-- RITTAL GmbH & Co. KG, Herborn
-- CMC-TC-MIB Version 1.1h
-- CMC-TC - DK7320.100
--
-- Management Information Base for SNMP Network Management
--
-- Copyright 2002 - 2007 Rittal Herborn.
-- All Rights Reserved.
--
-- The information in this document is subject to change without notice.
-- Refer to document "AGB_Software_Rittal.pdf"
--
--*********************************************************************
-- Release History
-- Date: October 17, 2002 (Version 1.0)
-- Revised by MHain
-- Date: April 1, 2003 (Version 1.1)
-- Added: unitXMsgQuit, cmcTcControl, Sensor types, Output types, Unit types
-- Date: November 3, 2003 (Version 1.1a)
-- Added: new sensors, new outputs (FCS, RTT)
-- Date: March 11, 2004 (Version 1.1b)
-- Added: new sensors, new outputs, new messages (RCT, PSM)
-- Date: Jan 11, 2006 (Version 1.1c)
-- Changed: sysName... FROM RFC1213-MIB, seperate lines, for HP SIM
-- Date: Jan 24, 2006 (Version 1.1d)
-- Added: new unit type (ActivePSM8)
-- Added: new output type (power output 16/20A)
-- Date: Dec 5, 2006 (Version 1.1e)
-- Added: sensor/output types MeteredPSM, LCP
-- Date: March 8, 2007 (Version 1.1f)
-- Changed: Output names (RTT, Power Out)
-- Date: March 22, 2007 (Version 1.1g)
-- Changed: New sensor units, wireless sensors, timer function SMS
-- Date: July 23, 2007 (Version 1.1h)
-- Added: New sensors/outputs LCP
--*********************************************************************
RITTAL-CMC-TC-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises FROM RFC1155-SMI
DisplayString FROM RFC1213-MIB
sysName FROM RFC1213-MIB
sysDescr FROM RFC1213-MIB
sysContact FROM RFC1213-MIB
sysLocation FROM RFC1213-MIB
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215;
rittal OBJECT IDENTIFIER ::= { enterprises 2606 }
cmcTc OBJECT IDENTIFIER ::= { rittal 4 }
cmcTcMibRev OBJECT IDENTIFIER ::= { cmcTc 1 }
cmcTcStatus OBJECT IDENTIFIER ::= { cmcTc 2 }
cmcTcStatusSensorUnit1 OBJECT IDENTIFIER ::= { cmcTcStatus 3 }
cmcTcStatusUnit1Sensors OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit1 5 }
cmcTcStatusUnit1Outputs OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit1 6 }
cmcTcStatusUnit1Msg OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit1 7 }
cmcTcStatusSensorUnit2 OBJECT IDENTIFIER ::= { cmcTcStatus 4 }
cmcTcStatusUnit2Sensors OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit2 5 }
cmcTcStatusUnit2Outputs OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit2 6 }
cmcTcStatusUnit2Msg OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit2 7 }
cmcTcStatusSensorUnit3 OBJECT IDENTIFIER ::= { cmcTcStatus 5 }
cmcTcStatusUnit3Sensors OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit3 5 }
cmcTcStatusUnit3Outputs OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit3 6 }
cmcTcStatusUnit3Msg OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit3 7 }
cmcTcStatusSensorUnit4 OBJECT IDENTIFIER ::= { cmcTcStatus 6 }
cmcTcStatusUnit4Sensors OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit4 5 }
cmcTcStatusUnit4Outputs OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit4 6 }
cmcTcStatusUnit4Msg OBJECT IDENTIFIER ::= { cmcTcStatusSensorUnit4 7 }
cmcTcStatusExtUnit OBJECT IDENTIFIER ::= { cmcTcStatus 7 }
cmcTcSetup OBJECT IDENTIFIER ::= { cmcTc 3 }
cmcTcSetupGeneral OBJECT IDENTIFIER ::= { cmcTcSetup 1 }
cmcTcTimerTable1 OBJECT IDENTIFIER ::= { cmcTcSetupGeneral 8 }
cmcTcTrapControl OBJECT IDENTIFIER ::= { cmcTc 4 }
cmcTcTraps OBJECT IDENTIFIER ::= { cmcTcTrapControl 7 }
cmcTcControl OBJECT IDENTIFIER ::= { cmcTc 5 }
--*****************************************************************************
--CMC-TC ComputerMultiControl-TopConcept DK7320.100
--*****************************************************************************
--cmcTcMibRev-group
cmcTcMibMajRev OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Major Revision level.
A change in the major revision level represents a major change
in the architecture of the MIB. A change in the major revision
level may indicate a significant change in the information,
correct interpretation of data may require a MIB document
with the same major revision level."
::= { cmcTcMibRev 1 }
cmcTcMibMinRev OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Minor Revision level.
A change in the minor revision level may represent some minor
additional support, no changes to any pre-existing information
has occurred."
::= { cmcTcMibRev 2 }
cmcTcMibCondition OBJECT-TYPE
SYNTAX INTEGER {
other (1),
ok (2),
degraded (3),
failed (4),
configChanged (5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The overall condition (status) of the system represented by
this MIB.
(2) OK
(3) a minor problem, warning condition (yellow LED on CMC)
(4) a major problem (red LED on CMC)
(5) configuration of sensor units changed or
unit detected (red/yellow/green LED on CMC)"
::= { cmcTcMibRev 3 }
--status-group
cmcTcStatusDeviceCMC OBJECT-TYPE
SYNTAX INTEGER {
failed(1),
ok(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"General Status of CMC-TC unit itself
(1) failed
(2) OK"
::= { cmcTcStatus 1 }
cmcTcUnitsConnected OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of sensor units connected to the CMC, Port 1 to 4"
::= { cmcTcStatus 2 }
--status sensor units-group
--unit 1
cmcTcUnit1TypeOfDevice OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
unitIO (2),
unitAccess (3),
unitClimate (4),
unitFCS (5),
unitRTT (6),
unitRCT (7),
unitPSM (8),
unitPSM8 (9),
unitPSMMetered (10),
unitIOWireless (11),
unitPSM6Schuko (12),
unitPSM6C19 (13)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of sensor unit connected to port 1"
::= { cmcTcStatusSensorUnit1 1 }
cmcTcUnit1Text OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..10))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for sensor unit connected to port 1"
::= { cmcTcStatusSensorUnit1 2 }
cmcTcUnit1Serial OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Serialnumber of sensor unit connected to port 1"
::= { cmcTcStatusSensorUnit1 3 }
cmcTcUnit1Status OBJECT-TYPE
SYNTAX INTEGER {
ok(1),
error(2),
changed(3),
quit(4),
timeout(5),
detected(6),
notAvail(7),
lowPower(8)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"General Status sensor unit connected to port 1
(1) OK
(2) error, e. g. value overflow
(3) configuration of sensor unit has changed, confirmation required
(4) Quit from sensor unit to confirm configuration changes
(5) timeout of sensor unit, confirmation required to unload this unit
(6) sensor unit detected, needs to be confirmed
(7) unit is not available
(8) supply voltage is too low"
::= { cmcTcStatusSensorUnit1 4 }
-- Sensors
cmcTcUnit1NumberOfSensors OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of sensors connected to sensor unit 1"
::= { cmcTcStatusUnit1Sensors 1 }
-- table with entry for each sensor available on this unit
cmcTcUnit1SensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcUnit1SensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of sensor table"
::= { cmcTcStatusUnit1Sensors 2 }
cmcTcUnit1SensorEntry OBJECT-TYPE
SYNTAX CmcTcUnit1SensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of sensor table"
INDEX { unit1SensorIndex }
::= { cmcTcUnit1SensorTable 1 }
CmcTcUnit1SensorEntry ::=
SEQUENCE {
unit1SensorIndex
INTEGER,
unit1SensorType
INTEGER,
unit1SensorText
DisplayString,
unit1SensorStatus
INTEGER,
unit1SensorValue
INTEGER,
unit1SensorSetHigh
INTEGER,
unit1SensorSetLow
INTEGER,
unit1SensorSetWarn
INTEGER
}
unit1SensorIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of value entries. Its value ranges
between 1 and the value of cmcTcUnit1NumberOfSensors."
