LIEBERT-GP-POWER-MIB DEFINITIONS ::= BEGIN
IMPORTS
MODULE-IDENTITY,
OBJECT-IDENTITY,
OBJECT-TYPE,
Integer32,
Unsigned32
FROM SNMPv2-SMI
lgpPower,
liebertPowerModuleReg
FROM LIEBERT-GP-REGISTRATION-MIB
;
-- =============================================================================
-- Module Identification and Registration
-- =============================================================================
liebertGlobalProductsPowerModule MODULE-IDENTITY
LAST-UPDATED "201307100000Z"
ORGANIZATION "Liebert Corporation"
CONTACT-INFO
"Contact: Technical Support
Postal:
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus OH, 43229
US
Tel: +1 (800) 222-5877
E-mail: liebert.monitoring@vertivco.com
Web: www.vertivco.com
Author: Gregory M. Hoge"
DESCRIPTION
"The MIB module used to register Liebert POWER related SNMP OIDs.
Copyright 2000-2008 Liebert Corporation. All rights reserved.
Reproduction of this document is authorized on the condition
that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Liebert Corporation
makes no warranty, either express or implied, as to the use,
operation, condition, or performance of the Specification."
REVISION "201307100000Z"
DESCRIPTION
"Added support for GXT4 economic operation mode and outlet control."
REVISION "200811170000Z"
DESCRIPTION
"Added support for NXL unit."
REVISION "200807020000Z"
DESCRIPTION
"Replaced INTEGER with Integer32 (SMIv2).
Minor spelling fixes and formatting."
REVISION "200801100000Z"
DESCRIPTION
"Modified contact email address and removed redundant
lgpPwrMeasurementPointNumLines."
REVISION "200602220000Z"
DESCRIPTION
"Added support for Liebert DS Unit."
::= { liebertPowerModuleReg 1 }
-- =============================================================================
-- lgpPower - Liebert Power Registrations
-- =============================================================================
lgpPwrBattery OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert Power Battery object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Power Battery Group."
::= { lgpPower 1 }
lgpPwrMeasurements OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree registers Liebert Power Measurement object
identifiers. The sub-tree contains tables and well known power
measurement points."
REFERENCE
"The registrations for the objects in this sub-tree are defined
below in the sub-section titled Liebert Power Measurement Group."
::= { lgpPower 2 }
lgpPwrStatus OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree registers Liebert Power Status object
identifiers. This is the location of power related status information
that does not fit into a more specific category such as the
lgpPwrConversion sub-tree."
REFERENCE
"The registrations for the objects in this sub-tree are defined
below in the sub-section titled Liebert Power Status Group"
::= { lgpPower 3 }
lgpPwrSettings OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree registers Liebert Power Static Switch object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are defined
below in the sub-section titled Liebert Power Settings Group."
::= { lgpPower 4 }
lgpPwrConversion OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert Power Conversion object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Power Conversion Group."
::= { lgpPower 5 }
lgpPwrControl OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert Power Control object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Power Control Group."
::= { lgpPower 6 }
lgpPwrTopology OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert Power Topology object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Power Topology Group."
::= { lgpPower 7 }
lgpPwrStatistic OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert Power Statistic object
identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Power Statistic Group."
::= { lgpPower 8 }
lgpPwrConfig OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register Liebert Power Configuration
Object identifiers."
REFERENCE
"The registrations for the objects in this sub-tree are
defined below in the sub-section titled Liebert Power Configuration
Group."
::= { lgpPower 9 }
-- =============================================================================
-- lgpPwrBattery - Liebert Power Battery Group
-- =============================================================================
lgpPwrNumberInstalledBatteryModules OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of battery modules installed in the device."
::= { lgpPwrBattery 1 }
lgpPwrNumberFailedBatteryModules OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of battery modules in the device that have failed."
::= { lgpPwrBattery 2 }
lgpPwrNumberRedundantBatteryModules OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of redundant battery modules in the device."
::= { lgpPwrBattery 3 }
lgpPwrNumberActiveBatteryModules OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of active battery modules in the device."
::= { lgpPwrBattery 4 }
lgpPwrConfigLowBatteryWarningTime OBJECT-TYPE
SYNTAX Integer32
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value of the device's estimated minutes of remaining battery
at which a lgpEventLowBatteryWarning notification will be sent."
::= { lgpPwrBattery 5 }
lgpPwrNumberBatteryModuleWarnings OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of battery modules in the device that have a warning."
::= { lgpPwrBattery 6 }
lgpPwrBatteryCount OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of batteries installed."
::= { lgpPwrBattery 7 }
lgpPwrBatteryTestResult OBJECT-TYPE
SYNTAX INTEGER
{
unknown(1),
passed(2),
failed(3),
inProgress(4),
systemFailure(5),
inhibited(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The outcome of the previous battery test."
::= { lgpPwrBattery 8 }
lgpPwrNominalBatteryCapacity OBJECT-TYPE
SYNTAX Integer32
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal battery capacity of the system (in minutes) at full load."
::= { lgpPwrBattery 9 }
lgpPwrBatteryFloatVoltage OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The battery float voltage of the system."
::= { lgpPwrBattery 10 }
lgpPwrBatteryEndOfDischargeVoltage OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The battery voltage threshold at which the batteries are considered
completely discharged."
::= { lgpPwrBattery 11 }
lgpPwrAutomaticBatteryTestInterval OBJECT-TYPE
SYNTAX Integer32
UNITS "hours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The automatic battery test interval."
::= { lgpPwrBattery 12 }
lgpPwrAutomaticBatteryTestCountdown OBJECT-TYPE
SYNTAX Integer32
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The time remaining before the next battery test."
::= { lgpPwrBattery 13 }
lgpPwrBatteryChargeStatus OBJECT-TYPE
SYNTAX INTEGER
{
fullycharged(1),
notfullycharged(2),
charging(3),
discharging(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the system's battery charge.
A value of 'charging' indicates the batteries are currently charging.
A value of 'discharging' indicates the batteries are currently
discharging. A value of 'fullycharged' indicates the batteries are
charged to their full capacity. A value of 'notfullycharged' indicates
the battery charge is neither fully charged, charging or discharging."
::= { lgpPwrBattery 14 }
lgpPwrBatteryLifeEnhancer OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the battery life enhancer. When 'on', it will
preserve battery life."
::= { lgpPwrBattery 15 }
lgpPwrBatteryCharger OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the battery charger."
::= { lgpPwrBattery 16 }
lgpPwrBatteryChargeMode OBJECT-TYPE
SYNTAX INTEGER
{
float(1),
equalize(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The mode of the battery charger: 'float' charging or 'equalize'
charging."
::= { lgpPwrBattery 17 }
lgpPwrBatteryTimeRemaining OBJECT-TYPE
SYNTAX Integer32
UNITS "minutes"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An estimate of the time to battery charge depletion under the present
load conditions if the utility power is off and remains off, or if it
were to be lost and remain off.
NOTE: A UPS is expected to provide a battery time remaining value
when not operating on battery. However, if the system is not capable of
providing this information, then this point will return 65535 to
indicate that the value is unavailable."
::= { lgpPwrBattery 18 }
lgpPwrBatteryCapacity OBJECT-TYPE
SYNTAX Integer32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present percentage of battery capacity."
::= { lgpPwrBattery 19 }
lgpPwrBatteryCabinet OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree contains items related to battery cabinets."
::= { lgpPwrBattery 20 }
lgpPwrBatteryCabinetCount OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of battery cabinets installed with this device.
Note some devices may not permit writing a value to this object."
::= { lgpPwrBatteryCabinet 1 }
lgpPwrBatteryCabinetType OBJECT-TYPE
SYNTAX INTEGER
{
notSpecified(1),
internal(2),
external(3),
lrt(4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The type of battery cabinet(s) installed on this device.
Enumeration definitions:
notSpecified - The type has not been specified in the
device's configuration.
internal - Battery cabinets are internal to the device.
external - Device has external battery cabinets installed.
lrt - Long Run Time cabinets.
Note some devices may not permit writing a value to this object."
::= { lgpPwrBatteryCabinet 2 }
lgpPwrBatteryCabinetRatedCapacity OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Amp-hour"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Battery cabinet rated capacity (tenths of Amp-hours).
This assumes that each cabinet is of the same type and capacity.
This is not a sum of the rating for all attached cabinets.
Note some devices may not permit writing a value to this object."
::= { lgpPwrBatteryCabinet 3 }
lgpPwrBatteryLeadAcidCellCount OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Battery cell count - lead-acid. The number of cells that comprise
the lead acid battery string."
::= { lgpPwrBatteryCabinet 4 }
lgpPwrBatteryNiCadCellCount OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Battery cell count - nickel-cadmium. The number of cells that
comprise the nickel-cadmium battery string."
::= { lgpPwrBatteryCabinet 5 }
lgpPwrBatteryAmpHoursConsumed OBJECT-TYPE
SYNTAX Integer32
UNITS "Amp-hour"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The cumulative battery Amp-hours withdrawn over the life of the
battery. This value persists across reboots. Typically, this value is
reset back to zero when the batteries are replaced."
