1107 lines
26 KiB
Plaintext
1107 lines
26 KiB
Plaintext
--
|
|
-- Copyright(C) 2019 Western Telematic, Inc.
|
|
--
|
|
|
|
WTI-CONSOLE-MIB DEFINITIONS ::= BEGIN
|
|
IMPORTS
|
|
MODULE-IDENTITY, NOTIFICATION-TYPE,
|
|
OBJECT-TYPE, enterprises FROM SNMPv2-SMI
|
|
DisplayString FROM SNMPv2-TC;
|
|
westernTelematic OBJECT IDENTIFIER ::= { enterprises 2634 }
|
|
console MODULE-IDENTITY
|
|
LAST-UPDATED "201901291600Z" -- 29 Jan 2019
|
|
ORGANIZATION "Western Telematic, Inc."
|
|
CONTACT-INFO
|
|
"Western Telematic, Inc.
|
|
5 Sterling
|
|
Irvine, Ca 92618
|
|
Email: anthonyb@wti.com"
|
|
DESCRIPTION
|
|
"This is the MIB module for console products"
|
|
REVISION "201901291600Z" -- 29 Jan 2019
|
|
DESCRIPTION
|
|
"V7.11 for console products "
|
|
::= { westernTelematic 1 }
|
|
--
|
|
-- System Tables
|
|
--
|
|
systemTables OBJECT IDENTIFIER ::= { console 100 }
|
|
--
|
|
-- Port Table
|
|
--
|
|
portTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PortEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of ports."
|
|
::= { systemTables 100 }
|
|
portEntry OBJECT-TYPE
|
|
SYNTAX PortEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Row definition for the port table."
|
|
INDEX {portIndex}
|
|
::= { portTable 1 }
|
|
PortEntry ::= SEQUENCE {
|
|
portIndex INTEGER,
|
|
portID DisplayString,
|
|
portName DisplayString,
|
|
portBufferThreshold INTEGER,
|
|
portUserName DisplayString,
|
|
portStatus DisplayString,
|
|
portBufferCt INTEGER
|
|
}
|
|
portIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..41)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index for the port table."
|
|
::= { portEntry 1 }
|
|
portID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(6..7))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ID of the port."
|
|
::= { portEntry 2 }
|
|
portName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the port."
|
|
::= { portEntry 3 }
|
|
portBufferThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER (1..262144)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Port buffer threshold"
|
|
::= { portEntry 4 }
|
|
portUserName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the user logged in to port"
|
|
::= { portEntry 5 }
|
|
portStatus OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the port."
|
|
::= { portEntry 6 }
|
|
portBufferCt OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Port byte threshold"
|
|
::= { portEntry 7 }
|
|
--
|
|
-- Plug Table
|
|
--
|
|
plugTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PlugEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of plugs."
|
|
::= { systemTables 200 }
|
|
plugEntry OBJECT-TYPE
|
|
SYNTAX PlugEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Row definition for the plug table."
|
|
INDEX { plugIndex }
|
|
::= { plugTable 1 }
|
|
PlugEntry ::= SEQUENCE {
|
|
plugIndex INTEGER,
|
|
plugID DisplayString,
|
|
plugStatus INTEGER,
|
|
plugAction INTEGER,
|
|
plugName DisplayString,
|
|
plugCurrent INTEGER,
|
|
plugPower INTEGER
|
|
}
|
|
plugIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..80)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index for the plug table."
|
|
::= { plugEntry 1 }
|
|
plugID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(9..11))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ID of the plug."
|
|
::= { plugEntry 2 }
|
|
plugStatus OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Plug status"
|
|
::= { plugEntry 3 }
|
|
plugAction OBJECT-TYPE
|
|
SYNTAX INTEGER (0..8)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Plug action"
|
|
::= { plugEntry 4 }
|
|
plugName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Name of the plug."
|
|
::= { plugEntry 5 }
|
|
plugCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Plug current (In tenths of amps, divide by 10 for value in amps)"
|
|
::= { plugEntry 7 }
|
|
plugPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Plug power (Watts)"
|
|
::= { plugEntry 8 }
|
|
--
|
|
-- Plug Group Table
|
|
--
|
|
plugGroupTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PlugGroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of plug groups."
