mibs/MIBS/schleifenbauer/SCHLEIFENBAUER-DATABUS-MIB
2023-12-05 12:25:34 +01:00

2152 lines
63 KiB
Plaintext

-------------------------------------------------------------------------------
--
-- SCHLEIFENBAUER-DATABUS-MIB.txt: Schleifenbauer MIB for databus devices
--
-- Copyright (c) 2016, 2020 by Schleifenbauer Holding BV
-- All rights reserved.
--
-------------------------------------------------------------------------------
SCHLEIFENBAUER-DATABUS-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY,
OBJECT-TYPE,
Integer32,
Unsigned32,
NOTIFICATION-TYPE
FROM SNMPv2-SMI
OBJECT-GROUP,
NOTIFICATION-GROUP,
MODULE-COMPLIANCE
FROM SNMPv2-CONF
TEXTUAL-CONVENTION,
DisplayString
FROM SNMPv2-TC
schleifenbauerMgmt
FROM SCHLEIFENBAUER-SMI;
schleifenbauerDatabusMIB MODULE-IDENTITY
LAST-UPDATED
"202004280000Z" -- April 28th, 2020
ORGANIZATION
"Schleifenbauer Engineering"
CONTACT-INFO
"Schleifenbauer Engineering
Alain Schuermans
Chief Technology Officer
Rietwaard 15
5236 WC 's-Hertogenbosch
The Netherlands
t +31 (0)73 52 30256
f +31 (0)73 521 23 83
alain@schleifenbauer.eu
www.schleifenbauer.eu"
DESCRIPTION
"This MIB describes the SNMP functions of network enabled databus
devices.
Copyright (c) 2016, 2020 by Schleifenbauer Holding BV
"
REVISION
"202004280000Z" -- April 28th, 2020
DESCRIPTION
"1. Added performance monitoring registers
2. Added sdbDevStUsbMode register
3. Added sdbDevIdDeviceType register
4. Added sdbDevIdLocateUnit"
REVISION
"201703060000Z" -- March 3rd, 2017
DESCRIPTION
"Renamed Deci prefix of custom TEXTUAL-CONVENTIONs to Centi"
REVISION
"201610210000Z" -- October 21th, 2016
DESCRIPTION
"1. Added sdbDevSsOutletVoltageDropAlert object.
2. Added sdbDevStAutoResetAlerts object.
3. Added sdbDevStExtendedNames object.
4. Added sdbDevSsOutletVoltageDropAlertDetected object."
REVISION
"201606160000Z" -- June 16th, 2016
DESCRIPTION
"1. Fixed incorrect range of sdbDevIdIndex."
REVISION
"201605100000Z" -- May 10th, 2016
DESCRIPTION
"1. Added sdbDevOutMtPowerVoltAmpere object.
2. Added sdbDevOutMtPowerWatt object."
REVISION
"201603240000Z" -- March 24th, 2016
DESCRIPTION
"1. Added sdbMgmtStsRingState object.
2. Added sdbMgmtStsBreachIndex object.
3. Added sdbMgmtStsRingStateChanged notification."
REVISION
"201602190000Z" -- February 19th, 2016
DESCRIPTION
"1. Fixed incorrect description of sdbDevIdIndex.
2. Fixed description of sdbDevSsSensorChangeAlertDetected. Removed
sdbDevSnsType from description."
REVISION
"201510230000Z" -- October 23th, 2015
DESCRIPTION
"The initial revision of this MIB module"
::= { schleifenbauerMgmt 1 }
CentiValue ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-2"
STATUS current
DESCRIPTION
"Data type for reporting generic measurements associated with
environmental sensors. If the underlying hardware sensor indicates
21.1 degrees Celsius, then the SNMP agent will report a value of 2110
CentiValue."
SYNTAX Integer32 (0..327680)
KiloWattHour ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d"
STATUS current
DESCRIPTION
"Data type for reporting measurements associated with energy
accumulation sensors. If the underlying hardware sensor indicates 1
kWh, then the SNMP agent will report a value of 1 kWh."
SYNTAX Integer32 (0..16777215)
-- START MIB --
CentiAmpere ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-2"
STATUS current
DESCRIPTION
"Data type for reporting measurements and thresholds associated with
current sensors. If the underlying hardware sensor indicates 1.1 A,
then the SNMP agent will report a value of 110 CentiAmpere."
SYNTAX Integer32 (0..327680)
CentiCelsius ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-2"
STATUS current
DESCRIPTION
"Data type for reporting sensor readings associated with temperature
sensors. If the underlying hardware sensor indicates 20.1 degrees
Celsius, then the SNMP agent will report a value of 2010 CentiCelsius."
SYNTAX Integer32 (0..9900)
CentiPercent ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-2"
STATUS current
DESCRIPTION
"Data type for reporting calculated percentages. If the calculated
percentage is 98.3%, then the SNMP agent will report a value of 9830
CentiPercent."
SYNTAX Integer32 (0..10000)
CentiVolt ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d-2"
STATUS current
DESCRIPTION
"Data type for reporting measurements and thresholds associated with
voltage sensors. If the underlying hardware sensor indicates 231.1 V,
then the SNMP agent will report a value of 23110 CentiVolt."
SYNTAX Integer32 (0..327680)
MilliSecond ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d"
STATUS current
DESCRIPTION
"Duration in milliseconds"
SYNTAX Integer32
Second ::= TEXTUAL-CONVENTION
DISPLAY-HINT "d"
STATUS current
DESCRIPTION
"Duration in seconds."
SYNTAX Integer32
sdbMIBNotifications OBJECT IDENTIFIER ::= { schleifenbauerDatabusMIB 0 }
sdbMIBObjects OBJECT IDENTIFIER ::= { schleifenbauerDatabusMIB 1 }
sdbMIBConformance OBJECT IDENTIFIER ::= { schleifenbauerDatabusMIB 2 }
sdbMgmt OBJECT IDENTIFIER ::= { sdbMIBObjects 1}
sdbDevice OBJECT IDENTIFIER ::= { sdbMIBObjects 2 }
sdbMgmtStatus OBJECT IDENTIFIER ::= { sdbMgmt 1 }
sdbMgmtControl OBJECT IDENTIFIER ::= { sdbMgmt 2 }
sdbDevIdentification OBJECT IDENTIFIER ::= { sdbDevice 1 }
sdbDevConfiguration OBJECT IDENTIFIER ::= { sdbDevice 2 }
sdbDevSystemStatus OBJECT IDENTIFIER ::= { sdbDevice 3 }
sdbDevReset OBJECT IDENTIFIER ::= { sdbDevice 4 }
sdbDevSettings OBJECT IDENTIFIER ::= { sdbDevice 5 }
sdbDevInput OBJECT IDENTIFIER ::= { sdbDevice 6 }
sdbDevOutlet OBJECT IDENTIFIER ::= { sdbDevice 7 }
sdbDevSensor OBJECT IDENTIFIER ::= { sdbDevice 8 }
sdbDevPerformance OBJECT IDENTIFIER ::= { sdbDevice 9 }
sdbMIBCompliances OBJECT IDENTIFIER ::= { sdbMIBConformance 1 }
sdbMIBGroups OBJECT IDENTIFIER ::= { sdbMIBConformance 2 }
sdbMgmtStsDevices OBJECT-TYPE
SYNTAX Integer32 (1..512)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of devices on the databus."
