| EATON-SENSOR-MIB DEFINITIONS ::= BEGIN
 | |
| 
 | |
| IMPORTS
 | |
|     OBJECT-TYPE, NOTIFICATION-TYPE, MODULE-IDENTITY, 
 | |
|     Counter32, Integer32
 | |
|         FROM SNMPv2-SMI
 | |
|     NOTIFICATION-GROUP, OBJECT-GROUP, MODULE-COMPLIANCE
 | |
|         FROM SNMPv2-CONF
 | |
|     TEXTUAL-CONVENTION
 | |
|         FROM SNMPv2-TC
 | |
|     sensorAgent
 | |
|         FROM EATON-OIDS;
 | |
| 
 | |
| eatonSensor MODULE-IDENTITY
 | |
|     LAST-UPDATED "201812171200Z"
 | |
|     ORGANIZATION 
 | |
|         "Eaton Corporation"
 | |
|     CONTACT-INFO 
 | |
|         "http://powerquality.eaton.com"
 | |
|     DESCRIPTION 
 | |
|         "The MIB module for Eaton Sensors."
 | |
|     REVISION "201812171200Z"
 | |
|     DESCRIPTION 
 | |
|         "Initial release."
 | |
| ::= { sensorAgent 1 }
 | |
| 
 | |
| -- eatonSensor { iso org(3) dod(6) internet(1) private(4)
 | |
| --       enterprises(1) eaton(534) products(6) sensorAgent(8) (1) }
 | |
| 
 | |
| sensor               OBJECT IDENTIFIER ::= { eatonSensor 1 }
 | |
| temperature          OBJECT IDENTIFIER ::= { eatonSensor 2 }
 | |
| humidity             OBJECT IDENTIFIER ::= { eatonSensor 3 }
 | |
| digitalInput         OBJECT IDENTIFIER ::= { eatonSensor 4 }
 | |
| conformance          OBJECT IDENTIFIER ::= { eatonSensor 10 }
 | |
| 
 | |
| -- Textual Conventions
 | |
| UnixTimeStamp ::= TEXTUAL-CONVENTION
 | |
|     DISPLAY-HINT      "dddddddddd"
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Unix time stamp. Measured in seconds since January 1, 1970."
 | |
|     SYNTAX  Counter32
 | |
| 
 | |
| PositionType ::= TEXTUAL-CONVENTION
 | |
|     STATUS  current
 | |
|     DESCRIPTION "Describes the position by reference to the data center aisle."
 | |
|     SYNTAX  INTEGER {
 | |
|         undefined(0),
 | |
|         other(1),
 | |
|         rackRear(2),
 | |
|         rackFront(3),
 | |
|         batteryRoom(4)
 | |
|         }
 | |
| 
 | |
| ElevationType ::= TEXTUAL-CONVENTION
 | |
|     STATUS  current
 | |
|     DESCRIPTION "Describes the elevation in the rack."
 | |
|     SYNTAX  INTEGER {
 | |
|         undefined(0),
 | |
|         other(1),
 | |
|         bottom(2),
 | |
|         middle(3),
 | |
|         top(4)
 | |
|         }
 | |
| 
 | |
| CommunicationStatus ::= TEXTUAL-CONVENTION
 | |
|     STATUS  current
 | |
|     DESCRIPTION "Describes the communication sensor status or probe status."
 | |
|     SYNTAX  INTEGER {
 | |
|         unknown(0),
 | |
|         communicationOK(2),
 | |
|         communicationLost(3)
 | |
|         }
 | |
| 
 | |
| ProbeConnectionType ::= TEXTUAL-CONVENTION
 | |
|     STATUS  current
 | |
|     DESCRIPTION "Describes the probe connection to the sensor or probe."
 | |
|     SYNTAX  INTEGER {
 | |
|         undefined(0),
 | |
|         internal(1),
 | |
|         wired(2),
 | |
|         wireless(3)
 | |
|         }
 | |
| 
 | |
| EnableType ::= TEXTUAL-CONVENTION
 | |
|     STATUS  current
 | |
|     DESCRIPTION "Describes enable/disable."
 | |
|     SYNTAX  INTEGER {
 | |
|         disabled(0),
 | |
|         enabled(1)
 | |
|         }
 | |
| 
 | |
| AlarmType ::= TEXTUAL-CONVENTION
 | |
|     STATUS  current
 | |
|     DESCRIPTION "Describes the alarm according to a measured value by reference to the triggers."
 | |
|     SYNTAX  INTEGER {
 | |
|         good(0),
 | |
|         lowWarning(1),
 | |
|         lowCritical(2),
 | |
|         highWarning(3),
 | |
|         highCritical(4)
 | |
|         }
 | |
| 
 | |
| ResetCommandType ::= TEXTUAL-CONVENTION
 | |
|     STATUS  current
 | |
|     DESCRIPTION "Commands a reset."
 | |
|     SYNTAX  INTEGER {
 | |
|         none(0),
 | |
|         reset(1)
 | |
|         }
 | |
| 
 | |
| PolarityType ::= TEXTUAL-CONVENTION
 | |
|     STATUS  current
 | |
|     DESCRIPTION "Describes the polarity configuration."
 | |
|     SYNTAX  INTEGER {
 | |
|         normallyOpened(0),
 | |
|         normallyClosed(1)
 | |
|         }
 | |
| 
 | |
| AlarmSeverityType ::= TEXTUAL-CONVENTION
 | |
|     STATUS  current
 | |
|     DESCRIPTION "Describes the alarm severity."
 | |
|     SYNTAX  INTEGER {
 | |
|         informationnal(1),
 | |
|         warning(2),
 | |
|         critical(3)
 | |
|         }
 | |
| 
 | |
| AlarmLevelType ::= TEXTUAL-CONVENTION
 | |
|     STATUS  current
 | |
|     DESCRIPTION "Describes the alarm level."
 | |
|     SYNTAX  INTEGER {
 | |
|         good(0),
 | |
|         informationnal(1),
 | |
|         warning(2),
 | |
|         critical(3)
 | |
|         }
 | |
| 
 | |
| StateType ::= TEXTUAL-CONVENTION
 | |
|     STATUS  current
 | |
|     DESCRIPTION "Describes the state of a digital input that depends on its measure
 | |
|                  and the polrity configuration."
 | |
|     SYNTAX  INTEGER {
 | |
|         inactive(0),
 | |
|         active(1)
 | |
|         }
 | |
| 
 | |
| TemperatureUnitType ::= TEXTUAL-CONVENTION
 | |
|     STATUS  current
 | |
|     DESCRIPTION "Describes the temperature unit used to read/write the temperature data."
 | |
|     SYNTAX  INTEGER {
 | |
|         tenthOfDegKelvin(0),
 | |
|         tenthOfDegCelsius(1),
 | |
|         tenthOfDegFarhenheit(2)
 | |
|         }
 | |
| 
 | |
| -- -----------------------------------------------------------------------------
 | |
| 
 | |
| sensorCount  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Number of sensor managed on this device."
