2368 lines
65 KiB
Plaintext
2368 lines
65 KiB
Plaintext
--PPC-MIB { iso(1) org(3) dod(6) internet(1) private(4)
|
|
-- enterprises(1) ppc(935) }
|
|
-- Title: PPC TOP LEVEL MIB
|
|
-- Date: January 07, 1994 Version 1.00
|
|
--
|
|
-- Date: January 17, 1994 Version 1.01
|
|
--
|
|
-- Date: July 14, 1994 Version 1.02
|
|
--
|
|
-- Date: May 16, 2003 Version 2.00
|
|
|
|
XPPC-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
TRAP-TYPE
|
|
FROM RFC-1215
|
|
DisplayString
|
|
FROM RFC1213-MIB
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
enterprises,
|
|
IpAddress
|
|
FROM RFC1155-SMI;
|
|
|
|
|
|
ppc OBJECT IDENTIFIER
|
|
::= { enterprises 935 }
|
|
|
|
products OBJECT IDENTIFIER
|
|
::= { ppc 1 }
|
|
|
|
ppcmgmt OBJECT IDENTIFIER
|
|
::= { ppc 2 }
|
|
|
|
hardware OBJECT IDENTIFIER
|
|
::= { products 1 }
|
|
|
|
mconfig OBJECT IDENTIFIER
|
|
::= { ppcmgmt 1 }
|
|
|
|
ups OBJECT IDENTIFIER
|
|
::= { hardware 1 }
|
|
|
|
upsIdentp OBJECT IDENTIFIER
|
|
::= { ups 1 }
|
|
|
|
upsBatteryp OBJECT IDENTIFIER
|
|
::= { ups 2 }
|
|
|
|
upsInputp OBJECT IDENTIFIER
|
|
::= { ups 3 }
|
|
|
|
upsOutputp OBJECT IDENTIFIER
|
|
::= { ups 4 }
|
|
|
|
upsConfigp OBJECT IDENTIFIER
|
|
::= { ups 5 }
|
|
|
|
upsControlp OBJECT IDENTIFIER
|
|
::= { ups 6 }
|
|
|
|
upsTestp OBJECT IDENTIFIER
|
|
::= { ups 7 }
|
|
|
|
upsThreePhase OBJECT IDENTIFIER
|
|
::= { ups 8 }
|
|
|
|
upsEnvironment OBJECT IDENTIFIER
|
|
::= { ups 9 }
|
|
|
|
upsBaseIdent OBJECT IDENTIFIER
|
|
::= { upsIdentp 1 }
|
|
|
|
upsSmartIdent OBJECT IDENTIFIER
|
|
::= { upsIdentp 2 }
|
|
|
|
upsBaseBattery OBJECT IDENTIFIER
|
|
::= { upsBatteryp 1 }
|
|
|
|
upsSmartBattery OBJECT IDENTIFIER
|
|
::= { upsBatteryp 2 }
|
|
|
|
upsBaseInput OBJECT IDENTIFIER
|
|
::= { upsInputp 1 }
|
|
|
|
upsSmartInput OBJECT IDENTIFIER
|
|
::= { upsInputp 2 }
|
|
|
|
upsBaseOutput OBJECT IDENTIFIER
|
|
::= { upsOutputp 1 }
|
|
|
|
upsSmartOutput OBJECT IDENTIFIER
|
|
::= { upsOutputp 2 }
|
|
|
|
upsBaseConfig OBJECT IDENTIFIER
|
|
::= { upsConfigp 1 }
|
|
|
|
upsSmartConfig OBJECT IDENTIFIER
|
|
::= { upsConfigp 2 }
|
|
|
|
upsBaseControl OBJECT IDENTIFIER
|
|
::= { upsControlp 1 }
|
|
|
|
upsSmartControl OBJECT IDENTIFIER
|
|
::= { upsControlp 2 }
|
|
|
|
upsBaseTest OBJECT IDENTIFIER
|
|
::= { upsTestp 1 }
|
|
|
|
upsSmartTest OBJECT IDENTIFIER
|
|
::= { upsTestp 2 }
|
|
|
|
upsThreePhaseBatteryGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 1 }
|
|
|
|
upsThreePhaseInputGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 2 }
|
|
|
|
upsThreePhaseOutputGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 3 }
|
|
|
|
upsThreePhaseBypassGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 4 }
|
|
|
|
upsThreePhaseDCandRectifierStatusGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 5 }
|
|
|
|
upsThreePhaseUPSStatusGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 6 }
|
|
|
|
upsThreePhaseFaultStatusGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 7 }
|
|
|
|
upsThreePhaseRatingGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 8 }
|
|
|
|
-- object types
|
|
-- the ppcmgmt group
|
|
-- the mconfig group
|
|
|
|
mconfigTrapsReceiversNum OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of managers to send traps to."
|
|
::= { mconfig 1 }
|
|
|
|
|
|
mconfigTrapsReceiversTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF MconfigTrapsReceiversEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of managers to send traps to. The number of
|
|
entries is given by the value of mconfigNumTrapReceivers"
|
|
::= { mconfig 2 }
|
|
|
|
|
|
mconfigTrapsReceiversEntry OBJECT-TYPE
|
|
SYNTAX MconfigTrapsReceiversEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The managers to send traps to."
|
|
INDEX {
|
|
trapsIndex }
|
|
::= { mconfigTrapsReceiversTable 1 }
|
|
|
|
|
|
MconfigTrapsReceiversEntry ::= SEQUENCE {
|
|
trapsIndex INTEGER,
|
|
trapsReceiverAddr IpAddress,
|
|
receiverCommunityString DisplayString,
|
|
severityLevel INTEGER,
|
|
receiverAccept INTEGER }
|
|
|
|
|
|
trapsIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to a trap receiver entry."
|
|
::= { mconfigTrapsReceiversEntry 1 }
|
|
|
|
|
|
trapsReceiverAddr OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The IP address of the manager to send a trap to."
|
|
::= { mconfigTrapsReceiversEntry 2 }
|
|
|
|
|
|
receiverCommunityString OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The community name to use in the trap when
|
|
sent to the manager."
|
|
::= { mconfigTrapsReceiversEntry 3 }
|
|
|
|
|
|
severityLevel OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
information(1),
|
|
warning(2),
|
|
severe(3) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The severity threshold of traps to send to the manager.
