PDU-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE FROM SNMPv2-SMI
|
|
enterprises, Integer32, Unsigned32, IpAddress FROM SNMPv2-SMI
|
|
MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF
|
|
InetAddress,InetAddressType FROM INET-ADDRESS-MIB
|
|
TEXTUAL-CONVENTION, DisplayString, MacAddress, DateAndTime, TruthValue FROM SNMPv2-TC;
|
|
|
|
raritan MODULE-IDENTITY
|
|
LAST-UPDATED "201602220000Z" -- February 22,2016
|
|
ORGANIZATION "Raritan"
|
|
CONTACT-INFO "
|
|
Author: Raritan Americas, Inc.
|
|
postal: Raritan Americas, Inc.
|
|
400 Cottontail Lane
|
|
Somerset, NJ 08873
|
|
email: tech@raritan.com
|
|
phone: +1 732 764 8886
|
|
"
|
|
DESCRIPTION "This mib describes the SNMP functions of the Dominion PX
|
|
Power Distribution Unit by Raritan Computer."
|
|
|
|
|
|
REVISION "201602220000Z" -- February 22,2016
|
|
DESCRIPTION "1) Added inletCurrentUnbalanceHysteresis to inletTable.
|
|
|
|
"
|
|
|
|
|
|
REVISION "201602030000Z" -- February 3,2016
|
|
DESCRIPTION "1) Added varbind sensorDescr to the following traps
|
|
managingenvironmentalSensor,
|
|
unmanagingenvironmentalSensor.
|
|
|
|
"
|
|
|
|
|
|
REVISION "201511020000Z" -- November 2,2015
|
|
DESCRIPTION "1) Added ipmiOverLAN to the info table.
|
|
|
|
"
|
|
|
|
|
|
REVISION "201510260000Z" -- October 26,2015
|
|
DESCRIPTION "1) Added Comment above primaryNTPServerAddressType
|
|
|
|
"
|
|
|
|
|
|
REVISION "201510160000Z" -- October 16,2015
|
|
DESCRIPTION "1) Modified DESCRIPTION clauses of the following traps.
|
|
ipmiOverLANEnabled,
|
|
ipmiOverLANDisabled
|
|
|
|
2) Added the following traps to the NOTIFICATION-GROUP trapsGroup
|
|
ipmiOverLANEnabled,
|
|
ipmiOverLANDisabled
|
|
|
|
"
|
|
|
|
REVISION "201510020000Z" -- October 2,2015
|
|
DESCRIPTION "1) Modified DESCRIPTION clause of thresholdAlarm trap
|
|
|
|
|
|
"
|
|
|
|
|
|
|
|
REVISION "201506190000Z" -- June 19,2015
|
|
DESCRIPTION "1) Modified DESCRIPTION clauses of
|
|
dataLogAvgExternalSensorValue,
|
|
dataLogMaxExternalSensorValue,
|
|
dataLogAvgExternalSensorValue
|
|
|
|
2) Modified DESCRIPTION CLAUSE of reorderexternalSensorTableEntries
|
|
|
|
"
|
|
|
|
|
|
REVISION "201503110000Z" -- March 11,2015
|
|
DESCRIPTION "1) Added the following under info.
|
|
thresholdValue,
|
|
sensorValue
|
|
|
|
2) Added thresholdValue and sensorValue to the following traps
|
|
thresholdAlarm
|
|
|
|
"
|
|
|
|
|
|
REVISION "201404030000Z" -- April 3,2014
|
|
DESCRIPTION "1) Modified the DESCRIPTION of the following.
|
|
inletActiveEnergy
|
|
inletPoleMaxCurrent
|
|
inletPoleActivePower
|
|
inletPoleApparentPower
|
|
inletPolePowerFactor
|
|
inletPoleActiveEnergy
|
|
neutralCurrentUpperWarning
|
|
neutralCurrentUppeCritical
|
|
dataLogAvgInletPoleActivePower
|
|
dataLogMaxInletPoleActivePower
|
|
dataLogMinInletPoleActivePower
|
|
dataLogAvgInletPoleApparentPower
|
|
dataLogMaxInletPoleApparentPower
|
|
dataLogMinInletPoleApparentPower
|
|
dataLogAvgInletPoleActiveEnergy
|
|
dataLogMaxInletPoleActiveEnergy
|
|
dataLogMinInletPoleActiveEnergy
|
|
currentUnbalance
|
|
2) Added the following traps
|
|
managingenvironmentalSensor,
|
|
unmanagingenvironmentalSensor
|
|
"
|
|
|
|
|
|
REVISION "201203220000Z" -- March 22,2012
|
|
DESCRIPTION "1) Added dataLogExternalSensorChanged to dataLogExternalSensorTable.
|
|
|
|
"
|
|
|
|
REVISION "201203150000Z" -- March 15,2012
|
|
DESCRIPTION "1) Added support for NTP servers.
|
|
Added the following objects under info
|
|
synchronizeWithNTPServer, useDHCPProvidedNTPServer,
|
|
primaryNTPServerAddressType, primaryNTPServerAddress,
|
|
secondaryNTPServerAddressType, secondaryNTPServerAddress,
|
|
daylightSavingsTime
|
|
"
|
|
|
|
|
|
REVISION "201203140000Z" -- March 14,2012
|
|
DESCRIPTION "1) Added support for external sensors in the data log
|
|
Added dataLogExternalSensorTable
|
|
"
|
|
|
|
REVISION "201111300000Z" -- Novemebr 30, 2011
|
|
DESCRIPTION "1) Modified DESCRIPTION of configureAlerts to note that Policy Name is case-sensitive
|
|
"
|
|
|
|
|
|
REVISION "201111070000Z" -- November 7, 2011
|
|
DESCRIPTION "1) Added configureAlerts under info
|
|
Added SensorClassEnumeration, EventTypeEnumeration, EventDirectionEnumeration
|
|
"
|
|
|
|
REVISION "201110060000Z" -- October 6, 2011
|
|
DESCRIPTION "1) Added fipsMode under info
|
|
2) Added EnabledDisabledEnumeration
|
|
3) Added fipsModeEnabled and fipsModeDisabled traps
|
|
"
|
|
|
|
REVISION "201105170000Z" -- May 17, 2011
|
|
DESCRIPTION "1) Added altitude under info
|
|
"
|
|
|
|
REVISION "201105110000Z" -- May 11, 2011
|
|
DESCRIPTION "1) Modified the DESCRIPTION clause of dataLoggingInterval and measurementsPerLogEntry
|
|
2) Added reorderExternaSensorTableEntries to specify the order of the entries in externalSensorTable
|
|
3) Added voltageMeasurementFailure trap
|
|
"
|
|
|
|
REVISION "201104180000Z" -- April 18, 2011
|
|
DESCRIPTION "1) Added dataLogAvgActivePower,dataLogMaxActivePower,dataLogMinActivePower,
|
|
dataLogAvgApparentPower,dataLogMaxApparentPower, dataLogMinApparentPower
|
|
to DataLogEntryStruct
|
|
|
|
2) Added dataLogAvgOutletCurrent,dataLogMaxOutletCurrent,dataLogMinOutletCurrent,
|
|
dataLogAvgOutletVoltage,dataLogMaxOutletVoltage,dataLogMinOutletVoltage,
|
|
dataLogAvgOutletPowerFactor,dataLogMaxOutletPowerFactor,dataLogMinOutletPowerFactor,
|
|
dataLogAvgOutletWattHours,dataLogMaxOutletWattHours,dataLogMinOutletWattHours
|
|
to DataLogOutletEntryStruct
|
|
|
|
3) Added dataLogAvgCircuitBreakerCurrent,dataLogMaxCircuitBreakerCurrent,dataLogMinCircuitBreakerCurrent
|
|
to DataLogCircuitBreakerEntryStruct
|
|
|
|
4) Added dataLogAvgInletCurrentUnbalance,dataLogMaxInletCurrentUnbalance,dataLogMinInletCurrentUnbalance,
|
|
dataLogAvgInletActivePower,dataLogMaxInletActivePower,dataLogMinInletActivePower,
|
|
dataLogAvgInletApparentPower,dataLogMaxInletApparentPower,dataLogMinInletApparentPower,
|
|
dataLogAvgInletActiveEnergy,dataLogMaxInletActiveEnergy,dataLogMinInletActiveEnergy,
|
|
to DataLogInletEntryStruct
|
|
|
|
5) Added dataLogAvgInletPoleCurrent,dataLogMaxInletPoleCurrent,dataLogMinInletPoleCurrent,
|
|
dataLogAvgInletPoleVoltage,dataLogMaxInletPoleVoltage,dataLogMinInletPoleVoltage,
|
|
dataLogAvgInletPoleActivePower,dataLogMaxInletPoleActivePower,dataLogMinInletPoleActivePower,
|
|
dataLogAvgInletPoleApparentPower,dataLogMaxInletPoleApparentPower,dataLogMinInletPoleApparentPower,
|
|
dataLogAvgInletPoleActiveEnergy,dataLogMaxInletPoleActiveEnergy,dataLogMinInletPoleActiveEnergy
|
|
to DataLogInletPoleEntryStruct
|
|
|
|
6) Added measurementsPerLogEntry under info.
|
|
|
|
7) Deprecated dataLogActivePower,dataLogApparentPower,dataLogOutletCurrent,
|
|
dataLogOutletVoltage,dataLogOutletPowerFactor, dataLogOutletOnTime,
|
|
dataLogCircuitBreakerCurrent,dataLogOutletWattHours,dataLogInletPoleCurrent,
|
|
dataLogInletPoleVoltage,dataLogInletCurrentUnbalance,dataLogInletActivePower,
|
|
dataLogInletApparentPower,dataLogInletActiveEnergy
|
|
|
|
8) Deprecated dataLoggingInterval
|
|
|
|
"
|
|
|
|
REVISION "201102140000Z" -- February 14, 2011
|
|
DESCRIPTION "1) Added PowerCIMStatusEnumeration and powerCIMStatus
|
|
"
|
|
|
|
REVISION "201101240000Z" -- January 24, 2011
|
|
DESCRIPTION "1) Added lastUpgradeStatus,lastUpgradeTimestamp, lastUpgradeErrorDescription
|
|
"
|
|
|
|
REVISION "201011300000Z" -- November 30, 2010
|
|
DESCRIPTION "1) Added externalSensorNumber,externalSensorType, externalSensorName, externalSensorChannelNumber, externalBinarySensorSubtype,
|
|
externalSensorSerialNumber to environmentalSensorsConnectivityRestored trap
|
|
2) Added externalSensorNumber,externalSensorType, externalSensorName, externalSensorChannelNumber, externalBinarySensorSubtype,
|
|
externalSensorSerialNumber to environmentalSensorsConnectivityLost trap
|
|
3) Added externalSensorSerialNumber to externalOnOffSensorStateChange
|
|
4) Added sensorIdentificationString to thresholdAlarm trap
|
|
5) Added none to TypeOfSensorEnumeration
|
|
"
|
|
|
|
|
|
REVISION "201011040000Z" -- November 4, 2010
|
|
DESCRIPTION "1) Added environmentalSensorsConnectivityRestored trap
|
|
2) Changed MAX-ACCESS of inlineMeter to read-only
|
|
"
|
|
|
|
REVISION "201007210000Z" -- July 21, 2010
|
|
DESCRIPTION "1) Renamed externalBinarySensorStateChange trap to externalOnOffSensorStateChange
|
|
"
|
|
|
|
REVISION "201007190000Z" -- July 19, 2010
|
|
DESCRIPTION "1) Added externalBinarySensorStateChange trap
|
|
2) Added contact to TypeOfSensorEnumeration"
|
|
|
|
REVISION "201007150000Z" -- July 15, 2010
|
|
DESCRIPTION "1) Added binary to TypeOfSensorEnumeration
|
|
2) Added externalBinarySensorSubtype to ExternalSensorEntryStruct"
|
|
|
|
REVISION "201007130000Z" -- July 13, 2010
|
|
DESCRIPTION "Added outletCurrentHysteresis
|
|
circuitBreakerCurrentHysteresis
|
|
unitOrLineVoltageHysteresis,
|
|
unitOrLineCurrentHysteresis,
|
|
unitTempHysteresis,
|
|
currentUnbalanceHysteresis
|
|
inletCurrentHysteresis,
|
|
inletVoltageHysteresis,
|
|
externalSensorHysteresis"
|
|
|
|
REVISION "201006290000Z" -- June 29, 2010
|
|
DESCRIPTION "Added externalSensorChannelNumber to externalSensorTable"
|
|
|
|
REVISION "201006070000Z" -- June 7, 2010
|
|
DESCRIPTION "Added Alarmed to StateOfSensorEnumeration"
|
|
|
|
REVISION "201005270000Z" -- May 27, 2010
|
|
DESCRIPTION "Moved the externalSensorTable from under board to under pdu"
|
|
|
|
REVISION "201005200000Z" -- May 20, 2010
|
|
DESCRIPTION "In the externalSensorTable, changed SYNTAX of externalSensorLowerCriticalThreshold, externalSensorLowerWarningThreshold,externalSensorUpperCriticalThreshold,
|
|
externalSensorUpperWarningThreshold to Integer32"
|
|
|
|
REVISION "201005170000Z" -- May 17, 2010
|
|
DESCRIPTION "Added externalSensorTable for representing all types of external sensors
|
|
Deprecated tempSensorTable and humiditySensorTable"
|
|
|
|
REVISION "200906090000Z" -- June 9, 2009
|
|
DESCRIPTION "Added support for multiple inlets/inline meters"
|
|
|
|
|
|
REVISION "200904200000Z" -- April 20, 2009
|
|
DESCRIPTION "For PX 1.3.5;Deprecated SensorStateEnumeration & SensorTypeEnumeration"
|
|
|
|
REVISION "200902130000Z" -- February 13, 2009
|
|
DESCRIPTION "For PX 1.3.5;Added support for environmental sensor coordinates:
|
|
added tempXCoordinate,tempYCoordinate,tempZCoordinate to tempSensorTable
|
|
added humidityXCoordinate,humidityYCoordinate,humidityZCoordinate to humiditySensorTable
|
|
added externalSensorsZCoordinateUnits under info "
|
|
|
|
REVISION "200902120000Z" -- February 12, 2009
|
|
DESCRIPTION "For PX 1.3.5;Added support for current unbalance: enabling/disabling, unbalance value and thresholds
|
|
currentUnbalanceSupport,currentUnbalance,currentUnbalanceUpperWarning,currentUnbalanceUpper"
|
|
|
|
|
|
REVISION "200812010000Z" -- December 1, 2008
|
|
DESCRIPTION "For PX 1.3;Added outletEnergySupport to indicate whether outlet energy is supported"
|
|
|
|
REVISION "200810240000Z" -- October 24, 2008
|
|
DESCRIPTION "For PX 1.3;Added Watt-Hours for outlets, lower current warning & lower critical thresholds for outlets"
|
|
|
|
|
|
REVISION "200809250000Z" -- September 25, 2008
|
|
DESCRIPTION "Added trap for environmental sensors disconnected"
|
|
|
|
REVISION "200809050000Z" -- September 5, 2008
|
|
DESCRIPTION "Add support for data Log ( line, circuit breaker,outlet ) Retrieval"
|
|
|
|
|
|
|
|
REVISION "200806050000Z" -- June 5, 2008
|
|
DESCRIPTION "PX 1.2 MIB supports 3-phase PDUs."
|
|
|
|
|
|
REVISION "200711280000Z" -- November 28, 2007
|
|
DESCRIPTION "Modfied MIB in effort to better support HP OpenView
|
|
and other SNMP managers."
|
|
|
|
REVISION "200706200000Z" -- June 20, 2007
|
|
DESCRIPTION "Updated version for remote access to pdu."
|
|
::= { enterprises 13742 }
|
|
|
|
pdu OBJECT IDENTIFIER ::= { raritan 4 }
|
|
|
|
traps OBJECT IDENTIFIER ::= { pdu 0 }
|
|
board OBJECT IDENTIFIER ::= { pdu 1 }
|
|
environmental OBJECT IDENTIFIER ::= { pdu 2 }
|
|
externalSensors OBJECT IDENTIFIER ::= { pdu 3 }
|
|
conformance OBJECT IDENTIFIER ::= { pdu 9 }
|
|
|
|
info OBJECT IDENTIFIER ::= { board 1 }
|
|
outlets OBJECT IDENTIFIER ::= { board 2 }
|
|
unit OBJECT IDENTIFIER ::= { board 3 }
|
|
lineCurrents OBJECT IDENTIFIER ::= { board 4 }
|
|
circuitBreaker OBJECT IDENTIFIER ::= { board 5 }
|
|
lineVoltages OBJECT IDENTIFIER ::= { board 6 }
|
|
dataLog OBJECT IDENTIFIER ::= { board 7 }
|
|
inlets OBJECT IDENTIFIER ::= { board 20 }
|
|
inletPole OBJECT IDENTIFIER ::= { board 21 }
|
|
dataLogOutlet OBJECT IDENTIFIER ::= { board 10 }
|
|
dataLogCircuitBreaker OBJECT IDENTIFIER ::= { board 15 }
|
|
dataLogInputLine OBJECT IDENTIFIER ::= { board 14 }
|
|
dataLogInlet OBJECT IDENTIFIER ::= { board 12 }
|
|
dataLogInletPole OBJECT IDENTIFIER ::= { board 13 }
|
|
dataLogExternalSensor OBJECT IDENTIFIER ::= { board 16 }
|
|
|
|
|
|
unitReadings OBJECT IDENTIFIER ::= { unit 1 }
|
|
|
|
compliances OBJECT IDENTIFIER ::= { conformance 1 }
|
|
groups OBJECT IDENTIFIER ::= { conformance 2 }
|
|
|
|
-- Conformance Information
|
|
-- compliance statements
|
|
|
|
compliance MODULE-COMPLIANCE
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The requirements for conformance to the PDU-MIB. This is deprecated and the new compliance
|
|
ComplianceRev1 has been added"
|
|
MODULE -- this module
|
|
|
|
GROUP infoGroup
|
|
DESCRIPTION
|
|
"The info group."
|
|
|
|
GROUP outletsGroup
|
|
DESCRIPTION
|
|
"The outlets group."
|
|
|
|
GROUP unitSensorsGroup
|
|
DESCRIPTION
|
|
"The unit sensor readings association group."
|
|
|
|
GROUP externalTemperatureGroup
|
|
DESCRIPTION
|
|
"The external temperature sensor association group."
|
|
|
|
GROUP externalHumidityGroup
|
|
DESCRIPTION
|
|
"The external humidity sensor association group."
