-- Mitsubishi.mib - MIB file for Mitsubishi UPSs
|
|
|
|
UPS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
TRAP-TYPE
|
|
FROM RFC-1215
|
|
DisplayString
|
|
FROM RFC1213-MIB
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
Gauge, Counter, TimeTicks, mgmt
|
|
FROM RFC1155-SMI
|
|
;
|
|
|
|
PositiveInteger ::= INTEGER
|
|
NonNegativeInteger ::= INTEGER
|
|
TimeStamp ::= TimeTicks
|
|
TimeInterval ::= INTEGER (0..2147483647)
|
|
TestAndIncr ::= INTEGER (0..2147483647)
|
|
AutonomousType ::= DisplayString
|
|
|
|
Tag OBJECT IDENTIFIER ::= { enterprises 13891 }
|
|
MitsubishiUPS OBJECT IDENTIFIER ::= { Tag 101 }
|
|
|
|
upsIdent OBJECT IDENTIFIER ::= { MitsubishiUPS 1 }
|
|
|
|
upsIdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the UPS manufacturer."
|
|
::= { upsIdent 1 }
|
|
|
|
upsIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Model designation."
|
|
::= { upsIdent 2 }
|
|
|
|
upsIdentUPSSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS firmware/software version(s). This variable
|
|
may or may not have the same value as
|
|
upsIdentAgentSoftwareVersion in some implementations."
|
|
::= { upsIdent 3 }
|
|
|
|
upsIdentAgentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS agent software version. This variable may or may
|
|
not have the same value as upsIdentUPSSoftwareVersion in
|
|
some implementations."
|
|
::= { upsIdent 4 }
|
|
|
|
upsIdentName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the UPS. This object should be
|
|
set by the administrator."
|
|
::= { upsIdent 5 }
|
|
|
|
upsIdentAttachedDevices OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the devices attached to the output
|
|
of the UPS. This object should be set by the administrator."
|
|
::= { upsIdent 6 }
|
|
|
|
upsBattery OBJECT IDENTIFIER ::= { MitsubishiUPS 2 }
|
|
|
|
upsBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
unknown(1),
|
|
batteryNormal(2),
|
|
batteryLow(3),
|
|
batteryDepleted(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The indication of the capacity remaining in the UPS batteries.
|
|
A value of batteryNormal indicates a normal battery condition.
|
|
A value of batteryLow indicates the remaining battery run-time
|
|
will not maintain the output load for an extended period of time.
|
|
A value of batteryDepleted indicates that the UPS will be unable
|
|
to sustain the present load when and if the utility power is lost."
|
|
::= { upsBattery 1 }
|
|
|
|
upsSecondsOnBattery OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS seconds
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the unit is on battery power, the elapsed time in seconds
|
|
since the UPS last switched to battery power, or the time since
|
|
the network management system was last restarted, whichever is less.
|
|
Zero shall be returned if the unit is not on battery power."
|
|
::= { upsBattery 2 }
|
|
|
|
upsEstimatedMinutesRemaining OBJECT-TYPE
|
|
SYNTAX PositiveInteger -- UNITS minutes
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An estimate of the time in minutes until the battery is depleted
|
|
under the present load conditions if the utility power is off and
|
|
remains off, or if it were to be lost and remain off."
|
|
::= { upsBattery 3 }
|
|
|
|
upsEstimatedChargeRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS percent
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An estimate of the battery charge remaining expressed as a
|
|
percent of full charge."
|
|
::= { upsBattery 4 }
|
|
|
|
upsBatteryVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Volt DC
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present battery voltage (0.1 Volt DC)."
|
|
::= { upsBattery 5 }
|
|
|
|
upsBatteryCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER (-2147483648..2147483647) -- UNITS 0.1 Amp DC
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present battery current (0.1 Amp DC)."
|
|
::= { upsBattery 6 }
|
|
|
|
upsBatteryTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER (-2147483648..2147483647) -- UNITS degrees Centigrade
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ambient temperature at or near the UPS Battery casing (degrees Centigrade)."
|
|
::= { upsBattery 7 }
|
|
|
|
upsInput OBJECT IDENTIFIER ::= { MitsubishiUPS 3 }
|
|
|
|
upsInputLineBads OBJECT-TYPE
|
|
SYNTAX Counter
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A count of the number of times the input entered an
|
|
out-of-tolerance condition as defined by the manufacturer.