|
|
traps are labeled in severity as informational(1), warning(2),
|
|
severe(3). Only traps of equal or greater severity than
|
|
this value are sent to the manager."
|
|
::= { mconfigTrapsReceiversEntry 4 }
|
|
|
|
|
|
receiverAccept OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(1),
|
|
no(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry will become active if yes, and will
|
|
be deleted if no."
|
|
::= { mconfigTrapsReceiversEntry 5 }
|
|
|
|
|
|
-- the ups group
|
|
-- the upsBaseIdent group
|
|
|
|
upsBaseIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS model name (e.g. 'Intelligent 8000E 900VA')."
|
|
::= { upsBaseIdent 1 }
|
|
|
|
|
|
upsBaseIdentUpsName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An 8 byte ID string identifying the UPS. This object
|
|
can be set by the administrator."
|
|
::= { upsBaseIdent 2 }
|
|
|
|
|
|
-- the upsSmartIdent group
|
|
|
|
upsSmartIdentFirmwareRevision OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The firmware revision of the UPS system."
|
|
::= { upsSmartIdent 1 }
|
|
|
|
|
|
upsSmartIdentDateOfManufacture OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date when the UPS was manufactured in mm/dd/yy format."
|
|
::= { upsSmartIdent 2 }
|
|
|
|
|
|
upsSmartIdentUpsSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An 8-character string identifying the serial number of
|
|
the UPS internal microprocessor. This number is set at
|
|
the factory. NOTE: This number does NOT correspond to
|
|
the serial number on the rear of the UPS."
|
|
::= { upsSmartIdent 3 }
|
|
|
|
|
|
upsSmartIdentAgentFirmwareRevision OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The firmware revision of the UPS SNMP Proxy agent."
|
|
::= { upsSmartIdent 4 }
|
|
|
|
|
|
-- the upsBaseBattery group
|
|
|
|
upsBaseBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
batteryNormal(2),
|
|
batteryLow(3) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of the UPS batteries. A batteryLow(3)
|
|
value indicates the UPS will be unable to sustain the
|
|
current load, and its services will be lost if power is
|
|
not restored. The amount of run time in reserve at the
|
|
time of low battery can be configured by the
|
|
upsSmartConfigLowBatteryRunTime."
|
|
::= { upsBaseBattery 1 }
|
|
|
|
|
|
upsBaseBatteryTimeOnBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The elapsed time in seconds since the UPS has switched
|
|
to battery power."
|
|
::= { upsBaseBattery 2 }
|
|
|
|
|
|
upsBaseBatteryLastReplaceDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date when the UPS system's batteries were last replaced
|
|
in mm/dd/yy format. For UPS models, this value is originally
|
|
set in the factory. When the UPS batteries are replaced,
|
|
this value should be reset by the administrator."
|
|
::= { upsBaseBattery 3 }
|
|
|
|
|
|
-- the upsSmartBattery group
|
|
|
|
upsSmartBatteryCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The remaining battery capacity expressed in
|
|
percent of full capacity."
|
|
::= { upsSmartBattery 1 }
|
|
|
|
|
|
upsSmartBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current battery voltage expressed in 1/10 VDC."
|
|
::= { upsSmartBattery 2 }
|
|
|
|
|
|
upsSmartBatteryTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current internal UPS temperature expressed in tenths of
|
|
a Celsius degree."
|
|
::= { upsSmartBattery 3 }
|
|
|
|
|
|
upsSmartBatteryRunTimeRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS battery run time remaining before battery
|
|
exhaustion, in seconds."
|
|
::= { upsSmartBattery 4 }
|
|
|
|
|
|
upsSmartBatteryReplaceIndicator OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noBatteryNeedsReplacing(1),
|
|
batteryNeedsReplacing(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates whether the UPS batteries need replacing."
|
|
::= { upsSmartBattery 5 }
|
|
|
|
|
|
upsSmartBatteryFullChargeVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The fully charged battery voltage of the battery system
|
|
used in the UPS, expressed in tenths of a volt."
|
|
::= { upsSmartBattery 6 }
|
|
|
|
|
|
upsSmartBatteryCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current battery current expressed in percent of
|
|
maximum current."
|
|
::= { upsSmartBattery 7 }
|
|
|
|
|
|
-- the upsBaseInput group
|
|
|
|
upsBaseInputPhase OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current AC input phase."
|
|
::= { upsBaseInput 1 }
|
|
|
|
|
|
-- the upsSmartInput group
|
|
|
|
upsSmartInputLineVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current utility line voltage in 1/10 VAC."
|
|
::= { upsSmartInput 1 }
|
|
|
|
|
|
upsSmartInputMaxLineVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum utility line voltage in 1/10 VAC over the
|
|
previous 1 minute period."
|
|
::= { upsSmartInput 2 }
|
|
|
|
|
|
upsSmartInputMinLineVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum utility line voltage in 1/10 VAC over the
|
|
previous 1 minute period."
|
|
::= { upsSmartInput 3 }
|
|
|
|
|
|
upsSmartInputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current input frequency to the UPS system in 1/10 Hz."
|
|
::= { upsSmartInput 4 }
|
|
|
|
|
|
upsSmartInputLineFailCause OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTransfer(1),
|
|
highLineVoltage(2),
|
|
brownout(3),
|
|
blackout(4),
|
|
smallMomentarySag(5),
|
|
deepMomentarySag(6),
|
|
smallMomentarySpike(7),
|
|
largeMomentarySpike(8) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The reason for the occurrence of the last transfer
|
|
to UPS battery power. The variable is set to
|
|
noTransfer(1) if there is no transfer yet. The variable
|
|
is set to highLineVoltage(2) if the transfer to battery is
|
|
caused by an over voltage greater than the high transfer
|
|
voltage. The variable is set to brownout(3) if the duration
|
|
of the outage is greater than five seconds and the line
|
|
voltage is between 40 percent of the rated output voltage and
|
|
the low transfer voltage. The variable is set to blackout(4)
|
|
if the duration of the outage is greater than five seconds and
|
|
the line voltage is between 40 percent of the rated output voltage
|
|
and ground. The variable is set to smallMomentarySag(5)
|
|
if the duration of the outage is less than five seconds and
|
|
the line voltage is between 40 percent of the rated output voltage
|
|
and the low transfer voltage. The variable is set to
|
|
deepMomentarySag(6) if the duration of the outage is less
|
|
than five seconds and the line voltage is between 40 percent of the
|
|
rated output voltage and ground."