|
|
|
|
GROUP trapsGroup
|
|
DESCRIPTION
|
|
"The traps group."
|
|
::= { compliances 1 }
|
|
|
|
complianceRev1 MODULE-COMPLIANCE
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The requirements for conformance to the PDU-MIB. This is deprecated and the new compliance
|
|
ComplianceRev2 has been added"
|
|
MODULE -- this module
|
|
|
|
GROUP infoGroup
|
|
DESCRIPTION
|
|
"The info group."
|
|
|
|
GROUP outletsGroup
|
|
DESCRIPTION
|
|
"The outlets group."
|
|
|
|
GROUP unitSensorsGroupRev
|
|
DESCRIPTION
|
|
"The unit sensor readings association group."
|
|
|
|
GROUP externalTemperatureGroup
|
|
DESCRIPTION
|
|
"The external temperature sensor association group."
|
|
|
|
GROUP externalHumidityGroup
|
|
DESCRIPTION
|
|
"The external humidity sensor association group."
|
|
|
|
GROUP trapsGroup
|
|
DESCRIPTION
|
|
"The traps group."
|
|
|
|
GROUP lineCurrentGroup
|
|
DESCRIPTION
|
|
"The line current group."
|
|
|
|
GROUP circuitBreakerGroup
|
|
DESCRIPTION
|
|
"The Circuit Breaker group."
|
|
|
|
GROUP lineVoltageGroup
|
|
DESCRIPTION
|
|
"The line Voltage group."
|
|
|
|
GROUP dataLogGroup
|
|
DESCRIPTION
|
|
"The pdu Data group."
|
|
::= { compliances 2 }
|
|
|
|
complianceRev2 MODULE-COMPLIANCE
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The requirements for conformance to the PDU-MIB. This is deprecated and the new compliance
|
|
ComplianceRev3 has been added"
|
|
MODULE -- this module
|
|
|
|
GROUP infoGroup
|
|
DESCRIPTION
|
|
"The info group."
|
|
|
|
|
|
GROUP outletsGroup
|
|
DESCRIPTION
|
|
"The outlets group."
|
|
|
|
GROUP unitSensorsGroupRev
|
|
DESCRIPTION
|
|
"The unit sensor readings association group."
|
|
|
|
GROUP externalTemperatureGroup
|
|
DESCRIPTION
|
|
"The external temperature sensor association group."
|
|
|
|
GROUP externalHumidityGroup
|
|
DESCRIPTION
|
|
"The external humidity sensor association group."
|
|
|
|
GROUP trapsGroup
|
|
DESCRIPTION
|
|
"The traps group."
|
|
|
|
GROUP circuitBreakerGroup
|
|
DESCRIPTION
|
|
"The Circuit Breaker group."
|
|
|
|
GROUP dataLogGroup
|
|
DESCRIPTION
|
|
"The pdu Data group."
|
|
::= { compliances 3 }
|
|
|
|
|
|
complianceRev3 MODULE-COMPLIANCE
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The requirements for conformance to the PDU-MIB.This is deprecated and the new compliance
|
|
ComplianceRev4 has been added"
|
|
MODULE -- this module
|
|
|
|
GROUP infoGroup
|
|
DESCRIPTION
|
|
"The info group."
|
|
|
|
GROUP inletsGroup
|
|
DESCRIPTION
|
|
"The inlets group."
|
|
|
|
GROUP outletsGroup
|
|
DESCRIPTION
|
|
"The outlets group."
|
|
|
|
GROUP unitSensorsGroupRev2
|
|
DESCRIPTION
|
|
"The unit sensor readings association group."
|
|
|
|
GROUP externalTemperatureGroup
|
|
DESCRIPTION
|
|
"The external temperature sensor association group."
|
|
|
|
GROUP externalHumidityGroup
|
|
DESCRIPTION
|
|
"The external humidity sensor association group."
|
|
|
|
GROUP trapsGroup
|
|
DESCRIPTION
|
|
"The traps group."
|
|
|
|
GROUP inletPoleGroup
|
|
DESCRIPTION
|
|
"The line current group."
|
|
|
|
GROUP circuitBreakerGroup
|
|
DESCRIPTION
|
|
"The Circuit Breaker group."
|
|
|
|
GROUP dataLogGroupRev
|
|
DESCRIPTION
|
|
"The pdu Data group."
|
|
::= { compliances 4 }
|
|
|
|
complianceRev4 MODULE-COMPLIANCE
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The requirements for conformance to the PDU-MIB. This is deprecated and the new compliance
|
|
ComplianceRev5 has been added"
|
|
MODULE -- this module
|
|
|
|
GROUP infoGroup
|
|
DESCRIPTION
|
|
"The info group."
|
|
|
|
GROUP inletsGroup
|
|
DESCRIPTION
|
|
"The inlets group."
|
|
|
|
GROUP outletsGroup
|
|
DESCRIPTION
|
|
"The outlets group."
|
|
|
|
GROUP unitSensorsGroupRev2
|
|
DESCRIPTION
|
|
"The unit sensor readings association group."
|
|
|
|
GROUP externalSensorsGroup
|
|
DESCRIPTION
|
|
"The external sesnors sensor association group."
|
|
|
|
GROUP trapsGroup
|
|
DESCRIPTION
|
|
"The traps group."
|
|
|
|
GROUP inletPoleGroup
|
|
DESCRIPTION
|
|
"The line current group."
|
|
|
|
GROUP circuitBreakerGroup
|
|
DESCRIPTION
|
|
"The Circuit Breaker group."
|
|
|
|
GROUP dataLogGroupRev
|
|
DESCRIPTION
|
|
"The pdu Data group."
|
|
::= { compliances 5 }
|
|
|
|
|
|
complianceRev5 MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The requirements for conformance to the PDU-MIB."
|
|
MODULE -- this module
|
|
|
|
GROUP infoGroupRev2
|
|
DESCRIPTION
|
|
"The info group."
|
|
|
|
GROUP inletsGroup
|
|
DESCRIPTION
|
|
"The inlets group."
|
|
|
|
GROUP outletsGroup
|
|
DESCRIPTION
|
|
"The outlets group."
|
|
|
|
GROUP unitSensorsGroupRev2
|
|
DESCRIPTION
|
|
"The unit sensor readings association group."
|
|
|
|
GROUP externalSensorsGroup
|
|
DESCRIPTION
|
|
"The external sesnors sensor association group."
|
|
|
|
GROUP trapsGroup
|
|
DESCRIPTION
|
|
"The traps group."
|
|
|
|
GROUP inletPoleGroup
|
|
DESCRIPTION
|
|
"The line current group."
|
|
|
|
GROUP circuitBreakerGroup
|
|
DESCRIPTION
|
|
"The Circuit Breaker group."
|
|
|
|
GROUP dataLogGroupRev2
|
|
DESCRIPTION
|
|
"The pdu Data group."
|
|
::= { compliances 6 }
|
|
|
|
-- units of conformance
|
|
|
|
infoGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
dataLoggingInterval
|
|
}
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A collection of objects providing basic information
|
|
about the pdu."
|
|
::= { groups 1 }
|
|
|
|
infoGroupRev2 OBJECT-GROUP
|
|
OBJECTS { firmwareVersion,
|
|
serialNumber,
|
|
ipAddress,
|
|
netmask,
|
|
gateway,
|
|
mac,
|
|
hardwareRev,
|
|
userName,
|
|
objectName,
|
|
objectInstance,
|
|
targetUser,
|
|
groupName,
|
|
imageVersion,
|
|
sensorDescr,
|
|
thresholdDescr,
|
|
thresholdSeverity,
|
|
thresholdEventType,
|
|
status,
|
|
slaveIpAddress,
|
|
inputCurrentRating,
|
|
ratedVoltage,
|
|
ratedPower,
|
|
outletSwitching,
|
|
dataLogging,
|
|
dataCollectionInterval,
|
|
outletEnergySupport,
|
|
currentUnbalanceSupport,
|
|
externalSensorsZCoordinateUnits,
|
|
inlineMeter,
|
|
oldSensorState,
|
|
externalSensorNumber,
|
|
sensorIdentificationString,
|
|
lastUpgradeStatus,
|
|
lastUpgradeTimestamp,
|
|
lastUpgradeErrorDescription,
|
|
powerCIMStatus,
|
|
measurementsPerLogEntry,
|
|
psocNumber,
|
|
altitude,
|
|
configureAlerts,
|
|
fipsMode,
|
|
synchronizeWithNTPServer,
|
|
useDHCPProvidedNTPServer,
|
|
primaryNTPServerAddressType,
|
|
primaryNTPServerAddress,
|
|
secondaryNTPServerAddressType,
|
|
secondaryNTPServerAddress,
|
|
daylightSavingsTime,
|
|
thresholdValue,
|
|
sensorValue,
|
|
ipmiOverLAN
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of objects providing basic information
|
|
about the pdu."
|
|
::= { groups 22 }
|
|
|
|
|
|
outletsGroup OBJECT-GROUP
|
|
OBJECTS { outletCount,
|
|
outletLabel,
|
|
outletCurrentRating,
|
|
outletOperationalState,
|
|
outletCurrent,
|
|
outletMaxCurrent,
|
|
outletVoltage,
|
|
outletActivePower,
|
|
outletApparentPower,
|
|
outletPowerFactor,
|
|
outletCurrentUpperWarning,
|
|
outletCurrentUpperCritical,
|
|
outletCurrentLowerWarning,
|
|
outletCurrentLowerCritical,
|
|
outletCurrentHysteresis,
|
|
outletWattHours
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of objects providing basic information
|
|
about the outlets, including sensor readings."
|
|
::= { groups 2 }
|
|
|
|
unitSensorsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
unitCurrent,
|
|
unitVoltage,
|
|
unitActivePower,
|
|
unitApparentPower,
|
|
unitCpuTemp,
|
|
unitVoltageLowerWarning,
|
|
unitVoltageUpperWarning,
|
|
unitVoltageLowerCritical,
|
|
unitVoltageUpperCritical,
|
|
unitCurrentUpperWarning,
|
|
unitCurrentUpperCritical,
|
|
unitTempLowerWarning,
|
|
unitTempUpperWarning,
|
|
unitTempLowerCritical,
|
|
unitTempUpperCritical }
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A collection of objects providing unit level sensor readings.This group is deprecated in favor
|
|
of unitSensorsGroupRev"
|
|
::= { groups 4 }
|
|
|
|
|
|
|
|
externalTemperatureGroup OBJECT-GROUP
|
|
OBJECTS { tempSensorCount,
|
|
tempSensorLabel,
|
|
temperature,
|
|
tempLowerWarning,
|
|
tempUpperWarning,
|
|
tempLowerCritical,
|
|
tempUpperCritical,
|
|
tempXCoordinate,
|
|
tempYCoordinate,
|
|
tempZCoordinate
|
|
}
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A collection of objects providing external temperature sensor readings and
|
|
threshold settings. This group is deprecated in favor of the externalSensorsGroup"
|
|
::= { groups 6 }
|
|
|
|
externalHumidityGroup OBJECT-GROUP
|
|
OBJECTS { humiditySensorCount,
|
|
humiditySensorLabel,
|
|
humidity,
|
|
humidityLowerWarning,
|
|
humidityUpperWarning,
|
|
humidityLowerCritical,
|
|
humidityUpperCritical,
|
|
humidityXCoordinate,
|
|
humidityYCoordinate,
|
|
humidityZCoordinate }
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A collection of objects providing external humidity sensor readings and threshold settings.
|
|
This group is deprecated in favor of the externalSensorsGroup"
|
|
::= { groups 7 }
|
|
|
|
trapsGroup NOTIFICATION-GROUP
|
|
NOTIFICATIONS { rebootStarted,
|
|
rebootCompleted,
|
|
userLogin,
|
|
userLogout,
|
|
userAuthenticationFailure,
|
|
userSessionTimeout,
|
|
userAdded,
|
|
userModified,
|
|
userDeleted,
|
|
groupAdded,
|
|
groupModified,
|
|
groupDeleted,
|
|
deviceUpdateStarted,
|
|
userBlocked,
|
|
powerControl,
|
|
userPasswordChanged,
|
|
passwordSettingsChanged,
|
|
firmwareFileDiscarded,
|
|
firmwareValidationFailed,
|
|
securityViolation,
|
|
logFileCleared,
|
|
thresholdAlarm,
|
|
outletGroupingConnectivityLost,
|
|
circuitBreakerTripped,
|
|
circuitBreakerRecovered,
|
|
bulkConfigurationSaved,
|
|
bulkConfigurationCopied,
|
|
environmentalSensorsConnectivityLost,
|
|
externalOnOffSensorStateChange,
|
|
environmentalSensorsConnectivityRestored,
|
|
voltageMeasurementError,
|
|
fipsModeEnabled,
|
|
fipsModeDisabled,
|
|
managingenvironmentalSensor,
|
|
unmanagingenvironmentalSensor,
|
|
ipmiOverLANEnabled,
|
|
ipmiOverLANDisabled
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of traps."
|
|
::= { groups 9 }
|
|
|
|
lineCurrentGroup OBJECT-GROUP
|
|
OBJECTS { lineCurrentCount,
|
|
lineCurrentLabel,
|
|
lineCurrent}
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A collection of objects describing the line inputs.
|
|
This group is deprecated in favor of inletPoleGroup"
|
|
::= { groups 10 }
|
|
|
|
|
|
circuitBreakerGroup OBJECT-GROUP
|
|
OBJECTS { circuitBreakerCount,
|
|
circuitBreakerLabel,
|
|
circuitBreakerCurrentRating,
|
|
circuitBreakerState,
|
|
circuitBreakerCurrent,
|
|
circuitBreakerCurrentUpperWarning,
|
|
circuitBreakerCurrentUpperCritical,
|
|
circuitBreakerCurrentHysteresis }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of objects describing the circuit breakers."
|
|
::= { groups 11 }
|
|
|
|
lineVoltageGroup OBJECT-GROUP
|
|
OBJECTS { lineVoltageCount,
|
|
lineVoltageLabel,
|
|
lineVoltage}
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A collection of objects describing the line voltages.
|
|
This group is deprecated in favor of inletPoleGroup"
|
|
::= { groups 12 }
|
|
|
|
unitSensorsGroupRev OBJECT-GROUP
|
|
OBJECTS {
|
|
unitActivePower,
|
|
unitApparentPower,
|
|
unitCpuTemp,
|
|
unitOrLineVoltageLowerWarning,
|
|
unitOrLineVoltageUpperWarning,
|
|
unitOrLineVoltageLowerCritical,
|
|
unitOrLineVoltageUpperCritical,
|
|
unitOrLineCurrentUpperWarning,
|
|
unitOrLineCurrentUpperCritical,
|
|
neutralCurrentUpperWarning,
|
|
neutralCurrentUpperCritical,
|
|
unitTempLowerWarning,
|
|
unitTempUpperWarning,
|
|
unitTempLowerCritical,
|
|
unitTempUpperCritical,
|
|
currentUnbalance,
|
|
currentUnbalanceUpperWarning,
|
|
currentUnbalanceUpperCritical}
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A collection of objects providing unit level sensor readings.This group is deprecated
|
|
in favor of unitSensorsGroupRev2"
|
|
::= { groups 13 }
|
|
|
|
unitSensorsGroupRev2 OBJECT-GROUP
|
|
OBJECTS {
|
|
unitCpuTemp,
|
|
unitOrLineVoltageLowerWarning,
|
|
unitOrLineVoltageUpperWarning,
|
|
unitOrLineVoltageLowerCritical,
|
|
unitOrLineVoltageUpperCritical,
|
|
unitOrLineCurrentUpperWarning,
|
|
unitOrLineCurrentUpperCritical,
|
|
neutralCurrentUpperWarning,
|
|
neutralCurrentUpperCritical,
|
|
unitTempLowerWarning,
|
|
unitTempUpperWarning,
|
|
unitTempLowerCritical,
|
|
unitTempUpperCritical,
|
|
currentUnbalance,
|
|
currentUnbalanceUpperWarning,
|
|
currentUnbalanceUpperCritical,
|
|
unitOrLineVoltageHysteresis,
|
|
unitOrLineCurrentHysteresis,
|
|
unitTempHysteresis,
|
|
currentUnbalanceHysteresis}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of objects providing unit level sensor readings."
|
|
::= { groups 18 }
|
|
|
|
dataLogGroup OBJECT-GROUP
|
|
OBJECTS { dataLogCount,
|
|
dataLogLatestIndex,
|
|
dataLogTimeStamp,
|
|
dataLogActivePower,
|
|
dataLogApparentPower,
|
|
dataLogOutletCurrent,
|
|
dataLogOutletVoltage,
|
|
dataLogOutletPowerFactor,
|
|
dataLogOutletOnTime,
|
|
dataLogCircuitBreakerCurrent,
|
|
dataLogInputLineCurrent,
|
|
dataLogInputLineVoltage,
|
|
dataLogOutletWattHours
|
|
|
|
}
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A collection of objects describing the pdu data.
|
|
This group is being deprecated in favor of dataLogGroupRev "
|
|
::= { groups 14 }
|
|
|
|
dataLogGroupRev OBJECT-GROUP
|
|
OBJECTS { dataLogCount,
|
|
dataLogLatestIndex,
|
|
dataLogTimeStamp,
|
|
dataLogActivePower,
|
|
dataLogApparentPower,
|
|
dataLogOutletCurrent,
|
|
dataLogOutletVoltage,
|
|
dataLogOutletPowerFactor,
|
|
dataLogOutletOnTime,
|
|
dataLogCircuitBreakerCurrent,
|
|
dataLogOutletWattHours,
|
|
dataLogInletPoleCurrent,
|
|
dataLogInletPoleVoltage,
|
|
dataLogInletCurrentUnbalance,
|
|
dataLogInletActivePower,
|
|
dataLogInletApparentPower,
|
|
dataLogInletActiveEnergy
|
|
}
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A collection of objects describing the pdu data.