|
|
This count is incremented by one each time the input
|
|
transitions from zero out-of-tolerance lines to one or more
|
|
input lines out-of-tolerance."
|
|
::= { upsInput 1 }
|
|
|
|
upsInputNumLines OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of input lines utilized in this device. This
|
|
variable indicates the number of rows in the input table."
|
|
::= { upsInput 2 }
|
|
|
|
upsInputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsInputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of input table entries. The number of entries
|
|
is given by the value of upsInputNumLines."
|
|
::= { upsInput 3 }
|
|
|
|
upsInputEntry OBJECT-TYPE
|
|
SYNTAX UpsInputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular input line."
|
|
INDEX { upsInputLineIndex }
|
|
::= { upsInputTable 1 }
|
|
|
|
UpsInputEntry ::=
|
|
SEQUENCE
|
|
{
|
|
upsInputLineIndex PositiveInteger,
|
|
upsInputFrequency NonNegativeInteger,
|
|
upsInputVoltage NonNegativeInteger,
|
|
upsInputCurrent NonNegativeInteger,
|
|
upsInputTruePower NonNegativeInteger
|
|
}
|
|
|
|
upsInputLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The input line identifier."
|
|
::= { upsInputEntry 1 }
|
|
|
|
upsInputFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present input frequency (0.1 Hertz)."
|
|
::= { upsInputEntry 2 }
|
|
|
|
upsInputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Volt
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input voltage (0.1 RMS Volt)."
|
|
::= { upsInputEntry 3 }
|
|
|
|
upsInputCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input current (0.1 RMS Amp)."
|
|
::= { upsInputEntry 4 }
|
|
|
|
upsInputTruePower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS Watts
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input true power (watts)."
|
|
::= { upsInputEntry 5 }
|
|
|
|
upsOutput OBJECT IDENTIFIER ::= { MitsubishiUPS 4 }
|
|
|
|
upsOutputSource OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
other(1),
|
|
none(2),
|
|
normal(3),
|
|
bypass(4),
|
|
battery(5),
|
|
booster(6),
|
|
reducer(7)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present source of output power. A value of none (2) indicates
|
|
there is no source of output power (and therefore no output power),
|
|
for example, the system has opened the output breaker."
|
|
::= { upsOutput 1 }
|
|
|
|
upsOutputFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output frequency (0.1 Hertz)."
|
|
::= { upsOutput 2 }
|
|
|
|
upsOutputNumLines OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of output lines utilized in this device. This
|
|
variable indicates the number of rows in the output table."
|
|
::= { upsOutput 3 }
|
|
|
|
upsOutputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsOutputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of output table entries. The number of
|
|
entries is given by the value of upsOutputNumLines."
|
|
::= { upsOutput 4 }
|
|
|
|
upsOutputEntry OBJECT-TYPE
|
|
SYNTAX UpsOutputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular output line."
|
|
INDEX { upsOutputLineIndex }
|
|
::= { upsOutputTable 1 }
|
|
|
|
UpsOutputEntry ::=
|
|
SEQUENCE
|
|
{
|
|
upsOutputLineIndex PositiveInteger,
|
|
upsOutputVoltage NonNegativeInteger,
|
|
upsOutputCurrent NonNegativeInteger,
|
|
upsOutputPower NonNegativeInteger,
|
|
upsOutputPercentLoad INTEGER
|
|
}
|
|
|
|
upsOutputLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output line identifier."
|
|
::= { upsOutputEntry 1 }
|
|
|
|
upsOutputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Volts
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output voltage (0.1 RMS Volt)."
|
|
::= { upsOutputEntry 2 }
|
|
|
|
upsOutputCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output current (0.1 RMS Amp)."
|
|
::= { upsOutputEntry 3 }
|
|
|
|
upsOutputPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS Watts
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output true power (watts)."
|
|
::= { upsOutputEntry 4 }
|
|
|
|
upsOutputPercentLoad OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS percent
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The percentage of the UPS power capacity presently being
|
|
used on this output line (the greater of the percent load
|
|
of true power capacity and the percent load of VA."
|
|
::= { upsOutputEntry 5 }
|
|
|
|
upsBypass OBJECT IDENTIFIER ::= { MitsubishiUPS 5 }
|
|
|
|
upsBypassFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass frequency."
|
|
::= { upsBypass 1 }
|
|
|
|
upsBypassNumLines OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of bypass lines utilized in this device. This
|
|
entry indicates the number of rows in the bypass table."
