mibs/MIBS/avocent/ACS-MIB

2573 lines
96 KiB
Plaintext
Raw Permalink Normal View History

2023-12-05 12:25:34 +01:00
--------------------------------------------------------------------------------
-- Avocent ACS MIB
-- Copyright 2009 Avocent Corporation
-- Revision: 2.0.1
-- Last Modified: October 10, 2010
--------------------------------------------------------------------------------
ACS-MIB DEFINITIONS ::= BEGIN
IMPORTS
Gauge,TimeTicks,IpAddress,Counter,NetworkAddress
FROM RFC1155-SMI
PhysAddress
FROM RFC1213-MIB
enterprises, MODULE-IDENTITY
FROM SNMPv2-SMI
OBJECT-TYPE, MODULE-IDENTITY, OBJECT-IDENTITY, Integer32
FROM SNMPv2-SMI
DisplayString
FROM SNMPv2-TC
InterfaceIndex, InterfaceIndexOrZero
FROM IF-MIB
TRAP-TYPE
FROM RFC-1215;
--------------------------------------------------------------------------------
-- Object Groupings
--------------------------------------------------------------------------------
--@ Note: every product type should be uniquely identified underneath the
--@ acsProducts object group. Each product should report its unique acsProducts
--@ OBJECT IDENTIFIER in mib-2.system.sysObjectID. Please see the file
--@ "_Avocent Enterprise Object Identifier Assignment.txt" for a list of the
--@ IDs that have been assigned.
-- enterprises .1.3.6.1.4.1
-- avocent OBJECT IDENTIFIER ::= { enterprises 10418 }
acs MODULE-IDENTITY
LAST-UPDATED "201010100000Z"
ORGANIZATION "Avocent Corporation"
CONTACT-INFO "postal : Avocent Corporation
47281 Bayside Parkway
Fremont, CA 94538, USA
e-mail : Technical Support
techsupport@avocent.com"
DESCRIPTION
"This module defines the Avocent MIB extensions to
ACS60xx products."
REVISION "201010100000Z"
DESCRIPTION "Add products acs6004 and acs6008"
REVISION "200912110000Z"
DESCRIPTION "Extended acsPowerMgmt to support data monitoring
and Avocent PM-PDUs"
REVISION "200709170000Z"
DESCRIPTION "First Draft"
::= { enterprises 10418 16 }
acsProducts OBJECT IDENTIFIER ::= { acs 1 }
acsManagement OBJECT IDENTIFIER ::= { acs 2 }
--
acs6016 OBJECT IDENTIFIER ::= { acsProducts 1 } -- 10418.16.1.1
acs6032 OBJECT IDENTIFIER ::= { acsProducts 2 } -- 10418.16.1.2
acs6048 OBJECT IDENTIFIER ::= { acsProducts 3 } -- 10418.16.1.3
acs6004 OBJECT IDENTIFIER ::= { acsProducts 4 } -- 10418.16.1.4
acs6008 OBJECT IDENTIFIER ::= { acsProducts 5 } -- 10418.16.1.5
acsAppliance OBJECT IDENTIFIER ::= { acsManagement 1 } -- 10418.16.2.1
acsSessions OBJECT IDENTIFIER ::= { acsManagement 2 } -- 10418.16.2.2
acsSerialPort OBJECT IDENTIFIER ::= { acsManagement 3 } -- 10418.16.2.3
acsPowerMgmt OBJECT IDENTIFIER ::= { acsManagement 5 } -- 10418.16.2.5
-- objects under acsPowerMgmt
-- acsPowerMgmtNumSerialPorts ::= { acsPowerMgmt 1 }
-- acsPowerMgmtSerialTable ::= { acsPowerMgmt 2 }
-- acsPowerMgmtPDUTable ::= { acsPowerMgmt 3 }
-- acsPowerMgmtTotalNumberOfOutlets ::= { acsPowerMgmt 4 }
-- acsPowerMgmtOutletsTable ::= { acsPowerMgmt 5 }
-- acsPowerMgmtNumberOfOutletGroup ::= { acsPowerMgmt 6 }
-- acsPowerMgmtGroupTable ::= { acsPowerMgmt 7 }
-- acsPowerMgmtPhasesTable ::= { acsPowerMgmt 8 }
-- acsPowerMgmtBanksTable ::= { acsPowerMgmt 9 }
-- acsPowerMgmtEnvMonTable ::= { acsPowerMgmt 10 }
-- acsPowerMgmtOutElecMonTable ::= { acsPowerMgmt 11 }
--
-- Note that traps are defined in a separate trap MIB
--
acsTrapObject OBJECT IDENTIFIER ::= { acsManagement 6 } -- 10418.16.2.6
--
-- Type Definitions
--
--
-- Each enumeration represents the states of the appliance power supplies.
PowerSupplyState ::= INTEGER
{
statePowerOn(1),
statePowerOff(2),
powerNotInstaled(9999)
}
--
-- Each enumeration represents the speed of the serial port.
SerialPortSpeed ::= INTEGER
{
speed300bps(300),
speed600bps(600),
speed1200bps(1200),
speed2400bps(2400),
speed4800bps(4800),
speed9600bps(9600),
speed19200bps(19200),
speed38400bps(38400),
speed57600bps(57600),
speed115200bps(115200),
speed230400bps(230400),
speed460800bps(460800)
}
--
-- Each enumeration represents the state of the RS-232C signal.
SerialPortSignalState ::=INTEGER
{
up(1),
down(2)
}
--
-- Each enumeration represents the RJ-45 pin-out
SerialPortPinOut ::=INTEGER
{
cyclades(1),
cisco(2)
}
--
-- acsAppliance
-- OBJECT IDENTIFIER ::= { acsManagement 1 } 10418.16.2.1
--
acsHostName OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The appliance name"
::= { acsAppliance 1 }
acsProductModel OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..50) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The appliance product model"
::= { acsAppliance 2 }
acsPartNumber OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The part number of this appliance as shown on the label
attached or imprinted on the appliance."
::= { acsAppliance 3 }
acsSerialNumber OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The serial number of this appliance as shown on the label
attached or imprinted on the appliance."
::= { acsAppliance 4 }
acsEIDNumber OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The electronic ID number (EID) of this appliance as shown on the label
attached or imprinted on the appliance."
::= { acsAppliance 5 }
acsBootcodeVersion OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The version of the bootcode of this appliance."
::= { acsAppliance 6 }
acsFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The version of the firmware of this appliance."
::= { acsAppliance 7 }
acsPowerSupply OBJECT-IDENTITY
STATUS current
DESCRIPTION
"It gives information about Power Supply of this appliance"
::= { acsAppliance 8 }
acsPowerSupplyNumber OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of the power supplies of this appliance"
::= { acsPowerSupply 1 }
acsPowerSupplyStatePw1 OBJECT-TYPE
SYNTAX PowerSupplyState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of the first power supply"
::= { acsPowerSupply 2 }
acsPowerSupplyStatePw2 OBJECT-TYPE
SYNTAX PowerSupplyState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of the second power supply"
::= { acsPowerSupply 3 }
acsReboot OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reboot(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of reboot(2) will reboot the appliance.
noAction(1) = always returned in a GET. Does nothing if SET.
reboot(2) = when SET the appliance immediately reboots."
::= { acsAppliance 9 }
--
-- acsSessions
-- OBJECT IDENTIFIER ::= { acsManagement 2 } 10418.16.2.2
--
acsActiveSessionsNumberOfSession OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of active sessions."
::= { acsSessions 1 }
acsActiveSessionsTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsActiveSessionsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the list of active sessions."