|
|
::= { systemTables 300 }
|
|
plugGroupEntry OBJECT-TYPE
|
|
SYNTAX PlugGroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Row definition for the plug group table."
|
|
INDEX { plugGroupIndex }
|
|
::= { plugGroupTable 1 }
|
|
PlugGroupEntry ::= SEQUENCE {
|
|
plugGroupIndex INTEGER,
|
|
plugGroupName DisplayString,
|
|
plugGroupAction INTEGER,
|
|
plugGroupCurrent INTEGER,
|
|
plugGroupPower INTEGER
|
|
}
|
|
plugGroupIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..54)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index for the plug group table."
|
|
::= { plugGroupEntry 1 }
|
|
plugGroupName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(1..24))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the plug group."
|
|
::= { plugGroupEntry 2 }
|
|
plugGroupAction OBJECT-TYPE
|
|
SYNTAX INTEGER (0..8)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Plug group action"
|
|
::= { plugGroupEntry 3 }
|
|
plugGroupCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Plug group current (In tenths of amps, divide by 10 for value in amps)"
|
|
::= { plugGroupEntry 4 }
|
|
plugGroupPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Plug group power (Watts)"
|
|
::= { plugGroupEntry 5 }
|
|
--
|
|
-- User Table
|
|
--
|
|
userTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UserEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of users."
|
|
::= { systemTables 400 }
|
|
userEntry OBJECT-TYPE
|
|
SYNTAX UserEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Row definition for the user table."
|
|
INDEX { userIndex }
|
|
::= { userTable 1 }
|
|
UserEntry ::= SEQUENCE {
|
|
userIndex INTEGER,
|
|
userName DisplayString,
|
|
userPasswd DisplayString,
|
|
userAccessLevel INTEGER,
|
|
userPortAccess DisplayString,
|
|
userPlugAccess DisplayString,
|
|
userGroupAccess DisplayString,
|
|
userSerialAccess INTEGER,
|
|
userTelnetSshAccess INTEGER,
|
|
userWebAccess INTEGER,
|
|
userOutboundTelAccess INTEGER,
|
|
userCurrentPowerMetering INTEGER,
|
|
userCallbackNum1 DisplayString,
|
|
userCallbackNum2 DisplayString,
|
|
userCallbackNum3 DisplayString,
|
|
userCallbackNum4 DisplayString,
|
|
userCallbackNum5 DisplayString,
|
|
userSubmit INTEGER
|
|
}
|
|
userIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..128)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index for the user table."
|
|
::= { userEntry 1 }
|
|
userName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the user."
|
|
::= { userEntry 2 }
|
|
userPasswd OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(1..16))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The password of the user."
|
|
::= { userEntry 3 }
|
|
userAccessLevel OBJECT-TYPE
|
|
SYNTAX INTEGER (0..3)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Users access level"
|
|
::= { userEntry 4 }
|
|
userPortAccess OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(1..41))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Access to ports."
|
|
::= { userEntry 5 }
|
|
userPlugAccess OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(1..20))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Access to plugs."
|
|
::= { userEntry 6 }
|
|
userGroupAccess OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(1..54))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Access to plug groups."
|
|
::= { userEntry 10 }
|
|
userSerialAccess OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Access to serial interface."
|
|
::= { userEntry 11 }
|
|
userTelnetSshAccess OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Access to Telnet/SSH interface."
|
|
::= { userEntry 12 }
|
|
userWebAccess OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Access to web interface."
|
|
::= { userEntry 13 }
|
|
userOutboundTelAccess OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Access to outbound telnet."
|
|
::= { userEntry 14 }
|
|
userCurrentPowerMetering OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Access to Current/Power Metering."
|
|
::= { userEntry 15 }
|
|
userCallbackNum1 OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Callback number1."
|
|
::= { userEntry 16 }
|
|
userCallbackNum2 OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Callback number2."
|
|
::= { userEntry 17 }
|
|
userCallbackNum3 OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Callback number3."
