209 lines
7.4 KiB
Plaintext
209 lines
7.4 KiB
Plaintext
CTRON-UPS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
-- ctron-ups-mib.txt
|
|
-- Revision: 1.03.00
|
|
-- Part Number: 2170564
|
|
-- Date: May 1, 1996
|
|
|
|
-- Cabletron Systems, Inc.
|
|
-- 35 Industrial Way, P.O. Box 5005
|
|
-- Rochester, NH 03867-0505
|
|
-- (603) 332-9400
|
|
-- support@ctron.com
|
|
|
|
-- This module provides authoritative definitions for Cabletron's
|
|
-- enterprise-specific UPS MIB.
|
|
--
|
|
-- This module will be extended, as required.
|
|
--
|
|
|
|
-- Cabletron Systems reserves the right to make changes in
|
|
-- specification and other information contained in this document
|
|
-- without prior notice. The reader should consult Cabletron Systems
|
|
-- to determine whether any such changes have been made.
|
|
--
|
|
-- In no event shall Cabletron Systems be liable for any incidental,
|
|
-- indirect, special, or consequential damages whatsoever (including
|
|
-- but not limited to lost profits) arising out of or related to this
|
|
-- document or the information contained in it, even if Cabletron
|
|
-- Systems has been advised of, known, or should have known, the
|
|
-- possibility of such damages.
|
|
--
|
|
-- Cabletron grants vendors, end-users, and other interested parties
|
|
-- a non-exclusive license to use this Specification in connection
|
|
-- with the management of Cabletron products.
|
|
|
|
-- Copyright October 95 Cabletron Systems
|
|
|
|
-- This MIB is implemented whenever a uninterruptable power
|
|
-- supply is implemented.
|
|
|
|
IMPORTS
|
|
ctUPowerSupply FROM CTRON-MIB-NAMES
|
|
OBJECT-TYPE FROM RFC-1212;
|
|
|
|
ctUPS OBJECT IDENTIFIER ::= { ctUPowerSupply 1 }
|
|
|
|
|
|
-- The ups group
|
|
|
|
-- Implementation of this group is mandatory for devices that
|
|
-- incorporate uninterruptible power supplies.
|
|
|
|
|
|
ctUpsID OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other(1), -- none of the following
|
|
aPCModel370(257),
|
|
aPCModel400(258),
|
|
aPCModel600(259),
|
|
aPCModel900(260),
|
|
aPCModel1250(261),
|
|
aPCModel2000(262),
|
|
matrix3000(263),
|
|
matrix5000(264),
|
|
su700(265),
|
|
su1400(266),
|
|
su2000XL(267),
|
|
aPCGeneric(268) -- Generic APC for use when APC is not
|
|
-- otherwise defined.
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Denotes a type code which refers to the
|
|
manufacturers and model of the UPS."
|
|
::= { ctUPS 1 }
|
|
|
|
ctUpsUpTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Denotes the operating time, in hours, since the UPS
|
|
was last powered on."
|
|
::= { ctUPS 2 }
|
|
|
|
ctUpsDisable OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Allows the UPS to be disabled. A set turns of the
|
|
UPS for those systems, so equipped. A get/get-next
|
|
always returns 0."
|
|
::= { ctUPS 3 }
|
|
|
|
ctUpsDisconnect OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Allows the UPS backup power system to conserve its
|
|
battery. A set turns off the power system. A
|
|
get/get-next always returns a 0."
|
|
::= { ctUPS 4 }
|
|
|
|
ctUpsTest OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unitOK(1),
|
|
unitFailed(2),
|
|
badBattery(3),
|
|
noRecentTest(4), -- no test performed in the last five
|
|
-- minutes
|
|
underTest(5)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Denotes the status performed on the UPS. A write
|
|
initiates the test. A read indicates status of
|
|
test."
|
|
::= { ctUPS 5 }
|
|
|
|
ctUpsBatteryCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Denotes the percentage of battery capacity left,
|
|
100% being a fully-charged battery."
|
|
::= { ctUPS 6 }
|
|
|
|
ctUpsACLineVoltsIn OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Denotes the input AC utility line voltage."
|
|
::= { ctUPS 7 }
|
|
|
|
ctUpsBatteryVoltsOut OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Denotes the battery voltage."
|
|
::= { ctUPS 8 }
|
|
|
|
-- Enterprise specific trap definitions
|
|
|
|
-- aPCLineFail OBJECT-TYPE
|
|
-- ENTERPRISE cabletron
|
|
-- DESCRIPTION
|
|
-- "This trap is generated in the event of an AC
|
|
-- utility line failure."
|
|
-- ::= 0x1101
|
|
--
|
|
-- aPCLineFailRecovery OBJECT-TYPE
|
|
-- ENTERPRISE cabletron
|
|
-- DESCRIPTION
|
|
-- "This trap is generated when the UPS switches back
|
|
-- to line, and only if the aPCLineFail trap was issued
|
|
-- first."
|
|
-- ::= 0x1102
|
|
--
|
|
-- aPCLowBattery OBJECT-TYPE
|
|
-- ENTERPRISE cabletron
|
|
-- DESCRIPTION
|
|
-- "This trap is generated in the event that the UPS'
|
|
-- battery is found to be low."
|
|
-- ::= 0x1103
|
|
--
|
|
-- aPCLowBatteryRecovery OBJECT-TYPE
|
|
-- ENTERPRISE cabletron
|
|
-- DESCRIPTION
|
|
-- "This trap is generated when the UPS' battery has
|
|
-- charged above the low-battery point, and only if the
|
|
-- aPCLowBattery trap was issued first."
|
|
-- ::= 0x1104
|
|
--
|
|
-- aPCAbnormalCondition OBJECT-TYPE
|
|
-- ENTERPRISE cabletron
|
|
-- DESCRIPTION
|
|
-- "This trap is generated in the event that the UPS
|
|
-- has entered an abnormal condition, such as an
|
|
-- overload or trip on low battery. This trap is also
|
|
-- sent, when the UPS is first turned on."
|
|
-- ::= 0x1105
|
|
--
|
|
-- aPCAbnormalConditionRecovery OBJECT-TYPE
|
|
-- ENTERPRISE cabletron
|
|
-- DESCRIPTION
|
|
-- "This trap is generated when the UPS has recovered
|
|
-- from an abnormal condition, and only if the
|
|
-- aPCAb-normalCondition trap was issued first."
|
|
-- ::= 0x1106
|
|
--
|
|
-- aPCShuttingDown OBJECT-TYPE
|
|
-- ENTERPRISE cabletron
|
|
-- DESCRIPTION
|
|
-- "This trap is generated in the event that the UPS
|
|
-- has been ordered to shut itself, or the load, off
|
|
-- over the serial line."
|
|
-- ::= 0x1107
|
|
--
|
|
--
|
|
|
|
END
|