mibs/MIBS/delta/DeltaUPS-MIB
2023-12-05 12:25:34 +01:00

1667 lines
44 KiB
Plaintext

--Delta-MIB { iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) delta(2254) ups(2) upsv4(4) }
DeltaUPS-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress
FROM RFC1155-SMI
DisplayString
FROM RFC1213-MIB
OBJECT-TYPE
FROM RFC-1212
TRAP-TYPE
FROM RFC-1215;
delta OBJECT IDENTIFIER ::= { enterprises 2254 }
ups OBJECT IDENTIFIER ::= { delta 2 }
upsv4 OBJECT IDENTIFIER ::= { ups 4 }
dupsIdent OBJECT IDENTIFIER ::= { upsv4 1 }
dupsControl OBJECT IDENTIFIER ::= { upsv4 2 }
dupsConfig OBJECT IDENTIFIER ::= { upsv4 3 }
dupsInput OBJECT IDENTIFIER ::= { upsv4 4 }
dupsOutput OBJECT IDENTIFIER ::= { upsv4 5 }
dupsBypass OBJECT IDENTIFIER ::= { upsv4 6 }
dupsBattery OBJECT IDENTIFIER ::= { upsv4 7 }
dupsTest OBJECT IDENTIFIER ::= { upsv4 8 }
dupsAlarm OBJECT IDENTIFIER ::= { upsv4 9 }
dupsEnvironment OBJECT IDENTIFIER ::= { upsv4 10 }
dupsTraps OBJECT IDENTIFIER ::= { upsv4 20 }
----------------------
-- dups Ident group --
----------------------
dupsIdentManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..20))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The name of the UPS manufacturer."
::= { dupsIdent 1 }
dupsIdentModel OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The UPS Model designation."
::= { dupsIdent 2 }
dupsIdentUPSSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..15))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The UPS firmware/software version(s). This variable
may or may not has the same value as
upsIdentAgentSoftwareVersion in some implementations."
::= { dupsIdent 3 }
dupsIdentAgentSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..15))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The UPS agent software version. This variable may or
may not has the same value as
upsIdentUPSSoftwareVersion in some implementations."
::= { dupsIdent 4 }
dupsIdentName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A string identifying the UPS. This object should be
set by the administrator."
::= { dupsIdent 5 }
dupsAttachedDevices OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A string identifying the devices attached to the
output(s) of the UPS. This object should be set by
the administrator."
::= { dupsIdent 6 }
dupsRatingOutputVA OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The magnitude of the nominal output VA rating."
::= { dupsIdent 7 }
dupsRatingOutputVoltage OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The magnitude of the nominal output voltage rating."
::= { dupsIdent 8 }
dupsRatingOutputFrequency OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The magnitude of the nominal output frequency rating."
::= { dupsIdent 9 }
dupsRatingInputVoltage OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The magnitude of the nominal input voltage rating."
::= { dupsIdent 10 }
dupsRatingInputFrequency OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The magnitude of the nominal input frequency rating."
::= { dupsIdent 11 }
dupsRatingBatteryVoltage OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The magnitude of the nominal battery voltage rating."
::= { dupsIdent 12 }
dupsLowTransferVoltUpBound OBJECT-TYPE
SYNTAX INTEGER
UNITS "Volt"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The minimum input line voltage upper bound allowed
before the UPS system transfers to battery backup."
::= { dupsIdent 13 }
dupsLowTransferVoltLowBound OBJECT-TYPE
SYNTAX INTEGER
UNITS "Volt"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The minimum input line voltage lower bound allowed
before the UPS system transfers to battery backup."
::= { dupsIdent 14 }
dupsHighTransferVoltUpBound OBJECT-TYPE
SYNTAX INTEGER
UNITS "Volt"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The maximum input line voltage upper bound allowed
before the UPS system transfers to battery backup."
::= { dupsIdent 15 }
dupsHighTransferVoltLowBound OBJECT-TYPE
SYNTAX INTEGER
UNITS "Volt"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The maximum input line voltage lower bound allowed
before the UPS system transfers to battery backup."
::= { dupsIdent 16 }
dupsLowBattTime OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Minutes, time from low battery to low battery shutdown."
::= { dupsIdent 17 }
dupsOutletRelays OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of outlet relay. If it is 0, the function is not
available for the UPS."