|
|
::= { upsSmartInput 5 }
|
|
|
|
|
|
-- the upsBaseOutput group
|
|
|
|
upsBaseOutputStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
onLine(2),
|
|
onBattery(3),
|
|
onBoost(4),
|
|
sleeping(5),
|
|
onBypass(6),
|
|
rebooting(7),
|
|
standBy(8),
|
|
onBuck(9) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current state of the UPS. If the UPS is unable
|
|
to determine the state of the UPS this variable is set
|
|
to unknown(1)."
|
|
::= { upsBaseOutput 1 }
|
|
|
|
|
|
upsBaseOutputPhase OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current output phase."
|
|
::= { upsBaseOutput 2 }
|
|
|
|
|
|
-- the upsSmartOutput group
|
|
|
|
upsSmartOutputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output voltage of the UPS system in 1/10 VAC."
|
|
::= { upsSmartOutput 1 }
|
|
|
|
|
|
upsSmartOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current output frequency of the UPS system in 1/10 Hz."
|
|
::= { upsSmartOutput 2 }
|
|
|
|
|
|
upsSmartOutputLoad OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current UPS load expressed in percent
|
|
of rated capacity."
|
|
::= { upsSmartOutput 3 }
|
|
|
|
|
|
-- the upsBaseConfig group
|
|
|
|
upsBaseConfigNumDevices OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of devices that are plugged into the UPS."
|
|
::= { upsBaseConfig 1 }
|
|
|
|
|
|
upsBaseConfigDeviceTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsBaseConfigDeviceEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of devices that are plugged into the UPS. The
|
|
number of entries is given by the value of
|
|
upsBaseConfigNumDevices."
|
|
::= { upsBaseConfig 2 }
|
|
|
|
|
|
upsBaseConfigDeviceEntry OBJECT-TYPE
|
|
SYNTAX UpsBaseConfigDeviceEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The devices plugged in to the UPS."
|
|
INDEX {
|
|
indexOfDevice }
|
|
::= { upsBaseConfigDeviceTable 1 }
|
|
|
|
|
|
UpsBaseConfigDeviceEntry ::= SEQUENCE {
|
|
indexOfDevice INTEGER,
|
|
nameOfDevice DisplayString,
|
|
vaRatingOfDevice INTEGER,
|
|
deviceAccept INTEGER }
|
|
|
|
|
|
indexOfDevice OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index of the device that is plugged into the UPS."
|
|
::= { upsBaseConfigDeviceEntry 1 }
|
|
|
|
|
|
nameOfDevice OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name/description of the device plugged into the UPS."
|
|
::= { upsBaseConfigDeviceEntry 2 }
|
|
|
|
|
|
vaRatingOfDevice OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The volt-amp rating of the device plugged into the UPS."
|
|
::= { upsBaseConfigDeviceEntry 3 }
|
|
|
|
|
|
deviceAccept OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(1),
|
|
no(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry is added if yes, the entry is deleted if no."
|
|
::= { upsBaseConfigDeviceEntry 4 }
|
|
|
|
|
|
-- the upsSmartConfig group
|
|
|
|
upsSmartConfigRatedOutputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The nominal output voltage from the UPS in 1/10 VAC.
|
|
Possible values are 1000, 1200, 2080, 2200, 2250, 2300
|
|
and 2400.
|
|
|
|
NOTE: Only units that are 2200, 2250, 2300 and 2400 can
|
|
be changed. Allowable values are 2200, 2250, 2300 and
|
|
2400.
|
|
|
|
For these adjustable units, if a value other than
|
|
a supported value is provided in a set request, the
|
|
UPS interprets it as the next lower acceptable value.
|
|
If the provided value is lower than the lowest acceptable
|
|
value, the lowest acceptable value is used."
|
|
::= { upsSmartConfig 1 }
|
|
|
|
|
|
upsSmartConfigHighTransferVolt OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum line voltage in 1/10 VAC allowed before the
|
|
UPS system transfers to battery backup.
|
|
|
|
Allowed value depend on the UPS used:
|
|
120 Volt units allow settings of 1290, 1320, 1350, 1380.
|
|
100 Volt units allow settings of 1080, 1100, 1120, 1140.
|
|
230 Volt units allow settings of 2530, 2640, 2710, 2800.
|
|
208 Volt units allow settings of 2240, 2290, 2340, 2390.
|
|
|
|
If a value other than a supported value is provided in a
|
|
set request, the UPS interprets it as the next lower
|
|
acceptable value. If the provided value is lower than
|
|
the lowest acceptable value, the lowest acceptable
|
|
value is used."
|
|
::= { upsSmartConfig 2 }
|
|
|
|
|
|
upsSmartConfigLowTransferVolt OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum line voltage in 1/10 VAC allowed before the
|
|
UPS system transfers to battery backup.
|
|
|
|
Allowable values depend on the UPS used:
|
|
120 Volt units allow settings of 970, 1000, 1030, 1060.
|
|
100 Volt units allow settings of 810, 830, 850, 870.
|
|
230 Volt units allow settings of 1880, 1960, 2040, 2080.
|
|
208 Volt units allow settings of 1680, 1720, 1770, 1820.
|
|
|
|
If a value other than a supported value is provided in a
|
|
set request, the UPS interprets it as a the next higher
|
|
acceptable value. If the provided value is higher than
|
|
the highest acceptable value, the highest acceptable
|
|
value is used."
|
|
::= { upsSmartConfig 3 }
|
|
|
|
|
|
upsSmartConfigAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
timed(1),
|
|
atLowBattery(2),
|
|
never(3) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A flag indicating how the UPS should handle audible line fail
|
|
alarms."
|
|
::= { upsSmartConfig 4 }
|
|
|
|
|
|
upsSmartConfigAlarmTimer OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time in seconds after initial line failure at which the
|
|
UPS begins emitting audible alarms (beeping). This timer is
|
|
observerd only if the value of extControlAlarm is timed(2).
|
|
Allowed values are 0 or 30 seconds.
|
|
|
|
If a value other than a supported value is provided in a
|
|
set request, the UPS interprets it as a the next lower
|
|
acceptable value. If the provided value is lower than
|
|
the lowest acceptable value, the lowest acceptable
|
|
value is used."
