--    PPC MIB
 | 
						|
--    ====================================================================
 | 
						|
--    Revision History
 | 
						|
--     v0.13  2011-11-10   Gavin Zhao created, Lilinhua modified
 | 
						|
--     *************************NMC v0.0.1.7***********************************
 | 
						|
--     v0.14  2011-11-18   Lilinhua
 | 
						|
--                         1. Modify string "ppcTrap" to "eppcTrap"
 | 
						|
--	      2012-02-09   Lilinhua
 | 
						|
--			   1. Modify upsESystemFaultCode's description "The warning code of UPS" to "The fault code of UPS".
 | 
						|
--     *************************NMC v1.1.0.4************************************
 | 
						|
--     v0.15  2012-07-20   Lilinhua
 | 
						|
--			   1. upsEShutdownWarningPeriodInterval, modify access from read-only to read-write.
 | 
						|
--			   2. upsEShutdownwarningPeriodTime, add unit second.
 | 
						|
--            2012-07-31   Lilinhua
 | 
						|
--                         1. Modify upsEBatteryTestElapsedTime's format from hh:mm:ss.ss to hh:mm:ss
 | 
						|
--            2012-08-09   Lilinhua
 | 
						|
--			   1. Modify values of upsEModuleWorkingMode as upsESystemStatus's.
 | 
						|
--     *************************NMC v1.1.0.6************************************
 | 
						|
--            2012-08-27   Lilinhua
 | 
						|
--			   1. Modify "Moudles" to "Modules", advised by Beth. 
 | 
						|
--			   2. Modify module name as phase name "upsEModuleOutputCurrentR", "upsEModuleOutputWattR", "upsEModuleOutputLoadR".
 | 
						|
--			   3. Add Convert module item "upsEModuleTrapState(12)".
 | 
						|
--			   4. Add Convert module item "upsEModuleConfigOutputVA(13)".
 | 
						|
--			   5. Add Convert module item "upsEModuleOutputCurrentS(14)", "upsEModuleOutputCurrentT(15)".
 | 
						|
--			   6. Add Convert module item "upsEModuleOutputWattS(16)", "upsEModuleOutputWattT(17)".
 | 
						|
--			   7. Add Convert module item "upsEModuleOutputLoadS(18)", "upsEModuleOutputLoadT(19)".
 | 
						|
--			   8. Add Convert module item "upsEModuleOutputVAR(20)", "upsEModuleOutputVAS(21)", "upsEModuleOutputVAT(22)".
 | 
						|
--			   9. Modify upsETrapState max length from 255 to 127.
 | 
						|
--     *************************NMC v1.1.0.6************************************
 | 
						|
--            2012-08-27   Lilinhua
 | 
						|
--			   1. Modify trap description of Overload, OverTemperature. 
 | 
						|
--     *************************NMC v1.3.0.0************************************
 | 
						|
--            2013-06-21   Lilinhua
 | 
						|
--			   1. Add two upsEShutdownEvents: "belowCapacityLimit(11), belowRemainTimeLimit(12)".
 | 
						|
--			   2. Add 4 traps: upsEBelowCapacityLimit, upsENotBelowCapacityLimit, upsEBelowRemainTimeLimit, upsENotBelowRemainTimeLimit.
 | 
						|
--			   3. Add 2 config data: upsESystemConfigBelowCapacityLimit, upsESystemConfigBelowRemainTimeLimit.
 | 
						|
--			   4. Modify upsETrapState's description: "trap 2(battery on)" to "trap 7(battery on)".
 | 
						|
--     *************************NMC v1.4.0.3************************************
 | 
						|
--            2014-10-15   Lilinhua
 | 
						|
--			   1. Modify descriptions of "upsEEnvironmentTemperatureHighSetPoint, upsEEnvironmentHumidityHighSetPoint,
 | 
						|
--			      upsEEnvironmentTemperatureLowSetPoint, upsEEnvironmentHumidityLowSetPoint".
 | 
						|
--     *************************NMC v1.5.0.4************************************
 | 
						|
--     v0.16  2015-01-05   Lilinhua
 | 
						|
--			   1. Modify MIB for add Load segment.
 | 
						|
 | 
						|
 | 
						|
EPPC-MIB	DEFINITIONS ::= BEGIN
 | 
						|
		IMPORTS
 | 
						|
		TRAP-TYPE
 | 
						|
			FROM RFC-1215
 | 
						|
		DisplayString
 | 
						|
			FROM SNMPv2-TC
 | 
						|
		OBJECT-TYPE
 | 
						|
			FROM RFC-1212
 | 
						|
		enterprises,Counter, IpAddress
 | 
						|
			FROM RFC1155-SMI
 | 
						|
                PositiveInteger,NonNegativeInteger
 | 
						|
                     	FROM UPS-MIB;
 | 
						|
 | 
						|
ppc         	           OBJECT IDENTIFIER ::=  {  enterprises  935  }
 | 
						|
 | 
						|
device			   OBJECT IDENTIFIER ::=  {  ppc  10  }
 | 
						|
upsAgent		   OBJECT IDENTIFIER ::=  {  device  1  }
 | 
						|
 | 
						|
upsE	                   OBJECT IDENTIFIER ::=  {  upsAgent  1  }
 | 
						|
upsETraps  		   OBJECT IDENTIFIER ::=  {  upsAgent  2  }
 | 
						|
upsEIdentity	       	   OBJECT IDENTIFIER ::=  {  upsE  1  }
 | 
						|
upsESystemSummary	   OBJECT IDENTIFIER ::=  {  upsE  2  }
 | 
						|
upsEBatterySystem	   OBJECT IDENTIFIER ::=  {  upsE  3  }
 | 
						|
upsEPowerConverterSystem   OBJECT IDENTIFIER ::=  {  upsE  4  }
 | 
						|
upsELoadSegment            OBJECT IDENTIFIER ::=  {  upsE  5  }
 | 
						|
upsEEnvironment	           OBJECT IDENTIFIER ::=  {  upsE  6 }
 | 
						|
upsEBatteryTest	           OBJECT IDENTIFIER ::=  {  upsE  7 }
 | 
						|
upsEControl                OBJECT IDENTIFIER ::=  {  upsE  8 }
 | 
						|
upsETrapControl		   OBJECT IDENTIFIER ::=  {  upsE  9 }
 | 
						|
 | 
						|
--========================================================================
 | 
						|
--upsEIdentity
 | 
						|
--========================================================================
 | 
						|
 | 
						|
	upsEIdentityManufacturer	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 31  ) ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The name of the UPS manufacturer."
 | 
						|
		::=  {  upsEIdentity  1  }
 | 
						|
 | 
						|
	upsEIdentityModel	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 63  ) ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The UPS Model designation."
 | 
						|
		::=  {  upsEIdentity  2  }
 | 
						|
 | 
						|
	upsEIdentityUPSFirmwareVerison	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 31  ) ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The UPS firmware/software version(s)."
 | 
						|
		::=  {  upsEIdentity  3  }
 | 
						|
 | 
						|
	upsEIndentityUPSSerialNumber	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 31  ) ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"optional.
 | 
						|
                               Most UPS don't supply the value of UPS serial No."
 | 
						|
		::=  {  upsEIdentity  4  }
 | 
						|
 | 
						|
	upsEIdentityDescription	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 63  ) ) 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"A string to identify the UPS. This object should be
 | 
						|
               set by the administrator."
 | 
						|
		::=  {  upsEIdentity  5  }
 | 
						|
 | 
						|
	upsEIdentityAgentSoftwareVerison	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 31  ) ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The Network Management Card software/firmware version.  
 | 
						|
                               This variable may or may not have the same value as
 | 
						|
                               upsEIdentGroupUPSSoftwareVersion in some implementations."
 | 
						|
		::=  {  upsEIdentity  6  }
 | 
						|
 | 
						|
	upsEIdentityAttachedDevices	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 63  ) ) 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"A string identifying the devices attached to the output(s) 
 | 
						|
                               of the UPS. This object should be set by the administrator"
 | 
						|
		::=  {  upsEIdentity  7  }
 | 
						|
 | 
						|
--========================================================================
 | 
						|
--upsESystemSummary
 | 
						|
--========================================================================
 | 
						|
 | 
						|
	upsESystemStatus	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { power-on ( 1 ) , stand-by( 2 ) , by-pass ( 3 ) ,
 | 
						|
                                                line( 4 ) , battery ( 5 ) , battery-test ( 6 ) , fault ( 7 ) ,
 | 
						|
                                               converter ( 8  ) , eco ( 9 ) , shutdown ( 10 ) , on-booster ( 11 ) , on-reducer ( 12 ) , other( 13 )  } 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The indication of UPS system status."
 | 
						|
		::=  {  upsESystemSummary  1  }
 | 
						|
 | 
						|
      upsESystemTemperature	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The temperature of UPS presented in 0.1 degree."
 | 
						|
		::=  {  upsESystemSummary  2  }
 | 
						|
 | 
						|
	upsESystemWarningCode	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 15 ) ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The warning code of UPS. Please refer the warning table 
 | 
						|
                              of 'Q6' for details."
 | 
						|
		::=  {  upsESystemSummary  3  }
 | 
						|
 | 
						|
	upsESystemFaultCode	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 15 ) ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The fault code of UPS.Please refer the fault code
 | 
						|
                              of 'Q6' for details."
 | 
						|
		::=  {  upsESystemSummary  4  }
 | 
						|
 | 
						|
	upsESystemConfigInputVoltage	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger  
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The magnitude of the nominal input voltage presented in 0.1 V. On those 
 | 
						|
                               systems  which support read-write access to this object, if there is an 
 | 
						|
                               attempt to set this variable to a value that is not supported,
 | 
						|
                               the request must be rejected and the agent shall respond with an 
 | 
						|
                               appropriate error message, i.e., badValue for SNMPv1, or 
 | 
						|
                               inconsistentValue for SNMPv2."
 | 
						|
		::=  {  upsESystemSummary  5  }
 | 
						|
 | 
						|
	upsESystemConfigInputFrequence	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The nominal input frequency presented in 0.1 Hz. On those systems which support 
 | 
						|
                               read-write access to this object, if there is an attempt to 
 | 
						|
                               set this variable to a value that is not supported, the request 
 | 
						|
                               must be rejected and the agent shall respond with an appropriate 
 | 
						|
                               error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2."
 | 
						|
		::=  {  upsESystemSummary  6  }
 | 
						|
 | 
						|
	upsESystemConfigOutputVoltage	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The magnitude of the nominal output voltage presented in 0.1V. On those systems
 | 
						|
                               which support read-write access to this object, if there is an 
 | 
						|
                               attempt to set this variable to a value that is not supported, 
 | 
						|
                               the request must be rejected and the agent shall respond with an
 | 
						|
                               appropriate error message, i.e., badValue for SNMPv1, or 
 | 
						|
                               inconsistentValue for SNMPv2"
 | 
						|
		::=  {  upsESystemSummary  7  }
 | 
						|
 | 
						|
	upsESystemConfigOutputFrequency	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger  
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The nominal output frequency presented in 0.1Hz. On those systems which support 
 | 
						|
                               read-write access to this object, if there is an attempt to set 
 | 
						|
                               this variable to a value that is not supported, the request must
 | 
						|
                               be rejected and the agent shall respond with an appropriate error 
 | 
						|
                               message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2."
