PACKETFLUX-STANDBYPOWER DEFINITIONS ::= BEGIN
|
|
IMPORTS
|
|
MODULE-IDENTITY, Integer32, OBJECT-TYPE,
|
|
Gauge32, TimeTicks
|
|
FROM SNMPv2-SMI
|
|
packetfluxMgmt
|
|
FROM PACKETFLUX-SMI
|
|
OBJECT-GROUP
|
|
FROM SNMPv2-CONF
|
|
TruthValue
|
|
FROM SNMPv2-TC;
|
|
|
|
standbypower MODULE-IDENTITY
|
|
LAST-UPDATED "201306041649Z"
|
|
ORGANIZATION "PacketFlux Technologies"
|
|
CONTACT-INFO "custsvc@packetflux.com
|
|
http://www.packetflux.com"
|
|
DESCRIPTION "MIB for the PacketFlux Standby Power Controller"
|
|
|
|
REVISION "201306041649Z"
|
|
DESCRIPTION "initial version of this module"
|
|
::= { packetfluxMgmt 2 }
|
|
|
|
|
|
powercontrollerstate OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
onprimarypower( 1 ),
|
|
startingstandby( 2 ),
|
|
transferringtostandby( 3 ),
|
|
onstandbypower( 4 ),
|
|
transferringtoprimary( 5 )
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The status of the standby power controller."
|
|
::= { standbypower 1 }
|
|
|
|
transferswitchstate OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
primary( 1 ),
|
|
transfertostandby1( 2 ),
|
|
transfertostandby2( 3 ),
|
|
transfertostandby3( 4 ),
|
|
standby( 5 ),
|
|
transfertoprimary1( 6 ),
|
|
transfertoprimary2( 7 ),
|
|
transfertoprimary3( 8 )
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The current state in the transfer sequence."
|
|
::= { standbypower 2 }
|
|
|
|
standbypowerstate OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
stopped( 1 ),
|
|
prepare1( 2 ),
|
|
prepare2( 3 ),
|
|
prepare3( 4 ),
|
|
startup1( 5 ),
|
|
startup2( 6 ),
|
|
startup3( 7 ),
|
|
checkrun( 8 ),
|
|
reprepare1( 9 ),
|
|
reprepare2( 10 ),
|
|
reprepare3( 11 ),
|
|
warmup1( 12 ),
|
|
warmup2( 13 ),
|
|
warmup3( 14 ),
|
|
verifyrun( 15 ),
|
|
running( 16 ),
|
|
cooldown1( 17 ),
|
|
cooldown2( 18 ),
|
|
cooldown3( 19 ),
|
|
shutdown1( 20 ),
|
|
shutdown2( 21 ),
|
|
shutdown3( 22 ),
|
|
verifystopped( 23 ),
|
|
postshutdown1( 24 ),
|
|
postshutdown2( 25 ),
|
|
postshutdown3( 26 )
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The current state in the standby power sequence."
|
|
::= { standbypower 3 }
|
|
|
|
ac1voltage OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The voltage of the AC input AC1 in 1/10ths of
|
|
a volt."
|
|
::= { standbypower 4 }
|
|
|
|
ac1frequency OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The frequency of the AC input AC1 in 1/100ths
|
|
of a Hertz."
|
|
::= { standbypower 5 }
|
|
|
|
ac2voltage OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The voltage of the AC input AC2 in 1/10ths of
|
|
a volt."
|
|
::= { standbypower 6 }
|
|
|
|
ac2frequency OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The frequency of the AC input AC2 in 1/100ths
|
|
of a Hertz."
|
|
::= { standbypower 7 }
|
|
|
|
mtr1voltage OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The voltage of the DC input Mtr1 in 1/10ths of
|
|
a volt."
|
|
::= { standbypower 8 }
|
|
|
|
mtr2voltage OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The voltage of the DC input Mtr2 in 1/10ths of
|
|
a volt."
|
|
::= { standbypower 9 }
|
|
|
|
pwr1voltage OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The voltage of the DC input Pwr3 in 1/10ths of
|
|
a volt."
|
|
::= { standbypower 10 }
|
|
|
|
pwr2voltage OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The voltage of the DC input Pwr2 in 1/10ths of
|
|
a volt."
