-- Avocent PM MIB
-- Copyright 2010 Avocent Corporation
-- Revision: 2.0.1
-- Last Modified: Nov 24, 2010
--------------------------------------------------------------------------------
PM-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, OBJECT-TYPE, MODULE-IDENTITY, Integer32
FROM SNMPv2-SMI
DisplayString
FROM SNMPv2-TC
InterfaceIndex, InterfaceIndexOrZero
FROM IF-MIB;
--------------------------------------------------------------------------------
-- Object Groupings
--------------------------------------------------------------------------------
--@ Note: every product type should be uniquely identified underneath the
--@ Products object group. Each product should report its unique Products
--@ OBJECT IDENTIFIER in mib-2.system.sysObjectID. Please see the file
--@ "_Avocent Enterprise Object Identifier Assignment.txt" for a list of the
--@ IDs that have been assigned.
-- enterprises .1.3.6.1.4.1
-- avocent OBJECT IDENTIFIER ::= { enterprises 10418 }
pm MODULE-IDENTITY
LAST-UPDATED "201011240000Z"
ORGANIZATION "Avocent Corporation"
CONTACT-INFO "postal : Avocent Corporation
47281 Bayside Parkway
Fremont, CA 94538, USA
e-mail : Technical Support
techsupport@avocent.com"
DESCRIPTION
"This module defines the Avocent MIB extensions to
PM-PDU products."
REVISION "201011240000Z"
DESCRIPTION "Adding Power Management OIDs.
Fixed SYNTAX of some OIDs.
Updating OIDs DESCRIPTION to include not applicable values."
REVISION "201009240000Z"
DESCRIPTION "Syntax fixed to pass validation level 3."
REVISION "201004140000Z"
DESCRIPTION "Obsoleting fixed index OIDs from PDU table.
Added measurent type and alarm in PDU table.
Added missing power factor reset in outlet table.
Added sensor type and digital status in sensors table."
REVISION "200905210000Z"
DESCRIPTION "New tables for power measurements"
::= { enterprises 10418 17 }
pmProducts OBJECT IDENTIFIER ::= { pm 1 }
pmManagement OBJECT IDENTIFIER ::= { pm 2 }
--
pm1024 OBJECT IDENTIFIER ::= { pmProducts 1 } -- 10418.17.1.1
pm2003 OBJECT IDENTIFIER ::= { pmProducts 2 } -- 10418.17.1.2
pm2006 OBJECT IDENTIFIER ::= { pmProducts 3 } -- 10418.17.1.3
pm2024 OBJECT IDENTIFIER ::= { pmProducts 4 }
pm3003 OBJECT IDENTIFIER ::= { pmProducts 5 }
pm3006 OBJECT IDENTIFIER ::= { pmProducts 6 }
pm3024 OBJECT IDENTIFIER ::= { pmProducts 7 }
pm1010 OBJECT IDENTIFIER ::= { pmProducts 8 }
pm2010 OBJECT IDENTIFIER ::= { pmProducts 9 }
pm3010 OBJECT IDENTIFIER ::= { pmProducts 10 }
pm1020 OBJECT IDENTIFIER ::= { pmProducts 11 }
pm2020 OBJECT IDENTIFIER ::= { pmProducts 12 }
pm3020 OBJECT IDENTIFIER ::= { pmProducts 13 }
pmAppliance OBJECT IDENTIFIER ::= { pmManagement 1 } -- 10418.17.2.1
pmSessions OBJECT IDENTIFIER ::= { pmManagement 2 } -- 10418.17.2.2
pmPowerMgmt OBJECT IDENTIFIER ::= { pmManagement 5 } -- 10418.17.2.5
--
-- Note that traps are defined in a separate trap MIB
--
pmTrapObject OBJECT IDENTIFIER ::= { pmManagement 6 } -- 10418.17.2.6
--
-- pmAppliance
-- OBJECT IDENTIFIER ::= { pmManagement 1 } 10418.17.2.1
--
pmHostName OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The appliance name"
::= { pmAppliance 1 }
pmProductModel OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..50) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The appliance product model"
::= { pmAppliance 2 }
pmPartNumber OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The part number of this appliance as shown on the label
attached or imprinted on the appliance."
::= { pmAppliance 3 }
pmSerialNumber OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The serial number of this appliance as shown on the label
attached or imprinted on the appliance."
::= { pmAppliance 4 }
pmEIDNumber OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The electronic ID number (EID) of this appliance as shown on the label
attached or imprinted on the appliance."
::= { pmAppliance 5 }
pmBootcodeVersion OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The version of the bootcode of this appliance."
::= { pmAppliance 6 }
pmFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The version of the firmware of this appliance."
::= { pmAppliance 7 }
pmReboot OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reboot(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of reboot(2) will reboot the appliance.
noAction(1) = always returned in a GET. Does nothing if SET.
reboot(2) = when SET the appliance immediately reboots."
::= { pmAppliance 9 }
--
-- pmSessions
-- OBJECT IDENTIFIER ::= { pmManagement 2 } 10418.17.2.2
--
pmActiveSessionsNumberOfSession OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of active sessions."
::= { pmSessions 1 }
pmActiveSessionsTable OBJECT-TYPE
SYNTAX SEQUENCE OF PmActiveSessionsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the list of active sessions."
::= { pmSessions 2 }
pmActiveSessionsTableEntry OBJECT-TYPE
SYNTAX PmActiveSessionsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the active session"
INDEX { pmActiveSessionsTableIndex }
::= { pmActiveSessionsTable 1 }
PmActiveSessionsTableEntry ::= SEQUENCE {
pmActiveSessionsTableIndex InterfaceIndexOrZero,
pmActiveSessionsTableUser DisplayString, -- user name
pmActiveSessionsTableGroup DisplayString, -- group name
pmActiveSessionsTableType DisplayString, -- RO/RW-ssh,telnet or web
pmActiveSessionsTableConnection DisplayString, -- type + target name
pmActiveSessionsTableSessionTime DisplayString, -- time of session
pmActiveSessionsTableFrom DisplayString, -- source of the session
pmActiveSessionsTableKill INTEGER
}
pmActiveSessionsTableIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique index representing an entry in this table."
::= { pmActiveSessionsTableEntry 1 }
pmActiveSessionsTableUser OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The name of the user that opens this session."
::= { pmActiveSessionsTableEntry 2 }
pmActiveSessionsTableGroup OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The name of the group that the user belongs to."
::= { pmActiveSessionsTableEntry 3 }
pmActiveSessionsTableType OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The session type."
::= { pmActiveSessionsTableEntry 4 }
pmActiveSessionsTableConnection OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Connection type."
::= { pmActiveSessionsTableEntry 5 }
pmActiveSessionsTableSessionTime OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Time of the session"
::= { pmActiveSessionsTableEntry 6 }
pmActiveSessionsTableFrom OBJECT-TYPE
SYNTAX DisplayString ( SIZE (0..32) )
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The source IP address of the session."
::= { pmActiveSessionsTableEntry 7 }
pmActiveSessionsTableKill OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
killSession(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of killSession(2) will kill the session.
noAction(1) = always returned in a GET. Does nothing if SET.
killSession(2)= when SET the appliance immediately kills the session."
::= { pmActiveSessionsTableEntry 8 }
--
-- pmPowerMgmt
-- OBJECT IDENTIFIER ::= { pmManagement 5 } 10418.17.2.5
--
pmPowerMgmtNumSerialPorts OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of Serial Ports that has PDU connected on the appliance."
::= { pmPowerMgmt 1 }
pmPowerMgmtSerialTable OBJECT-TYPE
SYNTAX SEQUENCE OF PmPowerMgmtSerialTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Information about each serial port thas has PDU connect."
::= { pmPowerMgmt 2 }
pmPowerMgmtSerialTableEntry OBJECT-TYPE
SYNTAX PmPowerMgmtSerialTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Information about each serial port thas has PDU connect."
INDEX { pmPowerMgmtSerialTableIndex }
::= { pmPowerMgmtSerialTable 1 }
PmPowerMgmtSerialTableEntry ::= SEQUENCE {
pmPowerMgmtSerialTableIndex InterfaceIndex,
pmPowerMgmtSerialTablePortNumber Integer32,
pmPowerMgmtSerialTableDeviceName DisplayString,
pmPowerMgmtSerialTableNumberPDUs Integer32,
pmPowerMgmtSerialTableBuzzer Integer32,
pmPowerMgmtSerialTableSyslog Integer32,
pmPowerMgmtSerialTableOverCurrent Integer32,
pmPowerMgmtSerialTableCycleInterval Integer32,
pmPowerMgmtSerialTablePollRate Integer32,
pmPowerMgmtSerialTablePassWord DisplayString,
pmPowerMgmtSerialTableSave INTEGER,
pmPowerMgmtSerialTableRestore INTEGER
}
pmPowerMgmtSerialTableIndex OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The index of the register."