 | 
						|
		::=  {  upsESystemSummary  8  }
 | 
						|
 | 
						|
	upsESystemConfigOutputVA	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger   
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The magnitude of the nominal Volt-Amp rating presented in VA."
 | 
						|
		::=  {  upsESystemSummary  9  }
 | 
						|
 | 
						|
	upsESystemConfigOutputPower	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger  
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The magnitude of the nominal true power rating presented in W ."
 | 
						|
		::=  {  upsESystemSummary  10  }
 | 
						|
 | 
						|
	upsESystemConfigOutputLoadHighSetPoint	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger   
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The maximum output load allowed before the load is too high for 
 | 
						|
                               UPS operation "
 | 
						|
		::=  {  upsESystemSummary  11  }
 | 
						|
 | 
						|
	upsESystemConfigOverTemperatureSetPoint	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger   
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The maximum temperature allowed before the UPS
 | 
						|
                                         operation temperature is too high, presented in 0.1 degree."
 | 
						|
		::=  {  upsESystemSummary  12  }
 | 
						|
 | 
						|
	upsESystemInputSourceNum	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The present external source of input power."
 | 
						|
		::=  {  upsESystemSummary  13  }
 | 
						|
 | 
						|
	upsESystemInputLineBads	OBJECT-TYPE	
 | 
						|
		SYNTAX			Counter
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The number of times the Input was out of tolerance in voltage or frequency.
 | 
						|
                               Its value should be initialized 0 after agent restarting. "
 | 
						|
		::=  {  upsESystemSummary  14  }
 | 
						|
 | 
						|
	upsESystemInputNumPhases	OBJECT-TYPE	
 | 
						|
		SYNTAX			PositiveInteger  ( 1 .. 3  ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The number of input phase utilized is this device, serves as the table index.
 | 
						|
                               This value indicate the device initialized feature."
 | 
						|
		::=  {  upsESystemSummary  15  }
 | 
						|
 | 
						|
	upsESystemInputTable	OBJECT-TYPE
 | 
						|
		SYNTAX		SEQUENCE  OF  UpsSystemInputEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	"A list of input table entries. The number of entries is given by the 
 | 
						|
                            value of upsESystemInputNumPhase."
 | 
						|
		::=  { upsESystemSummary  16 }
 | 
						|
 | 
						|
	upsESystemInputEntry	OBJECT-TYPE
 | 
						|
		SYNTAX		UpsSystemInputEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION 	"An entry containing information applicable to a particular input line."
 | 
						|
		INDEX		{  upsESystemInputPhase  }
 | 
						|
		::=  { upsESystemInputTable 1 }
 | 
						|
 | 
						|
	UpsSystemInputEntry  ::=  SEQUENCE {
 | 
						|
		upsESystemInputPhase  PositiveInteger,
 | 
						|
		upsESystemInputFrequency  NonNegativeInteger,
 | 
						|
		upsESystemInputVoltage  NonNegativeInteger,
 | 
						|
		upsESystemInputCurrent  NonNegativeInteger,
 | 
						|
		upsESystemInputWatts  NonNegativeInteger
 | 
						|
		}
 | 
						|
 | 
						|
 | 
						|
	upsESystemInputPhase	OBJECT-TYPE	
 | 
						|
		SYNTAX			PositiveInteger( 1 .. 3  ) 
 | 
						|
		ACCESS		not-accessible
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The number of the phase. Serves as index for input table"
 | 
						|
		::=  {  upsESystemInputEntry  1  }
 | 
						|
 | 
						|
 | 
						|
	upsESystemInputFrequency	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured input frquency from the UPS meters in 0.1Hz."
 | 
						|
		::=  {  upsESystemInputEntry  2  }
 | 
						|
 | 
						|
 | 
						|
	upsESystemInputVoltage	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured input voltage from the UPS meters in 0.1 volts"
 | 
						|
		::=  {  upsESystemInputEntry  3  }
 | 
						|
 | 
						|
 | 
						|
	upsESystemInputCurrent	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured input mandatory from the UPS meters in 0.1 amps."
 | 
						|
		::=  {  upsESystemInputEntry  4  }
 | 
						|
 | 
						|
 | 
						|
	upsESystemInputWatts	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured input real power in watts."
 | 
						|
		::=  {  upsESystemInputEntry  5  }
 | 
						|
 | 
						|
	upsESystemOutputNumPhase	OBJECT-TYPE	
 | 
						|
		SYNTAX			PositiveInteger ( 1 .. 3  ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The number of metered output phases, serves as the table index.
 | 
						|
                               This value indicate the device initialized feature."
 | 
						|
		::=  {  upsESystemSummary  17  }
 | 
						|
 | 
						|
	upsESystemOutputTable	OBJECT-TYPE
 | 
						|
		SYNTAX		SEQUENCE  OF  UpsSystemOutputEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	       "A list of output table entries. The number of entries is given 
 | 
						|
                                by the value of upsESystemOutputNumPhase."
 | 
						|
		::=  { upsESystemSummary  18 }
 | 
						|
 | 
						|
	upsESystemOutputEntry	OBJECT-TYPE
 | 
						|
		SYNTAX		UpsSystemOutputEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION  	"An entry containing information applicable to a particular line."
 | 
						|
		INDEX		{  upsESystemOutputPhase  }
 | 
						|
		::=  { upsESystemOutputTable 1 }
 | 
						|
 | 
						|
	UpsSystemOutputEntry  ::=  SEQUENCE {
 | 
						|
		upsESystemOutputPhase  PositiveInteger,
 | 
						|
		upsESystemOutputFrequency  NonNegativeInteger,
 | 
						|
		upsESystemOutputVoltage  NonNegativeInteger,
 | 
						|
		upsESystemOutputCurrent  NonNegativeInteger,
 | 
						|
		upsESystemOutputWatts  NonNegativeInteger,
 | 
						|
            upsESystemOutputVA   NonNegativeInteger,
 | 
						|
		upsESystemOutputLoad  NonNegativeInteger
 | 
						|
		}
 | 
						|
 | 
						|
 | 
						|
	upsESystemOutputPhase	OBJECT-TYPE	
 | 
						|
		SYNTAX			PositiveInteger ( 1 .. 3  ) 
 | 
						|
		ACCESS		not-accessible
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The number of the phase. Serves as index for output table"
 | 
						|
		::=  {  upsESystemOutputEntry  1  }
 | 
						|
 | 
						|
 | 
						|
	upsESystemOutputFrequency	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured output frequency from the UPS meters in 0.1Hz."
 | 
						|
		::=  {  upsESystemOutputEntry  2  }
 | 
						|
 | 
						|
 | 
						|
	upsESystemOutputVoltage	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured output voltage from the UPS meters in 0.1 volts"
 | 
						|
		::=  {  upsESystemOutputEntry  3  }
 | 
						|
 | 
						|
 | 
						|
	upsESystemOutputCurrent	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured output mandatory from the UPS meters in 0.1 amps."
 | 
						|
		::=  {  upsESystemOutputEntry  4  }
 | 
						|
 | 
						|
 | 
						|
	upsESystemOutputWatts	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured output real power in watts."
 | 
						|
		::=  {  upsESystemOutputEntry  5  }
 | 
						|
 | 
						|
	upsESystemOutputVA	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured output real complex power in VA."
 | 
						|
		::=  {  upsESystemOutputEntry  6  }
 | 
						|
 | 
						|
 | 
						|
	upsESystemOutputLoad	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The UPS output load in percent of rated capacity."
 | 
						|
		::=  {  upsESystemOutputEntry  7  }
 | 
						|
 | 
						|
	upsESystemBypassNumPhase	OBJECT-TYPE	
 | 
						|
		SYNTAX			PositiveInteger ( 1 .. 3  ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The number of  bypass phases, serves as the table index.
 | 
						|
                               This value indicate the device initialized feature"
 | 
						|
		::=  {  upsESystemSummary  19  }
 | 
						|
 | 
						|
	upsESystemBypassTable	OBJECT-TYPE
 | 
						|
		SYNTAX		SEQUENCE  OF  UpsSystemBypassEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	    "A list of bypass table entries. The number of entries is given by the
 | 
						|
                            value of upsESystemBypassNumPhase."
 | 
						|
		::=  { upsESystemSummary  20 }
 | 
						|
 | 
						|
 | 
						|
	upsESystemBypassEntry	OBJECT-TYPE
 | 
						|
		SYNTAX		UpsSystemBypassEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION 	"An entry containing information applicable to a particular line."
 | 
						|
		INDEX		{  upsESystemBypassPhase  }
 | 
						|
		::=  { upsESystemBypassTable 1 }
 | 
						|
 | 
						|
	UpsSystemBypassEntry  ::=  SEQUENCE {
 | 
						|
		upsESystemBypassPhase  PositiveInteger,
 | 
						|
		upsESystemBypassFrequency  NonNegativeInteger,
 | 
						|
		upsESystemBypassVoltage  NonNegativeInteger,
 | 
						|
		upsESystemBypassCurrent  NonNegativeInteger,
 | 
						|
		upsESystemBypassWatts  NonNegativeInteger
 | 
						|
		}
 | 
						|
 | 
						|
 | 
						|
	upsESystemBypassPhase	OBJECT-TYPE	
 | 
						|
		SYNTAX			PositiveInteger ( 1 .. 3  ) 
 | 
						|
		ACCESS		not-accessible
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The number of the phase. Serves as index for bypass table"
 | 
						|
		::=  {  upsESystemBypassEntry  1  }
 | 
						|
 | 
						|
 | 
						|
	upsESystemBypassFrequency	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured bypass frequency from the UPS meters in 0.1 Hz."
 | 
						|
		::=  {  upsESystemBypassEntry  2  }
 | 
						|
 | 
						|
 | 
						|
	upsESystemBypassVoltage	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured bypass voltage from the UPS meters in 0.1 volts"
 | 
						|
		::=  {  upsESystemBypassEntry  3  }
 | 
						|
 | 
						|
 | 
						|
	upsESystemBypassCurrent	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured bypass mandatory from the UPS meters in 0.1 amps"
 | 
						|
		::=  {  upsESystemBypassEntry  4  }
 | 
						|
 | 
						|
 | 
						|
	upsESystemBypassWatts	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured input real power in watts."
