-- Synso UPS Software Management Information Base
|
|
-- SYNSO-UPSMIB
|
|
-- {iso org(3) internet(1) private(4) enterprises(1) synso(9557)}
|
|
|
|
SYNSO-UPSMIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
enterprises, IpAddress
|
|
FROM RFC1155-SMI
|
|
DisplayString
|
|
FROM RFC1213-MIB;
|
|
|
|
|
|
synso OBJECT IDENTIFIER ::= {enterprises 9557}
|
|
synsoUpsSoftware OBJECT IDENTIFIER ::= {synso 1}
|
|
|
|
--
|
|
-- The Basic Setting Group
|
|
--
|
|
|
|
syupsBasicSetting OBJECT IDENTIFIER ::= {synsoUpsSoftware 1}
|
|
|
|
syupsPlatForm OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The platform which the UPS software is running on."
|
|
::= {syupsBasicSetting 1}
|
|
|
|
syupsFeatureTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SyupsFeatureEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A table containing the supported features."
|
|
::= {syupsBasicSetting 2}
|
|
|
|
syupsFeatureEntry OBJECT-TYPE
|
|
SYNTAX SyupsFeatureEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry representing the support information for a feature."
|
|
INDEX {syupsFeature}
|
|
::= {syupsFeatureTable 1}
|
|
|
|
SyupsFeatureEntry ::= SEQUENCE {
|
|
syupsFeature INTEGER,
|
|
syupsSupportInfo DisplayString
|
|
}
|
|
|
|
syupsFeature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The string representing a feature."
|
|
::= {syupsFeatureEntry 1}
|
|
|
|
syupsSupportInfo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The string containing the support information for a feature."
|
|
::= {syupsFeatureEntry 2}
|
|
|
|
syupsSystemStartTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time that the UPS software starts. It is the
|
|
number of seconds elapsed since 00:00:00,
|
|
January 1, 1970."
|
|
::= {syupsBasicSetting 3}
|
|
|
|
syupsSignalType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
basicSignal(0),
|
|
smartSignal(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The signaling method between the UPS and software.
|
|
|
|
When the basicSignal used, the UPS changes the voltage
|
|
level of some specific pins to notify the software of what
|
|
critical event occurs. Usually, the UPS will inform
|
|
software when a power failure or a low battery condition
|
|
occurs. On the other hand, the software can change the
|
|
voltage signal of a specific pin to ask the UPS to shut
|
|
down (turn off).
|
|
|
|
When the smartSignal used, the UPS asks like a standard
|
|
communication device (such as mouse or modem). That means
|
|
the UPS and software communicate with each other using a
|
|
pre-defined protocol. The protocol should include at
|
|
least the following commands:
|
|
- query the power status of the UPS
|
|
- query the power data of the UPS
|
|
- command the UPS to shut down
|
|
"
|
|
::= {syupsBasicSetting 4}
|
|
|
|
syupsBasicSignalDefinition OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The signal definitions for the basic signaling UPS. The
|
|
value can be the following bit combinations:
|
|
SG_POWER_FAILURE_ENABLE 0x01
|
|
SG_BATTERY_LOW_ENABLE 0x02
|
|
SG_SHUTDOWN_ENABLE 0x04
|
|
|
|
SG_POWER_FAILURE_VOLTHIGH 0x10
|
|
SG_BATTERY_LOW_VOLTHIGH 0x20
|
|
SG_SHUTDOWN_VOLTHIGH 0x40
|
|
|
|
SG_POWER_FAILURE_ENABLE, SG_BATTERY_LOW_ENABLE, and
|
|
SG_SHUTDOWN_ENABLE indicate whether the signals for
|
|
a power failure , a low battery condition, and the UPS
|
|
shutdown are enabled. SG_POWER_FAILURE_VOLTHIGH,
|
|
SG_BATTERY_LOW_VOLTHIGH, and SG_SHUTDOWN_VOLTHIGH indicate
|
|
whether the voltage level for these signals are high or low."
|
|
::= {syupsBasicSetting 5}
|
|
|
|
syupsUpsComPort OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The serial port which the UPS software use to communicate
|
|
with the UPS. The format varies from platform to platform.
|
|
For DOS program, the format is 'portNo, portAddress, portIRQ'
|
|
(e.g. '1, 0x2f8, 3' for COM2). For Windows program, it
|
|
is 'portNo'. For NetWare program, it is
|
|
'portType, boardNo, portNo'. For UNIX, it is 'device name'."
