mibs/MIBS/liebert/LIEBERT-GP-FLEXIBLE-COND-MIB

5535 lines
183 KiB
Plaintext
Raw Permalink Normal View History

2023-12-05 12:25:34 +01:00
LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY,
OBJECT-IDENTITY
FROM SNMPv2-SMI
liebertFlexibleConditionsModuleReg
FROM LIEBERT-GP-REGISTRATION-MIB
lgpFlexConditions
FROM LIEBERT-GP-CONDITIONS-MIB
;
-- =============================================================================
-- Module Identification and Registration
-- =============================================================================
liebertGlobalProductsFlexibleConditionsModule MODULE-IDENTITY
LAST-UPDATED "201810020000Z"
ORGANIZATION "Liebert Corporation"
CONTACT-INFO
"Contact: Technical Support
Postal:
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus OH, 43229
US
Tel: +1 (800) 222-5877
E-mail: liebert.monitoring@vertivco.com
Web: www.vertivco.com"
DESCRIPTION
"The MIB module used to register Liebert SNMP OIDs.
Copyright 2000-2018 Liebert Corporation. All rights reserved.
Reproduction of this document is authorized on the condition
that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Liebert Corporation
makes no warranty, either express or implied, as to the use,
operation, condition, or performance of the Specification."
REVISION "201810020000Z"
DESCRIPTION
"Compiled From GDD Version: 6825.1"
::= { liebertFlexibleConditionsModuleReg 1 }
-- =============================================================================
-- lgpFlexConditions - Liebert Conditions Registrations
-- =============================================================================
lgpFlexConditionsWellKnown OBJECT IDENTIFIER
-- STATUS current
-- DESCRIPTION
-- "Liebert well known conditions are defined by OIDs that
-- reside in this sub-tree."
::= { lgpFlexConditions 1 }
-- =============================================================================
-- lgpFlexConditionsWellKnown - Liebert "well-known" Conditions
-- =============================================================================
lgpCondId4122SystemInputPowerProblem OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The input is not qualified to provide power to the system."
::= { lgpFlexConditionsWellKnown 4122 }
lgpCondId4132BypassOverloadPhaseA OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An overload exists on output phase A while operating on the bypass."
::= { lgpFlexConditionsWellKnown 4132 }
lgpCondId4133BypassOverloadPhaseB OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An overload exists on output phase B while operating on the bypass."
::= { lgpFlexConditionsWellKnown 4133 }
lgpCondId4134BypassOverloadPhaseC OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An overload exists on output phase C while operating on the bypass."
::= { lgpFlexConditionsWellKnown 4134 }
lgpCondId4135BypassNotAvailable OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A problem associated with the bypass has been detected."
::= { lgpFlexConditionsWellKnown 4135 }
lgpCondId4137BypassAutoRetransferPrimed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Automatic retransfer from bypass to inverter is possible."
::= { lgpFlexConditionsWellKnown 4137 }
lgpCondId4138BypassAutoRetransferFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"After performing a recoverable transfer to bypass, an attempt to
auto retransfer from bypass to inverter failed."
::= { lgpFlexConditionsWellKnown 4138 }
lgpCondId4139BypassExcessAutoRetransfers OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The number of auto retransfers, from bypass to inverter, has
exceeded the maximum for a specified time interval."
::= { lgpFlexConditionsWellKnown 4139 }
lgpCondId4140BypassRestartInhibitExternal OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Restart of the bypass is inhibited by the state of an external
signal."
::= { lgpFlexConditionsWellKnown 4140 }
lgpCondId4141BypassBreakerClosed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The bypass breaker is closed."
::= { lgpFlexConditionsWellKnown 4141 }
lgpCondId4142BypassStaticSwitchOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Bypass off due to static switch overload."
::= { lgpFlexConditionsWellKnown 4142 }
lgpCondId4143BypassStaticSwitchUnavailable OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The static bypass is unavailable to support the critical load."
::= { lgpFlexConditionsWellKnown 4143 }
lgpCondId4144BypassExcessivePulseParallel OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has performed too many pulse parallel operations within
a specified time interval."
::= { lgpFlexConditionsWellKnown 4144 }
lgpCondId4145BypassAutoTransferFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An automatic transfer to static bypass failed."
::= { lgpFlexConditionsWellKnown 4145 }
lgpCondId4146SystemInputPhsRotationError OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The power conductors on the input line are not wired to the UPS in
the sequence preferred for the rectifier (A-B-C)."
::= { lgpFlexConditionsWellKnown 4146 }
lgpCondId4147SystemInputCurrentLimit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The RMS input current has reached the input current limit
threshold."
::= { lgpFlexConditionsWellKnown 4147 }
lgpCondId4162BatteryLow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The calculated battery time remaining has reached the low battery
threshold."
::= { lgpFlexConditionsWellKnown 4162 }
lgpCondId4163OutputOffEndofDischarge OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output turned off due to battery reaching end-of-discharge."
::= { lgpFlexConditionsWellKnown 4163 }
lgpCondId4164BatteryChargingError OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery is not charging properly."
::= { lgpFlexConditionsWellKnown 4164 }
lgpCondId4165BatteryChargingReducedExtrnl OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Using a reduced battery charging algorithm due to an external
signal."
::= { lgpFlexConditionsWellKnown 4165 }
lgpCondId4166BatteryCapacityLow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery capacity is low."
::= { lgpFlexConditionsWellKnown 4166 }
lgpCondId4167OutputOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output is off."
::= { lgpFlexConditionsWellKnown 4167 }
lgpCondId4168BatteryDischarging OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery is discharging."
::= { lgpFlexConditionsWellKnown 4168 }
lgpCondId4169BatteryTemperatureImbalance OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Excessive temperature differences between battery sensors detected."
::= { lgpFlexConditionsWellKnown 4169 }
lgpCondId4170BatteryEqualize OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The rectifier output voltage is increased to equalize the battery
voltage level."
::= { lgpFlexConditionsWellKnown 4170 }
lgpCondId4171BatteryManualTestInProgress OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Manual battery test is in progress."
::= { lgpFlexConditionsWellKnown 4171 }
lgpCondId4172BatteryAutoTestInProgress OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Automatic battery test is in progress."
::= { lgpFlexConditionsWellKnown 4172 }
lgpCondId4173MainBatteryDisconnectOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Main battery disconnect is open."
::= { lgpFlexConditionsWellKnown 4173 }
lgpCondId4174BatteryTemperatureSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A battery temperature sensor fault has been detected."
::= { lgpFlexConditionsWellKnown 4174 }
lgpCondId4175BypassFrequencyError OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The bypass frequency is outside the inverter synchronization
limits."
::= { lgpFlexConditionsWellKnown 4175 }
lgpCondId4176BatteryCircuitBreaker1Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 1 is open."
::= { lgpFlexConditionsWellKnown 4176 }
lgpCondId4177BatteryBreaker1OpenFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 1 failed to open."
::= { lgpFlexConditionsWellKnown 4177 }
lgpCondId4178BatteryBreaker1CloseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 1 failed to close."
::= { lgpFlexConditionsWellKnown 4178 }
lgpCondId4179BatteryCircuitBreaker2Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 2 is open."
::= { lgpFlexConditionsWellKnown 4179 }
lgpCondId4180BatteryBreaker2OpenFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 2 failed to open."
::= { lgpFlexConditionsWellKnown 4180 }
lgpCondId4181BatteryBreaker2CloseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 2 failed to close."
::= { lgpFlexConditionsWellKnown 4181 }
lgpCondId4182BatteryCircuitBreaker3Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 3 is open."
::= { lgpFlexConditionsWellKnown 4182 }
lgpCondId4183BatteryBreaker3OpenFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 3 failed to open."
::= { lgpFlexConditionsWellKnown 4183 }
lgpCondId4184BatteryBreaker3CloseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 3 failed to close."
::= { lgpFlexConditionsWellKnown 4184 }
lgpCondId4185BatteryCircuitBreaker4Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 4 is open."
::= { lgpFlexConditionsWellKnown 4185 }
lgpCondId4186BatteryBreaker4OpenFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 4 failed to open."
::= { lgpFlexConditionsWellKnown 4186 }
lgpCondId4187BatteryBreaker4CloseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 4 failed to close."
::= { lgpFlexConditionsWellKnown 4187 }
lgpCondId4188BatteryCircuitBreaker5Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 5 is open."
::= { lgpFlexConditionsWellKnown 4188 }
lgpCondId4189BatteryBreaker5OpenFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 5 failed to open."
::= { lgpFlexConditionsWellKnown 4189 }
lgpCondId4190BatteryBreaker5CloseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 5 failed to close."
::= { lgpFlexConditionsWellKnown 4190 }
lgpCondId4191BatteryCircuitBreaker6Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 6 is open."
::= { lgpFlexConditionsWellKnown 4191 }
lgpCondId4192BatteryBreaker6OpenFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 6 failed to open."
::= { lgpFlexConditionsWellKnown 4192 }
lgpCondId4193BatteryBreaker6CloseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 6 failed to close."
::= { lgpFlexConditionsWellKnown 4193 }
lgpCondId4194BatteryCircuitBreaker7Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 7 is open."
::= { lgpFlexConditionsWellKnown 4194 }
lgpCondId4195BatteryBreaker7OpenFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 7 failed to open."
::= { lgpFlexConditionsWellKnown 4195 }
lgpCondId4196BatteryBreaker7CloseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 7 failed to close."
::= { lgpFlexConditionsWellKnown 4196 }
lgpCondId4197BatteryCircuitBreaker8Open OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 8 is open."
::= { lgpFlexConditionsWellKnown 4197 }
lgpCondId4198BatteryBreaker8OpenFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 8 failed to open."
::= { lgpFlexConditionsWellKnown 4198 }
lgpCondId4199BatteryBreaker8CloseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery circuit breaker 8 failed to close."
::= { lgpFlexConditionsWellKnown 4199 }
lgpCondId4200BatteryChargingInhibited OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery charging is inhibited due to an external inhibit signal."
::= { lgpFlexConditionsWellKnown 4200 }
lgpCondId4213SystemShutdownEPO OBJECT-IDENTITY
STATUS current
DESCRIPTION
"System shutdown due to Emergency Power Off (EPO)."
::= { lgpFlexConditionsWellKnown 4213 }
lgpCondId4214SystemShutdownREPO OBJECT-IDENTITY
STATUS current
DESCRIPTION
"System shutdown due to Remote Emergency Power Off (REPO)."
::= { lgpFlexConditionsWellKnown 4214 }
lgpCondId4215SystemOutputOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system output is off."
::= { lgpFlexConditionsWellKnown 4215 }
lgpCondId4216BypassBackfeedDetected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system detected a voltage on the bypass when none was expected."
::= { lgpFlexConditionsWellKnown 4216 }
lgpCondId4217BypassManualXfrInhibited OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Manual transfer from inverter to bypass is inhibited - bypass not
qualified."
::= { lgpFlexConditionsWellKnown 4217 }
lgpCondId4218BypassManualRexfrInhibited OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Manual transfer from bypass to inverter is inhibited - inverter
output not qualified."
::= { lgpFlexConditionsWellKnown 4218 }
lgpCondId4219BatteryOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A battery temperature sensor is reporting a value above a
threshold."
::= { lgpFlexConditionsWellKnown 4219 }
lgpCondId4220BatteryExternalMonitor1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"External battery monitor 1 - battery maintenance required."
::= { lgpFlexConditionsWellKnown 4220 }
lgpCondId4221BatteryExternalMonitor2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"External battery monitor 2 - battery maintenance required."
::= { lgpFlexConditionsWellKnown 4221 }
lgpCondId4222BatteryGroundFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery system ground fault amperage exceeds the threshold."
::= { lgpFlexConditionsWellKnown 4222 }
lgpCondId4229EmergencyPowerOffLatched OBJECT-IDENTITY
STATUS current
DESCRIPTION
"System output is off - 'Emergency Power Off (EPO) - latched'
requires manual reset."
::= { lgpFlexConditionsWellKnown 4229 }
lgpCondId4230SystemOutputLowPowerFactor OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system output power factor is low, resulting in reduced output
capacity."
::= { lgpFlexConditionsWellKnown 4230 }
lgpCondId4231OutputCurrentExceedsThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output current for one or more phases exceeds a threshold."
::= { lgpFlexConditionsWellKnown 4231 }
lgpCondId4233InverterFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Inverter failure - inverter output is off."
::= { lgpFlexConditionsWellKnown 4233 }
lgpCondId4234InverterOverloadPhaseA OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Inverter is operating with an overload on phase A."
::= { lgpFlexConditionsWellKnown 4234 }
lgpCondId4235InverterOverloadPhaseB OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Inverter is operating with an overload on phase B."
::= { lgpFlexConditionsWellKnown 4235 }
lgpCondId4236InverterOverloadPhaseC OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Inverter is operating with an overload on phase C."
::= { lgpFlexConditionsWellKnown 4236 }
lgpCondId4237InverterInhibitExternal OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Restart of the inverter is inhibited by an external signal."
::= { lgpFlexConditionsWellKnown 4237 }
lgpCondId4238InverterOutBreakerOpenFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Inverter output breaker failed to open."
::= { lgpFlexConditionsWellKnown 4238 }
lgpCondId4239InverterOutBreakerCloseFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Inverter output breaker failed to close."
::= { lgpFlexConditionsWellKnown 4239 }
lgpCondId4270InputContact01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 1."
::= { lgpFlexConditionsWellKnown 4270 }
lgpCondId4271InputContact02 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 2."
::= { lgpFlexConditionsWellKnown 4271 }
lgpCondId4272InputContact03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 3."
::= { lgpFlexConditionsWellKnown 4272 }
lgpCondId4273InputContact04 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 4."
::= { lgpFlexConditionsWellKnown 4273 }
lgpCondId4274InputContact05 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 5."
::= { lgpFlexConditionsWellKnown 4274 }
lgpCondId4275InputContact06 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 6."
::= { lgpFlexConditionsWellKnown 4275 }
lgpCondId4276InputContact07 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 7."
::= { lgpFlexConditionsWellKnown 4276 }
lgpCondId4277InputContact08 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 8."
::= { lgpFlexConditionsWellKnown 4277 }
lgpCondId4278InputContact09 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 9."
::= { lgpFlexConditionsWellKnown 4278 }
lgpCondId4279InputContact10 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 10."
::= { lgpFlexConditionsWellKnown 4279 }
lgpCondId4280InputContact11 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 11."
::= { lgpFlexConditionsWellKnown 4280 }
lgpCondId4281InputContact12 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 12."
::= { lgpFlexConditionsWellKnown 4281 }
lgpCondId4282InputContact13 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 13."
::= { lgpFlexConditionsWellKnown 4282 }
lgpCondId4283InputContact14 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 14."
::= { lgpFlexConditionsWellKnown 4283 }
lgpCondId4284InputContact15 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 15."
::= { lgpFlexConditionsWellKnown 4284 }
lgpCondId4285InputContact16 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external input contact 16."
::= { lgpFlexConditionsWellKnown 4285 }
lgpCondId4286OutputAmpOverUserLimitPhsA OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The phase A output has exceeded the user amperage threshold."
::= { lgpFlexConditionsWellKnown 4286 }
lgpCondId4287OutputAmpOverUserLimitPhsB OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The phase B output has exceeded the user amperage threshold."
::= { lgpFlexConditionsWellKnown 4287 }
lgpCondId4288OutputAmpOverUserLimitPhsC OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The phase C output has exceeded the user amperage threshold."
::= { lgpFlexConditionsWellKnown 4288 }
lgpCondId4289InverterTransferInhibitExt OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Transfer of critical bus source to inverter is inhibited by an
external signal."
::= { lgpFlexConditionsWellKnown 4289 }
lgpCondId4290InverterShutdownOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter has shutdown due to a sustained overload."
::= { lgpFlexConditionsWellKnown 4290 }
lgpCondId4294InletAirOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inlet air exceeds the maximum temperature threshold."
::= { lgpFlexConditionsWellKnown 4294 }
lgpCondId4295RectifierFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Rectifier failure - rectifier is off."
::= { lgpFlexConditionsWellKnown 4295 }
lgpCondId4296RectifierOperationInhibitExt OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The operation of the rectifier is inhibited by an external signal."
::= { lgpFlexConditionsWellKnown 4296 }
lgpCondId4297UPSOutputonInverter OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output power is supplied by the inverter."