::= { sdbMgmtStatus 1}
sdbMgmtStsAddressableDevices OBJECT-TYPE
SYNTAX Integer32 (1..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of devices on the databus addressable by snmp."
::= { sdbMgmtStatus 2 }
sdbMgmtStsNewDevices OBJECT-TYPE
SYNTAX Integer32 (1..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of new devices on the databus."
::= { sdbMgmtStatus 3 }
sdbMgmtStsDuplicateDevices OBJECT-TYPE
SYNTAX Integer32 (1..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of duplicate devices on the databus."
::= { sdbMgmtStatus 4 }
sdbMgmtStsRingState OBJECT-TYPE
SYNTAX INTEGER {
open(0),
closed(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"If the device is in a bridge-like mode, this will indicate the actual
state of the databus."
::= { sdbMgmtStatus 5 }
sdbMgmtStsRingBreachIndex OBJECT-TYPE
SYNTAX Integer32 (0..65535)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the breach index if the current state of the data bus is
open. If the data bus is closed this has no meaning."
::= { sdbMgmtStatus 6 }
sdbMgmtCtrlScan OBJECT-TYPE
SYNTAX INTEGER {
idle(0),
scan(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Perform a bus scan.
To verify if scanning is completed the value of this object can be
read. During the bus scan the value remains 1. When the bus scan
completed the value will be 0."
::= { sdbMgmtControl 1 }
sdbMgmtCtrlRenumberAllFromN OBJECT-TYPE
SYNTAX Integer32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Renumber all devices on the databus.
If set to 0 all units will be set to 0. If set to another value, all
units will be numbered in sequence starting from the value set."
::= { sdbMgmtControl 2 }
sdbMgmtCtrlRenumberZeros OBJECT-TYPE
SYNTAX INTEGER {
idle(0),
renumber(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Renumber all devices on the databus having address 0.
Renumbering will be done in sequence. The sequence starts with the
highest address found on the databus."
::= { sdbMgmtControl 3 }
sdbMgmtCtrlDevicesTable OBJECT-TYPE
SYNTAX SEQUENCE OF SdbMgmtCtrlDevicesEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information of devices connected to the databus.
The number of entries is given by the value of sdbMgmtStsDevices."
::= { sdbMgmtControl 4 }
sdbMgmtCtrlDevicesEntry OBJECT-TYPE
SYNTAX SdbMgmtCtrlDevicesEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Information entry containing objects of a particular databus device."
INDEX { sdbMgmtCtrlDevIndex }
::= { sdbMgmtCtrlDevicesTable 1 }
SdbMgmtCtrlDevicesEntry ::=
SEQUENCE {
sdbMgmtCtrlDevIndex Integer32,
sdbMgmtCtrlDevUnitAddress Integer32,
sdbMgmtCtrlDevHardwareAddress DisplayString,
sdbMgmtCtrlDevIsNew Integer32,
sdbMgmtCtrlDevIsDuplicate Integer32
}
sdbMgmtCtrlDevIndex OBJECT-TYPE
SYNTAX Integer32 (1..255)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for each device. Its value ranges between 1 and the
value of sdbMgmtStsDevices with a maximum of 255. The value for each
device will remain constant until the next scan is performed."
::= { sdbMgmtCtrlDevicesEntry 1 }
sdbMgmtCtrlDevUnitAddress OBJECT-TYPE
SYNTAX Integer32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User defined address.
This will be used for addressing the device on the databus."
::= { sdbMgmtCtrlDevicesEntry 2 }
sdbMgmtCtrlDevHardwareAddress OBJECT-TYPE
SYNTAX DisplayString (SIZE(17))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Hardware serial number.
This cannot be changed. It can be used as backup unit address.
format as 3 unsigned ints separated by dashes: int - int - int"
::= { sdbMgmtCtrlDevicesEntry 3 }
sdbMgmtCtrlDevIsNew OBJECT-TYPE
SYNTAX INTEGER {
no(0),
yes(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indication if the device is new on the databus."
::= { sdbMgmtCtrlDevicesEntry 4 }
sdbMgmtCtrlDevIsDuplicate OBJECT-TYPE
SYNTAX
INTEGER {
no(0),
yes(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indication if the device is conflicting with another device on the
databus."
::= { sdbMgmtCtrlDevicesEntry 5 }
sdbDevIdTable OBJECT-TYPE
SYNTAX SEQUENCE OF SdbDevIdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing identification information of devices connected to
the databus.
The number of entries is given by the value of
sdbMgmtStsAddressableDevices."
::= { sdbDevIdentification 1 }
sdbDevIdEntry OBJECT-TYPE
SYNTAX SdbDevIdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Information entry containing information objects of a particular
databus device."
INDEX { sdbDevIdIndex }
::= { sdbDevIdTable 1 }
SdbDevIdEntry ::=
SEQUENCE {
sdbDevIdSPDMVersion Integer32,
sdbDevIdFirmwareVersion Integer32,
sdbDevIdBuildNumber DisplayString,
sdbDevIdSalesOrderNumber DisplayString,
sdbDevIdProductId DisplayString,
sdbDevIdSerialNumber DisplayString,
sdbDevIdHardwareAddress DisplayString,
sdbDevIdMacAddress DisplayString,
sdbDevIdUnitAddress Integer32,
sdbDevIdName DisplayString,
sdbDevIdLocation DisplayString,
sdbDevIdVanityTag DisplayString,
sdbDevIdIndex Integer32,
sdbDevIdDeviceType Integer32,
sdbDevIdLocateUnit Integer32
}
sdbDevIdSPDMVersion OBJECT-TYPE
SYNTAX Integer32 (0..9999)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Data model version."
::= { sdbDevIdEntry 1 }
sdbDevIdFirmwareVersion OBJECT-TYPE
SYNTAX Integer32 (0..9999)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The firmware revision number."
::= { sdbDevIdEntry 2 }
sdbDevIdBuildNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..12))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Date and time the firmware was built."
::= { sdbDevIdEntry 3 }
sdbDevIdSalesOrderNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..16))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SP sales order number."
::= { sdbDevIdEntry 4 }
sdbDevIdProductId OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..16))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SP product id."
::= { sdbDevIdEntry 5 }
sdbDevIdSerialNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..16))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"SP serial number."
::= { sdbDevIdEntry 6 }
sdbDevIdHardwareAddress OBJECT-TYPE
SYNTAX DisplayString (SIZE(17))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Hardware serial number.
This can not be changed. It can be used as backup unit address.
Format as 3 unsigned ints separated by dashes (-)
e.g. 12345-54321-00000"
::= { sdbDevIdEntry 7 }
sdbDevIdMacAddress OBJECT-TYPE
SYNTAX DisplayString (SIZE(17))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The MAC address.
This can not be changed. It represents an 802 MAC address as if it
were transmitted least significant bit first.