::= { acsSessions 2 }
acsActiveSessionsTableEntry OBJECT-TYPE
SYNTAX AcsActiveSessionsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the active session"
INDEX { acsActiveSessionsTableIndex }
::= { acsActiveSessionsTable 1 }
AcsActiveSessionsTableEntry ::= SEQUENCE {
acsActiveSessionsTableIndex InterfaceIndexOrZero,
acsActiveSessionsTableUser DisplayString, -- user name
acsActiveSessionsTableGroup DisplayString, -- group name
acsActiveSessionsTableType DisplayString, -- RO/RW-ssh,telnet or web
acsActiveSessionsTableConnection DisplayString, -- type + target name
acsActiveSessionsTableSessionTime DisplayString, -- time of session
acsActiveSessionsTableFrom DisplayString, -- source of the session
acsActiveSessionsTableKill INTEGER
}
acsActiveSessionsTableIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique index representing an entry in this table."
::= { acsActiveSessionsTableEntry 1 }
acsActiveSessionsTableUser OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The name of the user that opens this session."
::= { acsActiveSessionsTableEntry 2 }
acsActiveSessionsTableGroup OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The name of the group that the user belongs to."
::= { acsActiveSessionsTableEntry 3 }
acsActiveSessionsTableType OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The session type."
::= { acsActiveSessionsTableEntry 4 }
acsActiveSessionsTableConnection OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Connection type."
::= { acsActiveSessionsTableEntry 5 }
acsActiveSessionsTableSessionTime OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Time of the session"
::= { acsActiveSessionsTableEntry 6 }
acsActiveSessionsTableFrom OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The source IP address of the session."
::= { acsActiveSessionsTableEntry 7 }
acsActiveSessionsTableKill OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
killSession(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of killSession(2) will kill the session.
noAction(1) = always returned in a GET. Does nothing if SET.
killSession(2)= when SET the appliance immediately kills the session."
::= { acsActiveSessionsTableEntry 8 }
--
-- acsSerialPort
-- OBJECT IDENTIFIER ::= { acsManagement 3 } 10418.16.2.3
--
acsSerialPortNumberOfPorts OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of Serial Ports (physical serial port plus Aux Port."
::= { acsSerialPort 1 }
acsSerialPortTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsSerialPortTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains information about serial ports."
::= { acsSerialPort 2 }
acsSerialPortTableEntry OBJECT-TYPE
SYNTAX AcsSerialPortTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about specific serial port."
INDEX { acsSerialPortTableNumber }
::= { acsSerialPortTable 1 }
AcsSerialPortTableEntry ::= SEQUENCE {
acsSerialPortTableNumber Integer32, -- serial port number
acsSerialPortTableDeviceName DisplayString, -- associated device name
acsSerialPortTableStatus INTEGER, -- status of serial port
acsSerialPortTableName DisplayString, -- associated name
acsSerialPortTableProfile INTEGER, -- configured profile
acsSerialPortTablePinOut SerialPortPinOut, -- configure RJ45 pin-out
acsSerialPortTableComSpeed SerialPortSpeed, -- configured speed
acsSerialPortTableComParity INTEGER, -- configured parity
acsSerialPortTableComDataSize Integer32, -- configured data size
acsSerialPortTableComStopBits Integer32, -- configured stop bits
acsSerialPortTableComFlowControl INTEGER, -- configured flow control
acsSerialPortTableSignalStateDTR SerialPortSignalState, -- state of DTR RS-232C signal
acsSerialPortTableSignalStateDCD SerialPortSignalState, -- state of DCD RS-232C signal
acsSerialPortTableSignalStateRTS SerialPortSignalState, -- state of RTS RS-232C signal
acsSerialPortTableSignalStateCTS SerialPortSignalState, -- state of CTS RS-232C signal
acsSerialPortTableTxBytes Integer32, -- number of transmitted bytes
acsSerialPortTableRxBytes Integer32, -- number of received bytes
acsSerialPortTableFrameError Integer32, -- number of detected frame errors
acsSerialPortTableParityError Integer32, -- number of detected parity errors
acsSerialPortTableBreak Integer32, -- number of detected break
acsSerialPortTableOverrun Integer32 -- number of detected overrun errors
}
acsSerialPortTableNumber OBJECT-TYPE
SYNTAX Integer32 (1..49)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique index representing an entry in this table.
It is the number of the serial port. For AUX port,
the number will be the number of physical serial ports plus 1."
::= { acsSerialPortTableEntry 1 }
acsSerialPortTableDeviceName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The associated device name for the serial port."
::= { acsSerialPortTableEntry 2 }
acsSerialPortTableStatus OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
idle(2),
inUse(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of the serial port:
disabled(1) = it was configured as disable.
idle(2) = there is not any session opened in this port.
inUse(3) = there is session(s) opened in this port."
::= { acsSerialPortTableEntry 3 }
acsSerialPortTableName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name associated with this serial port."
::= { acsSerialPortTableEntry 4 }
acsSerialPortTableProfile OBJECT-TYPE
SYNTAX INTEGER {
casProfile(1),
tsProfile(2),
dialInProfile(3),
powerProfile(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Configured profile for this serial port."
::= { acsSerialPortTableEntry 5 }
acsSerialPortTablePinOut OBJECT-TYPE
SYNTAX SerialPortPinOut
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"RJ45 Pin-out configured for this serial port."
::= { acsSerialPortTableEntry 6 }
acsSerialPortTableComSpeed OBJECT-TYPE
SYNTAX SerialPortSpeed
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Speed configured for this serial port."
::= { acsSerialPortTableEntry 7 }
acsSerialPortTableComParity OBJECT-TYPE
SYNTAX INTEGER {
none(1),
odd(2),
even(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Parity configured for this serial port."
::= { acsSerialPortTableEntry 8 }
acsSerialPortTableComDataSize OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Data Size configured for this serial port."
::= { acsSerialPortTableEntry 9 }
acsSerialPortTableComStopBits OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of Stop Bits configured for this serial port."
::= { acsSerialPortTableEntry 10 }
acsSerialPortTableComFlowControl OBJECT-TYPE
SYNTAX INTEGER {
none(1),
hardware(2),
software(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Flow Control configured for this serial port."
::= { acsSerialPortTableEntry 11 }
acsSerialPortTableSignalStateDTR OBJECT-TYPE
SYNTAX SerialPortSignalState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of the DTR RS-232C signal."
::= { acsSerialPortTableEntry 12 }
acsSerialPortTableSignalStateDCD OBJECT-TYPE
SYNTAX SerialPortSignalState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of the DCD RS-232C signal."
::= { acsSerialPortTableEntry 13 }
acsSerialPortTableSignalStateRTS OBJECT-TYPE
SYNTAX SerialPortSignalState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of the RTS RS-232C signal."
::= { acsSerialPortTableEntry 14 }
acsSerialPortTableSignalStateCTS OBJECT-TYPE
SYNTAX SerialPortSignalState
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"State of the CTS RS-232C signal."
::= { acsSerialPortTableEntry 15 }
acsSerialPortTableTxBytes OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of transmited bytes by the serial port."
::= { acsSerialPortTableEntry 16 }
acsSerialPortTableRxBytes OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of received bytes by the serial port."
::= { acsSerialPortTableEntry 17 }
acsSerialPortTableFrameError OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of frame error detected in the serial port."
::= { acsSerialPortTableEntry 18 }
acsSerialPortTableParityError OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of parity error detected in the serial port."
::= { acsSerialPortTableEntry 19 }
acsSerialPortTableBreak OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of break detected in the serial port."
::= { acsSerialPortTableEntry 20 }
acsSerialPortTableOverrun OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of overrun error detected in the serial port."
::= { acsSerialPortTableEntry 21 }
--
-- acsPowerMgmt
-- OBJECT IDENTIFIER ::= { acsManagement 5 } 10418.16.2.5
--
acsPowerMgmtNumSerialPorts OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of Serial Ports that has PDU connected on the appliance."
::= { acsPowerMgmt 1 }
acsPowerMgmtSerialTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtSerialTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Information about each serial port thas has PDU connect."
