2529 lines
82 KiB
Plaintext
2529 lines
82 KiB
Plaintext
WebGraph-Thermo-Hygro-Barometer-MIB DEFINITIONS ::= BEGIN
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.30
|
||
----------------------------------------------------------------
|
||
-- 14.12.2009 RSS Feed
|
||
--
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.29
|
||
----------------------------------------------------------------
|
||
-- 02.06.2008 Correction wtWebGraphThermBaroHTTP
|
||
-- Correction wtWebGraphThermoBaroDiag
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.28
|
||
----------------------------------------------------------------
|
||
-- 19.01.2007 Webio
|
||
-- New Graphics java script base parameter
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.27
|
||
----------------------------------------------------------------
|
||
-- 09.11.2006 Webio
|
||
-- DHCP enable
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.26
|
||
----------------------------------------------------------------
|
||
-- 03.08.2006 wtWebGraphThermoBaroSensorNo korrigiert
|
||
--
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.25
|
||
----------------------------------------------------------------
|
||
-- 28.06.2006 New: Community String Trap
|
||
--
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.24
|
||
----------------------------------------------------------------
|
||
-- 26.07.2005 #57606, WebGraph Thermo-Hygrometer
|
||
-- CRON Zeitfunktion
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.23
|
||
----------------------------------------------------------------
|
||
-- 14.07.2005 #57606, WebGraph Thermo-Hygrometer
|
||
-- FTP Funktionen
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.22
|
||
----------------------------------------------------------------
|
||
-- 17.05.2005 #57606, WebGraph Thermo-Hygrometer
|
||
-- Trap NMS annotations
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.21
|
||
----------------------------------------------------------------
|
||
-- 19.04.2005 #57606, WebGraph Thermo-Hygrometer
|
||
-- Mail Authentication
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.20
|
||
----------------------------------------------------------------
|
||
-- 05.11.2004 #57606, WebGraph Themo-Hygrometer
|
||
-- Neu: Syslog
|
||
--
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.19
|
||
----------------------------------------------------------------
|
||
-- 08.09.2004 #57606 WebGraph Thermo-Hygrometer
|
||
-- Neu:
|
||
-- wtWebGraphThermoBaroAlarmRHMin
|
||
-- wtWebGraphThermoBaroAlarmRHMax
|
||
-- wtWebGraphThermoBaroAlarmRHHysteresis
|
||
-- wtWebGraphThermoBaroPortSensorSelect
|
||
-- wtWebGraphThermoBaroAlarmDeltaTemp
|
||
-- wtWebGraphThermoBaroAlarmAHMin
|
||
-- wtWebGraphThermoBaroAlarmAHMax
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.18
|
||
----------------------------------------------------------------
|
||
-- 21.07.2004 #57601/3/4, Webio Digital
|
||
-- Neu:
|
||
-- Diagnosis
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.17
|
||
----------------------------------------------------------------
|
||
-- 28.06.2004 #57630/1/2, Webio Digital
|
||
-- Neu: Puls Mode
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.16
|
||
----------------------------------------------------------------
|
||
-- 16.04.2004 neu: #57632, Webio Digital EA24x24
|
||
--
|
||
-- #57630/1, Webio Digital EA12x12
|
||
-- Neu:
|
||
-- wtWebioEA12x12InputCounterClear
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.15
|
||
----------------------------------------------------------------
|
||
-- 27.02.2004 #57630/1, Webio Digital EA12x12
|
||
-- Neu:
|
||
-- L<>nge erweitert auf 32 Bit:
|
||
-- wtWebioEA12x12InputValue
|
||
-- wtWebioEA12x12OutputValue
|
||
-- wtWebioEA12x12LoadControlView
|
||
-- wtWebioEA12x12LCShutDownView
|
||
-- wtWebioEA12x12SetOutput
|
||
-- wtWebioEA12x12AlarmInputTrigger
|
||
-- wtWebioEA12x12AlarmOutputTrigger
|
||
-- wtWebioEA12x12PortOutputSafetyState
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.14
|
||
----------------------------------------------------------------
|
||
-- 16.02.2004 #57630/1, Webio Digital EA12x12
|
||
-- Neu:
|
||
-- Texte: Location, Contact
|
||
-- SNMP: ColdStart, WarmStart, ComunityString Read/RW
|
||
-- Alarm: ColdStart / WarmStart trigger
|
||
--
|
||
-- #57601, 1xWebThermometer
|
||
-- #57603, 2xWebThermometer
|
||
-- #57604, 8xWebThermometer
|
||
-- Neu:
|
||
-- Alarm Hysterese
|
||
-- Alarm Clear Traps und Mails
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.13
|
||
----------------------------------------------------------------
|
||
-- 05.02.2004 #57601, 1xWebThermometer
|
||
-- #57603, 2xWebThermometer
|
||
-- #57604, 8xWebThermometer
|
||
-- Neu:
|
||
-- Texte: Location, Contact
|
||
-- SNMP: ColdStart, WarmStart, ComunityString Read/RW
|
||
-- Alarm: ColdStart / WarmStart trigger
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.12
|
||
----------------------------------------------------------------
|
||
-- 05.11.2003 #57601, 1xWebThermometer
|
||
-- #57603, 2xWebThermometer
|
||
-- #57604, 8xWebThermometer
|
||
-- Neu:
|
||
-- Mail Option: CSV attachment
|
||
-- Offsetkalibrierung
|
||
-- Alarm: Tcp Client mode
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.11
|
||
----------------------------------------------------------------
|
||
-- 28.10.2003 #57630/1, Webio Digital EA12x12
|
||
-- Neue Feature:
|
||
-- Alarm : TCP Client mode
|
||
-- INPUTS: Pulsfilter
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.10
|
||
----------------------------------------------------------------
|
||
-- 04.07.2003 #57630, Webio Digital EA12x12
|
||
-- Neuer Men<65>baum, neue Bin<69>rmodi
|
||
--
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.09
|
||
----------------------------------------------------------------
|
||
-- 24.03.2003 Trap Enterprise (Type 1, 2) korrigiert
|
||
--
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.08
|
||
----------------------------------------------------------------
|
||
-- 04.03.2003 Abgleich der Sprachversionen DE/US
|
||
--
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.07
|
||
----------------------------------------------------------------
|
||
-- 25.02.2003 Korrektur US: wtWebioEA12x12LoadControl
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.06
|
||
----------------------------------------------------------------
|
||
-- 24.02.2003 Neu:
|
||
-- #57630, Webio EA12x12, LoadControl Group
|
||
-- Korrektur: Trap variable Namen
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.05
|
||
----------------------------------------------------------------
|
||
-- 21.01.2003 Neu:
|
||
-- #57630, Webio EA12x12
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.04
|
||
----------------------------------------------------------------
|
||
-- 02.01.2003 Neu:
|
||
-- #57601, 1xWebThermometer
|
||
-- #57603, 2xWebThermometer, 8 Alarme
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.03
|
||
----------------------------------------------------------------
|
||
-- 21.11.2002 Neu:
|
||
-- #57604, 2xWebThermometer, BOOTP, StartupSite
|
||
-- #57603, 8xWebThermometer, BOOTP, StartupSite
|
||
----------------------------------------------------------------
|
||
-- Revison: 1.02
|
||
----------------------------------------------------------------
|
||
-- 26.07.2002 Neu:
|
||
-- #57604, 2xWebThermometer
|
||
-- #57603, 8xWebThermometer
|
||
--
|
||
|
||
IMPORTS
|
||
|
||
OBJECT-TYPE FROM RFC-1212
|
||
TRAP-TYPE FROM RFC-1215
|
||
DisplayString, PhysAddress FROM RFC1213-MIB
|
||
enterprises, TimeTicks, IpAddress, NetworkAddress FROM RFC1155-SMI;
|
||
|
||
|
||
-- IpAddress ::=
|
||
-- [APPLICATION 0]
|
||
-- IMPLICIT OCTET STRING (SIZE (4))
|
||
-- Counter ::=
|
||
-- [APPLICATION 1]
|
||
-- IMPLICIT INTEGER (0..4294967295)
|
||
-- Gauge ::=
|
||
-- [APPLICATION 2]
|
||
-- IMPLICIT INTEGER (0..4294967295)
|
||
-- TimeTicks ::=
|
||
-- [APPLICATION 3]
|
||
-- IMPLICIT INTEGER (0..4294967295)
|
||
|
||
|
||
-- DisplayString ::= OCTET STRING
|
||
-- PhysAddress ::= OCTET STRING
|
||
|
||
-- internet OBJECT IDENTIFIER ::= { iso org(3) dod(6) 1 }
|
||
-- privat OBJECT IDENTIFIER ::= { internet 4 }
|
||
-- enterprises OBJECT IDENTIFIER ::= { privat 1 }
|
||
|
||
|
||
|
||
-- Wiesemann & Theis Com-Server MIB
|
||
|
||
wut OBJECT IDENTIFIER ::= { enterprises 5040 }
|
||
wtComServer OBJECT IDENTIFIER ::= { wut 1 }
|
||
wtWebio OBJECT IDENTIFIER ::= { wtComServer 2 }
|
||
|
||
|
||
-- wtWebGraph Tree
|
||
|
||
wtWebGraphThermoBaro OBJECT IDENTIFIER ::= { wtWebio 16 }
