-- PPC MIB
-- ====================================================================
-- Revision History
-- v0.13 2011-11-10 Gavin Zhao created, Lilinhua modified
-- *************************NMC v0.0.1.7***********************************
-- v0.14 2011-11-18 Lilinhua
-- 1. Modify string "ppcTrap" to "eppcTrap"
-- 2012-02-09 Lilinhua
-- 1. Modify upsESystemFaultCode's description "The warning code of UPS" to "The fault code of UPS".
-- *************************NMC v1.1.0.4************************************
-- v0.15 2012-07-20 Lilinhua
-- 1. upsEShutdownWarningPeriodInterval, modify access from read-only to read-write.
-- 2. upsEShutdownwarningPeriodTime, add unit second.
-- 2012-07-31 Lilinhua
-- 1. Modify upsEBatteryTestElapsedTime's format from hh:mm:ss.ss to hh:mm:ss
-- 2012-08-09 Lilinhua
-- 1. Modify values of upsEModuleWorkingMode as upsESystemStatus's.
-- *************************NMC v1.1.0.6************************************
-- 2012-08-27 Lilinhua
-- 1. Modify "Moudles" to "Modules", advised by Beth.
-- 2. Modify module name as phase name "upsEModuleOutputCurrentR", "upsEModuleOutputWattR", "upsEModuleOutputLoadR".
-- 3. Add Convert module item "upsEModuleTrapState(12)".
-- 4. Add Convert module item "upsEModuleConfigOutputVA(13)".
-- 5. Add Convert module item "upsEModuleOutputCurrentS(14)", "upsEModuleOutputCurrentT(15)".
-- 6. Add Convert module item "upsEModuleOutputWattS(16)", "upsEModuleOutputWattT(17)".
-- 7. Add Convert module item "upsEModuleOutputLoadS(18)", "upsEModuleOutputLoadT(19)".
-- 8. Add Convert module item "upsEModuleOutputVAR(20)", "upsEModuleOutputVAS(21)", "upsEModuleOutputVAT(22)".
-- 9. Modify upsETrapState max length from 255 to 127.
-- *************************NMC v1.1.0.6************************************
-- 2012-08-27 Lilinhua
-- 1. Modify trap description of Overload, OverTemperature.
-- *************************NMC v1.3.0.0************************************
-- 2013-06-21 Lilinhua
-- 1. Add two upsEShutdownEvents: "belowCapacityLimit(11), belowRemainTimeLimit(12)".
-- 2. Add 4 traps: upsEBelowCapacityLimit, upsENotBelowCapacityLimit, upsEBelowRemainTimeLimit, upsENotBelowRemainTimeLimit.
-- 3. Add 2 config data: upsESystemConfigBelowCapacityLimit, upsESystemConfigBelowRemainTimeLimit.
-- 4. Modify upsETrapState's description: "trap 2(battery on)" to "trap 7(battery on)".
-- *************************NMC v1.4.0.3************************************
-- 2014-10-15 Lilinhua
-- 1. Modify descriptions of "upsEEnvironmentTemperatureHighSetPoint, upsEEnvironmentHumidityHighSetPoint,
-- upsEEnvironmentTemperatureLowSetPoint, upsEEnvironmentHumidityLowSetPoint".
-- *************************NMC v1.5.0.4************************************
-- v0.16 2015-01-05 Lilinhua
-- 1. Modify MIB for add Load segment.
EPPC-MIB DEFINITIONS ::= BEGIN
IMPORTS
TRAP-TYPE
FROM RFC-1215
DisplayString
FROM SNMPv2-TC
OBJECT-TYPE
FROM RFC-1212
enterprises,Counter, IpAddress
FROM RFC1155-SMI
PositiveInteger,NonNegativeInteger
FROM UPS-MIB;
ppc OBJECT IDENTIFIER ::= { enterprises 935 }
device OBJECT IDENTIFIER ::= { ppc 10 }
upsAgent OBJECT IDENTIFIER ::= { device 1 }
upsE OBJECT IDENTIFIER ::= { upsAgent 1 }
upsETraps OBJECT IDENTIFIER ::= { upsAgent 2 }
upsEIdentity OBJECT IDENTIFIER ::= { upsE 1 }
upsESystemSummary OBJECT IDENTIFIER ::= { upsE 2 }
upsEBatterySystem OBJECT IDENTIFIER ::= { upsE 3 }
upsEPowerConverterSystem OBJECT IDENTIFIER ::= { upsE 4 }
upsELoadSegment OBJECT IDENTIFIER ::= { upsE 5 }
upsEEnvironment OBJECT IDENTIFIER ::= { upsE 6 }
upsEBatteryTest OBJECT IDENTIFIER ::= { upsE 7 }
upsEControl OBJECT IDENTIFIER ::= { upsE 8 }
upsETrapControl OBJECT IDENTIFIER ::= { upsE 9 }
--========================================================================
--upsEIdentity
--========================================================================
upsEIdentityManufacturer OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 31 ) )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The name of the UPS manufacturer."
::= { upsEIdentity 1 }
upsEIdentityModel OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 63 ) )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The UPS Model designation."
::= { upsEIdentity 2 }
upsEIdentityUPSFirmwareVerison OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 31 ) )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The UPS firmware/software version(s)."
::= { upsEIdentity 3 }
upsEIndentityUPSSerialNumber OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 31 ) )
ACCESS read-only
STATUS mandatory
DESCRIPTION "optional.
Most UPS don't supply the value of UPS serial No."
::= { upsEIdentity 4 }
upsEIdentityDescription OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 63 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION "A string to identify the UPS. This object should be
set by the administrator."
::= { upsEIdentity 5 }
upsEIdentityAgentSoftwareVerison OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 31 ) )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The Network Management Card software/firmware version.
This variable may or may not have the same value as
upsEIdentGroupUPSSoftwareVersion in some implementations."
::= { upsEIdentity 6 }
upsEIdentityAttachedDevices OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 63 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION "A string identifying the devices attached to the output(s)
of the UPS. This object should be set by the administrator"
::= { upsEIdentity 7 }
--========================================================================
--upsESystemSummary
--========================================================================
upsESystemStatus OBJECT-TYPE
SYNTAX INTEGER { power-on ( 1 ) , stand-by( 2 ) , by-pass ( 3 ) ,
line( 4 ) , battery ( 5 ) , battery-test ( 6 ) , fault ( 7 ) ,
converter ( 8 ) , eco ( 9 ) , shutdown ( 10 ) , on-booster ( 11 ) , on-reducer ( 12 ) , other( 13 ) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "The indication of UPS system status."
::= { upsESystemSummary 1 }
upsESystemTemperature OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The temperature of UPS presented in 0.1 degree."
::= { upsESystemSummary 2 }
upsESystemWarningCode OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 15 ) )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The warning code of UPS. Please refer the warning table
of 'Q6' for details."
::= { upsESystemSummary 3 }
upsESystemFaultCode OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 15 ) )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The fault code of UPS.Please refer the fault code
of 'Q6' for details."
::= { upsESystemSummary 4 }
upsESystemConfigInputVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The magnitude of the nominal input voltage presented in 0.1 V. On those
systems which support read-write access to this object, if there is an
attempt to set this variable to a value that is not supported,
the request must be rejected and the agent shall respond with an
appropriate error message, i.e., badValue for SNMPv1, or
inconsistentValue for SNMPv2."