|
|
::= { upsSmartConfig 5 }
|
|
|
|
|
|
upsSmartConfigMinReturnCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum battery capacity as a percent of full capacity
|
|
required before the UPS will return from a low battery
|
|
shutdown condition. In other words, the UPS will not
|
|
re-energize the output until the battery capacity is equal
|
|
to this value. Allowed values are 0, 10, 25, or 90 percent.
|
|
|
|
If a value other than a supported value is provided in a
|
|
set request, the UPS interprets it as a the next higher
|
|
acceptable value. If the provided value is higher than
|
|
the highest acceptable value, the highest acceptable
|
|
value is used."
|
|
::= { upsSmartConfig 6 }
|
|
|
|
|
|
upsSmartConfigSensitivity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
auto(1),
|
|
low(2),
|
|
medium(3),
|
|
high(4) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The sensitivity of the UPS to utility line abnormalities
|
|
or noises."
|
|
::= { upsSmartConfig 7 }
|
|
|
|
|
|
upsSmartConfigLowBatteryRunTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The desired run time in seconds once the low battery
|
|
condition is reached. Allowed values are 120, 300, 420,
|
|
or 600 seconds. During this time the UPS will produce a
|
|
constant warning tone which can not be disabled.
|
|
|
|
If a value other than a supported value is provided in a
|
|
set request, the UPS interprets it as a the next higher
|
|
acceptable value. If the provided value is higher than
|
|
the highest acceptable value, the highest acceptable
|
|
value is used."
|
|
::= { upsSmartConfig 8 }
|
|
|
|
|
|
upsSmartConfigReturnDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The delay in seconds after utility line power returns
|
|
before the UPS will turn on. This value is also used
|
|
when the UPS comes out of a reboot and before the UPS
|
|
wakes up from 'sleep' mode. Allowed values are 0, 60,
|
|
180 and 300 seconds.
|
|
|
|
If a value other than a supported value is provided in a
|
|
set request, the UPS interprets it as a the next higher
|
|
acceptable value. If the provided value is higher than
|
|
the highest acceptable value, the highest acceptable
|
|
value is used."
|
|
::= { upsSmartConfig 9 }
|
|
|
|
|
|
upsSmartConfigShutoffDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The delay in seconds the UPS remains on after being told
|
|
to turn off. Allowed values are 12, 18, 24, 30, 36, 42,
|
|
48, 54, 60, 120, 180, 240, 300, 360, 420, 480, 540, and
|
|
600 seconds.
|
|
|
|
If a value other than a supported value is provided in a
|
|
set request, the UPS interprets it as next higher acceptable
|
|
value. If the provided value is higher than the highest
|
|
acceptable value, the highest acceptable value is used."
|
|
::= { upsSmartConfig 10 }
|
|
|
|
|
|
upsSmartConfigUpsSleepTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time in minutes for the UPS to go to 'sleep' when
|
|
instructed. When in sleep mode, the UPS will not provide
|
|
output power regardless of the input line state. Once the
|
|
specified time has elapsed, output power will be restored.
|
|
|
|
This is a configuration setting. The UPS will not go to
|
|
sleep until told to do so by the manager from a management
|
|
station.
|
|
|
|
Any input value is allowed, however the UPS only recognizes
|
|
0 - 9999 minutes in one minute increments.
|
|
|
|
If the provided value is higher than the highest acceptable
|
|
value, the highest acceptable value is used."
|
|
::= { upsSmartConfig 11 }
|
|
|
|
|
|
upsSmartConfigSetEEPROMDefaults OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noSetEEPROMDefaults(1),
|
|
setEEPROMDefaults(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"WRITE: Resets the UPS EEPROM variables to default values.
|
|
READ: returns 0"
|
|
::= { upsSmartConfig 12 }
|
|
|
|
|
|
-- the upsBaseControl group
|
|
|
|
upsBaseControlConserveBattery OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTurnOffUps(1),
|
|
turnUpsOffToConserveBattery(2),
|
|
turnUpsOffToConserveBatteryDelay(3) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to turnUpsOffToConserveBattery(2)
|
|
causes a UPS on battery to be put into 'sleep' mode immediately.
|
|
The (10) means suspending time(10 minutes) before turn off UPS.
|
|
UPS will turn back on when utility power is restored.
|
|
Attempting to turn off a UPS that is not on battery will
|
|
result in a badValue error.
|
|
|
|
Setting this value to noTurnOffUps(1) has no
|
|
effect.
|
|
|
|
The value noTurnOffUps(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsBaseControl 1 }
|
|
|
|
|
|
-- the upsSmartControl group
|
|
|
|
upsSmartControlUpsOff OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTurnUpsOff(1),
|
|
turnUpsOff(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to turnUpsOff(2) causes
|
|
the UPS to shut off. When in this state, the UPS
|
|
will not provide output power regardless of the input
|
|
line state. The on/off switch on the UPS
|
|
must be toggled for the UPS to return to operation.
|
|
|
|
Setting this value to noTurnUpsOff(1) has no
|
|
effect.
|
|
|
|
The value noTurnUpsOff(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsSmartControl 1 }
|
|
|
|
|
|
upsSmartControlRebootUps OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noRebootUps(1),
|
|
rebootUps(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to rebootUps(2) causes the
|
|
UPS to shut off and turn back on.
|
|
|
|
Setting this value to noRebootUps(1) has no effect.
|
|
|
|
The value noRebootUps(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsSmartControl 2 }
|
|
|
|
|
|
upsSmartControlUpsSleep OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noPutUpsToSleep(1),
|
|
putUpsToSleep(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to putUpsToSleep(2) causes
|
|
the UPS to go to sleep for the time specified by
|
|
upsSmartConfigUpsSleepTime.
|
|
|
|
When in sleep mode, the UPS will not provide output
|
|
power regardless of the input line state. Once the
|
|
specified time has elapsed, output power will be
|
|
restored.
|
|
|
|
Setting this value to noPutUpsToSleep(1) has no
|
|
effect.
|
|
|
|
The value noPutUpsToSleep(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsSmartControl 3 }
|
|
|
|
|
|
upsSmartControlSimulatePowerFail OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noSimulatePowerFailure(1),
|
|
simulatePowerFailure(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to simulatePowerFailure(2) causes
|
|
the UPS switch to battery power.
