3796 lines
155 KiB
Plaintext
3796 lines
155 KiB
Plaintext
ELTEK-BC2000-DC-POWER-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY
|
|
, OBJECT-TYPE
|
|
, NOTIFICATION-TYPE
|
|
, OBJECT-IDENTITY
|
|
, Counter32
|
|
, Gauge32
|
|
, Integer32
|
|
, enterprises
|
|
, IpAddress
|
|
-- , Gauge
|
|
FROM SNMPv2-SMI
|
|
|
|
Gauge
|
|
FROM RFC1155-SMI
|
|
|
|
DisplayString
|
|
, TimeStamp
|
|
-- , TimeInterval
|
|
-- , TestAndIncr
|
|
, AutonomousType
|
|
, TEXTUAL-CONVENTION
|
|
FROM SNMPv2-TC
|
|
|
|
-- MODULE-COMPLIANCE
|
|
-- , OBJECT-GROUP
|
|
-- FROM SNMPv2-CONF
|
|
|
|
-- sysUpTime
|
|
-- FROM RFC1213-MIB
|
|
;
|
|
|
|
--
|
|
-- date and time in UTC format YYYYMMDDHHmmZ
|
|
--
|
|
eltek MODULE-IDENTITY
|
|
LAST-UPDATED "201403271038Z"
|
|
ORGANIZATION "Eltek Inc."
|
|
CONTACT-INFO
|
|
"Contact: Eltek Customer Support
|
|
Postal: 2925 E. Plano Pkwy
|
|
Plano, TX-75074
|
|
Web: http://www.eltek.com
|
|
email: techsupport.us@eltek.com
|
|
Phone 800-435-4872
|
|
"
|
|
DESCRIPTION
|
|
"SNMP access to Eltek DC Power systems through the BC2000 controller."
|
|
REVISION "201403271038Z"
|
|
DESCRIPTION
|
|
" Need History here.
|
|
MIB Version 2.10
|
|
Final edits to PM (was TRIO) table (branch 17)
|
|
MIB Version 2.00
|
|
Synchronized with new release
|
|
MIB Version 0.97
|
|
Updated contact information
|
|
MIB Version 0.96
|
|
Changed LVD Timers to read-only. Write not supported in this release
|
|
MIB Version 0.95
|
|
Traps 70-72 added
|
|
Changed vpwrPMIndex variable to non negative integer
|
|
MIB Version 0.94
|
|
Fixed module inventory process
|
|
Removed unused module test groups
|
|
Removed unused thermal probe entries
|
|
Changed vpwrBoostDuration from Hours to Seconds
|
|
New traps 63-69 added, trap 99 unknown added
|
|
Corrected Ringer present MIB
|
|
MIB Version 0.93
|
|
Fixed spelling of vpwrBatteryCurrentCapacity
|
|
Fixed spelling of vpwrRingerAlarmAFailed
|
|
Fixed spelling of vpwrRingerAlarmBFailed
|
|
Fixed message with vpwrRingerAlarmBOverTemp
|
|
Fixed message with vpwrRingerAlarmBOverCurrent
|
|
Changed Centigrade to Celsius
|
|
Changed use of battety to battery throughout
|
|
Changed vpwrBDTDuration from 480 minutes to 1080
|
|
Updated settable ringer parameters
|
|
Spelling corrections
|
|
MIB Version 0.92
|
|
Fixed duplicate usage of vpwrTrapsMsgString
|
|
Fixed spelling of Gauge data type
|
|
MIB Version 0.91
|
|
Version 2 Traps
|
|
MIB Version 0.9
|
|
Sept 1, 06
|
|
New Table- System Alarm History
|
|
New Table- for BDT Result History
|
|
New Table- for AVESTOR Battery
|
|
|
|
New Traps -
|
|
Aux Alarm Source
|
|
Distribution Alarm Source
|
|
Battery Capacity Alarm
|
|
Battery Alarm Source
|
|
Battery SOC Trap
|
|
Battery SOH Trap
|
|
AC Fail Duration Trap
|
|
Battery Operational mode change
|
|
|
|
MIB Version 0.8
|
|
Add table to retrieve module inventory info
|
|
MIB Version 0.7
|
|
Dec 1, 05
|
|
Fixed HP Openview error
|
|
Fixed warnings generated by MG-SOFT
|
|
Add table to retrieve rectifier inventory info
|
|
MIB Version 0.6
|
|
Feb 10, 2004 Added additional traps.
|
|
Defined Ringers and other modules.
|
|
Feb 08, 2003 Changed vpwrTrapDestinationTable to vpwrTrapTable
|
|
Corrected entry for vpwrTrapTable to be VpwrTrapTableEntry
|
|
This fixes errors generated by MG-SOFT mib compiler.
|
|
Oct 30, 2002 initial release - version 0.4
|
|
"
|
|
|
|
::= {enterprises 13858}
|
|
|
|
PositiveInteger ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This data type is a non-zero and non-negative value."
|
|
SYNTAX Integer32 (1..2147483647)
|
|
|
|
NonNegativeInteger ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This data type is a non-negative value."
|
|
SYNTAX Integer32 (0..2147483647)
|
|
|
|
GenericEnableDisableTC ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The defines how was BDT started."
|
|
SYNTAX INTEGER {
|
|
disabled(0),
|
|
enabled(1)
|
|
}
|
|
|
|
SysInputValue ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"These are the results of the system input value definitions."
|
|
SYNTAX INTEGER {
|
|
disabled(-127),
|
|
removed(-126),
|
|
shorted(-125),
|
|
auxAlarm(-124),
|
|
auxNormal(-123),
|
|
distAlarm(-122),
|
|
distNormal(-121),
|
|
undefined(255)
|
|
-- (0..127)
|
|
}
|
|
|
|
-- BatteryOperModeTC ::= TEXTUAL-CONVENTION
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "The defines operational mode enumerations for the battery."
|
|
-- SYNTAX INTEGER {
|
|
-- batModeStandby (0),
|
|
-- batModeCharging(1),
|
|
-- batModeFloating(2),
|
|
-- batModeDischarging(3),
|
|
-- batModeNotAvailable(255)
|
|
-- }
|
|
|
|
VpwrPMCnfgValue ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"These are the results of the system input value definitions."
|
|
SYNTAX INTEGER {
|
|
disabled(0),
|
|
tProbe(1),
|
|
auxNO(2),
|
|
auxNC(3),
|
|
distNO(4),
|
|
distNC(5),
|
|
undefined(255)
|
|
}
|
|
|
|
|
|
-- BatteryOperStatusTC ::= TEXTUAL-CONVENTION
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "The defines operational mode
|
|
-- enumerations for the battery."
|
|
-- SYNTAX INTEGER {
|
|
-- batStatusOk (0),
|
|
-- batStatusMinorFault(1),
|
|
-- batStatusMajorFault(2),
|
|
-- batStatusNotAvailable(255)
|
|
-- }
|
|
|
|
|
|
BDTStartSourceTC ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The defines how was BDT started."
|
|
SYNTAX INTEGER {
|
|
bdtInactive(0),
|
|
bdtManualStart(1),
|
|
bdtSched01Start1(2),
|
|
bdtSched02Start2(3),
|
|
bdtSched03Start3(4),
|
|
bdtSched04Start4(5),
|
|
bdtSched05Start5(6),
|
|
bdtSched06Start6(7),
|
|
bdtSched07Start7(8),
|
|
bdtSched08Start8(9),
|
|
bdtSched09Start9(10),
|
|
bdtSched10Start10(11),
|
|
bdtSched11Start11(12),
|
|
bdtSched12Start12(13),
|
|
bdtACFailStart(14)
|
|
}
|
|
BDTResultTC ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The defines how was BDT started."
|
|
SYNTAX INTEGER {
|
|
bdtResultCleared(0),
|
|
bdtResultPassed(1),
|
|
bdtResultFailed(2),
|
|
bdtResultStopped(3),
|
|
bdtResultAborted(4),
|
|
bdtResultInProgress(5)
|
|
}
|
|
|
|
|
|
-- vpwrDcPowerProducts OBJECT IDENTIFIER ::= { eltek 1 }
|
|
vpwrDcPowerSystem OBJECT IDENTIFIER ::= { eltek 2 }
|
|
vpwrDcPowerRectifier OBJECT IDENTIFIER ::= { eltek 3 }
|
|
vpwrDcPowerLvd OBJECT IDENTIFIER ::= { eltek 4 }
|
|
-- vpwrDcPowerTest OBJECT IDENTIFIER ::= { eltek 5 }
|
|
vpwrDcPowerModuleIdent OBJECT IDENTIFIER ::= { eltek 6 }
|
|
vpwrDcPowerBatteryGroup OBJECT IDENTIFIER ::= { eltek 7 }
|
|
vpwrDcPowerAlarmGroup OBJECT IDENTIFIER ::= { eltek 8 }
|
|
vpwrDcPowerSnmpConfig OBJECT IDENTIFIER ::= { eltek 9 }
|
|
vpwrDcPowerTraps OBJECT IDENTIFIER ::= { eltek 10 }
|
|
vpwrDcPowerTrapVars OBJECT IDENTIFIER ::= { eltek 11 }
|
|
|
|
vpwrDcPowerRinger OBJECT IDENTIFIER ::= { eltek 12 }
|
|
vpwrDcPowerDcDcConverter OBJECT IDENTIFIER ::= { eltek 13 }
|
|
vpwrDcPowerDcAcInverter OBJECT IDENTIFIER ::= { eltek 14 }
|
|
vpwrDcPowerAcLineModule OBJECT IDENTIFIER ::= { eltek 15 }
|
|
vpwrDcPowerIoModule OBJECT IDENTIFIER ::= { eltek 16 }
|
|
|
|
vpwrDcPowerPMModule OBJECT IDENTIFIER ::= { eltek 17 }
|
|
vpwrDcPowerDistModule OBJECT IDENTIFIER ::= { eltek 18 }
|
|
vpwrDcPowerBattery OBJECT IDENTIFIER ::= { eltek 19 }
|
|
vpwrDcPowerController OBJECT IDENTIFIER ::= { eltek 20 }
|
|
vpwrDcPowerUnkModule OBJECT IDENTIFIER ::= { eltek 499 }
|
|
thirdPartyProduct OBJECT IDENTIFIER ::= { eltek 500 }
|
|
|
|
-- vpwrDcPowerTraps OBJECT IDENTIFIER ::= { vpwrDcPowerTrapsRoot 0 }
|
|
|
|
vpwrSystemIdentGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 1 }
|
|
vpwrSystemConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 2 }
|
|
vpwrSystemParameterGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 3 }
|
|
vpwrSystemPanelIdentGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 4 }
|
|
vpwrSystemHistoryGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 5 }
|
|
vpwrSystemAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerSystem 6 }
|
|
|
|
vpwrLvdConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerLvd 1 }
|
|
-- vpwrLvdAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerLvd 2 }
|
|
-- vpwrLvdTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerLvd 3 }
|
|
|
|
vpwrRectifierConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRectifier 1 }
|
|
vpwrRectifierAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRectifier 2 }
|
|
-- vpwrRectifierTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRectifier 3 }
|
|
|
|
vpwrBatteryTempGroup OBJECT IDENTIFIER ::= { vpwrDcPowerBatteryGroup 1 }
|
|
vpwrBatteryCurrentGroup OBJECT IDENTIFIER ::= { vpwrDcPowerBatteryGroup 2 }
|
|
vpwrBatteryBoostGroup OBJECT IDENTIFIER ::= { vpwrDcPowerBatteryGroup 3 }
|
|
vpwrBatteryDischargeTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerBatteryGroup 4 }
|
|
|
|
-- vpwrTrapsMsgString OBJECT IDENTIFIER ::= { vpwrDcPowerTrapVars 1 }
|
|
|
|
vpwrRingerConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRinger 1 }
|
|
vpwrRingerAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRinger 2 }
|
|
vpwrRingerTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerRinger 3 }
|
|
|
|
vpwrDcDcConverterConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcDcConverter 1 }
|
|
vpwrDcDcConverterAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcDcConverter 2 }
|
|
vpwrDcDcConverterTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcDcConverter 3 }
|
|
|
|
|
|
vpwrDcAcInverterConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcAcInverter 1 }
|
|
vpwrDcAcInverterAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcAcInverter 2 }
|
|
vpwrDcAcInverterTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerDcAcInverter 3 }
|
|
|
|
vpwrAcLineModuleConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerAcLineModule 1 }
|
|
vpwrAcLineModuleAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerAcLineModule 2 }
|
|
vpwrAcLineModuleTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerAcLineModule 3 }
|
|
|
|
vpwrIoModuleConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerIoModule 1 }
|
|
vpwrIoModuleAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerIoModule 2 }
|
|
vpwrIoModuleTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerIoModule 3 }
|
|
|
|
-- vpwrTrioModuleConfigGroup OBJECT IDENTIFIER ::= { vpwrDcPowerTrioModule 1 }
|
|
vpwrPMModuleAlarmGroup OBJECT IDENTIFIER ::= { vpwrDcPowerPMModule 4 }
|
|
vpwrPMModuleTestGroup OBJECT IDENTIFIER ::= { vpwrDcPowerPMModule 5 }
|
|
|
|
--
|
|
-- PM variables
|
|
--
|
|
|
|
--
|
|
-- Trap variables
|
|
--
|
|
|
|
vpwrTrapsMsgString OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (0..127))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Place holder for trap notification message string"
|
|
::= { vpwrDcPowerTrapVars 1 }
|
|
|
|
vpwrTrapUserIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Place holder for IP address of the user accessing the system"
|
|
::= { vpwrDcPowerTrapVars 2}
|
|
|
|
vpwrTrapAcfDuration OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Place holder for duration."