::= { upsESystemSummary 5 }
upsESystemConfigInputFrequence OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The nominal input frequency presented in 0.1 Hz. On those systems which support
read-write access to this object, if there is an attempt to
set this variable to a value that is not supported, the request
must be rejected and the agent shall respond with an appropriate
error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2."
::= { upsESystemSummary 6 }
upsESystemConfigOutputVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The magnitude of the nominal output voltage presented in 0.1V. On those systems
which support read-write access to this object, if there is an
attempt to set this variable to a value that is not supported,
the request must be rejected and the agent shall respond with an
appropriate error message, i.e., badValue for SNMPv1, or
inconsistentValue for SNMPv2"
::= { upsESystemSummary 7 }
upsESystemConfigOutputFrequency OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The nominal output frequency presented in 0.1Hz. On those systems which support
read-write access to this object, if there is an attempt to set
this variable to a value that is not supported, the request must
be rejected and the agent shall respond with an appropriate error
message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2."
::= { upsESystemSummary 8 }
upsESystemConfigOutputVA OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The magnitude of the nominal Volt-Amp rating presented in VA."
::= { upsESystemSummary 9 }
upsESystemConfigOutputPower OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The magnitude of the nominal true power rating presented in W ."
::= { upsESystemSummary 10 }
upsESystemConfigOutputLoadHighSetPoint OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-write
STATUS mandatory
DESCRIPTION "The maximum output load allowed before the load is too high for
UPS operation "
::= { upsESystemSummary 11 }
upsESystemConfigOverTemperatureSetPoint OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-write
STATUS mandatory
DESCRIPTION "The maximum temperature allowed before the UPS
operation temperature is too high, presented in 0.1 degree."
::= { upsESystemSummary 12 }
upsESystemInputSourceNum OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The present external source of input power."
::= { upsESystemSummary 13 }
upsESystemInputLineBads OBJECT-TYPE
SYNTAX Counter
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of times the Input was out of tolerance in voltage or frequency.
Its value should be initialized 0 after agent restarting. "
::= { upsESystemSummary 14 }
upsESystemInputNumPhases OBJECT-TYPE
SYNTAX PositiveInteger ( 1 .. 3 )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of input phase utilized is this device, serves as the table index.
This value indicate the device initialized feature."
::= { upsESystemSummary 15 }
upsESystemInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsSystemInputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "A list of input table entries. The number of entries is given by the
value of upsESystemInputNumPhase."
::= { upsESystemSummary 16 }
upsESystemInputEntry OBJECT-TYPE
SYNTAX UpsSystemInputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "An entry containing information applicable to a particular input line."
INDEX { upsESystemInputPhase }
::= { upsESystemInputTable 1 }
UpsSystemInputEntry ::= SEQUENCE {
upsESystemInputPhase PositiveInteger,
upsESystemInputFrequency NonNegativeInteger,
upsESystemInputVoltage NonNegativeInteger,
upsESystemInputCurrent NonNegativeInteger,
upsESystemInputWatts NonNegativeInteger
}
upsESystemInputPhase OBJECT-TYPE
SYNTAX PositiveInteger( 1 .. 3 )
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "The number of the phase. Serves as index for input table"
::= { upsESystemInputEntry 1 }
upsESystemInputFrequency OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured input frquency from the UPS meters in 0.1Hz."
::= { upsESystemInputEntry 2 }
upsESystemInputVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured input voltage from the UPS meters in 0.1 volts"
::= { upsESystemInputEntry 3 }
upsESystemInputCurrent OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured input mandatory from the UPS meters in 0.1 amps."
::= { upsESystemInputEntry 4 }
upsESystemInputWatts OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured input real power in watts."
::= { upsESystemInputEntry 5 }
upsESystemOutputNumPhase OBJECT-TYPE
SYNTAX PositiveInteger ( 1 .. 3 )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of metered output phases, serves as the table index.
This value indicate the device initialized feature."
::= { upsESystemSummary 17 }
upsESystemOutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsSystemOutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "A list of output table entries. The number of entries is given
by the value of upsESystemOutputNumPhase."
::= { upsESystemSummary 18 }
upsESystemOutputEntry OBJECT-TYPE
SYNTAX UpsSystemOutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "An entry containing information applicable to a particular line."
INDEX { upsESystemOutputPhase }
::= { upsESystemOutputTable 1 }
UpsSystemOutputEntry ::= SEQUENCE {
upsESystemOutputPhase PositiveInteger,
upsESystemOutputFrequency NonNegativeInteger,
upsESystemOutputVoltage NonNegativeInteger,
upsESystemOutputCurrent NonNegativeInteger,
upsESystemOutputWatts NonNegativeInteger,
upsESystemOutputVA NonNegativeInteger,
upsESystemOutputLoad NonNegativeInteger
}
upsESystemOutputPhase OBJECT-TYPE
SYNTAX PositiveInteger ( 1 .. 3 )
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "The number of the phase. Serves as index for output table"
::= { upsESystemOutputEntry 1 }
upsESystemOutputFrequency OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured output frequency from the UPS meters in 0.1Hz."
::= { upsESystemOutputEntry 2 }
upsESystemOutputVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured output voltage from the UPS meters in 0.1 volts"
::= { upsESystemOutputEntry 3 }
upsESystemOutputCurrent OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured output mandatory from the UPS meters in 0.1 amps."
::= { upsESystemOutputEntry 4 }
upsESystemOutputWatts OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured output real power in watts."
::= { upsESystemOutputEntry 5 }
upsESystemOutputVA OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured output real complex power in VA."
::= { upsESystemOutputEntry 6 }
upsESystemOutputLoad OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The UPS output load in percent of rated capacity."
::= { upsESystemOutputEntry 7 }
upsESystemBypassNumPhase OBJECT-TYPE
SYNTAX PositiveInteger ( 1 .. 3 )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of bypass phases, serves as the table index.
This value indicate the device initialized feature"
::= { upsESystemSummary 19 }
upsESystemBypassTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsSystemBypassEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "A list of bypass table entries. The number of entries is given by the
value of upsESystemBypassNumPhase."
::= { upsESystemSummary 20 }
upsESystemBypassEntry OBJECT-TYPE
SYNTAX UpsSystemBypassEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "An entry containing information applicable to a particular line."
INDEX { upsESystemBypassPhase }
::= { upsESystemBypassTable 1 }
UpsSystemBypassEntry ::= SEQUENCE {
upsESystemBypassPhase PositiveInteger,
upsESystemBypassFrequency NonNegativeInteger,
upsESystemBypassVoltage NonNegativeInteger,
upsESystemBypassCurrent NonNegativeInteger,
upsESystemBypassWatts NonNegativeInteger
}
upsESystemBypassPhase OBJECT-TYPE
SYNTAX PositiveInteger ( 1 .. 3 )
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "The number of the phase. Serves as index for bypass table"
::= { upsESystemBypassEntry 1 }
upsESystemBypassFrequency OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured bypass frequency from the UPS meters in 0.1 Hz."
::= { upsESystemBypassEntry 2 }
upsESystemBypassVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured bypass voltage from the UPS meters in 0.1 volts"
::= { upsESystemBypassEntry 3 }
upsESystemBypassCurrent OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured bypass mandatory from the UPS meters in 0.1 amps"
::= { upsESystemBypassEntry 4 }
upsESystemBypassWatts OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured input real power in watts."
