-- Avocent ACS MIB
|
|
-- Copyright 2009 Avocent Corporation
|
|
-- Revision: 2.0.1
|
|
-- Last Modified: October 10, 2010
|
|
--------------------------------------------------------------------------------
|
|
|
|
ACS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
Gauge,TimeTicks,IpAddress,Counter,NetworkAddress
|
|
FROM RFC1155-SMI
|
|
PhysAddress
|
|
FROM RFC1213-MIB
|
|
enterprises, MODULE-IDENTITY
|
|
FROM SNMPv2-SMI
|
|
OBJECT-TYPE, MODULE-IDENTITY, OBJECT-IDENTITY, Integer32
|
|
FROM SNMPv2-SMI
|
|
DisplayString
|
|
FROM SNMPv2-TC
|
|
InterfaceIndex, InterfaceIndexOrZero
|
|
FROM IF-MIB
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
--------------------------------------------------------------------------------
|
|
-- Object Groupings
|
|
--------------------------------------------------------------------------------
|
|
|
|
--@ Note: every product type should be uniquely identified underneath the
|
|
--@ acsProducts object group. Each product should report its unique acsProducts
|
|
--@ OBJECT IDENTIFIER in mib-2.system.sysObjectID. Please see the file
|
|
--@ "_Avocent Enterprise Object Identifier Assignment.txt" for a list of the
|
|
--@ IDs that have been assigned.
|
|
|
|
-- enterprises .1.3.6.1.4.1
|
|
|
|
-- avocent OBJECT IDENTIFIER ::= { enterprises 10418 }
|
|
|
|
acs MODULE-IDENTITY
|
|
LAST-UPDATED "201010100000Z"
|
|
ORGANIZATION "Avocent Corporation"
|
|
CONTACT-INFO "postal : Avocent Corporation
|
|
47281 Bayside Parkway
|
|
Fremont, CA 94538, USA
|
|
e-mail : Technical Support
|
|
techsupport@avocent.com"
|
|
DESCRIPTION
|
|
"This module defines the Avocent MIB extensions to
|
|
ACS60xx products."
|
|
REVISION "201010100000Z"
|
|
DESCRIPTION "Add products acs6004 and acs6008"
|
|
REVISION "200912110000Z"
|
|
DESCRIPTION "Extended acsPowerMgmt to support data monitoring
|
|
and Avocent PM-PDUs"
|
|
REVISION "200709170000Z"
|
|
DESCRIPTION "First Draft"
|
|
::= { enterprises 10418 16 }
|
|
|
|
acsProducts OBJECT IDENTIFIER ::= { acs 1 }
|
|
acsManagement OBJECT IDENTIFIER ::= { acs 2 }
|
|
--
|
|
acs6016 OBJECT IDENTIFIER ::= { acsProducts 1 } -- 10418.16.1.1
|
|
acs6032 OBJECT IDENTIFIER ::= { acsProducts 2 } -- 10418.16.1.2
|
|
acs6048 OBJECT IDENTIFIER ::= { acsProducts 3 } -- 10418.16.1.3
|
|
acs6004 OBJECT IDENTIFIER ::= { acsProducts 4 } -- 10418.16.1.4
|
|
acs6008 OBJECT IDENTIFIER ::= { acsProducts 5 } -- 10418.16.1.5
|
|
|
|
acsAppliance OBJECT IDENTIFIER ::= { acsManagement 1 } -- 10418.16.2.1
|
|
acsSessions OBJECT IDENTIFIER ::= { acsManagement 2 } -- 10418.16.2.2
|
|
acsSerialPort OBJECT IDENTIFIER ::= { acsManagement 3 } -- 10418.16.2.3
|
|
acsPowerMgmt OBJECT IDENTIFIER ::= { acsManagement 5 } -- 10418.16.2.5
|
|
|
|
-- objects under acsPowerMgmt
|
|
-- acsPowerMgmtNumSerialPorts ::= { acsPowerMgmt 1 }
|
|
-- acsPowerMgmtSerialTable ::= { acsPowerMgmt 2 }
|
|
-- acsPowerMgmtPDUTable ::= { acsPowerMgmt 3 }
|
|
-- acsPowerMgmtTotalNumberOfOutlets ::= { acsPowerMgmt 4 }
|
|
-- acsPowerMgmtOutletsTable ::= { acsPowerMgmt 5 }
|
|
-- acsPowerMgmtNumberOfOutletGroup ::= { acsPowerMgmt 6 }
|
|
-- acsPowerMgmtGroupTable ::= { acsPowerMgmt 7 }
|
|
-- acsPowerMgmtPhasesTable ::= { acsPowerMgmt 8 }
|
|
-- acsPowerMgmtBanksTable ::= { acsPowerMgmt 9 }
|
|
-- acsPowerMgmtEnvMonTable ::= { acsPowerMgmt 10 }
|
|
-- acsPowerMgmtOutElecMonTable ::= { acsPowerMgmt 11 }
|
|
|
|
|
|
--
|
|
-- Note that traps are defined in a separate trap MIB
|
|
--
|
|
acsTrapObject OBJECT IDENTIFIER ::= { acsManagement 6 } -- 10418.16.2.6
|
|
|
|
--
|
|
-- Type Definitions
|
|
--
|
|
|
|
--
|
|
-- Each enumeration represents the states of the appliance power supplies.
|
|
PowerSupplyState ::= INTEGER
|
|
{
|
|
statePowerOn(1),
|
|
statePowerOff(2),
|
|
powerNotInstaled(9999)
|
|
}
|
|
|
|
--
|
|
-- Each enumeration represents the speed of the serial port.
|
|
SerialPortSpeed ::= INTEGER
|
|
{
|
|
speed300bps(300),
|
|
speed600bps(600),
|
|
speed1200bps(1200),
|
|
speed2400bps(2400),
|
|
speed4800bps(4800),
|
|
speed9600bps(9600),
|
|
speed19200bps(19200),
|
|
speed38400bps(38400),
|
|
speed57600bps(57600),
|
|
speed115200bps(115200),
|
|
speed230400bps(230400),
|
|
speed460800bps(460800)
|
|
}
|
|
|
|
--
|
|
-- Each enumeration represents the state of the RS-232C signal.
|
|
SerialPortSignalState ::=INTEGER
|
|
{
|
|
up(1),
|
|
down(2)
|
|
}
|
|
|
|
--
|
|
-- Each enumeration represents the RJ-45 pin-out
|
|
SerialPortPinOut ::=INTEGER
|
|
{
|
|
cyclades(1),
|
|
cisco(2)
|
|
}
|
|
|
|
--
|
|
-- acsAppliance
|
|
-- OBJECT IDENTIFIER ::= { acsManagement 1 } 10418.16.2.1
|
|
--
|
|
acsHostName OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The appliance name"
|
|
::= { acsAppliance 1 }
|
|
|
|
acsProductModel OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..50) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The appliance product model"
|
|
::= { acsAppliance 2 }
|
|
|
|
acsPartNumber OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The part number of this appliance as shown on the label
|
|
attached or imprinted on the appliance."
|
|
::= { acsAppliance 3 }
|
|
|
|
acsSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The serial number of this appliance as shown on the label
|
|
attached or imprinted on the appliance."
|
|
::= { acsAppliance 4 }
|
|
|
|
acsEIDNumber OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The electronic ID number (EID) of this appliance as shown on the label
|
|
attached or imprinted on the appliance."
|
|
::= { acsAppliance 5 }
|
|
|
|
acsBootcodeVersion OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The version of the bootcode of this appliance."
|
|
::= { acsAppliance 6 }
|
|
|
|
acsFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The version of the firmware of this appliance."
|
|
::= { acsAppliance 7 }
|
|
|
|
acsPowerSupply OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"It gives information about Power Supply of this appliance"
|
|
::= { acsAppliance 8 }
|
|
|
|
acsPowerSupplyNumber OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of the power supplies of this appliance"
|
|
::= { acsPowerSupply 1 }
|
|
|
|
acsPowerSupplyStatePw1 OBJECT-TYPE
|
|
SYNTAX PowerSupplyState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the first power supply"
|
|
::= { acsPowerSupply 2 }
|
|
|
|
acsPowerSupplyStatePw2 OBJECT-TYPE
|
|
SYNTAX PowerSupplyState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the second power supply"
|
|
::= { acsPowerSupply 3 }
|
|
|
|
acsReboot OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reboot(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of reboot(2) will reboot the appliance.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reboot(2) = when SET the appliance immediately reboots."