::= { cmcTcUnit1SensorEntry 1 }
unit1SensorType OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
failure (2),
overflow (3),
access (4),
vibration (5),
motion (6),
smoke (7),
airFlow (8),
type6 (9),
temperature(10),
current4to20(11),
humidity(12),
userNO (13),
userNC (14),
lock (15),
unlock (16),
voltOK (17),
voltage (18),
fanOK (19),
readerKeypad (20),
dutyPWM (21),
fanStatus (22),
leakage (23),
warningRTT (24),
alarmRTT (25),
filterRTT (26),
heatflowRCT (27),
alarmRCT (28),
warningRCT (29),
currentPSM (30),
statusPSM (31),
positionPSM (32),
airFlap (33),
acoustic (34),
detACfault (35),
detACfirstAlarm (36),
detACmainAlarm (37),
rpm11LCP (40),
rpm12LCP (41),
rpm21LCP (42),
rpm22LCP (43),
rpm31LCP (44),
rpm32LCP (45),
rpm41LCP (46),
rpm42LCP (47),
airTemp11LCP (48),
airTemp12LCP (49),
airTemp21LCP (50),
airTemp22LCP (51),
airTemp31LCP (52),
airTemp32LCP (53),
airTemp41LCP (54),
airTemp42LCP (55),
temp1LCP (56),
temp2LCP (57),
waterInTemp (58),
waterOutTemp (59),
waterFlow (60),
fanSpeed (61),
valve (62),
statusLCP (63),
waterDelta (64),
valveActual (65),
contrTemp2 (66),
condensateDuration (67),
condensateCycles (68),
totalKWhPSM (72),
totalKWPSM (73),
frequencyPSM (74),
voltagePSM (75),
voltStatusPSM (76),
amperePSM (77),
ampStatusPSM (78),
kWPSM (79),
kWhPSM (80),
kWhTempPSM (81),
temperatureWL (100),
temperature1WL (101),
humidityWL (102),
accessWL (103),
userNOWL (104),
userNCWL (105),
analogWL (106)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of sensor which is connected to sensor unit 1 to sensor[unit1SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type 2, vibration sensor
6: sensor type 3, motion sensor
7: sensor type 4, smoke sensor
8: sensor type 5, air flow sensor
9: sensor type 6, reserved
10: sensor type 7, temperature sensor
11: sensor type 8, 4..20mA sensor
12: sensor type 9, humidity sensor
13: user sensor with normally opened contact
14: user sensor with normally closed contact
15: door locked sensor from locking device
16: remote unlock sensor (e.g. external keypad)
17: voltage sensor, indicates status of main voltage (OK, NOK)
18: voltage value
19: fan status, from CMC-TC-FAS-Unit
20: cardreader or keypad, connected to I2C port
21: duty cycle of fan, FCS-Unit
22: status of fan, FCS-Unit
23: leakage sensor
24: warning, RittalTopTherm(RTT)-Unit
25: alarm, RittalTopTherm-Unit
26: temperature difference filter monitor, RTT-Unit
27: heatflow RCT-Unit
28: alarm RCT-Unit
29: warning RCT-Unit
30: actual current*10, PSM-Unit
31: status PSM-Unit
32: position PSM-Unit, normal/reversed = circuit 1/2
33: air Flap
34: acoustic sensor
35: DET-AC fault (extinguisher)
36: DET-AC first alarm (extinguisher)
37: DET-AC main alarm (extinguisher)
40-47: RPM Fan 1.1 - Fan 4.2, LCP
48-55: Air temperature 1.1 - 4.2, LCP
56,57: actual temperature 1,2, LCP
58: water inlet temperature, LCP
59: water outlet temperature, LCP
60: water flow
61: fan speed (desired value)
62: status valve, LCP
63: status LCP
64: temperature difference water temperatures
65: control temperature 1, LCP
66: control temperature 2, LCP
67: condensate pump, duration, LCP
68: condensate pump, cycles, LCP
72: total energy*10 (kWh), PSM
73: total power*10 (kW), PSM
74: frequency*10 (Hz), PSM
75: voltage*10 (V), PSM
76: voltage status, PSM
77: current*10 (A), PSM
78: current status, PSM
79: power*10 (kW) per phase, PSM
80: energy*10 (kWh) per phase, PSM
81: temporary energy*10 (kWh) per phase, PSM
100: temperature sensor, wireless
101: temperature sensor (combi), wireless
102: humidity sensor, wireless
103: access sensor, wireless
104: user sensor with normally opened contact, wireless
105: user sensor with normally closed contact, wireless
106: analog sensor 4..20mA, wireless"
::= { cmcTcUnit1SensorEntry 2 }
unit1SensorText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each sensor (entry in the table)"
::= { cmcTcUnit1SensorEntry 3 }
unit1SensorStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
lost(2),
changed(3),
ok(4),
off(5),
on(6),
warning(7),
tooLow(8),
tooHigh(9)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual status of the sensor"
::= { cmcTcUnit1SensorEntry 4 }
unit1SensorValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Value of sensor"
::= { cmcTcUnit1SensorEntry 5 }
unit1SensorSetHigh OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for high setpoint of sensor"
::= { cmcTcUnit1SensorEntry 6 }
unit1SensorSetLow OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for low setpoint of sensor,
also used as alarm delay"
::= { cmcTcUnit1SensorEntry 7 }
unit1SensorSetWarn OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for warning setpoint of sensor,
also used as fan threshold"
::= { cmcTcUnit1SensorEntry 8 }
-- table END
-- Outputs
cmcTcUnit1NumberOfOutputs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of outputs available on sensor unit 1"
::= { cmcTcStatusUnit1Outputs 1 }
-- table with entry for each output available on this unit
cmcTcUnit1OutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcUnit1OutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of output table"
::= { cmcTcStatusUnit1Outputs 2 }
cmcTcUnit1OutputEntry OBJECT-TYPE
SYNTAX CmcTcUnit1OutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of output table"
INDEX { unit1OutputIndex }
::= { cmcTcUnit1OutputTable 1 }
CmcTcUnit1OutputEntry ::=
SEQUENCE {
unit1OutputIndex
INTEGER,
unit1OutputType
INTEGER,
unit1OutputText
DisplayString,
unit1OutputStatus
INTEGER,
unit1OutputValue
INTEGER,
unit1OutputSet
INTEGER,
unit1OutputConfig
INTEGER,
unit1OutputDelay
INTEGER,
unit1OutputTimeoutAction
INTEGER
}
unit1OutputIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of output entries. Its value ranges
between 1 and the value of cmcTcUnit1NumberOfOutputs."
::= { cmcTcUnit1OutputEntry 1 }
unit1OutputType OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
failure (2),
overflow (3),
doorLock (4),
univLock1 (5),
univLock2 (6),
fan (7),
fanSpeedContr (8),
universalOut (9),
roomLock(10),
powerOut(11),
doorLockMaster(12),
doorLockFRi (13),
setpoint (14),
setpointTimax (15),
hysteresisRCT (16),
commandRCT (17),
relayPSM (18),
setHighPSM (19),
setLowPSM (20),
setpointRTT (21),
setTimaxRTT (22),
powerOut1(23),
controlModeLCP (30),
minFanSpeedLCP (31),
minDeltaTLCP (32),
maxDeltaTLCP (33),
kPLCP (34),
kILCP (35),
kDLCP (36),
flowRateLCP(37),
cwValueLCP (38),
deltaTLCP (39),
ctrModLCP (40),
voltHighPSM (42),
voltLowPSM (43),
ampHighPSM (44),
ampLowPSM (45),
commandPSM (46)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of output which is connected to sensor unit 1 to output[unit1OutputIndex]
1: no output connected
2: output failure
3: value overflow
4: output type 1, door locking TS8,Ergoform
5: output type 2, universal lock 1, lock with power
6: output type 3, universal lock 2, unlock with power
7: output type 4, fan relay
8: output type 5, fan controlled
9: output type 6, universal relay output
10: output type 7, room door lock
11: output type 8, power output
12: output type 9, door lock with Master key
13: output type 10, door lock FR(i)
14: setpoint (FCS, LCP)
15: setpoint temperature monitoring (LCP)
16: hysteresis of setpoint (LCP)
17: command for remote control of RCT
18: relay PSM, 1=On, 0=Off
19: high setpoint current monitoring PSM
20: low setpoint current monitoring PSM
21: setpoint temperature RTT
22: setpoint temperature monitoring RTT
23: power output 20A
30: control mode, LCP
31: min fan speed (fan control), LCP
32: min delta T (fan control), LCP
33: max delta T (fan control), LCP
34: PID controller, KP, LCP
35: PID controller, KI, LCP
36 PID controller, KD, LCP
37 flowrate flowmeter, LCP
38: cw value of water (default: 4187), LCP
39: deltaT, LCP
40: control mode, LCP
42: setpoint high voltage PSM
43: setpoint low voltage PSM
44: setpoint high current PSM
45: setpoint low current PSM
46: command PSM"
::= { cmcTcUnit1OutputEntry 2 }
unit1OutputText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each output (entry in the table)"
::= { cmcTcUnit1OutputEntry 3 }
unit1OutputStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
lost(2),
changed(3),
ok(4),
off(5),
on(6),
setOff(7),
setOn(8)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Actual status of the output"
::= { cmcTcUnit1OutputEntry 4 }
unit1OutputValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for output"
::= { cmcTcUnit1OutputEntry 5 }
unit1OutputSet OBJECT-TYPE
SYNTAX INTEGER {
off (1),
on (2),
lock (3),
unlock (4),
unlockDelay (5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Command for output"
::= { cmcTcUnit1OutputEntry 6 }
unit1OutputConfig OBJECT-TYPE
SYNTAX INTEGER {
disRemote (1),
enRemote (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Configuration for output
1: disable remote control (e.g. keypad)
2: enable remote control "
::= { cmcTcUnit1OutputEntry 7 }
unit1OutputDelay OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unsigned Value for delay,
after this time the output will fall into the previous state"
::= { cmcTcUnit1OutputEntry 8 }
unit1OutputTimeoutAction OBJECT-TYPE
SYNTAX INTEGER {
stay (1),
off (2),
on (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"State for output if timeout (RS422) occurs"
::= { cmcTcUnit1OutputEntry 9 }
-- Messages
cmcTcUnit1NumberOfMsgs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of messages that can be created with sensor unit 1"
::= { cmcTcStatusUnit1Msg 1 }
-- table with entry for each alarm available on this unit
cmcTcUnit1MsgTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcUnit1MsgEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of message table"
::= { cmcTcStatusUnit1Msg 2 }
cmcTcUnit1MsgEntry OBJECT-TYPE
SYNTAX CmcTcUnit1MsgEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of message table"
INDEX { unit1MsgIndex }
::= { cmcTcUnit1MsgTable 1 }
CmcTcUnit1MsgEntry ::=
SEQUENCE {
unit1MsgIndex
INTEGER,
unit1MsgText
DisplayString,
unit1MsgStatus
INTEGER,
unit1MsgRelay
INTEGER,
unit1MsgBeeper
INTEGER,
unit1MsgTrap1
INTEGER,
unit1MsgTrap2
INTEGER,
unit1MsgTrap3
INTEGER,
unit1MsgTrap4
INTEGER,
unit1MsgQuit
INTEGER
}
unit1MsgIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of message entries. Its value ranges
between 1 and the value of cmcTcUnit1NumberOfMsgs."