Format as six groups of 2 hexadecimal digits separated by colons (:)
e.g. D0:22:12:B0:00:00"
::= { sdbDevIdEntry 8 }
sdbDevIdUnitAddress OBJECT-TYPE
SYNTAX Integer32 (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User defined address.
This will be used for addressing the device on the databus."
::= { sdbDevIdEntry 9 }
sdbDevIdName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..16))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User configurable device name or identifier."
::= { sdbDevIdEntry 10 }
sdbDevIdLocation OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..16))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User configurable device location identifier."
::= { sdbDevIdEntry 11 }
sdbDevIdVanityTag OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..20))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Characters to be displayed as vanity text in display."
::= { sdbDevIdEntry 12 }
sdbDevIdIndex OBJECT-TYPE
SYNTAX Integer32 (1..65535)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for each device. Its value represents the unit address
of the device and is used to address individual devices in the tree.
The value for each device will remain constant until the next scan is
performed."
::= { sdbDevIdEntry 13 }
sdbDevIdDeviceType OBJECT-TYPE
SYNTAX INTEGER {
pdu(0),
dpm(1),
hpdu-G3(2),
dpm27e(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique value for each device group.
Its value represents the device type of the device.
Refer to manual for more information."
::= { sdbDevIdEntry 14 }
sdbDevIdLocateUnit OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The LCD-backlight flashes in a heartbeat rhythm to locate the unit."
::= { sdbDevIdEntry 15 }
sdbDevCfTable OBJECT-TYPE
SYNTAX SEQUENCE OF SdbDevCfEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing configuration information of devices connected to
the databus.
The number of entries is given by the value of
sdbMgmtStsAddressableDevices."
::= { sdbDevConfiguration 1 }
sdbDevCfEntry OBJECT-TYPE
SYNTAX SdbDevCfEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Configuration entry containing configuration objects of a particular
databus device."
INDEX { sdbDevIdIndex }
::= { sdbDevCfTable 1 }
SdbDevCfEntry ::=
SEQUENCE {
sdbDevCfPhases Integer32,
sdbDevCfOutletsTotal Integer32,
sdbDevCfOutletsSwitched Integer32,
sdbDevCfOutletsMetered Integer32,
sdbDevCfSensors Integer32,
sdbDevCfMaximumLoad Integer32
}
sdbDevCfPhases OBJECT-TYPE
SYNTAX Integer32 (0 | 1 | 3)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of phases for input metering."
::= { sdbDevCfEntry 1 }
sdbDevCfOutletsTotal OBJECT-TYPE
SYNTAX Integer32 (0..48)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total number of outlets including hardwired without switch/metered
modules."
::= { sdbDevCfEntry 2 }
sdbDevCfOutletsSwitched OBJECT-TYPE
SYNTAX Integer32 (0..48)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of switched outlets.
If outlet numbering is non-contiguous its the highest outlet number."
::= { sdbDevCfEntry 3 }
sdbDevCfOutletsMetered OBJECT-TYPE
SYNTAX Integer32 (0..48)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of metered outlets.
If outlet numbering is non-contiguous its the highest outlet number."
::= { sdbDevCfEntry 4 }
sdbDevCfSensors OBJECT-TYPE
SYNTAX Integer32 (0..16)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number sensors."
::= { sdbDevCfEntry 5 }
sdbDevCfMaximumLoad OBJECT-TYPE
SYNTAX Integer32 (16 | 32)
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum rated load of device per phase"
::= { sdbDevCfEntry 6 }
sdbDevSsTable OBJECT-TYPE
SYNTAX SEQUENCE OF SdbDevSsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing system status information of devices connected to
the databus.
The number of entries is given by the value of
sdbMgmtStsAddressableDevices."
::= { sdbDevSystemStatus 1 }
sdbDevSsEntry OBJECT-TYPE
SYNTAX SdbDevSsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"System status entry containing system status objects of a particular
databus device."
INDEX { sdbDevIdIndex }
::= { sdbDevSsTable 1 }
SdbDevSsEntry ::=
SEQUENCE {
sdbDevSsDeviceStatusCode Integer32,
sdbDevSsTemperatureAlert Integer32,
sdbDevSsInputCurrentAlert Integer32,
sdbDevSsOutletCurrentAlert Integer32,
sdbDevSsInputVoltageAlert Integer32,
sdbDevSsOutletCurrentDropAlert Integer32,
sdbDevSsInputCurrentDropAlert Integer32,
sdbDevSsSensorChangeAlert Integer32,
sdbDevSsOutletVoltageDropAlert Integer32
}
sdbDevSsDeviceStatusCode OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Returns an internal status or error code.
A value of 0 means OK.
If not 0 it can be any of the following codes. Multiple status codes
can be active at the same time. The value will be the sum of the
active status codes.
1 = alert flagged
2 = settings(s) initialized
4 = power-on reset
8 = external reset
16 = watchdog timer caused reset
32 = brownout detected
64 = controller error
128 = slave module was reset"
::= { sdbDevSsEntry 1 }
sdbDevSsTemperatureAlert OBJECT-TYPE
SYNTAX Integer32 (0..2)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An alert has been raised due to temperature exceeding treshhold.
0 = no alert
1 = internal temperature sensor
2 = external temperature sensor"
::= { sdbDevSsEntry 2 }
sdbDevSsInputCurrentAlert OBJECT-TYPE
SYNTAX Integer32 (0..3)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An alert has been raised due to current exceeding treshhold.
The value indicates the exceeding phase. 0 = no alert."
::= { sdbDevSsEntry 3 }
sdbDevSsOutletCurrentAlert OBJECT-TYPE
SYNTAX Integer32 (0..48)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An alert has been raised due to current exceeding treshhold.
The value indicates the exceeding outlet. 0 = no alert."
::= { sdbDevSsEntry 4 }
sdbDevSsInputVoltageAlert OBJECT-TYPE
SYNTAX Integer32 (0..3)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An alert has been raised due to a voltage dip.
The value indicates the dipped phase. 0 = no alert."
::= { sdbDevSsEntry 5 }
sdbDevSsOutletCurrentDropAlert OBJECT-TYPE
SYNTAX Integer32 (0..48)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An alert has been raised due to the current of a metered outlet
suddenly dropping to near zero, possibly indicating a blown fuse.
The value indicates the dropped outlet. 0 = no alert."
::= { sdbDevSsEntry 6 }
sdbDevSsInputCurrentDropAlert OBJECT-TYPE
SYNTAX Integer32 (0..3)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An alert has been raised due to the current of a metered input
suddenly dropping to near zero, possibly indicating a blown fuse.
The value indicates the dropped phase. 0 = no alert."
::= { sdbDevSsEntry 7 }
sdbDevSsSensorChangeAlert OBJECT-TYPE
SYNTAX Integer32 (0..16)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An alert has been raised due to a change in the number of sensors.
The value indicates the previous amount of sensors."
::= { sdbDevSsEntry 8 }
sdbDevSsOutletVoltageDropAlert OBJECT-TYPE
SYNTAX Integer32 (0..48)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An alert has been raised due to voltage drop on this outlet.
The value indicates the first failed outlet."
