3232 lines
82 KiB
Plaintext
3232 lines
82 KiB
Plaintext
|
|
EATON-EPDU-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
OBJECT-TYPE, NOTIFICATION-TYPE, MODULE-IDENTITY,
|
|
Counter32, Unsigned32, Integer32, enterprises
|
|
FROM SNMPv2-SMI
|
|
NOTIFICATION-GROUP, OBJECT-GROUP, MODULE-COMPLIANCE
|
|
FROM SNMPv2-CONF
|
|
TEXTUAL-CONVENTION, DateAndTime, DisplayString
|
|
FROM SNMPv2-TC
|
|
pduAgent
|
|
FROM EATON-OIDS;
|
|
|
|
-- The 3 assignments below are redundant with the one declared in the import file EATON-OIDS.txt
|
|
-- because of the compatibility with some SNMP host software that do not support manufacturer import files.
|
|
-- Take care not to diverge from the import file.
|
|
eaton OBJECT IDENTIFIER ::= { enterprises 534 }
|
|
products OBJECT IDENTIFIER ::= { eaton 6 }
|
|
pduAgent OBJECT IDENTIFIER ::= { products 6 }
|
|
|
|
eatonEpdu MODULE-IDENTITY
|
|
LAST-UPDATED "201805301500Z"
|
|
ORGANIZATION
|
|
"Eaton Corporation"
|
|
CONTACT-INFO
|
|
"www.eaton.com/epdu"
|
|
DESCRIPTION
|
|
"The MIB module for Eaton ePDUs (Enclosure Power Distribution Units)."
|
|
|
|
REVISION "201805301500Z"
|
|
DESCRIPTION
|
|
"- Add information about architecture of the ePDU.
|
|
- Add outlet automatic shutoff."
|
|
|
|
REVISION "201709111200Z"
|
|
DESCRIPTION
|
|
"- Add physical name for input, outlet and gang.
|
|
- Add friendly name for input.
|
|
- Add input identification for outlet.
|
|
- Add the nominal power for ePDU input.
|
|
- Add a new outlet type sdg300 (31)."
|
|
|
|
REVISION "201704201200Z"
|
|
DESCRIPTION
|
|
"Add color codes for each input and group. Color codes are decimal values."
|
|
|
|
REVISION "201502231200Z"
|
|
DESCRIPTION
|
|
"Fix compatibility with some SNMP host software by adding some assignments."
|
|
|
|
REVISION "201409291200Z"
|
|
DESCRIPTION
|
|
"Added outletControlSwitchable and outletControlShutoffDelay object."
|
|
|
|
REVISION "201312181200Z"
|
|
DESCRIPTION
|
|
"Added notifyStrappingStatus and strappingStatus object."
|
|
|
|
REVISION "201309021200Z"
|
|
DESCRIPTION
|
|
"- Add values for commInterface : ftp (4), xml (5)"
|
|
|
|
REVISION "201305291200Z"
|
|
DESCRIPTION
|
|
"- Edited values for outletType: removed nema51520(21); added nemaL715(29), rf203p277 (30)"
|
|
|
|
REVISION "201302211200Z"
|
|
DESCRIPTION
|
|
"- Added unit objects : unitType.
|
|
- Added input objects : inputCurrentCrestFactor, inputCurrentPercentLoad, inputPowerFactor, inputVAR, inputPlugType.
|
|
- Added gang objects : groupCurrentCrestFactor, groupCurrentPercentLoad, groupPowerFactor, groupVAR.
|
|
- Added outlet objects : outletCurrentCrestFactor, outletCurrentPercentLoad, outletPowerFactor, outletVAR."
|
|
|
|
REVISION "201111211200Z"
|
|
DESCRIPTION
|
|
"- Added notifyGroupBreakerStatus object.
|
|
- Renamed groupStatus object to groupBreakerStatus. This object had not yet
|
|
been implemented so there is no user impact.
|
|
- Updated descriptions for inputWhTimer, groupWhTimer, and outletWhTimer."
|
|
|
|
REVISION "201110241200Z"
|
|
DESCRIPTION
|
|
"- Added notifyBootUp object.
|
|
- Added outletType object.
|
|
- Updated description for all lower and upper thresholds to indicate that
|
|
a value of -1 indicates that it is not supported by a particular ePDU model.
|
|
- Updated descriptions for inputVA, inputWatts, groupVA, groupWatts, outletVA,
|
|
outletWatts to indicate that a value of -1 indicates that it is not
|
|
supported by a particular ePDU model.
|
|
- Added a note to unit, group, and outlet level control command objects
|
|
indicating that some products (mainly with part numbers that begin with IPV
|
|
or IPC) do not support delayed outlet control commands and will reply with
|
|
an error if a command value is written that is > 0.
|
|
- Corrected description for inputType.
|
|
- Added a UnixTimeStamp Textual Convention and changed the SYNTAX of
|
|
inputWhTimer, groupWhTimer, and outletWhTimer to use it.
|
|
- Updated the contact info to reference the ePDU website."
|
|
|
|
REVISION "201102071529Z"
|
|
DESCRIPTION
|
|
"Initial release."
|
|
::= { pduAgent 7 }
|
|
|
|
UnixTimeStamp ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unix time stamp. Measured in seconds since January 1, 1970."
|
|
SYNTAX Counter32
|
|
|
|
|
|
-- eatonEpdu { iso org(3) dod(6) internet(1) private(4)
|
|
-- enterprises(1) eaton(534) products(6) pduAgent(6) (7) }
|
|
|
|
notifications OBJECT IDENTIFIER ::= { eatonEpdu 0 }
|
|
units OBJECT IDENTIFIER ::= { eatonEpdu 1 }
|
|
inputs OBJECT IDENTIFIER ::= { eatonEpdu 3 }
|
|
groups OBJECT IDENTIFIER ::= { eatonEpdu 5 }
|
|
outlets OBJECT IDENTIFIER ::= { eatonEpdu 6 }
|
|
environmental OBJECT IDENTIFIER ::= { eatonEpdu 7 }
|
|
conformance OBJECT IDENTIFIER ::= { eatonEpdu 25 }
|
|
objectGroups OBJECT IDENTIFIER ::= { conformance 5 }
|
|
|
|
notifyUserLogin NOTIFICATION-TYPE
|
|
OBJECTS { userName,
|
|
commInterface }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever a user logs in."
|
|
::= { notifications 1 }
|
|
|
|
notifyUserLogout NOTIFICATION-TYPE
|
|
OBJECTS { userName,
|
|
commInterface }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever a user logs out."
|
|
::= { notifications 2 }
|
|
|
|
notifyFailedLogin NOTIFICATION-TYPE
|
|
OBJECTS { userName,
|
|
commInterface }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent when someone attempts to log in and fails. On some models, may be
|
|
sent after three failed login attempts."
|
|
::= { notifications 3 }
|
|
|
|
notifyBootUp NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever an ePDU finishes booting up (hard or soft reboot)."
|
|
::= { notifications 4 }
|
|
|
|
notifyInputVoltageThStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
inputIndex,
|
|
inputVoltageIndex,
|
|
inputVoltage,
|
|
inputVoltageThStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever an input voltage threshold status changes."
|
|
::= { notifications 11 }
|
|
|
|
notifyInputCurrentThStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
inputIndex,
|
|
inputCurrentIndex,
|
|
inputCurrent,
|
|
inputCurrentThStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever an input current threshold status changes."
|
|
::= { notifications 12 }
|
|
|
|
notifyInputFrequencyStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
inputIndex,
|
|
inputFrequency,
|
|
inputFrequencyStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever the input frequency status changes."
|
|
::= { notifications 13 }
|
|
|
|
notifyGroupVoltageThStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
groupIndex,
|
|
groupVoltage,
|
|
groupVoltageThStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever a group voltage threshold status changes."
|
|
::= { notifications 21 }
|
|
|
|
notifyGroupCurrentThStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
groupIndex,
|
|
groupCurrent,
|
|
groupCurrentThStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever a group current threshold status changes."
|
|
::= { notifications 22 }
|
|
|
|
notifyGroupBreakerStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
groupIndex,
|
|
groupBreakerStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever a group status changes to indicate whether the circuit
|
|
breaker is on or off."
|
|
::= { notifications 23 }
|
|
|
|
notifyOutletVoltageThStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
outletIndex,
|
|
outletVoltage,
|
|
outletVoltageThStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever an outlet voltage threshold status changes."
|
|
::= { notifications 31 }
|
|
|
|
notifyOutletCurrentThStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
outletIndex,
|
|
outletCurrent,
|
|
outletCurrentThStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever an outlet current threshold status changes."
|
|
::= { notifications 32 }
|
|
|
|
notifyOutletControlStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
outletIndex,
|
|
outletControlStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever an outlet state On / Off changes."
|
|
::= { notifications 33 }
|
|
|
|
notifyTemperatureThStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
temperatureIndex,
|
|
temperatureValue,
|
|
temperatureThStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever a temperature threshold status changes."
|
|
::= { notifications 41 }
|
|
|
|
notifyHumidityThStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
humidityIndex,
|
|
humidityValue,
|
|
humidityThStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever a humidity threshold status changes."
|
|
::= { notifications 42 }
|
|
|
|
notifyContactState NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
contactIndex,
|
|
contactState }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever a contact sensor state changes."
|
|
::= { notifications 43 }
|
|
|
|
notifyProbeStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
temperatureIndex,
|
|
temperatureProbeStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever the environment probe status changes."
|
|
::= { notifications 44 }
|
|
|
|
notifyCommunicationStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
communicationStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever the PDU communication status changes."