|
|
::= { vpwrDcPowerTrapVars 3}
|
|
|
|
vpwrAlarmingSubModuleBitMap OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"indices of alarming sources are encoded as a bit-map
|
|
e.g.,
|
|
source 1 and source 2 will be encoded as hex 3.
|
|
source 1 and 3 will be encoded as hex 5.
|
|
"
|
|
::= { vpwrDcPowerTrapVars 4 }
|
|
|
|
vpwrBatteryCurrentCapacity OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Place holder for total battery capacity"
|
|
::= { vpwrDcPowerTrapVars 5 }
|
|
|
|
vpwrAlarmingModuleIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"index of alarming module.
|
|
"
|
|
::= { vpwrDcPowerTrapVars 6 }
|
|
vpwrAlarmingModuleOID OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"It indicates the type of the module by specifiying its OID"
|
|
::= { vpwrDcPowerTrapVars 7}
|
|
|
|
vpwrAlarmingModuleBitMap OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"indices of alarming sources are encoded as a bit-map
|
|
e.g.,
|
|
source 1 and source 2 will be encoded as hex 3.
|
|
source 1 and 3 will be encoded as hex 5.
|
|
"
|
|
::= { vpwrDcPowerTrapVars 8 }
|
|
|
|
vpwrBatteryRemainingTime OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Place holder for remaining battery
|
|
time at the current load
|
|
"
|
|
::= { vpwrDcPowerTrapVars 9 }
|
|
--
|
|
-- The Identification group.
|
|
--
|
|
|
|
|
|
vpwrIdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the DC Power manufacturer."
|
|
::= { vpwrSystemIdentGroup 1 }
|
|
|
|
|
|
vpwrIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The DC Power Model designation."
|
|
::= { vpwrSystemIdentGroup 2 }
|
|
|
|
vpwrIdentControllerVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hardware/firmware version(s). This variable
|
|
may or may not have the same value as
|
|
vpwrIdentAgentSoftwareVersion."
|
|
::= { vpwrSystemIdentGroup 3 }
|
|
|
|
vpwrIdentAgentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The SNMP agent software version. This variable may or
|
|
may not have the same value as
|
|
vpwrIdentControllerVersion."
|
|
::= { vpwrSystemIdentGroup 4 }
|
|
|
|
vpwrIdentName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying the system. This object should be
|
|
set by the administrator."
|
|
::= { vpwrSystemIdentGroup 5 }
|
|
|
|
--
|
|
-- The System Identifier group.
|
|
-- All objects in this group are read-only. It describes
|
|
-- various modules (rectifiers, converters, ringers, LVDs, etc.) that make up
|
|
-- the power system and are inserted into a shelf(.1) or panel(.2)
|
|
--
|
|
vpwrSystemIdentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrSystemIdentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This table describes shelves and modules
|
|
that make up the sysetm.
|
|
"
|
|
::= { vpwrSystemIdentGroup 6 }
|
|
|
|
--
|
|
-- The System Identifier Entry. Defines the sequence for module tables.
|
|
--
|
|
vpwrSystemIdentEntry OBJECT-TYPE
|
|
SYNTAX VpwrSystemIdentEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular alarm."
|
|
INDEX { vpwrBayIndex, vpwrModuleIndex }
|
|
::= { vpwrSystemIdentTable 1 }
|
|
|
|
|
|
VpwrSystemIdentEntry ::= SEQUENCE {
|
|
vpwrBayIndex PositiveInteger,
|
|
vpwrModuleIndex PositiveInteger,
|
|
vpwrModuleOID OBJECT IDENTIFIER ,
|
|
vpwrModuleCurrent INTEGER ,
|
|
vpwrModuleOperStatus INTEGER ,
|
|
vpwrModuleCapacity INTEGER
|
|
}
|
|
|
|
--
|
|
-- The System Shelf Identifier group.
|
|
--
|
|
-- vpwrShelfIdentEntry OBJECT-TYPE
|
|
-- SYNTAX VpwrSystemIdentEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "An entry containing information applicable to a
|
|
-- particular module making up the system."
|
|
-- INDEX { vpwrBayIndex, vpwrModuleIndex }
|
|
-- ::= { vpwrSystemIdentTable 1 }
|
|
--
|
|
vpwrBayIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Identifies shelf number that this module belongs to.
|
|
The possible values are 1 through 16 limited by vpwrSystemShelfCapacity."
|
|
::= { vpwrSystemIdentEntry 1 }
|
|
|
|
vpwrModuleIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object identifies the module by its position in the shelf.
|
|
Module numbering is left to right starting with module 1. So, the
|
|
module in the first slot has an index of 1, the next module is 2 and
|
|
so on."
|
|
::= { vpwrSystemIdentEntry 2 }
|
|
|
|
vpwrModuleOID OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"It indicates the type of the module by specifiying its OID"
|
|
::= { vpwrSystemIdentEntry 3}
|
|
|
|
vpwrModuleCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The meaning of this object depends upon the module type
|
|
which is indicated by vpwrModuleOID as follows
|
|
- Current for Rectifier module in centiamps.
|
|
- Not Applicable for LVD module
|
|
"
|
|
::= { vpwrSystemIdentEntry 4}
|
|
|
|
vpwrModuleOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
moduleStatusOK(0),
|
|
moduleStatusAlarm(1),
|
|
moduleStatusDisabled(2),
|
|
moduleStatusRingerAOn(3),
|
|
moduleStatusRingerBOn(4),
|
|
moduleStatusUnknown(5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object indicates current over all status of the module."
|
|
::= { vpwrSystemIdentEntry 5}
|
|
|
|
vpwrModuleCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The meaning of this object depends upon the module type
|
|
which is indicated by vpwrModuleOID as follows
|
|
- Capacity for Rectifier module.
|
|
- Not Applicable for LVD module
|
|
"
|
|
::= { vpwrSystemIdentEntry 6}
|
|
|
|
|
|
|
|
--
|
|
-- The System Panel Identifier group.
|
|
--
|
|
|
|
vpwrPanelStatusTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrPanelStatusEntrySEQ
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This table describes shelves and modules
|
|
that make up the panels.
|
|
"
|
|
::= { vpwrSystemPanelIdentGroup 1 }
|
|
|
|
vpwrPanelStatus OBJECT-TYPE
|
|
SYNTAX VpwrPanelStatusEntrySEQ
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular panel making up the system."
|
|
INDEX { vpwrPanelStatusIndex, vpwrPanelStatusModuleIndex }
|
|
::= { vpwrPanelStatusTable 1 }
|
|
|
|
VpwrPanelStatusEntrySEQ ::= SEQUENCE {
|
|
vpwrPanelStatusIndex PositiveInteger,
|
|
vpwrPanelStatusModuleIndex PositiveInteger,
|
|
vpwrPanelStatusModuleOID OBJECT IDENTIFIER ,
|
|
vpwrPanelStatusModuleCurrent INTEGER ,
|
|
vpwrpanelStatusModuleOperStatus INTEGER ,
|
|
vpwrPanelStatusModuleCapacity INTEGER
|
|
}
|
|
|
|
vpwrPanelStatusIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Identifies panel number that this module belongs to.
|
|
The possible values are 1 through 8, starting from the top."
|
|
::= { vpwrPanelStatus 1 }
|
|
|
|
vpwrPanelStatusModuleIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object identifies the module within the panel.
|
|
The orentation of modules within the panel is mappable."
|
|
::= { vpwrPanelStatus 2 }
|
|
|
|
vpwrPanelStatusModuleOID OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The module OID."
|
|
::= { vpwrPanelStatus 3}
|
|
|
|
vpwrPanelStatusModuleCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current measured by the device (if applicable). LVD current reported in deciAmps.
|
|
"
|
|
::= { vpwrPanelStatus 4}
|
|
|
|
vpwrpanelStatusModuleOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
moduleStatusOK(0),
|
|
moduleStatusAlarm(1),
|
|
moduleStatusDisabled(2),
|
|
moduleStatusRingerAOn(3),
|
|
moduleStatusRingerBOn(4),
|
|
moduleStatusUnknown(5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object indicates current over all status of the module."
|
|
::= { vpwrPanelStatus 5}
|
|
|
|
vpwrPanelStatusModuleCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum capacity of the module (if applicable)."
|
|
::= { vpwrPanelStatus 6}
|
|
|
|
|
|
vpwrPanelIdentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrPanelIdentEntrySEQ
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This table describes shelves and modules
|
|
that make up the panels.
|
|
"
|
|
::= { vpwrSystemPanelIdentGroup 2 }
|
|
|
|
|
|
|
|
vpwrPanelIdentEntry OBJECT-TYPE
|
|
SYNTAX VpwrPanelIdentEntrySEQ
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular panel making up the system."
