-- Title: DPS_V41v2.MIB
|
|
-- Version: v4.1 for SNMPv2c
|
|
--
|
|
-- Copyright @ 2011 DPS Inc. All Rights Reserved
|
|
--
|
|
-- This MIB defines objects for the DPS products.
|
|
--
|
|
-- Note: AnalogChannels table only available in NetGuardianG4 v4.2J or later
|
|
--
|
|
|
|
DPS-MIB-V38-V2 DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
DisplayString
|
|
FROM SNMPv2-TC
|
|
MODULE-IDENTITY,
|
|
NOTIFICATION-TYPE,
|
|
OBJECT-TYPE,
|
|
Integer32
|
|
FROM SNMPv2-SMI
|
|
dpsAlarmControl, tmonXM
|
|
FROM DPS-MIB-V38;
|
|
|
|
tmonV2XM MODULE-IDENTITY
|
|
LAST-UPDATED "201208081200Z" --August 8th, 2012 12:00 PDT
|
|
ORGANIZATION "DPS Telecom"
|
|
CONTACT-INFO "DPS Support Team
|
|
Web http://dpstele.com/support
|
|
E-Mail support@dpstele.com
|
|
Phone (559)454-1600"
|
|
DESCRIPTION "Second generation MIB for DPS Telecom products"
|
|
|
|
REVISION "201208081200Z" --August 8th, 2012 12:00 PDT
|
|
DESCRIPTION "Modified for proper smi/asn.1 formatting and structure (CBH)"
|
|
|
|
::= { dpsAlarmControl 3 }
|
|
|
|
tmonV2Ident OBJECT IDENTIFIER ::= {tmonV2XM 1}
|
|
|
|
tmonV2IdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The TMON/XM Unit manufacturer."
|
|
::= {tmonV2Ident 1}
|
|
|
|
tmonV2IdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The TMON/XM model designation."
|
|
::= {tmonV2Ident 2}
|
|
|
|
tmonV2IdentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The TMON/XM SNMP Agent software version."
|
|
::= {tmonV2Ident 3}
|
|
|
|
tmonV2AlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TMonV2AlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "A table of TMonV2 Alarm-specific information."
|
|
::= {tmonV2XM 2}
|
|
|
|
tmonV2AlarmEntry OBJECT-TYPE
|
|
SYNTAX TMonV2AlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Information about a particular TMonV2 alarm."
|
|
INDEX {tmonV2AIndex}
|
|
::= {tmonV2AlarmTable 1}
|
|
|
|
TMonV2AlarmEntry ::= SEQUENCE { tmonV2AIndex Integer32,
|
|
tmonV2ASite DisplayString,
|
|
tmonV2ADesc DisplayString,
|
|
tmonV2AState DisplayString,
|
|
tmonV2ASeverity DisplayString,
|
|
tmonV2AChgDate DisplayString,
|
|
tmonV2AChgTime DisplayString,
|
|
tmonV2AAuxDesc DisplayString,
|
|
tmonV2ADispDesc DisplayString,
|
|
tmonV2APntType Integer32,
|
|
tmonV2APort Integer32,
|
|
tmonV2AAddress Integer32,
|
|
tmonV2ADisplay Integer32,
|
|
tmonV2APoint Integer32,
|
|
tmonV2AEvent Integer32,
|
|
tmonV2AIPAddr DisplayString,
|
|
tmonV2ADevDesc DisplayString
|
|
}
|
|
|
|
tmonV2AIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Tmon alarm table index (1..NumberOfAlarms)."
|
|
::={tmonV2AlarmEntry 1}
|
|
|
|
tmonV2ASite OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The site of the alarm (i.e. Atlanta Hub, Sub-Station H32)."
|
|
::= {tmonV2AlarmEntry 2}
|
|
|
|
tmonV2ADesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "A user-defined text string associated with the alarm
|
|
(i.e. South Door, Generator, Power Grid 1)."
|
|
::= {tmonV2AlarmEntry 3}
|
|
|
|
tmonV2AState OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The current alarm state."
|
|
::= {tmonV2AlarmEntry 4}
|
|
|
|
tmonV2ASeverity OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The severity of the last alarm event."
|
|
::= {tmonV2AlarmEntry 5}
|
|
|
|
tmonV2AChgDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The date (mm/dd/yy) of the last alarm event."
|
|
::= {tmonV2AlarmEntry 6}
|
|
|
|
tmonV2AChgTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The time (hh:mm:ss) of the last alarm event."