::= { lgpFlexConditionsWellKnown 4297 }
lgpCondId4298UPSOutputonBypass OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output power is supplied by the bypass."
::= { lgpFlexConditionsWellKnown 4298 }
lgpCondId4299OutputLoadonMaintBypass OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output power is supplied by the maintenance bypass."
::= { lgpFlexConditionsWellKnown 4299 }
lgpCondId4300InternalCommunicationsFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The control has detected a communication failure of a component on
the internal communication bus."
::= { lgpFlexConditionsWellKnown 4300 }
lgpCondId4308DCBusGroundFaultPositive OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A ground fault has been detected on the positive DC Bus link."
::= { lgpFlexConditionsWellKnown 4308 }
lgpCondId4309DCBusGroundFaultNegative OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A ground fault has been detected on the negative DC Bus link."
::= { lgpFlexConditionsWellKnown 4309 }
lgpCondId4310EquipmentOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Equipment over temperature summary event."
::= { lgpFlexConditionsWellKnown 4310 }
lgpCondId4311SystemFanFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"System fan failure - one or more fans have failed."
::= { lgpFlexConditionsWellKnown 4311 }
lgpCondId4313PasswordChanged OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Password changed."
::= { lgpFlexConditionsWellKnown 4313 }
lgpCondId4314PowerSupplyFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Power supply failure."
::= { lgpFlexConditionsWellKnown 4314 }
lgpCondId4315OnGenerator OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A generator is supplying the power to the system."
::= { lgpFlexConditionsWellKnown 4315 }
lgpCondId4316AutoRestartInProgress OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Auto restart is in progress."
::= { lgpFlexConditionsWellKnown 4316 }
lgpCondId4317AutoRestartInhibitedExt OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Auto restart inhibited due to an external signal."
::= { lgpFlexConditionsWellKnown 4317 }
lgpCondId4320InitiatedTransfertoBypass OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User initiated manual transfer to bypass."
::= { lgpFlexConditionsWellKnown 4320 }
lgpCondId4321InitiatedTransfertoInverter OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User initiated manual transfer to inverter."
::= { lgpFlexConditionsWellKnown 4321 }
lgpCondId4322BatteryTestPassed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery test passed."
::= { lgpFlexConditionsWellKnown 4322 }
lgpCondId4323BatteryTestFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery test failed."
::= { lgpFlexConditionsWellKnown 4323 }
lgpCondId4324BatteryTestManuallyStopped OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery test was manually stopped prior to completion."
::= { lgpFlexConditionsWellKnown 4324 }
lgpCondId4325BackfeedBreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The backfeed breaker is in the open position."
::= { lgpFlexConditionsWellKnown 4325 }
lgpCondId4341VelocityAuthenticationFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Notification of a message rejected by Velocity due to an
authentication failure."
::= { lgpFlexConditionsWellKnown 4341 }
lgpCondId4360ReceptacleOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a receptacle over current condition."
::= { lgpFlexConditionsWellKnown 4360 }
lgpCondId4361ReceptacleUnderCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a receptacle under current condition."
::= { lgpFlexConditionsWellKnown 4361 }
lgpCondId4382SystemInputCurrentImbalance OBJECT-IDENTITY
STATUS current
DESCRIPTION
"System Input Currents are Imbalanced."
::= { lgpFlexConditionsWellKnown 4382 }
lgpCondId4383BypassStaticSwitchOffExtrnl OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Bypass static switch is off due to the state of an external signal."
::= { lgpFlexConditionsWellKnown 4383 }
lgpCondId4384BatteryEoDDisconnect OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery disconnect due to end-of-discharge."
::= { lgpFlexConditionsWellKnown 4384 }
lgpCondId4389SystemOutputFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A fault has been detected in the system output."
::= { lgpFlexConditionsWellKnown 4389 }
lgpCondId4390InverterOffExternal OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Inverter is off (operation is inhibited) due to external signal
state."
::= { lgpFlexConditionsWellKnown 4390 }
lgpCondId4391InverterStaticSwitchSCRShort OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a short across one or more inverter static
switch Silicon Controlled Rectifiers (SCR)."
::= { lgpFlexConditionsWellKnown 4391 }
lgpCondId4392TemperatureSensorError OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more temperature sensors cannot provide a valid temperature
reading (i.e. sensor failure, wiring failure, sense circuit
failure, etc)."
::= { lgpFlexConditionsWellKnown 4392 }
lgpCondId4406BranchOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module over current condition."
::= { lgpFlexConditionsWellKnown 4406 }
lgpCondId4407BranchUnderCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module under current condition."
::= { lgpFlexConditionsWellKnown 4407 }
lgpCondId4416BranchOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module over current condition."
::= { lgpFlexConditionsWellKnown 4416 }
lgpCondId4417BranchUnderCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module under current condition."
::= { lgpFlexConditionsWellKnown 4417 }
lgpCondId4421BranchFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more conditions indicate a Branch Receptacle Module failure
, service is required."
::= { lgpFlexConditionsWellKnown 4421 }
lgpCondId4436PDUOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module over current condition."
::= { lgpFlexConditionsWellKnown 4436 }
lgpCondId4437PDUUnderCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module under current condition."
::= { lgpFlexConditionsWellKnown 4437 }
lgpCondId4438SystemInternalTemperatureRise OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Excessive temperature rise internal to the system (i.e. difference
between the output versus input temperature is too large)."
::= { lgpFlexConditionsWellKnown 4438 }
lgpCondId4439AutomaticRestartFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Automatic restart failed."
::= { lgpFlexConditionsWellKnown 4439 }
lgpCondId4440FuseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A summary event indicating one or more fuse failures."
::= { lgpFlexConditionsWellKnown 4440 }
lgpCondId4441SystemControllerError OBJECT-IDENTITY
STATUS current
DESCRIPTION
"System controller internal error."
::= { lgpFlexConditionsWellKnown 4441 }
lgpCondId4442SystemBreakersOpenFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more breakers in the system failed to open."
::= { lgpFlexConditionsWellKnown 4442 }
lgpCondId4448PDUOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module over current condition."
::= { lgpFlexConditionsWellKnown 4448 }
lgpCondId4449PDUUnderCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module under current condition."
::= { lgpFlexConditionsWellKnown 4449 }
lgpCondId4468PDUOverCurrentL1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module over current condition on line 1."
::= { lgpFlexConditionsWellKnown 4468 }
lgpCondId4469PDUOverCurrentL2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module over current condition on line 2."
::= { lgpFlexConditionsWellKnown 4469 }
lgpCondId4470PDUOverCurrentL3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module over current condition on line 3."
::= { lgpFlexConditionsWellKnown 4470 }
lgpCondId4471PDUUnderCurrentL1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module under current condition on line 1."
::= { lgpFlexConditionsWellKnown 4471 }
lgpCondId4472PDUUnderCurrentL2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module under current condition on line 2."
::= { lgpFlexConditionsWellKnown 4472 }
lgpCondId4473PDUUnderCurrentL3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module under current condition on line 3."
::= { lgpFlexConditionsWellKnown 4473 }
lgpCondId4492ReceptaclePowerStateOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The receptacle power state changed to the ON state."
::= { lgpFlexConditionsWellKnown 4492 }
lgpCondId4493ReceptaclePowerStateOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The receptacle power state changed to the OFF state."
::= { lgpFlexConditionsWellKnown 4493 }
lgpCondId4494BranchBreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Branch Receptacle Module's input breaker is open."
::= { lgpFlexConditionsWellKnown 4494 }
lgpCondId4495DeviceConfigurationChange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Device Configuration Change."
::= { lgpFlexConditionsWellKnown 4495 }
lgpCondId4496BasicDisplayModuleRemoved OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Basic Display Module Removed."
::= { lgpFlexConditionsWellKnown 4496 }
lgpCondId4497BasicDisplayModuleDiscovered OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Basic Display Module Discovered."
::= { lgpFlexConditionsWellKnown 4497 }
lgpCondId4500PDUOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a power module over current condition."
::= { lgpFlexConditionsWellKnown 4500 }
lgpCondId4501PDUUnderCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a power module under current condition."
::= { lgpFlexConditionsWellKnown 4501 }
lgpCondId4502PDUFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more conditions indicate a power module failure, service is
required."
::= { lgpFlexConditionsWellKnown 4502 }
lgpCondId4503PDUCommunicationFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Internal communications failure with the Power Module."
::= { lgpFlexConditionsWellKnown 4503 }
lgpCondId4504BranchRemoved OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Branch Receptacle Module Removed."
::= { lgpFlexConditionsWellKnown 4504 }
lgpCondId4505BranchDiscovered OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Branch Receptacle Module Discovered."
::= { lgpFlexConditionsWellKnown 4505 }
lgpCondId4506BranchOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a Branch Receptacle Module over current
condition."
::= { lgpFlexConditionsWellKnown 4506 }
lgpCondId4507BranchCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a Branch Receptacle Module under current
condition."
::= { lgpFlexConditionsWellKnown 4507 }
lgpCondId4508ReceptacleLoadRemoved OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The receptacle's load stopped drawing power."
::= { lgpFlexConditionsWellKnown 4508 }
lgpCondId4509ReceptacleLoadAdded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The receptacle's load started to draw power."
::= { lgpFlexConditionsWellKnown 4509 }
lgpCondId4523ModuleRemoved OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Module Removed."
::= { lgpFlexConditionsWellKnown 4523 }
lgpCondId4524ModuleAdded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Module Added."
::= { lgpFlexConditionsWellKnown 4524 }
lgpCondId4550FirmwareUpdateRequired OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Module compatibility error requires a system firmware update to
resolve."
::= { lgpFlexConditionsWellKnown 4550 }
lgpCondId4551GenericTestEvent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A generic test event designed to evaluate system handling of
events."
::= { lgpFlexConditionsWellKnown 4551 }
lgpCondId4580OverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An over temperature condition was detected."
::= { lgpFlexConditionsWellKnown 4580 }
lgpCondId4581UnderTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An under temperature condition was detected."
::= { lgpFlexConditionsWellKnown 4581 }
lgpCondId4588OverRelativeHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An over relative humidity condition was detected."
::= { lgpFlexConditionsWellKnown 4588 }
lgpCondId4589UnderRelativeHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An under relative humidity condition was detected."
::= { lgpFlexConditionsWellKnown 4589 }
lgpCondId4601ExternalAirSensorAOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Ext Air Sensor A Temperature] has exceeded [External Air Over
Temp Threshold]."
::= { lgpFlexConditionsWellKnown 4601 }
lgpCondId4604ExternalAirSensorBOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Ext Air Sensor B Temperature] has exceeded [External Air Over
Temp Threshold]."
::= { lgpFlexConditionsWellKnown 4604 }
lgpCondId4608ExtAirSensorAUnderTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Ext Air Sensor A Temperature] has dropped below [Ext Air Under
Temp Threshold]."
::= { lgpFlexConditionsWellKnown 4608 }
lgpCondId4611ExtAirSensorBUnderTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Ext Air Sensor B Temperature] has dropped below [Ext Air Under
Temp Threshold]."
::= { lgpFlexConditionsWellKnown 4611 }
lgpCondId4615ExtDewPointOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"At least one dew point temperature reading ([Ext Air Sensor A Dew
Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded
[Ext Dew Point Over Temp Threshold]."
::= { lgpFlexConditionsWellKnown 4615 }
lgpCondId4618ExternalAirSensorAIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external air sensor A is disconnected or the signal is out of
range."
::= { lgpFlexConditionsWellKnown 4618 }
lgpCondId4621ExternalAirSensorBIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external air sensor B is disconnected or the signal is out of
range."
::= { lgpFlexConditionsWellKnown 4621 }
lgpCondId4626SupplyChilledWaterOverTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Supply Fluid Temperature] has exceeded [High Supply Fluid
Temperature Threshold]."
::= { lgpFlexConditionsWellKnown 4626 }
lgpCondId4629SupplyChilledWaterTempSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The supply chilled water temperature sensor is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 4629 }
lgpCondId4634SupplyRefrigerantOverTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Event that is activated when [Supply Refrigerant Temperature]
exceeds [Supply Refrig Over Temp Threshold]. The event is
deactivated when the temperature drops below the threshold."
::= { lgpFlexConditionsWellKnown 4634 }
lgpCondId4637SupplyRefrigerantUnderTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Supply Refrigerant Temperature] has dropped below a specified
threshold."
::= { lgpFlexConditionsWellKnown 4637 }
lgpCondId4640SupplyRefrigerantTempSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The supply refrigeramt temperature sensor is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 4640 }
lgpCondId4645SupplyFluidOverTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp
Threshold]."
::= { lgpFlexConditionsWellKnown 4645 }
lgpCondId4648SupplyFluidUnderTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Supply Fluid Temperature] has dropped below a specified threshold."
::= { lgpFlexConditionsWellKnown 4648 }
lgpCondId4651SupplyFluidTempSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The supply fluid temperature sensor is disconnected or the signal
is out of range."
::= { lgpFlexConditionsWellKnown 4651 }
lgpCondId4656Pump1LossofFlow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Loss of flow is detected in pump 1. The loss of flow condition
occurs when no differential pressure is detected across the pump."
::= { lgpFlexConditionsWellKnown 4656 }
lgpCondId4659Pump2LossofFlow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Loss of flow is detected in pump 2. The loss of flow condition
occurs when no differential pressure is detected across the pump."
::= { lgpFlexConditionsWellKnown 4659 }
lgpCondId4662PumpShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Pumps have short cycled. A short cycle is defined as turning on
and off a number of times over a set time period."
::= { lgpFlexConditionsWellKnown 4662 }
lgpCondId4669Compressor1AHighHeadPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor 1A high head pressure."
::= { lgpFlexConditionsWellKnown 4669 }
lgpCondId4672Compressor1BHighHeadPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor 1B high head pressure."
::= { lgpFlexConditionsWellKnown 4672 }
lgpCondId4675Compressor2AHighHeadPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor 2A high head pressure."
::= { lgpFlexConditionsWellKnown 4675 }
lgpCondId4678Compressor2BHighHeadPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor 2B high head pressure."
::= { lgpFlexConditionsWellKnown 4678 }
lgpCondId4681Compressor1AShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor 1A short cycle. A short cycle is defined as turning on
and off a number of times over a set time period."
::= { lgpFlexConditionsWellKnown 4681 }
lgpCondId4684Compressor1BShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor 1B short cycle. A short cycle is defined as turning on
and off a number of times over a set time period."
::= { lgpFlexConditionsWellKnown 4684 }
lgpCondId4687Compressor2AShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor 2A short cycle. A short cycle is defined as turning on
and off a number of times over a set time period."
::= { lgpFlexConditionsWellKnown 4687 }
lgpCondId4690Compressor2BShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor 2B short cycle. A short cycle is defined as turning on
and off a number of times over a set time period."
::= { lgpFlexConditionsWellKnown 4690 }
lgpCondId4693Tandem1LowSuctionPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"'Tandem compressors' 1 low suction pressure."
::= { lgpFlexConditionsWellKnown 4693 }
lgpCondId4696Tandem2LowSuctionPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"'Tandem compressors' 2 low suction pressure."
::= { lgpFlexConditionsWellKnown 4696 }
lgpCondId4703ChilledWaterControlValvePosition OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Chilled water valve out of position. Chilled water control valve
position does not match expected value."
::= { lgpFlexConditionsWellKnown 4703 }
lgpCondId4711SystemCondensationDetected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"System condensation detected."
::= { lgpFlexConditionsWellKnown 4711 }
lgpCondId4714ShutdownLossOfPower OBJECT-IDENTITY
STATUS current
DESCRIPTION
"System lost power. This event becomes active when the unit is
powered on following an unexpected loss of power."
::= { lgpFlexConditionsWellKnown 4714 }
lgpCondId4720SmokeDetected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Smoke detected."
::= { lgpFlexConditionsWellKnown 4720 }
lgpCondId4723WaterUnderFloor OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Water under the floor is detected."
::= { lgpFlexConditionsWellKnown 4723 }
lgpCondId4726ServiceRequired OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Unit requires servicing."
::= { lgpFlexConditionsWellKnown 4726 }
lgpCondId4729FanIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more fans are not operating within their operational
parameters."
::= { lgpFlexConditionsWellKnown 4729 }
lgpCondId4732ReceptacleLoadDropped OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The receptacle's load is not drawing power."
::= { lgpFlexConditionsWellKnown 4732 }
lgpCondId4740BatteryAutomaticTestInhibited OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Automatic (scheduled) battery tests are inhibited."