|
|
::= { notifications 51 }
|
|
|
|
notifyInternalStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
internalStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever the PDU internal status changes."
|
|
::= { notifications 52 }
|
|
|
|
notifyTest NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever the trap test feature is used by the communication card."
|
|
::= { notifications 53 }
|
|
|
|
notifyStrappingStatus NOTIFICATION-TYPE
|
|
OBJECTS { strappingIndex,
|
|
strappingStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sent whenever the strapping communication status changes."
|
|
::= { notifications 54 }
|
|
|
|
unitsPresent OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Each unit is identified by a Strapping Index. This object returns a comma-delimited list of the
|
|
Strapping Indexes of all units present in the strapping group. For example, if units 0, 1, 5,
|
|
and 7 are present, this value will be '0,1,5,7'. For units that do not support strapping,
|
|
a Strapping Index of '0' is assumed."
|
|
::= { units 1 }
|
|
|
|
unitTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UnitEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of units. In most cases this list will only contain one entry.
|
|
However, some units have a 'strapping' feature which allow units to be
|
|
daisy-chained together such that all of them can be accessed through
|
|
the SNMP interface of the master. If strapping is enabled, the
|
|
strapping indexes of the units that can be accessed will be listed in the
|
|
unitsPresent object."
|
|
::= { units 2 }
|
|
|
|
unitEntry OBJECT-TYPE
|
|
SYNTAX UnitEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a PDU."
|
|
INDEX { strappingIndex }
|
|
::= { unitTable 1 }
|
|
|
|
UnitEntry ::= SEQUENCE {
|
|
strappingIndex
|
|
Integer32,
|
|
productName
|
|
OCTET STRING,
|
|
partNumber
|
|
OCTET STRING,
|
|
serialNumber
|
|
OCTET STRING,
|
|
firmwareVersion
|
|
OCTET STRING,
|
|
unitName
|
|
OCTET STRING,
|
|
lcdControl
|
|
INTEGER,
|
|
clockValue
|
|
DateAndTime,
|
|
temperatureScale
|
|
INTEGER,
|
|
unitType
|
|
INTEGER,
|
|
systemType
|
|
INTEGER,
|
|
inputCount
|
|
Integer32,
|
|
groupCount
|
|
Integer32,
|
|
outletCount
|
|
Integer32,
|
|
temperatureCount
|
|
Integer32,
|
|
humidityCount
|
|
Integer32,
|
|
contactCount
|
|
Integer32,
|
|
communicationStatus
|
|
INTEGER,
|
|
internalStatus
|
|
INTEGER,
|
|
strappingStatus
|
|
INTEGER,
|
|
userName
|
|
OCTET STRING,
|
|
commInterface
|
|
INTEGER
|
|
}
|
|
|
|
strappingIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (0..23)
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"For units that support 'strapping' functionality, this will be a unique
|
|
value for each unit. If units do not support 'strapping', this will
|
|
always be '0'."
|
|
::= { unitEntry 1 }
|
|
|
|
productName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..127))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of the product."
|
|
::= { unitEntry 2 }
|
|
|
|
partNumber OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Part number of the unit."
|
|
::= { unitEntry 3 }
|
|
|
|
serialNumber OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number of the unit."
|
|
::= { unitEntry 4 }
|
|
|
|
firmwareVersion OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Firmware version."
|
|
::= { unitEntry 5 }
|
|
|
|
unitName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Descriptive name for the unit."
|
|
::= { unitEntry 6 }
|
|
|
|
lcdControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notApplicable (0),
|
|
lcdScreenOff (1),
|
|
lcdKeyLock (2),
|
|
lcdScreenOffAndKeyLock (3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Control the local LCD."
|
|
::= { unitEntry 7 }
|
|
|
|
clockValue OBJECT-TYPE
|
|
SYNTAX DateAndTime
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Clock value. This could be from either a real-time clock (in which case
|
|
it is likely writeable) or from a time server via NTP (probably read-only)."
|
|
::= { unitEntry 8 }
|
|
|
|
temperatureScale OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
celsius (0),
|
|
fahrenheit (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Scale used to return temperature objects."
|
|
::= { unitEntry 9 }
|
|
|
|
unitType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown (0),
|
|
switched (1),
|
|
advancedMonitored (2),
|
|
managed (3),
|
|
monitored (4),
|
|
basic (5),
|
|
inlineMonitored (6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Technical capabilities of the PDU. Functionality is as follows:
|
|
Monitored (MI) - input and usually section/group monitoring.
|
|
Advanced Monitored (AM) - input, section/group, and outlet monitoring.
|
|
Switched (SW) - input and section/group monitoring, outlet switching.
|
|
Basic (BA) - no communication card.
|
|
Inline Monitored (IL) - input and usually one section/group monitoring."
|
|
::= { unitEntry 10 }
|
|
|
|
systemType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown (0),
|
|
g3ePDU (1),
|
|
g3HDePDU (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Architecture of the ePDU electronic."
|
|
::= { unitEntry 11 }
|
|
|
|
inputCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of inputs on this ePDU."
|
|
::= { unitEntry 20 }
|
|
|
|
groupCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of groups on this ePDU. Groups include breakers, outlet sections,
|
|
and user-defined groups."
|
|
::= { unitEntry 21 }
|
|
|
|
outletCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of outlets on this ePDU."
|
|
::= { unitEntry 22 }
|
|
|
|
temperatureCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max number of temperature measurements on this ePDU."
|
|
::= { unitEntry 23 }
|
|
|
|
humidityCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max number of humidity measurements on this ePDU."
|
|
::= { unitEntry 24 }
|
|
|
|
contactCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max number of contact sensors on this ePDU."
|
|
::= { unitEntry 25 }
|
|
|
|
communicationStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good (0),
|
|
communicationLost (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the internal communication with the PDU."
|
|
::= { unitEntry 30 }
|
|
|
|
internalStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good (0),
|
|
internalFailure (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the internal failure inside the PDU."
|
|
::= { unitEntry 31 }
|
|
|
|
strappingStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good (0),
|
|
communicationLost (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the external communication with a strapping unit."
|
|
::= { unitEntry 32 }
|
|
|
|
userName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(0..31))
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Username used to log into the PDU."
|
|
::= { unitEntry 40 }
|
|
|
|
commInterface OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
serial (0),
|
|
usb (1),
|
|
telnet (2),
|
|
web (3),
|
|
ftp (4),
|
|
xml (5)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communications interface used to log into the PDU."
|
|
::= { unitEntry 41 }
|
|
|
|
unitControlTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UnitControlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of units that have controllable outlets."
|
|
::= { units 3 }
|
|
|
|
unitControlEntry OBJECT-TYPE
|
|
SYNTAX UnitControlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a PDU which has controllable outlets."
|
|
INDEX { strappingIndex }
|
|
::= { unitControlTable 1 }
|
|
|
|
UnitControlEntry ::= SEQUENCE {
|
|
unitControlOffCmd
|
|
Integer32,
|
|
unitControlOnCmd
|
|
Integer32
|
|
}
|
|
|
|
unitControlOffCmd OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..99999)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit-level outlet control command.
|
|
|
|
Once the command is issued, outlets will turn Off.
|
|
0-n : Time in seconds until the outlet Sequence Off command is issued
|
|
-1 : Cancel a pending unit-level Off command
|
|
|
|
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
|
|
|
|
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
|
|
commands. These will respond with an error if a command value of > 0 is written to this object."
|
|
::= { unitControlEntry 2 }
|
|
|
|
unitControlOnCmd OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..99999)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit-level outlet control command.
|
|
|
|
Once the command is issued, outlets will turn On according to their outletControlSequenceDelay value.
|
|
0-n : Time in seconds until the outlet Sequence On command is issued
|
|
-1 : Cancel a pending unit-level On command
|
|
|
|
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
|
|
|
|
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
|
|
commands. These will respond with an error if a command value of > 0 is written to this object."
|
|
::= { unitControlEntry 3 }
|
|
|
|
inputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF InputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"List of inputs to the PDU."
|
|
::= { inputs 1 }
|
|
|
|
inputEntry OBJECT-TYPE
|
|
SYNTAX InputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a particular input."
|
|
INDEX { strappingIndex,
|
|
inputIndex }
|
|
::= { inputTable 1 }
|
|
|
|
InputEntry ::= SEQUENCE {
|
|
inputIndex
|
|
Integer32,
|
|
inputType
|
|
INTEGER,
|
|
inputFrequency
|
|
Integer32,
|
|
inputFrequencyStatus
|
|
INTEGER,
|
|
inputVoltageCount
|
|
Integer32,
|
|
inputCurrentCount
|
|
Integer32,
|
|
inputPowerCount
|
|
Integer32,
|
|
inputPlugType
|
|
INTEGER,
|
|
inputFeedColor
|
|
Unsigned32,
|
|
inputFeedName
|
|
OCTET STRING
|
|
}
|
|
|
|
inputIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..2)
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each input. Its value ranges from 1 to inputCount."
|
|
::= { inputEntry 1 }
|
|
|
|
inputType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
singlePhase (1),
|
|
splitPhase (2),
|
|
threePhaseDelta (3),
|
|
threePhaseWye (4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Type of input - single phase, split phase, three phase delta, or three
|
|
phase wye."
|
|
::= { inputEntry 2 }
|
|
|
|
inputFrequency OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Units are 0.1 Hz; divide by ten to get Hz."
|
|
::= { inputEntry 3 }
|
|
|
|
inputFrequencyStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good (0),
|
|
outOfRange (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the measured input frequency relative to the nominal frequency and the admitted tolerance."
