5535 lines
183 KiB
Plaintext
5535 lines
183 KiB
Plaintext
LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY,
|
|
OBJECT-IDENTITY
|
|
FROM SNMPv2-SMI
|
|
liebertFlexibleConditionsModuleReg
|
|
FROM LIEBERT-GP-REGISTRATION-MIB
|
|
lgpFlexConditions
|
|
FROM LIEBERT-GP-CONDITIONS-MIB
|
|
;
|
|
|
|
-- =============================================================================
|
|
-- Module Identification and Registration
|
|
-- =============================================================================
|
|
|
|
liebertGlobalProductsFlexibleConditionsModule MODULE-IDENTITY
|
|
LAST-UPDATED "201810020000Z"
|
|
ORGANIZATION "Liebert Corporation"
|
|
CONTACT-INFO
|
|
"Contact: Technical Support
|
|
|
|
Postal:
|
|
Liebert Corporation
|
|
1050 Dearborn Drive
|
|
P.O. Box 29186
|
|
Columbus OH, 43229
|
|
US
|
|
|
|
Tel: +1 (800) 222-5877
|
|
|
|
E-mail: liebert.monitoring@vertivco.com
|
|
Web: www.vertivco.com"
|
|
|
|
DESCRIPTION
|
|
"The MIB module used to register Liebert SNMP OIDs.
|
|
|
|
Copyright 2000-2018 Liebert Corporation. All rights reserved.
|
|
Reproduction of this document is authorized on the condition
|
|
that the forgoing copyright notice is included.
|
|
|
|
This Specification is supplied 'AS IS' and Liebert Corporation
|
|
makes no warranty, either express or implied, as to the use,
|
|
operation, condition, or performance of the Specification."
|
|
|
|
REVISION "201810020000Z"
|
|
DESCRIPTION
|
|
"Compiled From GDD Version: 6825.1"
|
|
|
|
|
|
::= { liebertFlexibleConditionsModuleReg 1 }
|
|
|
|
-- =============================================================================
|
|
-- lgpFlexConditions - Liebert Conditions Registrations
|
|
-- =============================================================================
|
|
|
|
lgpFlexConditionsWellKnown OBJECT IDENTIFIER
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Liebert well known conditions are defined by OIDs that
|
|
-- reside in this sub-tree."
|
|
::= { lgpFlexConditions 1 }
|
|
|
|
-- =============================================================================
|
|
-- lgpFlexConditionsWellKnown - Liebert "well-known" Conditions
|
|
-- =============================================================================
|
|
|
|
lgpCondId4122SystemInputPowerProblem OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input is not qualified to provide power to the system."
|
|
::= { lgpFlexConditionsWellKnown 4122 }
|
|
|
|
lgpCondId4132BypassOverloadPhaseA OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An overload exists on output phase A while operating on the bypass."
|
|
::= { lgpFlexConditionsWellKnown 4132 }
|
|
|
|
lgpCondId4133BypassOverloadPhaseB OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An overload exists on output phase B while operating on the bypass."
|
|
::= { lgpFlexConditionsWellKnown 4133 }
|
|
|
|
lgpCondId4134BypassOverloadPhaseC OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An overload exists on output phase C while operating on the bypass."
|
|
::= { lgpFlexConditionsWellKnown 4134 }
|
|
|
|
lgpCondId4135BypassNotAvailable OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A problem associated with the bypass has been detected."
|
|
::= { lgpFlexConditionsWellKnown 4135 }
|
|
|
|
lgpCondId4137BypassAutoRetransferPrimed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatic retransfer from bypass to inverter is possible."
|
|
::= { lgpFlexConditionsWellKnown 4137 }
|
|
|
|
lgpCondId4138BypassAutoRetransferFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"After performing a recoverable transfer to bypass, an attempt to
|
|
auto retransfer from bypass to inverter failed."
|
|
::= { lgpFlexConditionsWellKnown 4138 }
|
|
|
|
lgpCondId4139BypassExcessAutoRetransfers OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of auto retransfers, from bypass to inverter, has
|
|
exceeded the maximum for a specified time interval."
|
|
::= { lgpFlexConditionsWellKnown 4139 }
|
|
|
|
lgpCondId4140BypassRestartInhibitExternal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Restart of the bypass is inhibited by the state of an external
|
|
signal."
|
|
::= { lgpFlexConditionsWellKnown 4140 }
|
|
|
|
lgpCondId4141BypassBreakerClosed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bypass breaker is closed."
|
|
::= { lgpFlexConditionsWellKnown 4141 }
|
|
|
|
lgpCondId4142BypassStaticSwitchOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass off due to static switch overload."
|
|
::= { lgpFlexConditionsWellKnown 4142 }
|
|
|
|
lgpCondId4143BypassStaticSwitchUnavailable OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The static bypass is unavailable to support the critical load."
|
|
::= { lgpFlexConditionsWellKnown 4143 }
|
|
|
|
lgpCondId4144BypassExcessivePulseParallel OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has performed too many pulse parallel operations within
|
|
a specified time interval."
|
|
::= { lgpFlexConditionsWellKnown 4144 }
|
|
|
|
lgpCondId4145BypassAutoTransferFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An automatic transfer to static bypass failed."
|
|
::= { lgpFlexConditionsWellKnown 4145 }
|
|
|
|
lgpCondId4146SystemInputPhsRotationError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power conductors on the input line are not wired to the UPS in
|
|
the sequence preferred for the rectifier (A-B-C)."
|
|
::= { lgpFlexConditionsWellKnown 4146 }
|
|
|
|
lgpCondId4147SystemInputCurrentLimit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The RMS input current has reached the input current limit
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 4147 }
|
|
|
|
lgpCondId4162BatteryLow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The calculated battery time remaining has reached the low battery
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 4162 }
|
|
|
|
lgpCondId4163OutputOffEndofDischarge OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output turned off due to battery reaching end-of-discharge."
|
|
::= { lgpFlexConditionsWellKnown 4163 }
|
|
|
|
lgpCondId4164BatteryChargingError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery is not charging properly."
|
|
::= { lgpFlexConditionsWellKnown 4164 }
|
|
|
|
lgpCondId4165BatteryChargingReducedExtrnl OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Using a reduced battery charging algorithm due to an external
|
|
signal."
|
|
::= { lgpFlexConditionsWellKnown 4165 }
|
|
|
|
lgpCondId4166BatteryCapacityLow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery capacity is low."
|
|
::= { lgpFlexConditionsWellKnown 4166 }
|
|
|
|
lgpCondId4167OutputOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output is off."
|
|
::= { lgpFlexConditionsWellKnown 4167 }
|
|
|
|
lgpCondId4168BatteryDischarging OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery is discharging."
|
|
::= { lgpFlexConditionsWellKnown 4168 }
|
|
|
|
lgpCondId4169BatteryTemperatureImbalance OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Excessive temperature differences between battery sensors detected."
|
|
::= { lgpFlexConditionsWellKnown 4169 }
|
|
|
|
lgpCondId4170BatteryEqualize OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The rectifier output voltage is increased to equalize the battery
|
|
voltage level."
|
|
::= { lgpFlexConditionsWellKnown 4170 }
|
|
|
|
lgpCondId4171BatteryManualTestInProgress OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Manual battery test is in progress."
|
|
::= { lgpFlexConditionsWellKnown 4171 }
|
|
|
|
lgpCondId4172BatteryAutoTestInProgress OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatic battery test is in progress."
|
|
::= { lgpFlexConditionsWellKnown 4172 }
|
|
|
|
lgpCondId4173MainBatteryDisconnectOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Main battery disconnect is open."
|
|
::= { lgpFlexConditionsWellKnown 4173 }
|
|
|
|
lgpCondId4174BatteryTemperatureSensorFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A battery temperature sensor fault has been detected."
|
|
::= { lgpFlexConditionsWellKnown 4174 }
|
|
|
|
lgpCondId4175BypassFrequencyError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bypass frequency is outside the inverter synchronization
|
|
limits."
|
|
::= { lgpFlexConditionsWellKnown 4175 }
|
|
|
|
lgpCondId4176BatteryCircuitBreaker1Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 1 is open."
|
|
::= { lgpFlexConditionsWellKnown 4176 }
|
|
|
|
lgpCondId4177BatteryBreaker1OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 1 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4177 }
|
|
|
|
lgpCondId4178BatteryBreaker1CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 1 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4178 }
|
|
|
|
lgpCondId4179BatteryCircuitBreaker2Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 2 is open."
|
|
::= { lgpFlexConditionsWellKnown 4179 }
|
|
|
|
lgpCondId4180BatteryBreaker2OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 2 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4180 }
|
|
|
|
lgpCondId4181BatteryBreaker2CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 2 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4181 }
|
|
|
|
lgpCondId4182BatteryCircuitBreaker3Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 3 is open."
|
|
::= { lgpFlexConditionsWellKnown 4182 }
|
|
|
|
lgpCondId4183BatteryBreaker3OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 3 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4183 }
|
|
|
|
lgpCondId4184BatteryBreaker3CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 3 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4184 }
|
|
|
|
lgpCondId4185BatteryCircuitBreaker4Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 4 is open."
|
|
::= { lgpFlexConditionsWellKnown 4185 }
|
|
|
|
lgpCondId4186BatteryBreaker4OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 4 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4186 }
|
|
|
|
lgpCondId4187BatteryBreaker4CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 4 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4187 }
|
|
|
|
lgpCondId4188BatteryCircuitBreaker5Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 5 is open."
|
|
::= { lgpFlexConditionsWellKnown 4188 }
|
|
|
|
lgpCondId4189BatteryBreaker5OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 5 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4189 }
|
|
|
|
lgpCondId4190BatteryBreaker5CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 5 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4190 }
|
|
|
|
lgpCondId4191BatteryCircuitBreaker6Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 6 is open."
|
|
::= { lgpFlexConditionsWellKnown 4191 }
|
|
|
|
lgpCondId4192BatteryBreaker6OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 6 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4192 }
|
|
|
|
lgpCondId4193BatteryBreaker6CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 6 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4193 }
|
|
|
|
lgpCondId4194BatteryCircuitBreaker7Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 7 is open."
|
|
::= { lgpFlexConditionsWellKnown 4194 }
|
|
|
|
lgpCondId4195BatteryBreaker7OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 7 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4195 }
|
|
|
|
lgpCondId4196BatteryBreaker7CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 7 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4196 }
|
|
|
|
lgpCondId4197BatteryCircuitBreaker8Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 8 is open."
|
|
::= { lgpFlexConditionsWellKnown 4197 }
|
|
|
|
lgpCondId4198BatteryBreaker8OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 8 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4198 }
|
|
|
|
lgpCondId4199BatteryBreaker8CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 8 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4199 }
|
|
|
|
lgpCondId4200BatteryChargingInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery charging is inhibited due to an external inhibit signal."
|
|
::= { lgpFlexConditionsWellKnown 4200 }
|
|
|
|
lgpCondId4213SystemShutdownEPO OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System shutdown due to Emergency Power Off (EPO)."
|
|
::= { lgpFlexConditionsWellKnown 4213 }
|
|
|
|
lgpCondId4214SystemShutdownREPO OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System shutdown due to Remote Emergency Power Off (REPO)."
|
|
::= { lgpFlexConditionsWellKnown 4214 }
|
|
|
|
lgpCondId4215SystemOutputOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system output is off."
|
|
::= { lgpFlexConditionsWellKnown 4215 }
|
|
|
|
lgpCondId4216BypassBackfeedDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system detected a voltage on the bypass when none was expected."
|
|
::= { lgpFlexConditionsWellKnown 4216 }
|
|
|
|
lgpCondId4217BypassManualXfrInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Manual transfer from inverter to bypass is inhibited - bypass not
|
|
qualified."
|
|
::= { lgpFlexConditionsWellKnown 4217 }
|
|
|
|
lgpCondId4218BypassManualRexfrInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Manual transfer from bypass to inverter is inhibited - inverter
|
|
output not qualified."
|
|
::= { lgpFlexConditionsWellKnown 4218 }
|
|
|
|
lgpCondId4219BatteryOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A battery temperature sensor is reporting a value above a
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 4219 }
|
|
|
|
lgpCondId4220BatteryExternalMonitor1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External battery monitor 1 - battery maintenance required."
|
|
::= { lgpFlexConditionsWellKnown 4220 }
|
|
|
|
lgpCondId4221BatteryExternalMonitor2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External battery monitor 2 - battery maintenance required."
|
|
::= { lgpFlexConditionsWellKnown 4221 }
|
|
|
|
lgpCondId4222BatteryGroundFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery system ground fault amperage exceeds the threshold."
|
|
::= { lgpFlexConditionsWellKnown 4222 }
|
|
|
|
lgpCondId4229EmergencyPowerOffLatched OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System output is off - 'Emergency Power Off (EPO) - latched'
|
|
requires manual reset."
|
|
::= { lgpFlexConditionsWellKnown 4229 }
|
|
|
|
lgpCondId4230SystemOutputLowPowerFactor OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system output power factor is low, resulting in reduced output
|
|
capacity."
|
|
::= { lgpFlexConditionsWellKnown 4230 }
|
|
|
|
lgpCondId4231OutputCurrentExceedsThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output current for one or more phases exceeds a threshold."
|
|
::= { lgpFlexConditionsWellKnown 4231 }
|
|
|
|
lgpCondId4233InverterFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter failure - inverter output is off."
|
|
::= { lgpFlexConditionsWellKnown 4233 }
|
|
|
|
lgpCondId4234InverterOverloadPhaseA OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter is operating with an overload on phase A."
|
|
::= { lgpFlexConditionsWellKnown 4234 }
|
|
|
|
lgpCondId4235InverterOverloadPhaseB OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter is operating with an overload on phase B."
|
|
::= { lgpFlexConditionsWellKnown 4235 }
|
|
|
|
lgpCondId4236InverterOverloadPhaseC OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter is operating with an overload on phase C."
|
|
::= { lgpFlexConditionsWellKnown 4236 }
|
|
|
|
lgpCondId4237InverterInhibitExternal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Restart of the inverter is inhibited by an external signal."
|
|
::= { lgpFlexConditionsWellKnown 4237 }
|
|
|
|
lgpCondId4238InverterOutBreakerOpenFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter output breaker failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4238 }
|
|
|
|
lgpCondId4239InverterOutBreakerCloseFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter output breaker failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4239 }
|
|
|
|
lgpCondId4270InputContact01 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 1."
|
|
::= { lgpFlexConditionsWellKnown 4270 }
|
|
|
|
lgpCondId4271InputContact02 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 2."
|
|
::= { lgpFlexConditionsWellKnown 4271 }
|
|
|
|
lgpCondId4272InputContact03 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 3."
|
|
::= { lgpFlexConditionsWellKnown 4272 }
|
|
|
|
lgpCondId4273InputContact04 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 4."
|
|
::= { lgpFlexConditionsWellKnown 4273 }
|
|
|
|
lgpCondId4274InputContact05 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 5."
|
|
::= { lgpFlexConditionsWellKnown 4274 }
|
|
|
|
lgpCondId4275InputContact06 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 6."
|
|
::= { lgpFlexConditionsWellKnown 4275 }
|
|
|
|
lgpCondId4276InputContact07 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 7."
|
|
::= { lgpFlexConditionsWellKnown 4276 }
|
|
|
|
lgpCondId4277InputContact08 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 8."
|
|
::= { lgpFlexConditionsWellKnown 4277 }
|
|
|
|
lgpCondId4278InputContact09 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 9."
|
|
::= { lgpFlexConditionsWellKnown 4278 }
|
|
|
|
lgpCondId4279InputContact10 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 10."
|
|
::= { lgpFlexConditionsWellKnown 4279 }
|
|
|
|
lgpCondId4280InputContact11 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 11."
|
|
::= { lgpFlexConditionsWellKnown 4280 }
|
|
|
|
lgpCondId4281InputContact12 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 12."
|
|
::= { lgpFlexConditionsWellKnown 4281 }
|
|
|
|
lgpCondId4282InputContact13 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 13."
|
|
::= { lgpFlexConditionsWellKnown 4282 }
|
|
|
|
lgpCondId4283InputContact14 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 14."
|
|
::= { lgpFlexConditionsWellKnown 4283 }
|
|
|
|
lgpCondId4284InputContact15 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 15."
|
|
::= { lgpFlexConditionsWellKnown 4284 }
|
|
|
|
lgpCondId4285InputContact16 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 16."
|
|
::= { lgpFlexConditionsWellKnown 4285 }
|
|
|
|
lgpCondId4286OutputAmpOverUserLimitPhsA OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The phase A output has exceeded the user amperage threshold."
|
|
::= { lgpFlexConditionsWellKnown 4286 }
|
|
|
|
lgpCondId4287OutputAmpOverUserLimitPhsB OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The phase B output has exceeded the user amperage threshold."
|
|
::= { lgpFlexConditionsWellKnown 4287 }
|
|
|
|
lgpCondId4288OutputAmpOverUserLimitPhsC OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The phase C output has exceeded the user amperage threshold."
|
|
::= { lgpFlexConditionsWellKnown 4288 }
|
|
|
|
lgpCondId4289InverterTransferInhibitExt OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Transfer of critical bus source to inverter is inhibited by an
|
|
external signal."
|
|
::= { lgpFlexConditionsWellKnown 4289 }
|
|
|
|
lgpCondId4290InverterShutdownOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter has shutdown due to a sustained overload."
|
|
::= { lgpFlexConditionsWellKnown 4290 }
|
|
|
|
lgpCondId4294InletAirOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inlet air exceeds the maximum temperature threshold."
|
|
::= { lgpFlexConditionsWellKnown 4294 }
|
|
|
|
lgpCondId4295RectifierFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier failure - rectifier is off."