::= { dupsIdent 18 }
dupsType OBJECT-TYPE
SYNTAX INTEGER {
on-line(1),
off-line(2),
line-interactive(3),
3phase(4),
splite-phase(5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the UPS type."
::= { dupsIdent 19 }
------------------------
-- dups Control group --
------------------------
dupsShutdownType OBJECT-TYPE
SYNTAX INTEGER {
output(1),
system(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This object determines the nature of the action to be
taken at the time when the countdown of the
upsShutdownAfterDelay and upsRebootWithDuration
objects reaches zero.
Setting this object to output(1) indicates that
shutdown requests should cause only the output of the
UPS to turn off. Setting this object to system(2)
indicates that shutdown requests will cause the entire
UPS system to turn off."
::= { dupsControl 1 }
dupsAutoReboot OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"In backup mode, the UPS may shutdown normally by SDA command,
dry-contact remote shutdown signal or low battery shutdown.
This command is used to determine the unit should restart or
not next time when the power restores"
::= { dupsControl 2 }
dupsShutdownAction OBJECT-TYPE
SYNTAX INTEGER
-- UNITS "Second"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"If the value is greater than 0 the UPS performs
shutdown action that defined by ShutdownType after
the seconds. 0, aborted."
::= { dupsControl 3 }
dupsRestartAction OBJECT-TYPE
SYNTAX INTEGER
-- UNITS "Minute"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"UPS will restart after the indicated number of minutes.
-1, aborted."
::= { dupsControl 4 }
dupsSetOutletRelay OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate which outlet relay, from 1,2,3... ."
::= { dupsControl 5 }
dupsRelayOffDelay OBJECT-TYPE
SYNTAX INTEGER
-- UNITS "Second"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Turn the relay off after the seconds. The relay was indicated
by SetOutletRelay."
::= { dupsControl 6 }
dupsRelayOnDelay OBJECT-TYPE
SYNTAX INTEGER
-- UNITS "Minute"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Turn the relay on after the seconds. The relay was indicated
by SetOutletRelay."
::= { dupsControl 7 }
--------------------------
-- dups Configure group --
--------------------------
dupsConfigBuzzerAlarm OBJECT-TYPE
SYNTAX INTEGER {
alarm(1),
silence(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"UPS will keep silence but will alarm again when
next power event is occurred"
::= { dupsConfig 1 }
dupsConfigBuzzerState OBJECT-TYPE
SYNTAX INTEGER {
enable(1),
disable(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"If it is disabled then the UPS is always muted."
::= { dupsConfig 2 }
dupsConfigSensitivity OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
reduced(1),
low(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The seneitivity of the UPS to utility line
abnormalities or noises."
::= { dupsConfig 3 }
dupsConfigLowVoltageTransferPoint OBJECT-TYPE
SYNTAX INTEGER
UNITS "Volt"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The minimum input line voltage allowed before the UPS
system transfers to battery backup."
::= { dupsConfig 4 }
dupsConfigHighVoltageTransferPoint OBJECT-TYPE
SYNTAX INTEGER
UNITS "Volt"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The maximum line voltage allowed before the UPS
system transfers to battery backup."
::= { dupsConfig 5 }
dupsConfigShutdownOSDelay OBJECT-TYPE
SYNTAX INTEGER
UNITS "Second"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The operating system shutdown delay time when the
input power fail. -1 will disable this option."
::= { dupsConfig 6 }
dupsConfigUPSBootDelay OBJECT-TYPE
SYNTAX INTEGER
UNITS "Second"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Delay the UPS startup after power restores. The power
quality may not stable when power restores, this
feature let the UPS wait a period of time to startup
the system."
::= { dupsConfig 7 }
dupsConfigExternalBatteryPack OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the number of external battery pack."
::= { dupsConfig 8 }
----------------------
-- dups Input group --
----------------------
dupsInputNumLines OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of input lines utilized in this device."
::= { dupsInput 1 }
dupsInputFrequency1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current input line 1 frequency to the UPS
system in 1/10 Hz."
::= { dupsInput 2 }
dupsInputVoltage1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Input line 1 voltage of the UPS system in 1/10 V."
::= { dupsInput 3 }
dupsInputCurrent1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Input line 1 current to the UPS system in 1/10 A."
::= { dupsInput 4 }
dupsInputFrequency2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current input line 2 frequency to the UPS system
in 1/10 Hz."