 | 
						|
		::=  {  upsESystemBypassEntry  5  }
 | 
						|
 | 
						|
 | 
						|
	upsESystemConfigBelowCapacityLimit	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger   
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The UPS batteries capacity(%) limit for shutdown"
 | 
						|
		::=  {  upsESystemSummary  21  }
 | 
						|
 | 
						|
	upsESystemConfigBelowRemainTimeLimit	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger   
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The UPS batteries backup time(minute) limit for shutdown"
 | 
						|
		::=  {  upsESystemSummary  22  }
 | 
						|
 | 
						|
--========================================================================
 | 
						|
--upsEBatterySystem
 | 
						|
--========================================================================
 | 
						|
 | 
						|
	upsEBatteryStatus	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { unknown ( 1 ) , batteryNormal ( 2 ) , batteryLow ( 3 ) , 
 | 
						|
                                               batteryDepleted ( 4 ) , batteryDischarging ( 5 ) , batteryFailure ( 6 ) } 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		" The status of UPS battery, a value of batteryLow indicates
 | 
						|
                                that the battery-low status bit has been set from device. 
 | 
						|
                                A value of batteryDepleted indicates that the UPS will be 
 | 
						|
                                unable to sustain the present load when and if the utility 
 | 
						|
                                power is lost (including the possibility that the  utility 
 | 
						|
                                power is mandatoryly absent and the UPS is unable to sustain
 | 
						|
                                the output)"
 | 
						|
		::=  {  upsEBatterySystem  1  }
 | 
						|
 | 
						|
	upsESecondsOnBattery	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"If the unit is on battery power, the elapsed time
 | 
						|
                                   since the UPS last switched to battery power, or the
 | 
						|
                                   time since the network management subsystem was last
 | 
						|
                                   restarted, whichever is less. 0 shall be returned
 | 
						|
                                   if the unit is not on battery power"
 | 
						|
		::=  {  upsEBatterySystem  2  }
 | 
						|
 | 
						|
	upsEBatteryEstimatedMinutesRemaining	OBJECT-TYPE	
 | 
						|
		SYNTAX			PositiveInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"An estimate of the time to battery charge depletion
 | 
						|
                                   under the present load conditions if the utility power
 | 
						|
                                   is off and remains off, or if it were to be lost and
 | 
						|
                                   remain off."
 | 
						|
		::=  {  upsEBatterySystem  3  }
 | 
						|
 | 
						|
	upsEBatteryEstimatedChargeRemaining	OBJECT-TYPE	
 | 
						|
		SYNTAX			Integer32  ( 0 .. 100  ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"An estimate of the battery charge remaining expressed
 | 
						|
                                   as a percent of full charge"
 | 
						|
		::=  {  upsEBatterySystem  4  }
 | 
						|
 | 
						|
	upsEPositiveBatteryVoltage	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The magnitude of the present positive battery voltage in 0.1 Volt DC"
 | 
						|
		::=  {  upsEBatterySystem  5  }
 | 
						|
 | 
						|
	upsENegativeBatteryVoltage	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The magnitude of the present negative battery voltage in 0.1 Volt DC"
 | 
						|
		::=  {  upsEBatterySystem  6  }
 | 
						|
 | 
						|
	upsEBatteryCellNumber	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"This object indicate the cell number of each set."
 | 
						|
		::=  {  upsEBatterySystem  7  }
 | 
						|
 | 
						|
	upsEBatteryTemperature	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The ambient temperature at or near the UPS Battery
 | 
						|
                               casing in 0.1 degree."
 | 
						|
		::=  {  upsEBatterySystem  8  }
 | 
						|
 | 
						|
	upsEBatteryLastReplacedDate	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 10 .. 10  ) ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The date when the Batteries in this UPS were last replaced.
 | 
						|
                               The format should be DD/MM/YYYY."
 | 
						|
		::=  {  upsEBatterySystem  9  }
 | 
						|
     
 | 
						|
       upsEBatteryABMStatus          OBJECT-TYPE
 | 
						|
            SYNTAX                  INTEGER { charge ( 1 ) , float ( 2 ) , rest ( 3 ) ,
 | 
						|
                                              discharge ( 4 ) , disable ( 5 ) }
 | 
						|
            ACCESS             read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		" The status of ABM."
 | 
						|
		::=  {  upsEBatterySystem  10  }
 | 
						|
 | 
						|
	upsEChargerModulesNum	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger  ( 0 .. 32  ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The number of charger modules inserted to UPS systems. served 
 | 
						|
                                   as the index of the upsEChargerModulesTable.
 | 
						|
                                   The default value 0 indicate that the UPS system don't have 
 | 
						|
                                   separate charger module."
 | 
						|
		::=  {  upsEBatterySystem  11  }
 | 
						|
 | 
						|
	upsEChargerModulesTable	OBJECT-TYPE
 | 
						|
		SYNTAX		SEQUENCE  OF  UpsChargerModulesEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	"A list of charger modules entries. The number of entries is given 
 | 
						|
                            by the value of upsEchargerModulesNum."
 | 
						|
		::=  { upsEBatterySystem  12 }
 | 
						|
 | 
						|
	upsEChargerModulesEntry	OBJECT-TYPE
 | 
						|
		SYNTAX		UpsChargerModulesEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	"An entry containing information applicable to a particular charger module."
 | 
						|
		INDEX		{  chargerModulesNum  }
 | 
						|
		::=  { upsEChargerModulesTable 1 }
 | 
						|
 | 
						|
	UpsChargerModulesEntry  ::=  SEQUENCE {
 | 
						|
		chargerModulesNum  PositiveInteger,
 | 
						|
		chargerModulesAddress  NonNegativeInteger  ,
 | 
						|
		positiveChargeVotlage  NonNegativeInteger,
 | 
						|
		negativeChargeVoltage  NonNegativeInteger,
 | 
						|
		positiveChargeCurrent  NonNegativeInteger,
 | 
						|
		negativeChargeCurrent  NonNegativeInteger,
 | 
						|
		chargerModulesTemperature  INTEGER,
 | 
						|
		chargerModulesMode  INTEGER
 | 
						|
		}
 | 
						|
 | 
						|
 | 
						|
	chargerModulesNum	OBJECT-TYPE	
 | 
						|
		SYNTAX			PositiveInteger ( 1 .. 32  ) 
 | 
						|
		ACCESS		not-accessible
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The number of charger modules. Serves as index for charger module table"
 | 
						|
		::=  {  upsEChargerModulesEntry  1  }
 | 
						|
 | 
						|
 | 
						|
	chargerModulesAddress	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger  
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"Charger Modules' address."
 | 
						|
		::=  {  upsEChargerModulesEntry  2  }
 | 
						|
 | 
						|
 | 
						|
	positiveChargeVotlage	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured positive charger voltage from the UPS meters in 0.1 volts"
 | 
						|
		::=  {  upsEChargerModulesEntry  3  }
 | 
						|
 | 
						|
 | 
						|
	negativeChargeVoltage	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured nepositive charger voltage from the UPS meters in 0.1 volts"
 | 
						|
		::=  {  upsEChargerModulesEntry  4  }
 | 
						|
 | 
						|
 | 
						|
	positiveChargeCurrent	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured positive charger mandatory from the UPS meters in in 0.1 amps."
 | 
						|
		::=  {  upsEChargerModulesEntry  5  }
 | 
						|
 | 
						|
 | 
						|
	negativeChargeCurrent	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured nepositive charger mandatory from the UPS meters in 0.1 amps."
 | 
						|
		::=  {  upsEChargerModulesEntry  6  }
 | 
						|
 | 
						|
 | 
						|
	chargerModulesTemperature	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured charger temperature from the UPS meters in 0.1 degree."
 | 
						|
		::=  {  upsEChargerModulesEntry  7  }
 | 
						|
 | 
						|
 | 
						|
	chargerModulesMode	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { powerOn ( 1 ) , standyby ( 2 ) , fault ( 3 ) , shutdown ( 4 ) , 
 | 
						|
                                               running ( 5 ) , suicide ( 6 ) , unknown ( 7 ) } 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The working mode of charger modules."
 | 
						|
		::=  {  upsEChargerModulesEntry  8  }
 | 
						|
 | 
						|
--========================================================================
 | 
						|
--upsEPowerConverterSystem
 | 
						|
--========================================================================
 | 
						|
 | 
						|
	upsEUPSModulesNum	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger ( 0 .. 32  ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The number of UPS modules inserted to UPS systems. 
 | 
						|
                                   served as the index of the upsEModulesTable.
 | 
						|
                                   the default value 0 indicate that the UPS system do not
 | 
						|
                                   have separate UPS module."
 | 
						|
		::=  {  upsEPowerConverterSystem  1  }
 | 
						|
 | 
						|
	upsEModulesTable	OBJECT-TYPE
 | 
						|
		SYNTAX		SEQUENCE  OF  UpsModulesEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	   "A list of UPS modules entries. The number of entries is 
 | 
						|
                            given by the value of upsEModulesNum."
 | 
						|
		::=  { upsEPowerConverterSystem  2 }
 | 
						|
 | 
						|
	upsEModulesEntry	OBJECT-TYPE
 | 
						|
		SYNTAX		UpsModulesEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	 "An entry containing information applicable to a particular upsE module."
 | 
						|
		INDEX		{  upsEModulesNum  }
 | 
						|
		::=  { upsEModulesTable 1 }
 | 
						|
 | 
						|
	UpsModulesEntry  ::=  SEQUENCE {
 | 
						|
		upsEModulesNum  PositiveInteger,
 | 
						|
		upsEModuleAddress  INTEGER,
 | 
						|
		upsEModulePositiveBusVolt  NonNegativeInteger,
 | 
						|
		upsEModuleNegativeBusVolt  NonNegativeInteger,
 | 
						|
		upsEModuleTemperature  INTEGER,
 | 
						|
		upsEModuleWorkingMode  INTEGER,
 | 
						|
		upsEModuleOutputCurrentR  NonNegativeInteger,
 | 
						|
		upsEModuleOutputWattR  NonNegativeInteger,
 | 
						|
		upsEModuleOutputLoadR  INTEGER,
 | 
						|
		upsEModuleWarningCode DisplayString,
 | 
						|
		upsEModuleFaultCode DisplayString,
 | 
						|
 | 
						|
		upsEModuleTrapState DisplayString,
 | 
						|
		upsEModuleConfigOutputVA  NonNegativeInteger,
 | 
						|
		upsEModuleOutputCurrentS  NonNegativeInteger,
 | 
						|
		upsEModuleOutputCurrentT  NonNegativeInteger,
 | 
						|
		upsEModuleOutputWattS  NonNegativeInteger,
 | 
						|
		upsEModuleOutputWattT  NonNegativeInteger,
 | 
						|
		upsEModuleOutputLoadS  INTEGER,
 | 
						|
		upsEModuleOutputLoadT  INTEGER,
 | 
						|
		upsEModuleOutputVAR  NonNegativeInteger,
 | 
						|
		upsEModuleOutputVAS  NonNegativeInteger,
 | 
						|
		upsEModuleOutputVAT  NonNegativeInteger
 | 
						|
		}
 | 
						|
 | 
						|
 | 
						|
	upsEModulesNum	OBJECT-TYPE	
 | 
						|
		SYNTAX			PositiveInteger  ( 1 .. 32  ) 
 | 
						|
		ACCESS		not-accessible
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The number of UPS modules. Serves as index for UPS module table"
 | 
						|
		::=  {  upsEModulesEntry  1  }
 | 
						|
 | 
						|
 | 
						|
	upsEModuleAddress	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"the address of UPS modules."