|
|
::= {syupsBasicSetting 6}
|
|
|
|
syupsModemComPort OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The serial port which the UPS software use to dial out
|
|
when some particular events occur. The format varies from
|
|
platform to platform. For DOS program, the format is
|
|
'portNo, portAddress, portIRQ' (e.g. '1, 0x2f8, 3' for COM2).
|
|
For Windows program, it is 'portNo'. For NetWare program,
|
|
it is 'portType, boardNo, portNo'. For UNIX, it is
|
|
'device name'."
|
|
::= {syupsBasicSetting 7}
|
|
|
|
|
|
--
|
|
-- The Ups Extension Group
|
|
--
|
|
|
|
syupsUpsExtension OBJECT IDENTIFIER ::= {synsoUpsSoftware 2}
|
|
|
|
|
|
syupsUpsAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"It is used internally. Each bit indicates a critical event,
|
|
such as input bad, on battery, communications lost, ...,etc."
|
|
::= {syupsUpsExtension 1}
|
|
|
|
syupsSerialNo OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The serial number of the UPS connected to the UPS software."
|
|
::= {syupsUpsExtension 2}
|
|
|
|
syupsConfigBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The nominal battery voltage."
|
|
::= {syupsUpsExtension 3}
|
|
|
|
syupsBatteryReplaceDate OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The last battery replacement date. It represents the
|
|
number of days elapsed since January 1, 1901."
|
|
::= {syupsUpsExtension 4}
|
|
|
|
syupsNoOutlet OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The total number of controllable outlets."
|
|
::= {syupsUpsExtension 5}
|
|
|
|
syupsOutletParamter OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object is not used any more."
|
|
::= {syupsUpsExtension 6}
|
|
|
|
syupsShutdownDepend OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..255))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string containing those who should perform their shutdown
|
|
procedure before the UPS turns off. The agent will inform each
|
|
one in the list to begin their shutdown procedure before it turns
|
|
off the power of the UPS."
|
|
::= {syupsUpsExtension 7}
|
|
|
|
syupsEnableAutoSave OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting it to 1, the agent will try to save all files opened by
|
|
applications before shutting down the operation system. Setting it
|
|
to 0 will disable the auto save feature."
|
|
::= {syupsUpsExtension 8}
|
|
|
|
syupsShutdownOsDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The delay time before shutting down the operation system.
|
|
When it is necessary to shut down the operation system, the agent
|
|
will run the specified command file and try to save all files
|
|
opened by applications before shutting down the OS. This delay
|
|
time is used to do such things."
|
|
::= {syupsUpsExtension 9}
|
|
|
|
syupsShutdownUpsDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The delay time before shutting down the UPS. Before shutting down
|
|
the operation system, the agent will send a command to tell the UPS
|
|
to shut down. This delay time is used to allow the agent to shut down
|
|
the operation system safely."
|
|
::= {syupsUpsExtension 10}
|
|
|
|
syupsSaveConfig OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Used to inform the agnet to save the configurations. Its value indicates
|
|
which group to be saved. For example, a 1 indicates group 1 (syupsBasicSetting)
|
|
to be saved, a 6 1 indicates group 6 (syupsCoworker) to be saved. You have to
|
|
use it to save configurations after changing settings, or the settings may be
|
|
lost."
|
|
::= {syupsUpsExtension 11}
|
|
|
|
syupsNoOutlets OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of controllable outlets."
|
|
::= {syupsUpsExtension 12}
|
|
|
|
|
|
syupsOutletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF syupsOutletEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of outlet table entries. The number of entries
|
|
is given by the value of syupsNoOutlets."
|
|
::= {syupsUpsExtension 13}
|
|
|
|
syupsOutletEntry OBJECT-TYPE
|
|
SYNTAX SyupsOutletEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular controllable outlet."
|
|
INDEX { syupsOutletIndex }
|
|
::= {syupsOutletTable 1}
|
|
|
|
syupsOutletEntry ::= SEQUENCE {
|
|
syupsOutletIndex INTEGER,
|
|
syupsOutletDescription DisplayString (SIZE (0..15)),
|
|
syupsOutletShutdownDelay INTEGER,
|
|
syupsOutletShutdownDepend DisplayString (SIZE (0..63))
|
|
}
|
|
|
|
syupsOutletIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The outlet identifier."
