LIEBERT-GP-POWER-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY,
|
|
OBJECT-IDENTITY,
|
|
OBJECT-TYPE,
|
|
Integer32,
|
|
Unsigned32
|
|
FROM SNMPv2-SMI
|
|
lgpPower,
|
|
liebertPowerModuleReg
|
|
FROM LIEBERT-GP-REGISTRATION-MIB
|
|
;
|
|
|
|
-- =============================================================================
|
|
-- Module Identification and Registration
|
|
-- =============================================================================
|
|
|
|
liebertGlobalProductsPowerModule MODULE-IDENTITY
|
|
LAST-UPDATED "201307100000Z"
|
|
ORGANIZATION "Liebert Corporation"
|
|
CONTACT-INFO
|
|
"Contact: Technical Support
|
|
|
|
Postal:
|
|
Liebert Corporation
|
|
1050 Dearborn Drive
|
|
P.O. Box 29186
|
|
Columbus OH, 43229
|
|
US
|
|
|
|
Tel: +1 (800) 222-5877
|
|
|
|
E-mail: liebert.monitoring@vertivco.com
|
|
Web: www.vertivco.com
|
|
|
|
Author: Gregory M. Hoge"
|
|
|
|
DESCRIPTION
|
|
"The MIB module used to register Liebert POWER related SNMP OIDs.
|
|
|
|
Copyright 2000-2008 Liebert Corporation. All rights reserved.
|
|
Reproduction of this document is authorized on the condition
|
|
that the forgoing copyright notice is included.
|
|
|
|
This Specification is supplied 'AS IS' and Liebert Corporation
|
|
makes no warranty, either express or implied, as to the use,
|
|
operation, condition, or performance of the Specification."
|
|
|
|
REVISION "201307100000Z"
|
|
DESCRIPTION
|
|
"Added support for GXT4 economic operation mode and outlet control."
|
|
|
|
REVISION "200811170000Z"
|
|
DESCRIPTION
|
|
"Added support for NXL unit."
|
|
|
|
REVISION "200807020000Z"
|
|
DESCRIPTION
|
|
"Replaced INTEGER with Integer32 (SMIv2).
|
|
Minor spelling fixes and formatting."
|
|
|
|
REVISION "200801100000Z"
|
|
DESCRIPTION
|
|
"Modified contact email address and removed redundant
|
|
lgpPwrMeasurementPointNumLines."
|
|
|
|
REVISION "200602220000Z"
|
|
DESCRIPTION
|
|
"Added support for Liebert DS Unit."
|
|
|
|
::= { liebertPowerModuleReg 1 }
|
|
|
|
-- =============================================================================
|
|
-- lgpPower - Liebert Power Registrations
|
|
-- =============================================================================
|
|
|
|
lgpPwrBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert Power Battery object
|
|
identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Power Battery Group."
|
|
::= { lgpPower 1 }
|
|
|
|
lgpPwrMeasurements OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree registers Liebert Power Measurement object
|
|
identifiers. The sub-tree contains tables and well known power
|
|
measurement points."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are defined
|
|
below in the sub-section titled Liebert Power Measurement Group."
|
|
::= { lgpPower 2 }
|
|
|
|
lgpPwrStatus OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree registers Liebert Power Status object
|
|
identifiers. This is the location of power related status information
|
|
that does not fit into a more specific category such as the
|
|
lgpPwrConversion sub-tree."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are defined
|
|
below in the sub-section titled Liebert Power Status Group"
|
|
::= { lgpPower 3 }
|
|
|
|
lgpPwrSettings OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree registers Liebert Power Static Switch object
|
|
identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are defined
|
|
below in the sub-section titled Liebert Power Settings Group."
|
|
::= { lgpPower 4 }
|
|
|
|
lgpPwrConversion OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert Power Conversion object
|
|
identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Power Conversion Group."
|
|
::= { lgpPower 5 }
|
|
|
|
lgpPwrControl OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert Power Control object
|
|
identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Power Control Group."
|
|
::= { lgpPower 6 }
|
|
|
|
lgpPwrTopology OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert Power Topology object
|
|
identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Power Topology Group."
|
|
::= { lgpPower 7 }
|
|
|
|
lgpPwrStatistic OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert Power Statistic object
|
|
identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Power Statistic Group."
|
|
::= { lgpPower 8 }
|
|
|
|
lgpPwrConfig OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register Liebert Power Configuration
|
|
Object identifiers."
|
|
REFERENCE
|
|
"The registrations for the objects in this sub-tree are
|
|
defined below in the sub-section titled Liebert Power Configuration
|
|
Group."
|
|
::= { lgpPower 9 }
|
|
|
|
-- =============================================================================
|
|
-- lgpPwrBattery - Liebert Power Battery Group
|
|
-- =============================================================================
|
|
|
|
lgpPwrNumberInstalledBatteryModules OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of battery modules installed in the device."
|
|
::= { lgpPwrBattery 1 }
|
|
|
|
lgpPwrNumberFailedBatteryModules OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of battery modules in the device that have failed."
|
|
::= { lgpPwrBattery 2 }
|
|
|
|
lgpPwrNumberRedundantBatteryModules OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of redundant battery modules in the device."
|
|
::= { lgpPwrBattery 3 }
|
|
|
|
lgpPwrNumberActiveBatteryModules OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of active battery modules in the device."
|
|
::= { lgpPwrBattery 4 }
|
|
|
|
lgpPwrConfigLowBatteryWarningTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the device's estimated minutes of remaining battery
|
|
at which a lgpEventLowBatteryWarning notification will be sent."
|
|
::= { lgpPwrBattery 5 }
|
|
|
|
lgpPwrNumberBatteryModuleWarnings OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of battery modules in the device that have a warning."
|
|
::= { lgpPwrBattery 6 }
|
|
|
|
lgpPwrBatteryCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of batteries installed."
|
|
::= { lgpPwrBattery 7 }
|
|
|
|
lgpPwrBatteryTestResult OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
unknown(1),
|
|
passed(2),
|
|
failed(3),
|
|
inProgress(4),
|
|
systemFailure(5),
|
|
inhibited(6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The outcome of the previous battery test."
|
|
::= { lgpPwrBattery 8 }
|
|
|
|
lgpPwrNominalBatteryCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal battery capacity of the system (in minutes) at full load."
|
|
::= { lgpPwrBattery 9 }
|
|
|
|
lgpPwrBatteryFloatVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery float voltage of the system."
|
|
::= { lgpPwrBattery 10 }
|
|
|
|
lgpPwrBatteryEndOfDischargeVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery voltage threshold at which the batteries are considered
|
|
completely discharged."
|
|
::= { lgpPwrBattery 11 }
|
|
|
|
lgpPwrAutomaticBatteryTestInterval OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "hours"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The automatic battery test interval."
|
|
::= { lgpPwrBattery 12 }
|
|
|
|
lgpPwrAutomaticBatteryTestCountdown OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The time remaining before the next battery test."
|
|
::= { lgpPwrBattery 13 }
|
|
|
|
lgpPwrBatteryChargeStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
fullycharged(1),
|
|
notfullycharged(2),
|
|
charging(3),
|
|
discharging(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the system's battery charge.
|
|
A value of 'charging' indicates the batteries are currently charging.
|
|
A value of 'discharging' indicates the batteries are currently
|
|
discharging. A value of 'fullycharged' indicates the batteries are
|
|
charged to their full capacity. A value of 'notfullycharged' indicates
|
|
the battery charge is neither fully charged, charging or discharging."
|
|
::= { lgpPwrBattery 14 }
|
|
|
|
lgpPwrBatteryLifeEnhancer OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the battery life enhancer. When 'on', it will
|
|
preserve battery life."
|
|
::= { lgpPwrBattery 15 }
|
|
|
|
lgpPwrBatteryCharger OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the battery charger."
|
|
::= { lgpPwrBattery 16 }
|
|
|
|
lgpPwrBatteryChargeMode OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
float(1),
|
|
equalize(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The mode of the battery charger: 'float' charging or 'equalize'
|
|
charging."
|
|
::= { lgpPwrBattery 17 }
|
|
|
|
lgpPwrBatteryTimeRemaining OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An estimate of the time to battery charge depletion under the present
|
|
load conditions if the utility power is off and remains off, or if it
|
|
were to be lost and remain off.
|
|
|
|
NOTE: A UPS is expected to provide a battery time remaining value
|
|
when not operating on battery. However, if the system is not capable of
|
|
providing this information, then this point will return 65535 to
|
|
indicate that the value is unavailable."
|
|
::= { lgpPwrBattery 18 }
|
|
|
|
lgpPwrBatteryCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present percentage of battery capacity."
|
|
::= { lgpPwrBattery 19 }
|
|
|
|
lgpPwrBatteryCabinet OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree contains items related to battery cabinets."
|
|
::= { lgpPwrBattery 20 }
|
|
|
|
lgpPwrBatteryCabinetCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of battery cabinets installed with this device.
|
|
Note some devices may not permit writing a value to this object."
|
|
::= { lgpPwrBatteryCabinet 1 }
|
|
|
|
lgpPwrBatteryCabinetType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
notSpecified(1),
|
|
internal(2),
|
|
external(3),
|
|
lrt(4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of battery cabinet(s) installed on this device.
|
|
Enumeration definitions:
|
|
notSpecified - The type has not been specified in the
|
|
device's configuration.
|
|
internal - Battery cabinets are internal to the device.
|
|
external - Device has external battery cabinets installed.
|
|
lrt - Long Run Time cabinets.
|
|
Note some devices may not permit writing a value to this object."
|
|
::= { lgpPwrBatteryCabinet 2 }
|
|
|
|
lgpPwrBatteryCabinetRatedCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 Amp-hour"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery cabinet rated capacity (tenths of Amp-hours).
|
|
This assumes that each cabinet is of the same type and capacity.
|
|
This is not a sum of the rating for all attached cabinets.
|
|
Note some devices may not permit writing a value to this object."
|
|
::= { lgpPwrBatteryCabinet 3 }
|
|
|
|
lgpPwrBatteryLeadAcidCellCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery cell count - lead-acid. The number of cells that comprise
|
|
the lead acid battery string."