::= { upsESystemBypassEntry 5 }
upsESystemConfigBelowCapacityLimit OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-write
STATUS mandatory
DESCRIPTION "The UPS batteries capacity(%) limit for shutdown"
::= { upsESystemSummary 21 }
upsESystemConfigBelowRemainTimeLimit OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-write
STATUS mandatory
DESCRIPTION "The UPS batteries backup time(minute) limit for shutdown"
::= { upsESystemSummary 22 }
--========================================================================
--upsEBatterySystem
--========================================================================
upsEBatteryStatus OBJECT-TYPE
SYNTAX INTEGER { unknown ( 1 ) , batteryNormal ( 2 ) , batteryLow ( 3 ) ,
batteryDepleted ( 4 ) , batteryDischarging ( 5 ) , batteryFailure ( 6 ) }
ACCESS read-only
STATUS mandatory
DESCRIPTION " The status of UPS battery, a value of batteryLow indicates
that the battery-low status bit has been set from device.
A value of batteryDepleted indicates that the UPS will be
unable to sustain the present load when and if the utility
power is lost (including the possibility that the utility
power is mandatoryly absent and the UPS is unable to sustain
the output)"
::= { upsEBatterySystem 1 }
upsESecondsOnBattery OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "If the unit is on battery power, the elapsed time
since the UPS last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is less. 0 shall be returned
if the unit is not on battery power"
::= { upsEBatterySystem 2 }
upsEBatteryEstimatedMinutesRemaining OBJECT-TYPE
SYNTAX PositiveInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "An estimate of the time to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off."
::= { upsEBatterySystem 3 }
upsEBatteryEstimatedChargeRemaining OBJECT-TYPE
SYNTAX Integer32 ( 0 .. 100 )
ACCESS read-only
STATUS mandatory
DESCRIPTION "An estimate of the battery charge remaining expressed
as a percent of full charge"
::= { upsEBatterySystem 4 }
upsEPositiveBatteryVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The magnitude of the present positive battery voltage in 0.1 Volt DC"
::= { upsEBatterySystem 5 }
upsENegativeBatteryVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The magnitude of the present negative battery voltage in 0.1 Volt DC"
::= { upsEBatterySystem 6 }
upsEBatteryCellNumber OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "This object indicate the cell number of each set."
::= { upsEBatterySystem 7 }
upsEBatteryTemperature OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The ambient temperature at or near the UPS Battery
casing in 0.1 degree."
::= { upsEBatterySystem 8 }
upsEBatteryLastReplacedDate OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 10 .. 10 ) )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The date when the Batteries in this UPS were last replaced.
The format should be DD/MM/YYYY."
::= { upsEBatterySystem 9 }
upsEBatteryABMStatus OBJECT-TYPE
SYNTAX INTEGER { charge ( 1 ) , float ( 2 ) , rest ( 3 ) ,
discharge ( 4 ) , disable ( 5 ) }
ACCESS read-only
STATUS mandatory
DESCRIPTION " The status of ABM."
::= { upsEBatterySystem 10 }
upsEChargerModulesNum OBJECT-TYPE
SYNTAX NonNegativeInteger ( 0 .. 32 )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of charger modules inserted to UPS systems. served
as the index of the upsEChargerModulesTable.
The default value 0 indicate that the UPS system don't have
separate charger module."
::= { upsEBatterySystem 11 }
upsEChargerModulesTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsChargerModulesEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "A list of charger modules entries. The number of entries is given
by the value of upsEchargerModulesNum."
::= { upsEBatterySystem 12 }
upsEChargerModulesEntry OBJECT-TYPE
SYNTAX UpsChargerModulesEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "An entry containing information applicable to a particular charger module."
INDEX { chargerModulesNum }
::= { upsEChargerModulesTable 1 }
UpsChargerModulesEntry ::= SEQUENCE {
chargerModulesNum PositiveInteger,
chargerModulesAddress NonNegativeInteger ,
positiveChargeVotlage NonNegativeInteger,
negativeChargeVoltage NonNegativeInteger,
positiveChargeCurrent NonNegativeInteger,
negativeChargeCurrent NonNegativeInteger,
chargerModulesTemperature INTEGER,
chargerModulesMode INTEGER
}
chargerModulesNum OBJECT-TYPE
SYNTAX PositiveInteger ( 1 .. 32 )
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "The number of charger modules. Serves as index for charger module table"
::= { upsEChargerModulesEntry 1 }
chargerModulesAddress OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "Charger Modules' address."
::= { upsEChargerModulesEntry 2 }
positiveChargeVotlage OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured positive charger voltage from the UPS meters in 0.1 volts"
::= { upsEChargerModulesEntry 3 }
negativeChargeVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured nepositive charger voltage from the UPS meters in 0.1 volts"
::= { upsEChargerModulesEntry 4 }
positiveChargeCurrent OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured positive charger mandatory from the UPS meters in in 0.1 amps."
::= { upsEChargerModulesEntry 5 }
negativeChargeCurrent OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured nepositive charger mandatory from the UPS meters in 0.1 amps."
::= { upsEChargerModulesEntry 6 }
chargerModulesTemperature OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured charger temperature from the UPS meters in 0.1 degree."
::= { upsEChargerModulesEntry 7 }
chargerModulesMode OBJECT-TYPE
SYNTAX INTEGER { powerOn ( 1 ) , standyby ( 2 ) , fault ( 3 ) , shutdown ( 4 ) ,
running ( 5 ) , suicide ( 6 ) , unknown ( 7 ) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "The working mode of charger modules."
::= { upsEChargerModulesEntry 8 }
--========================================================================
--upsEPowerConverterSystem
--========================================================================
upsEUPSModulesNum OBJECT-TYPE
SYNTAX NonNegativeInteger ( 0 .. 32 )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of UPS modules inserted to UPS systems.
served as the index of the upsEModulesTable.
the default value 0 indicate that the UPS system do not
have separate UPS module."
::= { upsEPowerConverterSystem 1 }
upsEModulesTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsModulesEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "A list of UPS modules entries. The number of entries is
given by the value of upsEModulesNum."
::= { upsEPowerConverterSystem 2 }
upsEModulesEntry OBJECT-TYPE
SYNTAX UpsModulesEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "An entry containing information applicable to a particular upsE module."
INDEX { upsEModulesNum }
::= { upsEModulesTable 1 }
UpsModulesEntry ::= SEQUENCE {
upsEModulesNum PositiveInteger,
upsEModuleAddress INTEGER,
upsEModulePositiveBusVolt NonNegativeInteger,
upsEModuleNegativeBusVolt NonNegativeInteger,
upsEModuleTemperature INTEGER,
upsEModuleWorkingMode INTEGER,
upsEModuleOutputCurrentR NonNegativeInteger,
upsEModuleOutputWattR NonNegativeInteger,
upsEModuleOutputLoadR INTEGER,
upsEModuleWarningCode DisplayString,
upsEModuleFaultCode DisplayString,
upsEModuleTrapState DisplayString,
upsEModuleConfigOutputVA NonNegativeInteger,
upsEModuleOutputCurrentS NonNegativeInteger,
upsEModuleOutputCurrentT NonNegativeInteger,
upsEModuleOutputWattS NonNegativeInteger,
upsEModuleOutputWattT NonNegativeInteger,
upsEModuleOutputLoadS INTEGER,
upsEModuleOutputLoadT INTEGER,
upsEModuleOutputVAR NonNegativeInteger,
upsEModuleOutputVAS NonNegativeInteger,
upsEModuleOutputVAT NonNegativeInteger
}
upsEModulesNum OBJECT-TYPE
SYNTAX PositiveInteger ( 1 .. 32 )
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "The number of UPS modules. Serves as index for UPS module table"
::= { upsEModulesEntry 1 }
upsEModuleAddress OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "the address of UPS modules."
