mibs/MIBS/vertiv/VERTIV-V5-MIB

6472 lines
146 KiB
Plaintext
Raw Permalink Normal View History

2023-12-05 12:25:34 +01:00
VERTIV-V5-MIB DEFINITIONS ::= BEGIN
IMPORTS
DisplayString, TruthValue, MacAddress FROM SNMPv2-TC
SnmpAdminString FROM SNMP-FRAMEWORK-MIB
MODULE-IDENTITY, OBJECT-TYPE, enterprises, Integer32,
Gauge32, NOTIFICATION-TYPE, OBJECT-IDENTITY FROM SNMPv2-SMI
sysName FROM SNMPv2-MIB;
vertiv MODULE-IDENTITY
LAST-UPDATED "202001070000Z"
ORGANIZATION "Vertiv"
CONTACT-INFO "support@geistglobal.com"
DESCRIPTION
"The MIB for Vertiv products"
REVISION "202001070000Z"
DESCRIPTION
"Updates for VRC spec change"
REVISION "201909300000Z"
DESCRIPTION
"Added hostname, alarm/warning count, and manufacturer to deviceInfo"
REVISION "201909120000Z"
DESCRIPTION
"Added SN-2D door switch sensor"
REVISION "201908300000Z"
DESCRIPTION
"Removed current min, max, and peak fields from pdu phase, line,
breaker, and outlet tables
Removed voltage min, max, and peak fields from pdu phase, line,
breaker, and outlet tables
Removed minmax reset value from pduOutletMeterReset
Added balance field to pdu phase table"
REVISION "201906060000Z"
DESCRIPTION
"Updated pduOutletSwitchControl description"
REVISION "201905070000Z"
DESCRIPTION
"Changed productMacAddress type to MacAddress"
REVISION "201904300000Z"
DESCRIPTION
"Added remote humidity-only sensor"
REVISION "201903070000Z"
DESCRIPTION
"Added VRC support"
REVISION "201801190000Z"
DESCRIPTION
"Modified pduOutletSwitchTable to support outlet actions with delays"
REVISION "201709190000Z"
DESCRIPTION
"Changed SYNTAX of objects, with a UTF-8 encoded string value, to
SnmpAdminString"
REVISION "201708100000Z"
DESCRIPTION
"Added pduBreakerCurrentPeak, pduLineCurrentPeak,
pduOutletMeterCurrentPeak, pduPhaseVoltagePeak, and
pduPhaseCurrentPeak
Updated object descriptions, indicating which fields are not supported
on all platforms"
REVISION "201705100000Z"
DESCRIPTION
"Added trapObj group with trap payload objects
Added additional payload objects to trap definitions"
REVISION "201704050000Z"
DESCRIPTION
"Added productPlatform to deviceInfo group
Added product identity entries"
REVISION "201606300000Z"
DESCRIPTION
"Raven version"
REVISION "201209110000Z"
DESCRIPTION
"Original version"
::= { enterprises 21239 }
v5 OBJECT IDENTIFIER ::= { vertiv 5 }
imd OBJECT IDENTIFIER ::= { v5 2 }
--###########################################################################################--
--deviceInfo--
--###########################################################################################--
deviceInfo OBJECT IDENTIFIER ::= { imd 1 }
productTitle OBJECT-TYPE
SYNTAX SnmpAdminString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Product name"
::= { deviceInfo 1 }
productVersion OBJECT-TYPE
SYNTAX SnmpAdminString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Product version"
::= { deviceInfo 2 }
productFriendlyName OBJECT-TYPE
SYNTAX SnmpAdminString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"User-assigned name"
::= { deviceInfo 3 }
productMacAddress OBJECT-TYPE
SYNTAX MacAddress
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Product's unique MAC address"
::= { deviceInfo 4 }
deviceCount OBJECT-TYPE
SYNTAX Integer32(0..16)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total number of devices on unit"
::= { deviceInfo 6 }
temperatureUnits OBJECT-TYPE
SYNTAX INTEGER {
fahrenheit(0),
celsius(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Current units for temperature/dewpoint values:
0 = Degrees Fahrenheit
1 = Degrees Celsius"
::= { deviceInfo 7 }
productModelNumber OBJECT-TYPE
SYNTAX SnmpAdminString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Product model number (factory-assigned)"
::= { deviceInfo 8 }
productPartNumber OBJECT-TYPE
SYNTAX SnmpAdminString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Product part number (factory-assigned)"
::= { deviceInfo 9 }
productSerialNumber OBJECT-TYPE
SYNTAX SnmpAdminString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Product serial number (factory-assigned)"
::= { deviceInfo 10 }
productPlatform OBJECT-TYPE
SYNTAX SnmpAdminString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Product platform"
::= { deviceInfo 11 }
productHostname OBJECT-TYPE
SYNTAX SnmpAdminString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Product hostname"
::= { deviceInfo 12 }
productAlarmCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of alarms currently tripped"
::= { deviceInfo 13 }
productWarnCount OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Number of warnings currently tripped"
::= { deviceInfo 14 }
productManufacturer OBJECT-TYPE
SYNTAX SnmpAdminString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Product manufacturer"
::= { deviceInfo 15 }
--###########################################################################################--
--pdu--
--###########################################################################################--
pdu OBJECT IDENTIFIER ::= { imd 3 }
--###########################################################################################--
--pduMainTable--
--###########################################################################################--
pduMainTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduMainEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"PDU general information"
::= { pdu 1 }
pduMainEntry OBJECT-TYPE
SYNTAX PduMainEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the pduMainTable table: each entry contains an index
and other sensor details"
INDEX { pduMainIndex }
::= { pduMainTable 1 }
PduMainEntry ::= SEQUENCE {
pduMainIndex Integer32,
pduMainSerial DisplayString,
pduMainName SnmpAdminString,
pduMainLabel SnmpAdminString,
pduMainAvail Gauge32,
pduMeterType INTEGER,
pduTotalName SnmpAdminString,
pduTotalLabel SnmpAdminString,
pduTotalRealPower Gauge32,
pduTotalApparentPower Gauge32,
pduTotalPowerFactor Gauge32,
pduTotalEnergy Gauge32
}
pduMainIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table entry index value"
::= { pduMainEntry 1 }
pduMainSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number"
::= { pduMainEntry 2 }
pduMainName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU name (factory-assigned)"
::= { pduMainEntry 3 }
pduMainLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"PDU label (user-defined)"
::= { pduMainEntry 4 }
pduMainAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable"
::= { pduMainEntry 5 }
pduMeterType OBJECT-TYPE
SYNTAX INTEGER {
wye(0),
delta(1)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current meter type:
0 = Wye
1 = Delta"
::= { pduMainEntry 6 }
pduTotalName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total name (factory-assigned)"
::= { pduMainEntry 7 }
pduTotalLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Total label (user-defined)"
::= { pduMainEntry 8 }
pduTotalRealPower OBJECT-TYPE
SYNTAX Gauge32(0..9999)
UNITS "watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU total real power"
::= { pduMainEntry 9 }
pduTotalApparentPower OBJECT-TYPE
SYNTAX Gauge32(0..9999)
UNITS "volt-amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU total apparent power"
::= { pduMainEntry 10 }
pduTotalPowerFactor OBJECT-TYPE
SYNTAX Gauge32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU total power factor"
::= { pduMainEntry 11 }
pduTotalEnergy OBJECT-TYPE
SYNTAX Gauge32(0..9999000)
UNITS "watt-hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU total accumulated energy in watt-hours"
::= { pduMainEntry 12 }
--###########################################################################################--
--pduPhaseTable--
--###########################################################################################--
pduPhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"PDU phases information"
::= { pdu 2 }
pduPhaseEntry OBJECT-TYPE
SYNTAX PduPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the pduPhaseTable table: each entry contains an index
and other sensor details"
INDEX { pduPhaseIndex }
::= { pduPhaseTable 1 }
PduPhaseEntry ::= SEQUENCE {
pduPhaseIndex Integer32,
pduPhaseName SnmpAdminString,
pduPhaseLabel SnmpAdminString,
pduPhaseVoltage Gauge32,
pduPhaseCurrent Gauge32,
pduPhaseRealPower Gauge32,
pduPhaseApparentPower Gauge32,
pduPhasePowerFactor Gauge32,
pduPhaseEnergy Gauge32,
pduPhaseBalance Gauge32,
pduPhaseCurrentCrestFactor Gauge32
}
pduPhaseIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table entry index value"
::= { pduPhaseEntry 1 }
pduPhaseName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU phase name (factory-assigned)"
::= { pduPhaseEntry 2 }
pduPhaseLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"PDU phase label (user-defined)"
::= { pduPhaseEntry 3 }
pduPhaseVoltage OBJECT-TYPE
SYNTAX Gauge32(0..3100)
UNITS "decivolts (rms)"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU phase voltage in tenths of a volt"
::= { pduPhaseEntry 4 }
pduPhaseCurrent OBJECT-TYPE
SYNTAX Gauge32(0..9900)
UNITS "centiamps (rms)"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU phase current reading in hundredths of an amp"
::= { pduPhaseEntry 8 }
pduPhaseRealPower OBJECT-TYPE
SYNTAX Gauge32(0..9999)
UNITS "watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Real power for phase in watts"