|
|
::= { lgpFlexConditionsWellKnown 4295 }
|
|
|
|
lgpCondId4296RectifierOperationInhibitExt OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The operation of the rectifier is inhibited by an external signal."
|
|
::= { lgpFlexConditionsWellKnown 4296 }
|
|
|
|
lgpCondId4297UPSOutputonInverter OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output power is supplied by the inverter."
|
|
::= { lgpFlexConditionsWellKnown 4297 }
|
|
|
|
lgpCondId4298UPSOutputonBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output power is supplied by the bypass."
|
|
::= { lgpFlexConditionsWellKnown 4298 }
|
|
|
|
lgpCondId4299OutputLoadonMaintBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output power is supplied by the maintenance bypass."
|
|
::= { lgpFlexConditionsWellKnown 4299 }
|
|
|
|
lgpCondId4300InternalCommunicationsFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The control has detected a communication failure of a component on
|
|
the internal communication bus."
|
|
::= { lgpFlexConditionsWellKnown 4300 }
|
|
|
|
lgpCondId4308DCBusGroundFaultPositive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A ground fault has been detected on the positive DC Bus link."
|
|
::= { lgpFlexConditionsWellKnown 4308 }
|
|
|
|
lgpCondId4309DCBusGroundFaultNegative OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A ground fault has been detected on the negative DC Bus link."
|
|
::= { lgpFlexConditionsWellKnown 4309 }
|
|
|
|
lgpCondId4310EquipmentOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Equipment over temperature summary event."
|
|
::= { lgpFlexConditionsWellKnown 4310 }
|
|
|
|
lgpCondId4311SystemFanFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System fan failure - one or more fans have failed."
|
|
::= { lgpFlexConditionsWellKnown 4311 }
|
|
|
|
lgpCondId4313PasswordChanged OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Password changed."
|
|
::= { lgpFlexConditionsWellKnown 4313 }
|
|
|
|
lgpCondId4314PowerSupplyFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power supply failure."
|
|
::= { lgpFlexConditionsWellKnown 4314 }
|
|
|
|
lgpCondId4315OnGenerator OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A generator is supplying the power to the system."
|
|
::= { lgpFlexConditionsWellKnown 4315 }
|
|
|
|
lgpCondId4316AutoRestartInProgress OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Auto restart is in progress."
|
|
::= { lgpFlexConditionsWellKnown 4316 }
|
|
|
|
lgpCondId4317AutoRestartInhibitedExt OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Auto restart inhibited due to an external signal."
|
|
::= { lgpFlexConditionsWellKnown 4317 }
|
|
|
|
lgpCondId4320InitiatedTransfertoBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User initiated manual transfer to bypass."
|
|
::= { lgpFlexConditionsWellKnown 4320 }
|
|
|
|
lgpCondId4321InitiatedTransfertoInverter OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User initiated manual transfer to inverter."
|
|
::= { lgpFlexConditionsWellKnown 4321 }
|
|
|
|
lgpCondId4322BatteryTestPassed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery test passed."
|
|
::= { lgpFlexConditionsWellKnown 4322 }
|
|
|
|
lgpCondId4323BatteryTestFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery test failed."
|
|
::= { lgpFlexConditionsWellKnown 4323 }
|
|
|
|
lgpCondId4324BatteryTestManuallyStopped OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery test was manually stopped prior to completion."
|
|
::= { lgpFlexConditionsWellKnown 4324 }
|
|
|
|
lgpCondId4325BackfeedBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The backfeed breaker is in the open position."
|
|
::= { lgpFlexConditionsWellKnown 4325 }
|
|
|
|
lgpCondId4341VelocityAuthenticationFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Notification of a message rejected by Velocity due to an
|
|
authentication failure."
|
|
::= { lgpFlexConditionsWellKnown 4341 }
|
|
|
|
lgpCondId4360ReceptacleOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a receptacle over current condition."
|
|
::= { lgpFlexConditionsWellKnown 4360 }
|
|
|
|
lgpCondId4361ReceptacleUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a receptacle under current condition."
|
|
::= { lgpFlexConditionsWellKnown 4361 }
|
|
|
|
lgpCondId4382SystemInputCurrentImbalance OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System Input Currents are Imbalanced."
|
|
::= { lgpFlexConditionsWellKnown 4382 }
|
|
|
|
lgpCondId4383BypassStaticSwitchOffExtrnl OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass static switch is off due to the state of an external signal."
|
|
::= { lgpFlexConditionsWellKnown 4383 }
|
|
|
|
lgpCondId4384BatteryEoDDisconnect OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery disconnect due to end-of-discharge."
|
|
::= { lgpFlexConditionsWellKnown 4384 }
|
|
|
|
lgpCondId4389SystemOutputFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A fault has been detected in the system output."
|
|
::= { lgpFlexConditionsWellKnown 4389 }
|
|
|
|
lgpCondId4390InverterOffExternal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter is off (operation is inhibited) due to external signal
|
|
state."
|
|
::= { lgpFlexConditionsWellKnown 4390 }
|
|
|
|
lgpCondId4391InverterStaticSwitchSCRShort OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short across one or more inverter static
|
|
switch Silicon Controlled Rectifiers (SCR)."
|
|
::= { lgpFlexConditionsWellKnown 4391 }
|
|
|
|
lgpCondId4392TemperatureSensorError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more temperature sensors cannot provide a valid temperature
|
|
reading (i.e. sensor failure, wiring failure, sense circuit
|
|
failure, etc)."
|
|
::= { lgpFlexConditionsWellKnown 4392 }
|
|
|
|
lgpCondId4406BranchOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module over current condition."
|
|
::= { lgpFlexConditionsWellKnown 4406 }
|
|
|
|
lgpCondId4407BranchUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under current condition."
|
|
::= { lgpFlexConditionsWellKnown 4407 }
|
|
|
|
lgpCondId4416BranchOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module over current condition."
|
|
::= { lgpFlexConditionsWellKnown 4416 }
|
|
|
|
lgpCondId4417BranchUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under current condition."
|
|
::= { lgpFlexConditionsWellKnown 4417 }
|
|
|
|
lgpCondId4421BranchFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more conditions indicate a Branch Receptacle Module failure
|
|
, service is required."
|
|
::= { lgpFlexConditionsWellKnown 4421 }
|
|
|
|
lgpCondId4436PDUOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module over current condition."
|
|
::= { lgpFlexConditionsWellKnown 4436 }
|
|
|
|
lgpCondId4437PDUUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under current condition."
|
|
::= { lgpFlexConditionsWellKnown 4437 }
|
|
|
|
lgpCondId4438SystemInternalTemperatureRise OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Excessive temperature rise internal to the system (i.e. difference
|
|
between the output versus input temperature is too large)."
|
|
::= { lgpFlexConditionsWellKnown 4438 }
|
|
|
|
lgpCondId4439AutomaticRestartFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatic restart failed."
|
|
::= { lgpFlexConditionsWellKnown 4439 }
|
|
|
|
lgpCondId4440FuseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A summary event indicating one or more fuse failures."
|
|
::= { lgpFlexConditionsWellKnown 4440 }
|
|
|
|
lgpCondId4441SystemControllerError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System controller internal error."
|
|
::= { lgpFlexConditionsWellKnown 4441 }
|
|
|
|
lgpCondId4442SystemBreakersOpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more breakers in the system failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4442 }
|
|
|
|
lgpCondId4448PDUOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module over current condition."
|
|
::= { lgpFlexConditionsWellKnown 4448 }
|
|
|
|
lgpCondId4449PDUUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under current condition."
|
|
::= { lgpFlexConditionsWellKnown 4449 }
|
|
|
|
lgpCondId4468PDUOverCurrentL1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module over current condition on line 1."
|
|
::= { lgpFlexConditionsWellKnown 4468 }
|
|
|
|
lgpCondId4469PDUOverCurrentL2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module over current condition on line 2."
|
|
::= { lgpFlexConditionsWellKnown 4469 }
|
|
|
|
lgpCondId4470PDUOverCurrentL3 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module over current condition on line 3."
|
|
::= { lgpFlexConditionsWellKnown 4470 }
|
|
|
|
lgpCondId4471PDUUnderCurrentL1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under current condition on line 1."
|
|
::= { lgpFlexConditionsWellKnown 4471 }
|
|
|
|
lgpCondId4472PDUUnderCurrentL2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under current condition on line 2."
|
|
::= { lgpFlexConditionsWellKnown 4472 }
|
|
|
|
lgpCondId4473PDUUnderCurrentL3 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under current condition on line 3."
|
|
::= { lgpFlexConditionsWellKnown 4473 }
|
|
|
|
lgpCondId4492ReceptaclePowerStateOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The receptacle power state changed to the ON state."
|
|
::= { lgpFlexConditionsWellKnown 4492 }
|
|
|
|
lgpCondId4493ReceptaclePowerStateOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The receptacle power state changed to the OFF state."
|
|
::= { lgpFlexConditionsWellKnown 4493 }
|
|
|
|
lgpCondId4494BranchBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Branch Receptacle Module's input breaker is open."
|
|
::= { lgpFlexConditionsWellKnown 4494 }
|
|
|
|
lgpCondId4495DeviceConfigurationChange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device Configuration Change."
|
|
::= { lgpFlexConditionsWellKnown 4495 }
|
|
|
|
lgpCondId4496BasicDisplayModuleRemoved OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Basic Display Module Removed."
|
|
::= { lgpFlexConditionsWellKnown 4496 }
|
|
|
|
lgpCondId4497BasicDisplayModuleDiscovered OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Basic Display Module Discovered."
|
|
::= { lgpFlexConditionsWellKnown 4497 }
|
|
|
|
lgpCondId4500PDUOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a power module over current condition."
|
|
::= { lgpFlexConditionsWellKnown 4500 }
|
|
|
|
lgpCondId4501PDUUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a power module under current condition."
|
|
::= { lgpFlexConditionsWellKnown 4501 }
|
|
|
|
lgpCondId4502PDUFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more conditions indicate a power module failure, service is
|
|
required."
|
|
::= { lgpFlexConditionsWellKnown 4502 }
|
|
|
|
lgpCondId4503PDUCommunicationFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Internal communications failure with the Power Module."
|
|
::= { lgpFlexConditionsWellKnown 4503 }
|
|
|
|
lgpCondId4504BranchRemoved OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Branch Receptacle Module Removed."
|
|
::= { lgpFlexConditionsWellKnown 4504 }
|
|
|
|
lgpCondId4505BranchDiscovered OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Branch Receptacle Module Discovered."
|
|
::= { lgpFlexConditionsWellKnown 4505 }
|
|
|
|
lgpCondId4506BranchOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a Branch Receptacle Module over current
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 4506 }
|
|
|
|
lgpCondId4507BranchCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a Branch Receptacle Module under current
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 4507 }
|
|
|
|
lgpCondId4508ReceptacleLoadRemoved OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The receptacle's load stopped drawing power."
|
|
::= { lgpFlexConditionsWellKnown 4508 }
|
|
|
|
lgpCondId4509ReceptacleLoadAdded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The receptacle's load started to draw power."
|
|
::= { lgpFlexConditionsWellKnown 4509 }
|
|
|
|
lgpCondId4523ModuleRemoved OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Module Removed."
|
|
::= { lgpFlexConditionsWellKnown 4523 }
|
|
|
|
lgpCondId4524ModuleAdded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Module Added."
|
|
::= { lgpFlexConditionsWellKnown 4524 }
|
|
|
|
lgpCondId4550FirmwareUpdateRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Module compatibility error requires a system firmware update to
|
|
resolve."
|
|
::= { lgpFlexConditionsWellKnown 4550 }
|
|
|
|
lgpCondId4551GenericTestEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A generic test event designed to evaluate system handling of
|
|
events."
|
|
::= { lgpFlexConditionsWellKnown 4551 }
|
|
|
|
lgpCondId4580OverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An over temperature condition was detected."
|
|
::= { lgpFlexConditionsWellKnown 4580 }
|
|
|
|
lgpCondId4581UnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An under temperature condition was detected."
|
|
::= { lgpFlexConditionsWellKnown 4581 }
|
|
|
|
lgpCondId4588OverRelativeHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An over relative humidity condition was detected."
|
|
::= { lgpFlexConditionsWellKnown 4588 }
|
|
|
|
lgpCondId4589UnderRelativeHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An under relative humidity condition was detected."
|
|
::= { lgpFlexConditionsWellKnown 4589 }
|
|
|
|
lgpCondId4601ExternalAirSensorAOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Ext Air Sensor A Temperature] has exceeded [External Air Over
|
|
Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 4601 }
|
|
|
|
lgpCondId4604ExternalAirSensorBOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Ext Air Sensor B Temperature] has exceeded [External Air Over
|
|
Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 4604 }
|
|
|
|
lgpCondId4608ExtAirSensorAUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Ext Air Sensor A Temperature] has dropped below [Ext Air Under
|
|
Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 4608 }
|
|
|
|
lgpCondId4611ExtAirSensorBUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Ext Air Sensor B Temperature] has dropped below [Ext Air Under
|
|
Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 4611 }
|
|
|
|
lgpCondId4615ExtDewPointOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"At least one dew point temperature reading ([Ext Air Sensor A Dew
|
|
Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded
|
|
[Ext Dew Point Over Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 4615 }
|
|
|
|
lgpCondId4618ExternalAirSensorAIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external air sensor A is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 4618 }
|
|
|
|
lgpCondId4621ExternalAirSensorBIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external air sensor B is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 4621 }
|
|
|
|
lgpCondId4626SupplyChilledWaterOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Fluid Temperature] has exceeded [High Supply Fluid
|
|
Temperature Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 4626 }
|
|
|
|
lgpCondId4629SupplyChilledWaterTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The supply chilled water temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 4629 }
|
|
|
|
lgpCondId4634SupplyRefrigerantOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event that is activated when [Supply Refrigerant Temperature]
|
|
exceeds [Supply Refrig Over Temp Threshold]. The event is
|
|
deactivated when the temperature drops below the threshold."
|
|
::= { lgpFlexConditionsWellKnown 4634 }
|
|
|
|
lgpCondId4637SupplyRefrigerantUnderTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Refrigerant Temperature] has dropped below a specified
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 4637 }
|
|
|
|
lgpCondId4640SupplyRefrigerantTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The supply refrigeramt temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 4640 }
|
|
|
|
lgpCondId4645SupplyFluidOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp
|
|
Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 4645 }
|
|
|
|
lgpCondId4648SupplyFluidUnderTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Fluid Temperature] has dropped below a specified threshold."
|
|
::= { lgpFlexConditionsWellKnown 4648 }
|
|
|
|
lgpCondId4651SupplyFluidTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The supply fluid temperature sensor is disconnected or the signal
|
|
is out of range."
|
|
::= { lgpFlexConditionsWellKnown 4651 }
|
|
|
|
lgpCondId4656Pump1LossofFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loss of flow is detected in pump 1. The loss of flow condition
|
|
occurs when no differential pressure is detected across the pump."
|
|
::= { lgpFlexConditionsWellKnown 4656 }
|
|
|
|
lgpCondId4659Pump2LossofFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loss of flow is detected in pump 2. The loss of flow condition
|
|
occurs when no differential pressure is detected across the pump."
|
|
::= { lgpFlexConditionsWellKnown 4659 }
|
|
|
|
lgpCondId4662PumpShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pumps have short cycled. A short cycle is defined as turning on
|
|
and off a number of times over a set time period."
|
|
::= { lgpFlexConditionsWellKnown 4662 }
|
|
|
|
lgpCondId4669Compressor1AHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1A high head pressure."
|
|
::= { lgpFlexConditionsWellKnown 4669 }
|
|
|
|
lgpCondId4672Compressor1BHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1B high head pressure."
|
|
::= { lgpFlexConditionsWellKnown 4672 }
|
|
|
|
lgpCondId4675Compressor2AHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 2A high head pressure."
|
|
::= { lgpFlexConditionsWellKnown 4675 }
|
|
|
|
lgpCondId4678Compressor2BHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 2B high head pressure."
|
|
::= { lgpFlexConditionsWellKnown 4678 }
|
|
|
|
lgpCondId4681Compressor1AShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1A short cycle. A short cycle is defined as turning on
|
|
and off a number of times over a set time period."
|
|
::= { lgpFlexConditionsWellKnown 4681 }
|
|
|
|
lgpCondId4684Compressor1BShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1B short cycle. A short cycle is defined as turning on
|
|
and off a number of times over a set time period."
|
|
::= { lgpFlexConditionsWellKnown 4684 }
|
|
|
|
lgpCondId4687Compressor2AShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 2A short cycle. A short cycle is defined as turning on
|
|
and off a number of times over a set time period."
|
|
::= { lgpFlexConditionsWellKnown 4687 }
|
|
|
|
lgpCondId4690Compressor2BShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 2B short cycle. A short cycle is defined as turning on
|
|
and off a number of times over a set time period."
|
|
::= { lgpFlexConditionsWellKnown 4690 }
|
|
|
|
lgpCondId4693Tandem1LowSuctionPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"'Tandem compressors' 1 low suction pressure."
|
|
::= { lgpFlexConditionsWellKnown 4693 }
|
|
|
|
lgpCondId4696Tandem2LowSuctionPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"'Tandem compressors' 2 low suction pressure."
|
|
::= { lgpFlexConditionsWellKnown 4696 }
|
|
|
|
lgpCondId4703ChilledWaterControlValvePosition OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water valve out of position. Chilled water control valve
|
|
position does not match expected value."
|
|
::= { lgpFlexConditionsWellKnown 4703 }
|
|
|
|
lgpCondId4711SystemCondensationDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System condensation detected."
|
|
::= { lgpFlexConditionsWellKnown 4711 }
|
|
|
|
lgpCondId4714ShutdownLossOfPower OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System lost power. This event becomes active when the unit is
|
|
powered on following an unexpected loss of power."