|
|
::= { acsAppliance 9 }
|
|
|
|
--
|
|
-- acsSessions
|
|
-- OBJECT IDENTIFIER ::= { acsManagement 2 } 10418.16.2.2
|
|
--
|
|
acsActiveSessionsNumberOfSession OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of active sessions."
|
|
::= { acsSessions 1 }
|
|
|
|
acsActiveSessionsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsActiveSessionsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the list of active sessions."
|
|
::= { acsSessions 2 }
|
|
|
|
acsActiveSessionsTableEntry OBJECT-TYPE
|
|
SYNTAX AcsActiveSessionsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about the active session"
|
|
INDEX { acsActiveSessionsTableIndex }
|
|
::= { acsActiveSessionsTable 1 }
|
|
|
|
AcsActiveSessionsTableEntry ::= SEQUENCE {
|
|
acsActiveSessionsTableIndex InterfaceIndexOrZero,
|
|
acsActiveSessionsTableUser DisplayString, -- user name
|
|
acsActiveSessionsTableGroup DisplayString, -- group name
|
|
acsActiveSessionsTableType DisplayString, -- RO/RW-ssh,telnet or web
|
|
acsActiveSessionsTableConnection DisplayString, -- type + target name
|
|
acsActiveSessionsTableSessionTime DisplayString, -- time of session
|
|
acsActiveSessionsTableFrom DisplayString, -- source of the session
|
|
acsActiveSessionsTableKill INTEGER
|
|
}
|
|
|
|
acsActiveSessionsTableIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique index representing an entry in this table."
|
|
::= { acsActiveSessionsTableEntry 1 }
|
|
|
|
acsActiveSessionsTableUser OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the user that opens this session."
|
|
::= { acsActiveSessionsTableEntry 2 }
|
|
|
|
acsActiveSessionsTableGroup OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the group that the user belongs to."
|
|
::= { acsActiveSessionsTableEntry 3 }
|
|
|
|
acsActiveSessionsTableType OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The session type."
|
|
::= { acsActiveSessionsTableEntry 4 }
|
|
|
|
acsActiveSessionsTableConnection OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Connection type."
|
|
::= { acsActiveSessionsTableEntry 5 }
|
|
|
|
acsActiveSessionsTableSessionTime OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time of the session"
|
|
::= { acsActiveSessionsTableEntry 6 }
|
|
|
|
acsActiveSessionsTableFrom OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The source IP address of the session."
|
|
::= { acsActiveSessionsTableEntry 7 }
|
|
|
|
acsActiveSessionsTableKill OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
killSession(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of killSession(2) will kill the session.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
killSession(2)= when SET the appliance immediately kills the session."
|
|
::= { acsActiveSessionsTableEntry 8 }
|
|
|
|
--
|
|
-- acsSerialPort
|
|
-- OBJECT IDENTIFIER ::= { acsManagement 3 } 10418.16.2.3
|
|
--
|
|
|
|
acsSerialPortNumberOfPorts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of Serial Ports (physical serial port plus Aux Port."
|
|
::= { acsSerialPort 1 }
|
|
|
|
acsSerialPortTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsSerialPortTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains information about serial ports."
|
|
::= { acsSerialPort 2 }
|
|
|
|
acsSerialPortTableEntry OBJECT-TYPE
|
|
SYNTAX AcsSerialPortTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about specific serial port."
|
|
INDEX { acsSerialPortTableNumber }
|
|
::= { acsSerialPortTable 1 }
|
|
|
|
AcsSerialPortTableEntry ::= SEQUENCE {
|
|
acsSerialPortTableNumber Integer32, -- serial port number
|
|
acsSerialPortTableDeviceName DisplayString, -- associated device name
|
|
acsSerialPortTableStatus INTEGER, -- status of serial port
|
|
acsSerialPortTableName DisplayString, -- associated name
|
|
acsSerialPortTableProfile INTEGER, -- configured profile
|
|
acsSerialPortTablePinOut SerialPortPinOut, -- configure RJ45 pin-out
|
|
acsSerialPortTableComSpeed SerialPortSpeed, -- configured speed
|
|
acsSerialPortTableComParity INTEGER, -- configured parity
|
|
acsSerialPortTableComDataSize Integer32, -- configured data size
|
|
acsSerialPortTableComStopBits Integer32, -- configured stop bits
|
|
acsSerialPortTableComFlowControl INTEGER, -- configured flow control
|
|
acsSerialPortTableSignalStateDTR SerialPortSignalState, -- state of DTR RS-232C signal
|
|
acsSerialPortTableSignalStateDCD SerialPortSignalState, -- state of DCD RS-232C signal
|
|
acsSerialPortTableSignalStateRTS SerialPortSignalState, -- state of RTS RS-232C signal
|
|
acsSerialPortTableSignalStateCTS SerialPortSignalState, -- state of CTS RS-232C signal
|
|
acsSerialPortTableTxBytes Integer32, -- number of transmitted bytes
|
|
acsSerialPortTableRxBytes Integer32, -- number of received bytes
|
|
acsSerialPortTableFrameError Integer32, -- number of detected frame errors
|
|
acsSerialPortTableParityError Integer32, -- number of detected parity errors
|
|
acsSerialPortTableBreak Integer32, -- number of detected break
|
|
acsSerialPortTableOverrun Integer32 -- number of detected overrun errors
|
|
}
|
|
|
|
acsSerialPortTableNumber OBJECT-TYPE
|
|
SYNTAX Integer32 (1..49)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique index representing an entry in this table.
|
|
It is the number of the serial port. For AUX port,
|
|
the number will be the number of physical serial ports plus 1."
|
|
::= { acsSerialPortTableEntry 1 }
|
|
|
|
acsSerialPortTableDeviceName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The associated device name for the serial port."
|
|
::= { acsSerialPortTableEntry 2 }
|
|
|
|
acsSerialPortTableStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
idle(2),
|
|
inUse(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the serial port:
|
|
disabled(1) = it was configured as disable.
|
|
idle(2) = there is not any session opened in this port.
|
|
inUse(3) = there is session(s) opened in this port."
|
|
::= { acsSerialPortTableEntry 3 }
|
|
|
|
acsSerialPortTableName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name associated with this serial port."
|
|
::= { acsSerialPortTableEntry 4 }
|
|
|
|
acsSerialPortTableProfile OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
casProfile(1),
|
|
tsProfile(2),
|
|
dialInProfile(3),
|
|
powerProfile(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configured profile for this serial port."
|
|
::= { acsSerialPortTableEntry 5 }
|
|
|
|
acsSerialPortTablePinOut OBJECT-TYPE
|
|
SYNTAX SerialPortPinOut
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RJ45 Pin-out configured for this serial port."
|
|
::= { acsSerialPortTableEntry 6 }
|
|
|
|
acsSerialPortTableComSpeed OBJECT-TYPE
|
|
SYNTAX SerialPortSpeed
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Speed configured for this serial port."
|
|
::= { acsSerialPortTableEntry 7 }
|
|
|
|
acsSerialPortTableComParity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(1),
|
|
odd(2),
|
|
even(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Parity configured for this serial port."
|
|
::= { acsSerialPortTableEntry 8 }
|
|
|
|
acsSerialPortTableComDataSize OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data Size configured for this serial port."
|
|
::= { acsSerialPortTableEntry 9 }
|
|
|
|
acsSerialPortTableComStopBits OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of Stop Bits configured for this serial port."
|
|
::= { acsSerialPortTableEntry 10 }
|
|
|
|
acsSerialPortTableComFlowControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(1),
|
|
hardware(2),
|
|
software(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Flow Control configured for this serial port."
|
|
::= { acsSerialPortTableEntry 11 }
|
|
|
|
acsSerialPortTableSignalStateDTR OBJECT-TYPE
|
|
SYNTAX SerialPortSignalState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the DTR RS-232C signal."
|
|
::= { acsSerialPortTableEntry 12 }
|
|
|
|
acsSerialPortTableSignalStateDCD OBJECT-TYPE
|
|
SYNTAX SerialPortSignalState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the DCD RS-232C signal."
|
|
::= { acsSerialPortTableEntry 13 }
|
|
|
|
acsSerialPortTableSignalStateRTS OBJECT-TYPE
|
|
SYNTAX SerialPortSignalState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the RTS RS-232C signal."
|
|
::= { acsSerialPortTableEntry 14 }
|
|
|
|
acsSerialPortTableSignalStateCTS OBJECT-TYPE
|
|
SYNTAX SerialPortSignalState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the CTS RS-232C signal."