|
|
::= { inputEntry 4 }
|
|
|
|
inputVoltageCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of input voltage measurements on this ePDU."
|
|
::= { inputEntry 5 }
|
|
|
|
inputCurrentCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of input current measurements on this ePDU."
|
|
::= { inputEntry 6 }
|
|
|
|
inputPowerCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of rows in the inputPowerTable."
|
|
::= { inputEntry 7 }
|
|
|
|
inputPlugType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other1Phase (100),
|
|
other2Phase (200),
|
|
other3Phase (300),
|
|
iecC14Inlet (101),
|
|
iecC20Inlet (102),
|
|
iec316P6 (103),
|
|
iec332P6 (104),
|
|
iec360P6 (105),
|
|
iecC14Plug (106),
|
|
iecC20Plug (107),
|
|
nema515 (120),
|
|
nemaL515 (121),
|
|
nema520 (122),
|
|
nemaL520 (123),
|
|
nema615 (124),
|
|
nemaL615 (125),
|
|
nemaL530 (126),
|
|
nema620 (127),
|
|
nemaL620 (128),
|
|
nemaL630 (129),
|
|
cs8265 (130),
|
|
french (150),
|
|
schuko (151),
|
|
uk (152),
|
|
nemaL1420 (201),
|
|
nemaL1430 (202),
|
|
iec516P6 (301),
|
|
iec460P9 (302),
|
|
iec560P9 (303),
|
|
iec532P6 (304),
|
|
iec563P6 (306),
|
|
nemaL1520 (320),
|
|
nemaL2120 (321),
|
|
nemaL1530 (322),
|
|
nemaL2130 (323),
|
|
cs8365 (324),
|
|
nemaL2220 (325),
|
|
nemaL2230 (326),
|
|
bladeUps208V (350),
|
|
bladeUps400V (351)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Identifies which plug is on the input."
|
|
::= { inputEntry 8 }
|
|
|
|
inputFeedColor OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..16777215)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Color code of the input feed."
|
|
::= { inputEntry 9 }
|
|
|
|
inputFeedName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..31))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A descriptive name for the input."
|
|
::= { inputEntry 10 }
|
|
|
|
|
|
|
|
|
|
inputVoltageTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF InputVoltageEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of input voltage measurements. The number of entries
|
|
is given by inputVoltageCount."
|
|
::= { inputs 2 }
|
|
|
|
inputVoltageEntry OBJECT-TYPE
|
|
SYNTAX InputVoltageEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a particular input voltage measurement."
|
|
INDEX { strappingIndex,
|
|
inputIndex,
|
|
inputVoltageIndex }
|
|
::= { inputVoltageTable 1 }
|
|
|
|
InputVoltageEntry ::= SEQUENCE {
|
|
inputVoltageIndex
|
|
Integer32,
|
|
inputVoltageMeasType
|
|
INTEGER,
|
|
inputVoltage
|
|
Integer32,
|
|
inputVoltageThStatus
|
|
INTEGER,
|
|
inputVoltageThLowerWarning
|
|
Integer32,
|
|
inputVoltageThLowerCritical
|
|
Integer32,
|
|
inputVoltageThUpperWarning
|
|
Integer32,
|
|
inputVoltageThUpperCritical
|
|
Integer32
|
|
}
|
|
|
|
inputVoltageIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..3)
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each input voltage measurement. Its value ranges
|
|
from 1 to inputVoltageCount."
|
|
::= { inputVoltageEntry 1 }
|
|
|
|
inputVoltageMeasType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
singlePhase (1),
|
|
phase1toN (2),
|
|
phase2toN (3),
|
|
phase3toN (4),
|
|
phase1to2 (5),
|
|
phase2to3 (6),
|
|
phase3to1 (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value indicates what input voltage is being measured in this table row - single phase
|
|
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
|
|
phase 2 to phase 3, or phase 3 to phase 1."
|
|
::= { inputVoltageEntry 2 }
|
|
|
|
inputVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input voltage measurement value. Units are millivolts."
|
|
::= { inputVoltageEntry 3 }
|
|
|
|
inputVoltageThStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good (0),
|
|
lowWarning (1),
|
|
lowCritical (2),
|
|
highWarning (3),
|
|
highCritical (4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the measured input voltage relative to the configured thresholds."
|
|
::= { inputVoltageEntry 4 }
|
|
|
|
inputVoltageThLowerWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..500000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower warning threshold. Units are millivolts. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputVoltageEntry 5 }
|
|
|
|
inputVoltageThLowerCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..500000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower critical threshold. Units are millivolts. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputVoltageEntry 6 }
|
|
|
|
inputVoltageThUpperWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..500000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper warning threshold. Units are millivolts. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputVoltageEntry 7 }
|
|
|
|
inputVoltageThUpperCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..500000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper critical threshold. Units are millivolts. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputVoltageEntry 8 }
|
|
|
|
|
|
|
|
inputCurrentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF InputCurrentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of input current measurements. The number of entries
|
|
is given by inputCurrentCount."
|
|
::= { inputs 3 }
|
|
|
|
inputCurrentEntry OBJECT-TYPE
|
|
SYNTAX InputCurrentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a particular input current measurement."
|
|
INDEX { strappingIndex,
|
|
inputIndex,
|
|
inputCurrentIndex }
|
|
::= { inputCurrentTable 1 }
|
|
|
|
InputCurrentEntry ::= SEQUENCE {
|
|
inputCurrentIndex
|
|
Integer32,
|
|
inputCurrentMeasType
|
|
INTEGER,
|
|
inputCurrentCapacity
|
|
Integer32,
|
|
inputCurrent
|
|
Integer32,
|
|
inputCurrentThStatus
|
|
INTEGER,
|
|
inputCurrentThLowerWarning
|
|
Integer32,
|
|
inputCurrentThLowerCritical
|
|
Integer32,
|
|
inputCurrentThUpperWarning
|
|
Integer32,
|
|
inputCurrentThUpperCritical
|
|
Integer32,
|
|
inputCurrentCrestFactor
|
|
Integer32,
|
|
inputCurrentPercentLoad
|
|
Integer32,
|
|
inputPhaseDesignator
|
|
DisplayString
|
|
}
|
|
|
|
inputCurrentIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..4)
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each input current measurement. Its value ranges
|
|
from 1 to inputCurrentCount."
|
|
::= { inputCurrentEntry 1 }
|
|
|
|
inputCurrentMeasType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
singlePhase (1),
|
|
neutral (2),
|
|
phase1 (3),
|
|
phase2 (4),
|
|
phase3 (5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Which input wire is being measured in this table row - single phase, neutral, phase 1,
|
|
phase 2, or phase 3."
|
|
::= { inputCurrentEntry 2 }
|
|
|
|
inputCurrentCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rated current capacity of the input. A negative value indicates that
|
|
the hardware current capacity is unknown. Units are milliamps."
|
|
::= { inputCurrentEntry 3 }
|
|
|
|
inputCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input current measurement value. Units are milliamps."
|
|
::= { inputCurrentEntry 4 }
|
|
|
|
inputCurrentThStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good (0),
|
|
lowWarning (1),
|
|
lowCritical (2),
|
|
highWarning (3),
|
|
highCritical (4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the measured input current relative to the configured thresholds."
|
|
::= { inputCurrentEntry 5 }
|
|
|
|
inputCurrentThLowerWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..100000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower warning threshold. Units are milliamps. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputCurrentEntry 6 }
|
|
|
|
inputCurrentThLowerCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..100000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower critical threshold. Units are milliamps. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputCurrentEntry 7 }
|
|
|
|
inputCurrentThUpperWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..100000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper warning threshold. Units are milliamps. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputCurrentEntry 8 }
|
|
|
|
inputCurrentThUpperCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..100000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper critical threshold. Units are milliamps. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputCurrentEntry 9 }
|
|
|
|
inputCurrentCrestFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current crest factor. Units are in milli, for example a crest factor of
|
|
1.414 will be returned as 1414. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputCurrentEntry 10 }
|
|
|
|
inputCurrentPercentLoad OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current percent load, based on the rated current capacity. Units are
|
|
percentage, for example 80% will be returned as 80. A negative
|
|
value indicates that this object is not available."
|
|
::= { inputCurrentEntry 11 }
|
|
|
|
inputPhaseDesignator OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(2..4))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alphanumeric physical name for the input."
|
|
::= { inputCurrentEntry 12 }
|
|
|
|
|
|
|
|
|
|
inputPowerTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF InputPowerEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of input power measurements. The number of entries
|
|
is given by inputPowerCount."
|
|
::= { inputs 4 }
|
|
|
|
inputPowerEntry OBJECT-TYPE
|
|
SYNTAX InputPowerEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for an input power measurement."
|
|
INDEX { strappingIndex,
|
|
inputIndex,
|
|
inputPowerIndex }
|
|
::= { inputPowerTable 1 }
|
|
|
|
InputPowerEntry ::= SEQUENCE {
|
|
inputPowerIndex
|
|
Integer32,
|
|
inputPowerMeasType
|
|
INTEGER,
|
|
inputVA
|
|
Integer32,
|
|
inputWatts
|
|
Integer32,
|
|
inputWh
|
|
Unsigned32,
|
|
inputWhTimer
|
|
UnixTimeStamp,
|
|
inputPowerFactor
|
|
Integer32,
|
|
inputVAR
|
|
Integer32
|
|
}
|
|
|
|
inputPowerIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..12)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each input power measurement. Its value ranges
|
|
from 1 to inputPowerCount."