|
|
::= { standbypower 11 }
|
|
|
|
shuntvoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The voltage of the DC input Shunt in 1/10ths of
|
|
a millivolt. Can be negative."
|
|
::= { standbypower 12 }
|
|
|
|
temperature OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The temperature of the onboard temperature sensor
|
|
in 1/10ths of a degree centigrade."
|
|
::= { standbypower 13 }
|
|
|
|
recentunsuccessfulstarts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The number of times the standby power source was
|
|
not successfully started. This counter resets
|
|
upon a successful start. It can also be reset
|
|
via the web interface or by writing 0 to this
|
|
object."
|
|
::= { standbypower 14 }
|
|
|
|
totalunsuccessfulstarts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The number of times the standby power source was
|
|
not successfully started. This counter DOES NOT
|
|
reset upon a successful start. It can be reset
|
|
via the web interface or by writing 0 to this
|
|
object."
|
|
::= { standbypower 15 }
|
|
|
|
recentstalls OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The number of times the standby power source has
|
|
stalled. This counter resets upon a clean shutdown.
|
|
It can also be reset via the web interface or
|
|
by writing 0 to this object."
|
|
::= { standbypower 16 }
|
|
|
|
totalstalls OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The number of times the standby power source has
|
|
stalled. This counter DOES NOT reset upon a clean
|
|
shutdown. It can be reset via the web interface
|
|
or by writing 0 to this object."
|
|
::= { standbypower 17 }
|
|
|
|
numberofstarts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The number of times the secondary power source
|
|
has started. This counter increments when the
|
|
standby sequence reaches the running state. This
|
|
counter can be reset via the web interface or
|
|
by writing 0 to this object."
|
|
::= { standbypower 18 }
|
|
|
|
numberoftransfers OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The number of times the power has transfered from
|
|
primary to standby, or back. A complete transfer
|
|
cycle from primary to standby and back to primary
|
|
will increment this counter twice. This counter
|
|
can be reset via the web interface or by writing
|
|
0 to this object."
|
|
::= { standbypower 19 }
|
|
|
|
currenttimeonprimary OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The amount of time the transfer switch has been
|
|
in the primary state (position) since the most
|
|
recent transfer to that state. This timer resets
|
|
to zero when the transfer switch leaves the primary
|
|
state (position). This timer can be reset via
|
|
the web interface or by writing 0 to this object."
|
|
::= { standbypower 20 }
|
|
|
|
totaltimeonprimary OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The amount of time the transfer switch has been
|
|
in the primary state (position) since power on
|
|
or the last reset of this counter. This timer
|
|
does not automatically reset. This timer can
|
|
be reset via the web interface or by writing
|
|
0 to this object."
|
|
::= { standbypower 21 }
|
|
|
|
currenttimeonstandby OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The amount of time the transfer switch has been
|
|
in the standby state (position) since the most
|
|
recent transfer to that state. This timer resets
|
|
to zero when the transfer switch leaves the primary
|
|
state (position). This timer can be reset via
|
|
the web interface or by writing 0 to this object."
|
|
::= { standbypower 22 }
|
|
|
|
totaltimeonstandby OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The amount of time the transfer switch has been
|
|
in the standby state (position) since power on
|
|
or the last reset of this counter. This timer
|
|
does not automatically reset. This timer can
|
|
be reset via the web interface or by writing
|
|
0 to this object."
|
|
::= { standbypower 23 }
|
|
|
|
currentstandbyruntime OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The amount of time the standby power source has
|
|
been running during it's current run. This timer
|
|
resets to zero when the standby power source
|
|
shuts down. This timer can be reset via the web
|
|
interface or by writing 0 to this object."
|
|
::= { standbypower 24 }
|
|
|
|
totalstandbyruntime OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The amount of time the standby power source has
|
|
been running since power on or the last reset
|
|
of this counter. This timer does not automatically
|
|
reset. This timer can be reset via the web interface
|
|
or by writing 0 to this object."
|
|
::= { standbypower 25 }
|
|
|
|
laststandbyrun OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The amount of time since the standby power source
|
|
ran last. This timer resets upon start of the
|
|
standby power source and starts timing upon shutdown
|
|
of the standby power source. This timer can be
|
|
reset via the web interface or by writing 0 to
|
|
this object."
