EATON-EMP-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE, Integer32
|
|
FROM SNMPv2-SMI
|
|
DisplayString
|
|
FROM SNMPv2-TC
|
|
MODULE-COMPLIANCE, OBJECT-GROUP
|
|
FROM SNMPv2-CONF
|
|
xupsEnvironment
|
|
FROM EATON-OIDS;
|
|
|
|
eatonEMPMIB MODULE-IDENTITY
|
|
LAST-UPDATED "200703120000Z"
|
|
ORGANIZATION "Eaton Corporation"
|
|
CONTACT-INFO
|
|
"Eaton Power Quality Technical Support (PQTS) group
|
|
www.eaton.com/powerxpert
|
|
Technical Resource Center phone numbers
|
|
United States: 1.800.843.9433 or 919.870.3028
|
|
Canada: 1.800.461.9166 ext. 260
|
|
All other countries: Call your local service representative."
|
|
DESCRIPTION
|
|
"The MIB module for Eaton Environment Monitoring Probes (EMP).
|
|
The elements of this MIB have been extracted from the
|
|
Eaton PowerMIB and placed in this separate MIB file for convenience.
|
|
|
|
Copyright (C) Eaton Corporation (2007)."
|
|
|
|
REVISION "200703120000Z"
|
|
DESCRIPTION
|
|
"Initial Version of eatonEMPMIB."
|
|
|
|
::= { xupsEnvironment 0 }
|
|
|
|
-- ::= { enterprises 534 8 1 }
|
|
-- eatonEMPMIB { iso org(3) dod(6) internet(1) private(4)
|
|
-- enterprises(1) eaton(534) xupsMIB(1) xupsEnvironment(6) (0) }
|
|
|
|
|
|
--
|
|
-- EMP group
|
|
--
|
|
-- The objects defined in this group are provided by the EMP.
|
|
-- They are Temperature and Humidity readings and alarming limits,
|
|
-- and the (two) contacts readings and setup information.
|
|
-- These objects are considered "Remote" since the EMP is a
|
|
-- separate probe from the Eaton device or gateway it is connected to.
|
|
--
|
|
-- Notices/Traps: two different types of traps may be sent in response
|
|
-- to EMP changes, depending upon the type of device the EMP is attached to.
|
|
-- If connected to a UPS device, normally the PowerMIB traps are sent:
|
|
-- xupstdRemoteTempBad
|
|
-- xupstdRemoteHumidityBad
|
|
-- xupstdContactActiveNotice
|
|
-- xupstdContactInactiveNotice
|
|
-- If connected to a Toolkit-enabled PowerXpert Gateway, Toolkit traps are sent:
|
|
-- powerChainCriticalAlarm
|
|
-- powerChainCautionaryAlarm
|
|
-- powerChainAlarmAcknowledged
|
|
-- powerChainAlarmCleared
|
|
-- Both sets of traps are defined in their respective MIB files.
|
|
|
|
|
|
xupsEnvRemoteTemp OBJECT-TYPE
|
|
SYNTAX Integer32 (-100..200)
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The reading of an EMP's temperature sensor."
|
|
::= { xupsEnvironment 5 }
|
|
|
|
xupsEnvRemoteHumidity OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The reading of an EMP's humidity sensor."
|
|
::= { xupsEnvironment 6 }
|
|
|
|
--
|
|
-- The Environmental Contact Sensing Table
|
|
-- Contains the table for monitoring all contacts (digital
|
|
-- inputs, normally 2 in an EMP).
|
|
--
|
|
|
|
xupsEnvNumContacts OBJECT-TYPE
|
|
SYNTAX Integer32 (1..1024)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of Contacts in the xupsContactSenseTable.
|
|
This object indicates the number of rows in the
|
|
xupsContactSenseTable."
|
|
::= { xupsEnvironment 7 }
|
|
|
|
xupsContactSenseTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF XupsContactsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of Contact Sensing table entries.
|
|
The number of entries is given by the value of
|
|
xupsEnvNumContacts."
|
|
::= { xupsEnvironment 8 }
|
|
|
|
xupsContactsTableEntry OBJECT-TYPE
|
|
SYNTAX XupsContactsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable
|
|
to a particular Contact input."
|
|
INDEX { xupsContactIndex }
|
|
::= { xupsContactSenseTable 1 }
|
|
|
|
XupsContactsTableEntry ::= SEQUENCE {
|
|
xupsContactIndex Integer32,
|
|
xupsContactType INTEGER,
|
|
xupsContactState INTEGER,
|
|
xupsContactDescr DisplayString
|
|
}
|
|
|
|
xupsContactIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..1024)
|
|
MAX-ACCESS read-only -- actually not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Contact identifier; identical to the Contact Number.
