UPS2-MIB DEFINITIONS ::= BEGIN
|
|
|
|
-- ctron-ups2-mib.txt The UPS Revision 2 MIB
|
|
-- Revision: 1.01.00
|
|
-- Part Number:
|
|
-- Date: September 12, 1995
|
|
|
|
-- Cabletron Systems, Inc.
|
|
-- 35 Industrial Way, P.O. Box 5005
|
|
-- Rochester, NH 03867-0505
|
|
-- (603) 332-9400
|
|
-- support@ctron.com
|
|
|
|
-- This module provides authoritative definitions for Cabletron's
|
|
-- enterprise-specific UPS MIB.
|
|
--
|
|
-- This module will be extended, as needed.
|
|
--
|
|
|
|
-- Cabletron Systems reserves the right to make changes in
|
|
-- specification and other information contained in this document
|
|
-- without prior notice. The reader should consult Cabletron Systems
|
|
-- to determine whether any such changes have been made.
|
|
--
|
|
-- In no event shall Cabletron Systems be liable for any incidental,
|
|
-- indirect, special, or consequential damages whatsoever (including
|
|
-- but not limited to lost profits) arising out of or related to this
|
|
-- document or the information contained in it, even if Cabletron
|
|
-- Systems has been advised of, known, or should have known, the
|
|
-- possibility of such damages.
|
|
--
|
|
-- Cabletron grants vendors, end-users, and other interested parties
|
|
-- a non-exclusive license to use this Specification in connection
|
|
-- with the management of Cabletron products.
|
|
|
|
-- Copyright August 95 Cabletron Systems
|
|
|
|
IMPORTS
|
|
ctUPS
|
|
FROM CTRON-MIB-NAMES
|
|
DisplayString
|
|
FROM RFC1213-MIB
|
|
OBJECT-TYPE
|
|
FROM RFC-1212;
|
|
|
|
-- Textual convention
|
|
|
|
|
|
-- DisplayString ::= OCTET STRING
|
|
-- This data type is used to model textual information taken from
|
|
-- the NVT ASCII character set. By convention, objects with this
|
|
-- syntax, unless explicitly stated, are declared as having:
|
|
--
|
|
-- SIZE (0..255)
|
|
|
|
|
|
--=============== group definitions ====================
|
|
|
|
upsSystem OBJECT IDENTIFIER ::= { ctUPS 1 }
|
|
upsId OBJECT IDENTIFIER ::= { ctUPS 2 }
|
|
upsBattery OBJECT IDENTIFIER ::= { ctUPS 3 }
|
|
upsInput OBJECT IDENTIFIER ::= { ctUPS 4 }
|
|
upsOutput OBJECT IDENTIFIER ::= { ctUPS 5 }
|
|
upsStatus OBJECT IDENTIFIER ::= { ctUPS 6 }
|
|
upsConfig OBJECT IDENTIFIER ::= { ctUPS 7 }
|
|
upsExtMeas OBJECT IDENTIFIER ::= { ctUPS 8 }
|
|
upsAddlFuncs OBJECT IDENTIFIER ::= { ctUPS 9 }
|
|
|
|
|
|
|
|
--================ upsSystem group ====================
|
|
|
|
-- UPS System Group
|
|
-- Implementation of this group is mandatory
|
|
-- This group covers system-level information on the UPSs available
|
|
|
|
upsNumUPSs OBJECT-TYPE
|
|
SYNTAX INTEGER (0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of UPSs available."
|
|
::= { upsSystem 1 }
|
|
|
|
|
|
|
|
--=============== upsId group =====================
|
|
|
|
-- UPS Identification Group
|
|
-- Implementation of this group is mandatory if one or more UPSs
|
|
-- are to be monitored
|
|
-- This group covers identification information on the UPSs available
|
|
|
|
upsIdTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsIdEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of identification table entries. The number of
|
|
entries is given by the value of upsNumUPSs."
|
|
::= { upsId 1 }
|
|
|
|
upsIdEntry OBJECT-TYPE
|
|
SYNTAX UpsIdEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing objects for a particular UPS."