::= { upsEModulesEntry 2 }
upsEModulePositiveBusVolt OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured positive upsE module voltage from the UPS meters in 0.1 volts"
::= { upsEModulesEntry 3 }
upsEModuleNegativeBusVolt OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured nepositive upsE module voltage from the UPS meters in 0.1 volts"
::= { upsEModulesEntry 4 }
upsEModuleTemperature OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured upsE module temperature from the UPS meters in 0.1 degree."
::= { upsEModulesEntry 5 }
upsEModuleWorkingMode OBJECT-TYPE
SYNTAX INTEGER {power-on ( 1 ) , stand-by( 2 ) , by-pass ( 3 ) ,
line( 4 ) , battery ( 5 ) , battery-test ( 6 ) , fault ( 7 ) ,
converter ( 8 ) , eco ( 9 ) , shutdown ( 10 ) , on-booster ( 11 ) , on-reducer ( 12 ) , other( 13 ) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "The working mode of UPS modules."
::= { upsEModulesEntry 6 }
upsEModuleOutputCurrentR OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured upsE module output mandatory from the UPS meters in 0.1 A."
::= { upsEModulesEntry 7 }
upsEModuleOutputWattR OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured upsE module output watts from the UPS meters in watts."
::= { upsEModulesEntry 8 }
upsEModuleOutputLoadR OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The output load of UPS modules in %."
::= { upsEModulesEntry 9 }
upsEModuleWarningCode OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 15 ) )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The warning code of ups modules.Please refer the warning table of 'QU,XX' for details."
::= { upsEModulesEntry 10 }
upsEModuleFaultCode OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 15 ) )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The fault code of ups modules.Please refer command 'QU,XX' for details."
::= { upsEModulesEntry 11 }
upsEModuleTrapState OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 127 ) )
ACCESS read-only
STATUS mandatory
DESCRIPTION "the values indicate the unrestored traps.
For example, after AC fail, so the value of upsETrapState should be '1'.
And then the AC restore, the value of upsEModuleTrapState
should change to empty."
::= { upsEModulesEntry 12 }
upsEModuleConfigOutputVA OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The magnitude of the nominal Volt-Amp rating presented in VA."
::= { upsEModulesEntry 13 }
upsEModuleOutputCurrentS OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured upsE module output mandatory from the UPS meters in 0.1 A."
::= { upsEModulesEntry 14 }
upsEModuleOutputCurrentT OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured upsE module output mandatory from the UPS meters in 0.1 A."
::= { upsEModulesEntry 15 }
upsEModuleOutputWattS OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured upsE module output watts from the UPS meters in watts."
::= { upsEModulesEntry 16 }
upsEModuleOutputWattT OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measured upsE module output watts from the UPS meters in watts."
::= { upsEModulesEntry 17 }
upsEModuleOutputLoadS OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The output load of UPS modules in %."
::= { upsEModulesEntry 18 }
upsEModuleOutputLoadT OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The output load of UPS modules in %."
::= { upsEModulesEntry 19 }
upsEModuleOutputVAR OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The magnitude of the nominal Volt-Amp rating presented in VA."
::= { upsEModulesEntry 20 }
upsEModuleOutputVAS OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The magnitude of the nominal Volt-Amp rating presented in VA."
::= { upsEModulesEntry 21 }
upsEModuleOutputVAT OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The magnitude of the nominal Volt-Amp rating presented in VA."
::= { upsEModulesEntry 22 }
--========================================================================
--upsELoadSegment
--========================================================================
upsELoadSegment1OffDelay OBJECT-TYPE
-- Valid value is from -1 to 32767
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION "Setting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less.
Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will
abort the countdown. Read this object will get countdown value of the Load Segment."
::= { upsELoadSegment 1 }
upsELoadSegment1OnDelay OBJECT-TYPE
-- Valid value is from -1 to 32767
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION "Setting this object will start the Load segment output after the indicated number of seconds,
including starting the UPS, if necessary. Setting this object to 0 will cause the startup
to occur immediately. Setting this object to -1 will abort the countdown."
::= { upsELoadSegment 2 }
upsELoadSegment1AutoOffTimer OBJECT-TYPE
-- Valid value is from -1 to 32767
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION "The load segment turns automatically off after the delay while the unit operates on battery,
but the shutdown is cancelled if the utility return before the delay has expired."
::= { upsELoadSegment 3 }
upsELoadSegment1AutoOnTimer OBJECT-TYPE
-- Valid value is from -1 to 32767
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION "The load segment is automatically turned on after a selected delay
if it has been shutdown due to on battery."
::= { upsELoadSegment 4 }
upsELoadSegment1State OBJECT-TYPE
SYNTAX INTEGER { off(1), on(2), off-pending(3), on-pending(4), not-support(5) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "Load segment output state."
::= { upsELoadSegment 5 }
upsELoadSegment2OffDelay OBJECT-TYPE
-- Valid value is from -1 to 32767
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION "Setting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less.
Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will
abort the countdown. Read this object will get countdown value of the Load Segment."
::= { upsELoadSegment 6 }
upsELoadSegment2OnDelay OBJECT-TYPE
-- Valid value is from -1 to 32767
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION "Setting this object will start the Load segment output after the indicated number of seconds,
including starting the UPS, if necessary. Setting this object to 0 will cause the startup
to occur immediately. Setting this object to -1 will abort the countdown."
::= { upsELoadSegment 7 }
upsELoadSegment2AutoOffTimer OBJECT-TYPE
-- Valid value is from -1 to 32767
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION "The load segment turns automatically off after the delay while the unit operates on battery,
but the shutdown is cancelled if the utility return before the delay has expired."
::= { upsELoadSegment 8 }
upsELoadSegment2AutoOnTimer OBJECT-TYPE
-- Valid value is from -1 to 32767
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION "The load segment is automatically turned on after a selected delay
if it has been shutdown due to on battery."
::= { upsELoadSegment 9 }
upsELoadSegment2State OBJECT-TYPE
SYNTAX INTEGER { off(1), on(2), off-pending(3), on-pending(4), not-support(5) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "Load segment output state."
::= { upsELoadSegment 10 }
--========================================================================
--upsEEnvironment
--========================================================================
upsEEnvironmentTemperature OBJECT IDENTIFIER ::= { upsEEnvironment 1 }
upsEEnvironmentCurrentTemperature OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measurement of temperature sensor, in 0.1 degree"
::= { upsEEnvironmentTemperature 1 }
upsEEnvironmentTemperatureHighSetPoint OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION "The set point for high temperature warning, in 0.1 degrees.
This value must be greater than upsEEnvironmentTemperatureLowSetPoint,
and the least significant digit must be zero."
::= { upsEEnvironmentTemperature 2 }
upsEEnvironmentTemperatureHighStatus OBJECT-TYPE
SYNTAX INTEGER { enable ( 1 ) , disable ( 2 ) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "To enable/disable high set point check with sensor temperature."
