EATON-ATS2-MIB DEFINITIONS ::= BEGIN
IMPORTS
OBJECT-TYPE, NOTIFICATION-TYPE, MODULE-IDENTITY,
Counter32
FROM SNMPv2-SMI
TEXTUAL-CONVENTION, DisplayString
FROM SNMPv2-TC
sts
FROM EATON-OIDS;
ats2 MODULE-IDENTITY
LAST-UPDATED "201407311200Z"
ORGANIZATION
"Eaton Corporation"
CONTACT-INFO
"www.eaton.com"
DESCRIPTION
"The MIB module for Eaton ATS (Automatic Transfer Switch)."
REVISION "201407311200Z"
DESCRIPTION
"Initial release."
::= { sts 2 }
-- EatonSTS-MIB { iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) eaton(534) sts(10) ats2(2) }
ats2Ident OBJECT IDENTIFIER ::= { ats2 1 }
ats2Measure OBJECT IDENTIFIER ::= { ats2 2 }
ats2Status OBJECT IDENTIFIER ::= { ats2 3 }
ats2Config OBJECT IDENTIFIER ::= { ats2 4 }
ats2Environment OBJECT IDENTIFIER ::= {ats2 5}
ats2Traps OBJECT IDENTIFIER ::= { ats2 10 }
-- Textual Conventions
UnixTimeStamp ::= TEXTUAL-CONVENTION
DISPLAY-HINT "dddddddddd"
STATUS current
DESCRIPTION
"Unix time stamp. Measured in seconds since January 1, 1970."
SYNTAX Counter32
--
-- Identification group
ats2IdentManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..16))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The manufacturer name."
::= { ats2Ident 1 }
ats2IdentModel OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..32))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device model name."
::= { ats2Ident 2 }
ats2IdentFWVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..16))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device F/W version."
::= { ats2Ident 3 }
ats2IdentRelease OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..16))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The released date."
::= { ats2Ident 4 }
ats2IdentSerialNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..20))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device serial number"
::= { ats2Ident 5 }
ats2IdentPartNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..20))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device part number"
::= { ats2Ident 6 }
ats2IdentAgentVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..20))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Communication Card F/W version"
::= { ats2Ident 7 }
--
-- Mesurement group
ats2Input OBJECT IDENTIFIER ::= { ats2Measure 1 }
ats2InputDephasing OBJECT-TYPE
SYNTAX INTEGER
UNITS "degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The dephasing in between Source 1 and Source 2."
::= { ats2Input 1 }
ats2InputTable OBJECT-TYPE
SYNTAX SEQUENCE OF ATSInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The table of input information."
::= { ats2Measure 2 }
ats2Output OBJECT IDENTIFIER ::= { ats2Measure 3 }
ats2OperationMode OBJECT-TYPE
SYNTAX INTEGER {
initialization(1),
diagnosis(2),
off(3),
source1(4),
source2(5),
safe(6),
fault(7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The operation mode."
::= { ats2Measure 4 }
--
-- Mesurement / Input group
ats2InputEntry OBJECT-TYPE
SYNTAX ATSInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input information of each source input:
<node>.1 source1
<node>.2 source2"
INDEX { ats2InputIndex }
::= { ats2InputTable 1 }
ATSInputEntry ::= SEQUENCE {
ats2InputIndex INTEGER,
ats2InputVoltage INTEGER,
ats2InputFrequency INTEGER
}
ats2InputIndex OBJECT-TYPE
SYNTAX INTEGER {
source1(1),
source2(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index to input."
::= { ats2InputEntry 1 }
ats2InputVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input voltage in front of relay. Units are 0.1 V."
::= { ats2InputEntry 2 }
ats2InputFrequency OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 Hz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input frequency. Units are 0.1 Hz."
::= { ats2InputEntry 3 }
--
-- Mesurement / Output group
ats2OutputVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output voltage. Units are 0.1 V."
::= { ats2Output 1 }
ats2OutputCurrent OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.1 A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output current. Units are 0.1 A."
::= { ats2Output 2 }
--
-- Status group
ats2InputStatus OBJECT IDENTIFIER ::= { ats2Status 1 }
ats2InputStatusDephasing OBJECT-TYPE
SYNTAX INTEGER {
normal (1),
outOfRange (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The dephasing status in between Source 1 and Source 2."
