LIEBERT-GP-FLEXIBLE-MIB DEFINITIONS ::= BEGIN
IMPORTS
DisplayString
FROM SNMPv2-TC
MODULE-IDENTITY,
OBJECT-IDENTITY,
OBJECT-TYPE,
Integer32,
Unsigned32
FROM SNMPv2-SMI
lgpFlexible,
liebertFlexibleModuleReg
FROM LIEBERT-GP-REGISTRATION-MIB
;
-- =============================================================================
-- Module Identification and Registration
-- =============================================================================
liebertGlobalProductsFlexibleModule MODULE-IDENTITY
LAST-UPDATED "201305140000Z"
ORGANIZATION "Liebert Corporation"
CONTACT-INFO
"Contact: Technical Support
Postal:
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus OH, 43229
US
Tel: +1 (800) 222-5877
E-mail: liebert.monitoring@vertivco.com
Web: www.vertivco.com
Author: Phil Ulrich"
DESCRIPTION
"The MIB module used to register Liebert Flexible related SNMP OIDs.
Copyright 2013 Liebert Corporation. All rights reserved.
Reproduction of this document is authorized on the condition
that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Liebert Corporation
makes no warranty, either express or implied, as to the use,
operation, condition, or performance of the Specification."
REVISION "201305140000Z"
DESCRIPTION
"Initial Version"
::= { liebertFlexibleModuleReg 1 }
-- =============================================================================
-- lgpFlexible - Liebert Flexible Registrations
-- =============================================================================
-- -----------------------------------------------------------------------------
-- Flexible Basic Table
-- -----------------------------------------------------------------------------
lgpFlexibleTableCount OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is the number of entries in the lgpFlexibleBasicTable."
::= { lgpFlexible 10 }
lgpFlexibleBasicTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpFlexibleBasicEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains data points supported by the managed device. The
data in this table is formatted in string form. This data is also
available in numerical form in the augmented
lgpFlexibleExtendedTable.
In this table, the row indexing is not necessarily sequential and
leads to a sparsely populated table."
::= { lgpFlexible 20 }
lgpFlexibleBasicEntry OBJECT-TYPE
SYNTAX LgpFlexibleBasicEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the columns to be populated in the
'lgpFlexibleBasicTable'."
INDEX
{
IMPLIED lgpFlexibleEntryIndex
}
::= { lgpFlexibleBasicTable 1 }
LgpFlexibleBasicEntry ::= SEQUENCE
{
lgpFlexibleEntryIndex OBJECT IDENTIFIER,
lgpFlexibleEntryDataLabel DisplayString,
lgpFlexibleEntryValue DisplayString,
lgpFlexibleEntryUnitsOfMeasure DisplayString
}
lgpFlexibleEntryIndex OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index which defines a specific row in the
lgpFlexibleBasicTable. Each row index is associated with a unique
data point ID which fixes the data point to its permanent location
in the table."
::= { lgpFlexibleBasicEntry 1 }
lgpFlexibleEntryDataLabel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A short description of the data reported in this row."
::= { lgpFlexibleBasicEntry 10 }
lgpFlexibleEntryValue OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A string representation of any data available. This is the
preferred method of data access, since this will give fully
scaled data for both integer and floating point data, in addition
to textual data. If this string column cannot be used, then
columns in the lgpFlexibleExtendedTable must be used in order
to get a fully scaled version of integer data."
::= { lgpFlexibleBasicEntry 20 }
lgpFlexibleEntryUnitsOfMeasure OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The unit of measure that the value will be presented in. This is
not populated when the data does not have a unit of measure
associated with it."
::= { lgpFlexibleBasicEntry 30 }
-- -----------------------------------------------------------------------------
-- Flexible Extended Table
-- -----------------------------------------------------------------------------
lgpFlexibleExtendedTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpFlexibleExtendedEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains data points supported by the managed device. This
table augments the lgpFlexibleBasicTable, providing additional
information that may be relevant to advanced users. Values presented
in string format in the lgpFlexibleBasicTable table are also available in
numeric form in this table.
Since the lgpFlexibleBasicTable and this table are both indexed by
lgpFlexibleEntryIndex, data applicable to a specific data point can be
found in both tables at the same index."
::= { lgpFlexible 30 }
lgpFlexibleExtendedEntry OBJECT-TYPE
SYNTAX LgpFlexibleExtendedEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the columns to be populated in the
'lgpFlexibleExtendedTable'."
AUGMENTS { lgpFlexibleBasicEntry }
::= { lgpFlexibleExtendedTable 1 }
LgpFlexibleExtendedEntry ::= SEQUENCE
{
lgpFlexibleEntryIntegerValue Integer32,
lgpFlexibleEntryUnsignedIntegerValue Unsigned32,
lgpFlexibleEntryDecimalPosition Unsigned32,
lgpFlexibleEntryDataType INTEGER,
lgpFlexibleEntryAccessibility INTEGER,
lgpFlexibleEntryUnitsOfMeasureEnum INTEGER,
lgpFlexibleEntryDataDescription DisplayString
}
lgpFlexibleEntryIntegerValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This is the data point value formatted as a signed integer. This
column is populated only for numerical data points whose type
requires a signed value.