::= { pduPhaseEntry 12 }
pduPhaseApparentPower OBJECT-TYPE
SYNTAX Gauge32(0..9999)
UNITS "volt-amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Apparent power for phase in volt-amps"
::= { pduPhaseEntry 13 }
pduPhasePowerFactor OBJECT-TYPE
SYNTAX Gauge32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power factor for phase"
::= { pduPhaseEntry 14 }
pduPhaseEnergy OBJECT-TYPE
SYNTAX Gauge32(0..9999000)
UNITS "watt-hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated energy for phase in watt-hours"
::= { pduPhaseEntry 15 }
pduPhaseBalance OBJECT-TYPE
SYNTAX Gauge32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase balance as percent"
::= { pduPhaseEntry 17 }
pduPhaseCurrentCrestFactor OBJECT-TYPE
SYNTAX Gauge32(0..9999)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current crest factor for phase, in hundredths"
::= { pduPhaseEntry 19 }
--###########################################################################################--
--pduBreakerTable--
--###########################################################################################--
pduBreakerTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduBreakerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"PDU breaker information"
::= { pdu 3 }
pduBreakerEntry OBJECT-TYPE
SYNTAX PduBreakerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the pduBreakerTable table: each entry contains an index
and other sensor details"
INDEX { pduBreakerIndex }
::= { pduBreakerTable 1 }
PduBreakerEntry ::= SEQUENCE {
pduBreakerIndex Integer32,
pduBreakerName SnmpAdminString,
pduBreakerLabel SnmpAdminString,
pduBreakerCurrent Gauge32,
pduBreakerVoltage Gauge32,
pduBreakerRealPower Gauge32,
pduBreakerApparentPower Gauge32,
pduBreakerPowerFactor Gauge32,
pduBreakerEnergy Gauge32
}
pduBreakerIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table entry index value"
::= { pduBreakerEntry 1 }
pduBreakerName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU breaker name (factory-assigned)"
::= { pduBreakerEntry 2 }
pduBreakerLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"PDU breaker label (user-defined)"
::= { pduBreakerEntry 3 }
pduBreakerCurrent OBJECT-TYPE
SYNTAX Gauge32(0..9900)
UNITS "centiamps (rms)"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU breaker current reading in hundredths of an amp"
::= { pduBreakerEntry 4 }
pduBreakerVoltage OBJECT-TYPE
SYNTAX Gauge32(0..3100)
UNITS "decivolts (rms)"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU breaker voltage in tenths of a volt. This object may not exist on
all platforms, due to hardware differences."
::= { pduBreakerEntry 8 }
pduBreakerRealPower OBJECT-TYPE
SYNTAX Gauge32(0..9999)
UNITS "watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Real power for breaker in watts. This object may not exist on all
platforms, due to hardware differences."
::= { pduBreakerEntry 12 }
pduBreakerApparentPower OBJECT-TYPE
SYNTAX Gauge32(0..9999)
UNITS "volt-amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Apparent power for breaker in volt-amps. This object may not exist on
all platforms, due to hardware differences."
::= { pduBreakerEntry 13 }
pduBreakerPowerFactor OBJECT-TYPE
SYNTAX Gauge32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power factor for breaker. This object may not exist on all platforms,
due to hardware differences."
::= { pduBreakerEntry 14 }
pduBreakerEnergy OBJECT-TYPE
SYNTAX Gauge32(0..9999000)
UNITS "watt-hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated energy for breaker in watt-hours. This object may not
exist on all platforms, due to hardware differences."
::= { pduBreakerEntry 15 }
--###########################################################################################--
--pduLineTable--
--###########################################################################################--
pduLineTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduLineEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"PDU line current information"
::= { pdu 4 }
pduLineEntry OBJECT-TYPE
SYNTAX PduLineEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the pduLineTable table: each entry contains an index
and other sensor details"
INDEX { pduLineIndex }
::= { pduLineTable 1 }
PduLineEntry ::= SEQUENCE {
pduLineIndex Integer32,
pduLineName SnmpAdminString,
pduLineLabel SnmpAdminString,
pduLineCurrent Gauge32
}
pduLineIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table entry index value"
::= { pduLineEntry 1 }
pduLineName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU line name (factory-assigned)"
::= { pduLineEntry 2 }
pduLineLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"PDU line label (user-defined)"
::= { pduLineEntry 3 }
pduLineCurrent OBJECT-TYPE
SYNTAX Gauge32(0..9900)
UNITS "centiamps (rms)"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU line current reading in hundredths of an amp"
::= { pduLineEntry 4 }
--###########################################################################################--
--pduOutletSwitchTable--
--###########################################################################################--
pduOutletSwitchTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutletSwitchEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Data, config and control for outlets with switching"
::= { pdu 5 }
pduOutletSwitchEntry OBJECT-TYPE
SYNTAX PduOutletSwitchEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the pduOutletSwitchTable table: each entry contains an index
and other sensor details"
INDEX { pduOutletSwitchIndex }
::= { pduOutletSwitchTable 1 }
PduOutletSwitchEntry ::= SEQUENCE {
pduOutletSwitchIndex Integer32,
pduOutletSwitchName SnmpAdminString,
pduOutletSwitchLabel SnmpAdminString,
pduOutletSwitchState INTEGER,
pduOutletSwitchRelayFailure TruthValue,
pduOutletSwitchControl INTEGER,
pduOutletSwitchTimeToAction Integer32,
pduOutletSwitchOnDelay Integer32,
pduOutletSwitchOffDelay Integer32,
pduOutletSwitchRebootDelay Integer32,
pduOutletSwitchRebootHoldDelay Integer32,
pduOutletSwitchPoaAction INTEGER,
pduOutletSwitchPoaDelay Integer32
}
pduOutletSwitchIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table entry index value"
::= { pduOutletSwitchEntry 1 }
pduOutletSwitchName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU outlet name (factory-assigned)"
::= { pduOutletSwitchEntry 2 }
pduOutletSwitchLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"PDU outlet label (user-defined)"
::= { pduOutletSwitchEntry 3 }
pduOutletSwitchState OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2),
on2off(3),
off2on(4),
rebootOn(5),
rebootOff(6),
unavailable(7)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Switch state of the outlet:
1 = Outlet is on
2 = Outlet is off
3 = Outlet is on, but will turn off after a delay
4 = Outlet is off, but will turn on after a delay
5 = Starting reboot cycle, outlet is on, but will go to the
rebootOff(6) state after a delay
6 = Rebooting, outlet is off, but it will turn on after a delay
7 = Cannot get outlet state"
::= { pduOutletSwitchEntry 4 }
pduOutletSwitchRelayFailure OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Tells if the outlet relay has failed. In normal operation, the value
will be false(2)."
::= { pduOutletSwitchEntry 5 }
pduOutletSwitchControl OBJECT-TYPE
SYNTAX INTEGER {
cancel(1),
on(2),
onAfterDelay(3),
off(4),
offAfterDelay(5),
reboot(6),
rebootAfterDelay(7),
none(8)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Used for manual control of the outlet. If the outlet is in manual
mode, this field can be set to one of the following values:
1 = Cancel pending operation
2 = Turn outlet on
3 = After delay (pduOutletSwitchOnDelay), turn outlet on
4 = Turn outlet off
5 = After delay (pduOutletSwitchOffDelay), turn outlet off
6 = Reboot: turn off, delay (pduOutletSwitchRebootHoldDelay), turn
outlet back on
7 = After delay (pduOutletSwitchRebootDelay), reboot outlet
When not in manual mode, setting this field will give an
inconsistentValue error. Returns none(8) for all get requests."
::= { pduOutletSwitchEntry 6 }
pduOutletSwitchTimeToAction OBJECT-TYPE
SYNTAX Integer32(0..600)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Seconds until an outlet state change. The value of
pduOutletSwitchState tells what state the outlet will be set, after
the delay."
::= { pduOutletSwitchEntry 7 }
pduOutletSwitchOnDelay OBJECT-TYPE
SYNTAX Integer32(0..600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Seconds to wait before powering on the outlet, during onAfterDelay(3)
operation. Changing this value has no effect on pending actions."
::= { pduOutletSwitchEntry 8 }
pduOutletSwitchOffDelay OBJECT-TYPE
SYNTAX Integer32(0..600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Seconds to wait before powering off the outlet, during
offAfterDelay(5) operation. Changing this value has no effect on
pending actions."
::= { pduOutletSwitchEntry 9 }
pduOutletSwitchRebootDelay OBJECT-TYPE
SYNTAX Integer32(0..600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Seconds to wait before powering off the outlet, during
rebootAfterDelay(7) operation. Changing this value has no effect on
pending actions. See pduOutletSwitchControl for more info."