|
|
::= {tmonV2AlarmEntry 7}
|
|
|
|
tmonV2AAuxDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "An auxiliary user-defined text string associated with the
|
|
alarm (i.e. This remote needs servicing)."
|
|
::= {tmonV2AlarmEntry 8}
|
|
|
|
tmonV2ADispDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "A description of the display on which this point appears."
|
|
::= {tmonV2AlarmEntry 9}
|
|
|
|
tmonV2APntType OBJECT-TYPE
|
|
SYNTAX Integer32 (0..999)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of this point."
|
|
::={tmonV2AlarmEntry 10}
|
|
|
|
tmonV2APort OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Port on which this point is reported."
|
|
::={tmonV2AlarmEntry 11}
|
|
|
|
tmonV2AAddress OBJECT-TYPE
|
|
SYNTAX Integer32 (0..9999)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Address of unit reporting this point."
|
|
::={tmonV2AlarmEntry 12}
|
|
|
|
tmonV2ADisplay OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Display on which this point appears."
|
|
::={tmonV2AlarmEntry 13}
|
|
|
|
tmonV2APoint OBJECT-TYPE
|
|
SYNTAX Integer32 (0..64)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Index into display of this point."
|
|
::={tmonV2AlarmEntry 14}
|
|
|
|
tmonV2AEvent OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Event id for this message."
|
|
::={tmonV2AlarmEntry 15}
|
|
|
|
tmonV2AIPAddr OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The IP Address of the device on which this point appears."
|
|
::= {tmonV2AlarmEntry 16}
|
|
|
|
tmonV2ADevDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "A description of the devie on which this point appears."
|
|
::= {tmonV2AlarmEntry 17}
|
|
|
|
-- structure used to issue a command to tmonV2XM element
|
|
|
|
tmonV2CommandGrid OBJECT IDENTIFIER ::= {tmonV2XM 3}
|
|
|
|
tmonV2CPType OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Tmon point type."
|
|
::= {tmonV2CommandGrid 1}
|
|
|
|
tmonV2CPort OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Tmon port number."
|
|
::= {tmonV2CommandGrid 2}
|
|
|
|
tmonV2CAddress OBJECT-TYPE
|
|
SYNTAX Integer32 (0..9999)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Tmon_port address number."
|
|
::= {tmonV2CommandGrid 3}
|
|
|
|
tmonV2CDisplay OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Tmon_port_address display number."
|
|
::= {tmonV2CommandGrid 4}
|
|
|
|
tmonV2CPoint OBJECT-TYPE
|
|
SYNTAX Integer32 (0..64)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Tmon_port_display point number (1-64)."
|
|
::= {tmonV2CommandGrid 5}
|
|
|
|
tmonV2CEvent OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Tmon event ID."
|
|
::= {tmonV2CommandGrid 6}
|
|
|
|
tmonV2CAction OBJECT-TYPE
|
|
SYNTAX INTEGER { latch(1),
|
|
release(2),
|
|
momentary(3),
|
|
ack(17),
|
|
tag(18),
|
|
untag(19)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Requested command action (tmonV2XM will ignore if invalid)."
|
|
::= {tmonV2CommandGrid 7}
|
|
|
|
tmonV2CAuxText OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "An auxiliary user-defined text string associated with the
|
|
command (i.e. User_initials)."
|
|
::= {tmonV2CommandGrid 8}
|
|
|
|
tmonV2CResult OBJECT-TYPE
|
|
SYNTAX INTEGER { success(1),
|
|
failure(2),
|
|
pending(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Command result."
|
|
::= {tmonV2CommandGrid 9}
|
|
|
|
|
|
|
|
dpsRTUv2 OBJECT IDENTIFIER ::= {dpsAlarmControl 4}
|
|
|
|
dpsRTUv2Ident OBJECT IDENTIFIER ::= {dpsRTUv2 1}
|
|
|
|
dpsRTUv2Manufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The Remote Telemetry Unit manufacturer."
|
|
::= {dpsRTUv2Ident 1}
|
|
|
|
dpsRTUv2Model OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The RTU model designation."
|
|
::= {dpsRTUv2Ident 2}
|
|
|
|
dpsRTUv2FirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The RTU firmware version."
|
|
::= {dpsRTUv2Ident 3}
|
|
|
|
dpsRTUv2DateTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The RTU system date and time."