 | 
						|
		::=  {  upsEModulesEntry  2  }
 | 
						|
 | 
						|
 | 
						|
	upsEModulePositiveBusVolt	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger  
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured positive upsE module voltage from the UPS meters in 0.1 volts"
 | 
						|
		::=  {  upsEModulesEntry  3  }
 | 
						|
 | 
						|
 | 
						|
	upsEModuleNegativeBusVolt	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured nepositive upsE module voltage from the UPS meters in 0.1 volts"
 | 
						|
		::=  {  upsEModulesEntry  4  }
 | 
						|
 | 
						|
 | 
						|
	upsEModuleTemperature	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured  upsE module temperature from the UPS meters in 0.1 degree."
 | 
						|
		::=  {  upsEModulesEntry  5  }
 | 
						|
 | 
						|
 | 
						|
	upsEModuleWorkingMode	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  {power-on ( 1 ) , stand-by( 2 ) , by-pass ( 3 ) ,
 | 
						|
                                                line( 4 ) , battery ( 5 ) , battery-test ( 6 ) , fault ( 7 ) ,
 | 
						|
                                               converter ( 8  ) , eco ( 9 ) , shutdown ( 10 ) , on-booster ( 11 ) , on-reducer ( 12 ) , other( 13 )  } 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The working mode of UPS modules."
 | 
						|
		::=  {  upsEModulesEntry  6  }
 | 
						|
 | 
						|
 | 
						|
	upsEModuleOutputCurrentR	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured  upsE module output mandatory from the UPS meters in 0.1 A."
 | 
						|
		::=  {  upsEModulesEntry  7  }
 | 
						|
 | 
						|
 | 
						|
	upsEModuleOutputWattR	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured  upsE module output watts from the UPS meters in watts."
 | 
						|
		::=  {  upsEModulesEntry  8  }
 | 
						|
 | 
						|
 | 
						|
	upsEModuleOutputLoadR	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The output load of UPS modules in %."
 | 
						|
		::=  {  upsEModulesEntry  9  }
 | 
						|
 | 
						|
       upsEModuleWarningCode	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 15 ) ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The warning code of ups modules.Please refer the warning table of 'QU,XX' for details."
 | 
						|
		::=  {  upsEModulesEntry  10 }
 | 
						|
 | 
						|
       upsEModuleFaultCode	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 15 ) ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The fault code of ups modules.Please refer command 'QU,XX' for details."
 | 
						|
		::=  {  upsEModulesEntry  11 }
 | 
						|
 | 
						|
	upsEModuleTrapState	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 127  ) ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"the values indicate the unrestored traps.
 | 
						|
					 For example, after AC fail, so the value of upsETrapState should be '1'. 
 | 
						|
					 And then the AC restore, the value of upsEModuleTrapState 
 | 
						|
					 should change to empty."
 | 
						|
		::=  {  upsEModulesEntry  12  }
 | 
						|
 | 
						|
 | 
						|
	upsEModuleConfigOutputVA	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The magnitude of the nominal Volt-Amp rating presented in VA."
 | 
						|
		::=  {  upsEModulesEntry  13  }
 | 
						|
 | 
						|
 | 
						|
	upsEModuleOutputCurrentS	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured  upsE module output mandatory from the UPS meters in 0.1 A."
 | 
						|
		::=  {  upsEModulesEntry  14  }
 | 
						|
 | 
						|
	upsEModuleOutputCurrentT	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured  upsE module output mandatory from the UPS meters in 0.1 A."
 | 
						|
		::=  {  upsEModulesEntry  15  }
 | 
						|
 | 
						|
	upsEModuleOutputWattS	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured  upsE module output watts from the UPS meters in watts."
 | 
						|
		::=  {  upsEModulesEntry  16  }
 | 
						|
 | 
						|
	upsEModuleOutputWattT	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measured  upsE module output watts from the UPS meters in watts."
 | 
						|
		::=  {  upsEModulesEntry  17  }
 | 
						|
 | 
						|
	upsEModuleOutputLoadS	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The output load of UPS modules in %."
 | 
						|
		::=  {  upsEModulesEntry  18  }
 | 
						|
 | 
						|
	upsEModuleOutputLoadT	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The output load of UPS modules in %."
 | 
						|
		::=  {  upsEModulesEntry  19  }
 | 
						|
 | 
						|
	upsEModuleOutputVAR	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The magnitude of the nominal Volt-Amp rating presented in VA."
 | 
						|
		::=  {  upsEModulesEntry  20  }
 | 
						|
 | 
						|
	upsEModuleOutputVAS	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The magnitude of the nominal Volt-Amp rating presented in VA."
 | 
						|
		::=  {  upsEModulesEntry  21  }
 | 
						|
 | 
						|
	upsEModuleOutputVAT	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The magnitude of the nominal Volt-Amp rating presented in VA."
 | 
						|
		::=  {  upsEModulesEntry  22  }
 | 
						|
 | 
						|
--========================================================================
 | 
						|
--upsELoadSegment          
 | 
						|
--========================================================================
 | 
						|
	upsELoadSegment1OffDelay 	OBJECT-TYPE
 | 
						|
		-- Valid value is from -1 to 32767
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS			read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"Setting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less. 
 | 
						|
					 Setting this object to 0 will cause the shutdown to occur immediately.  Setting this object to -1 will 
 | 
						|
					 abort the countdown. Read this object will get countdown value of the Load Segment."
 | 
						|
		::=  {  upsELoadSegment  1  }
 | 
						|
  	
 | 
						|
	upsELoadSegment1OnDelay		OBJECT-TYPE
 | 
						|
		-- Valid value is from -1 to 32767
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS			read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"Setting this object will start the Load segment output after the indicated number of seconds, 
 | 
						|
					 including starting the UPS, if necessary.  Setting this object to 0 will cause the startup 
 | 
						|
					 to occur immediately.  Setting this object to -1 will abort the countdown."
 | 
						|
		::=  {  upsELoadSegment  2  }
 | 
						|
 | 
						|
	upsELoadSegment1AutoOffTimer	OBJECT-TYPE
 | 
						|
		-- Valid value is from -1 to 32767
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS			read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The load segment turns automatically off after the delay while the unit operates on battery, 
 | 
						|
					 but the shutdown is cancelled if the utility return before the delay has expired." 
 | 
						|
		::=  {  upsELoadSegment  3  }
 | 
						|
 | 
						|
	upsELoadSegment1AutoOnTimer	OBJECT-TYPE
 | 
						|
		-- Valid value is from -1 to 32767
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS			read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The load segment is automatically turned on after a selected delay 
 | 
						|
					 if it has been shutdown due to on battery."
 | 
						|
		::=  {  upsELoadSegment  4  }
 | 
						|
 | 
						|
	upsELoadSegment1State		OBJECT-TYPE
 | 
						|
		SYNTAX			INTEGER  { off(1), on(2), off-pending(3), on-pending(4), not-support(5) } 
 | 
						|
		ACCESS			read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"Load segment output state."
 | 
						|
		::=  {  upsELoadSegment  5  }
 | 
						|
 | 
						|
	upsELoadSegment2OffDelay 	OBJECT-TYPE
 | 
						|
		-- Valid value is from -1 to 32767
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS			read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"Setting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less. 
 | 
						|
					 Setting this object to 0 will cause the shutdown to occur immediately.  Setting this object to -1 will 
 | 
						|
					 abort the countdown. Read this object will get countdown value of the Load Segment."
 | 
						|
		::=  {  upsELoadSegment  6  }
 | 
						|
  	
 | 
						|
	upsELoadSegment2OnDelay		OBJECT-TYPE
 | 
						|
		-- Valid value is from -1 to 32767
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS			read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"Setting this object will start the Load segment output after the indicated number of seconds, 
 | 
						|
					 including starting the UPS, if necessary.  Setting this object to 0 will cause the startup 
 | 
						|
					 to occur immediately.  Setting this object to -1 will abort the countdown."
 | 
						|
		::=  {  upsELoadSegment  7  }
 | 
						|
 | 
						|
	upsELoadSegment2AutoOffTimer	OBJECT-TYPE
 | 
						|
		-- Valid value is from -1 to 32767
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS			read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The load segment turns automatically off after the delay while the unit operates on battery, 
 | 
						|
					 but the shutdown is cancelled if the utility return before the delay has expired." 
 | 
						|
		::=  {  upsELoadSegment  8  }
 | 
						|
 | 
						|
	upsELoadSegment2AutoOnTimer	OBJECT-TYPE
 | 
						|
		-- Valid value is from -1 to 32767
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS			read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The load segment is automatically turned on after a selected delay 
 | 
						|
					 if it has been shutdown due to on battery."
 | 
						|
		::=  {  upsELoadSegment  9  }
 | 
						|
 | 
						|
	upsELoadSegment2State		OBJECT-TYPE
 | 
						|
		SYNTAX			INTEGER  { off(1), on(2), off-pending(3), on-pending(4), not-support(5) } 
 | 
						|
		ACCESS			read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"Load segment output state."
 | 
						|
		::=  {  upsELoadSegment  10  }
 | 
						|
 | 
						|
--========================================================================
 | 
						|
--upsEEnvironment
 | 
						|
--========================================================================
 | 
						|
 | 
						|
	upsEEnvironmentTemperature	OBJECT IDENTIFIER ::= { upsEEnvironment 1 }
 | 
						|
 | 
						|
	upsEEnvironmentCurrentTemperature	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measurement of  temperature sensor, in 0.1 degree"
 | 
						|
		::=  {  upsEEnvironmentTemperature  1  }
 | 
						|
 | 
						|
	upsEEnvironmentTemperatureHighSetPoint	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The set point for high temperature warning, in 0.1 degrees. 
 | 
						|
					This value must be greater than upsEEnvironmentTemperatureLowSetPoint,
 | 
						|
					and the least significant digit must be zero."
 | 
						|
		::=  {  upsEEnvironmentTemperature  2  }
 | 
						|
 | 
						|
	upsEEnvironmentTemperatureHighStatus	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { enable ( 1 ) , disable ( 2 ) } 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"To enable/disable high set point check with sensor temperature."
 | 
						|
		::=  {  upsEEnvironmentTemperature  3  }
 | 
						|
 | 
						|
	upsEEnvironmentTemperatureLowSetPoint	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The set point for low temperature warning, in 0.1 degrees.