|
|
::= {syupsOutletEntry 1}
|
|
|
|
syupsOutletDescription OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The outlet description."
|
|
::= {syupsOutletEntry 2}
|
|
|
|
syupsOutletShutdownDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The delay time (in seconds) before turning off the outlet.
|
|
Before turning off the outlet, the agent will send a shutdown
|
|
command to anyone specified in the syupsOutletShutdownDepend,
|
|
telling them to start their shutdown procedure. This delay
|
|
time is used to allow those cmputers to be shut down safely."
|
|
::= {syupsOutletEntry 3}
|
|
|
|
syupsOutletShutdownDepend OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string containing those who should perform their shutdown
|
|
procedure before the outlet turns off. The agent will inform each
|
|
one in the list to begin their shutdown procedure before it turns
|
|
off the power of the outlet."
|
|
::= {syupsOutletEntry 4}
|
|
|
|
syupsOutletOperator OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The operator is used to control the outlets. There are two commands:
|
|
1. 'SWITCH: OutletNo, OnOff'.
|
|
The OutletNo specify the outlet.
|
|
The OnOff can be 0 (off) or 1 (on).
|
|
For example, 'SWITCH: 2, 1' means turning on (1) the outlet #2.
|
|
'SWITCH: 4, 0' means turning off (0) the outlet #4.
|
|
2. 'SET: OutletNo, Desc, DelayTime, Depend'.
|
|
The OutletNo specify the outlet.
|
|
The Desc specifies the outlet description.
|
|
The DelayTime specifies the shutdown delay time for the outlet.
|
|
The Depend specifies the shutdown dependent list for the outlet.
|
|
For example, 'SET: 3, My Printer, 20, 192.168.1.9' means setting
|
|
the description of outlet #3 to 'My Printer', the shutdown delay
|
|
time to 20 seconds and the Shutdown Dependent to '192.168.1.9'."
|
|
::= {syupsUpsExtension 14}
|
|
|
|
--
|
|
-- The Event Action Group
|
|
--
|
|
|
|
syupsEventAction OBJECT IDENTIFIER ::= {synsoUpsSoftware 3}
|
|
|
|
syupsNoEventActionEntries OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of event-action items. This variable indicates
|
|
the number of rows in the event-action table."
|
|
::= {syupsEventAction 1}
|
|
|
|
syupsEventActionTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SyupsEventActionEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of event action entries. The number of entries
|
|
is given by the value of syupsNoEventActionEntries."
|
|
::= {syupsEventAction 2}
|
|
|
|
syupsEventActionEntry OBJECT-TYPE
|
|
SYNTAX SyupsEventActionEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular event action."
|
|
INDEX {syupsEventId}
|
|
::= {syupsEventActionTable 1}
|
|
|
|
SyupsEventActionEntry ::= SEQUENCE {
|
|
syupsEventId INTEGER,
|
|
syupsLogEnable INTEGER,
|
|
syupsNotifyEnable INTEGER,
|
|
syupsNotifyDelay INTEGER,
|
|
syupsNotifyMessage DisplayString (SIZE(0..63)),
|
|
syupsNotifyPeriod INTEGER,
|
|
syupsNotifyUsers DisplayString (SIZE(0..255)),
|
|
syupsEmailEnable INTEGER,
|
|
syupsEmailDelay INTEGER,
|
|
syupsEmailMessage DisplayString (SIZE(0..63)),
|
|
syupsEmailUsers DisplayString (SIZE(0..255)),
|
|
syupsPageEnable INTEGER,
|
|
syupsPageDelay INTEGER,
|
|
syupsPageMessage DisplayString (SIZE(0..63)),
|
|
syupsPageUsers DisplayString (SIZE(0..255)),
|
|
syupsCommandEnable INTEGER,
|
|
syupsCommandDelay INTEGER,
|
|
syupsCommandFile DisplayString (SIZE(0..255)),
|
|
syupsShutdownEnable INTEGER,
|
|
syupsShutdownDelay INTEGER
|
|
}
|
|
|
|
syupsEventId OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The event ID."
|
|
::= {syupsEventActionEntry 1}
|
|
|
|
syupsLogEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Whether to log the event in the log file when it occurs.
|
|
A 1 indicates enable, a 0 indicates disable."
|
|
::= {syupsEventActionEntry 2}
|
|
|
|
syupsNotifyEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Whether to notify users when the event occurs.