::= { acsPowerMgmt 2 }
acsPowerMgmtSerialTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtSerialTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Information about each serial port thas has PDU connect."
INDEX { acsPowerMgmtSerialTableIndex }
::= { acsPowerMgmtSerialTable 1 }
AcsPowerMgmtSerialTableEntry ::= SEQUENCE {
acsPowerMgmtSerialTableIndex InterfaceIndex,
acsPowerMgmtSerialTablePortNumber Integer32,
acsPowerMgmtSerialTableDeviceName DisplayString,
acsPowerMgmtSerialTableNumberPDUs Integer32
}
acsPowerMgmtSerialTableIndex OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The index of the register."
::= { acsPowerMgmtSerialTableEntry 1 }
acsPowerMgmtSerialTablePortNumber OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of the serial port when the PDU is connected."
::= { acsPowerMgmtSerialTableEntry 2 }
acsPowerMgmtSerialTableDeviceName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The device name of this serial port."
::= { acsPowerMgmtSerialTableEntry 3 }
acsPowerMgmtSerialTableNumberPDUs OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total number of units connected in this serial port."
::= { acsPowerMgmtSerialTableEntry 4 }
acsPowerMgmtPDUTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtPDUTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the list of detected PDUs."
::= { acsPowerMgmt 3 }
acsPowerMgmtPDUTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtPDUTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the PDU."
INDEX { acsPowerMgmtPDUTablePortNumber, acsPowerMgmtPDUTablePduIndex }
::= { acsPowerMgmtPDUTable 1 }
AcsPowerMgmtPDUTableEntry ::= SEQUENCE {
acsPowerMgmtPDUTablePortNumber InterfaceIndex, -- number of serial port
acsPowerMgmtPDUTablePduIndex InterfaceIndexOrZero,
acsPowerMgmtPDUTablePduId DisplayString, -- PDU identification
acsPowerMgmtPDUTablePortName DisplayString, -- Serial Port Name
acsPowerMgmtPDUTableModel DisplayString, -- PDU model
acsPowerMgmtPDUTableVendor DisplayString, -- Vendor
acsPowerMgmtPDUTableFirmwareVersion DisplayString, -- Firmware Version
acsPowerMgmtPDUTableNumberOfOutlets Integer32,
acsPowerMgmtPDUTableCurrentNOS Integer32, -- OBSOLETED number of current sensors
acsPowerMgmtPDUTableCurrent1Value Integer32, -- OBSOLETED actual value for current of the sensor 1
acsPowerMgmtPDUTableCurrent1Max Integer32, -- OBSOLETED max value for current of the sensor 1
acsPowerMgmtPDUTableCurrent2Value Integer32, -- OBSOLETED actual value for current of the sensor 2
acsPowerMgmtPDUTableCurrent2Max Integer32, -- OBSOLETED max value for current of the sensor 2
acsPowerMgmtPDUTableCurrent3Value Integer32, -- OBSOLETED actual value for current of the sensor 3
acsPowerMgmtPDUTableCurrent3Max Integer32, -- OBSOLETED max value for current of the sensor 3
acsPowerMgmtPDUTableTemperatureNOS Integer32, -- OBSOLETED number of temperature sensors
acsPowerMgmtPDUTableTemperature1Value Integer32, -- OBSOLETED actual value for Temperature 1
acsPowerMgmtPDUTableTemperature1Max Integer32, -- OBSOLETED max value for Temperature 1
acsPowerMgmtPDUTableTemperature2Value Integer32, -- OBSOLETED actual value for Temperaturet 2
acsPowerMgmtPDUTableTemperature2Max Integer32, -- OBSOLETED max value for Temperature 2
acsPowerMgmtPDUTableTemperature3Value Integer32, -- OBSOLETED actual value for Temperature 3
acsPowerMgmtPDUTableTemperature3Max Integer32, -- OBSOLETED max value for Temperature 3
acsPowerMgmtPDUTableHumidityNOS Integer32, -- OBSOLETED humidity number of humidity sensors
acsPowerMgmtPDUTableHumidity1Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 1
acsPowerMgmtPDUTableHumidity1Max Integer32, -- OBSOLETED max value for Humidityof the sensor 1
acsPowerMgmtPDUTableHumidity2Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 2
acsPowerMgmtPDUTableHumidity2Max Integer32, -- OBSOLETED max value for Humidity of the sensor 2
acsPowerMgmtPDUTableHumidity3Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 3
acsPowerMgmtPDUTableHumidity3Max Integer32, -- OBSOLETED max value for Humidity of the sensor 3
acsPowerMgmtPDUTableVoltageNOS Integer32, -- OBSOLETED number of voltage sensor
acsPowerMgmtPDUTableVoltage1Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 1
acsPowerMgmtPDUTableVoltage1Max Integer32, -- OBSOLETED max value for Voltage of the sensor 1
acsPowerMgmtPDUTableVoltage2Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 2
acsPowerMgmtPDUTableVoltage2Max Integer32, -- OBSOLETED max value for Voltaget of the sensor 2
acsPowerMgmtPDUTableVoltage3Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 3
acsPowerMgmtPDUTableVoltage3Max Integer32, -- OBSOLETED max value for Voltage of the sensor 3
acsPowerMgmtPDUTableNumberOfPhases Integer32, -- number of phases (single or 3-phases)
acsPowerMgmtPDUTableNumberOfBanks Integer32, -- number of banks
acsPowerMgmtPDUTableCurrentValue Integer32, -- actual value of PDU current sensor
acsPowerMgmtPDUTableCurrentMax Integer32, -- max detected value of current sensor
acsPowerMgmtPDUTableCurrentMin Integer32, -- min detected value of current sensor
acsPowerMgmtPDUTableCurrentAvg Integer32, -- average value for current sensor
acsPowerMgmtPDUTableCurrentReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPDUTableVoltageType INTEGER, -- type of PDU voltage
acsPowerMgmtPDUTableVoltageValue Integer32, -- actual value of PDU voltage
acsPowerMgmtPDUTableVoltageMax Integer32, -- max value of voltage sensor
acsPowerMgmtPDUTableVoltageMin Integer32, -- min value of voltage sensor
acsPowerMgmtPDUTableVoltageAvg Integer32, -- avg value of voltage sensor
acsPowerMgmtPDUTableVoltageReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPDUTablePowerType INTEGER, -- type of PDU power consumption
acsPowerMgmtPDUTablePowerValue Integer32, -- actual value of PDU power consumption
acsPowerMgmtPDUTablePowerMax Integer32, -- max value
acsPowerMgmtPDUTablePowerMin Integer32, -- min value
acsPowerMgmtPDUTablePowerAvg Integer32, -- average value
acsPowerMgmtPDUTablePowerReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPDUTablePowerFactorType INTEGER, -- type of PDU power factor
acsPowerMgmtPDUTablePowerFactorValue Integer32, -- actual value of PDU power factor
acsPowerMgmtPDUTablePowerFactorMax Integer32, -- max value for power factor
acsPowerMgmtPDUTablePowerFactorMin Integer32, -- min value for power factor
acsPowerMgmtPDUTablePowerFactorAvg Integer32, -- avg value for power factor
acsPowerMgmtPDUTablePowerFactorReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPDUTableAlarm INTEGER, -- status of PDU alarm
acsPowerMgmtPDUTableEnvSensors Integer32 -- number of environmental sensors
}
acsPowerMgmtPDUTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of serial port when the PDU is connected."
::= { acsPowerMgmtPDUTableEntry 1 }
acsPowerMgmtPDUTablePduIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A PDU position in the chain."
::= { acsPowerMgmtPDUTableEntry 2 }
acsPowerMgmtPDUTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU identification."
::= { acsPowerMgmtPDUTableEntry 3 }
acsPowerMgmtPDUTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of serial port when the PDU is connected."