::= { pduOutletSwitchEntry 10 }
pduOutletSwitchRebootHoldDelay OBJECT-TYPE
SYNTAX Integer32(0..600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Seconds to hold the outlet off, before powering on the outlet, during
rebootAfterDelay(7) operation. Changing this value has no effect on
pending actions. See pduOutletSwitchControl for more info."
::= { pduOutletSwitchEntry 11 }
pduOutletSwitchPoaAction OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2),
last(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The outlet is set to this state during power-up. The action can be
have one the following values:
1 = Outlet will be turned on
2 = Outlet will stay off
3 = Outlet will be set to last known state"
::= { pduOutletSwitchEntry 12 }
pduOutletSwitchPoaDelay OBJECT-TYPE
SYNTAX Integer32(0..600)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Seconds to wait before setting the outlet to the
pduOutletSwitchPoaAction state. The delay starts at power-up."
::= { pduOutletSwitchEntry 13 }
--###########################################################################################--
--pduOutletMeterTable--
--###########################################################################################--
pduOutletMeterTable OBJECT-TYPE
SYNTAX SEQUENCE OF PduOutletMeterEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Metering data for outlets that support this feature"
::= { pdu 6 }
pduOutletMeterEntry OBJECT-TYPE
SYNTAX PduOutletMeterEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the pduOutletMeterTable table: each entry contains an index
and other sensor details"
INDEX { pduOutletMeterIndex }
::= { pduOutletMeterTable 1 }
PduOutletMeterEntry ::= SEQUENCE {
pduOutletMeterIndex Integer32,
pduOutletMeterName SnmpAdminString,
pduOutletMeterLabel SnmpAdminString,
pduOutletMeterVoltage Gauge32,
pduOutletMeterCurrent Gauge32,
pduOutletMeterRealPower Gauge32,
pduOutletMeterApparentPower Gauge32,
pduOutletMeterPowerFactor Gauge32,
pduOutletMeterEnergy Gauge32,
pduOutletMeterReset INTEGER,
pduOutletCurrentCrestFactor Gauge32
}
pduOutletMeterIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table entry index value"
::= { pduOutletMeterEntry 1 }
pduOutletMeterName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU outlet name (factory-assigned)"
::= { pduOutletMeterEntry 2 }
pduOutletMeterLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"PDU outlet label (user-defined)"
::= { pduOutletMeterEntry 3 }
pduOutletMeterVoltage OBJECT-TYPE
SYNTAX Gauge32(0..3100)
UNITS "decivolts (rms)"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU outlet voltage in tenths of a volt"
::= { pduOutletMeterEntry 4 }
pduOutletMeterCurrent OBJECT-TYPE
SYNTAX Gauge32(0..9900)
UNITS "centiamps (rms)"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"PDU outlet current reading in hundredths of an amp"
::= { pduOutletMeterEntry 8 }
pduOutletMeterRealPower OBJECT-TYPE
SYNTAX Gauge32(0..9999)
UNITS "watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Real power for outlet in watts"
::= { pduOutletMeterEntry 12 }
pduOutletMeterApparentPower OBJECT-TYPE
SYNTAX Gauge32(0..9999)
UNITS "volt-amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Apparent power for outlet in volt-amps"
::= { pduOutletMeterEntry 13 }
pduOutletMeterPowerFactor OBJECT-TYPE
SYNTAX Gauge32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power factor for outlet"
::= { pduOutletMeterEntry 14 }
pduOutletMeterEnergy OBJECT-TYPE
SYNTAX Gauge32(0..9999000)
UNITS "watt-hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Accumulated energy for outlet in watt-hours"
::= { pduOutletMeterEntry 15 }
pduOutletMeterReset OBJECT-TYPE
SYNTAX INTEGER {
resetEnergy(1),
none(8)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Used to reset energy. If read, the value is none(8). It can be set to
resetEnergy(1), which sets outlet energy to 0"
::= { pduOutletMeterEntry 16 }
pduOutletCurrentCrestFactor OBJECT-TYPE
SYNTAX Gauge32(0..9999)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Current crest factor for outlet, in hundredths"
::= { pduOutletMeterEntry 19 }
--###########################################################################################--
--tempSensorTable--
--###########################################################################################--
tempSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF TempSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Remote Temperature (RT) sensor"
::= { imd 4 }
tempSensorEntry OBJECT-TYPE
SYNTAX TempSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the tempSensorTable table: each entry contains an index
and other sensor details"
INDEX { tempSensorIndex }
::= { tempSensorTable 1 }
TempSensorEntry ::= SEQUENCE {
tempSensorIndex Integer32,
tempSensorSerial DisplayString,
tempSensorLabel SnmpAdminString,
tempSensorAvail Gauge32,
tempSensorTemp Integer32
}
tempSensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table entry index value"
::= { tempSensorEntry 1 }
tempSensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number"
::= { tempSensorEntry 2 }
tempSensorLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined label"
::= { tempSensorEntry 3 }
tempSensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable"
::= { tempSensorEntry 4 }
tempSensorTemp OBJECT-TYPE
SYNTAX Integer32(-400..2540)
UNITS "decidegrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature in tenths of a degree. Units are given by temperatureUnits
field in deviceInfo."
::= { tempSensorEntry 5 }
--###########################################################################################--
--airFlowSensorTable--
--###########################################################################################--
airFlowSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF AirFlowSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Remote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor"
::= { imd 5 }
airFlowSensorEntry OBJECT-TYPE
SYNTAX AirFlowSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the airFlowSensorTable table: each entry contains an index
and other sensor details"
INDEX { airFlowSensorIndex }
::= { airFlowSensorTable 1 }
AirFlowSensorEntry ::= SEQUENCE {
airFlowSensorIndex Integer32,
airFlowSensorSerial DisplayString,
airFlowSensorLabel SnmpAdminString,
airFlowSensorAvail Gauge32,
airFlowSensorTemp Integer32,
airFlowSensorFlow Integer32,
airFlowSensorHumidity Integer32,
airFlowSensorDewPoint Integer32
}
airFlowSensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table entry index value"
::= { airFlowSensorEntry 1 }
airFlowSensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number"
::= { airFlowSensorEntry 2 }
airFlowSensorLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined label"
::= { airFlowSensorEntry 3 }
airFlowSensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable"
::= { airFlowSensorEntry 4 }
airFlowSensorTemp OBJECT-TYPE
SYNTAX Integer32(-400..2540)
UNITS "decidegrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature reading in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo."
::= { airFlowSensorEntry 5 }
airFlowSensorFlow OBJECT-TYPE
SYNTAX Integer32(0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Airflow reading. Still air will be less than 20, while rushing air
will be around 100."
::= { airFlowSensorEntry 6 }
airFlowSensorHumidity OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Humidity reading"
::= { airFlowSensorEntry 7 }
airFlowSensorDewPoint OBJECT-TYPE
SYNTAX Integer32(-400..2540)
UNITS "decidegrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Dewpoint reading in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo."
::= { airFlowSensorEntry 8 }
--###########################################################################################--
--t3hdSensorTable--
--###########################################################################################--
t3hdSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF T3hdSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Remote Temperature x 3, Humidity and Dewpoint Sensor"
::= { imd 8 }
t3hdSensorEntry OBJECT-TYPE
SYNTAX T3hdSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the t3hdSensorTable table: each entry contains an index
and other sensor details"
INDEX { t3hdSensorIndex }
::= { t3hdSensorTable 1 }
T3hdSensorEntry ::= SEQUENCE {
t3hdSensorIndex Integer32,
t3hdSensorSerial DisplayString,
t3hdSensorLabel SnmpAdminString,
t3hdSensorAvail Gauge32,
t3hdSensorIntLabel SnmpAdminString,
t3hdSensorIntTemp Integer32,
t3hdSensorIntHumidity Integer32,
t3hdSensorIntDewPoint Integer32,
t3hdSensorExtAAvail Gauge32,
t3hdSensorExtALabel SnmpAdminString,
t3hdSensorExtATemp Integer32,
t3hdSensorExtBAvail Gauge32,
t3hdSensorExtBLabel SnmpAdminString,
t3hdSensorExtBTemp Integer32
}
t3hdSensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table entry index value"
::= { t3hdSensorEntry 1 }
t3hdSensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number"
::= { t3hdSensorEntry 2 }
t3hdSensorLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined label"
::= { t3hdSensorEntry 3 }
t3hdSensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable"
::= { t3hdSensorEntry 4 }
t3hdSensorIntLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Internal label (user-defined)"
::= { t3hdSensorEntry 5 }
t3hdSensorIntTemp OBJECT-TYPE
SYNTAX Integer32(-400..2540)
UNITS "decidegrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Internal temperature in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo."
::= { t3hdSensorEntry 6 }
t3hdSensorIntHumidity OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Internal humidity"
::= { t3hdSensorEntry 7 }
t3hdSensorIntDewPoint OBJECT-TYPE
SYNTAX Integer32(-400..2540)
UNITS "decidegrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Internal dewpoint in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo."