|
|
::= { upsBypass 2 }
|
|
|
|
upsBypassTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsBypassEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of bypass table entries. The number of entries
|
|
is given by the value of upsBypassNumLines."
|
|
::= { upsBypass 3 }
|
|
|
|
upsBypassEntry OBJECT-TYPE
|
|
SYNTAX UpsBypassEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular bypass input."
|
|
INDEX { upsBypassLineIndex }
|
|
::= { upsBypassTable 1 }
|
|
|
|
UpsBypassEntry ::=
|
|
SEQUENCE
|
|
{
|
|
upsBypassLineIndex PositiveInteger,
|
|
upsBypassVoltage NonNegativeInteger,
|
|
upsBypassCurrent NonNegativeInteger,
|
|
upsBypassPower NonNegativeInteger
|
|
}
|
|
|
|
upsBypassLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line identifier."
|
|
::= { upsBypassEntry 1 }
|
|
|
|
upsBypassVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Volts
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass voltage (0.1 RMS Volt)."
|
|
::= { upsBypassEntry 2 }
|
|
|
|
upsBypassCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass current (0.1 RMS Amp)."
|
|
::= { upsBypassEntry 3 }
|
|
|
|
upsBypassPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS Watts
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present true power conveyed by the bypass (watts)."
|
|
::= { upsBypassEntry 4 }
|
|
|
|
upsAlarm OBJECT IDENTIFIER ::= { MitsubishiUPS 6 }
|
|
|
|
upsAlarmsPresent OBJECT-TYPE
|
|
SYNTAX Gauge
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present number of active alarm conditions."
|
|
::= { upsAlarm 1 }
|
|
|
|
upsAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of alarm table entries. Alarms are named by
|
|
an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single
|
|
table to reflect well known alarms plus alarms defined
|
|
by a particular implementation, i.e., as documented in
|
|
the private enterprise MIB definition for the device.
|
|
No two rows will have the same value of upsAlarmDescr,
|
|
since alarms define conditions. In order to meet this
|
|
requirement, care should be taken in the definition of
|
|
alarm conditions to insure that a system cannot enter
|
|
the same condition multiple times simultaneously.
|
|
|
|
The number of rows in the table at any given time is
|
|
reflected by the value of upsAlarmsPresent."
|
|
::= { upsAlarm 2 }
|
|
|
|
upsAlarmEntry OBJECT-TYPE
|
|
SYNTAX UpsAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular alarm."
|
|
INDEX { upsAlarmId }
|
|
::= { upsAlarmTable 1 }
|
|
|
|
UpsAlarmEntry ::=
|
|
SEQUENCE
|
|
{
|
|
upsAlarmId PositiveInteger,
|
|
upsAlarmDescr AutonomousType,
|
|
upsAlarmTime TimeStamp
|
|
}
|
|
|
|
upsAlarmId OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A unique identifier for an alarm condition. This
|
|
value must remain constant."
|
|
::= { upsAlarmEntry 1 }
|
|
|
|
upsAlarmDescr OBJECT-TYPE
|
|
SYNTAX AutonomousType
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A reference to an alarm description object. The object
|
|
referenced should not be accessible, but rather be used
|
|
to provide a unique description of the alarm condition."
|
|
::= { upsAlarmEntry 2 }
|
|
|
|
upsAlarmTime OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of sysUpTime when the alarm condition was
|
|
detected. If the alarm condition was detected at the
|
|
time of agent startup and presumably existed before
|
|
agent startup, the value of upsAlarmTime shall equal 0."
|
|
::= { upsAlarmEntry 3 }
|
|
|
|
upsAlarmID OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A unique identifier for an alarm condition. This
|
|
value must remain constant."
|
|
::= { upsAlarm 4 }
|
|
|
|
upsAlarmDESCR OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A reference to an alarm description object. The object
|
|
references should not be accessible, but rather be used
|
|
to provide a unique description of the alarm condition."
|
|
::= { upsAlarm 5 }
|
|
|
|
upsWellKnownAlarms OBJECT IDENTIFIER ::= { upsAlarm 3 }
|
|
|
|
upsAlarmBatteryBad OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"One or more batteries have been determined to require
|
|
replacement."
|
|
::= { upsWellKnownAlarms 1 }
|
|
|
|
upsAlarmOnBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS is drawing power from the batteries."