::= { cmcTcUnit1MsgEntry 1 }
unit1MsgText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each message (entry in the table)"
::= { cmcTcUnit1MsgEntry 2 }
unit1MsgStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
configChanged(2),
error(3),
ok(4),
alarm(5),
warning(6),
tooLow(7),
tooHigh(8),
setOff(9),
setOn(10),
open(11),
closed(12),
locked(13),
unlRemote(14),
unlReaderKeypad(15),
unlSNMP(16),
unlWEB(17),
unlTimer(18),
noAccess(19),
circuit1 (20),
circuit2 (21),
lowBatt (22)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog value too low, value reached low threshold
8: analog value too high, value reached high threshold
9: output is set to OFF
10: output is set to ON
11: door is open
12: door is closed
13: door is locked
14: door is unlocked by remote input, e.g. external cardreader
15: door is unlocked by reader or keypad connected to I2C
16: door is unlocked by SNMP set command (unit1OutputSet)
17: door is unlocked by WEB
18: door is unlocked by timer
19: no access, wrong keycode or cardnumber
20: orientation of PSM-Unit is circuit 1
21: orientation of PSM-Unit is circuit 2
22: battery low, wireless sensor"
::= { cmcTcUnit1MsgEntry 3 }
unit1MsgRelay OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup of Alarm relay for this message/alarm
1: no switching of alarm relay
2: switching of alarm relay"
::= { cmcTcUnit1MsgEntry 4 }
unit1MsgBeeper OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup of Alarm beeper for this alarm
1: no audible alarm
2: audible alarm"
::= { cmcTcUnit1MsgEntry 5 }
unit1MsgTrap1 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 1 activated"
::= { cmcTcUnit1MsgEntry 6 }
unit1MsgTrap2 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 2 activated"
::= { cmcTcUnit1MsgEntry 7 }
unit1MsgTrap3 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 3 activated"
::= { cmcTcUnit1MsgEntry 8 }
unit1MsgTrap4 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 4 and Event Logging activated"
::= { cmcTcUnit1MsgEntry 9 }
unit1MsgQuit OBJECT-TYPE
SYNTAX INTEGER {
auto (1),
manual (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' key"
::= { cmcTcUnit1MsgEntry 10 }
-- table unit 1 END
-- unit2
cmcTcUnit2TypeOfDevice OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
unitIO (2),
unitAccess (3),
unitClimate (4),
unitFCS (5),
unitRTT (6),
unitRCT (7),
unitPSM (8),
unitPSM8 (9),
unitPSMMetered (10),
unitIOWireless (11),
unitPSM6Schuko (12),
unitPSM6C19 (13)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of sensor unit connected to port 2"
::= { cmcTcStatusSensorUnit2 1 }
cmcTcUnit2Text OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..10))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for sensor unit connected to port 2"
::= { cmcTcStatusSensorUnit2 2 }
cmcTcUnit2Serial OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Serialnumber of sensor unit connected to port 2"
::= { cmcTcStatusSensorUnit2 3 }
cmcTcUnit2Status OBJECT-TYPE
SYNTAX INTEGER {
ok(1),
error(2),
changed(3),
quit(4),
timeout(5),
detected(6),
notAvail(7),
lowPower(8)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"General Status sensor unit connected to port 2
(1) OK
(2) error
(3) configuration of sensor unit has changed, confirmation required
(4) Quit from sensor unit to confirm configuration changes
(5) timeout of sensor unit, confirmation required
(6) sensor unit detected, needs to be confirmed
(8) supply voltage is too low"
::= { cmcTcStatusSensorUnit2 4 }
-- unit 2 table
-- Sensors
cmcTcUnit2NumberOfSensors OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of sensors connected to sensor unit 2"
::= { cmcTcStatusUnit2Sensors 1 }
-- table with entry for each sensor available on this unit
cmcTcUnit2SensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcUnit2SensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of sensor table"
::= { cmcTcStatusUnit2Sensors 2 }
cmcTcUnit2SensorEntry OBJECT-TYPE
SYNTAX CmcTcUnit2SensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of sensor table"
INDEX { unit2SensorIndex }
::= { cmcTcUnit2SensorTable 1 }
CmcTcUnit2SensorEntry ::=
SEQUENCE {
unit2SensorIndex
INTEGER,
unit2SensorType
INTEGER,
unit2SensorText
DisplayString,
unit2SensorStatus
INTEGER,
unit2SensorValue
INTEGER,
unit2SensorSetHigh
INTEGER,
unit2SensorSetLow
INTEGER,
unit2SensorSetWarn
INTEGER
}
unit2SensorIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of value entries. Its value ranges
between 1 and the value of cmcTcUnit2NumberOfSensors."
::= { cmcTcUnit2SensorEntry 1 }
unit2SensorType OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
failure (2),
overflow (3),
access (4),
vibration (5),
motion (6),
smoke (7),
airFlow (8),
type6 (9),
temperature(10),
current4to20(11),
humidity(12),
userNO (13),
userNC (14),
lock (15),
unlock (16),
voltOK (17),
voltage (18),
fanOK (19),
readerKeypad (20),
dutyPWM (21),
fanStatus (22),
leakage (23),
warningRTT (24),
alarmRTT (25),
filterRTT (26),
heatflowRCT (27),
alarmRCT (28),
warningRCT (29),
currentPSM (30),
statusPSM (31),
positionPSM (32),
airFlap (33),
detACfault (35),
detACfirstAlarm (36),
detACmainAlarm (37),
acoustic (34),
rpm11LCP (40),
rpm12LCP (41),
rpm21LCP (42),
rpm22LCP (43),
rpm31LCP (44),
rpm32LCP (45),
rpm41LCP (46),
rpm42LCP (47),
airTemp11LCP (48),
airTemp12LCP (49),
airTemp21LCP (50),
airTemp22LCP (51),
airTemp31LCP (52),
airTemp32LCP (53),
airTemp41LCP (54),
airTemp42LCP (55),
temp1LCP (56),
temp2LCP (57),
waterInTemp (58),
waterOutTemp (59),
waterFlow (60),
fanSpeed (61),
valve (62),
statusLCP (63),
waterDelta (64),
valveActual (65),
contrTemp2 (66),
condensateDuration (67),
condensateCycles (68),
totalKWhPSM (72),
totalKWPSM (73),
frequencyPSM (74),
voltagePSM (75),
voltStatusPSM (76),
amperePSM (77),
ampStatusPSM (78),
kWPSM (79),
kWhPSM (80),
kWhTempPSM (81),
temperatureWL (100),
temperature1WL (101),
humidityWL (102),
accessWL (103),
userNOWL (104),
userNCWL (105),
analogWL (106)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of sensor which is connected to sensor unit 2 to sensor[unit2SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type 2, vibration sensor
6: sensor type 3, motion sensor
7: sensor type 4, smoke sensor
8: sensor type 5, air flow sensor
9: sensor type 6, reserved
10: sensor type 7, temperature sensor
11: sensor type 8, 4..20mA sensor
12: sensor type 9, humidity sensor
13: user sensor with normally opened contact
14: user sensor with normally closed contact
15: door locked sensor from locking device
16: remote unlock sensor (e.g. external keypad)
17: voltage sensor, indicates status of main voltage
18: voltage value
19: fan status
20: cardreader or keypad, connected to I2C port
21: duty cycle of fan, FCS-Unit
22: status of fan, FCS-Unit
23: leakage sensor
24: warning, RittalTopTherm(RTT)-Unit
25: alarm, RittalTopTherm-Unit
26: temperature difference filter monitor, RTT-Unit
27: heatflow RCT-Unit
28: alarm RCT-Unit
29: warning RCT-Unit
30: actual current*10, PSM-Unit
31: status PSM-Unit
32: position PSM-Unit, normal/reversed = circuit 1/2
33: air Flap
34: acoustic sensor
35: DET-AC fault (extinguisher)
36: DET-AC first alarm (extinguisher)
37: DET-AC main alarm (extinguisher)
40-47: RPM Fan 1.1 - Fan 4.2, LCP
48-55: Air temperature 1.1 - 4.2, LCP
56,57: actual temperature 1,2, LCP
58: water inlet temperature, LCP
59: water outlet temperature, LCP
60: water flow
61: fan speed (desired value)
62: status valve, LCP
63: status LCP
64: temperature difference water temperatures
65: control temperature 1, LCP
66: control temperature 2, LCP
67: condensate pump, duration, LCP
68: condensate pump, cycles, LCP
72: total energy*10 (kWh), PSM
73: total power*10 (kW), PSM
74: frequency*10 (Hz), PSM
75: voltage*10 (V), PSM
76: voltage status, PSM
77: current*10 (A), PSM
78: current status, PSM
79: power*10 (kW) per phase, PSM
80: energy*10 (kWh) per phase, PSM
81: temporary energy*10 (kWh) per phase, PSM
100: temperature sensor, wireless
101: temperature sensor (combi), wireless
102: humidity sensor, wireless
103: access sensor, wireless
104: user sensor with normally opened contact, wireless
105: user sensor with normally closed contact, wireless
106: analog sensor 4..20mA, wireless"
::= { cmcTcUnit2SensorEntry 2 }
unit2SensorText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each sensor (entry in the table)"
::= { cmcTcUnit2SensorEntry 3 }
unit2SensorStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
lost(2),
changed(3),
ok(4),
off(5),
on(6),
warning(7),
tooLow(8),
tooHigh(9)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual status of the sensor"
::= { cmcTcUnit2SensorEntry 4 }
unit2SensorValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Value of sensor"
::= { cmcTcUnit2SensorEntry 5 }
unit2SensorSetHigh OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for high setpoint of sensor"
::= { cmcTcUnit2SensorEntry 6 }
unit2SensorSetLow OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for low setpoint of sensor,
also used as alarm delay"
::= { cmcTcUnit2SensorEntry 7 }
unit2SensorSetWarn OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for warning setpoint of sensor,
also used as fan threshold"
::= { cmcTcUnit2SensorEntry 8 }
-- table END
-- Outputs
cmcTcUnit2NumberOfOutputs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of outputs available on sensor unit 2"
::= { cmcTcStatusUnit2Outputs 1 }
-- table with entry for each output available on this unit
cmcTcUnit2OutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcUnit2OutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of output table"
::= { cmcTcStatusUnit2Outputs 2 }
cmcTcUnit2OutputEntry OBJECT-TYPE
SYNTAX CmcTcUnit2OutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of output table"
INDEX { unit2OutputIndex }
::= { cmcTcUnit2OutputTable 1 }
CmcTcUnit2OutputEntry ::=
SEQUENCE {
unit2OutputIndex
INTEGER,
unit2OutputType
INTEGER,
unit2OutputText
DisplayString,
unit2OutputStatus
INTEGER,
unit2OutputValue
INTEGER,
unit2OutputSet
INTEGER,
unit2OutputConfig
INTEGER,
unit2OutputDelay
INTEGER,
unit2OutputTimeoutAction
INTEGER
}
unit2OutputIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of output entries. Its value ranges
between 1 and the value of cmcTcUnit2NumberOfOutputs."