|
|
|
|
Setting this value to noSimulatePowerFailure(1) has no
|
|
effect.
|
|
|
|
The value noSimulatePowerFailure(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsSmartControl 4 }
|
|
|
|
|
|
upsSmartControlFlashAndBeep OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noFlashAndBeep(1),
|
|
flashAndBeep(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS to identify itself by lighting all indicators
|
|
and beeping.
|
|
|
|
Setting this variable to FlashAndBeep(2) causes
|
|
the UPS lights all panel indicators and beeps.
|
|
|
|
Setting this value to noFlashAndBeep(1) has no
|
|
effect.
|
|
|
|
The value noFlashAndBeep(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsSmartControl 5 }
|
|
|
|
|
|
upsSmartControlTurnOnUpsLoad OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noUpsSmartControlTurnOnUpsLoad(1),
|
|
upsSmartControlTurnOnUpsLoad(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to upsSmartControlTurnOnUpsLoad(2)
|
|
causes the UPS switch back to utility power if utility
|
|
power is present.
|
|
|
|
Setting this value to noUpsSmartControlTurnOnUpsLoad(1)
|
|
has no effect.
|
|
|
|
The value noUpsSmartControlTurnOnUpsLoad(1) will always
|
|
be returned when the variable is read."
|
|
::= { upsSmartControl 6 }
|
|
|
|
|
|
-- the upsBaseTest group
|
|
-- the upsSmartTest group
|
|
|
|
upsSmartTestDiagnosticSchedule OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
biweekly(2),
|
|
weekly(3),
|
|
never(4) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS system's automatic battery test schedule."
|
|
::= { upsSmartTest 1 }
|
|
|
|
|
|
upsSmartTestDiagnostics OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTestDiagnostics(1),
|
|
testDiagnostics(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to testDiagnostics(2) causes
|
|
the UPS to perform a diagnostic self test.
|
|
|
|
Setting this value to noTestDiagnostics(1) has no
|
|
effect.
|
|
|
|
The value noTestDiagnostics(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsSmartTest 2 }
|
|
|
|
|
|
upsSmartTestDiagnosticsResults OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok(1),
|
|
failed(2),
|
|
invalidTest(3),
|
|
testInProgress(4) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The results of the last UPS diagnostics test performed."
|
|
::= { upsSmartTest 3 }
|
|
|
|
|
|
upsSmartTestLastDiagnosticsDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date the last UPS diagnostics test was performed in
|
|
mm/dd/yy format."
|
|
::= { upsSmartTest 4 }
|
|
|
|
|
|
upsSmartTestIndicators OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTestIndicators(1),
|
|
testIndicators(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to testIndicators(2) causes
|
|
the UPS to perform a front panel indicator (lights) test.
|
|
|
|
Setting this value to noTestIndicators(1) has no effect.
|
|
|
|
The value noTestIndicators(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsSmartTest 5 }
|
|
|
|
|
|
upsSmartTestRuntimeCalibration OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noPerformCalibration(1),
|
|
performCalibration(2),
|
|
cancelCurrentCalibration(3) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to performCalibration(2) causes
|
|
the UPS to discharge to calibrate the UPS.
|
|
The test will only start if the battery capacity is 100 percent.
|
|
The test runs until capacity is less than 25 percent.
|
|
|
|
Setting this variable to cancelCurrentCalibration(3)
|
|
after setting performCalibration(2) will cancel the
|
|
current discharge.
|
|
|
|
Setting this variable to noPerformCalibration(1)
|
|
will have no effect.
|
|
|
|
The value noPerformCalibration(1) will always be returned
|
|
when the variable is read.
|
|
|
|
The result of the calibration will be saved in
|
|
upsSmartTestCalibrationResult."
|
|
::= { upsSmartTest 6 }
|
|
|
|
|
|
upsSmartTestCalibrationResults OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok(1),
|
|
invalidTest(2),
|
|
calibrationInProgress(3) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The results of the last runtime calibration.
|
|
|
|
Value ok(1) means a successful runtime calibration.
|
|
|
|
Value invalidTest(2) indicates last calibration did
|
|
not take place since the battery capacity was below
|
|
100 percent.
|
|
|
|
Value calibrationInProgress(3) means a calibration
|
|
is occurring now."
|
|
::= { upsSmartTest 7 }
|
|
|
|
|
|
upsSmartTestCalibrationDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date the last UPS runtime calibration was
|
|
performed in mm/dd/yy format."
|
|
::= { upsSmartTest 8 }
|
|
|
|
|
|
-----------------------
|
|
--ups ThreePhase group-
|
|
-----------------------
|
|
upsThreePhaseBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Battery Voltage"
|
|
::= { upsThreePhaseBatteryGrp 1 }
|
|
|
|
|
|
upsThreePhaseBatteryCapacityPercentage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Battery Capacity Percentage"
|
|
::= { upsThreePhaseBatteryGrp 2 }
|
|
|
|
|
|
upsThreePhaseBatteryTimeRemain OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Battery Time Remain (unit is Minute)"
|
|
::= { upsThreePhaseBatteryGrp 3 }
|
|
|
|
|
|
upsThreePhaseBatteryCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Battery Electric Current"
|
|
::= { upsThreePhaseBatteryGrp 4 }
|
|
|
|
|
|
upsThreePhaseBatteryTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Battery Temperature"
|
|
::= { upsThreePhaseBatteryGrp 5 }
|
|
|
|
|
|
upsThreePhaseInputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Input Frequency"
|
|
::= { upsThreePhaseInputGrp 1 }
|
|
|
|
|
|
upsThreePhaseInputVoltageR OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Input VoltageR"
|
|
::= { upsThreePhaseInputGrp 2 }
|
|
|
|
|
|
upsThreePhaseInputVoltageS OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Input VoltageS"
|
|
::= { upsThreePhaseInputGrp 3 }
|
|
|
|
|
|
upsThreePhaseInputVoltageT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Input VoltageT"
|
|
::= { upsThreePhaseInputGrp 4 }
|
|
|
|
|
|
upsThreePhaseOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output Frequency"
|
|
::= { upsThreePhaseOutputGrp 1 }
|
|
|
|
|
|
upsThreePhaseOutputVoltageR OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output VoltageR"
|
|
::= { upsThreePhaseOutputGrp 2 }
|
|
|
|
|
|