::= { ats2InputStatus 1 }
ats2InputStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF ATSInputStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The table of input status."
::= { ats2Status 2 }
ats2OutputStatus OBJECT IDENTIFIER ::= { ats2Status 3 }
--
-- Status / Input Flow group
ats2InputStatusEntry OBJECT-TYPE
SYNTAX ATSInputStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input flow status:
<node>.1 source1
<node>.2 source2"
INDEX { ats2InputStatusIndex }
::= { ats2InputStatusTable 1 }
ATSInputStatusEntry ::= SEQUENCE {
ats2InputStatusIndex INTEGER,
ats2InputStatusFrequency INTEGER,
ats2InputStatusGood INTEGER,
ats2InputStatusInternalFailure INTEGER,
ats2InputStatusVoltage INTEGER,
ats2InputStatusUsed INTEGER
}
ats2InputStatusIndex OBJECT-TYPE
SYNTAX INTEGER {
source1(1),
source2(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index of input entry."
::= { ats2InputStatusEntry 1 }
ats2InputStatusFrequency OBJECT-TYPE
SYNTAX INTEGER {
good (1),
outOfRange (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of input frequency."
::= { ats2InputStatusEntry 2 }
ats2InputStatusGood OBJECT-TYPE
SYNTAX INTEGER {
voltageOrFreqOutofRange(1),
voltageAndFreqNormalRange(2),
voltageDeratedRangeAndFreqNormalRange(3),
voltageAndFreqNormalRangeWaveformNok(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The summarized status of input AC flow."
::= { ats2InputStatusEntry 3 }
ats2InputStatusInternalFailure OBJECT-TYPE
SYNTAX INTEGER {
good (1),
internalFailure (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The internal fault status of input."
::= { ats2InputStatusEntry 4 }
ats2InputStatusVoltage OBJECT-TYPE
SYNTAX INTEGER {
normalRange(1),
deratedRange(2),
outofRange(3),
missing(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of input voltage."
::= { ats2InputStatusEntry 5 }
ats2InputStatusUsed OBJECT-TYPE
SYNTAX INTEGER {
notPoweringLoad(1),
poweringLoad(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of input relay."
::= { ats2InputStatusEntry 6 }
--
-- Status / Failure group
ats2StatusInternalFailure OBJECT-TYPE
SYNTAX INTEGER {
good (1),
internalFailure (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Output fault."
::= { ats2OutputStatus 1 }
ats2StatusOutput OBJECT-TYPE
SYNTAX INTEGER {
outputNotPowered(1),
outputPowered(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Output powered status."
::= { ats2OutputStatus 2 }
ats2StatusOverload OBJECT-TYPE
SYNTAX INTEGER {
noOverload(1),
warningOverload(2),
criticalOverload(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output overload status."
::= { ats2OutputStatus 3 }
ats2StatusOverTemperature OBJECT-TYPE
SYNTAX INTEGER {
noOverTemperature(1),
overTemperature(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The over temperature status."
::= { ats2OutputStatus 4 }
ats2StatusShortCircuit OBJECT-TYPE
SYNTAX INTEGER {
noShortCircuit(1),
shortCircuit(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Short circuit status."
::= { ats2OutputStatus 5 }
ats2StatusCommunicationLost OBJECT-TYPE
SYNTAX INTEGER {
good (1),
communicationLost (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Communication failure status."
::= { ats2OutputStatus 6 }
ats2StatusConfigurationFailure OBJECT-TYPE
SYNTAX INTEGER {
good (1),
configurationFailure (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Configuration failure status."
::= { ats2OutputStatus 7 }
--
-- Configuration group
ats2ConfigTime OBJECT IDENTIFIER ::= { ats2Config 1 }
ats2ConfigInputVoltageRating OBJECT-TYPE
SYNTAX INTEGER
UNITS "1 V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input voltage rating. Unit is 1 V."
::= { ats2Config 2 }
ats2ConfigInputFrequencyRating OBJECT-TYPE
SYNTAX INTEGER
UNITS "Hz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input frequency rating. Unit is 1 Hz."
