mibs/MIBS/geist/GEIST-V4-MIB
2023-12-05 12:25:34 +01:00

1404 lines
40 KiB
Plaintext

GEIST-V4-MIB DEFINITIONS ::= BEGIN
IMPORTS
DisplayString FROM SNMPv2-TC
MODULE-IDENTITY, OBJECT-TYPE, IpAddress, enterprises, Integer32, Gauge32, NOTIFICATION-TYPE FROM SNMPv2-SMI;
geist MODULE-IDENTITY
LAST-UPDATED "201209110000Z"
ORGANIZATION "Geist"
CONTACT-INFO "support@geistglobal.com"
DESCRIPTION "The MIB for Geist Products"
REVISION "201209110000Z"
DESCRIPTION "Original version"
::= { enterprises 21239 }
blackbird OBJECT IDENTIFIER
::= { geist 5 }
watchdog100 OBJECT IDENTIFIER
::= { blackbird 1 }
--###########################################################################################--
--deviceInfo--
--###########################################################################################--
deviceInfo OBJECT IDENTIFIER
::= { watchdog100 1 }
productTitle OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Product name"
::= { deviceInfo 1 }
productVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Product version"
::= { deviceInfo 2 }
productFriendlyName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "User-assigned name"
::= { deviceInfo 3 }
productMacAddress OBJECT-TYPE
SYNTAX OCTET STRING
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Product's unique MAC address"
::= { deviceInfo 4 }
productUrl OBJECT-TYPE
SYNTAX IpAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Product's main URL access point"
::= { deviceInfo 5 }
deviceCount OBJECT-TYPE
SYNTAX Integer32(0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Total number of devices on unit"
::= { deviceInfo 6 }
temperatureUnits OBJECT-TYPE
SYNTAX Integer32(0..1)
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Current units for temperature values. 0 = Degrees Fahrenheit, 1 = Degrees Celsius"
::= { deviceInfo 7 }
--###########################################################################################--
--internalTable--
--###########################################################################################--
internalTable OBJECT-TYPE
SYNTAX SEQUENCE OF InternalEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Internal sensors for units"
::= { watchdog100 2 }
internalEntry OBJECT-TYPE
SYNTAX InternalEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entry in the internalTable table: each entry contains an index and other sensor details"
INDEX { internalIndex }
::= { internalTable 1 }
InternalEntry ::= SEQUENCE {
internalIndex Integer32,
internalSerial DisplayString,
internalName DisplayString,
internalAvail Gauge32,
internalTemp Integer32,
internalHumidity Integer32,
internalDewPoint Integer32
}
internalIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Table entry index value"
::= { internalEntry 1 }
internalSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Serial Number"
::= { internalEntry 2 }
internalName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Friendly Name"
::= { internalEntry 3 }
internalAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable"
::= { internalEntry 4 }
internalTemp OBJECT-TYPE
SYNTAX Integer32(-40..200)
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo"
::= { internalEntry 5 }
internalHumidity OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Humidity reading"
::= { internalEntry 6 }
internalDewPoint OBJECT-TYPE
SYNTAX Integer32(-40..200)
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo"
::= { internalEntry 7 }
--###########################################################################################--
--tempSensorTable--
--###########################################################################################--
tempSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF TempSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Remote Temperature Sensor"
::= { watchdog100 4 }
tempSensorEntry OBJECT-TYPE
SYNTAX TempSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entry in the tempSensorTable table: each entry contains an index and other sensor details"
INDEX { tempSensorIndex }
::= { tempSensorTable 1 }
TempSensorEntry ::= SEQUENCE {
tempSensorIndex Integer32,
tempSensorSerial DisplayString,
tempSensorName DisplayString,
tempSensorAvail Gauge32,
tempSensorTemp Integer32
}
tempSensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Table entry index value"
::= { tempSensorEntry 1 }
tempSensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Serial Number"
::= { tempSensorEntry 2 }
tempSensorName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Friendly Name"
::= { tempSensorEntry 3 }
tempSensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable"
::= { tempSensorEntry 4 }
tempSensorTemp OBJECT-TYPE
SYNTAX Integer32(-40..200)
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo"
::= { tempSensorEntry 5 }
--###########################################################################################--
--airFlowSensorTable--
--###########################################################################################--
airFlowSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF AirFlowSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Remote Airflow, Humidity, Temperature and Dewpoint Sensor "
::= { watchdog100 5 }
airFlowSensorEntry OBJECT-TYPE
SYNTAX AirFlowSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entry in the airFlowSensorTable table: each entry contains an index and other sensor details"
INDEX { airFlowSensorIndex }
::= { airFlowSensorTable 1 }
AirFlowSensorEntry ::= SEQUENCE {
airFlowSensorIndex Integer32,
airFlowSensorSerial DisplayString,
airFlowSensorName DisplayString,
airFlowSensorAvail Gauge32,
airFlowSensorTemp Integer32,
airFlowSensorFlow Integer32,
airFlowSensorHumidity Integer32,
airFlowSensorDewPoint Integer32
}
airFlowSensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Table entry index value"
::= { airFlowSensorEntry 1 }
airFlowSensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Serial Number"
::= { airFlowSensorEntry 2 }
airFlowSensorName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Friendly Name"
::= { airFlowSensorEntry 3 }
airFlowSensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable"
::= { airFlowSensorEntry 4 }
airFlowSensorTemp OBJECT-TYPE
SYNTAX Integer32(-40..200)
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo"
::= { airFlowSensorEntry 5 }
airFlowSensorFlow OBJECT-TYPE
SYNTAX Integer32(0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "AFHT3 Airflow reading"
::= { airFlowSensorEntry 6 }
airFlowSensorHumidity OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "AFHT3 Humidity reading"
::= { airFlowSensorEntry 7 }
airFlowSensorDewPoint OBJECT-TYPE
SYNTAX Integer32(-40..200)
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current reading for Dew Point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo"
::= { airFlowSensorEntry 8 }
--###########################################################################################--
--dewPointSensorTable--
--###########################################################################################--
dewPointSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF DewPointSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Remote Dew Point sensor"
::= { watchdog100 6 }
dewPointSensorEntry OBJECT-TYPE
SYNTAX DewPointSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entry in the dewPointSensorTable table: each entry contains an index and other sensor details"
INDEX { dewPointSensorIndex }
::= { dewPointSensorTable 1 }
DewPointSensorEntry ::= SEQUENCE {
dewPointSensorIndex Integer32,
dewPointSensorSerial DisplayString,
dewPointSensorName DisplayString,
dewPointSensorAvail Gauge32,
dewPointSensorTemp Integer32,
dewPointSensorHumidity Integer32,
dewPointSensorDewPoint Integer32
}
dewPointSensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Table entry index value"
::= { dewPointSensorEntry 1 }
dewPointSensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Serial Number"
::= { dewPointSensorEntry 2 }
dewPointSensorName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Friendly Name"
::= { dewPointSensorEntry 3 }
dewPointSensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable"
::= { dewPointSensorEntry 4 }
dewPointSensorTemp OBJECT-TYPE
SYNTAX Integer32(-40..200)
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo"
::= { dewPointSensorEntry 5 }
dewPointSensorHumidity OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Humidity reading"
::= { dewPointSensorEntry 6 }
dewPointSensorDewPoint OBJECT-TYPE
SYNTAX Integer32(-40..200)
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo"
::= { dewPointSensorEntry 7 }
--###########################################################################################--
--ccatSensorTable--
--###########################################################################################--
ccatSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF CcatSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Remote CCAT sensor"
::= { watchdog100 7 }
ccatSensorEntry OBJECT-TYPE
SYNTAX CcatSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entry in the ccatSensorTable table: each entry contains an index and other sensor details"
INDEX { ccatSensorIndex }
::= { ccatSensorTable 1 }
CcatSensorEntry ::= SEQUENCE {
ccatSensorIndex Integer32,
ccatSensorSerial DisplayString,
ccatSensorName DisplayString,
ccatSensorAvail Gauge32,
ccatSensorValue Integer32,
ccatSensorType DisplayString,
ccatSensorDescription DisplayString
}
ccatSensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Table entry index value"
::= { ccatSensorEntry 1 }
ccatSensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Serial Number"
::= { ccatSensorEntry 2 }
ccatSensorName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Friendly Name"
::= { ccatSensorEntry 3 }
ccatSensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable"
::= { ccatSensorEntry 4 }
ccatSensorValue OBJECT-TYPE
SYNTAX Integer32(-100..5000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "CCAT sensor reading"
::= { ccatSensorEntry 5 }