::= { dupsInput 5 }
dupsInputVoltage2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Input line 2 voltage of the UPS system in 1/10 V."
::= { dupsInput 6 }
dupsInputCurrent2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Input line 2 current to the UPS system in 1/10 A."
::= { dupsInput 7 }
dupsInputFrequency3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current input line 3 frequency to the UPS system
in 1/10 Hz."
::= { dupsInput 8 }
dupsInputVoltage3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Input line 3 voltage of the UPS system in 1/10 V."
::= { dupsInput 9 }
dupsInputCurrent3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Input line 3 current to the UPS system in 1/10 A."
::= { dupsInput 10 }
-----------------------
-- dups Output group --
-----------------------
dupsOutputSource OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
battery(1),
bypass(2),
reducing(3),
boosting(4),
manualBypass(5),
other(6),
none(7)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The present source of output power. The enumeration
none(7) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker."
::= { dupsOutput 1 }
dupsOutputFrequency OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Hertz"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The present output frequency in 1/10 Hz."
::= { dupsOutput 2 }
dupsOutputNumLines OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of output lines utilized in this device."
::= { dupsOutput 3 }
dupsOutputVoltage1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Output line 1 voltage of the UPS system in 1/10 V."
::= { dupsOutput 4 }
dupsOutputCurrent1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Output line 1 current of the UPS system in 1/10 A."
::= { dupsOutput 5 }
dupsOutputPower1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Output line 1 real power of the UPS system in watts."
::= { dupsOutput 6 }
dupsOutputLoad1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current UPS output line 1 load expressed in percent
of rated capacity."
::= { dupsOutput 7 }
dupsOutputVoltage2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Output line 2 voltage of the UPS system in 1/10 V."
::= { dupsOutput 8 }
dupsOutputCurrent2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Output line 2 current of the UPS system in 1/10 A."
::= { dupsOutput 9 }
dupsOutputPower2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Output line 2 real power of the UPS system in watts."
::= { dupsOutput 10 }
dupsOutputLoad2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current UPS output line 2 load expressed in percent
of rated capacity."
::= { dupsOutput 11 }
dupsOutputVoltage3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Output line 3 voltage of the UPS system in 1/10 V."
::= { dupsOutput 12 }
dupsOutputCurrent3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Output line 3 current of the UPS system in 1/10 A."
::= { dupsOutput 13 }
dupsOutputPower3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Output line 3 real power of the UPS system in watts."
::= { dupsOutput 14 }
dupsOutputLoad3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current UPS output line 3 load expressed in percent
of rated capacity."
::= { dupsOutput 15 }
-----------------------
-- dups Bypass group --
-----------------------
dupsBypassFrequency OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Hertz"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The present bypass frequency in 1/10 Hz."
::= { dupsBypass 1 }
dupsBypassNumLines OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of bypass lines utilized in this device."
::= { dupsBypass 2 }
dupsBypassVoltage1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The bypass line 1 voltage of the UPS system in 1/10 V."
::= { dupsBypass 3 }
dupsBypassCurrent1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The bypass line 1 current of the UPS system in 1/10 A."
::= { dupsBypass 4 }
dupsBypassPower1 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The bypass line 1 real power of the UPS system in watts."
::= { dupsBypass 5 }
dupsBypassVoltage2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The bypass line 2 voltage of the UPS system in 1/10 V."
::= { dupsBypass 6 }
dupsBypassCurrent2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The bypass line 2 current of the UPS system in 1/10 A."
::= { dupsBypass 7 }
dupsBypassPower2 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The bypass line 2 real power of the UPS system in watts."
::= { dupsBypass 8 }
dupsBypassVoltage3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The bypass line 3 voltage of the UPS system in 1/10 V."
::= { dupsBypass 9 }
dupsBypassCurrent3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The bypass line 3 current of the UPS system in 1/10 A."
::= { dupsBypass 10 }
dupsBypassPower3 OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The bypass line 3 real power of the UPS system in watts."
::= { dupsBypass 11 }
------------------------
-- dups Battery group --
------------------------
dupsBatteryCondiction OBJECT-TYPE
SYNTAX INTEGER {
good(0),
weak(1),
replace(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The indication of the capacity remaining in the UPS
system's batteries when AC normal."