|
|
::= { upsWellKnownAlarms 2 }
|
|
|
|
upsAlarmLowBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The remaining battery run-time is less than or equal
|
|
to upsConfigLowBattTime."
|
|
::= { upsWellKnownAlarms 3 }
|
|
|
|
upsAlarmDepletedBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS will be unable to sustain the present load
|
|
when and if the utility power is lost."
|
|
::= { upsWellKnownAlarms 4 }
|
|
|
|
upsAlarmTempBad OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A temperature is out of tolerance."
|
|
::= { upsWellKnownAlarms 5 }
|
|
|
|
upsAlarmInputBad OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An input condition is out of tolerance."
|
|
::= { upsWellKnownAlarms 6 }
|
|
|
|
upsAlarmOutputBad OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An output condition (other than OutputOverload) is
|
|
out of tolerance."
|
|
::= { upsWellKnownAlarms 7 }
|
|
|
|
upsAlarmOutputOverload OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output load exceeds the UPS output capacity."
|
|
::= { upsWellKnownAlarms 8 }
|
|
|
|
upsAlarmOnBypass OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Bypass is presently engaged on the UPS."
|
|
::= { upsWellKnownAlarms 9 }
|
|
|
|
upsAlarmBypassBad OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Bypass is out of tolerance."
|
|
::= { upsWellKnownAlarms 10 }
|
|
|
|
upsAlarmOutputOffAsRequested OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS has shut down as requested, i.e., the output
|
|
is off."
|
|
::= { upsWellKnownAlarms 11 }
|
|
|
|
upsAlarmUpsOffAsRequested OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The entire UPS has shutdown as commanded."
|
|
::= { upsWellKnownAlarms 12 }
|
|
|
|
upsAlarmChargerFailed OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An uncorrected problem has been detected within the
|
|
UPS charger subsystem."
|
|
::= { upsWellKnownAlarms 13 }
|
|
|
|
upsAlarmUpsOutputOff OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output of the UPS is in the off state."
|
|
::= { upsWellKnownAlarms 14 }
|
|
|
|
upsAlarmUpsSystemOff OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS system is in the off state."
|
|
::= { upsWellKnownAlarms 15 }
|
|
|
|
upsAlarmFanFailure OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The failure of one or more fans in the UPS has been
|
|
detected."
|
|
::= { upsWellKnownAlarms 16 }
|
|
|
|
upsAlarmFuseFailure OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The failure of one or more fuses has been detected."
|
|
::= { upsWellKnownAlarms 17 }
|
|
|
|
upsAlarmGeneralFault OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A general fault in the UPS has been detected."
|
|
::= { upsWellKnownAlarms 18 }
|
|
|
|
upsAlarmDiagnosticTestFailed OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The result of the last diagnostic test indicates a
|
|
failure."
|
|
::= { upsWellKnownAlarms 19 }
|
|
|
|
upsAlarmCommunicationsLost OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A problem has been encountered in the
|
|
communications between the agent and the UPS."
|
|
::= { upsWellKnownAlarms 20 }
|
|
|
|
upsAlarmAwaitingPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS output is off and the UPS is awaiting the
|
|
return of input power."
|
|
::= { upsWellKnownAlarms 21 }
|
|
|
|
upsAlarmShutdownPending OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A upsShutdownAfterDelay countdown is underway."
|
|
::= { upsWellKnownAlarms 22 }
|
|
|
|
upsAlarmShutdownImminent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS will turn off power to the load in less than
|
|
5 seconds; this may be either a timed shutdown or a
|
|
low battery shutdown."
|
|
::= { upsWellKnownAlarms 23 }
|
|
|
|
upsAlarmTestInProgress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A test is in progress, as initiated and indicated by
|
|
the Test Group. Tests initiated via other
|
|
implementation-specific mechanisms can indicate the
|
|
presence of the testing in the alarm table, if
|
|
desired, via a OBJECT-TYPE macro in the MIB
|
|
document specific to that implementation and are
|
|
outside the scope of this OBJECT-TYPE."
|
|
::= { upsWellKnownAlarms 24 }
|
|
|
|
upsTest OBJECT IDENTIFIER ::= { MitsubishiUPS 7 }
|
|
|
|
upsTestId OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The test named by an OBJECT IDENTIFIER which
|
|
allows a standard mechanism for the initiation of
|
|
a test, including the well known tests identified in
|
|
this document."