ccatSensorType OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "CCAT sensor type"
::= { ccatSensorEntry 6 }
ccatSensorDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "CCAT sensor value description"
::= { ccatSensorEntry 7 }
--###########################################################################################--
--t3hdSensorTable--
--###########################################################################################--
t3hdSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF T3hdSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Remote Temperature x 3, Humidity and Dewpoint Sensor"
::= { watchdog100 8 }
t3hdSensorEntry OBJECT-TYPE
SYNTAX T3hdSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entry in the t3hdSensorTable table: each entry contains an index and other sensor details"
INDEX { t3hdSensorIndex }
::= { t3hdSensorTable 1 }
T3hdSensorEntry ::= SEQUENCE {
t3hdSensorIndex Integer32,
t3hdSensorSerial DisplayString,
t3hdSensorName DisplayString,
t3hdSensorAvail Gauge32,
t3hdSensorIntName DisplayString,
t3hdSensorIntTemp Integer32,
t3hdSensorIntHumidity Integer32,
t3hdSensorIntDewPoint Integer32,
t3hdSensorExtAAvail Gauge32,
t3hdSensorExtAName DisplayString,
t3hdSensorExtATemp Integer32,
t3hdSensorExtBAvail Gauge32,
t3hdSensorExtBName DisplayString,
t3hdSensorExtBTemp Integer32
}
t3hdSensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Table entry index value"
::= { t3hdSensorEntry 1 }
t3hdSensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Serial Number"
::= { t3hdSensorEntry 2 }
t3hdSensorName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Friendly Name"
::= { t3hdSensorEntry 3 }
t3hdSensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable"
::= { t3hdSensorEntry 4 }
t3hdSensorIntName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "T3HD Sensor Internal Friendly Name"
::= { t3hdSensorEntry 5 }
t3hdSensorIntTemp OBJECT-TYPE
SYNTAX Integer32(-40..200)
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current reading for Internal Temperature in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo"
::= { t3hdSensorEntry 6 }
t3hdSensorIntHumidity OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "T3HD Sensor Internal Humidity"
::= { t3hdSensorEntry 7 }
t3hdSensorIntDewPoint OBJECT-TYPE
SYNTAX Integer32(-40..200)
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current reading for Internal DewPoint in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo"
::= { t3hdSensorEntry 8 }
t3hdSensorExtAAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "T3HD External A status: 0 = Unavailable, 1 = Available"
::= { t3hdSensorEntry 9 }
t3hdSensorExtAName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "T3HD External A Friendly Name"
::= { t3hdSensorEntry 10 }
t3hdSensorExtATemp OBJECT-TYPE
SYNTAX Integer32(-40..200)
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current reading for External Temperature A in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo"
::= { t3hdSensorEntry 11 }
t3hdSensorExtBAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "T3HD External B status: 0 = Unavailable, 1 = Available"
::= { t3hdSensorEntry 12 }
t3hdSensorExtBName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "T3HD External B Friendly Name"
::= { t3hdSensorEntry 13 }
t3hdSensorExtBTemp OBJECT-TYPE
SYNTAX Integer32(-40..200)
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current reading for External Temperature B in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo"
::= { t3hdSensorEntry 14 }
--###########################################################################################--
--thdSensorTable--
--###########################################################################################--
thdSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF ThdSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Remote Temperature, Humidity and Dewpoint Sensor"
::= { watchdog100 9 }
thdSensorEntry OBJECT-TYPE
SYNTAX ThdSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entry in the thdSensorTable table: each entry contains an index and other sensor details"
INDEX { thdSensorIndex }
::= { thdSensorTable 1 }
ThdSensorEntry ::= SEQUENCE {
thdSensorIndex Integer32,
thdSensorSerial DisplayString,
thdSensorName DisplayString,
thdSensorAvail Gauge32,
thdSensorTemp Integer32,
thdSensorHumidity Integer32,
thdSensorDewPoint Integer32
}
thdSensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Table entry index value"
::= { thdSensorEntry 1 }
thdSensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Serial Number"
::= { thdSensorEntry 2 }
thdSensorName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Friendly Name"
::= { thdSensorEntry 3 }
thdSensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable"
::= { thdSensorEntry 4 }
thdSensorTemp OBJECT-TYPE
SYNTAX Integer32(-40..200)
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current reading for Temperature in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo"
::= { thdSensorEntry 5 }