upsThreePhaseOutputVoltageS OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output VoltageS"
|
|
::= { upsThreePhaseOutputGrp 3 }
|
|
|
|
|
|
upsThreePhaseOutputVoltageT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output VoltageT"
|
|
::= { upsThreePhaseOutputGrp 4 }
|
|
|
|
|
|
upsThreePhaseOutputLoadPercentageR OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Load PercentageR"
|
|
::= { upsThreePhaseOutputGrp 5 }
|
|
|
|
|
|
upsThreePhaseOutputLoadPercentageS OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Load PercentageS"
|
|
::= { upsThreePhaseOutputGrp 6 }
|
|
|
|
|
|
upsThreePhaseOutputLoadPercentageT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Load PercentageT"
|
|
::= { upsThreePhaseOutputGrp 7 }
|
|
|
|
|
|
upsThreePhaseBypassSourceFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass Frequency"
|
|
::= { upsThreePhaseBypassGrp 1 }
|
|
|
|
|
|
upsThreePhaseBypssSourceVoltageR OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass VoltageR"
|
|
::= { upsThreePhaseBypassGrp 2 }
|
|
|
|
|
|
upsThreePhaseBypssSourceVoltageS OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass VoltageS"
|
|
::= { upsThreePhaseBypassGrp 3 }
|
|
|
|
|
|
upsThreePhaseBypssSourceVoltageT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass VoltageT"
|
|
::= { upsThreePhaseBypassGrp 4 }
|
|
|
|
|
|
upsThreePhaseDCandRectifierStatusRecRotError OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Rectifier Rotation Error"
|
|
::= { upsThreePhaseDCandRectifierStatusGrp 1 }
|
|
|
|
|
|
upsThreePhaseDCandRectifierStatusLowBatteryShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Low Battery Shutdown"
|
|
::= { upsThreePhaseDCandRectifierStatusGrp 2 }
|
|
|
|
|
|
upsThreePhaseDCandRectifierStatusLowBattery OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Low Battery"
|
|
::= { upsThreePhaseDCandRectifierStatusGrp 3 }
|
|
|
|
|
|
upsThreePhaseDCandRectifierStatusInAndOut OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
threeInOneOut(2),
|
|
threeInThreeOut(3) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"In And Put"
|
|
::= { upsThreePhaseDCandRectifierStatusGrp 4 }
|
|
|
|
|
|
upsThreePhaseDCandRectifierStatusBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
backup(4),
|
|
acnormal(5) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Back Status"
|
|
::= { upsThreePhaseDCandRectifierStatusGrp 5 }
|
|
|
|
|
|
upsThreePhaseDCandRectifierStatusChargeStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
boost(6),
|
|
float(7),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Charge Status"
|
|
::= { upsThreePhaseDCandRectifierStatusGrp 6 }
|
|
|
|
|
|
upsThreePhaseDCandRectifierStatusRecOperating OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Rectifier Operating"
|
|
::= { upsThreePhaseDCandRectifierStatusGrp 7 }
|
|
|
|
|
|
upsThreePhaseUPSStatusBypassFreqFail OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass Status"
|
|
::= { upsThreePhaseUPSStatusGrp 1 }
|
|
|
|
|
|
upsThreePhaseUPSStatusManualBypassBreaker OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
close(8),
|
|
open(9) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Breaker Status"
|
|
::= { upsThreePhaseUPSStatusGrp 2 }
|
|
|
|
|
|
upsThreePhaseUPSStatusACStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(10),
|
|
abnormal(11) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"AC Status"
|
|
::= { upsThreePhaseUPSStatusGrp 3 }
|
|
|
|
|
|
upsThreePhaseUPSStaticSwitchMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
invermode(12),
|
|
bypassmode(13) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Switch Mode"
|
|
::= { upsThreePhaseUPSStatusGrp 4 }
|
|
|
|
|
|
upsThreePhaseUPSStatusInverterOperating OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Operating"
|
|
::= { upsThreePhaseUPSStatusGrp 5 }
|
|
|
|
|
|
upsThreePhaseFaultStatusEmergencyStop OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Emergency Stop"
|
|
::= { upsThreePhaseFaultStatusGrp 1 }
|
|
|
|
|
|
upsThreePhaseFaultStatusHighDCShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"High DC Shutdown"
|
|
::= { upsThreePhaseFaultStatusGrp 2 }
|
|
|
|
|
|
upsThreePhaseFaultStatusBypassBreaker OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass Breaker"
|
|
::= { upsThreePhaseFaultStatusGrp 3 }
|
|
|
|
|
|
upsThreePhaseFaultStatusOverLoad OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Over Load"
|
|
::= { upsThreePhaseFaultStatusGrp 4 }
|
|
|
|
|
|
upsThreePhaseFaultStatusInverterOutputFail OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output Fail"
|
|
::= { upsThreePhaseFaultStatusGrp 5 }
|
|
|
|
|
|
upsThreePhaseFaultStatusOverTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Over Temperature"
|
|
::= { upsThreePhaseFaultStatusGrp 6 }
|
|
|
|
|
|
upsThreePhaseFaultStatusShortCircuit OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Short Circuit"
|
|
::= { upsThreePhaseFaultStatusGrp 7 }
|
|
|
|
|
|
upsThreePhaseRatingRectifierVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Rectifier Voltage"
|
|
::= { upsThreePhaseRatingGrp 1 }
|
|
|
|
|
|
upsThreePhaseRatingRectifierFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Rectifier Frequency"
|
|
::= { upsThreePhaseRatingGrp 2 }
|
|
|
|
|
|
upsThreePhaseRatingBypassVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass Voltage"
|
|
::= { upsThreePhaseRatingGrp 3 }
|
|
|
|
|
|
upsThreePhaseRatingBypassFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass Frequency"
|
|
::= { upsThreePhaseRatingGrp 4 }
|
|
|
|
|
|
upsThreePhaseRatingOutputVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output Voltage"
|
|
::= { upsThreePhaseRatingGrp 5 }
|
|
|
|
|
|
upsThreePhaseRatingOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output Frequency"
|
|
::= { upsThreePhaseRatingGrp 6 }
|
|
|
|
|
|
upsThreePhaseRatingBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Battery Voltage"
|
|
::= { upsThreePhaseRatingGrp 7 }
|
|
|
|
|
|
upsThreePhaseRatingPower OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Power Rating"
|
|
::= { upsThreePhaseRatingGrp 8 }
|
|
|
|
|
|
-----------------------
|
|
-----------------------
|
|
|
|
upsEnvStatus OBJECT IDENTIFIER ::= { upsEnvironment 1 }
|
|
|
|
upsEnvTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ambient environment temperature."