|
|
::= { lgpFlexConditionsWellKnown 4714 }
|
|
|
|
lgpCondId4720SmokeDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Smoke detected."
|
|
::= { lgpFlexConditionsWellKnown 4720 }
|
|
|
|
lgpCondId4723WaterUnderFloor OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water under the floor is detected."
|
|
::= { lgpFlexConditionsWellKnown 4723 }
|
|
|
|
lgpCondId4726ServiceRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit requires servicing."
|
|
::= { lgpFlexConditionsWellKnown 4726 }
|
|
|
|
lgpCondId4729FanIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more fans are not operating within their operational
|
|
parameters."
|
|
::= { lgpFlexConditionsWellKnown 4729 }
|
|
|
|
lgpCondId4732ReceptacleLoadDropped OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The receptacle's load is not drawing power."
|
|
::= { lgpFlexConditionsWellKnown 4732 }
|
|
|
|
lgpCondId4740BatteryAutomaticTestInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatic (scheduled) battery tests are inhibited."
|
|
::= { lgpFlexConditionsWellKnown 4740 }
|
|
|
|
lgpCondId4741BatterySelfTest OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery self test is in progress."
|
|
::= { lgpFlexConditionsWellKnown 4741 }
|
|
|
|
lgpCondId4742BatteryLowShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery disconnect due to end-of-discharge."
|
|
::= { lgpFlexConditionsWellKnown 4742 }
|
|
|
|
lgpCondId4747EquipmentTemperatureSensorFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more temperature sensors report a temperature outside of
|
|
the range of expected operation."
|
|
::= { lgpFlexConditionsWellKnown 4747 }
|
|
|
|
lgpCondId4749SystemFanFailureRedundant OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Redundant system fan failure."
|
|
::= { lgpFlexConditionsWellKnown 4749 }
|
|
|
|
lgpCondId4750MultipleFanFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Multiple fan failure."
|
|
::= { lgpFlexConditionsWellKnown 4750 }
|
|
|
|
lgpCondId4753MainControllerFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Main Controller fault has been detected."
|
|
::= { lgpFlexConditionsWellKnown 4753 }
|
|
|
|
lgpCondId4754SystemBreakersCloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more breakers in the system failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4754 }
|
|
|
|
lgpCondId4755InputFilterCycleLock OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input filter disconnect is open due to exceeding the maximum
|
|
number of cycles."
|
|
::= { lgpFlexConditionsWellKnown 4755 }
|
|
|
|
lgpCondId4756ServiceCodeActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Service code is running."
|
|
::= { lgpFlexConditionsWellKnown 4756 }
|
|
|
|
lgpCondId4757LBSActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Load Bus Sync option is active."
|
|
::= { lgpFlexConditionsWellKnown 4757 }
|
|
|
|
lgpCondId4758LBSInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that conditions to perform Load Bus Sync
|
|
are not satisfied."
|
|
::= { lgpFlexConditionsWellKnown 4758 }
|
|
|
|
lgpCondId4759LeadingPowerFactor OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The leading output Power Factor has fallen below a specified value."
|
|
::= { lgpFlexConditionsWellKnown 4759 }
|
|
|
|
lgpCondId4760ControlsResetRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A controls reset is required due to one or more critical settings
|
|
changing."
|
|
::= { lgpFlexConditionsWellKnown 4760 }
|
|
|
|
lgpCondId4823ParallelCommWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Parallel communication bus warning."
|
|
::= { lgpFlexConditionsWellKnown 4823 }
|
|
|
|
lgpCondId4824SystemCommFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Failure of a device on the multi-module system communication bus."
|
|
::= { lgpFlexConditionsWellKnown 4824 }
|
|
|
|
lgpCondId4825LossofRedundancy OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The multi-module collection doesn't have enough modules to satisfy
|
|
the redundancy configuration."
|
|
::= { lgpFlexConditionsWellKnown 4825 }
|
|
|
|
lgpCondId4826BPSSStartupInhibit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Bypass Static Switch startup is inhibited."
|
|
::= { lgpFlexConditionsWellKnown 4826 }
|
|
|
|
lgpCondId4827MMSTransferInhibit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The critical load can not be manually transferred from inverter to
|
|
bypass."
|
|
::= { lgpFlexConditionsWellKnown 4827 }
|
|
|
|
lgpCondId4828MMSRetransferInhibit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The critical load can not be manually retransferred from bypass to
|
|
inverter."
|
|
::= { lgpFlexConditionsWellKnown 4828 }
|
|
|
|
lgpCondId4830MMSLossofSyncPulse OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Multi-module system loss of sync pulse."
|
|
::= { lgpFlexConditionsWellKnown 4830 }
|
|
|
|
lgpCondId4831MMSOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Multi-module system overload."
|
|
::= { lgpFlexConditionsWellKnown 4831 }
|
|
|
|
lgpCondId4834MMSOnBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The multi-module system is on battery."
|
|
::= { lgpFlexConditionsWellKnown 4834 }
|
|
|
|
lgpCondId4835MMSLowBatteryWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Multi-module system low battery warning."
|
|
::= { lgpFlexConditionsWellKnown 4835 }
|
|
|
|
lgpCondId4906LowAmbientTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low ambient temperature condition."
|
|
::= { lgpFlexConditionsWellKnown 4906 }
|
|
|
|
lgpCondId4907HighAmbientTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high ambient temperature condition."
|
|
::= { lgpFlexConditionsWellKnown 4907 }
|
|
|
|
lgpCondId4908LowOverallVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low battery string overall voltage
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 4908 }
|
|
|
|
lgpCondId4909HighOverallVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high battery string overall voltage
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 4909 }
|
|
|
|
lgpCondId4910HighBatteryStringCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high battery string current condition."
|
|
::= { lgpFlexConditionsWellKnown 4910 }
|
|
|
|
lgpCondId4911LowBatteryStringFloatCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low battery string float current
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 4911 }
|
|
|
|
lgpCondId4912HighBatteryStringFloatCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high battery string float current
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 4912 }
|
|
|
|
lgpCondId4913HighBatteryStringRippleCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high battery string ripple current
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 4913 }
|
|
|
|
lgpCondId4914BatteryStringDischargeDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery string discharge condition."
|
|
::= { lgpFlexConditionsWellKnown 4914 }
|
|
|
|
lgpCondId4915MaximumDischargeTimeExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an excessive discharge time condition."
|
|
::= { lgpFlexConditionsWellKnown 4915 }
|
|
|
|
lgpCondId4916DischargeLowOverallVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low battery string overall voltage
|
|
condition during a discharge."
|
|
::= { lgpFlexConditionsWellKnown 4916 }
|
|
|
|
lgpCondId4917DischargeLowCellVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low cell voltage condition during a
|
|
discharge."
|
|
::= { lgpFlexConditionsWellKnown 4917 }
|
|
|
|
lgpCondId4918DischargeHighBatteryStringCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high battery string current condition
|
|
during a discharge."
|
|
::= { lgpFlexConditionsWellKnown 4918 }
|
|
|
|
lgpCondId4919ExcessiveCelltoCellTemperatureDeviation OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an excessive cell to cell temperature
|
|
deviation condition."
|
|
::= { lgpFlexConditionsWellKnown 4919 }
|
|
|
|
lgpCondId4920ExcessiveCelltoAmbientTemperatureDeviation OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an excessive cell to ambient temperature
|
|
deviation condition."
|
|
::= { lgpFlexConditionsWellKnown 4920 }
|
|
|
|
lgpCondId4964LowCellVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low cell voltage condition."
|
|
::= { lgpFlexConditionsWellKnown 4964 }
|
|
|
|
lgpCondId4965HighCellVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high cell voltage condition."
|
|
::= { lgpFlexConditionsWellKnown 4965 }
|
|
|
|
lgpCondId4966LowCellTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low cell temperature condition."
|
|
::= { lgpFlexConditionsWellKnown 4966 }
|
|
|
|
lgpCondId4967HighCellTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high cell temperature condition."
|
|
::= { lgpFlexConditionsWellKnown 4967 }
|
|
|
|
lgpCondId4968LowInternalResistance OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low internal resistance condition."
|
|
::= { lgpFlexConditionsWellKnown 4968 }
|
|
|
|
lgpCondId4969HighInternalResistance OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high internal resistance condition."
|
|
::= { lgpFlexConditionsWellKnown 4969 }
|
|
|
|
lgpCondId4970HighIntercellResistance OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high intercell resistance condition."
|
|
::= { lgpFlexConditionsWellKnown 4970 }
|
|
|
|
lgpCondId4978IntertierResistanceHigh OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high intertier resistance condition."
|
|
::= { lgpFlexConditionsWellKnown 4978 }
|
|
|
|
lgpCondId4980SupplyChilledWaterLossofFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply chilled water or glycol flow is too low."
|
|
::= { lgpFlexConditionsWellKnown 4980 }
|
|
|
|
lgpCondId4983SupplyRefrigOverTempBand1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Refrigerant Temperature] is above the upper threshold
|
|
specified by [Supply Refrig Temp Band 1]."
|
|
::= { lgpFlexConditionsWellKnown 4983 }
|
|
|
|
lgpCondId4986SupplyRefrigUnderTempBand1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Refrigerant Temperature] is below the lower threshold
|
|
specified by [Supply Refrig Temp Band 1]."
|
|
::= { lgpFlexConditionsWellKnown 4986 }
|
|
|
|
lgpCondId4990SupplyRefrigOverTempBand2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Refrigerant Temperature] is above the upper threshold
|
|
specified by [Supply Refrig Temp Band 2]."
|
|
::= { lgpFlexConditionsWellKnown 4990 }
|
|
|
|
lgpCondId4993SupplyRefrigUnderTempBand2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Refrigerant Temperature] is below the lower threshold
|
|
specified by [Supply Refrig Temp Band 2]."
|
|
::= { lgpFlexConditionsWellKnown 4993 }
|
|
|
|
lgpCondId4996Inverter1ShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter for pump 1 has short cycled and is temporarily locked out
|
|
from further operation to protect from thermal overload. A short
|
|
cycle is defined as powering on and off a number of times over a
|
|
set time period."
|
|
::= { lgpFlexConditionsWellKnown 4996 }
|
|
|
|
lgpCondId4999Inverter2ShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter for pump 2 has short cycled and is temporarily locked out
|
|
from further operation to protect from thermal overload. A short
|
|
cycle is defined as powering on and off a number of times over a
|
|
set time period."
|
|
::= { lgpFlexConditionsWellKnown 4999 }
|
|
|
|
lgpCondId5015SupplyAirOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Air Temperature] has exceeded [High Supply Air Temperature
|
|
Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5015 }
|
|
|
|
lgpCondId5019SupplyAirUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Air Temperature] has dropped below [Low Supply Air
|
|
Temperature Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5019 }
|
|
|
|
lgpCondId5023ReturnAirOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Return Air Temperature] has exceeded [High Return Air Temperature
|
|
Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5023 }
|
|
|
|
lgpCondId5026SupplyAirSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The air sensor at the outlet of the unit is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5026 }
|
|
|
|
lgpCondId5034HighReturnHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Return Humidity] has exceeded [High Return Humidity Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5034 }
|
|
|
|
lgpCondId5036LowReturnHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Return Humidity] has dropped below [Low Return Humidity
|
|
Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5036 }
|
|
|
|
lgpCondId5037HumidifierHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Operating hours for the humidifier have exceeded the threshold."
|
|
::= { lgpFlexConditionsWellKnown 5037 }
|
|
|
|
lgpCondId5038DehumidifierHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Operating hours for the dehumidifier have exceeded the threshold."
|
|
::= { lgpFlexConditionsWellKnown 5038 }
|
|
|
|
lgpCondId5039HumidifierUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The electrical current to the humidifier has dropped below its
|
|
lower threshold."
|
|
::= { lgpFlexConditionsWellKnown 5039 }
|
|
|
|
lgpCondId5040HumidifierOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The electrical current to the humidifier has exceeded its upper
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 5040 }
|
|
|
|
lgpCondId5041HumidifierLowWater OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The water level in the humidifier has dropped below its threshold."
|
|
::= { lgpFlexConditionsWellKnown 5041 }
|
|
|
|
lgpCondId5042HumidifierCylinderWorn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidifier cylinder is not operating properly and needs to be
|
|
replaced."
|
|
::= { lgpFlexConditionsWellKnown 5042 }
|
|
|
|
lgpCondId5043HumidifierIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidifier issue detected, causing it to be locked out."
|
|
::= { lgpFlexConditionsWellKnown 5043 }
|
|
|
|
lgpCondId5044ExtHumidifierLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidifier is shut down and disabled by an external input
|
|
signal."
|
|
::= { lgpFlexConditionsWellKnown 5044 }
|
|
|
|
lgpCondId5045HumidifierControlBoardNotDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidifier control board is required to be connected, but no
|
|
signal is detected."
|
|
::= { lgpFlexConditionsWellKnown 5045 }
|
|
|
|
lgpCondId5046ReturnHumidityOutOfProportionalBand OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Return Humidity] has exceeded the upper limit of
|
|
[Dehumidification Proportional Band], or has dropped below the
|
|
lower limit of [Humidification Proportional Band] ], for an
|
|
extended period of time."
|
|
::= { lgpFlexConditionsWellKnown 5046 }
|
|
|
|
lgpCondId5053LossofAirFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No air flow through the unit due to failure of all fans."
|
|
::= { lgpFlexConditionsWellKnown 5053 }
|
|
|
|
lgpCondId5054FanHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Operating hours for the unit blower fan have exceeded the
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 5054 }
|
|
|
|
lgpCondId5055TopFanIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The top fan is not operating within its normal parameters."
|
|
::= { lgpFlexConditionsWellKnown 5055 }
|
|
|
|
lgpCondId5056BottomFanIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bottom fan is not operating within its normal parameters."
|
|
::= { lgpFlexConditionsWellKnown 5056 }
|
|
|
|
lgpCondId5060RemoteSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5060 }
|
|
|
|
lgpCondId5062Compressor1LowSuctionPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1 low suction pressure."
|
|
::= { lgpFlexConditionsWellKnown 5062 }
|
|
|
|
lgpCondId5063Compressor1HoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Operating hours for compressor 1 have exceeded the threshold."
|
|
::= { lgpFlexConditionsWellKnown 5063 }
|
|
|
|
lgpCondId5064DigScrollComp1TempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Digital scroll compressor 1 temperature sensor is disconnected or
|
|
the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5064 }
|
|
|
|
lgpCondId5065DigScrollComp1OverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Digital scroll compressor 1 shut off because its head temperature
|
|
has exceeded the upper threshold."
|
|
::= { lgpFlexConditionsWellKnown 5065 }
|
|
|
|
lgpCondId5066Compressor1LowPressureTransducerIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1 low pressure transducer is disconnected or the signal
|
|
is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5066 }
|
|
|
|
lgpCondId5067ExtCompressorLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The compressor is shut down and disabled by an external input
|
|
signal."
|
|
::= { lgpFlexConditionsWellKnown 5067 }
|
|
|
|
lgpCondId5068ReheaterOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature of the reheater has exceeded its threshold."
|
|
::= { lgpFlexConditionsWellKnown 5068 }
|
|
|
|
lgpCondId5069ElectricReheater1HoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Operating hours for electric reheater 1 have exceeded the
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 5069 }
|
|
|
|
lgpCondId5070ExtReheatLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The reheater is shut down and disabled by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5070 }
|
|
|
|
lgpCondId5071Condenser1Issue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser 1 is not operating within its normal parameters."
|
|
::= { lgpFlexConditionsWellKnown 5071 }
|
|
|
|
lgpCondId5072CondenserVFDIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser fan Variable Frequency Drive is offline."
|
|
::= { lgpFlexConditionsWellKnown 5072 }
|
|
|
|
lgpCondId5073CondenserTVSSIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser Transient Voltage Surge Suppressor or Surge
|
|
Protection Device has failed."
|
|
::= { lgpFlexConditionsWellKnown 5073 }
|
|
|
|
lgpCondId5104ExtOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A temperature has exceeded its threshold, as indicated by an
|
|
external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5104 }
|
|
|
|
lgpCondId5105ExtLossofFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loss of flow is detected, as indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5105 }
|
|
|
|
lgpCondId5106ExtCondenserPumpHighWater OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High water is detected in the condensate pump by the auxiliary
|
|
float, as indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5106 }
|
|
|
|
lgpCondId5107ExtStandbyGlycolPumpOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The standby glycol pump is on, as indicated by an external input
|
|
signal."
|
|
::= { lgpFlexConditionsWellKnown 5107 }
|
|
|
|
lgpCondId5108ExternalFireDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fire detected, as indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5108 }
|
|
|
|
lgpCondId5109UnitOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit was turned on."
|
|
::= { lgpFlexConditionsWellKnown 5109 }
|
|
|
|
lgpCondId5110UnitOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit was turned off."
|
|
::= { lgpFlexConditionsWellKnown 5110 }
|
|
|
|
lgpCondId5111UnitStandby OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit was placed in standby mode."
|
|
::= { lgpFlexConditionsWellKnown 5111 }
|
|
|
|
lgpCondId5112UnitPartialShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An event has occurred requiring some system components to be
|
|
shutdown and disabled."
|
|
::= { lgpFlexConditionsWellKnown 5112 }
|
|
|
|
lgpCondId5113UnitShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An event has occurred requiring the unit to be shutdown and
|
|
disabled to prevent damage to the system."
|
|
::= { lgpFlexConditionsWellKnown 5113 }
|
|
|
|
lgpCondId5114WaterLeakageDetectorSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The water leakage detector sensor is disconnected or the signal is
|
|
out of range."
|
|
::= { lgpFlexConditionsWellKnown 5114 }
|
|
|
|
lgpCondId5115BMSCommunicationsTimeout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Building Management System (or external monitoring system) has not
|
|
communicated with the system within the expected timeframe."