thdSensorHumidity OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "THD Sensor Humidity"
::= { thdSensorEntry 6 }
thdSensorDewPoint OBJECT-TYPE
SYNTAX Integer32(-40..200)
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current reading for DewPoint in 0.1 degrees. Units are given by temperatureUnits field in deviceInfo"
::= { thdSensorEntry 7 }
--###########################################################################################--
--rpmSensorTable--
--###########################################################################################--
rpmSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF RpmSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Remote Power Manager Sensor"
::= { watchdog100 10 }
rpmSensorEntry OBJECT-TYPE
SYNTAX RpmSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entry in the rpmSensorTable table: each entry contains an index and other sensor details"
INDEX { rpmSensorIndex }
::= { rpmSensorTable 1 }
RpmSensorEntry ::= SEQUENCE {
rpmSensorIndex Integer32,
rpmSensorSerial DisplayString,
rpmSensorName DisplayString,
rpmSensorAvail Gauge32,
rpmSensorEnergy Gauge32,
rpmSensorVoltage Gauge32,
rpmSensorVoltageMax Gauge32,
rpmSensorVoltageMin Gauge32,
rpmSensorVoltagePeak Gauge32,
rpmSensorCurrent Gauge32,
rpmSensorRealPower Gauge32,
rpmSensorApparentPower Gauge32,
rpmSensorPowerFactor Gauge32,
rpmSensorOutlet1 Gauge32,
rpmSensorOutlet2 Gauge32
}
rpmSensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Table entry index value"
::= { rpmSensorEntry 1 }
rpmSensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Serial Number"
::= { rpmSensorEntry 2 }
rpmSensorName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Friendly Name"
::= { rpmSensorEntry 3 }
rpmSensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable"
::= { rpmSensorEntry 4 }
rpmSensorEnergy OBJECT-TYPE
SYNTAX Gauge32
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RPM Sensor Accumulated Energy"
::= { rpmSensorEntry 5 }
rpmSensorVoltage OBJECT-TYPE
SYNTAX Gauge32
UNITS "Volts (rms)"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RPM Sensor Voltage"
::= { rpmSensorEntry 6 }
rpmSensorVoltageMax OBJECT-TYPE
SYNTAX Gauge32
UNITS "Volts (rms)"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RPM Sensor Voltage (Max)"
::= { rpmSensorEntry 7 }
rpmSensorVoltageMin OBJECT-TYPE
SYNTAX Gauge32
UNITS "Volts (rms)"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RPM Sensor Voltage (Min)"
::= { rpmSensorEntry 8 }
rpmSensorVoltagePeak OBJECT-TYPE
SYNTAX Gauge32
UNITS "Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RPM Sensor Voltage (Peak)"
::= { rpmSensorEntry 9 }
rpmSensorCurrent OBJECT-TYPE
SYNTAX Gauge32
UNITS "0.1 Amps (rms)"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RPM Sensor Current reading in deciAmps"
::= { rpmSensorEntry 10 }
rpmSensorRealPower OBJECT-TYPE
SYNTAX Gauge32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RPM Sensor Real Power"
::= { rpmSensorEntry 11 }
rpmSensorApparentPower OBJECT-TYPE
SYNTAX Gauge32
UNITS "Volt-Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RPM Sensor Apparent Power"
::= { rpmSensorEntry 12 }
rpmSensorPowerFactor OBJECT-TYPE
SYNTAX Gauge32
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RPM Sensor Power Factor"
::= { rpmSensorEntry 13 }
rpmSensorOutlet1 OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RPM Sensor Outlet 1 State: 0 = off, 1 = on"
::= { rpmSensorEntry 14 }
rpmSensorOutlet2 OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "RPM Sensor Outlet 2 State: 0 = off, 1 = on"
::= { rpmSensorEntry 15 }
--###########################################################################################--
--a2dSensorTable--
--###########################################################################################--
a2dSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF A2DSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Analog Measurement Sensor (Voltage, Current, or Dry Contact)"
::= { watchdog100 11 }
a2DSensorEntry OBJECT-TYPE
SYNTAX A2DSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION "Entry in the a2dSensorTable table: each entry contains an index and other sensor details"
INDEX { a2dSensorIndex }
::= { a2dSensorTable 1 }
A2DSensorEntry ::= SEQUENCE {
a2dSensorIndex Integer32,
a2dSensorSerial DisplayString,
a2dSensorName DisplayString,
a2dSensorAvail Gauge32,
a2dSensorValue Integer32
}
a2dSensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Table entry index value"
::= { a2DSensorEntry 1 }
a2dSensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Serial Number"
::= { a2DSensorEntry 2 }
a2dSensorName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Friendly Name"
::= { a2DSensorEntry 3 }
a2dSensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable"
::= { a2DSensorEntry 4 }
a2dSensorValue OBJECT-TYPE
SYNTAX Integer32(-1000000..1000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Current analog measurement reading within either a user defined or preset range depending on device mode."