|
|
::= { acsSerialPortTableEntry 15 }
|
|
|
|
acsSerialPortTableTxBytes OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of transmited bytes by the serial port."
|
|
::= { acsSerialPortTableEntry 16 }
|
|
|
|
acsSerialPortTableRxBytes OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of received bytes by the serial port."
|
|
::= { acsSerialPortTableEntry 17 }
|
|
|
|
acsSerialPortTableFrameError OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of frame error detected in the serial port."
|
|
::= { acsSerialPortTableEntry 18 }
|
|
|
|
acsSerialPortTableParityError OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of parity error detected in the serial port."
|
|
::= { acsSerialPortTableEntry 19 }
|
|
|
|
acsSerialPortTableBreak OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of break detected in the serial port."
|
|
::= { acsSerialPortTableEntry 20 }
|
|
|
|
acsSerialPortTableOverrun OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of overrun error detected in the serial port."
|
|
::= { acsSerialPortTableEntry 21 }
|
|
|
|
--
|
|
-- acsPowerMgmt
|
|
-- OBJECT IDENTIFIER ::= { acsManagement 5 } 10418.16.2.5
|
|
--
|
|
acsPowerMgmtNumSerialPorts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of Serial Ports that has PDU connected on the appliance."
|
|
::= { acsPowerMgmt 1 }
|
|
|
|
acsPowerMgmtSerialTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtSerialTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Information about each serial port thas has PDU connect."
|
|
::= { acsPowerMgmt 2 }
|
|
|
|
acsPowerMgmtSerialTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtSerialTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Information about each serial port thas has PDU connect."
|
|
INDEX { acsPowerMgmtSerialTableIndex }
|
|
::= { acsPowerMgmtSerialTable 1 }
|
|
|
|
AcsPowerMgmtSerialTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtSerialTableIndex InterfaceIndex,
|
|
acsPowerMgmtSerialTablePortNumber Integer32,
|
|
acsPowerMgmtSerialTableDeviceName DisplayString,
|
|
acsPowerMgmtSerialTableNumberPDUs Integer32
|
|
}
|
|
|
|
acsPowerMgmtSerialTableIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the register."
|
|
::= { acsPowerMgmtSerialTableEntry 1 }
|
|
|
|
acsPowerMgmtSerialTablePortNumber OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of the serial port when the PDU is connected."
|
|
::= { acsPowerMgmtSerialTableEntry 2 }
|
|
|
|
acsPowerMgmtSerialTableDeviceName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The device name of this serial port."
|
|
::= { acsPowerMgmtSerialTableEntry 3 }
|
|
|
|
acsPowerMgmtSerialTableNumberPDUs OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total number of units connected in this serial port."
|
|
::= { acsPowerMgmtSerialTableEntry 4 }
|
|
|
|
acsPowerMgmtPDUTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtPDUTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the list of detected PDUs."
|
|
::= { acsPowerMgmt 3 }
|
|
|
|
acsPowerMgmtPDUTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtPDUTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about the PDU."
|
|
INDEX { acsPowerMgmtPDUTablePortNumber, acsPowerMgmtPDUTablePduIndex }
|
|
::= { acsPowerMgmtPDUTable 1 }
|
|
|
|
AcsPowerMgmtPDUTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtPDUTablePortNumber InterfaceIndex, -- number of serial port
|
|
acsPowerMgmtPDUTablePduIndex InterfaceIndexOrZero,
|
|
acsPowerMgmtPDUTablePduId DisplayString, -- PDU identification
|
|
acsPowerMgmtPDUTablePortName DisplayString, -- Serial Port Name
|
|
acsPowerMgmtPDUTableModel DisplayString, -- PDU model
|
|
acsPowerMgmtPDUTableVendor DisplayString, -- Vendor
|
|
acsPowerMgmtPDUTableFirmwareVersion DisplayString, -- Firmware Version
|
|
acsPowerMgmtPDUTableNumberOfOutlets Integer32,
|
|
acsPowerMgmtPDUTableCurrentNOS Integer32, -- OBSOLETED number of current sensors
|
|
acsPowerMgmtPDUTableCurrent1Value Integer32, -- OBSOLETED actual value for current of the sensor 1
|
|
acsPowerMgmtPDUTableCurrent1Max Integer32, -- OBSOLETED max value for current of the sensor 1
|
|
acsPowerMgmtPDUTableCurrent2Value Integer32, -- OBSOLETED actual value for current of the sensor 2
|
|
acsPowerMgmtPDUTableCurrent2Max Integer32, -- OBSOLETED max value for current of the sensor 2
|
|
acsPowerMgmtPDUTableCurrent3Value Integer32, -- OBSOLETED actual value for current of the sensor 3
|
|
acsPowerMgmtPDUTableCurrent3Max Integer32, -- OBSOLETED max value for current of the sensor 3
|
|
acsPowerMgmtPDUTableTemperatureNOS Integer32, -- OBSOLETED number of temperature sensors
|
|
acsPowerMgmtPDUTableTemperature1Value Integer32, -- OBSOLETED actual value for Temperature 1
|
|
acsPowerMgmtPDUTableTemperature1Max Integer32, -- OBSOLETED max value for Temperature 1
|
|
acsPowerMgmtPDUTableTemperature2Value Integer32, -- OBSOLETED actual value for Temperaturet 2
|
|
acsPowerMgmtPDUTableTemperature2Max Integer32, -- OBSOLETED max value for Temperature 2
|
|
acsPowerMgmtPDUTableTemperature3Value Integer32, -- OBSOLETED actual value for Temperature 3
|
|
acsPowerMgmtPDUTableTemperature3Max Integer32, -- OBSOLETED max value for Temperature 3
|
|
acsPowerMgmtPDUTableHumidityNOS Integer32, -- OBSOLETED humidity number of humidity sensors
|
|
acsPowerMgmtPDUTableHumidity1Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 1
|
|
acsPowerMgmtPDUTableHumidity1Max Integer32, -- OBSOLETED max value for Humidityof the sensor 1
|
|
acsPowerMgmtPDUTableHumidity2Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 2
|
|
acsPowerMgmtPDUTableHumidity2Max Integer32, -- OBSOLETED max value for Humidity of the sensor 2
|
|
acsPowerMgmtPDUTableHumidity3Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 3
|
|
acsPowerMgmtPDUTableHumidity3Max Integer32, -- OBSOLETED max value for Humidity of the sensor 3
|
|
acsPowerMgmtPDUTableVoltageNOS Integer32, -- OBSOLETED number of voltage sensor
|
|
acsPowerMgmtPDUTableVoltage1Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 1
|
|
acsPowerMgmtPDUTableVoltage1Max Integer32, -- OBSOLETED max value for Voltage of the sensor 1
|
|
acsPowerMgmtPDUTableVoltage2Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 2
|
|
acsPowerMgmtPDUTableVoltage2Max Integer32, -- OBSOLETED max value for Voltaget of the sensor 2
|
|
acsPowerMgmtPDUTableVoltage3Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 3
|
|
acsPowerMgmtPDUTableVoltage3Max Integer32, -- OBSOLETED max value for Voltage of the sensor 3
|
|
acsPowerMgmtPDUTableNumberOfPhases Integer32, -- number of phases (single or 3-phases)
|
|
acsPowerMgmtPDUTableNumberOfBanks Integer32, -- number of banks
|
|
acsPowerMgmtPDUTableCurrentValue Integer32, -- actual value of PDU current sensor
|
|
acsPowerMgmtPDUTableCurrentMax Integer32, -- max detected value of current sensor
|
|
acsPowerMgmtPDUTableCurrentMin Integer32, -- min detected value of current sensor
|
|
acsPowerMgmtPDUTableCurrentAvg Integer32, -- average value for current sensor
|
|
acsPowerMgmtPDUTableCurrentReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPDUTableVoltageType INTEGER, -- type of PDU voltage
|
|
acsPowerMgmtPDUTableVoltageValue Integer32, -- actual value of PDU voltage
|
|
acsPowerMgmtPDUTableVoltageMax Integer32, -- max value of voltage sensor
|
|
acsPowerMgmtPDUTableVoltageMin Integer32, -- min value of voltage sensor
|
|
acsPowerMgmtPDUTableVoltageAvg Integer32, -- avg value of voltage sensor
|
|
acsPowerMgmtPDUTableVoltageReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPDUTablePowerType INTEGER, -- type of PDU power consumption
|
|
acsPowerMgmtPDUTablePowerValue Integer32, -- actual value of PDU power consumption
|
|
acsPowerMgmtPDUTablePowerMax Integer32, -- max value
|
|
acsPowerMgmtPDUTablePowerMin Integer32, -- min value
|
|
acsPowerMgmtPDUTablePowerAvg Integer32, -- average value
|
|
acsPowerMgmtPDUTablePowerReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPDUTablePowerFactorType INTEGER, -- type of PDU power factor
|
|
acsPowerMgmtPDUTablePowerFactorValue Integer32, -- actual value of PDU power factor
|
|
acsPowerMgmtPDUTablePowerFactorMax Integer32, -- max value for power factor
|
|
acsPowerMgmtPDUTablePowerFactorMin Integer32, -- min value for power factor
|
|
acsPowerMgmtPDUTablePowerFactorAvg Integer32, -- avg value for power factor
|
|
acsPowerMgmtPDUTablePowerFactorReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPDUTableAlarm INTEGER, -- status of PDU alarm
|
|
acsPowerMgmtPDUTableEnvSensors Integer32 -- number of environmental sensors
|
|
}
|
|
|
|
acsPowerMgmtPDUTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtPDUTableEntry 1 }
|
|
|
|
acsPowerMgmtPDUTablePduIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A PDU position in the chain."