::= { acsPowerMgmtPDUTableEntry 4 }
acsPowerMgmtPDUTableModel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Model of the PDU."
::= { acsPowerMgmtPDUTableEntry 5 }
acsPowerMgmtPDUTableVendor OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Vendor of the PDU."
::= { acsPowerMgmtPDUTableEntry 6 }
acsPowerMgmtPDUTableFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Version of the PDU firmware."
::= { acsPowerMgmtPDUTableEntry 7 }
acsPowerMgmtPDUTableNumberOfOutlets OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of outlets of the PDU."
::= { acsPowerMgmtPDUTableEntry 8 }
acsPowerMgmtPDUTableCurrentNOS OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Number of current sensors in the PDU."
::= { acsPowerMgmtPDUTableEntry 9 }
acsPowerMgmtPDUTableCurrent1Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Current of the sensor 1 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)"
::= { acsPowerMgmtPDUTableEntry 10 }
acsPowerMgmtPDUTableCurrent1Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum current of the sensor 1 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)
Clear this value, set it with Zero value."
::= { acsPowerMgmtPDUTableEntry 11 }
acsPowerMgmtPDUTableCurrent2Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Current of the sensor 2 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)"
::= { acsPowerMgmtPDUTableEntry 12 }
acsPowerMgmtPDUTableCurrent2Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum current of the sensor 2 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)
Clear this value, set it with Zero value."
::= { acsPowerMgmtPDUTableEntry 13}
acsPowerMgmtPDUTableCurrent3Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Current of the sensor 3 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)"
::= { acsPowerMgmtPDUTableEntry 14 }
acsPowerMgmtPDUTableCurrent3Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum current of the sensor 3 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)
Clear this value, set it with Zero value."
::= { acsPowerMgmtPDUTableEntry 15 }
acsPowerMgmtPDUTableTemperatureNOS OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Number of temperature sensors in the PDU."
::= { acsPowerMgmtPDUTableEntry 16 }
acsPowerMgmtPDUTableTemperature1Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
::= { acsPowerMgmtPDUTableEntry 17 }
acsPowerMgmtPDUTableTemperature1Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Set with Zero value to clear the max. temperature."
::= { acsPowerMgmtPDUTableEntry 18 }
acsPowerMgmtPDUTableTemperature2Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
::= { acsPowerMgmtPDUTableEntry 19 }
acsPowerMgmtPDUTableTemperature2Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Set with Zero value to clear the max. temperature."
::= { acsPowerMgmtPDUTableEntry 20 }
acsPowerMgmtPDUTableTemperature3Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
::= { acsPowerMgmtPDUTableEntry 21 }
acsPowerMgmtPDUTableTemperature3Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Set with Zero value to clear the max. temperature."
::= { acsPowerMgmtPDUTableEntry 22 }
acsPowerMgmtPDUTableHumidityNOS OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Number of humidity sensors in the PDU."
::= { acsPowerMgmtPDUTableEntry 23 }
acsPowerMgmtPDUTableHumidity1Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0."
::= { acsPowerMgmtPDUTableEntry 24 }
acsPowerMgmtPDUTableHumidity1Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero value to clear the max. temperature."
::= { acsPowerMgmtPDUTableEntry 25 }
acsPowerMgmtPDUTableHumidity2Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0."
::= { acsPowerMgmtPDUTableEntry 26 }
acsPowerMgmtPDUTableHumidity2Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero value to clear the max. temperature."
::= { acsPowerMgmtPDUTableEntry 27 }
acsPowerMgmtPDUTableHumidity3Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0."
::= { acsPowerMgmtPDUTableEntry 28 }
acsPowerMgmtPDUTableHumidity3Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero value to clear the max. temperature."
::= { acsPowerMgmtPDUTableEntry 29 }
acsPowerMgmtPDUTableVoltageNOS OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Number of voltage sensors in the PDU."
::= { acsPowerMgmtPDUTableEntry 30 }
acsPowerMgmtPDUTableVoltage1Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Voltage of this sensor in this PDU unit."
::= { acsPowerMgmtPDUTableEntry 31 }
acsPowerMgmtPDUTableVoltage1Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage."
::= { acsPowerMgmtPDUTableEntry 32 }
acsPowerMgmtPDUTableVoltage2Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Voltage of this sensor in this PDU unit."
::= { acsPowerMgmtPDUTableEntry 33 }
acsPowerMgmtPDUTableVoltage2Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage."
::= { acsPowerMgmtPDUTableEntry 34 }
acsPowerMgmtPDUTableVoltage3Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Voltage of this sensor in this PDU unit."
::= { acsPowerMgmtPDUTableEntry 35 }
acsPowerMgmtPDUTableVoltage3Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage."
::= { acsPowerMgmtPDUTableEntry 36 }
acsPowerMgmtPDUTableNumberOfPhases OBJECT-TYPE
SYNTAX INTEGER {
single-phase (0),
three-phase (3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of phases of this PDU unit."
::= { acsPowerMgmtPDUTableEntry 37 }
acsPowerMgmtPDUTableNumberOfBanks OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Number of banks of this PDU unit."
::= { acsPowerMgmtPDUTableEntry 38 }
acsPowerMgmtPDUTableCurrentValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of current sensor in this PDU.( A x 10 )"
::= { acsPowerMgmtPDUTableEntry 39 }
acsPowerMgmtPDUTableCurrentMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of current sensor in this PDU.( A x 10 )"
::= { acsPowerMgmtPDUTableEntry 40 }
acsPowerMgmtPDUTableCurrentMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of current sensor in this PDU.( A x 10 )"
::= { acsPowerMgmtPDUTableEntry 41 }
acsPowerMgmtPDUTableCurrentAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for current sensor in this PDU.( A x 10 )"
::= { acsPowerMgmtPDUTableEntry 42 }
acsPowerMgmtPDUTableCurrentReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of current."
::= { acsPowerMgmtPDUTableEntry 43 }
acsPowerMgmtPDUTableVoltageType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of voltage values."
::= { acsPowerMgmtPDUTableEntry 44 }
acsPowerMgmtPDUTableVoltageValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of voltage sensor in this PDU unit.( V )"
::= { acsPowerMgmtPDUTableEntry 45 }
acsPowerMgmtPDUTableVoltageMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of voltage sensor in this PDU unit.( V )"
::= { acsPowerMgmtPDUTableEntry 46 }
acsPowerMgmtPDUTableVoltageMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of voltage sensor in this PDU unit.( V )"
::= { acsPowerMgmtPDUTableEntry 47 }
acsPowerMgmtPDUTableVoltageAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for voltage sensor in this PDU unit.( V )"
::= { acsPowerMgmtPDUTableEntry 48 }
acsPowerMgmtPDUTableVoltageReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of voltage."
::= { acsPowerMgmtPDUTableEntry 49 }
acsPowerMgmtPDUTablePowerType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power consumption values.( W x 10 )"
::= { acsPowerMgmtPDUTableEntry 50 }
acsPowerMgmtPDUTablePowerValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power consumption in this PDU unit.( W x 10 )"
::= { acsPowerMgmtPDUTableEntry 51 }
acsPowerMgmtPDUTablePowerMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of power consumption in this PDU unit.( W x 10 )"
::= { acsPowerMgmtPDUTableEntry 52 }
acsPowerMgmtPDUTablePowerMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of power consumption in this PDU unit.( W x 10 )"
::= { acsPowerMgmtPDUTableEntry 53 }
acsPowerMgmtPDUTablePowerAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for power consumption in this PDU unit.( W x 10 )"
::= { acsPowerMgmtPDUTableEntry 54 }
acsPowerMgmtPDUTablePowerReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of power consumption."
::= { acsPowerMgmtPDUTableEntry 55 }
acsPowerMgmtPDUTablePowerFactorType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power factor values."