|
|
A 1 indicates enable, a 0 indicates disable."
|
|
::= {syupsEventActionEntry 3}
|
|
|
|
syupsNotifyDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"How long the event must last before notifying users."
|
|
::= {syupsEventActionEntry 4}
|
|
|
|
syupsNotifyMessage OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The message which will be sent when the event occurs."
|
|
::= {syupsEventActionEntry 5}
|
|
|
|
syupsNotifyPeriod OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"How often (in seconds) to send the message. The -1 means once."
|
|
::= {syupsEventActionEntry 6}
|
|
|
|
syupsNotifyUsers OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..255))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Who will receive the message when the event occurs."
|
|
::= {syupsEventActionEntry 7}
|
|
|
|
syupsEmailEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Whether to email users when the event occurs.
|
|
A 1 indicates enable, a 0 indicates disable."
|
|
::= {syupsEventActionEntry 8}
|
|
|
|
syupsEmailDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"How long the event must last before emailing users."
|
|
::= {syupsEventActionEntry 9}
|
|
|
|
syupsEmailMessage OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The additional message which will be sent when the event occurs."
|
|
::= {syupsEventActionEntry 10}
|
|
|
|
syupsEmailUsers OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..255))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Who will receive the mail when the event occurs."
|
|
::= {syupsEventActionEntry 11}
|
|
|
|
syupsPageEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Whether to page users when the event occurs.
|
|
A 1 indicates enable, a 0 indicates disable."
|
|
::= {syupsEventActionEntry 12}
|
|
|
|
syupsPageDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"How long the event must last before paging users."
|
|
::= {syupsEventActionEntry 13}
|
|
|
|
syupsPageMessage OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The message which will be sent when the event occurs."
|
|
::= {syupsEventActionEntry 14}
|
|
|
|
syupsPageUsers OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..255))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Who will receive the code when the event occurs."
|
|
::= {syupsEventActionEntry 15}
|
|
|
|
syupsCommandEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Whether to execute the external command file when the event occurs.
|
|
A 1 indicates enable, a 0 indicates disable."
|
|
::= {syupsEventActionEntry 16}
|
|
|
|
syupsCommandDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"How long the event must last before executing the external command file."
|
|
::= {syupsEventActionEntry 17}
|
|
|
|
syupsCommandFile OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The external command file which will be executed when the event occurs."
|
|
::= {syupsEventActionEntry 18}
|
|
|
|
syupsShutdownEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Whether to shut down the system when the event occurs.
|
|
A 1 indicates enable, a 0 indicates disable."
|
|
::= {syupsEventActionEntry 19}
|
|
|
|
syupsShutdownDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"How long the event must last before shutting down the system."
|
|
::= {syupsEventActionEntry 20}
|
|
|
|
|
|
--
|
|
-- The History Group
|
|
--
|
|
|
|
syupsHistory OBJECT IDENTIFIER ::= {synsoUpsSoftware 4}
|
|
|
|
syupsMaxEventFileLength OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum length (in bytes) of the event log file.
|
|
UPS software will cut the first half of the file whenever
|
|
the file exceeds this maximum length."
|
|
::= {syupsHistory 1}
|
|
|
|
syupsEventNumRecords OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The total number of records in the event log file."
|
|
::= {syupsHistory 2}
|
|
|
|
syupsEventTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SyupsEventEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of event entries. Each entry represents a record
|
|
in the event log file."
|
|
::= {syupsHistory 3}
|
|
|
|
syupsEventEntry OBJECT-TYPE
|
|
SYNTAX SyupsEventEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry representing a record in the event log file."
|
|
INDEX {syupsEventIndex}
|
|
::= {syupsEventTable 1}
|
|
|
|
SyupsEventEntry ::= SEQUENCE {
|
|
syupsEventIndex INTEGER,
|
|
syupsEventRecord DisplayString
|
|
}
|
|
|
|
syupsEventIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The record number of an event entry."
|
|
::= {syupsEventEntry 1}
|
|
|
|
syupsEventRecord OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The string containing an event entry."
|
|
::= {syupsEventEntry 2}
|
|
|
|
syupsDataRecordInterval OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of minutes to wait between each
|
|
recording to the data log file."
|
|
::= {syupsHistory 4}
|
|
|
|
syupsMaxDataFileLength OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum length (in bytes) of the data log file.