|
||
|
||
-- wtWebGraphThermoBaro Tree
|
||
|
||
wtWebGraphThermoBaroTemp OBJECT IDENTIFIER ::= { wtWebGraphThermoBaro 1 }
|
||
wtWebGraphThermoBaroSessCntrl OBJECT IDENTIFIER ::= { wtWebGraphThermoBaro 2 }
|
||
wtWebGraphThermoBaroConfig OBJECT IDENTIFIER ::= { wtWebGraphThermoBaro 3 }
|
||
wtWebGraphThermoBaroDiag OBJECT IDENTIFIER ::= { wtWebGraphThermoBaro 4 }
|
||
|
||
-- wtWebGraphThermoBaroConfig Tree
|
||
|
||
wtWebGraphThermoBaroDevice OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroConfig 1 }
|
||
wtWebGraphThermoBaroPorts OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroConfig 2 }
|
||
wtWebGraphThermoBaroManufact OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroConfig 3 }
|
||
|
||
-- wtWebGraphThermoBaroDevice Tree
|
||
|
||
wtWebGraphThermoBaroText OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroDevice 1 }
|
||
wtWebGraphThermoBaroTimeDate OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroDevice 2 }
|
||
wtWebGraphThermoBaroBasic OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroDevice 3 }
|
||
wtWebGraphThermoBaroDatalogger OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroDevice 4 }
|
||
wtWebGraphThermoBaroAlarm OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroDevice 5 }
|
||
wtWebGraphThermoBaroGraphics OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroDevice 6 }
|
||
|
||
-- wtWebGraphThermoBaroTimeDate Tree
|
||
|
||
wtWebGraphThermoBaroTimeZone OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroTimeDate 1 }
|
||
wtWebGraphThermoBaroTimeServer OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroTimeDate 2 }
|
||
wtWebGraphThermoBaroDeviceClock OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroTimeDate 3 }
|
||
|
||
-- wtWebGraphThermoBaroBasic Tree
|
||
|
||
wtWebGraphThermoBaroNetwork OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroBasic 1 }
|
||
wtWebGraphThermoBaroHTTP OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroBasic 2 }
|
||
wtWebGraphThermoBaroMail OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroBasic 3 }
|
||
wtWebGraphThermoBaroSNMP OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroBasic 4 }
|
||
wtWebGraphThermoBaroUDP OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroBasic 5 }
|
||
wtWebGraphThermoBaroSyslog OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroBasic 6 }
|
||
wtWebGraphThermoBaroFTP OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroBasic 7 }
|
||
wtWebGraphThermoBaroRSS OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroBasic 8 }
|
||
|
||
-- wtWebGraphThermoBaroGraphics Tree
|
||
|
||
wtWebGraphThermoBaroGraphicsBase OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroGraphics 1 }
|
||
wtWebGraphThermoBaroGraphicsSelect OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroGraphics 2 }
|
||
wtWebGraphThermoBaroGraphicsScale OBJECT IDENTIFIER ::= { wtWebGraphThermoBaroGraphics 3 }
|
||
|
||
|
||
|
||
-- wtWebGraphThermoBaroTemp Group
|
||
------------------------
|
||
|
||
wtWebGraphThermoBaroSensors OBJECT-TYPE
|
||
SYNTAX INTEGER (1..2)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Anzahl der Sensoren"
|
||
::= { wtWebGraphThermoBaroTemp 1 }
|
||
|
||
-- Interface Table
|
||
|
||
wtWebGraphThermoBaroSensorTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebGraphThermoBaroSensorEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Liste der Sensoren."
|
||
::= { wtWebGraphThermoBaroTemp 2 }
|
||
|
||
wtWebGraphThermoBaroSensorEntry OBJECT-TYPE
|
||
SYNTAX WtWebGraphThermoBaroSensorEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Nummern der Sensoren."
|
||
INDEX { wtWebGraphThermoBaroSensorNo }
|
||
::= { wtWebGraphThermoBaroSensorTable 1 }
|
||
|
||
WtWebGraphThermoBaroSensorEntry ::= SEQUENCE {
|
||
wtWebGraphThermoBaroSensorNo INTEGER
|
||
}
|
||
|
||
wtWebGraphThermoBaroSensorNo OBJECT-TYPE
|
||
SYNTAX INTEGER (1..3)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Nummer des Sensors."
|
||
::= { wtWebGraphThermoBaroSensorEntry 1 }
|
||
|
||
|
||
-- wtWebGraphThermoBaroTempValue Table
|
||
|
||
wtWebGraphThermoBaroTempValueTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebGraphThermoBaroTempValueEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Liste Sensormesswerte korrespondiernd zu den Kanalnummern."
|
||
::= { wtWebGraphThermoBaroTemp 3 }
|
||
|
||
wtWebGraphThermoBaroTempValueEntry OBJECT-TYPE
|
||
SYNTAX WtWebGraphThermoBaroTempValueEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Messwerte der Sensoren."
|
||
INDEX { wtWebGraphThermoBaroSensorNo }
|
||
::= { wtWebGraphThermoBaroTempValueTable 1 }
|
||
|
||
WtWebGraphThermoBaroTempValueEntry ::= SEQUENCE{
|
||
wtWebGraphThermoBaroTempValue OCTET STRING
|
||
}
|
||
|
||
wtWebGraphThermoBaroTempValue OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (5))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Messwert des Sensors, ASCII, 5 Zeichen lang."
|
||
::= { wtWebGraphThermoBaroTempValueEntry 1 }
|
||
|
||
-- wtWebGraphThermoBaroBinaryTempValue Table
|
||
|
||
wtWebGraphThermoBaroBinaryTempValueTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebGraphThermoBaroBinaryTempValueEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Liste bin<69>rer Messwerte korrespondiernd zu den Kanalnummern."
|
||
::= { wtWebGraphThermoBaroTemp 4 }
|
||
|
||
wtWebGraphThermoBaroBinaryTempValueEntry OBJECT-TYPE
|
||
SYNTAX WtWebGraphThermoBaroBinaryTempValueEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bin<69>re Messwerte der Sensoren."
|
||
INDEX { wtWebGraphThermoBaroSensorNo }
|
||
::= { wtWebGraphThermoBaroBinaryTempValueTable 1 }
|
||
|
||
WtWebGraphThermoBaroBinaryTempValueEntry ::= SEQUENCE{
|
||
wtWebGraphThermoBaroBinaryTempValue INTEGER
|
||
}
|
||
|
||
wtWebGraphThermoBaroBinaryTempValue OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bin<69>rer Messwert des Sensors in 1/10 Grad Celcius oder 1/10 Prozent,
|
||
vorzeichenbehaftete Zahl, der Wert 0x4FFF6 zeigt einen
|
||
ung<6E>ltigen Messwert an."
|
||
::= { wtWebGraphThermoBaroBinaryTempValueEntry 1 }
|
||
|
||
-- wtWebGraphThermoBaroTempValuePkt Table
|
||
|
||
wtWebGraphThermoBaroTempValuePktTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebGraphThermoBaroTempValuePktEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Liste Temperaturwerte korrespondiernd zu den Kanalnummern."
|
||
::= { wtWebGraphThermoBaroTemp 8 }
|
||
|
||
wtWebGraphThermoBaroTempValuePktEntry OBJECT-TYPE
|
||
SYNTAX WtWebGraphThermoBaroTempValuePktEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Temperaturen der Sensoren."
|
||
INDEX { wtWebGraphThermoBaroSensorNo }
|
||
::= { wtWebGraphThermoBaroTempValuePktTable 1 }
|
||
|
||
WtWebGraphThermoBaroTempValuePktEntry ::= SEQUENCE{
|
||
wtWebGraphThermoBaroTempValuePkt OCTET STRING
|
||
}
|
||
|
||
wtWebGraphThermoBaroTempValuePkt OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (5))
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Temperaturwert des Sensors, ASCII, 5 Zeichen lang, dezimal Punkt."
|
||
::= { wtWebGraphThermoBaroTempValuePktEntry 1 }
|
||
|
||
-- wtWebGraphThermoBaroSessCntrl Group
|
||
--------------------------------
|
||
|
||
wtWebGraphThermoBaroSessCntrlPassword OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Durch Eintrag diese Passworts wird eine Session er<65>ffnet, die durch Schreiben einer 1
|
||
in wtWebGraphThermoBaroSessCntrlLogout beendet wird. Gelesen liefert diese Variable einen String der
|
||
L<>nge Null."
|
||
::= { wtWebGraphThermoBaroSessCntrl 1 }
|
||
|
||
wtWebGraphThermoBaroSessCntrlConfigMode OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebGraphThermoBaroSessCntrl-NoSession(0),
|
||
wtWebGraphThermoBaroSessCntrl-Session(1)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Wenn sich das Ger<65>t im SNMP-Konfigurationsmodus befindet, wird der Wert
|
||
1 zur<75>ckgeliefert, ansonsten 0. Ist der ausgelesene Wert 0
|
||
obwohl das Passwort geschrieben wurde, befindet sich das Ger<65>t bereits
|
||
im Configmodus und die Variablen k<>nnen nur gelesen werden."
|
||
::= { wtWebGraphThermoBaroSessCntrl 2 }
|
||
|
||
wtWebGraphThermoBaroSessCntrlLogout OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Wenn sich das Ger<65>t im Konfigurationsmodus befindet und die Session wurde
|
||
von diesem SNMP Manager er<65>ffnet, kann durch Schreiben einer 1 in diese
|
||
Variable die Session beendet werden und alle Parameter werden gespeichert.
|
||
Durch Schreiben einer 2 werden alle Eingaben wieder verworfen.
|
||
Gelesen liefert diese Variable den Wert 0."