|
|
::= { lgpPwrBatteryCabinet 4 }
|
|
|
|
lgpPwrBatteryNiCadCellCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery cell count - nickel-cadmium. The number of cells that
|
|
comprise the nickel-cadmium battery string."
|
|
::= { lgpPwrBatteryCabinet 5 }
|
|
|
|
lgpPwrBatteryAmpHoursConsumed OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Amp-hour"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The cumulative battery Amp-hours withdrawn over the life of the
|
|
battery. This value persists across reboots. Typically, this value is
|
|
reset back to zero when the batteries are replaced."
|
|
::= { lgpPwrBattery 21 }
|
|
|
|
lgpPwrBatteryAmpHoursDischargeConsumed OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Amp-hour"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery Amp-hours withdrawn during the current/latest
|
|
discharge. This value does not persist across reboots."
|
|
::= { lgpPwrBattery 22 }
|
|
|
|
lgpPwrBatteryLastDischargeTime OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The date and time of the last battery discharge. Typically this is the
|
|
time when the discharge starts. This value persists across reboots.
|
|
The date and time are determined in seconds since the epoch on
|
|
January 1, 1970."
|
|
::= { lgpPwrBattery 23 }
|
|
|
|
lgpPwrBatteryLastCommissionTime OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The date and time when the battery system was put into service.
|
|
This information persists across system reboot events. It is the
|
|
responsibility of Service to reset this date/time when the batteries
|
|
are replaced. The date and time are determined in seconds since the
|
|
epoch on January 1, 1970."
|
|
::= { lgpPwrBattery 24 }
|
|
|
|
lgpPwrBatteryPresentDischargeTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total time spent on battery during the current or last discharge.
|
|
|
|
NOTE: While not discharging, some systems may display zero instead of
|
|
the last discharge."
|
|
::= { lgpPwrBattery 25 }
|
|
|
|
lgpPwrBatteryCapacityStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
unknown(1),
|
|
batteryNormal(2),
|
|
batteryLow(3),
|
|
batteryDepleted(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The indication of the capacity remaining in the UPS
|
|
system's batteries.
|
|
|
|
NOTE: In a single-module system, this point is intended to have the same
|
|
behavior as the RFC1628 point upsBatteryStatus."
|
|
::= { lgpPwrBattery 26 }
|
|
|
|
lgpPwrBatteryCircuitBreakerState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
unknown(0),
|
|
open(1),
|
|
closed(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the Battery Circuit Breaker."
|
|
::= { lgpPwrBattery 27 }
|
|
|
|
-- =============================================================================
|
|
-- lgpPwrMeasurements - Liebert Power Measurement Group
|
|
-- =============================================================================
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
-- Well Known Power Measurement Points
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPwrWellKnownMeasurementPoints OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree registers well known Liebert Power Measurement
|
|
Points. The object identifier names usually imply locations
|
|
where the measurement is taken -- such as 'input', 'output'
|
|
and 'bypass'."
|
|
REFERENCE
|
|
"These well known measurement identifiers are referenced in the
|
|
'lgpPwrMeasurementPointId' column in the
|
|
'lgpPwrMeasurementPointTable'."
|
|
::= { lgpPwrMeasurements 1 }
|
|
|
|
lgpPwrSource1Input OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register a source 1 input as a
|
|
well known measurement point. It is intended that no sub-trees
|
|
be created below this node.
|
|
|
|
Power input to the managed device from power source 1.
|
|
Many power systems contain more than one input source and
|
|
many of them have more than one measurement point per input
|
|
source. This identifier represents one input source for the
|
|
system but does not necessarily represent the 'first' one.
|
|
The input sources' numbering with respect to
|
|
'lgpPwrSource1Input' etc. may depend on the physical wiring
|
|
of the system when it was installed."
|
|
::= { lgpPwrWellKnownMeasurementPoints 1 }
|
|
|
|
lgpPwrSource2Input OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register a source 2 input as a
|
|
well known measurement point. It is intended that no sub-trees
|
|
be created below this node.
|
|
|
|
Power input to the managed device from power source 2.
|
|
Many power systems contain more than one input source and
|
|
many of them have more than one measurement point per input
|
|
source. This identifier represents one input source for the
|
|
system but does not necessarily represent the 'first' one.
|
|
The input sources' numbering with respect to
|
|
'lgpPwrSource2Input' etc. may depend on the physical wiring
|
|
of the system when it was installed."
|
|
::= { lgpPwrWellKnownMeasurementPoints 2 }
|
|
|
|
lgpPwrSourcePdu1Input OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register a source PDU 1 input as a
|
|
well known measurement point. It is intended that no sub-trees
|
|
be created below this node.
|
|
|
|
Power input to the managed device from power distribution
|
|
unit 1. Many power systems contain more than one input source
|
|
and many of them have more than one measurement point per input
|
|
source. This identifier represents one input source for the
|
|
system but does not necessarily represent the 'first' one.
|
|
The input sources' numbering with respect to
|
|
'lgpPwrSourcePdu1Input' etc. may depend on the physical wiring
|
|
of the system when it was installed."
|
|
::= { lgpPwrWellKnownMeasurementPoints 3 }
|
|
|
|
lgpPwrSourcePdu2Input OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register a source PDU 2 input as a
|
|
well known measurement point. It is intended that no sub-trees
|
|
be created below this node.
|
|
|
|
Power input to the managed device from power distribution
|
|
unit 1. Many power systems contain more than one input source
|
|
and many of them have more than one measurement point per input
|
|
source. This identifier represents one input source for the
|
|
system but does not necessarily represent the 'first' one.
|
|
The input sources' numbering with respect to
|
|
'lgpPwrSourcePdu2Input' etc. may depend on the physical wiring
|
|
of the system when it was installed."
|
|
::= { lgpPwrWellKnownMeasurementPoints 4 }
|
|
|
|
lgpPwrOutputToLoad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register the output to the critical
|
|
load as a well known measurement point. It is intended that
|
|
no sub-trees be created below this node."
|
|
::= { lgpPwrWellKnownMeasurementPoints 5 }
|
|
|
|
lgpPwrMeasBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register a battery as a well known
|
|
measurement point. It is intended that no sub-trees be created
|
|
below this node."
|
|
::= { lgpPwrWellKnownMeasurementPoints 6 }
|
|
|
|
lgpPwrMeasBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register a bypass as a well known
|
|
measurement point. It is intended that no sub-trees be created
|
|
below this node."
|
|
::= { lgpPwrWellKnownMeasurementPoints 7 }
|
|
|
|
lgpPwrMeasDcBus OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register a DC bus as a well known
|
|
measurement point. It is intended that no sub-trees be created
|
|
below this node."
|
|
::= { lgpPwrWellKnownMeasurementPoints 8 }
|
|
|
|
lgpPwrMeasSystemOutput OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register the output of a
|
|
multi-module system as a well known measurement point.
|
|
It is intended that no sub-trees be created below this node.
|
|
|
|
This identifier represents the power related data of the
|
|
system."
|
|
::= { lgpPwrWellKnownMeasurementPoints 9 }
|
|
|
|
lgpPwrMeasBatteryCabinet OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree is used to register the voltage between the
|
|
most negative and the most postive terminals of a battery
|
|
cabinet. To determine the cabinet being described in a
|
|
multi-cabinet system, this point implements an additional
|
|
two indexes. The first index describes the module the cabinet
|
|
is located in. The second index describes the cabinet
|
|
number. In an SMS(Single-Module System) the first index is
|
|
always 1.
|
|
|
|
Example: lgpPwrMeasBatteryCabinet.2.4
|
|
|
|
'lgpPwrMeasBatteryCabinet' = Point is a battery cabinet.
|
|
'.2' = Cabinet is in the second module.
|
|
'.4' = Cabinet number 4"
|
|
::= { lgpPwrWellKnownMeasurementPoints 10 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
-- AC Power Measurement Point Table
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPwrMeasurementPointTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpPwrMeasurementPointEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains a list of AC power measurement point entries.
|
|
The table contains zero, one, or many rows, depending upon the number
|
|
of power related measurement points available. The NMS cannot
|
|
create or delete rows from the table. The rows are created by the
|
|
agent based upon the capabilities of the managed device. Each row
|
|
in the table represents a series of measurements on a given point
|
|
or location within the system. Measurement points/locations are
|
|
identified by the object identifier 'lgpPwrMeasurementPointId' in the
|
|
'LgpPwrMeasurementPointEntry' object. The actual measurement being
|
|
taken at that identified point is identified by the other
|
|
corresponding columns in the LgpPwrMeasurementPointEntry for the
|
|
particular row of the table."
|
|
REFERENCE
|
|
"The measurement points represented by 'lgpPwrMeasurementPointId'
|
|
can be found in the sub-tree lgpPwrWellKnownMeasurementPoints.
|
|
Additional measurement detail on a 'per line' basis is available in
|
|
the lgpPwrLineMeasurementTable"
|
|
::= { lgpPwrMeasurements 2 }
|
|
|
|
lgpPwrMeasurementPointEntry OBJECT-TYPE
|
|
SYNTAX LgpPwrMeasurementPointEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the measurements to be populated in the
|
|
various columns of the 'lgpPwrMeasurementPointTable'."
|
|
INDEX { lgpPwrMeasurementPointIndex }
|
|
::= { lgpPwrMeasurementPointTable 1 }
|
|
|
|
LgpPwrMeasurementPointEntry ::= SEQUENCE
|
|
{
|
|
lgpPwrMeasurementPointIndex Unsigned32,
|
|
lgpPwrMeasurementPointId OBJECT IDENTIFIER,
|
|
lgpPwrMeasurementPointNumLines Integer32,
|
|
lgpPwrMeasurementPointNomVolts Integer32,
|
|
lgpPwrMeasurementPointNomFrequency Integer32,
|
|
lgpPwrMeasurementPointFrequency Integer32,
|
|
lgpPwrMeasurementPointApparentPower Integer32,
|
|
lgpPwrMeasurementPointTruePower Integer32,
|
|
lgpPwrMeasurementPointPowerFactor Integer32,
|
|
lgpPwrMeasurementPointWattHours Integer32,
|
|
lgpPwrMeasurementPointVAPercent Integer32,
|
|
lgpPwrMeasurementPointNeutralCurrent Integer32,
|
|
lgpPwrMeasurementPointGroundCurrent Integer32,
|
|
lgpPwrMeasurementPointNomCurrent Integer32,
|
|
lgpPwrMeasurementPointNomPowerFactor Integer32,
|
|
lgpPwrMeasurementPointNomVA Integer32,
|
|
lgpPwrMeasurementPointNomW Integer32,
|
|
lgpPwrMeasurementPointPowerFactorTag INTEGER
|
|
}
|
|
|
|
lgpPwrMeasurementPointIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index that indicates the row of the
|
|
'lgpPwrMeasurementPointTable' for a power measurement point."