|
|
::= { userEntry 18 }
|
|
userCallbackNum4 OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Callback number4."
|
|
::= { userEntry 19 }
|
|
userCallbackNum5 OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Callback number5."
|
|
::= { userEntry 20 }
|
|
userSubmit OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Submit changes to user."
|
|
::= { userEntry 31 }
|
|
--
|
|
-- Environment Tables
|
|
--
|
|
environmentTables OBJECT IDENTIFIER ::= { console 200 }
|
|
environmentUnitTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF EnvironmentUnitEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of environment status for units."
|
|
::= { environmentTables 10 }
|
|
environmentUnitEntry OBJECT-TYPE
|
|
SYNTAX EnvironmentUnitEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Row definition for the environment unit table."
|
|
INDEX { environmentUnitIndex }
|
|
::= { environmentUnitTable 1 }
|
|
EnvironmentUnitEntry ::= SEQUENCE {
|
|
environmentUnitIndex INTEGER,
|
|
environmentUnitName DisplayString,
|
|
environmentUnitTemperature INTEGER,
|
|
environmentUnitCurrentA INTEGER,
|
|
environmentUnitVoltageA INTEGER,
|
|
environmentUnitPowerA INTEGER,
|
|
environmentUnitCurrentB INTEGER,
|
|
environmentUnitVoltageB INTEGER,
|
|
environmentUnitPowerB INTEGER,
|
|
environmentUnitCurrentC INTEGER,
|
|
environmentUnitVoltageC INTEGER,
|
|
environmentUnitPowerC INTEGER,
|
|
environmentUnitCurrentD INTEGER,
|
|
environmentUnitVoltageD INTEGER,
|
|
environmentUnitPowerD INTEGER,
|
|
environmentSysRAM INTEGER,
|
|
environmentSysFlash INTEGER,
|
|
environmentMacEth0 DisplayString,
|
|
environmentMacEth1 DisplayString,
|
|
environmentInputPower1 INTEGER,
|
|
environmentInputPower2 INTEGER,
|
|
environmentInputPower3 INTEGER,
|
|
environmentInputPower4 INTEGER,
|
|
environmentModemPhoneNumber DisplayString,
|
|
environmentSerialNumber DisplayString,
|
|
environmentSoftwareVersion DisplayString
|
|
}
|
|
environmentUnitIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..3)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index for the environment unit table."
|
|
::= { environmentUnitEntry 1 }
|
|
environmentUnitName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the unit."
|
|
::= { environmentUnitEntry 2 }
|
|
environmentUnitTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature of the unit."
|
|
::= { environmentUnitEntry 3 }
|
|
environmentUnitCurrentA OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of amps in branch A for unit (In tenths of amps, divide by 10 for value in amps)."
|
|
::= { environmentUnitEntry 4 }
|
|
environmentUnitVoltageA OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The voltage of branch A for unit."
|
|
::= { environmentUnitEntry 5 }
|
|
environmentUnitPowerA OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of watts used by branch A for unit."
|
|
::= { environmentUnitEntry 6 }
|
|
environmentUnitCurrentB OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of amps in branch B for unit (In tenths of amps, divide by 10 for value in amps)."
|
|
::= { environmentUnitEntry 7 }
|
|
environmentUnitVoltageB OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The voltage of branch B for unit."
|
|
::= { environmentUnitEntry 8 }
|
|
environmentUnitPowerB OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of watts used by branch b for unit."
|
|
::= { environmentUnitEntry 9 }
|
|
environmentUnitCurrentC OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of amps in branch C for unit (In tenths of amps, divide by 10 for value in amps)."
|
|
::= { environmentUnitEntry 10 }
|
|
environmentUnitVoltageC OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The voltage of branch C for unit."
|
|
::= { environmentUnitEntry 11 }
|
|
environmentUnitPowerC OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of watts used by branch c for unit."
|
|
::= { environmentUnitEntry 12 }
|
|
environmentUnitCurrentD OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of amps in branch D for unit (In tenths of amps, divide by 10 for value in amps)."
|
|
::= { environmentUnitEntry 13 }
|
|
environmentUnitVoltageD OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The voltage of branch D for unit."