::= { upsEEnvironmentTemperature 3 }
upsEEnvironmentTemperatureLowSetPoint OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION "The set point for low temperature warning, in 0.1 degrees.
This value must be less than upsEEnvironmentTemperatureHighSetPoint,
and the least significant digit must be zero."
::= { upsEEnvironmentTemperature 4 }
upsEEnvironmentTemperatureLowStatus OBJECT-TYPE
SYNTAX INTEGER { enable ( 1 ) , disable ( 2 ) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "To enable/disable low set point check with sensor temperature."
::= { upsEEnvironmentTemperature 5 }
upsEEnvironmentTemperatureOffset OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION "The offset to calibrate temperature of EMD, in 0.1 degrees"
::= { upsEEnvironmentTemperature 6 }
upsEEnvironmentHumidity OBJECT IDENTIFIER ::= { upsEEnvironment 2 }
upsEEnvironmentCurrentHumidity OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The measurement of sensor humidity present in %."
::= { upsEEnvironmentHumidity 1 }
upsEEnvironmentHumidityHighSetPoint OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION "The set point for high humidity warning, in %.
This value must be greater than upsEEnvironmentHumidityLowSetPoint."
::= { upsEEnvironmentHumidity 2 }
upsEEnvironmentHumidityHighStatus OBJECT-TYPE
SYNTAX INTEGER { enable ( 1 ) , disable ( 2 ) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "To enable/disable high set point check with emd humidity."
::= { upsEEnvironmentHumidity 3 }
upsEEnvironmentHumidityLowSetPoint OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION "The set point for low humidity warning, in %.
This value must be less than upsEEnvironmentHumidityHighSetPoint."
::= { upsEEnvironmentHumidity 4 }
upsEEnvironmentHumidityLowStatus OBJECT-TYPE
SYNTAX INTEGER { enable ( 1 ) , disable ( 2 ) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "To enable/disable high set point check with emd humidity."
::= { upsEEnvironmentHumidity 5 }
upsEEnvironmentHumidityOffset OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION "The offset to calibrate humidity of EMD, in %."
::= { upsEEnvironmentHumidity 6 }
upsEEnvironmentContactsNum OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION "The number of environment contacts, serves as the table index."
::= { upsEEnvironment 3 }
upsEEnvironmentContactTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsEEnvironmentContactEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "A list of contacts table entries. The number of entries is given by the
value of upsEEnvironmentContactsNum"
::= { upsEEnvironment 4 }
upsEEnvironmentContactEntry OBJECT-TYPE
SYNTAX UpsEEnvironmentContactEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "An entry containing information applicable to a particular contact"
INDEX { upsEEnvironmentContactIndex }
::= { upsEEnvironmentContactTable 1 }
UpsEEnvironmentContactEntry ::= SEQUENCE {
upsEEnvironmentContactIndex PositiveInteger,
upsEEnvironmentContactType INTEGER,
upsEEnvironmentContactState INTEGER,
upsEEnvironmentContactDescription DisplayString
}
upsEEnvironmentContactIndex OBJECT-TYPE
SYNTAX PositiveInteger
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "The number of environment contacts. Serves as index for environment contact table"
::= { upsEEnvironmentContactEntry 1 }
upsEEnvironmentContactType OBJECT-TYPE
SYNTAX INTEGER { normallyOpen ( 1 ) , normallyClosed ( 2 ) , notUsed ( 3 ) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "operation type"
::= { upsEEnvironmentContactEntry 2 }
upsEEnvironmentContactState OBJECT-TYPE
SYNTAX INTEGER { open ( 1 ) , closed ( 2 ) , openWithNotice ( 3 ) , closedWithNotice ( 4 ) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "The mandatory status."
::= { upsEEnvironmentContactEntry 3 }
upsEEnvironmentContactDescription OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 31 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION "Description of environment contact."
::= { upsEEnvironmentContactEntry 4 }
--========================================================================
--upsEBatteryTest
--========================================================================
upsEBatteryTestStart OBJECT-TYPE
SYNTAX INTEGER { none ( 1 ) , batteryTest10Sec ( 2 ) , batteryTestUntilLow ( 3 ) ,
batteryTestWithTime ( 4 ) , cancelBatteryTest ( 5 ) , clearBatteryInfo ( 6 ) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "This object specify the battery test type and initiate battery test.
If battTestWithTime selected, the test time is refer to upsEBatteryTestSettingTime."
::= { upsEBatteryTest 1 }
upsEBatteryTestSettingTime OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-write
STATUS mandatory
DESCRIPTION "The object specify the test time for battery test in seconds."
::= { upsEBatteryTest 2 }
upsEBatteryTestResult OBJECT-TYPE
SYNTAX INTEGER { idle ( 1 ) , processing ( 2 ) , noFailure ( 3 ) ,
failureOrWarning ( 4 ) , notPossible ( 5 ) , testCancel ( 6 ) }
ACCESS read-only
STATUS mandatory
DESCRIPTION "This object indicate the test result of battery."
::= { upsEBatteryTest 3 }
upsEBatteryTestStartTime OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 19 .. 19 ) )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The value of the time the test in progress was initiated,
or, if no test is in progress, the time the previous test
was initiated. If the value of upsETestBatteryTestResult
is noTestsInitiated(6), upsETestStartTime has the value
01/01/1970 00:00:00."
::= { upsEBatteryTest 4 }
upsEBatteryTestElapsedTime OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 11 .. 11 ) )
ACCESS read-only
STATUS mandatory
DESCRIPTION "The amount of time in format hh:mm:ss, since the test in progress
was initiated, or, if no test is in progress, the previous
test took to complete. If the value of upsTestResultsSummary
is idle(1), upsTestElapsedTime has the value 00:00:00."
::= { upsEBatteryTest 5 }
upsEBatteryTestScheduleTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsBatteryTestScheduleEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "This table describes the schedule for automatically battery
test."
::= { upsEBatteryTest 6 }
upsEBatteryTestScheduleEntry OBJECT-TYPE
SYNTAX UpsBatteryTestScheduleEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "An entry containing information applicable to schedule test."
INDEX { upsEBatteryTestScheduleIndex }
::= { upsEBatteryTestScheduleTable 1 }
UpsBatteryTestScheduleEntry ::= SEQUENCE {
upsEBatteryTestScheduleIndex PositiveInteger,
upsEBatteryTestScheduleDay INTEGER,
upsEBatteryTestScheduleTime DisplayString,
upsEBatteryTestScheduleType INTEGER,
upsEBatteryTestScheduleTestWithTime NonNegativeInteger,
upsEBatteryTestScheduleSpecialDay DisplayString
}
upsEBatteryTestScheduleIndex OBJECT-TYPE
SYNTAX PositiveInteger
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "The index of battery test scheduled."
::= { upsEBatteryTestScheduleEntry 1 }
upsEBatteryTestScheduleDay OBJECT-TYPE
SYNTAX INTEGER { monday ( 1 ) , tuesday ( 2 ) , wednsday ( 3 ) ,
thusday ( 4 ) , friday ( 5 ) , saturday ( 6 ) ,
sunday ( 7 ) , specialday ( 8 ) , none ( 9 ) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "The weekday or specaial day on which the UPS should start battery test."
::= { upsEBatteryTestScheduleEntry 2 }
upsEBatteryTestScheduleTime OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 5 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION "The time that the battery test will be initiated in hh:mm format."