|
|
This group is being deprecated in favor of dataLogGroupRev2"
|
|
::= { groups 17 }
|
|
|
|
dataLogGroupRev2 OBJECT-GROUP
|
|
OBJECTS { dataLogCount,
|
|
dataLogLatestIndex,
|
|
dataLogTimeStamp,
|
|
dataLogAvgActivePower,
|
|
dataLogMaxActivePower,
|
|
dataLogMinActivePower,
|
|
dataLogAvgApparentPower,
|
|
dataLogMaxApparentPower,
|
|
dataLogMinApparentPower,
|
|
dataLogAvgOutletCurrent,
|
|
dataLogMaxOutletCurrent,
|
|
dataLogMinOutletCurrent,
|
|
dataLogAvgOutletVoltage,
|
|
dataLogMaxOutletVoltage,
|
|
dataLogMinOutletVoltage,
|
|
dataLogAvgOutletPowerFactor,
|
|
dataLogMaxOutletPowerFactor,
|
|
dataLogMinOutletPowerFactor,
|
|
dataLogAvgOutletWattHours,
|
|
dataLogMaxOutletWattHours,
|
|
dataLogMinOutletWattHours,
|
|
dataLogAvgCircuitBreakerCurrent,
|
|
dataLogMaxCircuitBreakerCurrent,
|
|
dataLogMinCircuitBreakerCurrent,
|
|
dataLogAvgInletCurrentUnbalance,
|
|
dataLogMaxInletCurrentUnbalance,
|
|
dataLogMinInletCurrentUnbalance,
|
|
dataLogAvgInletActivePower,
|
|
dataLogMaxInletActivePower,
|
|
dataLogMinInletActivePower,
|
|
dataLogAvgInletApparentPower,
|
|
dataLogMaxInletApparentPower,
|
|
dataLogMinInletApparentPower,
|
|
dataLogAvgInletActiveEnergy,
|
|
dataLogMaxInletActiveEnergy,
|
|
dataLogMinInletActiveEnergy,
|
|
dataLogAvgInletPoleCurrent,
|
|
dataLogMaxInletPoleCurrent,
|
|
dataLogMinInletPoleCurrent,
|
|
dataLogAvgInletPoleVoltage,
|
|
dataLogMaxInletPoleVoltage,
|
|
dataLogMinInletPoleVoltage,
|
|
dataLogAvgInletPoleActivePower,
|
|
dataLogMaxInletPoleActivePower,
|
|
dataLogMinInletPoleActivePower,
|
|
dataLogAvgInletPoleApparentPower,
|
|
dataLogMaxInletPoleApparentPower,
|
|
dataLogMinInletPoleApparentPower,
|
|
dataLogAvgInletPoleActiveEnergy,
|
|
dataLogMaxInletPoleActiveEnergy,
|
|
dataLogMinInletPoleActiveEnergy,
|
|
dataLogExternalSensorChanged,
|
|
dataLogExternalSensorState,
|
|
dataLogAvgExternalSensorValue,
|
|
dataLogMaxExternalSensorValue,
|
|
dataLogMinExternalSensorValue
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of objects describing the pdu data."
|
|
::= { groups 21 }
|
|
|
|
|
|
inletPoleGroup OBJECT-GROUP
|
|
OBJECTS { inletPoleCount,
|
|
inletPoleLabel,
|
|
inletPoleCurrent,
|
|
inletPoleVoltage,
|
|
inletPoleMaxCurrent,
|
|
inletPoleActivePower,
|
|
inletPoleApparentPower,
|
|
inletPolePowerFactor,
|
|
inletPoleActiveEnergy
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of objects describing the inlet poles."
|
|
::= { groups 15 }
|
|
|
|
inletsGroup OBJECT-GROUP
|
|
OBJECTS { inletCount,
|
|
inletCurrentRating,
|
|
inletCurrentUnbalanceUpperCritical,
|
|
inletCurrentUnbalanceUpperWarning,
|
|
inletCurrentUnbalance,
|
|
inletActivePower,
|
|
inletApparentPower,
|
|
inletPoleCount,
|
|
inletCurrent,
|
|
inletVoltage,
|
|
inletPowerFactor,
|
|
inletActiveEnergy,
|
|
inletCurrentUpperWarning,
|
|
inletCurrentUpperCritical,
|
|
inletCurrentLowerWarning,
|
|
inletCurrentLowerCritical,
|
|
inletVoltageUpperWarning,
|
|
inletVoltageUpperCritical,
|
|
inletVoltageLowerWarning,
|
|
inletVoltageLowerCritical,
|
|
inletCurrentHysteresis,
|
|
inletVoltageHysteresis,
|
|
inletCurrentUnbalanceHysteresis
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of objects providing basic information
|
|
about the inlets, including sensor readings."
|
|
::= { groups 16 }
|
|
|
|
externalSensorsGroup OBJECT-GROUP
|
|
OBJECTS { externalSensorCount,
|
|
externalSensorType,
|
|
externalSensorSerialNumber,
|
|
externalSensorName,
|
|
externalSensorChannelNumber,
|
|
externalSensorXCoordinate,
|
|
externalSensorYCoordinate,
|
|
externalSensorZCoordinate,
|
|
externalBinarySensorSubtype,
|
|
externalSensorUnits,
|
|
externalSensorDecimalDigits,
|
|
externalSensorLowerCriticalThreshold,
|
|
externalSensorLowerWarningThreshold,
|
|
externalSensorUpperCriticalThreshold,
|
|
externalSensorUpperWarningThreshold,
|
|
externalSensorState,
|
|
externalSensorValue,
|
|
externalSensorHysteresis,
|
|
reorderexternalSensorTableEntries
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A collection of objects providing external sensor readings
|
|
and configuration settings."
|
|
::= { groups 20 }
|
|
|
|
-- Textual Conventions
|
|
|
|
MilliAmps ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with current sensors. If the underlying hardware
|
|
sensor indicates 1 amp, then the SNMP agent will report
|
|
a value of 1000 milliamps. The value is scaled in this
|
|
manner as a way to deal with floating point types
|
|
that SNMP does not currently support."
|
|
SYNTAX Unsigned32
|
|
|
|
MilliVolts ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with voltage sensors. If the underlying hardware
|
|
sensor indicates 1 volts, then the SNMP agent will report
|
|
a value of 1000 millivolts. The value is scaled in this
|
|
manner as a way to deal with floating point types
|
|
that SNMP does not currently support."
|
|
SYNTAX Unsigned32
|
|
|
|
Watts ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with active power sensors. If the underlying hardware
|
|
sensor indicates 1 watt, then the SNMP agent will report
|
|
a value of 1 watt. No scaling is performed for this type."
|
|
SYNTAX Unsigned32
|
|
|
|
VoltAmps ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with apparent power sensors. If the underlying hardware
|
|
sensor indicates 1 volt-amp, then the SNMP agent will report
|
|
a value of 1 volt-amp. No scaling is performed for this type."
|
|
SYNTAX Unsigned32
|
|
|
|
DegreesCelsius ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting thresholds
|
|
associated with temperature sensors. If the underlying hardware
|
|
sensor indicates 1 degree Celsius, then the SNMP agent will report
|
|
a value of 1 degree Celsius. No scaling is performed for this type."
|
|
SYNTAX Unsigned32
|
|
|
|
TenthDegreesCelsius ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings
|
|
associated with temperature sensors. If the underlying hardware
|
|
sensor indicates 1 degree Celsius, then the SNMP agent will report
|
|
a value of 10 tenth degrees Celsius. The value is scaled in this
|
|
manner as a way to deal with floating point types
|
|
that SNMP does not currently support."
|
|
SYNTAX Unsigned32
|
|
|
|
Hertz ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with frequency sensors. If the underlying hardware
|
|
sensor indicates 1 Hertz, then the SNMP agent will report
|
|
a value of 1 Hertz. No scaling is performed for this type."
|
|
SYNTAX Unsigned32
|
|
|
|
RelativeHumidity ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with humidity sensors. Relative humidity is
|
|
expressed as percentage and is defined as the ratio of the
|
|
partial pressure of water vapor in a gaseous mixture of
|
|
air and water vapor to the saturated vapor pressure of water
|
|
at a given temperature."
|
|
SYNTAX Unsigned32 (0..100)
|
|
|
|
PowerFactorPercentage ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting sensor readings and thresholds
|
|
associated with power factor sensors. The power factor of
|
|
an AC power system is defined as the ratio of the real
|
|
or active power to the apparent power and is a number
|
|
between 0 and 1. A PowerFactorPercentage value is calculated
|
|
by taking this ratio and multiplying by 100. The power factor
|
|
is used to indicate how efficiently a particular load is
|
|
utilizing energy."
|
|
SYNTAX Unsigned32 (0..100)
|
|
|
|
Percentage ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting values in percentage."
|
|
SYNTAX Unsigned32 (0..100)
|
|
|
|
SensorTypeEnumeration ::= TEXTUAL-CONVENTION
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The types a sensor can be. This enumeration is deprecated starting with PX 1.3.5"
|
|
SYNTAX INTEGER { outletCurrent(0),
|
|
outletMaxCurrent(1),
|
|
outletVoltage(2),
|
|
outletActivePower(3),
|
|
outletApparentPower(4),
|
|
outletMaxActivePower(5),
|
|
outletAverageActivePower(6),
|
|
outletPowerFactor(7),
|
|
powerBranchVoltage(200),
|
|
powerBranchFrequency(201),
|
|
powerBranchTemperature(202),
|
|
powerBranchCurrent(203),
|
|
environmentalTemp1(300),
|
|
environmentalTemp2(301),
|
|
environmentalTemp3(302),
|
|
environmentalTemp4(303),
|
|
environmentalTemp5(304),
|
|
environmentalTemp6(305),
|
|
environmentalTemp7(306),
|
|
environmentalTemp8(307),
|
|
environmentalHumidity1(400),
|
|
environmentalHumidity2(401),
|
|
environmentalHumidity3(402),
|
|
environmentalHumidity4(403),
|
|
environmentalHumidity5(404),
|
|
environmentalHumidity6(405),
|
|
environmentalHumidity7(406),
|
|
environmentalHumidity8(407),
|
|
unitRmsCurrent(500),
|
|
unitMaxRmsCurrent(501),
|
|
unitVoltage(502),
|
|
unitCpuTemp(503),
|
|
unitActivePower(504),
|
|
unitApparentPower(505),
|
|
unitFrequency(506),
|
|
unitCircuitBreak0State(550),
|
|
unitCircuitBreak1State(551),
|
|
unitCircuitBreak2State(552),
|
|
unitCircuitBreak0Current(600),
|
|
unitCircuitBreak1Current(601),
|
|
unitCircuitBreak2Current(602) }
|
|
|
|
SensorStateEnumeration ::= TEXTUAL-CONVENTION
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The states a sensor can be in.This enumeration is deprecated starting with PX 1.3.5"
|
|
SYNTAX INTEGER { unavailable(-1),
|
|
ok(0),
|
|
belowLowerWarning(1),
|
|
aboveUpperWarning(2),
|
|
belowLowerCritical(3),
|
|
aboveUpperCritical(4) }
|
|
|
|
StateOfSensorEnumeration ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The states a sensor can be in."
|
|
SYNTAX INTEGER { unavailable(-1),
|
|
open(0),
|
|
closed(1),
|
|
belowLowerCritical(2),
|
|
belowLowerWarning(3),
|
|
normal(4),
|
|
aboveUpperWarning(5),
|
|
aboveUpperCritical(6),
|
|
on(7),
|
|
off(8),
|
|
detected(9),
|
|
notDetected(10),
|
|
alarmed(11)
|
|
|
|
}
|
|
|
|
TypeOfSensorEnumeration ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The types a sensor can be."
|
|
SYNTAX INTEGER {
|
|
rmsCurrent(1),
|
|
peakCurrent(2),
|
|
unbalancedCurrent(3),
|
|
rmsVoltage(4),
|
|
activePower(5),
|
|
apparentPower(6),
|
|
powerFactor(7),
|
|
activeEnergy(8),
|
|
apparentEnergy(9),
|
|
temperature(10),
|
|
humidity(11),
|
|
airFlow(12),
|
|
airPressure(13),
|
|
onOff(14),
|
|
trip(15),
|
|
vibration(16),
|
|
waterDetection(17),
|
|
smokeDetection(18),
|
|
binary(19),
|
|
contact(20),
|
|
other(30),
|
|
none(31)
|
|
}
|
|
|
|
WattHours ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data type for reporting the active energy"
|
|
SYNTAX Unsigned32
|
|
|
|
SensorUnitsEnumeration ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The types a sensor can be."
|
|
SYNTAX INTEGER { none(-1),
|
|
other(0),
|
|
volt(1),
|
|
amp(2),
|
|
watt(3),
|
|
voltamp(4),
|
|
wattHour(5),
|
|
voltampHour(6),
|
|
degreeC(7),
|
|
hertz(8),
|
|
percent(9),
|
|
meterpersec(10),
|
|
pascal(11),
|
|
psi(12),
|
|
g(13),
|
|
degreeF(14),
|
|
feet(15),
|
|
inches(16),
|
|
cm(17),
|
|
meters(18)
|
|
}
|
|
|
|
|
|
PowerCIMStatusEnumeration ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of a PowerCIM"
|
|
SYNTAX INTEGER { off(0),
|
|
on(1)
|
|
}
|
|
|
|
EnabledDisabledEnumeration ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of a PowerCIM"
|
|
SYNTAX INTEGER { disabled(0),
|
|
enabled(1)
|
|
}
|
|
|
|
SensorClassEnumeration ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The class of sensor in the event"
|
|
SYNTAX INTEGER { externalTemperature(0),
|
|
externalHumidity(1),
|
|
externalAirFlow(2),
|
|
externalAirPressure(3)
|
|
}
|
|
|
|
EventTypeEnumeration ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The event type"
|
|
SYNTAX INTEGER { aboveUpperCritical(0),
|
|
aboveUpperNonCritical(1),
|
|
belowLowerNonCritical(2),
|
|
belowLowerCritical(3)
|
|
}
|
|
EventDirectionEnumeration ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The event direction"
|
|
SYNTAX INTEGER { asserted(0),
|
|
deasserted(1),
|
|
both(2)
|
|
}
|
|
|
|
-- the info group
|
|
|
|
firmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current firmware version in the following format:
|
|
major.minor.dot.buildnumber.
|
|
Example: 1.3.5.7416"
|
|
::= { info 1 }
|
|
|
|
serialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The serial number."
|
|
::= { info 2 }
|
|
|
|
ipAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current IP address. A value of 0.0.0.0 indicates an error
|
|
or an unset option."
|
|
::= { info 3 }
|
|
|
|
netmask OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current Netmask. A value of 0.0.0.0 indicates an error
|
|
or an unset option."
|
|
::= { info 4 }
|
|
|
|
gateway OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current Gateway. A value of 0.0.0.0 indicates an error
|
|
or an unset option."
|
|
::= { info 5 }
|
|
|
|
mac OBJECT-TYPE
|
|
SYNTAX MacAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current MAC address."
|
|
::= { info 6 }
|
|
|
|
hardwareRev OBJECT-TYPE
|
|
SYNTAX Integer32(0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hardware revision number."
|
|
::= { info 7 }
|
|
|
|
userName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The login of a user."
|
|
::= { info 10 }
|
|
|
|
objectName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The model type of the device"
|
|
::= { info 12 }
|
|
|
|
objectInstance OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The device name."
|
|
::= { info 13}
|
|
|
|
targetUser OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user record being operated on"
|
|
::= { info 14}
|
|
|
|
groupName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The group record being operated on"
|
|
::= { info 15 }
|
|
|
|
imageVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The version of the Upgrade image"
|
|
::= { info 18 }
|
|
|
|
sensorDescr OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor description indicating which sensor experienced a threshold event.
|
|
When applicable, the description will indicate the sensor number."
|
|
::= { info 19 }
|
|
|
|
thresholdDescr OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Threshold description indicating which configured threshold has been triggered (or cleared)."
|
|
::= { info 20 }
|
|
|
|
thresholdSeverity OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"String (Warning, Critical, etc...) indicating the severity of the threshold which has been triggered (or cleared)."
|
|
::= { info 21 }
|
|
|
|
thresholdEventType OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"String (triggered, cleared) indicating if the threshold event indicates that a configured threshold
|
|
has been triggered or cleared."
|
|
::= { info 22 }
|
|
|
|
status OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The success status of an operation"
|
|
::= { info 23 }
|
|
|
|
slaveIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In an outlet grouping configuration, this is the IP address of slave PDU. A value of 0.0.0.0 indicates an error
|
|
or an unset option."
|
|
::= { info 24}
|
|
|
|
|
|
inputCurrentRating OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input current Rating"
|
|
::= { info 25}
|
|
|
|
ratedVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU Rated Voltage "
|
|
::= { info 26 }
|
|
|
|
ratedPower OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU Rated Power "
|
|
::= { info 27 }
|
|
|
|
|
|
outletSwitching OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet switching: enabled/disabled; for non-switched PDUs, this value can be read,
|
|
but cannot be written "
|
|
::= { info 28 }
|
|
|
|
dataLogging OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data Retrieval: enabled/disabled"
|
|
::= { info 29 }
|
|
|
|
|
|
dataLoggingInterval OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Data Logging periodicity in seconds. This is the periodicity of the data in the buffer.
|
|
This value must be a multiple of 3 between 3 and 600. For example, 60 is valid,
|
|
but 64 is not valid
|
|
This is being deprecated in favor of measurementsPerLogEntry.
|
|
The mapping is as follows.
|
|
|
|
dataLoggingInterval measurementsPerLogEntry
|
|
3n n
|
|
|
|
Example: dataLoggingInterval is 60, so every 60 seconds (or 20th sample)
|
|
data will be placed in the data log
|
|
measurementsPerLogEntry is 20, so the data log sill store the minimum, average
|
|
and maximum of every 20 samples
|
|
"
|
|
::= { info 30 }
|
|
|
|
dataCollectionInterval OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data Collection periodicity. This is the periodicity of the data collected by the PX. This value
|
|
is fixed at 3 seconds."
|
|
::= { info 31 }
|
|
|
|
outletEnergySupport OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet Energy Support: Yes/No
|
|
If the value is No, then outletWattHours and dataLogOutletWattHours will be zero "
|
|
::= { info 32 }
|
|
|
|
currentUnbalanceSupport OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current Unbalance calculations Supported: Yes/No
|
|
If the value is No, then currentUnbalance will be zero
|
|
Default is No "
|
|
::= { info 33 }
|
|
|
|
externalSensorsZCoordinateUnits OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External Sensor Z Coordinate units: Freeform or Rack Units (U)
|
|
Default is U "
|
|
::= { info 34 }
|
|
|
|
inlineMeter OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Is this unit an inline meter? Yes/No
|
|
If Yes, then the folowing pairings hold:
|
|
Inlet 1 <-> Outlet 1
|
|
Inlet 2 <-> Outlet 2
|
|
Inlet 3 <-> Outlet 3
|
|
Inlet 4 <-> Outlet 4
|
|
|
|
Use the inletTable to obtain inlet data
|
|
|
|
Use the inletPoleTable to obtain the line data for an inlet.