To convert this value to the units indicated in the units of
measure columns (lgpFlexibleEntryUnitsOfMeasure or
lgpFlexibleEntryUnitsOfMeasureEnum), divide this value
by 10^n, where n is the value from the
lgpFlexibleEntryDecimalPosition column.
For data points that are writable (as designated by the
lgpFlexibleEntryAccessibility column), the inverse
calculation must done. The desired value must be multiplied by
10^n before it is written to this column, where n is the value
from the lgpFlexibleEntryDecimalPosition column."
::= { lgpFlexibleExtendedEntry 10 }
lgpFlexibleEntryUnsignedIntegerValue OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This is the data point value formatted as an unsigned integer. This
column is populated only for numerical data points whose type
does not require a signed value.
To convert this value to the units indicated in the units of
measure columns (lgpFlexibleEntryUnitsOfMeasure or
lgpFlexibleEntryUnitsOfMeasureEnum), divide this value
by 10^n, where n is the value from the
lgpFlexibleEntryDecimalPosition column.
For data points that are writable (as designated by the
lgpFlexibleEntryAccessibility column), the inverse
calculation must done. The desired value must be multiplied by
10^n before it is written to this column, where n is the value
from the lgpFlexibleEntryDecimalPosition column."
::= { lgpFlexibleExtendedEntry 20 }
lgpFlexibleEntryDecimalPosition OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is a power of ten divider needed to convert values from the
signed and unsigned integer columns
(lgpFlexibleEntryIntegerValue or
lgpFlexibleEntryUnsignedIntegerValue) to floating
point values. This essentially tells how many positions to move
the decimal point to the left.
To convert the integer values to the units indicated in the units
of measure columns (lgpFlexibleEntryUnitsOfMeasure or
lgpFlexibleEntryUnitsOfMeasureEnum), divide the
integer value by 10^n, where n is the value from this column.
For data points that are writable (as designated by the
lgpFlexibleEntryAccessibility column), the inverse
calculation must done. The desired value must be multiplied by
10^n before it is written to the signed or unsigned integer
columns."
::= { lgpFlexibleExtendedEntry 30 }
lgpFlexibleEntryDataType OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
int16(1),
uint16(2),
int32(3),
uint32(4),
text(5),
enum(6),
event16(7),
event32(8),
ipv4(9),
time32(10)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The format that the data will appear as. This can be used to
determine which field the numerical data will appear in. Data of
type int16 and int32 will appear in the column
lgpFlexibleEntryIntegerValue. Data of type uint16,
uint32, and enum, will appear in the column
lgpFlexibleEntryUnsignedIntegerValue."
::= { lgpFlexibleExtendedEntry 40 }
lgpFlexibleEntryAccessibility OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
readonly(1),
writeonly(2),
readwrite(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This describes the read/write access that is available for the
data in the row."
::= { lgpFlexibleExtendedEntry 50 }
lgpFlexibleEntryUnitsOfMeasureEnum OBJECT-TYPE
SYNTAX INTEGER
{
not-specified(0),
milliSeconds(4096),
seconds(4097),
minutes(4098),
hours(4099),
voltsAcRms(4100),
milliVoltsAcRms(4101),
voltsDc(4102),
milliVoltsDc(4103),
voltsPeak(4104),
voltsPeakToPeak(4105),
ampsAcRms(4106),
milliAmpsAcRms(4107),
ampsDc(4108),
milliAmpsDc(4109),
voltAmps(4110),
kiloVoltAmps(4111),
voltAmpsReactive(4112),
kVAReactive(4113),
watts(4114),
kiloWatts(4115),
wattHours(4116),
kiloWattHour(4117),
ampDcHours(4118),
hertz(4119),
milliHertz(4120),
kiloHertz(4121),
megaHertz(4122),
gigaHertz(4123),
percent(4124),
degC(4125),
degCDelta(4126),
degF(4127),
degFDelta(4128),
psi(4129),
pascal(4130),
psia(4131),
relativeHumidity(4132),
thd(4133),
days(4134),
phase(4135),
microOhms(4136),
milliOhms(4137),
ohms(4138),
kiloOhms(4139),
megaOhms(4140),
bars(4141),
rpm(4142),
bytes(4143),
kilobytes(4144),
megabytes(4145),
gigabytes(4146),
terabytes(4147),
voltAmpHours(4148),
kiloVoltAmpHours(4149),
vaReactiveHours(4150),
kVAReactiveHours(4151),
meter(4152),
feet(4153),
cms(4154),
cmh(4155),
cfs(4156),
cfm(4157),
lpm(4158),
gpmUk(4159),
gpmUs(4160),
absoluteHumidity(4161),
kilograms(4162),
cubicMeters(4163),
btu(4164),
torrs(4165),
millitorrs(4166),
pounds(4167),
mps(4168),
fpm(4169),
liter(4170),
gallonUs(4171),
gallonUk(4172),
lps(4173),
mho(4174),
siemensCm(4175),
weeks(4176),
inWC(4177),
btuHours(4178)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The unit of measurement that the value will be in."
::= { lgpFlexibleExtendedEntry 60 }
lgpFlexibleEntryDataDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A description of the data reported in this row. This is generally
longer and more thorough than the simple label described by
lgpFlexibleEntryDataLabel."
::= { lgpFlexibleExtendedEntry 70 }
END