::= { upsEBatteryTestScheduleEntry 3 }
upsEBatteryTestScheduleType OBJECT-TYPE
SYNTAX INTEGER { none ( 1 ) , batteryTest10sec ( 2 ) , batteryTestUntilLow ( 3 ) ,
batteryTestWithTime ( 4 ) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "The type of battery test."
::= { upsEBatteryTestScheduleEntry 5 }
upsEBatteryTestScheduleTestWithTime OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-write
STATUS mandatory
DESCRIPTION "The battery time of setting time test in seconds."
::= { upsEBatteryTestScheduleEntry 6 }
upsEBatteryTestScheduleSpecialDay OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 10 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION "The special day that the battery test will be initiated in dd/mm/yyyy format."
::= { upsEBatteryTestScheduleEntry 7 }
--========================================================================
-- upsEControl
--========================================================================
upsEControlOutputOffDelay OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-write
STATUS mandatory
DESCRIPTION "Setting this value to other than zero will cause the UPS
output to turn off after the number of seconds. "
::= { upsEControl 1 }
upsEControlOutputOnDelay OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-write
STATUS mandatory
DESCRIPTION "Setting this value to other than zero will cause the
UPS output to turn on after the number of seconds. "
::= { upsEControl 2 }
upsEControlOutputOnOffControl OBJECT-TYPE
SYNTAX INTEGER { upsEOutputOff ( 1 ) , upsEOutputOffCancel ( 2 ) , upsESleep( 3 ) , none ( 4 ) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "upsEOutputOff ( 1 ) indicates the shutdown sequence,
upsEOutputOffCancel ( 2 ) indicates cancel the shutdown sequence,
upsESleep( 3 ) indicates shutdown UPS first, then switch on."
::= { upsEControl 3 }
upsEShutdownEventsTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsShutdownEventsEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "This table describes the parametes for shutdown process
when shutdown event occurs"
::= { upsEControl 4 }
upsEShutdownEventsEntry OBJECT-TYPE
SYNTAX UpsShutdownEventsEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "An entry containing information applicable to a particular shutdown
event line"
INDEX { upsEShutdownEvent }
::= { upsEShutdownEventsTable 1 }
UpsShutdownEventsEntry ::= SEQUENCE {
upsEShutdownEvent INTEGER,
upsEShutdownEventAction INTEGER,
upsEShutdownwarningPeriodTime NonNegativeInteger,
upsEShutdownWarningPeriodInterval NonNegativeInteger
}
upsEShutdownEvent OBJECT-TYPE
SYNTAX INTEGER { acFail ( 1 ) , batteryLow ( 2 ) , upsEOverLoad ( 3 ) ,
upsEOverTemperature ( 4 ) , upsEWeeklySchedule ( 5 ) ,
upsESpecialSchedule ( 6 ) , environmentTemperatureOverThreshold ( 7 ) ,
environmentHumidityOverThreshold ( 8 ) , environmentContact1Alarm ( 9 ) ,
environmentContact2Alarm ( 10 ), belowCapacityLimit( 11 ), belowRemainTimeLimit( 12 )}
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "The shutdown event identification"
::= { upsEShutdownEventsEntry 1 }
upsEShutdownEventAction OBJECT-TYPE
SYNTAX INTEGER { disable ( 1 ) , warning ( 2 ) , shutdownClient ( 3 ) , shutdownUPS ( 4 ) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "Status of the corresponding shutdown Event.
When set to disable(), shutdown process will not start when
corresponding event occured."
::= { upsEShutdownEventsEntry 2 }
upsEShutdownwarningPeriodTime OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-write
STATUS mandatory
DESCRIPTION "The Delay in seconds after the occurance of the curresponding shutdown
event, and warning message should be popped in this period."
::= { upsEShutdownEventsEntry 3 }
upsEShutdownWarningPeriodInterval OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-write
STATUS mandatory
DESCRIPTION "The frequency of sending warning messages to the connected
clients when the curresponding shutdown event occurs.
The value is in units of seconds."
::= { upsEShutdownEventsEntry 4 }
upsEControlWeeklyScheduleTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsControlWeeklyScheduleEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "The table to schedule shutting down the ups by weekly"
::= { upsEControl 5 }
upsEControlWeeklyScheduleEntry OBJECT-TYPE
SYNTAX UpsControlWeeklyScheduleEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "An entry containing information applicable to a particular line"
INDEX { upsEControlWeeklyScheduleIndex }
::= { upsEControlWeeklyScheduleTable 1 }
UpsControlWeeklyScheduleEntry ::= SEQUENCE {
upsEControlWeeklyScheduleIndex PositiveInteger,
upsEWeeklyScheduleShutdownDay INTEGER,
upsEWeeklyScheduleShutdownTime DisplayString,
upsEWeeklyScheduleRestartDay INTEGER,
upsEWeeklyScheduleRestartTime DisplayString
}
upsEControlWeeklyScheduleIndex OBJECT-TYPE
SYNTAX PositiveInteger
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "the index of schedule events."
::= { upsEControlWeeklyScheduleEntry 1 }
upsEWeeklyScheduleShutdownDay OBJECT-TYPE
SYNTAX INTEGER { monday ( 1 ) , tuesday ( 2 ) , wednesday ( 3 ) ,
thursday ( 4 ) , friday ( 5 ) , saturday ( 6 ) ,
sunday ( 7 ) , none ( 8 ) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "the weekday on which upsE shoud shutdown"
::= { upsEControlWeeklyScheduleEntry 2 }
upsEWeeklyScheduleShutdownTime OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 5 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION "The time that the process of shutting down the UPS will be initiated
in hh:mm format."
::= { upsEControlWeeklyScheduleEntry 3 }
upsEWeeklyScheduleRestartDay OBJECT-TYPE
SYNTAX INTEGER { monday ( 1 ) , tuesday ( 2 ) , wednesday ( 3 ) ,
thursday ( 4 ) , friday ( 5 ) , saturday ( 6 ) ,
sunday ( 7 ) , none ( 8 ) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "the weekday on which the UPS should restart."
::= { upsEControlWeeklyScheduleEntry 4 }
upsEWeeklyScheduleRestartTime OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 5 .. 5 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION "The time the UPS will restart in hh:mm format."
::= { upsEControlWeeklyScheduleEntry 5 }
upsEControlSpecialDayScheduleTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsControlSpecialDayScheduleEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "The table to schedule shutting down the ups."
::= { upsEControl 6 }
upsEControlSpecialDayScheduleEntry OBJECT-TYPE
SYNTAX UpsControlSpecialDayScheduleEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "An entry containing information applicable to a particular line."
INDEX { upsEControlSpecialDayScheduleIndex }
::= { upsEControlSpecialDayScheduleTable 1 }
UpsControlSpecialDayScheduleEntry ::= SEQUENCE {
upsEControlSpecialDayScheduleIndex PositiveInteger,
upsESpecialDayScheduleShutdownDay DisplayString,
upsESpecialDayScheduleShutdownTime DisplayString,
upsESpecialDayScheduleRestartDay DisplayString,
upsESpecialDayScheduleRestartTime DisplayString
}
upsEControlSpecialDayScheduleIndex OBJECT-TYPE
SYNTAX PositiveInteger
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "The index of special day schedule."
::= { upsEControlSpecialDayScheduleEntry 1 }
upsESpecialDayScheduleShutdownDay OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 10 .. 10 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION "The special day on which UPS should shutdown with the format
of DD/MM/YYYY."