|
|
::= {dpsRTUv2Ident 4}
|
|
|
|
dpsRTUv2SyncReq OBJECT-TYPE
|
|
SYNTAX INTEGER { sync(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Caution: SETting this object initiates traps for all
|
|
standing alarms."
|
|
::= {dpsRTUv2Ident 5}
|
|
|
|
|
|
-- structure used to access displays managed by this RTU
|
|
|
|
dpsRTUv2DisplayGrid OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DPSrtuV2DispEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Holds information on displays managed by the RTU."
|
|
::= {dpsRTUv2 2}
|
|
|
|
dpsRTUv2DisplayEntry OBJECT-TYPE
|
|
SYNTAX DPSrtuV2DispEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Information about a particular RTU display."
|
|
INDEX {dpsRTUv2Port, dpsRTUv2Address, dpsRTUv2Display}
|
|
::= {dpsRTUv2DisplayGrid 1}
|
|
|
|
DPSrtuV2DispEntry ::= SEQUENCE { dpsRTUv2Port Integer32,
|
|
dpsRTUv2Address Integer32,
|
|
dpsRTUv2Display Integer32,
|
|
dpsRTUv2DispDesc DisplayString,
|
|
dpsRTUv2PntMap DisplayString
|
|
}
|
|
|
|
dpsRTUv2Port OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "RTU port number."
|
|
::= {dpsRTUv2DisplayEntry 1}
|
|
|
|
dpsRTUv2Address OBJECT-TYPE
|
|
SYNTAX Integer32 (0..9999)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "RTU_port address number."
|
|
::= {dpsRTUv2DisplayEntry 2}
|
|
|
|
dpsRTUv2Display OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "RTU_port_address display number."
|
|
::= {dpsRTUv2DisplayEntry 3}
|
|
|
|
dpsRTUv2DispDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "A description of the associated display."
|
|
::= {dpsRTUv2DisplayEntry 4}
|
|
|
|
dpsRTUv2PntMap OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "A map of the points appearing in this display."
|
|
::= {dpsRTUv2DisplayEntry 5}
|
|
|
|
|
|
-- structure used to issue a control to a managed point
|
|
|
|
dpsRTUv2ControlGrid OBJECT IDENTIFIER ::= {dpsRTUv2 3}
|
|
|
|
dpsRTUv2CPort OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "RTU port number."
|
|
::= {dpsRTUv2ControlGrid 1}
|
|
|
|
dpsRTUv2CAddress OBJECT-TYPE
|
|
SYNTAX Integer32 (0..9999)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "RTU_port address number."
|
|
::= {dpsRTUv2ControlGrid 2}
|
|
|
|
dpsRTUv2CDisplay OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "RTU_port_address display number."
|
|
::= {dpsRTUv2ControlGrid 3}
|
|
|
|
dpsRTUv2CPoint OBJECT-TYPE
|
|
SYNTAX Integer32 (0..64)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "RTU_port_display point number (1-64)."
|
|
::= {dpsRTUv2ControlGrid 4}
|
|
|
|
dpsRTUv2CAction OBJECT-TYPE
|
|
SYNTAX INTEGER { latch(1),
|
|
release(2),
|
|
momentary(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Requested action on point (RTU will ignore if invalid)."
|
|
::= {dpsRTUv2ControlGrid 5}
|
|
|
|
|
|
|
|
dpsRTUv2AlarmGrid OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DPSrtuV2AlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Holds individual alarm point information."
|
|
::= {dpsRTUv2 5}
|
|
|
|
dpsRTUv2AlarmEntry OBJECT-TYPE
|
|
SYNTAX DPSrtuV2AlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Detailed information about a particular RTU display."
|
|
INDEX {dpsRTUv2APort, dpsRTUv2AAddress, dpsRTUv2ADisplay, dpsRTUv2APoint}
|
|
::= {dpsRTUv2AlarmGrid 1}
|
|
|
|
DPSrtuV2AlarmEntry ::= SEQUENCE { dpsRTUv2APort Integer32,
|
|
dpsRTUv2AAddress Integer32,
|
|
dpsRTUv2ADisplay Integer32,
|
|
dpsRTUv2APoint Integer32,
|
|
dpsRTUv2APntDesc DisplayString,
|
|
dpsRTUv2AState DisplayString
|
|
}
|
|
|
|
dpsRTUv2APort OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "RTU port number."