|
|
|
|
"
|
|
::= { info 35 }
|
|
|
|
|
|
oldSensorState OBJECT-TYPE
|
|
SYNTAX StateOfSensorEnumeration
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The old sensor state used in Sensor State Transition traps."
|
|
::= { info 36}
|
|
|
|
|
|
externalSensorNumber OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each sensor. Its value
|
|
ranges between 1 and the value of externalSensorCount."
|
|
::= { info 37 }
|
|
|
|
|
|
|
|
sensorIdentificationString OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"String that uniquely identifies the external sensor.
|
|
Format is: SensorType,ChannelNumber,SensorSubtype,SerialNumber
|
|
Example external temperature sensor: Temperature,,,AEI8160083
|
|
Example external smoke detection sensor: onOff,2,contact,AEJ8160085
|
|
Example outlet Current: rmsCurrent,,,
|
|
"
|
|
::= { info 38 }
|
|
|
|
|
|
|
|
lastUpgradeStatus OBJECT-TYPE
|
|
SYNTAX BITS{
|
|
mainController(0),
|
|
psoc1(1),
|
|
psoc2(2),
|
|
psoc3(3),
|
|
psoc4(4),
|
|
psoc5(5),
|
|
psoc6(6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A bit string which indicates which the status of the last upgrade.
|
|
A value of 1 for a bit position indicates that the corresponding upgrade failed.
|
|
If all bits are zero, then the upgrade succeeded;
|
|
otherwise check lastUpgradeErrorDescription for further information.
|
|
"
|
|
::= { info 39 }
|
|
|
|
|
|
lastUpgradeTimestamp OBJECT-TYPE
|
|
SYNTAX DateAndTime
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The time when the last upgrade completed"
|
|
::= { info 40 }
|
|
|
|
|
|
lastUpgradeErrorDescription OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"String that describes the upgrade errror.
|
|
This is an empty string if the upgrade succeeded.
|
|
Format is
|
|
Failed PSOCs: 1[O:1,2,3-7];3[O:6-9,10-12]
|
|
This indicates that upgrade of psocs 1 and 3 failed and
|
|
psoc1 affects outlets 1,2, 3-7
|
|
and psoc2 affects outlets 6-9,10-12
|
|
"
|
|
::= { info 41 }
|
|
|
|
|
|
powerCIMStatus OBJECT-TYPE
|
|
SYNTAX PowerCIMStatusEnumeration
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the Power CIM: on or off
|
|
"
|
|
::= { info 42 }
|
|
|
|
|
|
measurementsPerLogEntry OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of measurements used for each entry in the log.
|
|
1<= Value <= 200
|
|
Default is 20
|
|
This is related to dataLoggingInterval as shown below
|
|
|
|
dataLoggingInterval measurementsPerLogEntry
|
|
3n n
|
|
|
|
Example: dataLoggingInterval is 60, so every 60 seconds (or 20th sample)
|
|
data will be placed in the data log
|
|
measurementsPerLogEntry is 20, so the data log sill store the minimum, average
|
|
and maximum of every 20 samples"
|
|
::= { info 43}
|
|
|
|
psocNumber OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The psoc (Outlet Controller) number"
|
|
::= { info 44}
|
|
|
|
altitude OBJECT-TYPE
|
|
SYNTAX Integer32(0..3000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The altitude (height above sea level) of the PDU in meters.
|
|
0 <= Value <= 3000; default value is 0 meters "
|
|
::= { info 45}
|
|
|
|
configureAlerts OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is an operation. It has write-only semantics.
|
|
GET operation will return the empty string.
|
|
For SET operations, it configures alerts
|
|
The format is a comma separated list of the following parameters.
|
|
sensorClass, eventType, eventDirection, policyName
|
|
For sensorclass: use the SensorClass eumeration
|
|
For eventType: use the EventType enumeration
|
|
For eventDirection: use the EventDirection enumeration
|
|
For Policy Name: use the name of the policy; the Policy Name is case sensitive
|
|
Note: setting this variable will overwrite the existing policy
|
|
|
|
|
|
Example: if the External Temperature upper non-critical threshold is either asserted and deasserted,
|
|
then execute the policy named multiple destinations
|
|
the string would be
|
|
0,1,2,multiple destinations
|
|
|
|
|
|
|
|
"
|
|
::= { info 46 }
|
|
|
|
fipsMode OBJECT-TYPE
|
|
SYNTAX EnabledDisabledEnumeration
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The fips mode: either enabled or disabled.
|
|
The mode can be set (changed) only if both of the following conditions hold
|
|
a) the user is admin
|
|
b) snmpv3 is being used.
|
|
Changing this mode will result in a reboot of the PX
|
|
When the PX is in FIPS mode, the follwing conditions hold.
|
|
a) FIPS approved algorithms must be used
|
|
b) snmp v1 & v2c are not supported
|
|
b) snmp v3 must be used with AES and SHA
|
|
c) https must be used; http is not supported
|
|
d) Radius authentication is not supported
|
|
e) Ldaps must be used; ldap is not supported
|
|
f) ipmi v2.0 must be used
|
|
"
|
|
::= { info 47}
|
|
|
|
|
|
|
|
|
|
synchronizeWithNTPServer OBJECT-TYPE
|
|
SYNTAX EnabledDisabledEnumeration
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Will time be obtained using NTP?
|
|
Deafault is disabled, i.e. time will not be obtained from NTP servers."
|
|
|
|
::= { info 48 }
|
|
|
|
useDHCPProvidedNTPServer OBJECT-TYPE
|
|
SYNTAX EnabledDisabledEnumeration
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Will the NTP server addresses be provided by DHCP/BOOTP?
|
|
This is used only if synchronizeWithNTPServer is enabled
|
|
Default is enabled, i.e. DHCP provided NTP servers will be used "
|
|
|
|
::= { info 49 }
|
|
|
|
|
|
-- Corresponding InetAddressType objects and InetAddress objects must be consistent.
|
|
-- primaryNTPServerAddressType and primaryNTPServerAddress must be consistent
|
|
-- secondaryNTPServerAddressType and secondaryNTPServerAddress must be consistent
|
|
|
|
-- Attempts to set an InetAddress object to a value inconsistent with the associated InetAddressType
|
|
-- must fail with an inconsistentValue error.
|
|
-- Example:
|
|
-- Suppose InetAddressType = ipv4 and InetAddress = 192.168.25.67
|
|
-- Setting InetAddress to www.xyz.com will return inconsistentValue error
|
|
|
|
|
|
-- When InetAddressType is changed to a type inconsistent with InetAddress, InetAddress may not display
|
|
-- the correct value until the format of InetAddress is changed to be consistent with InetAddressType
|
|
-- Example:
|
|
-- Suppose InetAddressType = ipv4 and InetAddress = 192.168.25.67
|
|
-- InetAddressType is set to dns.
|
|
-- A GET operation on InetAddress may not display the correct value.
|
|
-- InetAddress is changed to www.xyz.com
|
|
-- A GET operation on InetAddress displays the correct value.
|
|
|
|
-- Recommended Approach to changing IP address representation.
|
|
|
|
-- 1) First change InetAddressType to the correct type.
|
|
-- 2) Next change InetAddress to a value consistent with the type.
|
|
|
|
-- Example: Change from IPv4 address to hostname
|
|
-- Intially: InetAddressType = ipv4
|
|
-- InetAddress = 192.168.25.67
|
|
-- Change: InetAddressType = dns
|
|
-- InetAddress = 192.67.29.36
|
|
|
|
|
|
primaryNTPServerAddressType OBJECT-TYPE
|
|
SYNTAX InetAddressType
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Represents the type of the corresponding instance
|
|
of primaryNTPServerAddress object.
|
|
|
|
|
|
"
|
|
DEFVAL { ipv4 }
|
|
::= { info 50 }
|
|
|
|
primaryNTPServerAddress OBJECT-TYPE
|
|
SYNTAX InetAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The address of the primary ntp server."
|
|
::= { info 51 }
|
|
|
|
|
|
secondaryNTPServerAddressType OBJECT-TYPE
|
|
SYNTAX InetAddressType
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Represents the type of the corresponding instance
|
|
of secondaryNTPServerAddress object.
|
|
Default is ipv4"
|
|
|
|
::= { info 52 }
|
|
|
|
secondaryNTPServerAddress OBJECT-TYPE
|
|
SYNTAX InetAddress
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The address of the secondary ntp server."
|
|
::= { info 53 }
|
|
|
|
|
|
|
|
|
|
|
|
daylightSavingsTime OBJECT-TYPE
|
|
SYNTAX EnabledDisabledEnumeration
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Is daylight savings time enabled?
|
|
Default is disabled "
|
|
|
|
::= { info 55 }
|
|
|
|
|
|
thresholdValue OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the threshold that has been triggered (or cleared).
|
|
It is used in the thresholdAlarm trap for external numeric sensors only."
|
|
::= { info 56 }
|
|
|
|
|
|
sensorValue OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The sensor reading that triggered (or cleared) the threshold.
|
|
It is used in the thresholdAlarm trap for external numeric sensors only."
|
|
::= { info 57 }
|
|
|
|
|
|
|
|
|
|
ipmiOverLAN OBJECT-TYPE
|
|
SYNTAX EnabledDisabledEnumeration
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"IPMI over LAN Mode: either enabled or disabled.
|
|
It is strongly recommended that SNMPv3 be used to change the mode;
|
|
SNMPv2c may also be used, but is not recommended.
|
|
If SNMPv3 is used, then the change can be made only by users belonging to the Admin group.
|
|
Changing the mode will result in a reboot of the PX.
|
|
|
|
"
|
|
::= { info 58}
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
-- the inlets group
|
|
|
|
-- Implementation for managing the inlets
|
|
|
|
inletCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of inlets present on this pdu."
|
|
::= { inlets 1 }
|
|
|
|
|
|
-- the inlets table
|
|
|
|
-- The inlets table contains information on the pdu's inlets.
|
|
-- It further provides functions for managing them.
|
|
|
|
inletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF InletEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of inlet entries. The number of
|
|
entries is given by the value of inletCount."
|
|
::= { inlets 2 }
|
|
|
|
inletEntry OBJECT-TYPE
|
|
SYNTAX InletEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An inlet entry containing objects for each inlet"
|
|
INDEX { inletIndex }
|
|
::= { inletTable 1 }
|
|
|
|
InletEntryStruct ::= SEQUENCE { inletIndex Integer32,
|
|
inletPoleCount Integer32,
|
|
inletCurrentRating MilliAmps,
|
|
inletCurrent MilliAmps,
|
|
inletVoltage MilliVolts,
|
|
inletActivePower Watts,
|
|
inletApparentPower VoltAmps,
|
|
inletPowerFactor PowerFactorPercentage,
|
|
inletActiveEnergy WattHours,
|
|
inletCurrentUnbalance DisplayString,
|
|
inletCurrentUpperWarning MilliAmps,
|
|
inletCurrentUpperCritical MilliAmps,
|
|
inletCurrentLowerWarning MilliAmps,
|
|
inletCurrentLowerCritical MilliAmps,
|
|
inletVoltageUpperWarning MilliVolts,
|
|
inletVoltageUpperCritical MilliVolts,
|
|
inletVoltageLowerWarning MilliVolts,
|
|
inletVoltageLowerCritical MilliVolts,
|
|
inletCurrentUnbalanceUpperCritical Percentage,
|
|
inletCurrentUnbalanceUpperWarning Percentage,
|
|
inletCurrentHysteresis Unsigned32,
|
|
inletVoltageHysteresis Unsigned32,
|
|
inletCurrentUnbalanceHysteresis Unsigned32
|
|
}
|
|
|
|
inletIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each inlet. Its value
|
|
ranges between 1 and the value of inletCount."
|
|
::= { inletEntry 1 }
|
|
|
|
inletPoleCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of poles for an inlet (1 for single phase, 3 for 3 phase Delta-wired,
|
|
4 for 3 phase WYE wired)."
|
|
::= { inletEntry 3 }
|
|
|
|
inletCurrentRating OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input current Rating"
|
|
::= { inletEntry 4}
|
|
|
|
inletCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the current sensor
|
|
attached to the inlet. This value is
|
|
reported in milliamps (1/1000th of an amp).
|
|
This OID does not apply to 3 phase systems;
|
|
a value of 0 will be reported for same."
|
|
::= { inletEntry 7 }
|
|
|
|
inletVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the voltage sensor
|
|
attached to the intlet.This value is
|
|
reported in millivolts (1/1000th of a volt).
|
|
This OID does not apply to 3 phase systems;
|
|
a value of 0 will be reported for same."
|
|
::= { inletEntry 8 }
|
|
|
|
inletActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The active power for the inlet
|
|
This value is reported in Watts."
|
|
::= { inletEntry 9 }
|
|
|
|
inletApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The apparent power for the inlet.
|
|
This value is reported in Volt-Amps"
|
|
::= { inletEntry 10 }
|
|
|
|
inletPowerFactor OBJECT-TYPE
|
|
SYNTAX PowerFactorPercentage
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the power factor
|
|
of the inlet. The reading represents a
|
|
percentage in the range of 0% to 100%."
|
|
::= { inletEntry 11 }
|
|
|
|
inletActiveEnergy OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object has an invalid value if outletEnergySupport = 'No';
|
|
In all other cases, it is the value of the cumulative active energy for this inlet.
|
|
This value is reported in WattHours"
|
|
::= { inletEntry 12 }
|
|
|
|
inletCurrentUnbalance OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string displaying the current unbalance in percent.
|
|
It will have the value NA if
|
|
the feature is disabled,
|
|
the PX is not a 3-phase unit,or
|
|
the average of the line currents is zero"
|
|
::= { inletEntry 15 }
|
|
|
|
inletCurrentUpperWarning OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical)
|
|
current threshold for the inlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { inletEntry 20 }
|
|
|
|
inletCurrentUpperCritical OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical current
|
|
threshold for the inlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { inletEntry 21 }
|
|
|
|
|
|
inletCurrentLowerWarning OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower warning (non-critical)
|
|
current threshold for the inlet. This value is
|
|
reported in milliamps (1/1000th of an amp).
|
|
This OID is valid for inline meter PDU's. only"
|
|
::= { inletEntry 22 }
|
|
|
|
inletCurrentLowerCritical OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower critical current
|
|
threshold for the inlet. This value is
|
|
reported in milliamps (1/1000th of an amp).
|
|
This OID is valid for inline meter PDU's only."
|
|
::= { inletEntry 23 }
|
|
|
|
inletVoltageUpperWarning OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical)
|
|
current threshold for the inlet. This value is
|
|
reported in millivolts (1/1000th of a volt)"
|
|
::= { inletEntry 24 }
|
|
|
|
inletVoltageUpperCritical OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical current
|
|
threshold for the inlet. This value is
|
|
reported in millivolts (1/1000th of a volt)"
|
|
::= { inletEntry 25 }
|
|
|
|
inletVoltageLowerWarning OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower warning (non-critical)
|
|
current threshold for the inlet. This value is
|
|
reported in millivolts (1/1000th of a volt)"
|
|
::= { inletEntry 26 }
|
|
|
|
inletVoltageLowerCritical OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower critical current
|
|
threshold for the inlet. This value is
|
|
reported in millivolts (1/1000th of a volt)"
|
|
::= { inletEntry 27 }
|
|
|
|
inletCurrentUnbalanceUpperCritical OBJECT-TYPE
|
|
SYNTAX Percentage
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical current Unbalance threshold."
|
|
::= { inletEntry 28 }
|
|
|
|
inletCurrentUnbalanceUpperWarning OBJECT-TYPE
|
|
SYNTAX Percentage
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning current Unbalance threshold."
|
|
::= { inletEntry 29 }
|
|
|
|
|
|
inletCurrentHysteresis OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for deassertions. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { inletEntry 30 }
|
|
|
|
|
|
inletVoltageHysteresis OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for deassertions. This value is
|
|
reported in millivolts (1/1000th of a volt)"
|
|
::= { inletEntry 31 }
|
|
|
|
inletCurrentUnbalanceHysteresis OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for deassertions. This value is
|
|
reported in percent"
|
|
::= { inletEntry 32 }
|
|
|
|
-- the inletPole group
|
|
|
|
-- Implementation for Line data
|
|
|
|
-- the inletPole table
|
|
|
|
-- The inletPoleTable table contains information on the poles for an inlet
|
|
|
|
inletPoleTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF InletPoleEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of line input entries. The number of entries is given by
|
|
the value of inletTable(inletIndex).inletPoleCount."
|
|
::= { inletPole 2 }
|
|
|
|
inletPoleEntry OBJECT-TYPE
|
|
SYNTAX InletPoleEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry in the data log containing input line values
|
|
for a particular input line."
|
|
INDEX { inletIndex,inletPoleIndex }
|
|
::= { inletPoleTable 1 }
|
|
|
|
InletPoleEntryStruct ::= SEQUENCE { inletPoleIndex Integer32,
|
|
inletPoleLabel DisplayString,
|
|
inletPoleCurrent MilliAmps,
|
|
inletPoleVoltage MilliVolts,
|
|
inletPoleMaxCurrent MilliAmps,
|
|
inletPoleActivePower Watts,
|
|
inletPoleApparentPower VoltAmps,
|
|
inletPolePowerFactor PowerFactorPercentage,
|
|
inletPoleActiveEnergy WattHours
|
|
}
|
|
|
|
inletPoleIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each line input. Its value
|
|
ranges between 1 and of inletTable(inletIndex).inletPoleCount."
|
|
::= { inletPoleEntry 1 }
|
|
|
|
|
|
inletPoleLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying the Line
|
|
For Single Phase: L1
|
|
For 3phase Delta wired outlets: L1, L2, L3
|
|
For 3phase WYE Wired Outlets: L1, L2, L3"
|
|
::= { inletPoleEntry 2 }
|
|
|
|
inletPoleCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the line current reported in MilliAmps.
|
|
inletPoleIndex = 1; For Single Phase, Input Line Current; For 3-phase, L1 Current
|
|
inletPoleIndex = 2; For 3-phase, L2 Current
|
|
inletPoleIndex = 3; For 3-phase, L3 Current"
|
|
::= { inletPoleEntry 3 }
|
|
|
|
inletPoleVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the line-line voltage reported in MilliVolts.
|
|
inletPoleIndex = 1; Single Phase Input Line Voltage
|
|
3-phase, L1-L2 Voltage or L1-N voltage
|
|
inletPoleIndex = 2; 3-phase L2-L3 Voltage or L2-N voltage
|
|
inletPoleaIndex = 3; 3-phase L3-L1 Voltage or L3-N voltage"
|
|
::= { inletPoleEntry 4 }
|
|
|
|
inletPoleMaxCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object has an invalid value for a single-phase PDU.