|
|
::= { acsPowerMgmtPDUTableEntry 2 }
|
|
|
|
acsPowerMgmtPDUTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { acsPowerMgmtPDUTableEntry 3 }
|
|
|
|
acsPowerMgmtPDUTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtPDUTableEntry 4 }
|
|
|
|
acsPowerMgmtPDUTableModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Model of the PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 5 }
|
|
|
|
acsPowerMgmtPDUTableVendor OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Vendor of the PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 6 }
|
|
|
|
acsPowerMgmtPDUTableFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Version of the PDU firmware."
|
|
::= { acsPowerMgmtPDUTableEntry 7 }
|
|
|
|
acsPowerMgmtPDUTableNumberOfOutlets OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of outlets of the PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 8 }
|
|
|
|
acsPowerMgmtPDUTableCurrentNOS OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Number of current sensors in the PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 9 }
|
|
|
|
acsPowerMgmtPDUTableCurrent1Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Current of the sensor 1 in this PDU unit in AMP.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)"
|
|
::= { acsPowerMgmtPDUTableEntry 10 }
|
|
|
|
acsPowerMgmtPDUTableCurrent1Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum current of the sensor 1 in this PDU unit in AMP.
|
|
When the PDU does not have support for maximum value,
|
|
the value will be 0.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)
|
|
Clear this value, set it with Zero value."
|
|
::= { acsPowerMgmtPDUTableEntry 11 }
|
|
|
|
acsPowerMgmtPDUTableCurrent2Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Current of the sensor 2 in this PDU unit in AMP.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)"
|
|
::= { acsPowerMgmtPDUTableEntry 12 }
|
|
|
|
acsPowerMgmtPDUTableCurrent2Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum current of the sensor 2 in this PDU unit in AMP.
|
|
When the PDU does not have support for maximum value,
|
|
the value will be 0.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)
|
|
Clear this value, set it with Zero value."
|
|
::= { acsPowerMgmtPDUTableEntry 13}
|
|
|
|
acsPowerMgmtPDUTableCurrent3Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Current of the sensor 3 in this PDU unit in AMP.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)"
|
|
::= { acsPowerMgmtPDUTableEntry 14 }
|
|
|
|
acsPowerMgmtPDUTableCurrent3Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum current of the sensor 3 in this PDU unit in AMP.
|
|
When the PDU does not have support for maximum value,
|
|
the value will be 0.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)
|
|
Clear this value, set it with Zero value."
|
|
::= { acsPowerMgmtPDUTableEntry 15 }
|
|
|
|
acsPowerMgmtPDUTableTemperatureNOS OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Number of temperature sensors in the PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 16 }
|
|
|
|
acsPowerMgmtPDUTableTemperature1Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Temperature of this PM unit in Celsius degrees.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
|
|
::= { acsPowerMgmtPDUTableEntry 17 }
|
|
|
|
acsPowerMgmtPDUTableTemperature1Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum temperature detected in this PM unit in Celsius degrees.
|
|
The value will be Zero when the PDU does not have support for maximum value.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { acsPowerMgmtPDUTableEntry 18 }
|
|
|
|
acsPowerMgmtPDUTableTemperature2Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Temperature of this PM unit in Celsius degrees.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
|
|
::= { acsPowerMgmtPDUTableEntry 19 }
|
|
|
|
acsPowerMgmtPDUTableTemperature2Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum temperature detected in this PM unit in Celsius degrees.
|
|
The value will be Zero when the PDU does not have support for maximum value.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { acsPowerMgmtPDUTableEntry 20 }
|
|
|
|
acsPowerMgmtPDUTableTemperature3Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Temperature of this PM unit in Celsius degrees.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
|
|
::= { acsPowerMgmtPDUTableEntry 21 }
|
|
|
|
acsPowerMgmtPDUTableTemperature3Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum temperature detected in this PM unit in Celsius degrees.
|
|
The value will be Zero when the PDU does not have support for maximum value.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { acsPowerMgmtPDUTableEntry 22 }
|
|
|
|
acsPowerMgmtPDUTableHumidityNOS OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Number of humidity sensors in the PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 23 }
|
|
|
|
acsPowerMgmtPDUTableHumidity1Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Humidity of this PM unit .
|
|
If the humidity measurement is not installed this
|
|
value will be 0."
|
|
::= { acsPowerMgmtPDUTableEntry 24 }
|
|
|
|
acsPowerMgmtPDUTableHumidity1Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum humidity detected in this PM unit.
|
|
If the humidity measurement is not installed or the PDU does not have support for maximum value this
|
|
value will be 0.
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { acsPowerMgmtPDUTableEntry 25 }
|
|
|
|
acsPowerMgmtPDUTableHumidity2Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Humidity of this PM unit .
|
|
If the humidity measurement is not installed this
|
|
value will be 0."
|
|
::= { acsPowerMgmtPDUTableEntry 26 }
|
|
|
|
acsPowerMgmtPDUTableHumidity2Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum humidity detected in this PM unit.
|
|
If the humidity measurement is not installed or the PDU does not have support for maximum value this
|
|
value will be 0.
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { acsPowerMgmtPDUTableEntry 27 }
|
|
|
|
acsPowerMgmtPDUTableHumidity3Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Humidity of this PM unit .
|
|
If the humidity measurement is not installed this
|
|
value will be 0."
|
|
::= { acsPowerMgmtPDUTableEntry 28 }
|
|
|
|
acsPowerMgmtPDUTableHumidity3Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum humidity detected in this PM unit.
|
|
If the humidity measurement is not installed or the PDU does not have support for maximum value this
|
|
value will be 0.
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { acsPowerMgmtPDUTableEntry 29 }
|
|
|
|
acsPowerMgmtPDUTableVoltageNOS OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Number of voltage sensors in the PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 30 }
|
|
|
|
acsPowerMgmtPDUTableVoltage1Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Voltage of this sensor in this PDU unit."
|
|
::= { acsPowerMgmtPDUTableEntry 31 }
|
|
|
|
acsPowerMgmtPDUTableVoltage1Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum voltage of this sensor in this PDU unit.
|
|
Set with Zero value to clear the maximum voltage."
|
|
::= { acsPowerMgmtPDUTableEntry 32 }
|
|
|
|
acsPowerMgmtPDUTableVoltage2Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Voltage of this sensor in this PDU unit."
|
|
::= { acsPowerMgmtPDUTableEntry 33 }
|
|
|
|
acsPowerMgmtPDUTableVoltage2Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum voltage of this sensor in this PDU unit.
|
|
Set with Zero value to clear the maximum voltage."
|
|
::= { acsPowerMgmtPDUTableEntry 34 }
|
|
|
|
acsPowerMgmtPDUTableVoltage3Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Voltage of this sensor in this PDU unit."
|
|
::= { acsPowerMgmtPDUTableEntry 35 }
|
|
|
|
acsPowerMgmtPDUTableVoltage3Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum voltage of this sensor in this PDU unit.
|
|
Set with Zero value to clear the maximum voltage."
|
|
::= { acsPowerMgmtPDUTableEntry 36 }
|
|
|
|
acsPowerMgmtPDUTableNumberOfPhases OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
single-phase (0),
|
|
three-phase (3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of phases of this PDU unit."