 | |
|     ::= { sensor 1 }
 | |
| 
 | |
| sensorIdentificationTable  OBJECT-TYPE
 | |
|     SYNTAX SEQUENCE OF SensorIdentificationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A list of sensor devices identification data.
 | |
|          The number of entries is given by sensorCount."
 | |
|     ::= { sensor  2}
 | |
| 
 | |
| sensorIdentificationEntry  OBJECT-TYPE
 | |
|     SYNTAX     SensorIdentificationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "An entry for a sensor device identification."
 | |
|     INDEX { sensorIndex }
 | |
|     ::= { sensorIdentificationTable 1 }
 | |
| 
 | |
| SensorIdentificationEntry ::= SEQUENCE {
 | |
|     sensorIndex
 | |
|         Integer32,
 | |
|     sensorUuid
 | |
|         OCTET STRING,
 | |
|     sensorConnectionType
 | |
|         ProbeConnectionType,
 | |
|     sensorAddress
 | |
|         OCTET STRING,
 | |
|     sensorMonitoredBy
 | |
|         OBJECT IDENTIFIER,
 | |
|     sensorManufacturer
 | |
|         OCTET STRING,
 | |
|     sensorModel
 | |
|         OCTET STRING,
 | |
|     sensorPartNumber
 | |
|         OCTET STRING,
 | |
|     sensorSerialNumber
 | |
|         OCTET STRING,
 | |
|     sensorFirmwareVersion
 | |
|         OCTET STRING
 | |
| }
 | |
| 
 | |
| sensorIndex  OBJECT-TYPE
 | |
|     SYNTAX     Integer32 (1..3)
 | |
|     MAX-ACCESS accessible-for-notify
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A unique value for each sensor device.  Its value
 | |
|          ranges from 1 to sensorCount."
 | |
|     ::= { sensorIdentificationEntry 1 }
 | |
| 
 | |
| sensorUuid  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A unique uuid value for each sensor device."
 | |
|     ::= { sensorIdentificationEntry 2 }
 | |
| 
 | |
| sensorConnectionType  OBJECT-TYPE
 | |
|     SYNTAX     ProbeConnectionType
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Sensor connection type with the device that monitors it."
 | |
|     ::= { sensorIdentificationEntry 3 }
 | |
| 
 | |
| sensorAddress  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Depending of the connection implementation : Modbus Slave Id, BT Mac address, ..."
 | |
|     ::= { sensorIdentificationEntry 4 }
 | |
| 
 | |
| sensorMonitoredBy  OBJECT-TYPE
 | |
|     SYNTAX     OBJECT IDENTIFIER
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Parent oid device where the sensor is connected to and monitored by."
 | |
|     ::= { sensorIdentificationEntry 5 }
 | |
| 
 | |
| sensorManufacturer  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING (SIZE(1..31))
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The vendor name of the sensor device."
 | |
|     ::= { sensorIdentificationEntry 6 }
 | |
| 
 | |
| sensorModel  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING (SIZE(1..31))
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The model name of the sensor device."
 | |
|     ::= { sensorIdentificationEntry 7 }
 | |
| 
 | |
| sensorPartNumber  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING (SIZE(1..31))
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The catalog part number of the sensor device."
 | |
|     ::= { sensorIdentificationEntry 8 }
 | |
| 
 | |
| sensorSerialNumber  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING (SIZE(1..31))
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The serial number of the sensor device."
 | |
|     ::= { sensorIdentificationEntry 9 }
 | |
| 
 | |
| sensorFirmwareVersion  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING (SIZE(1..31))
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The firmware version of the sensor device."
 | |
|     ::= { sensorIdentificationEntry 10 }
 | |
| 
 | |
| 
 | |
| sensorConfigurationTable  OBJECT-TYPE
 | |
|     SYNTAX SEQUENCE OF SensorConfigurationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A list of sensor devices configuration data.
 | |
|          The number of entries is given by sensorCount."
 | |
|     ::= { sensor 3 }
 | |
| 
 | |
| sensorConfigurationEntry  OBJECT-TYPE
 | |
|     SYNTAX     SensorConfigurationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "An entry for a sensor device configuration."
 | |
|     INDEX { sensorIndex }
 | |
|     ::= { sensorConfigurationTable 1 }
 | |
| 
 | |
| SensorConfigurationEntry ::= SEQUENCE {
 | |
|     sensorName
 | |
|         OCTET STRING,
 | |
|     sensorLocation
 | |
|         OCTET STRING,
 | |
|     sensorPosition
 | |
|         PositionType,
 | |
|     sensorElevation
 | |
|         ElevationType,
 | |
|     sensorUElevation
 | |
|         Integer32
 | |
| }
 | |
| 
 | |
| sensorName  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING (SIZE(1..31))
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The friendly name of the sensor device."
 | |
|     ::= { sensorConfigurationEntry 1 }
 | |
| 
 | |
| sensorLocation  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING (SIZE(1..31))
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The location of the sensor device."
 | |
|     ::= { sensorConfigurationEntry 2 }
 | |
|   
 | |
| sensorPosition  OBJECT-TYPE
 | |
|     SYNTAX     PositionType
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The Position by reference to the data center aisle."
 | |
|     ::= { sensorConfigurationEntry 3 }
 | |
| 
 | |
| sensorElevation  OBJECT-TYPE
 | |
|     SYNTAX     ElevationType
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The Elevation in the rack."
 | |
|     ::= { sensorConfigurationEntry 4 }
 | |
|   
 | |
| sensorUElevation  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The elevation in the rack in count of U position from the bottom."
 | |
|     ::= { sensorConfigurationEntry 5 }
 | |
| 
 | |
| 
 | |
| sensorMonitoringTable  OBJECT-TYPE
 | |
|     SYNTAX SEQUENCE OF SensorMonitoringEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A list of sensor devices monitoring data.
 | |
|          The number of entries is given by sensorCount."
 | |
|     ::= { sensor 4 }
 | |
| 
 | |
| sensorMonitoringEntry  OBJECT-TYPE
 | |
|     SYNTAX     SensorMonitoringEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "An entry for a sensor device monitoring."
 | |
|     INDEX { sensorIndex }
 | |
|     ::= { sensorMonitoringTable 1 }
 | |
| 
 | |
| SensorMonitoringEntry ::= SEQUENCE {
 | |
|     sensorStatus
 | |
|         CommunicationStatus,
 | |
|     sensorStatusSince
 | |
|         UnixTimeStamp,
 | |
|     sensorTemperatureCount
 | |
|         Integer32,
 | |
|     sensorHumidityCount
 | |
|         Integer32,
 | |
|     sensorDigitalInputCount
 | |
|         Integer32,
 | |
|     sensorAnalogInputCount
 | |
|         Integer32
 | |
| }
 | |
| 
 | |
| sensorStatus  OBJECT-TYPE
 | |
|     SYNTAX     CommunicationStatus
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Indicates how the sensor is communicating or not."