::= { lgpFlexConditionsWellKnown 4740 }
lgpCondId4741BatterySelfTest OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery self test is in progress."
::= { lgpFlexConditionsWellKnown 4741 }
lgpCondId4742BatteryLowShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery disconnect due to end-of-discharge."
::= { lgpFlexConditionsWellKnown 4742 }
lgpCondId4747EquipmentTemperatureSensorFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more temperature sensors report a temperature outside of
the range of expected operation."
::= { lgpFlexConditionsWellKnown 4747 }
lgpCondId4749SystemFanFailureRedundant OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Redundant system fan failure."
::= { lgpFlexConditionsWellKnown 4749 }
lgpCondId4750MultipleFanFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Multiple fan failure."
::= { lgpFlexConditionsWellKnown 4750 }
lgpCondId4753MainControllerFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A Main Controller fault has been detected."
::= { lgpFlexConditionsWellKnown 4753 }
lgpCondId4754SystemBreakersCloseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more breakers in the system failed to close."
::= { lgpFlexConditionsWellKnown 4754 }
lgpCondId4755InputFilterCycleLock OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The input filter disconnect is open due to exceeding the maximum
number of cycles."
::= { lgpFlexConditionsWellKnown 4755 }
lgpCondId4756ServiceCodeActive OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Service code is running."
::= { lgpFlexConditionsWellKnown 4756 }
lgpCondId4757LBSActive OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Load Bus Sync option is active."
::= { lgpFlexConditionsWellKnown 4757 }
lgpCondId4758LBSInhibited OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that conditions to perform Load Bus Sync
are not satisfied."
::= { lgpFlexConditionsWellKnown 4758 }
lgpCondId4759LeadingPowerFactor OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The leading output Power Factor has fallen below a specified value."
::= { lgpFlexConditionsWellKnown 4759 }
lgpCondId4760ControlsResetRequired OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A controls reset is required due to one or more critical settings
changing."
::= { lgpFlexConditionsWellKnown 4760 }
lgpCondId4823ParallelCommWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Parallel communication bus warning."
::= { lgpFlexConditionsWellKnown 4823 }
lgpCondId4824SystemCommFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Failure of a device on the multi-module system communication bus."
::= { lgpFlexConditionsWellKnown 4824 }
lgpCondId4825LossofRedundancy OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The multi-module collection doesn't have enough modules to satisfy
the redundancy configuration."
::= { lgpFlexConditionsWellKnown 4825 }
lgpCondId4826BPSSStartupInhibit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Bypass Static Switch startup is inhibited."
::= { lgpFlexConditionsWellKnown 4826 }
lgpCondId4827MMSTransferInhibit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The critical load can not be manually transferred from inverter to
bypass."
::= { lgpFlexConditionsWellKnown 4827 }
lgpCondId4828MMSRetransferInhibit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The critical load can not be manually retransferred from bypass to
inverter."
::= { lgpFlexConditionsWellKnown 4828 }
lgpCondId4830MMSLossofSyncPulse OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Multi-module system loss of sync pulse."
::= { lgpFlexConditionsWellKnown 4830 }
lgpCondId4831MMSOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Multi-module system overload."
::= { lgpFlexConditionsWellKnown 4831 }
lgpCondId4834MMSOnBattery OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The multi-module system is on battery."
::= { lgpFlexConditionsWellKnown 4834 }
lgpCondId4835MMSLowBatteryWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Multi-module system low battery warning."
::= { lgpFlexConditionsWellKnown 4835 }
lgpCondId4906LowAmbientTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low ambient temperature condition."
::= { lgpFlexConditionsWellKnown 4906 }
lgpCondId4907HighAmbientTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high ambient temperature condition."
::= { lgpFlexConditionsWellKnown 4907 }
lgpCondId4908LowOverallVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low battery string overall voltage
condition."
::= { lgpFlexConditionsWellKnown 4908 }
lgpCondId4909HighOverallVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high battery string overall voltage
condition."
::= { lgpFlexConditionsWellKnown 4909 }
lgpCondId4910HighBatteryStringCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high battery string current condition."
::= { lgpFlexConditionsWellKnown 4910 }
lgpCondId4911LowBatteryStringFloatCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low battery string float current
condition."
::= { lgpFlexConditionsWellKnown 4911 }
lgpCondId4912HighBatteryStringFloatCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high battery string float current
condition."
::= { lgpFlexConditionsWellKnown 4912 }
lgpCondId4913HighBatteryStringRippleCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high battery string ripple current
condition."
::= { lgpFlexConditionsWellKnown 4913 }
lgpCondId4914BatteryStringDischargeDetected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a battery string discharge condition."
::= { lgpFlexConditionsWellKnown 4914 }
lgpCondId4915MaximumDischargeTimeExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an excessive discharge time condition."
::= { lgpFlexConditionsWellKnown 4915 }
lgpCondId4916DischargeLowOverallVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low battery string overall voltage
condition during a discharge."
::= { lgpFlexConditionsWellKnown 4916 }
lgpCondId4917DischargeLowCellVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low cell voltage condition during a
discharge."
::= { lgpFlexConditionsWellKnown 4917 }
lgpCondId4918DischargeHighBatteryStringCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high battery string current condition
during a discharge."
::= { lgpFlexConditionsWellKnown 4918 }
lgpCondId4919ExcessiveCelltoCellTemperatureDeviation OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an excessive cell to cell temperature
deviation condition."
::= { lgpFlexConditionsWellKnown 4919 }
lgpCondId4920ExcessiveCelltoAmbientTemperatureDeviation OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an excessive cell to ambient temperature
deviation condition."
::= { lgpFlexConditionsWellKnown 4920 }
lgpCondId4964LowCellVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low cell voltage condition."
::= { lgpFlexConditionsWellKnown 4964 }
lgpCondId4965HighCellVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high cell voltage condition."
::= { lgpFlexConditionsWellKnown 4965 }
lgpCondId4966LowCellTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low cell temperature condition."
::= { lgpFlexConditionsWellKnown 4966 }
lgpCondId4967HighCellTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high cell temperature condition."
::= { lgpFlexConditionsWellKnown 4967 }
lgpCondId4968LowInternalResistance OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low internal resistance condition."
::= { lgpFlexConditionsWellKnown 4968 }
lgpCondId4969HighInternalResistance OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high internal resistance condition."
::= { lgpFlexConditionsWellKnown 4969 }
lgpCondId4970HighIntercellResistance OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high intercell resistance condition."
::= { lgpFlexConditionsWellKnown 4970 }
lgpCondId4978IntertierResistanceHigh OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high intertier resistance condition."
::= { lgpFlexConditionsWellKnown 4978 }
lgpCondId4980SupplyChilledWaterLossofFlow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Supply chilled water or glycol flow is too low."
::= { lgpFlexConditionsWellKnown 4980 }
lgpCondId4983SupplyRefrigOverTempBand1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Supply Refrigerant Temperature] is above the upper threshold
specified by [Supply Refrig Temp Band 1]."
::= { lgpFlexConditionsWellKnown 4983 }
lgpCondId4986SupplyRefrigUnderTempBand1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Supply Refrigerant Temperature] is below the lower threshold
specified by [Supply Refrig Temp Band 1]."
::= { lgpFlexConditionsWellKnown 4986 }
lgpCondId4990SupplyRefrigOverTempBand2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Supply Refrigerant Temperature] is above the upper threshold
specified by [Supply Refrig Temp Band 2]."
::= { lgpFlexConditionsWellKnown 4990 }
lgpCondId4993SupplyRefrigUnderTempBand2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Supply Refrigerant Temperature] is below the lower threshold
specified by [Supply Refrig Temp Band 2]."
::= { lgpFlexConditionsWellKnown 4993 }
lgpCondId4996Inverter1ShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Inverter for pump 1 has short cycled and is temporarily locked out
from further operation to protect from thermal overload. A short
cycle is defined as powering on and off a number of times over a
set time period."
::= { lgpFlexConditionsWellKnown 4996 }
lgpCondId4999Inverter2ShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Inverter for pump 2 has short cycled and is temporarily locked out
from further operation to protect from thermal overload. A short
cycle is defined as powering on and off a number of times over a
set time period."
::= { lgpFlexConditionsWellKnown 4999 }
lgpCondId5015SupplyAirOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Supply Air Temperature] has exceeded [High Supply Air Temperature
Threshold]."
::= { lgpFlexConditionsWellKnown 5015 }
lgpCondId5019SupplyAirUnderTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Supply Air Temperature] has dropped below [Low Supply Air
Temperature Threshold]."
::= { lgpFlexConditionsWellKnown 5019 }
lgpCondId5023ReturnAirOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Return Air Temperature] has exceeded [High Return Air Temperature
Threshold]."
::= { lgpFlexConditionsWellKnown 5023 }
lgpCondId5026SupplyAirSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The air sensor at the outlet of the unit is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 5026 }
lgpCondId5034HighReturnHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Return Humidity] has exceeded [High Return Humidity Threshold]."
::= { lgpFlexConditionsWellKnown 5034 }
lgpCondId5036LowReturnHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Return Humidity] has dropped below [Low Return Humidity
Threshold]."
::= { lgpFlexConditionsWellKnown 5036 }
lgpCondId5037HumidifierHoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Operating hours for the humidifier have exceeded the threshold."
::= { lgpFlexConditionsWellKnown 5037 }
lgpCondId5038DehumidifierHoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Operating hours for the dehumidifier have exceeded the threshold."
::= { lgpFlexConditionsWellKnown 5038 }
lgpCondId5039HumidifierUnderCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The electrical current to the humidifier has dropped below its
lower threshold."
::= { lgpFlexConditionsWellKnown 5039 }
lgpCondId5040HumidifierOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The electrical current to the humidifier has exceeded its upper
threshold."
::= { lgpFlexConditionsWellKnown 5040 }
lgpCondId5041HumidifierLowWater OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The water level in the humidifier has dropped below its threshold."
::= { lgpFlexConditionsWellKnown 5041 }
lgpCondId5042HumidifierCylinderWorn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Humidifier cylinder is not operating properly and needs to be
replaced."
::= { lgpFlexConditionsWellKnown 5042 }
lgpCondId5043HumidifierIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Humidifier issue detected, causing it to be locked out."
::= { lgpFlexConditionsWellKnown 5043 }
lgpCondId5044ExtHumidifierLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The humidifier is shut down and disabled by an external input
signal."
::= { lgpFlexConditionsWellKnown 5044 }
lgpCondId5045HumidifierControlBoardNotDetected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Humidifier control board is required to be connected, but no
signal is detected."
::= { lgpFlexConditionsWellKnown 5045 }
lgpCondId5046ReturnHumidityOutOfProportionalBand OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Return Humidity] has exceeded the upper limit of
[Dehumidification Proportional Band], or has dropped below the
lower limit of [Humidification Proportional Band] ], for an
extended period of time."
::= { lgpFlexConditionsWellKnown 5046 }
lgpCondId5053LossofAirFlow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"No air flow through the unit due to failure of all fans."
::= { lgpFlexConditionsWellKnown 5053 }
lgpCondId5054FanHoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Operating hours for the unit blower fan have exceeded the
threshold."
::= { lgpFlexConditionsWellKnown 5054 }
lgpCondId5055TopFanIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The top fan is not operating within its normal parameters."
::= { lgpFlexConditionsWellKnown 5055 }
lgpCondId5056BottomFanIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The bottom fan is not operating within its normal parameters."
::= { lgpFlexConditionsWellKnown 5056 }
lgpCondId5060RemoteSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Remote sensor is disconnected or the signal is out of range."
::= { lgpFlexConditionsWellKnown 5060 }
lgpCondId5062Compressor1LowSuctionPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor 1 low suction pressure."
::= { lgpFlexConditionsWellKnown 5062 }
lgpCondId5063Compressor1HoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Operating hours for compressor 1 have exceeded the threshold."
::= { lgpFlexConditionsWellKnown 5063 }
lgpCondId5064DigScrollComp1TempSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Digital scroll compressor 1 temperature sensor is disconnected or
the signal is out of range."
::= { lgpFlexConditionsWellKnown 5064 }
lgpCondId5065DigScrollComp1OverTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Digital scroll compressor 1 shut off because its head temperature
has exceeded the upper threshold."
::= { lgpFlexConditionsWellKnown 5065 }
lgpCondId5066Compressor1LowPressureTransducerIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor 1 low pressure transducer is disconnected or the signal
is out of range."
::= { lgpFlexConditionsWellKnown 5066 }
lgpCondId5067ExtCompressorLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The compressor is shut down and disabled by an external input
signal."
::= { lgpFlexConditionsWellKnown 5067 }
lgpCondId5068ReheaterOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature of the reheater has exceeded its threshold."
::= { lgpFlexConditionsWellKnown 5068 }
lgpCondId5069ElectricReheater1HoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Operating hours for electric reheater 1 have exceeded the
threshold."
::= { lgpFlexConditionsWellKnown 5069 }
lgpCondId5070ExtReheatLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The reheater is shut down and disabled by an external input signal."
::= { lgpFlexConditionsWellKnown 5070 }
lgpCondId5071Condenser1Issue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser 1 is not operating within its normal parameters."
::= { lgpFlexConditionsWellKnown 5071 }
lgpCondId5072CondenserVFDIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condenser fan Variable Frequency Drive is offline."
::= { lgpFlexConditionsWellKnown 5072 }
lgpCondId5073CondenserTVSSIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condenser Transient Voltage Surge Suppressor or Surge
Protection Device has failed."
::= { lgpFlexConditionsWellKnown 5073 }
lgpCondId5104ExtOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A temperature has exceeded its threshold, as indicated by an
external input signal."
::= { lgpFlexConditionsWellKnown 5104 }
lgpCondId5105ExtLossofFlow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Loss of flow is detected, as indicated by an external input signal."
::= { lgpFlexConditionsWellKnown 5105 }
lgpCondId5106ExtCondenserPumpHighWater OBJECT-IDENTITY
STATUS current
DESCRIPTION
"High water is detected in the condensate pump by the auxiliary
float, as indicated by an external input signal."
::= { lgpFlexConditionsWellKnown 5106 }
lgpCondId5107ExtStandbyGlycolPumpOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The standby glycol pump is on, as indicated by an external input
signal."
::= { lgpFlexConditionsWellKnown 5107 }
lgpCondId5108ExternalFireDetected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Fire detected, as indicated by an external input signal."
::= { lgpFlexConditionsWellKnown 5108 }
lgpCondId5109UnitOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Unit was turned on."
::= { lgpFlexConditionsWellKnown 5109 }
lgpCondId5110UnitOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Unit was turned off."
::= { lgpFlexConditionsWellKnown 5110 }
lgpCondId5111UnitStandby OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Unit was placed in standby mode."
::= { lgpFlexConditionsWellKnown 5111 }
lgpCondId5112UnitPartialShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An event has occurred requiring some system components to be
shutdown and disabled."
::= { lgpFlexConditionsWellKnown 5112 }
lgpCondId5113UnitShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An event has occurred requiring the unit to be shutdown and
disabled to prevent damage to the system."
::= { lgpFlexConditionsWellKnown 5113 }
lgpCondId5114WaterLeakageDetectorSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The water leakage detector sensor is disconnected or the signal is
out of range."
::= { lgpFlexConditionsWellKnown 5114 }
lgpCondId5115BMSCommunicationsTimeout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Building Management System (or external monitoring system) has not
communicated with the system within the expected timeframe."
::= { lgpFlexConditionsWellKnown 5115 }
lgpCondId5116MaintenanceDue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The calculated maintenance date has been reached."
::= { lgpFlexConditionsWellKnown 5116 }
lgpCondId5117MaintenanceCompleted OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Maintenance has been completed on the unit."
::= { lgpFlexConditionsWellKnown 5117 }
lgpCondId5118CloggedAirFilter OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Air filter is dirty and needs to be (cleaned or) replaced."
::= { lgpFlexConditionsWellKnown 5118 }
lgpCondId5119RAMBatteryIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"RAM or RAM backup battery is not operating correctly."
::= { lgpFlexConditionsWellKnown 5119 }
lgpCondId5120MasterUnitCommunicationLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Communication with master unit has been lost."
::= { lgpFlexConditionsWellKnown 5120 }
lgpCondId5121HighPowerShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Supply to high power components has been shutdown."