::= { t3hdSensorEntry 8 }
t3hdSensorExtAAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"External A status:
0 = Unavailable
1 = Available"
::= { t3hdSensorEntry 9 }
t3hdSensorExtALabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"External A label (user-defined)"
::= { t3hdSensorEntry 10 }
t3hdSensorExtATemp OBJECT-TYPE
SYNTAX Integer32(-400..2540)
UNITS "decidegrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"External A temperature in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo."
::= { t3hdSensorEntry 11 }
t3hdSensorExtBAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"External B status:
0 = Unavailable
1 = Available"
::= { t3hdSensorEntry 12 }
t3hdSensorExtBLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"External B label (user-defined)"
::= { t3hdSensorEntry 13 }
t3hdSensorExtBTemp OBJECT-TYPE
SYNTAX Integer32(-400..2540)
UNITS "decidegrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"External B temperature in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo."
::= { t3hdSensorEntry 14 }
--###########################################################################################--
--thdSensorTable--
--###########################################################################################--
thdSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF ThdSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Remote Temperature, Humidity, and Dewpoint (THD) Sensor"
::= { imd 9 }
thdSensorEntry OBJECT-TYPE
SYNTAX ThdSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the thdSensorTable table: each entry contains an index
and other sensor details"
INDEX { thdSensorIndex }
::= { thdSensorTable 1 }
ThdSensorEntry ::= SEQUENCE {
thdSensorIndex Integer32,
thdSensorSerial DisplayString,
thdSensorLabel SnmpAdminString,
thdSensorAvail Gauge32,
thdSensorTemp Integer32,
thdSensorHumidity Integer32,
thdSensorDewPoint Integer32
}
thdSensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table entry index value"
::= { thdSensorEntry 1 }
thdSensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number"
::= { thdSensorEntry 2 }
thdSensorLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined label"
::= { thdSensorEntry 3 }
thdSensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable"
::= { thdSensorEntry 4 }
thdSensorTemp OBJECT-TYPE
SYNTAX Integer32(-400..2540)
UNITS "decidegrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo."
::= { thdSensorEntry 5 }
thdSensorHumidity OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Humidity value"
::= { thdSensorEntry 6 }
thdSensorDewPoint OBJECT-TYPE
SYNTAX Integer32(-400..2540)
UNITS "decidegrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Dewpoint value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo."
::= { thdSensorEntry 7 }
--###########################################################################################--
--a2dSensorTable--
--###########################################################################################--
a2dSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF A2dSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Analog measurement (A2D) sensor (voltage, current, or dry-contact)"
::= { imd 11 }
a2dSensorEntry OBJECT-TYPE
SYNTAX A2dSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the a2dSensorTable table: each entry contains an index
and other sensor details"
INDEX { a2dSensorIndex }
::= { a2dSensorTable 1 }
A2dSensorEntry ::= SEQUENCE {
a2dSensorIndex Integer32,
a2dSensorSerial DisplayString,
a2dSensorLabel SnmpAdminString,
a2dSensorAvail Gauge32,
a2dSensorValue Integer32,
a2dSensorDisplayValue SnmpAdminString,
a2dSensorMode INTEGER,
a2dSensorUnits SnmpAdminString,
a2dSensorMin Integer32,
a2dSensorMax Integer32,
a2dSensorLowLabel SnmpAdminString,
a2dSensorHighLabel SnmpAdminString,
a2dSensorAnalogLabel SnmpAdminString
}
a2dSensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table entry index value"
::= { a2dSensorEntry 1 }
a2dSensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number"
::= { a2dSensorEntry 2 }
a2dSensorLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined label"
::= { a2dSensorEntry 3 }
a2dSensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable"
::= { a2dSensorEntry 4 }
a2dSensorValue OBJECT-TYPE
SYNTAX Integer32(-1000000..1000000)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Analog measurement value, within either a user-defined or preset
range, depending on a2dSensorMode."
::= { a2dSensorEntry 5 }
a2dSensorDisplayValue OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"For current/voltage modes, the analog value is given as a string. In
binary modes, the value is either a2dSensorLowLabel or
a2dSensorHighLabel, based on a2dSensorValue."
::= { a2dSensorEntry 6 }
a2dSensorMode OBJECT-TYPE
SYNTAX INTEGER {
door(1),
powerFailure(2),
flood(3),
wscLeak(4),
wscFault(5),
smoke(6),
ivsNegGnd(7),
ivsPosGnd(8),
customVoltage(9),
customBinary(10),
customCurrent(11)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Binary modes have two states represented by the values 0 (low) or 1
(high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel.
Current and voltage modes provide a scaled value from a2dSensorMin to
a2dSensorMax.
Analog modes:
1 = Door (binary)
2 = Power failure (binary)
3 = Flood (binary)
4 = Water-sensing cable leak (binary)
5 = Water-sensing cable fault (binary)
6 = Smoke alarm (binary)
7 = Isolated voltage negative ground (voltage)
8 = Isolated voltage positive ground (voltage)
9 = Custom voltage (voltage)
10 = Custom binary (binary)
11 = Custom current (current)"
::= { a2dSensorEntry 7 }
a2dSensorUnits OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..7))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The units for the analog value. If a2dSensorMode is customVoltage(9)
or customCurrent(11), then this field has a user-defined value.
Otherwise, the value is fixed, based on mode."
::= { a2dSensorEntry 8 }
a2dSensorMin OBJECT-TYPE
SYNTAX Integer32(-1000000..1000000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Minimum analog value, given as an integer. The analog measurement is
scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is
customVoltage(9) or customCurrent(11), then this field has a user-
defined value. Otherwise, the value is fixed, based on mode."
::= { a2dSensorEntry 9 }
a2dSensorMax OBJECT-TYPE
SYNTAX Integer32(-1000000..1000000)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Maximum analog value, given as an integer. The analog measurement is
scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is
customVoltage(9) or customCurrent(11), then this field has a user-
defined value. Otherwise, the value is fixed, based on mode."
::= { a2dSensorEntry 10 }
a2dSensorLowLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for 0 (low) binary value. This field is only applicable if
a2dSensorMode is one of the binary modes. If a2dSensorMode is
customBinary(10), then this field is user-defined. Otherwise, it has a
pre-defined value based on the mode."
::= { a2dSensorEntry 11 }
a2dSensorHighLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for 1 (high) binary value. The field is only applicable if
a2dSensorMode is one of the binary modes. If a2dSensorMode is
customBinary(10), then this field is user-defined. Otherwise, it has a
pre-defined value based on the mode."