|
|
::= { lgpPwrMeasurementPointEntry 1 }
|
|
|
|
lgpPwrMeasurementPointId OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An OID representing a well known measurement point.
|
|
These object identifiers indicate a point or location of power
|
|
measurement in a power system. The OID's name usually
|
|
implies a location of the measurement point such as
|
|
'input', 'output', 'bypass' etc."
|
|
REFERENCE
|
|
"The object identifiers in this column can be found in the sub-tree
|
|
'lgpPwrWellKnownMeasurementPoints'."
|
|
::= { lgpPwrMeasurementPointEntry 2 }
|
|
|
|
lgpPwrMeasurementPointNumLines OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of lines on the indicated power measurement point.
|
|
(i.e. the number of phases on the power source being measured.)"
|
|
::= { lgpPwrMeasurementPointEntry 3 }
|
|
|
|
lgpPwrMeasurementPointNomVolts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the nominal voltage on the power source being
|
|
measured."
|
|
::= { lgpPwrMeasurementPointEntry 4 }
|
|
|
|
lgpPwrMeasurementPointNomFrequency OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal or configured/expected frequency for the power
|
|
source indicated by 'lgpPwrMeasurementPointId' in the
|
|
corresponding row in the lgpPwrMeasurementPointTable."
|
|
::= { lgpPwrMeasurementPointEntry 5 }
|
|
|
|
lgpPwrMeasurementPointFrequency OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present (actual) frequency for the power source indicated
|
|
by 'lgpPwrMeasurementPointId' in the corresponding row in the
|
|
lgpPwrMeasurementPointTable."
|
|
::= { lgpPwrMeasurementPointEntry 6 }
|
|
|
|
lgpPwrMeasurementPointApparentPower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt-Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present apparent AC power for the power source
|
|
indicated by 'lgpPwrMeasurementPointId' in the corresponding row
|
|
in the lgpPwrMeasurementPointTable."
|
|
::= { lgpPwrMeasurementPointEntry 7 }
|
|
|
|
lgpPwrMeasurementPointTruePower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Watt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present AC power for the power source indicated by
|
|
'lgpPwrMeasurementPointId' in the corresponding row in the
|
|
lgpPwrMeasurementPointTable."
|
|
::= { lgpPwrMeasurementPointEntry 8 }
|
|
|
|
lgpPwrMeasurementPointPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".01 Power Factor"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present Power Factor for the power source indicated by
|
|
'lgpPwrMeasurementPointId' in the corresponding row in the
|
|
lgpPwrMeasurementPointTable."
|
|
::= { lgpPwrMeasurementPointEntry 9 }
|
|
|
|
lgpPwrMeasurementPointWattHours OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Watt-Hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present number of Watt Hours for the power source indicated by
|
|
'lgpPwrMeasurementPointId' in the corresponding row in the
|
|
lgpPwrMeasurementPointTable."
|
|
::= { lgpPwrMeasurementPointEntry 10 }
|
|
|
|
lgpPwrMeasurementPointVAPercent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 Percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the rated apparent AC power of the power
|
|
source indicated by 'lgpPwrMeasurementPointId' in the corresponding
|
|
row in the lgpPwrMeasurementPointTable."
|
|
::= { lgpPwrMeasurementPointEntry 11 }
|
|
|
|
lgpPwrMeasurementPointNeutralCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present neutral current of the power point indicated by
|
|
'lgpPwrMeasurementPointId' in the corresponding row in the
|
|
lgpPwrMeasurementPointTable."
|
|
::= { lgpPwrMeasurementPointEntry 12 }
|
|
|
|
lgpPwrMeasurementPointGroundCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present ground current of the power point indicated by
|
|
'lgpPwrMeasurementPointId' in the corresponding row in the
|
|
lgpPwrMeasurementPointTable."
|
|
::= { lgpPwrMeasurementPointEntry 13 }
|
|
|
|
lgpPwrMeasurementPointNomCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal or configured/expected current of the power point
|
|
indicated by 'lgpPwrMeasurementPointId' in the corresponding row
|
|
in the lgpPwrMeasurementPointTable."
|
|
::= { lgpPwrMeasurementPointEntry 14 }
|
|
|
|
lgpPwrMeasurementPointNomPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS ".01 Power Factor"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal or configured/expected power factor of the power point
|
|
indicated by 'lgpPwrMeasurementPointId' in the corresponding row
|
|
in the lgpPwrMeasurementPointTable."
|
|
::= { lgpPwrMeasurementPointEntry 15 }
|
|
|
|
lgpPwrMeasurementPointNomVA OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt-Amp"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal or configured/expected apparent AC power for the power
|
|
source indicated by 'lgpPwrMeasurementPointId' in the corresponding
|
|
row in the lgpPwrMeasurementPointTable."
|
|
::= { lgpPwrMeasurementPointEntry 16 }
|
|
|
|
lgpPwrMeasurementPointNomW OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Watt"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal or configured/expected true AC power for the power
|
|
source indicated by 'lgpPwrMeasurementPointId' in the corresponding
|
|
row in the lgpPwrMeasurementPointTable."
|
|
::= { lgpPwrMeasurementPointEntry 17 }
|
|
|
|
lgpPwrMeasurementPointPowerFactorTag OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
leading(1),
|
|
lagging(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present description of the Power Factor for the power source
|
|
indicated by 'lgpPwrMeasurementPointId' in the corresponding row
|
|
in the lgpPwrMeasurementPointTable. If Leading, the load is said
|
|
to be capacitive and the phase of the current leads the voltage.
|
|
If Lagging, the load is said to be inductive and the phase of the
|
|
current lags the voltage."
|
|
::= { lgpPwrMeasurementPointEntry 19 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
-- Source Measurement Line/Phase Table
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPwrLineMeasurementTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpPwrLineMeasurementEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of power measurements for each phase/line for a given
|
|
power measurement point/location in the 'lgpPwrMeasurementPointTable'.
|
|
The lgpPwrMeasurementPointIndex in this table corresponds to the
|
|
index in the lgpPwrMeasurementPointTable.
|
|
|
|
This table contains zero, one, or
|
|
many rows, depending upon the number of power line source objects
|
|
available. The NMS cannot create or delete rows from the table.
|
|
The rows are created by the agent based upon the capabilities of
|
|
the managed device."
|
|
::= { lgpPwrMeasurements 3 }
|
|
|
|
lgpPwrLineMeasurementEntry OBJECT-TYPE
|
|
SYNTAX LgpPwrLineMeasurementEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the contents of the columns for the table
|
|
'lgpPwrLineMeasurementTable'."
|
|
REFERENCE
|
|
"The lgpPwrMeasurementPointIndex can be found in the
|
|
lgpPwrMeasurementPointTable. This index identifies the measurement
|
|
point for which the line detail measurement in the table applies."
|
|
INDEX { lgpPwrMeasurementPtIndex, lgpPwrLineMeasurementIndex }
|
|
::= { lgpPwrLineMeasurementTable 1 }
|
|
|
|
LgpPwrLineMeasurementEntry ::= SEQUENCE
|
|
{
|
|
lgpPwrMeasurementPtIndex Unsigned32,
|
|
lgpPwrLineMeasurementIndex Unsigned32,
|
|
lgpPwrMeasurementPoint OBJECT IDENTIFIER,
|
|
lgpPwrLineMeasurementVoltsLL Integer32,
|
|
lgpPwrLineMeasurementVoltsLN Integer32,
|
|
lgpPwrLineMeasurementCurrent Integer32,
|
|
lgpPwrLineMeasurementCapacity Integer32,
|
|
lgpPwrLineMeasurementVA Integer32,
|
|
lgpPwrLineMeasurementTruePower Integer32,
|
|
lgpPwrLineMeasurementVoltageTHD Integer32,
|
|
lgpPwrLineMeasurementCurrentTHD Integer32,
|
|
lgpPwrLineMeasurementKFactorCurrent Integer32,
|
|
lgpPwrLineMeasurementCrestFactorCurrent Integer32,
|
|
lgpPwrLineMeasurementPowerFactor Integer32,
|
|
lgpPwrLineMeasurementPowerFactorTag INTEGER,
|
|
lgpPwrLineMeasurementMaxVolts Integer32,
|
|
lgpPwrLineMeasurementMinVolts Integer32,
|
|
lgpPwrLineMeasurementVAR Integer32,
|
|
lgpPwrLineMeasurementPercentLoad Integer32,
|
|
lgpPwrLineMeasurementVolts Integer32,
|
|
lgpPwrLineMeasurementVACapacity Integer32
|
|
}
|
|
|
|
lgpPwrMeasurementPtIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index indicating the row of the table
|
|
'lgpPwrMeasurementPointTable' for a power measurement point."
|
|
::= { lgpPwrLineMeasurementEntry 1 }
|
|
|
|
lgpPwrLineMeasurementIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index indicating the row of the table
|
|
'lgpPwrLineMeasurementTable' for a power measurement point."
|
|
::= { lgpPwrLineMeasurementEntry 2 }
|
|
|
|
lgpPwrMeasurementPoint OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An OID representing a well known measurement point.
|
|
These object identifiers indicate a point or location of power
|
|
measurement in a power system. The OID name usually
|
|
implies a location of the measurement point such as
|
|
'input', 'output', 'bypass', etc."
|
|
REFERENCE
|
|
"The object identifiers in this column can be found in the sub-tree
|
|
'lgpPwrWellKnownMeasurementPoints' and correspond to the entry in
|
|
the table lgpPwrMeasurementPointTable."