::= { dupsBattery 1 }
dupsBatteryStatus OBJECT-TYPE
SYNTAX INTEGER {
ok(0),
low(1),
depleted(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The indication of the capacity remaining in the UPS
system's batteries when AC failed. A value of ok
indicates that the remaining run-time is greater than
upsConfigLowBattTime. A value of low indicates
that the remaining battery run-time is less than or
equal to upsConfigLowBattTime. A value of
depleted indicates that the UPS will be unable
to sustain the present load when and if the utility
power is lost (including the possibility that the
utility power is currently absent and the UPS is
unable to sustain the output)."
::= { dupsBattery 2 }
dupsBatteryCharge OBJECT-TYPE
SYNTAX INTEGER {
floating(0),
charging(1),
resting(2),
discharging(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
""
::= { dupsBattery 3 }
dupsSecondsOnBattery OBJECT-TYPE
SYNTAX INTEGER
UNITS "seconds"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"If the unit is on battery power, the elapsed time
since the UPS last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is less. Zero shall be returned
if the unit is not on battery power."
::= { dupsBattery 4 }
dupsBatteryEstimatedTime OBJECT-TYPE
SYNTAX INTEGER
UNITS "minutes"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Estimated time from backup to low battery shutdown."
::= { dupsBattery 5 }
dupsBatteryVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Volt DC"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The magnitude of the present battery voltage
in 1/10 V."
::= { dupsBattery 6 }
dupsBatteryCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Amp DC"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The present battery current in 1/10 A."
::= { dupsBattery 7 }
dupsBatteryCapacity OBJECT-TYPE
SYNTAX INTEGER (0..100)
UNITS "percent"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An estimate of the battery charge remaining expressed
as a percent of full charge."
::= { dupsBattery 8 }
dupsTemperature OBJECT-TYPE
SYNTAX INTEGER
UNITS "degrees Centigrade"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The ambient temperature at or near the UPS Battery
casing."
::= { dupsBattery 9 }
dupsLastReplaceDate OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The last battery replacement date. The format is YYYYMMDD."
::= { dupsBattery 10 }
dupsNextReplaceDate OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The next battery replacement date. The format is YYYYMMDD."
::= { dupsBattery 11 }
-------------------
-- dups Test group
-------------------
dupsTestType OBJECT-TYPE
SYNTAX INTEGER {
abort(0),
generalTest(1),
batteryTest(2),
testFor10sec(3),
testUntilBattlow(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Perform the UPS Test procedure."
::= { dupsTest 1 }
dupsTestResultsSummary OBJECT-TYPE
SYNTAX INTEGER {
noTestsInitiated(0),
donePass(1),
inProgress(2),
generalTestFail(3),
batteryTestFail(4),
deepBatteryTestFail(5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The results of the current or last UPS diagnostics
test performed. The values for donePass(1),
generalTestFail(3), and batteryTestFail(4) indicate that the
test completed either successfully, with a warning, or
with an error, respectively.Tests which have not yet
concluded are indicated by inProgress(2). The value
noTestsInitiated(0) indicates that no previous test
results are available."
::= { dupsTest 2 }
dupsTestResultsDetail OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..255))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Additional information about upsTestResultsSummary.
If no additional information available, a zero length
string is returned."
::= { dupsTest 3 }
-----------------------
-- dups Alarm group --
-----------------------
dupsAlarmDisconnect OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS disconnect?"
::= { dupsAlarm 1 }
dupsAlarmPowerFail OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the input power fail?"
::= { dupsAlarm 2 }
dupsAlarmBatteryLow OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Are the UPS batteries low?"
::= { dupsAlarm 3 }
dupsAlarmLoadWarning OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS load percent over the load warning value?"
::= { dupsAlarm 4 }
dupsAlarmLoadSeverity OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS load percent over the load severity value?"
::= { dupsAlarm 5 }
dupsAlarmLoadOnBypass OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS load on bypass?"
::= { dupsAlarm 6 }
dupsAlarmUPSFault OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS general fail?"
::= { dupsAlarm 7 }
dupsAlarmBatteryGroundFault OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS battery ground fault?"
::= { dupsAlarm 8 }
dupsAlarmTestInProgress OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS test in progress?"
::= { dupsAlarm 9 }
dupsAlarmBatteryTestFail OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS test fail?"
::= { dupsAlarm 10 }
dupsAlarmFuseFailure OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS fuse failure?"
::= { dupsAlarm 11 }
dupsAlarmOutputOverload OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS output overload?"
::= { dupsAlarm 12 }
dupsAlarmOutputOverCurrent OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS output overcurrent?"