 | 
						|
					This value must be less than upsEEnvironmentTemperatureHighSetPoint,
 | 
						|
					and the least significant digit must be zero."
 | 
						|
		::=  {  upsEEnvironmentTemperature  4  }
 | 
						|
 | 
						|
	upsEEnvironmentTemperatureLowStatus	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { enable ( 1 ) , disable ( 2 ) } 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"To enable/disable low set point check with sensor temperature."
 | 
						|
		::=  {  upsEEnvironmentTemperature  5  }
 | 
						|
 | 
						|
	upsEEnvironmentTemperatureOffset	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The offset to calibrate temperature of EMD, in 0.1 degrees"
 | 
						|
		::=  {  upsEEnvironmentTemperature  6  }
 | 
						|
 | 
						|
	upsEEnvironmentHumidity	        OBJECT IDENTIFIER ::= { upsEEnvironment 2 }
 | 
						|
 | 
						|
	upsEEnvironmentCurrentHumidity	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The measurement of sensor humidity present in %."
 | 
						|
		::=  {  upsEEnvironmentHumidity  1  }
 | 
						|
 | 
						|
	upsEEnvironmentHumidityHighSetPoint	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The set point for high humidity warning, in %.
 | 
						|
					This value must be greater than upsEEnvironmentHumidityLowSetPoint."
 | 
						|
		::=  {  upsEEnvironmentHumidity  2  }
 | 
						|
 | 
						|
	upsEEnvironmentHumidityHighStatus	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { enable ( 1 ) , disable ( 2 ) } 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"To enable/disable high set point check with emd humidity."
 | 
						|
		::=  {  upsEEnvironmentHumidity  3  }
 | 
						|
 | 
						|
	upsEEnvironmentHumidityLowSetPoint	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The set point for low humidity warning, in %.
 | 
						|
					This value must be less than upsEEnvironmentHumidityHighSetPoint."
 | 
						|
		::=  {  upsEEnvironmentHumidity  4  }
 | 
						|
 | 
						|
	upsEEnvironmentHumidityLowStatus	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { enable ( 1 ) , disable ( 2 ) } 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"To enable/disable high set point check with emd humidity."
 | 
						|
		::=  {  upsEEnvironmentHumidity  5  }
 | 
						|
 | 
						|
	upsEEnvironmentHumidityOffset	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The offset to calibrate humidity of EMD, in %."
 | 
						|
		::=  {  upsEEnvironmentHumidity  6  }
 | 
						|
 | 
						|
	upsEEnvironmentContactsNum	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The number of environment contacts, serves as the table index."
 | 
						|
		::=  {  upsEEnvironment  3  }
 | 
						|
 | 
						|
	upsEEnvironmentContactTable	OBJECT-TYPE
 | 
						|
		SYNTAX		SEQUENCE  OF  UpsEEnvironmentContactEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	      "A list of contacts table entries. The number of entries is given by the
 | 
						|
                               value of upsEEnvironmentContactsNum"
 | 
						|
		::=  { upsEEnvironment  4 }
 | 
						|
 | 
						|
	upsEEnvironmentContactEntry	OBJECT-TYPE
 | 
						|
		SYNTAX		UpsEEnvironmentContactEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	     "An entry containing information applicable to a particular contact"
 | 
						|
		INDEX		{  upsEEnvironmentContactIndex  }
 | 
						|
		::=  { upsEEnvironmentContactTable 1 }
 | 
						|
 | 
						|
	UpsEEnvironmentContactEntry  ::=  SEQUENCE {
 | 
						|
		upsEEnvironmentContactIndex  PositiveInteger,
 | 
						|
		upsEEnvironmentContactType  INTEGER,
 | 
						|
		upsEEnvironmentContactState  INTEGER,
 | 
						|
		upsEEnvironmentContactDescription  DisplayString
 | 
						|
		}
 | 
						|
 | 
						|
 | 
						|
	upsEEnvironmentContactIndex	OBJECT-TYPE	
 | 
						|
		SYNTAX			PositiveInteger
 | 
						|
		ACCESS		not-accessible
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The number of environment contacts. Serves as index for environment contact table"
 | 
						|
		::=  {  upsEEnvironmentContactEntry  1  }
 | 
						|
 | 
						|
 | 
						|
	upsEEnvironmentContactType	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { normallyOpen ( 1 ) , normallyClosed ( 2 ) , notUsed ( 3 ) } 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"operation type"
 | 
						|
		::=  {  upsEEnvironmentContactEntry  2  }
 | 
						|
 | 
						|
 | 
						|
	upsEEnvironmentContactState	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { open ( 1 ) , closed ( 2 ) , openWithNotice ( 3 ) , closedWithNotice ( 4 ) } 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The mandatory status."
 | 
						|
		::=  {  upsEEnvironmentContactEntry  3  }
 | 
						|
 | 
						|
 | 
						|
	upsEEnvironmentContactDescription	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 31 ) ) 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"Description of environment contact."
 | 
						|
		::=  {  upsEEnvironmentContactEntry  4  }
 | 
						|
 | 
						|
--========================================================================
 | 
						|
--upsEBatteryTest
 | 
						|
--========================================================================
 | 
						|
 | 
						|
	upsEBatteryTestStart	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { none ( 1 ) , batteryTest10Sec ( 2 ) , batteryTestUntilLow ( 3 ) , 
 | 
						|
                                               batteryTestWithTime ( 4 ) , cancelBatteryTest ( 5 ) , clearBatteryInfo ( 6 ) } 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"This object specify the battery test type and initiate battery test. 
 | 
						|
                               If battTestWithTime selected, the test  time is refer to upsEBatteryTestSettingTime."
 | 
						|
		::=  {  upsEBatteryTest  1  }
 | 
						|
 | 
						|
	upsEBatteryTestSettingTime	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger  
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The object specify the test time for battery test in seconds."
 | 
						|
		::=  {  upsEBatteryTest  2  }
 | 
						|
 | 
						|
	upsEBatteryTestResult	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { idle ( 1 ) , processing ( 2 ) , noFailure ( 3 ) , 
 | 
						|
                                               failureOrWarning ( 4 ) , notPossible ( 5 ) , testCancel ( 6 ) } 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"This object indicate the test result of battery."
 | 
						|
		::=  {  upsEBatteryTest  3  }
 | 
						|
 | 
						|
	upsEBatteryTestStartTime	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 19 .. 19  ) ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The value of the time the test in progress was initiated,
 | 
						|
         				  or, if no test is in progress, the time the previous test
 | 
						|
         				 was initiated. If the value of upsETestBatteryTestResult
 | 
						|
        				  is noTestsInitiated(6), upsETestStartTime has the value
 | 
						|
        				  01/01/1970 00:00:00."
 | 
						|
		::=  {  upsEBatteryTest  4  }
 | 
						|
 | 
						|
         upsEBatteryTestElapsedTime     OBJECT-TYPE
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 11 .. 11  ) ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The amount of time in format hh:mm:ss, since the test in progress 
 | 
						|
                                         was initiated, or, if no test is in progress, the previous 
 | 
						|
                                         test took to complete. If the value of upsTestResultsSummary 
 | 
						|
                                         is idle(1), upsTestElapsedTime has the value 00:00:00."
 | 
						|
		::=  {  upsEBatteryTest  5  }
 | 
						|
               
 | 
						|
 | 
						|
	upsEBatteryTestScheduleTable	OBJECT-TYPE
 | 
						|
		SYNTAX		SEQUENCE  OF  UpsBatteryTestScheduleEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	     "This table describes the schedule for automatically battery
 | 
						|
                              test."
 | 
						|
		::=  { upsEBatteryTest  6 }
 | 
						|
 | 
						|
	upsEBatteryTestScheduleEntry	OBJECT-TYPE
 | 
						|
		SYNTAX		UpsBatteryTestScheduleEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	      "An entry containing information applicable to schedule test."
 | 
						|
		INDEX		{  upsEBatteryTestScheduleIndex  }
 | 
						|
		::=  { upsEBatteryTestScheduleTable 1 }
 | 
						|
 | 
						|
	UpsBatteryTestScheduleEntry  ::=  SEQUENCE {
 | 
						|
		upsEBatteryTestScheduleIndex  PositiveInteger,
 | 
						|
		upsEBatteryTestScheduleDay  INTEGER,
 | 
						|
		upsEBatteryTestScheduleTime  DisplayString,
 | 
						|
		upsEBatteryTestScheduleType  INTEGER,
 | 
						|
		upsEBatteryTestScheduleTestWithTime  NonNegativeInteger,
 | 
						|
		upsEBatteryTestScheduleSpecialDay  DisplayString
 | 
						|
		}
 | 
						|
 | 
						|
 | 
						|
	upsEBatteryTestScheduleIndex	OBJECT-TYPE	
 | 
						|
		SYNTAX			PositiveInteger
 | 
						|
		ACCESS		not-accessible
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The index of battery test scheduled."
 | 
						|
		::=  {  upsEBatteryTestScheduleEntry  1  }
 | 
						|
 | 
						|
 | 
						|
	upsEBatteryTestScheduleDay	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { monday ( 1 ) , tuesday ( 2 ) , wednsday ( 3 ) ,
 | 
						|
 							     thusday ( 4 ) , friday ( 5 ) , saturday ( 6 ) , 
 | 
						|
                                               sunday ( 7 ) , specialday ( 8 ) , none ( 9 ) } 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The weekday or specaial day on which the UPS should start battery test."
 | 
						|
		::=  {  upsEBatteryTestScheduleEntry  2  }
 | 
						|
 | 
						|
 | 
						|
	upsEBatteryTestScheduleTime	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 5  ) ) 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The time that the battery test will be initiated in hh:mm format."
 | 
						|
		::=  {  upsEBatteryTestScheduleEntry  3  }
 | 
						|
 | 
						|
 | 
						|
	upsEBatteryTestScheduleType	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { none ( 1 ) , batteryTest10sec ( 2 ) , batteryTestUntilLow ( 3 ) , 
 | 
						|
                                               batteryTestWithTime ( 4 ) } 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The type of battery test."
 | 
						|
		::=  {  upsEBatteryTestScheduleEntry  5  }
 | 
						|
 | 
						|
 | 
						|
	upsEBatteryTestScheduleTestWithTime	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The battery time of setting time test in seconds."
 | 
						|
		::=  {  upsEBatteryTestScheduleEntry  6  }
 | 
						|
 | 
						|
 | 
						|
	upsEBatteryTestScheduleSpecialDay	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 10  ) ) 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The special day that the battery test will be initiated in dd/mm/yyyy format."