::= { a2dSensorEntry 12 }
a2dSensorAnalogLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Label for the analog measurement"
::= { a2dSensorEntry 13 }
--###########################################################################################--
--humiditySensorTable--
--###########################################################################################--
humiditySensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF HumiditySensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Remote humidity sensor"
::= { imd 12 }
humiditySensorEntry OBJECT-TYPE
SYNTAX HumiditySensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the humiditySensorTable table: each entry contains an index
and other sensor details"
INDEX { humiditySensorIndex }
::= { humiditySensorTable 1 }
HumiditySensorEntry ::= SEQUENCE {
humiditySensorIndex Integer32,
humiditySensorSerial DisplayString,
humiditySensorLabel SnmpAdminString,
humiditySensorAvail Gauge32,
humiditySensorValue Integer32
}
humiditySensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table entry index value"
::= { humiditySensorEntry 1 }
humiditySensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number"
::= { humiditySensorEntry 2 }
humiditySensorLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined label"
::= { humiditySensorEntry 3 }
humiditySensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable"
::= { humiditySensorEntry 4 }
humiditySensorValue OBJECT-TYPE
SYNTAX Integer32(0..100)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Humidity value"
::= { humiditySensorEntry 5 }
--###########################################################################################--
--sn2dSensorTable--
--###########################################################################################--
sn2dSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF Sn2dSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"2 Door Switch Sensor (SN-2D)"
::= { imd 13 }
sn2dSensorEntry OBJECT-TYPE
SYNTAX Sn2dSensorEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the sn2dSensorTable table: each entry contains an index
and other sensor details"
INDEX { sn2dSensorIndex }
::= { sn2dSensorTable 1 }
Sn2dSensorEntry ::= SEQUENCE {
sn2dSensorIndex Integer32,
sn2dSensorSerial DisplayString,
sn2dSensorLabel SnmpAdminString,
sn2dSensorAvail Gauge32,
sn2dSensorDoor1Label SnmpAdminString,
sn2dSensorDoor1State INTEGER,
sn2dSensorDoor1DisplayState SnmpAdminString,
sn2dSensorDoor2Label SnmpAdminString,
sn2dSensorDoor2State INTEGER,
sn2dSensorDoor2DisplayState SnmpAdminString
}
sn2dSensorIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table entry index value"
::= { sn2dSensorEntry 1 }
sn2dSensorSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number"
::= { sn2dSensorEntry 2 }
sn2dSensorLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"User-defined label"
::= { sn2dSensorEntry 3 }
sn2dSensorAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable"
::= { sn2dSensorEntry 4 }
sn2dSensorDoor1Label OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Door switch 1 label"
::= { sn2dSensorEntry 5 }
sn2dSensorDoor1State OBJECT-TYPE
SYNTAX INTEGER {
open(1),
closed(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Door switch 1 state:
1 = open
2 = closed"
::= { sn2dSensorEntry 6 }
sn2dSensorDoor1DisplayState OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Door switch 1 state given as a string"
::= { sn2dSensorEntry 7 }
sn2dSensorDoor2Label OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Door switch 2 label"
::= { sn2dSensorEntry 8 }
sn2dSensorDoor2State OBJECT-TYPE
SYNTAX INTEGER {
open(1),
closed(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Door switch 2 state:
1 = open
2 = closed"
::= { sn2dSensorEntry 9 }
sn2dSensorDoor2DisplayState OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Door switch 2 state given as a string"
::= { sn2dSensorEntry 10 }
--###########################################################################################--
--cooling--
--###########################################################################################--
cooling OBJECT IDENTIFIER ::= { imd 30 }
--###########################################################################################--
--vrc--
--###########################################################################################--
vrc OBJECT IDENTIFIER ::= { cooling 1 }
--###########################################################################################--
--vrcMainTable--
--###########################################################################################--
vrcMainTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcMainEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table that contains general VRC information"
::= { vrc 1 }
vrcMainEntry OBJECT-TYPE
SYNTAX VrcMainEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcMainTable: each entry represents a VRC device"
INDEX { vrcMainIndex }
::= { vrcMainTable 1 }
VrcMainEntry ::= SEQUENCE {
vrcMainIndex Integer32,
vrcMainSerial DisplayString,
vrcMainName SnmpAdminString,
vrcMainLabel SnmpAdminString,
vrcMainAvail Gauge32
}
vrcMainIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcMainEntry 1 }
vrcMainSerial OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number"
::= { vrcMainEntry 2 }
vrcMainName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"VRC name (factory-assigned)"
::= { vrcMainEntry 3 }
vrcMainLabel OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (0..25))
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"VRC label (user-defined)"
::= { vrcMainEntry 4 }
vrcMainAvail OBJECT-TYPE
SYNTAX Gauge32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable"
::= { vrcMainEntry 5 }
--###########################################################################################--
--vrcMainPtTable--
--###########################################################################################--
vrcMainPtTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcMainPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table that contains general VRC status"
::= { vrc 2 }
vrcMainPtEntry OBJECT-TYPE
SYNTAX VrcMainPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcMainPtTable: each entry contains status data for a VRC
device"
INDEX { vrcMainPtIndex }
::= { vrcMainPtTable 1 }
VrcMainPtEntry ::= SEQUENCE {
vrcMainPtIndex Integer32,
vrcMainPtRunState INTEGER,
vrcMainPtEevOpened Integer32,
vrcMainPtAlarmNumbers Integer32,
vrcMainPtHistoryAlarmNumbers Integer32,
vrcMainPtHpAbnRecordCnt Integer32,
vrcMainPtMonitorBaudrate INTEGER,
vrcMainPtMonitorAddress Integer32,
vrcMainPtLp TruthValue,
vrcMainPtFilterMaintRemind TruthValue,
vrcMainPtCoolingFlag TruthValue,
vrcMainPtFirstOnFlag TruthValue,
vrcMainPtNewAlarmFlag TruthValue,
vrcMainPtComAlarmOutState TruthValue,
vrcMainPtHighWaterInput TruthValue,
vrcMainPtHighWaterAlarm TruthValue,
vrcMainPtWaterUnderFloorAlarm TruthValue,
vrcMainPtSwShutDownStatus TruthValue,
vrcMainPtRemoteShutdown TruthValue,
vrcMainPtRemoteShutDownFlag TruthValue,
vrcMainPtRemoteShutDownAlarm TruthValue,
vrcMainPtHmiShutDownFlag TruthValue,
vrcMainPtLpAlarm TruthValue,
vrcMainPtHpAlarm TruthValue,
vrcMainPtLpFreqAlarm TruthValue,
vrcMainPtHpFreqAlarm TruthValue,
vrcMainPtLpSensorFailAlarm TruthValue,
vrcMainPtHpSensorFailAlarm TruthValue,
vrcMainPtEevCommFailAlarm TruthValue
}
vrcMainPtIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcMainPtEntry 1 }
vrcMainPtRunState OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"VRC run state:
1 = on
2 = off"
::= { vrcMainPtEntry 2 }
vrcMainPtEevOpened OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Eev opened value (percent)"
::= { vrcMainPtEntry 3 }
vrcMainPtAlarmNumbers OBJECT-TYPE
SYNTAX Integer32(-32768..32767)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Alarm numbers value"
::= { vrcMainPtEntry 4 }
vrcMainPtHistoryAlarmNumbers OBJECT-TYPE
SYNTAX Integer32(-32768..32767)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"History alarm numbers value"
::= { vrcMainPtEntry 5 }
vrcMainPtHpAbnRecordCnt OBJECT-TYPE
SYNTAX Integer32(-32768..32767)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Hp Abnormal record count"
::= { vrcMainPtEntry 6 }
vrcMainPtMonitorBaudrate OBJECT-TYPE
SYNTAX INTEGER {
error(1),
baud1200(2),
baud2400(3),
baud4800(4),
baud9600(5),
baud19200(6)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Monitor baud rate:
1 = error
2 = 1200
3 = 2400
4 = 4800
5 = 9600
6 = 19200"
::= { vrcMainPtEntry 7 }
vrcMainPtMonitorAddress OBJECT-TYPE
SYNTAX Integer32(1..247)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Monitor address"
::= { vrcMainPtEntry 8 }
vrcMainPtLp OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Lp status"
::= { vrcMainPtEntry 9 }
vrcMainPtFilterMaintRemind OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Filter maintenance reminder status"
::= { vrcMainPtEntry 10 }
vrcMainPtCoolingFlag OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Cooling flag"
::= { vrcMainPtEntry 11 }
vrcMainPtFirstOnFlag OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"First on flag"
::= { vrcMainPtEntry 12 }
vrcMainPtNewAlarmFlag OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"New alarm flag"
::= { vrcMainPtEntry 13 }
vrcMainPtComAlarmOutState OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Common alarm output state"
::= { vrcMainPtEntry 14 }
vrcMainPtHighWaterInput OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"High water input"
::= { vrcMainPtEntry 15 }
vrcMainPtHighWaterAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"High water alarm status"
::= { vrcMainPtEntry 16 }
vrcMainPtWaterUnderFloorAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Water under floor alarm status"
::= { vrcMainPtEntry 17 }
vrcMainPtSwShutDownStatus OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Software shutdown status"
::= { vrcMainPtEntry 18 }
vrcMainPtRemoteShutdown OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Remote shutdown status"
::= { vrcMainPtEntry 19 }
vrcMainPtRemoteShutDownFlag OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Remote shutdown flag"
::= { vrcMainPtEntry 20 }
vrcMainPtRemoteShutDownAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Remote shutdown alarm status"
::= { vrcMainPtEntry 21 }
vrcMainPtHmiShutDownFlag OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Hmi shutdown flag"
::= { vrcMainPtEntry 22 }
vrcMainPtLpAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Low pressure alarm status"
::= { vrcMainPtEntry 23 }
vrcMainPtHpAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"High pressure alarm status"
::= { vrcMainPtEntry 24 }
vrcMainPtLpFreqAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Low pressure frequently alarm status"
::= { vrcMainPtEntry 25 }
vrcMainPtHpFreqAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"High pressure frequently alarm status"
::= { vrcMainPtEntry 26 }
vrcMainPtLpSensorFailAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Low pressure sensor failure alarm status"
::= { vrcMainPtEntry 27 }
vrcMainPtHpSensorFailAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"High pressure sensor failure alarm status"
::= { vrcMainPtEntry 28 }
vrcMainPtEevCommFailAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Eev communication failure alarm status"
::= { vrcMainPtEntry 29 }
--###########################################################################################--
--vrcMainCfgTable--
--###########################################################################################--
vrcMainCfgTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcMainCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table that contains general VRC configuration"
::= { vrc 3 }
vrcMainCfgEntry OBJECT-TYPE
SYNTAX VrcMainCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcMainCfgTable: each entry contains general config
fields for a VRC device"
INDEX { vrcMainCfgIndex }
::= { vrcMainCfgTable 1 }
VrcMainCfgEntry ::= SEQUENCE {
vrcMainCfgIndex Integer32,
vrcMainCfgModelSelect INTEGER,
vrcMainCfgSystemTimeYear Integer32,
vrcMainCfgSystemTimeMonth Integer32,
vrcMainCfgSystemTimeDay Integer32,
vrcMainCfgSystemTimeHour Integer32,
vrcMainCfgSystemTimeMin Integer32,
vrcMainCfgSystemTimeSec Integer32,
vrcMainCfgEevShtSettingMin Integer32,
vrcMainCfgEevShtSettingMax Integer32,
vrcMainCfgEevValveCloseSht Integer32,
vrcMainCfgEevMopPressSetting Integer32,
vrcMainCfgLpdt Integer32,
vrcMainCfgDeadBand Integer32,
vrcMainCfgOnOffSwitch TruthValue,
vrcMainCfgVacuumState TruthValue,
vrcMainCfgControlMode INTEGER,
vrcMainCfgManualRunEnable TruthValue,
vrcMainCfgRemShutdownInput TruthValue,
vrcMainCfgMonitorShutDownFlag TruthValue,
vrcMainCfgFirstOnPassword Integer32,
vrcMainCfgFilterMaintSetting TruthValue,
vrcMainCfgFilterMaintRemindTime Integer32,
vrcMainCfgFilterMaintRemindCtrl INTEGER,
vrcMainCfgCommonAlarmOutputDir TruthValue,
vrcMainCfgHpAbnAlarmSetting Integer32,
vrcMainCfgLpAlarmCtrl INTEGER,
vrcMainCfgHpAlarmCtrl INTEGER,
vrcMainCfgLpFreqAlarmCtrl INTEGER,
vrcMainCfgHpFreqAlarmCtrl INTEGER,
vrcMainCfgLpSensorFailAlarmCtrl INTEGER,
vrcMainCfgHpSensorFailAlarmCtrl INTEGER,
vrcMainCfgHighWaterAlarmCtrl INTEGER,
vrcMainCfgRemShutdownAlarmCtrl INTEGER,
vrcMainCfgEevCommFailAlarmCtrl INTEGER
}
vrcMainCfgIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcMainCfgEntry 1 }
vrcMainCfgModelSelect OBJECT-TYPE
SYNTAX INTEGER {
tmLoc(1),
r035Ap(2),
r035Ak(3),
scLoc(4),
zeroULoc(5),
r035Ep(6),
r035Ek(7)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Model Selection:
1 = TMM-Local 220V 50/60HZ
2 = TMM-Global 208/230V 50/60HZ
3 = TMM-Global 120V 50/60HZ
4 = SC 220V 50/60HZ
5 = 0U 220V 50/60HZ
6 = SS 208/230V 50/60HZ
7 = SS 120V 50/60HZ"
::= { vrcMainCfgEntry 2 }
vrcMainCfgSystemTimeYear OBJECT-TYPE
SYNTAX Integer32(2000..2099)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"System time - year"
::= { vrcMainCfgEntry 3 }
vrcMainCfgSystemTimeMonth OBJECT-TYPE
SYNTAX Integer32(1..12)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"System time - month"
::= { vrcMainCfgEntry 4 }
vrcMainCfgSystemTimeDay OBJECT-TYPE
SYNTAX Integer32(1..31)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"System time - day"
::= { vrcMainCfgEntry 5 }
vrcMainCfgSystemTimeHour OBJECT-TYPE
SYNTAX Integer32(0..23)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"System time - hour"
::= { vrcMainCfgEntry 6 }
vrcMainCfgSystemTimeMin OBJECT-TYPE
SYNTAX Integer32(0..59)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"System time - minutes"
::= { vrcMainCfgEntry 7 }
vrcMainCfgSystemTimeSec OBJECT-TYPE
SYNTAX Integer32(0..59)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"System time - seconds"
::= { vrcMainCfgEntry 8 }
vrcMainCfgEevShtSettingMin OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Min Eev sht in tenths of a degree. Units are given by temperatureUnits
field in deviceInfo. The settable range is determined by the current
temperature units.
Celsius: 50 to 200
Fahrenheit: 90 to 359"
::= { vrcMainCfgEntry 9 }
vrcMainCfgEevShtSettingMax OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Max Eev sht in tenths of a degree. Units are given by temperatureUnits
field in deviceInfo. The settable range is determined by the current
temperature units.
Celsius: 50 to 200
Fahrenheit: 90 to 359"
::= { vrcMainCfgEntry 10 }
vrcMainCfgEevValveCloseSht OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Eev valve close sht in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The settable range is determined
by the current temperature units.
Celsius: 0 to 100
Fahrenheit: 0 to 179"
::= { vrcMainCfgEntry 11 }
vrcMainCfgEevMopPressSetting OBJECT-TYPE
SYNTAX Integer32(0..200)
UNITS "decibars"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Eev mop pressure setting in tenths of a bar."
::= { vrcMainCfgEntry 12 }
vrcMainCfgLpdt OBJECT-TYPE
SYNTAX Integer32(30..600)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Low pressure dt in seconds"
::= { vrcMainCfgEntry 13 }
vrcMainCfgDeadBand OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Dead band in tenths of a degree. Units are given by temperatureUnits
field in deviceInfo. The settable range is determined by the current
temperature units.
Celsius: 0 to 20
Fahrenheit: 0 to 35"
::= { vrcMainCfgEntry 14 }
vrcMainCfgOnOffSwitch OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"On-off switch"
::= { vrcMainCfgEntry 15 }
vrcMainCfgVacuumState OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Vacuum state"
::= { vrcMainCfgEntry 16 }
vrcMainCfgControlMode OBJECT-TYPE
SYNTAX INTEGER {
supply(1),
return(2)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Control mode:
1 = supply
2 = return"
::= { vrcMainCfgEntry 17 }
vrcMainCfgManualRunEnable OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Manual run enable"
::= { vrcMainCfgEntry 18 }
vrcMainCfgRemShutdownInput OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Remote shutdown input"
::= { vrcMainCfgEntry 19 }
vrcMainCfgMonitorShutDownFlag OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Monitor shutdown flag"
::= { vrcMainCfgEntry 20 }
vrcMainCfgFirstOnPassword OBJECT-TYPE
SYNTAX Integer32(-32768..32767)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"First on password value"
::= { vrcMainCfgEntry 21 }
vrcMainCfgFilterMaintSetting OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Filter maintenance setting"
::= { vrcMainCfgEntry 22 }
vrcMainCfgFilterMaintRemindTime OBJECT-TYPE
SYNTAX Integer32(30..360)
UNITS "days"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Time between filter maintenance reminders in days"
::= { vrcMainCfgEntry 23 }
vrcMainCfgFilterMaintRemindCtrl OBJECT-TYPE
SYNTAX INTEGER {
close(1),
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Filter maintenance reminder:
1 = close
2 = suspend
3 = open"
::= { vrcMainCfgEntry 24 }
vrcMainCfgCommonAlarmOutputDir OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Common alarm output direction"
::= { vrcMainCfgEntry 25 }
vrcMainCfgHpAbnAlarmSetting OBJECT-TYPE
SYNTAX Integer32(300..360)
UNITS "decibars"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Abnormal high pressure alarm value in tenths of a bar"
::= { vrcMainCfgEntry 26 }
vrcMainCfgLpAlarmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Low pressure alarm control:
2 = suspend
3 = open"
::= { vrcMainCfgEntry 27 }
vrcMainCfgHpAlarmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"High pressure alarm control:
2 = suspend
3 = open"
::= { vrcMainCfgEntry 28 }
vrcMainCfgLpFreqAlarmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Low pressure frequently alarm control:
2 = suspend
3 = open"
::= { vrcMainCfgEntry 29 }
vrcMainCfgHpFreqAlarmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"High pressure frequently alarm control:
2 = suspend
3 = open"
::= { vrcMainCfgEntry 30 }
vrcMainCfgLpSensorFailAlarmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Low pressure sensor failure alarm control:
2 = suspend
3 = open"
::= { vrcMainCfgEntry 31 }
vrcMainCfgHpSensorFailAlarmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"High pressure sensor failure alarm control:
2 = suspend
3 = open"
::= { vrcMainCfgEntry 32 }
vrcMainCfgHighWaterAlarmCtrl OBJECT-TYPE
SYNTAX INTEGER {
close(1),
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"High water alarm control:
1 = close
2 = suspend
3 = open"
::= { vrcMainCfgEntry 33 }
vrcMainCfgRemShutdownAlarmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Remote shutdown alarm control:
2 = suspend
3 = open"
::= { vrcMainCfgEntry 34 }
vrcMainCfgEevCommFailAlarmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Eev communication failure alarm:
2 = suspend
3 = open"
::= { vrcMainCfgEntry 35 }
--###########################################################################################--
--vrcOutFanPtTable--
--###########################################################################################--
vrcOutFanPtTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcOutFanPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table that contains VRC out-fan status"
::= { vrc 4 }
vrcOutFanPtEntry OBJECT-TYPE
SYNTAX VrcOutFanPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcOutFanPtTable: each entry represents data for a VRC
out-fan"
INDEX { vrcOutFanPtIndex }
::= { vrcOutFanPtTable 1 }
VrcOutFanPtEntry ::= SEQUENCE {
vrcOutFanPtIndex Integer32,
vrcOutFanPtName SnmpAdminString,
vrcOutFanPtSpeed Integer32
}
vrcOutFanPtIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcOutFanPtEntry 1 }
vrcOutFanPtName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Out-fan name (factory-assigned)"
::= { vrcOutFanPtEntry 2 }
vrcOutFanPtSpeed OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Fan speed (percent)"
::= { vrcOutFanPtEntry 3 }
--###########################################################################################--
--vrcOutFanCfgTable--
--###########################################################################################--
vrcOutFanCfgTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcOutFanCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table used for VRC out-fan configuration"
::= { vrc 5 }
vrcOutFanCfgEntry OBJECT-TYPE
SYNTAX VrcOutFanCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcOutFanCfgTable: each entry contains config fields for
a VRC out-fan"
INDEX { vrcOutFanCfgIndex }
::= { vrcOutFanCfgTable 1 }
VrcOutFanCfgEntry ::= SEQUENCE {
vrcOutFanCfgIndex Integer32,
vrcOutFanCfgStartPress Integer32,
vrcOutFanCfgPressSetting Integer32,
vrcOutFanCfgMinPowerVoltage Integer32,
vrcOutFanCfgMaxPowerVoltage Integer32,
vrcOutFanCfgSpeed Integer32
}
vrcOutFanCfgIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcOutFanCfgEntry 1 }
vrcOutFanCfgStartPress OBJECT-TYPE
SYNTAX Integer32(190..250)
UNITS "decibars"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Out-fan start pressure in tenths of a bar"
::= { vrcOutFanCfgEntry 2 }
vrcOutFanCfgPressSetting OBJECT-TYPE
SYNTAX Integer32(50..80)
UNITS "decibars"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Out-fan pressure setting in tenths of a bar"
::= { vrcOutFanCfgEntry 3 }
vrcOutFanCfgMinPowerVoltage OBJECT-TYPE
SYNTAX Integer32(30..50)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Min out-fan voltage (percent)"
::= { vrcOutFanCfgEntry 4 }
vrcOutFanCfgMaxPowerVoltage OBJECT-TYPE
SYNTAX Integer32(60..100)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Max out-fan voltage (percent)"
::= { vrcOutFanCfgEntry 5 }
vrcOutFanCfgSpeed OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Out-fan speed (percent)"
::= { vrcOutFanCfgEntry 6 }
--###########################################################################################--
--vrcInFanPtTable--
--###########################################################################################--
vrcInFanPtTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcInFanPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table that contains VRC in-fan status"
::= { vrc 6 }
vrcInFanPtEntry OBJECT-TYPE
SYNTAX VrcInFanPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcInFanPtTable: each entry represents data for a VRC in-
fan"
INDEX { vrcInFanPtIndex }
::= { vrcInFanPtTable 1 }
VrcInFanPtEntry ::= SEQUENCE {
vrcInFanPtIndex Integer32,
vrcInFanPtName SnmpAdminString,
vrcInFanPtRunTimeHours Integer32,
vrcInFanPtStartStopCount Integer32
}
vrcInFanPtIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcInFanPtEntry 1 }
vrcInFanPtName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"In-fan name (factory-assigned)"
::= { vrcInFanPtEntry 2 }
vrcInFanPtRunTimeHours OBJECT-TYPE
SYNTAX Integer32(-32768..32767)
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"In-fan run time in hours"
::= { vrcInFanPtEntry 3 }
vrcInFanPtStartStopCount OBJECT-TYPE
SYNTAX Integer32(-32768..32767)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"In-fan start/stop count"
::= { vrcInFanPtEntry 4 }
--###########################################################################################--
--vrcInFanCfgTable--
--###########################################################################################--
vrcInFanCfgTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcInFanCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table used for VRC in-fan configuration"
::= { vrc 7 }
vrcInFanCfgEntry OBJECT-TYPE
SYNTAX VrcInFanCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcInFanCfgTable: each entry contains config fields for a
VRC in-fan"
INDEX { vrcInFanCfgIndex }
::= { vrcInFanCfgTable 1 }
VrcInFanCfgEntry ::= SEQUENCE {
vrcInFanCfgIndex Integer32,
vrcInFanCfgOutputStatus TruthValue,
vrcInFanCfgLowSpeedStep Integer32,
vrcInFanCfgHighSpeedStep Integer32,
vrcInFanCfgMinSpeed Integer32,
vrcInFanCfgStandardSpeed Integer32,
vrcInFanCfgMinCfc Integer32,
vrcInFanCfgStandardCfc Integer32,
vrcInFanCfgStartDelay Integer32,
vrcInFanCfgStopDelay Integer32,
vrcInFanCfgReduceSpeedDelay Integer32,
vrcInFanCfgJumpBand1 Integer32,
vrcInFanCfgJumpBand2 Integer32,
vrcInFanCfgJumpBand3 Integer32,
vrcInFanCfgJumpBand4 Integer32,
vrcInFanCfgJumpBand5 Integer32,
vrcInFanCfgJumpFreq1 Integer32,
vrcInFanCfgJumpFreq2 Integer32,
vrcInFanCfgJumpFreq3 Integer32,
vrcInFanCfgJumpFreq4 Integer32,
vrcInFanCfgJumpFreq5 Integer32,
vrcInFanCfgTempP Integer32,
vrcInFanCfgTempI Integer32,
vrcInFanCfgTempD Integer32
}
vrcInFanCfgIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcInFanCfgEntry 1 }
vrcInFanCfgOutputStatus OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan output status"
::= { vrcInFanCfgEntry 2 }
vrcInFanCfgLowSpeedStep OBJECT-TYPE
SYNTAX Integer32(1..20)
UNITS "0.1%/s"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan low speed step in tenths of a percent per second"
::= { vrcInFanCfgEntry 3 }
vrcInFanCfgHighSpeedStep OBJECT-TYPE
SYNTAX Integer32(1..50)
UNITS "0.1%/s"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan high speed step in tenths of a percent per second"
::= { vrcInFanCfgEntry 4 }
vrcInFanCfgMinSpeed OBJECT-TYPE
SYNTAX Integer32(30..80)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Min in-fan speed (percent)"
::= { vrcInFanCfgEntry 5 }
vrcInFanCfgStandardSpeed OBJECT-TYPE
SYNTAX Integer32(80..100)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Standard in-fan speed (percent)"
::= { vrcInFanCfgEntry 6 }
vrcInFanCfgMinCfc OBJECT-TYPE
SYNTAX Integer32(0..30)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Min in-fan cfc (percent)"
::= { vrcInFanCfgEntry 7 }
vrcInFanCfgStandardCfc OBJECT-TYPE
SYNTAX Integer32(85..100)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Standard in-fan cfc (percent)"
::= { vrcInFanCfgEntry 8 }
vrcInFanCfgStartDelay OBJECT-TYPE
SYNTAX Integer32(10..600)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan start delay in seconds"
::= { vrcInFanCfgEntry 9 }
vrcInFanCfgStopDelay OBJECT-TYPE
SYNTAX Integer32(10..300)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan stop delay in seconds"
::= { vrcInFanCfgEntry 10 }
vrcInFanCfgReduceSpeedDelay OBJECT-TYPE
SYNTAX Integer32(0..300)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan reduce speed delay in seconds"
::= { vrcInFanCfgEntry 11 }
vrcInFanCfgJumpBand1 OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan jump band 1 in tenths of a percent"
::= { vrcInFanCfgEntry 12 }
vrcInFanCfgJumpBand2 OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan jump band 2 in tenths of a percent"
::= { vrcInFanCfgEntry 13 }
vrcInFanCfgJumpBand3 OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan jump band 3 in tenths of a percent"
::= { vrcInFanCfgEntry 14 }
vrcInFanCfgJumpBand4 OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan jump band 4 in tenths of a percent"
::= { vrcInFanCfgEntry 15 }
vrcInFanCfgJumpBand5 OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan jump band 5 in tenths of a percent"
::= { vrcInFanCfgEntry 16 }
vrcInFanCfgJumpFreq1 OBJECT-TYPE
SYNTAX Integer32(0..1000)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan jump frequency 1 in tenths of a percent"
::= { vrcInFanCfgEntry 17 }
vrcInFanCfgJumpFreq2 OBJECT-TYPE
SYNTAX Integer32(0..1000)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan jump frequency 2 in tenths of a percent"
::= { vrcInFanCfgEntry 18 }
vrcInFanCfgJumpFreq3 OBJECT-TYPE
SYNTAX Integer32(0..1000)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan jump frequency 3 in tenths of a percent"
::= { vrcInFanCfgEntry 19 }
vrcInFanCfgJumpFreq4 OBJECT-TYPE
SYNTAX Integer32(0..1000)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan jump frequency 4 in tenths of a percent"
::= { vrcInFanCfgEntry 20 }
vrcInFanCfgJumpFreq5 OBJECT-TYPE
SYNTAX Integer32(0..1000)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan jump frequency 5 in tenths of a percent"
::= { vrcInFanCfgEntry 21 }
vrcInFanCfgTempP OBJECT-TYPE
SYNTAX Integer32(10..150)
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan temperature P in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo."