|
|
::= { lgpPwrLineMeasurementEntry 3 }
|
|
|
|
lgpPwrLineMeasurementVoltsLL OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present Line-to-Line voltage measurement for the indicated
|
|
source. The line being measured is given by the
|
|
lgpPwrLineMeasurementIndex [1 = AB, 2 = BC, 3 = CA]."
|
|
::= { lgpPwrLineMeasurementEntry 4 }
|
|
|
|
lgpPwrLineMeasurementVoltsLN OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present Line-to-neutral voltage measurement for the indicated
|
|
source. The line being measured is given by the
|
|
lgpPwrLineMeasurementIndex where [1 = A, 2 = B, 3 = C]."
|
|
::= { lgpPwrLineMeasurementEntry 5 }
|
|
|
|
lgpPwrLineMeasurementCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present current measurement for the indicated source. The line
|
|
being measured is given by the 'lgpPwrLineMeasurementIndex' where
|
|
[1 = A, 2 = B, 3 = C]."
|
|
::= { lgpPwrLineMeasurementEntry 6 }
|
|
|
|
lgpPwrLineMeasurementCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the power capacity presently being used on this
|
|
line."
|
|
::= { lgpPwrLineMeasurementEntry 7 }
|
|
|
|
lgpPwrLineMeasurementVA OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt-Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present apparent AC line power."
|
|
::= { lgpPwrLineMeasurementEntry 8 }
|
|
|
|
lgpPwrLineMeasurementTruePower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Watt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present AC line power measured in watts."
|
|
::= { lgpPwrLineMeasurementEntry 9 }
|
|
|
|
lgpPwrLineMeasurementVoltageTHD OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 Percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present total harmonic distortion on the AC line voltage."
|
|
::= { lgpPwrLineMeasurementEntry 10 }
|
|
|
|
lgpPwrLineMeasurementCurrentTHD OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 Percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present total harmonic distortion on the AC line current."
|
|
::= { lgpPwrLineMeasurementEntry 11 }
|
|
|
|
lgpPwrLineMeasurementKFactorCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 K Factor"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present line K Factor."
|
|
::= { lgpPwrLineMeasurementEntry 12 }
|
|
|
|
lgpPwrLineMeasurementCrestFactorCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 Crest Factor"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present crest factor of the line current."
|
|
::= { lgpPwrLineMeasurementEntry 13 }
|
|
|
|
lgpPwrLineMeasurementPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.01 Power Factor"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present Power Factor for the line."
|
|
::= { lgpPwrLineMeasurementEntry 14 }
|
|
|
|
lgpPwrLineMeasurementPowerFactorTag OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
leading(1),
|
|
lagging(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present description of the Power Factor for the line. If
|
|
Leading, the load is said to be capacitive and the phase of the
|
|
current leads the voltage. If Lagging, the load is said to be
|
|
inductive and the phase of the current lags the voltage."
|
|
::= { lgpPwrLineMeasurementEntry 15 }
|
|
|
|
lgpPwrLineMeasurementMaxVolts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum voltage measurement recorded for the indicated source
|
|
since the command 'lgpPwrStatisticsReset' was executed."
|
|
::= { lgpPwrLineMeasurementEntry 16 }
|
|
|
|
lgpPwrLineMeasurementMinVolts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum voltage measurement recorded for the
|
|
indicated source since the command 'lgpPwrStatisticsReset' was
|
|
executed."
|
|
::= { lgpPwrLineMeasurementEntry 17 }
|
|
|
|
lgpPwrLineMeasurementVAR OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt-Amp-Reactive"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present reactive AC line power of the power source indicated by
|
|
'lgpPwrMeasurementPoint'."
|
|
::= { lgpPwrLineMeasurementEntry 18 }
|
|
|
|
lgpPwrLineMeasurementPercentLoad OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present percent load of the AC line power."
|
|
::= { lgpPwrLineMeasurementEntry 19 }
|
|
|
|
lgpPwrLineMeasurementVolts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present voltage measurement for the indicated source."
|
|
::= { lgpPwrLineMeasurementEntry 20 }
|
|
|
|
lgpPwrLineMeasurementVACapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the apparent power capacity presently being
|
|
used on this line."
|
|
::= { lgpPwrLineMeasurementEntry 21 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
-- DC Power Measurement Point Table
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPwrDcMeasurementPointTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpPwrDcMeasurementPointEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains a list of DC power measurement point entries.
|
|
The table contains zero, one, or many rows, depending upon the number
|
|
of power related measurement points available. The NMS cannot
|
|
create or delete rows from the table. The rows are created by the
|
|
agent based upon the capabilities of the managed device. Each row
|
|
in the table represents a series of measurements on a given point
|
|
or location within the system. Measurement points/locations are
|
|
identified by the object identifier 'lgpPwrDcMeasurementPointId' in the
|
|
'LgpPwrDcMeasurementPointEntry' object. The actual measurement being
|
|
taken at that identified point is identified by the other
|
|
corresponding columns in the LgpPwrDcMeasurementPointEntry for the
|
|
particular row of the table."
|
|
REFERENCE
|
|
"The measurement points represented by 'lgpPwrDcMeasurementPointId'
|
|
can be found in the sub-tree lgpPwrWellKnownMeasurementPoints.
|
|
Additional measurement detail on a 'per line' basis is available in
|
|
the lgpPwrLineMeasurementTable"
|
|
::= { lgpPwrMeasurements 4 }
|
|
|
|
lgpPwrDcMeasurementPointEntry OBJECT-TYPE
|
|
SYNTAX LgpPwrDcMeasurementPointEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the measurements to be populated in the
|
|
various columns of the 'lgpPwrDcMeasurementPointTable'."
|
|
INDEX { lgpPwrDcMeasurementPointIndex }
|
|
::= { lgpPwrDcMeasurementPointTable 1 }
|
|
|
|
LgpPwrDcMeasurementPointEntry ::= SEQUENCE
|
|
{
|
|
lgpPwrDcMeasurementPointIndex Unsigned32,
|
|
lgpPwrDcMeasurementPointId OBJECT IDENTIFIER,
|
|
lgpPwrDcMeasurementPointSubID Integer32,
|
|
lgpPwrDcMeasurementPointVolts Integer32,
|
|
lgpPwrDcMeasurementPointCurrent Integer32,
|
|
lgpPwrDcMeasurementPointNomVolts Integer32,
|
|
lgpPwrDcMeasurementPointTruePower Integer32
|
|
}
|
|
|
|
lgpPwrDcMeasurementPointIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index that indicates the row of the
|
|
'lgpPwrMeasurementPointTable' for a power measurement point."
|
|
::= { lgpPwrDcMeasurementPointEntry 1 }
|
|
|
|
lgpPwrDcMeasurementPointId OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An OID representing a well known measurement point.
|
|
These object identifiers indicate a point or location of power
|
|
measurement in a power system. The OID's name usually
|
|
implies a location of the measurement point such as
|
|
'input', 'output', 'bypass' etc."
|
|
REFERENCE
|
|
"The object identifiers in this column can be found in the sub-tree
|
|
'lgpPwrWellKnownMeasurementPoints'."
|
|
::= { lgpPwrDcMeasurementPointEntry 2 }
|
|
|
|
lgpPwrDcMeasurementPointSubID OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The identifier used to differentiate between identical thresholds
|
|
for a given point index and point ID in the DC measurements table."
|
|
::= { lgpPwrDcMeasurementPointEntry 3 }
|
|
|
|
lgpPwrDcMeasurementPointVolts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present DC voltage for the power source indicated by
|
|
'lgpPwrDcMeasurementPointId' in the corresponding row in the
|
|
lgpPwrDcMeasurementPointTable."
|
|
::= { lgpPwrDcMeasurementPointEntry 4 }
|
|
|
|
lgpPwrDcMeasurementPointCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present DC current for the power source indicated by
|
|
'lgpPwrDcMeasurementPointId' in the corresponding row in the
|
|
lgpPwrDcMeasurementPointTable."
|
|
::= { lgpPwrDcMeasurementPointEntry 5 }
|
|
|
|
lgpPwrDcMeasurementPointNomVolts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal(configured/expected) DC voltage for the power source
|
|
indicated by 'lgpPwrDcMeasurementPointId' in the
|
|
corresponding row in the lgpPwrDcMeasurementPointTable."
|
|
::= { lgpPwrDcMeasurementPointEntry 6 }
|
|
|
|
lgpPwrDcMeasurementPointTruePower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Watt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present DC power for the power source indicated by
|
|
'lgpPwrDcMeasurementPointId' in the corresponding row in the
|
|
lgpPwrDcMeasurementPointTable."
|
|
::= { lgpPwrDcMeasurementPointEntry 7 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
-- Well Known Power Measurement Types
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPwrWellKnownMeasurementTypes OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree registers well known Liebert Power Measurement
|
|
Types. The object identifier names usually encompass units of
|
|
measure, lines of reference, and device location. The OID's
|
|
name usually implies a measurement type such as 'voltsAC',
|
|
'current', 'voltsDc', 'VoltsLL', etc."
|
|
::= { lgpPwrMeasurements 5 }
|
|
|
|
lgpPwrVoltsAc OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents an AC voltage."
|
|
::= { lgpPwrWellKnownMeasurementTypes 1 }
|
|
|
|
lgpPwrVoltsDc OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents a DC voltage."
|
|
::= { lgpPwrWellKnownMeasurementTypes 2 }
|
|
|
|
lgpPwrAmpsNeutral OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier represents a current measurement in Amps on the
|
|
neutral line."
|
|
::= { lgpPwrWellKnownMeasurementTypes 3 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
-- lgpPwrControl - Liebert Control Group
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPwrWellKnownControlPoints OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This sub-tree registers well known Liebert Power Control
|
|
Points. The object identifier names usually imply locations
|
|
where control of a device is available -- such 'output' or
|
|
'load circuits'."
|
|
REFERENCE
|
|
"These well known control identifiers are referenced in the
|
|
'lgpPwrLoadCircuitId' column in the
|
|
'lgpPwrLoadCircuitTable'."
|
|
::= { lgpPwrControl 1 }
|
|
|
|
lgpPwrLoadCircuit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The managed device's controllable load circuit.
|
|
Many power systems contain more than one load circuit.
|
|
This identifier represents one load circuit for the
|
|
system but does not necessarily represent the 'first' one.
