
|
|
|
|
-----------------------
|
|
-- dups Environment group --
|
|
-----------------------
|
|
|
|
dupsEnvTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ambient environmental temperature."
|
|
::= { dupsEnvironment 1 }
|
|
|
|
dupsEnvHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "percentage"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The environmental humidity."
|
|
::= { dupsEnvironment 2 }
|
|
|
|
dupsEnvSetTemperatureLimit OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm dupsAlarmOverTemperature on when the environmental
|
|
temperature over the value."
|
|
::= { dupsEnvironment 3 }
|
|
|
|
dupsEnvSetHumidityLimit OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "percentage"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm dupsAlarmOverHumidity on when the environmental
|
|
humidity over the value."
|
|
::= { dupsEnvironment 4 }
|
|
|
|
dupsEnvSetEnvRelay1 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
normalOpen(0),
|
|
normalClose(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 5 }
|
|
|
|
dupsEnvSetEnvRelay2 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
normalOpen(0),
|
|
normalClose(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 6 }
|
|
|
|
dupsEnvSetEnvRelay3 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
normalOpen(0),
|
|
normalClose(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 7 }
|
|
|
|
dupsEnvSetEnvRelay4 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
normalOpen(0),
|
|
normalClose(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 8 }
|
|
|
|
dupsAlarmOverEnvTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the environment over temperature?"
|
|
::= { dupsEnvironment 9 }
|
|
|
|
dupsAlarmOverEnvHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the environment over humidity?"
|
|
::= { dupsEnvironment 10 }
|
|
|
|
dupsAlarmEnvRelay1 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 11 }
|
|
|
|
dupsAlarmEnvRelay2 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 12 }
|
|
|
|
dupsAlarmEnvRelay3 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 13 }
|
|
|
|
dupsAlarmEnvRelay4 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 14 }
|
|
|
|
-----------------------
|
|
-- dups Trap group --
|
|
-----------------------
|
|
|
|
dupsCommunicationLost TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: Communication with the UPS failed."
|
|
::= 1
|
|
|
|
dupsCommunicationEstablished TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Communication with the UPS reestablished."
|
|
::= 2
|
|
|
|
dupsPowerFail TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"WARNING: Power failed! The UPS is operating on battery power."
|
|
::= 3
|
|
|
|
dupsPowerRestored TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Power restored! The utility power restored."
|
|
::= 4
|
|
|
|
dupsLowBattery TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS batteries are low and will soon be exhausted."
|
|
::= 5
|
|
|
|
dupsReturnFromLowBattery TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has returned from a low battery condition."
|
|
::= 6
|
|
|
|
dupsLoadWarning TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Loading percent of the UPS over the Load Warning value."
|
|
::= 7
|
|
|
|
dupsNoLongerLoadWarning TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Returnd from Load Warning condition."
|
|
::= 8
|
|
|
|
dupsLoadSeverity TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"Warning: Loading percent of the UPS over the Load Severity value."
|
|
::= 9
|
|
|
|
dupsNoLongerLoadSeverity TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Returned from Load Severity condition."
|
|
::= 10
|
|
|
|
dupsLoadOnBypass TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS loads on bypass."
|
|
::= 11
|
|
|
|
dupsNoLongerLoadOnBypass TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS is not on bypass mode."
|
|
::= 12
|
|
|
|
dupsUPSFault TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: A general fault caused in the UPS."
|
|
::= 13
|
|
|
|
dupsReturnFromUPSFault TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS is returned from general fault."
|
|
::= 14
|
|
|
|
dupsBatteryGroundFault TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS battery ground fault."
|
|
::= 15
|
|
|
|
dupsNoLongerBatteryFault TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS recovered from battery ground fault."
|
|
::= 16
|
|
|
|
dupsTestInProgress TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS test in progress."
|
|
::= 17
|
|
|
|
dupsBatteryTestFail TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS test fail."