|
|
INDEX { upsIndex }
|
|
::= { upsIdTable 1 }
|
|
|
|
UpsIdEntry ::=
|
|
SEQUENCE {
|
|
upsIndex
|
|
INTEGER,
|
|
upsName
|
|
DisplayString,
|
|
upsModelType
|
|
INTEGER,
|
|
upsFwVersion
|
|
DisplayString,
|
|
upsSerialNumber
|
|
DisplayString,
|
|
upsManufDate
|
|
DisplayString
|
|
}
|
|
|
|
upsIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A unique value which identifies a particular UPS."
|
|
::= { upsIdEntry 1 }
|
|
|
|
upsName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..8))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's name. A maximum of 8 characters may be specified.
|
|
This object is initialized to the UPS's model name."
|
|
::= { upsIdEntry 2 }
|
|
|
|
upsModelType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
smartUps250(1),
|
|
smartUps400(2),
|
|
smartUps600(3),
|
|
smartUps900(4),
|
|
smartUps1250(5),
|
|
smartUps2000(6),
|
|
matrixUps3000(7),
|
|
matrixUps5000(8),
|
|
other(9)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's base model type."
|
|
::= { upsIdEntry 3 }
|
|
|
|
upsFwVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's firmware version."
|
|
::= { upsIdEntry 4 }
|
|
|
|
upsSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..16))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's serial number as set at the factory."
|
|
::= { upsIdEntry 5 }
|
|
|
|
upsManufDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's date of manufacture in the format mm/dd/yy."
|
|
::= { upsIdEntry 6 }
|
|
|
|
|
|
|
|
--=============== upsBattery group ====================
|
|
|
|
-- UPS Battery Group
|
|
-- Implementation of this group is mandatory if one or more UPSs
|
|
-- are to be monitored
|
|
-- This group covers information on the Batteries within each UPS
|
|
|
|
|
|
upsBatteryTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsBatteryEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of battery table entries. The number of
|
|
entries is given by the value of upsNumUPSs."
|
|
::= { upsBattery 1 }
|
|
|
|
upsBatteryEntry OBJECT-TYPE
|
|
SYNTAX UpsBatteryEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing objects for a particular UPS."
|
|
INDEX { upsIndex }
|
|
::= { upsBatteryTable 1 }
|
|
|
|
UpsBatteryEntry ::=
|
|
SEQUENCE {
|
|
upsBatteryCapacity
|
|
INTEGER,
|
|
upsBatteryVoltage
|
|
INTEGER,
|
|
upsBatteryTest
|
|
INTEGER,
|
|
upsBatteryTestResult
|
|
INTEGER,
|
|
upsRunTimeCalibration
|
|
INTEGER,
|
|
upsEstimatedRunTimeRemaining
|
|
INTEGER,
|
|
upsTransferCause
|
|
INTEGER,
|
|
upsBatteryTestTime
|
|
INTEGER,
|
|
upsLowBatteryWarning
|
|
INTEGER
|
|
}
|
|
|
|
upsBatteryCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's remaining battery capacity expressed as a percent
|
|
of the fully charged condition. The value of this object is
|
|
the actual percentage * 10 (that is, to determine the actual
|
|
percentage, divide the value of this object by 10)."
|
|
::= { upsBatteryEntry 1 }
|
|
|
|
upsBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's present battery voltage. The value of this object
|
|
is the actual voltage * 100 (that is, to determine the actual
|
|
voltage, divide the value of this object by 100)."
|
|
::= { upsBatteryEntry 2 }
|
|
|
|
upsBatteryTest OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
initiateTest(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object may be written to initiate testing of the UPS's
|
|
battery packs. Reading this object will always return a 0."
|
|
::= { upsBatteryEntry 3 }
|
|
|
|
upsBatteryTestResult OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
batteryOK(1),
|
|
batteryBad(2),
|
|
noRecentTest(3),
|
|
invalidTestDueToOverload(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The result of the last battery test performed."