::= { lgpPwrBattery 21 }
lgpPwrBatteryAmpHoursDischargeConsumed OBJECT-TYPE
SYNTAX Integer32
UNITS "Amp-hour"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The battery Amp-hours withdrawn during the current/latest
discharge. This value does not persist across reboots."
::= { lgpPwrBattery 22 }
lgpPwrBatteryLastDischargeTime OBJECT-TYPE
SYNTAX Unsigned32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The date and time of the last battery discharge. Typically this is the
time when the discharge starts. This value persists across reboots.
The date and time are determined in seconds since the epoch on
January 1, 1970."
::= { lgpPwrBattery 23 }
lgpPwrBatteryLastCommissionTime OBJECT-TYPE
SYNTAX Unsigned32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The date and time when the battery system was put into service.
This information persists across system reboot events. It is the
responsibility of Service to reset this date/time when the batteries
are replaced. The date and time are determined in seconds since the
epoch on January 1, 1970."
::= { lgpPwrBattery 24 }
lgpPwrBatteryPresentDischargeTime OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total time spent on battery during the current or last discharge.
NOTE: While not discharging, some systems may display zero instead of
the last discharge."
::= { lgpPwrBattery 25 }
lgpPwrBatteryCapacityStatus OBJECT-TYPE
SYNTAX INTEGER
{
unknown(1),
batteryNormal(2),
batteryLow(3),
batteryDepleted(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The indication of the capacity remaining in the UPS
system's batteries.
NOTE: In a single-module system, this point is intended to have the same
behavior as the RFC1628 point upsBatteryStatus."
::= { lgpPwrBattery 26 }
lgpPwrBatteryCircuitBreakerState OBJECT-TYPE
SYNTAX INTEGER
{
unknown(0),
open(1),
closed(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the Battery Circuit Breaker."
::= { lgpPwrBattery 27 }
-- =============================================================================
-- lgpPwrMeasurements - Liebert Power Measurement Group
-- =============================================================================
-- -----------------------------------------------------------------------------
-- Well Known Power Measurement Points
-- -----------------------------------------------------------------------------
lgpPwrWellKnownMeasurementPoints OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree registers well known Liebert Power Measurement
Points. The object identifier names usually imply locations
where the measurement is taken -- such as 'input', 'output'
and 'bypass'."
REFERENCE
"These well known measurement identifiers are referenced in the
'lgpPwrMeasurementPointId' column in the
'lgpPwrMeasurementPointTable'."
::= { lgpPwrMeasurements 1 }
lgpPwrSource1Input OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register a source 1 input as a
well known measurement point. It is intended that no sub-trees
be created below this node.
Power input to the managed device from power source 1.
Many power systems contain more than one input source and
many of them have more than one measurement point per input
source. This identifier represents one input source for the
system but does not necessarily represent the 'first' one.
The input sources' numbering with respect to
'lgpPwrSource1Input' etc. may depend on the physical wiring
of the system when it was installed."
::= { lgpPwrWellKnownMeasurementPoints 1 }
lgpPwrSource2Input OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register a source 2 input as a
well known measurement point. It is intended that no sub-trees
be created below this node.
Power input to the managed device from power source 2.
Many power systems contain more than one input source and
many of them have more than one measurement point per input
source. This identifier represents one input source for the
system but does not necessarily represent the 'first' one.
The input sources' numbering with respect to
'lgpPwrSource2Input' etc. may depend on the physical wiring
of the system when it was installed."
::= { lgpPwrWellKnownMeasurementPoints 2 }
lgpPwrSourcePdu1Input OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register a source PDU 1 input as a
well known measurement point. It is intended that no sub-trees
be created below this node.
Power input to the managed device from power distribution
unit 1. Many power systems contain more than one input source
and many of them have more than one measurement point per input
source. This identifier represents one input source for the
system but does not necessarily represent the 'first' one.
The input sources' numbering with respect to
'lgpPwrSourcePdu1Input' etc. may depend on the physical wiring
of the system when it was installed."
::= { lgpPwrWellKnownMeasurementPoints 3 }
lgpPwrSourcePdu2Input OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register a source PDU 2 input as a
well known measurement point. It is intended that no sub-trees
be created below this node.
Power input to the managed device from power distribution
unit 1. Many power systems contain more than one input source
and many of them have more than one measurement point per input
source. This identifier represents one input source for the
system but does not necessarily represent the 'first' one.
The input sources' numbering with respect to
'lgpPwrSourcePdu2Input' etc. may depend on the physical wiring
of the system when it was installed."
::= { lgpPwrWellKnownMeasurementPoints 4 }
lgpPwrOutputToLoad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register the output to the critical
load as a well known measurement point. It is intended that
no sub-trees be created below this node."
::= { lgpPwrWellKnownMeasurementPoints 5 }
lgpPwrMeasBattery OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register a battery as a well known
measurement point. It is intended that no sub-trees be created
below this node."
::= { lgpPwrWellKnownMeasurementPoints 6 }
lgpPwrMeasBypass OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register a bypass as a well known
measurement point. It is intended that no sub-trees be created
below this node."
::= { lgpPwrWellKnownMeasurementPoints 7 }
lgpPwrMeasDcBus OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register a DC bus as a well known
measurement point. It is intended that no sub-trees be created
below this node."
::= { lgpPwrWellKnownMeasurementPoints 8 }
lgpPwrMeasSystemOutput OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register the output of a
multi-module system as a well known measurement point.
It is intended that no sub-trees be created below this node.
This identifier represents the power related data of the
system."
::= { lgpPwrWellKnownMeasurementPoints 9 }
lgpPwrMeasBatteryCabinet OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree is used to register the voltage between the
most negative and the most postive terminals of a battery
cabinet. To determine the cabinet being described in a
multi-cabinet system, this point implements an additional
two indexes. The first index describes the module the cabinet
is located in. The second index describes the cabinet
number. In an SMS(Single-Module System) the first index is
always 1.
Example: lgpPwrMeasBatteryCabinet.2.4
'lgpPwrMeasBatteryCabinet' = Point is a battery cabinet.
'.2' = Cabinet is in the second module.
'.4' = Cabinet number 4"
::= { lgpPwrWellKnownMeasurementPoints 10 }
-- -----------------------------------------------------------------------------
-- AC Power Measurement Point Table
-- -----------------------------------------------------------------------------
lgpPwrMeasurementPointTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPwrMeasurementPointEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains a list of AC power measurement point entries.
The table contains zero, one, or many rows, depending upon the number
of power related measurement points available. The NMS cannot
create or delete rows from the table. The rows are created by the
agent based upon the capabilities of the managed device. Each row
in the table represents a series of measurements on a given point
or location within the system. Measurement points/locations are
identified by the object identifier 'lgpPwrMeasurementPointId' in the
'LgpPwrMeasurementPointEntry' object. The actual measurement being
taken at that identified point is identified by the other
corresponding columns in the LgpPwrMeasurementPointEntry for the
particular row of the table."
REFERENCE
"The measurement points represented by 'lgpPwrMeasurementPointId'
can be found in the sub-tree lgpPwrWellKnownMeasurementPoints.
Additional measurement detail on a 'per line' basis is available in
the lgpPwrLineMeasurementTable"
::= { lgpPwrMeasurements 2 }
lgpPwrMeasurementPointEntry OBJECT-TYPE
SYNTAX LgpPwrMeasurementPointEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the measurements to be populated in the
various columns of the 'lgpPwrMeasurementPointTable'."
INDEX { lgpPwrMeasurementPointIndex }
::= { lgpPwrMeasurementPointTable 1 }
LgpPwrMeasurementPointEntry ::= SEQUENCE
{
lgpPwrMeasurementPointIndex Unsigned32,
lgpPwrMeasurementPointId OBJECT IDENTIFIER,
lgpPwrMeasurementPointNumLines Integer32,
lgpPwrMeasurementPointNomVolts Integer32,
lgpPwrMeasurementPointNomFrequency Integer32,
lgpPwrMeasurementPointFrequency Integer32,
lgpPwrMeasurementPointApparentPower Integer32,
lgpPwrMeasurementPointTruePower Integer32,
lgpPwrMeasurementPointPowerFactor Integer32,
lgpPwrMeasurementPointWattHours Integer32,
lgpPwrMeasurementPointVAPercent Integer32,
lgpPwrMeasurementPointNeutralCurrent Integer32,
lgpPwrMeasurementPointGroundCurrent Integer32,
lgpPwrMeasurementPointNomCurrent Integer32,
lgpPwrMeasurementPointNomPowerFactor Integer32,
lgpPwrMeasurementPointNomVA Integer32,
lgpPwrMeasurementPointNomW Integer32,
lgpPwrMeasurementPointPowerFactorTag INTEGER
}
lgpPwrMeasurementPointIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index that indicates the row of the
'lgpPwrMeasurementPointTable' for a power measurement point."