::= { lgpFlexConditionsWellKnown 5121 }
lgpCondId5126DigScrollComp2OverTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Digital scroll compressor 2 shut off because its head temperature
has exceeded the upper threshold."
::= { lgpFlexConditionsWellKnown 5126 }
lgpCondId5144OutputOfUf OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output frequency has exceeded a specified range for a
specified period of time."
::= { lgpFlexConditionsWellKnown 5144 }
lgpCondId5145MMSModuleAlarmActive OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Active alarm or fault of any module in a multi-module system."
::= { lgpFlexConditionsWellKnown 5145 }
lgpCondId5146CompressorPumpDownIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Unable to pump down suction-side pressure during compressor
shutdown."
::= { lgpFlexConditionsWellKnown 5146 }
lgpCondId5147ReturnAirSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The air sensor at the inlet of the unit is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 5147 }
lgpCondId5148CompressorHighPressureTransducerIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor high pressure transducer is disconnected or the signal
is out of range."
::= { lgpFlexConditionsWellKnown 5148 }
lgpCondId5149BatteryNotQualified OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS battery voltage is not qualified. This event will be
detected even in the absence of battery disconnect or when it is
open."
::= { lgpFlexConditionsWellKnown 5149 }
lgpCondId5150BatteryTerminalsReversed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The measured battery voltage is a negative value due to reverse
battery terminal connections."
::= { lgpFlexConditionsWellKnown 5150 }
lgpCondId5151BatteryConverterFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery converter failure. This is a summary event caused by one
or more power sub-modules in a UPS module."
::= { lgpFlexConditionsWellKnown 5151 }
lgpCondId5152InverterSCROpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an open across one or more inverter static
switch Silicon Controlled Rectifiers."
::= { lgpFlexConditionsWellKnown 5152 }
lgpCondId5153LoadSharingFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Difference between any phase inverter current of unit and the
relevant average output current of parallel system is more than a
specific percent of nominal current."
::= { lgpFlexConditionsWellKnown 5153 }
lgpCondId5154DCBusAbnormal OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected an abnormal DC Bus Voltage."
::= { lgpFlexConditionsWellKnown 5154 }
lgpCondId5155MainsInputNeutralLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Loss of neutral in the input source is detected."
::= { lgpFlexConditionsWellKnown 5155 }
lgpCondId5156LoadImpactTransfer OBJECT-IDENTITY
STATUS current
DESCRIPTION
"On bypass as result of load impact."
::= { lgpFlexConditionsWellKnown 5156 }
lgpCondId5157UserOperationInvalid OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User attempted an invalid operation."
::= { lgpFlexConditionsWellKnown 5157 }
lgpCondId5158PowerSubModuleFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more failures detected in power module, inverter or
rectifier."
::= { lgpFlexConditionsWellKnown 5158 }
lgpCondId5178OutputOvervoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more of the output phase voltages has exceeded the limit."
::= { lgpFlexConditionsWellKnown 5178 }
lgpCondId5179OutputUndervoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more of the output phase voltages has dropped below the
limit."
::= { lgpFlexConditionsWellKnown 5179 }
lgpCondId5180OutputOvercurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more of the phase currents has exceeded the limit."
::= { lgpFlexConditionsWellKnown 5180 }
lgpCondId5181NeutralOvercurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system's neutral current has exceeded the limit."
::= { lgpFlexConditionsWellKnown 5181 }
lgpCondId5182GroundOvercurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"System ground current has exceeded the limit."
::= { lgpFlexConditionsWellKnown 5182 }
lgpCondId5183OutputVoltageTHD OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Total Harmonic Distortion of the voltage on one or more of the
output phases has exceeded the limit."
::= { lgpFlexConditionsWellKnown 5183 }
lgpCondId5184OutputFrequencyError OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output frequency is outside a specified range."
::= { lgpFlexConditionsWellKnown 5184 }
lgpCondId5185TransformerOvertemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Indicates a unit transformer overtemperature condition."
::= { lgpFlexConditionsWellKnown 5185 }
lgpCondId5212PanelSummaryStatus OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The status for the panel. Detects and annunciates upon occurrence
of any branch or panelboard main breaker active event."
::= { lgpFlexConditionsWellKnown 5212 }
lgpCondId5213PanelOvervoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more of the phase voltages of this panel has exceeded the
limit."
::= { lgpFlexConditionsWellKnown 5213 }
lgpCondId5214PanelUndervoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more of the phase voltages of this panel is less than the
limit."
::= { lgpFlexConditionsWellKnown 5214 }
lgpCondId5215PanelOvercurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more of the phase currents of this panel has exceeded the
limit."
::= { lgpFlexConditionsWellKnown 5215 }
lgpCondId5216PanelNeutralOvercurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Neutral current of this panel has exceeded the limit."
::= { lgpFlexConditionsWellKnown 5216 }
lgpCondId5217PanelGroundOvercurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Ground current of this panel has exceeded the limit."
::= { lgpFlexConditionsWellKnown 5217 }
lgpCondId5226BranchOvercurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The current in one or more phases of this branch exceeds the limit."
::= { lgpFlexConditionsWellKnown 5226 }
lgpCondId5227BranchUndercurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The current in one or more phases of this branch is less than the
limit."
::= { lgpFlexConditionsWellKnown 5227 }
lgpCondId5245SubfeedPhaseOvercurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more of the phase currents in this subfeed has exceeded the
limit."
::= { lgpFlexConditionsWellKnown 5245 }
lgpCondId5246SubfeedNeutralOvercurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Neutral current in this subfeed has exceeded the limit."
::= { lgpFlexConditionsWellKnown 5246 }
lgpCondId5247SubfeedGroundOvercurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Ground current of this subfeed has exceeded the limit."
::= { lgpFlexConditionsWellKnown 5247 }
lgpCondId5249EventState OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The present state of this digital event input."
::= { lgpFlexConditionsWellKnown 5249 }
lgpCondId5263CompressorNotStopping OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor commanded to stop, but continues to run."
::= { lgpFlexConditionsWellKnown 5263 }
lgpCondId5269CompressorHoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Compressor Hours] has exceeded [Compressor Hours Threshold]."
::= { lgpFlexConditionsWellKnown 5269 }
lgpCondId5270CompressorHighHeadPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor is shut down due to high head pressure."
::= { lgpFlexConditionsWellKnown 5270 }
lgpCondId5271CompressorLowSuctionPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor is shut down due to low suction pressure."
::= { lgpFlexConditionsWellKnown 5271 }
lgpCondId5272CompressorThermalOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor is shut down due to thermal overload."
::= { lgpFlexConditionsWellKnown 5272 }
lgpCondId5273CompressorLowOilPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor low oil pressure."
::= { lgpFlexConditionsWellKnown 5273 }
lgpCondId5274CompressorHeadPressureOverThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor head pressure has exceeded an upper threshold."
::= { lgpFlexConditionsWellKnown 5274 }
lgpCondId5275CompressorLossofDifferentialPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor is shut down due to low differential pressure."
::= { lgpFlexConditionsWellKnown 5275 }
lgpCondId5277CondenserFanIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser fan is not operating within its operational parameters."
::= { lgpFlexConditionsWellKnown 5277 }
lgpCondId5278LowCondenserRefrigerantPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Refrigerant pressure in condenser coil is too low."
::= { lgpFlexConditionsWellKnown 5278 }
lgpCondId5280LowFluidPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Fluid Pressure] has dropped below a specified threshold."
::= { lgpFlexConditionsWellKnown 5280 }
lgpCondId5293ReturnFluidOverTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Return Fluid Temperature] has exceeded a specified threshold."
::= { lgpFlexConditionsWellKnown 5293 }
lgpCondId5294ReturnFluidUnderTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Return Fluid Temperature] has dropped below a specified threshold."
::= { lgpFlexConditionsWellKnown 5294 }
lgpCondId5295ReturnFluidTempSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The return fluid temperature sensor is disconnected or the signal
is out of range."
::= { lgpFlexConditionsWellKnown 5295 }
lgpCondId5296TeamworkReturnFluidTempSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The return fluid temperature sensors for all Teamwork units are
disconnected or the signals are out of range."
::= { lgpFlexConditionsWellKnown 5296 }
lgpCondId5297AllPumpsLossofFlow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"System is shut down due to loss of flow in all available pumps."
::= { lgpFlexConditionsWellKnown 5297 }
lgpCondId5300PumpHoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Pump Hours] has exceeded [Pump Hours Threshold]."
::= { lgpFlexConditionsWellKnown 5300 }
lgpCondId5306FreeCoolingValveHoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours
Threshold]."
::= { lgpFlexConditionsWellKnown 5306 }
lgpCondId5308EvaporatorInletTempSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The evaporator inlet temperature sensor is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 5308 }
lgpCondId5309TeamworkEvaporatorInletTempSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The evaporator inlet temperature sensors for all Teamwork units
are disconnected or the signals are out of range."
::= { lgpFlexConditionsWellKnown 5309 }
lgpCondId5310EvaporatorFluidFreezeAutoReset OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Evaporator outlet fluid temperature has dropped below the freeze
threshold. Evaporator has been shut down, but will restart when
the temperature rises above the threshold."
::= { lgpFlexConditionsWellKnown 5310 }
lgpCondId5311EvaporatorFluidFreezeManualResetRequired OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Evaporator outlet fluid temperature has dropped below the freeze
threshold. Evaporator has been shut down and requires a manual
reset."
::= { lgpFlexConditionsWellKnown 5311 }
lgpCondId5315SubgroupEventOccurredDuringCommunicationLoss OBJECT-IDENTITY
STATUS current
DESCRIPTION
"While subgroup unit communication was lost, an event occurred on
the subgroup unit. Please check subgroup unit event log."
::= { lgpFlexConditionsWellKnown 5315 }
lgpCondId5335ReturnAirUnderTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Return Air Temperature] has dropped below [Low Return Air
Temperature Threshold]."
::= { lgpFlexConditionsWellKnown 5335 }
lgpCondId5349ExtAirSensorAHighHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High
Humidity Threshold]."
::= { lgpFlexConditionsWellKnown 5349 }
lgpCondId5351ExtAirSensorALowHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A
Low Humidity Threshold]."
::= { lgpFlexConditionsWellKnown 5351 }
lgpCondId5352CompressorShortCycle OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor short cycle. A short cycle is defined as turning on and
off a number of times over a set time period."
::= { lgpFlexConditionsWellKnown 5352 }
lgpCondId5354DigScrollCompDischargeTempSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Digital scroll compressor discharge temperature sensor is
disconnected or the signal is out of range."
::= { lgpFlexConditionsWellKnown 5354 }
lgpCondId5355DigScrollCompOverTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Digital scroll compressor is shut down due to head temperature
exceeding an upper threshold."
::= { lgpFlexConditionsWellKnown 5355 }
lgpCondId5361ExtFreeCoolingLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Free cooling is disabled by an external input signal."
::= { lgpFlexConditionsWellKnown 5361 }
lgpCondId5362FreeCoolingTempSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The free cooling fluid temperature sensor is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 5362 }
lgpCondId5365HotWaterHotGasValveHoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot
Gas Valve Hours Threshold]."
::= { lgpFlexConditionsWellKnown 5365 }
lgpCondId5368ElectricReheaterHoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Electric Reheater Hours] has exceeded [Electric Reheaters Hours
Threshold]."
::= { lgpFlexConditionsWellKnown 5368 }
lgpCondId5376MainFanOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Main fan is shut down due to thermal overload."
::= { lgpFlexConditionsWellKnown 5376 }
lgpCondId5377Condenser OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser is not operating within its operational parameters."
::= { lgpFlexConditionsWellKnown 5377 }
lgpCondId5415ExtLossofAirBlower OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Loss of air blower is detected, as indicated by an external input
signal."
::= { lgpFlexConditionsWellKnown 5415 }
lgpCondId5416ExtStandbyUnitOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Standby unit is on, as indicated by an external input signal."
::= { lgpFlexConditionsWellKnown 5416 }
lgpCondId5417DigitalOutputBoardNotDetected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Digital output board is required to be connected, but no signal is
detected."
::= { lgpFlexConditionsWellKnown 5417 }
lgpCondId5418UnitCodeMissing OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Unit code has not been entered and saved."
::= { lgpFlexConditionsWellKnown 5418 }
lgpCondId5419UnitCommunicationLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Master has lost communication with one or more networked units."
::= { lgpFlexConditionsWellKnown 5419 }
lgpCondId5422OvertemperaturePowerOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Power turned off because equipment over temperature limit."
::= { lgpFlexConditionsWellKnown 5422 }
lgpCondId5423TooManySensors OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The number of sensors connected to the PDU exceeds the allowable
limit."
::= { lgpFlexConditionsWellKnown 5423 }
lgpCondId5432TransformerOvertemperaturePowerOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output power shutdown due to high transformer temperature."
::= { lgpFlexConditionsWellKnown 5432 }
lgpCondId5433TransformerOvertemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Transformer temperature has exceeded the limit."
::= { lgpFlexConditionsWellKnown 5433 }
lgpCondId5434TransformerTemperatureSensorFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Transformer temperature sensor has failed."
::= { lgpFlexConditionsWellKnown 5434 }
lgpCondId5436LowAmbientTemperatureProbeTwo OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low ambient temperature condition on
temperature probe 2."
::= { lgpFlexConditionsWellKnown 5436 }
lgpCondId5437HighAmbientTemperatureProbeTwo OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a high ambient temperature condition on
temperature probe 2."
::= { lgpFlexConditionsWellKnown 5437 }
lgpCondId5438ThermalRunawayDetected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a thermal runaway condition."
::= { lgpFlexConditionsWellKnown 5438 }
lgpCondId5439BatteryStringEqualize OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a battery string equalize condition."
::= { lgpFlexConditionsWellKnown 5439 }
lgpCondId5440BatteryStringOffline OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the battery string is offline."
::= { lgpFlexConditionsWellKnown 5440 }
lgpCondId5442DischargeLowCellVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a low cell voltage condition during a
discharge."
::= { lgpFlexConditionsWellKnown 5442 }
lgpCondId5447MMSPowerSharing OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A module is not sharing power with the other modules in a multi
-module system."
::= { lgpFlexConditionsWellKnown 5447 }
lgpCondId5453ModuleInStandbyIntelligentParalleling OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Module is placed into standby operation per Intelligent
Paralleling."
::= { lgpFlexConditionsWellKnown 5453 }
lgpCondId5456ECOModeActive OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Conditions for Activation or Automatic Reactivation have been
satisfied."
::= { lgpFlexConditionsWellKnown 5456 }
lgpCondId5457ECOModeSuspended OBJECT-IDENTITY
STATUS current
DESCRIPTION
"ECO Mode session is suspended."
::= { lgpFlexConditionsWellKnown 5457 }
lgpCondId5458ExcessECOSuspends OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Number of automatic suspensions has exceeded the ECO Mode -
Maximum Auto Suspensions setting."
::= { lgpFlexConditionsWellKnown 5458 }
lgpCondId5471DoorOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An open door was detected."
::= { lgpFlexConditionsWellKnown 5471 }
lgpCondId5472DoorSensorDisconnected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Door sensor disconnect detected."
::= { lgpFlexConditionsWellKnown 5472 }
lgpCondId5479ContactClosureOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An open circuit was detected."
::= { lgpFlexConditionsWellKnown 5479 }
lgpCondId5480ContactClosureClosed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A closed circuit was detected."
::= { lgpFlexConditionsWellKnown 5480 }
lgpCondId5492ExtSystemCondensationDetected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"External system condensation detected."
::= { lgpFlexConditionsWellKnown 5492 }
lgpCondId5495ExtFanIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more fans are not operating within their operational
parameters."
::= { lgpFlexConditionsWellKnown 5495 }
lgpCondId5500ExtRemoteShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Unit is shut down by a remote signal."
::= { lgpFlexConditionsWellKnown 5500 }
lgpCondId5505HotAisleTempOutofRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The air temperature in the Hot aisle is either above [Hot Aisle
Over Temp Threshold] or below [Hot Aisle Under Temp Threshold]."
::= { lgpFlexConditionsWellKnown 5505 }
lgpCondId5508ColdAisleTempOutofRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The air temperature in the cold aisle is either above [Cold Aisle
Over Temp Threshold] or below [Cold Aisle Under Temp Threshold]."
::= { lgpFlexConditionsWellKnown 5508 }
lgpCondId5512RemoteShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Unit is shut down by a remote signal."