|
|
::= { upsBatteryEntry 4 }
|
|
|
|
upsRunTimeCalibration OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
performTest(1),
|
|
abortTest(2),
|
|
testInProgress(3),
|
|
testNotInProgress(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object may be written to initiate or terminate the test
|
|
used to calibrate the returned run time value. This test
|
|
will only run if battery capacity is 100%. Results of this
|
|
test can be retrieved by upsEstimatedRunTimeRemaining. Valid
|
|
values for writing are 1 (initiate test) and 2 (terminate test).
|
|
In addition, this object may be read to determine whether
|
|
the test is currently running. Valid values for reading
|
|
are 3 (test is in progress) and 4 (test is not in progress)."
|
|
::= { upsBatteryEntry 5 }
|
|
|
|
upsEstimatedRunTimeRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's estimated remaining run time in minutes. The UPS
|
|
may be queried when operating in the on-line, bypass, or
|
|
on-battery modes of operation. The run time estimate is
|
|
based on available battery capacity and output load."
|
|
::= { upsBatteryEntry 6 }
|
|
|
|
upsTransferCause OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTransfer(1),
|
|
selfTest(2),
|
|
inputLineSpike(3),
|
|
inputLowVoltage(4),
|
|
inputHighVoltage(5),
|
|
inputLineFrequencyBad(6)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The reason for the most recent transfer to on-battery
|
|
operation."
|
|
::= { upsBatteryEntry 7 }
|
|
|
|
upsBatteryTestTime OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
twoWeeks(1),
|
|
oneWeek(2),
|
|
startupOnly(3),
|
|
off(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The frequency of execution of the UPS's automatic battery
|
|
test. The test may be run immediately upon startup, upon
|
|
startup and every 7 days thereafter, upon startup and every
|
|
14 days thereafter, or never."
|
|
DEFVAL { twoWeeks }
|
|
::= { upsBatteryEntry 8 }
|
|
|
|
upsLowBatteryWarning OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
twoMinutes(1),
|
|
fiveMinutes(2),
|
|
sevenMinutes(3),
|
|
tenMinutes(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The interval between activation of the UPS's low battery
|
|
alarm warnings and shutdown of the UPS."
|
|
DEFVAL { twoMinutes }
|
|
::= { upsBatteryEntry 9 }
|
|
|
|
|
|
--=============== upsInput group ====================
|
|
|
|
-- UPS Input Group
|
|
-- Implementation of this group is mandatory if one or more UPSs
|
|
-- are to be monitored
|
|
-- This group covers information on the AC Inputs to each UPS
|
|
|
|
upsInputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsInputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of input table entries. The number of
|
|
entries is given by the value of upsNumUPSs."
|
|
::= { upsInput 1 }
|
|
|
|
upsInputEntry OBJECT-TYPE
|
|
SYNTAX UpsInputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing objects for a particular UPS."
|
|
INDEX { upsIndex }
|
|
::= { upsInputTable 1 }
|
|
|
|
UpsInputEntry ::=
|
|
SEQUENCE {
|
|
upsInputUtilityVoltage
|
|
INTEGER,
|
|
upsInputVoltage
|
|
INTEGER,
|
|
upsInputFailureSensitivity
|
|
INTEGER,
|
|
upsInputMaxVoltage
|
|
INTEGER,
|
|
upsInputMinVoltage
|
|
INTEGER,
|
|
upsInputFrequency
|
|
INTEGER
|
|
}
|
|
|
|
upsInputUtilityVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
vac100(1),
|
|
vac120(2),
|
|
vac208(3),
|
|
vac220(4) -- 220/230/240
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's utility voltage version."
|
|
::= { upsInputEntry 1 }
|
|
|
|
upsInputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's measured utility input voltage. The value
|
|
of this object is the actual voltage * 10 (that is, to
|
|
determine the actual voltage, divide the value of this
|
|
object by 10)."
|
|
::= { upsInputEntry 2 }
|
|
|
|
upsInputFailureSensitivity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
high(1),
|
|
medium(2),
|
|
low(3),
|
|
auto(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The sensitivity of the UPS to rapid changes in utility
|
|
voltage (e.g., blackouts, spikes, or notches) or
|
|
abnormal changes in utility frequency."