|
|
INDEX { vpwrPanelIndex, vpwrPanelModuleIndex }
|
|
::= { vpwrPanelIdentTable 1 }
|
|
|
|
|
|
|
|
|
|
VpwrPanelIdentEntrySEQ ::= SEQUENCE {
|
|
vpwrPanelIndex PositiveInteger,
|
|
vpwrPanelModuleIndex PositiveInteger,
|
|
vpwrPanelModuleSerNum OBJECT IDENTIFIER ,
|
|
vpwrPanelModuleModelName OBJECT IDENTIFIER ,
|
|
vpwrPanelModuleFWVer OBJECT IDENTIFIER ,
|
|
vpwrPanelModuleTestDate INTEGER
|
|
}
|
|
|
|
vpwrPanelIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Identifies panel number that this module belongs to.
|
|
The possible values are 1 through 8, starting from the top."
|
|
::= { vpwrPanelIdentEntry 1 }
|
|
|
|
vpwrPanelModuleIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object identifies the module within the panel.
|
|
The orentation of modules within the panel is mappable."
|
|
::= { vpwrPanelIdentEntry 2 }
|
|
|
|
vpwrPanelModuleSerNum OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The module serial number."
|
|
::= { vpwrPanelIdentEntry 3}
|
|
|
|
vpwrPanelModuleModelName OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The model name of the device."
|
|
::= { vpwrPanelIdentEntry 4}
|
|
|
|
vpwrPanelModuleFWVer OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The module firmware version."
|
|
::= { vpwrPanelIdentEntry 5}
|
|
|
|
vpwrPanelModuleTestDate OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The manufacturing test date."
|
|
::= { vpwrPanelIdentEntry 6}
|
|
|
|
--
|
|
-- Power Module inventory info
|
|
--
|
|
vpwrDcPowerModuleIdentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DCPowerModuleIdentEntrySEQ
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This table describes power modules
|
|
that make up the system.
|
|
"
|
|
::= { vpwrDcPowerModuleIdent 1 }
|
|
|
|
--
|
|
-- The Module Identifier Entry. Defines the sequence for module tables.
|
|
--
|
|
|
|
vpwrDcPowerModuleIdentEntry OBJECT-TYPE
|
|
SYNTAX DCPowerModuleIdentEntrySEQ
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
power module."
|
|
INDEX { vpwrBayIndex1, vpwrDCModuleIndex }
|
|
::= { vpwrDcPowerModuleIdentTable 1 }
|
|
|
|
|
|
DCPowerModuleIdentEntrySEQ ::= SEQUENCE {
|
|
vpwrBayIndex1 PositiveInteger,
|
|
vpwrDCModuleIndex PositiveInteger,
|
|
vpwrModuleSerialNumber DisplayString ,
|
|
vpwrModuleModelNumber DisplayString ,
|
|
vpwrModuleFwVersion DisplayString ,
|
|
vpwrModuleTestDate DisplayString ,
|
|
vpwrModuleOperHours Counter32
|
|
}
|
|
|
|
vpwrBayIndex1 OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Identifies shelf number that this module belongs to.
|
|
The possible values are 1 through 2, starting from the top."
|
|
::= { vpwrDcPowerModuleIdentEntry 1 }
|
|
|
|
vpwrDCModuleIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object identifies the module within the shelf."
|
|
::= { vpwrDcPowerModuleIdentEntry 2 }
|
|
|
|
|
|
vpwrModuleSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Number of the module"
|
|
::= { vpwrDcPowerModuleIdentEntry 3}
|
|
|
|
vpwrModuleModelNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Model Number of the module."
|
|
::= { vpwrDcPowerModuleIdentEntry 4}
|
|
|
|
vpwrModuleFwVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Firmware version of the module."
|
|
::= { vpwrDcPowerModuleIdentEntry 5}
|
|
|
|
vpwrModuleTestDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Date when the module was last tested."
|
|
::= { vpwrDcPowerModuleIdentEntry 6}
|
|
|
|
vpwrModuleOperHours OBJECT-TYPE
|
|
SYNTAX Counter32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Cumulative Operating Hours."
|
|
::= { vpwrDcPowerModuleIdentEntry 7}
|
|
|
|
|
|
|
|
|
|
--
|
|
--
|
|
-- The System History group.
|
|
--
|
|
vpwrSysHistAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrSysHistAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This table provides a list of most recent alarms.
|
|
"
|
|
::= { vpwrSystemHistoryGroup 1 }
|
|
|
|
|
|
vpwrSysHistAlarmEntry OBJECT-TYPE
|
|
SYNTAX VpwrSysHistAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry describing an alarm."
|
|
INDEX { vpwrSysHistAlarmIndex}
|
|
::= { vpwrSysHistAlarmTable 1 }
|
|
|
|
VpwrSysHistAlarmEntry ::= SEQUENCE {
|
|
vpwrSysHistAlarmIndex PositiveInteger,
|
|
vpwrSysHistAlarmDescription DisplayString
|
|
}
|
|
|
|
vpwrSysHistAlarmIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alarm index."
|
|
::= { vpwrSysHistAlarmEntry 1 }
|
|
|
|
vpwrSysHistAlarmDescription OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alarm description including time stamp."
|
|
::= { vpwrSysHistAlarmEntry 2 }
|
|
|
|
|
|
|
|
--
|
|
-- --
|
|
--The System Configuration Parameters group.
|
|
-- --
|
|
|
|
vpwrSystemTempCompensation OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
tempCompDisabled(0),
|
|
tempCompEnabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter enables/disables temperature compensation.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrSystemConfigGroup 1}
|
|
|
|
vpwrSystemTempCompStartTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER (25..60)
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The temperature at which temperature compensation becomes
|
|
active.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemConfigGroup 2}
|
|
|
|
vpwrSystemTempCompStopVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" When temperature compensation is active, vpwrSystemTempCompStopVoltage is the
|
|
limit to which float voltage will be reduced.
|
|
For example, to set this voltage to 51.75 volts enter a value of 5175.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemConfigGroup 3}
|
|
|
|
vpwrSystemTempCompensationSlope OBJECT-TYPE
|
|
SYNTAX INTEGER (0..250)
|
|
UNITS " milli-Volts per degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The rate at which float voltage is changed, within the specified limits,
|
|
when temperature compensation is active.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemConfigGroup 4}
|
|
|
|
vpwrSystemThermalSenseType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
internal(0),
|
|
external(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter selects the temperature sensing point for temperature
|
|
compensation (in)activation.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemConfigGroup 5}
|
|
|
|
vpwrSystemHVAlarmSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System High voltage alarm voltage setting.
|
|
"
|
|
::= { vpwrSystemConfigGroup 6}
|
|
vpwrSystemBDAlarmSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System Battery Discharge voltage setting."
|
|
::= { vpwrSystemConfigGroup 7}
|
|
|
|
--
|
|
-- Threshold for Internal Temperature Trap
|
|
--
|
|
vpwrSystemInternalTempLThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature value at which temperature compensation inactive (clear)
|
|
trap would be sent if temperature compensation was active when this
|
|
value is reached.
|
|
"
|
|
::= { vpwrSystemConfigGroup 8}
|
|
|
|
vpwrSystemInternalTempUThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature value at which temperature compensation active (set) trap
|
|
would be sent.
|
|
"
|
|
::= { vpwrSystemConfigGroup 9}
|
|
|
|
--
|
|
-- The System Current Operating Parameters group.
|
|
--
|
|
|
|
|
|
vpwrSystemShelfCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER (1..16)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" It describes the maximum number of shelves that can/are controlled
|
|
by the controller. Each shelf is uniquely numbered in the range
|
|
from 1 to vpwrShelfCapacity.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemParameterGroup 1}
|
|
|
|
vpwrSystemVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The current system voltage.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemParameterGroup 2}
|
|
|
|
vpwrSystemCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " Amperes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The current system current.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemParameterGroup 3}
|
|
|
|
vpwrSystemControllerState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
systemControllerStateUnknown(0),
|
|
systemControllerStateNormal(1),
|
|
systemControllerStateChange(2) ,
|
|
systemControllerStateAlarm(3),
|
|
systemControllerStateMenu(4 ),
|
|
systemControllerStateIrActive(5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Current System state as shown on the enhanced display.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemParameterGroup 4}
|
|
|
|
|
|
vpwrSystemInternalTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The current controller internal temperature.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemParameterGroup 5}
|
|
|
|
vpwrSystemTempCompensationState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
systemTempCompInactive(0),
|
|
systemTempCompActive(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Active or Inactive. Applicable only if temperature compensation is enabled.
|
|
This means that the controller is temperature compensating the float voltage.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemParameterGroup 6}
|
|
|
|
vpwrSystemType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sysType48V (0),
|
|
sysType24V(1) ,
|
|
sysType12V(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This parameter describes the type of the system being managed.
|
|
This object is set by Eltek Valere Inc.
|
|
"
|
|
::= { vpwrSystemParameterGroup 7 }
|
|
|
|
vpwrSystemCumulativeUpTime OBJECT-TYPE
|
|
SYNTAX Gauge
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This parameter describes the cumulative runtime in seconds
|
|
of the Eltek Valere controller.
|
|
"
|
|
::= { vpwrSystemParameterGroup 8 }
|
|
|
|
vpwrSystemBatteryRemainingTime OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
UNITS "Hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This parameter describes the remaining battery capacity
|
|
based upon installed battery capacity and
|
|
plant load. This number would change as the SOC
|
|
parameters of the batteries changes.
|
|
"
|
|
::= { vpwrSystemParameterGroup 9 }
|
|
|
|
--
|
|
-- The System Alarm group.
|
|
--
|
|
|
|
|
|
vpwrSystemAlarmMajor OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Indicates a Major Alarm exists on the system.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemAlarmGroup 1}
|
|
|
|
vpwrSystemAlarmMinor OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Indicates a Minor Alarm exists on the system.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemAlarmGroup 2}
|
|
|
|
vpwrSystemACFailAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" One or more rectifiers have reported AC failure. If system
|
|
is configured to report rectifier communication failure as AC fail
|
|
this alarm will report.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemAlarmGroup 3}
|
|
|
|
vpwrSystemHighVoltageWarningAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" System has exceeded High Voltage Warning Setpoint. Check for high voltage on system bus.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemAlarmGroup 4}
|
|
|
|
|
|
vpwrSystemHighVoltageShutdownAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" One or more rectifiers have shut down due to high voltage present on output. Check bus voltage
|
|
and reseat rectifiers that have indicated this problem.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemAlarmGroup 5}
|
|
|
|
vpwrSystemBatteryonDischargeAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
systemTempCompInactive(0),
|
|
systemTempCompActive(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" System voltage has currently dropped below the alarm setpoint. This may be due to battery testing or AC failure.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrSystemAlarmGroup 6}
|
|
|
|
vpwrSystemLowVoltageWarningAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sysType48V (0),
|
|
sysType24V(1) ,
|
|
sysType12V(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System Voltage has dropped below setpoint for Low Voltage Alarm. This may occur during battery testing or AC failure
|
|
"
|
|
::= { vpwrSystemAlarmGroup 7 }
|
|
|
|
vpwrSystemLVDOpenAlarm OBJECT-TYPE
|
|
SYNTAX Gauge
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more contactors have opened. This occurs normally during system power on. If it occurs during operation this may
|
|
indicate system is operating below LVD disconnect voltage.
|
|
"
|
|
::= { vpwrSystemAlarmGroup 8 }
|
|
|
|
vpwrSystemDistributionAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more distribution alarm inputs are reporting an error condition. Check source of alarm and correct issue.
|
|
"
|
|
::= { vpwrSystemAlarmGroup 9 }
|
|
|
|
vpwrSystemAuxiliaryAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more Auxliary alarm inputs are reporting an error condition. Check source of alarm and correct issue.
