293 lines
7.8 KiB
Plaintext
Executable File
293 lines
7.8 KiB
Plaintext
Executable File
MBG-SNMP-FDMXPT-MIB DEFINITIONS ::= BEGIN
|
|
|
|
--
|
|
-- Top-level infrastructure of the MBG FDMXPT-SNMP project enterprise MIB tree
|
|
--
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE, Integer32, NOTIFICATION-TYPE FROM SNMPv2-SMI
|
|
MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF
|
|
DisplayString FROM SNMPv2-TC
|
|
|
|
mbgSnmpRoot FROM MBG-SNMP-ROOT-MIB;
|
|
|
|
mbgFDM MODULE-IDENTITY
|
|
LAST-UPDATED "201201250000Z"
|
|
ORGANIZATION "www.meinberg.de"
|
|
CONTACT-INFO
|
|
"postal: Meinberg Funkuhren
|
|
Auf der Landwehr 22
|
|
31812 Bad Pyrmont
|
|
Germany
|
|
|
|
email: info@meinberg.de"
|
|
DESCRIPTION
|
|
"Top-level infrastructure of the MBG-SNMP project enterprise MIB tree"
|
|
REVISION "201201250000Z"
|
|
DESCRIPTION
|
|
"Update to new format using MBG-SNMP-ROOT-MIB"
|
|
REVISION "200601200000Z"
|
|
DESCRIPTION
|
|
"Covering FDMXPT modules from Meinberg"
|
|
::= { mbgSnmpRoot 15 }
|
|
|
|
|
|
--
|
|
-- MBG-SNMP enterprise-specific management objects
|
|
--
|
|
--
|
|
-- Copy everything from here into your MBG-SNMP-MIB.txt file, if you are using several different SNMP-supporting Meinberg systems
|
|
--
|
|
|
|
mbgFDMData OBJECT IDENTIFIER ::= {mbgFDM 2}
|
|
mbgFDMTraps OBJECT IDENTIFIER ::= {mbgFDM 3}
|
|
|
|
|
|
|
|
mbgFDMMode OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current Mode of FDM"
|
|
::= { mbgFDMData 1 }
|
|
|
|
mbgFDMModeVal OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current Mode of FDM as value"
|
|
--- " 0: Normal Operation"
|
|
--- " 1: Direct Mode (no automatic monitoring)"
|
|
--- " 2: Timeout Error (no communication with FDM)"
|
|
--- " 3: Error (check error bits)"
|
|
DEFVAL { 0 }
|
|
::= { mbgFDMData 2 }
|
|
|
|
mbgFDMFrequency OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current powerline frequency in Hz as measured by FDM"
|
|
--- Example: "49.997" represents 49.997 Hz
|
|
::= { mbgFDMData 3 }
|
|
|
|
mbgFDMFrequencyVal OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current powerline frequency in Hz*1000 as value"
|
|
--- Example: 50034 represents 50.034 Hz
|
|
DEFVAL { 0 }
|
|
::= { mbgFDMData 4 }
|
|
|
|
|
|
mbgFDMRefTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current reference time of FDM"
|
|
--- Example: "15:35:01", is provided by the reference clock (e.g. GPS)
|
|
::= { mbgFDMData 5 }
|
|
|
|
mbgFDMPLTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current powerline time of FDM"
|
|
--- Example: "15:35:01", is initially read from the reference clock and then
|
|
--- the powerline frequency is used as a clock frequency
|
|
::= { mbgFDMData 6 }
|
|
|
|
mbgFDMFreqDev OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Frequency Devidation in Hz"
|
|
--- Example: "-00.002" represents a difference of -0.002 Hz
|
|
--- (current powerline frequency compared to nominal powerline frequency)
|
|
::= { mbgFDMData 7 }
|
|
|
|
mbgFDMFreqDevVal OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current frequency deviation in Hz*1000 as value"
|
|
--- Example: -22 represents -0.022 Hz
|
|
DEFVAL { 0 }
|
|
::= { mbgFDMData 8 }
|
|
|
|
mbgFDMTimeDev OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time Devidation in seconds"
|
|
--- Example: "-00.102" represents a time difference of -102 ms or -0.102 seconds"
|
|
--- (reftime compared to pltime)
|
|
::= { mbgFDMData 9 }
|
|
|
|
mbgFDMTimeDevVal OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current time deviation in ms"
|
|
--- Example: -22 represents -22 ms
|
|
DEFVAL { 0 }
|
|
::= { mbgFDMData 10 }
|
|
|
|
mbgFDMErrorStatus OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 8 error bits of the FDM in string format"
|
|
--- Example: "00000000" says "no error bits set"
|
|
--- and "00000101" says Error bits 1 and 3 set
|
|
::= { mbgFDMData 11 }
|
|
|
|
--
|
|
-- SNMP trap definitions
|
|
--
|
|
|
|
mbgFDMTrapInternalError NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when an internal error occurs (see error bits)"
|
|
::= { mbgFDMTraps 1 }
|
|
|
|
mbgFDMTrapNoTimeString NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when no time string can be read from reference clock"
|
|
::= { mbgFDMTraps 2 }
|
|
|
|
mbgFDMTrapNo10Mhz NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when the reference frequency is not available"
|
|
::= { mbgFDMTraps 3 }
|
|
|
|
mbgFDMTrapNoPPS NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when the reference Pulse Per Second is not available"
|
|
::= { mbgFDMTraps 4 }
|
|
|
|
mbgFDMTrapNoPowerline NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when powerline frequency could not be detected"
|
|
-- is the powerline connected?