::= { upsEControlSpecialDayScheduleEntry 2 }
upsESpecialDayScheduleShutdownTime OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 5 .. 5 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION "The time that the process of shutting down the UPS will be initiated
in hh:mm format."
::= { upsEControlSpecialDayScheduleEntry 3 }
upsESpecialDayScheduleRestartDay OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 10 .. 10 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION "The special day on which the UPS should restart with the format
of DD/MM/YYYY."
::= { upsEControlSpecialDayScheduleEntry 4 }
upsESpecialDayScheduleRestartTime OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 5 .. 5 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION "The time the UPS will restart in hh:mm format."
::= { upsEControlSpecialDayScheduleEntry 5 }
upsESystemMasterOffDelay OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The UPS output will shutdown after the indicated number of seconds, -1 indicate no action."
::= { upsEControl 7 }
upsESystemMasterOnDelay OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION "The UPS output will start on after the indicated number of seconds, -1 indicate no action."
::= { upsEControl 8 }
--========================================================================
-- upsETrapControl
--========================================================================
upsETrapsReceiversTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsTrapsReceiversEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION " This table list the managers'IP to send traps to."
::= { upsETrapControl 1 }
upsETrapsReceiversEntry OBJECT-TYPE
SYNTAX UpsTrapsReceiversEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "An entry containing information applicable to a particular input line."
INDEX { upsETrapsReceiversIndex }
::= { upsETrapsReceiversTable 1 }
UpsTrapsReceiversEntry ::= SEQUENCE {
upsETrapsReceiversIndex PositiveInteger,
upsETrapsReceiverAddress DisplayString,
upsETrapReceiverCommunityString DisplayString,
upsETrapType INTEGER,
upsETrapsSeverityLevel INTEGER,
upsETrapReceiverDescription DisplayString
}
upsETrapsReceiversIndex OBJECT-TYPE
SYNTAX PositiveInteger
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "The index to a trap receiver entry"
::= { upsETrapsReceiversEntry 1 }
upsETrapsReceiverAddress OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 45 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION "The IP address of the manager to send a trap to."
::= { upsETrapsReceiversEntry 2 }
upsETrapReceiverCommunityString OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 32 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION "The community name to use in the trap when
sent to the manager."
::= { upsETrapsReceiversEntry 3 }
upsETrapType OBJECT-TYPE
SYNTAX INTEGER { none ( 1 ) , rfc1628Trap ( 2 ) , eppcTrap ( 3 ) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "The type of trap to be received by the manager."
::= { upsETrapsReceiversEntry 4 }
upsETrapsSeverityLevel OBJECT-TYPE
SYNTAX INTEGER { informational ( 1 ) , warning ( 2 ) , severe ( 3 ) }
ACCESS read-write
STATUS mandatory
DESCRIPTION "The severity level of traps to be received by this manager."
::= { upsETrapsReceiversEntry 5 }
upsETrapReceiverDescription OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 63 ) )
ACCESS read-write
STATUS mandatory
DESCRIPTION "Description of trap receivers"
::= { upsETrapsReceiversEntry 6 }
upsETrapState OBJECT-TYPE
SYNTAX DisplayString ( SIZE ( 0 .. 127 ) )
ACCESS read-only
STATUS mandatory
DESCRIPTION "the values indicate the unrestored traps.
For example, after AC fail, the agent send
the trap 1(AC Fail) and trap 7(battery on) to
NMS. so the value of upsETrapState should be '1,7'.
And then the AC restore, the value of upsETrapState
should change to empty."
::= { upsETrapControl 2 }
-- ===========================================================================
-- Trap defination
-- ===========================================================================
upsEPowerFail TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Utility power not available."
::= 1
upsEPowerRestored TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Utility power has restored."
::= 2
upsELowBattery TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"SEVERE: The UPS batteries are low and will soon be exhausted."
::= 3
upsEReturnFromLowBattery TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: The UPS has return from a low battery condition."
::= 4
upsEFailed TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"SEVERE: The UPS is not working fine."
::= 5
upsEOk TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: The UPS is working fine."
::= 6
upsEOnBattery TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEBatteryEstimatedMinutesRemaining,
upsESecondsOnBattery
}
DESCRIPTION
"WARNING: The UPS has switched to battery backup power."
::= 7
upsENotOnBattery TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: The UPS is not on battery power."
::= 8
upsETestInProgress TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: The testing is going on ups."
::= 9
upsETestOver TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEBatteryTestStart,
upsEBatteryTestSettingTime,
upsEBatteryTestResult,
upsEBatteryTestStartTime
}
DESCRIPTION
"INFORMATION: The testing of UPS is completed."
::= 10
upsEBypassOn TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: The UPS has enabled bypass."
::= 11
upsEOnline TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: The UPS is not on Bypass and return to normal status."
::= 12
upsECommunicationLost TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"SEVERE: Communication to the UPS has been lost."
::= 13
upsECommunicationEstablished TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Communication with the UPS has been established."
::= 14
upsEGoingShutdown TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: The UPS is going to shutdown output."
::= 15
upsEShutdownCancelled TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: The UPS is not going to shutdown output."
::= 16
upsEOutlet1GoingShutdown TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: The UPS is going to shutdown outlet1."
::= 17
upsEOutlet1ShutdownCancelled TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: The UPS is not going to shutdown outlet1."
::= 18
upsEOutlet2GoingShutdown TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: The UPS is going to shutdown outlet2."
::= 19
upsEOutlet2ShutdownCancelled TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: The UPS is not going to shutdown outlet2."
::= 20
upsESleeping TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEControlOutputOnDelay
}
DESCRIPTION
"INFORMATION: UPS has entered sleep mode and power to load has been cut off."
::= 21
upsEWokeUp TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: The UPS woke up from sleep mode and power to load has been restored."
::= 22
upsEOverTemperature TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsESystemTemperature,
upsESystemConfigOverTemperatureSetPoint
}
DESCRIPTION
"WARNING: The UPS temperature is over the setting limit."
::= 23
upsENotOverTemperature TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsESystemTemperature,
upsESystemConfigOverTemperatureSetPoint
}
DESCRIPTION
"INFORMATION: The UPS temperature is not over the setting limit."
::= 24
upsEOverLoad TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsESystemOutputLoad,
upsESystemConfigOutputLoadHighSetPoint
}
DESCRIPTION
"WARNING: The UPS load is over the setting limit."
::= 25
upsENotOverLoad TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsESystemOutputLoad,
upsESystemConfigOutputLoadHighSetPoint
}
DESCRIPTION
"INFORMATION: The UPS load is not over the setting limit."
::= 26
upsEModuleInserted TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: UPS module or charger module plug-in."
::= 27
upsEModuleRemoved TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: UPS module or charger module unplugs."
::= 28
sensorTemperatureTooHigh TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEEnvironmentTemperatureHighSetPoint,
upsEEnvironmentCurrentTemperature
}
DESCRIPTION
"WARNING: Sensor Temperature over high Set point."
::= 29
sensorTemperatureNotHigh TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEEnvironmentTemperatureHighSetPoint,
upsEEnvironmentCurrentTemperature
}
DESCRIPTION
"INFORMATION: Sensor Temperature not over high Set point."
::= 30
sensorTemperatureTooLow TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEEnvironmentTemperatureLowSetPoint,
upsEEnvironmentCurrentTemperature
}
DESCRIPTION
"WARNING: Sensor Temperature under low Set point."