 | |
|     ::= { sensorMonitoringEntry 1 }
 | |
| 
 | |
| sensorStatusSince  OBJECT-TYPE
 | |
|     SYNTAX     UnixTimeStamp
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "UTC time in seconds since 1970/01/01 dating the sensor status last change."
 | |
|     ::= { sensorMonitoringEntry 2 }
 | |
| 
 | |
| sensorTemperatureCount  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Number of temperature probes managed by the sensor device."
 | |
|     ::= { sensorMonitoringEntry 3 }
 | |
| 
 | |
| sensorHumidityCount  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Number of humidity probes managed by the sensor device."
 | |
|     ::= { sensorMonitoringEntry 4 }
 | |
| 
 | |
| sensorDigitalInputCount  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Number of digital input probes managed by the sensor device."
 | |
|     ::= { sensorMonitoringEntry 5 }
 | |
| 
 | |
| sensorAnalogInputCount  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Number of analog input probes managed by the sensor device."
 | |
|     ::= { sensorMonitoringEntry 6 }
 | |
| 
 | |
| sensorNotification OBJECT IDENTIFIER ::= { sensor 0 }
 | |
| 
 | |
| notifySensorCount  NOTIFICATION-TYPE
 | |
|     OBJECTS { sensorCount }
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Sent whenever the sensor count changes after a discovery or removing 
 | |
|          from the UI."
 | |
|     ::= { sensorNotification 1 }
 | |
| 
 | |
| notifySensorStatus  NOTIFICATION-TYPE
 | |
|     OBJECTS { sensorIndex,
 | |
|               sensorUuid,
 | |
|               sensorStatus,
 | |
|               sensorStatusSince }
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Sent whenever the sensor status changes."
 | |
|     ::= { sensorNotification 2 }
 | |
| 
 | |
| -- -----------------------------------------------------------------------------
 | |
| 
 | |
| temperatureIdentificationTable  OBJECT-TYPE
 | |
|     SYNTAX SEQUENCE OF TemperatureIdentificationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A list of temperature probe measurements. the number of entries
 | |
|          is given by the temperature count."
 | |
|     ::= { temperature 1 }
 | |
| 
 | |
| temperatureIdentificationEntry  OBJECT-TYPE
 | |
|     SYNTAX     TemperatureIdentificationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "An entry for a temperature probe identification."
 | |
|     INDEX { sensorIndex, temperatureIndex }
 | |
|     ::= { temperatureIdentificationTable 1 }
 | |
| 
 | |
| TemperatureIdentificationEntry ::= SEQUENCE {
 | |
|     temperatureIndex
 | |
|         Integer32,
 | |
|     temperatureUuid
 | |
|         OCTET STRING,
 | |
|     temperatureConnectionType
 | |
|         ProbeConnectionType
 | |
| }
 | |
| 
 | |
| temperatureIndex  OBJECT-TYPE
 | |
|     SYNTAX     Integer32 (1..2)
 | |
|     MAX-ACCESS accessible-for-notify
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A unique value for each temperature probe measurement.  Its value
 | |
|               ranges from 1 to sensorTemperatureCount."
 | |
|     ::= { temperatureIdentificationEntry 1 }
 | |
| 
 | |
| temperatureUuid  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A unique uuid value for each temperature."
 | |
|     ::= { temperatureIdentificationEntry 2 }
 | |
| 
 | |
| temperatureConnectionType  OBJECT-TYPE
 | |
|     SYNTAX     ProbeConnectionType
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Probe connection type with the sensor that monitors it."
 | |
|     ::= { temperatureIdentificationEntry 3 }
 | |
| 
 | |
| 
 | |
| temperatureConfigurationTable  OBJECT-TYPE
 | |
|     SYNTAX SEQUENCE OF TemperatureConfigurationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A list of temperature probe configuration.  The number of entries is
 | |
|               given by sensorTemperatureCount."
 | |
|     ::= { temperature 2 }
 | |
| 
 | |
| temperatureConfigurationEntry  OBJECT-TYPE
 | |
|     SYNTAX     TemperatureConfigurationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "An entry for a temperature probe configuration."
 | |
|     INDEX { sensorIndex, temperatureIndex }
 | |
|     ::= { temperatureConfigurationTable 1 }
 | |
| 
 | |
| TemperatureConfigurationEntry ::= SEQUENCE {
 | |
|     temperatureName
 | |
|         OCTET STRING,
 | |
|     temperatureEnable
 | |
|         EnableType,
 | |
|     temperatureOffset
 | |
|         Integer32,
 | |
|     temperatureAlarmEnable
 | |
|         EnableType,
 | |
|     temperatureThresholdLowWarning
 | |
|          Integer32,
 | |
|     temperatureThresholdLowCritical
 | |
|          Integer32,
 | |
|     temperatureThresholdHighWarning
 | |
|          Integer32,
 | |
|     temperatureThresholdHighCritical
 | |
|          Integer32,
 | |
|     temperatureThresholdHysteresis
 | |
|          Integer32,
 | |
|     temperatureAlarmGracePeriod
 | |
|          Integer32
 | |
| }
 | |
| 
 | |
| temperatureName  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING (SIZE(1..31))
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The friendly name of the sensor temperature probe."
 | |
|     ::= { temperatureConfigurationEntry 1 }
 | |
| 
 | |
| temperatureEnable  OBJECT-TYPE
 | |
|     SYNTAX     EnableType
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Configure the temperature acquired or not.
 | |
|          0:disabled, 1:enabled"
 | |
|     ::= { temperatureConfigurationEntry 2 }
 | |
| 
 | |
| temperatureOffset  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Configure the offset (Minus or Plus) to be added to the acquired value
 | |
|          in order to correct the probe measurement error.
 | |
|          See temperatureUnit data for the units."
 | |
|     ::= { temperatureConfigurationEntry 3 }
 | |
| 
 | |
| temperatureAlarmEnable  OBJECT-TYPE
 | |
|     SYNTAX     EnableType
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Configure the temperature alarm depending on the thresholds evaluated or not.
 | |
|          0:disabled, 1:enabled"
 | |
|     ::= { temperatureConfigurationEntry 4 }
 | |
| 
 | |
| temperatureThresholdLowWarning  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Low warning temperature threshold.
 | |
|          See temperatureUnit data for the units."
 | |
|     ::= { temperatureConfigurationEntry 5 }
 | |
| 
 | |
| temperatureThresholdLowCritical  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Low critical temperature threshold.
 | |
|          See temperatureUnit data for the units."