::= { lgpFlexConditionsWellKnown 5512 }
lgpCondId5513CompressorCapacityReduced OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor capacity has been reduced."
::= { lgpFlexConditionsWellKnown 5513 }
lgpCondId5514CompressorLowPressureTransducerIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor low pressure transducer is disconnected or the signal
is out of range."
::= { lgpFlexConditionsWellKnown 5514 }
lgpCondId5524PDUNeutralOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a neutral over current condition."
::= { lgpFlexConditionsWellKnown 5524 }
lgpCondId5531CondenserCommunicationLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Communication with condenser unit has been lost."
::= { lgpFlexConditionsWellKnown 5531 }
lgpCondId5535CondenserOutsideAirTempSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser outside air temperature sensor is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 5535 }
lgpCondId5536CondenserOutsideAirTempOutofOperatingRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Condenser Outside Air Temperature] is either above an upper
threshold or below a lower threshold."
::= { lgpFlexConditionsWellKnown 5536 }
lgpCondId5537CondenserControlBoardIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condenser control board is reporting an issue."
::= { lgpFlexConditionsWellKnown 5537 }
lgpCondId5539CondenserRefrigerantPressureOverThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser refrigerant pressure has exceeded a threshold."
::= { lgpFlexConditionsWellKnown 5539 }
lgpCondId5540CondenserRefrigerantPressureUnderThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser refrigerant pressure has dropped below a threshold."
::= { lgpFlexConditionsWellKnown 5540 }
lgpCondId5541CondenserRefrigerantPressureSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser refrigerant pressure sensor is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 5541 }
lgpCondId5542CondenserSupplyRefrigerantOverTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser supply refrigerant temperature has exceeded a threshold."
::= { lgpFlexConditionsWellKnown 5542 }
lgpCondId5543CondenserSupplyRefrigerantUnderTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser supply refrigerant temperature has dropped below a
specified threshold."
::= { lgpFlexConditionsWellKnown 5543 }
lgpCondId5544CondenserSupplyRefrigerantTempSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser supply refrigerant temperature sensor is disconnected or
the signal is out of range."
::= { lgpFlexConditionsWellKnown 5544 }
lgpCondId5545CondenserMaxFanSpeedOverride OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Fan speed exceeding the maximum set point in order to alleviate a
high temperature or pressure condition."
::= { lgpFlexConditionsWellKnown 5545 }
lgpCondId5559EvaporatorReturnFluidOverTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Evaporator Return Fluid Temperature] has exceeded a threshold.
The event is deactivated when the temperature drops below the
threshold."
::= { lgpFlexConditionsWellKnown 5559 }
lgpCondId5560EvaporatorReturnFluidUnderTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Evaporator Return Fluid Temperature] has dropped below a
threshold. The event is deactivated when the temperature rises
above the threshold."
::= { lgpFlexConditionsWellKnown 5560 }
lgpCondId5561LBSActiveMaster OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This UPS system has been selected as the functional Master Load
Bus Synchronization (LBS) system."
::= { lgpFlexConditionsWellKnown 5561 }
lgpCondId5562LBSActiveSlave OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This UPS system is synchronized to the output bus of the UPS
system that has been selected as the Master Load Bus
Synchronization (LBS) system."
::= { lgpFlexConditionsWellKnown 5562 }
lgpCondId5563DCBusLowFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The DC Bus voltage has reached a critical low level."
::= { lgpFlexConditionsWellKnown 5563 }
lgpCondId5564FanContactorOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The fan contactor is open."
::= { lgpFlexConditionsWellKnown 5564 }
lgpCondId5565FanContactorOpenFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The fan contactor failed to open."
::= { lgpFlexConditionsWellKnown 5565 }
lgpCondId5566FanContactorCloseFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The fan contactor failed to close."
::= { lgpFlexConditionsWellKnown 5566 }
lgpCondId5567IPInhibit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The intelligent paralleling operation is inhibited."
::= { lgpFlexConditionsWellKnown 5567 }
lgpCondId5568InputUndervoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more of the input phase voltages has dropped below the
limit."
::= { lgpFlexConditionsWellKnown 5568 }
lgpCondId5569InputOvervoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more of the input phase voltages has exceeded the limit."
::= { lgpFlexConditionsWellKnown 5569 }
lgpCondId5573AmbientAirSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Ambient air sensor is disconnected or the signal is out of range."
::= { lgpFlexConditionsWellKnown 5573 }
lgpCondId5577ExtDewPointUnderTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"At least one dew point temperature reading ([Ext Air Sensor A Dew
Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped
below [Ext Dew Point Under Temp Threshold]."
::= { lgpFlexConditionsWellKnown 5577 }
lgpCondId5578DewPointOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Dew point temperature reading has exceeded the upper threshold."
::= { lgpFlexConditionsWellKnown 5578 }
lgpCondId5579DewPointUnderTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Dew point temperature reading has dropped below the lower
threshold."
::= { lgpFlexConditionsWellKnown 5579 }
lgpCondId5588UnspecifiedGeneralEvent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more unspecified events active. See local unit display for
further details."
::= { lgpFlexConditionsWellKnown 5588 }
lgpCondId5593RemoteSensorAverageOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Remote Sensor Average Temperature] has exceeded [Remote Sensor
Over Temp Threshold]."
::= { lgpFlexConditionsWellKnown 5593 }
lgpCondId5594RemoteSensorAverageUnderTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Remote Sensor Average Temperature] has dropped below [Remote
Sensor Under Temp Threshold]."
::= { lgpFlexConditionsWellKnown 5594 }
lgpCondId5595RemoteSensorSystemAverageOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Remote Sensor System Average Temperature] has exceeded [Remote
Sensor Over Temp Threshold]."
::= { lgpFlexConditionsWellKnown 5595 }
lgpCondId5596RemoteSensorSystemAverageUnderTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Remote Sensor System Average Temperature] has dropped below
[Remote Sensor Under Temp Threshold]."
::= { lgpFlexConditionsWellKnown 5596 }
lgpCondId5597RemoteSensorOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp
Threshold]."
::= { lgpFlexConditionsWellKnown 5597 }
lgpCondId5598RemoteSensorUnderTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Remote Sensor Temperature] has dropped below [Remote Sensor Under
Temp Threshold]."
::= { lgpFlexConditionsWellKnown 5598 }
lgpCondId5600AirEconomizerEmergencyOverride OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Indoor room temperature has exceeded its upper threshold and the
outdoor air damper has been opened for emergency cooling."
::= { lgpFlexConditionsWellKnown 5600 }
lgpCondId5601AirEconomizerReducedAirflow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Air economizer filter is dirty and needs to be cleaned or replaced."
::= { lgpFlexConditionsWellKnown 5601 }
lgpCondId5604CompressorSuperheatOverThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor discharge refrigerant superheat temperature has
exceeded an upper threshold."
::= { lgpFlexConditionsWellKnown 5604 }
lgpCondId5609ThermalRunawayCelltoAmbientTemperatureEvent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The delta temperature between a cell temperature and the ambient
temperature has exceeded the thermal runaway cell to ambient
temperature threshold."
::= { lgpFlexConditionsWellKnown 5609 }
lgpCondId5610ThermalRunawayCelltoCellTemperatureEvent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The delta temperature between two cells has exceeded the thermal
runaway cell to cell temperature threshold."
::= { lgpFlexConditionsWellKnown 5610 }
lgpCondId5611ThermalRunawayChargerCurrentLevelOneEvent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Battery-String charger current has exceeded the thermal
runaway charger current level one threshold."
::= { lgpFlexConditionsWellKnown 5611 }
lgpCondId5612ThermalRunawayChargerCurrentLevelTwoEvent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Battery-String charger current has exceeded the thermal
runaway charger current level two threshold."
::= { lgpFlexConditionsWellKnown 5612 }
lgpCondId5617TemperatureControlSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The air sensor selected for cooling control is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 5617 }
lgpCondId5621EEVSuperheatBelowThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Electronic expansion valve refrigerant low superheat event."
::= { lgpFlexConditionsWellKnown 5621 }
lgpCondId5622EEVDischargeTempAboveThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Electronic expansion valve refrigerant high discharge temperature
event."
::= { lgpFlexConditionsWellKnown 5622 }
lgpCondId5623EEVBatteryIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Electronic expansion valve battery cannot be recharged and needs
to be replaced."
::= { lgpFlexConditionsWellKnown 5623 }
lgpCondId5624EEVPowerIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Electronic expansion valve lost power and is running on battery
backup."
::= { lgpFlexConditionsWellKnown 5624 }
lgpCondId5625EEVUnspecifiedGeneralEvent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more unspecified electronic expansion valve events active.
See local unit display for further details."
::= { lgpFlexConditionsWellKnown 5625 }
lgpCondId5629StaticPressureSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The static pressure sensor is disconnected or the signal is out of
range."
::= { lgpFlexConditionsWellKnown 5629 }
lgpCondId5630HighStaticPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"High static pressure event."
::= { lgpFlexConditionsWellKnown 5630 }
lgpCondId5631LowStaticPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Low static pressure event."
::= { lgpFlexConditionsWellKnown 5631 }
lgpCondId5636PumpUnspecifiedGeneralEvent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more unspecified pump events active. See local unit display
for further details."
::= { lgpFlexConditionsWellKnown 5636 }
lgpCondId5637CondenserUnitUnspecifiedGeneralEvent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more unspecified condenser unit events active. See local
unit display for further details."
::= { lgpFlexConditionsWellKnown 5637 }
lgpCondId5638CondenserCircuitUnspecifiedGeneralEvent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more unspecified condenser circuit events active. See local
unit display for further details."
::= { lgpFlexConditionsWellKnown 5638 }
lgpCondId5642SFAReservedEvent1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5642 }
lgpCondId5643SFAReservedEvent2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5643 }
lgpCondId5644SFAReservedEvent3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5644 }
lgpCondId5645SFAReservedEvent4 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5645 }
lgpCondId5646SFAReservedEvent5 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5646 }
lgpCondId5647SFAReservedEvent6 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5647 }
lgpCondId5648SFAReservedEvent7 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5648 }
lgpCondId5649SFAReservedEvent8 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5649 }
lgpCondId5650SFAReservedEvent9 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5650 }
lgpCondId5651SFAReservedEvent10 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5651 }
lgpCondId5652SFAReservedEvent11 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5652 }
lgpCondId5653SFAReservedEvent12 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5653 }
lgpCondId5654SFAReservedEvent13 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5654 }
lgpCondId5655SFAReservedEvent14 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5655 }
lgpCondId5656SFAReservedEvent15 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5656 }
lgpCondId5657SFAReservedEvent16 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5657 }
lgpCondId5658SFAReservedEvent17 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5658 }
lgpCondId5659SFAReservedEvent18 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5659 }
lgpCondId5660SFAReservedEvent19 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5660 }
lgpCondId5661SFAReservedEvent20 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5661 }
lgpCondId5662SFAReservedEvent21 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5662 }
lgpCondId5663SFAReservedEvent22 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5663 }
lgpCondId5664SFAReservedEvent23 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5664 }
lgpCondId5665SFAReservedEvent24 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5665 }
lgpCondId5666SFAReservedEvent25 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 5666 }
lgpCondId5768OutletAirOvertemperatureLimit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The difference between the outlet air temperature and inlet air
temperature exceeds a specified maximum temperature."
::= { lgpFlexConditionsWellKnown 5768 }
lgpCondId5769EMOShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An Emergency Module Off command has been detected."
::= { lgpFlexConditionsWellKnown 5769 }
lgpCondId5770TopOutletFanFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Top outlet fan fault - one or more top outlet fans have failed."
::= { lgpFlexConditionsWellKnown 5770 }
lgpCondId5771MMSOverCapacity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The multi-module system load is larger than the apparent power
limit setting."
::= { lgpFlexConditionsWellKnown 5771 }
lgpCondId5773CompressorCapacityNormal OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor has returned to normal load capacity."
::= { lgpFlexConditionsWellKnown 5773 }
lgpCondId5774CompressorContactorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor contactor is not closing during compressor startup or
is not opening during compressor shutdown."
::= { lgpFlexConditionsWellKnown 5774 }
lgpCondId5775UnitShutdownUnspecifiedGeneralEvent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more unspecified unit shutdown events active. See local
unit display for further details."
::= { lgpFlexConditionsWellKnown 5775 }
lgpCondId5776PDULowVoltageLN OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module under voltage condition (LN)."
::= { lgpFlexConditionsWellKnown 5776 }
lgpCondId5777PDULowVoltageLL OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module under voltage condition (LL)."
::= { lgpFlexConditionsWellKnown 5777 }
lgpCondId5778PDULowVoltageL1L2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a line-to-line under voltage condition (L1
-L2)."
::= { lgpFlexConditionsWellKnown 5778 }
lgpCondId5779PDULowVoltageL2L3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a line-to-line under voltage condition (L2
-L3)."
::= { lgpFlexConditionsWellKnown 5779 }
lgpCondId5780PDULowVoltageL3L1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a line-to-line under voltage condition (L3
-L1)."
::= { lgpFlexConditionsWellKnown 5780 }
lgpCondId5781PDULowVoltageL1N OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a line to neutral under voltage condition
(L1-N)."
::= { lgpFlexConditionsWellKnown 5781 }
lgpCondId5782PDULowVoltageL2N OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a line to neutral under voltage condition
(L2-N)."
::= { lgpFlexConditionsWellKnown 5782 }
lgpCondId5783PDULowVoltageL3N OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a line to neutral under voltage condition
(L3-N)."
::= { lgpFlexConditionsWellKnown 5783 }
lgpCondId5784BranchLowVoltageLN OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module under voltage condition (LN)."
::= { lgpFlexConditionsWellKnown 5784 }
lgpCondId5785BranchLowVoltageLL OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module under voltage condition (LL)."
::= { lgpFlexConditionsWellKnown 5785 }
lgpCondId5786BranchLowVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module under voltage condition."
::= { lgpFlexConditionsWellKnown 5786 }
lgpCondId5788ContTieActive OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Continuous Power Tie Active."
::= { lgpFlexConditionsWellKnown 5788 }
lgpCondId5792UserkWhReset OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The user kWh accumulator was reset to zero by the operator."
::= { lgpFlexConditionsWellKnown 5792 }
lgpCondId5796PeakkWReset OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Peak kW was reset."
::= { lgpFlexConditionsWellKnown 5796 }
lgpCondId5798BypassOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Bypass overloaded, reduce load immediately."
::= { lgpFlexConditionsWellKnown 5798 }
lgpCondId5801LowBatteryShutdownImminent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"If active and guaranteed shutdown is enabled, a low battery
reserve condition exists that will shutdown the UPS."
::= { lgpFlexConditionsWellKnown 5801 }
lgpCondId5806OutputOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An overload exists on the output."
::= { lgpFlexConditionsWellKnown 5806 }
lgpCondId5807OutputOffPending OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output off pending - shutdown imminent."
::= { lgpFlexConditionsWellKnown 5807 }
lgpCondId5808SystemShutdownOutputShort OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Shutdown was due to a short on the output."
::= { lgpFlexConditionsWellKnown 5808 }
lgpCondId5809SystemShutdownLowBattery OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Shutdown was due to a low battery condition."
::= { lgpFlexConditionsWellKnown 5809 }
lgpCondId5810SystemShutdownRemoteShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Shutdown was due to a remote communications shutdown command."
::= { lgpFlexConditionsWellKnown 5810 }
lgpCondId5811SystemShutdownHardwareFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Shutdown was due to an externally applied hardware control signal."
::= { lgpFlexConditionsWellKnown 5811 }
lgpCondId5817LossofRedundancy OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has an insufficient number of power modules to provide
redundancy."
::= { lgpFlexConditionsWellKnown 5817 }
lgpCondId5818PowerModuleFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more conditions indicate a power module failure, service is
required."
::= { lgpFlexConditionsWellKnown 5818 }
lgpCondId5819PowerModuleWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more power modules is reporting a warning condition."
::= { lgpFlexConditionsWellKnown 5819 }
lgpCondId5838PowerModuleFanFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Power Module has detected a fan fault."
::= { lgpFlexConditionsWellKnown 5838 }
lgpCondId5839PowerModuleOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Power Module has detected an over temperature condition."
::= { lgpFlexConditionsWellKnown 5839 }
lgpCondId5840PowerModuleShutdownOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Power Module has shutdown due to over temperature."
::= { lgpFlexConditionsWellKnown 5840 }
lgpCondId5842ChargerModuleFanFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Charger Module has detected a fan fault."