::= { a2DSensorEntry 5 }
--###########################################################################################--
--Notifications--
--###########################################################################################--
trap OBJECT IDENTIFIER ::= { watchdog100 32767 }
trapPrefix OBJECT IDENTIFIER ::= { trap 0 }
internalTestNOTIFY NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Test SNMP Trap"
::= { trapPrefix 10101 }
--#####deviceInfo#####--
--#####internalTable#####--
internalAvailNOTIFY NOTIFICATION-TYPE
OBJECTS { internalAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap"
::= { trapPrefix 10204 }
internalAvailCLEAR NOTIFICATION-TYPE
OBJECTS { internalAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap"
::= { trapPrefix 20204 }
internalTempNOTIFY NOTIFICATION-TYPE
OBJECTS { internalTemp, temperatureUnits }
STATUS current
DESCRIPTION "Internal Temperature Sensor Trap"
::= { trapPrefix 10205 }
internalTempCLEAR NOTIFICATION-TYPE
OBJECTS { internalTemp, temperatureUnits }
STATUS current
DESCRIPTION "Internal Temperature Sensor Clear Trap"
::= { trapPrefix 20205 }
internalHumidityNOTIFY NOTIFICATION-TYPE
OBJECTS { internalHumidity }
STATUS current
DESCRIPTION "Humidity reading Trap"
::= { trapPrefix 10206 }
internalHumidityCLEAR NOTIFICATION-TYPE
OBJECTS { internalHumidity }
STATUS current
DESCRIPTION "Humidity reading Clear Trap"
::= { trapPrefix 20206 }
internalDewPointNOTIFY NOTIFICATION-TYPE
OBJECTS { internalDewPoint, temperatureUnits }
STATUS current
DESCRIPTION "Internal Dew Point Sensor Trap"
::= { trapPrefix 10207 }
internalDewPointCLEAR NOTIFICATION-TYPE
OBJECTS { internalDewPoint, temperatureUnits }
STATUS current
DESCRIPTION "Internal Dew Point Sensor Clear Trap"
::= { trapPrefix 20207 }
--#####tempSensorTable#####--
tempSensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS { tempSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap"
::= { trapPrefix 10404 }
tempSensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS { tempSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap"
::= { trapPrefix 20404 }
tempSensorTempNOTIFY NOTIFICATION-TYPE
OBJECTS { tempSensorTemp, temperatureUnits }
STATUS current
DESCRIPTION "Remote Temperature Sensor Trap"
::= { trapPrefix 10405 }
tempSensorTempCLEAR NOTIFICATION-TYPE
OBJECTS { tempSensorTemp, temperatureUnits }
STATUS current
DESCRIPTION "Remote Temperature Sensor Clear Trap"
::= { trapPrefix 20405 }
--#####airFlowSensorTable#####--
airFlowSensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS { airFlowSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap"
::= { trapPrefix 10504 }
airFlowSensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS { airFlowSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap"
::= { trapPrefix 20504 }
airFlowSensorTempNOTIFY NOTIFICATION-TYPE
OBJECTS { airFlowSensorTemp, temperatureUnits }
STATUS current
DESCRIPTION "AFHT3 Sensor Temperature Trap"
::= { trapPrefix 10505 }
airFlowSensorTempCLEAR NOTIFICATION-TYPE
OBJECTS { airFlowSensorTemp, temperatureUnits }
STATUS current
DESCRIPTION "AFHT3 Sensor Temperature Clear Trap"
::= { trapPrefix 20505 }
airFlowSensorFlowNOTIFY NOTIFICATION-TYPE
OBJECTS { airFlowSensorFlow }
STATUS current
DESCRIPTION "AFHT3 Airflow reading Trap"
::= { trapPrefix 10506 }
airFlowSensorFlowCLEAR NOTIFICATION-TYPE
OBJECTS { airFlowSensorFlow }
STATUS current
DESCRIPTION "AFHT3 Airflow reading Clear Trap"