|
|
::= { lgpFlexConditionsWellKnown 5115 }
|
|
|
|
lgpCondId5116MaintenanceDue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The calculated maintenance date has been reached."
|
|
::= { lgpFlexConditionsWellKnown 5116 }
|
|
|
|
lgpCondId5117MaintenanceCompleted OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maintenance has been completed on the unit."
|
|
::= { lgpFlexConditionsWellKnown 5117 }
|
|
|
|
lgpCondId5118CloggedAirFilter OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Air filter is dirty and needs to be (cleaned or) replaced."
|
|
::= { lgpFlexConditionsWellKnown 5118 }
|
|
|
|
lgpCondId5119RAMBatteryIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RAM or RAM backup battery is not operating correctly."
|
|
::= { lgpFlexConditionsWellKnown 5119 }
|
|
|
|
lgpCondId5120MasterUnitCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with master unit has been lost."
|
|
::= { lgpFlexConditionsWellKnown 5120 }
|
|
|
|
lgpCondId5121HighPowerShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply to high power components has been shutdown."
|
|
::= { lgpFlexConditionsWellKnown 5121 }
|
|
|
|
lgpCondId5126DigScrollComp2OverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Digital scroll compressor 2 shut off because its head temperature
|
|
has exceeded the upper threshold."
|
|
::= { lgpFlexConditionsWellKnown 5126 }
|
|
|
|
lgpCondId5144OutputOfUf OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output frequency has exceeded a specified range for a
|
|
specified period of time."
|
|
::= { lgpFlexConditionsWellKnown 5144 }
|
|
|
|
lgpCondId5145MMSModuleAlarmActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Active alarm or fault of any module in a multi-module system."
|
|
::= { lgpFlexConditionsWellKnown 5145 }
|
|
|
|
lgpCondId5146CompressorPumpDownIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unable to pump down suction-side pressure during compressor
|
|
shutdown."
|
|
::= { lgpFlexConditionsWellKnown 5146 }
|
|
|
|
lgpCondId5147ReturnAirSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The air sensor at the inlet of the unit is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5147 }
|
|
|
|
lgpCondId5148CompressorHighPressureTransducerIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor high pressure transducer is disconnected or the signal
|
|
is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5148 }
|
|
|
|
lgpCondId5149BatteryNotQualified OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS battery voltage is not qualified. This event will be
|
|
detected even in the absence of battery disconnect or when it is
|
|
open."
|
|
::= { lgpFlexConditionsWellKnown 5149 }
|
|
|
|
lgpCondId5150BatteryTerminalsReversed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured battery voltage is a negative value due to reverse
|
|
battery terminal connections."
|
|
::= { lgpFlexConditionsWellKnown 5150 }
|
|
|
|
lgpCondId5151BatteryConverterFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery converter failure. This is a summary event caused by one
|
|
or more power sub-modules in a UPS module."
|
|
::= { lgpFlexConditionsWellKnown 5151 }
|
|
|
|
lgpCondId5152InverterSCROpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an open across one or more inverter static
|
|
switch Silicon Controlled Rectifiers."
|
|
::= { lgpFlexConditionsWellKnown 5152 }
|
|
|
|
lgpCondId5153LoadSharingFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Difference between any phase inverter current of unit and the
|
|
relevant average output current of parallel system is more than a
|
|
specific percent of nominal current."
|
|
::= { lgpFlexConditionsWellKnown 5153 }
|
|
|
|
lgpCondId5154DCBusAbnormal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an abnormal DC Bus Voltage."
|
|
::= { lgpFlexConditionsWellKnown 5154 }
|
|
|
|
lgpCondId5155MainsInputNeutralLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loss of neutral in the input source is detected."
|
|
::= { lgpFlexConditionsWellKnown 5155 }
|
|
|
|
lgpCondId5156LoadImpactTransfer OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"On bypass as result of load impact."
|
|
::= { lgpFlexConditionsWellKnown 5156 }
|
|
|
|
lgpCondId5157UserOperationInvalid OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User attempted an invalid operation."
|
|
::= { lgpFlexConditionsWellKnown 5157 }
|
|
|
|
lgpCondId5158PowerSubModuleFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more failures detected in power module, inverter or
|
|
rectifier."
|
|
::= { lgpFlexConditionsWellKnown 5158 }
|
|
|
|
lgpCondId5178OutputOvervoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the output phase voltages has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5178 }
|
|
|
|
lgpCondId5179OutputUndervoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the output phase voltages has dropped below the
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5179 }
|
|
|
|
lgpCondId5180OutputOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the phase currents has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5180 }
|
|
|
|
lgpCondId5181NeutralOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system's neutral current has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5181 }
|
|
|
|
lgpCondId5182GroundOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System ground current has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5182 }
|
|
|
|
lgpCondId5183OutputVoltageTHD OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Total Harmonic Distortion of the voltage on one or more of the
|
|
output phases has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5183 }
|
|
|
|
lgpCondId5184OutputFrequencyError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output frequency is outside a specified range."
|
|
::= { lgpFlexConditionsWellKnown 5184 }
|
|
|
|
lgpCondId5185TransformerOvertemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates a unit transformer overtemperature condition."
|
|
::= { lgpFlexConditionsWellKnown 5185 }
|
|
|
|
lgpCondId5212PanelSummaryStatus OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status for the panel. Detects and annunciates upon occurrence
|
|
of any branch or panelboard main breaker active event."
|
|
::= { lgpFlexConditionsWellKnown 5212 }
|
|
|
|
lgpCondId5213PanelOvervoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the phase voltages of this panel has exceeded the
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5213 }
|
|
|
|
lgpCondId5214PanelUndervoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the phase voltages of this panel is less than the
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5214 }
|
|
|
|
lgpCondId5215PanelOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the phase currents of this panel has exceeded the
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5215 }
|
|
|
|
lgpCondId5216PanelNeutralOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Neutral current of this panel has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5216 }
|
|
|
|
lgpCondId5217PanelGroundOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Ground current of this panel has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5217 }
|
|
|
|
lgpCondId5226BranchOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current in one or more phases of this branch exceeds the limit."
|
|
::= { lgpFlexConditionsWellKnown 5226 }
|
|
|
|
lgpCondId5227BranchUndercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current in one or more phases of this branch is less than the
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5227 }
|
|
|
|
lgpCondId5245SubfeedPhaseOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the phase currents in this subfeed has exceeded the
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5245 }
|
|
|
|
lgpCondId5246SubfeedNeutralOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Neutral current in this subfeed has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5246 }
|
|
|
|
lgpCondId5247SubfeedGroundOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Ground current of this subfeed has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5247 }
|
|
|
|
lgpCondId5249EventState OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of this digital event input."
|
|
::= { lgpFlexConditionsWellKnown 5249 }
|
|
|
|
lgpCondId5263CompressorNotStopping OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor commanded to stop, but continues to run."
|
|
::= { lgpFlexConditionsWellKnown 5263 }
|
|
|
|
lgpCondId5269CompressorHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Compressor Hours] has exceeded [Compressor Hours Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5269 }
|
|
|
|
lgpCondId5270CompressorHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor is shut down due to high head pressure."
|
|
::= { lgpFlexConditionsWellKnown 5270 }
|
|
|
|
lgpCondId5271CompressorLowSuctionPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor is shut down due to low suction pressure."
|
|
::= { lgpFlexConditionsWellKnown 5271 }
|
|
|
|
lgpCondId5272CompressorThermalOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor is shut down due to thermal overload."
|
|
::= { lgpFlexConditionsWellKnown 5272 }
|
|
|
|
lgpCondId5273CompressorLowOilPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor low oil pressure."
|
|
::= { lgpFlexConditionsWellKnown 5273 }
|
|
|
|
lgpCondId5274CompressorHeadPressureOverThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor head pressure has exceeded an upper threshold."
|
|
::= { lgpFlexConditionsWellKnown 5274 }
|
|
|
|
lgpCondId5275CompressorLossofDifferentialPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor is shut down due to low differential pressure."
|
|
::= { lgpFlexConditionsWellKnown 5275 }
|
|
|
|
lgpCondId5277CondenserFanIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser fan is not operating within its operational parameters."
|
|
::= { lgpFlexConditionsWellKnown 5277 }
|
|
|
|
lgpCondId5278LowCondenserRefrigerantPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Refrigerant pressure in condenser coil is too low."
|
|
::= { lgpFlexConditionsWellKnown 5278 }
|
|
|
|
lgpCondId5280LowFluidPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Fluid Pressure] has dropped below a specified threshold."
|
|
::= { lgpFlexConditionsWellKnown 5280 }
|
|
|
|
lgpCondId5293ReturnFluidOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Return Fluid Temperature] has exceeded a specified threshold."
|
|
::= { lgpFlexConditionsWellKnown 5293 }
|
|
|
|
lgpCondId5294ReturnFluidUnderTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Return Fluid Temperature] has dropped below a specified threshold."
|
|
::= { lgpFlexConditionsWellKnown 5294 }
|
|
|
|
lgpCondId5295ReturnFluidTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The return fluid temperature sensor is disconnected or the signal
|
|
is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5295 }
|
|
|
|
lgpCondId5296TeamworkReturnFluidTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The return fluid temperature sensors for all Teamwork units are
|
|
disconnected or the signals are out of range."
|
|
::= { lgpFlexConditionsWellKnown 5296 }
|
|
|
|
lgpCondId5297AllPumpsLossofFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System is shut down due to loss of flow in all available pumps."
|
|
::= { lgpFlexConditionsWellKnown 5297 }
|
|
|
|
lgpCondId5300PumpHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Pump Hours] has exceeded [Pump Hours Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5300 }
|
|
|
|
lgpCondId5306FreeCoolingValveHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours
|
|
Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5306 }
|
|
|
|
lgpCondId5308EvaporatorInletTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The evaporator inlet temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5308 }
|
|
|
|
lgpCondId5309TeamworkEvaporatorInletTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The evaporator inlet temperature sensors for all Teamwork units
|
|
are disconnected or the signals are out of range."
|
|
::= { lgpFlexConditionsWellKnown 5309 }
|
|
|
|
lgpCondId5310EvaporatorFluidFreezeAutoReset OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Evaporator outlet fluid temperature has dropped below the freeze
|
|
threshold. Evaporator has been shut down, but will restart when
|
|
the temperature rises above the threshold."
|
|
::= { lgpFlexConditionsWellKnown 5310 }
|
|
|
|
lgpCondId5311EvaporatorFluidFreezeManualResetRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Evaporator outlet fluid temperature has dropped below the freeze
|
|
threshold. Evaporator has been shut down and requires a manual
|
|
reset."
|
|
::= { lgpFlexConditionsWellKnown 5311 }
|
|
|
|
lgpCondId5315SubgroupEventOccurredDuringCommunicationLoss OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"While subgroup unit communication was lost, an event occurred on
|
|
the subgroup unit. Please check subgroup unit event log."
|
|
::= { lgpFlexConditionsWellKnown 5315 }
|
|
|
|
lgpCondId5335ReturnAirUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Return Air Temperature] has dropped below [Low Return Air
|
|
Temperature Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5335 }
|
|
|
|
lgpCondId5349ExtAirSensorAHighHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High
|
|
Humidity Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5349 }
|
|
|
|
lgpCondId5351ExtAirSensorALowHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A
|
|
Low Humidity Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5351 }
|
|
|
|
lgpCondId5352CompressorShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor short cycle. A short cycle is defined as turning on and
|
|
off a number of times over a set time period."
|
|
::= { lgpFlexConditionsWellKnown 5352 }
|
|
|
|
lgpCondId5354DigScrollCompDischargeTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Digital scroll compressor discharge temperature sensor is
|
|
disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5354 }
|
|
|
|
lgpCondId5355DigScrollCompOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Digital scroll compressor is shut down due to head temperature
|
|
exceeding an upper threshold."
|
|
::= { lgpFlexConditionsWellKnown 5355 }
|
|
|
|
lgpCondId5361ExtFreeCoolingLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Free cooling is disabled by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5361 }
|
|
|
|
lgpCondId5362FreeCoolingTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The free cooling fluid temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5362 }
|
|
|
|
lgpCondId5365HotWaterHotGasValveHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot
|
|
Gas Valve Hours Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5365 }
|
|
|
|
lgpCondId5368ElectricReheaterHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Electric Reheater Hours] has exceeded [Electric Reheaters Hours
|
|
Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5368 }
|
|
|
|
lgpCondId5376MainFanOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Main fan is shut down due to thermal overload."
|
|
::= { lgpFlexConditionsWellKnown 5376 }
|
|
|
|
lgpCondId5377Condenser OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser is not operating within its operational parameters."
|
|
::= { lgpFlexConditionsWellKnown 5377 }
|
|
|
|
lgpCondId5415ExtLossofAirBlower OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loss of air blower is detected, as indicated by an external input
|
|
signal."
|
|
::= { lgpFlexConditionsWellKnown 5415 }
|
|
|
|
lgpCondId5416ExtStandbyUnitOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Standby unit is on, as indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5416 }
|
|
|
|
lgpCondId5417DigitalOutputBoardNotDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Digital output board is required to be connected, but no signal is
|
|
detected."
|
|
::= { lgpFlexConditionsWellKnown 5417 }
|
|
|
|
lgpCondId5418UnitCodeMissing OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit code has not been entered and saved."
|
|
::= { lgpFlexConditionsWellKnown 5418 }
|
|
|
|
lgpCondId5419UnitCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Master has lost communication with one or more networked units."
|
|
::= { lgpFlexConditionsWellKnown 5419 }
|
|
|
|
lgpCondId5422OvertemperaturePowerOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power turned off because equipment over temperature limit."
|
|
::= { lgpFlexConditionsWellKnown 5422 }
|
|
|
|
lgpCondId5423TooManySensors OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of sensors connected to the PDU exceeds the allowable
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5423 }
|
|
|
|
lgpCondId5432TransformerOvertemperaturePowerOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output power shutdown due to high transformer temperature."
|
|
::= { lgpFlexConditionsWellKnown 5432 }
|
|
|
|
lgpCondId5433TransformerOvertemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Transformer temperature has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5433 }
|
|
|
|
lgpCondId5434TransformerTemperatureSensorFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Transformer temperature sensor has failed."
|
|
::= { lgpFlexConditionsWellKnown 5434 }
|
|
|
|
lgpCondId5436LowAmbientTemperatureProbeTwo OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low ambient temperature condition on
|
|
temperature probe 2."
|
|
::= { lgpFlexConditionsWellKnown 5436 }
|
|
|
|
lgpCondId5437HighAmbientTemperatureProbeTwo OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high ambient temperature condition on
|
|
temperature probe 2."
|
|
::= { lgpFlexConditionsWellKnown 5437 }
|
|
|
|
lgpCondId5438ThermalRunawayDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a thermal runaway condition."
|
|
::= { lgpFlexConditionsWellKnown 5438 }
|
|
|
|
lgpCondId5439BatteryStringEqualize OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery string equalize condition."
|
|
::= { lgpFlexConditionsWellKnown 5439 }
|
|
|
|
lgpCondId5440BatteryStringOffline OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the battery string is offline."
|
|
::= { lgpFlexConditionsWellKnown 5440 }
|
|
|
|
lgpCondId5442DischargeLowCellVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low cell voltage condition during a
|
|
discharge."
|
|
::= { lgpFlexConditionsWellKnown 5442 }
|
|
|
|
lgpCondId5447MMSPowerSharing OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A module is not sharing power with the other modules in a multi
|
|
-module system."
|
|
::= { lgpFlexConditionsWellKnown 5447 }
|
|
|
|
lgpCondId5453ModuleInStandbyIntelligentParalleling OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Module is placed into standby operation per Intelligent
|
|
Paralleling."
|
|
::= { lgpFlexConditionsWellKnown 5453 }
|
|
|
|
lgpCondId5456ECOModeActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Conditions for Activation or Automatic Reactivation have been
|
|
satisfied."
|
|
::= { lgpFlexConditionsWellKnown 5456 }
|
|
|
|
lgpCondId5457ECOModeSuspended OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ECO Mode session is suspended."
|
|
::= { lgpFlexConditionsWellKnown 5457 }
|
|
|
|
lgpCondId5458ExcessECOSuspends OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of automatic suspensions has exceeded the ECO Mode -
|
|
Maximum Auto Suspensions setting."
|
|
::= { lgpFlexConditionsWellKnown 5458 }
|
|
|
|
lgpCondId5471DoorOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An open door was detected."
|
|
::= { lgpFlexConditionsWellKnown 5471 }
|
|
|
|
lgpCondId5472DoorSensorDisconnected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Door sensor disconnect detected."
|
|
::= { lgpFlexConditionsWellKnown 5472 }
|
|
|
|
lgpCondId5479ContactClosureOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An open circuit was detected."
|
|
::= { lgpFlexConditionsWellKnown 5479 }
|
|
|
|
lgpCondId5480ContactClosureClosed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A closed circuit was detected."
|
|
::= { lgpFlexConditionsWellKnown 5480 }
|
|
|
|
lgpCondId5492ExtSystemCondensationDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External system condensation detected."
|
|
::= { lgpFlexConditionsWellKnown 5492 }
|
|
|
|
lgpCondId5495ExtFanIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more fans are not operating within their operational
|
|
parameters."
|
|
::= { lgpFlexConditionsWellKnown 5495 }
|
|
|
|
lgpCondId5500ExtRemoteShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit is shut down by a remote signal."
|
|
::= { lgpFlexConditionsWellKnown 5500 }
|
|
|
|
lgpCondId5505HotAisleTempOutofRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The air temperature in the Hot aisle is either above [Hot Aisle
|
|
Over Temp Threshold] or below [Hot Aisle Under Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5505 }
|
|
|
|
lgpCondId5508ColdAisleTempOutofRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The air temperature in the cold aisle is either above [Cold Aisle
|
|
Over Temp Threshold] or below [Cold Aisle Under Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5508 }
|
|
|
|
lgpCondId5512RemoteShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit is shut down by a remote signal."