|
|
::= { upsTest 1 }
|
|
|
|
upsTestSpinLock OBJECT-TYPE
|
|
SYNTAX TestAndIncr
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A spin lock on the test subsystem."
|
|
::= { upsTest 2 }
|
|
|
|
upsTestResultsSummary OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
donePass(1),
|
|
doneWarning(2),
|
|
doneError(3),
|
|
aborted(4),
|
|
inProgress(5),
|
|
noTestsInitiated(6)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The results of the current or last UPS diagnostics
|
|
test performed. The values for donePass(1),
|
|
doneWarning(2), and doneError(3) indicate that the
|
|
test completed either successfully, with a warning, or
|
|
with an error, respectively. The value aborted(4) is
|
|
returned for tests which are aborted by setting the
|
|
value of upsTestId to upsTestAbortTestInProgress.
|
|
Tests which have not yet concluded are indicated by
|
|
inProgress(5). The value noTestsInitiated(6)
|
|
indicates that no previous test results are available,
|
|
such as is the case when no tests have been run since
|
|
the last reinitialization of the network management
|
|
subsystem and the system has no provision for non-
|
|
volatile storage of test results."
|
|
::= { upsTest 3 }
|
|
|
|
upsTestResultsDetail OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Additional information about upsTestResultsSummary.
|
|
If no additional information available, a zero length
|
|
string is returned."
|
|
::= { upsTest 4 }
|
|
|
|
upsTestStartTime OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of sysUpTime at the time the test in
|
|
progress was initiated, or, if no test is in progress,
|
|
the time the previous test was initiated. If the
|
|
value of upsTestResultsSummary is noTestsInitiated(6),
|
|
upsTestStartTime has the value 0."
|
|
::= { upsTest 5 }
|
|
|
|
upsTestElapsedTime OBJECT-TYPE
|
|
SYNTAX TimeInterval
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The amount of time, in TimeTicks, since the test in
|
|
progress was initiated, or, if no test is in progress,
|
|
the previous test took to complete. If the value of
|
|
upsTestResultsSummary is noTestsInitiated(6),
|
|
upsTestElapsedTime has the value 0."
|
|
::= { upsTest 6 }
|
|
|
|
upsWellKnownTests OBJECT IDENTIFIER ::= { upsTest 7 }
|
|
|
|
upsTestNoTestsInitiated OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"No tests have been initiated and no test is in progress."
|
|
::= { upsWellKnownTests 1 }
|
|
|
|
upsTestAbortTestInProgress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The test in progress is to be aborted / the test in
|
|
progress was aborted."
|
|
::= { upsWellKnownTests 2 }
|
|
|
|
upsTestGeneralSystemsTest OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The manufacturer's standard test of UPS device systems."
|
|
::= { upsWellKnownTests 3 }
|
|
|
|
upsTestQuickBatteryTest OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A test that is sufficient to determine if the battery
|
|
needs replacement."
|
|
::= { upsWellKnownTests 4 }
|
|
|
|
upsTestDeepBatteryCalibration OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The system is placed on battery to a discharge level,
|
|
set by the manufacturer, sufficient to determine
|
|
battery replacement and battery run-time with a high
|
|
degree of confidence. WARNING: this test will leave
|
|
the battery in a low charge state and will require
|
|
time for recharging to a level sufficient to provide
|
|
normal battery duration for the protected load."
|
|
::= { upsWellKnownTests 5 }
|
|
|
|
upsControl OBJECT IDENTIFIER ::= { MitsubishiUPS 8 }
|
|
|
|
upsShutdownType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
output(1),
|
|
system(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object determines the nature of the action to be
|
|
taken at the time when the countdown of the
|
|
upsShutdownAfterDelay and upsRebootWithDuration
|
|
objects reaches zero.
|
|
|
|
Setting this object to output(1) indicates that
|
|
shutdown requests should cause only the output of the
|
|
UPS to turn off. Setting this object to system(2)
|
|
indicates that shutdown requests will cause the entire
|
|
UPS system to turn off."