::= { sdbDevSsEntry 9 }
sdbDevRsTable OBJECT-TYPE
SYNTAX SEQUENCE OF SdbDevRsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table providing reset capabilities to devices connected to the
databus.
The number of entries is given by the value of
sdbMgmtStsAddressableDevices."
::= { sdbDevReset 1 }
sdbDevRsEntry OBJECT-TYPE
SYNTAX SdbDevRsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Reset entry providing reset objects of a particular databus device."
INDEX { sdbDevIdIndex }
::= { sdbDevRsTable 1 }
SdbDevRsEntry ::=
SEQUENCE {
sdbDevRsReboot Integer32,
sdbDevRsResetAlerts Integer32,
sdbDevRsZeroInputKWhSubtotal Integer32,
sdbDevRsZeroOutletKWhSubtotal Integer32,
sdbDevRsResetPeaksAndDips Integer32
}
sdbDevRsReboot OBJECT-TYPE
SYNTAX
INTEGER {
idle(0),
reboot(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Warm reboot/reset of device controller.
NOTE: this will have NO effect on outlet status!"
::= { sdbDevRsEntry 1 }
sdbDevRsResetAlerts OBJECT-TYPE
SYNTAX
INTEGER {
idle(0),
reset(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reset all alert signals and device status code."
::= { sdbDevRsEntry 2 }
sdbDevRsZeroInputKWhSubtotal OBJECT-TYPE
SYNTAX
INTEGER {
idle(0),
zero(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reset of all input kWh subtotal counters to zero."
::= { sdbDevRsEntry 3 }
sdbDevRsZeroOutletKWhSubtotal OBJECT-TYPE
SYNTAX
INTEGER {
idle(0),
zero(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reset of all outlet kWh subtotal counter to zero."
::= { sdbDevRsEntry 4 }
sdbDevRsResetPeaksAndDips OBJECT-TYPE
SYNTAX
INTEGER {
idle(0),
reset(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reset all peak and dip values to zero."
::= { sdbDevRsEntry 5 }
sdbDevStTable OBJECT-TYPE
SYNTAX SEQUENCE OF SdbDevStEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing setting information of devices connected to the
databus.
The number of entries is given by the value of
sdbMgmtStsAddressableDevices."
::= { sdbDevSettings 1 }
sdbDevStEntry OBJECT-TYPE
SYNTAX SdbDevStEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Setting entry containing settings objects of a particular databus
device."
INDEX { sdbDevIdIndex }
::= { sdbDevStTable 1 }
SdbDevStEntry ::=
SEQUENCE {
sdbDevStAutoResetAlerts Integer32,
sdbDevStExtendedNames Integer32,
sdbDevStPeakDuration MilliSecond,
sdbDevStFixedOutletDelay MilliSecond,
sdbDevStPowerSaverMode Second,
sdbDevStOutletPowerUpMode Integer32,
sdbDevStMaximumTemperature Integer32,
sdbDevStDisplayOrientation Integer32,
sdbDevStLocalAlertReset Integer32,
sdbDevStCurrentDropDetection Integer32,
sdbDevStUsbMode Integer32
}
sdbDevStAutoResetAlerts OBJECT-TYPE
SYNTAX Integer32 (0..65535)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Auto reset alerts configuration.
If set to 0 the auto reset alerts feature is disabled. If set to a
value greater then 0, the auto reset alerts feature is enabled and
alerts will get cleared after the configured amount of seconds since
the last alert condition have passed."
::= { sdbDevStEntry 2 }
sdbDevStExtendedNames OBJECT-TYPE
SYNTAX
INTEGER {
disabled(0),
enabled(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Use original or longer names for inputs, outlets and sensors."
::= { sdbDevStEntry 3 }
sdbDevStPeakDuration OBJECT-TYPE
SYNTAX MilliSecond (0..65535)
UNITS "ms"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Amount of ms a current peak should last before an alert is raised."
::= { sdbDevStEntry 4 }
sdbDevStFixedOutletDelay OBJECT-TYPE
SYNTAX MilliSecond (100..65535)
UNITS "ms"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Minimal delay between two successive relay switches in milliseconds.
Minimal delay is 100 ms. Will always be respected!"
::= { sdbDevStEntry 5 }
sdbDevStPowerSaverMode OBJECT-TYPE
SYNTAX Second (0 | 10 | 60 | 120 | 240)
UNITS "s"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set backlight on time in seconds.
0 keeps display always on.
Note that keeping the backlight on may decrease luminosity over time."
::= { sdbDevStEntry 6 }
sdbDevStOutletPowerUpMode OBJECT-TYPE
SYNTAX
INTEGER {
off(0), -- off
sameState(1), -- same state as at power down
sameStateDelayed(2) -- same state as at power down but delayed by
-- individual delay timer.
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Behaviour of outlets on power-up."
::= { sdbDevStEntry 7 }
sdbDevStMaximumTemperature OBJECT-TYPE
SYNTAX Integer32 (0..99)
UNITS "degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Maximum temperature threshold
An alert will be generated whenever the temperature is above this
value. Zero means disabled."
::= { sdbDevStEntry 8 }
sdbDevStDisplayOrientation OBJECT-TYPE
SYNTAX
INTEGER {
noDisplay(0),
verticalDisplayOnTop(1),
verticalDisplayUpsideDown(2),
horizontalDisplayAtLeft(3),
horizontalDisplayAtRight(4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Display orientation."
::= { sdbDevStEntry 9 }
sdbDevStLocalAlertReset OBJECT-TYPE
SYNTAX
INTEGER {
notAllowed(0),
allowed(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Allow alerts to be reset locally on device by pushing one of the
buttons."
::= { sdbDevStEntry 10 }
sdbDevStCurrentDropDetection OBJECT-TYPE
SYNTAX
INTEGER {
off(0),
inputsOnly(1),
outletsOnly(2),
inputsAndOutlets(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables the current drop detection function."
::= { sdbDevStEntry 11 }
sdbDevStUsbMode OBJECT-TYPE
SYNTAX
INTEGER {
usbDisabled(0),
onlyFirmwareUpdates(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Allow the USB port to be used for specific tasks"
::= { sdbDevStEntry 13 }
sdbDevInTable OBJECT-TYPE
SYNTAX SEQUENCE OF SdbDevInEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information of inputs of devices connected to the
databus."
::= { sdbDevInput 1 }
sdbDevInEntry OBJECT-TYPE
SYNTAX SdbDevInEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Inputs entry containing objects of an input of a particular databus
device.
Note that this table has two indexes. sdbDevIdIndex to identify a
particular device and sdbDevInIndex to identify a particular input
of the device identified by sdbDevIdIndex."