|
|
::= { acsPowerMgmtPDUTableEntry 37 }
|
|
|
|
acsPowerMgmtPDUTableNumberOfBanks OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of banks of this PDU unit."
|
|
::= { acsPowerMgmtPDUTableEntry 38 }
|
|
|
|
acsPowerMgmtPDUTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of current sensor in this PDU.( A x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 39 }
|
|
|
|
acsPowerMgmtPDUTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of current sensor in this PDU.( A x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 40 }
|
|
|
|
acsPowerMgmtPDUTableCurrentMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of current sensor in this PDU.( A x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 41 }
|
|
|
|
acsPowerMgmtPDUTableCurrentAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for current sensor in this PDU.( A x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 42 }
|
|
|
|
acsPowerMgmtPDUTableCurrentReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of current."
|
|
::= { acsPowerMgmtPDUTableEntry 43 }
|
|
|
|
acsPowerMgmtPDUTableVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of voltage values."
|
|
::= { acsPowerMgmtPDUTableEntry 44 }
|
|
|
|
acsPowerMgmtPDUTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of voltage sensor in this PDU unit.( V )"
|
|
::= { acsPowerMgmtPDUTableEntry 45 }
|
|
|
|
acsPowerMgmtPDUTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of voltage sensor in this PDU unit.( V )"
|
|
::= { acsPowerMgmtPDUTableEntry 46 }
|
|
|
|
acsPowerMgmtPDUTableVoltageMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of voltage sensor in this PDU unit.( V )"
|
|
::= { acsPowerMgmtPDUTableEntry 47 }
|
|
|
|
acsPowerMgmtPDUTableVoltageAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for voltage sensor in this PDU unit.( V )"
|
|
::= { acsPowerMgmtPDUTableEntry 48 }
|
|
|
|
acsPowerMgmtPDUTableVoltageReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of voltage."
|
|
::= { acsPowerMgmtPDUTableEntry 49 }
|
|
|
|
acsPowerMgmtPDUTablePowerType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power consumption values.( W x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 50 }
|
|
|
|
acsPowerMgmtPDUTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power consumption in this PDU unit.( W x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 51 }
|
|
|
|
acsPowerMgmtPDUTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of power consumption in this PDU unit.( W x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 52 }
|
|
|
|
acsPowerMgmtPDUTablePowerMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of power consumption in this PDU unit.( W x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 53 }
|
|
|
|
acsPowerMgmtPDUTablePowerAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for power consumption in this PDU unit.( W x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 54 }
|
|
|
|
acsPowerMgmtPDUTablePowerReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of power consumption."
|
|
::= { acsPowerMgmtPDUTableEntry 55 }
|
|
|
|
acsPowerMgmtPDUTablePowerFactorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power factor values."
|
|
::= { acsPowerMgmtPDUTableEntry 56 }
|
|
|
|
acsPowerMgmtPDUTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power factor in this PDU unit.( PF x 100 )"
|
|
::= { acsPowerMgmtPDUTableEntry 57 }
|
|
|
|
acsPowerMgmtPDUTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of power factor in this PDU unit.( PF x 100 )"
|
|
::= { acsPowerMgmtPDUTableEntry 58 }
|
|
|
|
acsPowerMgmtPDUTablePowerFactorMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of power factor in this PDU unit.( PF x 100 )"
|
|
::= { acsPowerMgmtPDUTableEntry 59 }
|
|
|
|
acsPowerMgmtPDUTablePowerFactorAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for power factor in this PDU unit.( PF x 100 )"
|
|
::= { acsPowerMgmtPDUTableEntry 60 }
|
|
|
|
acsPowerMgmtPDUTablePowerFactorReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of power factor."
|
|
::= { acsPowerMgmtPDUTableEntry 61 }
|
|
|
|
acsPowerMgmtPDUTableAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal (1),
|
|
blow-fuse (2),
|
|
hw-ocp (3),
|
|
high-critical (4),
|
|
high-warning (5),
|
|
low-warning (6),
|
|
low-critical (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Show the PDU alarm status."
|
|
::= { acsPowerMgmtPDUTableEntry 62 }
|
|
|
|
acsPowerMgmtPDUTableEnvSensors OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of environmental sensor in this PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 63 }
|
|
|
|
|
|
acsPowerMgmtTotalNumberOfOutlets OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of outlets managed by the appliance."
|
|
::= { acsPowerMgmt 4 }
|
|
|
|
acsPowerMgmtOutletsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtOutletsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the information about outlets."
|
|
::= { acsPowerMgmt 5 }
|
|
|
|
acsPowerMgmtOutletsTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtOutletsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about the outlet."
|
|
INDEX { acsPowerMgmtOutletsTablePortNumber,
|
|
acsPowerMgmtOutletsTablePduNumber,
|
|
acsPowerMgmtOutletsTableNumber }
|
|
::= { acsPowerMgmtOutletsTable 1 }
|
|
|
|
AcsPowerMgmtOutletsTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtOutletsTablePortNumber InterfaceIndex, -- serial port #
|
|
acsPowerMgmtOutletsTablePduNumber InterfaceIndex,
|
|
acsPowerMgmtOutletsTableNumber InterfaceIndex, -- outlet number in PDU
|
|
acsPowerMgmtOutletsTableName DisplayString, -- outlet name
|
|
acsPowerMgmtOutletsTableStatus INTEGER, -- outlet status
|
|
acsPowerMgmtOutletsTablePowerControl INTEGER, -- manage the outlet
|
|
acsPowerMgmtOutletsTablePortName DisplayString, -- serial port name
|
|
acsPowerMgmtOutletsTablePduId DisplayString -- PDU ID
|
|
}
|
|
|
|
acsPowerMgmtOutletsTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Port number."
|
|
::= { acsPowerMgmtOutletsTableEntry 1 }
|
|
|
|
acsPowerMgmtOutletsTablePduNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index."
|
|
::= { acsPowerMgmtOutletsTableEntry 2 }
|
|
|
|
acsPowerMgmtOutletsTableNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of the outlet in the PDU."
|
|
::= { acsPowerMgmtOutletsTableEntry 3 }
|
|
|
|
acsPowerMgmtOutletsTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of the outlet."
|
|
::= { acsPowerMgmtOutletsTableEntry 4 }
|
|
|
|
acsPowerMgmtOutletsTableStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the outlet."
|
|
::= { acsPowerMgmtOutletsTableEntry 5 }
|
|
|
|
acsPowerMgmtOutletsTablePowerControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
powerOn(2),
|
|
powerOff(3),
|
|
powerCycle(4),
|
|
powerLock(5),
|
|
powerUnlock(6)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of power*(2-6) will send command to PDU.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
powerOn(2) = when SET the power On command is sent to PDU.
|
|
powerOff(3) = when SET the power Off command is sent to PDU.
|
|
powerCycle(4)=when SET the power cycle command is sent to PDU.
|
|
powerLock(5)= when SET the power lock command is sent to PDU.
|
|
powerUnlock(6)=when SET the power unlock command is sent to PDU.
|
|
The powerLock and powerUnlock are valid only for Cyclades-PM PDUs"
|
|
::= { acsPowerMgmtOutletsTableEntry 6 }
|
|
|
|
acsPowerMgmtOutletsTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Port Name where the PDU is connected."
|
|
::= { acsPowerMgmtOutletsTableEntry 7 }
|
|
|
|
acsPowerMgmtOutletsTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { acsPowerMgmtOutletsTableEntry 8 }
|
|
|
|
acsPowerMgmtNumberOfOutletGroup OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of configured group of outlets."
|
|
::= { acsPowerMgmt 6 }
|
|
|
|
acsPowerMgmtGroupTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtGroupTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the information about group of outlets."
|
|
::= { acsPowerMgmt 7 }
|
|
|
|
acsPowerMgmtGroupTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtGroupTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about group of outlets."
|
|
INDEX { acsPowerMgmtGroupTableIndex }
|
|
::= { acsPowerMgmtGroupTable 1 }
|
|
|
|
AcsPowerMgmtGroupTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtGroupTableIndex InterfaceIndexOrZero,
|
|
acsPowerMgmtGroupTableName DisplayString, -- group name
|
|
acsPowerMgmtGroupTableStatus INTEGER, -- group status
|
|
acsPowerMgmtGroupTablePowerControl INTEGER -- manage the group
|
|
}
|
|
|
|
acsPowerMgmtGroupTableIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of the group."