|
|
The load circuits' numbering with respect to
|
|
'lgpPwrLoadCircuit1' etc. may depend on the physical wiring
|
|
of the system when it was installed."
|
|
::= { lgpPwrWellKnownControlPoints 1 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
-- Load Circuit Table
|
|
-- -----------------------------------------------------------------------------
|
|
lgpPwrLoadCircuitTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpPwrLoadCircuitEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of load circuits that can be controlled(opened or closed).
|
|
The NMS cannot create or delete rows from the table.
|
|
The rows are created by the agent based upon the capabilities of
|
|
the managed device."
|
|
::= { lgpPwrControl 2 }
|
|
|
|
lgpPwrLoadCircuitEntry OBJECT-TYPE
|
|
SYNTAX LgpPwrLoadCircuitEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the contents of the columns for the table
|
|
'lgpPwrLoadCircuitTable'."
|
|
INDEX { lgpPwrLoadCircuitIndex }
|
|
::= { lgpPwrLoadCircuitTable 1 }
|
|
|
|
LgpPwrLoadCircuitEntry ::= SEQUENCE
|
|
{
|
|
lgpPwrLoadCircuitIndex Unsigned32,
|
|
lgpPwrLoadCircuitId OBJECT IDENTIFIER,
|
|
lgpPwrLoadCircuitSubID Unsigned32,
|
|
lgpPwrLoadCircuitState INTEGER,
|
|
lgpPwrLoadCircuitStateAndControl INTEGER
|
|
|
|
}
|
|
|
|
lgpPwrLoadCircuitIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index indicating the row of the table
|
|
'lgpPwrLoadCircuitTable'."
|
|
::= { lgpPwrLoadCircuitEntry 1 }
|
|
|
|
lgpPwrLoadCircuitId OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An OID representing a well known load circuit identifier.
|
|
These load circuit identifiers indicate the name or type of load
|
|
circuit reference in the table."
|
|
REFERENCE
|
|
"The object identifiers in this column can be found in the sub-tree
|
|
'lgpPwrWellKnownMeasurementPoints'."
|
|
::= { lgpPwrLoadCircuitEntry 2 }
|
|
|
|
lgpPwrLoadCircuitSubID OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a sub identifier for the 'lgpPwrLoadCircuitId'.
|
|
It indicates the hardware identifier of the load control circuit."
|
|
::= { lgpPwrLoadCircuitEntry 3 }
|
|
|
|
lgpPwrLoadCircuitState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2),
|
|
default(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier indicates the state of the load circuit.
|
|
When read, only a closed or open response will be returned.
|
|
When written to, the state of the circuit will transition to
|
|
desired state."
|
|
::= { lgpPwrLoadCircuitEntry 4 }
|
|
|
|
lgpPwrLoadCircuitStateAndControl OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
off(0),
|
|
on(1),
|
|
reboot(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This identifier indicates the state of the load circuit.
|
|
When read, only a closed or open response will be returned.
|
|
When written to, the state of the circuit will transition to
|
|
desired state."
|
|
::= { lgpPwrLoadCircuitEntry 5 }
|
|
|
|
lgpPwrAlarmSilence OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Audible Alarm Silence Command. This command turns off the device's
|
|
audible alarm. It will not affect the status of the alarm(s) that
|
|
caused the audible alarm. This command should be sent with a
|
|
parameter of 1. This variable doesn't return a value when read."
|
|
::= { lgpPwrControl 3 }
|
|
|
|
lgpPwrBatteryTest OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
start(1),
|
|
abort(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery Test Command. This command will initiate a battery test if
|
|
one is not already in progress, or abort the current test if it is in
|
|
progress."
|
|
::= { lgpPwrControl 4 }
|
|
|
|
lgpPwrUpsAbortCommand OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"UPS Abort command. This command will abort the pending command on the
|
|
device. There is no guarantee a client using the abort command will
|
|
cancel a command sent moments before from the same client.
|
|
Another client could initiate a command and change what command is
|
|
actually pending on the device. This command should be sent with a
|
|
parameter of 1. This variable doesn't return a value when read."
|
|
::= { lgpPwrControl 5 }
|
|
|
|
lgpPwrTransferToBypass OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Transfer to Bypass Command. This command will initiate a transfer of
|
|
the load to the bypass of the system. This command should be sent with a
|
|
parameter of 1. This variable doesn't return a value when read."
|
|
::= { lgpPwrControl 6 }
|
|
|
|
lgpPwrTransferToInverter OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Transfer to Inverter Command. This command will initiate a transfer
|
|
of the load to the inverter of the system. This command should be sent
|
|
with a parameter of 1. This variable doesn't return a value when read."
|
|
::= { lgpPwrControl 7 }
|
|
|
|
lgpPwrOutputOnDelay OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output On Delay Command. This command will turn on the output of the
|
|
device after a user specified delay. The number of seconds to delay
|
|
is subject to the precision of the device and should be kept to 10
|
|
second intervals."
|
|
::= { lgpPwrControl 8 }
|
|
|
|
lgpPwrOutputOffDelayWithRestart OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output Off Delay with Restart Command. This command will turn off the
|
|
output of the device after a user specified delay. The number
|
|
of seconds to delay is subject to the precision of the device and
|
|
should be kept to 10 second intervals. The device will then
|
|
turn the output on again after a specified amount of time. "
|
|
::= { lgpPwrControl 9 }
|
|
|
|
lgpPwrOutputOffDelayWithoutRestart OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output Off Delay without Restart Command. This command will turn off
|
|
the output of the device after a specified delay. The number of seconds
|
|
to delay is subject to the precision of the device and should be kept
|
|
to 10 second intervals. The device will NOT automatically turn the
|
|
output on following this command."
|
|
::= { lgpPwrControl 10 }
|
|
|
|
-- =============================================================================
|
|
-- lgpPwrStatus - Liebert Power Status Group
|
|
-- =============================================================================
|
|
|
|
lgpPwrTransferCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of times that the output load has been transferred between the
|
|
available input sources."
|
|
::= { lgpPwrStatus 1 }
|
|
|
|
lgpPwrAutoTransferTimer OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The required wait time between output load auto transfer attempts
|
|
between available input sources."
|
|
::= { lgpPwrStatus 2 }
|
|
|
|
lgpPwrAutoReTransferEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
no (0),
|
|
yes (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ability to retransfer the output load automatically to the well
|
|
known measurement source from the 'lgpPwrWellKnownMeasurements'
|
|
sub-tree that is the preferred input source of the system"
|
|
::= { lgpPwrStatus 3 }
|
|
|
|
lgpPwrSyncPhaseAngle OBJECT-TYPE
|
|
SYNTAX Integer32(-3600..3600)
|
|
UNITS "0.1 Degrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The phase angle difference of source 1 in relation to source 2."
|
|
::= { lgpPwrStatus 4 }
|
|
|
|
lgpPwrParallelSystemOutputToLoadSource OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
unknown (0),
|
|
utility (1),
|
|
battery (2),
|
|
bypass (3),
|
|
none (4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The source supporting the parallel system's load."
|
|
::= { lgpPwrStatus 5 }
|
|
|
|
lgpPwrDcToDcConverter OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the DC to DC converter."
|
|
::= { lgpPwrStatus 6 }
|
|
|
|
lgpPwrOutputToLoadOnInverter OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present source of output power is the Inverter."
|
|
::= { lgpPwrStatus 7 }
|
|
|
|
lgpPwrBatteryChargeCompensating OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is adjusting the battery charging algorithm to accommodate
|
|
for the battery temperature."
|
|
::= { lgpPwrStatus 8 }
|
|
|
|
lgpPwrInverterReady OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ability of the inverter to support the output load of the system."
|
|
::= { lgpPwrStatus 9 }
|
|
|
|
lgpPwrOutputToLoadOnBypass OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present source of output power is the Bypass."
|
|
::= { lgpPwrStatus 10 }
|
|
|
|
lgpPwrBoost OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the boost circuitry"
|
|
::= { lgpPwrStatus 11 }
|
|
|
|
lgpPwrBuck OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of the buck circuitry"
|
|
::= { lgpPwrStatus 12 }
|
|
|
|
lgpPwrShutdownOverTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has previously shutdown due to an over temperature
|
|
condition."
|
|
::= { lgpPwrStatus 13 }
|
|
|
|
lgpPwrShutdownOverload OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has previously shutdown due to an over load condition."
|
|
::= { lgpPwrStatus 14 }
|
|
|
|
lgpPwrShutdownDcBusOverload OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has previously shutdown due to a DC bus over load
|
|
condition."
|
|
::= { lgpPwrStatus 15 }
|
|
|
|
lgpPwrShutdownOutputShort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has previously shutdown due to an output short condition."
|
|
::= { lgpPwrStatus 16 }
|
|
|
|
lgpPwrShutdownLineSwap OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has previously shutdown due to a condition where the line
|
|
and neutral were reversed."
|
|
::= { lgpPwrStatus 17 }
|
|
|
|
lgpPwrShutdownLowBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has previously shutdown due to a low battery condition."
|
|
::= { lgpPwrStatus 18 }
|
|
|
|
lgpPwrShutdownRemote OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has previously shutdown due to a remote shutdown command."
|
|
::= { lgpPwrStatus 19 }
|
|
|
|
lgpPwrShutdownInputUnderVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has previously shutdown due to an under voltage condition
|
|
during startup."
|
|
::= { lgpPwrStatus 20 }
|
|
|
|
lgpPwrShutdownPowerFactorCorrectionFailure OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has previously shutdown due to a power factor correction
|
|
startup failure."
|
|
::= { lgpPwrStatus 21 }
|
|
|
|
lgpPwrShutdownHardware OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has previously shutdown due external shutdown signal."
|
|
::= { lgpPwrStatus 22 }
|
|
|
|
lgpPwrRedundantSubModule OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has a redundant battery module installed."
|
|
::= { lgpPwrStatus 23 }
|
|
|
|
lgpPwrBypassReady OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ability of the bypass to support the output load of the system.
|
|
If Yes, the bypass is available to transfer to."
|
|
::= { lgpPwrStatus 24 }
|
|
|
|
lgpPwrGeneratorStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
connected(1),
|
|
disconnected(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the system generator."