::= { trapPrefix 20506 }
airFlowSensorHumidityNOTIFY NOTIFICATION-TYPE
OBJECTS { airFlowSensorHumidity }
STATUS current
DESCRIPTION "AFHT3 Humidity reading Trap"
::= { trapPrefix 10507 }
airFlowSensorHumidityCLEAR NOTIFICATION-TYPE
OBJECTS { airFlowSensorHumidity }
STATUS current
DESCRIPTION "AFHT3 Humidity reading Clear Trap"
::= { trapPrefix 20507 }
airFlowSensorDewPointNOTIFY NOTIFICATION-TYPE
OBJECTS { airFlowSensorDewPoint, temperatureUnits }
STATUS current
DESCRIPTION "AFHT3 Sensor Dew Point Trap"
::= { trapPrefix 10508 }
airFlowSensorDewPointCLEAR NOTIFICATION-TYPE
OBJECTS { airFlowSensorDewPoint, temperatureUnits }
STATUS current
DESCRIPTION "AFHT3 Sensor Dew Point Clear Trap"
::= { trapPrefix 20508 }
--#####dewPointSensorTable#####--
dewPointSensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS { dewPointSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap"
::= { trapPrefix 10604 }
dewPointSensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS { dewPointSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap"
::= { trapPrefix 20604 }
dewPointSensorTempNOTIFY NOTIFICATION-TYPE
OBJECTS { dewPointSensorTemp, temperatureUnits }
STATUS current
DESCRIPTION "Remote Dew Point Sensor Temperature Trap"
::= { trapPrefix 10605 }
dewPointSensorTempCLEAR NOTIFICATION-TYPE
OBJECTS { dewPointSensorTemp, temperatureUnits }
STATUS current
DESCRIPTION "Remote Dew Point Sensor Temperature Clear Trap"
::= { trapPrefix 20605 }
dewPointSensorHumidityNOTIFY NOTIFICATION-TYPE
OBJECTS { dewPointSensorHumidity }
STATUS current
DESCRIPTION "Humidity reading Trap"
::= { trapPrefix 10606 }
dewPointSensorHumidityCLEAR NOTIFICATION-TYPE
OBJECTS { dewPointSensorHumidity }
STATUS current
DESCRIPTION "Humidity reading Clear Trap"
::= { trapPrefix 20606 }
dewPointSensorDewPointNOTIFY NOTIFICATION-TYPE
OBJECTS { dewPointSensorDewPoint, temperatureUnits }
STATUS current
DESCRIPTION "Remote Dew Point Sensor Dew Point Trap"
::= { trapPrefix 10607 }
dewPointSensorDewPointCLEAR NOTIFICATION-TYPE
OBJECTS { dewPointSensorDewPoint, temperatureUnits }
STATUS current
DESCRIPTION "Remote Dew Point Sensor Dew Point Clear Trap"
::= { trapPrefix 20607 }
--#####ccatSensorTable#####--
ccatSensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS { ccatSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap"
::= { trapPrefix 10704 }
ccatSensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS { ccatSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap"
::= { trapPrefix 20704 }
ccatSensorValueNOTIFY NOTIFICATION-TYPE
OBJECTS { ccatSensorValue, ccatSensorType }
STATUS current
DESCRIPTION "CCAT sensor reading Trap"
::= { trapPrefix 10705 }
ccatSensorValueCLEAR NOTIFICATION-TYPE
OBJECTS { ccatSensorValue, ccatSensorType }
STATUS current
DESCRIPTION "CCAT sensor reading Clear Trap"
::= { trapPrefix 20705 }
--#####t3hdSensorTable#####--
t3hdSensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS { t3hdSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap"
::= { trapPrefix 10804 }
t3hdSensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS { t3hdSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap"
::= { trapPrefix 20804 }
t3hdSensorIntTempNOTIFY NOTIFICATION-TYPE
OBJECTS { t3hdSensorIntTemp, temperatureUnits }
STATUS current
DESCRIPTION "T3HD Sensor Temperature Trap"
::= { trapPrefix 10806 }
t3hdSensorIntTempCLEAR NOTIFICATION-TYPE