::= { acsPowerMgmtPDUTableEntry 56 }
acsPowerMgmtPDUTablePowerFactorValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power factor in this PDU unit.( PF x 100 )"
::= { acsPowerMgmtPDUTableEntry 57 }
acsPowerMgmtPDUTablePowerFactorMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of power factor in this PDU unit.( PF x 100 )"
::= { acsPowerMgmtPDUTableEntry 58 }
acsPowerMgmtPDUTablePowerFactorMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of power factor in this PDU unit.( PF x 100 )"
::= { acsPowerMgmtPDUTableEntry 59 }
acsPowerMgmtPDUTablePowerFactorAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for power factor in this PDU unit.( PF x 100 )"
::= { acsPowerMgmtPDUTableEntry 60 }
acsPowerMgmtPDUTablePowerFactorReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of power factor."
::= { acsPowerMgmtPDUTableEntry 61 }
acsPowerMgmtPDUTableAlarm OBJECT-TYPE
SYNTAX INTEGER {
normal (1),
blow-fuse (2),
hw-ocp (3),
high-critical (4),
high-warning (5),
low-warning (6),
low-critical (7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Show the PDU alarm status."
::= { acsPowerMgmtPDUTableEntry 62 }
acsPowerMgmtPDUTableEnvSensors OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of environmental sensor in this PDU."
::= { acsPowerMgmtPDUTableEntry 63 }
acsPowerMgmtTotalNumberOfOutlets OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of outlets managed by the appliance."
::= { acsPowerMgmt 4 }
acsPowerMgmtOutletsTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtOutletsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about outlets."
::= { acsPowerMgmt 5 }
acsPowerMgmtOutletsTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtOutletsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the outlet."
INDEX { acsPowerMgmtOutletsTablePortNumber,
acsPowerMgmtOutletsTablePduNumber,
acsPowerMgmtOutletsTableNumber }
::= { acsPowerMgmtOutletsTable 1 }
AcsPowerMgmtOutletsTableEntry ::= SEQUENCE {
acsPowerMgmtOutletsTablePortNumber InterfaceIndex, -- serial port #
acsPowerMgmtOutletsTablePduNumber InterfaceIndex,
acsPowerMgmtOutletsTableNumber InterfaceIndex, -- outlet number in PDU
acsPowerMgmtOutletsTableName DisplayString, -- outlet name
acsPowerMgmtOutletsTableStatus INTEGER, -- outlet status
acsPowerMgmtOutletsTablePowerControl INTEGER, -- manage the outlet
acsPowerMgmtOutletsTablePortName DisplayString, -- serial port name
acsPowerMgmtOutletsTablePduId DisplayString -- PDU ID
}
acsPowerMgmtOutletsTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port number."
::= { acsPowerMgmtOutletsTableEntry 1 }
acsPowerMgmtOutletsTablePduNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index."
::= { acsPowerMgmtOutletsTableEntry 2 }
acsPowerMgmtOutletsTableNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of the outlet in the PDU."
::= { acsPowerMgmtOutletsTableEntry 3 }
acsPowerMgmtOutletsTableName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of the outlet."
::= { acsPowerMgmtOutletsTableEntry 4 }
acsPowerMgmtOutletsTableStatus OBJECT-TYPE
SYNTAX INTEGER {
off(1),
on(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of the outlet."
::= { acsPowerMgmtOutletsTableEntry 5 }
acsPowerMgmtOutletsTablePowerControl OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
powerOn(2),
powerOff(3),
powerCycle(4),
powerLock(5),
powerUnlock(6)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of power*(2-6) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
powerOn(2) = when SET the power On command is sent to PDU.
powerOff(3) = when SET the power Off command is sent to PDU.
powerCycle(4)=when SET the power cycle command is sent to PDU.
powerLock(5)= when SET the power lock command is sent to PDU.
powerUnlock(6)=when SET the power unlock command is sent to PDU.
The powerLock and powerUnlock are valid only for Cyclades-PM PDUs"
::= { acsPowerMgmtOutletsTableEntry 6 }
acsPowerMgmtOutletsTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port Name where the PDU is connected."
::= { acsPowerMgmtOutletsTableEntry 7 }
acsPowerMgmtOutletsTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU identification."
::= { acsPowerMgmtOutletsTableEntry 8 }
acsPowerMgmtNumberOfOutletGroup OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of configured group of outlets."
::= { acsPowerMgmt 6 }
acsPowerMgmtGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtGroupTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about group of outlets."
::= { acsPowerMgmt 7 }
acsPowerMgmtGroupTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtGroupTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about group of outlets."
INDEX { acsPowerMgmtGroupTableIndex }
::= { acsPowerMgmtGroupTable 1 }
AcsPowerMgmtGroupTableEntry ::= SEQUENCE {
acsPowerMgmtGroupTableIndex InterfaceIndexOrZero,
acsPowerMgmtGroupTableName DisplayString, -- group name
acsPowerMgmtGroupTableStatus INTEGER, -- group status
acsPowerMgmtGroupTablePowerControl INTEGER -- manage the group
}
acsPowerMgmtGroupTableIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index of the group."
::= { acsPowerMgmtGroupTableEntry 1 }
acsPowerMgmtGroupTableName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of the group of outlets."
::= { acsPowerMgmtGroupTableEntry 2 }
acsPowerMgmtGroupTableStatus OBJECT-TYPE
SYNTAX INTEGER {
off(1),
on(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of the group of outlet."
::= { acsPowerMgmtGroupTableEntry 3 }
acsPowerMgmtGroupTablePowerControl OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
powerOn(2),
powerOff(3),
powerCycle(4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of power*(2-6) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
powerOn(2) = when SET the power On command is sent to PDU.
powerOff(3) = when SET the power Off command is sent to PDU.
powerCycle(4)=when SET the power cycle command is sent to PDU."
::= { acsPowerMgmtGroupTableEntry 4 }
acsPowerMgmtPhasesTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtPhasesTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains data monitoring of each detected phase."
::= { acsPowerMgmt 8 }
acsPowerMgmtPhasesTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtPhasesTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the data monitoring about phases."
INDEX { acsPowerMgmtPhasesTablePortNumber, acsPowerMgmtPhasesTablePduIndex, acsPowerMgmtPhasesTablePhaseIndex }
::= { acsPowerMgmtPhasesTable 1 }
AcsPowerMgmtPhasesTableEntry ::= SEQUENCE {
acsPowerMgmtPhasesTablePortNumber InterfaceIndex, -- number of serial port
acsPowerMgmtPhasesTablePduIndex InterfaceIndexOrZero, -- number of PDU
acsPowerMgmtPhasesTablePhaseIndex InterfaceIndexOrZero, -- phase index
acsPowerMgmtPhasesTablePhaseName DisplayString, -- Phase Name
acsPowerMgmtPhasesTablePduId DisplayString, -- PDU identification
acsPowerMgmtPhasesTablePortName DisplayString, -- Serial Port Name
acsPowerMgmtPhasesTableCurrentValue Integer32, -- actual value of Phase current sensor
acsPowerMgmtPhasesTableCurrentMax Integer32, -- max detected value of current sensor
acsPowerMgmtPhasesTableCurrentMin Integer32, -- min detected value of current sensor
acsPowerMgmtPhasesTableCurrentAvg Integer32, -- average value for current sensor
acsPowerMgmtPhasesTableCurrentReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPhasesTableVoltageType INTEGER, -- type of phase voltage
acsPowerMgmtPhasesTableVoltageValue Integer32, -- actual value of phase voltage
acsPowerMgmtPhasesTableVoltageMax Integer32, -- max value of voltage sensor
acsPowerMgmtPhasesTableVoltageMin Integer32, -- min value of voltage sensor
acsPowerMgmtPhasesTableVoltageAvg Integer32, -- avg value of voltage sensor
acsPowerMgmtPhasesTableVoltageReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPhasesTablePowerType INTEGER, -- type of phase power consumption
acsPowerMgmtPhasesTablePowerValue Integer32, -- actual value of phase power consumption
acsPowerMgmtPhasesTablePowerMax Integer32, -- max value
acsPowerMgmtPhasesTablePowerMin Integer32, -- min value
acsPowerMgmtPhasesTablePowerAvg Integer32, -- average value
acsPowerMgmtPhasesTablePowerReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPhasesTablePowerFactorType INTEGER, -- type of phase power factor
acsPowerMgmtPhasesTablePowerFactorValue Integer32, -- actual value of phase power factor
acsPowerMgmtPhasesTablePowerFactorMax Integer32, -- max value for power factor
acsPowerMgmtPhasesTablePowerFactorMin Integer32, -- min value for power factor
acsPowerMgmtPhasesTablePowerFactorAvg Integer32, -- avg value for power factor
acsPowerMgmtPhasesTablePowerFactorReset INTEGER, -- reset max, min and avg values
acsPowerMgmtPhasesTableAlarm INTEGER -- phase alarm status
}
acsPowerMgmtPhasesTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of serial port when the PDU is connected."