 | 
						|
		::=  {  upsEBatteryTestScheduleEntry  7  }
 | 
						|
 | 
						|
--========================================================================
 | 
						|
-- upsEControl  
 | 
						|
--========================================================================
 | 
						|
 | 
						|
	upsEControlOutputOffDelay	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger   
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"Setting this value to other than zero will cause the UPS 
 | 
						|
                               output to turn off after the number of seconds. "
 | 
						|
		::=  {  upsEControl  1  }
 | 
						|
 | 
						|
	upsEControlOutputOnDelay	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger  
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"Setting this value to other than zero will cause the 
 | 
						|
					UPS output to turn on after the number of seconds. "
 | 
						|
		::=  {  upsEControl  2  }
 | 
						|
 | 
						|
	upsEControlOutputOnOffControl	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { upsEOutputOff ( 1 ) , upsEOutputOffCancel ( 2 ) , upsESleep( 3 ) , none ( 4 )  }
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"upsEOutputOff ( 1 ) indicates the shutdown sequence,
 | 
						|
	                                 upsEOutputOffCancel ( 2 ) indicates cancel the shutdown sequence,
 | 
						|
        	                         upsESleep( 3 ) indicates shutdown UPS first, then switch on."
 | 
						|
		::=  {  upsEControl  3  }
 | 
						|
 | 
						|
	upsEShutdownEventsTable	OBJECT-TYPE
 | 
						|
		SYNTAX		SEQUENCE  OF  UpsShutdownEventsEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	     "This table describes the parametes for shutdown process
 | 
						|
                              when shutdown event occurs"
 | 
						|
		::=  { upsEControl  4 }
 | 
						|
 | 
						|
	upsEShutdownEventsEntry	OBJECT-TYPE
 | 
						|
		SYNTAX		UpsShutdownEventsEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	      "An entry containing information applicable to a particular shutdown
 | 
						|
                               event line"
 | 
						|
		INDEX		{  upsEShutdownEvent  }
 | 
						|
		::=  { upsEShutdownEventsTable 1 }
 | 
						|
 | 
						|
	UpsShutdownEventsEntry  ::=  SEQUENCE {
 | 
						|
		upsEShutdownEvent  INTEGER,
 | 
						|
		upsEShutdownEventAction  INTEGER,
 | 
						|
		upsEShutdownwarningPeriodTime  NonNegativeInteger,
 | 
						|
		upsEShutdownWarningPeriodInterval  NonNegativeInteger
 | 
						|
		}
 | 
						|
 | 
						|
 | 
						|
	upsEShutdownEvent	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { acFail ( 1 ) , batteryLow ( 2 ) , upsEOverLoad ( 3 ) ,
 | 
						|
                                               upsEOverTemperature ( 4 ) , upsEWeeklySchedule ( 5 ) , 
 | 
						|
                                               upsESpecialSchedule ( 6 ) , environmentTemperatureOverThreshold ( 7 ) ,
 | 
						|
                                               environmentHumidityOverThreshold ( 8 ) , environmentContact1Alarm ( 9 ) ,
 | 
						|
                                               environmentContact2Alarm ( 10 ), belowCapacityLimit( 11 ), belowRemainTimeLimit( 12 )} 
 | 
						|
		ACCESS		not-accessible
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The shutdown event identification"
 | 
						|
		::=  {  upsEShutdownEventsEntry  1  }
 | 
						|
 | 
						|
 | 
						|
	upsEShutdownEventAction	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { disable ( 1 ) , warning ( 2 ) , shutdownClient ( 3 ) , shutdownUPS ( 4 ) } 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"Status of the corresponding shutdown Event.
 | 
						|
 					When set to disable(), shutdown process will not start when
 | 
						|
				      corresponding event occured."
 | 
						|
		::=  {  upsEShutdownEventsEntry  2  }
 | 
						|
 | 
						|
 | 
						|
	upsEShutdownwarningPeriodTime	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The Delay in seconds after the occurance of the curresponding shutdown
 | 
						|
                                    event, and warning message should be popped in this period."
 | 
						|
		::=  {  upsEShutdownEventsEntry  3  }
 | 
						|
 | 
						|
 | 
						|
	upsEShutdownWarningPeriodInterval	OBJECT-TYPE	
 | 
						|
		SYNTAX			NonNegativeInteger
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The frequency of sending warning messages to the connected
 | 
						|
                                   clients when the curresponding shutdown event occurs.
 | 
						|
                                   The value is in units of seconds."
 | 
						|
		::=  {  upsEShutdownEventsEntry  4  }
 | 
						|
 | 
						|
	upsEControlWeeklyScheduleTable	OBJECT-TYPE
 | 
						|
		SYNTAX		SEQUENCE  OF  UpsControlWeeklyScheduleEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	     "The table to schedule shutting down the ups by weekly"
 | 
						|
		::=  { upsEControl  5 }
 | 
						|
 | 
						|
	upsEControlWeeklyScheduleEntry	OBJECT-TYPE
 | 
						|
		SYNTAX		UpsControlWeeklyScheduleEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	      "An entry containing information applicable to a particular line"
 | 
						|
		INDEX		{  upsEControlWeeklyScheduleIndex  }
 | 
						|
		::=  { upsEControlWeeklyScheduleTable 1 }
 | 
						|
 | 
						|
	UpsControlWeeklyScheduleEntry  ::=  SEQUENCE {
 | 
						|
		upsEControlWeeklyScheduleIndex  PositiveInteger,
 | 
						|
		upsEWeeklyScheduleShutdownDay  INTEGER,
 | 
						|
		upsEWeeklyScheduleShutdownTime  DisplayString,
 | 
						|
		upsEWeeklyScheduleRestartDay  INTEGER,
 | 
						|
		upsEWeeklyScheduleRestartTime  DisplayString
 | 
						|
		}
 | 
						|
 | 
						|
 | 
						|
	upsEControlWeeklyScheduleIndex	OBJECT-TYPE	
 | 
						|
		SYNTAX			PositiveInteger
 | 
						|
		ACCESS		not-accessible
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"the index of schedule events."
 | 
						|
		::=  {  upsEControlWeeklyScheduleEntry  1  }
 | 
						|
 | 
						|
 | 
						|
	upsEWeeklyScheduleShutdownDay	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { monday ( 1 ) , tuesday ( 2 ) , wednesday ( 3 ) , 
 | 
						|
                                               thursday ( 4 ) , friday ( 5 ) , saturday ( 6 ) , 
 | 
						|
                                               sunday ( 7 ) , none ( 8 ) } 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"the weekday on which upsE shoud shutdown"
 | 
						|
		::=  {  upsEControlWeeklyScheduleEntry  2  }
 | 
						|
 | 
						|
 | 
						|
	upsEWeeklyScheduleShutdownTime	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 5  ) ) 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The time that the process of shutting down the UPS will be initiated
 | 
						|
 					in hh:mm format."
 | 
						|
		::=  {  upsEControlWeeklyScheduleEntry  3  }
 | 
						|
 | 
						|
 | 
						|
	upsEWeeklyScheduleRestartDay	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { monday ( 1 ) , tuesday ( 2 ) , wednesday ( 3 ) , 
 | 
						|
                                               thursday ( 4 ) , friday ( 5 ) , saturday ( 6 ) , 
 | 
						|
                                               sunday ( 7 ) , none ( 8 ) } 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"the weekday on which the UPS should restart."
 | 
						|
		::=  {  upsEControlWeeklyScheduleEntry  4  }
 | 
						|
 | 
						|
 | 
						|
	upsEWeeklyScheduleRestartTime	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 5 .. 5 ) ) 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The time the UPS will restart in hh:mm format."
 | 
						|
		::=  {  upsEControlWeeklyScheduleEntry  5  }
 | 
						|
 | 
						|
      upsEControlSpecialDayScheduleTable	OBJECT-TYPE
 | 
						|
		SYNTAX		SEQUENCE  OF  UpsControlSpecialDayScheduleEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	     "The table to schedule shutting down the ups."
 | 
						|
		::=  { upsEControl  6 }
 | 
						|
 | 
						|
	upsEControlSpecialDayScheduleEntry	OBJECT-TYPE
 | 
						|
		SYNTAX		UpsControlSpecialDayScheduleEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	      "An entry containing information applicable to a particular line."
 | 
						|
		INDEX		{  upsEControlSpecialDayScheduleIndex  }
 | 
						|
		::=  { upsEControlSpecialDayScheduleTable 1 }
 | 
						|
 | 
						|
	UpsControlSpecialDayScheduleEntry  ::=  SEQUENCE {
 | 
						|
		upsEControlSpecialDayScheduleIndex  PositiveInteger,
 | 
						|
		upsESpecialDayScheduleShutdownDay  DisplayString,
 | 
						|
		upsESpecialDayScheduleShutdownTime  DisplayString,
 | 
						|
		upsESpecialDayScheduleRestartDay  DisplayString,
 | 
						|
		upsESpecialDayScheduleRestartTime  DisplayString
 | 
						|
		}
 | 
						|
 | 
						|
 | 
						|
	upsEControlSpecialDayScheduleIndex	OBJECT-TYPE	
 | 
						|
		SYNTAX			PositiveInteger
 | 
						|
		ACCESS		not-accessible
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The index of special day schedule."
 | 
						|
		::=  {  upsEControlSpecialDayScheduleEntry  1  }
 | 
						|
 | 
						|
 | 
						|
	upsESpecialDayScheduleShutdownDay	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 10 .. 10  ) ) 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The special day on which UPS should shutdown with the format
 | 
						|
                               of DD/MM/YYYY."
 | 
						|
		::=  {  upsEControlSpecialDayScheduleEntry  2  }
 | 
						|
 | 
						|
 | 
						|
	upsESpecialDayScheduleShutdownTime	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 5 .. 5 ) ) 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The time that the process of shutting down the UPS will be initiated
 | 
						|
 					in hh:mm format."
 | 
						|
		::=  {  upsEControlSpecialDayScheduleEntry  3  }
 | 
						|
 | 
						|
 | 
						|
	upsESpecialDayScheduleRestartDay	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 10 .. 10  ) ) 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The special day on which the UPS should restart with the format
 | 
						|
                               of DD/MM/YYYY."
 | 
						|
		::=  {  upsEControlSpecialDayScheduleEntry  4  }
 | 
						|
 | 
						|
 | 
						|
	upsESpecialDayScheduleRestartTime	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 5 .. 5 ) ) 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The time the UPS will restart in hh:mm format."
 | 
						|
		::=  {  upsEControlSpecialDayScheduleEntry  5  }
 | 
						|
 | 
						|
	upsESystemMasterOffDelay 	OBJECT-TYPE
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS			read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The UPS output will shutdown after the indicated number of seconds, -1 indicate no action."
 | 
						|
		::=  {  upsEControl  7  }
 | 
						|
	upsESystemMasterOnDelay 	OBJECT-TYPE
 | 
						|
		SYNTAX			INTEGER
 | 
						|
		ACCESS			read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The UPS output will start on after the indicated number of seconds, -1 indicate no action."