|
|
::= { upsEnvStatus 1 }
|
|
|
|
|
|
upsEnvHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The environment humidity."
|
|
::= { upsEnvStatus 2 }
|
|
|
|
|
|
upsEnvOverTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm dupsAlarmOverTemperature on when the environment
|
|
temperature over the value."
|
|
::= { upsEnvSetting 1 }
|
|
|
|
|
|
upsEnvOverHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm dupsAlarmOverHumidity on when the environment
|
|
humidity over the value."
|
|
::= { upsEnvSetting 3 }
|
|
|
|
|
|
upsEnvSecurity1 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Security status"
|
|
::= { upsEnvStatus 5 }
|
|
|
|
|
|
upsEnvSecurity2 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Security status"
|
|
::= { upsEnvStatus 6 }
|
|
|
|
|
|
upsEnvSecurity3 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Security status"
|
|
::= { upsEnvStatus 7 }
|
|
|
|
|
|
upsEnvSecurity4 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Security status"
|
|
::= { upsEnvStatus 8 }
|
|
|
|
|
|
upsEnvSecurity5 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Security status"
|
|
::= { upsEnvStatus 9 }
|
|
|
|
|
|
upsEnvSecurity6 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Security status"
|
|
::= { upsEnvStatus 10 }
|
|
|
|
|
|
upsEnvSecurity7 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Security status"
|
|
::= { upsEnvStatus 11 }
|
|
|
|
|
|
upsEnvWater OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Water status"
|
|
::= { upsEnvStatus 3 }
|
|
|
|
|
|
upsEnvSmoke OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Smoke status"
|
|
::= { upsEnvStatus 4 }
|
|
|
|
|
|
upsEnvSetting OBJECT IDENTIFIER ::= { upsEnvironment 2 }
|
|
|
|
upsEnvUnderTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm dupsAlarmUnderTemperature on when the environment
|
|
temperature below the value."
|
|
::= { upsEnvSetting 2 }
|
|
|
|
|
|
upsEnvUnderHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm dupsAlarmUnderHumidity on when the environment
|
|
humidity below the value."
|
|
::= { upsEnvSetting 4 }
|
|
|
|
|
|
|
|
communicationLost TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"SEVERE: Communication to the UPS has been lost. Steps
|
|
to reestablish communication are in progress."
|
|
--#TYPE "PPC UPS: Communication failure"
|
|
--#SUMMARY "Communication to the UPS has been lost."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY CRITICAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE DEGRADED
|
|
::= 1
|
|
|
|
|
|
|
|
upsOverLoad TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"SEVERE: The UPS has sensed a load greater than 100 percent
|
|
of its rated capacity."
|
|
--#TYPE "PPC UPS: UPS overload"
|
|
--#SUMMARY "The UPS has sensed a load greater than 100 percent of its rated capacity."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY CRITICAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE DEGRADED
|
|
::= 2
|
|
|
|
|
|
|
|
upsDiagnosticsFailed TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"SEVERE: The UPS failed its internal diagnostic self-test."
|
|
--#TYPE "PPC UPS: Failed self-test"
|
|
--#SUMMARY "The UPS has failed its internal diagnostic self-test."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY CRITICAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE DEGRADED
|
|
::= 3
|
|
|
|
|
|
|
|
upsDischarged TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"SEVERE: The UPS just started a runtime calibration
|
|
discharge. The UPS batteries are being discharged."
|
|
--#TYPE "PPC UPS: Deep discharge"
|
|
--#SUMMARY "The UPS has just started a runtime calibration discharge."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY CRITICAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE DEGRADED
|
|
::= 4
|
|
|
|
|
|
|
|
upsOnBattery TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS has switched to battery backup power."
|
|
--#TYPE "PPC UPS: On battery"
|
|
--#SUMMARY "The UPS has switched to battery backup power."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY MAJOR
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 5
|
|
|
|
|
|
|
|
boostOn TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS has enabled Boost."
|
|
--#TYPE "PPC UPS: SmartBoost"
|
|
--#SUMMARY "The UPS has enabled Boost."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY MINOR
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 6
|
|
|
|
|
|
|
|
lowBattery TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"SEVERE: The UPS batteries are low and will soon be exhausted.
|
|
If utility power is not restored the UPS will put itself
|
|
to 'sleep' and immediately cut power to the load."
|
|
--#TYPE "PPC UPS: Low battery"
|
|
--#SUMMARY "The UPS batteries are low and will soon be exhausted."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY CRITICAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE DEGRADED
|
|
::= 7
|
|
|
|
|
|
|
|
communicationEstablished TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: Communication with the UPS has been
|
|
established."
|
|
--#TYPE "PPC UPS: Communication established"
|
|
--#SUMMARY "Communication with the UPS has been established."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 8
|
|
|
|
|
|
|
|
powerRestored TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: Utility power has been restored."
|
|
--#TYPE "PPC UPS: Utility restored"
|
|
--#SUMMARY "Normal power has been restored to the UPS."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 9
|
|
|
|
|
|
|
|
upsDiagnosticsPassed TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS passed its internal self-test."
|
|
--#TYPE "PPC UPS: Passed self-test"
|
|
--#SUMMARY "The UPS has passed its internal self-test."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 10
|
|
|
|
|
|
|
|
returnFromLowBattery TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has returned from a low battery
|
|
condition."
|
|
--#TYPE "PPC UPS: Battery normal"
|
|
--#SUMMARY "The UPS has returned from a low battery condition."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 11
|
|
|
|
|
|
|
|
upsTurnedOff TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS has been turned 'off' by the
|
|
management station."
|
|
--#TYPE "PPC UPS: Switching off"
|
|
--#SUMMARY "The UPS is being switched off by a management station."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY MAJOR
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE NONOPERATIONAL
|
|
::= 12
|
|
|
|
|
|
|
|
upsSleeping TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS is entering 'sleep' mode. Power
|
|
to the load will be cut off."