|
|
::= { upsControl 1 }
|
|
|
|
upsShutdownAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS seconds
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object will shutdown (i.e., turn off)
|
|
either the UPS output or the UPS system (as determined
|
|
by the value of upsShutdownType at the time of
|
|
shutdown) after the indicated number of seconds, or
|
|
less if the UPS batteries become depleted. Setting
|
|
this object to 0 will cause the shutdown to occur
|
|
immediately. Setting this object to -1 will abort the
|
|
countdown. If the system is already in the desired
|
|
state at the time the countdown reaches 0, then
|
|
nothing will happen. That is, there is no additional
|
|
action at that time if upsShutdownType = system and
|
|
the system is already off. Similarly, there is no
|
|
additional action at that time if upsShutdownType =
|
|
output and the output is already off. When read,
|
|
upsShutdownAfterDelay will return the number of
|
|
seconds remaining until shutdown, or -1 if no shutdown
|
|
countdown is in effect. On some systems, if the agent
|
|
is restarted while a shutdown countdown is in effect,
|
|
the countdown may be aborted. Sets to this object
|
|
override any upsShutdownAfterDelay already in effect."
|
|
::= { upsControl 2 }
|
|
|
|
upsStartupAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS seconds
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object will start the output after the
|
|
indicated number of seconds, including starting the
|
|
UPS, if necessary. Setting this object to 0 will
|
|
cause the startup to occur immediately. Setting this
|
|
object to -1 will abort the countdown. If the output
|
|
is already on at the time the countdown reaches 0,
|
|
then nothing will happen. Sets to this object
|
|
override the effect of any upsStartupAfterDelay
|
|
countdown or upsRebootWithDuration countdown in
|
|
progress. When read, upsStartupAfterDelay will return
|
|
the number of seconds until startup, or -1 if no
|
|
startup countdown is in effect. If the countdown
|
|
expires during a utility failure, the startup shall
|
|
not occur until the utility power is restored. On
|
|
some systems, if the agent is restarted while a
|
|
startup countdown is in effect, the countdown is
|
|
aborted."
|
|
::= { upsControl 3 }
|
|
|
|
upsRebootWithDuration OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS seconds
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object will immediately shutdown (i.e.,
|
|
turn off) either the UPS output or the UPS system (as
|
|
determined by the value of upsShutdownType at the time
|
|
of shutdown) for a period equal to the indicated
|
|
number of seconds, after which time the output will be
|
|
started, including starting the UPS, if necessary. If
|
|
the number of seconds required to perform the request
|
|
is greater than the requested duration, then the
|
|
requested shutdown and startup cycle shall be
|
|
performed in the minimum time possible, but in no case
|
|
shall this require more than the requested duration
|
|
plus 60 seconds. When read, upsRebootWithDuration
|
|
shall return the number of seconds remaining in the
|
|
countdown, or -1 if no countdown is in progress. If
|
|
the startup should occur during a utility failure, the
|
|
startup shall not occur until the utility power is
|
|
restored."
|
|
::= { upsControl 4 }
|
|
|
|
upsAutoRestart OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object to 'on' will cause the UPS system
|
|
to restart after a shutdown if the shutdown occurred
|
|
during a power loss as a result of either a
|
|
upsShutdownAfterDelay or an internal battery depleted
|
|
condition. Setting this object to 'off' will prevent
|
|
the UPS system from restarting after a shutdown until
|
|
an operator manually or remotely explicitly restarts
|
|
it. If the UPS is in a startup or reboot countdown,
|
|
then the UPS will not restart until that delay has
|
|
been satisfied."
|
|
::= { upsControl 5 }
|
|
|
|
upsConfig OBJECT IDENTIFIER ::= { MitsubishiUPS 9 }
|
|
|
|
upsConfigInputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS RMS Volts
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal input voltage (RMS Volts).
|
|
On those systems which support read-write access to this
|
|
object, if there is an attempt to set this variable to
|
|
a value that is not supported, the request must be
|
|
rejected and the agent shall respond with an
|
|
appropriate error message, i.e., badValue for SNMPv1,
|
|
or inconsistentValue for SNMPv2."
|
|
::= { upsConfig 1 }
|
|
|
|
upsConfigInputFreq OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The nominal input frequency (0.1 Hertz). On those systems
|
|
which support read-write access to this object, if there is
|
|
an attempt to set this variable to a value that is not
|
|
supported, the request must be rejected and the agent
|
|
shall respond with an appropriate error message, i.e.,
|
|
badValue for SNMPv1, or inconsistentValue for SNMPv2."
|
|
::= { upsConfig 2 }
|
|
|
|
upsConfigOutputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS RMS Volts
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal output voltage (RMS Volts).
|
|
On those systems which support read-write access to this
|
|
object, if there is an attempt to set this variable to
|
|
a value that is not supported, the request must be
|
|
rejected and the agent shall respond with an
|
|
appropriate error message, i.e., badValue for SNMPv1,
|
|
or inconsistentValue for SNMPv2."