::= { ats2Config 3 }
ats2ConfigOutputVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "1 V"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The output voltage config. Unit is 1 V."
::= { ats2Config 4 }
ats2ConfigPreferred OBJECT-TYPE
SYNTAX INTEGER {
source1(1),
source2(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The preferred source."
::= { ats2Config 5 }
ats2ConfigSensitivity OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
highSensitivity (2),
lowSensitivity (3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The AC Blackout Sensitivity."
::= { ats2Config 6 }
ats2ConfigTransferMode OBJECT-TYPE
SYNTAX INTEGER {
standard(1),
gap(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"behavior configuration when transfering from one source to other source not synchronized."
::= { ats2Config 7 }
ats2ConfigTransferTest OBJECT-TYPE
SYNTAX INTEGER {
doneAndPassed (1),
doneAndWarning (2),
doneAndError (3),
aborted (4),
inProgress (5),
noTestInitiated (6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of transfer test."
::= { ats2Config 8 }
ats2ConfigBrownoutLow OBJECT-TYPE
SYNTAX INTEGER
UNITS "1 V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Setting of input brownout low voltage. Unit is 1 V."
::= { ats2Config 9 }
ats2ConfigBrownoutLowDerated OBJECT-TYPE
SYNTAX INTEGER
UNITS "1 V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Setting of input brownout low derated voltage. Unit is 1 V."
::= { ats2Config 10 }
ats2ConfigBrownoutHigh OBJECT-TYPE
SYNTAX INTEGER
UNITS "1 V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Setting of input brownout high voltage. Unit is 1 V."
::= { ats2Config 11 }
ats2ConfigHysteresisVoltage OBJECT-TYPE
SYNTAX INTEGER
UNITS "1 V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Hysteresis between loss point and comeback point. Unit is 1 V."
::= { ats2Config 12 }
--
-- Configuration / Time group
ats2ConfigTimeRTC OBJECT-TYPE
SYNTAX UnixTimeStamp
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Clock value. This could be from either a real-time clock (in which case
it is likely writeable) or from a time server via NTP (probably read-only).
(since 1/1/1970 at 1:00:00)."
::= { ats2ConfigTime 1 }
ats2ConfigTimeTextDate OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..10))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present date in MM/DD/YYYY text format."
::= { ats2ConfigTime 2 }
ats2ConfigTimeTextTime OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..8))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present time in hh:mm:ss text format."
::= { ats2ConfigTime 3 }
--
-- EMP group
--
-- The objects defined in this group are provided by the EMP.
-- They are Temperature and Humidity readings and alarming limits,
-- and the (two) contacts readings and setup information.
-- These objects are related to the separate EMP probe that can be connected to
-- the communication card.
--
-- Notices/Traps: traps related to the probe are
-- ats2tdRemoteTempBad
-- ats2tdRemoteHumidityBad
-- ats2tdContactActiveNotice
-- ats2tdContactInactiveNotice
ats2EnvRemoteTemp OBJECT-TYPE
SYNTAX INTEGER (-100..200)
UNITS "degrees Centigrade"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The reading of an EMP's temperature sensor."
::= { ats2Environment 1 }
ats2EnvRemoteHumidity OBJECT-TYPE
SYNTAX INTEGER (0..100)
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The reading of an EMP's humidity sensor."
::= { ats2Environment 2 }
--
-- The Environmental Contact Sensing Table
-- Contains the table for monitoring all contacts (digital
-- inputs, normally 2 in an EMP).
--
ats2EnvNumContacts OBJECT-TYPE
SYNTAX INTEGER (1..1024)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of Contacts in the ats2ContactSenseTable.
This object indicates the number of rows in the
ats2ContactSenseTable."
::= { ats2Environment 3 }
ats2ContactSenseTable OBJECT-TYPE
SYNTAX SEQUENCE OF Ats2ContactsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of Contact Sensing table entries.
The number of entries is given by the value of
ats2EnvNumContacts."
::= { ats2Environment 4 }
ats2ContactsTableEntry OBJECT-TYPE
SYNTAX Ats2ContactsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable
to a particular Contact input."