::= { lgpPwrMeasurementPointEntry 1 }
lgpPwrMeasurementPointId OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An OID representing a well known measurement point.
These object identifiers indicate a point or location of power
measurement in a power system. The OID's name usually
implies a location of the measurement point such as
'input', 'output', 'bypass' etc."
REFERENCE
"The object identifiers in this column can be found in the sub-tree
'lgpPwrWellKnownMeasurementPoints'."
::= { lgpPwrMeasurementPointEntry 2 }
lgpPwrMeasurementPointNumLines OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of lines on the indicated power measurement point.
(i.e. the number of phases on the power source being measured.)"
::= { lgpPwrMeasurementPointEntry 3 }
lgpPwrMeasurementPointNomVolts OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the nominal voltage on the power source being
measured."
::= { lgpPwrMeasurementPointEntry 4 }
lgpPwrMeasurementPointNomFrequency OBJECT-TYPE
SYNTAX Integer32
UNITS "Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal or configured/expected frequency for the power
source indicated by 'lgpPwrMeasurementPointId' in the
corresponding row in the lgpPwrMeasurementPointTable."
::= { lgpPwrMeasurementPointEntry 5 }
lgpPwrMeasurementPointFrequency OBJECT-TYPE
SYNTAX Integer32
UNITS "Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present (actual) frequency for the power source indicated
by 'lgpPwrMeasurementPointId' in the corresponding row in the
lgpPwrMeasurementPointTable."
::= { lgpPwrMeasurementPointEntry 6 }
lgpPwrMeasurementPointApparentPower OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt-Amp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present apparent AC power for the power source
indicated by 'lgpPwrMeasurementPointId' in the corresponding row
in the lgpPwrMeasurementPointTable."
::= { lgpPwrMeasurementPointEntry 7 }
lgpPwrMeasurementPointTruePower OBJECT-TYPE
SYNTAX Integer32
UNITS "Watt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present AC power for the power source indicated by
'lgpPwrMeasurementPointId' in the corresponding row in the
lgpPwrMeasurementPointTable."
::= { lgpPwrMeasurementPointEntry 8 }
lgpPwrMeasurementPointPowerFactor OBJECT-TYPE
SYNTAX Integer32
UNITS ".01 Power Factor"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present Power Factor for the power source indicated by
'lgpPwrMeasurementPointId' in the corresponding row in the
lgpPwrMeasurementPointTable."
::= { lgpPwrMeasurementPointEntry 9 }
lgpPwrMeasurementPointWattHours OBJECT-TYPE
SYNTAX Integer32
UNITS "Watt-Hour"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present number of Watt Hours for the power source indicated by
'lgpPwrMeasurementPointId' in the corresponding row in the
lgpPwrMeasurementPointTable."
::= { lgpPwrMeasurementPointEntry 10 }
lgpPwrMeasurementPointVAPercent OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the rated apparent AC power of the power
source indicated by 'lgpPwrMeasurementPointId' in the corresponding
row in the lgpPwrMeasurementPointTable."
::= { lgpPwrMeasurementPointEntry 11 }
lgpPwrMeasurementPointNeutralCurrent OBJECT-TYPE
SYNTAX Integer32
UNITS "Amp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present neutral current of the power point indicated by
'lgpPwrMeasurementPointId' in the corresponding row in the
lgpPwrMeasurementPointTable."
::= { lgpPwrMeasurementPointEntry 12 }
lgpPwrMeasurementPointGroundCurrent OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Amp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present ground current of the power point indicated by
'lgpPwrMeasurementPointId' in the corresponding row in the
lgpPwrMeasurementPointTable."
::= { lgpPwrMeasurementPointEntry 13 }
lgpPwrMeasurementPointNomCurrent OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Amp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal or configured/expected current of the power point
indicated by 'lgpPwrMeasurementPointId' in the corresponding row
in the lgpPwrMeasurementPointTable."
::= { lgpPwrMeasurementPointEntry 14 }
lgpPwrMeasurementPointNomPowerFactor OBJECT-TYPE
SYNTAX Integer32
UNITS ".01 Power Factor"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal or configured/expected power factor of the power point
indicated by 'lgpPwrMeasurementPointId' in the corresponding row
in the lgpPwrMeasurementPointTable."
::= { lgpPwrMeasurementPointEntry 15 }
lgpPwrMeasurementPointNomVA OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt-Amp"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal or configured/expected apparent AC power for the power
source indicated by 'lgpPwrMeasurementPointId' in the corresponding
row in the lgpPwrMeasurementPointTable."
::= { lgpPwrMeasurementPointEntry 16 }
lgpPwrMeasurementPointNomW OBJECT-TYPE
SYNTAX Integer32
UNITS "Watt"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal or configured/expected true AC power for the power
source indicated by 'lgpPwrMeasurementPointId' in the corresponding
row in the lgpPwrMeasurementPointTable."
::= { lgpPwrMeasurementPointEntry 17 }
lgpPwrMeasurementPointPowerFactorTag OBJECT-TYPE
SYNTAX INTEGER
{
leading(1),
lagging(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present description of the Power Factor for the power source
indicated by 'lgpPwrMeasurementPointId' in the corresponding row
in the lgpPwrMeasurementPointTable. If Leading, the load is said
to be capacitive and the phase of the current leads the voltage.
If Lagging, the load is said to be inductive and the phase of the
current lags the voltage."
::= { lgpPwrMeasurementPointEntry 19 }
-- -----------------------------------------------------------------------------
-- Source Measurement Line/Phase Table
-- -----------------------------------------------------------------------------
lgpPwrLineMeasurementTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPwrLineMeasurementEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of power measurements for each phase/line for a given
power measurement point/location in the 'lgpPwrMeasurementPointTable'.
The lgpPwrMeasurementPointIndex in this table corresponds to the
index in the lgpPwrMeasurementPointTable.
This table contains zero, one, or
many rows, depending upon the number of power line source objects
available. The NMS cannot create or delete rows from the table.
The rows are created by the agent based upon the capabilities of
the managed device."
::= { lgpPwrMeasurements 3 }
lgpPwrLineMeasurementEntry OBJECT-TYPE
SYNTAX LgpPwrLineMeasurementEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the contents of the columns for the table
'lgpPwrLineMeasurementTable'."
REFERENCE
"The lgpPwrMeasurementPointIndex can be found in the
lgpPwrMeasurementPointTable. This index identifies the measurement
point for which the line detail measurement in the table applies."
INDEX { lgpPwrMeasurementPtIndex, lgpPwrLineMeasurementIndex }
::= { lgpPwrLineMeasurementTable 1 }
LgpPwrLineMeasurementEntry ::= SEQUENCE
{
lgpPwrMeasurementPtIndex Unsigned32,
lgpPwrLineMeasurementIndex Unsigned32,
lgpPwrMeasurementPoint OBJECT IDENTIFIER,
lgpPwrLineMeasurementVoltsLL Integer32,
lgpPwrLineMeasurementVoltsLN Integer32,
lgpPwrLineMeasurementCurrent Integer32,
lgpPwrLineMeasurementCapacity Integer32,
lgpPwrLineMeasurementVA Integer32,
lgpPwrLineMeasurementTruePower Integer32,
lgpPwrLineMeasurementVoltageTHD Integer32,
lgpPwrLineMeasurementCurrentTHD Integer32,
lgpPwrLineMeasurementKFactorCurrent Integer32,
lgpPwrLineMeasurementCrestFactorCurrent Integer32,
lgpPwrLineMeasurementPowerFactor Integer32,
lgpPwrLineMeasurementPowerFactorTag INTEGER,
lgpPwrLineMeasurementMaxVolts Integer32,
lgpPwrLineMeasurementMinVolts Integer32,
lgpPwrLineMeasurementVAR Integer32,
lgpPwrLineMeasurementPercentLoad Integer32,
lgpPwrLineMeasurementVolts Integer32,
lgpPwrLineMeasurementVACapacity Integer32
}
lgpPwrMeasurementPtIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index indicating the row of the table
'lgpPwrMeasurementPointTable' for a power measurement point."
::= { lgpPwrLineMeasurementEntry 1 }
lgpPwrLineMeasurementIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index indicating the row of the table
'lgpPwrLineMeasurementTable' for a power measurement point."
::= { lgpPwrLineMeasurementEntry 2 }
lgpPwrMeasurementPoint OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An OID representing a well known measurement point.
These object identifiers indicate a point or location of power
measurement in a power system. The OID name usually
implies a location of the measurement point such as
'input', 'output', 'bypass', etc."
REFERENCE
"The object identifiers in this column can be found in the sub-tree
'lgpPwrWellKnownMeasurementPoints' and correspond to the entry in
the table lgpPwrMeasurementPointTable."
::= { lgpPwrLineMeasurementEntry 3 }
lgpPwrLineMeasurementVoltsLL OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present Line-to-Line voltage measurement for the indicated
source. The line being measured is given by the
lgpPwrLineMeasurementIndex [1 = AB, 2 = BC, 3 = CA]."