 | |
|     ::= { temperatureConfigurationEntry 6 }
 | |
| 
 | |
| temperatureThresholdHighWarning  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "High warning temperature threshold.
 | |
|          See temperatureUnit data for the units."
 | |
|     ::= { temperatureConfigurationEntry 7 }
 | |
| 
 | |
| temperatureThresholdHighCritical  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "High critical temperature threshold.
 | |
|          See temperatureUnit data for the units."
 | |
|     ::= { temperatureConfigurationEntry 8 }
 | |
| 
 | |
| temperatureThresholdHysteresis  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Temperature threshold hysteresis.
 | |
|          See temperatureUnit data for the units."
 | |
|     ::= { temperatureConfigurationEntry 9 }
 | |
| 
 | |
| temperatureAlarmGracePeriod  OBJECT-TYPE
 | |
|     SYNTAX     Integer32 (1..60)
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The grace period the alarm triggers after the acquired value crosses
 | |
|          a trigger value (in seconds)."
 | |
|     ::= { temperatureConfigurationEntry 10 }
 | |
| 
 | |
| 
 | |
| temperatureMonitoringTable  OBJECT-TYPE
 | |
|     SYNTAX SEQUENCE OF TemperatureMonitoringEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A list of temperature probe monitoring.  The number of entries is
 | |
|          given by sensorTemperatureCount."
 | |
|     ::= { temperature 3 }
 | |
| 
 | |
| temperatureMonitoringEntry  OBJECT-TYPE
 | |
|     SYNTAX     TemperatureMonitoringEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "An entry for a temperature probe monitoring."
 | |
|     INDEX { sensorIndex, temperatureIndex }
 | |
|     ::= { temperatureMonitoringTable 1 }
 | |
| 
 | |
| TemperatureMonitoringEntry ::= SEQUENCE {
 | |
|     temperatureAlarm
 | |
|          AlarmType,
 | |
|     temperatureAlarmChangeSince
 | |
|          UnixTimeStamp,
 | |
|     temperatureValue
 | |
|          Integer32,
 | |
|     temperatureCommunicationStatus
 | |
|          CommunicationStatus,
 | |
|     temperatureCommunicationStatusSince
 | |
|          UnixTimeStamp
 | |
| }
 | |
| 
 | |
| temperatureAlarm  OBJECT-TYPE
 | |
|     SYNTAX     AlarmType
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Alarm set according to the realtime measure compared to the thresholds."
 | |
|     ::= { temperatureMonitoringEntry 1 }
 | |
| 
 | |
| temperatureAlarmChangeSince  OBJECT-TYPE
 | |
|     SYNTAX     UnixTimeStamp
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "UTC time in seconds since 1970/01/01 dating the temperature alarm last change."
 | |
|     ::= { temperatureMonitoringEntry 2 }
 | |
| 
 | |
| temperatureValue  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Realtime measured value after correction with the offset.
 | |
|          See temperatureUnit data for the units."
 | |
|     ::= { temperatureMonitoringEntry 3 }
 | |
| 
 | |
| temperatureCommunicationStatus  OBJECT-TYPE
 | |
|     SYNTAX     CommunicationStatus
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Indicates how the temperature probe is communicating or not."
 | |
|     ::= { temperatureMonitoringEntry 4 }
 | |
| 
 | |
| temperatureCommunicationStatusSince  OBJECT-TYPE
 | |
|     SYNTAX     UnixTimeStamp
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "UTC time in seconds since 1970/01/01 dating the temperature communication status last change."
 | |
|     ::= { temperatureMonitoringEntry 5 }
 | |
| 
 | |
| 
 | |
| temperatureMonitoringMinMaxTable  OBJECT-TYPE
 | |
|     SYNTAX SEQUENCE OF TemperatureMonitoringMinMaxEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A list of temperature probe monitoring Min and Max.  The number of entries is
 | |
|          given by sensorTemperatureCount."
 | |
|     ::= { temperature 4 }
 | |
| 
 | |
| temperatureMonitoringMinMaxEntry  OBJECT-TYPE
 | |
|     SYNTAX     TemperatureMonitoringMinMaxEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "An entry for a temperature probe monitoring Min and Max."
 | |
|     INDEX { sensorIndex, temperatureIndex }
 | |
|     ::= { temperatureMonitoringMinMaxTable 1 }
 | |
| 
 | |
| TemperatureMonitoringMinMaxEntry ::= SEQUENCE {
 | |
|     temperatureMinValue
 | |
|          Integer32,
 | |
|     temperatureMinValueSince
 | |
|          UnixTimeStamp,
 | |
|     temperatureMaxValue
 | |
|          Integer32,
 | |
|     temperatureMaxValueSince
 | |
|          UnixTimeStamp,
 | |
|     temperatureResetMinMax
 | |
|          ResetCommandType
 | |
| }
 | |
| 
 | |
| temperatureMinValue  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Minimum value registered since the 1st connection of the sensor or the last reset.
 | |
|          See temperatureUnit data for the units."
 | |
|     ::= { temperatureMonitoringMinMaxEntry 1 }
 | |
| 
 | |
| temperatureMinValueSince  OBJECT-TYPE
 | |
|     SYNTAX     UnixTimeStamp
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "UTC time in seconds since 1970/01/01 dating the temperature min value last change."
 | |
|     ::= { temperatureMonitoringMinMaxEntry 2 }
 | |
| 
 | |
| temperatureMaxValue  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Maximum value registered since the 1st connection of the sensor or the last reset.
 | |
|          See temperatureUnit data for the units."
 | |
|     ::= { temperatureMonitoringMinMaxEntry 3 }
 | |
| 
 | |
| temperatureMaxValueSince  OBJECT-TYPE
 | |
|     SYNTAX     UnixTimeStamp
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "UTC time in seconds since 1970/01/01 dating the temperature max value last change."
 | |
|     ::= { temperatureMonitoringMinMaxEntry 4 }
 | |
| 
 | |
| temperatureResetMinMax  OBJECT-TYPE
 | |
|     SYNTAX     ResetCommandType
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Command that resets the min and max data with the current measure.
 | |
|          0:None, 1:Reset"
 | |
|     ::= { temperatureMonitoringMinMaxEntry 5 }
 | |
| 
 | |
| temperatureUnit  OBJECT-TYPE
 | |
|     SYNTAX     TemperatureUnitType
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Temperature unit configuration. It is a global setting for all the v1
 | |
|          and  v3 SNMP client. It does not involve the temperature unit of data
 | |
|          stored and managed in the card. But it does configure the unit the temperatures
 | |
|          data are red and written in this Mib.
 | |
|          The possible values are tenthOfDegCelsius(0), tenthOfDegFarhenheit(1),
 | |
|          tenthOfDegKelvin(2)."