::= { acsPowerMgmtPhasesTableEntry 1 }
acsPowerMgmtPhasesTablePduIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A PDU position in the chain."
::= { acsPowerMgmtPhasesTableEntry 2 }
acsPowerMgmtPhasesTablePhaseIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"phase index in the PDU."
::= { acsPowerMgmtPhasesTableEntry 3 }
acsPowerMgmtPhasesTablePhaseName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"phase name in the PDU."
::= { acsPowerMgmtPhasesTableEntry 4 }
acsPowerMgmtPhasesTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU identification."
::= { acsPowerMgmtPhasesTableEntry 5 }
acsPowerMgmtPhasesTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of serial port when the PDU is connected."
::= { acsPowerMgmtPhasesTableEntry 6 }
acsPowerMgmtPhasesTableCurrentValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of current sensor in this phase.( A x 10 )"
::= { acsPowerMgmtPhasesTableEntry 7 }
acsPowerMgmtPhasesTableCurrentMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of current sensor in this phase.( A x 10 )"
::= { acsPowerMgmtPhasesTableEntry 8 }
acsPowerMgmtPhasesTableCurrentMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of current sensor in this phase.( A x 10 )"
::= { acsPowerMgmtPhasesTableEntry 9 }
acsPowerMgmtPhasesTableCurrentAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for current sensor in this phase.( A x 10 )"
::= { acsPowerMgmtPhasesTableEntry 10 }
acsPowerMgmtPhasesTableCurrentReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of current."
::= { acsPowerMgmtPhasesTableEntry 11 }
acsPowerMgmtPhasesTableVoltageType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of voltage values."
::= { acsPowerMgmtPhasesTableEntry 12 }
acsPowerMgmtPhasesTableVoltageValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of voltage sensor in this phase.( V )"
::= { acsPowerMgmtPhasesTableEntry 13 }
acsPowerMgmtPhasesTableVoltageMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of voltage sensor in this phase.( V )"
::= { acsPowerMgmtPhasesTableEntry 14 }
acsPowerMgmtPhasesTableVoltageMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of voltage sensor in this phase.( V )"
::= { acsPowerMgmtPhasesTableEntry 15 }
acsPowerMgmtPhasesTableVoltageAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for voltage sensor in this phase.( V )"
::= { acsPowerMgmtPhasesTableEntry 16 }
acsPowerMgmtPhasesTableVoltageReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of voltage."
::= { acsPowerMgmtPhasesTableEntry 17 }
acsPowerMgmtPhasesTablePowerType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power consumption values."
::= { acsPowerMgmtPhasesTableEntry 18 }
acsPowerMgmtPhasesTablePowerValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power consumption in this phase.( W x 10 )"
::= { acsPowerMgmtPhasesTableEntry 19 }
acsPowerMgmtPhasesTablePowerMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of power consumption in this phase.( W x 10 )"
::= { acsPowerMgmtPhasesTableEntry 20 }
acsPowerMgmtPhasesTablePowerMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of power consumption in this phase.( W x 10 )"
::= { acsPowerMgmtPhasesTableEntry 21 }
acsPowerMgmtPhasesTablePowerAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for power consumption in this phase.( W x 10 )"
::= { acsPowerMgmtPhasesTableEntry 22 }
acsPowerMgmtPhasesTablePowerReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of power consumption."
::= { acsPowerMgmtPhasesTableEntry 23 }
acsPowerMgmtPhasesTablePowerFactorType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power factor values."
::= { acsPowerMgmtPhasesTableEntry 24 }
acsPowerMgmtPhasesTablePowerFactorValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power factor in this phase.( PF x 100 )"
::= { acsPowerMgmtPhasesTableEntry 25 }
acsPowerMgmtPhasesTablePowerFactorMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of power factor in this phase.( PF x 100 )"
::= { acsPowerMgmtPhasesTableEntry 26 }
acsPowerMgmtPhasesTablePowerFactorMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of power factor in this phase.( PF x 100 )"
::= { acsPowerMgmtPhasesTableEntry 27 }
acsPowerMgmtPhasesTablePowerFactorAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for power factor in this phase.( PF x 100 )"
::= { acsPowerMgmtPhasesTableEntry 28 }
acsPowerMgmtPhasesTablePowerFactorReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of power factor."
::= { acsPowerMgmtPhasesTableEntry 29 }
acsPowerMgmtPhasesTableAlarm OBJECT-TYPE
SYNTAX INTEGER {
normal (1),
blow-fuse (2),
hw-ocp (3),
high-critical (4),
high-warning (5),
low-warning (6),
low-critical (7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Show the phase alarm status."
::= { acsPowerMgmtPhasesTableEntry 30 }
acsPowerMgmtBanksTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtBanksTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains data monitoring of each detected bank."
::= { acsPowerMgmt 9 }
acsPowerMgmtBanksTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtBanksTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the data monitoring about bank."
INDEX { acsPowerMgmtBanksTablePortNumber, acsPowerMgmtBanksTablePduIndex, acsPowerMgmtBanksTableBankIndex }
::= { acsPowerMgmtBanksTable 1 }
AcsPowerMgmtBanksTableEntry ::= SEQUENCE {
acsPowerMgmtBanksTablePortNumber InterfaceIndex, -- number of serial port
acsPowerMgmtBanksTablePduIndex InterfaceIndexOrZero, -- number of PDU
acsPowerMgmtBanksTableBankIndex InterfaceIndexOrZero, -- bank index
acsPowerMgmtBanksTableBankName DisplayString, -- Bank Name
acsPowerMgmtBanksTablePduId DisplayString, -- PDU identification
acsPowerMgmtBanksTablePortName DisplayString, -- Serial Port Name
acsPowerMgmtBanksTableCurrentValue Integer32, -- actual value of bank current sensor
acsPowerMgmtBanksTableCurrentMax Integer32, -- max detected value of current sensor
acsPowerMgmtBanksTableCurrentMin Integer32, -- min detected value of current sensor
acsPowerMgmtBanksTableCurrentAvg Integer32, -- average value for current sensor
acsPowerMgmtBanksTableCurrentReset INTEGER, -- reset max, min and avg values
acsPowerMgmtBanksTableVoltageType INTEGER, -- type of bank voltage
acsPowerMgmtBanksTableVoltageValue Integer32, -- actual value of bank voltage
acsPowerMgmtBanksTableVoltageMax Integer32, -- max value of voltage sensor
acsPowerMgmtBanksTableVoltageMin Integer32, -- min value of voltage sensor
acsPowerMgmtBanksTableVoltageAvg Integer32, -- avg value of voltage sensor
acsPowerMgmtBanksTableVoltageReset INTEGER, -- reset max, min and avg values
acsPowerMgmtBanksTablePowerType INTEGER, -- type of bank power consumption
acsPowerMgmtBanksTablePowerValue Integer32, -- actual value of bank power consumption
acsPowerMgmtBanksTablePowerMax Integer32, -- max value
acsPowerMgmtBanksTablePowerMin Integer32, -- min value
acsPowerMgmtBanksTablePowerAvg Integer32, -- average value
acsPowerMgmtBanksTablePowerReset INTEGER, -- reset max, min and avg values
acsPowerMgmtBanksTablePowerFactorType INTEGER, -- type of bank power factor
acsPowerMgmtBanksTablePowerFactorValue Integer32, -- actual value of bank power factor
acsPowerMgmtBanksTablePowerFactorMax Integer32, -- max value for power factor
acsPowerMgmtBanksTablePowerFactorMin Integer32, -- min value for power factor
acsPowerMgmtBanksTablePowerFactorAvg Integer32, -- avg value for power factor
acsPowerMgmtBanksTablePowerFactorReset INTEGER, -- reset max, min and avg values
acsPowerMgmtBanksTableAlarm INTEGER -- status of bank alarm
}
acsPowerMgmtBanksTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of serial port when the PDU is connected."