|
|
DEFVAL { high }
|
|
::= { upsInputEntry 3 }
|
|
|
|
upsInputMaxVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's maximum input voltage recorded since this object
|
|
was last read. The value of this object is the actual
|
|
voltage * 10 (that is, to determine the actual voltage,
|
|
divide the value of this object by 10)."
|
|
::= { upsInputEntry 4 }
|
|
|
|
upsInputMinVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's minimum input voltage recorded since this object
|
|
was last read. The value of this object is the actual
|
|
voltage * 10 (that is, to determine the actual voltage,
|
|
divide the value of this object by 10)."
|
|
::= { upsInputEntry 5 }
|
|
|
|
upsInputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's present internal operating frequency in Hz.
|
|
The value of this object is the actual frequency * 100
|
|
(that is, to determine the actual frequency, divide
|
|
the value of this object by 100)."
|
|
::= { upsInputEntry 6 }
|
|
|
|
|
|
--=============== upsOutput group ===================
|
|
|
|
-- UPS Output Group
|
|
-- Implementation of this group is mandatory if one or more UPSs
|
|
-- are to be monitored
|
|
-- This group covers information on the AC Outputs from each UPS
|
|
|
|
upsOutputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsOutputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of output table entries. The number of
|
|
entries is given by the value of upsNumUPSs."
|
|
::= { upsOutput 1 }
|
|
|
|
upsOutputEntry OBJECT-TYPE
|
|
SYNTAX UpsOutputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing objects for a particular UPS."
|
|
INDEX { upsIndex }
|
|
::= { upsOutputTable 1 }
|
|
|
|
UpsOutputEntry ::=
|
|
SEQUENCE {
|
|
upsOutputVoltage
|
|
INTEGER,
|
|
upsOutputUtilityVoltage
|
|
INTEGER,
|
|
upsOutputPower
|
|
INTEGER
|
|
}
|
|
|
|
upsOutputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The measured UPS output voltage. The value of this
|
|
object is the actual voltage * 10 (that is, to determine
|
|
the actual voltage, divide the value of this object by
|
|
10)."
|
|
::= { upsOutputEntry 1 }
|
|
|
|
upsOutputUtilityVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
vac225(1),
|
|
vac230(2),
|
|
vac240(3),
|
|
vac220(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's current on-battery output voltage setting
|
|
(valid for 220/230/240 Vac version UPSs only). For other
|
|
version UPSs, reading this object will always return a 0
|
|
and writing this object will have no effect."
|
|
DEFVAL { vac225 }
|
|
::= { upsOutputEntry 2 }
|
|
|
|
upsOutputPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's output load represented as a percentage of full
|
|
rated load in Watts. The value of this object is the actual
|
|
percentage * 10 (that is, to determine the actual percentage,
|
|
divide the value of this object by 10)."
|
|
::= { upsOutputEntry 3 }
|
|
|
|
|
|
--============== upsStatus group ===================
|
|
|
|
-- UPS Status Group
|
|
-- Implementation of this group is mandatory if one or more UPSs
|
|
-- are to be monitored
|
|
-- This group covers information on the Status of each UPS
|
|
|
|
upsStatusTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsStatusEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of status table entries. The number of
|
|
entries is given by the value of upsNumUPSs."
|
|
::= { upsStatus 1 }
|
|
|
|
upsStatusEntry OBJECT-TYPE
|
|
SYNTAX UpsStatusEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing objects for a particular UPS."
|
|
INDEX { upsIndex }
|
|
::= { upsStatusTable 1 }
|
|
|
|
UpsStatusEntry ::=
|
|
SEQUENCE {
|
|
upsStatusOperational
|
|
INTEGER,
|
|
upsStatusFault
|
|
INTEGER,
|
|
upsStatusTemp
|
|
INTEGER
|
|
}
|
|
|
|
upsStatusOperational OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object contains 8 bits of information about the current
|
|
operational status of the UPS. The bits are encoded as
|
|
follows:
|
|
|
|
BIT 7: 1=replace battery condition
|
|
BIT 6: 1=low battery condition
|
|
BIT 5: 1=overloaded output condition
|
|
BIT 4: 1=on-battery mode of operation
|
|
BIT 3: 1=on-line mode of operation
|
|
BIT 2: 1=Smart Boost mode of operation (where applicable)
|
|
BIT 1: 1=UPS shut down due to low battery, overload,
|
|
or `sleep' mode
|
|
BIT 0: 1=run time calibration running
|
|
|
|
Note that bit 0 is the low-order bit."