 | |
|     ::= { temperature 5 }
 | |
| 
 | |
| 
 | |
| temperatureNotification OBJECT IDENTIFIER ::= { temperature 0 }
 | |
| 
 | |
| notifyTemperatureAlarm  NOTIFICATION-TYPE
 | |
|     OBJECTS { sensorIndex,
 | |
|               temperatureIndex,
 | |
|               temperatureUuid,
 | |
|               temperatureAlarm,
 | |
|               temperatureAlarmChangeSince,
 | |
|               temperatureValue }
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Sent whenever the temperature alarm changes."
 | |
|     ::= { temperatureNotification 1 }
 | |
| 
 | |
| notifyTemperatureCommunicationStatus  NOTIFICATION-TYPE
 | |
|     OBJECTS { sensorIndex,
 | |
|               temperatureIndex,
 | |
|               temperatureUuid,
 | |
|               temperatureCommunicationStatus,
 | |
|               temperatureCommunicationStatusSince }
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Sent whenever the temperature communication status changes.
 | |
|          Is not implemented when the probe is internal (see temperatureConnectionType)."
 | |
|     ::= { temperatureNotification 2 }
 | |
| 
 | |
| -- -----------------------------------------------------------------------------
 | |
| 
 | |
| 
 | |
| humidityIdentificationTable  OBJECT-TYPE
 | |
|     SYNTAX SEQUENCE OF HumidityIdentificationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A list of humidity probe measurements. the number of entries
 | |
|          is given by the humidity count."
 | |
|     ::= { humidity 1 }
 | |
| 
 | |
| humidityIdentificationEntry  OBJECT-TYPE
 | |
|     SYNTAX     HumidityIdentificationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "An entry for a humidity probe identification."
 | |
|     INDEX { sensorIndex, humidityIndex }
 | |
|     ::= { humidityIdentificationTable 1 }
 | |
| 
 | |
| HumidityIdentificationEntry ::= SEQUENCE {
 | |
|     humidityIndex
 | |
|         Integer32,
 | |
|     humidityUuid
 | |
|         OCTET STRING,
 | |
|     humidityConnectionType
 | |
|         ProbeConnectionType
 | |
| }
 | |
| 
 | |
| humidityIndex  OBJECT-TYPE
 | |
|     SYNTAX     Integer32 (1..2)
 | |
|     MAX-ACCESS accessible-for-notify
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A unique value for each humidity probe measurement.  Its value
 | |
|               ranges from 1 to sensorhumidityCount."
 | |
|     ::= { humidityIdentificationEntry 1 }
 | |
| 
 | |
| humidityUuid  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A unique uuid value for each humidity."
 | |
|     ::= { humidityIdentificationEntry 2 }
 | |
| 
 | |
| humidityConnectionType  OBJECT-TYPE
 | |
|     SYNTAX     ProbeConnectionType
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Probe connection type with the sensor that monitors it."
 | |
|     ::= { humidityIdentificationEntry 3 }
 | |
| 
 | |
| 
 | |
| humidityConfigurationTable  OBJECT-TYPE
 | |
|     SYNTAX SEQUENCE OF HumidityConfigurationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A list of humidity probe configuration.  The number of entries is
 | |
|               given by sensorhumidityCount."
 | |
|     ::= { humidity 2 }
 | |
| 
 | |
| humidityConfigurationEntry  OBJECT-TYPE
 | |
|     SYNTAX     HumidityConfigurationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "An entry for a humidity probe configuration."
 | |
|     INDEX { sensorIndex, humidityIndex }
 | |
|     ::= { humidityConfigurationTable 1 }
 | |
| 
 | |
| HumidityConfigurationEntry ::= SEQUENCE {
 | |
|     humidityName
 | |
|         OCTET STRING,
 | |
|     humidityEnable
 | |
|         EnableType,
 | |
|     humidityOffset
 | |
|         Integer32,
 | |
|     humidityAlarmEnable
 | |
|         EnableType,
 | |
|     humidityThresholdLowWarning
 | |
|          Integer32,
 | |
|     humidityThresholdLowCritical
 | |
|          Integer32,
 | |
|     humidityThresholdHighWarning
 | |
|          Integer32,
 | |
|     humidityThresholdHighCritical
 | |
|          Integer32,
 | |
|     humidityThresholdHysteresis
 | |
|          Integer32,
 | |
|     humidityAlarmGracePeriod
 | |
|          Integer32
 | |
| }
 | |
| 
 | |
| humidityName  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING (SIZE(1..31))
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The friendly name of the sensor humidity probe."
 | |
|     ::= { humidityConfigurationEntry 1 }
 | |
| 
 | |
| humidityEnable  OBJECT-TYPE
 | |
|     SYNTAX     EnableType
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Configure the humidity acquired or not.
 | |
|          0:disabled, 1:enabled"
 | |
|     ::= { humidityConfigurationEntry 2 }
 | |
| 
 | |
| humidityOffset  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Configure the offset (Minus or Plus) to be added to the acquired value
 | |
|          in order to correct the probe measurement error. in tenth of % units."
 | |
|     ::= { humidityConfigurationEntry 3 }
 | |
| 
 | |
| humidityAlarmEnable  OBJECT-TYPE
 | |
|     SYNTAX     EnableType
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Configure the humidity alarm depending on the thresholds evaluated or not.
 | |
|          0:disabled, 1:enabled"
 | |
|     ::= { humidityConfigurationEntry 4 }
 | |
| 
 | |
| humidityThresholdLowWarning  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Low warning humidity threshold in tenth of % units."
 | |
|     ::= { humidityConfigurationEntry 5 }
 | |
| 
 | |
| humidityThresholdLowCritical  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Low critical humidity threshold in tenth of % units."
 | |
|     ::= { humidityConfigurationEntry 6 }
 | |
| 
 | |
| humidityThresholdHighWarning  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "High warning humidity threshold in tenth of % units."
 | |
|     ::= { humidityConfigurationEntry 7 }
 | |
| 
 | |
| humidityThresholdHighCritical  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "High critical humidity threshold in tenth of % units."
 | |
|     ::= { humidityConfigurationEntry 8 }
 | |
| 
 | |
| humidityThresholdHysteresis  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "humidity threshold hysteresis in tenth of % units."
 | |
|     ::= { humidityConfigurationEntry 9 }
 | |
| 
 | |
| humidityAlarmGracePeriod  OBJECT-TYPE
 | |
|     SYNTAX     Integer32 (1..60)
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The grace period the alarm triggers after the acquired value crosses
 | |
|          a trigger value (in seconds)."
 | |
|     ::= { humidityConfigurationEntry 10 }
 | |
| 
 | |
| 
 | |
| humidityMonitoringTable  OBJECT-TYPE
 | |
|     SYNTAX SEQUENCE OF HumidityMonitoringEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A list of humidity probe monitoring.  The number of entries is
 | |
|          given by sensorhumidityCount."