::= { lgpFlexConditionsWellKnown 5842 }
lgpCondId5847BatteryModuleTemperatureSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A Battery Module temperature sensor fault has been detected."
::= { lgpFlexConditionsWellKnown 5847 }
lgpCondId5848BatteryModuleOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Battery Module has detected an over temperature condition."
::= { lgpFlexConditionsWellKnown 5848 }
lgpCondId5849ReplaceBatteryModule OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Battery Module needs to be replaced."
::= { lgpFlexConditionsWellKnown 5849 }
lgpCondId5850SystemShutdownTransformerOverTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"System shutdown due to transformer over temperature."
::= { lgpFlexConditionsWellKnown 5850 }
lgpCondId5851MaximumLoadAlarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Maximum load alarm indicating load setting has been exceeded."
::= { lgpFlexConditionsWellKnown 5851 }
lgpCondId5856BatteryModuleFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more battery modules are reporting a fault condition."
::= { lgpFlexConditionsWellKnown 5856 }
lgpCondId5857BatteryModuleWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more battery modules are reporting a warning condition."
::= { lgpFlexConditionsWellKnown 5857 }
lgpCondId5862CheckAirFilter OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Please check air filter, it may need to be cleaned or replaced."
::= { lgpFlexConditionsWellKnown 5862 }
lgpCondId5863TransformerFanFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The transformer fan has failed."
::= { lgpFlexConditionsWellKnown 5863 }
lgpCondId5865NoLoadWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Indicates the UPS has output voltage but the output current is
below a set threshold [No Load Warning Current Threshold] for a
set period of time [No Load Warning Delay]."
::= { lgpFlexConditionsWellKnown 5865 }
lgpCondId5871BatteryOverTemperatureLimit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A battery temperature sensor is reporting a value above a
predetermined limit."
::= { lgpFlexConditionsWellKnown 5871 }
lgpCondId5873UnexpectedMainBatteryDisconnectClosure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The main battery disconnect has closed unexpectedly."
::= { lgpFlexConditionsWellKnown 5873 }
lgpCondId5874BatteryOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected that the battery voltage has exceeded a
predetermined limit."
::= { lgpFlexConditionsWellKnown 5874 }
lgpCondId5875BatteryFuseFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more battery fuse faults has occurred."
::= { lgpFlexConditionsWellKnown 5875 }
lgpCondId5878MainBatteryDisconnectForcedToUnlock OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The main battery disconnect is forced to the unlocked state."
::= { lgpFlexConditionsWellKnown 5878 }
lgpCondId5879VdcBackfeed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The voltage between battery and DC bus measurements is out of
tolerance."
::= { lgpFlexConditionsWellKnown 5879 }
lgpCondId5880RectifierConfigurationChangeRequest OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This event indicates that the battery is not configured and PFC is
not enabled."
::= { lgpFlexConditionsWellKnown 5880 }
lgpCondId5881RegenerationActive OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Regeneration operation is active."
::= { lgpFlexConditionsWellKnown 5881 }
lgpCondId5882RegenerationOperationTerminated OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Regeneration operation is not active."
::= { lgpFlexConditionsWellKnown 5882 }
lgpCondId5883RegenerationOperationFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Regeneration operation has been terminated due to bypass source
instability or unit misoperation."
::= { lgpFlexConditionsWellKnown 5883 }
lgpCondId5884ProgramInputContact01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"When the signal from [Program Input Contact 01] is active the
function assigned to this contact is executed."
::= { lgpFlexConditionsWellKnown 5884 }
lgpCondId5885ProgramInputContact02 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"When the signal from [Program Input Contact 02] is active the
function assigned to this contact is executed."
::= { lgpFlexConditionsWellKnown 5885 }
lgpCondId5886ProgramInputContact03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"When the signal from [Program Input Contact 03] is active the
function assigned to this contact is executed."
::= { lgpFlexConditionsWellKnown 5886 }
lgpCondId5887ProgramInputContact04 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"When the signal from [Program Input Contact 04] is active the
function assigned to this contact is executed."
::= { lgpFlexConditionsWellKnown 5887 }
lgpCondId5888ProgramInputContact05 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"When the signal from [Program Input Contact 05] is active the
function assigned to this contact is executed."
::= { lgpFlexConditionsWellKnown 5888 }
lgpCondId5889ProgramInputContact06 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"When the signal from [Program Input Contact 06] is active the
function assigned to this contact is executed."
::= { lgpFlexConditionsWellKnown 5889 }
lgpCondId5890ProgramInputContact07 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"When the signal from [Program Input Contact 07] is active the
function assigned to this contact is executed."
::= { lgpFlexConditionsWellKnown 5890 }
lgpCondId5891ProgramInputContact08 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"When the signal from [Program Input Contact 08] is active the
function assigned to this contact is executed."
::= { lgpFlexConditionsWellKnown 5891 }
lgpCondId5892ProgramInputContact09 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"When the signal from [Program Input Contact 09] is active the
function assigned to this contact is executed."
::= { lgpFlexConditionsWellKnown 5892 }
lgpCondId5893ProgramInputContact10 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"When the signal from [Program Input Contact 10] is active the
function assigned to this contact is executed."
::= { lgpFlexConditionsWellKnown 5893 }
lgpCondId5894ProgramInputContact11 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"When the signal from [Program Input Contact 11] is active the
function assigned to this contact is executed."
::= { lgpFlexConditionsWellKnown 5894 }
lgpCondId5895ProgramInputContact12 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"When the signal from [Program Input Contact 12] is active the
function assigned to this contact is executed."
::= { lgpFlexConditionsWellKnown 5895 }
lgpCondId5896GroundFaultDetected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a ground fault on a Battery-String."
::= { lgpFlexConditionsWellKnown 5896 }
lgpCondId5902ReturnHumiditySensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The humidity sensor at the inlet of the unit is disconnected or
the signal is out of range."
::= { lgpFlexConditionsWellKnown 5902 }
lgpCondId5903CompressorLowDifferentialPressureLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor exceeded maximum startup attempts due to low
differential pressure. Compressor is shutdown and has been
disabled."
::= { lgpFlexConditionsWellKnown 5903 }
lgpCondId5906AirflowSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Airflow sensor is disconnected or the signal is out of range."
::= { lgpFlexConditionsWellKnown 5906 }
lgpCondId5907ExtAirDamperPositionIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Air damper position does not match expected value, as indicated by
an external input signal."
::= { lgpFlexConditionsWellKnown 5907 }
lgpCondId5908ExtPowerSourceAFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Unit main power source A failure, as indicated by an external
input signal."
::= { lgpFlexConditionsWellKnown 5908 }
lgpCondId5909ExtPowerSourceBFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Unit main power source B failure, as indicated by an external
input signal."
::= { lgpFlexConditionsWellKnown 5909 }
lgpCondId5910StaticPressureSensorOutofRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Static pressure sensor signal is out of its configured range."
::= { lgpFlexConditionsWellKnown 5910 }
lgpCondId5911FluidTemperatureSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The fluid temperature sensor is disconnected or the signal is out
of range."
::= { lgpFlexConditionsWellKnown 5911 }
lgpCondId5912FluidFlowSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The fluid flow sensor is disconnected or the signal is out of
range."
::= { lgpFlexConditionsWellKnown 5912 }
lgpCondId5914OverDifferentialPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An over differential pressure condition was detected."
::= { lgpFlexConditionsWellKnown 5914 }
lgpCondId5915UnderDifferentialPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An under differential pressure condition was detected."
::= { lgpFlexConditionsWellKnown 5915 }
lgpCondId5924MixedModeLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Mixed mode has been entered too many times over a rolling time
period and has been temporarily disabled. Mixed mode is defined
as the use of a compressor on one refrigeration circuit and the
use of a refrigerant pump on the other circuit."
::= { lgpFlexConditionsWellKnown 5924 }
lgpCondId5928UnbalancedLoadCondition OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a line-to-line unbalanced load condition."
::= { lgpFlexConditionsWellKnown 5928 }
lgpCondId5939BranchOverCurrentProtection OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Branch Receptacle Module's over current protection is
triggered."
::= { lgpFlexConditionsWellKnown 5939 }
lgpCondId5948BranchLowVoltageLL OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a module under voltage condition (LL)."
::= { lgpFlexConditionsWellKnown 5948 }
lgpCondId5957BypassInputVoltageFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected the bypass voltage is unqualified."
::= { lgpFlexConditionsWellKnown 5957 }
lgpCondId5958BatteryTemperatureOutofRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery temperature is outside of acceptable range."
::= { lgpFlexConditionsWellKnown 5958 }
lgpCondId5960InverterOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Inverter in overload fault."
::= { lgpFlexConditionsWellKnown 5960 }
lgpCondId5966AuxAirTempDeviceCommunicationLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Communication with external auxiliary device providing an air
temperature value has been lost."
::= { lgpFlexConditionsWellKnown 5966 }
lgpCondId5967ModbusPowerMeterCommunicationLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Communication with Modbus power meter has been lost."
::= { lgpFlexConditionsWellKnown 5967 }
lgpCondId5968InverterDesaturation OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Inverter Desaturation."
::= { lgpFlexConditionsWellKnown 5968 }
lgpCondId5969GenericDICFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The control board reports a fault - Service required."
::= { lgpFlexConditionsWellKnown 5969 }
lgpCondId5970GroundFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An AC phase to ground fault or three phase fault to ground exists
on the output of the UPS."
::= { lgpFlexConditionsWellKnown 5970 }
lgpCondId5973InputBreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The main input breaker is open."
::= { lgpFlexConditionsWellKnown 5973 }
lgpCondId5974NeutralBreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The neutral breaker is open."
::= { lgpFlexConditionsWellKnown 5974 }
lgpCondId5975OutputBreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output breaker is open."
::= { lgpFlexConditionsWellKnown 5975 }
lgpCondId5976MaintenanceBypassBreakerClosed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The maintenance bypass breaker is closed."
::= { lgpFlexConditionsWellKnown 5976 }
lgpCondId5977BatteryBreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery circuit is open."
::= { lgpFlexConditionsWellKnown 5977 }
lgpCondId5978RectifierIsolationBreakerRFBOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The rectifier isolation breaker (RFB) indicates that it is in the
open position."
::= { lgpFlexConditionsWellKnown 5978 }
lgpCondId5982BypassBreakerSBBOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The bypass circuit breaker (SBB) indicates that it is in the open
position."
::= { lgpFlexConditionsWellKnown 5982 }
lgpCondId5983BypassIsolationBreakerBIBOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The bypass isolation breaker (BIB) indicates that it is in the
open position."
::= { lgpFlexConditionsWellKnown 5983 }
lgpCondId5984BypassUndervoltageWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The voltage on one or more bypass phases is less than a specified
percentage of the nominal voltage."
::= { lgpFlexConditionsWellKnown 5984 }
lgpCondId5985BypassStaticSwitchBPSSOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Bypass Static Switch has been turned on."
::= { lgpFlexConditionsWellKnown 5985 }
lgpCondId5998BattOvtempWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A battery temperature sensor is reporting a value above the
setpoint."
::= { lgpFlexConditionsWellKnown 5998 }
lgpCondId6009InverterOutputBreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter output breaker indicates that it is in the open
position."
::= { lgpFlexConditionsWellKnown 6009 }
lgpCondId6011EquipmentOverTempWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Equipment over temperature warning is a summary event based on the
detection of at least one measured temperature exceeding a
threshold."
::= { lgpFlexConditionsWellKnown 6011 }
lgpCondId6012EquipmentOvertemperatureLimit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The equipment air temperature has exceeded its maximum set point."
::= { lgpFlexConditionsWellKnown 6012 }
lgpCondId6045RectifierInputBreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The rectifier isolation breaker indicates that it is in the open
position."
::= { lgpFlexConditionsWellKnown 6045 }
lgpCondId6046LoadonUPS OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output is being supplied power from the inverter."
::= { lgpFlexConditionsWellKnown 6046 }
lgpCondId6047Core2CoreFuseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Core-2-core fuse failure."
::= { lgpFlexConditionsWellKnown 6047 }
lgpCondId6052SystemOutputBreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system output breaker is open."
::= { lgpFlexConditionsWellKnown 6052 }
lgpCondId6059InverterRelayFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter relay has malfunctioned."
::= { lgpFlexConditionsWellKnown 6059 }
lgpCondId6060TransfertoBypassSystemOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS System has transferred to bypass because the active power
modules cannot support the critical load."
::= { lgpFlexConditionsWellKnown 6060 }
lgpCondId6061InputSourceBackfeed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery is backfeeding the input source."
::= { lgpFlexConditionsWellKnown 6061 }
lgpCondId6062LossofSynchronization OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter and bypass are no longer synchronized. ."
::= { lgpFlexConditionsWellKnown 6062 }
lgpCondId6063BatteryConverterCurrentLimit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery converter has reached is maximum current limit. ."
::= { lgpFlexConditionsWellKnown 6063 }
lgpCondId6064LBSCableFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load Bus Sync communications is abnormal. A problem with the LBS
cable may exist."
::= { lgpFlexConditionsWellKnown 6064 }
lgpCondId6065BatteryChargeEqualizationTimeout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery equalizing is time out."
::= { lgpFlexConditionsWellKnown 6065 }
lgpCondId6066ParallelCableFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS parallel system communications is abnormal. A problem with
the parallel cable may exist."
::= { lgpFlexConditionsWellKnown 6066 }
lgpCondId6067BatteryFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A short circuit exists in the battery system."
::= { lgpFlexConditionsWellKnown 6067 }
lgpCondId6068BatteryRoomAlarm OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The ambient temperature of the battery room is abnormal."
::= { lgpFlexConditionsWellKnown 6068 }
lgpCondId6080UPSCCommunicationFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPSC has failed to communicate in a designated time period."
::= { lgpFlexConditionsWellKnown 6080 }
lgpCondId6092Compressor1BThermalOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Fixed compressor 1B is shut down due to thermal overload."
::= { lgpFlexConditionsWellKnown 6092 }
lgpCondId6093Compressor2BThermalOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Fixed compressor 2B is shut down due to thermal overload."
::= { lgpFlexConditionsWellKnown 6093 }
lgpCondId6094Compressor1BHoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Fixed compressor 1B run hours have exceeded the threshold."
::= { lgpFlexConditionsWellKnown 6094 }
lgpCondId6095Compressor2BHoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Fixed compressor 2B run hours have exceeded the threshold."
::= { lgpFlexConditionsWellKnown 6095 }
lgpCondId6100CondenserRemoteShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser is shut down by a remote signal."
::= { lgpFlexConditionsWellKnown 6100 }
lgpCondId6105ExternalCondenserTVSSIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condenser Transient Voltage Surge Suppressor or Surge
Protection Device has failed, as indicated by an external input
signal."
::= { lgpFlexConditionsWellKnown 6105 }
lgpCondId6106ExternalCondenserVFDIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condenser fan Variable Frequency Drive is offline, as
indicated by an external input signal."
::= { lgpFlexConditionsWellKnown 6106 }
lgpCondId6107ExternalCondenserIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Condenser is not operating within its operational parameters, as
indicated by an external input signal."
::= { lgpFlexConditionsWellKnown 6107 }
lgpCondId6119Slotsnotavailable OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The number of sensors exceeds the number of allocated slots and
cannot be displayed."
::= { lgpFlexConditionsWellKnown 6119 }
lgpCondId6180BatteryUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery voltage is too low."
::= { lgpFlexConditionsWellKnown 6180 }
lgpCondId6182ReplaceBattery OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery is due for replacement."
::= { lgpFlexConditionsWellKnown 6182 }
lgpCondId6186InputFrequencyDeviation OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The input frequency is outside of the normal range."
::= { lgpFlexConditionsWellKnown 6186 }
lgpCondId6187ShutdownPending OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Shutdown is pending."
::= { lgpFlexConditionsWellKnown 6187 }
lgpCondId6194SystemRebootCommandIssued OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reboot command issued to the system."
::= { lgpFlexConditionsWellKnown 6194 }
lgpCondId6203SensorAdded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Sensor Added."
::= { lgpFlexConditionsWellKnown 6203 }
lgpCondId6204SensorRemoved OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Sensor Removed."
::= { lgpFlexConditionsWellKnown 6204 }
lgpCondId6205WaterLeakDetected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Water leak detected."