|
|
::= { upsStatusEntry 1 }
|
|
|
|
upsStatusFault OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object contains 8 bits of information about the current
|
|
fault conditions of the UPS. The bits are encoded as
|
|
follows:
|
|
|
|
BIT 7: 1=UPS fault - internal temperature has exceeded
|
|
nominal limits
|
|
BIT 6: 1=UPS fault - bypass relay (where applicable) malfunction
|
|
BIT 5: 1=UPS fault - battery charger failure
|
|
BIT 4: 1=UPS in shut down mode via `S' command
|
|
BIT 3: 1=UPS in `sleep' mode via `@ddd' command
|
|
BIT 2: 1=UPS fault - main relay malfunction
|
|
BIT 1: 1=UPS unable to transfer to on-battery operation
|
|
due to overload
|
|
BIT 0: 1=UPS's output unpowered due to low battery shut down
|
|
|
|
Note that bit 0 is the low-order bit."
|
|
::= { upsStatusEntry 2 }
|
|
|
|
upsStatusTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's present internal operating temperature in degrees
|
|
Fahrenheit. The value of this object is the actual
|
|
temperature * 10 (that is, to determine the actual
|
|
temperature, divide the value of this object by 10)."
|
|
::= { upsStatusEntry 3 }
|
|
|
|
|
|
--=============== upsConfig group ====================
|
|
|
|
-- UPS Config Group
|
|
-- Implementation of this group is mandatory if one or more UPSs
|
|
-- are to be monitored
|
|
-- This group covers information on the Configuration of each UPS
|
|
|
|
upsConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsConfigEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of configuration table entries. The number of
|
|
entries is given by the value of upsNumUPSs."
|
|
::= { upsConfig 1 }
|
|
|
|
upsConfigEntry OBJECT-TYPE
|
|
SYNTAX UpsConfigEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing objects for a particular UPS."
|
|
INDEX { upsIndex }
|
|
::= { upsConfigTable 1 }
|
|
|
|
UpsConfigEntry ::=
|
|
SEQUENCE {
|
|
upsConfigAlarm
|
|
INTEGER,
|
|
upsConfigRestoreDefaults
|
|
INTEGER
|
|
}
|
|
|
|
upsConfigAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
uponUtilityFailure(1),
|
|
thirtySecondsAfterUtilityFailure(2),
|
|
lowBatteryOnly(3),
|
|
noAudibleAlarm(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's current audible alarm setting. The alarm
|
|
may be set to activate immediately upon utility failure
|
|
and for low battery condition, to activate 30 seconds
|
|
after utility failure and immediately upon low battery
|
|
condition, to activate upon low battery condition only,
|
|
or to not activate under any conditions."
|
|
DEFVAL { uponUtilityFailure }
|
|
::= { upsConfigEntry 1 }
|
|
|
|
upsConfigRestoreDefaults OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
restoreDefaults(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object may be written to force the UPS to restore
|
|
the factory default settings for most of the UPS's
|
|
customizable parameters. Reading this object will always
|
|
return a 0."
|
|
::= { upsConfigEntry 2 }
|
|
|
|
|
|
|
|
--=============== upsExtMeas group ====================
|
|
|
|
-- UPS ExtMeas Group
|
|
-- Implementation of this group is mandatory if one or more UPSs
|
|
-- are to be monitored AND an External Measurement Unit is attached
|
|
-- to at least one UPS
|
|
-- This group covers information on the External Measurement Unit of
|
|
-- each UPS
|
|
|
|
upsExtMeasTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsExtMeasEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of external measurement table entries. The number of
|
|
entries is the number of available UPSs to which External
|
|
Measurement Units are attached."
|
|
::= { upsExtMeas 1 }
|
|
|
|
upsExtMeasEntry OBJECT-TYPE
|
|
SYNTAX UpsExtMeasEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing objects for a particular UPS."