|
|
If inletPoleCount = 1, then the value is invalid;
|
|
In all other cases, it is the value of the max. current sensor
|
|
attached to the inlet Pole. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { inletPoleEntry 5 }
|
|
|
|
inletPoleActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object has a valid value only for inline meters.
|
|
If inlineMeter = 'No', then the value is invalid;
|
|
In all other cases, it is the active power for the line/pole.
|
|
The value is reported in Watts."
|
|
::= { inletPoleEntry 7 }
|
|
|
|
inletPoleApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object has a valid value only for inline meters.
|
|
If inlineMeter = 'No', then the value is invalid;
|
|
In all other cases, it is the apparent power for the line/pole.
|
|
The value is reported in Volt-Amps"
|
|
::= { inletPoleEntry 8 }
|
|
|
|
inletPolePowerFactor OBJECT-TYPE
|
|
SYNTAX PowerFactorPercentage
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object has a valid value only for inline meters.
|
|
If inlineMeter = 'No', then the value is invalid;
|
|
In all other cases, it is the power factor for the line/pole
|
|
The reading represents a percentage in the range of 0% to 100%."
|
|
::= { inletPoleEntry 9 }
|
|
|
|
inletPoleActiveEnergy OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object has a valid value only for inline meters.
|
|
If inlineMeter = 'No', then the value is invalid;
|
|
In all other cases, it is the cumulative active energy for the line/pole.
|
|
The value is reported in WattHours"
|
|
::= { inletPoleEntry 11 }
|
|
|
|
|
|
-- the outlets group
|
|
|
|
-- Implementation for managing the outlets
|
|
|
|
outletCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of outlets (regardless of
|
|
their current state) present on this pdu."
|
|
::= { outlets 1 }
|
|
|
|
-- the outlets table
|
|
|
|
-- The outlets table contains information on the pdu's outlets.
|
|
-- It further provides functions for managing them.
|
|
|
|
outletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF OutletEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of outlet entries. The number of
|
|
entries is given by the value of outletCount."
|
|
::= { outlets 2 }
|
|
|
|
outletEntry OBJECT-TYPE
|
|
SYNTAX OutletEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An outlet entry containing objects at the
|
|
for a particular outlet."
|
|
INDEX { outletIndex }
|
|
::= { outletTable 1 }
|
|
|
|
OutletEntryStruct ::= SEQUENCE { outletIndex Integer32,
|
|
outletLabel DisplayString,
|
|
outletOperationalState INTEGER,
|
|
outletCurrent MilliAmps,
|
|
outletMaxCurrent MilliAmps,
|
|
outletVoltage MilliVolts,
|
|
outletActivePower Watts,
|
|
outletApparentPower VoltAmps,
|
|
outletPowerFactor PowerFactorPercentage,
|
|
outletCurrentUpperWarning MilliAmps,
|
|
outletCurrentUpperCritical MilliAmps,
|
|
outletCurrentLowerWarning MilliAmps,
|
|
outletCurrentLowerCritical MilliAmps,
|
|
outletCurrentHysteresis Unsigned32,
|
|
outletCurrentRating MilliAmps,
|
|
outletWattHours WattHours }
|
|
|
|
outletIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each outlet. Its value
|
|
ranges between 1 and the value of outletCount."
|
|
::= { outletEntry 1 }
|
|
|
|
outletLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A textual string containing information
|
|
about the outlet."
|
|
::= { outletEntry 2 }
|
|
|
|
|
|
outletOperationalState OBJECT-TYPE
|
|
SYNTAX INTEGER { error(-1),
|
|
off(0),
|
|
on(1),
|
|
cycling(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A value for each outlet which describes the
|
|
operational state of the outlet. It is also
|
|
used to set the operational state of the outlet"
|
|
::= { outletEntry 3 }
|
|
|
|
outletCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the current sensor
|
|
attached to the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { outletEntry 4 }
|
|
|
|
outletMaxCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the max. current sensor
|
|
attached to the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { outletEntry 5 }
|
|
|
|
outletVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the voltage sensor
|
|
attached to the outlet.This value is
|
|
reported in millivolts (1/1000th of a volt)"
|
|
::= { outletEntry 6 }
|
|
|
|
outletActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the active power sensor
|
|
attached to the outlet. This value is
|
|
reported in Watts."
|
|
::= { outletEntry 7 }
|
|
|
|
outletApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the apparent power sensor
|
|
attached to the outlet. This value is
|
|
reported in Volt-Amps"
|
|
::= { outletEntry 8 }
|
|
|
|
outletPowerFactor OBJECT-TYPE
|
|
SYNTAX PowerFactorPercentage
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for the power factor
|
|
of the outlet. The reading represents a
|
|
percentage in the range of 0% to 100%."
|
|
::= { outletEntry 9 }
|
|
|
|
outletCurrentUpperWarning OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical)
|
|
current threshold for the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { outletEntry 20 }
|
|
|
|
outletCurrentUpperCritical OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical current
|
|
threshold for the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { outletEntry 21 }
|
|
|
|
|
|
outletCurrentLowerWarning OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower warning (non-critical)
|
|
current threshold for the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { outletEntry 22 }
|
|
|
|
outletCurrentLowerCritical OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower critical current
|
|
threshold for the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { outletEntry 23 }
|
|
|
|
outletCurrentHysteresis OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for deassertions. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { outletEntry 24 }
|
|
|
|
outletCurrentRating OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current rating of the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { outletEntry 30 }
|
|
|
|
outletWattHours OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the cumulative active energy for this outlet.
|
|
This value is reported in WattHours"
|
|
::= { outletEntry 31 }
|
|
|
|
-- the unitReadings group
|
|
|
|
-- The unitReadings group contains sensor reading values
|
|
-- for the PDU unit as a whole
|
|
|
|
unitCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value for the unit's current sensor in millamps.This object is deprecated
|
|
in favour of lineCurrent corresponding to lineCurrentLabel = L1"
|
|
::= { unitReadings 1 }
|
|
|
|
unitVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value for the unit's voltage sensor in millivolts.This object is deprecated
|
|
in favour of lineVoltage corresponding to lineVoltageLabel = L1"
|
|
::= { unitReadings 2 }
|
|
|
|
unitActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value for the unit's active power in watts.This object is deprecated
|
|
in favour of inletTable.inletActivePower"
|
|
::= { unitReadings 3 }
|
|
|
|
unitApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value for the unit's apparent power in volt-amps. This object is deprecated
|
|
in favour of inletTable.inletApparentPower"
|
|
::= { unitReadings 4 }
|
|
|
|
unitCpuTemp OBJECT-TYPE
|
|
SYNTAX TenthDegreesCelsius
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value for the unit's CPU temperature sensor in tenth degrees celsius."
|
|
::= { unitReadings 5 }
|
|
|
|
unitVoltageLowerWarning OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the lower warning (non-critical) unit level voltage threshold.This object is deprecated
|
|
in favour of unitOrLineVoltageLowerWarning"
|
|
::= { unitReadings 60 }
|
|
|
|
unitVoltageLowerCritical OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the lower critical unit level voltage threshold.This object is deprecated
|
|
in favour of unitOrLineVoltageLowerCritical"
|
|
::= { unitReadings 61 }
|
|
|
|
unitVoltageUpperWarning OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) unit level voltage threshold.This object is deprecated
|
|
in favour of unitOrLineVoltageUpperWarning"
|
|
::= { unitReadings 62 }
|
|
|
|
unitVoltageUpperCritical OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the upper critical unit level voltage threshold.This object is deprecated
|
|
in favour of unitOrLineVoltageUpperCritical"
|
|
::= { unitReadings 63 }
|
|
|
|
unitCurrentUpperWarning OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) unit level current threshold.This object is deprecated
|
|
in favour of unitOrLineCurrentUpperWarning"
|
|
::= { unitReadings 70 }
|
|
|
|
unitCurrentUpperCritical OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the upper critical unit level current threshold. NOTE: This
|
|
particular threshold is NOT settable. This object is deprecated
|
|
in favour of unitOrLineCurrentUpperCritica"
|
|
::= { unitReadings 71 }
|
|
|
|
unitOrLineVoltageLowerWarning OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower warning (non-critical) unit level voltage threshold."
|
|
::= { unitReadings 90 }
|
|
|
|
unitOrLineVoltageLowerCritical OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower critical unit level voltage threshold."
|
|
::= { unitReadings 91 }
|
|
|
|
unitOrLineVoltageUpperWarning OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) unit level voltage"
|
|
::= { unitReadings 92 }
|
|
|
|
unitOrLineVoltageUpperCritical OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical unit level voltage threshold."
|
|
::= { unitReadings 93 }
|
|
|
|
unitOrLineCurrentUpperWarning OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) unit level current threshold"
|
|
::= { unitReadings 94 }
|
|
|
|
unitOrLineCurrentUpperCritical OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical unit level current threshold. "
|
|
::= { unitReadings 95 }
|
|
|
|
neutralCurrentUpperWarning OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object has an invalid value if inletPoleCount is not equal to 4.
|
|
If inletPoleCount = 4, then it is the value of the upper warning (non-critical) threshold
|
|
for the neutral current"
|
|
::= { unitReadings 96 }
|
|
|
|
neutralCurrentUpperCritical OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object has an invalid value if inletPoleCount is not equal to 4.
|
|
If inletPoleCount = 4, then it is the value of the upper critical threshold
|
|
for the neutral current."
|
|
::= { unitReadings 97 }
|
|
|
|
unitTempLowerWarning OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower warning (non-critical) unit level temperature threshold."
|
|
::= { unitReadings 80 }
|
|
|
|
unitTempLowerCritical OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the lower critical unit level temperature threshold."
|
|
::= { unitReadings 81 }
|
|
|
|
unitTempUpperWarning OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) unit level temperature threshold."
|
|
::= { unitReadings 82 }
|
|
|
|
unitTempUpperCritical OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical unit level temperature threshold."
|
|
::= { unitReadings 83 }
|
|
|
|
currentUnbalance OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string displaying the current unbalance in percent.
|
|
It will have the value NA if
|
|
the PX is not a 3-phase unit (inletPoleCount = 1),or
|
|
the feature is disabled (currentUnbalanceSupport = 'No'), or
|
|
the average of the line currents is zero (inletPoleCurrent = 0 for 1 <= inlePoleIndex <= 3)"
|
|
::= { unitReadings 84 }
|
|
|
|
currentUnbalanceUpperWarning OBJECT-TYPE
|
|
SYNTAX Percentage
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) current unbalance threshold."
|
|
::= { unitReadings 85 }
|
|
|
|
currentUnbalanceUpperCritical OBJECT-TYPE
|
|
SYNTAX Percentage
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical current Unbalance threshold."
|
|
::= { unitReadings 86 }
|
|
|
|
unitOrLineCurrentHysteresis OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for deassertions. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { unitReadings 98 }
|
|
|
|
unitOrLineVoltageHysteresis OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for deassertions. This value is
|
|
reported in millivolts (1/1000th of a volt)"
|
|
::= { unitReadings 99 }
|
|
|
|
|
|
|
|
unitTempHysteresis OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for deassertions
|
|
"
|
|
::= { unitReadings 100 }
|
|
|
|
|
|
currentUnbalanceHysteresis OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for deassertions
|
|
"
|
|
::= { unitReadings 101 }
|
|
|
|
-- the externalTemperature group
|
|
|
|
-- Implementation for managing external temperature sensors
|
|
|
|
tempSensorCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The number of external temperature sensors (regardless of
|
|
their current state) present on this pdu.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { environmental 1 }
|
|
|
|
-- the temperature sensors table
|
|
|
|
-- The tempSensorTable table contains information on the pdu's external temperature sensors.
|
|
|
|
tempSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TempSensorEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A list of temperature sensor entries. The number of
|
|
entries is given by the value of tempSensorCount.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { environmental 2 }
|
|
|
|
tempSensorEntry OBJECT-TYPE
|
|
SYNTAX TempSensorEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"An entry containing sensor reading and threshold
|
|
settings for a particular temperature sensor.
|
|
This is deprecated in favor of externalSensors"
|
|
INDEX { tempSensorIndex }
|
|
::= { tempSensorTable 1 }
|
|
|
|
TempSensorEntryStruct ::= SEQUENCE { tempSensorIndex Integer32,
|
|
tempSensorLabel DisplayString,
|
|
temperature TenthDegreesCelsius,
|
|
tempLowerWarning DegreesCelsius,
|
|
tempUpperWarning DegreesCelsius,
|
|
tempLowerCritical DegreesCelsius,
|
|
tempUpperCritical DegreesCelsius,
|
|
tempXCoordinate DisplayString,
|
|
tempYCoordinate DisplayString,
|
|
tempZCoordinate DisplayString}
|
|
|
|
tempSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A unique value for each temperature sensor. Its value
|
|
ranges between 1 and tempSensorCount.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { tempSensorEntry 1 }
|
|
|
|
tempSensorLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A settable human-readable label for the external temperature
|
|
sensor. One possible use for this label is to convey sensor
|
|
location.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { tempSensorEntry 2 }
|
|
|
|
temperature OBJECT-TYPE
|
|
SYNTAX TenthDegreesCelsius
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the external temperature sensor reported
|
|
in tenth degrees celsius.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { tempSensorEntry 3 }
|
|
|
|
tempLowerWarning OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the lower warning (non-critical) threshold.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { tempSensorEntry 4 }
|
|
|
|
tempUpperWarning OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) threshold.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { tempSensorEntry 5 }
|
|
|
|
tempLowerCritical OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the lower critical threshold.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { tempSensorEntry 6 }
|
|
|
|
tempUpperCritical OBJECT-TYPE
|
|
SYNTAX DegreesCelsius
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the upper critical threshold.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { tempSensorEntry 7 }
|
|
|
|
tempXCoordinate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of X coordinate in freeform
|
|
with number of characters <= 24
|
|
This is deprecated in favor of externalSensors"
|
|
::= { tempSensorEntry 8 }
|
|
|
|
tempYCoordinate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of Y coordinate in freeform
|
|
with number of characters <= 24
|
|
This is deprecated in favor of externalSensors"
|
|
::= { tempSensorEntry 9 }
|
|
|
|
tempZCoordinate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of Z coordinate in one of two formats:
|
|
either freeform with number of characters <= 24
|
|
or in Z units so that 0 =< integer value <= 60
|
|
This is deprecated in favor of externalSensors"
|
|
::= { tempSensorEntry 10 }
|
|
|
|
-- the externalHumidity group
|
|
|
|
-- Implementation for managing external humidity sensors
|
|
|
|
humiditySensorCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The number of external humidity sensors (regardless of
|
|
their current state) present on this pdu.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { environmental 3 }
|
|
|
|
-- the humidity sensors table
|
|
|
|
-- The humiditySensorTable table contains information on the pdu's external humidity sensors.
|
|
|
|
humiditySensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HumiditySensorEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A list of humidity sensor entries. The number of
|
|
entries is given by the value of humiditySensorCount.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { environmental 4 }
|
|
|
|
humiditySensorEntry OBJECT-TYPE
|
|
SYNTAX HumiditySensorEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"An entry containing sensor reading and threshold
|
|
settings for a particular humidity sensor.
|
|
This is deprecated in favor of externalSensors"
|
|
INDEX { humiditySensorIndex }
|
|
::= { humiditySensorTable 1 }
|
|
|
|
HumiditySensorEntryStruct ::= SEQUENCE { humiditySensorIndex Integer32,
|
|
humiditySensorLabel DisplayString,
|
|
humidity RelativeHumidity,
|
|
humidityLowerWarning RelativeHumidity,
|
|
humidityUpperWarning RelativeHumidity,
|
|
humidityLowerCritical RelativeHumidity,
|
|
humidityUpperCritical RelativeHumidity,
|
|
humidityXCoordinate DisplayString,
|
|
humidityYCoordinate DisplayString,
|
|
humidityZCoordinate DisplayString }
|
|
|
|
humiditySensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A unique value for each humidity sensor. Its value
|
|
ranges between 1 and humiditySensorCount.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { humiditySensorEntry 1 }
|
|
|
|
humiditySensorLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A settable human-readable label for the external humidity
|
|
sensor. One possible use for this label is to convey sensor
|
|
location.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { humiditySensorEntry 2 }
|
|
|
|
humidity OBJECT-TYPE
|
|
SYNTAX RelativeHumidity
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the external humidity sensor reported
|
|
as relative humidity (a percentage).
|
|
This is deprecated in favor of externalSensors"
|
|
::= { humiditySensorEntry 3 }
|
|
|
|
humidityLowerWarning OBJECT-TYPE
|
|
SYNTAX RelativeHumidity
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the lower warning (non-critical) threshold.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { humiditySensorEntry 4 }
|
|
|
|
humidityUpperWarning OBJECT-TYPE
|
|
SYNTAX RelativeHumidity
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) threshold.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { humiditySensorEntry 5 }
|
|
|
|
humidityLowerCritical OBJECT-TYPE
|
|
SYNTAX RelativeHumidity
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the lower critical threshold.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { humiditySensorEntry 6 }
|
|
|
|
humidityUpperCritical OBJECT-TYPE
|
|
SYNTAX RelativeHumidity
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the upper critical threshold.
|
|
This is deprecated in favor of externalSensors"
|
|
::= { humiditySensorEntry 7 }
|
|
|
|
|
|
humidityXCoordinate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of X coordinate in freeform
|
|
with number of characters <= 24
|
|
This is deprecated in favor of externalSensors"
|
|
::= { humiditySensorEntry 8 }
|
|
|
|
humidityYCoordinate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of Y coordinate in freeform
|
|
with number of characters <= 24
|
|
This is deprecated in favor of externalSensors"
|
|
::= { humiditySensorEntry 9 }
|
|
|
|
humidityZCoordinate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of Z coordinate in one of two formats:
|
|
either freeform with number of characters <= 24
|
|
or in Z units so that 0 =< integer value <= 60
|
|
This is deprecated in favor of externalSensors"
|
|
::= { humiditySensorEntry 10 }
|
|
|
|
-- the externalSensor table
|
|
|
|
-- The externalSensor table contains information on the pdu's external Sensors
|
|
|
|
externalSensorCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of external sensors"
|
|
::= { externalSensors 1}
|
|
|
|
reorderexternalSensorTableEntries OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is an operation. It has write-only semantics.
|
|
GET operation will return the empty string.
|
|
For SET operations, it specifies the new order of the externalSensorTable entries.