|
||
::= { wtWebGraphThermoBaroSessCntrl 3 }
|
||
|
||
wtWebGraphThermoBaroSessCntrlAdminPassword OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Dieses Passwort sch<63>tzt den Zugang der Variablen mit Administratorrechten. Es kann nur vom
|
||
Administrator ver<65>ndert werden. Wurde kein Passwort vergeben so ist public das g<>ltige Passwort.
|
||
Gelesen liefert diese Variable einen Null-Pointer."
|
||
::= { wtWebGraphThermoBaroSessCntrl 4 }
|
||
|
||
wtWebGraphThermoBaroSessCntrlConfigPassword OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Dieses Passwort sch<63>tzt den Zugang der Variablen mit Configuratorrechten. Es kann vom
|
||
Administrator und vom Configurator ver<65>ndert werden. Wurde kein Passwort vergeben so ist
|
||
public das g<>ltige Passwort.Gelesen liefert diese Variable einen Null-Pointer."
|
||
::= { wtWebGraphThermoBaroSessCntrl 5 }
|
||
|
||
|
||
-- wtWebGraphThermoBaroText Group
|
||
------------------------
|
||
|
||
wtWebGraphThermoBaroDeviceName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name des Webio's, der userdefinierbar ist."
|
||
::= { wtWebGraphThermoBaroText 1 }
|
||
|
||
wtWebGraphThermoBaroDeviceText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Beschreibung des Webio's, die userdefinierbar ist."
|
||
::= { wtWebGraphThermoBaroText 2 }
|
||
|
||
wtWebGraphThermoBaroDeviceLocation OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Aufstellort des Webio's, die userdefinierbar ist."
|
||
::= { wtWebGraphThermoBaroText 3 }
|
||
|
||
wtWebGraphThermoBaroDeviceContact OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Kontaktadresse im Servicefall des Webio's, die userdefinierbar ist."
|
||
::= { wtWebGraphThermoBaroText 4 }
|
||
|
||
-- wtWebGraphThermoBaroTimeZone Group
|
||
----------------------------
|
||
|
||
wtWebGraphThermoBaroTzOffsetHrs OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset Stunden der Zeitzone (Winterzeit) in Bezug auf UTC."
|
||
::= { wtWebGraphThermoBaroTimeZone 1 }
|
||
|
||
wtWebGraphThermoBaroTzOffsetMin OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset Minuten der Zeitzone (Winterzeit) in Bezug auf UTC."
|
||
::= { wtWebGraphThermoBaroTimeZone 2 }
|
||
|
||
wtWebGraphThermoBaroTzEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bin<69>r kodierte Bedingung:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 1-7: ungenutzt
|
||
Bit 0 : Apply Timezone"
|
||
::= { wtWebGraphThermoBaroTimeZone 3 }
|
||
|
||
wtWebGraphThermoBaroStTzOffsetHrs OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset Stunden der Zeitzone (Sommerzeit) in Bezug auf UTC."
|
||
::= { wtWebGraphThermoBaroTimeZone 4 }
|
||
|
||
wtWebGraphThermoBaroStTzOffsetMin OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset Minuten der Zeitzone (Sommerzeit) in Bezug auf UTC."
|
||
::= { wtWebGraphThermoBaroTimeZone 5 }
|
||
|
||
wtWebGraphThermoBaroStTzEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bin<69>r kodierte Bedingung:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 1-7: ungenutzt
|
||
Bit 0 : Apply Summertime"
|
||
::= { wtWebGraphThermoBaroTimeZone 6 }
|
||
|
||
wtWebGraphThermoBaroStTzStartMonth OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebGraphThermoBaroStartMonth-January(1),
|
||
wtWebGraphThermoBaroStartMonth-February(2),
|
||
wtWebGraphThermoBaroStartMonth-March(3),
|
||
wtWebGraphThermoBaroStartMonth-April(4),
|
||
wtWebGraphThermoBaroStartMonth-May(5),
|
||
wtWebGraphThermoBaroStartMonth-June(6),
|
||
wtWebGraphThermoBaroStartMonth-July(7),
|
||
wtWebGraphThermoBaroStartMonth-August(8),
|
||
wtWebGraphThermoBaroStartMonth-September(9),
|
||
wtWebGraphThermoBaroStartMonth-October(10),
|
||
wtWebGraphThermoBaroStartMonth-November(11),
|
||
wtWebGraphThermoBaroStartMonth-December(12)
|
||
}
|
||
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Monat, in dem von Winterzeit auf Sommerzeit umgestellt wird."
|
||
::= { wtWebGraphThermoBaroTimeZone 7 }
|
||
|
||
wtWebGraphThermoBaroStTzStartMode OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebGraphThermoBaroStartMode-first(1),
|
||
wtWebGraphThermoBaroStartMode-second(2),
|
||
wtWebGraphThermoBaroStartMode-third(3),
|
||
wtWebGraphThermoBaroStartMode-fourth(4),
|
||
wtWebGraphThermoBaroStartMode-last(5)
|
||
}
|
||
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Modus des Wochentages, bei dem von Winterzeit auf Sommerzeit umgestellt wird."
|
||
::= { wtWebGraphThermoBaroTimeZone 8 }
|
||
|
||
wtWebGraphThermoBaroStTzStartWday OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebGraphThermoBaroStartWday-Sunday(1),
|
||
wtWebGraphThermoBaroStartWday-Monday(2),
|
||
wtWebGraphThermoBaroStartWday-Tuesday(3),
|
||
wtWebGraphThermoBaroStartWday-Thursday(4),
|
||
wtWebGraphThermoBaroStartWday-Wednesday(5),
|
||
wtWebGraphThermoBaroStartWday-Friday(6),
|
||
wtWebGraphThermoBaroStartWday-Saturday(7)
|
||
}
|
||
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Wochentag, bei dem von Winterzeit auf Sommerzeit umgestellt wird"
|
||
::= { wtWebGraphThermoBaroTimeZone 9 }
|
||
|
||
wtWebGraphThermoBaroStTzStartHrs OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Stunde, in der die Zeitzone von Winter auf Sommerzeit in Bezug auf UTC
|
||
umgestellt wird."
|
||
::= { wtWebGraphThermoBaroTimeZone 10 }
|
||
|
||
wtWebGraphThermoBaroStTzStartMin OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Minute, in der die Zeitzone von Winter auf Sommerzeit in Bezug auf UTC
|
||
umgestellt wird."
|
||
::= { wtWebGraphThermoBaroTimeZone 11 }
|
||
|
||
wtWebGraphThermoBaroStTzStopMonth OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebGraphThermoBaroStopMonth-January(1),
|
||
wtWebGraphThermoBaroStopMonth-February(2),
|
||
wtWebGraphThermoBaroStopMonth-March(3),
|
||
wtWebGraphThermoBaroStopMonth-April(4),
|
||
wtWebGraphThermoBaroStopMonth-May(5),
|
||
wtWebGraphThermoBaroStopMonth-June(6),
|
||
wtWebGraphThermoBaroStopMonth-July(7),
|
||
wtWebGraphThermoBaroStopMonth-August(8),
|
||
wtWebGraphThermoBaroStopMonth-September(9),
|
||
wtWebGraphThermoBaroStopMonth-October(10),
|
||
wtWebGraphThermoBaroStopMonth-November(11),
|
||
wtWebGraphThermoBaroStopMonth-December(12)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Monat, bei dem von Sommerzeit auf Winterzeit umgestellt wird."
|
||
::= { wtWebGraphThermoBaroTimeZone 12 }
|
||
|
||
wtWebGraphThermoBaroStTzStopMode OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebGraphThermoBaroStopMode-first(1),
|
||
wtWebGraphThermoBaroStopMode-second(2),
|
||
wtWebGraphThermoBaroStopMode-third(3),
|
||
wtWebGraphThermoBaroStopMode-fourth(4),
|
||
wtWebGraphThermoBaroStopMode-last(5)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Modus des Wochentages, bei dem von Sommerzeit auf Winterzeit umgestellt wird."
|
||
::= { wtWebGraphThermoBaroTimeZone 13 }
|
||
|
||
wtWebGraphThermoBaroStTzStopWday OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebGraphThermoBaroStopWday-Sunday(1),
|
||
wtWebGraphThermoBaroStopWday-Monday(2),
|
||
wtWebGraphThermoBaroStopWday-Tuesday(3),
|
||
wtWebGraphThermoBaroStopWday-Thursday(4),
|
||
wtWebGraphThermoBaroStopWday-Wednesday(5),
|
||
wtWebGraphThermoBaroStopWday-Friday(6),
|
||
wtWebGraphThermoBaroStopWday-Saturday(7)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Wochentage, bei dem von Sommerzeit auf Winterzeit umgestellt wird."
|
||
::= { wtWebGraphThermoBaroTimeZone 14 }
|
||
|
||
wtWebGraphThermoBaroStTzStopHrs OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Stunde, in der die Zeitzone von Sommer auf Winterzeit in Bezug auf UTC
|
||
umgestellt wird."
|
||
::= { wtWebGraphThermoBaroTimeZone 15 }
|
||
|
||
wtWebGraphThermoBaroStTzStopMin OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Minute, in der die Zeitzone von Sommer auf Winterzeit in Bezug auf UTC
|
||
umgestellt wird."