::= 31
sensorTemperatureNotLow TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEEnvironmentTemperatureLowSetPoint,
upsEEnvironmentCurrentTemperature
}
DESCRIPTION
"INFORMATION: Sensor Temperature not under low Set point."
::= 32
sensorHumidityTooHigh TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEEnvironmentHumidityHighSetPoint,
upsEEnvironmentCurrentHumidity
}
DESCRIPTION
"WARNING: Sensor Humidity over high Set point."
::= 33
sensorHumidityNotHigh TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEEnvironmentHumidityHighSetPoint,
upsEEnvironmentCurrentHumidity
}
DESCRIPTION
"INFORMATION: Sensor Humidity not over high Set point."
::= 34
sensorHumidityTooLow TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEEnvironmentHumidityLowSetPoint,
upsEEnvironmentCurrentHumidity
}
DESCRIPTION
"WARNING: Sensor Humidity under low Set point."
::= 35
sensorHumidityNotLow TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEEnvironmentHumidityLowSetPoint,
upsEEnvironmentCurrentHumidity
}
DESCRIPTION
"INFORMATION: Sensor Humidity not under low Set point."
::= 36
contactAlarm1Active TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEEnvironmentContactType,
upsEEnvironmentContactDescription
}
DESCRIPTION
"WARNING: Contact Alarm-1 activated."
::= 37
concactAlarm1Normal TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEEnvironmentContactType,
upsEEnvironmentContactDescription
}
DESCRIPTION
"INFORMATION: Contact Alarm-1 not active."
::= 38
contactAlarm2Active TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEEnvironmentContactType,
upsEEnvironmentContactDescription
}
DESCRIPTION
"WARNING: Contact Alarm-2 activated."
::= 39
contactAlarm2Normal TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEEnvironmentContactType,
upsEEnvironmentContactDescription
}
DESCRIPTION
"INFORMATION: Contact Alarm-2 not active."
::= 40
upsEInternalwarning TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Internal warning."
::= 41
upsEReturnFromInternalwarning TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Internal warning."
::= 42
upsEEPOActive TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: EPO Active."
::= 43
upsEReturnFromEPOActive TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from EPO Active."
::= 44
upsEModuleUnlock TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Module Unlock."
::= 45
upsEReturnFromModuleUnlock TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Module Unlock."
::= 46
upsEMain1Neutralloss TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Main 1 Neutral loss."
::= 47
upsEReturnFromMain1Neutralloss TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Main 1 Neutral loss."
::= 48
upsEMain1phaseerror TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Main 1 phase error."
::= 49
upsEReturnFromMain1phaseerror TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Main 1 phase error."
::= 50
upsESitefault TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Site fault."
::= 51
upsEReturnFromSitefault TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Site fault."
::= 52
upsEBypassAbnormal TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Bypass Abnormal."
::= 53
upsEReturnFromBypassAbnormal TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Bypass Abnormal."
::= 54
upsEBypassPhaseError TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Bypass Phase Error."
::= 55
upsEReturnFromBypassPhaseError TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Bypass Phase Error."
::= 56
upsEBatteryOpen TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Battery Open."
::= 57
upsEReturnFromBatteryOpen TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Battery Open."
::= 58
upsEBatteryOverCharge TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Battery Over Charge."
::= 59
upsEReturnFromBatteryOverCharge TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Battery Over Charge."
::= 60
upsEBatteryReverse TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Battery Reverse."
::= 61
upsEReturnFromBatteryReverse TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Battery Reverse."
::= 62
upsEOverloadforewarning TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Overload forewarning."
::= 63
upsEReturnFromOverloadforewarning TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Overload forewarning."
::= 64
upsEOverloadWarning TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Overload Warning."
::= 65
upsEReturnFromOverloadWarning TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Overload Warning."
::= 66
upsEFanLock TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Fan Lock."
::= 67
upsEReturnFromFanLock TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Fan Lock."
::= 68
upsEMaintaincoverisopen TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Maintain cover is open."
::= 69
upsEReturnFromMaintaincoverisopen TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Maintain cover is open."
::= 70
upsEChargerfault TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Charger fault."
::= 71
upsEReturnFromChargerfault TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Charger fault."
::= 72
upsEModulelocationerror TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Module location error."
::= 73
upsEReturnFromModulelocationerror TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Module location error."
::= 74
upsETurnonabnormal TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Turn on abnormal."
::= 75
upsEReturnFromTurnonabnormal TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Turn on abnormal."
::= 76
upsERedundancyloss TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Redundancy loss."
::= 77
upsEReturnFromRedundancyloss TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Redundancy loss."
::= 78
upsEHotSwapActived TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Hot Swap Active."
::= 79
upsEReturnFromHotSwapActived TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Hot Swap Active."
::= 80
upsEBatteryInform TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Battery Inform."
::= 81
upsEReturnFromBatteryInform TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Battery Inform."
::= 82
upsEInspectionInform TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Inspection Inform."
::= 83
upsEReturnFromInspectionInform TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Inspection Inform."
::= 84
upsEGuaranteeInform TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Guarantee Inform."
::= 85
upsEReturnFromGuaranteeInform TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Guarantee Inform."
::= 86
upsETemperatureLow TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Temperature Low."
::= 87
upsEReturnFromTemperatureLow TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Temperature Low."
::= 88
upsETemperatureHigh TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Temperature High."
::= 89
upsEReturnFromTemperatureHigh TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Temperature High."
::= 90
upsEBatteryOverTemperature TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Battery Over Temperature."
::= 91
upsEReturnFromBatteryOverTemperature TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Battery Over Temperature."
::= 92
upsEFanMaintainInform TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Fan Maintain Inform."
::= 93
upsEReturnFromFanMaintainInform TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Fan Maintain Inform."
::= 94
upsEBusCapacitanceMaintainInform TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Bus Capacitance Maintain Inform."
::= 95
upsEReturnFromBusCapacitanceMaintainInform TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from Bus Capacitance Maintain Inform."
::= 96
upsESystemOverCapacity TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: System Over Capacity."
::= 97
upsEReturnFromSystemOverCapacity TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Return from System Over Capacity."
::= 98
-- Trap Id 99-122 is not defined.
upsEBelowCapacityLimit TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEBatteryEstimatedChargeRemaining,
upsESystemConfigBelowCapacityLimit
}
DESCRIPTION
"SEVERE: The UPS batteries capacity is lower than setting limit."
::= 123
upsENotBelowCapacityLimit TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: The UPS batteries capacity is not lower than setting limit."
::= 124
upsEBelowRemainTimeLimit TRAP-TYPE
ENTERPRISE upsETraps
VARIABLES {
upsEBatteryEstimatedMinutesRemaining,
upsESystemConfigBelowRemainTimeLimit
}
DESCRIPTION
"SEVERE: The UPS batteries backup time is below the setting limit."
::= 125
upsENotBelowRemainTimeLimit TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: The UPS batteries backup time is not below the setting limit."
::= 126
upsELoadSegment1Off TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Load segment 1 is off."
::= 127
upsELoadSegment1On TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Load segment 1 is on."
::= 128
upsELoadSegment2Off TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"WARNING: Load segment 2 is off."
::= 129
upsELoadSegment2On TRAP-TYPE
ENTERPRISE upsETraps
DESCRIPTION
"INFORMATION: Load segment 2 is on."
::= 130
END