|
|
::= { inputPowerEntry 1 }
|
|
|
|
inputPowerMeasType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown (0),
|
|
phase1 (1),
|
|
phase2 (2),
|
|
phase3 (3),
|
|
total (4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value indicates what is being measured in this table row."
|
|
::= { inputPowerEntry 2 }
|
|
|
|
inputVA OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input VA value. Units are VA. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputPowerEntry 3 }
|
|
|
|
inputWatts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input Watts value. Units are Watts. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputPowerEntry 4 }
|
|
|
|
inputWh OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..4294967295)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
|
|
written to, the inputWhTimer will be reset updated as well."
|
|
::= { inputPowerEntry 5 }
|
|
|
|
inputWhTimer OBJECT-TYPE
|
|
SYNTAX UnixTimeStamp
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Timestamp of when input Watt-hours (inputWh) was last reset."
|
|
::= { inputPowerEntry 6 }
|
|
|
|
inputPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input PF value. Units are in thousandths, for example a power factor
|
|
of 0.958 would be returned as 958, and 0.92 would be returned
|
|
as 920. A negative value indicates that this object is not
|
|
available."
|
|
::= { inputPowerEntry 7 }
|
|
|
|
inputVAR OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input VAR value. Units are VAR. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputPowerEntry 8 }
|
|
|
|
|
|
|
|
|
|
|
|
inputTotalPowerTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF InputTotalPowerEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of total input power measurements."
|
|
::= { inputs 5 }
|
|
|
|
inputTotalPowerEntry OBJECT-TYPE
|
|
SYNTAX InputTotalPowerEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a total input power measurement."
|
|
INDEX { strappingIndex,
|
|
inputIndex }
|
|
::= { inputTotalPowerTable 1 }
|
|
|
|
InputTotalPowerEntry ::= SEQUENCE {
|
|
inputTotalVA
|
|
Integer32,
|
|
inputTotalWatts
|
|
Integer32,
|
|
inputTotalWh
|
|
Unsigned32,
|
|
inputTotalWhTimer
|
|
UnixTimeStamp,
|
|
inputTotalPowerFactor
|
|
Integer32,
|
|
inputTotalVAR
|
|
Integer32,
|
|
inputPowerCapacity
|
|
Integer32
|
|
}
|
|
|
|
inputTotalVA OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input VA value. Units are VA. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputTotalPowerEntry 3 }
|
|
|
|
inputTotalWatts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input Watts value. Units are Watts. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputTotalPowerEntry 4 }
|
|
|
|
inputTotalWh OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..4294967295)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
|
|
written to, the inputWhTimer will be reset updated as well."
|
|
::= { inputTotalPowerEntry 5 }
|
|
|
|
inputTotalWhTimer OBJECT-TYPE
|
|
SYNTAX UnixTimeStamp
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Timestamp of when input Watt-hours (inputWh) was last reset."
|
|
::= { inputTotalPowerEntry 6 }
|
|
|
|
inputTotalPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input PF value. Units are in thousandths, for example a power factor
|
|
of 0.958 would be returned as 958, and 0.92 would be returned
|
|
as 920. A negative value indicates that this object is not
|
|
available."
|
|
::= { inputTotalPowerEntry 7 }
|
|
|
|
inputTotalVAR OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input VAR value. Units are VAR. A negative value indicates
|
|
that this object is not available."
|
|
::= { inputTotalPowerEntry 8 }
|
|
|
|
inputPowerCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Typical power capacity of the input. A negative value indicates that
|
|
the hardware current capacity is unknown."
|
|
::= { inputTotalPowerEntry 9 }
|
|
|
|
|
|
|
|
|
|
groupTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF GroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of groups. The number of entries is given by groupCount."
|
|
::= { groups 1 }
|
|
|
|
groupEntry OBJECT-TYPE
|
|
SYNTAX GroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a particular group."
|
|
INDEX { strappingIndex,
|
|
groupIndex }
|
|
::= { groupTable 1 }
|
|
|
|
GroupEntry ::= SEQUENCE {
|
|
groupIndex
|
|
Integer32,
|
|
groupID
|
|
DisplayString,
|
|
groupName
|
|
OCTET STRING,
|
|
groupType
|
|
INTEGER,
|
|
groupBreakerStatus
|
|
INTEGER,
|
|
groupChildCount
|
|
Integer32,
|
|
groupColor
|
|
Unsigned32,
|
|
groupDesignator
|
|
DisplayString,
|
|
groupInputIndex
|
|
Integer32
|
|
}
|
|
|
|
groupIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..64)
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each group. Its value ranges from 1 to groupCount."
|
|
::= { groupEntry 1 }
|
|
|
|
groupID OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(2..4))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alphanumeric designator for the group. This value may be written
|
|
on the face of the unit."
|
|
::= { groupEntry 2 }
|
|
|
|
groupName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..31))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A descriptive name for the group."
|
|
::= { groupEntry 3 }
|
|
|
|
groupType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown (0),
|
|
breaker1pole (1),
|
|
breaker2pole (2),
|
|
breaker3pole (3),
|
|
outletSection (4),
|
|
userDefined (5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of the group."
|
|
::= { groupEntry 4 }
|
|
|
|
groupBreakerStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notApplicable (0),
|
|
breakerOn (1),
|
|
breakerOff (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Only applicable to breaker-groups. Indicates whether a breaker is turned
|
|
off or on."
|
|
::= { groupEntry 5 }
|
|
|
|
groupChildCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of children for this group."
|
|
::= { groupEntry 6 }
|
|
|
|
groupColor OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..16777215)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Background color code of the group. Color codes are decimal values."
|
|
::= { groupEntry 7 }
|
|
|
|
groupDesignator OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(2..4))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alphanumeric physical name for the group. This value may be written
|
|
on the face of the unit."
|
|
::= { groupEntry 8 }
|
|
|
|
groupInputIndex OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Identifies the input on which the group is connected."
|
|
::= { groupEntry 9 }
|
|
|
|
|
|
|
|
groupChildTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF GroupChildEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of children for this group. For example, this table will link
|
|
to all of the outlets that are contained in a particular group."
|
|
::= { groups 2 }
|
|
|
|
groupChildEntry OBJECT-TYPE
|
|
SYNTAX GroupChildEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a particular child."
|
|
INDEX { strappingIndex,
|
|
groupIndex,
|
|
groupChildIndex }
|
|
::= { groupChildTable 1 }
|
|
|
|
GroupChildEntry ::= SEQUENCE {
|
|
groupChildIndex
|
|
Integer32,
|
|
groupChildType
|
|
INTEGER,
|
|
groupChildOID
|
|
OBJECT IDENTIFIER
|
|
}
|
|
|
|
groupChildIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..32)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each child. Its value ranges from 1 to groupChildCount."
|
|
::= { groupChildEntry 1 }
|
|
|
|
groupChildType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown (0),
|
|
section (2),
|
|
custom (3),
|
|
outlet (4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of the child."
|
|
::= { groupChildEntry 2 }
|
|
|
|
groupChildOID OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Object ID of a child object."
|
|
::= { groupChildEntry 3 }
|
|
|
|
groupVoltageTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF GroupVoltageEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of group voltage measurements. There can be only one voltage
|
|
measurement for each group."
|
|
::= { groups 3 }
|
|
|
|
groupVoltageEntry OBJECT-TYPE
|
|
SYNTAX GroupVoltageEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a group voltage measurement."
|
|
INDEX { strappingIndex,
|
|
groupIndex }
|
|
::= { groupVoltageTable 1 }
|
|
|
|
GroupVoltageEntry ::= SEQUENCE {
|
|
groupVoltageMeasType
|
|
INTEGER,
|
|
groupVoltage
|
|
Integer32,
|
|
groupVoltageThStatus
|
|
INTEGER,
|
|
groupVoltageThLowerWarning
|
|
Integer32,
|
|
groupVoltageThLowerCritical
|
|
Integer32,
|
|
groupVoltageThUpperWarning
|
|
Integer32,
|
|
groupVoltageThUpperCritical
|
|
Integer32
|
|
}
|
|
|
|
groupVoltageMeasType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown (0),
|
|
singlePhase (1),
|
|
phase1toN (2),
|
|
phase2toN (3),
|
|
phase3toN (4),
|
|
phase1to2 (5),
|
|
phase2to3 (6),
|
|
phase3to1 (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value indicates what voltage is being measured in this table row."
|
|
::= { groupVoltageEntry 2 }
|
|
|
|
groupVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Units are millivolts."
|
|
::= { groupVoltageEntry 3 }
|
|
|
|
groupVoltageThStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good (0),
|
|
lowWarning (1),
|
|
lowCritical (2),
|
|
highWarning (3),
|
|
highCritical (4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the measured group voltage relative to the configured thresholds."
|
|
::= { groupVoltageEntry 4 }
|
|
|
|
groupVoltageThLowerWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..500000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower warning threshold. Units are millivolts. A negative value indicates
|
|
that this object is not available."
|
|
::= { groupVoltageEntry 5 }
|
|
|
|
groupVoltageThLowerCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..500000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower critical threshold. Units are millivolts. A negative value indicates
|
|
that this object is not available."
|
|
::= { groupVoltageEntry 6 }
|
|
|
|
groupVoltageThUpperWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..500000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper warning threshold. Units are millivolts. A negative value indicates
|
|
that this object is not available."
|
|
::= { groupVoltageEntry 7 }
|
|
|
|
groupVoltageThUpperCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..500000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper critical threshold. Units are millivolts. A negative value indicates
|
|
that this object is not available."
|
|
::= { groupVoltageEntry 8 }
|
|
|
|
groupCurrentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF GroupCurrentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of group current measurements. There can be only one current
|
|
measurement for each group."