::= { cmcTcUnit2OutputEntry 1 }
unit2OutputType OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
failure (2),
overflow (3),
doorLock (4),
univLock1 (5),
univLock2 (6),
fan (7),
fanSpeedContr (8),
universalOut (9),
roomLock(10),
powerOut(11),
doorLockMaster(12),
doorLockFRi (13),
setpoint (14),
setpointTimax (15),
hysteresisRCT (16),
commandRCT (17),
relayPSM (18),
setHighPSM (19),
setLowPSM (20),
setpointRTT (21),
setTimaxRTT (22),
powerOut1(23),
controlModeLCP (30),
minFanSpeedLCP (31),
minDeltaTLCP (32),
maxDeltaTLCP (33),
kPLCP (34),
kILCP (35),
kDLCP (36),
flowRateLCP(37),
cwValueLCP (38),
deltaTLCP (39),
ctrModLCP (40),
voltHighPSM (42),
voltLowPSM (43),
ampHighPSM (44),
ampLowPSM (45),
commandPSM (46)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of output which is connected to sensor unit 2 to output[unit2OutputIndex]
1: no output connected
2: output failure
3: value overflow
4: output type 1, door locking TS8,Ergoform
5: output type 2, universal lock 1, lock with power
6: output type 3, universal lock 2, unlock with power
7: output type 4, fan relay
8: output type 5, fan controlled
9: output type 6, universal relay output
10: output type 7, room door lock
11: output type 8, power output
12: output type 9, door lock with Master key
13: output type 10, door lock FR(i)
14: setpoint (FCS, RTT)
15: setpoint temperature monitoring (RTT)
16: hysteresis of setpoint (RCT)
17: command for remote control of RCT
18: relay PSM, 1=On, 0=Off
19: high setpoint current monitoring PSM
20: low setpoint current monitoring PSM
21: setpoint temperature RTT
22: setpoint temperature monitoring RTT
23: power output 20A
30: control mode LCP
31: min fan speed (fan control) LCP
32: min delta T (fan control) LCP
33: max delta T (fan control) LCP
34: PID controller, KP, LCP
35: PID controller, KI, LCP
36 PID controller, KD, LCP
37 flowrate flowmeter, LCP
38: cw value of water (default: 4187) LCP
39: deltaT, LCP
40: control mode, LCP
42: setpoint high voltage PSM
43: setpoint low voltage PSM
44: setpoint high current PSM
45: setpoint low current PSM
46: command PSM"
::= { cmcTcUnit2OutputEntry 2 }
unit2OutputText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each output (entry in the table)"
::= { cmcTcUnit2OutputEntry 3 }
unit2OutputStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
lost(2),
changed(3),
ok(4),
off(5),
on(6),
setOff(7),
setOn(8)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Actual status of the output"
::= { cmcTcUnit2OutputEntry 4 }
unit2OutputValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Signed value for output"
::= { cmcTcUnit2OutputEntry 5 }
unit2OutputSet OBJECT-TYPE
SYNTAX INTEGER {
off (1),
on (2),
lock (3),
unlock (4),
unlockDelay (5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Command for output"
::= { cmcTcUnit2OutputEntry 6 }
unit2OutputConfig OBJECT-TYPE
SYNTAX INTEGER {
disRemote (1),
enRemote (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Configuration for output
1: disable remote control (e.g. keypad)
2: enable remote control "
::= { cmcTcUnit2OutputEntry 7 }
unit2OutputDelay OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unsigned Value for delay,
after this time the output will fall into the previous state"
::= { cmcTcUnit2OutputEntry 8 }
unit2OutputTimeoutAction OBJECT-TYPE
SYNTAX INTEGER {
stay (1),
off (2),
on (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"State for output if timeout (RS422) occurs"
::= { cmcTcUnit2OutputEntry 9 }
-- Alarms
cmcTcUnit2NumberOfMsgs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of alarms that can be created with sensor unit 2"
::= { cmcTcStatusUnit2Msg 1 }
-- table with entry for each alarm available on this unit
cmcTcUnit2MsgTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcUnit2MsgEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of message table"
::= { cmcTcStatusUnit2Msg 2 }
cmcTcUnit2MsgEntry OBJECT-TYPE
SYNTAX CmcTcUnit2MsgEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of message table"
INDEX { unit2MsgIndex }
::= { cmcTcUnit2MsgTable 1 }
CmcTcUnit2MsgEntry ::=
SEQUENCE {
unit2MsgIndex
INTEGER,
unit2MsgText
DisplayString,
unit2MsgStatus
INTEGER,
unit2MsgRelay
INTEGER,
unit2MsgBeeper
INTEGER,
unit2MsgTrap1
INTEGER,
unit2MsgTrap2
INTEGER,
unit2MsgTrap3
INTEGER,
unit2MsgTrap4
INTEGER,
unit2MsgQuit
INTEGER
}
unit2MsgIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of alarm entries. Its value ranges
between 1 and the value of cmcTcUnit2NumberOfMsgs."
::= { cmcTcUnit2MsgEntry 1 }
unit2MsgText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each message (entry in the table)"
::= { cmcTcUnit2MsgEntry 2 }
unit2MsgStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
configChanged(2),
error(3),
ok(4),
alarm(5),
warning(6),
tooLow(7),
tooHigh(8),
setOff(9),
setOn(10),
open(11),
closed(12),
locked(13),
unlRemote(14),
unlReaderKeypad(15),
unlSNMP(16),
unlWEB(17),
unlTimer(18),
noAccess(19),
circuit1 (20),
circuit2 (21),
lowBatt (22)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog value too low, value reached low threshold
8: analog value too high, value reached high threshold
9: output is set to OFF
10: output is set to ON
11: door is open
12: door is closed
13: door is locked
14: door is unlocked by remote input, e.g. external cardreader
15: door is unlocked by reader or keypad connected to I2C
16: door is unlocked by SNMP set command (unit1OutputSet)
17: door is unlocked by WEB
18: door is unlocked by timer
19: no access, wrong keycode or cardnumber
20: orientation of PSM-Unit is circuit 1
21: orientation of PSM-Unit is circuit 2
22: battery low, wireless sensor"
::= { cmcTcUnit2MsgEntry 3 }
unit2MsgRelay OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup of Alarm relay for this alarm
2: no switching of alarm relay
1: switching of alarm relay"
::= { cmcTcUnit2MsgEntry 4 }
unit2MsgBeeper OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup of Alarm beeper for this alarm
2: no audible alarm
1: audible alarm"
::= { cmcTcUnit2MsgEntry 5 }
unit2MsgTrap1 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 1 activated"
::= { cmcTcUnit2MsgEntry 6 }
unit2MsgTrap2 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 2 activated"
::= { cmcTcUnit2MsgEntry 7 }
unit2MsgTrap3 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 3 activated"
::= { cmcTcUnit2MsgEntry 8 }
unit2MsgTrap4 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 4 and Event Logging activated"
::= { cmcTcUnit2MsgEntry 9 }
unit2MsgQuit OBJECT-TYPE
SYNTAX INTEGER {
auto (1),
manual (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' key"
::= { cmcTcUnit2MsgEntry 10 }
-- table END
-- unit 3
cmcTcUnit3TypeOfDevice OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
unitIO (2),
unitAccess (3),
unitClimate (4),
unitFCS (5),
unitRTT (6),
unitRCT (7),
unitPSM (8),
unitPSM8 (9),
unitPSMMetered (10),
unitIOWireless (11),
unitPSM6Schuko (12),
unitPSM6C19 (13)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of sensor unit connected to port 3"
::= { cmcTcStatusSensorUnit3 1 }
cmcTcUnit3Text OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..10))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for sensor unit connected to port 3"
::= { cmcTcStatusSensorUnit3 2 }
cmcTcUnit3Serial OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Serialnumber of sensor unit connected to port 3"
::= { cmcTcStatusSensorUnit3 3 }
cmcTcUnit3Status OBJECT-TYPE
SYNTAX INTEGER {
ok(1),
error(2),
changed(3),
quit(4),
timeout(5),
detected(6),
notAvail(7),
lowPower(8)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"General Status sensor unit connected to port 3
(1) OK
(2) error, e. g. value overflow
(3) configuration of sensor unit has changed, confirmation required
(4) Quit from sensor unit to confirm configuration changes
(5) timeout of sensor unit, confirmation required to unload this unit
(6) sensor unit detected, needs to be confirmed
(7) unit is not available
(8) supply voltage is too low"
::= { cmcTcStatusSensorUnit3 4 }
-- Sensors
cmcTcUnit3NumberOfSensors OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of sensors connected to sensor unit 3"
::= { cmcTcStatusUnit3Sensors 1 }
-- table with entry for each sensor available on this unit
cmcTcUnit3SensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcUnit3SensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of sensor table"
::= { cmcTcStatusUnit3Sensors 2 }
cmcTcUnit3SensorEntry OBJECT-TYPE
SYNTAX CmcTcUnit3SensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of sensor table"
INDEX { unit3SensorIndex }
::= { cmcTcUnit3SensorTable 1 }
CmcTcUnit3SensorEntry ::=
SEQUENCE {
unit3SensorIndex
INTEGER,
unit3SensorType
INTEGER,
unit3SensorText
DisplayString,
unit3SensorStatus
INTEGER,
unit3SensorValue
INTEGER,
unit3SensorSetHigh
INTEGER,
unit3SensorSetLow
INTEGER,
unit3SensorSetWarn
INTEGER
}
unit3SensorIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of value entries. Its value ranges
between 1 and the value of cmcTcUnit3NumberOfSensors."