|
|
::= { standbypower 26 }
|
|
|
|
laststandbygracefulstop OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The amount of time since standby power source
|
|
was gracefully shutdown. This timer resets and
|
|
starts timing upon graceful shutdown of the standby
|
|
power source. This timer can be reset via the
|
|
web interface or by writing 0 to this object."
|
|
::= { standbypower 27 }
|
|
|
|
laststandbyunsuccessfulstart OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The amount of time since the last failed start
|
|
of the standby power source . This timer resets
|
|
and starts timing upon a unsuccessful start of
|
|
the power source. This timer can be reset via
|
|
the web interface or by writing 0 to this object."
|
|
::= { standbypower 28 }
|
|
|
|
laststandbyfailure OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "The amount of time since the stall or failure
|
|
while running of the standby power source . This
|
|
timer resets and starts timing upon a stall/failure
|
|
of the power source. This timer can be reset
|
|
via the web interface or by writing 0 to this
|
|
object."
|
|
::= { standbypower 29 }
|
|
|
|
switch1closed OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the Switch 1 input is closed (shorted/on).
|
|
False(2) if it is open."
|
|
::= { standbypower 30 }
|
|
|
|
switch2closed OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the Switch 2 input is closed (shorted/on).
|
|
False(2) if it is open."
|
|
::= { standbypower 31 }
|
|
|
|
switch3closed OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the Switch 3 input is closed (shorted/on).
|
|
False(2) if it is open."
|
|
::= { standbypower 32 }
|
|
|
|
switch4closed OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the Switch 4 input is closed (shorted/on).
|
|
False(2) if it is open."
|
|
::= { standbypower 33 }
|
|
|
|
switch5closed OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the Switch 5 input is closed (shorted/on).
|
|
False(2) if it is open."
|
|
::= { standbypower 34 }
|
|
|
|
enabled OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the enable input is closed (shorted/on).
|
|
False(2) if it is open."
|
|
::= { standbypower 35 }
|
|
|
|
relay1on OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the Relay 1 ouput is on (C and NO connected).
|
|
False(2) if it is off (C and NC connected)."
|
|
::= { standbypower 36 }
|
|
|
|
relay2on OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the Relay 2 ouput is on (C and NO connected).
|
|
False(2) if it is off (C and NC connected)."
|
|
::= { standbypower 37 }
|
|
|
|
relay3on OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the Relay 3 ouput is on (C and NO connected).
|
|
False(2) if it is off (C and NC connected)."
|
|
::= { standbypower 38 }
|
|
|
|
relay4on OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the Relay 4 ouput is on (C and NO connected).
|
|
False(2) if it is off (C and NC connected)."
|
|
::= { standbypower 39 }
|
|
|
|
relay5on OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the Relay 5 output is on (C and NO
|
|
connected). False(2) if it is off (C and NC connected)."
|
|
::= { standbypower 40 }
|
|
|
|
relay6on OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the Relay 6 output is on (C and NO
|
|
connected). False(2) if it is off (C and NC connected)."
|
|
::= { standbypower 41 }
|
|
|
|
relay7on OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the Relay 7 output is on (C and NO
|
|
connected). False(2) if it is off (C and NC connected)."
|
|
::= { standbypower 42 }
|
|
|
|
ruleswitchstandby OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the switch to standby rule is true.
|
|
False(2) if it is not."
|
|
::= { standbypower 43 }
|
|
|
|
rulereturnprimary OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the return to primary rule is true.
|
|
False(2) if it is not."
|
|
::= { standbypower 44 }
|
|
|
|
rulestandbygood OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the standby power good rule is true.
|
|
False(2) if it is not."
|
|
::= { standbypower 45 }
|
|
|
|
rulestopstandby OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the stop standby and consider it failed
|
|
rule is true. False(2) if it is not."
|
|
::= { standbypower 46 }
|
|
|
|
ruleexercisestandby OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the exercise standby without transfer
|
|
rule is true. False(2) if it is not."
|
|
::= { standbypower 47 }
|
|
|
|
webcontrol1 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the webcontrol 1 virtual toggle switch
|
|
is in the on position. False(2) if it is not.