|
|
INDEX { upsIndex }
|
|
::= { upsExtMeasTable 1 }
|
|
|
|
UpsExtMeasEntry ::=
|
|
SEQUENCE {
|
|
upsExtMeasFwVersion
|
|
DisplayString,
|
|
upsExtMeasTemp
|
|
INTEGER,
|
|
upsExtMeasHumidity
|
|
INTEGER,
|
|
upsExtMeasAlarmStatus
|
|
INTEGER,
|
|
upsExtMeasMaxTemp
|
|
INTEGER,
|
|
upsExtMeasMinTemp
|
|
INTEGER,
|
|
upsExtMeasMaxHumidity
|
|
INTEGER,
|
|
upsExtMeasMinHumidity
|
|
INTEGER,
|
|
upsExtMeasContact1AlarmControl
|
|
INTEGER,
|
|
upsExtMeasContact2AlarmControl
|
|
INTEGER,
|
|
upsExtMeasContact3AlarmControl
|
|
INTEGER,
|
|
upsExtMeasContact4AlarmControl
|
|
INTEGER,
|
|
upsExtMeasMaxTempAlarmControl
|
|
INTEGER,
|
|
upsExtMeasMinTempAlarmControl
|
|
INTEGER,
|
|
upsExtMeasMaxHumidityAlarmControl
|
|
INTEGER,
|
|
upsExtMeasMinHumidityAlarmControl
|
|
INTEGER
|
|
}
|
|
|
|
upsExtMeasFwVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..1))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The External Measurement Unit's firmware version letter."
|
|
::= { upsExtMeasEntry 1 }
|
|
|
|
upsExtMeasTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The local ambient temperature in degrees Fahrenheit as measured
|
|
by the External Measurement Unit. The value of this object
|
|
is the actual temperature * 100 (that is, to determine the
|
|
actual temperature, divide the value of this object by 100)."
|
|
::= { upsExtMeasEntry 2 }
|
|
|
|
upsExtMeasHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The local ambient relative humidity in percent as measured
|
|
by the External Measurement Unit. The value of this object
|
|
is the actual humidity * 10 (that is, to determine the
|
|
actual humidity, divide the value of this object by 10)."
|
|
::= { upsExtMeasEntry 3 }
|
|
|
|
upsExtMeasAlarmStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object contains 8 bits of information about the current
|
|
alarm status of the External Measurement Unit. The bits are
|
|
encoded as follows:
|
|
|
|
BIT 7: 1=Upper temperature limit exceeded
|
|
BIT 6: 1=Lower temperature limit exceeded
|
|
BIT 5: 1=Upper relative humidity limit exceeded
|
|
BIT 4: 1=Lower relative humidity limit exceeded
|
|
BIT 3: 1=Contact input channel #4 alarm state
|
|
BIT 2: 1=Contact input channel #3 alarm state
|
|
BIT 1: 1=Contact input channel #2 alarm state
|
|
BIT 0: 1=Contact input channel #1 alarm state
|
|
|
|
Note that bit 0 is the low-order bit."
|
|
::= { upsExtMeasEntry 4 }
|
|
|
|
upsExtMeasMaxTemp OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ninetyDegreesF(1),
|
|
oneHundredFifteenDegreesF(2),
|
|
oneHundredThirtyDegreesF(3),
|
|
oneHundredSeventyFiveDegreesF(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The upper temperature limit at which an alarm will be sent."
|
|
DEFVAL { ninetyDegreesF }
|
|
::= { upsExtMeasEntry 5 }
|
|
|
|
upsExtMeasMinTemp OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
fortyDegreesF(1),
|
|
fiftyDegreesF(2),
|
|
fiftyEightDegreesF(3),
|
|
sixtyFiveDegreesF(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The lower temperature limit at which an alarm will be sent."
|
|
DEFVAL { fortyDegreesF }
|
|
::= { upsExtMeasEntry 6 }
|
|
|
|
upsExtMeasMaxHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
seventyPercent(1),
|
|
eightyPercent(2),
|
|
eightyFivePercent(3),
|
|
ninetyPercent(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The upper humidity limit at which an alarm will be sent."