 | 
						|
		::=  {  upsEControl  8  }
 | 
						|
 | 
						|
--========================================================================
 | 
						|
-- upsETrapControl
 | 
						|
--========================================================================
 | 
						|
 | 
						|
	upsETrapsReceiversTable	OBJECT-TYPE
 | 
						|
		SYNTAX		SEQUENCE  OF  UpsTrapsReceiversEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	      " This table list the managers'IP to send traps to."
 | 
						|
		::=  { upsETrapControl  1 }
 | 
						|
 | 
						|
	upsETrapsReceiversEntry	OBJECT-TYPE
 | 
						|
		SYNTAX		UpsTrapsReceiversEntry
 | 
						|
		ACCESS	not-accessible
 | 
						|
		STATUS		mandatory
 | 
						|
		DESCRIPTION	      "An entry containing information applicable to a particular input line."
 | 
						|
		INDEX		{  upsETrapsReceiversIndex  }
 | 
						|
		::=  { upsETrapsReceiversTable 1 }
 | 
						|
 | 
						|
	UpsTrapsReceiversEntry  ::=  SEQUENCE {
 | 
						|
		upsETrapsReceiversIndex  PositiveInteger,
 | 
						|
		upsETrapsReceiverAddress  DisplayString,
 | 
						|
		upsETrapReceiverCommunityString  DisplayString,
 | 
						|
		upsETrapType  INTEGER,
 | 
						|
		upsETrapsSeverityLevel  INTEGER,
 | 
						|
		upsETrapReceiverDescription  DisplayString
 | 
						|
		}
 | 
						|
 | 
						|
	upsETrapsReceiversIndex	OBJECT-TYPE	
 | 
						|
		SYNTAX			PositiveInteger
 | 
						|
		ACCESS		not-accessible
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The index to a trap receiver entry"
 | 
						|
		::=  {  upsETrapsReceiversEntry  1  }
 | 
						|
 | 
						|
	upsETrapsReceiverAddress	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 45  ) )
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The IP address of the manager to send a trap to."
 | 
						|
		::=  {  upsETrapsReceiversEntry  2  }
 | 
						|
 | 
						|
	upsETrapReceiverCommunityString	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 32  ) ) 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The community name to use in the trap when
 | 
						|
					 sent to the manager."
 | 
						|
		::=  {  upsETrapsReceiversEntry  3  }
 | 
						|
 | 
						|
	upsETrapType	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { none ( 1 ) , rfc1628Trap ( 2 ) , eppcTrap ( 3 ) } 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The type of trap to be received by the manager."
 | 
						|
		::=  {  upsETrapsReceiversEntry  4  }
 | 
						|
 | 
						|
	upsETrapsSeverityLevel	OBJECT-TYPE	
 | 
						|
		SYNTAX			INTEGER  { informational ( 1 ) , warning ( 2 ) , severe ( 3 ) } 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"The severity level of traps to be received by this manager."
 | 
						|
		::=  {  upsETrapsReceiversEntry  5  }
 | 
						|
 | 
						|
	upsETrapReceiverDescription	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 63  ) ) 
 | 
						|
		ACCESS		read-write
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"Description of trap receivers"
 | 
						|
		::=  {  upsETrapsReceiversEntry  6  }
 | 
						|
 | 
						|
	upsETrapState	OBJECT-TYPE	
 | 
						|
		SYNTAX			DisplayString  ( SIZE ( 0 .. 127  ) ) 
 | 
						|
		ACCESS		read-only
 | 
						|
		STATUS			mandatory
 | 
						|
		DESCRIPTION		"the values indicate the unrestored traps.
 | 
						|
					 For example, after AC fail, the agent send
 | 
						|
					 the trap 1(AC Fail) and trap 7(battery on) to 
 | 
						|
					 NMS. so the value of upsETrapState should be '1,7'. 
 | 
						|
					And then the AC restore, the value of upsETrapState 
 | 
						|
					should change to empty."
 | 
						|
		::=  {  upsETrapControl  2  }
 | 
						|
 | 
						|
-- ===========================================================================
 | 
						|
-- Trap defination
 | 
						|
-- ===========================================================================
 | 
						|
 | 
						|
upsEPowerFail       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Utility power not available."
 | 
						|
        ::= 1
 | 
						|
 | 
						|
upsEPowerRestored TRAP-TYPE
 | 
						|
        ENTERPRISE upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Utility power has restored."
 | 
						|
        ::= 2
 | 
						|
 | 
						|
upsELowBattery TRAP-TYPE
 | 
						|
        ENTERPRISE upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "SEVERE: The UPS batteries are low and will soon be exhausted."
 | 
						|
        ::= 3
 | 
						|
 | 
						|
upsEReturnFromLowBattery TRAP-TYPE
 | 
						|
        ENTERPRISE upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: The UPS has return from a low battery condition."
 | 
						|
        ::= 4
 | 
						|
 | 
						|
upsEFailed       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "SEVERE: The UPS is not working fine."
 | 
						|
        ::= 5
 | 
						|
 | 
						|
upsEOk   TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: The UPS is working fine."
 | 
						|
        ::= 6
 | 
						|
 | 
						|
upsEOnBattery TRAP-TYPE
 | 
						|
        ENTERPRISE upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEBatteryEstimatedMinutesRemaining,
 | 
						|
        upsESecondsOnBattery
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: The UPS has switched to battery backup power."
 | 
						|
        ::= 7 
 | 
						|
 | 
						|
upsENotOnBattery TRAP-TYPE
 | 
						|
        ENTERPRISE upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: The UPS is not on battery power."
 | 
						|
        ::= 8
 | 
						|
 | 
						|
upsETestInProgress TRAP-TYPE
 | 
						|
        ENTERPRISE upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: The testing is going on ups."
 | 
						|
        ::= 9
 | 
						|
 | 
						|
upsETestOver TRAP-TYPE
 | 
						|
        ENTERPRISE upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEBatteryTestStart,
 | 
						|
        upsEBatteryTestSettingTime,
 | 
						|
        upsEBatteryTestResult,
 | 
						|
        upsEBatteryTestStartTime
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: The testing of UPS is completed."
 | 
						|
        ::= 10
 | 
						|
 | 
						|
upsEBypassOn TRAP-TYPE
 | 
						|
        ENTERPRISE upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: The UPS has enabled bypass."
 | 
						|
        ::= 11
 | 
						|
 | 
						|
upsEOnline TRAP-TYPE
 | 
						|
        ENTERPRISE upsETraps
 | 
						|
                DESCRIPTION
 | 
						|
                        "INFORMATION: The UPS is not on Bypass and return to normal status."
 | 
						|
        ::= 12
 | 
						|
 | 
						|
upsECommunicationLost TRAP-TYPE
 | 
						|
        ENTERPRISE upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                 "SEVERE: Communication to the UPS has been lost."
 | 
						|
        ::= 13
 | 
						|
 | 
						|
upsECommunicationEstablished TRAP-TYPE
 | 
						|
        ENTERPRISE upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Communication with the UPS has been established."
 | 
						|
        ::= 14
 | 
						|
 | 
						|
upsEGoingShutdown    TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: The UPS is going to shutdown output."
 | 
						|
        ::= 15
 | 
						|
 | 
						|
upsEShutdownCancelled    TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: The UPS is not going to shutdown output."
 | 
						|
        ::= 16
 | 
						|
 | 
						|
upsEOutlet1GoingShutdown   TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: The UPS is going to shutdown outlet1."
 | 
						|
        ::= 17
 | 
						|
 | 
						|
upsEOutlet1ShutdownCancelled    TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: The UPS is not going to shutdown outlet1."
 | 
						|
        ::= 18
 | 
						|
 | 
						|
upsEOutlet2GoingShutdown   TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: The UPS is going to shutdown outlet2."
 | 
						|
        ::= 19
 | 
						|
 | 
						|
upsEOutlet2ShutdownCancelled    TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: The UPS is not going to shutdown outlet2."
 | 
						|
        ::= 20
 | 
						|
 | 
						|
upsESleeping             TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEControlOutputOnDelay
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: UPS has entered sleep mode and power to load has been cut off."
 | 
						|
        ::= 21
 | 
						|
 | 
						|
upsEWokeUp               TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: The UPS woke up from sleep mode and power to load has been restored."
 | 
						|
        ::= 22
 | 
						|
 | 
						|
upsEOverTemperature   TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsESystemTemperature,
 | 
						|
        upsESystemConfigOverTemperatureSetPoint
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: The UPS temperature is over the setting limit."
 | 
						|
        ::= 23
 | 
						|
 | 
						|
upsENotOverTemperature   TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsESystemTemperature,
 | 
						|
        upsESystemConfigOverTemperatureSetPoint
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: The UPS temperature is not over the setting limit."
 | 
						|
        ::= 24
 | 
						|
 | 
						|
upsEOverLoad   TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsESystemOutputLoad,
 | 
						|
        upsESystemConfigOutputLoadHighSetPoint
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: The UPS load is over the setting limit."
 | 
						|
        ::= 25
 | 
						|
 | 
						|
upsENotOverLoad       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsESystemOutputLoad,
 | 
						|
        upsESystemConfigOutputLoadHighSetPoint
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: The UPS load is not over the setting limit."
 | 
						|
        ::= 26
 | 
						|
 | 
						|
upsEModuleInserted   TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: UPS module or charger module plug-in."
 | 
						|
        ::= 27
 | 
						|
 | 
						|
upsEModuleRemoved    TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: UPS module or charger module unplugs."
 | 
						|
        ::= 28
 | 
						|
 | 
						|
sensorTemperatureTooHigh   TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEEnvironmentTemperatureHighSetPoint,
 | 
						|
        upsEEnvironmentCurrentTemperature
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Sensor Temperature over high Set point."
 | 
						|
        ::= 29
 | 
						|
 | 
						|
sensorTemperatureNotHigh   TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEEnvironmentTemperatureHighSetPoint,
 | 
						|
        upsEEnvironmentCurrentTemperature
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Sensor Temperature not over high Set point."
 | 
						|
        ::= 30
 | 
						|
 | 
						|
sensorTemperatureTooLow    TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEEnvironmentTemperatureLowSetPoint,
 | 
						|
        upsEEnvironmentCurrentTemperature
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Sensor Temperature under low Set point."
 | 
						|
        ::= 31
 | 
						|
 | 
						|
sensorTemperatureNotLow    TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEEnvironmentTemperatureLowSetPoint,
 | 
						|
        upsEEnvironmentCurrentTemperature
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Sensor Temperature not under low Set point."
 | 
						|
        ::= 32
 | 
						|
 | 
						|
sensorHumidityTooHigh      TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEEnvironmentHumidityHighSetPoint,
 | 
						|
        upsEEnvironmentCurrentHumidity
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Sensor Humidity over high Set point."
 | 
						|
        ::= 33
 | 
						|
 | 
						|
sensorHumidityNotHigh      TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEEnvironmentHumidityHighSetPoint,
 | 
						|
        upsEEnvironmentCurrentHumidity
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Sensor Humidity not over high Set point."