|
|
::= { environmentUnitEntry 14 }
|
|
environmentUnitPowerD OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of watts used by branch d for unit."
|
|
::= { environmentUnitEntry 15 }
|
|
environmentSysRAM OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total system RAM."
|
|
::= { environmentUnitEntry 18 }
|
|
environmentSysFlash OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total system Flash."
|
|
::= { environmentUnitEntry 19 }
|
|
environmentMacEth0 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"MAC Address Eth0"
|
|
::= { environmentUnitEntry 20 }
|
|
environmentMacEth1 OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"MAC Address Eth1"
|
|
::= { environmentUnitEntry 21 }
|
|
environmentInputPower1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of first power input."
|
|
::= { environmentUnitEntry 22 }
|
|
environmentInputPower2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of second power input."
|
|
::= { environmentUnitEntry 23 }
|
|
environmentInputPower3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of third power input."
|
|
::= { environmentUnitEntry 24 }
|
|
environmentInputPower4 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of fourth power input."
|
|
::= { environmentUnitEntry 25 }
|
|
environmentModemPhoneNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit modem phone number"
|
|
::= { environmentUnitEntry 26 }
|
|
environmentSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit serial number"
|
|
::= { environmentUnitEntry 27 }
|
|
environmentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit software version"
|
|
::= { environmentUnitEntry 28 }
|
|
environmentSystemTotalCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total current for system (In tenths of amps, divide by 10 for value in amps)."
|
|
::= { environmentTables 60 }
|
|
environmentSystemTotalPower OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total power on system."
|
|
::= { environmentTables 70 }
|
|
environmentMonthlyPowerLog OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The monthly power usage log"
|
|
::= { environmentTables 80 }
|
|
--
|
|
-- Alarm Tables
|
|
--
|
|
alarmTables OBJECT IDENTIFIER ::= { console 280 }
|
|
alarmOverCurrentInitial OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Over Current Initial Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 1 }
|
|
alarmOverCurrentCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Over Current Critical Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 2 }
|
|
alarmOverTemperatureInitial OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Over Temperature Initial Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 3 }
|
|
alarmOverTemperatureCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Over Temperature Critical Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 4 }
|
|
alarmCircuitBreakerOpen OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Circuit Breaker Open Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 5 }
|
|
alarmCommLoss OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Communication Loss Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 6 }
|
|
alarmLostVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Lost Voltage (Line Input) Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 7 }
|
|
alarmPingNoAnswer OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Ping No Answer Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 8 }
|
|
alarmInvalidAccessLockout OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Invalid Access Lockout Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 9 }
|
|
alarmPowerCycle OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Power Cycle Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 10 }
|
|
alarmBufferThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Buffer Threshold Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 11 }
|
|
alarmPlugCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Plug Current Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 13 }