|
|
::= { groups 4 }
|
|
|
|
groupCurrentEntry OBJECT-TYPE
|
|
SYNTAX GroupCurrentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a group current measurement."
|
|
INDEX { strappingIndex,
|
|
groupIndex }
|
|
::= { groupCurrentTable 1 }
|
|
|
|
GroupCurrentEntry ::= SEQUENCE {
|
|
groupCurrentCapacity
|
|
Integer32,
|
|
groupCurrent
|
|
Integer32,
|
|
groupCurrentThStatus
|
|
INTEGER,
|
|
groupCurrentThLowerWarning
|
|
Integer32,
|
|
groupCurrentThLowerCritical
|
|
Integer32,
|
|
groupCurrentThUpperWarning
|
|
Integer32,
|
|
groupCurrentThUpperCritical
|
|
Integer32,
|
|
groupCurrentCrestFactor
|
|
Integer32,
|
|
groupCurrentPercentLoad
|
|
Integer32
|
|
}
|
|
|
|
groupCurrentCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rated current capacity of the group. Units are milliamps. A negative
|
|
value indicates that the hardware current capacity is unknown (it
|
|
will always be unknown for custom groups)."
|
|
::= { groupCurrentEntry 2 }
|
|
|
|
groupCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group current measurement value. Units are milliamps."
|
|
::= { groupCurrentEntry 3 }
|
|
|
|
groupCurrentThStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good (0),
|
|
lowWarning (1),
|
|
lowCritical (2),
|
|
highWarning (3),
|
|
highCritical (4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the measured group current relative to the configured thresholds."
|
|
::= { groupCurrentEntry 4 }
|
|
|
|
groupCurrentThLowerWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..100000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower warning threshold. Units are milliamps. A negative value indicates
|
|
that this object is not available."
|
|
::= { groupCurrentEntry 5 }
|
|
|
|
groupCurrentThLowerCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..100000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower critical threshold. Units are milliamps. A negative value indicates
|
|
that this object is not available."
|
|
::= { groupCurrentEntry 6 }
|
|
|
|
groupCurrentThUpperWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..100000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper warning threshold. Units are milliamps. A negative value indicates
|
|
that this object is not available."
|
|
::= { groupCurrentEntry 7 }
|
|
|
|
groupCurrentThUpperCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..100000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper critical threshold. Units are milliamps. A negative value indicates
|
|
that this object is not available."
|
|
::= { groupCurrentEntry 8 }
|
|
|
|
groupCurrentCrestFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current crest factor. Units are in milli, for example a crest factor of
|
|
1.414 will be returned as 1414. A negative value indicates
|
|
that this object is not available."
|
|
::= { groupCurrentEntry 9 }
|
|
|
|
groupCurrentPercentLoad OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current percent load, based on the rated current capacity. Units are
|
|
percentage, for example 80% will be returned as 80. A negative
|
|
value indicates that this object is not available."
|
|
::= { groupCurrentEntry 10 }
|
|
|
|
groupPowerTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF GroupPowerEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of group power measurements. There can be only one power
|
|
measurement for each group."
|
|
::= { groups 5 }
|
|
|
|
groupPowerEntry OBJECT-TYPE
|
|
SYNTAX GroupPowerEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a group power measurement."
|
|
INDEX { strappingIndex,
|
|
groupIndex }
|
|
::= { groupPowerTable 1 }
|
|
|
|
GroupPowerEntry ::= SEQUENCE {
|
|
groupVA
|
|
Integer32,
|
|
groupWatts
|
|
Integer32,
|
|
groupWh
|
|
Unsigned32,
|
|
groupWhTimer
|
|
UnixTimeStamp,
|
|
groupPowerFactor
|
|
Integer32,
|
|
groupVAR
|
|
Integer32
|
|
}
|
|
|
|
groupVA OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group VA value. Units are VA. A negative value indicates
|
|
that this object is not available."
|
|
::= { groupPowerEntry 2 }
|
|
|
|
groupWatts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group Watts value. Units are Watts. A negative value indicates
|
|
that this object is not available."
|
|
::= { groupPowerEntry 3 }
|
|
|
|
groupWh OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..4294967295)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
|
|
written to, the inputWhTotalTimer will be reset to 0 as well."
|
|
::= { groupPowerEntry 4 }
|
|
|
|
groupWhTimer OBJECT-TYPE
|
|
SYNTAX UnixTimeStamp
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Timestamp of when group Watt-hours (groupWh) was last reset."
|
|
::= { groupPowerEntry 5 }
|
|
|
|
groupPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group PF value. Units are in thousandths, for example a power factor
|
|
of 0.958 would be returned as 958, and 0.92 would be returned
|
|
as 920. A negative value indicates that this object is not available."
|
|
::= { groupPowerEntry 6 }
|
|
|
|
groupVAR OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group VAR value. Units are VAR. A negative value indicates
|
|
that this object is not available."
|
|
::= { groupPowerEntry 7 }
|
|
|
|
groupControlTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF GroupControlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of controllable groups."
|
|
::= { groups 6 }
|
|
|
|
groupControlEntry OBJECT-TYPE
|
|
SYNTAX GroupControlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a controllable group."
|
|
INDEX { strappingIndex,
|
|
groupIndex }
|
|
::= { groupControlTable 1 }
|
|
|
|
GroupControlEntry ::= SEQUENCE {
|
|
groupControlStatus
|
|
INTEGER,
|
|
groupControlOffCmd
|
|
Integer32,
|
|
groupControlOnCmd
|
|
Integer32,
|
|
groupControlRebootCmd
|
|
Integer32
|
|
}
|
|
|
|
groupControlStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1),
|
|
rebooting (2),
|
|
mixed (3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current state of a controlled group. A value of 'mixed' means that
|
|
that the outlets within the group have differing states."
|
|
::= { groupControlEntry 2 }
|
|
|
|
groupControlOffCmd OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..99999)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Group-level outlet control command.
|
|
|
|
Once the command is issued, the outlets in the group will turn Off immediately.
|
|
0-n : Time in seconds until the group command is issued
|
|
-1 : Cancel a pending group-level Off command
|
|
|
|
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
|
|
|
|
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
|
|
commands. These will respond with an error if a command value of > 0 is written to this object."
|
|
::= { groupControlEntry 3 }
|
|
|
|
groupControlOnCmd OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..99999)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Group-level outlet control command.
|
|
|
|
Once the command is issued, the outlets in the group will turn On immediately.
|
|
0-n : Time in seconds until the group command is issued
|
|
-1 : Cancel a pending group-level On command
|
|
|
|
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
|
|
|
|
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
|
|
commands. These will respond with an error if a command value of > 0 is written to this object."
|
|
::= { groupControlEntry 4 }
|
|
|
|
groupControlRebootCmd OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..0)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Group-level outlet control command.
|
|
|
|
For outlets that are On prior to the Reboot command, they will switch Off immediately when the command is
|
|
issued, remain Off for outletControlRebootOffTime seconds, and then turn back On.
|
|
For outlets that are Off prior to the Reboot command, they will turn On after a delay of outletControlRebootOffTime
|
|
seconds from when the command is issued.
|
|
0-n : Time in seconds until the Reboot command is issued
|
|
-1 : Cancel a pending group-level Reboot command
|
|
|
|
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
|
|
|
|
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
|
|
commands. These will respond with an error if a command value of > 0 is written to this object."
|
|
::= { groupControlEntry 5 }
|
|
|
|
outletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF OutletEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of outlets. The number of entries is given by outletCount."
|
|
::= { outlets 1 }
|
|
|
|
outletEntry OBJECT-TYPE
|
|
SYNTAX OutletEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a particular outlet."
|
|
INDEX { strappingIndex,
|
|
outletIndex }
|
|
::= { outletTable 1 }
|
|
|
|
OutletEntry ::= SEQUENCE {
|
|
outletIndex
|
|
Integer32,
|
|
outletID
|
|
DisplayString,
|
|
outletName
|
|
OCTET STRING,
|
|
outletParentCount
|
|
Integer32,
|
|
outletType
|
|
INTEGER,
|
|
outletDesignator
|
|
DisplayString,
|
|
outletPhaseID
|
|
INTEGER
|
|
}
|
|
|
|
outletIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..64)
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each outlet. its value ranges from 1 to outletCount."
|
|
::= { outletEntry 1 }
|
|
|
|
outletID OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(2..4))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alphanumeric designator for the outlet."
|
|
::= { outletEntry 2 }
|
|
|
|
outletName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..31))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A descriptive name for the outlet."
|
|
::= { outletEntry 3 }
|
|
|
|
outletParentCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of parents for this outlet."
|
|
::= { outletEntry 4 }
|
|
|
|
outletType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown (0),
|
|
iecC13 (1),
|
|
iecC19 (2),
|
|
uk (10),
|
|
french (11),
|
|
schuko (12),
|
|
nema515 (20),
|
|
nema51520 (21),
|
|
nema520 (22),
|
|
nemaL520 (23),
|
|
nemaL530 (24),
|
|
nema615 (25),
|
|
nema620 (26),
|
|
nemaL620 (27),
|
|
nemaL630 (28),
|
|
nemaL715 (29),
|
|
rf203p277 (30),
|
|
sdg300 (31)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The physical type of outlet."
|
|
::= { outletEntry 5 }
|
|
|
|
outletDesignator OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(2..4))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alphanumeric physical name for the outlet."