|
|
::= { lgpPwrStatus 25 }
|
|
|
|
lgpPwrRotaryBreakerStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
unknown(1),
|
|
closed(2),
|
|
test(3),
|
|
normal(4),
|
|
bypass(5),
|
|
maintenance(6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the system rotary breaker."
|
|
::= { lgpPwrStatus 26 }
|
|
|
|
lgpPwrPowerFactorCorrection OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the power factor correction circuitry of the system."
|
|
::= { lgpPwrStatus 27 }
|
|
|
|
lgpPwrBypassSyncDiff OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 Degrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The phase angle difference between the inverter output and bypass
|
|
source. A positive value means the inverter leads the bypass source.
|
|
A negative value means the inverter lags the bypass source."
|
|
::= { lgpPwrStatus 28 }
|
|
|
|
lgpPwrBypassOverloadShutdownTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The calculated time remaining before bypass static switch shutdown due
|
|
to the present overload condition. If the bypass is not in an overload
|
|
condition, this object returns -1."
|
|
::= { lgpPwrStatus 29 }
|
|
|
|
lgpPwrInverterOverloadShutdownTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The calculated time remaining before inverter shutdown. The calculated
|
|
time of inverter operation remaining for the present overload event.
|
|
|
|
Note: If the inverter is not experiencing an overload event this point
|
|
will return 65535 indicating this value is unavailable."
|
|
::= { lgpPwrStatus 30 }
|
|
|
|
lgpPwrStateOutputSource OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
none(1),
|
|
inverter(2),
|
|
bypass(3),
|
|
maintenanceBypass(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS's output power source (inverter, bypass, or none).
|
|
NOTE: It is possible that the load still has power from the
|
|
Maintenance Bypass."
|
|
::= { lgpPwrStatus 31 }
|
|
|
|
lgpPwrStateInputSource OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
none(1),
|
|
utility(2),
|
|
generator(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system input power source (none, utility, generator)."
|
|
::= { lgpPwrStatus 32 }
|
|
|
|
lgpPwrStateInputQualification OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
fail(1),
|
|
marginalLow(2),
|
|
normal(3),
|
|
marginalHigh(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current state of the system input. The unit may or may not operate
|
|
normally under 'marginalLow' and 'marginalHigh' states."
|
|
::= { lgpPwrStatus 33 }
|
|
|
|
lgpPwrStateBypassStaticSwitchState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current state of the bypass static switch."
|
|
::= { lgpPwrStatus 34 }
|
|
|
|
lgpPwrStateBypassQualification OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
fail(1),
|
|
marginalLow(2),
|
|
normal(3),
|
|
marginalHigh(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current operational state of the bypass static switch. The unit may
|
|
or may not operate normally under 'marginalLow' and 'marginalHigh'
|
|
states."
|
|
::= { lgpPwrStatus 35 }
|
|
|
|
lgpPwrStateDCBusQualification OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
fail(1),
|
|
marginalLow(2),
|
|
normal(3),
|
|
marginalHigh(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current operational state of the DC bus. The unit may or may not
|
|
operate normally under 'marginalLow' and 'marginalHigh' states."
|
|
::= { lgpPwrStatus 36 }
|
|
|
|
lgpPwrStateOutQualification OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
fail(1),
|
|
marginalLow(2),
|
|
normal(3),
|
|
marginalHigh(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current operational state of the output. The unit may or may not
|
|
operate normally under 'marginalLow' and 'marginalHigh' states."
|
|
::= { lgpPwrStatus 37 }
|
|
|
|
lgpPwrStateInverterQualification OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
fail(1),
|
|
marginalLow(2),
|
|
normal(3),
|
|
marginalHigh(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current operational state of the inverter. The unit may or may not
|
|
operate normally under 'marginalLow' and 'marginalHigh' states."
|
|
::= { lgpPwrStatus 38 }
|
|
|
|
lgpPwrStateInverterState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current state of the inverter."
|
|
::= { lgpPwrStatus 39 }
|
|
|
|
lgpPwrStateRectifierState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current state of the rectifier."
|
|
::= { lgpPwrStatus 40 }
|
|
|
|
lgpPwrStateModuleGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This group contains UPS module information."
|
|
::= { lgpPwrStatus 41 }
|
|
|
|
lgpPwrStateUpsModuleCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of UPS modules in the system. In a single module system, this
|
|
value is one."
|
|
::= { lgpPwrStateModuleGroup 1 }
|
|
|
|
lgpPwrStateUpsModuleRedundantCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of redundant UPS modules in the system. In a single module
|
|
system, the value is zero. This value is dependent upon the present
|
|
load and the number of modules (i.e. the value may change during normal
|
|
operation based upon a load change). This value represents the number
|
|
of extra modules above the minimum needed to support the load."
|
|
::= { lgpPwrStateModuleGroup 2 }
|
|
|
|
lgpPwrStateBackfeedBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the Static Bypass Switch Line Disconnect Breaker."
|
|
::= { lgpPwrStatus 42 }
|
|
|
|
lgpPwrStateLoadDisconnectState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the Static Bypass Switch Load Disconnect Breaker."
|
|
::= { lgpPwrStatus 43 }
|
|
|
|
lgpPwrStateInputBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the Input Disconnect Breaker."
|
|
::= { lgpPwrStatus 44 }
|
|
|
|
lgpPwrStateTrapFilterBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the Trap Filter Disconnect Breaker."
|
|
::= { lgpPwrStatus 45 }
|
|
|
|
lgpPwrStateInvOutputBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the Inverter Output Disconnect Breaker."
|
|
::= { lgpPwrStatus 46 }
|
|
|
|
lgpPwrStateIntBypassBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the Internal Bypass Breaker."
|
|
::= { lgpPwrStatus 47 }
|
|
|
|
lgpPwrStateBypassIsolBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the Bypass Isolation Breaker."
|
|
::= { lgpPwrStatus 48 }
|
|
|
|
lgpPwrStateRectifierIsolBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the Rectifier Isolation Breaker."
|
|
::= { lgpPwrStatus 49 }
|
|
|
|
lgpPwrStateMaintBypassBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the Maintenance Bypass Breaker."
|
|
::= { lgpPwrStatus 50 }
|
|
|
|
lgpPwrStateMaintIsolBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the Maintenance Isolation Breaker."
|
|
::= { lgpPwrStatus 51 }
|
|
|
|
lgpPwrStateOutStaticSwState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
off(1),
|
|
on(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the Output Series Static Switch."
|
|
::= { lgpPwrStatus 52 }
|
|
|
|
lgpPwrStateModuleOutBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the Module Output Breaker."
|
|
::= { lgpPwrStatus 53 }
|
|
|
|
lgpPwrBypassReXfrRemainTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The time remaining before an inverter overload or inverter fault can
|
|
be cleared and auto retransfer from the bypass to the inverter can take
|
|
place.
|
|
|
|
Note: If an inverter overload or fault is not taking place, this point
|
|
will return 65535."
|
|
::= { lgpPwrStatus 54 }
|
|
|
|
lgpPwrStateUpsOutputSource OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
other(1),
|
|
none(2),
|
|
normal(3),
|
|
bypass(4),
|
|
battery(5),
|
|
booster(6),
|
|
reducer(7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present source of output power. The enumeration
|
|
none(2) indicates that there is no source of output
|
|
power (and therefore no output power), for example,
|
|
the system has opened the output breaker.
|
|
|
|
NOTE: In a single-module system, this point is intended to have the same
|
|
behavior as the RFC1628 point upsOutputSource."
|
|
::= { lgpPwrStatus 55 }
|
|
|
|
lgpPwrStateLoadBusSynchronization OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
unknown(0),
|
|
active(1),
|
|
abnormal(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The state of the Load Bus Synchronizer (LBS)."
|
|
::= { lgpPwrStatus 56 }
|
|
|
|
lgpPwrStateCircuitBrkrStateGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This group contains Static Switch circuit breaker state information."
|
|
::= { lgpPwrStatus 57 }
|
|
|
|
lgpPwrStateSource1InputBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The states of Source 1 Input Breaker."
|
|
::= { lgpPwrStateCircuitBrkrStateGroup 1 }
|
|
|
|
lgpPwrStateSource2InputBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The states of Source 2 Input Breaker."
|
|
::= { lgpPwrStateCircuitBrkrStateGroup 2 }
|
|
|
|
lgpPwrStateSource1BypassBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The states of Source 1 Bypass Breaker."
|
|
::= { lgpPwrStateCircuitBrkrStateGroup 3 }
|
|
|
|
lgpPwrStateSource2BypassBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The states of Source 2 Bypass Breaker."
|
|
::= { lgpPwrStateCircuitBrkrStateGroup 4 }
|
|
|
|
lgpPwrStateOutputBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The states of Output Breaker."
|
|
::= { lgpPwrStateCircuitBrkrStateGroup 5 }
|
|
|
|
lgpPwrStateAuxOutputBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The states of Auxiliary Output Breaker."
|
|
::= { lgpPwrStateCircuitBrkrStateGroup 6 }
|
|
|
|
lgpPwrStateSource1PduInputBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The states of Source 1 PDU Input Breaker."
|
|
::= { lgpPwrStateCircuitBrkrStateGroup 7 }
|
|
|
|
lgpPwrStateSource2PduInputBrkrState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
open(1),
|
|
closed(2),
|
|
notInstalled(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The states of Source 2 PDU Input Breaker."
|
|
::= { lgpPwrStateCircuitBrkrStateGroup 8 }
|
|
|
|
lgpPwrEconomicOperation OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of ECO mode operation,
|
|
on(1) if system is on bypass due to ECO mode operation,
|
|
off(0) any other time."
|
|
::= { lgpPwrStatus 58 }
|
|
|
|
-- =============================================================================
|
|
-- lgpPwrSettings - Liebert Power Settings Group
|
|
-- =============================================================================
|
|
|
|
lgpPwrPreferredSource OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The well known measurement source from the
|
|
'lgpPwrWellKnownMeasurements' sub-tree that is the preferred
|
|
input source of the system."
|
|
::= { lgpPwrSettings 1 }
|
|
|
|
lgpPwrLoadOnSource OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The well known measurement source from the
|
|
'lgpPwrWellKnownMeasurements' sub-tree that is currently
|
|
powering the output (load)."