|
||
::= { wtWebGraphThermoBaroTimeZone 16 }
|
||
|
||
-- wtWebGraphThermoBaroTimeServer Group
|
||
----------------------------
|
||
|
||
wtWebGraphThermoBaroTimeServer1 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"IP-Adresse oder Name des 1. Time Servers in ASCII"
|
||
::= { wtWebGraphThermoBaroTimeServer 1 }
|
||
|
||
wtWebGraphThermoBaroTimeServer2 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"IP-Adresse oder Name des 2. Time Servers in ASCII"
|
||
::= { wtWebGraphThermoBaroTimeServer 2 }
|
||
|
||
wtWebGraphThermoBaroTsEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bin<69>r kodierte Bedingung:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 1-7: ungenutzt
|
||
Bit 0 : Apply Time Server"
|
||
::= { wtWebGraphThermoBaroTimeServer 3 }
|
||
|
||
wtWebGraphThermoBaroTsSyncTime OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Die Abfrage der Timeserver erfolgt zu dieser vollen Stunde (0-23)."
|
||
::= { wtWebGraphThermoBaroTimeServer 4 }
|
||
|
||
-- wtWebGraphThermoBaroDeviceClock Group
|
||
----------------------------
|
||
|
||
wtWebGraphThermoBaroClockHrs OBJECT-TYPE
|
||
SYNTAX INTEGER (0..23)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Uhrzeit Stunde, unter Ber<65>cksichtigung der Zeitzoneneinstellungen."
|
||
::= { wtWebGraphThermoBaroDeviceClock 1 }
|
||
|
||
wtWebGraphThermoBaroClockMin OBJECT-TYPE
|
||
SYNTAX INTEGER (0..59)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Uhrzeit Minute, unter Ber<65>cksichtigung der Zeitzoneneinstellungen."
|
||
::= { wtWebGraphThermoBaroDeviceClock 2 }
|
||
|
||
wtWebGraphThermoBaroClockDay OBJECT-TYPE
|
||
SYNTAX INTEGER (1..31)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Datum: Tag des Monats, unter Ber<65>cksichtigung der Zeitzoneneinstellungen."
|
||
::= { wtWebGraphThermoBaroDeviceClock 3 }
|
||
|
||
wtWebGraphThermoBaroClockMonth OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebGraphThermoBaroClockMonth-January(1),
|
||
wtWebGraphThermoBaroClockMonth-February(2),
|
||
wtWebGraphThermoBaroClockMonth-March(3),
|
||
wtWebGraphThermoBaroClockMonth-April(4),
|
||
wtWebGraphThermoBaroClockMonth-May(5),
|
||
wtWebGraphThermoBaroClockMonth-June(6),
|
||
wtWebGraphThermoBaroClockMonth-July(7),
|
||
wtWebGraphThermoBaroClockMonth-August(8),
|
||
wtWebGraphThermoBaroClockMonth-September(9),
|
||
wtWebGraphThermoBaroClockMonth-October(10),
|
||
wtWebGraphThermoBaroClockMonth-November(11),
|
||
wtWebGraphThermoBaroClockMonth-December(12)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Datum: Monat, unter Ber<65>cksichtigung der Zeitzoneneinstellungen."
|
||
::= { wtWebGraphThermoBaroDeviceClock 4 }
|
||
|
||
wtWebGraphThermoBaroClockYear OBJECT-TYPE
|
||
SYNTAX INTEGER (0..65535)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Datum: Jahr, unter Ber<65>cksichtigung der Zeitzoneneinstellungen."
|
||
::= { wtWebGraphThermoBaroDeviceClock 5 }
|
||
|
||
|
||
-- wtWebGraphThermoBaroNetwork Group
|
||
------------------------
|
||
|
||
wtWebGraphThermoBaroIpAddress OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"IP-Adresse des Webio's"
|
||
::= { wtWebGraphThermoBaroNetwork 1 }
|
||
|
||
wtWebGraphThermoBaroSubnetMask OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Subnetmask des Webio's"
|
||
::= { wtWebGraphThermoBaroNetwork 2 }
|
||
|
||
wtWebGraphThermoBaroGateway OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Gateway des Webio's"
|
||
::= { wtWebGraphThermoBaroNetwork 3 }
|
||
|
||
wtWebGraphThermoBaroDnsServer1 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"IP-Adresse des 1. DNS Servers in ASCII"
|
||
::= { wtWebGraphThermoBaroNetwork 4 }
|
||
|
||
wtWebGraphThermoBaroDnsServer2 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"IP-Adresse des 2. DNS Servers in ASCII"
|
||
::= { wtWebGraphThermoBaroNetwork 5 }
|
||
|
||
wtWebGraphThermoBaroAddConfig OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Zusatzkonfiguration (1=EIN):
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 1: DHCP disable
|
||
Bit 0: BOOTP disable
|
||
"
|
||
::= { wtWebGraphThermoBaroNetwork 6 }
|
||
|
||
-- wtWebGraphThermoBaroHTTP Group
|
||
--------------------------------
|
||
|
||
wtWebGraphThermoBaroStartup OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Legt die Startseite fest, nur eine Auswahl zul<75>ssig:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 2: user.htm
|
||
Bit 1: home.htm
|
||
Bit 0: index.htm"
|
||
::= { wtWebGraphThermoBaroHTTP 1 }
|
||
|
||
wtWebGraphThermoBaroGetHeaderEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Wenn freigeschaltet, wird eine Erkennungssequenz und /oder ein HTTP-Kopf nach
|
||
jeder GET-Anfrage der Antwort vorangestellt:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 1-6: ungenutzt
|
||
Bit 1 : GET HTTP enable
|
||
Bit 0 : GET Header enable"
|
||
::= { wtWebGraphThermoBaroHTTP 2 }
|
||
|
||
wtWebGraphThermoBaroHttpPort OBJECT-TYPE
|
||
SYNTAX INTEGER (1..65535)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"HTTP Port, an den die TCP-Anfragen gesendet werden k<>nnen (Default: 80)."
|
||
::= { wtWebGraphThermoBaroHTTP 3 }
|
||
|
||
-- wtWebGraphThermoBaroMail Group
|
||
--------------------------------
|
||
|
||
wtWebGraphThermoBaroMailAdName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Ger<65>tename f<>r die Mail-Administration."
|
||
::= { wtWebGraphThermoBaroMail 1 }
|
||
|
||
wtWebGraphThermoBaroMailReply OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Reply-Adresse f<>r den Mailserver."
|
||
::= { wtWebGraphThermoBaroMail 2 }
|
||
|
||
wtWebGraphThermoBaroMailServer OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name oder Ip-Adresse des Mailservers."
|
||
::= { wtWebGraphThermoBaroMail 3 }
|
||
|
||
wtWebGraphThermoBaroMailEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Erlaubt das versenden von Mails:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 1-7: ungenutzt
|
||
Bit 0 : Mail enable"
|
||
::= { wtWebGraphThermoBaroMail 4 }
|
||
|
||
wtWebGraphThermoBaroMailAuthentication OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE (4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Auswahl des Authenticationmodi:
|
||
die OCTETS werden bitweise interpretiert, es darf nur ein Bit gesetzt sein.
|
||
Bit 0 entspricht dem LSB.
|
||
OCTET 1: ungenutzt
|
||
OCTET 2: ungenutzt
|
||
OCTET 3: ungenutzt
|
||
OCTET 4: Bit 3-7: ungenutzt
|
||
Bit 2 : POP3 vor SMTP
|
||
Bit 1 : ESMTP, Authentifizierung
|
||
Bit 0 : SMTP, keine Authentifizierung"
|
||
::= { wtWebGraphThermoBaroMail 5 }
|
||
|
||
wtWebGraphThermoBaroMailAuthUser OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name des Postfaches / Postfachusers."
|
||
::= { wtWebGraphThermoBaroMail 6 }
|
||
|
||
wtWebGraphThermoBaroMailAuthPassword OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Passwort zur Identifizierung des Users."
|
||
::= { wtWebGraphThermoBaroMail 7 }
|
||
|
||
wtWebGraphThermoBaroMailPop3Server OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name oder Ip-Adresse des POP3 Servers."
|
||
::= { wtWebGraphThermoBaroMail 8 }
|
||
|
||
-- wtWebGraphThermoBaroSNMP Group
|
||
--------------------------------
|
||
|
||
wtWebGraphThermoBaroSnmpCommunityStringRead OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Community string read only"
|
||
::= { wtWebGraphThermoBaroSNMP 1 }
|
||
|
||
wtWebGraphThermoBaroSnmpCommunityStringReadWrite OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Community string read / write"
|
||
::= { wtWebGraphThermoBaroSNMP 2 }
|
||
|
||
wtWebGraphThermoBaroSystemTrapManagerIP OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name oder IP-Adresse des SNMP-Managers, der den System Trap entgegen nimmt."
|
||
::= { wtWebGraphThermoBaroSNMP 3 }
|
||
|
||
wtWebGraphThermoBaroSystemTrapEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bin<69>r kodierte Triggerbedingungen:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 0: ColdStart
|
||
Bit 1: WarmStart
|
||
Bit 2-7: ungenutzt"
|
||
::= { wtWebGraphThermoBaroSNMP 4 }
|
||
|
||
wtWebGraphThermoBaroSnmpEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bit 0 schaltet SNMP frei:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 1-7: ungenutzt
|
||
Bit 0 : SNMP enable"
|
||
::= { wtWebGraphThermoBaroSNMP 5 }
|
||
|
||
wtWebGraphThermoBaroSnmpCommunityStringTrap OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Community string der Traps."