|
|
UPS software will cut the first half of the file whenever
|
|
the file exceeds this maximum length."
|
|
::= {syupsHistory 5}
|
|
|
|
syupsDataNumRecords OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The total number of records in the data log file."
|
|
::= {syupsHistory 6}
|
|
|
|
syupsDataTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SyupsDataEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of data entries. Each entry represents a record
|
|
in the data log file."
|
|
::= {syupsHistory 7}
|
|
|
|
syupsDataEntry OBJECT-TYPE
|
|
SYNTAX SyupsDataEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry representing a record in the data log file."
|
|
INDEX {syupsDataIndex}
|
|
::= {syupsDataTable 1}
|
|
|
|
SyupsDataEntry ::= SEQUENCE {
|
|
syupsDataIndex INTEGER,
|
|
syupsDataRecord DisplayString
|
|
}
|
|
|
|
syupsDataIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The record number of a data entry."
|
|
::= {syupsDataEntry 1}
|
|
|
|
syupsDataRecord OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The string containing a data entry."
|
|
::= {syupsDataEntry 2}
|
|
|
|
syupsHistoryOperator OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The operator which is used to operate on the
|
|
history file. The command format is
|
|
'Command, File, Range'. So far, Command can be
|
|
PURGE, File can be EVENT or DATA, and Range can be
|
|
ALL or 'mm/dd/year..mm/dd/year'. For example,
|
|
'PURGE, EVENT, ALL' tells the UPS software to purge
|
|
all entries in the event log file. And
|
|
'PURGE, DATA, 03/20/1995..07/02/1995' tells the UPS
|
|
software to purge the entries which are recorded
|
|
form 03/20/1995 to 07/20/1995 from the event log
|
|
file."
|
|
::= {syupsHistory 8}
|
|
|
|
syupsScopeSettings OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The string contains the settings for UPS Scope Chart,
|
|
including Value Original Point, Value Unit, Time Unit,
|
|
Time Interval, and Display Items. The format for the
|
|
settings string is '%d, %d, %d, %d, %d'. Display Items can
|
|
be any one or any combination of the following items:
|
|
SCOPE_INPUT_VOLT 0x0001
|
|
SCOPE_OUTPUT_VOLT 0x0010
|
|
SCOPE_INPUT_FREQ 0x0100
|
|
SCOPE_OUTPUT_FREQ 0x1000
|
|
"
|
|
::= {syupsHistory 9}
|
|
|
|
|
|
|
|
--
|
|
-- The Schedule Group
|
|
--
|
|
|
|
syupsSchedule OBJECT IDENTIFIER ::= {synsoUpsSoftware 5}
|
|
|
|
syupsNoSchEntries OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The total number of schedule entries."
|
|
::= {syupsSchedule 1}
|
|
|
|
syupsSchOperator OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The operator which is used to operate on the
|
|
schedule table. There are three commands:
|
|
1. 'ADD: action, mm/dd/yyyy, hh:mm:ss,
|
|
week_day, repeat' indicates to add a new entry
|
|
to the schedule list.
|
|
2. 'REPLACE: i, action, mm/dd/yyyy, hh:mm:ss,
|
|
week_day, repeat' indicates to replace the
|
|
i-th entry in the table with the new settings.
|
|
3. 'DELETE:n1, n2' indicates to delete the entries
|
|
ranging from number n1 to number n2 from the schedule
|
|
table.
|
|
'action' could be the following:
|
|
General System Test (1)
|
|
Quick Battery Test (2)
|
|
Deep Battery Test (3)
|
|
Turn On UPS (11)
|
|
Turn Off UPS (21)
|
|
Turn On Outlet (100+x)
|
|
Turn Off Outlet (200+x)
|
|
where x indicates the outlet number.
|
|
'mm/dd/year' and 'hh:mm:ss' specify the action's
|
|
starting time. 'repeat' indicates the frequency
|
|
of the action, it could be Once(1), Daily(2),
|
|
Weekly(3) and Monthly(4). 'week_day' indicating the
|
|
day of week is meaningful only when the repeat is
|
|
set to Weekly, and it could be Sun(0), Mon(1), ...,
|
|
and Sat(6).
|
|
For example, '1, 07/08/1994, 15:30:00, 0, 4'
|
|
indicates that the UPS will do a General System Test
|
|
at 3:30 PM every month from July 8, 1994.