 | |
|     ::= { humidity 3 }
 | |
| 
 | |
| humidityMonitoringEntry  OBJECT-TYPE
 | |
|     SYNTAX     HumidityMonitoringEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "An entry for a humidity probe monitoring."
 | |
|     INDEX { sensorIndex, humidityIndex }
 | |
|     ::= { humidityMonitoringTable 1 }
 | |
| 
 | |
| HumidityMonitoringEntry ::= SEQUENCE {
 | |
|     humidityAlarm
 | |
|          AlarmType,
 | |
|     humidityAlarmChangeSince
 | |
|          UnixTimeStamp,
 | |
|     humidityValue
 | |
|          Integer32,
 | |
|     humidityCommunicationStatus
 | |
|          CommunicationStatus,
 | |
|     humidityCommunicationStatusSince
 | |
|          UnixTimeStamp
 | |
| }
 | |
| 
 | |
| humidityAlarm  OBJECT-TYPE
 | |
|     SYNTAX     AlarmType
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Alarm set according to the realtime measure compared to the thresholds."
 | |
|     ::= { humidityMonitoringEntry 1 }
 | |
| 
 | |
| humidityAlarmChangeSince  OBJECT-TYPE
 | |
|     SYNTAX     UnixTimeStamp
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "UTC time in seconds since 1970/01/01 dating the humidity alarm last change."
 | |
|     ::= { humidityMonitoringEntry 2 }
 | |
| 
 | |
| humidityValue  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Realtime measured value after correction with the offset. in tenth of % units."
 | |
|     ::= { humidityMonitoringEntry 3 }
 | |
| 
 | |
| humidityCommunicationStatus  OBJECT-TYPE
 | |
|     SYNTAX     CommunicationStatus
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Indicates how the humidity probe is communicating or not."
 | |
|     ::= { humidityMonitoringEntry 4 }
 | |
| 
 | |
| humidityCommunicationStatusSince  OBJECT-TYPE
 | |
|     SYNTAX     UnixTimeStamp
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "UTC time in seconds since 1970/01/01 dating the humidity communication status last change."
 | |
|     ::= { humidityMonitoringEntry 5 }
 | |
| 
 | |
| 
 | |
| humidityMonitoringMinMaxTable  OBJECT-TYPE
 | |
|     SYNTAX SEQUENCE OF HumidityMonitoringMinMaxEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A list of humidity probe monitoring Min and Max.  The number of entries is
 | |
|          given by sensorhumidityCount."
 | |
|     ::= { humidity 4 }
 | |
| 
 | |
| humidityMonitoringMinMaxEntry  OBJECT-TYPE
 | |
|     SYNTAX     HumidityMonitoringMinMaxEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "An entry for a humidity probe monitoring Min and Max."
 | |
|     INDEX { sensorIndex, humidityIndex }
 | |
|     ::= { humidityMonitoringMinMaxTable 1 }
 | |
| 
 | |
| HumidityMonitoringMinMaxEntry ::= SEQUENCE {
 | |
|     humidityMinValue
 | |
|          Integer32,
 | |
|     humidityMinValueSince
 | |
|          UnixTimeStamp,
 | |
|     humidityMaxValue
 | |
|          Integer32,
 | |
|     humidityMaxValueSince
 | |
|          UnixTimeStamp,
 | |
|     humidityResetMinMax
 | |
|          ResetCommandType
 | |
| }
 | |
| 
 | |
| humidityMinValue  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Minimum value registered since the 1st connection of the sensor or the last reset.
 | |
|          in tenth of % units."
 | |
|     ::= { humidityMonitoringMinMaxEntry 1 }
 | |
| 
 | |
| humidityMinValueSince  OBJECT-TYPE
 | |
|     SYNTAX     UnixTimeStamp
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "UTC time in seconds since 1970/01/01 dating the humidity min value last change."
 | |
|     ::= { humidityMonitoringMinMaxEntry 2 }
 | |
| 
 | |
| humidityMaxValue  OBJECT-TYPE
 | |
|     SYNTAX     Integer32
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Maximum value registered since the 1st connection of the sensor or the last reset.
 | |
|          in tenth of % units."
 | |
|     ::= { humidityMonitoringMinMaxEntry 3 }
 | |
| 
 | |
| humidityMaxValueSince  OBJECT-TYPE
 | |
|     SYNTAX     UnixTimeStamp
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "UTC time in seconds since 1970/01/01 dating the humidity max value last change."
 | |
|     ::= { humidityMonitoringMinMaxEntry 4 }
 | |
| 
 | |
| humidityResetMinMax  OBJECT-TYPE
 | |
|     SYNTAX     ResetCommandType
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Command that resets the min and max data with the current measure.
 | |
|          0:None, 1:Reset"
 | |
|     ::= { humidityMonitoringMinMaxEntry 5 }
 | |
| 
 | |
| 
 | |
| humidityNotification OBJECT IDENTIFIER ::= { humidity 0 }
 | |
| 
 | |
| notifyHumidityAlarm  NOTIFICATION-TYPE
 | |
|     OBJECTS { sensorIndex,
 | |
|               humidityIndex,
 | |
|               humidityUuid,
 | |
|               humidityAlarm,
 | |
|               humidityAlarmChangeSince,
 | |
|               humidityValue }
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Sent whenever the humidity alarm changes."
 | |
|     ::= { humidityNotification 1 }
 | |
| 
 | |
| notifyHumidityCommunicationStatus  NOTIFICATION-TYPE
 | |
|     OBJECTS { sensorIndex,
 | |
|               humidityIndex,
 | |
|               humidityUuid,
 | |
|               humidityCommunicationStatus,
 | |
|               humidityCommunicationStatusSince }
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Sent whenever the humidity communication status changes.
 | |
|          Is not implemented when the probe is internal (see humidityConnectionType)."
 | |
|     ::= { humidityNotification 2 }
 | |
| 
 | |
| -- -----------------------------------------------------------------------------
 | |
| 
 | |
| 
 | |
| digitalInputIdentificationTable  OBJECT-TYPE
 | |
|     SYNTAX SEQUENCE OF DigitalInputIdentificationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A list of digital input probe measurements.  The number of entries is
 | |
|               given by sensorDigitalInputCount."
 | |
|     ::= { digitalInput 1 }
 | |
| 
 | |
| digitalInputIdentificationEntry  OBJECT-TYPE
 | |
|     SYNTAX     DigitalInputIdentificationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "An entry for a digital input identification."
 | |
|     INDEX { sensorIndex, digitalInputIndex }
 | |
|     ::= { digitalInputIdentificationTable 1 }
 | |
| 
 | |
| DigitalInputIdentificationEntry ::= SEQUENCE {
 | |
|     digitalInputIndex
 | |
|         Integer32,
 | |
|     digitalInputUuid
 | |
|         OCTET STRING,
 | |
|     digitalInputConnectionType
 | |
|         ProbeConnectionType
 | |
| }
 | |
| 
 | |
| digitalInputIndex  OBJECT-TYPE
 | |
|     SYNTAX     Integer32 (1..2)
 | |
|     MAX-ACCESS accessible-for-notify
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A unique value for each digital input probe measurement.  Its value
 | |
|               ranges from 1 to sensorDigitalInputCount."