|
|
::= { mbgFDMTraps 5 }
|
|
|
|
mbgFDMTrapTimeDeviationOverflow NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when a time deviation overflow happens"
|
|
::= { mbgFDMTraps 6 }
|
|
|
|
mbgFDMTrapA1Overflow NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when Analog1 overflows"
|
|
::= { mbgFDMTraps 7 }
|
|
|
|
mbgFDMTrapA2Overflow NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when Analog2 overflows"
|
|
::= { mbgFDMTraps 8 }
|
|
|
|
mbgFDMTrapFreqLimitExceeded NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when the current frequency exceeds the valid frequency range"
|
|
::= { mbgFDMTraps 9 }
|
|
|
|
mbgFDMXPTReboot NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when the FDMXPT module starts up"
|
|
-- happens at system startup and if the FDMXPT module reboots
|
|
::= { mbgFDMTraps 10 }
|
|
|
|
mbgFDMNormalOperation NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when the FDM status is OK (Normal Operation)"
|
|
-- happens at system startup and as soon as all error conditions have been cleared
|
|
::= { mbgFDMTraps 99 }
|
|
|
|
--
|
|
-- Conformance Statements
|
|
--
|
|
|
|
|
|
mbgFDMConformance OBJECT IDENTIFIER ::= { mbgFDM 90 }
|
|
mbgFDMCompliances OBJECT IDENTIFIER ::= { mbgFDMConformance 1 }
|
|
mbgFDMGroups OBJECT IDENTIFIER ::= { mbgFDMConformance 2 }
|
|
|
|
mbgFDMCompliance MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The compliance statement for SNMP entities which implement version 2
|
|
of the XPT MIB"
|
|
MODULE -- this module
|
|
MANDATORY-GROUPS {
|
|
mbgFDMObjectsGroup,
|
|
mbgFDMTrapsGroup
|
|
}
|
|
::= { mbgFDMCompliances 1 }
|
|
|
|
|
|
mbgFDMObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
mbgFDMMode,
|
|
mbgFDMModeVal,
|
|
mbgFDMFrequency,
|
|
mbgFDMFrequencyVal,
|
|
mbgFDMRefTime,
|
|
mbgFDMPLTime,
|
|
mbgFDMFreqDev,
|
|
mbgFDMFreqDevVal,
|
|
mbgFDMTimeDev,
|
|
mbgFDMTimeDevVal,
|
|
mbgFDMErrorStatus
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The collection of objects for the MBG FDMXPT MIB"
|
|
|
|
::= { mbgFDMGroups 1 }
|
|
|
|
mbgFDMTrapsGroup NOTIFICATION-GROUP
|
|
NOTIFICATIONS {
|
|
mbgFDMTrapInternalError,
|
|
mbgFDMTrapNoTimeString,
|
|
mbgFDMTrapNo10Mhz,
|
|
mbgFDMTrapNoPPS,
|
|
mbgFDMTrapNoPowerline,
|
|
mbgFDMTrapTimeDeviationOverflow,
|
|
mbgFDMTrapA1Overflow,
|
|
mbgFDMTrapA2Overflow,
|
|
mbgFDMTrapFreqLimitExceeded,
|
|
mbgFDMXPTReboot,
|
|
mbgFDMNormalOperation
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The collection of traps for the MBG FDMXPT MIB"
|
|
|
|
::= { mbgFDMGroups 2 }
|
|
|
|
END
|