::= { lgpFlexConditionsWellKnown 6205 }
lgpCondId6210FirmwareUpdateInProgress OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Firmware update has started and is in progress."
::= { lgpFlexConditionsWellKnown 6210 }
lgpCondId6211FirmwareUpdateCompletedSuccessfully OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Firmware update has completed successfully."
::= { lgpFlexConditionsWellKnown 6211 }
lgpCondId6212FirmwareUpdateCompletedUnsuccessfully OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Firmware update has completed, but was not successful."
::= { lgpFlexConditionsWellKnown 6212 }
lgpCondId6216PrechargeCircuitFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"DC Bus precharge/discharge didn't reach specified level within a
specified time."
::= { lgpFlexConditionsWellKnown 6216 }
lgpCondId6217MemoryCardRemoved OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The memory card on the control board has been removed."
::= { lgpFlexConditionsWellKnown 6217 }
lgpCondId6218AutoCalibrationActive OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system is automatically calibrating ADC channels."
::= { lgpFlexConditionsWellKnown 6218 }
lgpCondId6219AutoCalibrationFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"ADC channel calibration has failed."
::= { lgpFlexConditionsWellKnown 6219 }
lgpCondId6220ModuleOutputBreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The module output breaker is open."
::= { lgpFlexConditionsWellKnown 6220 }
lgpCondId6221NeutralVoltageFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Voltage observed on neutral line."
::= { lgpFlexConditionsWellKnown 6221 }
lgpCondId6222BranchLoadLoss OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Loss of load on branch detected. Branch circuit breaker might be
open."
::= { lgpFlexConditionsWellKnown 6222 }
lgpCondId6225RemoteSensorLowHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Remote sensor humidity has dropped below a lower threshold. The
event is deactivated when the humidity rises above the threshold."
::= { lgpFlexConditionsWellKnown 6225 }
lgpCondId6226RemoteSensorHighHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Remote sensor humidity has exceeded an upper threshold. The event
is deactivated when the humidity drops below the threshold."
::= { lgpFlexConditionsWellKnown 6226 }
lgpCondId6227RemoteSensorAverageLowHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The average humidity of multiple remote sensors on the cooling
unit has dropped below a lower threshold. The event is
deactivated when the humidity rises above the threshold."
::= { lgpFlexConditionsWellKnown 6227 }
lgpCondId6228RemoteSensorAverageHighHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The average humidity of multiple remote sensors on the cooling
unit has exceeded an upper threshold. The event is deactivated
when the humidity drops below the threshold."
::= { lgpFlexConditionsWellKnown 6228 }
lgpCondId6229RemoteSensorSystemAverageLowHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The average humidity of multiple remote sensors on interconnected
cooling units in a single system has dropped below a lower
threshold. The event is deactivated when the humidity rises
above the threshold."
::= { lgpFlexConditionsWellKnown 6229 }
lgpCondId6230RemoteSensorSystemAverageHighHumidity OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The average humidity of multiple remote sensors on interconnected
cooling units in a single system has exceeded an upper threshold.
The event is deactivated when the humidity drops below the
threshold."
::= { lgpFlexConditionsWellKnown 6230 }
lgpCondId6231LowCompressorSuperheat OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor suction superheat has dropped below a lower threshold."
::= { lgpFlexConditionsWellKnown 6231 }
lgpCondId6232SECUnspecifiedGeneralEvent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more unspecified events active for the Superheat and
Envelope Controller. See local unit display for further details."
::= { lgpFlexConditionsWellKnown 6232 }
lgpCondId6233SECCommunicationLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Communication with the Superheat and Envelope Controller has been
lost. The event is deactivated when communication is re
-established."
::= { lgpFlexConditionsWellKnown 6233 }
lgpCondId6236PowerSourceAIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"No power is detected at power source input 'A'."
::= { lgpFlexConditionsWellKnown 6236 }
lgpCondId6237PowerSourceBIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"No power is detected at power source input 'B'."
::= { lgpFlexConditionsWellKnown 6237 }
lgpCondId6239FluidValveHoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Operating hours for the fluid valve have exceeded the threshold."
::= { lgpFlexConditionsWellKnown 6239 }
lgpCondId6253BoosterFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Booster failure - boost is off."
::= { lgpFlexConditionsWellKnown 6253 }
lgpCondId6254ChargerFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Charger Failure - Charger is off."
::= { lgpFlexConditionsWellKnown 6254 }
lgpCondId6274UnitTopReturnAirSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Return air sensor at the top of the unit is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 6274 }
lgpCondId6275UnitMiddleReturnAirSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Return air sensor in the middle of the unit is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 6275 }
lgpCondId6276UnitBottomReturnAirSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Return air sensor at the bottom of the unit is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 6276 }
lgpCondId6277UnitTopSupplyAirSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Supply air sensor at the top of the unit is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 6277 }
lgpCondId6278UnitMiddleFirstSupplyAirSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"First supply air sensor in the middle of the unit is disconnected
or the signal is out of range."
::= { lgpFlexConditionsWellKnown 6278 }
lgpCondId6279UnitBottomSupplyAirSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Supply air sensor at the bottom of the unit is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 6279 }
lgpCondId6284UnitMiddleSecondSupplyAirSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Second supply air sensor in the middle of the unit is disconnected
or the signal is out of range."
::= { lgpFlexConditionsWellKnown 6284 }
lgpCondId6293ChilledWaterControlActive OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Chilled water inlet temperature control function is enabled due to
'bad' water."
::= { lgpFlexConditionsWellKnown 6293 }
lgpCondId6294ChilledWaterFlowTransducerFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Chilled water flow transducer is disconnected or the signal is out
of range."
::= { lgpFlexConditionsWellKnown 6294 }
lgpCondId6295ChilledWaterInletTemperatureSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Chilled water inlet temperature sensor is disconnected or the
signal is out of range. The sensor is mandatory for the chilled
water flow function."
::= { lgpFlexConditionsWellKnown 6295 }
lgpCondId6296ChilledWaterHighInletTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Chilled water inlet temperature has exceeded an upper threshold."
::= { lgpFlexConditionsWellKnown 6296 }
lgpCondId6297Modbus010VModuleCommunicationFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Modbus 0-10V module for managing the second Chilled Water circuit
valve is disconnected or the signal is out of range."
::= { lgpFlexConditionsWellKnown 6297 }
lgpCondId6299RackDoorsOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Rack doors opened due to supply air temperature exceeding the
[Rack Door Open High Supply Air Temperature Threshold]."
::= { lgpFlexConditionsWellKnown 6299 }
lgpCondId6303TeamStaticPressureSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The team static pressure sensor is disconnected or the signal is
out of range."
::= { lgpFlexConditionsWellKnown 6303 }
lgpCondId6304HeatingLockout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Heating is shut down and disabled."
::= { lgpFlexConditionsWellKnown 6304 }
lgpCondId6305FreeCoolingStoppedHighRoomTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Free cooling is temporarily disabled due to room temperature
exceeding a preset delta above the the set point."
::= { lgpFlexConditionsWellKnown 6305 }
lgpCondId6306ColdAisleTemperatureHumidityTeamSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Cold aisle team sensor measuring air temperature and humidity is
disconnected or the signal is out of range."
::= { lgpFlexConditionsWellKnown 6306 }
lgpCondId6309ColdAisleAirSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Cold aisle sensor measuring air temperature and humidity is
disconnected or the signal is out of range."
::= { lgpFlexConditionsWellKnown 6309 }
lgpCondId6310ChilledWaterInletTemperatureControlActive OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Chilled water inlet temperature control is active."
::= { lgpFlexConditionsWellKnown 6310 }
lgpCondId6313ChilledWaterInletTemperatureSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Chilled water inlet temperature sensor is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 6313 }
lgpCondId6314ChilledWaterOutletTemperatureSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Chilled water outlet temperature sensor is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 6314 }
lgpCondId6315ChilledWaterFlowMeterSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Chilled water flow meter sensor is disconnected or the signal is
out of range."
::= { lgpFlexConditionsWellKnown 6315 }
lgpCondId6333Bypassoutofsync OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Bypass and Inverter inputs are not in sync."
::= { lgpFlexConditionsWellKnown 6333 }
lgpCondId6348SystemOutputoffasrequested OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS has shutdown as requested, i.e., the output is off."
::= { lgpFlexConditionsWellKnown 6348 }
lgpCondId6349SystemOffasrequested OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The entire UPS has shutdown as commanded."
::= { lgpFlexConditionsWellKnown 6349 }
lgpCondId6350GeneralFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A general fault in the UPS has been detected."
::= { lgpFlexConditionsWellKnown 6350 }
lgpCondId6351UPSAwaitingPower OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS output is off and the UPS is awaiting the return of input
power."
::= { lgpFlexConditionsWellKnown 6351 }
lgpCondId6352AutonomyCalibration OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Calibration test occurred."
::= { lgpFlexConditionsWellKnown 6352 }
lgpCondId6353GeneralWarning OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A warning in the UPS has been detected."
::= { lgpFlexConditionsWellKnown 6353 }
lgpCondId6354BatteryCharging OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The UPS battery is charging (battery charge percentage lower than
98)."
::= { lgpFlexConditionsWellKnown 6354 }
lgpCondId6355BackfeedRelayFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Bypass SCR is wrongly on or commutated."
::= { lgpFlexConditionsWellKnown 6355 }
lgpCondId6356BatteryCircuitOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Battery Circuit Open."
::= { lgpFlexConditionsWellKnown 6356 }
lgpCondId6357SystemRestartPending OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A request for UPS restart has been received."
::= { lgpFlexConditionsWellKnown 6357 }
lgpCondId6358PipeTemperatureSensorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Air temperature sensor located in the pipe is not sending a valid
value."
::= { lgpFlexConditionsWellKnown 6358 }
lgpCondId6362SFAReservedEvent26 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6362 }
lgpCondId6363SFAReservedEvent27 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6363 }
lgpCondId6364SFAReservedEvent28 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6364 }
lgpCondId6365SFAReservedEvent29 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6365 }
lgpCondId6366SFAReservedEvent30 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6366 }
lgpCondId6367SFAReservedEvent31 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6367 }
lgpCondId6368SFAReservedEvent32 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6368 }
lgpCondId6369SFAReservedEvent33 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6369 }
lgpCondId6370SFAReservedEvent34 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6370 }
lgpCondId6371SFAReservedEvent35 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6371 }
lgpCondId6372SFAReservedEvent36 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6372 }
lgpCondId6373SFAReservedEvent37 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6373 }
lgpCondId6374SFAReservedEvent38 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6374 }
lgpCondId6375SFAReservedEvent39 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6375 }
lgpCondId6376SFAReservedEvent40 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6376 }
lgpCondId6377SFAReservedEvent41 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6377 }
lgpCondId6378SFAReservedEvent42 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6378 }
lgpCondId6379SFAReservedEvent43 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6379 }
lgpCondId6380SFAReservedEvent44 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6380 }
lgpCondId6381SFAReservedEvent45 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6381 }
lgpCondId6382SFAReservedEvent46 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6382 }
lgpCondId6383SFAReservedEvent47 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6383 }
lgpCondId6384SFAReservedEvent48 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6384 }
lgpCondId6385SFAReservedEvent49 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6385 }
lgpCondId6386SFAReservedEvent50 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Reserved event for SFA use."
::= { lgpFlexConditionsWellKnown 6386 }
lgpCondId6438PowerModuleInputCurrentAbnormal OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Input current of the power module is abnormal."
::= { lgpFlexConditionsWellKnown 6438 }
lgpCondId6439PowerModuleBalancerofDCBusFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Balancer of DC Bus in the power module has failed."
::= { lgpFlexConditionsWellKnown 6439 }
lgpCondId6440PowerModuleFuseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A summary event indicating one or more fuse failures in the power
module."
::= { lgpFlexConditionsWellKnown 6440 }
lgpCondId6441PowerModulePowerSupplyFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Power module power supply failure."
::= { lgpFlexConditionsWellKnown 6441 }
lgpCondId6450PDUPoweredOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The PDU was powered on."
::= { lgpFlexConditionsWellKnown 6450 }
lgpCondId6453InputWiringFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The neutral/ground conductors on the input wiring are not properly
bonded, or the line/neutral conductors have been swapped."
::= { lgpFlexConditionsWellKnown 6453 }
lgpCondId6454DCtoDCConverterFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A failure has occurred in the battery discharge circuit."
::= { lgpFlexConditionsWellKnown 6454 }
lgpCondId6455LeakSensorCableFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A fault is detected in the 'Leak Sensor' cable."
::= { lgpFlexConditionsWellKnown 6455 }
lgpCondId6518StandbyUnitActivatedDuetoChillerFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"External chiller unit has failed for this unit, so the standby
cooling unit has been activated."
::= { lgpFlexConditionsWellKnown 6518 }
lgpCondId6522PDUResidualOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a PDU residual over current condition."
::= { lgpFlexConditionsWellKnown 6522 }
lgpCondId6527PDUOverCurrentProtection OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The PDU over current protection is triggered."
::= { lgpFlexConditionsWellKnown 6527 }
lgpCondId6528PowerModuleLeverUnlocked OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The power module is inactive because the lever is in the unlocked
position."
::= { lgpFlexConditionsWellKnown 6528 }
lgpCondId6529HardwareMismatch OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The assigned system model settings do not match the actual
installed hardware. The module count is wrong, or a module of the
wrong type is installed."
::= { lgpFlexConditionsWellKnown 6529 }
lgpCondId6530SupplyNTCAirSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The supply NTC air sensor is disconnected or the signal is out of
range."
::= { lgpFlexConditionsWellKnown 6530 }
lgpCondId6531ExternalAirSensorCIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external air sensor C is disconnected or the signal is out of
range."
::= { lgpFlexConditionsWellKnown 6531 }
lgpCondId6532ExternalAirSensorDIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external air sensor D is disconnected or the signal is out of
range."
::= { lgpFlexConditionsWellKnown 6532 }
lgpCondId6533ExternalAirSensorEIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The external air sensor E is disconnected or the signal is out of
range."
::= { lgpFlexConditionsWellKnown 6533 }
lgpCondId6534PumpThermalOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Pump is shut down due to thermal overload."
::= { lgpFlexConditionsWellKnown 6534 }
lgpCondId6535XDModuleCommunicationLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Communication with XD Module has been lost."
::= { lgpFlexConditionsWellKnown 6535 }
lgpCondId6536MMSCapacityExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The critical load is larger than the redundant rating of a 1+N
redundant multi-module system."
::= { lgpFlexConditionsWellKnown 6536 }
lgpCondId6538TSAControlInputIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The analog input used to set the air temperature set point for
cooling control is disconnected or the signal is out of range."
::= { lgpFlexConditionsWellKnown 6538 }
lgpCondId6539ChilledWaterValveHoursExceeded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"[Chilled Water Valve Hours] has exceeded [Chilled Water Valve
Operating Hours Threshold]."
::= { lgpFlexConditionsWellKnown 6539 }
lgpCondId6540FSAControlInputIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The analog input used to set the air temperature set point for fan
speed control is disconnected or the signal is out of range."
::= { lgpFlexConditionsWellKnown 6540 }
lgpCondId6541AutoTuneLicenseExpiring OBJECT-IDENTITY
STATUS current
DESCRIPTION
"License for the AutoTune feature has not been refreshed in 30 days
and will be expiring soon."
::= { lgpFlexConditionsWellKnown 6541 }
lgpCondId6542AutoTuneLicenseExpired OBJECT-IDENTITY
STATUS current
DESCRIPTION
"License for the AutoTune feature has expired."
::= { lgpFlexConditionsWellKnown 6542 }
lgpCondId6543UnitInStandbyDueToCoolingLoss OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Unit forced into standby because it is unable to provide any
cooling."
::= { lgpFlexConditionsWellKnown 6543 }
lgpCondId6544ControlUnitsRemoteShutdownMismatch OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The remote shutdown status of the primary control unit does not
match the remote shutdown status of the secondary control unit."
::= { lgpFlexConditionsWellKnown 6544 }
lgpCondId6545SecondaryControlUnitCommunicationLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The primary control unit has lost Ethernet communications with the
secondary control unit."
::= { lgpFlexConditionsWellKnown 6545 }
lgpCondId6546ControlUnitsUnitCodeMismatch OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Unit codes for the primary and secondary control units do not
match."
::= { lgpFlexConditionsWellKnown 6546 }
lgpCondId6547SSAControlInputIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The analog input used to set the static pressure set point for fan
speed control is disconnected or the signal is out of range."