::= { lgpPwrLineMeasurementEntry 4 }
lgpPwrLineMeasurementVoltsLN OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present Line-to-neutral voltage measurement for the indicated
source. The line being measured is given by the
lgpPwrLineMeasurementIndex where [1 = A, 2 = B, 3 = C]."
::= { lgpPwrLineMeasurementEntry 5 }
lgpPwrLineMeasurementCurrent OBJECT-TYPE
SYNTAX Integer32
UNITS "Amp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present current measurement for the indicated source. The line
being measured is given by the 'lgpPwrLineMeasurementIndex' where
[1 = A, 2 = B, 3 = C]."
::= { lgpPwrLineMeasurementEntry 6 }
lgpPwrLineMeasurementCapacity OBJECT-TYPE
SYNTAX Integer32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the power capacity presently being used on this
line."
::= { lgpPwrLineMeasurementEntry 7 }
lgpPwrLineMeasurementVA OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt-Amp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present apparent AC line power."
::= { lgpPwrLineMeasurementEntry 8 }
lgpPwrLineMeasurementTruePower OBJECT-TYPE
SYNTAX Integer32
UNITS "Watt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present AC line power measured in watts."
::= { lgpPwrLineMeasurementEntry 9 }
lgpPwrLineMeasurementVoltageTHD OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present total harmonic distortion on the AC line voltage."
::= { lgpPwrLineMeasurementEntry 10 }
lgpPwrLineMeasurementCurrentTHD OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present total harmonic distortion on the AC line current."
::= { lgpPwrLineMeasurementEntry 11 }
lgpPwrLineMeasurementKFactorCurrent OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 K Factor"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present line K Factor."
::= { lgpPwrLineMeasurementEntry 12 }
lgpPwrLineMeasurementCrestFactorCurrent OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Crest Factor"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present crest factor of the line current."
::= { lgpPwrLineMeasurementEntry 13 }
lgpPwrLineMeasurementPowerFactor OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Power Factor"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present Power Factor for the line."
::= { lgpPwrLineMeasurementEntry 14 }
lgpPwrLineMeasurementPowerFactorTag OBJECT-TYPE
SYNTAX INTEGER
{
leading(1),
lagging(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present description of the Power Factor for the line. If
Leading, the load is said to be capacitive and the phase of the
current leads the voltage. If Lagging, the load is said to be
inductive and the phase of the current lags the voltage."
::= { lgpPwrLineMeasurementEntry 15 }
lgpPwrLineMeasurementMaxVolts OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum voltage measurement recorded for the indicated source
since the command 'lgpPwrStatisticsReset' was executed."
::= { lgpPwrLineMeasurementEntry 16 }
lgpPwrLineMeasurementMinVolts OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minimum voltage measurement recorded for the
indicated source since the command 'lgpPwrStatisticsReset' was
executed."
::= { lgpPwrLineMeasurementEntry 17 }
lgpPwrLineMeasurementVAR OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt-Amp-Reactive"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present reactive AC line power of the power source indicated by
'lgpPwrMeasurementPoint'."
::= { lgpPwrLineMeasurementEntry 18 }
lgpPwrLineMeasurementPercentLoad OBJECT-TYPE
SYNTAX Integer32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present percent load of the AC line power."
::= { lgpPwrLineMeasurementEntry 19 }
lgpPwrLineMeasurementVolts OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present voltage measurement for the indicated source."
::= { lgpPwrLineMeasurementEntry 20 }
lgpPwrLineMeasurementVACapacity OBJECT-TYPE
SYNTAX Integer32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the apparent power capacity presently being
used on this line."
::= { lgpPwrLineMeasurementEntry 21 }
-- -----------------------------------------------------------------------------
-- DC Power Measurement Point Table
-- -----------------------------------------------------------------------------
lgpPwrDcMeasurementPointTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPwrDcMeasurementPointEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This table contains a list of DC power measurement point entries.
The table contains zero, one, or many rows, depending upon the number
of power related measurement points available. The NMS cannot
create or delete rows from the table. The rows are created by the
agent based upon the capabilities of the managed device. Each row
in the table represents a series of measurements on a given point
or location within the system. Measurement points/locations are
identified by the object identifier 'lgpPwrDcMeasurementPointId' in the
'LgpPwrDcMeasurementPointEntry' object. The actual measurement being
taken at that identified point is identified by the other
corresponding columns in the LgpPwrDcMeasurementPointEntry for the
particular row of the table."
REFERENCE
"The measurement points represented by 'lgpPwrDcMeasurementPointId'
can be found in the sub-tree lgpPwrWellKnownMeasurementPoints.
Additional measurement detail on a 'per line' basis is available in
the lgpPwrLineMeasurementTable"
::= { lgpPwrMeasurements 4 }
lgpPwrDcMeasurementPointEntry OBJECT-TYPE
SYNTAX LgpPwrDcMeasurementPointEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the measurements to be populated in the
various columns of the 'lgpPwrDcMeasurementPointTable'."
INDEX { lgpPwrDcMeasurementPointIndex }
::= { lgpPwrDcMeasurementPointTable 1 }
LgpPwrDcMeasurementPointEntry ::= SEQUENCE
{
lgpPwrDcMeasurementPointIndex Unsigned32,
lgpPwrDcMeasurementPointId OBJECT IDENTIFIER,
lgpPwrDcMeasurementPointSubID Integer32,
lgpPwrDcMeasurementPointVolts Integer32,
lgpPwrDcMeasurementPointCurrent Integer32,
lgpPwrDcMeasurementPointNomVolts Integer32,
lgpPwrDcMeasurementPointTruePower Integer32
}
lgpPwrDcMeasurementPointIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index that indicates the row of the
'lgpPwrMeasurementPointTable' for a power measurement point."
::= { lgpPwrDcMeasurementPointEntry 1 }
lgpPwrDcMeasurementPointId OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An OID representing a well known measurement point.
These object identifiers indicate a point or location of power
measurement in a power system. The OID's name usually
implies a location of the measurement point such as
'input', 'output', 'bypass' etc."
REFERENCE
"The object identifiers in this column can be found in the sub-tree
'lgpPwrWellKnownMeasurementPoints'."
::= { lgpPwrDcMeasurementPointEntry 2 }
lgpPwrDcMeasurementPointSubID OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The identifier used to differentiate between identical thresholds
for a given point index and point ID in the DC measurements table."
::= { lgpPwrDcMeasurementPointEntry 3 }
lgpPwrDcMeasurementPointVolts OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present DC voltage for the power source indicated by
'lgpPwrDcMeasurementPointId' in the corresponding row in the
lgpPwrDcMeasurementPointTable."
::= { lgpPwrDcMeasurementPointEntry 4 }
lgpPwrDcMeasurementPointCurrent OBJECT-TYPE
SYNTAX Integer32
UNITS "Amp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present DC current for the power source indicated by
'lgpPwrDcMeasurementPointId' in the corresponding row in the
lgpPwrDcMeasurementPointTable."
::= { lgpPwrDcMeasurementPointEntry 5 }
lgpPwrDcMeasurementPointNomVolts OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal(configured/expected) DC voltage for the power source
indicated by 'lgpPwrDcMeasurementPointId' in the
corresponding row in the lgpPwrDcMeasurementPointTable."
::= { lgpPwrDcMeasurementPointEntry 6 }
lgpPwrDcMeasurementPointTruePower OBJECT-TYPE
SYNTAX Integer32
UNITS "Watt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present DC power for the power source indicated by
'lgpPwrDcMeasurementPointId' in the corresponding row in the
lgpPwrDcMeasurementPointTable."
::= { lgpPwrDcMeasurementPointEntry 7 }
-- -----------------------------------------------------------------------------
-- Well Known Power Measurement Types
-- -----------------------------------------------------------------------------
lgpPwrWellKnownMeasurementTypes OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree registers well known Liebert Power Measurement
Types. The object identifier names usually encompass units of
measure, lines of reference, and device location. The OID's
name usually implies a measurement type such as 'voltsAC',
'current', 'voltsDc', 'VoltsLL', etc."
::= { lgpPwrMeasurements 5 }
lgpPwrVoltsAc OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents an AC voltage."
::= { lgpPwrWellKnownMeasurementTypes 1 }
lgpPwrVoltsDc OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents a DC voltage."
::= { lgpPwrWellKnownMeasurementTypes 2 }
lgpPwrAmpsNeutral OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This identifier represents a current measurement in Amps on the
neutral line."
::= { lgpPwrWellKnownMeasurementTypes 3 }
-- -----------------------------------------------------------------------------
-- lgpPwrControl - Liebert Control Group
-- -----------------------------------------------------------------------------
lgpPwrWellKnownControlPoints OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This sub-tree registers well known Liebert Power Control
Points. The object identifier names usually imply locations
where control of a device is available -- such 'output' or
'load circuits'."
REFERENCE
"These well known control identifiers are referenced in the
'lgpPwrLoadCircuitId' column in the
'lgpPwrLoadCircuitTable'."