::= { cmcTcUnit3SensorEntry 1 }
unit3SensorType OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
failure (2),
overflow (3),
access (4),
vibration (5),
motion (6),
smoke (7),
airFlow (8),
type6 (9),
temperature(10),
current4to20(11),
humidity(12),
userNO (13),
userNC (14),
lock (15),
unlock (16),
voltOK (17),
voltage (18),
fanOK (19),
readerKeypad (20),
dutyPWM (21),
fanStatus (22),
leakage (23),
warningRTT (24),
alarmRTT (25),
filterRTT (26),
heatflowRCT (27),
alarmRCT (28),
warningRCT (29),
currentPSM (30),
statusPSM (31),
positionPSM (32),
airFlap (33),
acoustic (34),
detACfault (35),
detACfirstAlarm (36),
detACmainAlarm (37),
rpm11LCP (40),
rpm12LCP (41),
rpm21LCP (42),
rpm22LCP (43),
rpm31LCP (44),
rpm32LCP (45),
rpm41LCP (46),
rpm42LCP (47),
airTemp11LCP (48),
airTemp12LCP (49),
airTemp21LCP (50),
airTemp22LCP (51),
airTemp31LCP (52),
airTemp32LCP (53),
airTemp41LCP (54),
airTemp42LCP (55),
temp1LCP (56),
temp2LCP (57),
waterInTemp (58),
waterOutTemp (59),
waterFlow (60),
fanSpeed (61),
valve (62),
statusLCP (63),
waterDelta (64),
valveActual (65),
contrTemp2 (66),
condensateDuration (67),
condensateCycles (68),
totalKWhPSM (72),
totalKWPSM (73),
frequencyPSM (74),
voltagePSM (75),
voltStatusPSM (76),
amperePSM (77),
ampStatusPSM (78),
kWPSM (79),
kWhPSM (80),
kWhTempPSM (81),
temperatureWL (100),
temperature1WL (101),
humidityWL (102),
accessWL (103),
userNOWL (104),
userNCWL (105),
analogWL (106)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of sensor which is connected to sensor unit 3 to sensor[unit3SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type 2, vibration sensor
6: sensor type 3, motion sensor
7: sensor type 4, smoke sensor
8: sensor type 5, air flow sensor
9: sensor type 6, reserved
10: sensor type 7, temperature sensor
11: sensor type 8, 4..20mA sensor
12: sensor type 9, humidity sensor
13: user sensor with normally opened contact
14: user sensor with normally closed contact
15: door locked sensor from locking device
16: remote unlock sensor (e.g. external keypad)
17: voltage sensor, indicates status of main voltage
18: voltage value
19: fan status
20: cardreader or keypad, connected to I2C port
21: duty cycle of fan, FCS-Unit
22: status of fan, FCS-Unit
23: leakage sensor
24: warning, RittalTopTherm(RTT)-Unit
25: alarm, RittalTopTherm-Unit
26: temperature difference filter monitor, RTT-Unit
27: heatflow RCT-Unit
28: alarm RCT-Unit
29: warning RCT-Unit
30: actual current*10, PSM-Unit
31: status PSM-Unit
32: position PSM-Unit, normal/reversed = circuit 1/2
33: air Flap
34: acoustic sensor
35: DET-AC fault (extinguisher)
36: DET-AC first alarm (extinguisher)
37: DET-AC main alarm (extinguisher)
40-47: RPM Fan 1.1 - Fan 4.2, LCP
48-55: Air temperature 1.1 - 4.2, LCP
56,57: actual temperature 1,2, LCP
58: water inlet temperature, LCP
59: water outlet temperature, LCP
60: water flow
61: fan speed (desired value)
62: status valve, LCP
63: status LCP
64: temperature difference water temperatures
65: control temperature 1, LCP
66: control temperature 2, LCP
67: condensate pump, duration, LCP
68: condensate pump, cycles, LCP
72: total energy*10 (kWh), PSM
73: total power*10 (kW), PSM
74: frequency*10 (Hz), PSM
75: voltage*10 (V), PSM
76: voltage status, PSM
77: current*10 (A), PSM
78: current status, PSM
79: power*10 (kW) per phase, PSM
80: energy*10 (kWh) per phase, PSM
81: temporary energy*10 (kWh) per phase, PSM
100: temperature sensor, wireless
101: temperature sensor (combi), wireless
102: humidity sensor, wireless
103: access sensor, wireless
104: user sensor with normally opened contact, wireless
105: user sensor with normally closed contact, wireless
106: analog sensor 4..20mA, wireless"
::= { cmcTcUnit3SensorEntry 2 }
unit3SensorText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each sensor (entry in the table)"
::= { cmcTcUnit3SensorEntry 3 }
unit3SensorStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
lost(2),
changed(3),
ok(4),
off(5),
on(6),
warning(7),
tooLow(8),
tooHigh(9)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual status of the sensor"
::= { cmcTcUnit3SensorEntry 4 }
unit3SensorValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Value of sensor"
::= { cmcTcUnit3SensorEntry 5 }
unit3SensorSetHigh OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for high setpoint of sensor"
::= { cmcTcUnit3SensorEntry 6 }
unit3SensorSetLow OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for low setpoint of sensor"
::= { cmcTcUnit3SensorEntry 7 }
unit3SensorSetWarn OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for warning setpoint of sensor,
also used as fan threshold"
::= { cmcTcUnit3SensorEntry 8 }
-- table END
-- Outputs
cmcTcUnit3NumberOfOutputs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of outputs available on sensor unit 3"
::= { cmcTcStatusUnit3Outputs 1 }
-- table with entry for each output available on this unit
cmcTcUnit3OutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcUnit3OutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of output table"
::= { cmcTcStatusUnit3Outputs 2 }
cmcTcUnit3OutputEntry OBJECT-TYPE
SYNTAX CmcTcUnit3OutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of output table"
INDEX { unit3OutputIndex }
::= { cmcTcUnit3OutputTable 1 }
CmcTcUnit3OutputEntry ::=
SEQUENCE {
unit3OutputIndex
INTEGER,
unit3OutputType
INTEGER,
unit3OutputText
DisplayString,
unit3OutputStatus
INTEGER,
unit3OutputValue
INTEGER,
unit3OutputSet
INTEGER,
unit3OutputConfig
INTEGER,
unit3OutputDelay
INTEGER,
unit3OutputTimeoutAction
INTEGER
}
unit3OutputIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of output entries. Its value ranges
between 1 and the value of cmcTcUnit3NumberOfOutputs."
::= { cmcTcUnit3OutputEntry 1 }
unit3OutputType OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
failure (2),
overflow (3),
doorLock (4),
univLock1 (5),
univLock2 (6),
fan (7),
fanSpeedContr (8),
universalOut (9),
roomLock(10),
powerOut(11),
doorLockMaster(12),
doorLockFRi (13),
setpoint (14),
setpointTimax (15),
hysteresisRCT (16),
commandRCT (17),
relayPSM (18),
setHighPSM (19),
setLowPSM (20),
setpointRTT (21),
setTimaxRTT (22),
powerOut1(23),
controlModeLCP (30),
minFanSpeedLCP (31),
minDeltaTLCP (32),
maxDeltaTLCP (33),
kPLCP (34),
kILCP (35),
kDLCP (36),
flowRateLCP(37),
cwValueLCP (38),
deltaTLCP (39),
ctrModLCP (40),
voltHighPSM (42),
voltLowPSM (43),
ampHighPSM (44),
ampLowPSM (45),
commandPSM (46)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of output which is connected to sensor unit 3 to output[unit3OutputIndex]
1: no output connected
2: output failure
3: value overflow
4: output type 1, door locking TS8,Ergoform
5: output type 2, universal lock 1, lock with power
6: output type 3, universal lock 2, unlock with power
7: output type 4, fan relay
8: output type 5, fan controlled
9: output type 6, universal relay output
10: output type 7, room door lock
11: output type 8, power output
12: output type 9, door lock with Master key
13: output type 10, door lock FR(i)
14: setpoint (FCS, RTT)
15: setpoint temperature monitoring (RTT)
16: hysteresis of setpoint (RCT)
17: command for remote control of RCT
18: relay PSM, 1=On, 0=Off
19: high setpoint current monitoring PSM
20: low setpoint current monitoring PSM
21: setpoint temperature RTT
22: setpoint temperature monitoring RTT
23: power output 20A
30: control mode LCP
31: min fan speed (fan control) LCP
32: min delta T (fan control) LCP
33: max delta T (fan control) LCP
34: PID controller, KP, LCP
35: PID controller, KI, LCP
36 PID controller, KD, LCP
37 flowrate flowmeter, LCP
38: cw value of water (default: 4187) LCP
39: deltaT, LCP
40: control mode, LCP
42: setpoint high voltage PSM
43: setpoint low voltage PSM
44: setpoint high current PSM
45: setpoint low current PSM
46: command PSM"
::= { cmcTcUnit3OutputEntry 2 }
unit3OutputText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each output (entry in the table)"
::= { cmcTcUnit3OutputEntry 3 }
unit3OutputStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
lost(2),
changed(3),
ok(4),
off(5),
on(6),
setOff(7),
setOn(8)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Actual status of the output"
::= { cmcTcUnit3OutputEntry 4 }
unit3OutputValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for output"
::= { cmcTcUnit3OutputEntry 5 }
unit3OutputSet OBJECT-TYPE
SYNTAX INTEGER {
off (1),
on (2),
lock (3),
unlock (4),
unlockDelay (5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Command for output"
::= { cmcTcUnit3OutputEntry 6 }
unit3OutputConfig OBJECT-TYPE
SYNTAX INTEGER {
disRemote (1),
enRemote (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Configuration for output
1: disable remote control (e.g. keypad)
2: enable remote control "
::= { cmcTcUnit3OutputEntry 7 }
unit3OutputDelay OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unsigned Value for delay,
after this time the output will fall into the previous state"
::= { cmcTcUnit3OutputEntry 8 }
unit3OutputTimeoutAction OBJECT-TYPE
SYNTAX INTEGER {
stay (1),
off (2),
on (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"State for output if timeout (RS422) occurs"
::= { cmcTcUnit3OutputEntry 9 }
-- Msgs
cmcTcUnit3NumberOfMsgs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of alarms that can be created with sensor unit 3"
::= { cmcTcStatusUnit3Msg 1 }
-- table with entry for each alarm available on this unit
cmcTcUnit3MsgTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcUnit3MsgEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of message table"
::= { cmcTcStatusUnit3Msg 2 }
cmcTcUnit3MsgEntry OBJECT-TYPE
SYNTAX CmcTcUnit3MsgEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of message table"
INDEX { unit3MsgIndex }
::= { cmcTcUnit3MsgTable 1 }
CmcTcUnit3MsgEntry ::=
SEQUENCE {
unit3MsgIndex
INTEGER,
unit3MsgText
DisplayString,
unit3MsgStatus
INTEGER,
unit3MsgRelay
INTEGER,
unit3MsgBeeper
INTEGER,
unit3MsgTrap1
INTEGER,
unit3MsgTrap2
INTEGER,
unit3MsgTrap3
INTEGER,
unit3MsgTrap4
INTEGER,
unit3MsgQuit
INTEGER
}
unit3MsgIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of alarm entries. Its value ranges
between 1 and the value of cmcTcUnit3NumberOfMsgs."