::= { acsPowerMgmtBanksTableEntry 1 }
acsPowerMgmtBanksTablePduIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A PDU position in the chain."
::= { acsPowerMgmtBanksTableEntry 2 }
acsPowerMgmtBanksTableBankIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bank index in the PDU."
::= { acsPowerMgmtBanksTableEntry 3 }
acsPowerMgmtBanksTableBankName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bank name in the PDU."
::= { acsPowerMgmtBanksTableEntry 4 }
acsPowerMgmtBanksTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU identification."
::= { acsPowerMgmtBanksTableEntry 5 }
acsPowerMgmtBanksTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of serial port when the PDU is connected."
::= { acsPowerMgmtBanksTableEntry 6 }
acsPowerMgmtBanksTableCurrentValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of current sensor in this bank.( A x 10 )"
::= { acsPowerMgmtBanksTableEntry 7 }
acsPowerMgmtBanksTableCurrentMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of current sensor in this bank.( A x 10 )"
::= { acsPowerMgmtBanksTableEntry 8 }
acsPowerMgmtBanksTableCurrentMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of current sensor in this bank.( A x 10 )"
::= { acsPowerMgmtBanksTableEntry 9 }
acsPowerMgmtBanksTableCurrentAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for current sensor in this bank.( A x 10 )"
::= { acsPowerMgmtBanksTableEntry 10 }
acsPowerMgmtBanksTableCurrentReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of current."
::= { acsPowerMgmtBanksTableEntry 11 }
acsPowerMgmtBanksTableVoltageType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of voltage values."
::= { acsPowerMgmtBanksTableEntry 12 }
acsPowerMgmtBanksTableVoltageValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of voltage sensor in this bank.( V )"
::= { acsPowerMgmtBanksTableEntry 13 }
acsPowerMgmtBanksTableVoltageMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of voltage sensor in this bank.( V )"
::= { acsPowerMgmtBanksTableEntry 14 }
acsPowerMgmtBanksTableVoltageMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of voltage sensor in this bank.( V )"
::= { acsPowerMgmtBanksTableEntry 15 }
acsPowerMgmtBanksTableVoltageAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for voltage sensor in this bank.( V )"
::= { acsPowerMgmtBanksTableEntry 16 }
acsPowerMgmtBanksTableVoltageReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of voltage."
::= { acsPowerMgmtBanksTableEntry 17 }
acsPowerMgmtBanksTablePowerType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power consumption values."
::= { acsPowerMgmtBanksTableEntry 18 }
acsPowerMgmtBanksTablePowerValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power consumption in this bank.( W x 10 )"
::= { acsPowerMgmtBanksTableEntry 19 }
acsPowerMgmtBanksTablePowerMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of power consumption in this bank.( W x 10 )"
::= { acsPowerMgmtBanksTableEntry 20 }
acsPowerMgmtBanksTablePowerMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of power consumption in this bank.( W x 10 )"
::= { acsPowerMgmtBanksTableEntry 21 }
acsPowerMgmtBanksTablePowerAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for power consumption in this bank.( W x 10 )"
::= { acsPowerMgmtBanksTableEntry 22 }
acsPowerMgmtBanksTablePowerReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of power consumption."
::= { acsPowerMgmtBanksTableEntry 23 }
acsPowerMgmtBanksTablePowerFactorType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
read (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power factor values."
::= { acsPowerMgmtBanksTableEntry 24 }
acsPowerMgmtBanksTablePowerFactorValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power factor in this bank.( PF x 100 )"
::= { acsPowerMgmtBanksTableEntry 25 }
acsPowerMgmtBanksTablePowerFactorMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of power factor in this bank.( PF x 100 )"
::= { acsPowerMgmtBanksTableEntry 26 }
acsPowerMgmtBanksTablePowerFactorMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of power factor in this bank.( PF x 100 )"
::= { acsPowerMgmtBanksTableEntry 27 }
acsPowerMgmtBanksTablePowerFactorAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for power factor in this bank.( PF x 100 )"
::= { acsPowerMgmtBanksTableEntry 28 }
acsPowerMgmtBanksTablePowerFactorReset OBJECT-TYPE
SYNTAX INTEGER {
no-action (1),
reset (2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION "Reset max, min and avg values of power factor."
::= { acsPowerMgmtBanksTableEntry 29 }
acsPowerMgmtBanksTableAlarm OBJECT-TYPE
SYNTAX INTEGER {
normal (1),
blow-fuse (2),
hw-ocp (3),
high-critical (4),
high-warning (5),
low-warning (6),
low-critical (7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Show the bank alarm status."
::= { acsPowerMgmtBanksTableEntry 30 }
acsPowerMgmtEnvMonTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtEnvMonTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains data monitoring of each detected environmental sensor."
::= { acsPowerMgmt 10 }
acsPowerMgmtEnvMonTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtEnvMonTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the data monitoring about environmental sensors."
INDEX { acsPowerMgmtEnvMonTablePortNumber, acsPowerMgmtEnvMonTablePduIndex, acsPowerMgmtEnvMonTableIndex }
::= { acsPowerMgmtEnvMonTable 1 }
AcsPowerMgmtEnvMonTableEntry ::= SEQUENCE {
acsPowerMgmtEnvMonTablePortNumber InterfaceIndex, -- number of serial port
acsPowerMgmtEnvMonTablePduIndex InterfaceIndexOrZero, -- number of PDU
acsPowerMgmtEnvMonTableIndex InterfaceIndexOrZero, -- index
acsPowerMgmtEnvMonTableName DisplayString, -- sensor name
acsPowerMgmtEnvMonTablePduId DisplayString, -- PDU identification
acsPowerMgmtEnvMonTablePortName DisplayString, -- Serial Port Name
acsPowerMgmtEnvMonTableType INTEGER, -- environmental sensor type
acsPowerMgmtEnvMonTableStatus INTEGER, -- state of digital sensor
acsPowerMgmtEnvMonTableValue Integer32, -- value
acsPowerMgmtEnvMonTableMaxValue Integer32 -- max value
}
acsPowerMgmtEnvMonTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of serial port when the PDU is connected."
::= { acsPowerMgmtEnvMonTableEntry 1 }
acsPowerMgmtEnvMonTablePduIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A PDU position in the chain."
::= { acsPowerMgmtEnvMonTableEntry 2 }
acsPowerMgmtEnvMonTableIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"envmon sensor index."
::= { acsPowerMgmtEnvMonTableEntry 3 }
acsPowerMgmtEnvMonTableName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"envmon sensor name."
::= { acsPowerMgmtEnvMonTableEntry 4 }
acsPowerMgmtEnvMonTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU identification."
::= { acsPowerMgmtEnvMonTableEntry 5 }
acsPowerMgmtEnvMonTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of serial port when the PDU is connected."