OBJECTS { t3hdSensorIntTemp, temperatureUnits }
STATUS current
DESCRIPTION "T3HD Sensor Temperature Clear Trap"
::= { trapPrefix 20806 }
t3hdSensorIntHumidityNOTIFY NOTIFICATION-TYPE
OBJECTS { t3hdSensorIntHumidity }
STATUS current
DESCRIPTION "T3HD Sensor Internal Humidity Trap"
::= { trapPrefix 10807 }
t3hdSensorIntHumidityCLEAR NOTIFICATION-TYPE
OBJECTS { t3hdSensorIntHumidity }
STATUS current
DESCRIPTION "T3HD Sensor Internal Humidity Clear Trap"
::= { trapPrefix 20807 }
t3hdSensorIntDewPointNOTIFY NOTIFICATION-TYPE
OBJECTS { t3hdSensorIntDewPoint, temperatureUnits }
STATUS current
DESCRIPTION "T3HD Sensor Dew Point Trap"
::= { trapPrefix 10808 }
t3hdSensorIntDewPointCLEAR NOTIFICATION-TYPE
OBJECTS { t3hdSensorIntDewPoint, temperatureUnits }
STATUS current
DESCRIPTION "T3HD Sensor Dew Point Clear Trap"
::= { trapPrefix 20808 }
t3hdSensorExtATempNOTIFY NOTIFICATION-TYPE
OBJECTS { t3hdSensorExtATemp, temperatureUnits }
STATUS current
DESCRIPTION "T3HD Sensor External A Temperature Trap"
::= { trapPrefix 10811 }
t3hdSensorExtATempCLEAR NOTIFICATION-TYPE
OBJECTS { t3hdSensorExtATemp, temperatureUnits }
STATUS current
DESCRIPTION "T3HD Sensor External A Temperature Clear Trap"
::= { trapPrefix 20811 }
t3hdSensorExtBTempNOTIFY NOTIFICATION-TYPE
OBJECTS { t3hdSensorExtBTemp, temperatureUnits }
STATUS current
DESCRIPTION "T3HD Sensor External B Temperature Trap"
::= { trapPrefix 10814 }
t3hdSensorExtBTempCLEAR NOTIFICATION-TYPE
OBJECTS { t3hdSensorExtBTemp, temperatureUnits }
STATUS current
DESCRIPTION "T3HD Sensor External B Temperature Clear Trap"
::= { trapPrefix 20814 }
--#####thdSensorTable#####--
thdSensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS { thdSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap"
::= { trapPrefix 10904 }
thdSensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS { thdSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap"
::= { trapPrefix 20904 }
thdSensorTempNOTIFY NOTIFICATION-TYPE
OBJECTS { thdSensorTemp, temperatureUnits }
STATUS current
DESCRIPTION "THD Sensor Temperature Trap"
::= { trapPrefix 10905 }
thdSensorTempCLEAR NOTIFICATION-TYPE
OBJECTS { thdSensorTemp, temperatureUnits }
STATUS current
DESCRIPTION "THD Sensor Temperature Clear Trap"
::= { trapPrefix 20905 }
thdSensorHumidityNOTIFY NOTIFICATION-TYPE
OBJECTS { thdSensorHumidity }
STATUS current
DESCRIPTION "THD Sensor Humidity Trap"
::= { trapPrefix 10906 }
thdSensorHumidityCLEAR NOTIFICATION-TYPE
OBJECTS { thdSensorHumidity }
STATUS current
DESCRIPTION "THD Sensor Humidity Clear Trap"
::= { trapPrefix 20906 }
thdSensorDewPointNOTIFY NOTIFICATION-TYPE
OBJECTS { thdSensorDewPoint, temperatureUnits }
STATUS current
DESCRIPTION "THD Sensor Dew Point Trap"
::= { trapPrefix 10907 }
thdSensorDewPointCLEAR NOTIFICATION-TYPE
OBJECTS { thdSensorDewPoint, temperatureUnits }
STATUS current
DESCRIPTION "THD Sensor Dew Point Clear Trap"
::= { trapPrefix 20907 }
--#####rpmSensorTable#####--
rpmSensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS { rpmSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap"
::= { trapPrefix 11004 }
rpmSensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS { rpmSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap"
::= { trapPrefix 21004 }
rpmSensorEnergyNOTIFY NOTIFICATION-TYPE
OBJECTS { rpmSensorEnergy }
STATUS current
DESCRIPTION "RPM Sensor Accumulated Energy Trap"
::= { trapPrefix 11005 }
rpmSensorEnergyCLEAR NOTIFICATION-TYPE