|
|
::= { outletEntry 6 }
|
|
|
|
outletPhaseID OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
singlePhase (1),
|
|
phase1toN (2),
|
|
phase2toN (3),
|
|
phase3toN (4),
|
|
phase1to2 (5),
|
|
phase2to3 (6),
|
|
phase3to1 (7),
|
|
phase12N (8),
|
|
phase23N (9),
|
|
phase31N (10),
|
|
phase123 (11),
|
|
phase123N (12)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value indicates which phases are connected to each outlet in this table row - single phase
|
|
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
|
|
phase 2 to phase 3, phase 3 to phase 1, split-phase with phases 1 and 2, split phase
|
|
with phases 2 and 3, split phase with phases 3 and 1, three-phase delta, and three-phase wye."
|
|
::= { outletEntry 7 }
|
|
|
|
|
|
|
|
|
|
outletParentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF OutletParentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of parents for this outlet. For example, this table will link
|
|
to all of the groups that have this outlet as a child."
|
|
::= { outlets 2 }
|
|
|
|
outletParentEntry OBJECT-TYPE
|
|
SYNTAX OutletParentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a particular parent."
|
|
INDEX { strappingIndex,
|
|
outletIndex,
|
|
outletParentIndex }
|
|
::= { outletParentTable 1 }
|
|
|
|
OutletParentEntry ::= SEQUENCE {
|
|
outletParentIndex
|
|
Integer32,
|
|
outletParentType
|
|
INTEGER,
|
|
outletParentOID
|
|
OBJECT IDENTIFIER
|
|
}
|
|
|
|
outletParentIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..32)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each parent. Its value ranges from 1 to outletParentCount."
|
|
::= { outletParentEntry 1 }
|
|
|
|
outletParentType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown (0),
|
|
breaker (1),
|
|
section (2),
|
|
custom (3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of the parent."
|
|
::= { outletParentEntry 2 }
|
|
|
|
outletParentOID OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Object ID of a parent object."
|
|
::= { outletParentEntry 3 }
|
|
|
|
outletVoltageTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF OutletVoltageEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of outlet voltage measurements."
|
|
::= { outlets 3 }
|
|
|
|
outletVoltageEntry OBJECT-TYPE
|
|
SYNTAX OutletVoltageEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for an outlet voltage measurement."
|
|
INDEX { strappingIndex,
|
|
outletIndex }
|
|
::= { outletVoltageTable 1 }
|
|
|
|
OutletVoltageEntry ::= SEQUENCE {
|
|
outletVoltage
|
|
Integer32,
|
|
outletVoltageThStatus
|
|
INTEGER,
|
|
outletVoltageThLowerWarning
|
|
Integer32,
|
|
outletVoltageThLowerCritical
|
|
Integer32,
|
|
outletVoltageThUpperWarning
|
|
Integer32,
|
|
outletVoltageThUpperCritical
|
|
Integer32
|
|
}
|
|
|
|
outletVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Units are millivolts."
|
|
::= { outletVoltageEntry 2 }
|
|
|
|
outletVoltageThStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good (0),
|
|
lowWarning (1),
|
|
lowCritical (2),
|
|
highWarning (3),
|
|
highCritical (4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the measured outlet voltage relative to the configured thresholds."
|
|
::= { outletVoltageEntry 3 }
|
|
|
|
outletVoltageThLowerWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..500000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower warning threshold. Units are millivolts. A negative value indicates
|
|
that this object is not available."
|
|
::= { outletVoltageEntry 4 }
|
|
|
|
outletVoltageThLowerCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..500000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower critical threshold. Units are millivolts. A negative value indicates
|
|
that this object is not available."
|
|
::= { outletVoltageEntry 5 }
|
|
|
|
outletVoltageThUpperWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..500000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper warning threshold. Units are millivolts. A negative value indicates
|
|
that this object is not available."
|
|
::= { outletVoltageEntry 6 }
|
|
|
|
outletVoltageThUpperCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..500000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper critical threshold. Units are millivolts. A negative value indicates
|
|
that this object is not available."
|
|
::= { outletVoltageEntry 7 }
|
|
|
|
outletCurrentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF OutletCurrentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of outlet current measurements."
|
|
::= { outlets 4 }
|
|
|
|
outletCurrentEntry OBJECT-TYPE
|
|
SYNTAX OutletCurrentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for an outlet current measurement."
|
|
INDEX { strappingIndex,
|
|
outletIndex }
|
|
::= { outletCurrentTable 1 }
|
|
|
|
OutletCurrentEntry ::= SEQUENCE {
|
|
outletCurrentCapacity
|
|
Integer32,
|
|
outletCurrent
|
|
Integer32,
|
|
outletCurrentThStatus
|
|
INTEGER,
|
|
outletCurrentThLowerWarning
|
|
Integer32,
|
|
outletCurrentThLowerCritical
|
|
Integer32,
|
|
outletCurrentThUpperWarning
|
|
Integer32,
|
|
outletCurrentThUpperCritical
|
|
Integer32,
|
|
outletCurrentCrestFactor
|
|
Integer32,
|
|
outletCurrentPercentLoad
|
|
Integer32
|
|
}
|
|
|
|
outletCurrentCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rated current capacity of the outlet. Units are milliamps. A negative
|
|
value indicates that the hardware current capacity is unknown."
|
|
::= { outletCurrentEntry 2 }
|
|
|
|
outletCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An outlet current measurement value. Units are milliamps."
|
|
::= { outletCurrentEntry 3 }
|
|
|
|
outletCurrentThStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good (0),
|
|
lowWarning (1),
|
|
lowCritical (2),
|
|
highWarning (3),
|
|
highCritical (4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the measured outlet current relative to the configured thresholds.
|
|
A negative value indicates that this object is not available."
|
|
::= { outletCurrentEntry 4 }
|
|
|
|
outletCurrentThLowerWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..100000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower warning threshold. Units are milliamps. A negative value indicates
|
|
that this object is not available."
|
|
::= { outletCurrentEntry 5 }
|
|
|
|
outletCurrentThLowerCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..100000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower critical threshold. Units are milliamps. A negative value indicates
|
|
that this object is not available."
|
|
::= { outletCurrentEntry 6 }
|
|
|
|
outletCurrentThUpperWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..100000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper warning threshold. Units are milliamps. A negative value indicates
|
|
that this object is not available."
|
|
::= { outletCurrentEntry 7 }
|
|
|
|
outletCurrentThUpperCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..100000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper critical threshold. Units are milliamps. A negative value indicates
|
|
that this object is not available."
|
|
::= { outletCurrentEntry 8 }
|
|
|
|
outletCurrentCrestFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current crest factor. Units are in milli, for example a crest factor of
|
|
1.414 will be returned as 1414. A negative value indicates
|
|
that this object is not available."
|
|
::= { outletCurrentEntry 9 }
|
|
|
|
outletCurrentPercentLoad OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current percent load, based on the rated current capacity. Units are
|
|
percentage, for example 80% will be returned as 80. A negative
|
|
value indicates that this object is not available."
|
|
::= { outletCurrentEntry 10 }
|
|
|
|
outletPowerTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF OutletPowerEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of outlet power measurements."
|
|
::= { outlets 5 }
|
|
|
|
outletPowerEntry OBJECT-TYPE
|
|
SYNTAX OutletPowerEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for an outlet power measurement."
|
|
INDEX { strappingIndex,
|
|
outletIndex }
|
|
::= { outletPowerTable 1 }
|
|
|
|
OutletPowerEntry ::= SEQUENCE {
|
|
outletVA
|
|
Integer32,
|
|
outletWatts
|
|
Integer32,
|
|
outletWh
|
|
Unsigned32,
|
|
outletWhTimer
|
|
UnixTimeStamp,
|
|
outletPowerFactor
|
|
Integer32,
|
|
outletVAR
|
|
Integer32
|
|
}
|
|
|
|
outletVA OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An outlet VA value. Units are VA. A negative value indicates
|
|
that this object is not available."
|
|
::= { outletPowerEntry 2 }
|
|
|
|
outletWatts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An outlet Watts value. Units are Watts. A negative value indicates
|
|
that this object is not available."
|
|
::= { outletPowerEntry 3 }
|
|
|
|
outletWh OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..4294967295)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
|
|
written to, the inputWhTotalTimer will be reset to 0 as well."
|
|
::= { outletPowerEntry 4 }
|
|
|
|
outletWhTimer OBJECT-TYPE
|
|
SYNTAX UnixTimeStamp
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Timestamp of when outlet Watt-hours (outletWh) was last reset."
|
|
::= { outletPowerEntry 5 }
|
|
|
|
outletPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An outlet PF value. Units are in thousandths, for example a power factor
|
|
of 0.958 would be returned as 958, and 0.92 would be returned
|
|
as 920. A negative value indicates that this object is not available."
|
|
::= { outletPowerEntry 6 }
|
|
|
|
outletVAR OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An outlet VAR value. Units are VAR. A negative value indicates
|
|
that this object is not available."
|
|
::= { outletPowerEntry 7 }
|
|
|
|
outletControlTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF OutletControlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of controllable outlets."
|
|
::= { outlets 6 }
|
|
|
|
outletControlEntry OBJECT-TYPE
|
|
SYNTAX OutletControlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a controllable outlet."
|
|
INDEX { strappingIndex,
|
|
outletIndex }
|
|
::= { outletControlTable 1 }
|
|
|
|
OutletControlEntry ::= SEQUENCE {
|
|
outletControlStatus
|
|
INTEGER,
|
|
outletControlOffCmd
|
|
Integer32,
|
|
outletControlOnCmd
|
|
Integer32,
|
|
outletControlRebootCmd
|
|
Integer32,
|
|
outletControlPowerOnState
|
|
INTEGER,
|
|
outletControlSequenceDelay
|
|
Integer32,
|
|
outletControlRebootOffTime
|
|
Integer32,
|
|
outletControlSwitchable
|
|
INTEGER,
|
|
outletControlShutoffDelay
|
|
Integer32
|
|
}
|
|
|
|
outletControlStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1),
|
|
pendingOff (2),
|
|
pendingOn (3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current state of a controlled outlet."