::= { lgpPwrControl 1 }
lgpPwrLoadCircuit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The managed device's controllable load circuit.
Many power systems contain more than one load circuit.
This identifier represents one load circuit for the
system but does not necessarily represent the 'first' one.
The load circuits' numbering with respect to
'lgpPwrLoadCircuit1' etc. may depend on the physical wiring
of the system when it was installed."
::= { lgpPwrWellKnownControlPoints 1 }
-- -----------------------------------------------------------------------------
-- Load Circuit Table
-- -----------------------------------------------------------------------------
lgpPwrLoadCircuitTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPwrLoadCircuitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of load circuits that can be controlled(opened or closed).
The NMS cannot create or delete rows from the table.
The rows are created by the agent based upon the capabilities of
the managed device."
::= { lgpPwrControl 2 }
lgpPwrLoadCircuitEntry OBJECT-TYPE
SYNTAX LgpPwrLoadCircuitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the contents of the columns for the table
'lgpPwrLoadCircuitTable'."
INDEX { lgpPwrLoadCircuitIndex }
::= { lgpPwrLoadCircuitTable 1 }
LgpPwrLoadCircuitEntry ::= SEQUENCE
{
lgpPwrLoadCircuitIndex Unsigned32,
lgpPwrLoadCircuitId OBJECT IDENTIFIER,
lgpPwrLoadCircuitSubID Unsigned32,
lgpPwrLoadCircuitState INTEGER,
lgpPwrLoadCircuitStateAndControl INTEGER
}
lgpPwrLoadCircuitIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index indicating the row of the table
'lgpPwrLoadCircuitTable'."
::= { lgpPwrLoadCircuitEntry 1 }
lgpPwrLoadCircuitId OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An OID representing a well known load circuit identifier.
These load circuit identifiers indicate the name or type of load
circuit reference in the table."
REFERENCE
"The object identifiers in this column can be found in the sub-tree
'lgpPwrWellKnownMeasurementPoints'."
::= { lgpPwrLoadCircuitEntry 2 }
lgpPwrLoadCircuitSubID OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is a sub identifier for the 'lgpPwrLoadCircuitId'.
It indicates the hardware identifier of the load control circuit."
::= { lgpPwrLoadCircuitEntry 3 }
lgpPwrLoadCircuitState OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2),
default(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This identifier indicates the state of the load circuit.
When read, only a closed or open response will be returned.
When written to, the state of the circuit will transition to
desired state."
::= { lgpPwrLoadCircuitEntry 4 }
lgpPwrLoadCircuitStateAndControl OBJECT-TYPE
SYNTAX INTEGER
{
off(0),
on(1),
reboot(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This identifier indicates the state of the load circuit.
When read, only a closed or open response will be returned.
When written to, the state of the circuit will transition to
desired state."
::= { lgpPwrLoadCircuitEntry 5 }
lgpPwrAlarmSilence OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Audible Alarm Silence Command. This command turns off the device's
audible alarm. It will not affect the status of the alarm(s) that
caused the audible alarm. This command should be sent with a
parameter of 1. This variable doesn't return a value when read."
::= { lgpPwrControl 3 }
lgpPwrBatteryTest OBJECT-TYPE
SYNTAX INTEGER
{
start(1),
abort(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Battery Test Command. This command will initiate a battery test if
one is not already in progress, or abort the current test if it is in
progress."
::= { lgpPwrControl 4 }
lgpPwrUpsAbortCommand OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"UPS Abort command. This command will abort the pending command on the
device. There is no guarantee a client using the abort command will
cancel a command sent moments before from the same client.
Another client could initiate a command and change what command is
actually pending on the device. This command should be sent with a
parameter of 1. This variable doesn't return a value when read."
::= { lgpPwrControl 5 }
lgpPwrTransferToBypass OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Transfer to Bypass Command. This command will initiate a transfer of
the load to the bypass of the system. This command should be sent with a
parameter of 1. This variable doesn't return a value when read."
::= { lgpPwrControl 6 }
lgpPwrTransferToInverter OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Transfer to Inverter Command. This command will initiate a transfer
of the load to the inverter of the system. This command should be sent
with a parameter of 1. This variable doesn't return a value when read."
::= { lgpPwrControl 7 }
lgpPwrOutputOnDelay OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Output On Delay Command. This command will turn on the output of the
device after a user specified delay. The number of seconds to delay
is subject to the precision of the device and should be kept to 10
second intervals."
::= { lgpPwrControl 8 }
lgpPwrOutputOffDelayWithRestart OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Output Off Delay with Restart Command. This command will turn off the
output of the device after a user specified delay. The number
of seconds to delay is subject to the precision of the device and
should be kept to 10 second intervals. The device will then
turn the output on again after a specified amount of time. "
::= { lgpPwrControl 9 }
lgpPwrOutputOffDelayWithoutRestart OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Output Off Delay without Restart Command. This command will turn off
the output of the device after a specified delay. The number of seconds
to delay is subject to the precision of the device and should be kept
to 10 second intervals. The device will NOT automatically turn the
output on following this command."
::= { lgpPwrControl 10 }
-- =============================================================================
-- lgpPwrStatus - Liebert Power Status Group
-- =============================================================================
lgpPwrTransferCount OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of times that the output load has been transferred between the
available input sources."
::= { lgpPwrStatus 1 }
lgpPwrAutoTransferTimer OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The required wait time between output load auto transfer attempts
between available input sources."
::= { lgpPwrStatus 2 }
lgpPwrAutoReTransferEnabled OBJECT-TYPE
SYNTAX INTEGER
{
no (0),
yes (1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ability to retransfer the output load automatically to the well
known measurement source from the 'lgpPwrWellKnownMeasurements'
sub-tree that is the preferred input source of the system"
::= { lgpPwrStatus 3 }
lgpPwrSyncPhaseAngle OBJECT-TYPE
SYNTAX Integer32(-3600..3600)
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The phase angle difference of source 1 in relation to source 2."
::= { lgpPwrStatus 4 }
lgpPwrParallelSystemOutputToLoadSource OBJECT-TYPE
SYNTAX INTEGER
{
unknown (0),
utility (1),
battery (2),
bypass (3),
none (4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The source supporting the parallel system's load."
::= { lgpPwrStatus 5 }
lgpPwrDcToDcConverter OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the DC to DC converter."
::= { lgpPwrStatus 6 }
lgpPwrOutputToLoadOnInverter OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present source of output power is the Inverter."
::= { lgpPwrStatus 7 }
lgpPwrBatteryChargeCompensating OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system is adjusting the battery charging algorithm to accommodate
for the battery temperature."
::= { lgpPwrStatus 8 }
lgpPwrInverterReady OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ability of the inverter to support the output load of the system."
::= { lgpPwrStatus 9 }
lgpPwrOutputToLoadOnBypass OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present source of output power is the Bypass."
::= { lgpPwrStatus 10 }
lgpPwrBoost OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the boost circuitry"
::= { lgpPwrStatus 11 }
lgpPwrBuck OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the buck circuitry"
::= { lgpPwrStatus 12 }
lgpPwrShutdownOverTemperature OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system has previously shutdown due to an over temperature
condition."
::= { lgpPwrStatus 13 }
lgpPwrShutdownOverload OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system has previously shutdown due to an over load condition."
::= { lgpPwrStatus 14 }
lgpPwrShutdownDcBusOverload OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system has previously shutdown due to a DC bus over load
condition."
::= { lgpPwrStatus 15 }
lgpPwrShutdownOutputShort OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system has previously shutdown due to an output short condition."
::= { lgpPwrStatus 16 }
lgpPwrShutdownLineSwap OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system has previously shutdown due to a condition where the line
and neutral were reversed."
::= { lgpPwrStatus 17 }
lgpPwrShutdownLowBattery OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system has previously shutdown due to a low battery condition."
::= { lgpPwrStatus 18 }
lgpPwrShutdownRemote OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system has previously shutdown due to a remote shutdown command."
::= { lgpPwrStatus 19 }
lgpPwrShutdownInputUnderVoltage OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system has previously shutdown due to an under voltage condition
during startup."
::= { lgpPwrStatus 20 }
lgpPwrShutdownPowerFactorCorrectionFailure OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system has previously shutdown due to a power factor correction
startup failure."
::= { lgpPwrStatus 21 }
lgpPwrShutdownHardware OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system has previously shutdown due external shutdown signal."
::= { lgpPwrStatus 22 }
lgpPwrRedundantSubModule OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system has a redundant battery module installed."
::= { lgpPwrStatus 23 }
lgpPwrBypassReady OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ability of the bypass to support the output load of the system.
If Yes, the bypass is available to transfer to."
::= { lgpPwrStatus 24 }
lgpPwrGeneratorStatus OBJECT-TYPE
SYNTAX INTEGER
{
connected(1),
disconnected(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the system generator."
::= { lgpPwrStatus 25 }
lgpPwrRotaryBreakerStatus OBJECT-TYPE
SYNTAX INTEGER
{
unknown(1),
closed(2),
test(3),
normal(4),
bypass(5),
maintenance(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the system rotary breaker."