|
|
'203, 06/20/1995, 07:00:00, 0, 1' indicates that the UPS
|
|
will turn off outlet #3 at 7 o'clock on June 20, 1995 and
|
|
do it only once."
|
|
::= {syupsSchedule 2}
|
|
|
|
syupsSchTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SyupsSchEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of schedule entries."
|
|
::= {syupsSchedule 3}
|
|
|
|
syupsSchEntry OBJECT-TYPE
|
|
SYNTAX SyupsSchEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A schedule entry."
|
|
INDEX {syupsSchIndex}
|
|
::= {syupsSchTable 1}
|
|
|
|
SyupsSchEntry ::= SEQUENCE {
|
|
syupsSchIndex INTEGER,
|
|
syupsSchStartDate DisplayString,
|
|
syupsSchStartTime DisplayString,
|
|
syupsSchWeekDay INTEGER,
|
|
syupsSchAction INTEGER,
|
|
syupsSchRepeat INTEGER
|
|
}
|
|
|
|
syupsSchIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The entry number of a schedule setting."
|
|
::= {syupsSchEntry 1}
|
|
|
|
syupsSchStartDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The starting date (mm/dd/yyyy) of the schedule entry."
|
|
::= {syupsSchEntry 2}
|
|
|
|
syupsSchStartTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The starting time (hh:mm:ss) of the schedule entry."
|
|
::= {syupsSchEntry 3}
|
|
|
|
syupsSchWeekDay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sunday(0),
|
|
monday(1),
|
|
tuesday(2),
|
|
wednesday(3),
|
|
thursday(4),
|
|
friday(5),
|
|
saturday(6)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The starting day of week for the schedule entry. It could
|
|
be Sun(0), Mon(1), ..., and Sat(6). It is used when syupsSchRepeat
|
|
is set to weekly."
|
|
::= {syupsSchEntry 4}
|
|
|
|
syupsSchAction OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The action of the schedule entry. It could be:
|
|
General System Test (1)
|
|
Quick Battery Test (2)
|
|
Deep Battery Test (3)
|
|
Turn On UPS (11)
|
|
Turn Off UPS (21)
|
|
Turn On Outlet (100+x)
|
|
Turn Off Outlet (200+x)
|
|
where x indicates the outlet number."
|
|
::= {syupsSchEntry 5}
|
|
|
|
syupsSchRepeat OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
once(1),
|
|
daily(2),
|
|
weekly(3),
|
|
monthly(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"It indicates the frequency of the action, it could be
|
|
Once(1), Daily(2), Weekly(3) and Monthly(4)."
|
|
::= {syupsSchEntry 6}
|
|
|
|
|
|
--
|
|
-- The Co-worker Group
|
|
--
|
|
|
|
syupsCoworker OBJECT IDENTIFIER ::= {synsoUpsSoftware 6}
|
|
|
|
syupsNoAccessControl OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The total number of access control entries."
|
|
::= {syupsCoworker 1}
|
|
|
|
syupsAccessControlOperator OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The operator which is used to operate on the
|
|
access control table. There are three commands:
|
|
1. 'ADD: community' indicates
|
|
to add a new entry to the access control list.
|
|
2. 'REPLACE: x, community'
|
|
indicates to replace the x-th entry in the table
|
|
with the new settings.
|
|
3. 'DELETE:n1, n2' indicates to delete the entries
|
|
from number n1 to number n2 from the access control
|
|
table."
|
|
::= {syupsCoworker 2}
|
|
|
|
syupsAccessControlTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SyupsAccessControlEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of access control entries. Only entries in this list
|
|
can have access to the agent."
|
|
::= {syupsCoworker 3}
|
|
|
|
syupsAccessControlEntry OBJECT-TYPE
|
|
SYNTAX SyupsAccessControlEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An access control entry."
|
|
INDEX {syupsAccessControlIndex}
|
|
::= {syupsAccessControlTable 1}
|
|
|
|
SyupsAccessControlEntry ::= SEQUENCE {
|
|
syupsAccessControlIndex INTEGER,
|
|
syupsAccessControlSetting DisplayString
|
|
}
|
|
|
|
syupsAccessControlIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The entry number of a access control setting."
|
|
::= {syupsAccessControlEntry 1}
|
|
|
|
syupsAccessControlSetting OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string containing the community name."
|
|
::= {syupsAccessControlEntry 2}
|
|
|
|
|
|
syupsNoTrapReceiver OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The total number of trap receiver entries."