|
|
::= { lgpPwrSettings 2 }
|
|
|
|
lgpPwrNominalVoltageDeviation OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal voltage deviation between the well known
|
|
measurement source lgpPwrSource1Input and lgpPwrSource2Input."
|
|
::= { lgpPwrSettings 3 }
|
|
|
|
lgpPwrNominalVoltageDeviationPercent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the nominal voltage deviation between the well known
|
|
measurement source lgpPwrSource1Input and lgpPwrSource2Input."
|
|
::= { lgpPwrSettings 4 }
|
|
|
|
lgpPwrPhaseDifferenceLimit OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 Degrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum phase difference (between the well known
|
|
input sources ) in which a transfer to an available input source is
|
|
permitted."
|
|
::= { lgpPwrSettings 5 }
|
|
|
|
lgpPwrFrequencyDeviationLimit OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum frequency deviation (between the well known
|
|
input sources ) in which a transfer to an available input source is
|
|
permitted."
|
|
::= { lgpPwrSettings 6 }
|
|
|
|
-- -----------------------------------------------------------------------------
|
|
-- Thresholds Table
|
|
-- -----------------------------------------------------------------------------
|
|
|
|
lgpPwrThresholdTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpPwrThresholdEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of power thresholds for a given power measurement at a
|
|
point/location in the system.
|
|
The lgpPwrThresholdType in this table corresponds to the
|
|
type of measurement the high and low thresholds applies to.
|
|
|
|
This table contains zero, one, or many rows, depending upon the number
|
|
of 'lgpPwrThresholdPoint' and 'lgpPwrThresholdSubID' available in the
|
|
table.
|
|
The NMS cannot create or delete rows from the table.
|
|
The rows are created by the agent based upon the capabilities of
|
|
the managed device."
|
|
::= { lgpPwrSettings 7 }
|
|
|
|
lgpPwrThresholdEntry OBJECT-TYPE
|
|
SYNTAX LgpPwrThresholdEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the contents of the columns for the table
|
|
'lgpPwrThresholdTable'."
|
|
REFERENCE
|
|
"The lgpPwrThresholdType in this table corresponds to the
|
|
type of measurement the high and low thresholds applies to."
|
|
INDEX { lgpPwrThresholdIndex }
|
|
::= { lgpPwrThresholdTable 1 }
|
|
|
|
LgpPwrThresholdEntry ::= SEQUENCE
|
|
{
|
|
lgpPwrThresholdIndex Unsigned32,
|
|
lgpPwrThresholdPoint OBJECT IDENTIFIER,
|
|
lgpPwrThresholdSubID Unsigned32,
|
|
lgpPwrThresholdType OBJECT IDENTIFIER,
|
|
lgpPwrThresholdHighWarning Integer32,
|
|
lgpPwrThresholdHighFailure Integer32,
|
|
lgpPwrThresholdLowWarning Integer32,
|
|
lgpPwrThresholdLowFailure Integer32
|
|
}
|
|
|
|
lgpPwrThresholdIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index indicating the row of the table
|
|
'lgpPwrLineMeasurementTable' for a power measurement point."
|
|
::= { lgpPwrThresholdEntry 1 }
|
|
|
|
lgpPwrThresholdPoint OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An OID representing a well known measurement point.
|
|
These object identifiers indicate a point or location of power
|
|
measurement in a power system. The OID's name usually
|
|
implies a location of the measurement point such as
|
|
'input', 'output', 'bypass' etc."
|
|
REFERENCE
|
|
"The object identifiers in this column can be found in the sub-tree
|
|
'lgpPwrWellKnownMeasurementPoints' and correspond to the
|
|
entry in the table 'lgpPwrThresholdTable'."
|
|
::= { lgpPwrThresholdEntry 2 }
|
|
|
|
lgpPwrThresholdSubID OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a sub identifier for the 'lgpPwrThresholdPoint'.
|
|
It indicates the instance number of the well known threshold point."
|
|
::= { lgpPwrThresholdEntry 3 }
|
|
|
|
lgpPwrThresholdType OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An OID representing a well known measurement type.
|
|
These object identifiers indicate the type of measurement referenced
|
|
by the row of the table. These object identifiers can encompass
|
|
units of measure, lines of reference, and device location.
|
|
The OID's name usually implies a measurement type such as
|
|
'voltsAc', 'current', 'voltsDc', 'VoltsLL', etc."
|
|
REFERENCE
|
|
"The object identifiers in this column can be found in the sub-tree
|
|
'lgpPwrWellKnownThresholdTypes' and correspond to the
|
|
entry in the table lgpPwrThresholdTable."
|
|
::= { lgpPwrThresholdEntry 4 }
|
|
|
|
lgpPwrThresholdHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high warning threshold of a type of measurement designated by
|
|
the 'lgpPwrThresholdType' at a location designated by the
|
|
'lgpPwrThresholdPoint'. If multiple thresholds are available at a
|
|
single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType',
|
|
then the 'lgpPwrThresholdSubID' will differentiate between them.
|
|
When this threshold is met, the agent will send a notification."
|
|
::= { lgpPwrThresholdEntry 5 }
|
|
|
|
lgpPwrThresholdHighFailure OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high failure threshold of a type of measurement designated by
|
|
the 'lgpPwrThresholdType' at a location designated by the
|
|
'lgpPwrThresholdPoint'. If multiple thresholds are available at a
|
|
single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType',
|
|
then the 'lgpPwrThresholdSubID' will differentiate between them.
|
|
When this threshold is met, the agent will send a notification."
|
|
::= { lgpPwrThresholdEntry 6 }
|
|
|
|
lgpPwrThresholdLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low warning threshold of a type of measurement designated by
|
|
the 'lgpPwrThresholdType' at a location designated by the
|
|
'lgpPwrThresholdPoint'. If multiple thresholds are available at a
|
|
single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType',
|
|
then the 'lgpPwrThresholdSubID' will differentiate between them.
|
|
When this threshold is met, the agent will send a notification."
|
|
::= { lgpPwrThresholdEntry 7 }
|
|
|
|
lgpPwrThresholdLowFailure OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low failure threshold of a type of measurement designated by
|
|
the 'lgpPwrThresholdType' at a location designated by the
|
|
'lgpPwrThresholdPoint'. If multiple thresholds are available at a
|
|
single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType',
|
|
then the 'lgpPwrThresholdSubID' will differentiate between them.
|
|
When this threshold is met, the agent will send a notification."
|
|
::= { lgpPwrThresholdEntry 8 }
|
|
|
|
lgpPwrUpsAutoRestart OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The device will automatically restart when utility power is restored
|
|
following a battery discharge."
|
|
::= { lgpPwrSettings 8 }
|
|
|
|
lgpPwrUpsAutoRestartDelay OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The device will automatically delay a certain number of seconds and
|
|
then restart after utility power is restored following a battery
|
|
discharge. The number of seconds to delay is subject to the precision
|
|
of the device and should be kept to 10 second intervals."
|
|
::= { lgpPwrSettings 9 }
|
|
|
|
lgpPwrAutoRestartBatteryChargeThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery charge percentage required before the device can
|
|
automatically restart."
|
|
::= { lgpPwrSettings 10 }
|
|
|
|
lgpPwrParallelModuleCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of modules in the parallel system."
|
|
::= { lgpPwrSettings 11 }
|
|
|
|
lgpPwrParallelRedundancyCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of redundant modules in the parallel system."
|
|
::= { lgpPwrSettings 12 }
|
|
|
|
lgpPwrLoadBusSyncMode OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
master(1),
|
|
slave(2),
|
|
none(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The configuration of Load Bus Synchronization (LBS) between
|
|
independent systems."
|
|
::= { lgpPwrSettings 13 }
|
|
|
|
lgpPwrEconomicOperationMode OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The configuration of the economic operation mode of the system."
|
|
::= { lgpPwrSettings 14 }
|
|
|
|
lgpPwrAutomaticBatteryTest OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatic battery test option. If enabled, the battery will be tested
|
|
on a fixed interval. If disabled, the battery test must be initiated
|
|
by a battery test command. The interval at which a battery test is
|
|
performed is defined by 'lgpPwrAutomaticBatteryTestInterval'."
|
|
::= { lgpPwrSettings 15 }
|
|
|
|
lgpPwrMinimumRedundantPowerModule OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum number of redundant power modules that must be present
|
|
before sending a loss of power redundancy alarm. If 0, there is no
|
|
redundant power functionality."
|
|
::= { lgpPwrSettings 16 }
|
|
|
|
lgpPwrMinimumRedundantBatteryModule OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum number of redundant battery modules that must be present
|
|
before sending an alarm. If 0, the redundant battery module alarm is
|
|
disabled."
|
|
::= { lgpPwrSettings 17 }
|
|
|
|
lgpPwrOutputToLoadUserOverloadLimit OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt-Amp"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the user specified maximum load the device can support
|
|
without sending an alarm."
|
|
::= { lgpPwrSettings 18 }
|
|
|
|
lgpPwrNoLoadWarningLimit OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Amp"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum current draw on the output in which the device considers
|
|
there to be a load present on the output. The condition
|
|
lgpConditionWarningNoLoadDetected will be triggered if the output
|
|
current falls below this value. If this value is '-1' then the
|
|
lgpConditionNoLoadDetectedWarning condition is 'disabled'."
|
|
::= { lgpPwrSettings 19 }
|
|
|
|
lgpPwrNoLoadWarningDelay OBJECT-TYPE
|
|
SYNTAX Integer32(0..10000)
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of time to delay before annunciation of the condition
|
|
lgpConditionNoLoadDetectedWarning after the output current load
|
|
falls below the threshold lgpPwrOutputNoLoadWarningLimit."
|
|
::= { lgpPwrSettings 20 }
|
|
|
|
lgpPwrEconomicOperationModeControl OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disabled(0),
|
|
mode1(1),
|
|
mode2(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The configuration of the economic operation mode of the system.
|
|
Note that this supersedes lgpPwrEconomicOperationMode in newer devices."