|
|
::= { outletControlEntry 2 }
|
|
|
|
outletControlOffCmd OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..99999)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet control command.
|
|
|
|
Once the command is issued, the outlet will turn Off immediately.
|
|
0-n : Time in seconds until the outlet command is issued
|
|
-1 : Cancel a pending outlet Off command
|
|
|
|
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
|
|
|
|
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
|
|
commands. These will respond with an error if a command value of > 0 is written to this object."
|
|
::= { outletControlEntry 3 }
|
|
|
|
outletControlOnCmd OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..99999)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet control command.
|
|
|
|
Once the command is issued, the outlet will turn On immediately.
|
|
0-n : Time in seconds until the outlet command is issued
|
|
-1 : Cancel a pending outlet On command
|
|
|
|
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
|
|
|
|
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
|
|
commands. These will respond with an error if a command value of > 0 is written to this object."
|
|
::= { outletControlEntry 4 }
|
|
|
|
outletControlRebootCmd OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..99999)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet control command.
|
|
|
|
For outlets that are On prior to this Reboot command, they will switch Off immediately when the command is
|
|
issued, remain Off for outletControlRebootOffTime seconds, and then turn back On.
|
|
For outlets that are Off prior to the Reboot command, they will turn On after a delay of outletControlRebootOffTime
|
|
seconds from when the command is issued.
|
|
0-n : Time in seconds until the Reboot command is issued
|
|
-1 : Cancel a pending outlet Reboot command
|
|
|
|
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
|
|
|
|
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
|
|
commands. These will respond with an error if a command value of > 0 is written to this object."
|
|
::= { outletControlEntry 5 }
|
|
|
|
outletControlPowerOnState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1),
|
|
lastState (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Determines the outlet state when power is applied to the unit.
|
|
0 : not restart at device startup
|
|
1 : should sequence back ON in line with outletControlSequenceTime
|
|
2 : should take the state the outlet had when power was lost.
|
|
If the state was ON, should sequence back ON in line with outletControlSequenceTime."
|
|
::= { outletControlEntry 6 }
|
|
|
|
outletControlSequenceDelay OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..99999)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time delay in seconds from when a Global Sequence On command is issued to
|
|
when the command is executed on this outlet. This delay is also used as a power-on
|
|
delay. Set to -1 to exclude this outlet from Global Sequence On
|
|
commands."
|
|
::= { outletControlEntry 7 }
|
|
|
|
outletControlRebootOffTime OBJECT-TYPE
|
|
SYNTAX Integer32 (1..99999)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command."
|
|
::= { outletControlEntry 8 }
|
|
|
|
outletControlSwitchable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
switchable (1),
|
|
notSwitchable (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Determines the outlet capability to be controlled On/Off from the communication channels.
|
|
1 : control On/Off enabled
|
|
2 : control On/Off disabled."
|
|
::= { outletControlEntry 9 }
|
|
|
|
outletControlShutoffDelay OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..99999)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time delay in seconds that could be taken in account before shutting of the outlet.
|
|
An application which need to shutoff properly an outlet will read this parameter first
|
|
then write it to the command outletControlOffCmd."
|
|
::= { outletControlEntry 10 }
|
|
|
|
|
|
outletGlobalTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF OutletGlobalEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of globlal configuration on all outlets."
|
|
::= { outlets 7 }
|
|
|
|
outletGlobalEntry OBJECT-TYPE
|
|
SYNTAX OutletGlobalEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a global variable on all outlets."
|
|
INDEX { strappingIndex
|
|
}
|
|
::= { outletGlobalTable 1 }
|
|
|
|
OutletGlobalEntry ::= SEQUENCE {
|
|
outletAutomaticShutoff
|
|
INTEGER
|
|
}
|
|
|
|
outletAutomaticShutoff OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notApplicable (0),
|
|
keepTheCurrentPosition (1),
|
|
shutoffTheOutlets (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Determines the state of all outlets when the unit is power off:
|
|
0 : not applicable (read only)
|
|
1 : Keep the outlet relays in the current position when the PDU is powered down
|
|
2 : Makes the outlet relays go to the position that shutoffs the outlets when the PDU is powered down"
|
|
::= { outletGlobalEntry 2 }
|
|
|
|
|
|
|
|
temperatureTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TemperatureEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of temperature probe measurements. The number of entries is
|
|
given by temperatureCount."
|
|
::= { environmental 1 }
|
|
|
|
temperatureEntry OBJECT-TYPE
|
|
SYNTAX TemperatureEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a temperature measurement."
|
|
INDEX { strappingIndex,
|
|
temperatureIndex }
|
|
::= { temperatureTable 1 }
|
|
|
|
TemperatureEntry ::= SEQUENCE {
|
|
temperatureIndex
|
|
Integer32,
|
|
temperatureName
|
|
OCTET STRING,
|
|
temperatureProbeStatus
|
|
INTEGER,
|
|
temperatureValue
|
|
Integer32,
|
|
temperatureThStatus
|
|
INTEGER,
|
|
temperatureThLowerWarning
|
|
Integer32,
|
|
temperatureThLowerCritical
|
|
Integer32,
|
|
temperatureThUpperWarning
|
|
Integer32,
|
|
temperatureThUpperCritical
|
|
Integer32
|
|
}
|
|
|
|
temperatureIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..2)
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each temperature probe measurement. Its value
|
|
ranges from 1 to temperatureCount."
|
|
::= { temperatureEntry 1 }
|
|
|
|
temperatureName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..31))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A descriptive name for the temperature probe."
|
|
::= { temperatureEntry 2 }
|
|
|
|
temperatureProbeStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
bad (-1),
|
|
disconnected (0),
|
|
connected (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates whether a probe is connected or not."
|
|
::= { temperatureEntry 3 }
|
|
|
|
temperatureValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Units are in tenths of a degree according to the scale specified by
|
|
temperatureScale (either Fahrenheit or Celsius). Divide by ten to get
|
|
degrees."
|
|
::= { temperatureEntry 4 }
|
|
|
|
temperatureThStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good (0),
|
|
lowWarning (1),
|
|
lowCritical (2),
|
|
highWarning (3),
|
|
highCritical (4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the measured temperature relative to the configured
|
|
thresholds."
|
|
::= { temperatureEntry 5 }
|
|
|
|
temperatureThLowerWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..150000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower warning threshold. Units are tenths of a degree. A negative value
|
|
indicates that this object is not available."
|
|
::= { temperatureEntry 6 }
|
|
|
|
temperatureThLowerCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..150000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower critical threshold. Units are tenths of a degree. A negative value
|
|
indicates that this object is not available."
|
|
::= { temperatureEntry 7 }
|
|
|
|
temperatureThUpperWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..150000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper warning threshold. Units are tenths of a degree. A negative value
|
|
indicates that this object is not available."
|
|
::= { temperatureEntry 8 }
|
|
|
|
temperatureThUpperCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..150000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper critical threshold. Units are tenths of a degree. A negative value
|
|
indicates that this object is not available."
|
|
::= { temperatureEntry 9 }
|
|
|
|
humidityTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HumidityEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of humidity probe measurements. The number of entries is
|
|
given by humidityCount."
|
|
::= { environmental 2 }
|
|
|
|
humidityEntry OBJECT-TYPE
|
|
SYNTAX HumidityEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a humidity measurement."
|
|
INDEX { strappingIndex,
|
|
humidityIndex }
|
|
::= { humidityTable 1 }
|
|
|
|
HumidityEntry ::= SEQUENCE {
|
|
humidityIndex
|
|
Integer32,
|
|
humidityName
|
|
OCTET STRING,
|
|
humidityProbeStatus
|
|
INTEGER,
|
|
humidityValue
|
|
Integer32,
|
|
humidityThStatus
|
|
INTEGER,
|
|
humidityThLowerWarning
|
|
Integer32,
|
|
humidityThLowerCritical
|
|
Integer32,
|
|
humidityThUpperWarning
|
|
Integer32,
|
|
humidityThUpperCritical
|
|
Integer32
|
|
}
|
|
|
|
humidityIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..2)
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each humidity probe measurement. Its value
|
|
ranges from 1 to humidityCount."
|
|
::= { humidityEntry 1 }
|
|
|
|
humidityName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..31))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A descriptive name for the humidity probe."
|
|
::= { humidityEntry 2 }
|
|
|
|
humidityProbeStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
bad (-1),
|
|
disconnected (0),
|
|
connected (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates whether a probe is connected or not."
|
|
::= { humidityEntry 3 }
|
|
|
|
humidityValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Units are tenths of a percent relative humidity. Divide the value by 10 to get %RH."
|
|
::= { humidityEntry 4 }
|
|
|
|
humidityThStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good (0),
|
|
lowWarning (1),
|
|
lowCritical (2),
|
|
highWarning (3),
|
|
highCritical (4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the measured humidity relative to the configured
|
|
thresholds."
|
|
::= { humidityEntry 5 }
|
|
|
|
humidityThLowerWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..1000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower warning threshold. Units are 0.1 %RH. A negative value
|
|
indicates that this object is not available."
|
|
::= { humidityEntry 6 }
|
|
|
|
humidityThLowerCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..1000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lower critical threshold. Units are 0.1 %RH. A negative value
|
|
indicates that this object is not available."
|
|
::= { humidityEntry 7 }
|
|
|
|
humidityThUpperWarning OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..1000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper warning threshold. Units are 0.1 %RH. A negative value
|
|
indicates that this object is not available."