INDEX {
sdbDevIdIndex,
sdbDevInIndex
}
::= { sdbDevInTable 1 }
SdbDevInEntry ::=
SEQUENCE {
sdbDevInIndex Integer32,
sdbDevInKWhTotal KiloWattHour,
sdbDevInKWhSubtotal KiloWattHour,
sdbDevInPowerFactor CentiPercent,
sdbDevInActualCurrent CentiAmpere,
sdbDevInPeakCurrent CentiAmpere,
sdbDevInActualVoltage CentiVolt,
sdbDevInMinVoltage CentiVolt,
sdbDevInPowerVoltAmpere Integer32,
sdbDevInPowerWatt Integer32,
sdbDevInMaxAmps CentiAmpere,
sdbDevInCTRatio Integer32,
sdbDevInName DisplayString,
sdbDevInZeroKWhSubtotal Integer32
}
sdbDevInIndex OBJECT-TYPE
SYNTAX Integer32 (1..48)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for each input. Its value ranges between 1 and the
value of sdbDevCfPhases."
::= { sdbDevInEntry 1 }
sdbDevInKWhTotal OBJECT-TYPE
SYNTAX KiloWattHour
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total kWh value of an input. This value can not be reset."
::= { sdbDevInEntry 2 }
sdbDevInKWhSubtotal OBJECT-TYPE
SYNTAX KiloWattHour
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Subtotal kWh value of an input. This value can be reset."
::= { sdbDevInEntry 3 }
sdbDevInPowerFactor OBJECT-TYPE
SYNTAX CentiPercent
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power factor of input.
The power factor of an AC power system is defined as the ratio of the
real or active power to the apparent power and is a number between 0
and 1. This value is expressed as a percentage between 0% and 100%."
::= { sdbDevInEntry 4 }
sdbDevInActualCurrent OBJECT-TYPE
SYNTAX CentiAmpere
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual apparent, RMS current."
::= { sdbDevInEntry 5 }
sdbDevInPeakCurrent OBJECT-TYPE
SYNTAX CentiAmpere
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak apparent, RMS current.
Highest value since last reset of the alerts."
::= { sdbDevInEntry 6 }
sdbDevInActualVoltage OBJECT-TYPE
SYNTAX CentiVolt
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The actual voltage."
::= { sdbDevInEntry 7 }
sdbDevInMinVoltage OBJECT-TYPE
SYNTAX CentiVolt
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RMS voltage dip.
Lowest value since reset of alerts."
::= { sdbDevInEntry 8 }
sdbDevInPowerVoltAmpere OBJECT-TYPE
SYNTAX Integer32 (0..327680)
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Calculated apparent power."
::= { sdbDevInEntry 9 }
sdbDevInPowerWatt OBJECT-TYPE
SYNTAX Integer32 (0..327680)
UNITS "W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Calculated real power."
::= { sdbDevInEntry 10 }
sdbDevInMaxAmps OBJECT-TYPE
SYNTAX CentiAmpere
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Maximum current per input phase.
Should last at least sdbDevStPeakDuration ms before triggering an
alert."
::= { sdbDevInEntry 11 }
sdbDevInCTRatio OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The multiplier to use for the input CTs."
::= { sdbDevInEntry 12 }
sdbDevInName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..8))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User configurable naming of inputs or phases."
::= { sdbDevInEntry 13 }
sdbDevInZeroKWhSubtotal OBJECT-TYPE
SYNTAX
INTEGER {
idle(0),
zero(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reset input kWh subtotal counter of a single input to zero."
::= { sdbDevInEntry 14 }
sdbDevOutTable OBJECT-TYPE
SYNTAX SEQUENCE OF SdbDevOutEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information of outlets of devices connected to the
databus."
::= { sdbDevOutlet 1 }
sdbDevOutEntry OBJECT-TYPE
SYNTAX SdbDevOutEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Outlets entry containing objects of an outlet of a particular databus
device.
Note that this table has two indexes. sdbDevIdIndex to identify a
particular device and sdbDevOutIndex to identify a particular outlet
of the device identified by sdbDevIdIndex."
INDEX {
sdbDevIdIndex,
sdbDevOutIndex
}
::= { sdbDevOutTable 1 }
SdbDevOutEntry ::=
SEQUENCE {
sdbDevOutIndex Integer32,
sdbDevOutName DisplayString
}
sdbDevOutIndex OBJECT-TYPE
SYNTAX Integer32 (1..48)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for each outlet. Its value ranges between 1 and the
value of sdbDevCfOutletsTotal."
::= { sdbDevOutEntry 1 }
sdbDevOutName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..8))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User configurable naming of individual outlets."
::= { sdbDevOutEntry 2 }
sdbDevOutMtTable OBJECT-TYPE
SYNTAX SEQUENCE OF SdbDevOutMtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information of metered outlets of devices connected
to the databus."
::= { sdbDevOutlet 2 }
sdbDevOutMtEntry OBJECT-TYPE
SYNTAX SdbDevOutMtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Metered outlets entry containing objects of a metered outlet of a
particular databus device.
Note that this table has two indexes. sdbDevIdIndex to identify a
particular device and sdbDevOutMtIndex to identify a particular outlet
of the device identified by sdbDevIdIndex."
INDEX {
sdbDevIdIndex,
sdbDevOutMtIndex
}
::= { sdbDevOutMtTable 1 }
SdbDevOutMtEntry ::=
SEQUENCE {
sdbDevOutMtIndex Integer32,
sdbDevOutMtKWhTotal KiloWattHour,
sdbDevOutMtKWhSubtotal KiloWattHour,
sdbDevOutMtPowerFactor CentiPercent,
sdbDevOutMtActualCurrent CentiAmpere,
sdbDevOutMtPeakCurrent CentiAmpere,
sdbDevOutMtActualVoltage CentiVolt,
sdbDevOutMtMaxAmps CentiAmpere,
sdbDevOutMtCTRatio Integer32,
sdbDevOutMtPowerVoltAmpere Integer32,
sdbDevOutMtPowerWatt Integer32
}
sdbDevOutMtIndex OBJECT-TYPE
SYNTAX Integer32 (1..48)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for each outlet. Its value ranges between 1 and the
value of sdbDevCfOutletsMetered."
::= { sdbDevOutMtEntry 1 }
sdbDevOutMtKWhTotal OBJECT-TYPE
SYNTAX KiloWattHour
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total kWh value of an outlet. This value can not be reset."
::= { sdbDevOutMtEntry 2 }
sdbDevOutMtKWhSubtotal OBJECT-TYPE
SYNTAX KiloWattHour
UNITS "kWh"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Subotal kWh value of an outlet. This value can be reset."
::= { sdbDevOutMtEntry 3 }
sdbDevOutMtPowerFactor OBJECT-TYPE
SYNTAX CentiPercent
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power factor of outlet.
The power factor of an AC power system is defined as the ratio of the
real or active power to the apparent power and is a number between 0
and 1. This number is expressed as a percentage between 0% and 100%."
::= { sdbDevOutMtEntry 4 }
sdbDevOutMtActualCurrent OBJECT-TYPE
SYNTAX CentiAmpere
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual apparent, RMS current."
::= { sdbDevOutMtEntry 5 }
sdbDevOutMtPeakCurrent OBJECT-TYPE
SYNTAX CentiAmpere
UNITS "A"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak apparent, RMS current.
Highest value since last reset of the alerts."
::= { sdbDevOutMtEntry 6 }
sdbDevOutMtActualVoltage OBJECT-TYPE
SYNTAX CentiVolt
UNITS "V"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual voltage on outlet."