::= { pmPowerMgmtSerialTableEntry 1 }
pmPowerMgmtSerialTablePortNumber OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of the serial port when the PDU is connected."
::= { pmPowerMgmtSerialTableEntry 2 }
pmPowerMgmtSerialTableDeviceName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The device name of this serial port."
::= { pmPowerMgmtSerialTableEntry 3 }
pmPowerMgmtSerialTableNumberPDUs OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total number of units connected in this serial port."
::= { pmPowerMgmtSerialTableEntry 4 }
pmPowerMgmtSerialTableBuzzer OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"set/get buzzer(s) on or off for the chain.
Returns 0 if not supported."
::= { pmPowerMgmtSerialTableEntry 10 }
pmPowerMgmtSerialTableSyslog OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"set/get syslog on or off for the chain.
Returns 0 if not supported."
::= { pmPowerMgmtSerialTableEntry 11 }
pmPowerMgmtSerialTableOverCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"set/get over current proctection on or off for the chain.
Returns 0 if not supported."
::= { pmPowerMgmtSerialTableEntry 12 }
pmPowerMgmtSerialTableCycleInterval OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"set/get cycle interval for the chain in whole seconds.
Returns 0 if not supported."
::= { pmPowerMgmtSerialTableEntry 13 }
pmPowerMgmtSerialTablePollRate OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"set/get the poll rate for the chain in whole seconds.
Returns 0 if not supported."
::= { pmPowerMgmtSerialTableEntry 14 }
pmPowerMgmtSerialTablePassWord OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"set the global password for admin user"
::= { pmPowerMgmtSerialTableEntry 15 }
pmPowerMgmtSerialTableSave OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
save(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
save(2) = when SET the save command is sent to PDU."
::= { pmPowerMgmtSerialTableEntry 20 }
pmPowerMgmtSerialTableRestore OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
restore(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
restore(2) = when SET the restore command is sent to PDU."
::= { pmPowerMgmtSerialTableEntry 21 }
pmPowerMgmtPDUTable OBJECT-TYPE
SYNTAX SEQUENCE OF PmPowerMgmtPDUTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the list of detected PDUs."
::= { pmPowerMgmt 3 }
pmPowerMgmtPDUTableEntry OBJECT-TYPE
SYNTAX PmPowerMgmtPDUTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the PDU."
INDEX { pmPowerMgmtPDUTablePortNumber, pmPowerMgmtPDUTablePduIndex }
::= { pmPowerMgmtPDUTable 1 }
PmPowerMgmtPDUTableEntry ::= SEQUENCE {
pmPowerMgmtPDUTablePortNumber InterfaceIndex, -- number of serial port
pmPowerMgmtPDUTablePduIndex InterfaceIndexOrZero,
pmPowerMgmtPDUTablePduId DisplayString, -- PDU identification
pmPowerMgmtPDUTablePortName DisplayString, -- Serial Port Name
pmPowerMgmtPDUTableModel DisplayString, -- PDU model
pmPowerMgmtPDUTableVendor DisplayString, -- Vendor
pmPowerMgmtPDUTableFirmwareVersion DisplayString, -- Firmware Version
pmPowerMgmtPDUTableNumberOfOutlets Integer32,
pmPowerMgmtPDUTableCurrentNOS Integer32, -- OBSOLETED number of current sensors
pmPowerMgmtPDUTableCurrent1Value Integer32, -- OBSOLETED actual value for current of the sensor 1
pmPowerMgmtPDUTableCurrent1Max Integer32, -- OBSOLETED max value for current of the sensor 1
pmPowerMgmtPDUTableCurrent2Value Integer32, -- OBSOLETED actual value for current of the sensor 2
pmPowerMgmtPDUTableCurrent2Max Integer32, -- OBSOLETED max value for current of the sensor 2
pmPowerMgmtPDUTableCurrent3Value Integer32, -- OBSOLETED actual value for current of the sensor 3
pmPowerMgmtPDUTableCurrent3Max Integer32, -- OBSOLETED max value for current of the sensor 3
pmPowerMgmtPDUTableTemperatureNOS Integer32, -- OBSOLETED number of temperature sensors
pmPowerMgmtPDUTableTemperature1Value Integer32, -- OBSOLETED actual value for Temperature 1
pmPowerMgmtPDUTableTemperature1Max Integer32, -- OBSOLETED max value for Temperature 1
pmPowerMgmtPDUTableTemperature2Value Integer32, -- OBSOLETED actual value for Temperaturet 2
pmPowerMgmtPDUTableTemperature2Max Integer32, -- OBSOLETED max value for Temperature 2
pmPowerMgmtPDUTableTemperature3Value Integer32, -- OBSOLETED actual value for Temperature 3
pmPowerMgmtPDUTableTemperature3Max Integer32, -- OBSOLETED max value for Temperature 3
pmPowerMgmtPDUTableHumidityNOS Integer32, -- OBSOLETED humidity number of humidity sensors
pmPowerMgmtPDUTableHumidity1Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 1
pmPowerMgmtPDUTableHumidity1Max Integer32, -- OBSOLETED max value for Humidityof the sensor 1
pmPowerMgmtPDUTableHumidity2Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 2
pmPowerMgmtPDUTableHumidity2Max Integer32, -- OBSOLETED max value for Humidity of the sensor 2
pmPowerMgmtPDUTableHumidity3Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 3
pmPowerMgmtPDUTableHumidity3Max Integer32, -- OBSOLETED max value for Humidity of the sensor 3
pmPowerMgmtPDUTableVoltageNOS Integer32, -- OBSOLETED number of voltage sensor
pmPowerMgmtPDUTableVoltage1Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 1
pmPowerMgmtPDUTableVoltage1Max Integer32, -- OBSOLETED max value for Voltage of the sensor 1
pmPowerMgmtPDUTableVoltage2Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 2
pmPowerMgmtPDUTableVoltage2Max Integer32, -- OBSOLETED max value for Voltaget of the sensor 2
pmPowerMgmtPDUTableVoltage3Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 3
pmPowerMgmtPDUTableVoltage3Max Integer32, -- OBSOLETED max value for Voltage of the sensor 3
pmPowerMgmtPDUTableNumberOfPhases Integer32, -- number of phases (0 if single phase)
pmPowerMgmtPDUTableNumberOfBanks Integer32, -- number of banks
pmPowerMgmtPDUTableNumberOfSensors Integer32, -- number of sensors
pmPowerMgmtPDUTableFactoryDefault INTEGER, -- set PDU to factory default settings
pmPowerMgmtPDUTableColdStartDelay Integer32, -- get/set PDUs cold start delay
pmPowerMgmtPDUTableReboot INTEGER, -- reboot the PDU
pmPowerMgmtPDUTableMaxCurrent Integer32, -- max value allowed for current
pmPowerMgmtPDUTableAlarm INTEGER, -- PDU alarm status
pmPowerMgmtPDUTableCurrentValue Integer32, -- actual value for current of the sensor
pmPowerMgmtPDUTableCurrentMax Integer32, -- max value for current
pmPowerMgmtPDUTableCurrentMin Integer32, -- min value for current
pmPowerMgmtPDUTableCurrentAvg Integer32, -- average value for current
pmPowerMgmtPDUTableCurrentReset INTEGER, -- reset the current stats
pmPowerMgmtPDUTablePowerValue Integer32, -- actual value for power
pmPowerMgmtPDUTablePowerMax Integer32, -- max value for power
pmPowerMgmtPDUTablePowerMin Integer32, -- min value for power
pmPowerMgmtPDUTablePowerAvg Integer32, -- average value for power
pmPowerMgmtPDUTablePowerReset INTEGER, -- reset the power stats
pmPowerMgmtPDUTablePowerType INTEGER, -- type of power measurement
pmPowerMgmtPDUTableVoltageValue Integer32, -- actual value for voltage
pmPowerMgmtPDUTableVoltageMax Integer32, -- max value for voltage
pmPowerMgmtPDUTableVoltageMin Integer32, -- min value for voltage
pmPowerMgmtPDUTableVoltageAvg Integer32, -- average value for voltage
pmPowerMgmtPDUTableVoltageReset INTEGER, -- reset the voltage stats
pmPowerMgmtPDUTableVoltageType INTEGER, -- type of voltage measurement
pmPowerMgmtPDUTablePowerFactorValue Integer32, -- actual value for powerfactor
pmPowerMgmtPDUTablePowerFactorMax Integer32, -- max value for powerfactor
pmPowerMgmtPDUTablePowerFactorMin Integer32, -- min value for powerfactor
pmPowerMgmtPDUTablePowerFactorAvg Integer32, -- average value for powerfactor
pmPowerMgmtPDUTablePowerFactorReset INTEGER, -- reset the powerfactor stats
pmPowerMgmtPDUTablePowerFactorType INTEGER, -- type of power factor measurement
pmPowerMgmtPDUTablePowerControl INTEGER, -- manage the outlets in this PDU
pmPowerMgmtPDUTableResetOCP INTEGER, -- reset the ocp (pdu wide)
pmPowerMgmtPDUTableCurrentHighCritical Integer32, -- get/set current high critical threshold
pmPowerMgmtPDUTableCurrentHighWarning Integer32, -- get/set current high warning threshold
pmPowerMgmtPDUTableCurrentLowWarning Integer32, -- get/set current low warning threshold
pmPowerMgmtPDUTableCurrentLowCritical Integer32, -- get/set current low critical threshold
pmPowerMgmtPDUTableEnergyValue Integer32, -- Energy value
pmPowerMgmtPDUTableEnergyStartTime DisplayString, -- time at which energy calculation commenced
pmPowerMgmtPDUTableEnergyReset INTEGER -- reset energy calculation and start time to now
}
pmPowerMgmtPDUTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of serial port when the PDU is connected."