|
|
::= {dpsRTUv2AlarmEntry 1}
|
|
|
|
dpsRTUv2AAddress OBJECT-TYPE
|
|
SYNTAX Integer32 (0..9999)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "RTU_port address number."
|
|
::= {dpsRTUv2AlarmEntry 2}
|
|
|
|
dpsRTUv2ADisplay OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "RTU_port_address display number."
|
|
::= {dpsRTUv2AlarmEntry 3}
|
|
|
|
dpsRTUv2APoint OBJECT-TYPE
|
|
SYNTAX Integer32 (0..64)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "RTU_port_address_display point number."
|
|
::= {dpsRTUv2AlarmEntry 4}
|
|
|
|
dpsRTUv2APntDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "A description of this point."
|
|
::= {dpsRTUv2AlarmEntry 5}
|
|
|
|
dpsRTUv2AState OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The current state of this point."
|
|
::= {dpsRTUv2AlarmEntry 6}
|
|
|
|
|
|
--Table for accessing analog channel value
|
|
|
|
analogChannelsv2 OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF ChannelEntryv2
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Holds information on analog channels"
|
|
::= {dpsRTUv2 6}
|
|
|
|
channelEntryv2 OBJECT-TYPE
|
|
SYNTAX ChannelEntryv2
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "Information about a particular channel"
|
|
INDEX {channelNumberv2}
|
|
::= {analogChannelsv2 1}
|
|
|
|
ChannelEntryv2 ::= SEQUENCE { channelNumberv2 Integer32,
|
|
enabledv2 Integer32,
|
|
descriptionv2 DisplayString,
|
|
valuev2 DisplayString,
|
|
thresholdsv2 Integer32
|
|
}
|
|
|
|
channelNumberv2 OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Input channel number"
|
|
::= {channelEntryv2 1}
|
|
|
|
enabledv2 OBJECT-TYPE
|
|
SYNTAX INTEGER { disabled (0),
|
|
enabled (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Enable status of channel"
|
|
::= {channelEntryv2 2}
|
|
|
|
descriptionv2 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The user defined description of the channel"
|
|
::= {channelEntryv2 3}
|
|
|
|
valuev2 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The current value of the channel"
|
|
::= {channelEntryv2 4}
|
|
|
|
thresholdsv2 OBJECT-TYPE
|
|
SYNTAX INTEGER { noAlarms (0),
|
|
minorUnder (1),
|
|
minorOver (2),
|
|
majorUnder (3),
|
|
majorOver (4),
|
|
notDetected (5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Highest threshold level crossed, if MJ, MN is assumed"
|
|
::= {channelEntryv2 5}
|
|
|
|
-- TRAP definitions
|
|
|
|
tmonV2CRalarmSet NOTIFICATION-TYPE
|
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
|
STATUS current
|
|
DESCRIPTION "Generated when a critical alarm is set."
|
|
-- ::= {tmonV2XM 10}
|
|
::= {tmonXM 10}
|
|
|
|
|
|
tmonV2CRalarmClr NOTIFICATION-TYPE
|
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
|
STATUS current
|
|
DESCRIPTION "Generated when a critical alarm clears."
|
|
-- ::= {tmonV2XM 11}
|
|
::= {tmonXM 11}
|
|
|
|
tmonV2MJalarmSet NOTIFICATION-TYPE
|
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
|
STATUS current
|
|
DESCRIPTION "Generated when a major alarm is set."
|
|
-- ::= {tmonV2XM 12}
|
|
::= {tmonXM 12}
|
|
|
|
tmonV2MJalarmClr NOTIFICATION-TYPE
|
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
|
STATUS current
|
|
DESCRIPTION "Generated when a major alarm clears."
|
|
-- ::= {tmonV2XM 13}
|
|
::= {tmonXM 13}
|
|
|
|
tmonV2MNalarmSet NOTIFICATION-TYPE
|
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
|
STATUS current
|
|
DESCRIPTION "Generated when a minor alarm is set."
|
|
-- ::= {tmonV2XM 14}
|
|
::= {tmonXM 14}
|
|
|
|
tmonV2MNalarmClr NOTIFICATION-TYPE
|
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
|
STATUS current
|
|
DESCRIPTION "Generated when a minor alarm clears."
|
|
-- ::= {tmonV2XM 15}
|
|
::= {tmonXM 15}
|
|
|
|
tmonV2STalarmSet NOTIFICATION-TYPE
|
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
|
STATUS current
|
|
DESCRIPTION "Generated when a status alarm is set."