|
|
alarmLostOptoVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Lost Voltage (Line Input) Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 14 }
|
|
alarmEmergencyShutoff OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Emergency Shutoff Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 15 }
|
|
alarmNoDialtone OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the No Dialtone Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 16 }
|
|
alarmWakeupOnFailure OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Wakeup On Failure Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 17 }
|
|
alarmIpPassthroughDataUsage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the IP Passthrough Data Usage Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 18 }
|
|
alarmBufferFiltering OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the Buffer Filtering Alarm (0 = Inactive, 1 = Active)"
|
|
::= { alarmTables 19 }
|
|
--
|
|
-- Traps
|
|
--
|
|
wtiTraps OBJECT IDENTIFIER ::= { console 300 }
|
|
-- Trap Info
|
|
trapInfo OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alarm information"
|
|
::= { wtiTraps 1 }
|
|
-- Test Traps
|
|
testTraps OBJECT IDENTIFIER ::= { wtiTraps 2}
|
|
testTrap TRAP-TYPE
|
|
ENTERPRISE testTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"A test trap"
|
|
::= 1
|
|
-- Alarm Traps
|
|
bufferThresholdTraps OBJECT IDENTIFIER ::= { wtiTraps 3}
|
|
bufferThresholdCrossedSetTrap TRAP-TYPE
|
|
ENTERPRISE bufferThresholdTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Buffer Threshold Crossed Alarm"
|
|
::= 1
|
|
bufferThresholdCrossedClearTrap TRAP-TYPE
|
|
ENTERPRISE bufferThresholdTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Buffer Threshold Crossed Alarm (Clear)"
|
|
::= 2
|
|
overCurrentInitialTraps OBJECT IDENTIFIER ::= { wtiTraps 4}
|
|
overCurrentInitialSetTrap TRAP-TYPE
|
|
ENTERPRISE overCurrentInitialTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Over Current Initial Alarm"
|
|
::= 1
|
|
overCurrentInitialClearTrap TRAP-TYPE
|
|
ENTERPRISE overCurrentInitialTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Over Current Initial Alarm (Clear)"
|
|
::= 2
|
|
overCurrentCriticalTraps OBJECT IDENTIFIER ::= { wtiTraps 5}
|
|
overCurrentCriticalSetTrap TRAP-TYPE
|
|
ENTERPRISE overCurrentCriticalTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Over Current Critical Alarm"
|
|
::= 1
|
|
overCurrentCriticalClearTrap TRAP-TYPE
|
|
ENTERPRISE overCurrentCriticalTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Over Current Critical Alarm (Clear)"
|
|
::= 2
|
|
overTemperatureInitialTraps OBJECT IDENTIFIER ::= { wtiTraps 6}
|
|
overTemperatureInitialSetTrap TRAP-TYPE
|
|
ENTERPRISE overTemperatureInitialTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Over Temperature Initial Alarm"
|
|
::= 1
|
|
overTemperatureInitialClearTrap TRAP-TYPE
|
|
ENTERPRISE overTemperatureInitialTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Over Temperature Initial Alarm (Clear)"
|
|
::= 2
|
|
overTemperatureCriticalTraps OBJECT IDENTIFIER ::= { wtiTraps 7}
|
|
overTemperatureCriticalSetTrap TRAP-TYPE
|
|
ENTERPRISE overTemperatureCriticalTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Over Temperature Critical Alarm"
|
|
::= 1
|
|
overTemperatureCriticalClearTrap TRAP-TYPE
|
|
ENTERPRISE overTemperatureCriticalTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Over Temperature Critical Alarm (Clear)"
|
|
::= 2
|
|
circuitBreakerOpenTraps OBJECT IDENTIFIER ::= { wtiTraps 8}
|
|
circuitBreakerOpenSetTrap TRAP-TYPE
|
|
ENTERPRISE circuitBreakerOpenTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Circuit Breaker Open Alarm"
|
|
::= 1
|
|
circuitBreakerOpenClearTrap TRAP-TYPE
|
|
ENTERPRISE circuitBreakerOpenTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Circuit Breaker Open Alarm (Clear)"
|
|
::= 2
|
|
lostCommTraps OBJECT IDENTIFIER ::= { wtiTraps 9}
|
|
lostCommSetTrap TRAP-TYPE
|
|
ENTERPRISE lostCommTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Lost Communication with AUX Unit"