|
|
This value can be written to affect the position
|
|
of the toggle switch."
|
|
::= { standbypower 48 }
|
|
|
|
webcontrol2 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the webcontrol 2 virtual toggle switch
|
|
is in the on position. False(2) if it is not.
|
|
This value can be written to affect the position
|
|
of the toggle switch."
|
|
::= { standbypower 49 }
|
|
|
|
webcontrol3 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the webcontrol 3 virtual toggle switch
|
|
is in the on position. False(2) if it is not.
|
|
This value can be written to affect the position
|
|
of the toggle switch."
|
|
::= { standbypower 50 }
|
|
|
|
webcontrol4 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the webcontrol 4 virtual toggle switch
|
|
is in the on position. False(2) if it is not.
|
|
This value can be written to affect the position
|
|
of the toggle switch."
|
|
::= { standbypower 51 }
|
|
|
|
webcontrol5 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the webcontrol 5 virtual toggle switch
|
|
is in the on position. False(2) if it is not.
|
|
This value can be written to affect the position
|
|
of the toggle switch."
|
|
::= { standbypower 52 }
|
|
|
|
webcontrol6 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the webcontrol 6 virtual toggle switch
|
|
is in the on position. False(2) if it is not.
|
|
This value can be written to affect the position
|
|
of the toggle switch."
|
|
::= { standbypower 53 }
|
|
|
|
webcontrol7 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the webcontrol 7 virtual toggle switch
|
|
is in the on position. False(2) if it is not.
|
|
This value can be written to affect the position
|
|
of the toggle switch."
|
|
::= { standbypower 54 }
|
|
|
|
webcontrol8 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "True(1) if the webcontrol 8 virtual toggle switch
|
|
is in the on position. False(2) if it is not.
|
|
This value can be written to affect the position
|
|
of the toggle switch."
|
|
::= { standbypower 55 }
|
|
|
|
standbypowerConformance OBJECT IDENTIFIER ::= { standbypower 256 }
|
|
|
|
standbypowerGroups OBJECT IDENTIFIER ::= { standbypowerConformance 1 }
|
|
|
|
packetfluxStandbypowerAllObjects OBJECT-GROUP
|
|
OBJECTS {
|
|
powercontrollerstate,
|
|
transferswitchstate,
|
|
standbypowerstate,
|
|
ac1voltage,
|
|
ac1frequency,
|
|
ac2voltage,
|
|
ac2frequency,
|
|
mtr1voltage,
|
|
mtr2voltage,
|
|
pwr1voltage,
|
|
pwr2voltage,
|
|
shuntvoltage,
|
|
temperature,
|
|
recentunsuccessfulstarts,
|
|
totalunsuccessfulstarts,
|
|
recentstalls,
|
|
totalstalls,
|
|
numberofstarts,
|
|
numberoftransfers,
|
|
currenttimeonprimary,
|
|
totaltimeonprimary,
|
|
currenttimeonstandby,
|
|
totaltimeonstandby,
|
|
currentstandbyruntime,
|
|
totalstandbyruntime,
|
|
laststandbyrun,
|
|
laststandbygracefulstop,
|
|
laststandbyunsuccessfulstart,
|
|
laststandbyfailure,
|
|
switch1closed,
|
|
switch2closed,
|
|
switch3closed,
|
|
switch4closed,
|
|
switch5closed,
|
|
enabled,
|
|
relay1on,
|
|
relay2on,
|
|
relay3on,
|
|
relay4on,
|
|
relay5on,
|
|
relay6on,
|
|
relay7on,
|
|
ruleswitchstandby,
|
|
rulereturnprimary,
|
|
rulestandbygood,
|
|
rulestopstandby,
|
|
ruleexercisestandby,
|
|
webcontrol1,
|
|
webcontrol2,
|
|
webcontrol3,
|
|
webcontrol4,
|
|
webcontrol5,
|
|
webcontrol6,
|
|
webcontrol7,
|
|
webcontrol8
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "This automatically created object group contains
|
|
all those objects that do not belong to any other
|
|
OBJECT-GROUP"
|
|
::= { standbypowerGroups 1 }
|
|
|
|
|
|
END
|