|
|
::= { acsPowerMgmtGroupTableEntry 1 }
|
|
|
|
acsPowerMgmtGroupTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of the group of outlets."
|
|
::= { acsPowerMgmtGroupTableEntry 2 }
|
|
|
|
acsPowerMgmtGroupTableStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the group of outlet."
|
|
::= { acsPowerMgmtGroupTableEntry 3 }
|
|
|
|
acsPowerMgmtGroupTablePowerControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
powerOn(2),
|
|
powerOff(3),
|
|
powerCycle(4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of power*(2-6) will send command to PDU.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
powerOn(2) = when SET the power On command is sent to PDU.
|
|
powerOff(3) = when SET the power Off command is sent to PDU.
|
|
powerCycle(4)=when SET the power cycle command is sent to PDU."
|
|
::= { acsPowerMgmtGroupTableEntry 4 }
|
|
|
|
acsPowerMgmtPhasesTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtPhasesTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains data monitoring of each detected phase."
|
|
::= { acsPowerMgmt 8 }
|
|
|
|
acsPowerMgmtPhasesTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtPhasesTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the data monitoring about phases."
|
|
INDEX { acsPowerMgmtPhasesTablePortNumber, acsPowerMgmtPhasesTablePduIndex, acsPowerMgmtPhasesTablePhaseIndex }
|
|
::= { acsPowerMgmtPhasesTable 1 }
|
|
|
|
AcsPowerMgmtPhasesTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtPhasesTablePortNumber InterfaceIndex, -- number of serial port
|
|
acsPowerMgmtPhasesTablePduIndex InterfaceIndexOrZero, -- number of PDU
|
|
acsPowerMgmtPhasesTablePhaseIndex InterfaceIndexOrZero, -- phase index
|
|
acsPowerMgmtPhasesTablePhaseName DisplayString, -- Phase Name
|
|
acsPowerMgmtPhasesTablePduId DisplayString, -- PDU identification
|
|
acsPowerMgmtPhasesTablePortName DisplayString, -- Serial Port Name
|
|
acsPowerMgmtPhasesTableCurrentValue Integer32, -- actual value of Phase current sensor
|
|
acsPowerMgmtPhasesTableCurrentMax Integer32, -- max detected value of current sensor
|
|
acsPowerMgmtPhasesTableCurrentMin Integer32, -- min detected value of current sensor
|
|
acsPowerMgmtPhasesTableCurrentAvg Integer32, -- average value for current sensor
|
|
acsPowerMgmtPhasesTableCurrentReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPhasesTableVoltageType INTEGER, -- type of phase voltage
|
|
acsPowerMgmtPhasesTableVoltageValue Integer32, -- actual value of phase voltage
|
|
acsPowerMgmtPhasesTableVoltageMax Integer32, -- max value of voltage sensor
|
|
acsPowerMgmtPhasesTableVoltageMin Integer32, -- min value of voltage sensor
|
|
acsPowerMgmtPhasesTableVoltageAvg Integer32, -- avg value of voltage sensor
|
|
acsPowerMgmtPhasesTableVoltageReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPhasesTablePowerType INTEGER, -- type of phase power consumption
|
|
acsPowerMgmtPhasesTablePowerValue Integer32, -- actual value of phase power consumption
|
|
acsPowerMgmtPhasesTablePowerMax Integer32, -- max value
|
|
acsPowerMgmtPhasesTablePowerMin Integer32, -- min value
|
|
acsPowerMgmtPhasesTablePowerAvg Integer32, -- average value
|
|
acsPowerMgmtPhasesTablePowerReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPhasesTablePowerFactorType INTEGER, -- type of phase power factor
|
|
acsPowerMgmtPhasesTablePowerFactorValue Integer32, -- actual value of phase power factor
|
|
acsPowerMgmtPhasesTablePowerFactorMax Integer32, -- max value for power factor
|
|
acsPowerMgmtPhasesTablePowerFactorMin Integer32, -- min value for power factor
|
|
acsPowerMgmtPhasesTablePowerFactorAvg Integer32, -- avg value for power factor
|
|
acsPowerMgmtPhasesTablePowerFactorReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPhasesTableAlarm INTEGER -- phase alarm status
|
|
}
|
|
|
|
acsPowerMgmtPhasesTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtPhasesTableEntry 1 }
|
|
|
|
acsPowerMgmtPhasesTablePduIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A PDU position in the chain."
|
|
::= { acsPowerMgmtPhasesTableEntry 2 }
|
|
|
|
acsPowerMgmtPhasesTablePhaseIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"phase index in the PDU."
|
|
::= { acsPowerMgmtPhasesTableEntry 3 }
|
|
|
|
acsPowerMgmtPhasesTablePhaseName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"phase name in the PDU."
|
|
::= { acsPowerMgmtPhasesTableEntry 4 }
|
|
|
|
acsPowerMgmtPhasesTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { acsPowerMgmtPhasesTableEntry 5 }
|
|
|
|
acsPowerMgmtPhasesTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtPhasesTableEntry 6 }
|
|
|
|
acsPowerMgmtPhasesTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of current sensor in this phase.( A x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 7 }
|
|
|
|
acsPowerMgmtPhasesTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of current sensor in this phase.( A x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 8 }
|
|
|
|
acsPowerMgmtPhasesTableCurrentMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of current sensor in this phase.( A x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 9 }
|
|
|
|
acsPowerMgmtPhasesTableCurrentAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for current sensor in this phase.( A x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 10 }
|
|
|
|
acsPowerMgmtPhasesTableCurrentReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of current."
|
|
::= { acsPowerMgmtPhasesTableEntry 11 }
|
|
|
|
acsPowerMgmtPhasesTableVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of voltage values."
|
|
::= { acsPowerMgmtPhasesTableEntry 12 }
|
|
|
|
acsPowerMgmtPhasesTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of voltage sensor in this phase.( V )"
|
|
::= { acsPowerMgmtPhasesTableEntry 13 }
|
|
|
|
acsPowerMgmtPhasesTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of voltage sensor in this phase.( V )"
|
|
::= { acsPowerMgmtPhasesTableEntry 14 }
|
|
|
|
acsPowerMgmtPhasesTableVoltageMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of voltage sensor in this phase.( V )"
|
|
::= { acsPowerMgmtPhasesTableEntry 15 }
|
|
|
|
acsPowerMgmtPhasesTableVoltageAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for voltage sensor in this phase.( V )"
|
|
::= { acsPowerMgmtPhasesTableEntry 16 }
|
|
|
|
acsPowerMgmtPhasesTableVoltageReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of voltage."
|
|
::= { acsPowerMgmtPhasesTableEntry 17 }
|
|
|
|
acsPowerMgmtPhasesTablePowerType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power consumption values."
|
|
::= { acsPowerMgmtPhasesTableEntry 18 }
|
|
|
|
acsPowerMgmtPhasesTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power consumption in this phase.( W x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 19 }
|
|
|
|
acsPowerMgmtPhasesTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of power consumption in this phase.( W x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 20 }
|
|
|
|
acsPowerMgmtPhasesTablePowerMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of power consumption in this phase.( W x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 21 }
|
|
|
|
acsPowerMgmtPhasesTablePowerAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for power consumption in this phase.( W x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 22 }
|
|
|
|
acsPowerMgmtPhasesTablePowerReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of power consumption."
|
|
::= { acsPowerMgmtPhasesTableEntry 23 }
|
|
|
|
acsPowerMgmtPhasesTablePowerFactorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power factor values."
|
|
::= { acsPowerMgmtPhasesTableEntry 24 }
|
|
|
|
acsPowerMgmtPhasesTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power factor in this phase.( PF x 100 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 25 }
|
|
|
|
acsPowerMgmtPhasesTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of power factor in this phase.( PF x 100 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 26 }
|
|
|
|
acsPowerMgmtPhasesTablePowerFactorMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of power factor in this phase.( PF x 100 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 27 }
|
|
|
|
acsPowerMgmtPhasesTablePowerFactorAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for power factor in this phase.( PF x 100 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 28 }
|
|
|
|
acsPowerMgmtPhasesTablePowerFactorReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of power factor."
|
|
::= { acsPowerMgmtPhasesTableEntry 29 }
|
|
|
|
acsPowerMgmtPhasesTableAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal (1),
|
|
blow-fuse (2),
|
|
hw-ocp (3),
|
|
high-critical (4),
|
|
high-warning (5),
|
|
low-warning (6),
|
|
low-critical (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Show the phase alarm status."