::= { sdbDevOutMtEntry 7 }
sdbDevOutMtMaxAmps OBJECT-TYPE
SYNTAX CentiAmpere
UNITS "A"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Maximum current per outlet.
Should last at least sdbDevStPeakDuration ms before triggering an
alert."
::= { sdbDevOutMtEntry 8 }
sdbDevOutMtCTRatio OBJECT-TYPE
SYNTAX Integer32 (0..255)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The multiplier to use for the outlet CTs."
::= { sdbDevOutMtEntry 9 }
sdbDevOutMtPowerVoltAmpere OBJECT-TYPE
SYNTAX Integer32 (0..327680)
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Calculated apparent power."
::= { sdbDevOutMtEntry 10 }
sdbDevOutMtPowerWatt OBJECT-TYPE
SYNTAX Integer32 (0..327680)
UNITS "W"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Calculated real power."
::= { sdbDevOutMtEntry 11 }
sdbDevOutSwTable OBJECT-TYPE
SYNTAX SEQUENCE OF SdbDevOutSwEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information of switched outlets of devices
connected to the databus."
::= { sdbDevOutlet 3 }
sdbDevOutSwEntry OBJECT-TYPE
SYNTAX SdbDevOutSwEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Switched outlets entry containing objects of a switched outlet of a
particular databus device.
Note that this table has two indexes. sdbDevIdIndex to identify a
particular device and sdbDevOutSwIndex to identify a particular outlet
of the device identified by sdbDevIdIndex."
INDEX {
sdbDevIdIndex,
sdbDevOutSwIndex
}
::= { sdbDevOutSwTable 1 }
SdbDevOutSwEntry ::=
SEQUENCE {
sdbDevOutSwIndex Integer32,
sdbDevOutSwCurrentState Integer32,
sdbDevOutSwScheduled Integer32,
sdbDevOutSwUnlock Integer32,
sdbDevOutSwIndividualOutletDelay Second,
sdbDevOutSwReboot Integer32
}
sdbDevOutSwIndex OBJECT-TYPE
SYNTAX Integer32 (1..48)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for each outlet. Its value ranges between 1 and the
value of sdbDevCfOutletsSwitched."
::= { sdbDevOutSwEntry 1 }
sdbDevOutSwCurrentState OBJECT-TYPE
SYNTAX
INTEGER {
off(0),
on(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The actual state of the outlet relay.
Note that Writing is only effective after setting sdbDevOutSwUnlock."
::= { sdbDevOutSwEntry 2 }
sdbDevOutSwScheduled OBJECT-TYPE
SYNTAX
INTEGER {
idle(0),
scheduled(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A one indicates pending activity; the switch delay has not yet
expired."
::= { sdbDevOutSwEntry 3 }
sdbDevOutSwUnlock OBJECT-TYPE
SYNTAX
INTEGER {
locked(0),
unlocked(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Switching and rebooting is unlocked for 10 seconds by writing a 1."
::= { sdbDevOutSwEntry 4 }
sdbDevOutSwIndividualOutletDelay OBJECT-TYPE
SYNTAX Second (0..65535)
UNITS "s"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Delay before an individual outlet switches on at power-up."
::= { sdbDevOutSwEntry 5 }
sdbDevOutSwReboot OBJECT-TYPE
SYNTAX
INTEGER {
idle(0),
reboot(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reboot outlet relay if current state is on and outlet is unlocked;
The outlet will be turned on after 10 seconds."
::= { sdbDevOutSwEntry 6 }
sdbDevMeasuresTable OBJECT-TYPE
SYNTAX SEQUENCE OF SdbDevMeasuresEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information of temperatures of devices connected to
the databus."
::= { sdbDevSensor 1 }
sdbDevMeasuresEntry OBJECT-TYPE
SYNTAX SdbDevMeasuresEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Device measures entry containing temperature information objects of a
particular databus device."
INDEX { sdbDevIdIndex }
::= { sdbDevMeasuresTable 1 }
SdbDevMeasuresEntry ::=
SEQUENCE {
sdbDevMsIntTemperature CentiCelsius,
sdbDevMsExtTemperature CentiCelsius,
sdbDevMsIntTemperaturePeak CentiCelsius,
sdbDevMsExtTemperaturePeak CentiCelsius
}
sdbDevMsIntTemperature OBJECT-TYPE
SYNTAX CentiCelsius
UNITS "degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual internal device temperature in deg C"
::= { sdbDevMeasuresEntry 1 }
sdbDevMsExtTemperature OBJECT-TYPE
SYNTAX CentiCelsius
UNITS "degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual external device temperature sensor in deg C."
::= { sdbDevMeasuresEntry 2 }
sdbDevMsIntTemperaturePeak OBJECT-TYPE
SYNTAX CentiCelsius
UNITS "degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak internal device temperature since last reset of alerts."
::= { sdbDevMeasuresEntry 3 }
sdbDevMsExtTemperaturePeak OBJECT-TYPE
SYNTAX CentiCelsius
UNITS "degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Peak external device temperature since last reset of alerts."
::= { sdbDevMeasuresEntry 4 }
sdbDevSnsTable OBJECT-TYPE
SYNTAX SEQUENCE OF SdbDevSnsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information of sensors of devices connected to the
databus."
::= { sdbDevSensor 2 }
sdbDevSnsEntry OBJECT-TYPE
SYNTAX SdbDevSnsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Sensors entry containing objects of a sensor of a particular databus
device.
Note that this table has two indexes. sdbDevIdIndex to identify a
particular device and sdbDevSnsIndex to identify a particular sensor
of the device identified by sdbDevIdIndex."
INDEX {
sdbDevIdIndex,
sdbDevSnsIndex
}
::= { sdbDevSnsTable 1 }
SdbDevSnsEntry ::=
SEQUENCE {
sdbDevSnsIndex Integer32,
sdbDevSnsType DisplayString,
sdbDevSnsValue CentiValue,
sdbDevSnsName DisplayString
}
sdbDevSnsIndex OBJECT-TYPE
SYNTAX Integer32 (1..16)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for each sensor. Its value ranges between 1 and the
value of sdbDevCfSensors."
::= { sdbDevSnsEntry 1 }
sdbDevSnsType OBJECT-TYPE
SYNTAX DisplayString (SIZE(1))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Type of connected sensor.
T = Temperature (C)
H = Humidity (%)
I = dry switch contact"
::= { sdbDevSnsEntry 2 }
sdbDevSnsValue OBJECT-TYPE
SYNTAX CentiValue (0..327680)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Value of connected sensor"
::= { sdbDevSnsEntry 3 }
sdbDevSnsName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..6))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User definable name for sensors."
::= { sdbDevSnsEntry 4 }
-- ---------------------------------------------------------------------------------------------
sdbDevPerformanceTable OBJECT-TYPE
SYNTAX SEQUENCE OF SdbDevPerformanceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing information of sensors of devices connected to the
databus."
::= { sdbDevPerformance 1 }
sdbDevPerformanceEntry OBJECT-TYPE
SYNTAX SdbDevPerformanceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Performance counters of a particular databus device.