::= { pmPowerMgmtPDUTableEntry 1 }
pmPowerMgmtPDUTablePduIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A PDU position in the chain."
::= { pmPowerMgmtPDUTableEntry 2 }
pmPowerMgmtPDUTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"PDU identification."
::= { pmPowerMgmtPDUTableEntry 3 }
pmPowerMgmtPDUTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of serial port when the PDU is connected."
::= { pmPowerMgmtPDUTableEntry 4 }
pmPowerMgmtPDUTableModel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Model of the PDU.
Returns N/A if not applicable."
::= { pmPowerMgmtPDUTableEntry 5 }
pmPowerMgmtPDUTableVendor OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Vendor of the PDU.
Returns N/A if not applicable."
::= { pmPowerMgmtPDUTableEntry 6 }
pmPowerMgmtPDUTableFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Version of the PDU firmware.
Returns N/A if not applicable."
::= { pmPowerMgmtPDUTableEntry 7 }
pmPowerMgmtPDUTableNumberOfOutlets OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of outlets of the PDU."
::= { pmPowerMgmtPDUTableEntry 8 }
pmPowerMgmtPDUTableCurrentNOS OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Number of current sensors in the PDU."
::= { pmPowerMgmtPDUTableEntry 9 }
pmPowerMgmtPDUTableCurrent1Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Current of the sensor 1 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.).
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableCurrentValue,
pmPowerMgmtPhasesTableCurrentValue, or
pmPowerMgmtOutletsTableCurrentValue"
::= { pmPowerMgmtPDUTableEntry 10 }
pmPowerMgmtPDUTableCurrent1Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum current of the sensor 1 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)
Clear this value, set it with Zero value.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableCurrentMax,
pmPowerMgmtPhasesTableCurrentMax, or
pmPowerMgmtOutletsTableCurrentMax"
::= { pmPowerMgmtPDUTableEntry 11 }
pmPowerMgmtPDUTableCurrent2Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Current of the sensor 2 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.).
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableCurrentValue,
pmPowerMgmtPhasesTableCurrentValue, or
pmPowerMgmtOutletsTableCurrentValue"
::= { pmPowerMgmtPDUTableEntry 12 }
pmPowerMgmtPDUTableCurrent2Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum current of the sensor 2 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)
Clear this value, set it with Zero value.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableCurrentMax,
pmPowerMgmtPhasesTableCurrentMax, or
pmPowerMgmtOutletsTableCurrentMax"
::= { pmPowerMgmtPDUTableEntry 13}
pmPowerMgmtPDUTableCurrent3Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Current of the sensor 3 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableCurrentValue,
pmPowerMgmtPhasesTableCurrentValue, or
pmPowerMgmtOutletsTableCurrentValue"
::= { pmPowerMgmtPDUTableEntry 14 }
pmPowerMgmtPDUTableCurrent3Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum current of the sensor 3 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.)
Clear this value, set it with Zero value.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableCurrentMax,
pmPowerMgmtPhasesTableCurrentMax, or
pmPowerMgmtOutletsTableCurrentMax"
::= { pmPowerMgmtPDUTableEntry 15 }
pmPowerMgmtPDUTableTemperatureNOS OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Number of temperature sensors in the PDU."
::= { pmPowerMgmtPDUTableEntry 16 }
pmPowerMgmtPDUTableTemperature1Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
::= { pmPowerMgmtPDUTableEntry 17 }
pmPowerMgmtPDUTableTemperature1Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Set with Zero value to clear the max. temperature."
::= { pmPowerMgmtPDUTableEntry 18 }
pmPowerMgmtPDUTableTemperature2Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
::= { pmPowerMgmtPDUTableEntry 19 }
pmPowerMgmtPDUTableTemperature2Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Set with Zero value to clear the max. temperature."
::= { pmPowerMgmtPDUTableEntry 20 }
pmPowerMgmtPDUTableTemperature3Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
::= { pmPowerMgmtPDUTableEntry 21 }
pmPowerMgmtPDUTableTemperature3Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, the temperature is 24 Celsius.)
If the temperature measurement is not installed this
value will be 0.
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
Set with Zero value to clear the max. temperature."
::= { pmPowerMgmtPDUTableEntry 22 }
pmPowerMgmtPDUTableHumidityNOS OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Number of humidity sensors in the PDU."
::= { pmPowerMgmtPDUTableEntry 23 }
pmPowerMgmtPDUTableHumidity1Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0."
::= { pmPowerMgmtPDUTableEntry 24 }
pmPowerMgmtPDUTableHumidity1Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero value to clear the max. temperature."
::= { pmPowerMgmtPDUTableEntry 25 }
pmPowerMgmtPDUTableHumidity2Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0."
::= { pmPowerMgmtPDUTableEntry 26 }
pmPowerMgmtPDUTableHumidity2Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero value to clear the max. temperature."
::= { pmPowerMgmtPDUTableEntry 27 }
pmPowerMgmtPDUTableHumidity3Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0."
::= { pmPowerMgmtPDUTableEntry 28 }
pmPowerMgmtPDUTableHumidity3Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero value to clear the max. temperature."
::= { pmPowerMgmtPDUTableEntry 29 }
pmPowerMgmtPDUTableVoltageNOS OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Number of voltage sensors in the PDU."
::= { pmPowerMgmtPDUTableEntry 30 }
pmPowerMgmtPDUTableVoltage1Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Voltage of this sensor in this PDU unit.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageValue,
pmPowerMgmtPhasesTableVoltageValue, or
pmPowerMgmtOutletsTableVoltageValue"
::= { pmPowerMgmtPDUTableEntry 31 }
pmPowerMgmtPDUTableVoltage1Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageMax,
pmPowerMgmtPhasesTableVoltageMax, or
pmPowerMgmtOutletsTableVoltageMax"
::= { pmPowerMgmtPDUTableEntry 32 }
pmPowerMgmtPDUTableVoltage2Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Voltage of this sensor in this PDU unit.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageValue,
pmPowerMgmtPhasesTableVoltageValue, or
pmPowerMgmtOutletsTableVoltageValue"
::= { pmPowerMgmtPDUTableEntry 33 }
pmPowerMgmtPDUTableVoltage2Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageMax,
pmPowerMgmtPhasesTableVoltageMax, or
pmPowerMgmtOutletsTableVoltageMax"
::= { pmPowerMgmtPDUTableEntry 34 }
pmPowerMgmtPDUTableVoltage3Value OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS obsolete
DESCRIPTION
"Voltage of this sensor in this PDU unit.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageValue,
pmPowerMgmtPhasesTableVoltageValue, or
pmPowerMgmtOutletsTableVoltageValue"
::= { pmPowerMgmtPDUTableEntry 35 }
pmPowerMgmtPDUTableVoltage3Max OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageMax,
pmPowerMgmtPhasesTableVoltageMax, or
pmPowerMgmtOutletsTableVoltageMax"
::= { pmPowerMgmtPDUTableEntry 36 }
pmPowerMgmtPDUTableNumberOfPhases OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of phases of the PDU."