|
|
--#TYPE "PPC UPS: Going to sleep"
|
|
--#SUMMARY "The UPS is going into sleep mode."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY MAJOR
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE NONOPERATIONAL
|
|
::= 13
|
|
|
|
|
|
|
|
upsWokeUp TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS woke up from 'sleep' mode. Power
|
|
to the load has been restored."
|
|
--#TYPE "PPC UPS: Wake up"
|
|
--#SUMMARY "The UPS has woke up from sleep mode."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 14
|
|
|
|
|
|
|
|
upsRebootStarted TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS has started its reboot sequence. After
|
|
the specified delay the UPS will perform a reboot."
|
|
--#TYPE "PPC UPS: Starting reboot"
|
|
--#SUMMARY "The UPS has started its reboot sequence."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY MAJOR
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE NONOPERATIONAL
|
|
::= 15
|
|
|
|
|
|
envOverTemperature TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The environment temperature exceed the normal value."
|
|
::= 16
|
|
|
|
|
|
envTemperatureNormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: The environment temperature is normal."
|
|
::= 17
|
|
|
|
|
|
envOverHumidity TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The environment humidity exceed the normal value."
|
|
::= 18
|
|
|
|
|
|
envHumidityNormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: The environment humidity is normal."
|
|
::= 19
|
|
|
|
|
|
envSmokeAbnormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Smoke is abnormal."
|
|
::= 20
|
|
|
|
|
|
envWaterAbnormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Water is abnormal."
|
|
::= 21
|
|
|
|
|
|
envSecurityAbnormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security is abnormal."
|
|
::= 22
|
|
|
|
|
|
--envSmokeNormal TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "INFORMATION: Smoke is normal."
|
|
-- ::= 23
|
|
|
|
|
|
envWaterNormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: Water is normal."
|
|
::= 24
|
|
|
|
|
|
--envSecurityNormal TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "INFORMATION: Security is normal."
|
|
-- ::= 25
|
|
|
|
|
|
envGasAbnormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Gas Alarm"
|
|
::= 26
|
|
|
|
|
|
upsTemp TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: UPS Temperature Overrun"
|
|
::= 27
|
|
|
|
|
|
upsLoadNormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: UPS Load Normal"
|
|
::= 28
|
|
|
|
|
|
upsTempNormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: UPS temperature Normal"
|
|
::= 29
|
|
|
|
|
|
envUnderTemperature TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The environment temperature below the normal value."
|
|
::= 30
|
|
|
|
|
|
envUnderHumidity TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The environment humidity below the normal value."
|
|
::= 31
|
|
|
|
|
|
upsBypass TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS is entering 'bypass' mode."
|
|
::= 32
|
|
|
|
|
|
envSecurity1 TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security1 Alarm."
|
|
::= 33
|
|
|
|
|
|
envSecurity2 TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security2 Alarm."
|
|
::= 34
|
|
|
|
|
|
envSecurity3 TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security3 Alarm."
|
|
::= 35
|
|
|
|
|
|
envSecurity4 TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security4 Alarm."
|
|
::= 36
|
|
|
|
|
|
envSecurity5 TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security5 Alarm."
|
|
::= 37
|
|
|
|
|
|
envSecurity6 TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security6 Alarm."
|
|
::= 38
|
|
|
|
|
|
envSecurity7 TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security7 Alarm."
|
|
::= 39
|
|
|
|
|
|
--envSecurity1Return TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "WARNING: Security1 Normal."
|
|
-- ::= 40
|
|
|
|
|
|
--envSecurity2Return TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "WARNING: Security2 Normal"
|
|
-- ::= 41
|
|
|
|
|
|
--envSecurity3Return TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "WARNING: Security3 Normal."
|
|
-- ::= 42
|
|
|
|
|
|
--envSecurity4Return TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "WARNING: Security4 Normal."
|
|
-- ::= 43
|
|
|
|
|
|
--envSecurity5Return TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "WARNING: Security5 Normal."
|
|
-- ::= 44
|
|
|
|
|
|
--envSecurity6Return TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "WARNING: Security6 Normal."
|
|
-- ::= 45
|
|
|
|
|
|
--envSecurity7Return TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "WARNING: Security7 Normal."
|
|
-- ::= 46
|
|
|
|
|
|
upsRecroterror TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Rectifier Rotation Error"
|
|
::= 47
|
|
|
|
|
|
upsBypassFreFail TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Bypass Frequency Fail"
|
|
::= 48
|
|
|
|
|
|
upsBypassacnormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Bypass AC Normal"
|
|
::= 49
|
|
|
|
|
|
upsBypassacabnormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Bypass AC Abnormal"
|
|
::= 50
|
|
|
|
|
|
upsTest TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: UPS Test"
|
|
::= 51
|
|
|
|
|
|
upsScheduleShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: UPS Schedule Shutdown"
|
|
::= 52
|
|
|
|
upsBypassReturn TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS return from Bypass Mode"
|
|
::= 53
|
|
|
|
upsShortCircuitShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Short Circuit Shutdown"
|
|
::= 54
|
|
|
|
upsInverterOutputFailShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Inverter Output Fail Shutdown"
|
|
::= 55
|
|
|
|
upsBypassBreadkerOnShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Manual Bypass Breaker on Shutdown"
|
|
::= 56
|
|
|
|
upsHighDCShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS High DC Shutdown"
|
|
::= 57
|
|
|
|
upsEmergencyStop TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Emergency Stop"
|
|
::= 58
|
|
|
|
upsInverterMode TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Static Switch in Inverter Mode"
|
|
::= 59
|
|
|
|
upsBypassMode TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Static Switch in Bypass Mode"
|
|
::= 60
|
|
|
|
upsOverTemperatureShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Over Temperature Shutdown"
|
|
::= 61
|
|
|
|
upsOverLoadShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Overload Shutdown"
|
|
::= 62
|
|
|
|
upsCapacityUnderrun TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Capacity Underrun"
|
|
::= 63
|
|
|
|
upsCapacityNormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Capacity Normal"
|
|
::= 64
|
|
|
|
upsLowBatteryShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Low Battery Shutdown"
|
|
::= 67
|
|
|
|
buckOn TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS has enabled Buck."
|
|
::= 68
|
|
|
|
returnFromBuck TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS has return from Buck."
|
|
::= 69
|
|
|
|
returnFromBoost TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS has return from Boost."
|
|
::= 70
|
|
|
|
END
|