|
|
"
|
|
::= { vpwrSystemAlarmGroup 10 }
|
|
|
|
vpwrSystemRedundantCapAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system load has exceeded the requirements for redundancy. This may be a temporary system overload condition or caused by a rectifier alarm.
|
|
"
|
|
::= { vpwrSystemAlarmGroup 11 }
|
|
|
|
vpwrSystemRectIShareAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more rectifiers are reporting a mismatch in current. This may be due to mismatched rectifier models or one or more rectifiers not current sharing
|
|
"
|
|
::= { vpwrSystemAlarmGroup 12 }
|
|
|
|
vpwrSystemSnglRectAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= { vpwrSystemAlarmGroup 13 }
|
|
|
|
vpwrSystemMultRectAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= { vpwrSystemAlarmGroup 14 }
|
|
|
|
vpwrSystemModlCommAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= { vpwrSystemAlarmGroup 15 }
|
|
|
|
vpwrSystemOverTempAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= { vpwrSystemAlarmGroup 16 }
|
|
|
|
vpwrSystemThermRAAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Thermal Runaway has occurred on system. Check temperature inputs.
|
|
"
|
|
::= { vpwrSystemAlarmGroup 17 }
|
|
|
|
vpwrSystemBDTAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System has entered Battery Discharge Test mode
|
|
"
|
|
::= { vpwrSystemAlarmGroup 18 }
|
|
|
|
vpwrSystemRectUVAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier output has dropped 1V below Low Voltage Alarm setpoint
|
|
"
|
|
::= { vpwrSystemAlarmGroup 19 }
|
|
|
|
vpwrSystemMultRectUVAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= { vpwrSystemAlarmGroup 20 }
|
|
|
|
vpwrSystemSnglRngrAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= { vpwrSystemAlarmGroup 21 }
|
|
|
|
vpwrSystemMultRngrAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= { vpwrSystemAlarmGroup 22 }
|
|
|
|
vpwrSystemTempProbeAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temp probe input missing or failed
|
|
"
|
|
::= { vpwrSystemAlarmGroup 23 }
|
|
|
|
vpwrSystemRngrCommAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ringer Module has stopped communicating with Controller.
|
|
"
|
|
::= { vpwrSystemAlarmGroup 24 }
|
|
|
|
vpwrSystemDistPMCommAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more distribution alarm modules, TRIOs, or PM modules has stopped communicating with Controller.
|
|
"
|
|
::= { vpwrSystemAlarmGroup 25 }
|
|
|
|
vpwrSystemRectILimitAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier has reached current limit setpoint.
|
|
"
|
|
::= { vpwrSystemAlarmGroup 26 }
|
|
|
|
vpwrSystemMultRectILimitAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= { vpwrSystemAlarmGroup 27 }
|
|
|
|
vpwrSystemUnmappedI2CCANAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Recheck all I2C and CAN dip switch settings. One or more devices in conflict.
|
|
"
|
|
::= { vpwrSystemAlarmGroup 28 }
|
|
|
|
vpwrSystemConfigErrAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Recheck all I2C and CAN dip switch settings. One or more devices in conflict.
|
|
"
|
|
::= { vpwrSystemAlarmGroup 29 }
|
|
|
|
vpwrSystemDispFWAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= { vpwrSystemAlarmGroup 30 }
|
|
|
|
vpwrSystemUndefinedAlarm OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= { vpwrSystemAlarmGroup 31 }
|
|
|
|
-- vpwrSystemModlCommAlarm OBJECT-TYPE
|
|
-- SYNTAX PositiveInteger
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "
|
|
-- "
|
|
-- ::= { vpwrSystemAlarmGroup 32 }
|
|
|
|
--
|
|
-- The System LVD Operating Setpoints group.
|
|
--
|
|
|
|
vpwrLvdWarningSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " * .01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Warning voltage setpoint."
|
|
::= { vpwrLvdConfigGroup 1}
|
|
|
|
vpwrLvdDisconnectSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD disconnect voltage setpoint."
|
|
::= { vpwrLvdConfigGroup 2}
|
|
vpwrLvdReconnectSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Reconnect voltage setpoint."
|
|
::= { vpwrLvdConfigGroup 3}
|
|
vpwrLvdReconnectDelayTimer OBJECT-TYPE
|
|
SYNTAX INTEGER (20..240)
|
|
UNITS " Seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay time, in seconds, before LVD is reconnected"
|
|
::= { vpwrLvdConfigGroup 4}
|
|
--
|
|
-- The System LVD Operating Setpoints group.
|
|
--
|
|
|
|
vpwrLvd2DisconnectSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD disconnect voltage setpoint."
|
|
::= { vpwrLvdConfigGroup 7}
|
|
vpwrLvd2ReconnectSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Reconnect voltage setpoint."
|
|
::= { vpwrLvdConfigGroup 8}
|
|
vpwrLvd2ReconnectDelayTimer OBJECT-TYPE
|
|
SYNTAX INTEGER (20..240)
|
|
UNITS " Seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay time, in seconds, before LVD is reconnected"
|
|
::= { vpwrLvdConfigGroup 9}
|
|
|
|
|
|
--
|
|
-- The System LVD Operating Setpoints group.
|
|
--
|
|
|
|
vpwrLvd3DisconnectSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD disconnect voltage setpoint."
|
|
::= { vpwrLvdConfigGroup 11}
|
|
vpwrLvd3ReconnectSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Reconnect voltage setpoint."
|
|
::= { vpwrLvdConfigGroup 12}
|
|
vpwrLvd3ReconnectDelayTimer OBJECT-TYPE
|
|
SYNTAX INTEGER (20..240)
|
|
UNITS " Seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay time, in seconds, before LVD is reconnected"
|
|
::= { vpwrLvdConfigGroup 13}
|
|
|
|
--
|
|
-- The System LVD Operating Setpoints group.
|
|
--
|
|
|
|
|
|
vpwrLvd4DisconnectSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD disconnect voltage setpoint."
|
|
::= { vpwrLvdConfigGroup 15}
|
|
vpwrLvd4ReconnectSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Reconnect voltage setpoint."
|
|
::= { vpwrLvdConfigGroup 16}
|
|
vpwrLvd4ReconnectDelayTimer OBJECT-TYPE
|
|
SYNTAX INTEGER (20..240)
|
|
UNITS " Seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay time, in seconds, before LVD is reconnected"
|
|
::= { vpwrLvdConfigGroup 17}
|
|
|
|
-- vpwrLvd4DisconnectDelayTimer OBJECT-TYPE
|
|
-- SYNTAX INTEGER (20..240)
|
|
-- UNITS " Seconds"
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "The delay time, in seconds, before LVD is reconnected"
|
|
-- ::= { vpwrLvdConfigGroup 18}
|
|
--
|
|
-- The Rectifier Operating Parameters group.
|
|
--
|
|
|
|
vpwrRectifierFVSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System Float Voltage setting"
|
|
::= { vpwrRectifierConfigGroup 1}
|
|
vpwrRectifierHVSDSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System High Voltage Shutdown voltage setting"
|
|
::= { vpwrRectifierConfigGroup 2}
|
|
|
|
vpwrRectifierCurrentLimitAdminState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
rectCurrentLimitDisabled(0),
|
|
rectCurrentLimitEnabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter allows enabling or rectifier current limit"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrRectifierConfigGroup 3}
|
|
|
|
vpwrRectifierCurrentLimit OBJECT-TYPE
|
|
SYNTAX INTEGER (5..220)
|
|
UNITS "Amperes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier current limit setpoint"
|
|
::= { vpwrRectifierConfigGroup 4}
|
|
|
|
vpwrRectifierFallbackAdminState OBJECT-TYPE
|
|
SYNTAX GenericEnableDisableTC
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enables Rectifier to use
|
|
Fallback Voltage when it loses
|
|
communication with the controller.
|
|
This applies to all rectifiers."
|
|
::= { vpwrRectifierConfigGroup 5}
|
|
|
|
vpwrRectifierFallbackVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fallback Voltage setpoint to use
|
|
when rectifier loses
|
|
communication with the controller.
|
|
This applies to all rectifiers."
|
|
::= { vpwrRectifierConfigGroup 6}
|
|
|
|
--
|
|
-- The Alarm group.
|
|
--
|
|
|
|
|
|
vpwrAlarmsPresent OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present number of active alarm conditions."
|
|
::= { vpwrDcPowerAlarmGroup 1 }
|
|
|
|
vpwrAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrAlarmEntrySEQ
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of alarm table entries. The table contains
|
|
zero, one, or multiple rows at any time depending upon
|
|
the number of alarm conditions in effect. The table
|
|
is initially empty at agent startup. The agent
|
|
creates a row in the table each time a condition is
|
|
detected and deletes that row when that condition no
|
|
longer exists.
|
|
The vpwrAlarmIndex, for each type of module starts at 1
|
|
and is limited by the total number of alarms that can be
|
|
generated by the module.
|
|
|
|
Alarms are named by an AutonomousType (OBJECT
|
|
IDENTIFIER), vpwrAlarmDescr, to allow a single table to
|
|
reflect alarms for different types of modules.
|
|
|
|
The number of rows in the table at any given time is
|
|
reflected by the value of vpwrAlarmsPresent."
|
|
|
|
::= { vpwrDcPowerAlarmGroup 2 }
|
|
|
|
vpwrAlarmEntry OBJECT-TYPE
|
|
SYNTAX VpwrAlarmEntrySEQ
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular alarm."
|
|
INDEX { vpwrBayIndex, vpwrModuleIndex, vpwrAlarmIndex }
|
|
::= { vpwrAlarmTable 1 }
|
|
|
|
VpwrAlarmEntrySEQ ::= SEQUENCE {
|
|
vpwrAlarmIndex PositiveInteger,
|
|
vpwrAlarmDescr AutonomousType,
|
|
vpwrAlarmTime TimeStamp
|
|
}
|
|
|
|
vpwrAlarmIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Identifies the alarm associated with the module.
|
|
It is unique on per module type basis. For example,
|
|
multiple rectifiers can have the same alarm and therefore same
|
|
vpwrAlarmIndex active at any one time.
|
|
"
|
|
::= { vpwrAlarmEntry 1 }
|
|
|
|
|
|
vpwrAlarmDescr OBJECT-TYPE
|
|
SYNTAX AutonomousType
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A reference to an alarm description object. The
|
|
object referenced should not be accessible, but rather
|
|
be used to provide a unique description of the alarm
|
|
condition."
|
|
::= { vpwrAlarmEntry 2 }
|
|
|
|
vpwrAlarmTime OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of sysUpTime when the alarm condition was
|
|
detected."
|
|
|
|
::= { vpwrAlarmEntry 3 }
|
|
|
|
|
|
|
|
--
|
|
-- The Battery Group
|
|
--
|
|
|
|
|
|
|
|
vpwrBatteryTempTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrBatteryTempEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table describes battery temperature probes.
|
|
"
|
|
::= { vpwrBatteryTempGroup 1 }
|
|
|
|
vpwrBatteryTempEntry OBJECT-TYPE
|
|
SYNTAX VpwrBatteryTempEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular temperature probe."