|
|
::= 18
|
|
|
|
dupsFuseFailure TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS fuse failed."
|
|
::= 19
|
|
|
|
dupsFuseRecovered TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS fuse recovered."
|
|
::= 20
|
|
|
|
dupsOutputOverload TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS overload!."
|
|
::= 21
|
|
|
|
dupsNoLongerOverload TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Recovered from UPS overload."
|
|
::= 22
|
|
|
|
dupsOutputOverCurrent TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS output overcurrent."
|
|
::= 23
|
|
|
|
dupsNoLongerOutputOverCurrent TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Recovered from UPS overcurrent."
|
|
::= 24
|
|
|
|
dupsInverterAbnormal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS inverter abnormal."
|
|
::= 25
|
|
|
|
dupsInverterRecovered TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Recovered from UPS inverter abnormal."
|
|
::= 26
|
|
|
|
dupsRectifierAbnormal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS rectifier abnormal."
|
|
::= 27
|
|
|
|
dupsRectifierRecovered TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS recovered from rectifier abnormal."
|
|
::= 28
|
|
|
|
dupsReserveAbnormal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS rectifier abnormal."
|
|
::= 29
|
|
|
|
dupsReserveRecovered TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS rectifier abnormal."
|
|
::= 30
|
|
|
|
dupsLoadOnReserve TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS load on reserve."
|
|
::= 31
|
|
|
|
dupsNoLongerLoadOnReserve TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS no longer load on reserve."
|
|
::= 32
|
|
|
|
dupsEnvOverTemperature TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"WARNING: The environment overtemperature."
|
|
::= 33
|
|
|
|
dupsNoLongerEnvOverTemperature TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment recovered from overtemperature."
|
|
::= 34
|
|
|
|
dupsEnvOverHumidity TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"WARNING: The environment overhumidity."
|
|
::= 35
|
|
|
|
dupsNoLongerEnvOverHumidity TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment recovered from overhumidity."
|
|
::= 36
|
|
|
|
dupsEnvRelay1Alarm TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay1 is not in normal state."
|
|
::= 37
|
|
|
|
dupsEnvRelay1Normal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay1 is in normal state."
|
|
::= 38
|
|
|
|
dupsEnvRelay2Alarm TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay2 is not in normal state."
|
|
::= 39
|
|
|
|
dupsEnvRelay2Normal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay2 is in normal state."
|
|
::= 40
|
|
|
|
dupsEnvRelay3Alarm TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay3 is not in normal state."
|
|
::= 41
|
|
|
|
dupsEnvRelay3Normal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay3 is in normal state."
|
|
::= 42
|
|
|
|
dupsEnvRelay4Alarm TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay4 is not in normal state."
|
|
::= 43
|
|
|
|
dupsEnvRelay4Normal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay4 is in normal state."
|
|
::= 44
|
|
|
|
dupsSmartShutdown TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: Smart Shutdown is initiated."
|
|
::= 45
|
|
|
|
dupsCancelShutdown TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Cancel UPS Shutdown."
|
|
::= 46
|
|
|
|
dupsTestCompleted TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: This trap is sent upon completion of a UPS diagnostic test."
|
|
::= 47
|
|
|
|
dupsEPOON TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: This trap is sent when emergency power off is on."
|
|
::= 48
|
|
|
|
dupsEPOOFF TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: This trap is sent when UPS recover from emergency power off."
|
|
::= 49
|
|
|
|
dupsOverTemperature TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: This trap is sent when the UPS is over heat."
|
|
::= 50
|
|
|
|
dupsNormalTemperature TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: This trap is sent when UPS recover from over heat."
|
|
::= 51
|
|
|
|
dupsBattReplace TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"WARNING: The battery needs to be replaced."
|
|
::= 52
|
|
|
|
dupsReturnFromBattReplace TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS recovered from battery replacement."
|
|
::= 53
|
|
END
|