|
||
::= { wtWebGraphThermoBaroSNMP 6 }
|
||
|
||
|
||
-- wtWebGraphThermoBaroUDP Group
|
||
--------------------------------
|
||
|
||
wtWebGraphThermoBaroUdpPort OBJECT-TYPE
|
||
SYNTAX INTEGER (1..65535)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Udp Port, an den die Udp-Anfragen GET Single gesendet werden k<>nnen"
|
||
::= { wtWebGraphThermoBaroUDP 1 }
|
||
|
||
wtWebGraphThermoBaroUdpEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Schaltet UDP frei:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 1-7: ungenutzt
|
||
Bit 0 : UDP enable"
|
||
::= { wtWebGraphThermoBaroUDP 2 }
|
||
|
||
-- wtWebGraphThermoBaroSyslog Group
|
||
--------------------------------
|
||
|
||
wtWebGraphThermoBaroSyslogServerIP OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name oder IP-Adresse des Syslog-Servers, der die Syslog-Nachricht entgegen nimmt."
|
||
::= { wtWebGraphThermoBaroSyslog 1 }
|
||
|
||
wtWebGraphThermoBaroSyslogServerPort OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Portnummer des Syslog-Servers, default ist 514."
|
||
::= { wtWebGraphThermoBaroSyslog 2 }
|
||
|
||
wtWebGraphThermoBaroSyslogSystemMessagesEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bin<69>r kodierte Triggerbedingungen:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 0: ColdStart
|
||
Bit 1: WarmStart
|
||
Bit 2: Diag Messages
|
||
Bit 3-7: ungenutzt"
|
||
::= { wtWebGraphThermoBaroSyslog 3 }
|
||
|
||
wtWebGraphThermoBaroSyslogEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bit 0 schaltet Syslog frei:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 1-7: ungenutzt
|
||
Bit 0 : Syslog enable"
|
||
::= { wtWebGraphThermoBaroSyslog 4 }
|
||
|
||
-- wtWebGraphThermoBaroFTP Group
|
||
--------------------------------
|
||
|
||
wtWebGraphThermoBaroFTPServerIP OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name oder IP-Adresse des FTP-Servers, der die FTP-Nachricht entgegen nimmt."
|
||
::= { wtWebGraphThermoBaroFTP 1 }
|
||
|
||
wtWebGraphThermoBaroFTPServerControlPort OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Portnummer des Kontrollports des FTP-Servers, default ist 21."
|
||
::= { wtWebGraphThermoBaroFTP 2 }
|
||
|
||
wtWebGraphThermoBaroFTPUserName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"FTP Loggin: Name des Anwenders."
|
||
::= { wtWebGraphThermoBaroFTP 3 }
|
||
|
||
wtWebGraphThermoBaroFTPPassword OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"FTP Loggin: Passwort des Anwenders."
|
||
::= { wtWebGraphThermoBaroFTP 4 }
|
||
|
||
wtWebGraphThermoBaroFTPAccount OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"FTP Loggin: Account-Name des Anwenderkontos."
|
||
::= { wtWebGraphThermoBaroFTP 5 }
|
||
|
||
wtWebGraphThermoBaroFTPOption OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bit 0 schaltet den FTP Server in den Passiv-Modus,
|
||
der Client kontrolliert die Datenverbindung allein:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 1-7: ungenutzt
|
||
Bit 0 : PASV enable"
|
||
::= { wtWebGraphThermoBaroFTP 6 }
|
||
|
||
wtWebGraphThermoBaroFTPEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bit 0 schaltet FTP frei:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 1-7: ungenutzt
|
||
Bit 0 : FTP enable"
|
||
::= { wtWebGraphThermoBaroFTP 7 }
|
||
|
||
|
||
-- wtWebGraphThermoBaroDatalogger Group
|
||
--------------------------------
|
||
|
||
wtWebGraphThermoBaroLoggerTimebase OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
wtWebGraphThermoBaroDatalogger-1Min(1),
|
||
wtWebGraphThermoBaroDatalogger-5Min(2),
|
||
wtWebGraphThermoBaroDatalogger-15Min(3),
|
||
wtWebGraphThermoBaroDatalogger-60Min(4)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Zeitbasis des Dataloggers"
|
||
::= { wtWebGraphThermoBaroDatalogger 1 }
|
||
|
||
wtWebGraphThermoBaroLoggerSensorSel OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bin<69>r kodierte Triggerbedingungen:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 0 : Sensor 1
|
||
Bit 1 : Sensor 2
|
||
Bit 2-7: ungenutzt"
|
||
::= { wtWebGraphThermoBaroDatalogger 2 }
|
||
|
||
|
||
-- wtWebGraphThermoBaroRSS Group
|
||
--------------------------------
|
||
|
||
wtWebGraphThermoBaroRSSChannelTitle OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name des RSS Feeds."
|
||
::= { wtWebGraphThermoBaroRSS 1 }
|
||
|
||
wtWebGraphThermoBaroRSSChannelLink OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Link des RSS Feeds."
|
||
::= { wtWebGraphThermoBaroRSS 2 }
|
||
|
||
wtWebGraphThermoBaroRSSChannelDescription OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Beschreibungstext des RSS Feeds."
|
||
::= { wtWebGraphThermoBaroRSS 3 }
|
||
|
||
wtWebGraphThermoBaroRSSChannelImage OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Link zu eine Bild, dass mit dem Datens<6E>tzen in der Kopfzeile angezeigt wird."
|
||
::= { wtWebGraphThermoBaroRSS 4 }
|
||
|
||
wtWebGraphThermoBaroRSSChannelImageTitle OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name des Bildes."
|
||
::= { wtWebGraphThermoBaroRSS 5 }
|
||
|
||
wtWebGraphThermoBaroRSSChannelImageLink OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Link, der dem Bild in der Kopfzeile hinterlegt wird."
|
||
::= { wtWebGraphThermoBaroRSS 6 }
|
||
|
||
wtWebGraphThermoBaroRSSChannelItemTitle OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name des RSS Feeds Eintrages."
|
||
::= { wtWebGraphThermoBaroRSS 7 }
|
||
|
||
wtWebGraphThermoBaroRSSChannelItemLink OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Link des RSS Feeds Eintrages."
|
||
::= { wtWebGraphThermoBaroRSS 8 }
|
||
|
||
wtWebGraphThermoBaroRSSChannelItemDescription OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Text des RSS Feeds Eintrages."
|
||
::= { wtWebGraphThermoBaroRSS 9 }
|
||
|
||
wtWebGraphThermoBaroRSSChannelItemQuantity OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Anzahl der auszugebenen RSS Feeds Eintr<74>ge."
|
||
::= { wtWebGraphThermoBaroRSS 10 }
|
||
|
||
-- wtWebGraphThermoBaroAlarm Group
|
||
--------------------------------
|
||
|
||
wtWebGraphThermoBaroAlarmCount OBJECT-TYPE
|
||
SYNTAX INTEGER (1..8)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Anzahl der unabh<62>ngigen Alarme."
|
||
::= { wtWebGraphThermoBaroAlarm 1 }
|
||
|
||
-- Alarm Interface Table
|
||
|
||
wtWebGraphThermoBaroAlarmIfTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebGraphThermoBaroAlarmIfEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Liste der Alarmindizes."
|
||
::= { wtWebGraphThermoBaroAlarm 2 }
|
||
|
||
wtWebGraphThermoBaroAlarmIfEntry OBJECT-TYPE
|
||
SYNTAX WtWebGraphThermoBaroAlarmIfEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Nummern der Alarme."
|
||
INDEX { wtWebGraphThermoBaroAlarmNo }
|
||
::= { wtWebGraphThermoBaroAlarmIfTable 1 }
|
||
|
||
WtWebGraphThermoBaroAlarmIfEntry ::= SEQUENCE {
|
||
wtWebGraphThermoBaroAlarmNo INTEGER
|
||
}
|
||
|
||
wtWebGraphThermoBaroAlarmNo OBJECT-TYPE
|
||
SYNTAX INTEGER (1..8)
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Nummer des Alarms."
|
||
::= { wtWebGraphThermoBaroAlarmIfEntry 1 }
|
||
|
||
-- Alarm Table
|
||
|
||
wtWebGraphThermoBaroAlarmTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebGraphThermoBaroAlarmEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Liste der Einstellungen abh<62>ngig von der Alarmnummer."
|
||
::= { wtWebGraphThermoBaroAlarm 3 }
|
||
|
||
wtWebGraphThermoBaroAlarmEntry OBJECT-TYPE
|
||
SYNTAX WtWebGraphThermoBaroAlarmEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Alarm-Parameter der einzelnen Alarme."