|
|
::= { lgpFlexConditionsWellKnown 5512 }
|
|
|
|
lgpCondId5513CompressorCapacityReduced OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor capacity has been reduced."
|
|
::= { lgpFlexConditionsWellKnown 5513 }
|
|
|
|
lgpCondId5514CompressorLowPressureTransducerIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor low pressure transducer is disconnected or the signal
|
|
is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5514 }
|
|
|
|
lgpCondId5524PDUNeutralOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a neutral over current condition."
|
|
::= { lgpFlexConditionsWellKnown 5524 }
|
|
|
|
lgpCondId5531CondenserCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with condenser unit has been lost."
|
|
::= { lgpFlexConditionsWellKnown 5531 }
|
|
|
|
lgpCondId5535CondenserOutsideAirTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser outside air temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5535 }
|
|
|
|
lgpCondId5536CondenserOutsideAirTempOutofOperatingRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Condenser Outside Air Temperature] is either above an upper
|
|
threshold or below a lower threshold."
|
|
::= { lgpFlexConditionsWellKnown 5536 }
|
|
|
|
lgpCondId5537CondenserControlBoardIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser control board is reporting an issue."
|
|
::= { lgpFlexConditionsWellKnown 5537 }
|
|
|
|
lgpCondId5539CondenserRefrigerantPressureOverThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser refrigerant pressure has exceeded a threshold."
|
|
::= { lgpFlexConditionsWellKnown 5539 }
|
|
|
|
lgpCondId5540CondenserRefrigerantPressureUnderThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser refrigerant pressure has dropped below a threshold."
|
|
::= { lgpFlexConditionsWellKnown 5540 }
|
|
|
|
lgpCondId5541CondenserRefrigerantPressureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser refrigerant pressure sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5541 }
|
|
|
|
lgpCondId5542CondenserSupplyRefrigerantOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser supply refrigerant temperature has exceeded a threshold."
|
|
::= { lgpFlexConditionsWellKnown 5542 }
|
|
|
|
lgpCondId5543CondenserSupplyRefrigerantUnderTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser supply refrigerant temperature has dropped below a
|
|
specified threshold."
|
|
::= { lgpFlexConditionsWellKnown 5543 }
|
|
|
|
lgpCondId5544CondenserSupplyRefrigerantTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser supply refrigerant temperature sensor is disconnected or
|
|
the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5544 }
|
|
|
|
lgpCondId5545CondenserMaxFanSpeedOverride OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fan speed exceeding the maximum set point in order to alleviate a
|
|
high temperature or pressure condition."
|
|
::= { lgpFlexConditionsWellKnown 5545 }
|
|
|
|
lgpCondId5559EvaporatorReturnFluidOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Evaporator Return Fluid Temperature] has exceeded a threshold.
|
|
The event is deactivated when the temperature drops below the
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 5559 }
|
|
|
|
lgpCondId5560EvaporatorReturnFluidUnderTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Evaporator Return Fluid Temperature] has dropped below a
|
|
threshold. The event is deactivated when the temperature rises
|
|
above the threshold."
|
|
::= { lgpFlexConditionsWellKnown 5560 }
|
|
|
|
lgpCondId5561LBSActiveMaster OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This UPS system has been selected as the functional Master Load
|
|
Bus Synchronization (LBS) system."
|
|
::= { lgpFlexConditionsWellKnown 5561 }
|
|
|
|
lgpCondId5562LBSActiveSlave OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This UPS system is synchronized to the output bus of the UPS
|
|
system that has been selected as the Master Load Bus
|
|
Synchronization (LBS) system."
|
|
::= { lgpFlexConditionsWellKnown 5562 }
|
|
|
|
lgpCondId5563DCBusLowFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The DC Bus voltage has reached a critical low level."
|
|
::= { lgpFlexConditionsWellKnown 5563 }
|
|
|
|
lgpCondId5564FanContactorOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The fan contactor is open."
|
|
::= { lgpFlexConditionsWellKnown 5564 }
|
|
|
|
lgpCondId5565FanContactorOpenFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The fan contactor failed to open."
|
|
::= { lgpFlexConditionsWellKnown 5565 }
|
|
|
|
lgpCondId5566FanContactorCloseFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The fan contactor failed to close."
|
|
::= { lgpFlexConditionsWellKnown 5566 }
|
|
|
|
lgpCondId5567IPInhibit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The intelligent paralleling operation is inhibited."
|
|
::= { lgpFlexConditionsWellKnown 5567 }
|
|
|
|
lgpCondId5568InputUndervoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the input phase voltages has dropped below the
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5568 }
|
|
|
|
lgpCondId5569InputOvervoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the input phase voltages has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5569 }
|
|
|
|
lgpCondId5573AmbientAirSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ambient air sensor is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5573 }
|
|
|
|
lgpCondId5577ExtDewPointUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"At least one dew point temperature reading ([Ext Air Sensor A Dew
|
|
Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped
|
|
below [Ext Dew Point Under Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5577 }
|
|
|
|
lgpCondId5578DewPointOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Dew point temperature reading has exceeded the upper threshold."
|
|
::= { lgpFlexConditionsWellKnown 5578 }
|
|
|
|
lgpCondId5579DewPointUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Dew point temperature reading has dropped below the lower
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 5579 }
|
|
|
|
lgpCondId5588UnspecifiedGeneralEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more unspecified events active. See local unit display for
|
|
further details."
|
|
::= { lgpFlexConditionsWellKnown 5588 }
|
|
|
|
lgpCondId5593RemoteSensorAverageOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Remote Sensor Average Temperature] has exceeded [Remote Sensor
|
|
Over Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5593 }
|
|
|
|
lgpCondId5594RemoteSensorAverageUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Remote Sensor Average Temperature] has dropped below [Remote
|
|
Sensor Under Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5594 }
|
|
|
|
lgpCondId5595RemoteSensorSystemAverageOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Remote Sensor System Average Temperature] has exceeded [Remote
|
|
Sensor Over Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5595 }
|
|
|
|
lgpCondId5596RemoteSensorSystemAverageUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Remote Sensor System Average Temperature] has dropped below
|
|
[Remote Sensor Under Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5596 }
|
|
|
|
lgpCondId5597RemoteSensorOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp
|
|
Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5597 }
|
|
|
|
lgpCondId5598RemoteSensorUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Remote Sensor Temperature] has dropped below [Remote Sensor Under
|
|
Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5598 }
|
|
|
|
lgpCondId5600AirEconomizerEmergencyOverride OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indoor room temperature has exceeded its upper threshold and the
|
|
outdoor air damper has been opened for emergency cooling."
|
|
::= { lgpFlexConditionsWellKnown 5600 }
|
|
|
|
lgpCondId5601AirEconomizerReducedAirflow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Air economizer filter is dirty and needs to be cleaned or replaced."
|
|
::= { lgpFlexConditionsWellKnown 5601 }
|
|
|
|
lgpCondId5604CompressorSuperheatOverThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor discharge refrigerant superheat temperature has
|
|
exceeded an upper threshold."
|
|
::= { lgpFlexConditionsWellKnown 5604 }
|
|
|
|
lgpCondId5609ThermalRunawayCelltoAmbientTemperatureEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delta temperature between a cell temperature and the ambient
|
|
temperature has exceeded the thermal runaway cell to ambient
|
|
temperature threshold."
|
|
::= { lgpFlexConditionsWellKnown 5609 }
|
|
|
|
lgpCondId5610ThermalRunawayCelltoCellTemperatureEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delta temperature between two cells has exceeded the thermal
|
|
runaway cell to cell temperature threshold."
|
|
::= { lgpFlexConditionsWellKnown 5610 }
|
|
|
|
lgpCondId5611ThermalRunawayChargerCurrentLevelOneEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Battery-String charger current has exceeded the thermal
|
|
runaway charger current level one threshold."
|
|
::= { lgpFlexConditionsWellKnown 5611 }
|
|
|
|
lgpCondId5612ThermalRunawayChargerCurrentLevelTwoEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Battery-String charger current has exceeded the thermal
|
|
runaway charger current level two threshold."
|
|
::= { lgpFlexConditionsWellKnown 5612 }
|
|
|
|
lgpCondId5617TemperatureControlSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The air sensor selected for cooling control is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5617 }
|
|
|
|
lgpCondId5621EEVSuperheatBelowThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic expansion valve refrigerant low superheat event."
|
|
::= { lgpFlexConditionsWellKnown 5621 }
|
|
|
|
lgpCondId5622EEVDischargeTempAboveThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic expansion valve refrigerant high discharge temperature
|
|
event."
|
|
::= { lgpFlexConditionsWellKnown 5622 }
|
|
|
|
lgpCondId5623EEVBatteryIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic expansion valve battery cannot be recharged and needs
|
|
to be replaced."
|
|
::= { lgpFlexConditionsWellKnown 5623 }
|
|
|
|
lgpCondId5624EEVPowerIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic expansion valve lost power and is running on battery
|
|
backup."
|
|
::= { lgpFlexConditionsWellKnown 5624 }
|
|
|
|
lgpCondId5625EEVUnspecifiedGeneralEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more unspecified electronic expansion valve events active.
|
|
See local unit display for further details."
|
|
::= { lgpFlexConditionsWellKnown 5625 }
|
|
|
|
lgpCondId5629StaticPressureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The static pressure sensor is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 5629 }
|
|
|
|
lgpCondId5630HighStaticPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High static pressure event."
|
|
::= { lgpFlexConditionsWellKnown 5630 }
|
|
|
|
lgpCondId5631LowStaticPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Low static pressure event."
|
|
::= { lgpFlexConditionsWellKnown 5631 }
|
|
|
|
lgpCondId5636PumpUnspecifiedGeneralEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more unspecified pump events active. See local unit display
|
|
for further details."
|
|
::= { lgpFlexConditionsWellKnown 5636 }
|
|
|
|
lgpCondId5637CondenserUnitUnspecifiedGeneralEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more unspecified condenser unit events active. See local
|
|
unit display for further details."
|
|
::= { lgpFlexConditionsWellKnown 5637 }
|
|
|
|
lgpCondId5638CondenserCircuitUnspecifiedGeneralEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more unspecified condenser circuit events active. See local
|
|
unit display for further details."
|
|
::= { lgpFlexConditionsWellKnown 5638 }
|
|
|
|
lgpCondId5642SFAReservedEvent1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5642 }
|
|
|
|
lgpCondId5643SFAReservedEvent2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5643 }
|
|
|
|
lgpCondId5644SFAReservedEvent3 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5644 }
|
|
|
|
lgpCondId5645SFAReservedEvent4 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5645 }
|
|
|
|
lgpCondId5646SFAReservedEvent5 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5646 }
|
|
|
|
lgpCondId5647SFAReservedEvent6 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5647 }
|
|
|
|
lgpCondId5648SFAReservedEvent7 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5648 }
|
|
|
|
lgpCondId5649SFAReservedEvent8 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5649 }
|
|
|
|
lgpCondId5650SFAReservedEvent9 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5650 }
|
|
|
|
lgpCondId5651SFAReservedEvent10 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5651 }
|
|
|
|
lgpCondId5652SFAReservedEvent11 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5652 }
|
|
|
|
lgpCondId5653SFAReservedEvent12 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5653 }
|
|
|
|
lgpCondId5654SFAReservedEvent13 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5654 }
|
|
|
|
lgpCondId5655SFAReservedEvent14 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5655 }
|
|
|
|
lgpCondId5656SFAReservedEvent15 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5656 }
|
|
|
|
lgpCondId5657SFAReservedEvent16 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5657 }
|
|
|
|
lgpCondId5658SFAReservedEvent17 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5658 }
|
|
|
|
lgpCondId5659SFAReservedEvent18 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5659 }
|
|
|
|
lgpCondId5660SFAReservedEvent19 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5660 }
|
|
|
|
lgpCondId5661SFAReservedEvent20 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5661 }
|
|
|
|
lgpCondId5662SFAReservedEvent21 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5662 }
|
|
|
|
lgpCondId5663SFAReservedEvent22 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5663 }
|
|
|
|
lgpCondId5664SFAReservedEvent23 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5664 }
|
|
|
|
lgpCondId5665SFAReservedEvent24 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5665 }
|
|
|
|
lgpCondId5666SFAReservedEvent25 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5666 }
|
|
|
|
lgpCondId5768OutletAirOvertemperatureLimit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The difference between the outlet air temperature and inlet air
|
|
temperature exceeds a specified maximum temperature."
|
|
::= { lgpFlexConditionsWellKnown 5768 }
|
|
|
|
lgpCondId5769EMOShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An Emergency Module Off command has been detected."
|
|
::= { lgpFlexConditionsWellKnown 5769 }
|
|
|
|
lgpCondId5770TopOutletFanFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Top outlet fan fault - one or more top outlet fans have failed."
|
|
::= { lgpFlexConditionsWellKnown 5770 }
|
|
|
|
lgpCondId5771MMSOverCapacity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The multi-module system load is larger than the apparent power
|
|
limit setting."
|
|
::= { lgpFlexConditionsWellKnown 5771 }
|
|
|
|
lgpCondId5773CompressorCapacityNormal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor has returned to normal load capacity."
|
|
::= { lgpFlexConditionsWellKnown 5773 }
|
|
|
|
lgpCondId5774CompressorContactorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor contactor is not closing during compressor startup or
|
|
is not opening during compressor shutdown."
|
|
::= { lgpFlexConditionsWellKnown 5774 }
|
|
|
|
lgpCondId5775UnitShutdownUnspecifiedGeneralEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more unspecified unit shutdown events active. See local
|
|
unit display for further details."
|
|
::= { lgpFlexConditionsWellKnown 5775 }
|
|
|
|
lgpCondId5776PDULowVoltageLN OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under voltage condition (LN)."
|
|
::= { lgpFlexConditionsWellKnown 5776 }
|
|
|
|
lgpCondId5777PDULowVoltageLL OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under voltage condition (LL)."
|
|
::= { lgpFlexConditionsWellKnown 5777 }
|
|
|
|
lgpCondId5778PDULowVoltageL1L2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a line-to-line under voltage condition (L1
|
|
-L2)."
|
|
::= { lgpFlexConditionsWellKnown 5778 }
|
|
|
|
lgpCondId5779PDULowVoltageL2L3 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a line-to-line under voltage condition (L2
|
|
-L3)."
|
|
::= { lgpFlexConditionsWellKnown 5779 }
|
|
|
|
lgpCondId5780PDULowVoltageL3L1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a line-to-line under voltage condition (L3
|
|
-L1)."
|
|
::= { lgpFlexConditionsWellKnown 5780 }
|
|
|
|
lgpCondId5781PDULowVoltageL1N OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a line to neutral under voltage condition
|
|
(L1-N)."
|
|
::= { lgpFlexConditionsWellKnown 5781 }
|
|
|
|
lgpCondId5782PDULowVoltageL2N OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a line to neutral under voltage condition
|
|
(L2-N)."
|
|
::= { lgpFlexConditionsWellKnown 5782 }
|
|
|
|
lgpCondId5783PDULowVoltageL3N OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a line to neutral under voltage condition
|
|
(L3-N)."
|
|
::= { lgpFlexConditionsWellKnown 5783 }
|
|
|
|
lgpCondId5784BranchLowVoltageLN OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under voltage condition (LN)."
|
|
::= { lgpFlexConditionsWellKnown 5784 }
|
|
|
|
lgpCondId5785BranchLowVoltageLL OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under voltage condition (LL)."
|
|
::= { lgpFlexConditionsWellKnown 5785 }
|
|
|
|
lgpCondId5786BranchLowVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under voltage condition."
|
|
::= { lgpFlexConditionsWellKnown 5786 }
|
|
|
|
lgpCondId5788ContTieActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Continuous Power Tie Active."
|
|
::= { lgpFlexConditionsWellKnown 5788 }
|
|
|
|
lgpCondId5792UserkWhReset OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user kWh accumulator was reset to zero by the operator."
|
|
::= { lgpFlexConditionsWellKnown 5792 }
|
|
|
|
lgpCondId5796PeakkWReset OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Peak kW was reset."
|
|
::= { lgpFlexConditionsWellKnown 5796 }
|
|
|
|
lgpCondId5798BypassOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass overloaded, reduce load immediately."
|
|
::= { lgpFlexConditionsWellKnown 5798 }
|
|
|
|
lgpCondId5801LowBatteryShutdownImminent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"If active and guaranteed shutdown is enabled, a low battery
|
|
reserve condition exists that will shutdown the UPS."
|
|
::= { lgpFlexConditionsWellKnown 5801 }
|
|
|
|
lgpCondId5806OutputOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An overload exists on the output."
|
|
::= { lgpFlexConditionsWellKnown 5806 }
|
|
|
|
lgpCondId5807OutputOffPending OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output off pending - shutdown imminent."
|
|
::= { lgpFlexConditionsWellKnown 5807 }
|
|
|
|
lgpCondId5808SystemShutdownOutputShort OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shutdown was due to a short on the output."
|
|
::= { lgpFlexConditionsWellKnown 5808 }
|
|
|
|
lgpCondId5809SystemShutdownLowBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shutdown was due to a low battery condition."
|
|
::= { lgpFlexConditionsWellKnown 5809 }
|
|
|
|
lgpCondId5810SystemShutdownRemoteShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shutdown was due to a remote communications shutdown command."
|
|
::= { lgpFlexConditionsWellKnown 5810 }
|
|
|
|
lgpCondId5811SystemShutdownHardwareFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shutdown was due to an externally applied hardware control signal."
|
|
::= { lgpFlexConditionsWellKnown 5811 }
|
|
|
|
lgpCondId5817LossofRedundancy OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has an insufficient number of power modules to provide
|
|
redundancy."