|
|
INDEX { vpwrBatteryTempIndex }
|
|
::= { vpwrBatteryTempTable 1 }
|
|
|
|
VpwrBatteryTempEntry ::= SEQUENCE {
|
|
vpwrBatteryTempIndex INTEGER,
|
|
vpwrBatteryTempName DisplayString,
|
|
vpwrBatteryTemp SysInputValue
|
|
}
|
|
|
|
vpwrBatteryTempIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index into temperature table"
|
|
::= { vpwrBatteryTempEntry 1}
|
|
|
|
vpwrBatteryTempName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1..8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying probe location."
|
|
::= { vpwrBatteryTempEntry 2}
|
|
|
|
vpwrBatteryTemp OBJECT-TYPE
|
|
SYNTAX SysInputValue
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current temperature as recorded by the probe."
|
|
::= { vpwrBatteryTempEntry 3}
|
|
|
|
|
|
-- Threshold for Battery Temperature Trap
|
|
|
|
vpwrBatteryTempLThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature value at which a clear trap would be sent.
|
|
All three battery temperature must be at or below this value
|
|
to trigger this trap.
|
|
"
|
|
::= { vpwrBatteryTempGroup 2}
|
|
|
|
vpwrBatteryTempUThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature value at which a set trap would be sent.
|
|
Any one of the three battery temperatures at or exceeding this limit
|
|
would trigger the trap.
|
|
"
|
|
::= { vpwrBatteryTempGroup 3}
|
|
|
|
batteryTempCompensation OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
tempCompDisabled(0),
|
|
tempCompEnabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter enables/disables temperature compensation.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryTempGroup 4}
|
|
|
|
batteryTempCompHighStartTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER (25..60)
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The temperature at which temperature compensation becomes
|
|
active.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 5}
|
|
|
|
batteryTempCompHighStopVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" When temperature compensation is active, batteryTempCompHighStopVoltage is the
|
|
limit to which float voltage will be reduced.
|
|
For example, to set this voltage to 51.75 volts enter a value of 5175.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 6}
|
|
|
|
batteryTempCompHighSlope OBJECT-TYPE
|
|
SYNTAX INTEGER (0..250)
|
|
UNITS " milli-Volts per degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The rate at which float voltage is changed, within the specified limits,
|
|
when temperature compensation is active.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 7}
|
|
|
|
|
|
batteryTempCompLowStartTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The temperature at which temperature compensation becomes
|
|
active.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 8}
|
|
|
|
batteryTempCompLowStopVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" When temperature compensation is active, batteryTempCompLowStopVoltage is the
|
|
limit to which float voltage will be reduced.
|
|
For example, to set this voltage to 51.75 volts enter a value of 5175.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 9}
|
|
|
|
batteryTempCompLowSlope OBJECT-TYPE
|
|
SYNTAX INTEGER (0..250)
|
|
UNITS " milli-Volts per degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The rate at which float voltage is changed, within the specified limits,
|
|
when temperature compensation is active.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 10}
|
|
|
|
batteryTempCompRunawayTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER (25..60)
|
|
UNITS "degrees Celsius"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The temperature at which system voltage will be set to
|
|
batteryTempCompRunawayStopVoltage.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 11}
|
|
|
|
batteryTempCompRunawayStopVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" When temperature compensation is enabled, float voltage will be reduced to
|
|
batteryTempCompRunawayStopVoltage if temperature
|
|
reaches batteryTempCompRunawayTemperature.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 12}
|
|
|
|
batteryTempCompSenseSource OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
internal(0),
|
|
external(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter selects the temperature sensing point for temperature
|
|
compensation (in)activation.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 13}
|
|
|
|
batteryTempCompRunawayState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
inactive(0),
|
|
active(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter selects the temperature sensing point for temperature
|
|
compensation (in)activation.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryTempGroup 14}
|
|
|
|
-- thermalProbeTable OBJECT-TYPE
|
|
-- SYNTAX SEQUENCE OF ThermalProbeEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "This table describes battery temperature probes.
|
|
-- "
|
|
-- ::= { vpwrBatteryTempGroup 15 }
|
|
--
|
|
-- thermalProbeEntry OBJECT-TYPE
|
|
-- SYNTAX ThermalProbeEntry
|
|
-- MAX-ACCESS not-accessible
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "An entry containing information applicable to a
|
|
-- particular temperature probe."
|
|
-- INDEX { vpwrBatteryTempIndex }
|
|
-- AUGMENTS {vpwrBatteryTempEntry}
|
|
-- ::= { thermalProbeTable 1 }
|
|
--
|
|
-- ThermalProbeEntry ::= SEQUENCE {
|
|
-- thermalProbeState INTEGER
|
|
-- }
|
|
--
|
|
-- thermalProbeState OBJECT-TYPE
|
|
-- SYNTAX INTEGER {
|
|
-- notPresent(0),
|
|
-- present(1),
|
|
-- removed(2),
|
|
-- shorted(3)
|
|
-- }
|
|
-- MAX-ACCESS read-only
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "State of thermal probe."
|
|
-- ::= { thermalProbeEntry 1}
|
|
|
|
|
|
--
|
|
-- The SNMP Configuration Parameters
|
|
--
|
|
|
|
vpwrTrapTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrTrapEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of possible trap destinations depending upon
|
|
the criticality of the trap.
|
|
"
|
|
::= { vpwrDcPowerSnmpConfig 1 }
|
|
|
|
vpwrTrapEntry OBJECT-TYPE
|
|
SYNTAX VpwrTrapEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular trap destination."
|
|
INDEX { vpwrTrapIpIndex }
|
|
::= { vpwrTrapTable 1 }
|
|
|
|
VpwrTrapEntry ::= SEQUENCE {
|
|
vpwrTrapIpIndex INTEGER,
|
|
vpwrTrapIpAddress IpAddress,
|
|
vpwrTrapCriticality INTEGER
|
|
}
|
|
vpwrTrapIpIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap Entry Index "
|
|
::= { vpwrTrapEntry 1}
|
|
|
|
vpwrTrapIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Trap destination IP Address"
|
|
::= { vpwrTrapEntry 2}
|
|
|
|
vpwrTrapCriticality OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Criticality of traps sent to this IP Address"
|
|
::= { vpwrTrapEntry 3}
|
|
|
|
|
|
vpwrReadCommunityString OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (3..8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This allows setting password to be able to do Get operations"
|
|
::= { vpwrDcPowerSnmpConfig 2 }
|
|
|
|
vpwrWriteCommunityString OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (3..8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This allows setting password to be able to do Get and Set
|
|
operations.
|
|
The read-access is not allowed in the actual implementation.
|
|
"
|
|
::= { vpwrDcPowerSnmpConfig 3 }
|
|
|
|
vpwrTrapCommunityString OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE (3..8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This allows setting community string required for the
|
|
trap to be accepted at the destination.
|
|
"
|
|
::= { vpwrDcPowerSnmpConfig 4 }
|
|
|
|
vpwrTrapVersion OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This allows setting the version of trap message sent from the system"
|
|
::= { vpwrDcPowerSnmpConfig 5 }
|
|
|
|
|
|
|
|
--
|
|
-- LVD Alarm Group
|
|
--
|
|
|
|
-- vpwrLvdAlarmContactorOpen OBJECT-IDENTITY
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Contactor open"
|
|
-- ::= {vpwrLvdAlarmGroup 1 }
|
|
|
|
|
|
-- vpwrLvdAlarmCBOpen OBJECT-IDENTITY
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Circuit Breaker open"
|
|
-- ::= {vpwrLvdAlarmGroup 2 }
|
|
|
|
-- vpwrTrapLvdFuseOpen OBJECT-IDENTITY
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Fuse open"
|
|
-- ::= {vpwrLvdAlarmGroup 3 }
|
|
|
|
-- vpwrLvdAlarmWarning OBJECT-IDENTITY
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Plant Voltage below warning threshold"
|
|
-- ::= {vpwrLvdAlarmGroup 4 }
|
|
|
|
--
|
|
-- Rectifier Alarm Group
|
|
--
|
|
|
|
vpwrRectAlarmDCFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 1}
|
|
|
|
vpwrRectAlarmBoostFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 2}
|
|
|
|
vpwrRectAlarmACFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 3}
|
|
|
|
vpwrRectAlarmHVSD OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 4}
|
|
|
|
vpwrRectAlarmFanFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 5}
|
|
|
|
vpwrRectAlarmAmbTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 6}
|
|
vpwrRectAlarmIntTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 7}
|
|
|
|
vpwrRectAlarmIShare OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 8}
|
|
|
|
vpwrRectAlarmUV OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 9}
|
|
|
|
vpwrRectAlarmLowVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 10}
|
|
|
|
vpwrRectAlarmReserved OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 11}
|
|
|
|
vpwrRectAlarmDCEnable OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 12}
|
|
|
|
vpwrRectAlarmRemoteShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 13}
|
|
|
|
vpwrRectAlarmModDisableShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 14}
|
|
|
|
vpwrRectAlarmShortPinShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 15}
|
|
|
|
vpwrRectAlarmBoostComm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
::= {vpwrRectifierAlarmGroup 16}
|
|
|
|
|
|
|
|
|
|
|
|
sysAlarmConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SysAlarmConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table describes system alarm configuration and current
|
|
status.
|
|
"
|
|
::= { vpwrDcPowerAlarmGroup 3 }
|
|
|
|
sysAlarmConfigEntry OBJECT-TYPE
|
|
SYNTAX SysAlarmConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular system alarm."
|
|
INDEX { sysAlarmIndex }
|
|
::= { sysAlarmConfigTable 1 }
|
|
|
|
SysAlarmConfigEntry ::= SEQUENCE {
|
|
sysAlarmIndex INTEGER,
|
|
sysAlarmDefaultName DisplayString,
|
|
sysAlarmCustomName DisplayString,
|
|
sysAlarmSeverity INTEGER ,
|
|
sysAlarmToRelayMapping DisplayString ,
|
|
sysAlarmOperStatus INTEGER
|
|
}
|
|
|
|
sysAlarmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index into system alarm table"
|
|
::= { sysAlarmConfigEntry 1}
|
|
|
|
sysAlarmDefaultName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1..8))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Default alarm name."
|
|
::= { sysAlarmConfigEntry 2}
|
|
|
|
sysAlarmCustomName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1..8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A custom alarm name."
|
|
::= { sysAlarmConfigEntry 3}
|
|
|
|
sysAlarmSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(0),
|
|
major(1),
|
|
minor(2),
|
|
majorAndMinor(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alarm Severity as denoted by Major and Minor Alarm Mask"
|
|
::= { sysAlarmConfigEntry 4}
|
|
|
|
sysAlarmToRelayMapping OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (1..8))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No additional mapping = 0
|
|
Map to Relay A = 1
|
|
Map to Relay B = 2
|
|
Map to Relay C = 4
|
|
Map to Relay D = 8
|
|
Map to Relay E = 16
|
|
Map to Relay F = 32
|
|
Map to Relay A and B = (1 + 2) and so on
|
|
The major/minor classification of alarms automatically
|
|
associates it with Major/Minor relay. Assigning a null
|
|
mapping here does not override vpwrPMRelayAlarmSeverity for
|
|
the alarm.
|
|
It should be used to define mapping to additional relays.
|
|
"
|
|
::= { sysAlarmConfigEntry 5}
|
|
|
|
sysAlarmOperStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
inactive(0),
|
|
active(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates current alarm status"
|
|
::= { sysAlarmConfigEntry 6}
|
|
|
|
|
|
|
|
|
|
sysAlarmComFailState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(0),
|
|
enabled(1),
|
|
other(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enable/Disable generation of comm fail alarm."