::= { lgpPwrStatus 26 }
lgpPwrPowerFactorCorrection OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the power factor correction circuitry of the system."
::= { lgpPwrStatus 27 }
lgpPwrBypassSyncDiff OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The phase angle difference between the inverter output and bypass
source. A positive value means the inverter leads the bypass source.
A negative value means the inverter lags the bypass source."
::= { lgpPwrStatus 28 }
lgpPwrBypassOverloadShutdownTime OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The calculated time remaining before bypass static switch shutdown due
to the present overload condition. If the bypass is not in an overload
condition, this object returns -1."
::= { lgpPwrStatus 29 }
lgpPwrInverterOverloadShutdownTime OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The calculated time remaining before inverter shutdown. The calculated
time of inverter operation remaining for the present overload event.
Note: If the inverter is not experiencing an overload event this point
will return 65535 indicating this value is unavailable."
::= { lgpPwrStatus 30 }
lgpPwrStateOutputSource OBJECT-TYPE
SYNTAX INTEGER
{
none(1),
inverter(2),
bypass(3),
maintenanceBypass(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The UPS's output power source (inverter, bypass, or none).
NOTE: It is possible that the load still has power from the
Maintenance Bypass."
::= { lgpPwrStatus 31 }
lgpPwrStateInputSource OBJECT-TYPE
SYNTAX INTEGER
{
none(1),
utility(2),
generator(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system input power source (none, utility, generator)."
::= { lgpPwrStatus 32 }
lgpPwrStateInputQualification OBJECT-TYPE
SYNTAX INTEGER
{
fail(1),
marginalLow(2),
normal(3),
marginalHigh(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the system input. The unit may or may not operate
normally under 'marginalLow' and 'marginalHigh' states."
::= { lgpPwrStatus 33 }
lgpPwrStateBypassStaticSwitchState OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the bypass static switch."
::= { lgpPwrStatus 34 }
lgpPwrStateBypassQualification OBJECT-TYPE
SYNTAX INTEGER
{
fail(1),
marginalLow(2),
normal(3),
marginalHigh(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current operational state of the bypass static switch. The unit may
or may not operate normally under 'marginalLow' and 'marginalHigh'
states."
::= { lgpPwrStatus 35 }
lgpPwrStateDCBusQualification OBJECT-TYPE
SYNTAX INTEGER
{
fail(1),
marginalLow(2),
normal(3),
marginalHigh(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current operational state of the DC bus. The unit may or may not
operate normally under 'marginalLow' and 'marginalHigh' states."
::= { lgpPwrStatus 36 }
lgpPwrStateOutQualification OBJECT-TYPE
SYNTAX INTEGER
{
fail(1),
marginalLow(2),
normal(3),
marginalHigh(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current operational state of the output. The unit may or may not
operate normally under 'marginalLow' and 'marginalHigh' states."
::= { lgpPwrStatus 37 }
lgpPwrStateInverterQualification OBJECT-TYPE
SYNTAX INTEGER
{
fail(1),
marginalLow(2),
normal(3),
marginalHigh(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current operational state of the inverter. The unit may or may not
operate normally under 'marginalLow' and 'marginalHigh' states."
::= { lgpPwrStatus 38 }
lgpPwrStateInverterState OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the inverter."
::= { lgpPwrStatus 39 }
lgpPwrStateRectifierState OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the rectifier."
::= { lgpPwrStatus 40 }
lgpPwrStateModuleGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This group contains UPS module information."
::= { lgpPwrStatus 41 }
lgpPwrStateUpsModuleCount OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Number of UPS modules in the system. In a single module system, this
value is one."
::= { lgpPwrStateModuleGroup 1 }
lgpPwrStateUpsModuleRedundantCount OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of redundant UPS modules in the system. In a single module
system, the value is zero. This value is dependent upon the present
load and the number of modules (i.e. the value may change during normal
operation based upon a load change). This value represents the number
of extra modules above the minimum needed to support the load."
::= { lgpPwrStateModuleGroup 2 }
lgpPwrStateBackfeedBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the Static Bypass Switch Line Disconnect Breaker."
::= { lgpPwrStatus 42 }
lgpPwrStateLoadDisconnectState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the Static Bypass Switch Load Disconnect Breaker."
::= { lgpPwrStatus 43 }
lgpPwrStateInputBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the Input Disconnect Breaker."
::= { lgpPwrStatus 44 }
lgpPwrStateTrapFilterBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the Trap Filter Disconnect Breaker."
::= { lgpPwrStatus 45 }
lgpPwrStateInvOutputBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the Inverter Output Disconnect Breaker."
::= { lgpPwrStatus 46 }
lgpPwrStateIntBypassBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the Internal Bypass Breaker."
::= { lgpPwrStatus 47 }
lgpPwrStateBypassIsolBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the Bypass Isolation Breaker."
::= { lgpPwrStatus 48 }
lgpPwrStateRectifierIsolBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the Rectifier Isolation Breaker."
::= { lgpPwrStatus 49 }
lgpPwrStateMaintBypassBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the Maintenance Bypass Breaker."
::= { lgpPwrStatus 50 }
lgpPwrStateMaintIsolBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the Maintenance Isolation Breaker."
::= { lgpPwrStatus 51 }
lgpPwrStateOutStaticSwState OBJECT-TYPE
SYNTAX INTEGER
{
off(1),
on(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the Output Series Static Switch."
::= { lgpPwrStatus 52 }
lgpPwrStateModuleOutBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the Module Output Breaker."
::= { lgpPwrStatus 53 }
lgpPwrBypassReXfrRemainTime OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The time remaining before an inverter overload or inverter fault can
be cleared and auto retransfer from the bypass to the inverter can take
place.
Note: If an inverter overload or fault is not taking place, this point
will return 65535."
::= { lgpPwrStatus 54 }
lgpPwrStateUpsOutputSource OBJECT-TYPE
SYNTAX INTEGER
{
other(1),
none(2),
normal(3),
bypass(4),
battery(5),
booster(6),
reducer(7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker.
NOTE: In a single-module system, this point is intended to have the same
behavior as the RFC1628 point upsOutputSource."
::= { lgpPwrStatus 55 }
lgpPwrStateLoadBusSynchronization OBJECT-TYPE
SYNTAX INTEGER
{
unknown(0),
active(1),
abnormal(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The state of the Load Bus Synchronizer (LBS)."
::= { lgpPwrStatus 56 }
lgpPwrStateCircuitBrkrStateGroup OBJECT-IDENTITY
STATUS current
DESCRIPTION
"This group contains Static Switch circuit breaker state information."
::= { lgpPwrStatus 57 }
lgpPwrStateSource1InputBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The states of Source 1 Input Breaker."
::= { lgpPwrStateCircuitBrkrStateGroup 1 }
lgpPwrStateSource2InputBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The states of Source 2 Input Breaker."
::= { lgpPwrStateCircuitBrkrStateGroup 2 }
lgpPwrStateSource1BypassBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The states of Source 1 Bypass Breaker."
::= { lgpPwrStateCircuitBrkrStateGroup 3 }
lgpPwrStateSource2BypassBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The states of Source 2 Bypass Breaker."
::= { lgpPwrStateCircuitBrkrStateGroup 4 }
lgpPwrStateOutputBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The states of Output Breaker."
::= { lgpPwrStateCircuitBrkrStateGroup 5 }
lgpPwrStateAuxOutputBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The states of Auxiliary Output Breaker."
::= { lgpPwrStateCircuitBrkrStateGroup 6 }
lgpPwrStateSource1PduInputBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The states of Source 1 PDU Input Breaker."
::= { lgpPwrStateCircuitBrkrStateGroup 7 }
lgpPwrStateSource2PduInputBrkrState OBJECT-TYPE
SYNTAX INTEGER
{
open(1),
closed(2),
notInstalled(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The states of Source 2 PDU Input Breaker."
::= { lgpPwrStateCircuitBrkrStateGroup 8 }
lgpPwrEconomicOperation OBJECT-TYPE
SYNTAX INTEGER
{
off(0),
on(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of ECO mode operation,
on(1) if system is on bypass due to ECO mode operation,
off(0) any other time."
::= { lgpPwrStatus 58 }
-- =============================================================================
-- lgpPwrSettings - Liebert Power Settings Group
-- =============================================================================
lgpPwrPreferredSource OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The well known measurement source from the
'lgpPwrWellKnownMeasurements' sub-tree that is the preferred
input source of the system."
::= { lgpPwrSettings 1 }
lgpPwrLoadOnSource OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The well known measurement source from the
'lgpPwrWellKnownMeasurements' sub-tree that is currently
powering the output (load)."
::= { lgpPwrSettings 2 }
lgpPwrNominalVoltageDeviation OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal voltage deviation between the well known
measurement source lgpPwrSource1Input and lgpPwrSource2Input."