Note that this table has two indexes. sdbDevIdIndex to identify a
particular device and sdbDevPerformanceIndex to identify a particular counter
of the device identified by sdbDevIdIndex."
INDEX {
sdbDevIdIndex,
sdbDevPerformanceIndex
}
::= { sdbDevPerformanceTable 1 }
SdbDevPerformanceEntry ::=
SEQUENCE {
sdbDevPerformanceIndex Integer32,
sdbDevPerformanceValue Integer32,
sdbDevPerformanceMax Integer32,
sdbDevPerformanceLimit Integer32,
sdbDevPerformanceName DisplayString
}
sdbDevPerformanceIndex OBJECT-TYPE
SYNTAX Integer32 (1..16)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A unique value for each counter. Its value ranges between 1 and 16."
::= { sdbDevPerformanceEntry 1 }
sdbDevPerformanceValue OBJECT-TYPE
SYNTAX Integer32 (0..16777215)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Value of counter"
::= { sdbDevPerformanceEntry 2 }
sdbDevPerformanceMax OBJECT-TYPE
SYNTAX Integer32 (0..16777215)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max of counter"
::= { sdbDevPerformanceEntry 3 }
sdbDevPerformanceLimit OBJECT-TYPE
SYNTAX Integer32 (0..16777215)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Limit of counter"
::= { sdbDevPerformanceEntry 4 }
sdbDevPerformanceName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..12))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User definable name for counter."
::= { sdbDevPerformanceEntry 5 }
-- ---------------------------------------------------------------------------------------------
sdbDevPerformanceResetTable OBJECT-TYPE
SYNTAX SEQUENCE OF SdbDevPerformanceResetEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A table containing the last reset reason of the device"
::= { sdbDevPerformance 2 }
sdbDevPerformanceResetEntry OBJECT-TYPE
SYNTAX SdbDevPerformanceResetEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Setting entry containing settings objects of a particular databus
device."
INDEX { sdbDevIdIndex }
::= { sdbDevPerformanceResetTable 1 }
SdbDevPerformanceResetEntry ::=
SEQUENCE {
sdbDevPerformanceResetReason DisplayString,
sdbDevResetUptime Unsigned32
}
sdbDevPerformanceResetReason OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..64))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Last reset reason."
::= { sdbDevPerformanceResetEntry 1 }
sdbDevResetUptime OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Uptime before last reset"
::= { sdbDevPerformanceResetEntry 2 }
-- ---------------------------------------------------------------------------------------------
sdbDevSsDeviceStatusCodeChanged NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Device status code changed.
OBJECTS {
sdbDevSsDeviceStatusCode
}"
::= { sdbMIBNotifications 1 }
sdbDevSsTemperatureAlertDetected NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Temperature alert detected.
Internal temperature alert:
OBJECTS {
sdbDevSsTemperatureAlert,
sdbDevMsIntTemperature,
sdbDevMsIntTemperaturePeak
}
External analog temperature alert:
OBJECTS {
sdbDevSsTemperatureAlert,
sdbDevMsExtTemperature,
sdbDevMsExtTemperaturePeak
}
External digital temperature alert:
OBJECTS {
sdbDevSsTemperatureAlert,
sdbDevSnsValue
}"
::= { sdbMIBNotifications 2 }
sdbDevSsInputCurrentAlertDetected NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Input current alert detected.
OBJECTS {
sdbDevSsInputCurrentAlert,
sdbDevInActualCurrent
}"
::= { sdbMIBNotifications 3 }
sdbDevSsOutletCurrentAlertDetected NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Outlet current alert detected.
OBJECTS {
sdbDevSsOutletCurrentAlert,
sdbDevOutMtActualCurrent
}"
::= { sdbMIBNotifications 4 }
sdbDevSsInputVoltageAlertDetected NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Input voltage alert detected.
OBJECTS {
sdbDevSsInputVoltageAlert,
sdbDevInActualVoltage
}"
::= { sdbMIBNotifications 5 }
sdbDevSsOutletCurrentDropAlertDetected NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Outlet current drop alert detected.
OBJECTS {
sdbDevSsOutletCurrentDropAlert,
sdbDevOutMtActualCurrent
}"
::= { sdbMIBNotifications 6 }
sdbDevSsInputCurrentDropAlertDetected NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Input current drop alert detected.
OBJECTS {
sdbDevSsInputCurrentDropAlert,
sdbDevInActualCurrent
}"
::= { sdbMIBNotifications 7 }
sdbDevSsSensorChangeAlertDetected NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Sensor channel change alert detected.
OBJECTS {
sdbDevSsSensorChangeAlert
}"
::= { sdbMIBNotifications 8 }
sdbMgmtStsRingStateChanged NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Ring state changed.
Ring state changded to open:
OBJECTS {
sdbMgmtStsRingState,
sdbMgmtStsRingBreachIndex
}
Ring state changded to closed:
OBJECTS {
sdbMgmtStsRingState
}"
::= { sdbMIBNotifications 9 }
sdbDevSsOutletVoltageDropAlertDetected NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Outlet voltage drop alert detected.
OBJECTS {
sdbDevSsOutletVoltageDropAlert,
sdbDevOutMtActualVoltage
}"
::= { sdbMIBNotifications 10 }
sdbMIBCompliance MODULE-COMPLIANCE
STATUS current
DESCRIPTION
"The requirements for conformance to the SCHLEIFENBAUER-DATABUS-MIB."
MODULE SCHLEIFENBAUER-DATABUS-MIB
GROUP sdbMIBNotificationGroup
DESCRIPTION
"The notification group."
GROUP sdbMIBDevSensorGroup
DESCRIPTION
"The sensors group."
GROUP sdbMIBDevOutGroup
DESCRIPTION
"The outlet group."
GROUP sdbMIBDevOutMtGroup
DESCRIPTION
"The outletMetering group."
GROUP sdbMIBDevOutSwGroup
DESCRIPTION
"The outletSwitched group."
GROUP sdbMIBDevInGroup
DESCRIPTION
"The inputMeasures group."
GROUP sdbMIBDevStGroup
DESCRIPTION
"The settings group."
GROUP sdbMIBDevSsGroup
DESCRIPTION
"The systemStatus group."
GROUP sdbMIBDevCfGroup
DESCRIPTION
"The configuration group."
GROUP sdbMIBDevIdGroup
DESCRIPTION
"The identification group."
GROUP sdbMIBDevRsGroup
DESCRIPTION
"resettable attributes in device"
GROUP sdbMIBMgmtStatusGroup
DESCRIPTION
"The databus management status group."
GROUP sdbMIBMgmtControlGroup
DESCRIPTION
"The databus management control group."
GROUP sdbMIBDevPerformanceGroup
DESCRIPTION
"The databus management control group."
::= { sdbMIBCompliances 1 }
sdbMIBNotificationGroup NOTIFICATION-GROUP
NOTIFICATIONS {
sdbDevSsDeviceStatusCodeChanged,
sdbDevSsTemperatureAlertDetected,
sdbDevSsInputCurrentAlertDetected,
sdbDevSsOutletCurrentAlertDetected,
sdbDevSsInputVoltageAlertDetected,
sdbDevSsOutletCurrentDropAlertDetected,
sdbDevSsInputCurrentDropAlertDetected,
sdbDevSsSensorChangeAlertDetected,
sdbMgmtStsRingStateChanged,
sdbDevSsOutletVoltageDropAlertDetected
}
STATUS current
DESCRIPTION
"A collection of notifications."