|
|
::= { lgpFlexConditionsWellKnown 5817 }
|
|
|
|
lgpCondId5818PowerModuleFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more conditions indicate a power module failure, service is
|
|
required."
|
|
::= { lgpFlexConditionsWellKnown 5818 }
|
|
|
|
lgpCondId5819PowerModuleWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more power modules is reporting a warning condition."
|
|
::= { lgpFlexConditionsWellKnown 5819 }
|
|
|
|
lgpCondId5838PowerModuleFanFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Power Module has detected a fan fault."
|
|
::= { lgpFlexConditionsWellKnown 5838 }
|
|
|
|
lgpCondId5839PowerModuleOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Power Module has detected an over temperature condition."
|
|
::= { lgpFlexConditionsWellKnown 5839 }
|
|
|
|
lgpCondId5840PowerModuleShutdownOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power Module has shutdown due to over temperature."
|
|
::= { lgpFlexConditionsWellKnown 5840 }
|
|
|
|
lgpCondId5842ChargerModuleFanFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Charger Module has detected a fan fault."
|
|
::= { lgpFlexConditionsWellKnown 5842 }
|
|
|
|
lgpCondId5847BatteryModuleTemperatureSensorFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Battery Module temperature sensor fault has been detected."
|
|
::= { lgpFlexConditionsWellKnown 5847 }
|
|
|
|
lgpCondId5848BatteryModuleOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Battery Module has detected an over temperature condition."
|
|
::= { lgpFlexConditionsWellKnown 5848 }
|
|
|
|
lgpCondId5849ReplaceBatteryModule OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Battery Module needs to be replaced."
|
|
::= { lgpFlexConditionsWellKnown 5849 }
|
|
|
|
lgpCondId5850SystemShutdownTransformerOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System shutdown due to transformer over temperature."
|
|
::= { lgpFlexConditionsWellKnown 5850 }
|
|
|
|
lgpCondId5851MaximumLoadAlarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum load alarm indicating load setting has been exceeded."
|
|
::= { lgpFlexConditionsWellKnown 5851 }
|
|
|
|
lgpCondId5856BatteryModuleFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more battery modules are reporting a fault condition."
|
|
::= { lgpFlexConditionsWellKnown 5856 }
|
|
|
|
lgpCondId5857BatteryModuleWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more battery modules are reporting a warning condition."
|
|
::= { lgpFlexConditionsWellKnown 5857 }
|
|
|
|
lgpCondId5862CheckAirFilter OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Please check air filter, it may need to be cleaned or replaced."
|
|
::= { lgpFlexConditionsWellKnown 5862 }
|
|
|
|
lgpCondId5863TransformerFanFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The transformer fan has failed."
|
|
::= { lgpFlexConditionsWellKnown 5863 }
|
|
|
|
lgpCondId5865NoLoadWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the UPS has output voltage but the output current is
|
|
below a set threshold [No Load Warning Current Threshold] for a
|
|
set period of time [No Load Warning Delay]."
|
|
::= { lgpFlexConditionsWellKnown 5865 }
|
|
|
|
lgpCondId5871BatteryOverTemperatureLimit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A battery temperature sensor is reporting a value above a
|
|
predetermined limit."
|
|
::= { lgpFlexConditionsWellKnown 5871 }
|
|
|
|
lgpCondId5873UnexpectedMainBatteryDisconnectClosure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The main battery disconnect has closed unexpectedly."
|
|
::= { lgpFlexConditionsWellKnown 5873 }
|
|
|
|
lgpCondId5874BatteryOverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that the battery voltage has exceeded a
|
|
predetermined limit."
|
|
::= { lgpFlexConditionsWellKnown 5874 }
|
|
|
|
lgpCondId5875BatteryFuseFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more battery fuse faults has occurred."
|
|
::= { lgpFlexConditionsWellKnown 5875 }
|
|
|
|
lgpCondId5878MainBatteryDisconnectForcedToUnlock OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The main battery disconnect is forced to the unlocked state."
|
|
::= { lgpFlexConditionsWellKnown 5878 }
|
|
|
|
lgpCondId5879VdcBackfeed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The voltage between battery and DC bus measurements is out of
|
|
tolerance."
|
|
::= { lgpFlexConditionsWellKnown 5879 }
|
|
|
|
lgpCondId5880RectifierConfigurationChangeRequest OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This event indicates that the battery is not configured and PFC is
|
|
not enabled."
|
|
::= { lgpFlexConditionsWellKnown 5880 }
|
|
|
|
lgpCondId5881RegenerationActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Regeneration operation is active."
|
|
::= { lgpFlexConditionsWellKnown 5881 }
|
|
|
|
lgpCondId5882RegenerationOperationTerminated OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Regeneration operation is not active."
|
|
::= { lgpFlexConditionsWellKnown 5882 }
|
|
|
|
lgpCondId5883RegenerationOperationFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Regeneration operation has been terminated due to bypass source
|
|
instability or unit misoperation."
|
|
::= { lgpFlexConditionsWellKnown 5883 }
|
|
|
|
lgpCondId5884ProgramInputContact01 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 01] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5884 }
|
|
|
|
lgpCondId5885ProgramInputContact02 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 02] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5885 }
|
|
|
|
lgpCondId5886ProgramInputContact03 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 03] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5886 }
|
|
|
|
lgpCondId5887ProgramInputContact04 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 04] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5887 }
|
|
|
|
lgpCondId5888ProgramInputContact05 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 05] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5888 }
|
|
|
|
lgpCondId5889ProgramInputContact06 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 06] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5889 }
|
|
|
|
lgpCondId5890ProgramInputContact07 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 07] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5890 }
|
|
|
|
lgpCondId5891ProgramInputContact08 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 08] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5891 }
|
|
|
|
lgpCondId5892ProgramInputContact09 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 09] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5892 }
|
|
|
|
lgpCondId5893ProgramInputContact10 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 10] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5893 }
|
|
|
|
lgpCondId5894ProgramInputContact11 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 11] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5894 }
|
|
|
|
lgpCondId5895ProgramInputContact12 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 12] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5895 }
|
|
|
|
lgpCondId5896GroundFaultDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a ground fault on a Battery-String."
|
|
::= { lgpFlexConditionsWellKnown 5896 }
|
|
|
|
lgpCondId5902ReturnHumiditySensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidity sensor at the inlet of the unit is disconnected or
|
|
the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5902 }
|
|
|
|
lgpCondId5903CompressorLowDifferentialPressureLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor exceeded maximum startup attempts due to low
|
|
differential pressure. Compressor is shutdown and has been
|
|
disabled."
|
|
::= { lgpFlexConditionsWellKnown 5903 }
|
|
|
|
lgpCondId5906AirflowSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Airflow sensor is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5906 }
|
|
|
|
lgpCondId5907ExtAirDamperPositionIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Air damper position does not match expected value, as indicated by
|
|
an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5907 }
|
|
|
|
lgpCondId5908ExtPowerSourceAFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit main power source A failure, as indicated by an external
|
|
input signal."
|
|
::= { lgpFlexConditionsWellKnown 5908 }
|
|
|
|
lgpCondId5909ExtPowerSourceBFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit main power source B failure, as indicated by an external
|
|
input signal."
|
|
::= { lgpFlexConditionsWellKnown 5909 }
|
|
|
|
lgpCondId5910StaticPressureSensorOutofRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Static pressure sensor signal is out of its configured range."
|
|
::= { lgpFlexConditionsWellKnown 5910 }
|
|
|
|
lgpCondId5911FluidTemperatureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The fluid temperature sensor is disconnected or the signal is out
|
|
of range."
|
|
::= { lgpFlexConditionsWellKnown 5911 }
|
|
|
|
lgpCondId5912FluidFlowSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The fluid flow sensor is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 5912 }
|
|
|
|
lgpCondId5914OverDifferentialPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An over differential pressure condition was detected."
|
|
::= { lgpFlexConditionsWellKnown 5914 }
|
|
|
|
lgpCondId5915UnderDifferentialPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An under differential pressure condition was detected."
|
|
::= { lgpFlexConditionsWellKnown 5915 }
|
|
|
|
lgpCondId5924MixedModeLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Mixed mode has been entered too many times over a rolling time
|
|
period and has been temporarily disabled. Mixed mode is defined
|
|
as the use of a compressor on one refrigeration circuit and the
|
|
use of a refrigerant pump on the other circuit."
|
|
::= { lgpFlexConditionsWellKnown 5924 }
|
|
|
|
lgpCondId5928UnbalancedLoadCondition OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a line-to-line unbalanced load condition."
|
|
::= { lgpFlexConditionsWellKnown 5928 }
|
|
|
|
lgpCondId5939BranchOverCurrentProtection OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Branch Receptacle Module's over current protection is
|
|
triggered."
|
|
::= { lgpFlexConditionsWellKnown 5939 }
|
|
|
|
lgpCondId5948BranchLowVoltageLL OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under voltage condition (LL)."
|
|
::= { lgpFlexConditionsWellKnown 5948 }
|
|
|
|
lgpCondId5957BypassInputVoltageFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the bypass voltage is unqualified."
|
|
::= { lgpFlexConditionsWellKnown 5957 }
|
|
|
|
lgpCondId5958BatteryTemperatureOutofRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery temperature is outside of acceptable range."
|
|
::= { lgpFlexConditionsWellKnown 5958 }
|
|
|
|
lgpCondId5960InverterOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter in overload fault."
|
|
::= { lgpFlexConditionsWellKnown 5960 }
|
|
|
|
lgpCondId5966AuxAirTempDeviceCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with external auxiliary device providing an air
|
|
temperature value has been lost."
|
|
::= { lgpFlexConditionsWellKnown 5966 }
|
|
|
|
lgpCondId5967ModbusPowerMeterCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with Modbus power meter has been lost."
|
|
::= { lgpFlexConditionsWellKnown 5967 }
|
|
|
|
lgpCondId5968InverterDesaturation OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter Desaturation."
|
|
::= { lgpFlexConditionsWellKnown 5968 }
|
|
|
|
lgpCondId5969GenericDICFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The control board reports a fault - Service required."
|
|
::= { lgpFlexConditionsWellKnown 5969 }
|
|
|
|
lgpCondId5970GroundFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An AC phase to ground fault or three phase fault to ground exists
|
|
on the output of the UPS."
|
|
::= { lgpFlexConditionsWellKnown 5970 }
|
|
|
|
lgpCondId5973InputBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The main input breaker is open."
|
|
::= { lgpFlexConditionsWellKnown 5973 }
|
|
|
|
lgpCondId5974NeutralBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The neutral breaker is open."
|
|
::= { lgpFlexConditionsWellKnown 5974 }
|
|
|
|
lgpCondId5975OutputBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output breaker is open."
|
|
::= { lgpFlexConditionsWellKnown 5975 }
|
|
|
|
lgpCondId5976MaintenanceBypassBreakerClosed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maintenance bypass breaker is closed."
|
|
::= { lgpFlexConditionsWellKnown 5976 }
|
|
|
|
lgpCondId5977BatteryBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery circuit is open."
|
|
::= { lgpFlexConditionsWellKnown 5977 }
|
|
|
|
lgpCondId5978RectifierIsolationBreakerRFBOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The rectifier isolation breaker (RFB) indicates that it is in the
|
|
open position."
|
|
::= { lgpFlexConditionsWellKnown 5978 }
|
|
|
|
lgpCondId5982BypassBreakerSBBOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bypass circuit breaker (SBB) indicates that it is in the open
|
|
position."
|
|
::= { lgpFlexConditionsWellKnown 5982 }
|
|
|
|
lgpCondId5983BypassIsolationBreakerBIBOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bypass isolation breaker (BIB) indicates that it is in the
|
|
open position."
|
|
::= { lgpFlexConditionsWellKnown 5983 }
|
|
|
|
lgpCondId5984BypassUndervoltageWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The voltage on one or more bypass phases is less than a specified
|
|
percentage of the nominal voltage."
|
|
::= { lgpFlexConditionsWellKnown 5984 }
|
|
|
|
lgpCondId5985BypassStaticSwitchBPSSOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Bypass Static Switch has been turned on."
|
|
::= { lgpFlexConditionsWellKnown 5985 }
|
|
|
|
lgpCondId5998BattOvtempWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A battery temperature sensor is reporting a value above the
|
|
setpoint."
|
|
::= { lgpFlexConditionsWellKnown 5998 }
|
|
|
|
lgpCondId6009InverterOutputBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter output breaker indicates that it is in the open
|
|
position."
|
|
::= { lgpFlexConditionsWellKnown 6009 }
|
|
|
|
lgpCondId6011EquipmentOverTempWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Equipment over temperature warning is a summary event based on the
|
|
detection of at least one measured temperature exceeding a
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 6011 }
|
|
|
|
lgpCondId6012EquipmentOvertemperatureLimit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The equipment air temperature has exceeded its maximum set point."
|
|
::= { lgpFlexConditionsWellKnown 6012 }
|
|
|
|
lgpCondId6045RectifierInputBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The rectifier isolation breaker indicates that it is in the open
|
|
position."
|
|
::= { lgpFlexConditionsWellKnown 6045 }
|
|
|
|
lgpCondId6046LoadonUPS OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output is being supplied power from the inverter."
|
|
::= { lgpFlexConditionsWellKnown 6046 }
|
|
|
|
lgpCondId6047Core2CoreFuseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Core-2-core fuse failure."
|
|
::= { lgpFlexConditionsWellKnown 6047 }
|
|
|
|
lgpCondId6052SystemOutputBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system output breaker is open."
|
|
::= { lgpFlexConditionsWellKnown 6052 }
|
|
|
|
lgpCondId6059InverterRelayFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter relay has malfunctioned."
|
|
::= { lgpFlexConditionsWellKnown 6059 }
|
|
|
|
lgpCondId6060TransfertoBypassSystemOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS System has transferred to bypass because the active power
|
|
modules cannot support the critical load."
|
|
::= { lgpFlexConditionsWellKnown 6060 }
|
|
|
|
lgpCondId6061InputSourceBackfeed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery is backfeeding the input source."
|
|
::= { lgpFlexConditionsWellKnown 6061 }
|
|
|
|
lgpCondId6062LossofSynchronization OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter and bypass are no longer synchronized. ."
|
|
::= { lgpFlexConditionsWellKnown 6062 }
|
|
|
|
lgpCondId6063BatteryConverterCurrentLimit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery converter has reached is maximum current limit. ."
|
|
::= { lgpFlexConditionsWellKnown 6063 }
|
|
|
|
lgpCondId6064LBSCableFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Load Bus Sync communications is abnormal. A problem with the LBS
|
|
cable may exist."
|
|
::= { lgpFlexConditionsWellKnown 6064 }
|
|
|
|
lgpCondId6065BatteryChargeEqualizationTimeout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery equalizing is time out."
|
|
::= { lgpFlexConditionsWellKnown 6065 }
|
|
|
|
lgpCondId6066ParallelCableFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS parallel system communications is abnormal. A problem with
|
|
the parallel cable may exist."
|
|
::= { lgpFlexConditionsWellKnown 6066 }
|
|
|
|
lgpCondId6067BatteryFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A short circuit exists in the battery system."
|
|
::= { lgpFlexConditionsWellKnown 6067 }
|
|
|
|
lgpCondId6068BatteryRoomAlarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ambient temperature of the battery room is abnormal."
|
|
::= { lgpFlexConditionsWellKnown 6068 }
|
|
|
|
lgpCondId6080UPSCCommunicationFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPSC has failed to communicate in a designated time period."
|
|
::= { lgpFlexConditionsWellKnown 6080 }
|
|
|
|
lgpCondId6092Compressor1BThermalOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fixed compressor 1B is shut down due to thermal overload."
|
|
::= { lgpFlexConditionsWellKnown 6092 }
|
|
|
|
lgpCondId6093Compressor2BThermalOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fixed compressor 2B is shut down due to thermal overload."
|
|
::= { lgpFlexConditionsWellKnown 6093 }
|
|
|
|
lgpCondId6094Compressor1BHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fixed compressor 1B run hours have exceeded the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6094 }
|
|
|
|
lgpCondId6095Compressor2BHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fixed compressor 2B run hours have exceeded the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6095 }
|
|
|
|
lgpCondId6100CondenserRemoteShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser is shut down by a remote signal."
|
|
::= { lgpFlexConditionsWellKnown 6100 }
|
|
|
|
lgpCondId6105ExternalCondenserTVSSIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser Transient Voltage Surge Suppressor or Surge
|
|
Protection Device has failed, as indicated by an external input
|
|
signal."
|
|
::= { lgpFlexConditionsWellKnown 6105 }
|
|
|
|
lgpCondId6106ExternalCondenserVFDIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser fan Variable Frequency Drive is offline, as
|
|
indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 6106 }
|
|
|
|
lgpCondId6107ExternalCondenserIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser is not operating within its operational parameters, as
|
|
indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 6107 }
|
|
|
|
lgpCondId6119Slotsnotavailable OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of sensors exceeds the number of allocated slots and
|
|
cannot be displayed."
|
|
::= { lgpFlexConditionsWellKnown 6119 }
|
|
|
|
lgpCondId6180BatteryUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery voltage is too low."
|
|
::= { lgpFlexConditionsWellKnown 6180 }
|
|
|
|
lgpCondId6182ReplaceBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery is due for replacement."
|
|
::= { lgpFlexConditionsWellKnown 6182 }
|
|
|
|
lgpCondId6186InputFrequencyDeviation OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input frequency is outside of the normal range."
|
|
::= { lgpFlexConditionsWellKnown 6186 }
|
|
|
|
lgpCondId6187ShutdownPending OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shutdown is pending."
|
|
::= { lgpFlexConditionsWellKnown 6187 }
|
|
|
|
lgpCondId6194SystemRebootCommandIssued OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reboot command issued to the system."