::= { pmPowerMgmtPDUTableEntry 37 }
pmPowerMgmtPDUTableNumberOfBanks OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of banks in the PDU."
::= { pmPowerMgmtPDUTableEntry 38 }
pmPowerMgmtPDUTableNumberOfSensors OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of sensors in the PDU."
::= { pmPowerMgmtPDUTableEntry 40 }
pmPowerMgmtPDUTableFactoryDefault OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of 2 will set the PDU to factory default settings.
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the factory default command is sent to the PDU."
::= { pmPowerMgmtPDUTableEntry 41 }
pmPowerMgmtPDUTableColdStartDelay OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"PDUs cold start delay in whole seconds (0-60).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 42 }
pmPowerMgmtPDUTableReboot OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reboot(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of power*(2) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
reboot(2) = when SET the reboot command is sent to PDU."
::= { pmPowerMgmtPDUTableEntry 43 }
pmPowerMgmtPDUTableMaxCurrent OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of current allowed in the PDU (A x 10)."
::= { pmPowerMgmtPDUTableEntry 44 }
pmPowerMgmtPDUTableAlarm OBJECT-TYPE
SYNTAX INTEGER {
normal (1),
blow-fuse (2),
hw-ocp (3),
high-critical (4),
high-warning (5),
low-warning (6),
low-critical (7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Show the PDU alarm status.
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 45 }
--@ Note: Intentionally left space for future expansion (thanks!)
pmPowerMgmtPDUTableCurrentValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of current in the PDU (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 50 }
pmPowerMgmtPDUTableCurrentMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of current in the PDU (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 51 }
pmPowerMgmtPDUTableCurrentMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of current in the PDU (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 52 }
pmPowerMgmtPDUTableCurrentAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of current in the PDU (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 53 }
pmPowerMgmtPDUTableCurrentReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtPDUTableEntry 54 }
pmPowerMgmtPDUTablePowerValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power in the PDU (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 60 }
pmPowerMgmtPDUTablePowerMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of power in the PDU (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 61 }
pmPowerMgmtPDUTablePowerMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of power in the PDU (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 62 }
pmPowerMgmtPDUTablePowerAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of power in the PDU (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 63 }
pmPowerMgmtPDUTablePowerReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtPDUTableEntry 64 }
pmPowerMgmtPDUTablePowerType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
measured (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power values.
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 65 }
pmPowerMgmtPDUTableVoltageValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of voltage in the PDU (V).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 70 }
pmPowerMgmtPDUTableVoltageMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of voltage in the PDU (V).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 71 }
pmPowerMgmtPDUTableVoltageMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of voltage in the PDU (V).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 72 }
pmPowerMgmtPDUTableVoltageAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of voltage in the PDU (V).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 73 }
pmPowerMgmtPDUTableVoltageReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtPDUTableEntry 74 }
pmPowerMgmtPDUTableVoltageType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
measured (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of voltage values.
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 75 }
pmPowerMgmtPDUTablePowerFactorValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power factor in the PDU (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 80 }
pmPowerMgmtPDUTablePowerFactorMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of power factor in the PDU (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 81 }
pmPowerMgmtPDUTablePowerFactorMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of power factor in the PDU (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 82 }
pmPowerMgmtPDUTablePowerFactorAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of power factor in the PDU (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 83 }
pmPowerMgmtPDUTablePowerFactorReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtPDUTableEntry 84 }
pmPowerMgmtPDUTablePowerFactorType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
measured (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power values.
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 85 }
pmPowerMgmtPDUTablePowerControl OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
powerOn(2),
powerOff(3),
powerCycle(4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of power*(2-4) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
powerOn(2) = when SET the power On command is sent to PDU.
powerOff(3) = when SET the power Off command is sent to PDU.
powerCycle(4)=when SET the power cycle command is sent to PDU.
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 90 }
pmPowerMgmtPDUTableResetOCP OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of power*(2) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 91 }
pmPowerMgmtPDUTableCurrentHighCritical OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"outlet high critical (alarm) current threshold (A x 10).
Set fails if value is lower that CurrentHighWarning.
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 100 }
pmPowerMgmtPDUTableCurrentHighWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"outlet high warning current threshold (A x 10).
Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning.
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 101 }
pmPowerMgmtPDUTableCurrentLowWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"outlet low warning current threshold (A x 10).
Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical.
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 102 }
pmPowerMgmtPDUTableCurrentLowCritical OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"outlet low critical current threshold (A x 10).
Set fails if value is higher than CurrentLowWarning.
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 103 }
pmPowerMgmtPDUTableEnergyValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"pdu energy value (Wh).
Returns 0 if not supported."
::= { pmPowerMgmtPDUTableEntry 105 }
pmPowerMgmtPDUTableEnergyStartTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"time at which energy calculation commenced (ISO8601 format).
Returns N/A if not applicable."
::= { pmPowerMgmtPDUTableEntry 106 }
pmPowerMgmtPDUTableEnergyReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtPDUTableEntry 107 }
pmPowerMgmtTotalNumberOfOutlets OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of outlets managed by the appliance."
::= { pmPowerMgmt 4 }
pmPowerMgmtOutletsTable OBJECT-TYPE
SYNTAX SEQUENCE OF PmPowerMgmtOutletsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about outlets."
::= { pmPowerMgmt 5 }
pmPowerMgmtOutletsTableEntry OBJECT-TYPE
SYNTAX PmPowerMgmtOutletsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the outlet."
INDEX { pmPowerMgmtOutletsTablePortNumber,
pmPowerMgmtOutletsTablePduNumber,
pmPowerMgmtOutletsTableNumber }
::= { pmPowerMgmtOutletsTable 1 }
PmPowerMgmtOutletsTableEntry ::= SEQUENCE {
pmPowerMgmtOutletsTablePortNumber InterfaceIndex, -- serial port #
pmPowerMgmtOutletsTablePduNumber InterfaceIndex,
pmPowerMgmtOutletsTableNumber InterfaceIndex, -- outlet number in PDU
pmPowerMgmtOutletsTableName DisplayString, -- outlet name
pmPowerMgmtOutletsTableStatus INTEGER, -- outlet status
pmPowerMgmtOutletsTablePowerControl INTEGER, -- manage the outlet
pmPowerMgmtOutletsTablePortName DisplayString, -- serial port name
pmPowerMgmtOutletsTablePduId DisplayString, -- PDU ID
pmPowerMgmtOutletsTablePostOnDelay Integer32, -- outlet post on delay delay/post power on
pmPowerMgmtOutletsTablePostOffDelay Integer32, -- outlet post off delay/post power off
pmPowerMgmtOutletsTableAlarm INTEGER, -- outlet alarm status
pmPowerMgmtOutletsTableCurrentValue Integer32, -- actual value for current of the sensor
pmPowerMgmtOutletsTableCurrentMax Integer32, -- max value for current
pmPowerMgmtOutletsTableCurrentMin Integer32, -- min value for current
pmPowerMgmtOutletsTableCurrentAvg Integer32, -- average value for current
pmPowerMgmtOutletsTableCurrentReset INTEGER, -- reset the current stats
pmPowerMgmtOutletsTablePowerValue Integer32, -- actual value for power
pmPowerMgmtOutletsTablePowerMax Integer32, -- max value for power
pmPowerMgmtOutletsTablePowerMin Integer32, -- min value for power
pmPowerMgmtOutletsTablePowerAvg Integer32, -- average value for power
pmPowerMgmtOutletsTablePowerReset INTEGER, -- reset the power stats
pmPowerMgmtOutletsTablePowerType INTEGER, -- power type
pmPowerMgmtOutletsTableVoltageValue Integer32, -- actual value for voltage
pmPowerMgmtOutletsTableVoltageMax Integer32, -- max value for voltage
pmPowerMgmtOutletsTableVoltageMin Integer32, -- min value for voltage
pmPowerMgmtOutletsTableVoltageAvg Integer32, -- average value for voltage
pmPowerMgmtOutletsTableVoltageReset INTEGER, -- reset the voltage stats
pmPowerMgmtOutletsTableVoltageType INTEGER, -- type of voltage measurement
pmPowerMgmtOutletsTablePowerFactorValue Integer32, -- actual value for powerfactor
pmPowerMgmtOutletsTablePowerFactorMax Integer32, -- max value for powerfactor
pmPowerMgmtOutletsTablePowerFactorMin Integer32, -- min value for powerfactor
pmPowerMgmtOutletsTablePowerFactorAvg Integer32, -- average value for powerfactor
pmPowerMgmtOutletsTablePowerFactorReset INTEGER, -- reset the powerfactor stats
pmPowerMgmtOutletsTablePowerFactorType INTEGER, -- power factor type
pmPowerMgmtOutletsTableCurrentHighCritical Integer32, -- outlet current high critical threshold
pmPowerMgmtOutletsTableCurrentHighWarning Integer32, -- outlet current high warning threshold
pmPowerMgmtOutletsTableCurrentLowWarning Integer32, -- outlet current low warning threshold
pmPowerMgmtOutletsTableCurrentLowCritical Integer32, -- outlet current low critical threshold
pmPowerMgmtOutletsTableEnergyValue Integer32, -- Energy value
pmPowerMgmtOutletsTableEnergyStartTime DisplayString, -- time at which energy calculation commenced
pmPowerMgmtOutletsTableEnergyReset INTEGER -- reset energy calculation and start time to now
}
pmPowerMgmtOutletsTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port number."