::= { lgpFlexConditionsWellKnown 6547 }
lgpCondId6574SubfeedPhaseUndercurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Subfeed breaker phase current has dropped below the threshold."
::= { lgpFlexConditionsWellKnown 6574 }
lgpCondId6587TransferCountCleared OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A system event indicating the transfer count has been cleared."
::= { lgpFlexConditionsWellKnown 6587 }
lgpCondId6588EnergyCounterCleared OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A system event indicating the energy counter (e.g. KWH) has been
cleared."
::= { lgpFlexConditionsWellKnown 6588 }
lgpCondId6589HistoryLogsFull OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The history logs are full."
::= { lgpFlexConditionsWellKnown 6589 }
lgpCondId6590HistoryLogsCleared OBJECT-IDENTITY
STATUS current
DESCRIPTION
"History logs have been cleared."
::= { lgpFlexConditionsWellKnown 6590 }
lgpCondId6591EventLogCleared OBJECT-IDENTITY
STATUS current
DESCRIPTION
"All past alarms and faults have been cleared."
::= { lgpFlexConditionsWellKnown 6591 }
lgpCondId6592SystemDateChanged OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system date has been updated."
::= { lgpFlexConditionsWellKnown 6592 }
lgpCondId6593SystemTimeChanged OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system time has been updated."
::= { lgpFlexConditionsWellKnown 6593 }
lgpCondId6594AccessPasswordChanged OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The access password has been changed."
::= { lgpFlexConditionsWellKnown 6594 }
lgpCondId6595ConfigModified OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A setpoint has been updated."
::= { lgpFlexConditionsWellKnown 6595 }
lgpCondId6612SCRShort OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The SCR is in a short condition."
::= { lgpFlexConditionsWellKnown 6612 }
lgpCondId6613SCROpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The SCR is in an open condition."
::= { lgpFlexConditionsWellKnown 6613 }
lgpCondId6614ACPowerSupplyFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A failure of the AC Power Supply has been detected."
::= { lgpFlexConditionsWellKnown 6614 }
lgpCondId6615DCPowerSupplyFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A failure of the DC Power Supply has been detected."
::= { lgpFlexConditionsWellKnown 6615 }
lgpCondId6616VoltageSensorFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A voltage sensor failure has been detected."
::= { lgpFlexConditionsWellKnown 6616 }
lgpCondId6617SCRSensorFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The SCR sensor module failed."
::= { lgpFlexConditionsWellKnown 6617 }
lgpCondId6618CurrentSensorFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The current sensor module failed."
::= { lgpFlexConditionsWellKnown 6618 }
lgpCondId6619GateDriveFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Gate Drive module failed."
::= { lgpFlexConditionsWellKnown 6619 }
lgpCondId6620SurgeFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The surge module failed for the input source."
::= { lgpFlexConditionsWellKnown 6620 }
lgpCondId6621FastUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Fast under voltage detected."
::= { lgpFlexConditionsWellKnown 6621 }
lgpCondId6622SlowUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Slow under voltage detected."
::= { lgpFlexConditionsWellKnown 6622 }
lgpCondId6623OverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Over voltage detected."
::= { lgpFlexConditionsWellKnown 6623 }
lgpCondId6624OverUnderFrequencyFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An over or under frequency condition has been detected."
::= { lgpFlexConditionsWellKnown 6624 }
lgpCondId6625GeneralSourceFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A non-specific failure has been detected in the source."
::= { lgpFlexConditionsWellKnown 6625 }
lgpCondId6626OverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An over current has been detected."
::= { lgpFlexConditionsWellKnown 6626 }
lgpCondId6627PeakCurrentOffLimit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The peak current has exceeded the setpoint defined by I-PK Xfer
Lockout."
::= { lgpFlexConditionsWellKnown 6627 }
lgpCondId6628SyncFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A phase rotation/out of synchronization failure has been detected."
::= { lgpFlexConditionsWellKnown 6628 }
lgpCondId6629InputOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Input over voltage."
::= { lgpFlexConditionsWellKnown 6629 }
lgpCondId6630InputUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Input under voltage."
::= { lgpFlexConditionsWellKnown 6630 }
lgpCondId6631InputOverUnderFrequency OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Input over/under frequency."
::= { lgpFlexConditionsWellKnown 6631 }
lgpCondId6635VoltageSenseFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output voltage sense failure."
::= { lgpFlexConditionsWellKnown 6635 }
lgpCondId6636LoadonAlternateSource OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The load is on the alternate source."
::= { lgpFlexConditionsWellKnown 6636 }
lgpCondId6637UnderVoltageFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output under voltage failure."
::= { lgpFlexConditionsWellKnown 6637 }
lgpCondId6638OutputOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output is over current."
::= { lgpFlexConditionsWellKnown 6638 }
lgpCondId6639GroundOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Ground is over current."
::= { lgpFlexConditionsWellKnown 6639 }
lgpCondId6640NeutralOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Neutral is over current."
::= { lgpFlexConditionsWellKnown 6640 }
lgpCondId6641LoadVoltageTHD OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load voltage THD has exceeded the set limit."
::= { lgpFlexConditionsWellKnown 6641 }
lgpCondId6662ControlLogicFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A control logic module has failed."
::= { lgpFlexConditionsWellKnown 6662 }
lgpCondId6663PowerSupplyLogicFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A power supply module has failed."
::= { lgpFlexConditionsWellKnown 6663 }
lgpCondId6664ExternalCommsFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"External communications failure."
::= { lgpFlexConditionsWellKnown 6664 }
lgpCondId6665HeatSinkOverTemp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system heat sink temperature has exceeded design limits."
::= { lgpFlexConditionsWellKnown 6665 }
lgpCondId6666AutomaticTransferInhibited OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Automatic transfer is inhibited."
::= { lgpFlexConditionsWellKnown 6666 }
lgpCondId6667InputSourceTransferInhibited OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Input source transfer is inhibited."
::= { lgpFlexConditionsWellKnown 6667 }
lgpCondId6676CB1ShuntTrip OBJECT-IDENTITY
STATUS current
DESCRIPTION
"CB1 Shunt Trip event."
::= { lgpFlexConditionsWellKnown 6676 }
lgpCondId6677CB2ShuntTrip OBJECT-IDENTITY
STATUS current
DESCRIPTION
"CB2 Shunt Trip event."
::= { lgpFlexConditionsWellKnown 6677 }
lgpCondId6678CB6NeutralOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"CB6 neutral open event."
::= { lgpFlexConditionsWellKnown 6678 }
lgpCondId6679ContactorNeutralFail OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Contactor Neutral Fail event."
::= { lgpFlexConditionsWellKnown 6679 }
lgpCondId6680CB1BreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"CB1 Breaker open event. Normal state is breaker closed. Latched
state is breaker open."
::= { lgpFlexConditionsWellKnown 6680 }
lgpCondId6681CB2BreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"CB2 Breaker open event. Normal state is breaker closed. Latched
state is breaker open."
::= { lgpFlexConditionsWellKnown 6681 }
lgpCondId6682CB4BreakerClosed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"CB4 breaker closed event. Normal state is breaker open. Latched
state is breaker closed."
::= { lgpFlexConditionsWellKnown 6682 }
lgpCondId6683CB5BreakerClosed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"CB5 breaker closed event. Normal state is breaker open. Latched
state is breaker closed."
::= { lgpFlexConditionsWellKnown 6683 }
lgpCondId6684CB3BreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"CB3 breaker open event. Normal state is breaker closed. Latched
state is breaker open."
::= { lgpFlexConditionsWellKnown 6684 }
lgpCondId6685CB3ABreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"CB3A breaker open event. Normal state is breaker closed. Latched
state is breaker open."
::= { lgpFlexConditionsWellKnown 6685 }
lgpCondId6686CB6BreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"CB6 breaker open event. Normal state is breaker closed. Latched
state is breaker open."
::= { lgpFlexConditionsWellKnown 6686 }
lgpCondId6687CB7BreakerOpen OBJECT-IDENTITY
STATUS current
DESCRIPTION
"CB7 breaker open event. Normal state is breaker closed. Latched
state is breaker open."
::= { lgpFlexConditionsWellKnown 6687 }
lgpCondId6691GroupIndependentOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The group standby/cascade state for this unit has been overridden.
The unit has been forced on."
::= { lgpFlexConditionsWellKnown 6691 }
lgpCondId6692GroupIndependentOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The group standby/cascade state for this unit has been overridden.
The unit has been forced off."
::= { lgpFlexConditionsWellKnown 6692 }
lgpCondId6693BranchResidualOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a branch residual over current condition."
::= { lgpFlexConditionsWellKnown 6693 }
lgpCondId6694ReceptacleResidualOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The system has detected a receptacle residual over current
condition."
::= { lgpFlexConditionsWellKnown 6694 }
lgpCondId6728BuckOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The input voltage is currently being bucked (lowered) by the
inverter."
::= { lgpFlexConditionsWellKnown 6728 }
lgpCondId6729BoostOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The input voltage is currently being boosted (raised) by the
inverter."
::= { lgpFlexConditionsWellKnown 6729 }
lgpCondId6739Compressor1HighPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor 1 High Pressure."
::= { lgpFlexConditionsWellKnown 6739 }
lgpCondId6740Compressor2HighPressure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor 2 High Pressure."
::= { lgpFlexConditionsWellKnown 6740 }
lgpCondId6741Compressor1ThermalOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor 1 Thermal Overload."
::= { lgpFlexConditionsWellKnown 6741 }
lgpCondId6742Compressor2ThermalOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor 2 Thermal Overload."
::= { lgpFlexConditionsWellKnown 6742 }
lgpCondId6758CompressorFreezeProtection OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Compressor has entered the freeze protection phase."
::= { lgpFlexConditionsWellKnown 6758 }
lgpCondId6773FanTemperatureCompensationLimitReached OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Unit is configured for fan temperature compensation, and the fan
control set point cannot be reduced any further due to high
remote air temperature sensor readings."
::= { lgpFlexConditionsWellKnown 6773 }
lgpCondId6774ModbusECFanCommunicationLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Communication with Modbus EC fan has been lost."
::= { lgpFlexConditionsWellKnown 6774 }
lgpCondId6785AnalogTemperatureControlIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Analog input used for creating the control temperature (instead of
reading a sensor) is disconnected or the signal is out of range."
::= { lgpFlexConditionsWellKnown 6785 }
lgpCondId6786SubgroupFirmwareUpdateRequired OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Mismatch of subgroup firmware. Both the primary and secondary
control boards must be running the same firmware version."
::= { lgpFlexConditionsWellKnown 6786 }
lgpCondId6787SubgroupSecondaryControlUnitIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Subgroup secondary control unit is reporting an unspecified issue."
::= { lgpFlexConditionsWellKnown 6787 }
lgpCondId6788EEVCommunicationLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Communication with Electronic Expansion Valve unit has been lost."
::= { lgpFlexConditionsWellKnown 6788 }
lgpCondId6789EEVMotorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Electronic Expansion Valve stepper motor issue."
::= { lgpFlexConditionsWellKnown 6789 }
lgpCondId6790EEVFeedbackIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Electronic Expansion Valve feedback error."
::= { lgpFlexConditionsWellKnown 6790 }
lgpCondId6791EEVPressureSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Electronic Expansion Valve refrigerant pressure sensor is
disconnected or the signal is out of range."
::= { lgpFlexConditionsWellKnown 6791 }
lgpCondId6792EEVCoilTemperatureSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Electronic Expansion Valve coil temperature sensor is disconnected
or the signal is out of range."
::= { lgpFlexConditionsWellKnown 6792 }
lgpCondId6793EEVDischargeTemperatureSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Electronic Expansion Valve discharge temperature sensor is
disconnected or the signal is out of range."
::= { lgpFlexConditionsWellKnown 6793 }
lgpCondId6794EEVSumpTemperatureSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Electronic Expansion Valve sump temperature sensor is disconnected
or the signal is out of range."
::= { lgpFlexConditionsWellKnown 6794 }
lgpCondId6795EEVBatteryTestIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Electronic Expansion Valve battery state cannot be determined."
::= { lgpFlexConditionsWellKnown 6795 }
lgpCondId6796EEVBatteryPersistentIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Electronic Expansion Valve has continuously detected a 'bad'
battery condition for an extended period of time."
::= { lgpFlexConditionsWellKnown 6796 }
lgpCondId6798PumpCycleLockOut OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Pump is locked out due to multiple pump-to-compressor transitions
at cold ambient air temperature."
::= { lgpFlexConditionsWellKnown 6798 }
lgpCondId6799PumpBoardFirmwareUpdateRequired OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Mismatch of pump board firmware. All pump boards must be running
the same firmware version."
::= { lgpFlexConditionsWellKnown 6799 }
lgpCondId6800PumpControlBoardIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Pump is shut down due to a pump control board issue. Control
board must be rebooted."
::= { lgpFlexConditionsWellKnown 6800 }
lgpCondId6801PumpInvalidDataShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Pump is shut down due to invalid data."
::= { lgpFlexConditionsWellKnown 6801 }
lgpCondId6802PumpInputPressureSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Pump input refrigerant pressure sensor is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 6802 }
lgpCondId6803PumpInputTemperatureSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Pump input refrigerant temperature sensor is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 6803 }
lgpCondId6804PumpOutputPressureSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Pump output refrigerant pressure sensor is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 6804 }
lgpCondId6805PumpOutputTemperatureSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Pump output refrigerant temperature sensor is disconnected or the
signal is out of range."
::= { lgpFlexConditionsWellKnown 6805 }
lgpCondId6806PumpCommunicationLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Communication with pump unit has been lost."
::= { lgpFlexConditionsWellKnown 6806 }
lgpCondId6807PumpRemoteShutdown OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Pump is shut down by a remote signal."
::= { lgpFlexConditionsWellKnown 6807 }
lgpCondId6808PumpUSBEthernetPortIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Pump control board USB or Ethernet interface has failed."
::= { lgpFlexConditionsWellKnown 6808 }
lgpCondId6809PumpStartupFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Multiple attempts to start the pump have failed."
::= { lgpFlexConditionsWellKnown 6809 }
lgpCondId6810PumpInverterFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Pump inverter is reporting a failure."
::= { lgpFlexConditionsWellKnown 6810 }
lgpCondId6811PumpTVSSIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Pump Transient Voltage Surge Suppressor or Surge Protection Device
has failed."
::= { lgpFlexConditionsWellKnown 6811 }
lgpCondId6812PumpHighSuperheat OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Pump inlet refrigerant superheat temperature is too high, or the
pump has been running too long with the condenser fan off."
::= { lgpFlexConditionsWellKnown 6812 }
lgpCondId6813CondenserHighAmbientAirTempDelta OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The difference between condenser measured ambient air temperatures
has been too large for an extended period of time."
::= { lgpFlexConditionsWellKnown 6813 }
lgpCondId6814CondenserLeeTempOptionMismatch OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Lee-Temp option configured at a condenser unit does not match Lee
-Temp option configured at the control unit."
::= { lgpFlexConditionsWellKnown 6814 }
lgpCondId6815CondenserBoardFirmwareUpdateRequired OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Mismatch of condenser board firmware. All condenser boards must
be running the same firmware version."
::= { lgpFlexConditionsWellKnown 6815 }
lgpCondId6816CondenserToPumpHighRefrigerantTempDelta OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Temperature delta between the condenser output refrigerant and
pump inlet refrigerant is too large."
::= { lgpFlexConditionsWellKnown 6816 }
lgpCondId6817CondenserRefrigerantTypeMismatch OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Refrigerant type configured at condenser unit does not match
refrigerant type configured at the control unit."
::= { lgpFlexConditionsWellKnown 6817 }
lgpCondId6818ExternalSupplyFluidHighTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Supply fluid temperature has exceeded a threshold, as indicated by
an external input signal."
::= { lgpFlexConditionsWellKnown 6818 }
lgpCondId6819ExternalSupplyFluidTempSensorIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Supply fluid temperature sensor is disconnected or the signal is
out of range, as indicated by an external input signal."
::= { lgpFlexConditionsWellKnown 6819 }
lgpCondId6822AuditLogUpdate OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Audit log has been updated."
::= { lgpFlexConditionsWellKnown 6822 }
lgpCondId6824ExternalSupplyFluidFlowIssue OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Supply fluid flow issue, as indicated by an external input signal."
::= { lgpFlexConditionsWellKnown 6824 }
END