|
|
-- ::= {tmonV2XM 16}
|
|
::= {tmonXM 16}
|
|
|
|
tmonV2STalarmClr NOTIFICATION-TYPE
|
|
OBJECTS { tmonV2ASite, tmonV2ADesc, tmonV2AState, tmonV2ASeverity, tmonV2AChgDate,
|
|
tmonV2AChgTime, tmonV2AAuxDesc, tmonV2ADispDesc, tmonV2APntType,
|
|
tmonV2APort, tmonV2AAddress, tmonV2ADisplay, tmonV2APoint, tmonV2CEvent,
|
|
tmonV2AIPAddr, tmonV2ADevDesc }
|
|
STATUS current
|
|
DESCRIPTION "Generated when a status alarm clears."
|
|
-- ::= {tmonV2XM 17}
|
|
::= {tmonXM 17}
|
|
|
|
--dpsRTUv2PointSet NOTIFICATION-TYPE
|
|
-- OBJECTS { sysDescr, sysLocation, dpsRTUv2DateTime,
|
|
-- dpsRTUv2APort, dpsRTUv2AAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
|
-- STATUS current
|
|
-- DESCRIPTION "Generated when a point is set."
|
|
-- ::= {dpsRTUv2 20}
|
|
--
|
|
--dpsRTUv2PointClr NOTIFICATION-TYPE
|
|
-- OBJECTS { sysDescr, sysLocation, dpsRTUv2DateTime,
|
|
-- dpsRTUv2APort, dpsRTUv2CAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
|
-- STATUS current
|
|
-- DESCRIPTION "Generated when a point clears."
|
|
-- ::= {dpsRTUv2 21}
|
|
--
|
|
--dpsRTUv2sumPSet NOTIFICATION-TYPE
|
|
-- OBJECTS { sysDescr, sysLocation, dpsRTUv2DateTime }
|
|
-- STATUS current
|
|
-- DESCRIPTION "Generated when any point is set."
|
|
-- ::= {dpsRTUv2 101}
|
|
--
|
|
--dpsRTUv2sumPClr NOTIFICATION-TYPE
|
|
-- OBJECTS { sysDescr, sysLocation, dpsRTUv2DateTime }
|
|
-- STATUS current
|
|
-- DESCRIPTION "Generated when all points clear."
|
|
-- ::= {dpsRTUv2 102}
|
|
--
|
|
--dpsRTUv2comFailed NOTIFICATION-TYPE
|
|
-- OBJECTS { sysDescr, sysLocation, dpsRTUv2DateTime }
|
|
-- STATUS current
|
|
-- DESCRIPTION "Generated when polled unit fails to respond."
|
|
-- ::= {dpsRTUv2 103}
|
|
--
|
|
--dpsRTUv2comRestored NOTIFICATION-TYPE
|
|
-- OBJECTS { sysDescr, sysLocation, dpsRTUv2DateTime }
|
|
-- STATUS current
|
|
-- DESCRIPTION "Generated when failed unit resumes responding."
|
|
-- ::= {dpsRTUv2 104}
|
|
--
|
|
-- **************************************************************************
|
|
-- Granular TRAP definitions
|
|
--
|
|
-- The following section supports granular trapping available on selected
|
|
-- DPS remote telemetry units. This software selectable facility changes the
|
|
-- trap sent by a remote so equipped. The standard trap identifies a SET or
|
|
-- CLR event in the trap ID and binds variables identifying the specific
|
|
-- remote point associated with the event. A granular trap identifies a SET
|
|
-- or CLR event and the specific point associated with the event all in the
|
|
-- trap ID. This is accomplished by mapping all SET event/points into the
|
|
-- trap ID range 10001-19999 and all CLR event/points into the trap ID range
|
|
-- 20001-29999.
|
|
-- If the unit manages multiple displays, the displays are mapped
|
|
-- sequentially with each display occupying a 64 point range. For example, a
|
|
-- standalone standard or timestamp KDA which manages two displays, reports
|
|
-- SET event/points in the first display (discrete alarm points) in the range
|
|
-- 10001-10064. The CLR event/points for the same display would be reported
|
|
-- in the range 20001-20064. The second display (controls & housekeeping
|
|
-- alarm points) would have its SET event/points reported in the range 10065-
|
|
-- 10128 and its CLR event/points reported in the range 20065-20128.