|
|
::= { upsConfig 3 }
|
|
|
|
upsConfigOutputFreq OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The nominal output frequency (0.1 Hertz). On those systems
|
|
which support read-write access to this object, if there is
|
|
an attempt to set this variable to a value that is not
|
|
supported, the request must be rejected and the agent
|
|
shall respond with an appropriate error message, i.e.,
|
|
badValue for SNMPv1, or inconsistentValue for SNMPv2."
|
|
::= { upsConfig 4 }
|
|
|
|
upsConfigOutputVA OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS Volt-Amps
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal Volt-Amp rating (Volt-Amps)."
|
|
::= { upsConfig 5 }
|
|
|
|
upsConfigOutputPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS Watts
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal true power rating (watts)."
|
|
::= { upsConfig 6 }
|
|
|
|
upsConfigLowBattTime OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS minutes
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of upsEstimatedMinutesRemaining at which a
|
|
lowBattery condition is declared. For agents which
|
|
support only discrete (discontinuous) values, then the
|
|
agent shall round up to the next supported value. If
|
|
the requested value is larger than the largest
|
|
supported value, then the largest supported value
|
|
shall be selected."
|
|
::= { upsConfig 7 }
|
|
|
|
upsConfigAudibleStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
disabled(1),
|
|
enabled(2),
|
|
muted(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The requested state of the audible alarm. When in
|
|
the disabled state, the audible alarm should never
|
|
sound. The enabled state is self-describing. Setting
|
|
this object to muted(3) when the audible alarm is
|
|
sounding shall temporarily silence the alarm. It will
|
|
remain muted until it would normally stop sounding and
|
|
the value returned for read operations during this
|
|
period shall equal muted(3). At the end of this
|
|
period, the value shall revert to enabled(2). Writes
|
|
of the value muted(3) when the audible alarm is not
|
|
sounding shall be accepted but otherwise shall have no
|
|
effect."
|
|
::= { upsConfig 8 }
|
|
|
|
upsConfigLowVoltageTransferPoint OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS RMS Volts
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum input line voltage (RMS Volts) allowed before
|
|
the UPS system transfers to battery backup."
|
|
::= { upsConfig 9 }
|
|
|
|
upsConfigHighVoltageTransferPoint OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS RMS Volts
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum line voltage (RMS Volts) allowed before the UPS
|
|
system transfers to battery backup."
|
|
::= { upsConfig 10 }
|
|
|
|
-- UPS trap information group
|
|
upsTrapInfo OBJECT IDENTIFIER ::= { MitsubishiUPS 10 }
|
|
|
|
trapCode OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A number identifying the event for that last trap that was sent."
|
|
::= { upsTrapInfo 1 }
|
|
|
|
trapDescription OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the event for that last trap that was sent."
|
|
::= { upsTrapInfo 2 }
|
|
|
|
-- UPS Traps
|
|
-- upsTraps OBJECT IDENTIFIER ::= { Tag 101 }
|
|
|
|
alarmCritical TRAP-TYPE
|
|
ENTERPRISE MitsubishiUPS
|
|
VARIABLES { trapCode, trapDescription }
|
|
DESCRIPTION
|
|
"Critical alarm."
|
|
::= 1
|
|
|
|
alarmWarning TRAP-TYPE
|
|
ENTERPRISE MitsubishiUPS
|
|
VARIABLES { trapCode, trapDescription }
|
|
DESCRIPTION
|
|
"Warning alarm."
|
|
::= 2
|
|
|
|
alarmInformation TRAP-TYPE
|
|
ENTERPRISE MitsubishiUPS
|
|
VARIABLES { trapCode, trapDescription }
|
|
DESCRIPTION
|
|
"Information alarm."
|
|
::= 3
|
|
|
|
upsAlarmCleared TRAP-TYPE
|
|
ENTERPRISE MitsubishiUPS
|
|
VARIABLES { trapCode, trapDescription }
|
|
DESCRIPTION
|
|
"Alarm cleared."
|
|
::= 4
|
|
|
|
upsTrapInitialization TRAP-TYPE
|
|
ENTERPRISE MitsubishiUPS
|
|
VARIABLES { upsIdentName }
|
|
DESCRIPTION
|
|
"This trap is sent each time a NetCom device is initialized."
|
|
::= 5
|
|
|
|
END
|