::= { pmPowerMgmtOutletsTableEntry 1 }
pmPowerMgmtOutletsTablePduNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index."
::= { pmPowerMgmtOutletsTableEntry 2 }
pmPowerMgmtOutletsTableNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of the outlet in the PDU."
::= { pmPowerMgmtOutletsTableEntry 3 }
pmPowerMgmtOutletsTableName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Name of the outlet."
::= { pmPowerMgmtOutletsTableEntry 4 }
pmPowerMgmtOutletsTableStatus OBJECT-TYPE
SYNTAX INTEGER {
off(1),
on(2),
offLocked(3),
onLocked(4),
offCycle(5),
onPendingOff(6),
offPendingOn(7),
onPendingCycle(8),
notSet(9),
onFixed(10),
offShutdown(11),
tripped(12)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of the outlet.
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 5 }
pmPowerMgmtOutletsTablePowerControl OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
powerOn(2),
powerOff(3),
powerCycle(4),
powerLock(5),
powerUnlock(6)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of power*(2-6) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
powerOn(2) = when SET the power On command is sent to PDU.
powerOff(3) = when SET the power Off command is sent to PDU.
powerCycle(4)=when SET the power cycle command is sent to PDU.
powerLock(5)= when SET the power lock command is sent to PDU.
powerUnlock(6)=when SET the power unlock command is sent to PDU.
The powerLock and powerUnlock are valid only for Cyclades-PM PDUs"
::= { pmPowerMgmtOutletsTableEntry 6 }
pmPowerMgmtOutletsTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port Name where the PDU is connected."
::= { pmPowerMgmtOutletsTableEntry 7 }
pmPowerMgmtOutletsTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU identification."
::= { pmPowerMgmtOutletsTableEntry 8 }
pmPowerMgmtOutletsTablePostOnDelay OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"post on delay for the outlet (seconds x 10)
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 9 }
pmPowerMgmtOutletsTablePostOffDelay OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"post off delay for the outlet (seconds x 10)
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 10 }
pmPowerMgmtOutletsTableAlarm OBJECT-TYPE
SYNTAX INTEGER {
normal (1),
blow-fuse (2),
hw-ocp (3),
high-critical (4),
high-warning (5),
low-warning (6),
low-critical (7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Show the outlet alarm status.
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 45 }
--@ Note: Intentionally left space for future expansion
pmPowerMgmtOutletsTableCurrentValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of current in the outlet (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 50 }
pmPowerMgmtOutletsTableCurrentMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of current in the outlet (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 51 }
pmPowerMgmtOutletsTableCurrentMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of current in the outlet (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 52 }
pmPowerMgmtOutletsTableCurrentAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of current in the outlet (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 53 }
pmPowerMgmtOutletsTableCurrentReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtOutletsTableEntry 54 }
pmPowerMgmtOutletsTablePowerValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power in the outlet (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 60 }
pmPowerMgmtOutletsTablePowerMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of power in the outlet (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 61 }
pmPowerMgmtOutletsTablePowerMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of power in the outlet (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 62 }
pmPowerMgmtOutletsTablePowerAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of power in the outlet (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 63 }
pmPowerMgmtOutletsTablePowerReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtOutletsTableEntry 64 }
pmPowerMgmtOutletsTablePowerType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
measured (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power values.
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 65 }
pmPowerMgmtOutletsTableVoltageValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of voltage in the outlet (V).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 70 }
pmPowerMgmtOutletsTableVoltageMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of voltage in the outlet (V).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 71 }
pmPowerMgmtOutletsTableVoltageMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of voltage in the outlet (V).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 72 }
pmPowerMgmtOutletsTableVoltageAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of voltage in the outlet (V).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 73 }
pmPowerMgmtOutletsTableVoltageReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtOutletsTableEntry 74 }
pmPowerMgmtOutletsTableVoltageType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
measured (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of voltage values.
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 75 }
pmPowerMgmtOutletsTablePowerFactorValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power factor in the outlet (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 80 }
pmPowerMgmtOutletsTablePowerFactorMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of power factor in the outlet (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 81 }
pmPowerMgmtOutletsTablePowerFactorMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of power factor in the outlet (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 82 }
pmPowerMgmtOutletsTablePowerFactorAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of power factor in the outlet (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 83 }
pmPowerMgmtOutletsTablePowerFactorReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtOutletsTableEntry 84 }
pmPowerMgmtOutletsTablePowerFactorType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
measured (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power factor values.
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 85 }
pmPowerMgmtOutletsTableCurrentHighCritical OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"outlet high critical (alarm) current threshold (A x 10).
Set fails if value is lower that CurrentHighWarning.
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 100 }
pmPowerMgmtOutletsTableCurrentHighWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"outlet high warning current threshold (A x 10).
Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning.
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 101 }
pmPowerMgmtOutletsTableCurrentLowWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"outlet low warning current threshold (A x 10).
Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical.
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 102 }
pmPowerMgmtOutletsTableCurrentLowCritical OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"outlet low critical current threshold (A x 10).
Set fails if value is higher than CurrentLowWarning.
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 103 }
pmPowerMgmtOutletsTableEnergyValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"outlet energy value (Wh).
Returns 0 if not supported."
::= { pmPowerMgmtOutletsTableEntry 105 }
pmPowerMgmtOutletsTableEnergyStartTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"time at which energy calculation commenced (ISO8601 format).
Returns N/A if not applicable."
::= { pmPowerMgmtOutletsTableEntry 106 }
pmPowerMgmtOutletsTableEnergyReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtOutletsTableEntry 107 }
pmPowerMgmtNumberOfOutletGroup OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of configured group of outlets."
::= { pmPowerMgmt 6 }
pmPowerMgmtGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF PmPowerMgmtGroupTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about group of outlets."
::= { pmPowerMgmt 7 }
pmPowerMgmtGroupTableEntry OBJECT-TYPE
SYNTAX PmPowerMgmtGroupTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about group of outlets."
INDEX { pmPowerMgmtGroupTableIndex }
::= { pmPowerMgmtGroupTable 1 }
PmPowerMgmtGroupTableEntry ::= SEQUENCE {
pmPowerMgmtGroupTableIndex InterfaceIndexOrZero,
pmPowerMgmtGroupTableName DisplayString, -- group name
pmPowerMgmtGroupTableStatus INTEGER, -- group status
pmPowerMgmtGroupTablePowerControl INTEGER -- manage the group
}
pmPowerMgmtGroupTableIndex OBJECT-TYPE
SYNTAX InterfaceIndexOrZero
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index of the group."
::= { pmPowerMgmtGroupTableEntry 1 }
pmPowerMgmtGroupTableName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of the group of outlets."
::= { pmPowerMgmtGroupTableEntry 2 }
pmPowerMgmtGroupTableStatus OBJECT-TYPE
SYNTAX INTEGER {
off(1),
on(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of the group of outlet."