::= { lgpPwrSettings 3 }
lgpPwrNominalVoltageDeviationPercent OBJECT-TYPE
SYNTAX Integer32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the nominal voltage deviation between the well known
measurement source lgpPwrSource1Input and lgpPwrSource2Input."
::= { lgpPwrSettings 4 }
lgpPwrPhaseDifferenceLimit OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Degrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum phase difference (between the well known
input sources ) in which a transfer to an available input source is
permitted."
::= { lgpPwrSettings 5 }
lgpPwrFrequencyDeviationLimit OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum frequency deviation (between the well known
input sources ) in which a transfer to an available input source is
permitted."
::= { lgpPwrSettings 6 }
-- -----------------------------------------------------------------------------
-- Thresholds Table
-- -----------------------------------------------------------------------------
lgpPwrThresholdTable OBJECT-TYPE
SYNTAX SEQUENCE OF LgpPwrThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of power thresholds for a given power measurement at a
point/location in the system.
The lgpPwrThresholdType in this table corresponds to the
type of measurement the high and low thresholds applies to.
This table contains zero, one, or many rows, depending upon the number
of 'lgpPwrThresholdPoint' and 'lgpPwrThresholdSubID' available in the
table.
The NMS cannot create or delete rows from the table.
The rows are created by the agent based upon the capabilities of
the managed device."
::= { lgpPwrSettings 7 }
lgpPwrThresholdEntry OBJECT-TYPE
SYNTAX LgpPwrThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This entry defines the contents of the columns for the table
'lgpPwrThresholdTable'."
REFERENCE
"The lgpPwrThresholdType in this table corresponds to the
type of measurement the high and low thresholds applies to."
INDEX { lgpPwrThresholdIndex }
::= { lgpPwrThresholdTable 1 }
LgpPwrThresholdEntry ::= SEQUENCE
{
lgpPwrThresholdIndex Unsigned32,
lgpPwrThresholdPoint OBJECT IDENTIFIER,
lgpPwrThresholdSubID Unsigned32,
lgpPwrThresholdType OBJECT IDENTIFIER,
lgpPwrThresholdHighWarning Integer32,
lgpPwrThresholdHighFailure Integer32,
lgpPwrThresholdLowWarning Integer32,
lgpPwrThresholdLowFailure Integer32
}
lgpPwrThresholdIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"This is the index indicating the row of the table
'lgpPwrLineMeasurementTable' for a power measurement point."
::= { lgpPwrThresholdEntry 1 }
lgpPwrThresholdPoint OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An OID representing a well known measurement point.
These object identifiers indicate a point or location of power
measurement in a power system. The OID's name usually
implies a location of the measurement point such as
'input', 'output', 'bypass' etc."
REFERENCE
"The object identifiers in this column can be found in the sub-tree
'lgpPwrWellKnownMeasurementPoints' and correspond to the
entry in the table 'lgpPwrThresholdTable'."
::= { lgpPwrThresholdEntry 2 }
lgpPwrThresholdSubID OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This is a sub identifier for the 'lgpPwrThresholdPoint'.
It indicates the instance number of the well known threshold point."
::= { lgpPwrThresholdEntry 3 }
lgpPwrThresholdType OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An OID representing a well known measurement type.
These object identifiers indicate the type of measurement referenced
by the row of the table. These object identifiers can encompass
units of measure, lines of reference, and device location.
The OID's name usually implies a measurement type such as
'voltsAc', 'current', 'voltsDc', 'VoltsLL', etc."
REFERENCE
"The object identifiers in this column can be found in the sub-tree
'lgpPwrWellKnownThresholdTypes' and correspond to the
entry in the table lgpPwrThresholdTable."
::= { lgpPwrThresholdEntry 4 }
lgpPwrThresholdHighWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The high warning threshold of a type of measurement designated by
the 'lgpPwrThresholdType' at a location designated by the
'lgpPwrThresholdPoint'. If multiple thresholds are available at a
single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType',
then the 'lgpPwrThresholdSubID' will differentiate between them.
When this threshold is met, the agent will send a notification."
::= { lgpPwrThresholdEntry 5 }
lgpPwrThresholdHighFailure OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The high failure threshold of a type of measurement designated by
the 'lgpPwrThresholdType' at a location designated by the
'lgpPwrThresholdPoint'. If multiple thresholds are available at a
single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType',
then the 'lgpPwrThresholdSubID' will differentiate between them.
When this threshold is met, the agent will send a notification."
::= { lgpPwrThresholdEntry 6 }
lgpPwrThresholdLowWarning OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The low warning threshold of a type of measurement designated by
the 'lgpPwrThresholdType' at a location designated by the
'lgpPwrThresholdPoint'. If multiple thresholds are available at a
single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType',
then the 'lgpPwrThresholdSubID' will differentiate between them.
When this threshold is met, the agent will send a notification."
::= { lgpPwrThresholdEntry 7 }
lgpPwrThresholdLowFailure OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The low failure threshold of a type of measurement designated by
the 'lgpPwrThresholdType' at a location designated by the
'lgpPwrThresholdPoint'. If multiple thresholds are available at a
single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType',
then the 'lgpPwrThresholdSubID' will differentiate between them.
When this threshold is met, the agent will send a notification."
::= { lgpPwrThresholdEntry 8 }
lgpPwrUpsAutoRestart OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The device will automatically restart when utility power is restored
following a battery discharge."
::= { lgpPwrSettings 8 }
lgpPwrUpsAutoRestartDelay OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The device will automatically delay a certain number of seconds and
then restart after utility power is restored following a battery
discharge. The number of seconds to delay is subject to the precision
of the device and should be kept to 10 second intervals."
::= { lgpPwrSettings 9 }
lgpPwrAutoRestartBatteryChargeThreshold OBJECT-TYPE
SYNTAX Integer32
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The battery charge percentage required before the device can
automatically restart."
::= { lgpPwrSettings 10 }
lgpPwrParallelModuleCount OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of modules in the parallel system."
::= { lgpPwrSettings 11 }
lgpPwrParallelRedundancyCount OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of redundant modules in the parallel system."
::= { lgpPwrSettings 12 }
lgpPwrLoadBusSyncMode OBJECT-TYPE
SYNTAX INTEGER
{
master(1),
slave(2),
none(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The configuration of Load Bus Synchronization (LBS) between
independent systems."
::= { lgpPwrSettings 13 }
lgpPwrEconomicOperationMode OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The configuration of the economic operation mode of the system."
::= { lgpPwrSettings 14 }
lgpPwrAutomaticBatteryTest OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Automatic battery test option. If enabled, the battery will be tested
on a fixed interval. If disabled, the battery test must be initiated
by a battery test command. The interval at which a battery test is
performed is defined by 'lgpPwrAutomaticBatteryTestInterval'."
::= { lgpPwrSettings 15 }
lgpPwrMinimumRedundantPowerModule OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum number of redundant power modules that must be present
before sending a loss of power redundancy alarm. If 0, there is no
redundant power functionality."
::= { lgpPwrSettings 16 }
lgpPwrMinimumRedundantBatteryModule OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum number of redundant battery modules that must be present
before sending an alarm. If 0, the redundant battery module alarm is
disabled."
::= { lgpPwrSettings 17 }
lgpPwrOutputToLoadUserOverloadLimit OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt-Amp"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This is the user specified maximum load the device can support
without sending an alarm."
::= { lgpPwrSettings 18 }
lgpPwrNoLoadWarningLimit OBJECT-TYPE
SYNTAX Integer32
UNITS "Amp"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum current draw on the output in which the device considers
there to be a load present on the output. The condition
lgpConditionWarningNoLoadDetected will be triggered if the output
current falls below this value. If this value is '-1' then the
lgpConditionNoLoadDetectedWarning condition is 'disabled'."
::= { lgpPwrSettings 19 }
lgpPwrNoLoadWarningDelay OBJECT-TYPE
SYNTAX Integer32(0..10000)
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The amount of time to delay before annunciation of the condition
lgpConditionNoLoadDetectedWarning after the output current load
falls below the threshold lgpPwrOutputNoLoadWarningLimit."
::= { lgpPwrSettings 20 }
lgpPwrEconomicOperationModeControl OBJECT-TYPE
SYNTAX INTEGER
{
disabled(0),
mode1(1),
mode2(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The configuration of the economic operation mode of the system.
Note that this supersedes lgpPwrEconomicOperationMode in newer devices."
::= { lgpPwrSettings 21 }
-- =============================================================================
-- lgpPwrStatistic - Liebert Power Statistic Group
-- =============================================================================
lgpPwrBrownOutCount OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of occurrences where the input line voltage has fallen below
a pre-determined threshold for a specified amount of time. This number
resets when the command 'lgpPwrStatisticsReset' is executed."
::= { lgpPwrStatistic 1 }
lgpPwrBlackOutCount OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of occurrences where there is a total loss of electric power.
This number resets when the command 'lgpPwrStatisticsReset' is
executed."