|
|
::= { lgpPwrSettings 21 }
|
|
|
|
-- =============================================================================
|
|
-- lgpPwrStatistic - Liebert Power Statistic Group
|
|
-- =============================================================================
|
|
lgpPwrBrownOutCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of occurrences where the input line voltage has fallen below
|
|
a pre-determined threshold for a specified amount of time. This number
|
|
resets when the command 'lgpPwrStatisticsReset' is executed."
|
|
::= { lgpPwrStatistic 1 }
|
|
|
|
lgpPwrBlackOutCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of occurrences where there is a total loss of electric power.
|
|
This number resets when the command 'lgpPwrStatisticsReset' is
|
|
executed."
|
|
::= { lgpPwrStatistic 2 }
|
|
|
|
lgpPwrTransientCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of occurrences where the input line voltage spikes above a
|
|
pre-determined threshold for a specified amount of time. This number
|
|
resets when the command 'lgpPwrStatisticsReset' is executed."
|
|
::= { lgpPwrStatistic 3 }
|
|
|
|
lgpPwrBatteryDischargeCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of battery discharges since the last reset."
|
|
::= { lgpPwrStatistic 4 }
|
|
|
|
lgpPwrBatteryDischargeTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total accumulated time spent on battery since the last reset."
|
|
::= { lgpPwrStatistic 5 }
|
|
|
|
lgpPwrBatteryAmpHours OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Amp-hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total accumulated Amp-hours removed from the battery since last
|
|
reset."
|
|
::= { lgpPwrStatistic 6 }
|
|
|
|
lgpPwrBatteryWattHours OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Watt-Hour"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total accumulated Watt-Hours removed from the battery since last
|
|
reset. This command should be sent with a parameter of 1. This
|
|
variable doesn't return a value when read."
|
|
::= { lgpPwrStatistic 7 }
|
|
|
|
lgpPwrBatteryStatisticsReset OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery statistics clear command. The command to reset all battery
|
|
statistics stored by the device. This command should be sent with a
|
|
parameter of 1. This variable doesn't return a value when read."
|
|
::= { lgpPwrStatistic 8 }
|
|
|
|
lgpPwrStatisticsReset OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reset Power Statistics Command. This command will reset the power
|
|
statistics stored in the system. This command should be sent with a
|
|
parameter of 1. This variable doesn't return a value when read."
|
|
::= { lgpPwrStatistic 9 }
|
|
|
|
-- =============================================================================
|
|
-- lgpPwrConversion - Liebert Power Conversion Group
|
|
-- =============================================================================
|
|
|
|
lgpPwrNumberInstalledPowerModules OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of power modules installed in the device."
|
|
::= { lgpPwrConversion 1 }
|
|
|
|
lgpPwrNumberFailedPowerModules OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of power modules in the device that have failed."
|
|
::= { lgpPwrConversion 2 }
|
|
|
|
lgpPwrNumberRedundantPowerModules OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of redundant power modules installed in the device."
|
|
::= { lgpPwrConversion 3 }
|
|
|
|
lgpPwrNumberActivePowerModules OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of active power modules in the device."
|
|
::= { lgpPwrConversion 4 }
|
|
|
|
lgpPwrNumberPowerModuleWarnings OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Count"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of power modules in the device that have a warning."
|
|
::= { lgpPwrConversion 6 }
|
|
|
|
lgpPwrUpsInverterStandby OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output to the load is supported by the bypass and the inverter is
|
|
on standby."
|
|
::= { lgpPwrConversion 7 }
|
|
|
|
-- =============================================================================
|
|
-- lgpPwrTopology - Liebert Power Topology Group
|
|
-- =============================================================================
|
|
|
|
lgpPwrUpsTopOffline OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS has an offline topology. Under normal operating conditions,
|
|
AC power from the utility passes straight through the UPS
|
|
to the critical load. The inverter is used to convert the DC power
|
|
from the battery to create AC power to support the load when the
|
|
utility fails. Normally the inverter is operating in the stand-by mode,
|
|
keeping the batteries charged. Should the utility power go out of
|
|
specification, the inverter will power the load by drawing energy from
|
|
the battery."
|
|
::= { lgpPwrTopology 1 }
|
|
|
|
lgpPwrUpsTopLineInteractive OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS has a line-interactive topology. This topology
|
|
resembles the offline product, but inserts a transformer or inductor
|
|
in series between the utility power source and the load. This inline
|
|
inductor enables the UPS inverter to interact with incoming power
|
|
and provide a measure of power conditioning to the load. This
|
|
buck-and-boost circuitry helps with high and low input voltage
|
|
conditions."
|
|
::= { lgpPwrTopology 2 }
|
|
|
|
lgpPwrUPSTopDualInput OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has separate input sources for the bypass and inverter."
|
|
::= { lgpPwrTopology 3 }
|
|
|
|
lgpPwrTopFrequencyConverter OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has a frequency converter."
|
|
::= { lgpPwrTopology 4 }
|
|
|
|
lgpPwrTopVoltageConverter OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has a voltage converter."
|
|
::= { lgpPwrTopology 5 }
|
|
|
|
lgpPwrTopMaximumFrameCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt-Amp"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum device system capacity."
|
|
::= { lgpPwrTopology 6 }
|
|
|
|
lgpPwrTopRedundantControlModules OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The device has a redundant control module installed."
|
|
::= { lgpPwrTopology 7 }
|
|
|
|
lgpPwrInputIsolationTransformerInstalled OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
notInstalled(1),
|
|
installed(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates whether the input isolation transformer is installed."
|
|
::= { lgpPwrTopology 8 }
|
|
|
|
lgpPwrStateStaticSwitchType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
notApplicable(1),
|
|
continuousDuty(2),
|
|
momentaryDuty(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Static switch type (N/A, continous duty, or momentary duty)."
|
|
::= { lgpPwrTopology 9 }
|
|
|
|
lgpPwrStateModuleType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
singleModuleSystem(1),
|
|
module1plus1(2),
|
|
module1plusN(3),
|
|
moduleNplus1(4),
|
|
systemControlCabinet(5),
|
|
mainStaticSwitch(6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"UPS module type.
|
|
SMS -- Single Module System
|
|
1 + 1 -- Redundant system for capacity
|
|
1 + N -- Distributed multi-module system
|
|
N + 1 -- A multi-module system with one bypass for the system
|
|
SCC -- System Control Cabinet used in an N+1 system to
|
|
provide a single bypass for the system.
|
|
MSS -- Main Static Switch"
|
|
::= { lgpPwrTopology 10 }
|
|
|
|
lgpPwrStateBypassInputConfig OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
singlePhase2WireL1WithReturn(1),
|
|
twoPhase2WireL1L2(2),
|
|
twoPhase3WireL1L2WithNeutral(3),
|
|
threePhase3WireL1L2L3(4),
|
|
threePhase4WireL1L2L3WithNeutral(5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass input wire physical wiring configuration.
|
|
singlePhase2WireL1WithReturn
|
|
Single phase input with 2 wires (Line 1, and Return).
|
|
twoPhase2WireL1L2
|
|
Two phase input with 2 wires (Line 1, and Line 2).
|
|
twoPhase3WireL1L2WithNeutral
|
|
Two phase input with 3 wires (Line 1, Line 2, and Neutral)
|
|
threePhase3WireL1L2L3
|
|
Three phase input with 3 wires (Line 1, Line 2, and Line 3)
|
|
threePhase4WireL1L2L3WithNeutral
|
|
Three phase input with 4 wires (Line 1, Line 2, Line 3, and
|
|
Neutral)."
|
|
::= { lgpPwrTopology 11 }
|
|
|
|
lgpPwrStateOutputConfig OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
singlePhase2WireL1WithReturn(1),
|
|
twoPhase2WireL1L2(2),
|
|
twoPhase3WireL1L2WithNeutral(3),
|
|
threePhase3WireL1L2L3(4),
|
|
threePhase4WireL1L2L3WithNeutral(5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output wire physical wiring configuration.
|
|
singlePhase2WireL1WithReturn
|
|
Single phase output with 2 wires (Line 1, and Return).
|
|
twoPhase2WireL1L2
|
|
Two phase output with 2 wires (Line 1, and Line 2).
|
|
twoPhase3WireL1L2WithNeutral
|
|
Two phase output with 3 wires (Line 1, Line 2, and Neutral)
|
|
threePhase3WireL1L2L3
|
|
Three phase output with 3 wires (Line 1, Line 2, and Line 3)
|
|
threePhase4WireL1L2L3WithNeutral
|
|
Three phase output with 4 wires (Line 1, Line 2, Line 3, and
|
|
Neutral)."
|
|
::= { lgpPwrTopology 12 }
|
|
|
|
lgpPwrRectifierPassiveFilterInstalled OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
notInstalled(1),
|
|
installed(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates whether the rectifier passive filter is installed."
|
|
::= { lgpPwrTopology 13 }
|
|
|
|
lgpPwrRectifierTrapInstalled OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
notInstalled(1),
|
|
installed(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates whether the rectifier input passive filter is installed."
|
|
::= { lgpPwrTopology 14 }
|
|
|
|
lgpPwrRectifierActiveFilterInstalled OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
notInstalled(1),
|
|
installed(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates whether the rectifier active filter is installed."
|
|
::= { lgpPwrTopology 15 }
|
|
|
|
-- =============================================================================
|
|
-- lgpPwrConfig - Liebert Power Config Group
|
|
-- =============================================================================
|
|
|
|
lgpPwrSysCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Volt-Amp"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current device system capacity."
|
|
::= { lgpPwrConfig 1 }
|
|
|
|
lgpPwrUPSModuleMode OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
single(1),
|
|
parallel(2),
|
|
hotmaster(3),
|
|
hotslave(4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The module mode of the UPS."
|
|
::= { lgpPwrConfig 2 }
|
|
|
|
lgpPwrMaxRatedCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System output maximum amperage rating. The maximum rated amperage for
|
|
the system. This value is based upon the model type and is typically
|
|
limited by the wiring, breakers, power devices, etc."
|
|
::= { lgpPwrConfig 3 }
|
|
|
|
lgpPwrRectifierPulseCount OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
sixPulse(1),
|
|
twelvePulse(2),
|
|
eighteenPulse(3),
|
|
twentyFourPulse(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier pulse count per waveform cycle (6-, 12-, 18-, or 24-pulse)."
|
|
::= { lgpPwrConfig 4 }
|
|
END
|