|
|
::= {syupsCoworker 4}
|
|
|
|
syupsTrapReceiverOperator OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The operator which is used to operate on the
|
|
trap receiver table. There are three commands:
|
|
1. 'ADD: ipAddress' indicates to add a new
|
|
entry to the trap receiver list.
|
|
2. 'REPLACE: x, ipAddress' indicates to replace
|
|
the x-th entry in the table with the new settings.
|
|
3. 'DELETE:n1, n2' indicates to delete the entries
|
|
from number n1 to number n2 from the trap receiver
|
|
table."
|
|
::= {syupsCoworker 5}
|
|
|
|
syupsTrapReceiverTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SyupsTrapReceiverEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of trap receiver entries. When an important event
|
|
occurs, the agent will send traps to all the entries in the
|
|
list."
|
|
::= {syupsCoworker 6}
|
|
|
|
syupsTrapReceiverEntry OBJECT-TYPE
|
|
SYNTAX SyupsTrapReceiverEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An trap receiver entry."
|
|
INDEX {syupsTrapReceiverIndex}
|
|
::= {syupsTrapReceiverTable 1}
|
|
|
|
SyupsTrapReceiverEntry ::= SEQUENCE {
|
|
syupsTrapReceiverIndex INTEGER,
|
|
syupsTrapReceiverSetting DisplayString
|
|
}
|
|
|
|
syupsTrapReceiverIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The entry number of a trap receiver setting."
|
|
::= {syupsTrapReceiverEntry 1}
|
|
|
|
syupsTrapReceiverSetting OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string containing a trap receiver's IP address."
|
|
::= {syupsTrapReceiverEntry 2}
|
|
|
|
|
|
--
|
|
-- notifications, i.e., traps
|
|
--
|
|
syupsTraps OBJECT IDENTIFIER ::= { synsoUpsSoftware 7 }
|
|
|
|
-- This section defines the extension notifications sent by
|
|
-- UPS agents.
|
|
|
|
syupsTrapOverTemperature NOTIFICATION-TYPE
|
|
OBJECTS { upsBatteryTemperature }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery temperature is too high. This trap is
|
|
persistent and is resent at one minute intervals until
|
|
the UPS either turns off or the status is no longer
|
|
present."
|
|
::= { syupsTraps 1 }
|
|
|
|
syupsTrapOverCurrent NOTIFICATION-TYPE
|
|
OBJECTS { upsInputCurrent }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current is too high. This trap is
|
|
persistent and is resent at one minute intervals until
|
|
the UPS either turns off or the status is no longer
|
|
present."
|
|
::= { syupsTraps 2 }
|
|
|
|
syupsTrapOverVoltage NOTIFICATION-TYPE
|
|
OBJECTS { upsInputVoltage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The voltage is too high. This trap is
|
|
persistent and is resent at one minute intervals until
|
|
the UPS either turns off or the status is no longer
|
|
present."
|
|
::= { syupsTraps 3 }
|
|
|
|
syupsTrapUnderVoltage NOTIFICATION-TYPE
|
|
OBJECTS { upsInputVoltage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The voltage is too low. This trap is
|
|
persistent and is resent at one minute intervals until
|
|
the UPS either turns off or the status is no longer
|
|
present."
|
|
::= { syupsTraps 4 }
|
|
|
|
syupsOffFrequency NOTIFICATION-TYPE
|
|
OBJECTS { upsInputFrequency }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The frequency is abnormal. This trap is
|
|
persistent and is resent at one minute intervals until
|
|
the UPS either turns off or the status is no longer
|
|
present."
|
|
::= { syupsTraps 5 }
|
|
|
|
syupsLowBattery NOTIFICATION-TYPE
|
|
OBJECTS { upsBatteryStatus, upsBatteryVoltage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery is too low. This trap is
|
|
persistent and is resent at one minute intervals until
|
|
the UPS either turns off or the status is no longer
|
|
present."
|
|
::= { syupsTraps 6 }
|
|
|
|
syupsBadBattery NOTIFICATION-TYPE
|
|
OBJECTS { upsBatteryStatus, upsBatteryVoltage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery is bad. This trap is
|
|
persistent and is resent at one minute intervals until
|
|
the UPS either turns off or the status is no longer
|
|
present."
|
|
::= { syupsTraps 7 }
|
|
|
|
END
|