::= { cmcTcUnit3MsgEntry 1 }
unit3MsgText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each message (entry in the table)"
::= { cmcTcUnit3MsgEntry 2 }
unit3MsgStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
configChanged(2),
error(3),
ok(4),
alarm(5),
warning(6),
tooLow(7),
tooHigh(8),
setOff(9),
setOn(10),
open(11),
closed(12),
locked(13),
unlRemote(14),
unlReaderKeypad(15),
unlSNMP(16),
unlWEB(17),
unlTimer(18),
noAccess(19),
circuit1 (20),
circuit2 (21),
lowBatt (22)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog value too low, value reached low threshold
8: analog value too high, value reached high threshold
9: output is set to OFF
10: output is set to ON
11: door is open
12: door is closed
13: door is locked
14: door is unlocked by remote input, e.g. external cardreader
15: door is unlocked by reader or keypad connected to I2C
16: door is unlocked by SNMP set command (unit1OutputSet)
17: door is unlocked by WEB
18: door is unlocked by timer
19: no access, wrong keycode or cardnumber
20: orientation of PSM-Unit is circuit 1
21: orientation of PSM-Unit is circuit 2
22: battery low, wireless sensor"
::= { cmcTcUnit3MsgEntry 3 }
unit3MsgRelay OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup of Alarm relay for this alarm
1: no switching of alarm relay
2: switching of alarm relay"
::= { cmcTcUnit3MsgEntry 4 }
unit3MsgBeeper OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup of Alarm beeper for this alarm
1: no audible alarm
2: audible alarm"
::= { cmcTcUnit3MsgEntry 5 }
unit3MsgTrap1 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 1 activated"
::= { cmcTcUnit3MsgEntry 6 }
unit3MsgTrap2 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 2 activated"
::= { cmcTcUnit3MsgEntry 7 }
unit3MsgTrap3 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 3 activated"
::= { cmcTcUnit3MsgEntry 8 }
unit3MsgTrap4 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 4 and Event Logging activated"
::= { cmcTcUnit3MsgEntry 9 }
unit3MsgQuit OBJECT-TYPE
SYNTAX INTEGER {
auto (1),
manual (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' key"
::= { cmcTcUnit3MsgEntry 10 }
-- table END
-- unit4
cmcTcUnit4TypeOfDevice OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
unitIO (2),
unitAccess (3),
unitClimate (4),
unitFCS (5),
unitRTT (6),
unitRCT (7),
unitPSM (8),
unitPSM8 (9),
unitPSMMetered (10),
unitIOWireless (11),
unitPSM6Schuko (12),
unitPSM6C19 (13)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of sensor unit connected to port 4"
::= { cmcTcStatusSensorUnit4 1 }
cmcTcUnit4Text OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..10))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for sensor unit connected to port 4"
::= { cmcTcStatusSensorUnit4 2 }
cmcTcUnit4Serial OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Serialnumber of sensor unit connected to port 4"
::= { cmcTcStatusSensorUnit4 3 }
cmcTcUnit4Status OBJECT-TYPE
SYNTAX INTEGER {
ok(1),
error(2),
changed(3),
quit(4),
timeout(5),
detected(6),
notAvail(7),
lowPower(8)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"General Status sensor unit connected to port 4
(1) OK
(2) error, e. g. value overflow
(3) configuration of sensor unit has changed, confirmation required
(4) Quit from sensor unit to confirm configuration changes
(5) timeout of sensor unit, confirmation required to unload this unit
(6) sensor unit detected, needs to be confirmed
(7) unit is not available
(8) supply voltage is too low"
::= { cmcTcStatusSensorUnit4 4 }
-- Sensors
cmcTcUnit4NumberOfSensors OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of sensors connected to sensor unit 4"
::= { cmcTcStatusUnit4Sensors 1 }
-- table with entry for each sensor available on this unit
cmcTcUnit4SensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcUnit4SensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of sensor table"
::= { cmcTcStatusUnit4Sensors 2 }
cmcTcUnit4SensorEntry OBJECT-TYPE
SYNTAX CmcTcUnit4SensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of sensor table"
INDEX { unit4SensorIndex }
::= { cmcTcUnit4SensorTable 1 }
CmcTcUnit4SensorEntry ::=
SEQUENCE {
unit4SensorIndex
INTEGER,
unit4SensorType
INTEGER,
unit4SensorText
DisplayString,
unit4SensorStatus
INTEGER,
unit4SensorValue
INTEGER,
unit4SensorSetHigh
INTEGER,
unit4SensorSetLow
INTEGER,
unit4SensorSetWarn
INTEGER
}
unit4SensorIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of value entries. Its value ranges
between 1 and the value of cmcTcUnit4NumberOfSensors."
::= { cmcTcUnit4SensorEntry 1 }
unit4SensorType OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
failure (2),
overflow (3),
access (4),
vibration (5),
motion (6),
smoke (7),
airFlow (8),
type6 (9),
temperature(10),
current4to20(11),
humidity(12),
userNO (13),
userNC (14),
lock (15),
unlock (16),
voltOK (17),
voltage (18),
fanOK (19),
readerKeypad (20),
dutyPWM (21),
fanStatus (22),
leakage (23),
warningRTT (24),
alarmRTT (25),
filterRTT (26),
heatflowRCT (27),
alarmRCT (28),
warningRCT (29),
currentPSM (30),
statusPSM (31),
positionPSM (32),
airFlap (33),
acoustic (34),
detACfault (35),
detACfirstAlarm (36),
detACmainAlarm (37),
rpm11LCP (40),
rpm12LCP (41),
rpm21LCP (42),
rpm22LCP (43),
rpm31LCP (44),
rpm32LCP (45),
rpm41LCP (46),
rpm42LCP (47),
airTemp11LCP (48),
airTemp12LCP (49),
airTemp21LCP (50),
airTemp22LCP (51),
airTemp31LCP (52),
airTemp32LCP (53),
airTemp41LCP (54),
airTemp42LCP (55),
temp1LCP (56),
temp2LCP (57),
waterInTemp (58),
waterOutTemp (59),
waterFlow (60),
fanSpeed (61),
valve (62),
statusLCP (63),
waterDelta (64),
valveActual (65),
contrTemp2 (66),
condensateDuration (67),
condensateCycles (68),
totalKWhPSM (72),
totalKWPSM (73),
frequencyPSM (74),
voltagePSM (75),
voltStatusPSM (76),
amperePSM (77),
ampStatusPSM (78),
kWPSM (79),
kWhPSM (80),
kWhTempPSM (81),
temperatureWL (100),
temperature1WL (101),
humidityWL (102),
accessWL (103),
userNOWL (104),
userNCWL (105),
analogWL (106)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of sensor which is connected to sensor unit 4 to sensor[unit4SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type 2, vibration sensor
6: sensor type 3, motion sensor
7: sensor type 4, smoke sensor
8: sensor type 5, air flow sensor
9: sensor type 6, reserved
10: sensor type 7, temperature sensor
11: sensor type 8, 4..20mA sensor
12: sensor type 9, humidity sensor
13: user sensor with normally opened contact
14: user sensor with normally closed contact
15: door locked sensor from locking device
16: remote unlock sensor (e.g. external keypad)
17: voltage sensor, indicates status of main voltage
18: voltage value
19: fan status
20: cardreader or keypad, connected to I2C port
21: duty cycle of fan, FCS-Unit
22: status of fan, FCS-Unit
23: leakage sensor
24: warning, RittalTopTherm(RTT)-Unit
25: alarm, RittalTopTherm-Unit
26: temperature difference filter monitor, RTT-Unit
27: heatflow RCT-Unit
28: alarm RCT-Unit
29: warning RCT-Unit
30: actual current*10, PSM-Unit
31: status PSM-Unit
32: position PSM-Unit, normal/reversed = circuit 1/2
33: air Flap
34: acoustic sensor
35: DET-AC fault (extinguisher)
36: DET-AC first alarm (extinguisher)
37: DET-AC main alarm (extinguisher)
40-47: RPM Fan 1.1 - Fan 4.2, LCP
48-55: Air temperature 1.1 - 4.2, LCP
56,57: actual temperature 1,2, LCP
58: water inlet temperature, LCP
59: water outlet temperature, LCP
60: water flow
61: fan speed (desired value)
62: status valve, LCP
63: status LCP
64: temperature difference water temperatures
65: control temperature 1, LCP
66: control temperature 2, LCP
67: condensate pump, duration, LCP
68: condensate pump, cycles, LCP
72: total energy*10 (kWh), PSM
73: total power*10 (kW), PSM
74: frequency*10 (Hz), PSM
75: voltage*10 (V), PSM
76: voltage status, PSM
77: current*10 (A), PSM
78: current status, PSM
79: power*10 (kW) per phase, PSM
80: energy*10 (kWh) per phase, PSM
81: temporary energy*10 (kWh) per phase, PSM
100: temperature sensor, wireless
101: temperature sensor (combi), wireless
102: humidity sensor, wireless
103: access sensor, wireless
104: user sensor with normally opened contact, wireless
105: user sensor with normally closed contact, wireless
106: analog sensor 4..20mA, wireless"
::= { cmcTcUnit4SensorEntry 2 }
unit4SensorText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each sensor (entry in the table)"
::= { cmcTcUnit4SensorEntry 3 }
unit4SensorStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
lost(2),
changed(3),
ok(4),
off(5),
on(6),
warning(7),
tooLow(8),
tooHigh(9)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual status of the sensor"
::= { cmcTcUnit4SensorEntry 4 }
unit4SensorValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Value of sensor"
::= { cmcTcUnit4SensorEntry 5 }
unit4SensorSetHigh OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for high setpoint of sensor"
::= { cmcTcUnit4SensorEntry 6 }
unit4SensorSetLow OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for low setpoint of sensor"
::= { cmcTcUnit4SensorEntry 7 }
unit4SensorSetWarn OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for warning setpoint of sensor,
also used as fan threshold"
::= { cmcTcUnit4SensorEntry 8 }
-- table END
-- Outputs
cmcTcUnit4NumberOfOutputs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of outputs available on sensor unit 4"
::= { cmcTcStatusUnit4Outputs 1 }
-- table with entry for each output available on this unit
cmcTcUnit4OutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcUnit4OutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of output table"
::= { cmcTcStatusUnit4Outputs 2 }
cmcTcUnit4OutputEntry OBJECT-TYPE
SYNTAX CmcTcUnit4OutputEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of output table"
INDEX { unit4OutputIndex }
::= { cmcTcUnit4OutputTable 1 }
CmcTcUnit4OutputEntry ::=
SEQUENCE {
unit4OutputIndex
INTEGER,
unit4OutputType
INTEGER,
unit4OutputText
DisplayString,
unit4OutputStatus
INTEGER,
unit4OutputValue
INTEGER,
unit4OutputSet
INTEGER,
unit4OutputConfig
INTEGER,
unit4OutputDelay
INTEGER,
unit4OutputTimeoutAction
INTEGER
}
unit4OutputIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of output entries. Its value ranges
between 1 and the value of cmcTcUnit4NumberOfOutputs."