INDEX { ats2ContactIndex }
::= { ats2ContactSenseTable 1 }
Ats2ContactsTableEntry ::= SEQUENCE {
ats2ContactIndex INTEGER,
ats2ContactType INTEGER,
ats2ContactState INTEGER,
ats2ContactDescr DisplayString
}
ats2ContactIndex OBJECT-TYPE
SYNTAX INTEGER (1..1024)
MAX-ACCESS read-only -- actually not-accessible
STATUS current
DESCRIPTION
"The Contact identifier; identical to the Contact Number.
This object is not-accessible to MIB browsers, but had to be changed to
read-only to satisfy SMIv2 syntax checkers if it is included in traps."
::= { ats2ContactsTableEntry 1 }
ats2ContactType OBJECT-TYPE
SYNTAX INTEGER {
normallyOpen(1), -- or Input Normally High
normallyClosed(2), -- or Input Normally Low
anyChange(3), -- No normal Open/Closed state
notUsed(4) -- Contact not in service or not alarming
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The normal state for this contact. The 'other' (not 'Normally')
state is the Active state for generating the ats2tdContactActiveNotice
trap. If anyChange(3) is selected, then this trap is sent
any time the contact changes to either Open or Closed.
No traps are sent if the Contact is set to notUsed(4).
In many cases, the configuration for Contacts may be done by other
means, so this object may be read-only."
::= { ats2ContactsTableEntry 2 }
ats2ContactState OBJECT-TYPE
SYNTAX INTEGER {
open(1),
closed(2),
openWithNotice(3),
closedWithNotice(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the Contact input;
the value is based on the open/closed input state
and the setting for ats2ContactType.
When entering the openWithNotice(3) and closedWithNotice(4)
states, no entries added to the ats2AlarmTable, but
the ats2tdContactActiveNotice trap is sent."
::= { ats2ContactsTableEntry 3 }
ats2ContactDescr OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A label identifying the Contact. This object should be
set by the administrator."
::= { ats2ContactsTableEntry 4 }
ats2EnvRemoteTempLowerLimit OBJECT-TYPE
SYNTAX INTEGER (-100..200)
UNITS "degrees Centigrade"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The Lower Limit of the EMP temperature; if ats2EnvRemoteTemp
falls below this value, the ats2RemoteTempBad alarm will occur."
::= { ats2Environment 5 }
ats2EnvRemoteTempUpperLimit OBJECT-TYPE
SYNTAX INTEGER (-100..200)
UNITS "degrees Centigrade"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The Upper Limit of the EMP temperature; if ats2EnvRemoteTemp
rises above this value, the ats2RemoteTempBad alarm will occur.
This value should be greater than ats2EnvRemoteTempLowerLimit."
::= { ats2Environment 6 }
ats2EnvRemoteHumidityLowerLimit OBJECT-TYPE
SYNTAX INTEGER (0..100)
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The Lower Limit of the EMP humidity reading; if ats2EnvRemoteHumidity
falls below this value, the ats2RemoteHumidityBad alarm will occur."
::= { ats2Environment 7 }
ats2EnvRemoteHumidityUpperLimit OBJECT-TYPE
SYNTAX INTEGER (0..100)
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The Upper Limit of the EMP humidity reading; if ats2EnvRemoteHumidity
rises above this value, the ats2RemoteHumidityBad alarm will occur.
This value should be greater than ats2EnvRemoteHumidityLowerLimit."
::= { ats2Environment 8 }
--
-- Traps / Notifications for the EMP in the PowerMIB style
-- The special EMP traps are not normally provided by Power Xpert Gateways (which use
-- the PXG-style traps instead) but could be provided by PowerMIB implementations
-- These are found in the PowerMIB:
-- ats2tdContactActiveNotice
-- ats2tdContactInactiveNotice
-- ats2tdRemoteTempBad
-- ats2tdRemoteHumidityBad
--
-- Traps group
ats2TrapCommunicationLost NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Communication with the ATS failed."
::= { ats2Traps 1 }
ats2TrapCommunicationRecovered NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Communication with the ATS recovered."
::= { ats2Traps 2 }
ats2TrapOutputPowered NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The ATS powers the load."
::= { ats2Traps 3 }
ats2TrapOutputNotPowered NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The ATS does not powers the load."