::= { lgpPwrStatistic 2 }
lgpPwrTransientCount OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of occurrences where the input line voltage spikes above a
pre-determined threshold for a specified amount of time. This number
resets when the command 'lgpPwrStatisticsReset' is executed."
::= { lgpPwrStatistic 3 }
lgpPwrBatteryDischargeCount OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of battery discharges since the last reset."
::= { lgpPwrStatistic 4 }
lgpPwrBatteryDischargeTime OBJECT-TYPE
SYNTAX Integer32
UNITS "minutes"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total accumulated time spent on battery since the last reset."
::= { lgpPwrStatistic 5 }
lgpPwrBatteryAmpHours OBJECT-TYPE
SYNTAX Integer32
UNITS "Amp-hour"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total accumulated Amp-hours removed from the battery since last
reset."
::= { lgpPwrStatistic 6 }
lgpPwrBatteryWattHours OBJECT-TYPE
SYNTAX Integer32
UNITS "Watt-Hour"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total accumulated Watt-Hours removed from the battery since last
reset. This command should be sent with a parameter of 1. This
variable doesn't return a value when read."
::= { lgpPwrStatistic 7 }
lgpPwrBatteryStatisticsReset OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Battery statistics clear command. The command to reset all battery
statistics stored by the device. This command should be sent with a
parameter of 1. This variable doesn't return a value when read."
::= { lgpPwrStatistic 8 }
lgpPwrStatisticsReset OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reset Power Statistics Command. This command will reset the power
statistics stored in the system. This command should be sent with a
parameter of 1. This variable doesn't return a value when read."
::= { lgpPwrStatistic 9 }
-- =============================================================================
-- lgpPwrConversion - Liebert Power Conversion Group
-- =============================================================================
lgpPwrNumberInstalledPowerModules OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of power modules installed in the device."
::= { lgpPwrConversion 1 }
lgpPwrNumberFailedPowerModules OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of power modules in the device that have failed."
::= { lgpPwrConversion 2 }
lgpPwrNumberRedundantPowerModules OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of redundant power modules installed in the device."
::= { lgpPwrConversion 3 }
lgpPwrNumberActivePowerModules OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of active power modules in the device."
::= { lgpPwrConversion 4 }
lgpPwrNumberPowerModuleWarnings OBJECT-TYPE
SYNTAX Integer32
UNITS "Count"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of power modules in the device that have a warning."
::= { lgpPwrConversion 6 }
lgpPwrUpsInverterStandby OBJECT-TYPE
SYNTAX INTEGER
{
on(1),
off(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The output to the load is supported by the bypass and the inverter is
on standby."
::= { lgpPwrConversion 7 }
-- =============================================================================
-- lgpPwrTopology - Liebert Power Topology Group
-- =============================================================================
lgpPwrUpsTopOffline OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The UPS has an offline topology. Under normal operating conditions,
AC power from the utility passes straight through the UPS
to the critical load. The inverter is used to convert the DC power
from the battery to create AC power to support the load when the
utility fails. Normally the inverter is operating in the stand-by mode,
keeping the batteries charged. Should the utility power go out of
specification, the inverter will power the load by drawing energy from
the battery."
::= { lgpPwrTopology 1 }
lgpPwrUpsTopLineInteractive OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The UPS has a line-interactive topology. This topology
resembles the offline product, but inserts a transformer or inductor
in series between the utility power source and the load. This inline
inductor enables the UPS inverter to interact with incoming power
and provide a measure of power conditioning to the load. This
buck-and-boost circuitry helps with high and low input voltage
conditions."
::= { lgpPwrTopology 2 }
lgpPwrUPSTopDualInput OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system has separate input sources for the bypass and inverter."
::= { lgpPwrTopology 3 }
lgpPwrTopFrequencyConverter OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system has a frequency converter."
::= { lgpPwrTopology 4 }
lgpPwrTopVoltageConverter OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The system has a voltage converter."
::= { lgpPwrTopology 5 }
lgpPwrTopMaximumFrameCapacity OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt-Amp"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The maximum device system capacity."
::= { lgpPwrTopology 6 }
lgpPwrTopRedundantControlModules OBJECT-TYPE
SYNTAX INTEGER
{
yes(1),
no(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The device has a redundant control module installed."
::= { lgpPwrTopology 7 }
lgpPwrInputIsolationTransformerInstalled OBJECT-TYPE
SYNTAX INTEGER
{
notInstalled(1),
installed(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the input isolation transformer is installed."
::= { lgpPwrTopology 8 }
lgpPwrStateStaticSwitchType OBJECT-TYPE
SYNTAX INTEGER
{
notApplicable(1),
continuousDuty(2),
momentaryDuty(3)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Static switch type (N/A, continous duty, or momentary duty)."
::= { lgpPwrTopology 9 }
lgpPwrStateModuleType OBJECT-TYPE
SYNTAX INTEGER
{
singleModuleSystem(1),
module1plus1(2),
module1plusN(3),
moduleNplus1(4),
systemControlCabinet(5),
mainStaticSwitch(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"UPS module type.
SMS -- Single Module System
1 + 1 -- Redundant system for capacity
1 + N -- Distributed multi-module system
N + 1 -- A multi-module system with one bypass for the system
SCC -- System Control Cabinet used in an N+1 system to
provide a single bypass for the system.
MSS -- Main Static Switch"
::= { lgpPwrTopology 10 }
lgpPwrStateBypassInputConfig OBJECT-TYPE
SYNTAX INTEGER
{
singlePhase2WireL1WithReturn(1),
twoPhase2WireL1L2(2),
twoPhase3WireL1L2WithNeutral(3),
threePhase3WireL1L2L3(4),
threePhase4WireL1L2L3WithNeutral(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Bypass input wire physical wiring configuration.
singlePhase2WireL1WithReturn
Single phase input with 2 wires (Line 1, and Return).
twoPhase2WireL1L2
Two phase input with 2 wires (Line 1, and Line 2).
twoPhase3WireL1L2WithNeutral
Two phase input with 3 wires (Line 1, Line 2, and Neutral)
threePhase3WireL1L2L3
Three phase input with 3 wires (Line 1, Line 2, and Line 3)
threePhase4WireL1L2L3WithNeutral
Three phase input with 4 wires (Line 1, Line 2, Line 3, and
Neutral)."
::= { lgpPwrTopology 11 }
lgpPwrStateOutputConfig OBJECT-TYPE
SYNTAX INTEGER
{
singlePhase2WireL1WithReturn(1),
twoPhase2WireL1L2(2),
twoPhase3WireL1L2WithNeutral(3),
threePhase3WireL1L2L3(4),
threePhase4WireL1L2L3WithNeutral(5)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Output wire physical wiring configuration.
singlePhase2WireL1WithReturn
Single phase output with 2 wires (Line 1, and Return).
twoPhase2WireL1L2
Two phase output with 2 wires (Line 1, and Line 2).
twoPhase3WireL1L2WithNeutral
Two phase output with 3 wires (Line 1, Line 2, and Neutral)
threePhase3WireL1L2L3
Three phase output with 3 wires (Line 1, Line 2, and Line 3)
threePhase4WireL1L2L3WithNeutral
Three phase output with 4 wires (Line 1, Line 2, Line 3, and
Neutral)."
::= { lgpPwrTopology 12 }
lgpPwrRectifierPassiveFilterInstalled OBJECT-TYPE
SYNTAX INTEGER
{
notInstalled(1),
installed(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the rectifier passive filter is installed."
::= { lgpPwrTopology 13 }
lgpPwrRectifierTrapInstalled OBJECT-TYPE
SYNTAX INTEGER
{
notInstalled(1),
installed(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the rectifier input passive filter is installed."
::= { lgpPwrTopology 14 }
lgpPwrRectifierActiveFilterInstalled OBJECT-TYPE
SYNTAX INTEGER
{
notInstalled(1),
installed(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the rectifier active filter is installed."
::= { lgpPwrTopology 15 }
-- =============================================================================
-- lgpPwrConfig - Liebert Power Config Group
-- =============================================================================
lgpPwrSysCapacity OBJECT-TYPE
SYNTAX Integer32
UNITS "Volt-Amp"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The current device system capacity."
::= { lgpPwrConfig 1 }
lgpPwrUPSModuleMode OBJECT-TYPE
SYNTAX INTEGER
{
single(1),
parallel(2),
hotmaster(3),
hotslave(4)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The module mode of the UPS."
::= { lgpPwrConfig 2 }
lgpPwrMaxRatedCurrent OBJECT-TYPE
SYNTAX Integer32
UNITS "Amp"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"System output maximum amperage rating. The maximum rated amperage for
the system. This value is based upon the model type and is typically
limited by the wiring, breakers, power devices, etc."
::= { lgpPwrConfig 3 }
lgpPwrRectifierPulseCount OBJECT-TYPE
SYNTAX INTEGER
{
sixPulse(1),
twelvePulse(2),
eighteenPulse(3),
twentyFourPulse(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Rectifier pulse count per waveform cycle (6-, 12-, 18-, or 24-pulse)."
::= { lgpPwrConfig 4 }
END