|
||
INDEX { wtWebGraphThermoBaroAlarmNo }
|
||
::= { wtWebGraphThermoBaroAlarmTable 1 }
|
||
|
||
WtWebGraphThermoBaroAlarmEntry ::= SEQUENCE {
|
||
wtWebGraphThermoBaroAlarmTrigger OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmMin OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmMax OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmHysteresis OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmDelay OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmInterval OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmEnable OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmEMailAddr OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmMailSubject OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmMailText OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmManagerIP OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmTrapText OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmMailOptions OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmTcpIpAddr OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmTcpPort INTEGER,
|
||
wtWebGraphThermoBaroAlarmTcpText OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmClearMailSubject OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmClearMailText OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmClearTrapText OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmClearTcpText OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmDeltaTemp OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmRHMin OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmRHMax OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmRHHysteresis OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmAHMin OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmAHMax OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmSyslogIpAddr OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmSyslogPort INTEGER,
|
||
wtWebGraphThermoBaroAlarmSyslogText OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmSyslogClearText OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmFtpDataPort OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmFtpFileName OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmFtpText OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmFtpClearText OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmFtpOption OCTET STRING,
|
||
wtWebGraphThermoBaroAlarmTimerCron OCTET STRING
|
||
|
||
}
|
||
|
||
wtWebGraphThermoBaroAlarmTrigger OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bin<69>r kodierte Triggerbedingungen:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3:
|
||
Bit 0: Timer
|
||
Bit 1: ColdStart
|
||
Bit 2: WarmStart
|
||
Bit 3: Sensor lost
|
||
Bit 4-7 ungenutzt
|
||
Octet 4:
|
||
Bit 0: Sensor 1
|
||
Bit 1: Sensor 2
|
||
Bit 2-7: ungenutzt"
|
||
::= { wtWebGraphThermoBaroAlarmEntry 1 }
|
||
|
||
wtWebGraphThermoBaroAlarmMin OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Minimum Temperatur in Grad mit maximal 2 Nachkommastellen."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 2 }
|
||
|
||
wtWebGraphThermoBaroAlarmMax OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Maximum Temperatur in Grad mit maximal 2 Nachkommastellen."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 3 }
|
||
|
||
wtWebGraphThermoBaroAlarmHysteresis OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bei <20>berschreiten der Temperatur Min+Hyst. und Unterschreiten der Temperatur Max-Hyst.
|
||
wird der Alarm gel<65>scht: pos. Temperaturdifferenz in Grad mit maximal 2 Nachkommastellen."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 4 }
|
||
|
||
wtWebGraphThermoBaroAlarmDelay OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Der Alarm wird erst ausgel<65>st, wenn f<>r die Dauer dieser Zeit
|
||
die Alarmbedingungen erf<72>llt sind (Zeit in Minuten)."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 5 }
|
||
|
||
wtWebGraphThermoBaroAlarmInterval OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Sendeintervall von Alarmmeldungen."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 6 }
|
||
|
||
wtWebGraphThermoBaroAlarmEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bin<69>r kodierte Alarmfreischaltung:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 0: Mail Enable
|
||
Bit 1: SNMP Trap enable
|
||
Bit 2: TCP Client enable"
|
||
::= { wtWebGraphThermoBaroAlarmEntry 7 }
|
||
|
||
wtWebGraphThermoBaroAlarmEMailAddr OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"E-Mail Adresse, an die die Alarmmail gesendet werden soll."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 8 }
|
||
|
||
wtWebGraphThermoBaroAlarmMailSubject OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Betreffzeile der Alarmmail."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 9 }
|
||
|
||
wtWebGraphThermoBaroAlarmMailText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Text der Alarmmail: <Tn> liefert die aktuelle Temperatur; n = 1..8.
|
||
<Z> liefert die aktuelle Zeit."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 10 }
|
||
|
||
wtWebGraphThermoBaroAlarmManagerIP OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name oder IP-Adresse des SNMP-Managers, der den Trap entgegen nimmt."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 11 }
|
||
|
||
wtWebGraphThermoBaroAlarmTrapText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Dieser Text wird im Trapbody gesendet."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 12 }
|
||
|
||
wtWebGraphThermoBaroAlarmMailOptions OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bin<69>r kodierte Optionen:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 0 : Attach Thermo.csv Enable
|
||
Bit 1 : CSV-Data_since_last_report
|
||
Bit 2-7: ungenutzt"
|
||
::= { wtWebGraphThermoBaroAlarmEntry 13 }
|
||
|
||
wtWebGraphThermoBaroAlarmTcpIpAddr OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"IP-Adresse des Ger<65>tes, dass eine TCP-Nachricht empfangen soll."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 14 }
|
||
|
||
wtWebGraphThermoBaroAlarmTcpPort OBJECT-TYPE
|
||
SYNTAX INTEGER (1..65535)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Portnummer des Ger<65>tes, dass eine TCP-Nachricht empfangen soll."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 15 }
|
||
|
||
wtWebGraphThermoBaroAlarmTcpText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Dieser Text wird im TCP Trapbody gesendet."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 16 }
|
||
|
||
wtWebGraphThermoBaroAlarmClearMailSubject OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Betreffzeile der Alarm Clear Mail."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 17 }
|
||
|
||
wtWebGraphThermoBaroAlarmClearMailText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Text der Alarm Clear Mail: <Tn> liefert die aktuelle Temperatur; n = 1..8.
|
||
<Z> liefert die aktuelle Zeit."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 18 }
|
||
|
||
wtWebGraphThermoBaroAlarmClearTrapText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Dieser Text wird im Trapbody gesendet."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 19 }
|
||
|
||
wtWebGraphThermoBaroAlarmClearTcpText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Dieser Text wird im TCP Trapbody gesendet."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 20 }
|
||
|
||
wtWebGraphThermoBaroAlarmDeltaTemp OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Maximale Temperatur<75>nderung in Grad/min mit maximal 2 Nachkommastellen.
|
||
Es wird ein Mittelwert einer Periode von 5 Minuten verglichen."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 21 }
|
||
|
||
wtWebGraphThermoBaroAlarmRHMin OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Minimum rel. Feuchte in Prozent mit maximal 2 Nachkommastellen."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 22 }
|
||
|
||
wtWebGraphThermoBaroAlarmRHMax OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Maximum rel.Feuchte in Prozent mit maximal 2 Nachkommastellen."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 23 }
|
||
|
||
wtWebGraphThermoBaroAlarmRHHysteresis OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Hysterese rel. Feuchte in Prozent mit maximal 2 Nachkommastellen."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 24 }
|
||
|
||
wtWebGraphThermoBaroAlarmAHMin OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Minimum abs. Feuchte in g/(m*m*m) mit maximal 2 Nachkommastellen."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 25 }
|
||
|
||
wtWebGraphThermoBaroAlarmAHMax OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Maximum abs. Feuchte in g/(m*m*m) mit maximal 2 Nachkommastellen."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 26 }
|
||
|
||
wtWebGraphThermoBaroAlarmSyslogIpAddr OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"IP-Adresse des Ger<65>tes, dass eine Syslog-Nachricht empfangen soll."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 27 }
|
||
|
||
wtWebGraphThermoBaroAlarmSyslogPort OBJECT-TYPE
|
||
SYNTAX INTEGER (1..65535)
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Portnummer des Ger<65>tes, dass eine Syslog-Nachricht empfangen soll, default Port ist 514."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 28 }
|
||
|
||
wtWebGraphThermoBaroAlarmSyslogText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Jede Syslog-Nachricht beginnt mit einem Priorit<69>tsschl<68>ssel, einem Zeitstempel und der Host Ip-Nummer gem<65><6D> RFC3164.
|
||
Dieser Text wird im darauf folgenden Syslog-Nachrichtenteil gesendet."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 29 }
|
||
|
||
wtWebGraphThermoBaroAlarmSyslogClearText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Jede Syslog-Nachricht beginnt mit einem Priorit<69>tsschl<68>ssel, einem Zeitstempel und der Host Ip-Nummer gem<65><6D> RFC3164.
|
||
Dieser Text wird im darauf folgenden Syslog-Nachrichtenteil gesendet."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 30 }
|
||
|
||
wtWebGraphThermoBaroAlarmFtpDataPort OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Lokaler Datenport: 1..65535 oder AUTO: der n<>chste ungenutzte Port wird automatisch zugewiesen."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 31 }
|
||
|
||
wtWebGraphThermoBaroAlarmFtpFileName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Der File Name kann auch Pfadinformationen enthalten."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 32 }
|
||
|
||
wtWebGraphThermoBaroAlarmFtpText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Dieser Text wird in die angegebene Datei geschrieben."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 33 }
|
||
|
||
wtWebGraphThermoBaroAlarmFtpClearText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Dieser Text wird in die angegebene Datei geschrieben."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 34 }
|
||
|
||
wtWebGraphThermoBaroAlarmFtpOptions OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bin<69>r kodierte Optionen, nur eine Option darf eingeschaltet sein:
|
||
STORE = Datei ersetzen
|
||
APPEND = Nachrichten ans Dateiende anh<6E>ngen
|
||
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 0 : STORE
|
||
Bit 1 : APPEND
|
||
Bit 2-7: ungenutzt"
|
||
::= { wtWebGraphThermoBaroAlarmEntry 35 }
|
||
|
||
wtWebGraphThermoBaroAlarmTimerCron OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Dieser Eintrag enth<74>lt 5 Leerzeichen- oder Tab-getrente Felder zur Definition von zeitgesteuerten
|
||
Ausgabe von Alarmnachrichten. Jedes der 5 Felder muss mit der aktuelle Zeit <20>bereinstimmen, um
|
||
das Senden einer Nachricht auszul<75>sen, Wochentag und Monatstag werden getrennt ausgewertet.
|
||
Feld m<>glicher Zahlenbereich
|
||
1: Minuten 0-59
|
||
2. Stunden 0-23, 0 ist Mitternacht
|
||
3: Monatstag 1-31
|
||
4: Monat 1-12
|
||
5: Wochentag 0-6, 0 ist Sonntag
|
||
|
||
F<>r jedes Feld kann nun angegeben werden:
|
||
- eine ganze Zahl aus dem angegebenen Zahlenbereich
|
||
- ein Teil-Zahlenbereich (wie z.B. 1-5) innerhalb des angegebenen Zahlenbereichs
|
||
- eine mit Komma getrennte Liste von ganzen Zahlen oder Tei-Zahlenbereichen (wie z.B. 2,4-6,8,10)
|
||
- ein Stern * (deckt den gesamten erlaubten Bereich ab)
|
||
- ein / gibt die Schrittweite bei Teil-Zahlenbereichen an (z.B. 0-59/2 jede zweite Minute)."