|
|
|
|
a) The list must contain entries for each managed sensor, even if the sensor is not being moved.
|
|
b) The list must not have more than 16 entries.
|
|
c) 1 <= Valid sensorID <= 16
|
|
d) The length of the list is the value of the largest sensorID in the
|
|
original (before the move) list of managed sensors.
|
|
e) Each sensorID must appear only once in the list.
|
|
f) If there are missing numbers in the original list of sensorIDs,
|
|
then each missing number must be indicated by a comma.
|
|
|
|
|
|
EXAMPLE 1: Managed sensors have IDs 1,2,3,4,5
|
|
Move 1 to 13; 2 to 8; 3 to 9; 4 is not moved; 5 moves to 2
|
|
Existing Position New Position
|
|
1 --> 13
|
|
2 --> 8
|
|
3 --> 9
|
|
4 --> 4
|
|
5 --> 2
|
|
Since the largest sensorID before the move is 5, the length of the list is 5
|
|
Comma separated list is 13,8,9,4,2
|
|
|
|
EXAMPLE 2: Managed sensors have IDs 2,5,6,7,11
|
|
Sensor IDs 1,3,4,8,9,10 do not appear in the list.
|
|
These positions must be indicated by commas.
|
|
Move 2 to 13; 5 to 8; 6 to 9; 7 to 16; 11 does not move
|
|
Existing Position New Position
|
|
2 --> 13
|
|
5 --> 8
|
|
6 --> 9
|
|
7 --> 16
|
|
11 --> 11
|
|
Since the largest sensorID before the move is 11, the length of the list is 11
|
|
Comma separated list is ,13,,,8,9,16,,,,11
|
|
|
|
"
|
|
::= { externalSensors 2 }
|
|
|
|
externalSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF ExternalSensorEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of externalSensor entries. The number of
|
|
entries is given by the value of externalSensorCount for the pdu."
|
|
::= { externalSensors 3 }
|
|
|
|
externalSensorEntry OBJECT-TYPE
|
|
SYNTAX ExternalSensorEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An externalSensor entry containing objects at the
|
|
for a particular PDU."
|
|
INDEX { sensorID }
|
|
::= { externalSensorTable 1 }
|
|
|
|
ExternalSensorEntryStruct ::= SEQUENCE {sensorID Integer32,
|
|
externalSensorType TypeOfSensorEnumeration,
|
|
externalSensorSerialNumber DisplayString,
|
|
externalSensorName DisplayString,
|
|
externalSensorChannelNumber Integer32,
|
|
externalSensorXCoordinate DisplayString,
|
|
externalSensorYCoordinate DisplayString,
|
|
externalSensorZCoordinate DisplayString,
|
|
externalBinarySensorSubtype TypeOfSensorEnumeration,
|
|
externalSensorUnits SensorUnitsEnumeration,
|
|
externalSensorDecimalDigits Unsigned32,
|
|
externalSensorLowerCriticalThreshold Integer32,
|
|
externalSensorLowerWarningThreshold Integer32,
|
|
externalSensorUpperCriticalThreshold Integer32,
|
|
externalSensorUpperWarningThreshold Integer32,
|
|
externalSensorHysteresis Unsigned32,
|
|
externalSensorState StateOfSensorEnumeration,
|
|
externalSensorValue Integer32 }
|
|
|
|
sensorID OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each sesnor. Its value
|
|
ranges between 1 and the value of externalSensorCount."
|
|
::= { externalSensorEntry 1 }
|
|
|
|
|
|
externalSensorType OBJECT-TYPE
|
|
SYNTAX TypeOfSensorEnumeration
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of sensor"
|
|
::= { externalSensorEntry 2 }
|
|
|
|
externalSensorSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The sensor serial number"
|
|
::= { externalSensorEntry 3 }
|
|
|
|
externalSensorName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user given name"
|
|
::= { externalSensorEntry 4 }
|
|
|
|
|
|
externalSensorChannelNumber OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The channel number, applies only to contact sensors;
|
|
-1 for other sensors"
|
|
::= { externalSensorEntry 5 }
|
|
|
|
externalSensorXCoordinate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The X coordinate"
|
|
::= { externalSensorEntry 6 }
|
|
|
|
externalSensorYCoordinate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Y coordinate"
|
|
::= { externalSensorEntry 7 }
|
|
|
|
externalSensorZCoordinate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Z coordinate"
|
|
::= { externalSensorEntry 8 }
|
|
|
|
externalBinarySensorSubtype OBJECT-TYPE
|
|
SYNTAX TypeOfSensorEnumeration
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The subtype of the binary sensor
|
|
This OID is valid for discrete sensors only."
|
|
::= { externalSensorEntry 9 }
|
|
|
|
externalSensorUnits OBJECT-TYPE
|
|
SYNTAX SensorUnitsEnumeration
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The base units. Does not apply (gets will return 0)
|
|
to onOff, trip, vibration, waterDetection,
|
|
smokeDetection sensors"
|
|
::= { externalSensorEntry 16 }
|
|
|
|
externalSensorDecimalDigits OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of digits displayed to the right of the decimal point.
|
|
Does not apply (gets will return 0)
|
|
to onOff, trip, vibration, waterDetection,
|
|
smokeDetection sensors"
|
|
::= { externalSensorEntry 17 }
|
|
|
|
externalSensorLowerCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The lower critical threshold
|
|
The value of this OID variable should be scaled by
|
|
externalSensorDecimalDigits. For example, if the value is 1 and
|
|
externalSensorDecimalDigits is 2, then actual value is .01
|
|
Does not apply (gets will return 0)
|
|
to onOff, trip, vibration, waterDetection,
|
|
smokeDetection sensors"
|
|
::= { externalSensorEntry 31 }
|
|
|
|
externalSensorLowerWarningThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The lower non-critical (warning) threshold
|
|
The value of this OID variable should be scaled by
|
|
externalSensorDecimalDigits. For example, if the value is 1 and
|
|
externalSensorDecimalDigits is 2, then actual value is .01
|
|
Does not apply (gets will return 0)
|
|
to onOff, trip, vibration, waterDetection,
|
|
smokeDetection sensors"
|
|
::= { externalSensorEntry 32 }
|
|
|
|
externalSensorUpperCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upper critical threshold
|
|
The value of this OID variable should be scaled by
|
|
externalSensorDecimalDigits. For example, if the value is 1 and
|
|
externalSensorDecimalDigits is 2, then actual value is .01
|
|
Does not apply (gets will return 0)
|
|
to onOff, trip, vibration, waterDetection,
|
|
smokeDetection sensors"
|
|
::= { externalSensorEntry 33 }
|
|
|
|
externalSensorUpperWarningThreshold OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upper non-critical (warning) threshold
|
|
The value of this OID variable should be scaled by
|
|
externalSensorDecimalDigits. For example, if the value is 1 and
|
|
externalSensorDecimalDigits is 2, then actual value is .01
|
|
Does not apply (gets will return 0)
|
|
to onOff, trip, vibration, waterDetection,
|
|
smokeDetection sensors"
|
|
::= { externalSensorEntry 34 }
|
|
|
|
externalSensorHysteresis OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for deassertions
|
|
The value of this OID variable should be scaled by
|
|
externalSensorDecimalDigits. For example, if the value is 1 and
|
|
externalSensorDecimalDigits is 2, then actual value is 0.01.
|
|
This parameter does not apply
|
|
to onOff, trip, vibration, waterDetection,
|
|
smokeDetection sensors."
|
|
::= { externalSensorEntry 35 }
|
|
|
|
|
|
externalSensorState OBJECT-TYPE
|
|
SYNTAX StateOfSensorEnumeration
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The sensor state"
|
|
::= { externalSensorEntry 40 }
|
|
|
|
externalSensorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The sensor reading
|
|
Does not apply (gets will return 0)
|
|
to onOff, trip, vibration, waterDetection,
|
|
smokeDetection sensors"
|
|
::= { externalSensorEntry 41 }
|
|
|
|
-- the line Current group
|
|
|
|
-- Implementation for line Inputs
|
|
|
|
lineCurrentCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The number of line currents (1 for single phase, 3 for 3 phase Delta-wired,
|
|
4 for 3 phase WYE wired).This object is deprecated in favour of inletPoleTable"
|
|
::= { lineCurrents 1 }
|
|
|
|
-- the line input table
|
|
|
|
-- The lineCurrentTable table contains information on the line inputs.
|
|
|
|
lineCurrentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LineCurrentEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A list of line input entries. The number of
|
|
entries is given by the value of lineInputCount.
|
|
This object is deprecated in favour of inletPoleTable"
|
|
::= { lineCurrents 2 }
|
|
|
|
lineCurrentEntry OBJECT-TYPE
|
|
SYNTAX LineCurrentEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"An entry containing values and threshold
|
|
settings for a particular line input.This object is deprecated in favour of inletPoleTable"
|
|
INDEX { lineCurrentIndex }
|
|
::= { lineCurrentTable 1 }
|
|
|
|
LineCurrentEntryStruct ::= SEQUENCE { lineCurrentIndex Integer32,
|
|
lineCurrentLabel DisplayString,
|
|
lineCurrent MilliAmps}
|
|
|
|
lineCurrentIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A unique value for each line input. Its value
|
|
ranges between 1 and lineInputCount.
|
|
This object is deprecated in favour of inletPoleTable"
|
|
::= { lineCurrentEntry 1 }
|
|
|
|
lineCurrentLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A string identifying the Line
|
|
For Single Phase: L1
|
|
For 3phase Delta wired outlets: L1, L2, L3
|
|
For 3phase WYE Wired Outlets: L1, L2, L3, N
|
|
This object is deprecated in favour of inletPoleTable"
|
|
::= { lineCurrentEntry 2 }
|
|
|
|
lineCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the current reported in MilliAmps.
|
|
This object is deprecated in favour of inletPoleTable"
|
|
::= { lineCurrentEntry 3 }
|
|
|
|
-- the circuitBreaker group
|
|
|
|
-- Implementation for circuit Breakers
|
|
|
|
circuitBreakerCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of circuit breakers."
|
|
::= { circuitBreaker 1 }
|
|
-- the circuit breaker table
|
|
|
|
-- The circuitBreakerTable table contains information on the circuit breakers.
|
|
|
|
circuitBreakerTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CircuitBreakerEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of line input entries. The number of
|
|
entries is given by the value of lineInputCount."
|
|
::= { circuitBreaker 2 }
|
|
|
|
circuitBreakerEntry OBJECT-TYPE
|
|
SYNTAX CircuitBreakerEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing values and threshold
|
|
settings for a particular line input."
|
|
INDEX { circuitBreakerIndex }
|
|
::= { circuitBreakerTable 1 }
|
|
|
|
CircuitBreakerEntryStruct ::= SEQUENCE { circuitBreakerIndex Integer32,
|
|
circuitBreakerLabel DisplayString,
|
|
circuitBreakerState INTEGER,
|
|
circuitBreakerCurrentRating MilliAmps,
|
|
circuitBreakerCurrent MilliAmps,
|
|
circuitBreakerCurrentUpperWarning MilliAmps,
|
|
circuitBreakerCurrentUpperCritical MilliAmps,
|
|
circuitBreakerCurrentHysteresis Unsigned32 }
|
|
|
|
circuitBreakerIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each circuit breaker. Its value
|
|
ranges between 1 and circuitBreakerCount."
|
|
::= { circuitBreakerEntry 1 }
|
|
|
|
circuitBreakerLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying the circuit breaker "
|
|
::= { circuitBreakerEntry 2 }
|
|
|
|
circuitBreakerState OBJECT-TYPE
|
|
SYNTAX INTEGER { ok(0),
|
|
tripped(1) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value for the circuit breaker state ."
|
|
::= { circuitBreakerEntry 3 }
|
|
|
|
circuitBreakerCurrentRating OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the circuit breaker current rating
|
|
in MilliAmps."
|
|
::= { circuitBreakerEntry 4 }
|
|
|
|
circuitBreakerCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the current reported
|
|
in MilliAmps."
|
|
::= { circuitBreakerEntry 5 }
|
|
|
|
circuitBreakerCurrentUpperWarning OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper warning (non-critical) threshold."
|
|
::= { circuitBreakerEntry 7 }
|
|
|
|
circuitBreakerCurrentUpperCritical OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the upper critical threshold."
|
|
::= { circuitBreakerEntry 9 }
|
|
|
|
circuitBreakerCurrentHysteresis OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for deassertions
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { circuitBreakerEntry 10 }
|
|
|
|
-- the line Voltage group
|
|
|
|
-- Implementation for line Voltages
|
|
|
|
lineVoltageCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The number of line voltages (1 for single phase, 3 for 3 phase.
|
|
This object is deprecated in favour of inletPoleTable"
|
|
::= { lineVoltages 1 }
|
|
|
|
-- the line voltage table
|
|
|
|
-- The linevoltageTable table contains information on the line voltages.
|
|
|
|
lineVoltageTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LineVoltageEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A list of line input entries. The number of
|
|
entries is given by the value of lineInputCount.
|
|
This object is deprecated in favour of linletPoleTable"
|
|
::= { lineVoltages 2 }
|
|
|
|
lineVoltageEntry OBJECT-TYPE
|
|
SYNTAX LineVoltageEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"An entry containing values and threshold
|
|
settings for a particular line input.
|
|
This object is deprecated in favour of inletPoleTable"
|
|
INDEX { lineVoltageIndex }
|
|
::= { lineVoltageTable 1 }
|
|
|
|
LineVoltageEntryStruct ::= SEQUENCE { lineVoltageIndex Integer32,
|
|
lineVoltageLabel DisplayString,
|
|
lineVoltage MilliVolts}
|
|
|
|
lineVoltageIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A unique value for each line input. Its value
|
|
ranges between 1 and lineInputCount.
|
|
This object is deprecated in favour of inletPoleTable"
|
|
::= { lineVoltageEntry 1 }
|
|
|
|
lineVoltageLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A string identifying the Line
|
|
For Single Phase: L1
|
|
For 3phase Delta-wired: L1-L2, L2-L3, L3-L1
|
|
For 3phase Wye-wired: L1-N, L2-N, L3-N
|
|
This object is deprecated in favour of inletPoleTable"
|
|
::= { lineVoltageEntry 2 }
|
|
|
|
lineVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the voltage reported in MilliVolts.
|
|
This object is deprecated in favour of inletPoleTable"
|
|
::= { lineVoltageEntry 3 }
|
|
|
|
-- the data Log group
|
|
|
|
-- Implementation for data Log
|
|
|
|
dataLogCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of entries in the dataLog table which is a circular buffer."
|
|
::= { dataLog 1 }
|
|
|
|
dataLogLatestIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the latest (most recent) entry in dataLogTable ."
|
|
::= { dataLog 2 }
|
|
|
|
-- the data log
|
|
|
|
-- The dataLogTable table contains the data log.
|
|
|
|
dataLogTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DataLogEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of data log entries. The number of
|
|
entries is given by the value of dataLogCount."
|
|
::= { dataLog 3 }
|
|
|
|
dataLogEntry OBJECT-TYPE
|
|
SYNTAX DataLogEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry in the dataLog buffer containing the unit data collected at the instant
|
|
specified by dataLogTimeStamp"
|
|
INDEX { dataLogIndex }
|
|
::= { dataLogTable 1 }
|
|
|
|
DataLogEntryStruct ::= SEQUENCE { dataLogIndex Integer32,
|
|
dataLogTimeStamp Unsigned32,
|
|
dataLogActivePower Watts,
|
|
dataLogApparentPower VoltAmps,
|
|
dataLogAvgActivePower Watts,
|
|
dataLogMaxActivePower Watts,
|
|
dataLogMinActivePower Watts,
|
|
dataLogAvgApparentPower VoltAmps,
|
|
dataLogMaxApparentPower VoltAmps,
|
|
dataLogMinApparentPower VoltAmps}
|
|
|
|
dataLogIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each data sample. Its value
|
|
ranges between 1 and dataLogCount ."
|
|
::= { dataLogEntry 1 }
|
|
|
|
dataLogTimeStamp OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The time when the data was collected. It is measured in seconds relative to
|
|
January 1, 1970 (midnight UTC/GMT), i.e a value of 0 indicates
|
|
January 1, 1970 (midnight UTC/GMT)"
|
|
::= { dataLogEntry 2 }
|
|
|
|
dataLogActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value for the pdu's active power sensor in watts.
|
|
This has been deprecated in favor of
|
|
dataLogAvgActivePower, dataLogMaxActivePower,dataLogMinActivePower "
|
|
::= { dataLogEntry 3 }
|
|
|
|
dataLogApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value for the pdu's apparent power sensor in volt-amps.
|
|
This has been deprecated in favor of
|
|
dataLogAvgApparentPower, dataLogMaxApparentPower,dataLogMinApparentPower "
|
|
::= { dataLogEntry 4 }
|
|
|
|
dataLogAvgActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The average active power for this measurement period"
|
|
::= { dataLogEntry 5 }
|
|
|
|
|
|
dataLogMaxActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum active power for this measurement period"
|
|
::= { dataLogEntry 6 }
|
|
|
|
dataLogMinActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum active power for this measurement period"
|
|
::= { dataLogEntry 7 }
|
|
|
|
dataLogAvgApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The average apparent power for this measurement period"
|
|
::= { dataLogEntry 8 }
|
|
|
|
dataLogMaxApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum apparent power for this measurement period"
|
|
::= { dataLogEntry 9 }
|
|
|
|
dataLogMinApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum apparent power for this measurement period"
|
|
::= { dataLogEntry 10 }
|
|
|
|
-- the outlets data group
|
|
|
|
-- Implementation for storing outlet data
|
|
|
|
-- the outlets data table
|
|
|
|
-- The outlets read-only data table contains information on the pdu's outlets.
|
|
-- This data can be uploaded to the manager
|
|
|
|
dataLogOutletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DataLogOutletEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of outlet entries. The number of
|
|
entries is given by the value of outletCount."
|
|
::= { dataLogOutlet 1 }
|
|
|
|
dataLogOutletEntry OBJECT-TYPE
|
|
SYNTAX DataLogOutletEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry in the data log containing outlet level data
|
|
for a particular outlet."