 | |
|     ::= { digitalInputIdentificationEntry 1 }
 | |
| 
 | |
| digitalInputUuid  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A unique uuid value for each digital Input."
 | |
|     ::= { digitalInputIdentificationEntry 2 }
 | |
| 
 | |
| digitalInputConnectionType  OBJECT-TYPE
 | |
|     SYNTAX     ProbeConnectionType
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Probe connection type with the sensor that monitors it."
 | |
|     ::= { digitalInputIdentificationEntry 3 }
 | |
| 
 | |
| 
 | |
| digitalInputConfigurationTable  OBJECT-TYPE
 | |
|     SYNTAX SEQUENCE OF DigitalInputConfigurationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A list of digital input probe configuration.  The number of entries is
 | |
|               given by sensorDigitalInputCount."
 | |
|     ::= { digitalInput 2 }
 | |
| 
 | |
| digitalInputConfigurationEntry  OBJECT-TYPE
 | |
|     SYNTAX     DigitalInputConfigurationEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "An entry for a digital input probe configuration."
 | |
|     INDEX { sensorIndex, digitalInputIndex }
 | |
|     ::= { digitalInputConfigurationTable 1 }
 | |
| 
 | |
| DigitalInputConfigurationEntry ::= SEQUENCE {
 | |
|     digitalInputName
 | |
|         OCTET STRING,
 | |
|     digitalInputEnable
 | |
|         EnableType,
 | |
|     digitalInputPolarity
 | |
|         PolarityType,
 | |
|     digitalInputAlarmEnable
 | |
|         EnableType,
 | |
|     digitalInputAlarmSeverity
 | |
|         AlarmSeverityType,
 | |
|     digitalInputAlarmGracePeriod
 | |
|         Integer32
 | |
| }
 | |
| 
 | |
| digitalInputName  OBJECT-TYPE
 | |
|     SYNTAX     OCTET STRING (SIZE(1..31))
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The friendly name of the digital input probe."
 | |
|     ::= { digitalInputConfigurationEntry 1 }
 | |
| 
 | |
| digitalInputEnable  OBJECT-TYPE
 | |
|     SYNTAX     EnableType
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Configure the digital input acquired or not.
 | |
|          0:disabled, 1:enabled"
 | |
|     ::= { digitalInputConfigurationEntry 2 }
 | |
| 
 | |
| digitalInputPolarity  OBJECT-TYPE
 | |
|     SYNTAX     PolarityType
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Configure the digitalInput polarity.
 | |
|         0 : Normally opened, 1 : Normally closed"
 | |
|     ::= { digitalInputConfigurationEntry 3 }
 | |
| 
 | |
| digitalInputAlarmEnable  OBJECT-TYPE
 | |
|     SYNTAX     EnableType
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Configure the digitalInput alarm depending on the polarity evaluated or not.
 | |
|          0:disabled, 1:enabled"
 | |
|     ::= { digitalInputConfigurationEntry 4 }
 | |
| 
 | |
| digitalInputAlarmSeverity  OBJECT-TYPE
 | |
|     SYNTAX     AlarmSeverityType
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Configure the alarm severity."
 | |
|     ::= { digitalInputConfigurationEntry 5 }
 | |
| 
 | |
| digitalInputAlarmGracePeriod  OBJECT-TYPE
 | |
|     SYNTAX     Integer32 (1..60)
 | |
|     MAX-ACCESS read-write
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The delay the alarm triggers when the state change event occurs (in seconds)."
 | |
|     ::= { digitalInputConfigurationEntry 6 }
 | |
| 
 | |
| 
 | |
| digitalInputMonitoringTable  OBJECT-TYPE
 | |
|     SYNTAX SEQUENCE OF DigitalInputMonitoringEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "A list of digital input probee monitoring.  The number of entries is
 | |
|          given by sensorDigitalInputCount."
 | |
|     ::= { digitalInput 3 }
 | |
| 
 | |
| digitalInputMonitoringEntry  OBJECT-TYPE
 | |
|     SYNTAX     DigitalInputMonitoringEntry
 | |
|     MAX-ACCESS not-accessible
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "An entry for a digital Input probe."
 | |
|     INDEX { sensorIndex, digitalInputIndex }
 | |
|     ::= { digitalInputMonitoringTable 1 }
 | |
| 
 | |
| DigitalInputMonitoringEntry ::= SEQUENCE {
 | |
|     digitalInputAlarm
 | |
|          AlarmLevelType,
 | |
|     digitalInputAlarmChangeSince
 | |
|          UnixTimeStamp,
 | |
|     digitalInputState
 | |
|          Integer32,
 | |
|     digitalInputStateSince
 | |
|          UnixTimeStamp,
 | |
|     digitalInputCommunicationStatus
 | |
|          CommunicationStatus,
 | |
|     digitalInputCommunicationStatusSince
 | |
|          UnixTimeStamp
 | |
| }
 | |
| 
 | |
| digitalInputAlarm  OBJECT-TYPE
 | |
|     SYNTAX     AlarmLevelType
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Alarm set according to the polarity and alarm severity configuration."
 | |
|     ::= { digitalInputMonitoringEntry 1 }
 | |
| 
 | |
| digitalInputAlarmChangeSince  OBJECT-TYPE
 | |
|     SYNTAX     UnixTimeStamp
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "UTC time in seconds since 1970/01/01 dating the digital input alarm last change."
 | |
|     ::= { digitalInputMonitoringEntry 2 }
 | |
| 
 | |
| digitalInputState  OBJECT-TYPE
 | |
|     SYNTAX     StateType
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Measure of the digital input after applying the polarity configured.
 | |
|          0 : Inactive, 1 : Active"
 | |
|     ::= { digitalInputMonitoringEntry 3 }
 | |
| 
 | |
| digitalInputStateSince  OBJECT-TYPE
 | |
|     SYNTAX     UnixTimeStamp
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "UTC time in seconds since 1970/01/01 dating the digital input state last change."
 | |
|     ::= { digitalInputMonitoringEntry 4 }
 | |
| 
 | |
| digitalInputCommunicationStatus  OBJECT-TYPE
 | |
|     SYNTAX     CommunicationStatus
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Indicates how the digital input is communicating or not."
 | |
|     ::= { digitalInputMonitoringEntry 5 }
 | |
| 
 | |
| digitalInputCommunicationStatusSince  OBJECT-TYPE
 | |
|     SYNTAX     UnixTimeStamp
 | |
|     MAX-ACCESS read-only
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "UTC time in seconds since 1970/01/01 dating the digital input communication status last change."