|
|
-- SET and CLR definitions for the first 64 points have been included and
|
|
-- can be used as is for driving most SNMP manager mechanisms designed to key
|
|
-- on the trap ID for distinguishing and managing events. Additional events
|
|
-- can be added simply by editing the following trap definitions prior to
|
|
-- compiling this file into your SNMP manager. We recommend managing the SET
|
|
-- and CLR event definitions for a specific point as a single unit and using
|
|
-- the following simple rules:
|
|
-- + Adjust the numeric portion of the label preceeding NOTIFICATION-TYPE.
|
|
-- + Adjust the numeric reference in the DESCRIPTION text.
|
|
-- + Adjust the number on the last line of the definition.
|
|
--
|
|
-- Using these rules a definition for the 65th point would be:
|
|
--
|
|
-- dpsRTUv2p0065Set NOTIFICATION-TYPE
|
|
-- ENTERPRISE dpsRTUv2
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUv2DateTime,
|
|
-- dpsRTUv2APort, dpsRTUv2CAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
|
-- DESCRIPTION "Generated when granular point 65 is set."
|
|
-- ::= 10065
|
|
--
|
|
-- dpsRTUv2p0065Clr NOTIFICATION-TYPE
|
|
-- ENTERPRISE dpsRTUv2
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUv2DateTime,
|
|
-- dpsRTUv2APort, dpsRTUv2CAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
|
-- DESCRIPTION "Generated when granular point 65 clears."
|
|
-- ::= 20065
|
|
--
|
|
-- This editing can can be accomplished quite easily using a plain ASCII
|
|
-- file editor. The repetitive structure of the definitions also makes for
|
|
-- rapid scripted or programmed generation if any such tools are available.
|
|
-- A compressed file containing event/point definitions for 144 displays is
|
|
-- available (DPS_G36.zip 150K) which uncompressed (DPS_G36.mib 6.2M) can be
|
|
-- used for cut-and-paste editing if desired.
|
|
-- The definitions can be further customized if desired by similar editing
|
|
-- prior to compiling carefully observing the following conventions:
|
|
-- + The label preceeding the NOTIFICATION-TYPE designator can be edited with some
|
|
-- freedom but the label must be utterly unique among all trap definitions.
|
|
-- + The ENTERPRISE and VARIABLES sections must not be changed.
|
|
-- + The DESCRIPTION can be edited with complete freedom and is typically
|
|
-- ignored within the context of standard SNMP manager trap handling. The
|
|
-- quote mark before and after the text of the description are required.
|
|
-- + The number on the last line of the definition is the actual trap ID
|
|
-- defined and must also be utterly unique.
|
|
--
|
|
-- For example:
|
|
--
|
|
-- dpsRTUv2p0001Set NOTIFICATION-TYPE
|
|
-- ENTERPRISE dpsRTUv2
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUv2DateTime,
|
|
-- dpsRTUv2APort, dpsRTUv2CAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
|
-- DESCRIPTION "Generated when granular point 1 is set."
|
|
-- ::= 10001
|
|
--
|
|
-- dpsRTUv2p0001Clr NOTIFICATION-TYPE
|
|
-- ENTERPRISE dpsRTUv2
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUv2DateTime,
|
|
-- dpsRTUv2APort, dpsRTUv2CAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
|
-- DESCRIPTION "Generated when granular point 1 clears."
|
|
-- ::= 20001
|
|
--
|
|
-- Could be customized as:
|
|
--
|
|
-- dpsRTUv2FireAlarm NOTIFICATION-TYPE
|
|
-- ENTERPRISE dpsRTUv2
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUv2DateTime,
|
|
-- dpsRTUv2APort, dpsRTUv2CAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
|
-- DESCRIPTION "Generated when smoke detector activates."
|
|
-- ::= 10001
|
|
--
|
|
-- dpsRTUv2FireOut NOTIFICATION-TYPE
|
|
-- ENTERPRISE dpsRTUv2
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUv2DateTime,
|
|
-- dpsRTUv2APort, dpsRTUv2CAddress, dpsRTUv2ADisplay, dpsRTUv2APoint,
|
|
-- dpsRTUv2APntDesc, dpsRTUv2AState }
|
|
-- DESCRIPTION "Generated when smoke detector deactivates."
|
|
-- ::= 20001
|
|
-- **************************************************************************
|
|
|
|
|
|
END
|