|
|
DEFVAL { seventyPercent }
|
|
::= { upsExtMeasEntry 7 }
|
|
|
|
upsExtMeasMinHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
tenPercent(1),
|
|
twentyPercent(2),
|
|
thirtyPercent(3),
|
|
fortyPercent(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The lower humidity limit at which an alarm will be sent."
|
|
DEFVAL { tenPercent }
|
|
::= { upsExtMeasEntry 8 }
|
|
|
|
upsExtMeasContact1AlarmControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm enable state for the External Measurement Unit's
|
|
contact input channel #1. If enabled, an alarm will be
|
|
sent when contact input channel #1 has changed to abnormal
|
|
state."
|
|
::= { upsExtMeasEntry 9 }
|
|
|
|
upsExtMeasContact2AlarmControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm enable state for the External Measurement Unit's
|
|
contact input channel #2. If enabled, an alarm will be
|
|
sent when contact input channel #2 has changed to abnormal
|
|
state."
|
|
::= { upsExtMeasEntry 10 }
|
|
|
|
upsExtMeasContact3AlarmControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm enable state for the External Measurement Unit's
|
|
contact input channel #3. If enabled, an alarm will be
|
|
sent when contact input channel #3 has changed to abnormal
|
|
state."
|
|
::= { upsExtMeasEntry 11 }
|
|
|
|
upsExtMeasContact4AlarmControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm enable state for the External Measurement Unit's
|
|
contact input channel #4. If enabled, an alarm will be
|
|
sent when contact input channel #4 has changed to abnormal
|
|
state."
|
|
::= { upsExtMeasEntry 12 }
|
|
|
|
upsExtMeasMaxTempAlarmControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm enable state for the External Measurement Unit's
|
|
upper temperature limit. If enabled, an alarm will be
|
|
sent when the ambient temperature rises above the upper
|
|
temperature limit."
|
|
::= { upsExtMeasEntry 13 }
|
|
|
|
upsExtMeasMinTempAlarmControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm enable state for the External Measurement Unit's
|
|
lower temperature limit. If enabled, an alarm will be
|
|
sent when the ambient temperature falls below the lower
|
|
temperature limit."
|
|
::= { upsExtMeasEntry 14 }
|
|
|
|
upsExtMeasMaxHumidityAlarmControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm enable state for the External Measurement Unit's
|
|
upper humidity limit. If enabled, an alarm will be sent
|
|
when the ambient relative humidity rises above the upper
|
|
humidity limit."
|
|
::= { upsExtMeasEntry 15 }
|
|
|
|
upsExtMeasMinHumidityAlarmControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm enable state for the External Measurement Unit's
|
|
lower humidity limit. If enabled, an alarm will be sent
|
|
when the ambient relative humidity falls below the lower
|
|
humidity limit."
|
|
::= { upsExtMeasEntry 16 }
|
|
|
|
|
|
|
|
--=============== upsAddlFuncs group ====================
|
|
|
|
-- UPS AddlFuncs Group
|
|
-- Implementation of this group is mandatory if one or more UPSs
|
|
-- are to be monitored AND at least one UPS is capable of supporting
|
|
-- these additional functions
|
|
-- This group covers information on the Additional Functions of each
|
|
-- UPS
|
|
|
|
upsAddlFuncsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsAddlFuncsEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of additional functions table entries. The number of
|
|
entries is the number of available UPSs which are capable of
|
|
supporting these additional functions."
|
|
::= { upsAddlFuncs 1 }
|
|
|
|
upsAddlFuncsEntry OBJECT-TYPE
|
|
SYNTAX UpsAddlFuncsEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing objects for a particular UPS."