::= { sdbMIBGroups 1 }
sdbMIBDevIdGroup OBJECT-GROUP
OBJECTS {
sdbDevIdSPDMVersion,
sdbDevIdFirmwareVersion,
sdbDevIdSalesOrderNumber,
sdbDevIdProductId,
sdbDevIdSerialNumber,
sdbDevIdHardwareAddress,
sdbDevIdUnitAddress,
sdbDevIdName,
sdbDevIdLocation,
sdbDevIdVanityTag,
sdbDevIdMacAddress,
sdbDevIdBuildNumber,
sdbDevIdDeviceType,
sdbDevIdLocateUnit
}
STATUS current
DESCRIPTION
"A collection of objects providing identification information about the
device."
::= { sdbMIBGroups 3 }
sdbMIBDevCfGroup OBJECT-GROUP
OBJECTS {
sdbDevCfPhases,
sdbDevCfOutletsTotal,
sdbDevCfOutletsSwitched,
sdbDevCfOutletsMetered,
sdbDevCfMaximumLoad,
sdbDevCfSensors
}
STATUS current
DESCRIPTION
"A collection of objects providing configuration information about the
device."
::= { sdbMIBGroups 4 }
sdbMIBDevSsGroup OBJECT-GROUP
OBJECTS {
sdbDevSsDeviceStatusCode,
sdbDevSsTemperatureAlert,
sdbDevSsInputCurrentAlert,
sdbDevSsOutletCurrentAlert,
sdbDevSsInputVoltageAlert,
sdbDevSsOutletCurrentDropAlert,
sdbDevSsInputCurrentDropAlert,
sdbDevSsSensorChangeAlert,
sdbDevSsOutletVoltageDropAlert
}
STATUS current
DESCRIPTION
"A collection of objects providing status information about the
device."
::= { sdbMIBGroups 5 }
sdbMIBDevRsGroup OBJECT-GROUP
OBJECTS {
sdbDevRsResetAlerts,
sdbDevRsResetPeaksAndDips,
sdbDevRsReboot,
sdbDevRsZeroInputKWhSubtotal,
sdbDevRsZeroOutletKWhSubtotal
}
STATUS current
DESCRIPTION
"Groups resettable attributes op the device."
::= { sdbMIBGroups 6 }
sdbMIBDevStGroup OBJECT-GROUP
OBJECTS {
sdbDevStAutoResetAlerts,
sdbDevStExtendedNames,
sdbDevStPeakDuration,
sdbDevStLocalAlertReset,
sdbDevStFixedOutletDelay,
sdbDevStPowerSaverMode,
sdbDevStOutletPowerUpMode,
sdbDevStMaximumTemperature,
sdbDevStDisplayOrientation,
sdbDevStCurrentDropDetection,
sdbDevStUsbMode
}
STATUS current
DESCRIPTION
"A collection of objects providing the actual settings about the
device."
::= { sdbMIBGroups 7 }
sdbMIBDevInGroup OBJECT-GROUP
OBJECTS {
sdbDevInKWhTotal,
sdbDevInKWhSubtotal,
sdbDevInPowerFactor,
sdbDevInActualCurrent,
sdbDevInPeakCurrent,
sdbDevInActualVoltage,
sdbDevInMinVoltage,
sdbDevInPowerVoltAmpere,
sdbDevInPowerWatt,
sdbDevInMaxAmps,
sdbDevInCTRatio,
sdbDevInName,
sdbDevInZeroKWhSubtotal
}
STATUS current
DESCRIPTION
"A collection of objects providing the actual input measurements of the
device."
::= { sdbMIBGroups 8 }
sdbMIBDevOutGroup OBJECT-GROUP
OBJECTS {
sdbDevOutName
}
STATUS current
DESCRIPTION
"A collection of objects providing the actual outlet measurements of
the device."
::= { sdbMIBGroups 9 }
sdbMIBDevOutMtGroup OBJECT-GROUP
OBJECTS {
sdbDevOutMtKWhTotal,
sdbDevOutMtKWhSubtotal,
sdbDevOutMtPowerFactor,
sdbDevOutMtActualCurrent,
sdbDevOutMtPeakCurrent,
sdbDevOutMtActualVoltage,
sdbDevOutMtMaxAmps,
sdbDevOutMtCTRatio,
sdbDevOutMtPowerVoltAmpere,
sdbDevOutMtPowerWatt
}
STATUS current
DESCRIPTION
"A collection of objects providing the actual outlet measurements of
the device."
::= { sdbMIBGroups 10 }
sdbMIBDevOutSwGroup OBJECT-GROUP
OBJECTS {
sdbDevOutSwCurrentState,
sdbDevOutSwScheduled,
sdbDevOutSwUnlock,
sdbDevOutSwIndividualOutletDelay,
sdbDevOutSwReboot
}
STATUS current
DESCRIPTION
"A collection of objects providing the actual outlet measurements of
the device."
::= { sdbMIBGroups 11 }
sdbMIBDevSensorGroup OBJECT-GROUP
OBJECTS {
sdbDevSnsType,
sdbDevSnsValue,
sdbDevSnsName,
sdbDevMsIntTemperature,
sdbDevMsExtTemperature,
sdbDevMsIntTemperaturePeak,
sdbDevMsExtTemperaturePeak
}
STATUS current
DESCRIPTION
"A collection of objects providing the actual environmental
measurements of the device."
::= { sdbMIBGroups 12 }
sdbMIBMgmtStatusGroup OBJECT-GROUP
OBJECTS {
sdbMgmtStsDevices,
sdbMgmtStsAddressableDevices,
sdbMgmtStsNewDevices,
sdbMgmtStsDuplicateDevices,
sdbMgmtStsRingState,
sdbMgmtStsRingBreachIndex
}
STATUS current
DESCRIPTION
"A collection of objects providing management status information about
the databus."
::= { sdbMIBGroups 13 }
sdbMIBMgmtControlGroup OBJECT-GROUP
OBJECTS {
sdbMgmtCtrlScan,
sdbMgmtCtrlRenumberAllFromN,
sdbMgmtCtrlRenumberZeros,
sdbMgmtCtrlDevUnitAddress,
sdbMgmtCtrlDevHardwareAddress,
sdbMgmtCtrlDevIsNew,
sdbMgmtCtrlDevIsDuplicate
}
STATUS current
DESCRIPTION
"A collection of objects providing management control information about
the databus."
::= { sdbMIBGroups 14 }
sdbMIBDevPerformanceGroup OBJECT-GROUP
OBJECTS {
sdbDevPerformanceValue,
sdbDevPerformanceMax,
sdbDevPerformanceLimit,
sdbDevPerformanceName,
sdbDevPerformanceResetReason,
sdbDevResetUptime
}
STATUS current
DESCRIPTION
"A collection of objects providing performance information about the MCU"
::= { sdbMIBGroups 15 }
END