::= { ats2Traps 4 }
ats2TrapOverload NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The ATS has sensed a critical overload."
::= { ats2Traps 5 }
ats2TrapNoOverLoad NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The critical overload disappeared."
::= { ats2Traps 6 }
ats2TrapInternalFailure NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The ATS has an internal failure (sum of all HW internal failure)."
::= { ats2Traps 7 }
ats2TrapNoInternalFailure NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The ATS internal failure disappeared."
::= { ats2Traps 8 }
ats2TrapSource1Normal NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Source 1 returns to normal."
::= { ats2Traps 9 }
ats2TrapSource1OutOfRange NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Source 1 out of range."
::= { ats2Traps 10 }
ats2TrapSource2Normal NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Source 2 returns to normal."
::= { ats2Traps 11 }
ats2TrapSource2OutOfRange NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Source 2 out of range."
::= { ats2Traps 12 }
ats2TrapSourceDesynchronized NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Source 1 and Source 2 phase are desynchronized."
::= { ats2Traps 13 }
ats2TrapSourceSynchronized NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Source 1 and Source 2 phase are synchronized."
::= { ats2Traps 14 }
ats2TrapOutputPoweredBySource1 NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Source 1 powers the output."
::= { ats2Traps 15 }
ats2TrapOutputPoweredBySource2 NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Source 2 powers the output."
::= { ats2Traps 16 }
-- Added to provide additional information with the RemoteTemp and RemoteHumidity
ats2TrapRemoteTempLow NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The remote temperature, ats2EnvRemoteTemp, has fallen below
the set lower limit, ats2EnvRemoteTempLowerLimit."
--#SEVERITY MAJOR
::= { ats2Traps 20 }
ats2TrapRemoteTempHigh NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The remote temperature, ats2EnvRemoteTemp, has risen above
the set upper limit, xupsEnvRemoteTempUpperLimit."
--#SEVERITY MAJOR
::= { ats2Traps 21 }
ats2TrapRemoteTempNormal NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The remote temperature, ats2EnvRemoteTemp, is inside the interval
defined by the lower limit and the upper limit."
--#SEVERITY MAJOR
::= { ats2Traps 22 }
ats2TrapRemoteHumidityLow NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The remote humidity, ats2EnvRemoteHumidity, has fallen below
the set lower limit, ats2EnvRemoteHumidityLowerLimit."
--#SEVERITY MAJOR
::= { ats2Traps 23 }
ats2TrapRemoteHumidityHigh NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The remote humidity, ats2EnvRemoteHumidity, has risen above
the set upper limit, ats2EnvRemoteHumidityUpperLimit."
--#SEVERITY MAJOR
::= { ats2Traps 24 }
ats2TrapRemoteHumidityNormal NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The remote humidity, ats2EnvRemoteHumidity, is inside the interval
defined by the lower limit and the upper limit."
--#SEVERITY MAJOR
::= { ats2Traps 25 }
ats2Contact1ActiveNotice NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The Contact 1 is in its Active state.
The following are the situations that generate this trap:
For ats2ContactType: and ats2ContactState:
normallyOpen(1) and closedWithNotice(4)
normallyClosed(2) and openWithNotice(3)
anyChange(3) and openWithNotice(3) or closedWithNotice(4)"
--#SEVERITY MAJOR
::= { ats2Traps 26 }
ats2Contact1InactiveNotice NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The Contact 1 has changed to its Inactive state."
--#SEVERITY INFORMATIONAL
::= { ats2Traps 27 }
ats2Contact2ActiveNotice NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The Contact 2 is in its Active state.
The following are the situations that generate this trap:
For ats2ContactType: and ats2ContactState:
normallyOpen(1) and closedWithNotice(4)
normallyClosed(2) and openWithNotice(3)
anyChange(3) and openWithNotice(3) or closedWithNotice(4)"
--#SEVERITY MAJOR
::= { ats2Traps 28 }
ats2Contact2InactiveNotice NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"The Contact 2 has changed to its Inactive state."
--#SEVERITY INFORMATIONAL
::= { ats2Traps 29 }
ats2TestTrap NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Sent whenever the trap test feature is used by the communication card."
--#SEVERITY INFORMATIONAL
::= { ats2Traps 40 }
END