 | 
						|
        ::= 34
 | 
						|
 | 
						|
sensorHumidityTooLow       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEEnvironmentHumidityLowSetPoint,
 | 
						|
        upsEEnvironmentCurrentHumidity
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Sensor Humidity under low Set point."
 | 
						|
        ::= 35
 | 
						|
 | 
						|
sensorHumidityNotLow       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEEnvironmentHumidityLowSetPoint,
 | 
						|
        upsEEnvironmentCurrentHumidity
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Sensor Humidity not under low Set point."
 | 
						|
        ::= 36
 | 
						|
 | 
						|
contactAlarm1Active TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEEnvironmentContactType,
 | 
						|
        upsEEnvironmentContactDescription
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Contact Alarm-1 activated."
 | 
						|
        ::= 37
 | 
						|
 | 
						|
concactAlarm1Normal TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEEnvironmentContactType,
 | 
						|
        upsEEnvironmentContactDescription
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Contact Alarm-1 not active."
 | 
						|
        ::= 38
 | 
						|
 | 
						|
contactAlarm2Active TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEEnvironmentContactType,
 | 
						|
        upsEEnvironmentContactDescription
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Contact Alarm-2 activated."
 | 
						|
        ::= 39
 | 
						|
 | 
						|
contactAlarm2Normal TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEEnvironmentContactType,
 | 
						|
        upsEEnvironmentContactDescription
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Contact Alarm-2 not active."
 | 
						|
        ::= 40
 | 
						|
        
 | 
						|
upsEInternalwarning       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Internal warning."
 | 
						|
        ::= 41           
 | 
						|
 | 
						|
upsEReturnFromInternalwarning       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Internal warning."
 | 
						|
        ::= 42           
 | 
						|
 | 
						|
upsEEPOActive       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: EPO Active."
 | 
						|
        ::= 43  
 | 
						|
 | 
						|
upsEReturnFromEPOActive       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from EPO Active."
 | 
						|
        ::= 44   
 | 
						|
 | 
						|
upsEModuleUnlock       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Module Unlock."
 | 
						|
        ::= 45   
 | 
						|
 | 
						|
upsEReturnFromModuleUnlock       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Module Unlock."
 | 
						|
        ::= 46  
 | 
						|
        
 | 
						|
upsEMain1Neutralloss       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Main 1 Neutral loss."
 | 
						|
        ::= 47     
 | 
						|
 | 
						|
upsEReturnFromMain1Neutralloss       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Main 1 Neutral loss."
 | 
						|
        ::= 48  
 | 
						|
 | 
						|
upsEMain1phaseerror       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Main 1 phase error."
 | 
						|
        ::= 49  
 | 
						|
 | 
						|
upsEReturnFromMain1phaseerror       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Main 1 phase error."
 | 
						|
        ::= 50 
 | 
						|
 | 
						|
upsESitefault       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Site fault."
 | 
						|
        ::= 51
 | 
						|
 | 
						|
upsEReturnFromSitefault       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Site fault."
 | 
						|
        ::= 52
 | 
						|
 | 
						|
upsEBypassAbnormal       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Bypass Abnormal."
 | 
						|
        ::= 53  
 | 
						|
 | 
						|
upsEReturnFromBypassAbnormal       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Bypass Abnormal."
 | 
						|
        ::= 54 
 | 
						|
 | 
						|
upsEBypassPhaseError       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Bypass Phase Error."
 | 
						|
        ::= 55           
 | 
						|
 | 
						|
upsEReturnFromBypassPhaseError       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Bypass Phase Error."
 | 
						|
        ::= 56  
 | 
						|
 | 
						|
upsEBatteryOpen       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Battery Open."
 | 
						|
        ::= 57   
 | 
						|
 | 
						|
upsEReturnFromBatteryOpen       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Battery Open."
 | 
						|
        ::= 58  
 | 
						|
        
 | 
						|
upsEBatteryOverCharge       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Battery Over Charge."
 | 
						|
        ::= 59   
 | 
						|
 | 
						|
upsEReturnFromBatteryOverCharge       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Battery Over Charge."
 | 
						|
        ::= 60   
 | 
						|
        
 | 
						|
upsEBatteryReverse       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Battery Reverse."
 | 
						|
        ::= 61      
 | 
						|
 | 
						|
upsEReturnFromBatteryReverse       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Battery Reverse."
 | 
						|
        ::= 62
 | 
						|
 | 
						|
upsEOverloadforewarning       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Overload forewarning."
 | 
						|
        ::= 63  
 | 
						|
 | 
						|
upsEReturnFromOverloadforewarning       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Overload forewarning."
 | 
						|
        ::= 64   
 | 
						|
 | 
						|
upsEOverloadWarning       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Overload Warning."
 | 
						|
        ::= 65  
 | 
						|
 | 
						|
upsEReturnFromOverloadWarning       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Overload Warning."
 | 
						|
        ::= 66 
 | 
						|
 | 
						|
upsEFanLock       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Fan Lock."
 | 
						|
        ::= 67  
 | 
						|
 | 
						|
upsEReturnFromFanLock       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Fan Lock."
 | 
						|
        ::= 68 
 | 
						|
        
 | 
						|
upsEMaintaincoverisopen       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Maintain cover is open."
 | 
						|
        ::= 69         
 | 
						|
 | 
						|
upsEReturnFromMaintaincoverisopen       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Maintain cover is open."
 | 
						|
        ::= 70  
 | 
						|
 | 
						|
upsEChargerfault       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Charger fault."
 | 
						|
        ::= 71  
 | 
						|
 | 
						|
upsEReturnFromChargerfault       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Charger fault."
 | 
						|
        ::= 72
 | 
						|
 | 
						|
upsEModulelocationerror       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Module location error."
 | 
						|
        ::= 73 
 | 
						|
 | 
						|
upsEReturnFromModulelocationerror       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Module location error."
 | 
						|
        ::= 74  
 | 
						|
        
 | 
						|
upsETurnonabnormal       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Turn on abnormal."
 | 
						|
        ::= 75  
 | 
						|
 | 
						|
upsEReturnFromTurnonabnormal       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Turn on abnormal."
 | 
						|
        ::= 76  
 | 
						|
      
 | 
						|
upsERedundancyloss       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Redundancy loss."
 | 
						|
        ::= 77     
 | 
						|
 | 
						|
upsEReturnFromRedundancyloss       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Redundancy loss."
 | 
						|
        ::= 78 
 | 
						|
 | 
						|
upsEHotSwapActived       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Hot Swap Active."
 | 
						|
        ::= 79  
 | 
						|
 | 
						|
upsEReturnFromHotSwapActived       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Hot Swap Active."
 | 
						|
        ::= 80
 | 
						|
 | 
						|
upsEBatteryInform       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Battery Inform."
 | 
						|
        ::= 81  
 | 
						|
 | 
						|
upsEReturnFromBatteryInform       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Battery Inform."
 | 
						|
        ::= 82
 | 
						|
 | 
						|
upsEInspectionInform       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Inspection Inform."
 | 
						|
        ::= 83
 | 
						|
 | 
						|
upsEReturnFromInspectionInform       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Inspection Inform."
 | 
						|
        ::= 84  
 | 
						|
 | 
						|
upsEGuaranteeInform       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Guarantee Inform."
 | 
						|
        ::= 85          
 | 
						|
 | 
						|
upsEReturnFromGuaranteeInform       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Guarantee Inform."
 | 
						|
        ::= 86 
 | 
						|
 | 
						|
upsETemperatureLow       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Temperature Low."
 | 
						|
        ::= 87  
 | 
						|
 | 
						|
upsEReturnFromTemperatureLow       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Temperature Low."
 | 
						|
        ::= 88 
 | 
						|
 | 
						|
upsETemperatureHigh       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Temperature High."
 | 
						|
        ::= 89  
 | 
						|
 | 
						|
upsEReturnFromTemperatureHigh       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Temperature High."
 | 
						|
        ::= 90  
 | 
						|
        
 | 
						|
upsEBatteryOverTemperature       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Battery Over Temperature."
 | 
						|
        ::= 91  
 | 
						|
 | 
						|
upsEReturnFromBatteryOverTemperature       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Battery Over Temperature."
 | 
						|
        ::= 92
 | 
						|
        
 | 
						|
upsEFanMaintainInform       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Fan Maintain Inform."
 | 
						|
        ::= 93    
 | 
						|
 | 
						|
upsEReturnFromFanMaintainInform       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Fan Maintain Inform."
 | 
						|
        ::= 94   
 | 
						|
 | 
						|
upsEBusCapacitanceMaintainInform       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Bus Capacitance Maintain Inform."
 | 
						|
        ::= 95  
 | 
						|
 | 
						|
upsEReturnFromBusCapacitanceMaintainInform       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from Bus Capacitance Maintain Inform."
 | 
						|
        ::= 96
 | 
						|
 | 
						|
upsESystemOverCapacity       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: System Over Capacity."
 | 
						|
        ::= 97  
 | 
						|
 | 
						|
upsEReturnFromSystemOverCapacity       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Return from System Over Capacity."
 | 
						|
        ::= 98  
 | 
						|
 | 
						|
-- Trap Id 99-122 is not defined.
 | 
						|
 | 
						|
upsEBelowCapacityLimit       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEBatteryEstimatedChargeRemaining,
 | 
						|
        upsESystemConfigBelowCapacityLimit
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "SEVERE: The UPS batteries capacity is lower than setting limit."
 | 
						|
        ::= 123
 | 
						|
 | 
						|
upsENotBelowCapacityLimit       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: The UPS batteries capacity is not lower than setting limit."
 | 
						|
        ::= 124
 | 
						|
 | 
						|
upsEBelowRemainTimeLimit       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        VARIABLES {
 | 
						|
        upsEBatteryEstimatedMinutesRemaining,
 | 
						|
        upsESystemConfigBelowRemainTimeLimit
 | 
						|
        }
 | 
						|
        DESCRIPTION
 | 
						|
                "SEVERE: The UPS batteries backup time is below the setting limit."
 | 
						|
        ::= 125
 | 
						|
 | 
						|
upsENotBelowRemainTimeLimit       TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: The UPS batteries backup time is not below the setting limit."
 | 
						|
        ::= 126
 | 
						|
 | 
						|
upsELoadSegment1Off	TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Load segment 1 is off."
 | 
						|
        ::= 127
 | 
						|
upsELoadSegment1On	TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Load segment 1 is on."
 | 
						|
        ::= 128
 | 
						|
 | 
						|
upsELoadSegment2Off	TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "WARNING: Load segment 2 is off."
 | 
						|
        ::= 129
 | 
						|
upsELoadSegment2On	TRAP-TYPE
 | 
						|
        ENTERPRISE      upsETraps
 | 
						|
        DESCRIPTION
 | 
						|
                "INFORMATION: Load segment 2 is on."
 | 
						|
        ::= 130
 | 
						|
 | 
						|
END
 | 
						|
 |