|
|
::= { lgpFlexConditionsWellKnown 6194 }
|
|
|
|
lgpCondId6203SensorAdded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor Added."
|
|
::= { lgpFlexConditionsWellKnown 6203 }
|
|
|
|
lgpCondId6204SensorRemoved OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor Removed."
|
|
::= { lgpFlexConditionsWellKnown 6204 }
|
|
|
|
lgpCondId6205WaterLeakDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water leak detected."
|
|
::= { lgpFlexConditionsWellKnown 6205 }
|
|
|
|
lgpCondId6210FirmwareUpdateInProgress OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Firmware update has started and is in progress."
|
|
::= { lgpFlexConditionsWellKnown 6210 }
|
|
|
|
lgpCondId6211FirmwareUpdateCompletedSuccessfully OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Firmware update has completed successfully."
|
|
::= { lgpFlexConditionsWellKnown 6211 }
|
|
|
|
lgpCondId6212FirmwareUpdateCompletedUnsuccessfully OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Firmware update has completed, but was not successful."
|
|
::= { lgpFlexConditionsWellKnown 6212 }
|
|
|
|
lgpCondId6216PrechargeCircuitFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"DC Bus precharge/discharge didn't reach specified level within a
|
|
specified time."
|
|
::= { lgpFlexConditionsWellKnown 6216 }
|
|
|
|
lgpCondId6217MemoryCardRemoved OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The memory card on the control board has been removed."
|
|
::= { lgpFlexConditionsWellKnown 6217 }
|
|
|
|
lgpCondId6218AutoCalibrationActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is automatically calibrating ADC channels."
|
|
::= { lgpFlexConditionsWellKnown 6218 }
|
|
|
|
lgpCondId6219AutoCalibrationFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ADC channel calibration has failed."
|
|
::= { lgpFlexConditionsWellKnown 6219 }
|
|
|
|
lgpCondId6220ModuleOutputBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The module output breaker is open."
|
|
::= { lgpFlexConditionsWellKnown 6220 }
|
|
|
|
lgpCondId6221NeutralVoltageFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage observed on neutral line."
|
|
::= { lgpFlexConditionsWellKnown 6221 }
|
|
|
|
lgpCondId6222BranchLoadLoss OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loss of load on branch detected. Branch circuit breaker might be
|
|
open."
|
|
::= { lgpFlexConditionsWellKnown 6222 }
|
|
|
|
lgpCondId6225RemoteSensorLowHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor humidity has dropped below a lower threshold. The
|
|
event is deactivated when the humidity rises above the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6225 }
|
|
|
|
lgpCondId6226RemoteSensorHighHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor humidity has exceeded an upper threshold. The event
|
|
is deactivated when the humidity drops below the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6226 }
|
|
|
|
lgpCondId6227RemoteSensorAverageLowHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The average humidity of multiple remote sensors on the cooling
|
|
unit has dropped below a lower threshold. The event is
|
|
deactivated when the humidity rises above the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6227 }
|
|
|
|
lgpCondId6228RemoteSensorAverageHighHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The average humidity of multiple remote sensors on the cooling
|
|
unit has exceeded an upper threshold. The event is deactivated
|
|
when the humidity drops below the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6228 }
|
|
|
|
lgpCondId6229RemoteSensorSystemAverageLowHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The average humidity of multiple remote sensors on interconnected
|
|
cooling units in a single system has dropped below a lower
|
|
threshold. The event is deactivated when the humidity rises
|
|
above the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6229 }
|
|
|
|
lgpCondId6230RemoteSensorSystemAverageHighHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The average humidity of multiple remote sensors on interconnected
|
|
cooling units in a single system has exceeded an upper threshold.
|
|
The event is deactivated when the humidity drops below the
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 6230 }
|
|
|
|
lgpCondId6231LowCompressorSuperheat OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor suction superheat has dropped below a lower threshold."
|
|
::= { lgpFlexConditionsWellKnown 6231 }
|
|
|
|
lgpCondId6232SECUnspecifiedGeneralEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more unspecified events active for the Superheat and
|
|
Envelope Controller. See local unit display for further details."
|
|
::= { lgpFlexConditionsWellKnown 6232 }
|
|
|
|
lgpCondId6233SECCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with the Superheat and Envelope Controller has been
|
|
lost. The event is deactivated when communication is re
|
|
-established."
|
|
::= { lgpFlexConditionsWellKnown 6233 }
|
|
|
|
lgpCondId6236PowerSourceAIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No power is detected at power source input 'A'."
|
|
::= { lgpFlexConditionsWellKnown 6236 }
|
|
|
|
lgpCondId6237PowerSourceBIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No power is detected at power source input 'B'."
|
|
::= { lgpFlexConditionsWellKnown 6237 }
|
|
|
|
lgpCondId6239FluidValveHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Operating hours for the fluid valve have exceeded the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6239 }
|
|
|
|
lgpCondId6253BoosterFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Booster failure - boost is off."
|
|
::= { lgpFlexConditionsWellKnown 6253 }
|
|
|
|
lgpCondId6254ChargerFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Charger Failure - Charger is off."
|
|
::= { lgpFlexConditionsWellKnown 6254 }
|
|
|
|
lgpCondId6274UnitTopReturnAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return air sensor at the top of the unit is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6274 }
|
|
|
|
lgpCondId6275UnitMiddleReturnAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return air sensor in the middle of the unit is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6275 }
|
|
|
|
lgpCondId6276UnitBottomReturnAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return air sensor at the bottom of the unit is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6276 }
|
|
|
|
lgpCondId6277UnitTopSupplyAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply air sensor at the top of the unit is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6277 }
|
|
|
|
lgpCondId6278UnitMiddleFirstSupplyAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"First supply air sensor in the middle of the unit is disconnected
|
|
or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6278 }
|
|
|
|
lgpCondId6279UnitBottomSupplyAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply air sensor at the bottom of the unit is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6279 }
|
|
|
|
lgpCondId6284UnitMiddleSecondSupplyAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Second supply air sensor in the middle of the unit is disconnected
|
|
or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6284 }
|
|
|
|
lgpCondId6293ChilledWaterControlActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water inlet temperature control function is enabled due to
|
|
'bad' water."
|
|
::= { lgpFlexConditionsWellKnown 6293 }
|
|
|
|
lgpCondId6294ChilledWaterFlowTransducerFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water flow transducer is disconnected or the signal is out
|
|
of range."
|
|
::= { lgpFlexConditionsWellKnown 6294 }
|
|
|
|
lgpCondId6295ChilledWaterInletTemperatureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water inlet temperature sensor is disconnected or the
|
|
signal is out of range. The sensor is mandatory for the chilled
|
|
water flow function."
|
|
::= { lgpFlexConditionsWellKnown 6295 }
|
|
|
|
lgpCondId6296ChilledWaterHighInletTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water inlet temperature has exceeded an upper threshold."
|
|
::= { lgpFlexConditionsWellKnown 6296 }
|
|
|
|
lgpCondId6297Modbus010VModuleCommunicationFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Modbus 0-10V module for managing the second Chilled Water circuit
|
|
valve is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6297 }
|
|
|
|
lgpCondId6299RackDoorsOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rack doors opened due to supply air temperature exceeding the
|
|
[Rack Door Open High Supply Air Temperature Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 6299 }
|
|
|
|
lgpCondId6303TeamStaticPressureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The team static pressure sensor is disconnected or the signal is
|
|
out of range."
|
|
::= { lgpFlexConditionsWellKnown 6303 }
|
|
|
|
lgpCondId6304HeatingLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Heating is shut down and disabled."
|
|
::= { lgpFlexConditionsWellKnown 6304 }
|
|
|
|
lgpCondId6305FreeCoolingStoppedHighRoomTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Free cooling is temporarily disabled due to room temperature
|
|
exceeding a preset delta above the the set point."
|
|
::= { lgpFlexConditionsWellKnown 6305 }
|
|
|
|
lgpCondId6306ColdAisleTemperatureHumidityTeamSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Cold aisle team sensor measuring air temperature and humidity is
|
|
disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6306 }
|
|
|
|
lgpCondId6309ColdAisleAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Cold aisle sensor measuring air temperature and humidity is
|
|
disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6309 }
|
|
|
|
lgpCondId6310ChilledWaterInletTemperatureControlActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water inlet temperature control is active."
|
|
::= { lgpFlexConditionsWellKnown 6310 }
|
|
|
|
lgpCondId6313ChilledWaterInletTemperatureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water inlet temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6313 }
|
|
|
|
lgpCondId6314ChilledWaterOutletTemperatureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water outlet temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6314 }
|
|
|
|
lgpCondId6315ChilledWaterFlowMeterSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water flow meter sensor is disconnected or the signal is
|
|
out of range."
|
|
::= { lgpFlexConditionsWellKnown 6315 }
|
|
|
|
lgpCondId6333Bypassoutofsync OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass and Inverter inputs are not in sync."
|
|
::= { lgpFlexConditionsWellKnown 6333 }
|
|
|
|
lgpCondId6348SystemOutputoffasrequested OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS has shutdown as requested, i.e., the output is off."
|
|
::= { lgpFlexConditionsWellKnown 6348 }
|
|
|
|
lgpCondId6349SystemOffasrequested OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The entire UPS has shutdown as commanded."
|
|
::= { lgpFlexConditionsWellKnown 6349 }
|
|
|
|
lgpCondId6350GeneralFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A general fault in the UPS has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6350 }
|
|
|
|
lgpCondId6351UPSAwaitingPower OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS output is off and the UPS is awaiting the return of input
|
|
power."
|
|
::= { lgpFlexConditionsWellKnown 6351 }
|
|
|
|
lgpCondId6352AutonomyCalibration OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Calibration test occurred."
|
|
::= { lgpFlexConditionsWellKnown 6352 }
|
|
|
|
lgpCondId6353GeneralWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A warning in the UPS has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6353 }
|
|
|
|
lgpCondId6354BatteryCharging OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS battery is charging (battery charge percentage lower than
|
|
98)."
|
|
::= { lgpFlexConditionsWellKnown 6354 }
|
|
|
|
lgpCondId6355BackfeedRelayFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass SCR is wrongly on or commutated."
|
|
::= { lgpFlexConditionsWellKnown 6355 }
|
|
|
|
lgpCondId6356BatteryCircuitOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery Circuit Open."
|
|
::= { lgpFlexConditionsWellKnown 6356 }
|
|
|
|
lgpCondId6357SystemRestartPending OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A request for UPS restart has been received."
|
|
::= { lgpFlexConditionsWellKnown 6357 }
|
|
|
|
lgpCondId6358PipeTemperatureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Air temperature sensor located in the pipe is not sending a valid
|
|
value."
|
|
::= { lgpFlexConditionsWellKnown 6358 }
|
|
|
|
lgpCondId6362SFAReservedEvent26 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6362 }
|
|
|
|
lgpCondId6363SFAReservedEvent27 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6363 }
|
|
|
|
lgpCondId6364SFAReservedEvent28 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6364 }
|
|
|
|
lgpCondId6365SFAReservedEvent29 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6365 }
|
|
|
|
lgpCondId6366SFAReservedEvent30 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6366 }
|
|
|
|
lgpCondId6367SFAReservedEvent31 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6367 }
|
|
|
|
lgpCondId6368SFAReservedEvent32 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6368 }
|
|
|
|
lgpCondId6369SFAReservedEvent33 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6369 }
|
|
|
|
lgpCondId6370SFAReservedEvent34 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6370 }
|
|
|
|
lgpCondId6371SFAReservedEvent35 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6371 }
|
|
|
|
lgpCondId6372SFAReservedEvent36 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6372 }
|
|
|
|
lgpCondId6373SFAReservedEvent37 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6373 }
|
|
|
|
lgpCondId6374SFAReservedEvent38 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6374 }
|
|
|
|
lgpCondId6375SFAReservedEvent39 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6375 }
|
|
|
|
lgpCondId6376SFAReservedEvent40 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6376 }
|
|
|
|
lgpCondId6377SFAReservedEvent41 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6377 }
|
|
|
|
lgpCondId6378SFAReservedEvent42 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6378 }
|
|
|
|
lgpCondId6379SFAReservedEvent43 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6379 }
|
|
|
|
lgpCondId6380SFAReservedEvent44 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6380 }
|
|
|
|
lgpCondId6381SFAReservedEvent45 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6381 }
|
|
|
|
lgpCondId6382SFAReservedEvent46 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6382 }
|
|
|
|
lgpCondId6383SFAReservedEvent47 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6383 }
|
|
|
|
lgpCondId6384SFAReservedEvent48 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6384 }
|
|
|
|
lgpCondId6385SFAReservedEvent49 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6385 }
|
|
|
|
lgpCondId6386SFAReservedEvent50 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6386 }
|
|
|
|
lgpCondId6438PowerModuleInputCurrentAbnormal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input current of the power module is abnormal."
|
|
::= { lgpFlexConditionsWellKnown 6438 }
|
|
|
|
lgpCondId6439PowerModuleBalancerofDCBusFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Balancer of DC Bus in the power module has failed."
|
|
::= { lgpFlexConditionsWellKnown 6439 }
|
|
|
|
lgpCondId6440PowerModuleFuseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A summary event indicating one or more fuse failures in the power
|
|
module."
|
|
::= { lgpFlexConditionsWellKnown 6440 }
|
|
|
|
lgpCondId6441PowerModulePowerSupplyFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power module power supply failure."
|
|
::= { lgpFlexConditionsWellKnown 6441 }
|
|
|
|
lgpCondId6450PDUPoweredOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The PDU was powered on."
|
|
::= { lgpFlexConditionsWellKnown 6450 }
|
|
|
|
lgpCondId6453InputWiringFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The neutral/ground conductors on the input wiring are not properly
|
|
bonded, or the line/neutral conductors have been swapped."
|
|
::= { lgpFlexConditionsWellKnown 6453 }
|
|
|
|
lgpCondId6454DCtoDCConverterFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A failure has occurred in the battery discharge circuit."
|
|
::= { lgpFlexConditionsWellKnown 6454 }
|
|
|
|
lgpCondId6455LeakSensorCableFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A fault is detected in the 'Leak Sensor' cable."
|
|
::= { lgpFlexConditionsWellKnown 6455 }
|
|
|
|
lgpCondId6518StandbyUnitActivatedDuetoChillerFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External chiller unit has failed for this unit, so the standby
|
|
cooling unit has been activated."
|
|
::= { lgpFlexConditionsWellKnown 6518 }
|
|
|
|
lgpCondId6522PDUResidualOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a PDU residual over current condition."
|
|
::= { lgpFlexConditionsWellKnown 6522 }
|
|
|
|
lgpCondId6527PDUOverCurrentProtection OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The PDU over current protection is triggered."
|
|
::= { lgpFlexConditionsWellKnown 6527 }
|
|
|
|
lgpCondId6528PowerModuleLeverUnlocked OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power module is inactive because the lever is in the unlocked
|
|
position."
|
|
::= { lgpFlexConditionsWellKnown 6528 }
|
|
|
|
lgpCondId6529HardwareMismatch OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The assigned system model settings do not match the actual
|
|
installed hardware. The module count is wrong, or a module of the
|
|
wrong type is installed."
|
|
::= { lgpFlexConditionsWellKnown 6529 }
|
|
|
|
lgpCondId6530SupplyNTCAirSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The supply NTC air sensor is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 6530 }
|
|
|
|
lgpCondId6531ExternalAirSensorCIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external air sensor C is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 6531 }
|
|
|
|
lgpCondId6532ExternalAirSensorDIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external air sensor D is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 6532 }
|
|
|
|
lgpCondId6533ExternalAirSensorEIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external air sensor E is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 6533 }
|
|
|
|
lgpCondId6534PumpThermalOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump is shut down due to thermal overload."
|
|
::= { lgpFlexConditionsWellKnown 6534 }
|
|
|
|
lgpCondId6535XDModuleCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with XD Module has been lost."
|
|
::= { lgpFlexConditionsWellKnown 6535 }
|
|
|
|
lgpCondId6536MMSCapacityExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The critical load is larger than the redundant rating of a 1+N
|
|
redundant multi-module system."
|
|
::= { lgpFlexConditionsWellKnown 6536 }
|
|
|
|
lgpCondId6538TSAControlInputIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The analog input used to set the air temperature set point for
|
|
cooling control is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6538 }
|
|
|
|
lgpCondId6539ChilledWaterValveHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Chilled Water Valve Hours] has exceeded [Chilled Water Valve
|
|
Operating Hours Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 6539 }
|
|
|
|
lgpCondId6540FSAControlInputIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The analog input used to set the air temperature set point for fan
|
|
speed control is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6540 }
|
|
|
|
lgpCondId6541AutoTuneLicenseExpiring OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"License for the AutoTune feature has not been refreshed in 30 days
|
|
and will be expiring soon."
|
|
::= { lgpFlexConditionsWellKnown 6541 }
|
|
|
|
lgpCondId6542AutoTuneLicenseExpired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"License for the AutoTune feature has expired."
|
|
::= { lgpFlexConditionsWellKnown 6542 }
|
|
|
|
lgpCondId6543UnitInStandbyDueToCoolingLoss OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit forced into standby because it is unable to provide any
|
|
cooling."
|
|
::= { lgpFlexConditionsWellKnown 6543 }
|
|
|
|
lgpCondId6544ControlUnitsRemoteShutdownMismatch OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The remote shutdown status of the primary control unit does not
|
|
match the remote shutdown status of the secondary control unit."
|
|
::= { lgpFlexConditionsWellKnown 6544 }
|
|
|
|
lgpCondId6545SecondaryControlUnitCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The primary control unit has lost Ethernet communications with the
|
|
secondary control unit."
|
|
::= { lgpFlexConditionsWellKnown 6545 }
|
|
|
|
lgpCondId6546ControlUnitsUnitCodeMismatch OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit codes for the primary and secondary control units do not
|
|
match."