::= { dupsAlarm 13 }
dupsAlarmInverterAbnormal OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS inverter abnormal?"
::= { dupsAlarm 14 }
dupsAlarmRectifierAbnormal OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS rectifier abnormal?"
::= { dupsAlarm 15 }
dupsAlarmReserveAbnormal OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS reserve abnormal?"
::= { dupsAlarm 16 }
dupsAlarmLoadOnReserve OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS load on reserve?"
::= { dupsAlarm 17 }
dupsAlarmOverTemperature OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS over heat?"
::= { dupsAlarm 18 }
dupsAlarmOutputBad OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Is the UPS output abnormal?"
::= { dupsAlarm 19 }
dupsAlarmBypassBad OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Is the UPS bypass bad?"
::= { dupsAlarm 20 }
dupsAlarmUPSOff OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Is the UPS in standby mode?"
::= { dupsAlarm 21 }
dupsAlarmChargerFail OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS charger fail?"
::= { dupsAlarm 22 }
dupsAlarmFanFail OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the UPS fan fail?"
::= { dupsAlarm 23 }
dupsAlarmEconomicMode OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates whether the UPS is in the economic mode."
::= { dupsAlarm 24 }
dupsAlarmOutputOff OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates whether the UPS output is turned off or not."
::= { dupsAlarm 25 }
dupsAlarmSmartShutdown OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates whether the Smart Shutdown is in progress."
::= { dupsAlarm 26 }
dupsAlarmEmergencyPowerOff OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"UPS emergency power off."
::= { dupsAlarm 27 }
dupsAlarmUPSShutdown OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"UPS shutdown."
::= { dupsAlarm 28 }
-----------------------
-- dups Environment group --
-----------------------
dupsEnvTemperature OBJECT-TYPE
SYNTAX INTEGER
UNITS "degrees Centigrade"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The ambient environmental temperature."
::= { dupsEnvironment 1 }
dupsEnvHumidity OBJECT-TYPE
SYNTAX INTEGER
UNITS "percentage"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The environmental humidity."
::= { dupsEnvironment 2 }
dupsEnvSetTemperatureLimit OBJECT-TYPE
SYNTAX INTEGER
UNITS "degrees Centigrade"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alarm dupsAlarmOverTemperature on when the environmental
temperature over the value."
::= { dupsEnvironment 3 }
dupsEnvSetHumidityLimit OBJECT-TYPE
SYNTAX INTEGER
UNITS "percentage"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Alarm dupsAlarmOverHumidity on when the environmental
humidity over the value."
::= { dupsEnvironment 4 }
dupsEnvSetEnvRelay1 OBJECT-TYPE
SYNTAX INTEGER{
normalOpen(0),
normalClose(1)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
""
::= { dupsEnvironment 5 }
dupsEnvSetEnvRelay2 OBJECT-TYPE
SYNTAX INTEGER{
normalOpen(0),
normalClose(1)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
""
::= { dupsEnvironment 6 }
dupsEnvSetEnvRelay3 OBJECT-TYPE
SYNTAX INTEGER{
normalOpen(0),
normalClose(1)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
""
::= { dupsEnvironment 7 }
dupsEnvSetEnvRelay4 OBJECT-TYPE
SYNTAX INTEGER{
normalOpen(0),
normalClose(1)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
""
::= { dupsEnvironment 8 }
dupsAlarmOverEnvTemperature OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the environment over temperature?"
::= { dupsEnvironment 9 }
dupsAlarmOverEnvHumidity OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Does the environment over humidity?"
::= { dupsEnvironment 10 }
dupsAlarmEnvRelay1 OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
""
::= { dupsEnvironment 11 }
dupsAlarmEnvRelay2 OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
""
::= { dupsEnvironment 12 }
dupsAlarmEnvRelay3 OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
""
::= { dupsEnvironment 13 }
dupsAlarmEnvRelay4 OBJECT-TYPE
SYNTAX INTEGER{
off(0),
on(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
""
::= { dupsEnvironment 14 }
-----------------------
-- dups Trap group --
-----------------------
dupsCommunicationLost TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: Communication with the UPS failed."
::= 1
dupsCommunicationEstablished TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: Communication with the UPS reestablished."
::= 2
dupsPowerFail TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"WARNING: Power failed! The UPS is operating on battery power."