|
|
::= 1
|
|
lostCommClearTrap TRAP-TYPE
|
|
ENTERPRISE lostCommTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Lost Communication with AUX Unit (Clear)"
|
|
::= 2
|
|
lostVoltageTraps OBJECT IDENTIFIER ::= { wtiTraps 10}
|
|
lostVoltageSetTrap TRAP-TYPE
|
|
ENTERPRISE lostVoltageTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Lost Voltage (Line In)"
|
|
::= 1
|
|
lostVoltageClearTrap TRAP-TYPE
|
|
ENTERPRISE lostVoltageTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Lost Voltage (Line In) (Clear)"
|
|
::= 2
|
|
pingNoAnswerTraps OBJECT IDENTIFIER ::= { wtiTraps 11}
|
|
pingNoAnswerSetTrap TRAP-TYPE
|
|
ENTERPRISE pingNoAnswerTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Ping No Answer"
|
|
::= 1
|
|
pingNoAnswerClearTrap TRAP-TYPE
|
|
ENTERPRISE pingNoAnswerTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Ping No Answer (Clear)"
|
|
::= 2
|
|
lockoutTraps OBJECT IDENTIFIER ::= { wtiTraps 12}
|
|
lockoutSetTrap TRAP-TYPE
|
|
ENTERPRISE lockoutTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Invalid Access Lockout"
|
|
::= 1
|
|
lockoutClearTrap TRAP-TYPE
|
|
ENTERPRISE lockoutTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Invalid Access Lockout (Clear)"
|
|
::= 2
|
|
powercycleTraps OBJECT IDENTIFIER ::= { wtiTraps 13}
|
|
powercycleSetTrap TRAP-TYPE
|
|
ENTERPRISE powercycleTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Power Cycle"
|
|
::= 1
|
|
plugCurrentTraps OBJECT IDENTIFIER ::= { wtiTraps 15}
|
|
plugCurrentSetTrap TRAP-TYPE
|
|
ENTERPRISE plugCurrentTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Plug Current"
|
|
::= 1
|
|
plugCurrentClearTrap TRAP-TYPE
|
|
ENTERPRISE plugCurrentTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Plug Current (Clear)"
|
|
::= 2
|
|
lostOptoVoltageTraps OBJECT IDENTIFIER ::= { wtiTraps 16}
|
|
lostOptoVoltageSetTrap TRAP-TYPE
|
|
ENTERPRISE lostOptoVoltageTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Lost Voltage"
|
|
::= 1
|
|
lostOptoVoltageClearTrap TRAP-TYPE
|
|
ENTERPRISE lostOptoVoltageTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Lost Voltage (Clear)"
|
|
::= 2
|
|
emergencyShutoffTraps OBJECT IDENTIFIER ::= { wtiTraps 17}
|
|
emergencyShutoffSetTrap TRAP-TYPE
|
|
ENTERPRISE emergencyShutoffTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Emergency Shutoff"
|
|
::= 1
|
|
emergencyShutoffClearTrap TRAP-TYPE
|
|
ENTERPRISE emergencyShutoffTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Emergency Shutoff (Clear)"
|
|
::= 2
|
|
noDialtoneTraps OBJECT IDENTIFIER ::= { wtiTraps 18}
|
|
noDialtoneSetTrap TRAP-TYPE
|
|
ENTERPRISE noDialtoneTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"No Dialtone"
|
|
::= 1
|
|
noDialtoneClearTrap TRAP-TYPE
|
|
ENTERPRISE noDialtoneTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"No Dialtone (Clear)"
|
|
::= 2
|
|
wakeupOnFailureTraps OBJECT IDENTIFIER ::= { wtiTraps 19}
|
|
wakeupOnFailureSetTrap TRAP-TYPE
|
|
ENTERPRISE wakeupOnFailureTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Wakeup On Failure"
|
|
::= 1
|
|
wakeupOnFailureClearTrap TRAP-TYPE
|
|
ENTERPRISE wakeupOnFailureTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Wakeup On Failure (Clear)"
|
|
::= 2
|
|
ipPassthroughDataUsageTraps OBJECT IDENTIFIER ::= { wtiTraps 20}
|
|
ipPassthroughDataUsageSetTrap TRAP-TYPE
|
|
ENTERPRISE ipPassthroughDataUsageTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"IP Passthrough Data Usage"
|
|
::= 1
|
|
ipPassthroughDataUsageClearTrap TRAP-TYPE
|
|
ENTERPRISE ipPassthroughDataUsageTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"IP Passthrough Data Usage (Clear)"
|
|
::= 2
|
|
bufferFilteringTraps OBJECT IDENTIFIER ::= { wtiTraps 21}
|
|
bufferFilteringSetTrap TRAP-TYPE
|
|
ENTERPRISE bufferFilteringTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Buffer Filtering"
|
|
::= 1
|
|
bufferFilteringClearTrap TRAP-TYPE
|
|
ENTERPRISE bufferFilteringTraps
|
|
VARIABLES {
|
|
trapInfo
|
|
}
|
|
DESCRIPTION
|
|
"Buffer Filtering (Clear)"
|
|
::= 2
|
|
END
|