::= { pmPowerMgmtGroupTableEntry 3 }
pmPowerMgmtGroupTablePowerControl OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
powerOn(2),
powerOff(3),
powerCycle(4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A set value of power*(2-4) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
powerOn(2) = when SET the power On command is sent to PDU.
powerOff(3) = when SET the power Off command is sent to PDU.
powerCycle(4)=when SET the power cycle command is sent to PDU."
::= { pmPowerMgmtGroupTableEntry 4 }
pmPowerMgmtTotalNumberOfPhases OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of phases managed by the appliance."
::= { pmPowerMgmt 8 }
pmPowerMgmtPhasesTable OBJECT-TYPE
SYNTAX SEQUENCE OF PmPowerMgmtPhasesTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about phases."
::= { pmPowerMgmt 9 }
pmPowerMgmtPhasesTableEntry OBJECT-TYPE
SYNTAX PmPowerMgmtPhasesTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the phases."
INDEX { pmPowerMgmtPhasesTablePortNumber,
pmPowerMgmtPhasesTablePduNumber,
pmPowerMgmtPhasesTableNumber }
::= { pmPowerMgmtPhasesTable 1 }
PmPowerMgmtPhasesTableEntry ::= SEQUENCE {
pmPowerMgmtPhasesTablePortNumber InterfaceIndex, -- serial port #
pmPowerMgmtPhasesTablePduNumber InterfaceIndex,
pmPowerMgmtPhasesTableNumber InterfaceIndex, -- phase number in PDU
pmPowerMgmtPhasesTableName DisplayString, -- phase sysname
pmPowerMgmtPhasesTablePortName DisplayString, -- serial port name
pmPowerMgmtPhasesTablePduId DisplayString, -- PDU ID
pmPowerMgmtPhasesTableAlarm INTEGER, -- phase alarm status
pmPowerMgmtPhasesTableCurrentValue Integer32, -- actual value for current of the sensor
pmPowerMgmtPhasesTableCurrentMax Integer32, -- max value for current
pmPowerMgmtPhasesTableCurrentMin Integer32, -- min value for current
pmPowerMgmtPhasesTableCurrentAvg Integer32, -- average value for current
pmPowerMgmtPhasesTableCurrentReset INTEGER, -- reset the current stats
pmPowerMgmtPhasesTablePowerValue Integer32, -- actual value for power
pmPowerMgmtPhasesTablePowerMax Integer32, -- max value for power
pmPowerMgmtPhasesTablePowerMin Integer32, -- min value for power
pmPowerMgmtPhasesTablePowerAvg Integer32, -- average value for power
pmPowerMgmtPhasesTablePowerReset INTEGER, -- reset the power stats
pmPowerMgmtPhasesTablePowerType INTEGER, -- power type
pmPowerMgmtPhasesTableVoltageValue Integer32, -- actual value for voltage
pmPowerMgmtPhasesTableVoltageMax Integer32, -- max value for voltage
pmPowerMgmtPhasesTableVoltageMin Integer32, -- min value for voltage
pmPowerMgmtPhasesTableVoltageAvg Integer32, -- average value for voltage
pmPowerMgmtPhasesTableVoltageReset INTEGER, -- reset the voltage stats
pmPowerMgmtPhasesTableVoltageType INTEGER, -- voltage type
pmPowerMgmtPhasesTablePowerFactorValue Integer32, -- actual value for powerfactor
pmPowerMgmtPhasesTablePowerFactorMax Integer32, -- max value for powerfactor
pmPowerMgmtPhasesTablePowerFactorMin Integer32, -- min value for powerfactor
pmPowerMgmtPhasesTablePowerFactorAvg Integer32, -- average value for powerfactor
pmPowerMgmtPhasesTablePowerFactorReset INTEGER, -- reset the powerfactor stats
pmPowerMgmtPhasesTablePowerFactorType INTEGER, -- power factor type
pmPowerMgmtPhasesTableCurrentHighCritical Integer32, -- outlet current high critical threshold
pmPowerMgmtPhasesTableCurrentHighWarning Integer32, -- outlet current high warning threshold
pmPowerMgmtPhasesTableCurrentLowWarning Integer32, -- outlet current low warning threshold
pmPowerMgmtPhasesTableCurrentLowCritical Integer32 -- outlet current low critical threshold
}
pmPowerMgmtPhasesTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port number."
::= { pmPowerMgmtPhasesTableEntry 1 }
pmPowerMgmtPhasesTablePduNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index."
::= { pmPowerMgmtPhasesTableEntry 2 }
pmPowerMgmtPhasesTableNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of the phase in the PDU."
::= { pmPowerMgmtPhasesTableEntry 3 }
pmPowerMgmtPhasesTableName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of the phase.
Returns N/A if not applicable."
::= { pmPowerMgmtPhasesTableEntry 4 }
pmPowerMgmtPhasesTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port Name where the PDU is connected."
::= { pmPowerMgmtPhasesTableEntry 5 }
pmPowerMgmtPhasesTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU identification."
::= { pmPowerMgmtPhasesTableEntry 6 }
pmPowerMgmtPhasesTableAlarm OBJECT-TYPE
SYNTAX INTEGER {
normal (1),
blow-fuse (2),
hw-ocp (3),
high-critical (4),
high-warning (5),
low-warning (6),
low-critical (7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Show the phase alarm status.
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 45 }
--@ Note: Intentionally left space for future expansion
pmPowerMgmtPhasesTableCurrentValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of current in the phase (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 50 }
pmPowerMgmtPhasesTableCurrentMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of current in the phase (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 51 }
pmPowerMgmtPhasesTableCurrentMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of current in the phase (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 52 }
pmPowerMgmtPhasesTableCurrentAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of current in the phase (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 53 }
pmPowerMgmtPhasesTableCurrentReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtPhasesTableEntry 54 }
pmPowerMgmtPhasesTablePowerValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power in the phase (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 60 }
pmPowerMgmtPhasesTablePowerMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of power in the phase (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 61 }
pmPowerMgmtPhasesTablePowerMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of power in the phase (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 62 }
pmPowerMgmtPhasesTablePowerAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of power in the phase (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 63 }
pmPowerMgmtPhasesTablePowerReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtPhasesTableEntry 64 }
pmPowerMgmtPhasesTablePowerType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
measured (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power values.
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 65 }
pmPowerMgmtPhasesTableVoltageValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of voltage in the phase (V).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 70 }
pmPowerMgmtPhasesTableVoltageMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of voltage in the phase (V).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 71 }
pmPowerMgmtPhasesTableVoltageMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of voltage in the phase (V).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 72 }
pmPowerMgmtPhasesTableVoltageAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of voltage in the phase (V).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 73 }
pmPowerMgmtPhasesTableVoltageReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtPhasesTableEntry 74 }
pmPowerMgmtPhasesTableVoltageType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
measured (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of voltage values.
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 75 }
pmPowerMgmtPhasesTablePowerFactorValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power factor in the phase (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 80 }
pmPowerMgmtPhasesTablePowerFactorMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of power factor in the phase (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 81 }
pmPowerMgmtPhasesTablePowerFactorMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of power factor in the phase (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 82 }
pmPowerMgmtPhasesTablePowerFactorAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of power factor in the phase (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 83 }
pmPowerMgmtPhasesTablePowerFactorReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtPhasesTableEntry 84 }
pmPowerMgmtPhasesTablePowerFactorType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
measured (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power factor values.
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 85 }
pmPowerMgmtPhasesTableCurrentHighCritical OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"phase high critical (alarm) current threshold (A x 10).
Set fails if value is lower that CurrentHighWarning.
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 100 }
pmPowerMgmtPhasesTableCurrentHighWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"phase high warning current threshold (A x 10).
Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning.
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 101 }
pmPowerMgmtPhasesTableCurrentLowWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"phase low warning current threshold (A x 10).
Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical.
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 102 }
pmPowerMgmtPhasesTableCurrentLowCritical OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"phase low critical current threshold (A x 10).
Set fails if value is higher than CurrentLowWarning.
Returns 0 if not supported."
::= { pmPowerMgmtPhasesTableEntry 103 }
--@ BANKS
pmPowerMgmtTotalNumberOfBanks OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of banks managed by the appliance."
::= { pmPowerMgmt 10 }
pmPowerMgmtBanksTable OBJECT-TYPE
SYNTAX SEQUENCE OF PmPowerMgmtBanksTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about banks."