|
|
::= { acsPowerMgmtPhasesTableEntry 30 }
|
|
|
|
acsPowerMgmtBanksTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtBanksTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains data monitoring of each detected bank."
|
|
::= { acsPowerMgmt 9 }
|
|
|
|
acsPowerMgmtBanksTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtBanksTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the data monitoring about bank."
|
|
INDEX { acsPowerMgmtBanksTablePortNumber, acsPowerMgmtBanksTablePduIndex, acsPowerMgmtBanksTableBankIndex }
|
|
::= { acsPowerMgmtBanksTable 1 }
|
|
|
|
AcsPowerMgmtBanksTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtBanksTablePortNumber InterfaceIndex, -- number of serial port
|
|
acsPowerMgmtBanksTablePduIndex InterfaceIndexOrZero, -- number of PDU
|
|
acsPowerMgmtBanksTableBankIndex InterfaceIndexOrZero, -- bank index
|
|
acsPowerMgmtBanksTableBankName DisplayString, -- Bank Name
|
|
acsPowerMgmtBanksTablePduId DisplayString, -- PDU identification
|
|
acsPowerMgmtBanksTablePortName DisplayString, -- Serial Port Name
|
|
acsPowerMgmtBanksTableCurrentValue Integer32, -- actual value of bank current sensor
|
|
acsPowerMgmtBanksTableCurrentMax Integer32, -- max detected value of current sensor
|
|
acsPowerMgmtBanksTableCurrentMin Integer32, -- min detected value of current sensor
|
|
acsPowerMgmtBanksTableCurrentAvg Integer32, -- average value for current sensor
|
|
acsPowerMgmtBanksTableCurrentReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtBanksTableVoltageType INTEGER, -- type of bank voltage
|
|
acsPowerMgmtBanksTableVoltageValue Integer32, -- actual value of bank voltage
|
|
acsPowerMgmtBanksTableVoltageMax Integer32, -- max value of voltage sensor
|
|
acsPowerMgmtBanksTableVoltageMin Integer32, -- min value of voltage sensor
|
|
acsPowerMgmtBanksTableVoltageAvg Integer32, -- avg value of voltage sensor
|
|
acsPowerMgmtBanksTableVoltageReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtBanksTablePowerType INTEGER, -- type of bank power consumption
|
|
acsPowerMgmtBanksTablePowerValue Integer32, -- actual value of bank power consumption
|
|
acsPowerMgmtBanksTablePowerMax Integer32, -- max value
|
|
acsPowerMgmtBanksTablePowerMin Integer32, -- min value
|
|
acsPowerMgmtBanksTablePowerAvg Integer32, -- average value
|
|
acsPowerMgmtBanksTablePowerReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtBanksTablePowerFactorType INTEGER, -- type of bank power factor
|
|
acsPowerMgmtBanksTablePowerFactorValue Integer32, -- actual value of bank power factor
|
|
acsPowerMgmtBanksTablePowerFactorMax Integer32, -- max value for power factor
|
|
acsPowerMgmtBanksTablePowerFactorMin Integer32, -- min value for power factor
|
|
acsPowerMgmtBanksTablePowerFactorAvg Integer32, -- avg value for power factor
|
|
acsPowerMgmtBanksTablePowerFactorReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtBanksTableAlarm INTEGER -- status of bank alarm
|
|
}
|
|
|
|
acsPowerMgmtBanksTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtBanksTableEntry 1 }
|
|
|
|
acsPowerMgmtBanksTablePduIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A PDU position in the chain."
|
|
::= { acsPowerMgmtBanksTableEntry 2 }
|
|
|
|
acsPowerMgmtBanksTableBankIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank index in the PDU."
|
|
::= { acsPowerMgmtBanksTableEntry 3 }
|
|
|
|
acsPowerMgmtBanksTableBankName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank name in the PDU."
|
|
::= { acsPowerMgmtBanksTableEntry 4 }
|
|
|
|
acsPowerMgmtBanksTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { acsPowerMgmtBanksTableEntry 5 }
|
|
|
|
acsPowerMgmtBanksTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtBanksTableEntry 6 }
|
|
|
|
acsPowerMgmtBanksTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of current sensor in this bank.( A x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 7 }
|
|
|
|
acsPowerMgmtBanksTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of current sensor in this bank.( A x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 8 }
|
|
|
|
acsPowerMgmtBanksTableCurrentMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of current sensor in this bank.( A x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 9 }
|
|
|
|
acsPowerMgmtBanksTableCurrentAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for current sensor in this bank.( A x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 10 }
|
|
|
|
acsPowerMgmtBanksTableCurrentReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of current."
|
|
::= { acsPowerMgmtBanksTableEntry 11 }
|
|
|
|
acsPowerMgmtBanksTableVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of voltage values."
|
|
::= { acsPowerMgmtBanksTableEntry 12 }
|
|
|
|
acsPowerMgmtBanksTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of voltage sensor in this bank.( V )"
|
|
::= { acsPowerMgmtBanksTableEntry 13 }
|
|
|
|
acsPowerMgmtBanksTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of voltage sensor in this bank.( V )"
|
|
::= { acsPowerMgmtBanksTableEntry 14 }
|
|
|
|
acsPowerMgmtBanksTableVoltageMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of voltage sensor in this bank.( V )"
|
|
::= { acsPowerMgmtBanksTableEntry 15 }
|
|
|
|
acsPowerMgmtBanksTableVoltageAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for voltage sensor in this bank.( V )"
|
|
::= { acsPowerMgmtBanksTableEntry 16 }
|
|
|
|
acsPowerMgmtBanksTableVoltageReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of voltage."
|
|
::= { acsPowerMgmtBanksTableEntry 17 }
|
|
|
|
acsPowerMgmtBanksTablePowerType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power consumption values."
|
|
::= { acsPowerMgmtBanksTableEntry 18 }
|
|
|
|
acsPowerMgmtBanksTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power consumption in this bank.( W x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 19 }
|
|
|
|
acsPowerMgmtBanksTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of power consumption in this bank.( W x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 20 }
|
|
|
|
acsPowerMgmtBanksTablePowerMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of power consumption in this bank.( W x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 21 }
|
|
|
|
acsPowerMgmtBanksTablePowerAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for power consumption in this bank.( W x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 22 }
|
|
|
|
acsPowerMgmtBanksTablePowerReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of power consumption."
|
|
::= { acsPowerMgmtBanksTableEntry 23 }
|
|
|
|
acsPowerMgmtBanksTablePowerFactorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power factor values."
|
|
::= { acsPowerMgmtBanksTableEntry 24 }
|
|
|
|
acsPowerMgmtBanksTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power factor in this bank.( PF x 100 )"
|
|
::= { acsPowerMgmtBanksTableEntry 25 }
|
|
|
|
acsPowerMgmtBanksTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of power factor in this bank.( PF x 100 )"
|
|
::= { acsPowerMgmtBanksTableEntry 26 }
|
|
|
|
acsPowerMgmtBanksTablePowerFactorMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of power factor in this bank.( PF x 100 )"
|
|
::= { acsPowerMgmtBanksTableEntry 27 }
|
|
|
|
acsPowerMgmtBanksTablePowerFactorAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for power factor in this bank.( PF x 100 )"
|
|
::= { acsPowerMgmtBanksTableEntry 28 }
|
|
|
|
acsPowerMgmtBanksTablePowerFactorReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of power factor."
|
|
::= { acsPowerMgmtBanksTableEntry 29 }
|
|
|
|
acsPowerMgmtBanksTableAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal (1),
|
|
blow-fuse (2),
|
|
hw-ocp (3),
|
|
high-critical (4),
|
|
high-warning (5),
|
|
low-warning (6),
|
|
low-critical (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Show the bank alarm status."
|
|
::= { acsPowerMgmtBanksTableEntry 30 }
|
|
|
|
acsPowerMgmtEnvMonTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtEnvMonTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains data monitoring of each detected environmental sensor."
|
|
::= { acsPowerMgmt 10 }
|
|
|
|
acsPowerMgmtEnvMonTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtEnvMonTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the data monitoring about environmental sensors."