|
|
::= { lgpFlexConditionsWellKnown 6546 }
|
|
|
|
lgpCondId6547SSAControlInputIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The analog input used to set the static pressure set point for fan
|
|
speed control is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6547 }
|
|
|
|
lgpCondId6574SubfeedPhaseUndercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Subfeed breaker phase current has dropped below the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6574 }
|
|
|
|
lgpCondId6587TransferCountCleared OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A system event indicating the transfer count has been cleared."
|
|
::= { lgpFlexConditionsWellKnown 6587 }
|
|
|
|
lgpCondId6588EnergyCounterCleared OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A system event indicating the energy counter (e.g. KWH) has been
|
|
cleared."
|
|
::= { lgpFlexConditionsWellKnown 6588 }
|
|
|
|
lgpCondId6589HistoryLogsFull OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The history logs are full."
|
|
::= { lgpFlexConditionsWellKnown 6589 }
|
|
|
|
lgpCondId6590HistoryLogsCleared OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"History logs have been cleared."
|
|
::= { lgpFlexConditionsWellKnown 6590 }
|
|
|
|
lgpCondId6591EventLogCleared OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"All past alarms and faults have been cleared."
|
|
::= { lgpFlexConditionsWellKnown 6591 }
|
|
|
|
lgpCondId6592SystemDateChanged OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system date has been updated."
|
|
::= { lgpFlexConditionsWellKnown 6592 }
|
|
|
|
lgpCondId6593SystemTimeChanged OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system time has been updated."
|
|
::= { lgpFlexConditionsWellKnown 6593 }
|
|
|
|
lgpCondId6594AccessPasswordChanged OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The access password has been changed."
|
|
::= { lgpFlexConditionsWellKnown 6594 }
|
|
|
|
lgpCondId6595ConfigModified OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A setpoint has been updated."
|
|
::= { lgpFlexConditionsWellKnown 6595 }
|
|
|
|
lgpCondId6612SCRShort OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The SCR is in a short condition."
|
|
::= { lgpFlexConditionsWellKnown 6612 }
|
|
|
|
lgpCondId6613SCROpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The SCR is in an open condition."
|
|
::= { lgpFlexConditionsWellKnown 6613 }
|
|
|
|
lgpCondId6614ACPowerSupplyFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A failure of the AC Power Supply has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6614 }
|
|
|
|
lgpCondId6615DCPowerSupplyFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A failure of the DC Power Supply has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6615 }
|
|
|
|
lgpCondId6616VoltageSensorFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A voltage sensor failure has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6616 }
|
|
|
|
lgpCondId6617SCRSensorFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The SCR sensor module failed."
|
|
::= { lgpFlexConditionsWellKnown 6617 }
|
|
|
|
lgpCondId6618CurrentSensorFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current sensor module failed."
|
|
::= { lgpFlexConditionsWellKnown 6618 }
|
|
|
|
lgpCondId6619GateDriveFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Gate Drive module failed."
|
|
::= { lgpFlexConditionsWellKnown 6619 }
|
|
|
|
lgpCondId6620SurgeFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The surge module failed for the input source."
|
|
::= { lgpFlexConditionsWellKnown 6620 }
|
|
|
|
lgpCondId6621FastUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fast under voltage detected."
|
|
::= { lgpFlexConditionsWellKnown 6621 }
|
|
|
|
lgpCondId6622SlowUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Slow under voltage detected."
|
|
::= { lgpFlexConditionsWellKnown 6622 }
|
|
|
|
lgpCondId6623OverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Over voltage detected."
|
|
::= { lgpFlexConditionsWellKnown 6623 }
|
|
|
|
lgpCondId6624OverUnderFrequencyFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An over or under frequency condition has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6624 }
|
|
|
|
lgpCondId6625GeneralSourceFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A non-specific failure has been detected in the source."
|
|
::= { lgpFlexConditionsWellKnown 6625 }
|
|
|
|
lgpCondId6626OverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An over current has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6626 }
|
|
|
|
lgpCondId6627PeakCurrentOffLimit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The peak current has exceeded the setpoint defined by I-PK Xfer
|
|
Lockout."
|
|
::= { lgpFlexConditionsWellKnown 6627 }
|
|
|
|
lgpCondId6628SyncFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A phase rotation/out of synchronization failure has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6628 }
|
|
|
|
lgpCondId6629InputOverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input over voltage."
|
|
::= { lgpFlexConditionsWellKnown 6629 }
|
|
|
|
lgpCondId6630InputUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input under voltage."
|
|
::= { lgpFlexConditionsWellKnown 6630 }
|
|
|
|
lgpCondId6631InputOverUnderFrequency OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input over/under frequency."
|
|
::= { lgpFlexConditionsWellKnown 6631 }
|
|
|
|
lgpCondId6635VoltageSenseFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output voltage sense failure."
|
|
::= { lgpFlexConditionsWellKnown 6635 }
|
|
|
|
lgpCondId6636LoadonAlternateSource OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The load is on the alternate source."
|
|
::= { lgpFlexConditionsWellKnown 6636 }
|
|
|
|
lgpCondId6637UnderVoltageFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output under voltage failure."
|
|
::= { lgpFlexConditionsWellKnown 6637 }
|
|
|
|
lgpCondId6638OutputOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output is over current."
|
|
::= { lgpFlexConditionsWellKnown 6638 }
|
|
|
|
lgpCondId6639GroundOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ground is over current."
|
|
::= { lgpFlexConditionsWellKnown 6639 }
|
|
|
|
lgpCondId6640NeutralOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Neutral is over current."
|
|
::= { lgpFlexConditionsWellKnown 6640 }
|
|
|
|
lgpCondId6641LoadVoltageTHD OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Load voltage THD has exceeded the set limit."
|
|
::= { lgpFlexConditionsWellKnown 6641 }
|
|
|
|
lgpCondId6662ControlLogicFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A control logic module has failed."
|
|
::= { lgpFlexConditionsWellKnown 6662 }
|
|
|
|
lgpCondId6663PowerSupplyLogicFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A power supply module has failed."
|
|
::= { lgpFlexConditionsWellKnown 6663 }
|
|
|
|
lgpCondId6664ExternalCommsFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External communications failure."
|
|
::= { lgpFlexConditionsWellKnown 6664 }
|
|
|
|
lgpCondId6665HeatSinkOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system heat sink temperature has exceeded design limits."
|
|
::= { lgpFlexConditionsWellKnown 6665 }
|
|
|
|
lgpCondId6666AutomaticTransferInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatic transfer is inhibited."
|
|
::= { lgpFlexConditionsWellKnown 6666 }
|
|
|
|
lgpCondId6667InputSourceTransferInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input source transfer is inhibited."
|
|
::= { lgpFlexConditionsWellKnown 6667 }
|
|
|
|
lgpCondId6676CB1ShuntTrip OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB1 Shunt Trip event."
|
|
::= { lgpFlexConditionsWellKnown 6676 }
|
|
|
|
lgpCondId6677CB2ShuntTrip OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB2 Shunt Trip event."
|
|
::= { lgpFlexConditionsWellKnown 6677 }
|
|
|
|
lgpCondId6678CB6NeutralOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB6 neutral open event."
|
|
::= { lgpFlexConditionsWellKnown 6678 }
|
|
|
|
lgpCondId6679ContactorNeutralFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Contactor Neutral Fail event."
|
|
::= { lgpFlexConditionsWellKnown 6679 }
|
|
|
|
lgpCondId6680CB1BreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB1 Breaker open event. Normal state is breaker closed. Latched
|
|
state is breaker open."
|
|
::= { lgpFlexConditionsWellKnown 6680 }
|
|
|
|
lgpCondId6681CB2BreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB2 Breaker open event. Normal state is breaker closed. Latched
|
|
state is breaker open."
|
|
::= { lgpFlexConditionsWellKnown 6681 }
|
|
|
|
lgpCondId6682CB4BreakerClosed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB4 breaker closed event. Normal state is breaker open. Latched
|
|
state is breaker closed."
|
|
::= { lgpFlexConditionsWellKnown 6682 }
|
|
|
|
lgpCondId6683CB5BreakerClosed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB5 breaker closed event. Normal state is breaker open. Latched
|
|
state is breaker closed."
|
|
::= { lgpFlexConditionsWellKnown 6683 }
|
|
|
|
lgpCondId6684CB3BreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB3 breaker open event. Normal state is breaker closed. Latched
|
|
state is breaker open."
|
|
::= { lgpFlexConditionsWellKnown 6684 }
|
|
|
|
lgpCondId6685CB3ABreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB3A breaker open event. Normal state is breaker closed. Latched
|
|
state is breaker open."
|
|
::= { lgpFlexConditionsWellKnown 6685 }
|
|
|
|
lgpCondId6686CB6BreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB6 breaker open event. Normal state is breaker closed. Latched
|
|
state is breaker open."
|
|
::= { lgpFlexConditionsWellKnown 6686 }
|
|
|
|
lgpCondId6687CB7BreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB7 breaker open event. Normal state is breaker closed. Latched
|
|
state is breaker open."
|
|
::= { lgpFlexConditionsWellKnown 6687 }
|
|
|
|
lgpCondId6691GroupIndependentOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The group standby/cascade state for this unit has been overridden.
|
|
The unit has been forced on."
|
|
::= { lgpFlexConditionsWellKnown 6691 }
|
|
|
|
lgpCondId6692GroupIndependentOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The group standby/cascade state for this unit has been overridden.
|
|
The unit has been forced off."
|
|
::= { lgpFlexConditionsWellKnown 6692 }
|
|
|
|
lgpCondId6693BranchResidualOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a branch residual over current condition."
|
|
::= { lgpFlexConditionsWellKnown 6693 }
|
|
|
|
lgpCondId6694ReceptacleResidualOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a receptacle residual over current
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 6694 }
|
|
|
|
lgpCondId6728BuckOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input voltage is currently being bucked (lowered) by the
|
|
inverter."
|
|
::= { lgpFlexConditionsWellKnown 6728 }
|
|
|
|
lgpCondId6729BoostOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input voltage is currently being boosted (raised) by the
|
|
inverter."
|
|
::= { lgpFlexConditionsWellKnown 6729 }
|
|
|
|
lgpCondId6739Compressor1HighPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1 High Pressure."
|
|
::= { lgpFlexConditionsWellKnown 6739 }
|
|
|
|
lgpCondId6740Compressor2HighPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 2 High Pressure."
|
|
::= { lgpFlexConditionsWellKnown 6740 }
|
|
|
|
lgpCondId6741Compressor1ThermalOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1 Thermal Overload."
|
|
::= { lgpFlexConditionsWellKnown 6741 }
|
|
|
|
lgpCondId6742Compressor2ThermalOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 2 Thermal Overload."
|
|
::= { lgpFlexConditionsWellKnown 6742 }
|
|
|
|
lgpCondId6758CompressorFreezeProtection OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor has entered the freeze protection phase."
|
|
::= { lgpFlexConditionsWellKnown 6758 }
|
|
|
|
lgpCondId6773FanTemperatureCompensationLimitReached OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit is configured for fan temperature compensation, and the fan
|
|
control set point cannot be reduced any further due to high
|
|
remote air temperature sensor readings."
|
|
::= { lgpFlexConditionsWellKnown 6773 }
|
|
|
|
lgpCondId6774ModbusECFanCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with Modbus EC fan has been lost."
|
|
::= { lgpFlexConditionsWellKnown 6774 }
|
|
|
|
lgpCondId6785AnalogTemperatureControlIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Analog input used for creating the control temperature (instead of
|
|
reading a sensor) is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6785 }
|
|
|
|
lgpCondId6786SubgroupFirmwareUpdateRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Mismatch of subgroup firmware. Both the primary and secondary
|
|
control boards must be running the same firmware version."
|
|
::= { lgpFlexConditionsWellKnown 6786 }
|
|
|
|
lgpCondId6787SubgroupSecondaryControlUnitIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Subgroup secondary control unit is reporting an unspecified issue."
|
|
::= { lgpFlexConditionsWellKnown 6787 }
|
|
|
|
lgpCondId6788EEVCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with Electronic Expansion Valve unit has been lost."
|
|
::= { lgpFlexConditionsWellKnown 6788 }
|
|
|
|
lgpCondId6789EEVMotorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve stepper motor issue."
|
|
::= { lgpFlexConditionsWellKnown 6789 }
|
|
|
|
lgpCondId6790EEVFeedbackIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve feedback error."
|
|
::= { lgpFlexConditionsWellKnown 6790 }
|
|
|
|
lgpCondId6791EEVPressureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve refrigerant pressure sensor is
|
|
disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6791 }
|
|
|
|
lgpCondId6792EEVCoilTemperatureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve coil temperature sensor is disconnected
|
|
or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6792 }
|
|
|
|
lgpCondId6793EEVDischargeTemperatureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve discharge temperature sensor is
|
|
disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6793 }
|
|
|
|
lgpCondId6794EEVSumpTemperatureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve sump temperature sensor is disconnected
|
|
or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6794 }
|
|
|
|
lgpCondId6795EEVBatteryTestIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve battery state cannot be determined."
|
|
::= { lgpFlexConditionsWellKnown 6795 }
|
|
|
|
lgpCondId6796EEVBatteryPersistentIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve has continuously detected a 'bad'
|
|
battery condition for an extended period of time."
|
|
::= { lgpFlexConditionsWellKnown 6796 }
|
|
|
|
lgpCondId6798PumpCycleLockOut OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump is locked out due to multiple pump-to-compressor transitions
|
|
at cold ambient air temperature."
|
|
::= { lgpFlexConditionsWellKnown 6798 }
|
|
|
|
lgpCondId6799PumpBoardFirmwareUpdateRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Mismatch of pump board firmware. All pump boards must be running
|
|
the same firmware version."
|
|
::= { lgpFlexConditionsWellKnown 6799 }
|
|
|
|
lgpCondId6800PumpControlBoardIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump is shut down due to a pump control board issue. Control
|
|
board must be rebooted."
|
|
::= { lgpFlexConditionsWellKnown 6800 }
|
|
|
|
lgpCondId6801PumpInvalidDataShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump is shut down due to invalid data."
|
|
::= { lgpFlexConditionsWellKnown 6801 }
|
|
|
|
lgpCondId6802PumpInputPressureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump input refrigerant pressure sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6802 }
|
|
|
|
lgpCondId6803PumpInputTemperatureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump input refrigerant temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6803 }
|
|
|
|
lgpCondId6804PumpOutputPressureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump output refrigerant pressure sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6804 }
|
|
|
|
lgpCondId6805PumpOutputTemperatureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump output refrigerant temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6805 }
|
|
|
|
lgpCondId6806PumpCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with pump unit has been lost."
|
|
::= { lgpFlexConditionsWellKnown 6806 }
|
|
|
|
lgpCondId6807PumpRemoteShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump is shut down by a remote signal."
|
|
::= { lgpFlexConditionsWellKnown 6807 }
|
|
|
|
lgpCondId6808PumpUSBEthernetPortIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump control board USB or Ethernet interface has failed."
|
|
::= { lgpFlexConditionsWellKnown 6808 }
|
|
|
|
lgpCondId6809PumpStartupFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Multiple attempts to start the pump have failed."
|
|
::= { lgpFlexConditionsWellKnown 6809 }
|
|
|
|
lgpCondId6810PumpInverterFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump inverter is reporting a failure."
|
|
::= { lgpFlexConditionsWellKnown 6810 }
|
|
|
|
lgpCondId6811PumpTVSSIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump Transient Voltage Surge Suppressor or Surge Protection Device
|
|
has failed."
|
|
::= { lgpFlexConditionsWellKnown 6811 }
|
|
|
|
lgpCondId6812PumpHighSuperheat OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump inlet refrigerant superheat temperature is too high, or the
|
|
pump has been running too long with the condenser fan off."
|
|
::= { lgpFlexConditionsWellKnown 6812 }
|
|
|
|
lgpCondId6813CondenserHighAmbientAirTempDelta OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The difference between condenser measured ambient air temperatures
|
|
has been too large for an extended period of time."
|
|
::= { lgpFlexConditionsWellKnown 6813 }
|
|
|
|
lgpCondId6814CondenserLeeTempOptionMismatch OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lee-Temp option configured at a condenser unit does not match Lee
|
|
-Temp option configured at the control unit."
|
|
::= { lgpFlexConditionsWellKnown 6814 }
|
|
|
|
lgpCondId6815CondenserBoardFirmwareUpdateRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Mismatch of condenser board firmware. All condenser boards must
|
|
be running the same firmware version."
|
|
::= { lgpFlexConditionsWellKnown 6815 }
|
|
|
|
lgpCondId6816CondenserToPumpHighRefrigerantTempDelta OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature delta between the condenser output refrigerant and
|
|
pump inlet refrigerant is too large."
|
|
::= { lgpFlexConditionsWellKnown 6816 }
|
|
|
|
lgpCondId6817CondenserRefrigerantTypeMismatch OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Refrigerant type configured at condenser unit does not match
|
|
refrigerant type configured at the control unit."
|
|
::= { lgpFlexConditionsWellKnown 6817 }
|
|
|
|
lgpCondId6818ExternalSupplyFluidHighTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply fluid temperature has exceeded a threshold, as indicated by
|
|
an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 6818 }
|
|
|
|
lgpCondId6819ExternalSupplyFluidTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply fluid temperature sensor is disconnected or the signal is
|
|
out of range, as indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 6819 }
|
|
|
|
lgpCondId6822AuditLogUpdate OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Audit log has been updated."
|
|
::= { lgpFlexConditionsWellKnown 6822 }
|
|
|
|
lgpCondId6824ExternalSupplyFluidFlowIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply fluid flow issue, as indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 6824 }
|
|
|
|
END
|