::= { acsPowerMgmtEnvMonTableEntry 6 }
acsPowerMgmtEnvMonTableType OBJECT-TYPE
SYNTAX INTEGER {
temp-internal (1),
temperature (2),
humidity (3),
air-flow (4),
smoke (5),
dry-concact (6),
water-level (7),
motion (8),
unplugged (9),
unknown (10)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "The type of environmental monitor."
::= { acsPowerMgmtEnvMonTableEntry 7 }
acsPowerMgmtEnvMonTableStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
triggered(2),
not-applicable(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Status of digital sensors:
Dry-Contact, Water level, Smoke sensor, Motion sensor."
::= { acsPowerMgmtEnvMonTableEntry 8 }
acsPowerMgmtEnvMonTableValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu."
::= { acsPowerMgmtEnvMonTableEntry 9 }
acsPowerMgmtEnvMonTableMaxValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu."
::= { acsPowerMgmtEnvMonTableEntry 10 }
acsPowerMgmtOutElecMonTable OBJECT-TYPE
SYNTAX SEQUENCE OF AcsPowerMgmtOutElecMonTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about data monitoring of outlets."
::= { acsPowerMgmt 11 }
acsPowerMgmtOutElecMonTableEntry OBJECT-TYPE
SYNTAX AcsPowerMgmtOutElecMonTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the outlet."
INDEX { acsPowerMgmtOutElecMonTablePortNumber,
acsPowerMgmtOutElecMonTablePduNumber,
acsPowerMgmtOutElecMonTableNumber }
::= { acsPowerMgmtOutElecMonTable 1 }
AcsPowerMgmtOutElecMonTableEntry ::= SEQUENCE {
acsPowerMgmtOutElecMonTablePortNumber InterfaceIndex, -- serial port #
acsPowerMgmtOutElecMonTablePduNumber InterfaceIndex,
acsPowerMgmtOutElecMonTableNumber InterfaceIndex, -- outlet number in PDU
acsPowerMgmtOutElecMonTableCurrentValue Integer32, -- actual value for current
acsPowerMgmtOutElecMonTableCurrentMax Integer32, -- max detected value for current
acsPowerMgmtOutElecMonTableCurrentMin Integer32, -- min detected value for current
acsPowerMgmtOutElecMonTableCurrentAvg Integer32, -- average value for current
acsPowerMgmtOutElecMonTableCurrentReset INTEGER, -- reset max, min and avg values of current
acsPowerMgmtOutElecMonTablePowerValue Integer32, -- actual value for power
acsPowerMgmtOutElecMonTablePowerMax Integer32, -- max detected value for power
acsPowerMgmtOutElecMonTablePowerMin Integer32, -- min detected value for power
acsPowerMgmtOutElecMonTablePowerAvg Integer32, -- average value for power
acsPowerMgmtOutElecMonTablePowerReset INTEGER, -- reset max, min and avg values of power
acsPowerMgmtOutElecMonTableVoltageValue Integer32, -- actual value for voltage
acsPowerMgmtOutElecMonTableVoltageMax Integer32, -- max detected value for voltage
acsPowerMgmtOutElecMonTableVoltageMin Integer32, -- min detected value for voltage
acsPowerMgmtOutElecMonTableVoltageAvg Integer32, -- average value for voltage
acsPowerMgmtOutElecMonTableVoltageReset INTEGER, -- reset max, min and avg values of voltage
acsPowerMgmtOutElecMonTablePowerFactorValue Integer32, -- actual value for power factor
acsPowerMgmtOutElecMonTablePowerFactorMax Integer32, -- max detected value for power factor
acsPowerMgmtOutElecMonTablePowerFactorMin Integer32, -- min detected value for power factor
acsPowerMgmtOutElecMonTablePowerFactorAvg Integer32, -- avg value for power factor
acsPowerMgmtOutElecMonTablePowerFactorReset INTEGER, -- reset max, min and avg values of power factor
acsPowerMgmtOutElecMonTableAlarm INTEGER -- outlet alarm status
}
acsPowerMgmtOutElecMonTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port number."
::= { acsPowerMgmtOutElecMonTableEntry 1 }
acsPowerMgmtOutElecMonTablePduNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index."
::= { acsPowerMgmtOutElecMonTableEntry 2 }
acsPowerMgmtOutElecMonTableNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of the outlet in the PDU."
::= { acsPowerMgmtOutElecMonTableEntry 3 }
acsPowerMgmtOutElecMonTableCurrentValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of outlet current sensor.( A x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 4 }
acsPowerMgmtOutElecMonTableCurrentMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of outlet current sensor.( A x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 5 }
acsPowerMgmtOutElecMonTableCurrentMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of outlet current sensor.( A x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 6 }
acsPowerMgmtOutElecMonTableCurrentAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for outlet current sensor.( A x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 7 }
acsPowerMgmtOutElecMonTableCurrentReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reset max, min and avertage values of outlet current."
::= { acsPowerMgmtOutElecMonTableEntry 8 }
acsPowerMgmtOutElecMonTablePowerValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of outlet power comsumption sensor.( W x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 9 }
acsPowerMgmtOutElecMonTablePowerMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of outlet power comsumption sensor.( W x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 10 }
acsPowerMgmtOutElecMonTablePowerMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of outlet power comsumption sensor.( W x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 11 }
acsPowerMgmtOutElecMonTablePowerAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for outlet power comsumption sensor.( W x 10 )"
::= { acsPowerMgmtOutElecMonTableEntry 12 }
acsPowerMgmtOutElecMonTablePowerReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reset max, min and avertage values of outlet power comsumption."
::= { acsPowerMgmtOutElecMonTableEntry 13 }
acsPowerMgmtOutElecMonTableVoltageValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of outlet voltage sensor.( V )"
::= { acsPowerMgmtOutElecMonTableEntry 14 }
acsPowerMgmtOutElecMonTableVoltageMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of outlet voltage sensor.( V )"
::= { acsPowerMgmtOutElecMonTableEntry 15 }
acsPowerMgmtOutElecMonTableVoltageMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of outlet voltage sensor.( V )"
::= { acsPowerMgmtOutElecMonTableEntry 16 }
acsPowerMgmtOutElecMonTableVoltageAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for outlet voltage sensor.( V )"
::= { acsPowerMgmtOutElecMonTableEntry 17 }
acsPowerMgmtOutElecMonTableVoltageReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reset max, min and avertage values of outlet voltage."
::= { acsPowerMgmtOutElecMonTableEntry 18 }
acsPowerMgmtOutElecMonTablePowerFactorValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of outlet power-factor sensor.( PF x 100 )"
::= { acsPowerMgmtOutElecMonTableEntry 19 }
acsPowerMgmtOutElecMonTablePowerFactorMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Max detected value of outlet power-factor sensor.( PF x 100 )"
::= { acsPowerMgmtOutElecMonTableEntry 20 }
acsPowerMgmtOutElecMonTablePowerFactorMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Min detected value of outlet power-factor sensor.( PF x 100 )"
::= { acsPowerMgmtOutElecMonTableEntry 21 }
acsPowerMgmtOutElecMonTablePowerFactorAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value for outlet power-factor sensor.( PF x 100 )"
::= { acsPowerMgmtOutElecMonTableEntry 22 }
acsPowerMgmtOutElecMonTablePowerFactorReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reset max, min and avertage values of outlet power-factor."
::= { acsPowerMgmtOutElecMonTableEntry 23 }
acsPowerMgmtOutElecMonTableAlarm OBJECT-TYPE
SYNTAX INTEGER {
normal (1),
blow-fuse (2),
hw-ocp (3),
high-critical (4),
high-warning (5),
low-warning (6),
low-critical (7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Show the outlet alarm status."
::= { acsPowerMgmtOutElecMonTableEntry 24 }
END