|
|
INDEX { acsPowerMgmtEnvMonTablePortNumber, acsPowerMgmtEnvMonTablePduIndex, acsPowerMgmtEnvMonTableIndex }
|
|
::= { acsPowerMgmtEnvMonTable 1 }
|
|
|
|
AcsPowerMgmtEnvMonTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtEnvMonTablePortNumber InterfaceIndex, -- number of serial port
|
|
acsPowerMgmtEnvMonTablePduIndex InterfaceIndexOrZero, -- number of PDU
|
|
acsPowerMgmtEnvMonTableIndex InterfaceIndexOrZero, -- index
|
|
acsPowerMgmtEnvMonTableName DisplayString, -- sensor name
|
|
acsPowerMgmtEnvMonTablePduId DisplayString, -- PDU identification
|
|
acsPowerMgmtEnvMonTablePortName DisplayString, -- Serial Port Name
|
|
acsPowerMgmtEnvMonTableType INTEGER, -- environmental sensor type
|
|
acsPowerMgmtEnvMonTableStatus INTEGER, -- state of digital sensor
|
|
acsPowerMgmtEnvMonTableValue Integer32, -- value
|
|
acsPowerMgmtEnvMonTableMaxValue Integer32 -- max value
|
|
}
|
|
|
|
acsPowerMgmtEnvMonTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtEnvMonTableEntry 1 }
|
|
|
|
acsPowerMgmtEnvMonTablePduIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A PDU position in the chain."
|
|
::= { acsPowerMgmtEnvMonTableEntry 2 }
|
|
|
|
acsPowerMgmtEnvMonTableIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"envmon sensor index."
|
|
::= { acsPowerMgmtEnvMonTableEntry 3 }
|
|
|
|
acsPowerMgmtEnvMonTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"envmon sensor name."
|
|
::= { acsPowerMgmtEnvMonTableEntry 4 }
|
|
|
|
acsPowerMgmtEnvMonTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { acsPowerMgmtEnvMonTableEntry 5 }
|
|
|
|
acsPowerMgmtEnvMonTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtEnvMonTableEntry 6 }
|
|
|
|
acsPowerMgmtEnvMonTableType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
temp-internal (1),
|
|
temperature (2),
|
|
humidity (3),
|
|
air-flow (4),
|
|
smoke (5),
|
|
dry-concact (6),
|
|
water-level (7),
|
|
motion (8),
|
|
unplugged (9),
|
|
unknown (10)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The type of environmental monitor."
|
|
::= { acsPowerMgmtEnvMonTableEntry 7 }
|
|
|
|
acsPowerMgmtEnvMonTableStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
triggered(2),
|
|
not-applicable(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of digital sensors:
|
|
Dry-Contact, Water level, Smoke sensor, Motion sensor."
|
|
::= { acsPowerMgmtEnvMonTableEntry 8 }
|
|
|
|
acsPowerMgmtEnvMonTableValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu."
|
|
::= { acsPowerMgmtEnvMonTableEntry 9 }
|
|
|
|
acsPowerMgmtEnvMonTableMaxValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu."
|
|
::= { acsPowerMgmtEnvMonTableEntry 10 }
|
|
|
|
acsPowerMgmtOutElecMonTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtOutElecMonTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the information about data monitoring of outlets."
|
|
::= { acsPowerMgmt 11 }
|
|
|
|
acsPowerMgmtOutElecMonTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtOutElecMonTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about the outlet."
|
|
INDEX { acsPowerMgmtOutElecMonTablePortNumber,
|
|
acsPowerMgmtOutElecMonTablePduNumber,
|
|
acsPowerMgmtOutElecMonTableNumber }
|
|
::= { acsPowerMgmtOutElecMonTable 1 }
|
|
|
|
AcsPowerMgmtOutElecMonTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtOutElecMonTablePortNumber InterfaceIndex, -- serial port #
|
|
acsPowerMgmtOutElecMonTablePduNumber InterfaceIndex,
|
|
acsPowerMgmtOutElecMonTableNumber InterfaceIndex, -- outlet number in PDU
|
|
acsPowerMgmtOutElecMonTableCurrentValue Integer32, -- actual value for current
|
|
acsPowerMgmtOutElecMonTableCurrentMax Integer32, -- max detected value for current
|
|
acsPowerMgmtOutElecMonTableCurrentMin Integer32, -- min detected value for current
|
|
acsPowerMgmtOutElecMonTableCurrentAvg Integer32, -- average value for current
|
|
acsPowerMgmtOutElecMonTableCurrentReset INTEGER, -- reset max, min and avg values of current
|
|
acsPowerMgmtOutElecMonTablePowerValue Integer32, -- actual value for power
|
|
acsPowerMgmtOutElecMonTablePowerMax Integer32, -- max detected value for power
|
|
acsPowerMgmtOutElecMonTablePowerMin Integer32, -- min detected value for power
|
|
acsPowerMgmtOutElecMonTablePowerAvg Integer32, -- average value for power
|
|
acsPowerMgmtOutElecMonTablePowerReset INTEGER, -- reset max, min and avg values of power
|
|
acsPowerMgmtOutElecMonTableVoltageValue Integer32, -- actual value for voltage
|
|
acsPowerMgmtOutElecMonTableVoltageMax Integer32, -- max detected value for voltage
|
|
acsPowerMgmtOutElecMonTableVoltageMin Integer32, -- min detected value for voltage
|
|
acsPowerMgmtOutElecMonTableVoltageAvg Integer32, -- average value for voltage
|
|
acsPowerMgmtOutElecMonTableVoltageReset INTEGER, -- reset max, min and avg values of voltage
|
|
acsPowerMgmtOutElecMonTablePowerFactorValue Integer32, -- actual value for power factor
|
|
acsPowerMgmtOutElecMonTablePowerFactorMax Integer32, -- max detected value for power factor
|
|
acsPowerMgmtOutElecMonTablePowerFactorMin Integer32, -- min detected value for power factor
|
|
acsPowerMgmtOutElecMonTablePowerFactorAvg Integer32, -- avg value for power factor
|
|
acsPowerMgmtOutElecMonTablePowerFactorReset INTEGER, -- reset max, min and avg values of power factor
|
|
acsPowerMgmtOutElecMonTableAlarm INTEGER -- outlet alarm status
|
|
}
|
|
|
|
acsPowerMgmtOutElecMonTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Port number."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 1 }
|
|
|
|
acsPowerMgmtOutElecMonTablePduNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 2 }
|
|
|
|
acsPowerMgmtOutElecMonTableNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of the outlet in the PDU."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 3 }
|
|
|
|
acsPowerMgmtOutElecMonTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of outlet current sensor.( A x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 4 }
|
|
|
|
acsPowerMgmtOutElecMonTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of outlet current sensor.( A x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 5 }
|
|
|
|
acsPowerMgmtOutElecMonTableCurrentMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of outlet current sensor.( A x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 6 }
|
|
|
|
acsPowerMgmtOutElecMonTableCurrentAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for outlet current sensor.( A x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 7 }
|
|
|
|
acsPowerMgmtOutElecMonTableCurrentReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reset max, min and avertage values of outlet current."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 8 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of outlet power comsumption sensor.( W x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 9 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of outlet power comsumption sensor.( W x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 10 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of outlet power comsumption sensor.( W x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 11 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for outlet power comsumption sensor.( W x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 12 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reset max, min and avertage values of outlet power comsumption."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 13 }
|
|
|
|
acsPowerMgmtOutElecMonTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of outlet voltage sensor.( V )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 14 }
|
|
|
|
acsPowerMgmtOutElecMonTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of outlet voltage sensor.( V )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 15 }
|
|
|
|
acsPowerMgmtOutElecMonTableVoltageMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of outlet voltage sensor.( V )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 16 }
|
|
|
|
acsPowerMgmtOutElecMonTableVoltageAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for outlet voltage sensor.( V )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 17 }
|
|
|
|
acsPowerMgmtOutElecMonTableVoltageReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reset max, min and avertage values of outlet voltage."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 18 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of outlet power-factor sensor.( PF x 100 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 19 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of outlet power-factor sensor.( PF x 100 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 20 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerFactorMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of outlet power-factor sensor.( PF x 100 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 21 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerFactorAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for outlet power-factor sensor.( PF x 100 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 22 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerFactorReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reset max, min and avertage values of outlet power-factor."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 23 }
|
|
|
|
acsPowerMgmtOutElecMonTableAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal (1),
|
|
blow-fuse (2),
|
|
hw-ocp (3),
|
|
high-critical (4),
|
|
high-warning (5),
|
|
low-warning (6),
|
|
low-critical (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Show the outlet alarm status."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 24 }
|
|
|
|
END
|