OBJECTS { rpmSensorEnergy }
STATUS current
DESCRIPTION "RPM Sensor Accumulated Energy Clear Trap"
::= { trapPrefix 21005 }
rpmSensorVoltageNOTIFY NOTIFICATION-TYPE
OBJECTS { rpmSensorVoltage }
STATUS current
DESCRIPTION "RPM Sensor Voltage Trap"
::= { trapPrefix 11006 }
rpmSensorVoltageCLEAR NOTIFICATION-TYPE
OBJECTS { rpmSensorVoltage }
STATUS current
DESCRIPTION "RPM Sensor Voltage Clear Trap"
::= { trapPrefix 21006 }
rpmSensorVoltageMaxNOTIFY NOTIFICATION-TYPE
OBJECTS { rpmSensorVoltageMax }
STATUS current
DESCRIPTION "RPM Sensor Voltage (Max) Trap"
::= { trapPrefix 11007 }
rpmSensorVoltageMaxCLEAR NOTIFICATION-TYPE
OBJECTS { rpmSensorVoltageMax }
STATUS current
DESCRIPTION "RPM Sensor Voltage (Max) Clear Trap"
::= { trapPrefix 21007 }
rpmSensorVoltageMinNOTIFY NOTIFICATION-TYPE
OBJECTS { rpmSensorVoltageMin }
STATUS current
DESCRIPTION "RPM Sensor Voltage (Min) Trap"
::= { trapPrefix 11008 }
rpmSensorVoltageMinCLEAR NOTIFICATION-TYPE
OBJECTS { rpmSensorVoltageMin }
STATUS current
DESCRIPTION "RPM Sensor Voltage (Min) Clear Trap"
::= { trapPrefix 21008 }
rpmSensorVoltagePeakNOTIFY NOTIFICATION-TYPE
OBJECTS { rpmSensorVoltagePeak }
STATUS current
DESCRIPTION "RPM Sensor Voltage (Peak) Trap"
::= { trapPrefix 11009 }
rpmSensorVoltagePeakCLEAR NOTIFICATION-TYPE
OBJECTS { rpmSensorVoltagePeak }
STATUS current
DESCRIPTION "RPM Sensor Voltage (Peak) Clear Trap"
::= { trapPrefix 21009 }
rpmSensorCurrentNOTIFY NOTIFICATION-TYPE
OBJECTS { rpmSensorCurrent }
STATUS current
DESCRIPTION "RPM Sensor Current Trap"
::= { trapPrefix 11010 }
rpmSensorCurrentCLEAR NOTIFICATION-TYPE
OBJECTS { rpmSensorCurrent }
STATUS current
DESCRIPTION "RPM Sensor Current Clear Trap"
::= { trapPrefix 21010 }
rpmSensorRealPowerNOTIFY NOTIFICATION-TYPE
OBJECTS { rpmSensorRealPower }
STATUS current
DESCRIPTION "RPM Sensor Real Power Trap"
::= { trapPrefix 11011 }
rpmSensorRealPowerCLEAR NOTIFICATION-TYPE
OBJECTS { rpmSensorRealPower }
STATUS current
DESCRIPTION "RPM Sensor Real Power Clear Trap"
::= { trapPrefix 21011 }
rpmSensorApparentPowerNOTIFY NOTIFICATION-TYPE
OBJECTS { rpmSensorApparentPower }
STATUS current
DESCRIPTION "RPM Sensor Apparent Power Trap"
::= { trapPrefix 11012 }
rpmSensorApparentPowerCLEAR NOTIFICATION-TYPE
OBJECTS { rpmSensorApparentPower }
STATUS current
DESCRIPTION "RPM Sensor Apparent Power Clear Trap"
::= { trapPrefix 21012 }
rpmSensorPowerFactorNOTIFY NOTIFICATION-TYPE
OBJECTS { rpmSensorPowerFactor }
STATUS current
DESCRIPTION "RPM Sensor Power Factor Trap"
::= { trapPrefix 11013 }
rpmSensorPowerFactorCLEAR NOTIFICATION-TYPE
OBJECTS { rpmSensorPowerFactor }
STATUS current
DESCRIPTION "RPM Sensor Power Factor Clear Trap"
::= { trapPrefix 21013 }
--#####a2dSensorTable#####--
a2dSensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS { a2dSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Trap"
::= { trapPrefix 11104 }
a2dSensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS { a2dSensorAvail }
STATUS current
DESCRIPTION "Device availability. 0 = Unavailable, 1 = Available, 2 = Partially Unavailable Clear Trap"
::= { trapPrefix 21104 }
a2dSensorValueNOTIFY NOTIFICATION-TYPE
OBJECTS { a2dSensorValue }
STATUS current
DESCRIPTION "A2D Analog Sensor Measurement Trap"
::= { trapPrefix 11105 }
a2dSensorValueCLEAR NOTIFICATION-TYPE
OBJECTS { a2dSensorValue }
STATUS current
DESCRIPTION "A2D Analog Sensor Measurement Clear Trap"
::= { trapPrefix 21105 }
END