|
|
::= { humidityEntry 8 }
|
|
|
|
humidityThUpperCritical OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..1000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Upper critical threshold. Units are 0.1 %RH. A negative value
|
|
indicates that this object is not available."
|
|
::= { humidityEntry 9 }
|
|
|
|
contactTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF ContactEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of contact sensors. The number of entries is
|
|
given by contactCount."
|
|
::= { environmental 3 }
|
|
|
|
contactEntry OBJECT-TYPE
|
|
SYNTAX ContactEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry for a contact sensor"
|
|
INDEX { strappingIndex,
|
|
contactIndex }
|
|
::= { contactTable 1 }
|
|
|
|
ContactEntry ::= SEQUENCE {
|
|
contactIndex
|
|
Integer32,
|
|
contactName
|
|
OCTET STRING,
|
|
contactProbeStatus
|
|
INTEGER,
|
|
contactState
|
|
INTEGER
|
|
}
|
|
|
|
contactIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..3)
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each contact sensor. Its value ranges from 1 to
|
|
contactCount."
|
|
::= { contactEntry 1 }
|
|
|
|
contactName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..31))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A descriptive name for the contact sensor."
|
|
::= { contactEntry 2 }
|
|
|
|
contactProbeStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
bad (-1),
|
|
disconnected (0),
|
|
connected (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates whether a probe is connected or not.
|
|
Will not be returned if the contact sensor is internal to the ePDU,
|
|
in that case only contactState should be read."
|
|
::= { contactEntry 3 }
|
|
|
|
contactState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
contactBad (-1),
|
|
contactOpen (0),
|
|
contactClosed (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the contact sensor."
|
|
::= { contactEntry 4 }
|
|
|
|
eatonEpduCompliances MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The requirements for conforming to the ePDU MIB."
|
|
MODULE
|
|
MANDATORY-GROUPS { epduRequiredGroup }
|
|
GROUP epduOptionalGroup
|
|
DESCRIPTION
|
|
"Different ePDUs will support a subset of the defined objects."
|
|
GROUP epduNotifyGroup
|
|
DESCRIPTION
|
|
"Different ePDUs will support a subset of the defined notifications."
|
|
::= { conformance 1 }
|
|
|
|
epduRequiredGroup OBJECT-GROUP
|
|
OBJECTS { unitName,
|
|
firmwareVersion }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimal objects are required to conform to this MIB."
|
|
::= { objectGroups 1 }
|
|
|
|
epduOptionalGroup OBJECT-GROUP
|
|
OBJECTS { clockValue,
|
|
commInterface,
|
|
communicationStatus,
|
|
contactCount,
|
|
contactIndex,
|
|
contactName,
|
|
contactProbeStatus,
|
|
contactState,
|
|
groupBreakerStatus,
|
|
groupChildCount,
|
|
groupChildOID,
|
|
groupChildType,
|
|
groupColor,
|
|
groupControlOnCmd,
|
|
groupControlOffCmd,
|
|
groupControlRebootCmd,
|
|
groupControlStatus,
|
|
groupCount,
|
|
groupCurrent,
|
|
groupCurrentCapacity,
|
|
groupCurrentCrestFactor,
|
|
groupCurrentPercentLoad,
|
|
groupCurrentThLowerCritical,
|
|
groupCurrentThLowerWarning,
|
|
groupCurrentThStatus,
|
|
groupCurrentThUpperCritical,
|
|
groupCurrentThUpperWarning,
|
|
groupDesignator,
|
|
groupID,
|
|
groupIndex,
|
|
groupInputIndex,
|
|
groupName,
|
|
groupPowerFactor,
|
|
groupType,
|
|
groupVA,
|
|
groupVAR,
|
|
groupVoltage,
|
|
groupVoltageMeasType,
|
|
groupVoltageThLowerCritical,
|
|
groupVoltageThLowerWarning,
|
|
groupVoltageThStatus,
|
|
groupVoltageThUpperCritical,
|
|
groupVoltageThUpperWarning,
|
|
groupWatts,
|
|
groupWh,
|
|
groupWhTimer,
|
|
humidityCount,
|
|
humidityIndex,
|
|
humidityName,
|
|
humidityProbeStatus,
|
|
humidityThLowerCritical,
|
|
humidityThLowerWarning,
|
|
humidityThStatus,
|
|
humidityThUpperCritical,
|
|
humidityThUpperWarning,
|
|
humidityValue,
|
|
inputCount,
|
|
inputCurrent,
|
|
inputCurrentCapacity,
|
|
inputCurrentCount,
|
|
inputCurrentCrestFactor,
|
|
inputCurrentIndex,
|
|
inputCurrentMeasType,
|
|
inputCurrentPercentLoad,
|
|
inputCurrentThLowerCritical,
|
|
inputCurrentThLowerWarning,
|
|
inputCurrentThStatus,
|
|
inputCurrentThUpperCritical,
|
|
inputCurrentThUpperWarning,
|
|
inputFeedColor,
|
|
inputFeedName,
|
|
inputFrequency,
|
|
inputFrequencyStatus,
|
|
inputIndex,
|
|
inputPhaseDesignator,
|
|
inputPlugType,
|
|
inputPowerCapacity,
|
|
inputPowerCount,
|
|
inputPowerFactor,
|
|
inputPowerMeasType,
|
|
inputTotalPowerFactor,
|
|
inputTotalVA,
|
|
inputTotalVAR,
|
|
inputTotalWatts,
|
|
inputTotalWh,
|
|
inputTotalWhTimer,
|
|
inputType,
|
|
inputVA,
|
|
inputVAR,
|
|
inputVoltage,
|
|
inputVoltageCount,
|
|
inputVoltageIndex,
|
|
inputVoltageMeasType,
|
|
inputVoltageThLowerCritical,
|
|
inputVoltageThLowerWarning,
|
|
inputVoltageThStatus,
|
|
inputVoltageThUpperCritical,
|
|
inputVoltageThUpperWarning,
|
|
inputWatts,
|
|
inputWh,
|
|
inputWhTimer,
|
|
internalStatus,
|
|
lcdControl,
|
|
outletAutomaticShutoff,
|
|
outletControlSwitchable,
|
|
outletControlShutoffDelay,
|
|
outletControlOffCmd,
|
|
outletControlOnCmd,
|
|
outletControlPowerOnState,
|
|
outletControlRebootCmd,
|
|
outletControlRebootOffTime,
|
|
outletControlSequenceDelay,
|
|
outletControlStatus,
|
|
outletCount,
|
|
outletCurrent,
|
|
outletCurrentCapacity,
|
|
outletCurrentCrestFactor,
|
|
outletCurrentPercentLoad,
|
|
outletCurrentThLowerCritical,
|
|
outletCurrentThLowerWarning,
|
|
outletCurrentThStatus,
|
|
outletCurrentThUpperCritical,
|
|
outletCurrentThUpperWarning,
|
|
outletDesignator,
|
|
outletID,
|
|
outletIndex,
|
|
outletName,
|
|
outletParentCount,
|
|
outletParentOID,
|
|
outletParentType,
|
|
outletPhaseID,
|
|
outletPowerFactor,
|
|
outletType,
|
|
outletVA,
|
|
outletVAR,
|
|
outletVoltage,
|
|
outletVoltageThLowerCritical,
|
|
outletVoltageThLowerWarning,
|
|
outletVoltageThStatus,
|
|
outletVoltageThUpperCritical,
|
|
outletVoltageThUpperWarning,
|
|
outletWatts,
|
|
outletWh,
|
|
outletWhTimer,
|
|
partNumber,
|
|
productName,
|
|
serialNumber,
|
|
strappingIndex,
|
|
strappingStatus,
|
|
systemType,
|
|
temperatureCount,
|
|
temperatureIndex,
|
|
temperatureName,
|
|
temperatureProbeStatus,
|
|
temperatureScale,
|
|
temperatureThLowerCritical,
|
|
temperatureThLowerWarning,
|
|
temperatureThStatus,
|
|
temperatureThUpperCritical,
|
|
temperatureThUpperWarning,
|
|
temperatureValue,
|
|
unitControlOffCmd,
|
|
unitControlOnCmd,
|
|
unitName,
|
|
unitsPresent,
|
|
unitType,
|
|
userName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Most objects in this MIB are optional."
|
|
::= { objectGroups 2 }
|
|
|
|
epduNotifyGroup NOTIFICATION-GROUP
|
|
NOTIFICATIONS { notifyBootUp,
|
|
notifyCommunicationStatus,
|
|
notifyContactState,
|
|
notifyFailedLogin,
|
|
notifyGroupCurrentThStatus,
|
|
notifyGroupVoltageThStatus,
|
|
notifyGroupBreakerStatus,
|
|
notifyHumidityThStatus,
|
|
notifyInputCurrentThStatus,
|
|
notifyInputFrequencyStatus,
|
|
notifyInputVoltageThStatus,
|
|
notifyInternalStatus,
|
|
notifyOutletControlStatus,
|
|
notifyOutletCurrentThStatus,
|
|
notifyOutletVoltageThStatus,
|
|
notifyProbeStatus,
|
|
notifyStrappingStatus,
|
|
notifyTemperatureThStatus,
|
|
notifyTest,
|
|
notifyUserLogin,
|
|
notifyUserLogout }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"These notifications will be supported depending on the features of the ePDU.
|
|
Check the web interface for options to turn these notifications on/off. If
|
|
an option is not listed, then the ePDU likely does not support that
|
|
notification."
|
|
::= { objectGroups 3 }
|
|
END
|
|
|
|
|
|