::= { cmcTcUnit4OutputEntry 1 }
unit4OutputType OBJECT-TYPE
SYNTAX INTEGER {
notAvail (1),
failure (2),
overflow (3),
doorLock (4),
univLock1 (5),
univLock2 (6),
fan (7),
fanSpeedContr (8),
universalOut (9),
roomLock(10),
powerOut(11),
doorLockMaster(12),
doorLockFRi (13),
setpoint (14),
setpointTimax (15),
hysteresisRCT (16),
commandRCT (17),
relayPSM (18),
setHighPSM (19),
setLowPSM (20),
setpointRTT (21),
setTimaxRTT (22),
powerOut1(23),
controlModeLCP (30),
minFanSpeedLCP (31),
minDeltaTLCP (32),
maxDeltaTLCP (33),
kPLCP (34),
kILCP (35),
kDLCP (36),
flowRateLCP(37),
cwValueLCP (38),
deltaTLCP (39),
ctrModLCP (40),
voltHighPSM (42),
voltLowPSM (43),
ampHighPSM (44),
ampLowPSM (45),
commandPSM (46)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Type of output which is connected to sensor unit 4 to output[unit4OutputIndex]
1: no output connected
2: output failure
3: value overflow
4: output type 1, door locking TS8,Ergoform
5: output type 2, universal lock 1, lock with power
6: output type 3, universal lock 2, unlock with power
7: output type 4, fan relay
8: output type 5, fan controlled
9: output type 6, universal relay output
10: output type 7, room door lock
11: output type 8, power output
12: output type 9, door lock with Master key
13: output type 10, door lock FR(i)
14: setpoint (FCS, RTT)
15: setpoint temperature monitoring (RTT)
16: hysteresis of setpoint (RCT)
17: command for remote control of RCT
18: relay PSM, 1=On, 0=Off
19: high setpoint current monitoring PSM
20: low setpoint current monitoring PSM
21: setpoint temperature RTT
22: setpoint temperature monitoring RTT
23: power output 20A
30: control mode LCP
31: min fan speed (fan control) LCP
32: min delta T (fan control) LCP
33: max delta T (fan control) LCP
34: PID controller, KP, LCP
35: PID controller, KI, LCP
36 PID controller, KD, LCP
37 flowrate flowmeter, LCP
38: cw value of water (default: 4187) LCP
39: deltaT, LCP
40: control mode, LCP
42: setpoint high voltage PSM
43: setpoint low voltage PSM
44: setpoint high current PSM
45: setpoint low current PSM
46: command PSM"
::= { cmcTcUnit4OutputEntry 2 }
unit4OutputText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each output (entry in the table)"
::= { cmcTcUnit4OutputEntry 3 }
unit4OutputStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
lost(2),
changed(3),
ok(4),
off(5),
on(6),
setOff(7),
setOn(8)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Actual status of the output"
::= { cmcTcUnit4OutputEntry 4 }
unit4OutputValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for output"
::= { cmcTcUnit4OutputEntry 5 }
unit4OutputSet OBJECT-TYPE
SYNTAX INTEGER {
off (1),
on (2),
lock (3),
unlock (4),
unlockDelay (5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Command for output"
::= { cmcTcUnit4OutputEntry 6 }
unit4OutputConfig OBJECT-TYPE
SYNTAX INTEGER {
disRemote (1),
enRemote (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Configuration for output
1: disable remote control (e.g. keypad)
2: enable remote control "
::= { cmcTcUnit4OutputEntry 7 }
unit4OutputDelay OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unsigned Value for delay,
after this time the output will fall into the previous state"
::= { cmcTcUnit4OutputEntry 8 }
unit4OutputTimeoutAction OBJECT-TYPE
SYNTAX INTEGER {
stay (1),
off (2),
on (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"State for output if timeout (RS422) occurs"
::= { cmcTcUnit4OutputEntry 9 }
-- Msgs
cmcTcUnit4NumberOfMsgs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of alarms that can be created with sensor unit 4"
::= { cmcTcStatusUnit4Msg 1 }
-- table with entry for each alarm available on this unit
cmcTcUnit4MsgTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcUnit4MsgEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of message table"
::= { cmcTcStatusUnit4Msg 2 }
cmcTcUnit4MsgEntry OBJECT-TYPE
SYNTAX CmcTcUnit4MsgEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of message table"
INDEX { unit4MsgIndex }
::= { cmcTcUnit4MsgTable 1 }
CmcTcUnit4MsgEntry ::=
SEQUENCE {
unit4MsgIndex
INTEGER,
unit4MsgText
DisplayString,
unit4MsgStatus
INTEGER,
unit4MsgRelay
INTEGER,
unit4MsgBeeper
INTEGER,
unit4MsgTrap1
INTEGER,
unit4MsgTrap2
INTEGER,
unit4MsgTrap3
INTEGER,
unit4MsgTrap4
INTEGER,
unit4MsgQuit
INTEGER
}
unit4MsgIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of alarm entries. Its value ranges
between 1 and the value of cmcTcUnit4NumberOfMsgs."
::= { cmcTcUnit4MsgEntry 1 }
unit4MsgText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each message (entry in the table)"
::= { cmcTcUnit4MsgEntry 2 }
unit4MsgStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
configChanged(2),
error(3),
ok(4),
alarm(5),
warning(6),
tooLow(7),
tooHigh(8),
setOff(9),
setOn(10),
open(11),
closed(12),
locked(13),
unlRemote(14),
unlReaderKeypad(15),
unlSNMP(16),
unlWEB(17),
unlTimer(18),
noAccess(19),
circuit1 (20),
circuit2 (21),
lowBatt (22)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog value too low, value reached low threshold
8: analog value too high, value reached high threshold
9: output is set to OFF
10: output is set to ON
11: door is open
12: door is closed
13: door is locked
14: door is unlocked by remote input, e.g. external cardreader
15: door is unlocked by reader or keypad connected to I2C
16: door is unlocked by SNMP set command (unit1OutputSet)
17: door is unlocked by WEB
18: door is unlocked by timer
19: no access, wrong keycode or cardnumber
20: orientation of PSM-Unit is circuit 1
21: orientation of PSM-Unit is circuit 2
22: battery low, wireless sensor"
::= { cmcTcUnit4MsgEntry 3 }
unit4MsgRelay OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup of Alarm relay for this alarm
1: no switching of alarm relay
2: switching of alarm relay"
::= { cmcTcUnit4MsgEntry 4 }
unit4MsgBeeper OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup of Alarm beeper for this alarm
1: no audible alarm
2: audible alarm"
::= { cmcTcUnit4MsgEntry 5 }
unit4MsgTrap1 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 1 activated"
::= { cmcTcUnit4MsgEntry 6 }
unit4MsgTrap2 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 2 activated"
::= { cmcTcUnit4MsgEntry 7 }
unit4MsgTrap3 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 3 activated"
::= { cmcTcUnit4MsgEntry 8 }
unit4MsgTrap4 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 4 and Event Logging activated"
::= { cmcTcUnit4MsgEntry 9 }
unit4MsgQuit OBJECT-TYPE
SYNTAX INTEGER {
auto (1),
manual (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reset of this alarm
1: auto
2: manual, alarm needs confirmation, e. g. with 'C' key"
::= { cmcTcUnit4MsgEntry 10 }
-- table END
--Status extension unit
cmcTcValuesRelay OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup of Alarm relay for alarm ext. unit(s)
1: no switching of alarm relay
2: switching of alarm relay"
::= { cmcTcStatusExtUnit 1 }
cmcTcValuesBeeper OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup of Alarm beeper for alarm ext. unit(s)
1: no audible alarm
2: audible alarm"
::= { cmcTcStatusExtUnit 2 }
cmcTcValuesTrap1 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 1 activated"
::= { cmcTcStatusExtUnit 3 }
cmcTcValuesTrap2 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 2 activated"
::= { cmcTcStatusExtUnit 4 }
cmcTcValuesTrap3 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 3 activated"
::= { cmcTcStatusExtUnit 5 }
cmcTcValuesTrap4 OBJECT-TYPE
SYNTAX INTEGER {
disable (1),
enable (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Trap receiver 4 and Event Logging activated"
::= { cmcTcStatusExtUnit 6 }
cmcTcNumberOfValues OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of values availabel on extension units connected to the CMC"
::= { cmcTcStatusExtUnit 7 }
-- table with entry for each value available on extension units
cmcTcValuesTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcValuesEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of values-table"
::= { cmcTcStatusExtUnit 8 }
cmcTcValuesEntry OBJECT-TYPE
SYNTAX CmcTcValuesEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of values-table"
INDEX { valuesIndex }
::= { cmcTcValuesTable 1 }
CmcTcValuesEntry ::=
SEQUENCE {
valuesIndex
INTEGER,
valuesText
DisplayString,
valuesStatus
INTEGER,
valuesValue
INTEGER,
valuesSetHigh
INTEGER,
valuesSetLow
INTEGER
}
valuesIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of value entries. Its value ranges
between 1 and the value of cmcTcNumberOfValues."
::= { cmcTcValuesEntry 1 }
valuesText OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..20))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Descriptional text for each value (entry in the table)
of the extension card"
::= { cmcTcValuesEntry 2 }
valuesStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
lost(2),
changed(3),
ok(4),
tooLow(5),
tooHigh(6),
error(7)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual status of the value of the extension card"
::= { cmcTcValuesEntry 3 }
valuesValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Value of sensor"
::= { cmcTcValuesEntry 4 }
valuesSetHigh OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for high setpoint of sensor"
::= { cmcTcValuesEntry 5 }
valuesSetLow OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Value for low setpoint of sensor"
::= { cmcTcValuesEntry 6 }
-- table END
--setupGeneral-group
cmcTcSetTempUnit OBJECT-TYPE
SYNTAX INTEGER {
celsius(1),
fahrenheit(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Unit of all temperature values and setpoints, Celsius or Fahrenheit"
::= { cmcTcSetupGeneral 1 }
cmcTcSetBeeper OBJECT-TYPE
SYNTAX INTEGER {
off(1),
on(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Audible alarm in CMC-TC unit:
(2): beeper is on
(1): beeper is off (general)"
::= { cmcTcSetupGeneral 2 }
cmcTcQuitRelay OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable acknowledging currently active alarm relay
(with 'C' on CMC-TC)."