|
|
INDEX { upsIndex }
|
|
::= { upsAddlFuncsTable 1 }
|
|
|
|
UpsAddlFuncsEntry ::=
|
|
SEQUENCE {
|
|
upsAddlFuncsNumBatteryPacks
|
|
INTEGER,
|
|
upsAddlFuncsNumBadBatteryPacks
|
|
INTEGER,
|
|
upsAddlFuncsOutputCurrent
|
|
INTEGER,
|
|
upsAddlFuncsOutputApparentPower
|
|
INTEGER,
|
|
upsAddlFuncsStatusOperational
|
|
INTEGER,
|
|
upsAddlFuncsStatusFault
|
|
INTEGER,
|
|
upsAddlFuncsConfigPassword
|
|
OCTET STRING,
|
|
upsAddlFuncsConfigDisable
|
|
INTEGER,
|
|
upsAddlFuncsConfigBypass
|
|
INTEGER
|
|
}
|
|
|
|
upsAddlFuncsNumBatteryPacks OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of battery pack units connected to the UPS."
|
|
::= { upsAddlFuncsEntry 1 }
|
|
|
|
upsAddlFuncsNumBadBatteryPacks OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of bad (faulty) battery pack units connected
|
|
to the UPS."
|
|
::= { upsAddlFuncsEntry 2 }
|
|
|
|
upsAddlFuncsOutputCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The true rms load current drawn from the UPS. The value
|
|
of this object is the actual amperage * 100 (that is, to
|
|
determine the actual amperage, divide the value of this
|
|
object by 100)."
|
|
::= { upsAddlFuncsEntry 3 }
|
|
|
|
upsAddlFuncsOutputApparentPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS's output load represented as a percentage of full rated
|
|
load in Volt-Amps. The value of this object is the actual
|
|
percentage * 10 (that is, to determine the actual percentage,
|
|
divide the value of this object by 10)."
|
|
::= { upsAddlFuncsEntry 4 }
|
|
|
|
upsAddlFuncsStatusOperational OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object contains 8 bits of information about the current
|
|
operational status of the UPS. The bits are encoded as
|
|
follows:
|
|
|
|
BIT 7: 1=UPS ready to power load upon return of normal line
|
|
or upon user command
|
|
BIT 6: 1=UPS ready to power load upon user command
|
|
BIT 5: 1=UPS in bypass mode as a result of manual bypass
|
|
control
|
|
BIT 4: 1=UPS is returning from bypass mode
|
|
BIT 3: 1=UPS in bypass mode as a result of UPS-Link or
|
|
key command
|
|
BIT 2: 1=UPS going to bypass mode as a result of UPS-Link
|
|
or key command
|
|
BIT 1: 1=not defined
|
|
BIT 0: 1=wakeup mode - startup test lasting < 2 sec
|
|
|
|
Note that bit 0 is the low-order bit."
|
|
::= { upsAddlFuncsEntry 5 }
|
|
|
|
upsAddlFuncsStatusFault OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object contains 8 bits of information about the current
|
|
fault conditions of the UPS. The bits are encoded as
|
|
follows:
|
|
|
|
BIT 7: reserved for future use
|
|
BIT 6: reserved for future use
|
|
BIT 5: reserved for future use
|
|
BIT 4: 1=UPS fault - DC imbalance, UPS in bypass
|
|
BIT 3: 1=UPS fault - output voltage select failure, UPS
|
|
in bypass
|
|
BIT 2: 1=UPS fault - bypass supply failure
|
|
BIT 1: 1=UPS fault - Isolation Unit fan failure
|
|
BIT 0: 1=UPS fault - Electronics Unit fan failure, UPS
|
|
in bypass
|
|
|
|
Note that bit 0 is the low-order bit."
|
|
::= { upsAddlFuncsEntry 6 }
|
|
|
|
upsAddlFuncsConfigPassword OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The password that controls access to the UPS's LCD display.
|
|
A maximum of 4 characters may be entered."
|
|
::= { upsAddlFuncsEntry 7 }
|
|
|
|
upsAddlFuncsConfigDisable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disableUps(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object may be written to immediately shut down the
|
|
UPS, requiring a manual reset. Reading this object will
|
|
always return a 0."
|
|
::= { upsAddlFuncsEntry 8 }
|
|
|
|
upsAddlFuncsConfigBypass OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
bypassMode(1),
|
|
exitBypassMode(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object may be written to cause the UPS to transfer
|
|
to or from the bypass mode. Reading this object will
|
|
always return a 0."
|
|
::= { upsAddlFuncsEntry 9 }
|
|
|
|
END
|