|
|
This object is not-accessible to MIB browsers, but had to be changed to
|
|
read-only to satisfy SMIv2 syntax checkers if it is included in traps."
|
|
::= { xupsContactsTableEntry 1 }
|
|
|
|
xupsContactType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normallyOpen(1), -- or Input Normally High
|
|
normallyClosed(2), -- or Input Normally Low
|
|
anyChange(3), -- No normal Open/Closed state
|
|
notUsed(4) -- Contact not in service or not alarming
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The normal state for this contact. The 'other' (not 'Normally')
|
|
state is the Active state for generating the xupstdContactActiveNotice
|
|
trap. If anyChange(3) is selected, then this trap is sent
|
|
any time the contact changes to either Open or Closed.
|
|
No traps are sent if the Contact is set to notUsed(4).
|
|
In many cases, the configuration for Contacts may be done by other
|
|
means, so this object may be read-only."
|
|
::= { xupsContactsTableEntry 2 }
|
|
|
|
xupsContactState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
open(1),
|
|
closed(2),
|
|
openWithNotice(3),
|
|
closedWithNotice(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current state of the Contact input;
|
|
the value is based on the open/closed input state
|
|
and the setting for xupsContactType.
|
|
When entering the openWithNotice(3) and closedWithNotice(4)
|
|
states, no entries added to the xupsAlarmTable, but
|
|
the xupstdContactActiveNotice trap is sent."
|
|
::= { xupsContactsTableEntry 3 }
|
|
|
|
xupsContactDescr OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A label identifying the Contact. This object should be
|
|
set by the administrator."
|
|
::= { xupsContactsTableEntry 4 }
|
|
|
|
xupsEnvRemoteTempLowerLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (-100..200)
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Lower Limit of the EMP temperature; if xupsEnvRemoteTemp
|
|
falls below this value, the xupsRemoteTempBad alarm will occur."
|
|
::= { xupsEnvironment 9 }
|
|
|
|
xupsEnvRemoteTempUpperLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (-100..200)
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Upper Limit of the EMP temperature; if xupsEnvRemoteTemp
|
|
rises above this value, the xupsRemoteTempBad alarm will occur.
|
|
This value should be greater than xupsEnvRemoteTempLowerLimit."
|
|
::= { xupsEnvironment 10 }
|
|
|
|
xupsEnvRemoteHumidityLowerLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Lower Limit of the EMP humidity reading; if xupsEnvRemoteHumidity
|
|
falls below this value, the xupsRemoteHumidityBad alarm will occur."
|
|
::= { xupsEnvironment 11 }
|
|
|
|
xupsEnvRemoteHumidityUpperLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Upper Limit of the EMP humidity reading; if xupsEnvRemoteHumidity
|
|
rises above this value, the xupsRemoteHumidityBad alarm will occur.
|
|
This value should be greater than xupsEnvRemoteHumidityLowerLimit."
|
|
::= { xupsEnvironment 12 }
|
|
|
|
|
|
--
|
|
-- Traps / Notifications for the EMP in the PowerMIB style
|
|
-- The special EMP traps are not normally provided by Power Xpert Gateways (which use
|
|
-- the PXG-style traps instead) but could be provided by PowerMIB implementations
|
|
-- These are found in the PowerMIB:
|
|
-- xupstdContactActiveNotice
|
|
-- xupstdContactInactiveNotice
|
|
-- xupstdRemoteTempBad
|
|
-- xupstdRemoteHumidityBad
|
|
|
|
|
|
--
|
|
-- Conformance-related definitions
|
|
--
|
|
eatonEMPConformance OBJECT IDENTIFIER ::= { eatonEMPMIB 2 }
|
|
|
|
eatonEMPGroup OBJECT-GROUP
|
|
OBJECTS { xupsEnvRemoteTemp, xupsEnvRemoteHumidity,
|
|
xupsEnvRemoteTempLowerLimit, xupsEnvRemoteTempUpperLimit,
|
|
xupsEnvRemoteHumidityLowerLimit, xupsEnvRemoteHumidityUpperLimit }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The EMP scalar objects."
|
|
::= { eatonEMPConformance 1 }
|
|
|
|
eatonEMPTableGroup OBJECT-GROUP
|
|
OBJECTS { xupsEnvNumContacts, xupsContactIndex, xupsContactType,
|
|
xupsContactState, xupsContactDescr }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The EMP Contacts Table objects."
|
|
::= { eatonEMPConformance 2 }
|
|
|
|
|
|
eatonEMPSimpleCompliance MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The compliance statement for a normal EMP."
|
|
MODULE -- this module
|
|
MANDATORY-GROUPS { eatonEMPGroup, eatonEMPTableGroup }
|
|
::= { eatonEMPConformance 4 }
|
|
|
|
|
|
|
|
|
|
|
|
END
|
|
|