::= { cmcTcSetupGeneral 3 }
cmcTcLogicRelay OBJECT-TYPE
SYNTAX INTEGER {
closeAtAlarm(1),
openAtAlarm(2),
off(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Logic of alarm relay:
(1) Relay will pick up in case of an alarm
(2) Relay will release in case of an alarm
(3) Relay off (general)"
::= { cmcTcSetupGeneral 4 }
cmcTcWebAccess OBJECT-TYPE
SYNTAX INTEGER {
viewOnly(1),
fullAccess(2),
off(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Web access via HTTP:
(1) view only
(2) full Access, read and set
(3) Web disabled (general)"
::= { cmcTcSetupGeneral 5 }
-- SetupClock
cmcTcSetupDate OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..10))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"actual Date in format DD.MM.YYYY"
::= { cmcTcSetupGeneral 6 }
cmcTcSetupTime OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)"
::= { cmcTcSetupGeneral 7 }
-- table for timer function
cmcTcTimerNumber OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of value-table entries=number of outlets available on this unit"
::= { cmcTcTimerTable1 1 }
cmcTcTimerTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcTimerEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Headline of status-table"
::= { cmcTcTimerTable1 2 }
cmcTcTimerEntry OBJECT-TYPE
SYNTAX CmcTcTimerEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of timer-table"
INDEX { cmcTcTimerIndex }
::= { cmcTcTimerTable 1 }
CmcTcTimerEntry ::=
SEQUENCE {
cmcTcTimerIndex
INTEGER,
cmcTcTimerStatus
INTEGER,
cmcTcTimerDayOfWeek
INTEGER,
cmcTcTimeOn
DisplayString,
cmcTcTimeOff
DisplayString,
cmcTcTimeControl
INTEGER,
cmcTcTimerFunction
INTEGER
}
cmcTcTimerIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the list of timer entries. Its value ranges
between 1 and the value of cmcTcTimerNumber."
::= { cmcTcTimerEntry 1 }
cmcTcTimerStatus OBJECT-TYPE
SYNTAX INTEGER {
switchedOff(1),
switchedOn(2),
noTime(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual status of the timer"
::= { cmcTcTimerEntry 2 }
cmcTcTimerDayOfWeek OBJECT-TYPE
SYNTAX INTEGER {
sun(1),
mon(2),
tue(3) ,
wed(4),
thu(5),
fri(6),
sat(7),
sat-sun(8),
mon-fri(9),
mon-sun(10)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Selection of day of week for timer to switch"
::= { cmcTcTimerEntry 3 }
cmcTcTimeOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..5))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Time to switch on current function,
Format: HH:MM"
::= { cmcTcTimerEntry 4 }
cmcTcTimeOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..5))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Time to switch off current function,
Format: HH:MM"
::= { cmcTcTimerEntry 5 }
cmcTcTimeControl OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Control via RTC"
::= { cmcTcTimerEntry 6 }
cmcTcTimerFunction OBJECT-TYPE
SYNTAX INTEGER {
disKeypad1-1 (1),
disKeypad2-1 (2),
disKeypad1-2 (3),
disKeypad2-2 (4),
disKeypad1-3 (5),
disKeypad2-3 (6),
disKeypad1-4 (7),
disKeypad2-4 (8),
unlDoor1-1 (9),
unlDoor2-1 (10),
unlDoor1-2 (11),
unlDoor2-2 (12),
unlDoor1-3 (13),
unlDoor2-3 (14),
unlDoor1-4 (15),
unlDoor2-5 (16),
disTrapRec1 (17),
disTrapRec2 (18),
disTrapRec3 (19),
disTrapRec4 (20),
disSMS (21),
schedule1 (22),
schedule2 (23),
schedule3 (24),
schedule4 (25),
disSMS1 (26),
disSMS2 (27),
disSMS3 (28),
disSMS4 (29)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Function which is controlled via timer
1: unlock via keypad 1 on unit 1 or remote input lock 1 is disabled
2: unlock via keypad 2 on unit 1 or remote input lock 2 is disabled
3 unlock via keypad 1 on unit 2 or remote input lock 1 is disabled
4: unlock via keypad 2 on unit 2 or remote input lock 2 is disabled
5: unlock via keypad 1 on unit 3 or remote input lock 1 is disabled
6: unlock via keypad 2 on unit 3 or remote input lock 2 is disabled
7: unlock via keypad 1 on unit 4 or remote input lock 1 is disabled
8: unlock via keypad 2 on unit 4 or remote input lock 2 is disabled
9: Lock of door 1 on unit 1 will be unlocked
10: Lock of door 2 on unit 1 will be unlocked
11: Lock of door 1 on unit 2 will be unlocked
12: Lock of door 2 on unit 2 will be unlocked
13: Lock of door 1 on unit 3 will be unlocked
14: Lock of door 2 on unit 3 will be unlocked
15: Lock of door 1 on unit 4 will be unlocked
16: Lock of door 2 on unit 4 will be unlocked
17-20: sending Traps to this Trap receiver will be disabled
21: sending SMS will be disabled generally
22-25: Scheduled alarm off
26-29: sending SMS to phone number 1..4 will be disabled"
::= { cmcTcTimerEntry 7 }
--cmcTcTrapTable-group
cmcTcTraptableNumber OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of trapTable entries. The number of trap-receiver"
::= { cmcTcTraps 1 }
cmcTcTrapTableTable OBJECT-TYPE
SYNTAX SEQUENCE OF CmcTcTrapTableEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of trap-receiver entries"
::= { cmcTcTraps 2 }
cmcTcTrapTableEntry OBJECT-TYPE
SYNTAX CmcTcTrapTableEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Entries of trapTable"
INDEX { trapIndex }
::= { cmcTcTrapTableTable 1 }
CmcTcTrapTableEntry ::=
SEQUENCE {
trapIndex
INTEGER,
trapStatus
INTEGER,
trapIPaddress
DisplayString
}
trapIndex OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Index for the trap-receiver-table. Its value ranges between
1 and the value of traptableNumber "
::= { cmcTcTrapTableEntry 1 }
trapStatus OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable trap receiver"
::= { cmcTcTrapTableEntry 2 }
trapIPaddress OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP-address of trap-receiver"
::= { cmcTcTrapTableEntry 3 }
--cmcTcControl-group (Added in Version 1.1)
cmcTcQuitUnit OBJECT-TYPE
SYNTAX INTEGER {
noQuit(1),
quit(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Command to quit (acknowledge) alarms of CMC-TC unit.
Setting to 'quit' (2) will have same result as pressing 'C' on Units.
Variable is automatically set back to 'noQuit' (1)."
::= { cmcTcControl 1 }
--Traps
alarmSensorUnit1 TRAP-TYPE
ENTERPRISE cmcTc
VARIABLES { sysContact, sysName, sysLocation,
unit1MsgIndex, unit1MsgText, unit1MsgStatus, unit1SensorValue }
DESCRIPTION
"Alarm of sensor unit 1"
--
--#TYPE "Sensor unit alarm"
--#SUMMARY "Location: %s, Alarm[%s]: %s, Status: %s, from: %s, contact %s"
--#ARGUMENTS {3,4,6,5,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 6
--#STATE OPERATIONAL
--
::= 1
alarmSensorUnit2 TRAP-TYPE
ENTERPRISE cmcTc
VARIABLES { sysContact, sysName, sysLocation,
unit2MsgIndex, unit2MsgText, unit2MsgStatus, unit2SensorValue }
DESCRIPTION
"Alarm of sensor unit 2"
--
--#TYPE "Sensor unit alarm"
--#SUMMARY "Location: %s, Message: %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 6
--#STATE OPERATIONAL
--
::= 2
alarmSensorUnit3 TRAP-TYPE
ENTERPRISE cmcTc
VARIABLES { sysContact, sysName, sysLocation,
unit3MsgIndex, unit3MsgText, unit3MsgStatus, unit3SensorValue }
DESCRIPTION
"Alarm of sensor unit 3"
--
--#TYPE "Sensor unit alarm"
--#SUMMARY "Location: %s, Message: %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 6
--#STATE OPERATIONAL
--
::= 3
alarmSensorUnit4 TRAP-TYPE
ENTERPRISE cmcTc
VARIABLES { sysContact, sysName, sysLocation,
unit4MsgIndex, unit4MsgText, unit4MsgStatus, unit4SensorValue }
DESCRIPTION
"Alarm of sensor unit 4"
--
--#TYPE "Sensor unit alarm"
--#SUMMARY "Location: %s, Message: %s from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 6
--#STATE OPERATIONAL
--
::= 4
alarmUnit1 TRAP-TYPE
ENTERPRISE cmcTc
VARIABLES { sysContact, sysName, sysLocation,
cmcTcUnit1Text, cmcTcUnit1Status }
DESCRIPTION
"Alarm of unit 1"
--
--#TYPE "Unit alarm"
--#SUMMARY "Location: %s, Status: %s, from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 6
--#STATE OPERATIONAL
--
::= 5
alarmUnit2 TRAP-TYPE
ENTERPRISE cmcTc
VARIABLES { sysContact, sysName, sysLocation,
cmcTcUnit2Text, cmcTcUnit2Status }
DESCRIPTION
"Alarm of unit 2"
--
--#TYPE "Unit alarm"
--#SUMMARY "Location: %s, Status: %s, from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 6
--#STATE OPERATIONAL
--
::= 6
alarmUnit3 TRAP-TYPE
ENTERPRISE cmcTc
VARIABLES { sysContact, sysName, sysLocation,
cmcTcUnit3Text, cmcTcUnit3Status }
DESCRIPTION
"Alarm of unit 3"
--
--#TYPE "Unit alarm"
--#SUMMARY "Location: %s, Status: %s, from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 6
--#STATE OPERATIONAL
--
::= 7
alarmUnit4 TRAP-TYPE
ENTERPRISE cmcTc
VARIABLES { sysContact, sysName, sysLocation,
cmcTcUnit4Text, cmcTcUnit4Status }
DESCRIPTION
"Alarm of unit 4"
--
--#TYPE "Unit alarm"
--#SUMMARY "Location: %s, Status: %s, from: %s, contact %s"
--#ARGUMENTS {3,4,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 6
--#STATE OPERATIONAL
--
::= 8
alarmValues TRAP-TYPE
ENTERPRISE cmcTc
VARIABLES { sysContact, sysName, sysLocation,
valuesIndex, valuesText, valuesStatus }
DESCRIPTION
"Alarm of values measured by external card"
--
--#TYPE "Values alarm"
--#SUMMARY "Location: %s, Message: %s, Status: %s from: %s, contact %s"
--#ARGUMENTS {3,5,6,2,1}
--#SEVERITY MAJOR
--#TIMEINDEX 6
--#STATE OPERATIONAL
--
::= 9
configChanged TRAP-TYPE
ENTERPRISE cmcTc
VARIABLES { sysDescr, sysContact, sysName, sysLocation }
DESCRIPTION
"The configuration of the cmc has changed,
this trap is send if new setup is saved.
Configuration can be changed by Terminal, Telnet, Web or SNMP
*** NOT IMPLEMENTED *** "
--
--#TYPE "Configuration is changed"
--#SUMMARY "Location: %s, Configuration of %s, unit %s has changed, contact %s"
--#ARGUMENTS {3,2,0,1}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 6
--#STATE OPERATIONAL
--
::= 10
END