|
|
::= { vpwrDcPowerAlarmGroup 4 }
|
|
|
|
sysAlarmIShareState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(0),
|
|
enabled(1),
|
|
other(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enable/Disable generation of current share alarm."
|
|
::= { vpwrDcPowerAlarmGroup 5}
|
|
|
|
sysAlarmRedundancyState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(0),
|
|
nPlus1(1),
|
|
nPlus2(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enable/Disable generation of redundancy alarm."
|
|
::= { vpwrDcPowerAlarmGroup 6}
|
|
|
|
sysAlarmComFailToACFailState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(0),
|
|
enabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enable/Disable generation of ACF upon Com Fail"
|
|
::= { vpwrDcPowerAlarmGroup 7}
|
|
|
|
-------------------------------------------------------------------------------------------
|
|
|
|
vpwrDCPowerLampTest OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
disabled(0),
|
|
enabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lamp Test for modules"
|
|
::= { eltek 5 }
|
|
|
|
vpwrPMCnfgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrPMCnfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table shows the current configuration of the TRIO/PM86000/Controller inputs."
|
|
::= { vpwrDcPowerPMModule 1 }
|
|
|
|
vpwrPMCnfgEntry OBJECT-TYPE
|
|
SYNTAX VpwrPMCnfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing current configuration of the TRIO/PM86000/Controller inputs."
|
|
INDEX { vpwrPMIndex }
|
|
::= { vpwrPMCnfgTable 1 }
|
|
|
|
VpwrPMCnfgEntry ::= SEQUENCE {
|
|
vpwrPMIndex NonNegativeInteger,
|
|
vpwrPMDescription DisplayString,
|
|
vpwrPMCnfg1 VpwrPMCnfgValue,
|
|
vpwrPMCnfg2 VpwrPMCnfgValue,
|
|
vpwrPMCnfg3 VpwrPMCnfgValue,
|
|
vpwrPMCnfg4 VpwrPMCnfgValue,
|
|
vpwrPMCnfg5 VpwrPMCnfgValue,
|
|
vpwrPMCnfg6 VpwrPMCnfgValue,
|
|
vpwrPMCnfg7 VpwrPMCnfgValue,
|
|
vpwrPMCnfg8 VpwrPMCnfgValue
|
|
}
|
|
|
|
vpwrPMIndex OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter describes which TRIO/PM86000 device is being accessed."
|
|
::= {vpwrPMCnfgEntry 1}
|
|
|
|
vpwrPMDescription OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter describes the configuration of the TRIO/PM86000 device."
|
|
::= {vpwrPMCnfgEntry 2}
|
|
|
|
vpwrPMCnfg1 OBJECT-TYPE
|
|
SYNTAX VpwrPMCnfgValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current configuration of the TRIO/PM86000, input 1"
|
|
::= {vpwrPMCnfgEntry 3}
|
|
|
|
vpwrPMCnfg2 OBJECT-TYPE
|
|
SYNTAX VpwrPMCnfgValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current configuration of the TRIO/PM86000, input 2"
|
|
::= {vpwrPMCnfgEntry 4}
|
|
|
|
vpwrPMCnfg3 OBJECT-TYPE
|
|
SYNTAX VpwrPMCnfgValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current configuration of the TRIO/PM86000, input 3"
|
|
::= {vpwrPMCnfgEntry 5}
|
|
|
|
vpwrPMCnfg4 OBJECT-TYPE
|
|
SYNTAX VpwrPMCnfgValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current configuration of the TRIO/PM86000, input 4"
|
|
::= {vpwrPMCnfgEntry 6}
|
|
|
|
vpwrPMCnfg5 OBJECT-TYPE
|
|
SYNTAX VpwrPMCnfgValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current configuration of the TRIO/PM86000, input 5"
|
|
::= {vpwrPMCnfgEntry 7}
|
|
|
|
vpwrPMCnfg6 OBJECT-TYPE
|
|
SYNTAX VpwrPMCnfgValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current configuration of the TRIO/PM86000, input 6"
|
|
::= {vpwrPMCnfgEntry 8}
|
|
|
|
vpwrPMCnfg7 OBJECT-TYPE
|
|
SYNTAX VpwrPMCnfgValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current configuration of the TRIO (PM86000), input 7"
|
|
::= {vpwrPMCnfgEntry 9}
|
|
|
|
vpwrPMCnfg8 OBJECT-TYPE
|
|
SYNTAX VpwrPMCnfgValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current configuration of the TRIO/PM86000, input 8"
|
|
::= {vpwrPMCnfgEntry 10}
|
|
|
|
-------------------------------------------------------------------------------------------
|
|
|
|
vpwrPMInputStatusTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrPMInputStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table shows the current values of the TRIO/PM86000/Controller inputs."
|
|
::= { vpwrDcPowerPMModule 2 }
|
|
|
|
vpwrPMInputStatusEntry OBJECT-TYPE
|
|
SYNTAX VpwrPMInputStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing current state of the TRIO/PM86000/Controller inputs."
|
|
INDEX { vpwrPMIndex1 }
|
|
::= { vpwrPMInputStatusTable 1 }
|
|
|
|
VpwrPMInputStatusEntry ::= SEQUENCE {
|
|
vpwrPMIndex1 NonNegativeInteger,
|
|
vpwrPMDescription1 DisplayString,
|
|
vpwrPMInput1State SysInputValue,
|
|
vpwrPMInput2State SysInputValue,
|
|
vpwrPMInput3State SysInputValue,
|
|
vpwrPMInput4State SysInputValue,
|
|
vpwrPMInput5State SysInputValue,
|
|
vpwrPMInput6State SysInputValue,
|
|
vpwrPMInput7State SysInputValue,
|
|
vpwrPMInput8State SysInputValue
|
|
}
|
|
|
|
vpwrPMIndex1 OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter describes which TRIO/PM86000 device is being accessed."
|
|
::= {vpwrPMInputStatusEntry 1}
|
|
|
|
vpwrPMDescription1 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter describes the input values of the TRIO/PM86000 device."
|
|
::= {vpwrPMInputStatusEntry 2}
|
|
|
|
vpwrPMInput1State OBJECT-TYPE
|
|
SYNTAX SysInputValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current state of input 1"
|
|
::= {vpwrPMInputStatusEntry 3}
|
|
|
|
vpwrPMInput2State OBJECT-TYPE
|
|
SYNTAX SysInputValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current state of input 2"
|
|
::= {vpwrPMInputStatusEntry 4}
|
|
|
|
vpwrPMInput3State OBJECT-TYPE
|
|
SYNTAX SysInputValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current state of input 3"
|
|
::= {vpwrPMInputStatusEntry 5}
|
|
|
|
vpwrPMInput4State OBJECT-TYPE
|
|
SYNTAX SysInputValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current state of input 4"
|
|
::= {vpwrPMInputStatusEntry 6}
|
|
|
|
vpwrPMInput5State OBJECT-TYPE
|
|
SYNTAX SysInputValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current state of input 5"
|
|
::= {vpwrPMInputStatusEntry 7}
|
|
|
|
vpwrPMInput6State OBJECT-TYPE
|
|
SYNTAX SysInputValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current state of input 6"
|
|
::= {vpwrPMInputStatusEntry 8}
|
|
|
|
vpwrPMInput7State OBJECT-TYPE
|
|
SYNTAX SysInputValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current state of input 7"
|
|
::= {vpwrPMInputStatusEntry 9}
|
|
|
|
vpwrPMInput8State OBJECT-TYPE
|
|
SYNTAX SysInputValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter gets the current state of input 8"
|
|
::= {vpwrPMInputStatusEntry 10}
|
|
|
|
-------------------------------------------------------------------------------------------
|
|
vpwrPMRelayCtrlTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrPMRelayCtrlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table describes/controls system relays."
|
|
::= { vpwrDcPowerPMModule 3 }
|
|
|
|
vpwrPMRelayCtrlEntry OBJECT-TYPE
|
|
SYNTAX VpwrPMRelayCtrlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing current state of the relays."
|
|
INDEX { vpwrPMIndex2 }
|
|
::= { vpwrPMRelayCtrlTable 1 }
|
|
|
|
VpwrPMRelayCtrlEntry ::= SEQUENCE {
|
|
vpwrPMIndex2 NonNegativeInteger,
|
|
vpwrPMDescription2 DisplayString,
|
|
vpwrPMRelay1State INTEGER,
|
|
vpwrPMRelay2State INTEGER,
|
|
vpwrPMRelay3State INTEGER,
|
|
vpwrPMRelay4State INTEGER,
|
|
vpwrPMRelay5State INTEGER,
|
|
vpwrPMRelay6State INTEGER
|
|
}
|
|
|
|
vpwrPMIndex2 OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter describes the TRIO/PM device"
|
|
::= {vpwrPMRelayCtrlEntry 1}
|
|
|
|
vpwrPMDescription2 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter describes the TRIO/PM device"
|
|
::= {vpwrPMRelayCtrlEntry 2}
|
|
|
|
vpwrPMRelay1State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
vpwrPMRelayOff(0),
|
|
vpwrPMRelayOn(1),
|
|
undefined(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter sets the current state of relay 1"
|
|
::= {vpwrPMRelayCtrlEntry 3}
|
|
|
|
vpwrPMRelay2State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
vpwrPMRelayOff(0),
|
|
vpwrPMRelayOn(1),
|
|
undefined(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter sets the current state of relay 2"
|
|
::= {vpwrPMRelayCtrlEntry 4}
|
|
|
|
vpwrPMRelay3State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
vpwrPMRelayOff(0),
|
|
vpwrPMRelayOn(1),
|
|
undefined(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter sets the current state of relay 3"
|
|
::= {vpwrPMRelayCtrlEntry 5}
|
|
|
|
vpwrPMRelay4State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
vpwrPMRelayOff(0),
|
|
vpwrPMRelayOn(1),
|
|
undefined(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter sets the current state of relay 4"
|
|
::= {vpwrPMRelayCtrlEntry 6}
|
|
|
|
vpwrPMRelay5State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
vpwrPMRelayOff(0),
|
|
vpwrPMRelayOn(1),
|
|
undefined(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter sets the current state of relay 5"
|
|
::= {vpwrPMRelayCtrlEntry 7}
|
|
|
|
vpwrPMRelay6State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
vpwrPMRelayOff(0),
|
|
vpwrPMRelayOn(1),
|
|
undefined(255)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter sets the current state of relay 6"
|
|
::= {vpwrPMRelayCtrlEntry 8}
|
|
|
|
|
|
|
|
--
|
|
-- The Ringer Configuration Parameters group.
|
|
--
|
|
|
|
|
|
vpwrRingerIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..2)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter allows selecting ringer A or Ringer B as the active ringer.
|
|
"
|
|
::= {vpwrRingerConfigGroup 1}
|
|
|
|
vpwrRingerParameterAdminState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ringerDisabled(0),
|
|
ringerAOn(1) ,
|
|
ringerBOn(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter allows selecting ringer A or Ringer B as the active ringer.
|
|
"
|
|
::= {vpwrRingerConfigGroup 2}
|
|
|
|
vpwrRingerParameterAcVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER (7000..10000)
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter sets the output AC voltage of the ringer.