::= { pmPowerMgmt 11 }
pmPowerMgmtBanksTableEntry OBJECT-TYPE
SYNTAX PmPowerMgmtBanksTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the banks."
INDEX { pmPowerMgmtBanksTablePortNumber,
pmPowerMgmtBanksTablePduNumber,
pmPowerMgmtBanksTableNumber }
::= { pmPowerMgmtBanksTable 1 }
PmPowerMgmtBanksTableEntry ::= SEQUENCE {
pmPowerMgmtBanksTablePortNumber InterfaceIndex, -- serial port #
pmPowerMgmtBanksTablePduNumber InterfaceIndex,
pmPowerMgmtBanksTableNumber InterfaceIndex, -- bank number in PDU
pmPowerMgmtBanksTableName DisplayString, -- bank sysname
pmPowerMgmtBanksTablePortName DisplayString, -- serial port name
pmPowerMgmtBanksTablePduId DisplayString, -- PDU ID
pmPowerMgmtBanksTableAlarm INTEGER, -- bank alarm status
pmPowerMgmtBanksTableCurrentValue Integer32, -- actual value for current of the sensor
pmPowerMgmtBanksTableCurrentMax Integer32, -- max value for current
pmPowerMgmtBanksTableCurrentMin Integer32, -- min value for current
pmPowerMgmtBanksTableCurrentAvg Integer32, -- average value for current
pmPowerMgmtBanksTableCurrentReset INTEGER, -- reset current stats
pmPowerMgmtBanksTablePowerValue Integer32, -- actual value for power
pmPowerMgmtBanksTablePowerMax Integer32, -- max value for power
pmPowerMgmtBanksTablePowerMin Integer32, -- min value for power
pmPowerMgmtBanksTablePowerAvg Integer32, -- average value for power
pmPowerMgmtBanksTablePowerReset INTEGER, -- reset power stats
pmPowerMgmtBanksTablePowerType INTEGER, -- power type
pmPowerMgmtBanksTableVoltageValue Integer32, -- actual value for voltage
pmPowerMgmtBanksTableVoltageMax Integer32, -- max value for voltage
pmPowerMgmtBanksTableVoltageMin Integer32, -- min value for voltage
pmPowerMgmtBanksTableVoltageAvg Integer32, -- average value for voltage
pmPowerMgmtBanksTableVoltageReset INTEGER, -- reset voltage stats
pmPowerMgmtBanksTableVoltageType INTEGER, -- voltage type
pmPowerMgmtBanksTablePowerFactorValue Integer32, -- actual value for powerfactor
pmPowerMgmtBanksTablePowerFactorMax Integer32, -- max value for powerfactor
pmPowerMgmtBanksTablePowerFactorMin Integer32, -- min value for powerfactor
pmPowerMgmtBanksTablePowerFactorAvg Integer32, -- average value for powerfactor
pmPowerMgmtBanksTablePowerFactorReset INTEGER, -- reset powerfactor stats
pmPowerMgmtBanksTablePowerFactorType INTEGER, -- power factor type
pmPowerMgmtBanksTableCurrentHighCritical Integer32, -- outlet current high critical threshold
pmPowerMgmtBanksTableCurrentHighWarning Integer32, -- outlet current high warning threshold
pmPowerMgmtBanksTableCurrentLowWarning Integer32, -- outlet current low warning threshold
pmPowerMgmtBanksTableCurrentLowCritical Integer32, -- outlet current low critical threshold
pmPowerMgmtBanksTableEnergyValue Integer32, -- Energy value
pmPowerMgmtBanksTableEnergyStartTime DisplayString, -- time at which energy calculation commenced
pmPowerMgmtBanksTableEnergyReset INTEGER -- reset energy calculation and start time to now
}
pmPowerMgmtBanksTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port number."
::= { pmPowerMgmtBanksTableEntry 1 }
pmPowerMgmtBanksTablePduNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index."
::= { pmPowerMgmtBanksTableEntry 2 }
pmPowerMgmtBanksTableNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of the bank in the PDU."
::= { pmPowerMgmtBanksTableEntry 3 }
pmPowerMgmtBanksTableName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Name of the bank."
::= { pmPowerMgmtBanksTableEntry 4 }
pmPowerMgmtBanksTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port Name where the PDU is connected."
::= { pmPowerMgmtBanksTableEntry 5 }
pmPowerMgmtBanksTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU identification."
::= { pmPowerMgmtBanksTableEntry 6 }
pmPowerMgmtBanksTableAlarm OBJECT-TYPE
SYNTAX INTEGER {
normal (1),
blow-fuse (2),
hw-ocp (3),
high-critical (4),
high-warning (5),
low-warning (6),
low-critical (7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Show the bank alarm status.
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 45 }
--@ Note: Intentionally left space for future expansion
pmPowerMgmtBanksTableCurrentValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of current in the bank (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 50 }
pmPowerMgmtBanksTableCurrentMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of current in the bank (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 51 }
pmPowerMgmtBanksTableCurrentMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of current in the bank (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 52 }
pmPowerMgmtBanksTableCurrentAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of current in the bank (A x 10).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 53 }
pmPowerMgmtBanksTableCurrentReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtBanksTableEntry 54 }
pmPowerMgmtBanksTablePowerValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power in the bank (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 60 }
pmPowerMgmtBanksTablePowerMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of power in the bank (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 61 }
pmPowerMgmtBanksTablePowerMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of power in the bank (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 62 }
pmPowerMgmtBanksTablePowerAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of power in the bank (W x 10).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 63 }
pmPowerMgmtBanksTablePowerReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtBanksTableEntry 64 }
pmPowerMgmtBanksTablePowerType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
measured (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power values.
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 65 }
pmPowerMgmtBanksTableVoltageValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of voltage in the bank (V).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 70 }
pmPowerMgmtBanksTableVoltageMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of voltage in the bank (V).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 71 }
pmPowerMgmtBanksTableVoltageMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of voltage in the bank (V).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 72 }
pmPowerMgmtBanksTableVoltageAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of voltage in the bank (V).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 73 }
pmPowerMgmtBanksTableVoltageReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtBanksTableEntry 74 }
pmPowerMgmtBanksTableVoltageType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
measured (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of voltage values.
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 75 }
pmPowerMgmtBanksTablePowerFactorValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of power factor in the bank (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 80 }
pmPowerMgmtBanksTablePowerFactorMax OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of power factor in the bank (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 81 }
pmPowerMgmtBanksTablePowerFactorMin OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of power factor in the bank (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 82 }
pmPowerMgmtBanksTablePowerFactorAvg OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of power factor in the bank (Pf x 100).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 83 }
pmPowerMgmtBanksTablePowerFactorReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtBanksTableEntry 84 }
pmPowerMgmtBanksTablePowerFactorType OBJECT-TYPE
SYNTAX INTEGER {
none-sensor (0),
estimated (1),
measured (2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION "Type of power factor values.
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 85 }
pmPowerMgmtBanksTableCurrentHighCritical OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"bank high critical (alarm) current threshold (A x 10).
Set fails if value is lower that CurrentHighWarning.
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 100 }
pmPowerMgmtBanksTableCurrentHighWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"bank high warning current threshold (A x 10).
Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning.
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 101 }
pmPowerMgmtBanksTableCurrentLowWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"bank low warning current threshold (A x 10).
Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical.
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 102 }
pmPowerMgmtBanksTableCurrentLowCritical OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"bank low critical current threshold (A x 10).
Set fails if value is higher than CurrentLowWarning.
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 103 }
pmPowerMgmtBanksTableEnergyValue OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"bank energy value (Wh).
Returns 0 if not supported."
::= { pmPowerMgmtBanksTableEntry 105 }
pmPowerMgmtBanksTableEnergyStartTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"time at which energy calculation commenced (ISO8601 format).
Returns N/A if not applicable."
::= { pmPowerMgmtBanksTableEntry 106 }
pmPowerMgmtBanksTableEnergyReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU."
::= { pmPowerMgmtBanksTableEntry 107 }
--@ Sensors
pmPowerMgmtTotalNumberOfSensors OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of Sensors managed by the appliance."
::= { pmPowerMgmt 12 }
pmPowerMgmtSensorsTable OBJECT-TYPE
SYNTAX SEQUENCE OF PmPowerMgmtSensorsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains the information about sensors."