 | |
|     ::= { digitalInputMonitoringEntry 6 }
 | |
| 
 | |
| 
 | |
| digitalInputNotification OBJECT IDENTIFIER ::= { digitalInput 0 }
 | |
| 
 | |
| notifyDigitalInputAlarm  NOTIFICATION-TYPE
 | |
|     OBJECTS { sensorIndex,
 | |
|               digitalInputIndex,
 | |
|               digitalInputUuid,
 | |
|               digitalInputAlarm,
 | |
|               digitalInputAlarmChangeSince,
 | |
|               digitalInputState,
 | |
|               digitalInputStateSince }
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Sent whenever the digital input alarm changes."
 | |
|     ::= { digitalInputNotification 1 }
 | |
| 
 | |
| notifydigitalInputCommunicationStatus  NOTIFICATION-TYPE
 | |
|     OBJECTS { sensorIndex,
 | |
|               digitalInputIndex,
 | |
|               digitalInputUuid,
 | |
|               digitalInputCommunicationStatus,
 | |
|               digitalInputCommunicationStatusSince }
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "Sent whenever the digital input communication status changes.
 | |
|          Is not implemented when the probe is internal (see digitalInputConnectionType)."
 | |
|     ::= { digitalInputNotification 2 }
 | |
| 
 | |
| 
 | |
| eatonSensorCompliances  MODULE-COMPLIANCE
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "The requirements for conforming to the Sensor MIB."
 | |
|     MODULE
 | |
|         MANDATORY-GROUPS { sensorRequiredGroup } 
 | |
|         GROUP sensorOptionalGroup
 | |
|         DESCRIPTION 
 | |
|         "Different sensors will support a subset of the defined objects."
 | |
|         GROUP sensorNotifyGroup
 | |
|         DESCRIPTION 
 | |
|         "Different sensors will support a subset of the defined notifications."
 | |
|     ::= { conformance 1 }
 | |
| 
 | |
| objectGroups         OBJECT IDENTIFIER ::= { conformance 2 }
 | |
| 
 | |
| sensorRequiredGroup  OBJECT-GROUP
 | |
|     OBJECTS { sensorCount,
 | |
|               sensorIndex,
 | |
|               sensorManufacturer,
 | |
|               sensorModel,
 | |
|               sensorPartNumber,
 | |
|               sensorSerialNumber,
 | |
|               sensorFirmwareVersion,
 | |
|               sensorName,
 | |
|               sensorStatus,
 | |
|               sensorStatusSince,
 | |
|               sensorTemperatureCount,
 | |
|               sensorHumidityCount,
 | |
|               sensorDigitalInputCount,
 | |
|               temperatureIndex,
 | |
|               temperatureName,
 | |
|               temperatureValue,
 | |
|               temperatureUnit,
 | |
|               humidityIndex,
 | |
|               humidityName,
 | |
|               humidityValue,
 | |
|               digitalInputIndex,
 | |
|               digitalInputName
 | |
|             }
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "These objects are required to conform to this MIB."
 | |
|     ::= { objectGroups 1 }
 | |
| 
 | |
| sensorOptionalGroup  OBJECT-GROUP
 | |
|     OBJECTS { sensorUuid,
 | |
|               sensorConnectionType,
 | |
|               sensorAddress,
 | |
|               sensorMonitoredBy,
 | |
|               sensorLocation,
 | |
|               sensorPosition,
 | |
|               sensorElevation,
 | |
|               sensorUElevation,
 | |
|               sensorAnalogInputCount,
 | |
|               temperatureUuid,
 | |
|               temperatureConnectionType,
 | |
|               temperatureEnable,
 | |
|               temperatureOffset,
 | |
|               temperatureAlarmEnable,                                                 
 | |
|               temperatureThresholdLowWarning,
 | |
|               temperatureThresholdLowCritical,
 | |
|               temperatureThresholdHighWarning,
 | |
|               temperatureThresholdHighCritical,
 | |
|               temperatureThresholdHysteresis,
 | |
|               temperatureAlarmGracePeriod,
 | |
|               temperatureAlarm,
 | |
|               temperatureAlarmChangeSince,
 | |
|               temperatureCommunicationStatus,
 | |
|               temperatureCommunicationStatusSince,
 | |
|               temperatureMinValue,
 | |
|               temperatureMinValueSince,
 | |
|               temperatureMaxValue,
 | |
|               temperatureMaxValueSince,
 | |
|               temperatureResetMinMax,
 | |
|               humidityUuid,
 | |
|               humidityConnectionType,
 | |
|               humidityEnable,
 | |
|               humidityOffset,
 | |
|               humidityAlarmEnable,                                                 
 | |
|               humidityThresholdLowWarning,
 | |
|               humidityThresholdLowCritical,
 | |
|               humidityThresholdHighWarning,
 | |
|               humidityThresholdHighCritical,
 | |
|               humidityThresholdHysteresis,
 | |
|               humidityAlarmGracePeriod,
 | |
|               humidityAlarm,
 | |
|               humidityAlarmChangeSince,
 | |
|               humidityCommunicationStatus,
 | |
|               humidityCommunicationStatusSince,
 | |
|               humidityMinValue,
 | |
|               humidityMinValueSince,
 | |
|               humidityMaxValue,
 | |
|               humidityMaxValueSince,
 | |
|               humidityResetMinMax,
 | |
|               digitalInputUuid,
 | |
|               digitalInputConnectionType,
 | |
|               digitalInputEnable,
 | |
|               digitalInputPolarity,
 | |
|               digitalInputAlarmEnable,                                                 
 | |
|               digitalInputAlarmSeverity,
 | |
|               digitalInputAlarmGracePeriod,
 | |
|               digitalInputState,
 | |
|               digitalInputStateSince,
 | |
|               digitalInputAlarm,
 | |
|               digitalInputAlarmChangeSince,
 | |
|               digitalInputCommunicationStatus,
 | |
|               digitalInputCommunicationStatusSince
 | |
|          }
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "These objects in this MIB are optional."
 | |
|     ::= { objectGroups 2 }
 | |
| 
 | |
| sensorNotifyGroup  NOTIFICATION-GROUP
 | |
|     NOTIFICATIONS { notifySensorStatus,
 | |
|                     notifySensorCount,
 | |
|                     notifyTemperatureAlarm,
 | |
|                     notifyTemperatureCommunicationStatus,
 | |
|                     notifyHumidityAlarm,
 | |
|                     notifyHumidityCommunicationStatus,
 | |
|                     notifyDigitalInputAlarm,
 | |
|                     notifydigitalInputCommunicationStatus
 | |
|          }
 | |
|     STATUS     current
 | |
|     DESCRIPTION 
 | |
|         "These notifications will be supported depending on the features of the sensor."
 | |
|     ::= { objectGroups 3 }
 | |
| 
 | |
| 
 | |
| END
 | 