|
|
"
|
|
::= {vpwrRingerConfigGroup 3}
|
|
|
|
vpwrRingerParameterDcVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER (0..5500 )
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter sets the DC offset value of the ringer.
|
|
"
|
|
::= {vpwrRingerConfigGroup 4}
|
|
|
|
vpwrRingerParameterFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER (17..50)
|
|
UNITS " Hz"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter sets the ringer AC frequency.
|
|
"
|
|
::= {vpwrRingerConfigGroup 5}
|
|
|
|
vpwrRingerNumberPresent OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present number of ringer modules."
|
|
::= { vpwrRingerConfigGroup 6 }
|
|
|
|
|
|
--
|
|
-- ringer Alarm Group
|
|
--
|
|
|
|
vpwrRingerAlarmAFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ringer A Failed"
|
|
::= {vpwrRingerAlarmGroup 1 }
|
|
|
|
vpwrRingerAlarmAOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ringer A Heatsink Over-Temperature"
|
|
::= {vpwrRingerAlarmGroup 2 }
|
|
|
|
vpwrRingerAlarmAOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ringer A Over-Current protection"
|
|
::= {vpwrRingerAlarmGroup 3 }
|
|
|
|
vpwrRingerAlarmBFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ringer B Failed"
|
|
::= {vpwrRingerAlarmGroup 4 }
|
|
|
|
vpwrRingerAlarmBOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ringer B Heatsink Over-Temperature"
|
|
::= {vpwrRingerAlarmGroup 5 }
|
|
|
|
vpwrRingerAlarmBOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ringer B Over-Current protection"
|
|
::= {vpwrRingerAlarmGroup 6 }
|
|
|
|
|
|
|
|
vpwrBoostAdminState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
boostDisabled(0),
|
|
boostEnabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter allows enabling or disabling boost.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryBoostGroup 1}
|
|
|
|
vpwrBoostVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryBoostGroup 2}
|
|
|
|
vpwrBoostDuration OBJECT-TYPE
|
|
SYNTAX INTEGER (1..921599)
|
|
UNITS "Seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Number of seconds for boost.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryBoostGroup 3}
|
|
|
|
vpwrBoostOperState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
boostInactive(0),
|
|
boostActive(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter allows starting or stopping boost if it is enabled.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryBoostGroup 4}
|
|
|
|
|
|
vpwrBatteryCurrentLimitAdminState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
batteryCurrentLimitDisabled(0),
|
|
batteryCurrentLimitEnabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This parameter allows enabling or disabling battery current limit.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryCurrentGroup 1}
|
|
|
|
vpwrBatteryCurrentLimit OBJECT-TYPE
|
|
SYNTAX INTEGER (5..600)
|
|
UNITS "Ampere"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryCurrentGroup 2}
|
|
|
|
vpwrBatteryCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Ampere"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery current
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryCurrentGroup 3}
|
|
|
|
|
|
|
|
vpwrBDTAdminState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
bdtManualDisabled(0),
|
|
bdtManualEnabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Enable / Disable Battery Discharge Test execution.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryDischargeTestGroup 1}
|
|
|
|
vpwrBDTDuration OBJECT-TYPE
|
|
SYNTAX INTEGER (0..64799)
|
|
UNITS "Seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"BDT Duration Setpoint.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryDischargeTestGroup 2}
|
|
vpwrBDTAlarmVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"BDT Alarm Voltage Setpoint.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryDischargeTestGroup 3}
|
|
|
|
vpwrBDTAbortVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"BDT Abort Voltage Setpoint.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryDischargeTestGroup 4}
|
|
|
|
vpwrBDTAlarmCoefficient OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "None"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Deprecated. Always returns 1
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBatteryDischargeTestGroup 5}
|
|
|
|
vpwrBDTOperState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
bdtInactive(0),
|
|
bdtManualStart(1),
|
|
bdtACFailStart(14)
|
|
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Start/Stop Battery Discharge Test execution.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryDischargeTestGroup 6}
|
|
|
|
vpwrBDTClearAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
bdtNoAlarm(0),
|
|
bdtAlarmPresent(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Clears any active BDT alarm.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryDischargeTestGroup 7}
|
|
|
|
vpwrBDTActualTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Actual BDT runtime in minutes.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryDischargeTestGroup 8}
|
|
|
|
vpwrBDTAlarmDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Delay, in minutes, before checking and raising
|
|
BDT alarm.
|
|
Test: Plant Voltage <= BDTAlarmVoltage
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryDischargeTestGroup 9}
|
|
vpwrBDTResult OBJECT-TYPE
|
|
SYNTAX BDTResultTC
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Results of BDT.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryDischargeTestGroup 10}
|
|
|
|
vpwrBDTAutoAdminState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
bdtAutoDisabled(0),
|
|
bdtAutoEnabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Enable /Disable Battery Discharge Test data collection
|
|
upon detecting AC Fail condition.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBatteryDischargeTestGroup 11}
|
|
|
|
--
|
|
-- BDT History Start
|
|
--
|
|
-- The System History group.
|
|
--
|
|
vpwrBDTHistTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrBDTHistEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This table provides results of past BDT test.
|
|
"
|
|
::= { vpwrBatteryDischargeTestGroup 12 }
|
|
|
|
|
|
vpwrBDTHistEntry OBJECT-TYPE
|
|
SYNTAX VpwrBDTHistEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular BDT History."
|
|
|
|
INDEX { vpwrBDTHistIndex }
|
|
|
|
::= { vpwrBDTHistTable 1 }
|
|
VpwrBDTHistEntry ::= SEQUENCE {
|
|
vpwrBDTHistIndex PositiveInteger,
|
|
vpwrBDTHistDateTime DisplayString,
|
|
vpwrBDTHistDuration PositiveInteger,
|
|
vpwrBDTHistAlarmVoltage PositiveInteger,
|
|
vpwrBDTHistAbortVoltage PositiveInteger,
|
|
vpwrBDTHistStartMethod BDTStartSourceTC,
|
|
vpwrBDTHistResult BDTResultTC,
|
|
vpwrBDTHistActualTime PositiveInteger,
|
|
vpwrBDTHistStartVoltage PositiveInteger,
|
|
vpwrBDTHistEndVoltage PositiveInteger
|
|
}
|
|
|
|
vpwrBDTHistIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"BDT History index."
|
|
::= { vpwrBDTHistEntry 1 }
|
|
|
|
vpwrBDTHistDateTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" BDT run date as
|
|
yr-mm-dd hh:mm
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBDTHistEntry 2}
|
|
vpwrBDTHistDuration OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
UNITS "Minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"BDT duration at the time
|
|
this test was run.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBDTHistEntry 3}
|
|
|
|
vpwrBDTHistAlarmVoltage OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"BDT Alarm Voltage setpoint when
|
|
this test was run.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBDTHistEntry 4}
|
|
|
|
vpwrBDTHistAbortVoltage OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"BDT Abort Voltage setpoint when
|
|
this test was run.
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBDTHistEntry 5}
|
|
|
|
|
|
vpwrBDTHistStartMethod OBJECT-TYPE
|
|
SYNTAX BDTStartSourceTC
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"How Battery Discharge Test
|
|
was started.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBDTHistEntry 6}
|
|
|
|
vpwrBDTHistResult OBJECT-TYPE
|
|
SYNTAX BDTResultTC
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Results of BDT.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBDTHistEntry 7}
|
|
|
|
vpwrBDTHistActualTime OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" Actual BDT runtime in minutes.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBDTHistEntry 8}
|
|
|
|
vpwrBDTHistStartVoltage OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Plant Voltage at the time
|
|
the BDT was started.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBDTHistEntry 9}
|
|
vpwrBDTHistEndVoltage OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
UNITS " *.01 Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Plant Voltage at the time
|
|
the BDT was completed.
|
|
"
|
|
REFERENCE " "
|
|
|
|
::= {vpwrBDTHistEntry 10}
|
|
|
|
-- BDT History End
|
|
|
|
-- BDT scheduled Start
|
|
--
|
|
-- The System History group.
|
|
--
|
|
vpwrBDTSchedTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VpwrBDTSchedEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This table provides the list of the 12 BDTs that can be
|
|
scheduled. Need to set date(month and day) and
|
|
time (hh and minutes) when the test should be
|
|
started.
|
|
"
|
|
::= { vpwrBatteryDischargeTestGroup 13 }
|
|
|
|
|
|
vpwrBDTSchedEntry OBJECT-TYPE
|
|
SYNTAX VpwrBDTSchedEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry describing an alarm."
|
|
INDEX { vpwrBDTSchedIndex}
|
|
::= { vpwrBDTSchedTable 1 }
|
|
|
|
VpwrBDTSchedEntry ::= SEQUENCE {
|
|
vpwrBDTSchedIndex PositiveInteger,
|
|
vpwrBDTSchedMonth PositiveInteger,
|
|
vpwrBDTSchedDay PositiveInteger,
|
|
vpwrBDTSchedHour PositiveInteger,
|
|
vpwrBDTSchedMinute PositiveInteger
|
|
}
|
|
|
|
vpwrBDTSchedIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"BDT Sched index."