|
||
::= { wtWebGraphThermoBaroAlarmEntry 36 }
|
||
|
||
-- wtWebGraphThermoBaroGraphicsBase Group
|
||
----------------------------
|
||
|
||
wtWebGraphThermoBaroGraphicsBaseEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Legt die Anzeigeelemente der Grafik fest:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 0 : Auto scroll enable
|
||
Bit 1 : Show table
|
||
Bit 2 : Show graph
|
||
Bit 3 : Show control buttons
|
||
Bit 4 : Show config menu
|
||
Bit 5-7: ungenutzt"
|
||
::= { wtWebGraphThermoBaroGraphicsBase 1 }
|
||
|
||
wtWebGraphThermoBaroGraphicsBaseWidth OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Definiert die Breite der Grafik in Pixeln."
|
||
::= { wtWebGraphThermoBaroGraphicsBase 2 }
|
||
|
||
wtWebGraphThermoBaroGraphicsBaseHeight OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Definiert die H<>he der Grafik in Pixeln."
|
||
::= { wtWebGraphThermoBaroGraphicsBase 3 }
|
||
|
||
wtWebGraphThermoBaroGraphicsBaseFrameColor OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(3))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Farbe des Rahmens in der grafischen Darstellung."
|
||
::= { wtWebGraphThermoBaroGraphicsBase 4 }
|
||
|
||
wtWebGraphThermoBaroGraphicsBaseBackgroundColor OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(3))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Farbe der Hintergrundfarbe in der grafischen Darstellung."
|
||
::= { wtWebGraphThermoBaroGraphicsBase 5 }
|
||
|
||
wtWebGraphThermoBaroGraphicsBasePollingrate OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Definiert die Abfragerate in Sekunden,
|
||
mit der die Grafik aktualisiert wird."
|
||
::= { wtWebGraphThermoBaroGraphicsBase 6 }
|
||
|
||
-- wtWebGraphThermoBaroGraphicsSelect Group
|
||
----------------------------
|
||
|
||
wtWebGraphThermoBaroGraphicsSelectDisplaySensorSel OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Die hier ausgew<65>hlten Sensoren werden grafisch angezeigt:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 0: Sensor 1
|
||
Bit 1: Sensor 2
|
||
Bit 2: Sensor 3
|
||
Bit 3-7: ungenutzt"
|
||
::= { wtWebGraphThermoBaroGraphicsSelect 1 }
|
||
|
||
wtWebGraphThermoBaroGraphicsSelectDisplayShowExtrem OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(4))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Die Anzeige von Minima und Maxima der hier ausgew<65>hlten Sensoren
|
||
wird freigeschaltet:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 0: Sensor 1
|
||
Bit 1: Sensor 2
|
||
Bit 2: Sensor 3
|
||
Bit 3-7: ungenutzt"
|
||
::= { wtWebGraphThermoBaroGraphicsSelect 2 }
|
||
|
||
-- Graph Sensor Color Table
|
||
|
||
wtWebGraphThermoBaroSensorColorTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebGraphThermoBaroSensorColorEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Liste der Sensorfarben in der grafischen Darstellung."
|
||
::= { wtWebGraphThermoBaroGraphicsSelect 3 }
|
||
|
||
wtWebGraphThermoBaroSensorColorEntry OBJECT-TYPE
|
||
SYNTAX WtWebGraphThermoBaroSensorColorEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Nummern der Sensoren."
|
||
INDEX { wtWebGraphThermoBaroSensorNo }
|
||
::= { wtWebGraphThermoBaroSensorColorTable 1 }
|
||
|
||
wtWebGraphThermoBaroSensorColorEntry ::= SEQUENCE {
|
||
wtWebGraphThermoBaroGraphicsSensorColor OCTET STRING,
|
||
wtWebGraphThermoBaroGraphicsSelectScale OCTET STRING
|
||
}
|
||
|
||
wtWebGraphThermoBaroGraphicsSensorColor OBJECT-TYPE
|
||
SYNTAX OCTET STRING (SIZE(3))
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Farbe des Sensors in der grafischen Darstellung."
|
||
::= { wtWebGraphThermoBaroSensorColorEntry 1 }
|
||
|
||
wtWebGraphThermoBaroGraphicsSelectScale OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Zuweisung einer Skalierung zu einem Sensor:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 0 : Use Scale 1
|
||
Bit 1 : Use Scale 2
|
||
Bit 2 : Use Scale 3
|
||
Bit 3-7: ungenutzt"
|
||
::= { wtWebGraphThermoBaroSensorColorEntry 2 }
|
||
|
||
-- wtWebGraphThermoBaroGraphicsScale Group
|
||
----------------------------
|
||
|
||
wtWebGraphThermoBaroGraphicsScaleAutoScaleEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"W<>hlt den Auto Scale Modus f<>r die jeweilige Skalierung aus:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 0 : Scale 1 Auto scale enable
|
||
Bit 1 : Scale 2 Auto scale enable
|
||
Bit 2 : Scale 3 Auto scale enable
|
||
Bit 3-7: ungenutzt"
|
||
::= { wtWebGraphThermoBaroGraphicsScale 1 }
|
||
|
||
wtWebGraphThermoBaroGraphicsScaleAutoFitEnable OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"W<>hlt den Auto Fit Modus f<>r die jeweilige Skalierung aus:
|
||
Octet 1: ungenutzt
|
||
Octet 2: ungenutzt
|
||
Octet 3: ungenutzt
|
||
Octet 4:
|
||
Bit 0 : Scale 1 Auto fit enable
|
||
Bit 1 : Scale 2 Auto fit enable
|
||
Bit 2 : Scale 3 Auto fit enable
|
||
Bit 3-7: ungenutzt"
|
||
::= { wtWebGraphThermoBaroGraphicsScale 2 }
|
||
|
||
wtWebGraphThermoBaroGraphicsScale1Min OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Skalierung 1: Minimum."
|
||
::= { wtWebGraphThermoBaroGraphicsScale 3 }
|
||
|
||
wtWebGraphThermoBaroGraphicsScale2Min OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Skalierung 2: Minimum."
|
||
::= { wtWebGraphThermoBaroGraphicsScale 4 }
|
||
|
||
wtWebGraphThermoBaroGraphicsScale3Min OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Skalierung 3: Minimum."
|
||
::= { wtWebGraphThermoBaroGraphicsScale 5 }
|
||
|
||
wtWebGraphThermoBaroGraphicsScale4Min OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Skalierung 4: Minimum."
|
||
::= { wtWebGraphThermoBaroGraphicsScale 6 }
|
||
|
||
wtWebGraphThermoBaroGraphicsScale1Max OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Skalierung 1: Maximum."
|
||
::= { wtWebGraphThermoBaroGraphicsScale 7 }
|
||
|
||
wtWebGraphThermoBaroGraphicsScale2Max OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Skalierung 2: Maximum."
|
||
::= { wtWebGraphThermoBaroGraphicsScale 8 }
|
||
|
||
wtWebGraphThermoBaroGraphicsScale3Max OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Skalierung 3: Maximum."
|
||
::= { wtWebGraphThermoBaroGraphicsScale 9 }
|
||
|
||
wtWebGraphThermoBaroGraphicsScale4Max OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Skalierung 4: Maximum."
|
||
::= { wtWebGraphThermoBaroGraphicsScale 10 }
|
||
|
||
wtWebGraphThermoBaroGraphicsScale1Unit OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Skalierung 1: Einheit."
|
||
::= { wtWebGraphThermoBaroGraphicsScale 11 }
|
||
|
||
wtWebGraphThermoBaroGraphicsScale2Unit OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Skalierung 2: Einheit."
|
||
::= { wtWebGraphThermoBaroGraphicsScale 12 }
|
||
|
||
wtWebGraphThermoBaroGraphicsScale3Unit OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Skalierung 3: Einheit."
|
||
::= { wtWebGraphThermoBaroGraphicsScale 13 }
|
||
|
||
wtWebGraphThermoBaroGraphicsScale4Unit OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Skalierung 4: Einheit."
|
||
::= { wtWebGraphThermoBaroGraphicsScale 14 }
|
||
|
||
|
||
-- wtWebGraphThermoBaroPorts Group
|
||
----------------------------
|
||
|
||
-- Table
|
||
|
||
wtWebGraphThermoBaroPortTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF WtWebGraphThermoBaroPortEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Liste der Einstellungen abh<62>ngig von der Sensornummer."
|
||
::= { wtWebGraphThermoBaroPorts 1 }
|
||
|
||
wtWebGraphThermoBaroPortEntry OBJECT-TYPE
|
||
SYNTAX WtWebGraphThermoBaroPortEntry
|
||
ACCESS not-accessible
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Sensor-Parameter der einzelnen Sensoren."
|
||
INDEX { wtWebGraphThermoBaroSensorNo }
|
||
::= { wtWebGraphThermoBaroPortTable 1 }
|
||
|
||
WtWebGraphThermoBaroPortEntry ::= SEQUENCE {
|
||
wtWebGraphThermoBaroPortName OCTET STRING,
|
||
wtWebGraphThermoBaroPortText OCTET STRING,
|
||
wtWebGraphThermoBaroPortOffset1 OCTET STRING,
|
||
wtWebGraphThermoBaroPortTemperature1 OCTET STRING,
|
||
wtWebGraphThermoBaroPortOffset2 OCTET STRING,
|
||
wtWebGraphThermoBaroPortTemperature2 OCTET STRING,
|
||
wtWebGraphThermoBaroPortComment OCTET STRING,
|
||
wtWebGraphThermoBaroPortSensorSelect OCTET STRING
|
||
}
|
||
|
||
wtWebGraphThermoBaroPortName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Name des Sensors."