|
|
INDEX { dataLogIndex,dataLogOutletIndex }
|
|
::= { dataLogOutletTable 1 }
|
|
|
|
DataLogOutletEntryStruct ::= SEQUENCE { dataLogOutletIndex Integer32,
|
|
dataLogOutletCurrent MilliAmps,
|
|
dataLogOutletVoltage MilliVolts,
|
|
dataLogOutletPowerFactor PowerFactorPercentage,
|
|
dataLogOutletOnTime Unsigned32,
|
|
dataLogOutletWattHours WattHours,
|
|
dataLogAvgOutletCurrent MilliAmps,
|
|
dataLogMaxOutletCurrent MilliAmps,
|
|
dataLogMinOutletCurrent MilliAmps,
|
|
dataLogAvgOutletVoltage MilliVolts,
|
|
dataLogMaxOutletVoltage MilliVolts,
|
|
dataLogMinOutletVoltage MilliVolts,
|
|
dataLogAvgOutletPowerFactor PowerFactorPercentage,
|
|
dataLogMaxOutletPowerFactor PowerFactorPercentage,
|
|
dataLogMinOutletPowerFactor PowerFactorPercentage,
|
|
dataLogAvgOutletWattHours WattHours,
|
|
dataLogMaxOutletWattHours WattHours,
|
|
dataLogMinOutletWattHours WattHours
|
|
}
|
|
|
|
dataLogOutletIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each outlet. Its value
|
|
ranges between 1 and the value of outletCount."
|
|
::= { dataLogOutletEntry 1 }
|
|
|
|
dataLogOutletCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A unique value for the current sensor
|
|
attached to the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)
|
|
This has been deprecated in favor of
|
|
dataLogAvgOutletCurrent , dataLogMaxOutletCurrent ,dataLogMinOutletCurrent "
|
|
::= { dataLogOutletEntry 2 }
|
|
|
|
dataLogOutletVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A unique value for the voltage sensor
|
|
attached to the outlet.This value is
|
|
reported in millivolts (1/1000th of a volt)
|
|
This has been deprecated in favor of
|
|
dataLogAvgOutletVoltage , dataLogMaxOutletVoltage ,dataLogMinOutletVoltage "
|
|
::= { dataLogOutletEntry 3 }
|
|
|
|
dataLogOutletPowerFactor OBJECT-TYPE
|
|
SYNTAX PowerFactorPercentage
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A unique value for the power factor
|
|
of the outlet. The reading represents a
|
|
percentage in the range of 0% to 100%.
|
|
This has been deprecated in favor of
|
|
dataLogAvgOutletPowerFactor, dataLogMaxOutletPowerFactor,dataLogMinOutletPowerFactor "
|
|
::= { dataLogOutletEntry 4 }
|
|
|
|
dataLogOutletOnTime OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of time since this outlet was last switched on.
|
|
This value is reported in seconds. "
|
|
::= { dataLogOutletEntry 5 }
|
|
|
|
dataLogOutletWattHours OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The cumulative Active Energy for this outlet. This value is
|
|
reported in WattHours
|
|
This has been deprecated in favor of
|
|
dataLogAvgOutletWattHours , dataLogMaxOutletWattHours ,dataLogMinOutletWattHours"
|
|
::= { dataLogOutletEntry 6 }
|
|
|
|
dataLogAvgOutletCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Average value for the measurement period:
|
|
A unique value for the current sensor
|
|
attached to the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { dataLogOutletEntry 7 }
|
|
|
|
dataLogMaxOutletCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Maximum value for the measurement period:
|
|
A unique value for the current sensor
|
|
attached to the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { dataLogOutletEntry 8 }
|
|
|
|
dataLogMinOutletCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Minimum value for the measurement period:
|
|
A unique value for the current sensor
|
|
attached to the outlet. This value is
|
|
reported in milliamps (1/1000th of an amp)"
|
|
::= { dataLogOutletEntry 9 }
|
|
|
|
dataLogAvgOutletVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Average value for the measurement period:
|
|
A unique value for the voltage sensor
|
|
attached to the outlet.This value is
|
|
reported in millivolts (1/1000th of a volt)"
|
|
::= { dataLogOutletEntry 10 }
|
|
|
|
dataLogMaxOutletVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Maximum value for the measurement period:
|
|
A unique value for the voltage sensor
|
|
attached to the outlet.This value is
|
|
reported in millivolts (1/1000th of a volt)"
|
|
::= { dataLogOutletEntry 11 }
|
|
|
|
dataLogMinOutletVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Minimum value for the measurement period:
|
|
A unique value for the voltage sensor
|
|
attached to the outlet.This value is
|
|
reported in millivolts (1/1000th of a volt)"
|
|
::= { dataLogOutletEntry 12 }
|
|
|
|
|
|
dataLogAvgOutletPowerFactor OBJECT-TYPE
|
|
SYNTAX PowerFactorPercentage
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Average value for the measurement period:
|
|
A unique value for the power factor
|
|
of the outlet. The reading represents a
|
|
percentage in the range of 0% to 100%"
|
|
::= { dataLogOutletEntry 13 }
|
|
|
|
dataLogMaxOutletPowerFactor OBJECT-TYPE
|
|
SYNTAX PowerFactorPercentage
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Maximum value for the measurement period:
|
|
A unique value for the power factor
|
|
of the outlet. The reading represents a
|
|
percentage in the range of 0% to 100%"
|
|
::= { dataLogOutletEntry 14 }
|
|
|
|
dataLogMinOutletPowerFactor OBJECT-TYPE
|
|
SYNTAX PowerFactorPercentage
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Minimum value for the measurement period:
|
|
A unique value for the power factor
|
|
of the outlet. The reading represents a
|
|
percentage in the range of 0% to 100%"
|
|
::= { dataLogOutletEntry 15 }
|
|
|
|
dataLogAvgOutletWattHours OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Average value for the measurement period:
|
|
The cumulative Active Energy for this outlet. This value is
|
|
reported in WattHours"
|
|
::= { dataLogOutletEntry 16 }
|
|
|
|
dataLogMaxOutletWattHours OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Maximum value for the measurement period:
|
|
The cumulative Active Energy for this outlet. This value is
|
|
reported in WattHours"
|
|
::= { dataLogOutletEntry 17 }
|
|
|
|
dataLogMinOutletWattHours OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Minimum value for the measurement period:
|
|
The cumulative Active Energy for this outlet. This value is
|
|
reported in WattHours"
|
|
::= { dataLogOutletEntry 18 }
|
|
|
|
|
|
|
|
-- the circuitBreaker Data group
|
|
|
|
-- Implementation for circuit Breakers
|
|
|
|
-- the circuit breaker table
|
|
|
|
-- The circuitBreakerTable table contains information on the circuit breakers.
|
|
|
|
dataLogCircuitBreakerTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DataLogCircuitBreakerEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of circuit breaker entries. The number of
|
|
entries is given by the value of circuitBreakerCount."
|
|
::= { dataLogCircuitBreaker 1 }
|
|
|
|
dataLogCircuitBreakerEntry OBJECT-TYPE
|
|
SYNTAX DataLogCircuitBreakerEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry in the data log containing circuit breaker values"
|
|
INDEX { dataLogIndex, dataLogCircuitBreakerIndex }
|
|
::= { dataLogCircuitBreakerTable 1 }
|
|
|
|
DataLogCircuitBreakerEntryStruct ::= SEQUENCE { dataLogCircuitBreakerIndex Integer32,
|
|
dataLogCircuitBreakerCurrent MilliAmps,
|
|
dataLogAvgCircuitBreakerCurrent MilliAmps,
|
|
dataLogMaxCircuitBreakerCurrent MilliAmps,
|
|
dataLogMinCircuitBreakerCurrent MilliAmps }
|
|
|
|
dataLogCircuitBreakerIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each circuit breaker. Its value
|
|
ranges between 1 and circuitBreakerCount."
|
|
::= { dataLogCircuitBreakerEntry 1 }
|
|
|
|
dataLogCircuitBreakerCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the current reported
|
|
in MilliAmps.
|
|
This has been deprecated in favor of
|
|
dataLogAvgCircuitBreakerCurrent, dataLogMaxOutletCircuitBreakerCurrent,
|
|
dataLogMinCircuitBreakerCurrent "
|
|
::= { dataLogCircuitBreakerEntry 2 }
|
|
|
|
dataLogAvgCircuitBreakerCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Average value for the measurement period:
|
|
The value of the current reported
|
|
in MilliAmps."
|
|
::= { dataLogCircuitBreakerEntry 3 }
|
|
|
|
dataLogMaxCircuitBreakerCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Maximum value for the measurement period:
|
|
The value of the current reported
|
|
in MilliAmps."
|
|
::= { dataLogCircuitBreakerEntry 4 }
|
|
|
|
dataLogMinCircuitBreakerCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Minimum value for the measurement period:
|
|
The value of the current reported
|
|
in MilliAmps."
|
|
::= { dataLogCircuitBreakerEntry 5 }
|
|
|
|
|
|
-- the Input Line group
|
|
|
|
-- Implementation for Input Line
|
|
|
|
-- the line input table
|
|
|
|
-- The dataLogInputLineTable table contains information on the line inputs.
|
|
|
|
dataLogInputLineTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DataLogInputLineEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A list of line input entries. The number of
|
|
entries is given by the value of lineCurrentCount.
|
|
This object is deprecated in favour of dataLogInletLineTable"
|
|
::= { dataLogInputLine 1 }
|
|
|
|
dataLogInputLineEntry OBJECT-TYPE
|
|
SYNTAX DataLogInputLineEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"An entry in the data log containing input line values for a particular input line.
|
|
This object is deprecated in favour of dataLogInletLineTable"
|
|
INDEX { dataLogIndex,dataLogInputLineIndex }
|
|
::= { dataLogInputLineTable 1 }
|
|
|
|
DataLogInputLineEntryStruct ::= SEQUENCE { dataLogInputLineIndex Integer32,
|
|
dataLogInputLineCurrent MilliAmps,
|
|
dataLogInputLineVoltage MilliVolts}
|
|
|
|
dataLogInputLineIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A unique value for each line input. Its value
|
|
ranges between 1 and inletTable(inletIndex).inletPoleCount.
|
|
This object is deprecated in favour of dataLogInletLineTable"
|
|
::= { dataLogInputLineEntry 1 }
|
|
|
|
dataLogInputLineCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the current reported
|
|
in MilliAmps.
|
|
For Single Phase: Input Line Current
|
|
For 3phase Delta-wired: Current for L1, L2, L3
|
|
For 3phase WYE-wired: Current for L1, L2, L3, N
|
|
This object is deprecated in favour of dataLogInletLineTable"
|
|
::= { dataLogInputLineEntry 2 }
|
|
|
|
dataLogInputLineVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the voltage reported
|
|
in MilliVolts.
|
|
For Single Phase: Input Line Voltage
|
|
For 3phase Delta-wired: Voltages for L1-L2, L2-L3, L3-L1
|
|
For 3phase WYE-wired: Voltages for L1-N, L2-N, L3-N
|
|
This object is deprecated in favour of dataLogInletLineTable"
|
|
::= { dataLogInputLineEntry 3 }
|
|
|
|
-- the data Log inlets group
|
|
|
|
-- the inlets table for dataLog
|
|
|
|
dataLogInletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DataLogInletEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of inlet entries. The number of
|
|
entries is given by the value of inletCount."
|
|
::= { dataLogInlet 2 }
|
|
|
|
dataLogInletEntry OBJECT-TYPE
|
|
SYNTAX DataLogInletEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An inlet entry containing objects at the
|
|
for a particular outlet."
|
|
INDEX { dataLogIndex, dataLogInletIndex }
|
|
::= { dataLogInletTable 1 }
|
|
|
|
DataLogInletEntryStruct ::= SEQUENCE { dataLogInletIndex Integer32,
|
|
dataLogInletCurrentUnbalance DisplayString,
|
|
dataLogInletActivePower Watts,
|
|
dataLogInletApparentPower VoltAmps,
|
|
dataLogInletActiveEnergy WattHours,
|
|
dataLogAvgInletCurrentUnbalance DisplayString,
|
|
dataLogMaxInletCurrentUnbalance DisplayString,
|
|
dataLogMinInletCurrentUnbalance DisplayString,
|
|
dataLogAvgInletActivePower Watts,
|
|
dataLogMaxInletActivePower Watts,
|
|
dataLogMinInletActivePower Watts,
|
|
dataLogAvgInletApparentPower VoltAmps,
|
|
dataLogMaxInletApparentPower VoltAmps,
|
|
dataLogMinInletApparentPower VoltAmps,
|
|
dataLogAvgInletActiveEnergy WattHours,
|
|
dataLogMaxInletActiveEnergy WattHours,
|
|
dataLogMinInletActiveEnergy WattHours
|
|
}
|
|
|
|
dataLogInletIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each inlet. Its value
|
|
ranges between 1 and the value of inletCount."
|
|
::= { dataLogInletEntry 1 }
|
|
|
|
dataLogInletCurrentUnbalance OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A string displaying the current unbalance in percent.
|
|
It will have the value NA if the feature is disabled,
|
|
the PX is not a 3-phase unit,or the average of the line currents is zero
|
|
This has been deprecated in favor of
|
|
dataLogAvgInletCurrentUnbalance, dataLogMaxInletCurrentUnbalance,
|
|
dataLogMinInletCurrentUnbalance "
|
|
::= { dataLogInletEntry 10 }
|
|
|
|
dataLogInletActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The active power for the inlet
|
|
This value is reported in Watts.
|
|
This has been deprecated in favor of
|
|
dataLogAvgInletActivePower, dataLogMaxInletActivePower,
|
|
dataLogMinInletActivePower"
|
|
::= { dataLogInletEntry 11 }
|
|
|
|
dataLogInletApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The apparent power for the inlet.
|
|
This value is reported in Volt-Amps
|
|
This has been deprecated in favor of
|
|
dataLogAvgInletApparentPower, dataLogMaxInletApparentPower,
|
|
dataLogMinInletApparentPower"
|
|
::= { dataLogInletEntry 12 }
|
|
|
|
dataLogInletActiveEnergy OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the cumulative active energy for this inlet.
|
|
This value is reported in WattHours
|
|
This has been deprecated in favor of
|
|
dataLogAvgInletActiveEnergy, dataLogMaxInletActiveEnergy,
|
|
dataLogMinInletActiveEnergy"
|
|
::= { dataLogInletEntry 13 }
|
|
|
|
dataLogAvgInletCurrentUnbalance OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The average value of the current unbalance for this measurement period
|
|
A string displaying the current unbalance in percent.
|
|
It will have the value NA if the feature is disabled,
|
|
the PX is not a 3-phase unit,or the average of the line currents is zero"
|
|
::= { dataLogInletEntry 14 }
|
|
|
|
dataLogMaxInletCurrentUnbalance OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Maximum value for the measurement period:
|
|
A string displaying the current unbalance in percent.
|
|
It will have the value NA if the feature is disabled,
|
|
the PX is not a 3-phase unit,or the average of the line currents is zero"
|
|
::= { dataLogInletEntry 15 }
|
|
|
|
dataLogMinInletCurrentUnbalance OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Minimum value for the measurement period:
|
|
A string displaying the current unbalance in percent.
|
|
It will have the value NA if the feature is disabled,
|
|
the PX is not a 3-phase unit,or the average of the line currents is zero"
|
|
::= { dataLogInletEntry 16 }
|
|
|
|
dataLogAvgInletActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Average value for the measurement period:
|
|
The active power for the inlet
|
|
This value is reported in Watts."
|
|
::= { dataLogInletEntry 17 }
|
|
|
|
dataLogMaxInletActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Maximum value for the measurement period:
|
|
The active power for the inlet
|
|
This value is reported in Watts."
|
|
::= { dataLogInletEntry 18 }
|
|
|
|
dataLogMinInletActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Minimum value for the measurement period:
|
|
The active power for the inlet
|
|
This value is reported in Watts."
|
|
::= { dataLogInletEntry 19 }
|
|
|
|
dataLogAvgInletApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Average value for the measurement period:
|
|
The apparent power for the inlet.
|
|
This value is reported in Volt-Amps"
|
|
::= { dataLogInletEntry 20 }
|
|
|
|
dataLogMaxInletApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Maximum value for the measurement period:
|
|
The apparent power for the inlet.
|
|
This value is reported in Volt-Amps"
|
|
::= { dataLogInletEntry 21 }
|
|
|
|
dataLogMinInletApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Minimum value for the measurement period:
|
|
The apparent power for the inlet.
|
|
This value is reported in Volt-Amps"
|
|
::= { dataLogInletEntry 22 }
|
|
|
|
dataLogAvgInletActiveEnergy OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" The Average value for the measurement period:
|
|
The value of the cumulative active energy for this inlet.
|
|
This value is reported in WattHours"
|
|
::= { dataLogInletEntry 23 }
|
|
|
|
dataLogMaxInletActiveEnergy OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Maximum value for the measurement period:
|
|
The value of the cumulative active energy for this inlet.
|
|
This value is reported in WattHours"
|
|
::= { dataLogInletEntry 24 }
|
|
|
|
dataLogMinInletActiveEnergy OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Minimum value for the measurement period:
|
|
The value of the cumulative active energy for this inlet.
|
|
This value is reported in WattHours"
|
|
::= { dataLogInletEntry 25 }
|
|
|
|
|
|
|
|
|
|
-- the dataLogInletPoleTable
|
|
|
|
-- The dataLogInletPoleTable table contains information on the inlet poles.
|
|
|
|
dataLogInletPoleTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DataLogInletPoleEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of line input entries. The number of
|
|
entries is given by the value of dataLoginletTable(dataLogInletIndex).inletPoleCount."
|
|
::= { dataLogInletPole 1 }
|
|
|
|
dataLogInletPoleEntry OBJECT-TYPE
|
|
SYNTAX DataLogInletPoleEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry in the data log containing input line values
|
|
for a particular input line."
|
|
INDEX { dataLogIndex, dataLogInletIndex, dataLogInletPoleIndex }
|
|
::= { dataLogInletPoleTable 1 }
|
|
|
|
DataLogInletPoleEntryStruct ::= SEQUENCE { dataLogInletPoleIndex Integer32,
|
|
dataLogInletPoleCurrent MilliAmps,
|
|
dataLogInletPoleVoltage MilliVolts,
|
|
dataLogAvgInletPoleCurrent MilliAmps,
|
|
dataLogMaxInletPoleCurrent MilliAmps,
|
|
dataLogMinInletPoleCurrent MilliAmps,
|
|
dataLogAvgInletPoleVoltage MilliVolts,
|
|
dataLogMaxInletPoleVoltage MilliVolts,
|
|
dataLogMinInletPoleVoltage MilliVolts,
|
|
dataLogAvgInletPoleActivePower Watts,
|
|
dataLogMaxInletPoleActivePower Watts,
|
|
dataLogMinInletPoleActivePower Watts,
|
|
dataLogAvgInletPoleApparentPower VoltAmps,
|
|
dataLogMaxInletPoleApparentPower VoltAmps,
|
|
dataLogMinInletPoleApparentPower VoltAmps,
|
|
dataLogAvgInletPoleActiveEnergy WattHours,
|
|
dataLogMaxInletPoleActiveEnergy WattHours,
|
|
dataLogMinInletPoleActiveEnergy WattHours}
|
|
|
|
dataLogInletPoleIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each line input. Its value
|
|
ranges between 1 and lineCurrentCount."