::= 3
dupsPowerRestored TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: Power restored! The utility power restored."
::= 4
dupsLowBattery TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: The UPS batteries are low and will soon be exhausted."
::= 5
dupsReturnFromLowBattery TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The UPS has returned from a low battery condition."
::= 6
dupsLoadWarning TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: Loading percent of the UPS over the Load Warning value."
::= 7
dupsNoLongerLoadWarning TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: Returnd from Load Warning condition."
::= 8
dupsLoadSeverity TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"Warning: Loading percent of the UPS over the Load Severity value."
::= 9
dupsNoLongerLoadSeverity TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: Returned from Load Severity condition."
::= 10
dupsLoadOnBypass TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: The UPS loads on bypass."
::= 11
dupsNoLongerLoadOnBypass TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The UPS is not on bypass mode."
::= 12
dupsUPSFault TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: A general fault caused in the UPS."
::= 13
dupsReturnFromUPSFault TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The UPS is returned from general fault."
::= 14
dupsBatteryGroundFault TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: The UPS battery ground fault."
::= 15
dupsNoLongerBatteryFault TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The UPS recovered from battery ground fault."
::= 16
dupsTestInProgress TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The UPS test in progress."
::= 17
dupsBatteryTestFail TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: The UPS test fail."
::= 18
dupsFuseFailure TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: The UPS fuse failed."
::= 19
dupsFuseRecovered TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The UPS fuse recovered."
::= 20
dupsOutputOverload TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: The UPS overload!."
::= 21
dupsNoLongerOverload TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: Recovered from UPS overload."
::= 22
dupsOutputOverCurrent TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: The UPS output overcurrent."
::= 23
dupsNoLongerOutputOverCurrent TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: Recovered from UPS overcurrent."
::= 24
dupsInverterAbnormal TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: The UPS inverter abnormal."
::= 25
dupsInverterRecovered TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: Recovered from UPS inverter abnormal."
::= 26
dupsRectifierAbnormal TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: The UPS rectifier abnormal."
::= 27
dupsRectifierRecovered TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The UPS recovered from rectifier abnormal."
::= 28
dupsReserveAbnormal TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: The UPS rectifier abnormal."
::= 29
dupsReserveRecovered TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The UPS rectifier abnormal."
::= 30
dupsLoadOnReserve TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: The UPS load on reserve."
::= 31
dupsNoLongerLoadOnReserve TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The UPS no longer load on reserve."
::= 32
dupsEnvOverTemperature TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"WARNING: The environment overtemperature."
::= 33
dupsNoLongerEnvOverTemperature TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The environment recovered from overtemperature."
::= 34
dupsEnvOverHumidity TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"WARNING: The environment overhumidity."
::= 35
dupsNoLongerEnvOverHumidity TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The environment recovered from overhumidity."
::= 36
dupsEnvRelay1Alarm TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The environment relay1 is not in normal state."
::= 37
dupsEnvRelay1Normal TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The environment relay1 is in normal state."
::= 38
dupsEnvRelay2Alarm TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The environment relay2 is not in normal state."
::= 39
dupsEnvRelay2Normal TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The environment relay2 is in normal state."
::= 40
dupsEnvRelay3Alarm TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The environment relay3 is not in normal state."
::= 41
dupsEnvRelay3Normal TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The environment relay3 is in normal state."
::= 42
dupsEnvRelay4Alarm TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The environment relay4 is not in normal state."
::= 43
dupsEnvRelay4Normal TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The environment relay4 is in normal state."
::= 44
dupsSmartShutdown TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: Smart Shutdown is initiated."
::= 45
dupsCancelShutdown TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: Cancel UPS Shutdown."
::= 46
dupsTestCompleted TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: This trap is sent upon completion of a UPS diagnostic test."
::= 47
dupsEPOON TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: This trap is sent when emergency power off is on."
::= 48
dupsEPOOFF TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: This trap is sent when UPS recover from emergency power off."
::= 49
dupsOverTemperature TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"SEVER: This trap is sent when the UPS is over heat."
::= 50
dupsNormalTemperature TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: This trap is sent when UPS recover from over heat."
::= 51
dupsBattReplace TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"WARNING: The battery needs to be replaced."
::= 52
dupsReturnFromBattReplace TRAP-TYPE
ENTERPRISE dupsTraps
DESCRIPTION
"INFORMATION: The UPS recovered from battery replacement."
::= 53
END