|
|
::= { vpwrBDTSchedEntry 1 }
|
|
|
|
vpwrBDTSchedDay OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" 1 to 28,29,30 or 31 depending upon the month
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBDTSchedEntry 2}
|
|
|
|
vpwrBDTSchedMonth OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" range 1 to 12
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBDTSchedEntry 3}
|
|
|
|
vpwrBDTSchedHour OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" range 0 to 23
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBDTSchedEntry 4}
|
|
|
|
vpwrBDTSchedMinute OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" range 0 to 59
|
|
"
|
|
REFERENCE " "
|
|
::= {vpwrBDTSchedEntry 5}
|
|
|
|
|
|
-- BDT Scheduled End
|
|
|
|
--
|
|
-- traps
|
|
--
|
|
-- New Rules for trap numbering
|
|
-- Rules are even number = trap set
|
|
-- odd number = trap clear
|
|
|
|
vpwrTrapPowerMajorAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Major Alarm"
|
|
::= {vpwrDcPowerTraps 1}
|
|
|
|
vpwrTrapPowerMinorAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Minor Alarm"
|
|
::= {vpwrDcPowerTraps 2}
|
|
|
|
vpwrTrapACFAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "AC Fail Alarm"
|
|
::= {vpwrDcPowerTraps 3}
|
|
|
|
vpwrTrapHVAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "High Voltage Warning Alarm"
|
|
::= {vpwrDcPowerTraps 4}
|
|
|
|
vpwrTrapHVSDAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "High Voltage Shutdown Alarm"
|
|
::= {vpwrDcPowerTraps 5}
|
|
|
|
vpwrTrapBDAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Battery on Discharge Alarm"
|
|
::= {vpwrDcPowerTraps 6}
|
|
|
|
vpwrTrapLVDWarningAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "LVD Warning Alarm"
|
|
::= {vpwrDcPowerTraps 7}
|
|
|
|
vpwrTrapLVDOpenAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "LVD Open Alarm"
|
|
::= {vpwrDcPowerTraps 8}
|
|
|
|
vpwrTrapDistAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Distribution Open Alarm"
|
|
::= {vpwrDcPowerTraps 9}
|
|
|
|
vpwrTrapAuxAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Auxiliary System Alarm"
|
|
::= {vpwrDcPowerTraps 10}
|
|
|
|
vpwrTrapSystemRedundancyAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "System Redundant Capacity Alarm"
|
|
::= {vpwrDcPowerTraps 11}
|
|
|
|
vpwrTrapIShareAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Rectifier Current Share Alarm"
|
|
::= {vpwrDcPowerTraps 12}
|
|
|
|
vpwrTrapModuleFailAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Single Rectifier Fail Alarm"
|
|
::= {vpwrDcPowerTraps 13}
|
|
|
|
vpwrTrapMultipleModuleFailAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Multiple Rectifier Fail Alarm"
|
|
::= {vpwrDcPowerTraps 14}
|
|
|
|
vpwrTrapModuleCommAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Power Module Communication Alarm"
|
|
::= {vpwrDcPowerTraps 15}
|
|
|
|
vpwrTrapSystemOverTemperatureAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "System Over Temperature Alarm"
|
|
::= {vpwrDcPowerTraps 16}
|
|
|
|
vpwrTrapSystemOK NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "SYSTEM OK - No Active Alarms"
|
|
::= {vpwrDcPowerTraps 17}
|
|
|
|
vpwrTrapModuleInserted NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString, vpwrBayIndex, vpwrModuleIndex }
|
|
STATUS current
|
|
DESCRIPTION "A new module has been inserted into the system"
|
|
::= {vpwrDcPowerTraps 18}
|
|
|
|
vpwrTrapModuleRemoved NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString,vpwrBayIndex, vpwrModuleIndex }
|
|
STATUS current
|
|
DESCRIPTION "A module has been removed from the system"
|
|
::= {vpwrDcPowerTraps 19}
|
|
|
|
vpwrTrapThermalCompActive NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Thermal compensation has become active"
|
|
::= {vpwrDcPowerTraps 20}
|
|
|
|
vpwrTrapThermalCompInactive NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Thermal compensation has been de-activated"
|
|
::= {vpwrDcPowerTraps 21}
|
|
|
|
vpwrTrapInternalTempAlarmSet NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Internal Temperature upper threshold exceeded"
|
|
::= {vpwrDcPowerTraps 22}
|
|
|
|
vpwrTrapInternalTempAlarmCleared NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Internal Temperature within limits"
|
|
::= {vpwrDcPowerTraps 23}
|
|
|
|
vpwrTrapBatteryTempAlarmSet NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
At least one Battery Temperature exceeded upper threshold"
|
|
::= {vpwrDcPowerTraps 24}
|
|
|
|
vpwrTrapBatteryTempAlarmCleared NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
All Battery Temperatures within limits"
|
|
::= {vpwrDcPowerTraps 25}
|
|
|
|
vpwrTrapLoginFail NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Admin login failed due to wrong username/password"
|
|
::= {vpwrDcPowerTraps 26}
|
|
|
|
vpwrTrapLoginSuccess NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Admin login successful"
|
|
::= {vpwrDcPowerTraps 27}
|
|
|
|
vpwrTrapLogout NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Admin logout"
|
|
::= {vpwrDcPowerTraps 28}
|
|
|
|
vpwrTrapAdminPwdChange NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Config change submitted with invalid access"
|
|
::= {vpwrDcPowerTraps 29}
|
|
|
|
vpwrTrapIllegalConfigSubmit NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Config change submitted with invalid access"
|
|
::= {vpwrDcPowerTraps 30}
|
|
|
|
vpwrTrapCfgChange NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Config change submitted"
|
|
::= {vpwrDcPowerTraps 31}
|
|
|
|
vpwrTrapClearEventHistory NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Clear Event history buffer clear request"
|
|
::= {vpwrDcPowerTraps 32}
|
|
|
|
vpwrTrapSwDownloadNoReboot NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
System software upgrade without reboot"
|
|
::= {vpwrDcPowerTraps 33}
|
|
|
|
vpwrTrapSwDownloadAndReboot NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
System reboot due to software upgrade"
|
|
::= {vpwrDcPowerTraps 34}
|
|
|
|
vpwrTrapSystemClockChange NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
System clock updated"
|
|
::= {vpwrDcPowerTraps 35}
|
|
|
|
vpwrTrapModuleAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Module Alarm"
|
|
::= {vpwrDcPowerTraps 36}
|
|
|
|
vpwrTrapOIDChange NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Change in OID"
|
|
::= {vpwrDcPowerTraps 37}
|
|
|
|
vpwrTrapThermalRunaway NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Thermal Runaway Alarm"
|
|
::= {vpwrDcPowerTraps 38}
|
|
|
|
vpwrTrapBatteryDischargeTestAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "System Voltage dropped to BDT Alarm Setpoint"
|
|
::= {vpwrDcPowerTraps 39}
|
|
|
|
vpwrTrapBayUnnameAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Unassigned Bay Fail Alarm"
|
|
::= {vpwrDcPowerTraps 40}
|
|
|
|
vpwrTrapPMComFailAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
PM Communication Fail Alarm"
|
|
::= {vpwrDcPowerTraps 41}
|
|
|
|
vpwrTrapFuseOverloadAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Fuse Overload Alarm"
|
|
::= {vpwrDcPowerTraps 42}
|
|
|
|
vpwrTrapPeripheralAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Peripheral Alarm."
|
|
::= {vpwrDcPowerTraps 43}
|
|
|
|
vpwrTrapThermalProbeAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Thermal Probe Missing Alarm"
|
|
::= {vpwrDcPowerTraps 44}
|
|
|
|
vpwrTrapBayCommAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Bay Communication Alarm"
|
|
::= {vpwrDcPowerTraps 45}
|
|
|
|
vpwrTrapDistributionCommAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Distribution Communication Alarm"
|
|
::= {vpwrDcPowerTraps 46}
|
|
|
|
vpwrTrapConverterAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Single Converter Fail Alarm"
|
|
::= {vpwrDcPowerTraps 47}
|
|
|
|
vpwrTrapMultipleConvFailAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Multiple Converter Fail Alarm"
|
|
::= {vpwrDcPowerTraps 48}
|
|
|
|
vpwrTrapDGUAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! For Future Use. !!!
|
|
DGU Alarm"
|
|
::= {vpwrDcPowerTraps 49}
|
|
|
|
vpwrTrapConfigErrorAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Configuration Error"
|
|
::= {vpwrDcPowerTraps 50}
|
|
|
|
vpwrTrapDisplayFirmwareMismatchAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Display Firmware Mismatch"
|
|
::= {vpwrDcPowerTraps 51}
|
|
|
|
vpwrTrapConverterInputFailAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Converter Input Fail Alarm"
|
|
::= {vpwrDcPowerTraps 52}
|
|
|
|
vpwrTrapBatteryRechgIlimitFailAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Battery Recharge Current Limit Fail"
|
|
::= {vpwrDcPowerTraps 53}
|
|
|
|
vpwrTrapSystemAlive NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Periodic Keepalive trap"
|
|
::= {vpwrDcPowerTraps 54}
|
|
|
|
vpwrTrapSystemAuxAlmSource NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString,
|
|
vpwrAlarmingModuleOID,
|
|
vpwrAlarmingModuleIndex,
|
|
vpwrAlarmingSubModuleBitMap }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Source of Auxilary Alarms.
|
|
Indicates the module and the aux within
|
|
the module causing alarms"
|
|
::= {vpwrDcPowerTraps 55}
|
|
|
|
vpwrTrapSystemDistAlmSource NOTIFICATION-TYPE
|
|
OBJECTS{ vpwrTrapsMsgString,
|
|
vpwrAlarmingModuleOID,
|
|
vpwrAlarmingModuleIndex,
|
|
vpwrAlarmingSubModuleBitMap }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Source of Distribution Alarms.
|
|
Indicates the module and the dist within
|
|
the module causing alarms"
|
|
::= {vpwrDcPowerTraps 56}
|
|
|
|
vpwrTrapSystemBatCapacityAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString,
|
|
vpwrSystemCurrent,
|
|
vpwrBatteryCurrentCapacity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Plant Load exceeds Plant Battery Current Capacity.
|
|
Useful for batteries that limit maximum discharge current
|
|
It will not be sent out for VRLA batteries, eg"
|
|
|
|
::= {vpwrDcPowerTraps 58}
|
|
|
|
vpwrTrapSystemACFClearAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString,
|
|
vpwrTrapAcfDuration}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC Fail (ACF) Conditioned Cleared Alarm.
|
|
Duration is in minutes.
|
|
"
|
|
::= {vpwrDcPowerTraps 61}
|
|
|
|
vpwrTrapSystemACFSetAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString,
|
|
vpwrTrapAcfDuration}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ACF Conditioned detected Alarm.
|
|
The duration would always be zero.
|
|
Msg String: ACF Alarm Set
|
|
"
|
|
::= {vpwrDcPowerTraps 62}
|
|
|
|
vpwrTrapSystemBatCapacityLeft NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString,
|
|
vpwrBatteryRemainingTime }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"!!! For Future Use. !!!
|
|
Battery Useful Capacity Remaining"
|
|
::= {vpwrDcPowerTraps 64}
|
|
|
|
vpwrTrapRectifierUVAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString, vpwrBayIndex, vpwrModuleIndex }
|
|
STATUS current
|
|
DESCRIPTION "Rectifier Under Voltage Alarm"
|
|
::= {vpwrDcPowerTraps 65}
|
|
|
|
vpwrTrapMultRectifierUVAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! For Future Use. !!!
|
|
Multiple Rectifier Under Voltage Alarm"
|
|
::= {vpwrDcPowerTraps 66}
|
|
|
|
vpwrTrapRingerAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Ringer Alarm"
|
|
::= {vpwrDcPowerTraps 67}
|
|
|
|
vpwrTrapMultRingerAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString}
|
|
STATUS current
|
|
DESCRIPTION "!!! For Future Use. !!!
|
|
Multiple Ringer Alarm"
|
|
::= {vpwrDcPowerTraps 68}
|
|
|
|
vpwrTrapI2CCANAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString}
|
|
STATUS current
|
|
DESCRIPTION "!!! For Future Use. !!!
|
|
Unmapped I2C/CAN Address Alarm
|
|
One of your I2C or CAN devices
|
|
has a duplicate or invalid address
|
|
and can not be mapped. Please
|
|
recheck all device addresses."
|
|
::= {vpwrDcPowerTraps 69}
|
|
|
|
vpwrTrapRectifierIlimitAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString, vpwrBayIndex, vpwrModuleIndex }
|
|
STATUS current
|
|
DESCRIPTION "Rectifier Current Limit Alarm"
|
|
::= {vpwrDcPowerTraps 70}
|
|
|
|
vpwrTrapMultRectifierIlimitAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "!!! For Future Use. !!!
|
|
Multiple Rectifier Current Limit Alarm"
|
|
::= {vpwrDcPowerTraps 71}
|
|
|
|
vpwrTrapRingerCommAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString }
|
|
STATUS current
|
|
DESCRIPTION "Ringer Communication Alarm"
|
|
::= {vpwrDcPowerTraps 72}
|
|
|
|
vpwrTrapUnassignedAlarm NOTIFICATION-TYPE
|
|
OBJECTS { vpwrTrapsMsgString}
|
|
STATUS current
|
|
DESCRIPTION "!!! NOT VALID FOR BC2000 CONTROLLER !!!
|
|
Unassigned Alarm(Trap) - Check Web Page"
|
|
::= {vpwrDcPowerTraps 99}
|
|
|
|
END
|