::= { pmPowerMgmt 13 }
pmPowerMgmtSensorsTableEntry OBJECT-TYPE
SYNTAX PmPowerMgmtSensorsTableEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"each entry has the information about the sensors."
INDEX { pmPowerMgmtSensorsTablePortNumber,
pmPowerMgmtSensorsTablePduNumber,
pmPowerMgmtSensorsTableNumber }
::= { pmPowerMgmtSensorsTable 1 }
PmPowerMgmtSensorsTableEntry ::= SEQUENCE {
pmPowerMgmtSensorsTablePortNumber InterfaceIndex, -- serial port #
pmPowerMgmtSensorsTablePduNumber InterfaceIndex,
pmPowerMgmtSensorsTableNumber InterfaceIndex, -- sensor number in PDU
pmPowerMgmtSensorsTableName DisplayString, -- sensor name
pmPowerMgmtSensorsTablePortName DisplayString, -- serial port name
pmPowerMgmtSensorsTablePduId DisplayString, -- PDU ID
pmPowerMgmtSensorsTableType INTEGER, -- sensor type
pmPowerMgmtSensorsTableStatus INTEGER, -- digital sensor status
pmPowerMgmtSensorsTableValue DisplayString, -- actual value for current of the sensor
pmPowerMgmtSensorsTableValueMax DisplayString, -- max value for current
pmPowerMgmtSensorsTableValueMin DisplayString, -- min value for current
pmPowerMgmtSensorsTableValueAvg DisplayString, -- average value for current
pmPowerMgmtSensorsTableValueInt Integer32, -- actual value for current of the sensor
pmPowerMgmtSensorsTableValueMaxInt Integer32, -- max value for current
pmPowerMgmtSensorsTableValueMinInt Integer32, -- min value for current
pmPowerMgmtSensorsTableValueAvgInt Integer32, -- average value for current
pmPowerMgmtSensorsTableValueReset INTEGER, -- reset current stats
pmPowerMgmtSensorsTableHighCritical Integer32, -- set/get sensor high critical threshold
pmPowerMgmtSensorsTableHighWarning Integer32, -- set/get sensor high warning threshold
pmPowerMgmtSensorsTableLowWarning Integer32, -- set/get sensor low warning threshold
pmPowerMgmtSensorsTableLowCritical Integer32, -- set/get sensor low critical threshold
pmPowerMgmtSensorsTableUnit INTEGER, -- set/get sensor unit of measurement
pmPowerMgmtSensorsTableHighCriticalC Integer32, -- get sensor high critical threshold
pmPowerMgmtSensorsTableHighWarningC Integer32, -- get sensor high warning threshold
pmPowerMgmtSensorsTableLowWarningC Integer32, -- get sensor low warning threshold
pmPowerMgmtSensorsTableLowCriticalC Integer32, -- get sensor low critical threshold
pmPowerMgmtSensorsTableHighCriticalF Integer32, -- get sensor high critical threshold
pmPowerMgmtSensorsTableHighWarningF Integer32, -- get sensor high warning threshold
pmPowerMgmtSensorsTableLowWarningF Integer32, -- get sensor low warning threshold
pmPowerMgmtSensorsTableLowCriticalF Integer32 -- get sensor low critical threshold
}
pmPowerMgmtSensorsTablePortNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port number."
::= { pmPowerMgmtSensorsTableEntry 1 }
pmPowerMgmtSensorsTablePduNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Index."
::= { pmPowerMgmtSensorsTableEntry 2 }
pmPowerMgmtSensorsTableNumber OBJECT-TYPE
SYNTAX InterfaceIndex
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of the sensor in the PDU."
::= { pmPowerMgmtSensorsTableEntry 3 }
pmPowerMgmtSensorsTableName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Name of the sensor."
::= { pmPowerMgmtSensorsTableEntry 4 }
pmPowerMgmtSensorsTablePortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial Port Name where the PDU is connected."
::= { pmPowerMgmtSensorsTableEntry 5 }
pmPowerMgmtSensorsTablePduId OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU identification."
::= { pmPowerMgmtSensorsTableEntry 6 }
pmPowerMgmtSensorsTableType OBJECT-TYPE
SYNTAX INTEGER {
temp-internal (1),
temperature (2),
humidity (3),
air-flow (4),
smoke (5),
dry-concact (6),
water-level (7),
motion (8),
unplugged (9),
unknown (10)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of environmental monitor.
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 7 }
pmPowerMgmtSensorsTableStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(1),
triggered(2),
not-applicable(3),
opened(4),
closed(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Status of digital sensors: Dry-Contact, Water level, Smoke sensor, Motion sensor.
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 8 }
--@ Note: Intentionally left space for future expansion
pmPowerMgmtSensorsTableValue OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of the sensor.
Returns N/A if not applicable."
::= { pmPowerMgmtSensorsTableEntry 20 }
pmPowerMgmtSensorsTableValueMax OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of the sensor.
Returns N/A if not applicable."
::= { pmPowerMgmtSensorsTableEntry 21 }
pmPowerMgmtSensorsTableValueMin OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of the sensor.
Returns N/A if not applicable."
::= { pmPowerMgmtSensorsTableEntry 22 }
pmPowerMgmtSensorsTableValueAvg OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of the sensor.
Returns N/A if not applicable."
::= { pmPowerMgmtSensorsTableEntry 23 }
pmPowerMgmtSensorsTableValueInt OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Actual value of the sensor.
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 25 }
pmPowerMgmtSensorsTableValueMaxInt OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Maximum value of the sensor.
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 26 }
pmPowerMgmtSensorsTableValueMinInt OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Minimum value of the sensor.
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 27 }
pmPowerMgmtSensorsTableValueAvgInt OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Average value of the sensor.
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 28 }
pmPowerMgmtSensorsTableValueReset OBJECT-TYPE
SYNTAX INTEGER {
noAction(1),
reset(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to sensor."
::= { pmPowerMgmtSensorsTableEntry 30 }
pmPowerMgmtSensorsTableHighCritical OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"sensor high critical (alarm) threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit.
Set fails if value is lower that CurrentHighWarning.
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 40 }
pmPowerMgmtSensorsTableHighWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"sensor high warning threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit.
Set fails if value is higher than HighCritical or lower than LowWarning.
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 41 }
pmPowerMgmtSensorsTableLowWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"sensor low warning threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit.
Set fails if value is higher than HighWarning or lower than LowCritical.
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 42 }
pmPowerMgmtSensorsTableLowCritical OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"sensor low critical threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit.
Set fails if value is higher than LowWarning.
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 43 }
pmPowerMgmtSensorsTableUnit OBJECT-TYPE
SYNTAX INTEGER {
undefined (1),
fahrenheit (2),
celsius (3),
percent (4),
afu (5)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"sensor unit.
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 45 }
pmPowerMgmtSensorsTableHighCriticalC OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"sensor high critical (alarm) threshold (Celcius x 10).
to SET: use pmPowerMgmtSensorsTableHighCritical in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 50 }
pmPowerMgmtSensorsTableHighWarningC OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"sensor high warning threshold (Celcius x 10).
to SET: use pmPowerMgmtSensorsTableHighWarning in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 51 }
pmPowerMgmtSensorsTableLowWarningC OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"sensor low warning threshold (Celcius x 10).
to SET: use pmPowerMgmtSensorsTableLowWarning in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 52 }
pmPowerMgmtSensorsTableLowCriticalC OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"sensor low critical threshold (Celcius x 10).
to SET: use pmPowerMgmtSensorsTableLowCritical in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 53 }
pmPowerMgmtSensorsTableHighCriticalF OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"sensor high critical (alarm) threshold (Fahrenheit x 10).
to SET: use pmPowerMgmtSensorsTableHighCritical in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 60 }
pmPowerMgmtSensorsTableHighWarningF OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"sensor high warning threshold (Fahrenheit x 10).
to SET: use pmPowerMgmtSensorsTableHighWarning in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 61 }
pmPowerMgmtSensorsTableLowWarningF OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"sensor low warning threshold (Fahrenheit x 10).
to SET: use pmPowerMgmtSensorsTableLowWarning in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 62 }
pmPowerMgmtSensorsTableLowCriticalF OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"sensor low critical threshold (Fahrenheit x 10).
to SET: use pmPowerMgmtSensorsTableLowCritical in proper units (pmPowerMgmtSensorsTableUnit).
Returns 0 if not supported."
::= { pmPowerMgmtSensorsTableEntry 63 }
END