|
|
::= { dataLogInletPoleEntry 1 }
|
|
|
|
dataLogInletPoleCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the current reported
|
|
in MilliAmps.
|
|
For Single Phase: Input Line Current
|
|
For 3phase Delta-wired: Current for L1, L2, L3
|
|
For 3phase WYE-wired: Current for L1, L2, L3, N
|
|
This has been deprecated in favor of
|
|
dataLogAvgInletPoleCurrent, dataLogMaxInletPoleCurrent,
|
|
dataLogMinInletPoleCurrent"
|
|
::= { dataLogInletPoleEntry 2 }
|
|
|
|
dataLogInletPoleVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The value of the voltage reported
|
|
in MilliVolts.
|
|
For Single Phase: Input Line Voltage
|
|
For 3phase Delta-wired: Voltages for L1-L2, L2-L3, L3-L1
|
|
For 3phase WYE-wired: Voltages for L1-N, L2-N, L3-N
|
|
This has been deprecated in favor of
|
|
dataLogAvgInletPoleVoltage, dataLogMaxInletPoleVoltage,
|
|
dataLogMinInletPoleVoltage"
|
|
::= { dataLogInletPoleEntry 3 }
|
|
|
|
dataLogAvgInletPoleCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Average value for the measurement period:
|
|
The value of the current reported
|
|
in MilliAmps.
|
|
For Single Phase: Input Line Current
|
|
For 3phase Delta-wired: Current for L1, L2, L3
|
|
For 3phase WYE-wired: Current for L1, L2, L3, N"
|
|
::= { dataLogInletPoleEntry 4 }
|
|
|
|
dataLogMaxInletPoleCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Maximum value for the measurement period:
|
|
The value of the current reported
|
|
in MilliAmps.
|
|
For Single Phase: Input Line Current
|
|
For 3phase Delta-wired: Current for L1, L2, L3
|
|
For 3phase WYE-wired: Current for L1, L2, L3, N"
|
|
::= { dataLogInletPoleEntry 5 }
|
|
|
|
|
|
dataLogMinInletPoleCurrent OBJECT-TYPE
|
|
SYNTAX MilliAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Minimum value for the measurement period:
|
|
The value of the current reported
|
|
in MilliAmps.
|
|
For Single Phase: Input Line Current
|
|
For 3phase Delta-wired: Current for L1, L2, L3
|
|
For 3phase WYE-wired: Current for L1, L2, L3, N"
|
|
::= { dataLogInletPoleEntry 6 }
|
|
|
|
dataLogAvgInletPoleVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Average value for the measurement period:
|
|
The value of the voltage reported
|
|
in MilliVolts.
|
|
For Single Phase: Input Line Voltage
|
|
For 3phase Delta-wired: Voltages for L1-L2, L2-L3, L3-L1
|
|
For 3phase WYE-wired: Voltages for L1-N, L2-N, L3-N"
|
|
::= { dataLogInletPoleEntry 7 }
|
|
|
|
dataLogMaxInletPoleVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Maximum value for the measurement period:
|
|
The value of the voltage reported
|
|
in MilliVolts.
|
|
For Single Phase: Input Line Voltage
|
|
For 3phase Delta-wired: Voltages for L1-L2, L2-L3, L3-L1
|
|
For 3phase WYE-wired: Voltages for L1-N, L2-N, L3-N"
|
|
::= { dataLogInletPoleEntry 8 }
|
|
|
|
dataLogMinInletPoleVoltage OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Minimum value for the measurement period:
|
|
The value of the voltage reported
|
|
in MilliVolts.
|
|
For Single Phase: Input Line Voltage
|
|
For 3phase Delta-wired: Voltages for L1-L2, L2-L3, L3-L1
|
|
For 3phase WYE-wired: Voltages for L1-N, L2-N, L3-N"
|
|
::= { dataLogInletPoleEntry 9 }
|
|
|
|
|
|
dataLogAvgInletPoleActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object has a valid value only for inline meters.
|
|
If inlineMeter = 'No', then the value is invalid;
|
|
In all other cases, it is the the Average value of the active power
|
|
for the measurement period.
|
|
The value is reported in Watts."
|
|
::= { dataLogInletPoleEntry 10 }
|
|
|
|
dataLogMaxInletPoleActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This object has a valid value only for inline meters.
|
|
If inlineMeter = 'No', then the value is invalid;
|
|
In all other cases, it is the the Maximum value of the active power
|
|
for the measurement period.
|
|
The value is reported in Watts."
|
|
::= { dataLogInletPoleEntry 11 }
|
|
|
|
dataLogMinInletPoleActivePower OBJECT-TYPE
|
|
SYNTAX Watts
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This object has a valid value only for inline meters.
|
|
If inlineMeter = 'No', then the value is invalid;
|
|
In all other cases, it is the the Minimum value of the active power
|
|
for the measurement period.
|
|
The value is reported in Watts."
|
|
::= { dataLogInletPoleEntry 12 }
|
|
|
|
dataLogAvgInletPoleApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object has a valid value only for inline meters.
|
|
If inlineMeter = 'No', then the value is invalid;
|
|
In all other cases, it is the the Average value of the apparent power
|
|
for the measurement period.
|
|
The value is reported in Volt-Amps"
|
|
::= { dataLogInletPoleEntry 13 }
|
|
|
|
dataLogMaxInletPoleApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This object has a valid value only for inline meters.
|
|
If inlineMeter = 'No', then the value is invalid;
|
|
In all other cases, it is the the Maximum value of the apparent power
|
|
for the measurement period.
|
|
The value is reported in Volt-Amps"
|
|
::= { dataLogInletPoleEntry 14 }
|
|
|
|
dataLogMinInletPoleApparentPower OBJECT-TYPE
|
|
SYNTAX VoltAmps
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This object has a valid value only for inline meters.
|
|
If inlineMeter = 'No', then the value is invalid;
|
|
In all other cases, it is the the Minimum value of the apparent power
|
|
for the measurement period.
|
|
The value is reported in Volt-Amps"
|
|
::= { dataLogInletPoleEntry 15 }
|
|
|
|
dataLogAvgInletPoleActiveEnergy OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This object has a valid value only for inline meters.
|
|
If inlineMeter = 'No', then the value is invalid;
|
|
In all other cases, it is the the Average value of the active energy
|
|
for the measurement period.
|
|
The value is reported in WattHours"
|
|
::= { dataLogInletPoleEntry 16 }
|
|
|
|
dataLogMaxInletPoleActiveEnergy OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This object has a valid value only for inline meters.
|
|
If inlineMeter = 'No', then the value is invalid;
|
|
In all other cases, it is the the Maximum value of the active energy
|
|
for the measurement period.
|
|
The value is reported in WattHours"
|
|
::= { dataLogInletPoleEntry 17 }
|
|
|
|
dataLogMinInletPoleActiveEnergy OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" This object has a valid value only for inline meters.
|
|
If inlineMeter = 'No', then the value is invalid;
|
|
In all other cases, it is the the Minimum value of the active energy
|
|
for the measurement period.
|
|
The value is reported in WattHours"
|
|
::= { dataLogInletPoleEntry 18 }
|
|
|
|
|
|
|
|
|
|
-- the external sensors Data group
|
|
|
|
-- Implementation for external sensors
|
|
|
|
-- the external sensor table
|
|
|
|
-- The externalSensorTable table contains information on the external sensors.
|
|
|
|
dataLogExternalSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DataLogExternalSensorEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of external sensor entries. The number of
|
|
entries is given by the value of externalSensorCount."
|
|
::= { dataLogExternalSensor 1 }
|
|
|
|
dataLogExternalSensorEntry OBJECT-TYPE
|
|
SYNTAX DataLogExternalSensorEntryStruct
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry in the data log containing external sensor values"
|
|
INDEX { dataLogIndex, dataLogExternalSensorIndex }
|
|
::= { dataLogExternalSensorTable 1 }
|
|
|
|
DataLogExternalSensorEntryStruct ::= SEQUENCE { dataLogExternalSensorIndex Integer32,
|
|
dataLogExternalSensorChanged DisplayString,
|
|
dataLogExternalSensorState StateOfSensorEnumeration,
|
|
dataLogAvgExternalSensorValue Integer32,
|
|
dataLogMaxExternalSensorValue Integer32,
|
|
dataLogMinExternalSensorValue Integer32 }
|
|
|
|
dataLogExternalSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each external sensor. Its value
|
|
ranges between 1 and externalSensorCount."
|
|
::= { dataLogExternalSensorEntry 1 }
|
|
|
|
dataLogExternalSensorChanged OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates whether there has been a change in the sensor type/subtype/channel number for this sensorID.
|
|
This can occur if sensorIDs have been reassigned as a result of
|
|
a GUI operation or a SET operation on reorderexternalSensorTableEntries.
|
|
|
|
Format: SerialNumber=xxxxxxxx; SensorType=dd; SensorSubType=d; ChannelNumber=d
|
|
SensorSubType and ChannelNumber are present only if NewSensorType=onOff
|
|
If there was no change from the previous sample, then
|
|
this string is empty.
|
|
|
|
Examples:
|
|
Sensor changed to Temperature:
|
|
SerialNumber=AEI8160083; SensorType=10;
|
|
Sensor changed to onOff/SmokeDetection:
|
|
SerialNumber=AEI8160083; SensorType=14; SensorSubType= 18; ChannelNumber=1
|
|
Sensor Channel Number changed:
|
|
SerialNumber=AEI8160083; SensorType=14; SensorSubType= 18; ChannelNumber=2
|
|
Sensor SubType changed:
|
|
SerialNumber=AEI8160083; SensorType=14; SensorSubType= 19; ChannelNumber=2
|
|
"
|
|
::= { dataLogExternalSensorEntry 2 }
|
|
|
|
dataLogExternalSensorState OBJECT-TYPE
|
|
SYNTAX StateOfSensorEnumeration
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The sensor state.
|
|
"
|
|
::= { dataLogExternalSensorEntry 3 }
|
|
|
|
dataLogAvgExternalSensorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Average of the sensor values
|
|
Does not apply (gets will return 0)
|
|
to onOff, trip, vibration, waterDetection,
|
|
smokeDetection sensors.
|
|
This value is not valid if dataLogExternalSensorState is unavailable(-1).
|
|
"
|
|
::= { dataLogExternalSensorEntry 4 }
|
|
|
|
dataLogMaxExternalSensorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Maximum of the sensor values
|
|
Does not apply (gets will return 0)
|
|
to onOff, trip, vibration, waterDetection,
|
|
smokeDetection sensors
|
|
This value is not valid if dataLogExternalSensorState is unavailable(-1).
|
|
"
|
|
::= { dataLogExternalSensorEntry 5 }
|
|
|
|
dataLogMinExternalSensorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Minimum of the sensor values.
|
|
Does not apply (gets will return 0)
|
|
to onOff, trip, vibration, waterDetection,
|
|
smokeDetection sensors
|
|
This value is not valid if dataLogExternalSensorState is unavailable(-1).
|
|
"
|
|
::= { dataLogExternalSensorEntry 6 }
|
|
|
|
|
|
|
|
|
|
-- Start the traps
|
|
|
|
rebootStarted NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The reboot process has started"
|
|
::= { traps 1 }
|
|
|
|
rebootCompleted NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The reboot process is complete"
|
|
::= { traps 2 }
|
|
|
|
userLogin NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user logged in"
|
|
::= { traps 3 }
|
|
|
|
userLogout NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user logged out"
|
|
::= { traps 4 }
|
|
|
|
userAuthenticationFailure NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user authentication attempt failed"
|
|
::= { traps 5 }
|
|
|
|
userSessionTimeout NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user timed out from the device"
|
|
::= { traps 8 }
|
|
|
|
userAdded NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
targetUser }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user was added to the system"
|
|
::= { traps 11 }
|
|
|
|
userModified NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
targetUser }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user account was modified"
|
|
::= { traps 12 }
|
|
|
|
userDeleted NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
targetUser }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user was deleted from the system"
|
|
::= { traps 13 }
|
|
|
|
groupAdded NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
groupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group was added to the system"
|
|
::= { traps 14 }
|
|
|
|
groupModified NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
groupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group was modified"
|
|
::= { traps 15 }
|
|
|
|
|
|
groupDeleted NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
groupName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A group was deleted from the system"
|
|
::= { traps 16 }
|
|
|
|
deviceUpdateStarted NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress,
|
|
imageVersion }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The device update has started"
|
|
::= { traps 20 }
|
|
|
|
userBlocked NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A blocked user tried to log in"
|
|
::= { traps 22 }
|
|
|
|
powerControl NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress,
|
|
outletLabel,
|
|
outletOperationalState }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An outlet has been switched"
|
|
::= { traps 23 }
|
|
|
|
userPasswordChanged NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
targetUser,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user password was changed"
|
|
::= { traps 24 }
|
|
|
|
passwordSettingsChanged NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
status }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Strong password settings changed "
|
|
::= { traps 28 }
|
|
|
|
-- Start new event to support RP products
|
|
|
|
firmwareFileDiscarded NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A firmware file discarded "
|
|
::= { traps 36 }
|
|
|
|
firmwareValidationFailed NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A firmware validation failed "
|
|
::= { traps 38 }
|
|
|
|
securityViolation NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Security violation."
|
|
::= { traps 39 }
|
|
|
|
logFileCleared NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The log file has been cleared."
|
|
::= { traps 41 }
|
|
|
|
-- Sensor threshold traps
|
|
thresholdAlarm NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
ipAddress,
|
|
sensorDescr,
|
|
thresholdDescr,
|
|
thresholdSeverity,
|
|
thresholdEventType,
|
|
sensorIdentificationString,
|
|
thresholdValue,
|
|
sensorValue }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configured sensor theshold event. The 'thresholdEventType' variable will indicate whether or not
|
|
the threshold triggered or cleared.
|
|
thresholdValue and sensorValue have valid values only for external temperature and humidity sensors.
|
|
"
|
|
::= { traps 45 }
|
|
|
|
-- Outlet Grouping Connectivity Application traps
|
|
outletGroupingConnectivityLost NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
ipAddress,
|
|
slaveIpAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Master PDU lost contact with the slave PDU in an outlet grouping configuration."
|
|
::= { traps 50 }
|
|
|
|
-- circuit Breaker tripped/recovered traps
|
|
circuitBreakerTripped NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
ipAddress,
|
|
circuitBreakerLabel }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Circuit Breaker Tripped."
|
|
::= { traps 51 }
|
|
|
|
circuitBreakerRecovered NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
ipAddress,
|
|
circuitBreakerLabel }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Circuit Breaker Recovered."
|
|
::= { traps 52 }
|
|
|
|
|
|
bulkConfigurationSaved NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bulk Configuration saved."
|
|
::= { traps 53 }
|
|
|
|
bulkConfigurationCopied NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
ipAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bulk Configuration saved."
|
|
::= { traps 54 }
|
|
|
|
|
|
environmentalSensorsConnectivityLost NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
ipAddress,
|
|
sensorDescr,
|
|
externalSensorNumber,
|
|
externalSensorType,
|
|
externalSensorName,
|
|
externalSensorChannelNumber,
|
|
externalBinarySensorSubtype,
|
|
externalSensorSerialNumber }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"lost connectivity to environmental Sensors"
|
|
::= { traps 55 }
|
|
|
|
|
|
|
|
externalOnOffSensorStateChange NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
objectName,
|
|
objectInstance,
|
|
ipAddress,
|
|
externalSensorNumber,
|
|
externalSensorType,
|
|
externalSensorName,
|
|
externalSensorChannelNumber,
|
|
externalBinarySensorSubtype,
|
|
externalSensorState,
|
|
oldSensorState,
|
|
externalSensorSerialNumber
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External OnOff Sensor State Change."
|
|
::= { traps 56 }
|
|
|
|
|
|
environmentalSensorsConnectivityRestored NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
ipAddress,
|
|
externalSensorNumber,
|
|
externalSensorType,
|
|
externalSensorName,
|
|
externalSensorChannelNumber,
|
|
externalBinarySensorSubtype,
|
|
externalSensorSerialNumber }
|
|
STATUS current
|
|
DESCRIPTION
|
|
" connectivity to environmental Sensor was restored"
|
|
::= { traps 57 }
|
|
|
|
|
|
voltageMeasurementError NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
ipAddress,
|
|
psocNumber
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
" voltage measurement error, a Psoc (Outlet Controller) reported zero voltage and non-zero current.
|
|
Voltage, power and energy measurements may be in error "
|
|
::= { traps 58 }
|
|
|
|
|
|
fipsModeEnabled NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"FIPS Mode Enabled "
|
|
::= { traps 59 }
|
|
|
|
|
|
fipsModeDisabled NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"FIPS Mode Disabled "
|
|
::= { traps 60 }
|
|
|
|
|
|
managingenvironmentalSensor NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
ipAddress,
|
|
sensorDescr,
|
|
externalSensorNumber,
|
|
externalSensorType,
|
|
externalSensorName,
|
|
externalSensorChannelNumber,
|
|
externalBinarySensorSubtype,
|
|
externalSensorSerialNumber }
|
|
STATUS current
|
|
DESCRIPTION
|
|
" begin managing environmental Sensor "
|
|
::= { traps 61 }
|
|
|
|
|
|
|
|
unmanagingenvironmentalSensor NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
ipAddress,
|
|
sensorDescr,
|
|
externalSensorNumber,
|
|
externalSensorType,
|
|
externalSensorName,
|
|
externalSensorChannelNumber,
|
|
externalBinarySensorSubtype,
|
|
externalSensorSerialNumber }
|
|
STATUS current
|
|
DESCRIPTION
|
|
" cease managing environmental Sensor"
|
|
::= { traps 62 }
|
|
|
|
ipmiOverLANEnabled NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"IPMI Over LAN Mode has been Enabled "
|
|
::= { traps 63 }
|
|
|
|
|
|
ipmiOverLANDisabled NOTIFICATION-TYPE
|
|
OBJECTS { objectName,
|
|
objectInstance,
|
|
userName
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"IPMI Over LAN Mode has been Disabled "
|
|
::= { traps 64 }
|
|
|
|
|
|
|
|
END
|