|
||
::= { wtWebGraphThermoBaroPortEntry 1 }
|
||
|
||
wtWebGraphThermoBaroPortText OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Beschreibung des Sensors."
|
||
::= { wtWebGraphThermoBaroPortEntry 2 }
|
||
|
||
wtWebGraphThermoBaroPortOffset1 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset-Kalibrierung: Offset in Grad mit max. 2 Nachkommastellen bei Temperatur 1."
|
||
::= { wtWebGraphThermoBaroPortEntry 3 }
|
||
|
||
wtWebGraphThermoBaroPortTemperature1 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset-Kalibrierung: Referenztemperatur 1 in Grad mit max. 2 Nachkommastellen."
|
||
::= { wtWebGraphThermoBaroPortEntry 4 }
|
||
|
||
wtWebGraphThermoBaroPortOffset2 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset-Kalibrierung: Offset in Grad mit max. 2 Nachkommastellen bei Temperatur 2."
|
||
::= { wtWebGraphThermoBaroPortEntry 5 }
|
||
|
||
wtWebGraphThermoBaroPortTemperature2 OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset-Kalibrierung: Referenztemperatur 2 in Grad mit max. 2 Nachkommastellen."
|
||
::= { wtWebGraphThermoBaroPortEntry 6 }
|
||
|
||
wtWebGraphThermoBaroPortComment OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Offset-Kalibrierung: Angaben zu Datum, Referenzger<65>t, Operator."
|
||
::= { wtWebGraphThermoBaroPortEntry 7 }
|
||
|
||
wtWebGraphThermoBaroPortAltidude OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"H<>he des Sensors <20>ber Meeresh<73>he (<28>NN)."
|
||
::= { wtWebGraphThermoBaroPorts 2 }
|
||
|
||
-- wtWebGraphThermoBaroManufact Group
|
||
----------------------------
|
||
|
||
wtWebGraphThermoBaroMfName OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Hersteller Firmenname"
|
||
::= { wtWebGraphThermoBaroManufact 1 }
|
||
|
||
wtWebGraphThermoBaroMfAddr OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Adresse des Herstellers."
|
||
::= { wtWebGraphThermoBaroManufact 2 }
|
||
|
||
wtWebGraphThermoBaroMfHotline OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Hotline des Herstellers."
|
||
::= { wtWebGraphThermoBaroManufact 3 }
|
||
|
||
wtWebGraphThermoBaroMfInternet OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Internet-Adresse des Herstellers."
|
||
::= { wtWebGraphThermoBaroManufact 4 }
|
||
|
||
wtWebGraphThermoBaroMfDeviceTyp OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Ger<65>tebezeichnung (Typ) des Herstellers."
|
||
::= { wtWebGraphThermoBaroManufact 5 }
|
||
|
||
wtWebGraphThermoBaroMfOrderNo OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bestellnummer des Ger<65>tes des Herstellers."
|
||
::= { wtWebGraphThermoBaroManufact 6 }
|
||
|
||
-- wtWebGraphThermoBaroDiag Group
|
||
----------------------------
|
||
|
||
wtWebGraphThermoBaroDiagErrorCount OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Anzahl der Eintr<74>ge im Fehlerspeicher."
|
||
::= { wtWebGraphThermoBaroDiag 1 }
|
||
|
||
wtWebGraphThermoBaroDiagBinaryError OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Bitweise kodierte Fehlerursachen."
|
||
::= { wtWebGraphThermoBaroDiag 2 }
|
||
|
||
wtWebGraphThermoBaroDiagErrorIndex OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Der Wert dieser Variable wird als Index f<>r die Ausgabe
|
||
eines Fehlertextes (wtWebGraphThermoBaroDiagErrorMessage) verwendet.
|
||
Die Fehler im Speicher sind von 1 bis wtWebGraphThermoBaroDiagErrorCount durchnummeriert.
|
||
Nach dem Schreiben einens g<>ltigen Wertes in diese Variable kann der dazugeh<65>rige Text
|
||
in wtWebGraphThermoBaroDiagErrorMessage ausgelesen werden."
|
||
::= { wtWebGraphThermoBaroDiag 3 }
|
||
|
||
wtWebGraphThermoBaroDiagErrorMessage OBJECT-TYPE
|
||
SYNTAX OCTET STRING
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Abh<62>ngig vom Wert wtWebGraphThermoBaroDiagErrorIndex wird ein Fehlertext angezeigt."
|
||
::= { wtWebGraphThermoBaroDiag 4 }
|
||
|
||
wtWebGraphThermoBaroDiagErrorClear OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS write-only
|
||
STATUS mandatory
|
||
DESCRIPTION
|
||
"Durch Schreiben eine 1 in diese Variable, wird der Fehlerspeicher gel<65>scht."
|
||
::= { wtWebGraphThermoBaroDiag 5 }
|
||
|
||
-- TRAP DEFINITIONS
|
||
|
||
-- Diese SNMP-Traps werden gesendet, wenn die Alarmtriggerbedingungen zutreffen
|
||
|
||
wtWebGraphThermoBaroAlert1 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 1 ausgel<65>st wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Alarm 1"
|
||
--#SUMMARY "Alarm 1: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 31
|
||
|
||
wtWebGraphThermoBaroAlert2 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 2 ausgel<65>st wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Alarm 2"
|
||
--#SUMMARY "Alarm 2: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 32
|
||
|
||
wtWebGraphThermoBaroAlert3 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 3 ausgel<65>st wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Alarm 3"
|
||
--#SUMMARY "Alarm 3: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 33
|
||
|
||
wtWebGraphThermoBaroAlert4 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 4 ausgel<65>st wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Alarm 4"
|
||
--#SUMMARY "Alarm 4: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 34
|
||
|
||
wtWebGraphThermoBaroAlert5 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 5 ausgel<65>st wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Alarm 5"
|
||
--#SUMMARY "Alarm 5: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 35
|
||
|
||
wtWebGraphThermoBaroAlert6 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 6 ausgel<65>st wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Alarm 6"
|
||
--#SUMMARY "Alarm 6: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 36
|
||
|
||
wtWebGraphThermoBaroAlert7 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 7 ausgel<65>st wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Alarm 7"
|
||
--#SUMMARY "Alarm 7: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 37
|
||
|
||
wtWebGraphThermoBaroAlert8 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 8 ausgel<65>st wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Alarm 8"
|
||
--#SUMMARY "Alarm 8: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 38
|
||
|
||
wtWebGraphThermoBaroAlert9 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 1 gel<65>scht wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Release Alarm 1"
|
||
--#SUMMARY "Release Alarm 1: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 91
|
||
|
||
wtWebGraphThermoBaroAlert10 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 2 gel<65>scht wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Release Alarm 2"
|
||
--#SUMMARY "Release Alarm 2: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 92
|
||
|
||
wtWebGraphThermoBaroAlert11 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 3 gel<65>scht wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Release Alarm 3"
|
||
--#SUMMARY "Release Alarm 3: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 93
|
||
|
||
wtWebGraphThermoBaroAlert12 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 4 gel<65>scht wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Release Alarm 4"
|
||
--#SUMMARY "Release Alarm 4: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 94
|
||
|
||
wtWebGraphThermoBaroAlert13 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 5 gel<65>scht wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Release Alarm 5"
|
||
--#SUMMARY "Release Alarm 5: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 95
|
||
|
||
wtWebGraphThermoBaroAlert14 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 6 gel<65>scht wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Release Alarm 6"
|
||
--#SUMMARY "Release Alarm 6: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 96
|
||
|
||
wtWebGraphThermoBaroAlert15 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 7 gel<65>scht wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Release Alarm 7"
|
||
--#SUMMARY "Release Alarm 7: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 97
|
||
|
||
wtWebGraphThermoBaroAlert16 TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES { wtWebGraphThermoBaroAlarmClearTrapText }
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn der Alarm 8 gel<65>scht wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Release Alarm 8"
|
||
--#SUMMARY "Release Alarm 8: %s"
|
||
--#ARGUMENTS {0}
|
||
--#SEVERITY INFORMATIONAL
|
||
--#TIMEINDEX 99
|
||
--#STATE OPERATIONAL
|
||
::= 98
|
||
|
||
wtWebGraphThermoBaroAlertDiag TRAP-TYPE
|
||
ENTERPRISE wtWebGraphThermoBaro
|
||
VARIABLES {
|
||
wtWebGraphThermoBaroDiagErrorIndex,
|
||
wtWebGraphThermoBaroDiagErrorMessage
|
||
}
|
||
DESCRIPTION
|
||
"Dieser SNMP-Trap wird generiert, wenn eine Diagnose/Error-Message ausgel<65>st wurde,
|
||
das SNMP-Trap-Enable gesetzt ist und
|
||
SNMP in Enable freigegeben ist."
|
||
-- NMS trap annotation
|
||
--#TYPE "Thermo-Hygrometer Diagnose Error"
|
||
--#SUMMARY "Diagnose error index: %d, Message: %s."
|
||
--#ARGUMENTS {0,1}
|
||
--#SEVERITY MAJOR
|
||
--#TIMEINDEX 99
|
||
--#STATE DEGRADED
|
||
::= 110
|
||
|
||
END
|