::= { vrcInFanCfgEntry 22 }
vrcInFanCfgTempI OBJECT-TYPE
SYNTAX Integer32(0..900)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan temperature I in seconds"
::= { vrcInFanCfgEntry 23 }
vrcInFanCfgTempD OBJECT-TYPE
SYNTAX Integer32(0..900)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"In-fan temperature D in seconds"
::= { vrcInFanCfgEntry 24 }
--###########################################################################################--
--vrcCompPtTable--
--###########################################################################################--
vrcCompPtTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcCompPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table that contains VRC compressor status"
::= { vrc 8 }
vrcCompPtEntry OBJECT-TYPE
SYNTAX VrcCompPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcCompPtTable: each entry represents data for a VRC
compressor"
INDEX { vrcCompPtIndex }
::= { vrcCompPtTable 1 }
VrcCompPtEntry ::= SEQUENCE {
vrcCompPtIndex Integer32,
vrcCompPtName SnmpAdminString,
vrcCompPtCapacity Integer32,
vrcCompPtRunTimeHours Integer32,
vrcCompPtStartStopCount Integer32,
vrcCompPtDriverFaultU00 TruthValue,
vrcCompPtDriverFaultU01 TruthValue,
vrcCompPtDriverFaultU02 TruthValue,
vrcCompPtDriverFaultU03 TruthValue,
vrcCompPtDriverFaultU04 TruthValue,
vrcCompPtDriverFaultU05 TruthValue,
vrcCompPtDriverFaultU06 TruthValue,
vrcCompPtDriverFaultU07 TruthValue,
vrcCompPtDriverFaultU08 TruthValue,
vrcCompPtDriverFaultU09 TruthValue,
vrcCompPtDriverFaultU10 TruthValue,
vrcCompPtDriverFaultU11 TruthValue,
vrcCompPtDriverFaultU12 TruthValue,
vrcCompPtDriverFaultU13 TruthValue,
vrcCompPtDriverFaultU14 TruthValue,
vrcCompPtDriverFaultU15 TruthValue,
vrcCompPtDriverCommFailAlarm TruthValue,
vrcCompPtFaultLockAlarm TruthValue
}
vrcCompPtIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcCompPtEntry 1 }
vrcCompPtName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor name (factory-assigned)"
::= { vrcCompPtEntry 2 }
vrcCompPtCapacity OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "%"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor capacity value (percent)"
::= { vrcCompPtEntry 3 }
vrcCompPtRunTimeHours OBJECT-TYPE
SYNTAX Integer32(-32768..32767)
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor run time in hours"
::= { vrcCompPtEntry 4 }
vrcCompPtStartStopCount OBJECT-TYPE
SYNTAX Integer32(-32768..32767)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor start/stop count"
::= { vrcCompPtEntry 5 }
vrcCompPtDriverFaultU00 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U00 state"
::= { vrcCompPtEntry 6 }
vrcCompPtDriverFaultU01 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U01 state"
::= { vrcCompPtEntry 7 }
vrcCompPtDriverFaultU02 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U02 state"
::= { vrcCompPtEntry 8 }
vrcCompPtDriverFaultU03 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U03 state"
::= { vrcCompPtEntry 9 }
vrcCompPtDriverFaultU04 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U04 state"
::= { vrcCompPtEntry 10 }
vrcCompPtDriverFaultU05 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U05 state"
::= { vrcCompPtEntry 11 }
vrcCompPtDriverFaultU06 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U06 state"
::= { vrcCompPtEntry 12 }
vrcCompPtDriverFaultU07 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U07 state"
::= { vrcCompPtEntry 13 }
vrcCompPtDriverFaultU08 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U08 state"
::= { vrcCompPtEntry 14 }
vrcCompPtDriverFaultU09 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U09 state"
::= { vrcCompPtEntry 15 }
vrcCompPtDriverFaultU10 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U10 state"
::= { vrcCompPtEntry 16 }
vrcCompPtDriverFaultU11 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U11 state"
::= { vrcCompPtEntry 17 }
vrcCompPtDriverFaultU12 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U12 state"
::= { vrcCompPtEntry 18 }
vrcCompPtDriverFaultU13 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U13 state"
::= { vrcCompPtEntry 19 }
vrcCompPtDriverFaultU14 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U14 state"
::= { vrcCompPtEntry 20 }
vrcCompPtDriverFaultU15 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver fault alarm U15 state"
::= { vrcCompPtEntry 21 }
vrcCompPtDriverCommFailAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor driver communication failure alarm state"
::= { vrcCompPtEntry 22 }
vrcCompPtFaultLockAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Compressor fault lock alarm state"
::= { vrcCompPtEntry 23 }
--###########################################################################################--
--vrcCompCfgTable--
--###########################################################################################--
vrcCompCfgTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcCompCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table used for VRC compressor configuration"
::= { vrc 9 }
vrcCompCfgEntry OBJECT-TYPE
SYNTAX VrcCompCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcCompCfgTable: each entry contains config fields for a
VRC compressor"
INDEX { vrcCompCfgIndex }
::= { vrcCompCfgTable 1 }
VrcCompCfgEntry ::= SEQUENCE {
vrcCompCfgIndex Integer32,
vrcCompCfgOutputStatus TruthValue,
vrcCompCfgOutputDeadBand Integer32,
vrcCompCfgCapacityOutputValue Integer32,
vrcCompCfgMinCapacity Integer32,
vrcCompCfgStartCapacity Integer32,
vrcCompCfgStandardCapacity Integer32,
vrcCompCfgStartCfc Integer32,
vrcCompCfgStopCfc Integer32,
vrcCompCfgMinRunTime Integer32,
vrcCompCfgMinStopTime Integer32,
vrcCompCfgJumpBand1 Integer32,
vrcCompCfgJumpBand2 Integer32,
vrcCompCfgJumpBand3 Integer32,
vrcCompCfgJumpBand4 Integer32,
vrcCompCfgJumpBand5 Integer32,
vrcCompCfgJumpFreq1 Integer32,
vrcCompCfgJumpFreq2 Integer32,
vrcCompCfgJumpFreq3 Integer32,
vrcCompCfgJumpFreq4 Integer32,
vrcCompCfgJumpFreq5 Integer32,
vrcCompCfgTempP Integer32,
vrcCompCfgTempI Integer32,
vrcCompCfgTempD Integer32,
vrcCompCfgDriverFaultAlmCtrl INTEGER,
vrcCompCfgDriverCommFailAlmCtrl INTEGER,
vrcCompCfgFaultLockAlmCtrl INTEGER
}
vrcCompCfgIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcCompCfgEntry 1 }
vrcCompCfgOutputStatus OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor output status"
::= { vrcCompCfgEntry 2 }
vrcCompCfgOutputDeadBand OBJECT-TYPE
SYNTAX Integer32(0..50)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor output dead band in tenths of a percent"
::= { vrcCompCfgEntry 3 }
vrcCompCfgCapacityOutputValue OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor capacity output (percent)"
::= { vrcCompCfgEntry 4 }
vrcCompCfgMinCapacity OBJECT-TYPE
SYNTAX Integer32(15..50)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor min capacity (percent)"
::= { vrcCompCfgEntry 5 }
vrcCompCfgStartCapacity OBJECT-TYPE
SYNTAX Integer32(40..100)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor start capacity (percent)"
::= { vrcCompCfgEntry 6 }
vrcCompCfgStandardCapacity OBJECT-TYPE
SYNTAX Integer32(80..100)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor standard capacity (percent)"
::= { vrcCompCfgEntry 7 }
vrcCompCfgStartCfc OBJECT-TYPE
SYNTAX Integer32(1..100)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor start cfc (percent)"
::= { vrcCompCfgEntry 8 }
vrcCompCfgStopCfc OBJECT-TYPE
SYNTAX Integer32(-200..-50)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor stop cfc (percent)"
::= { vrcCompCfgEntry 9 }
vrcCompCfgMinRunTime OBJECT-TYPE
SYNTAX Integer32(0..30)
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor min run time in minutes"
::= { vrcCompCfgEntry 10 }
vrcCompCfgMinStopTime OBJECT-TYPE
SYNTAX Integer32(0..10)
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor min stop time in minutes"
::= { vrcCompCfgEntry 11 }
vrcCompCfgJumpBand1 OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor jump band 1 in tenths of a percent"
::= { vrcCompCfgEntry 12 }
vrcCompCfgJumpBand2 OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor jump band 2 in tenths of a percent"
::= { vrcCompCfgEntry 13 }
vrcCompCfgJumpBand3 OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor jump band 3 in tenths of a percent"
::= { vrcCompCfgEntry 14 }
vrcCompCfgJumpBand4 OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor jump band 4 in tenths of a percent"
::= { vrcCompCfgEntry 15 }
vrcCompCfgJumpBand5 OBJECT-TYPE
SYNTAX Integer32(0..100)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor jump band 5 in tenths of a percent"
::= { vrcCompCfgEntry 16 }
vrcCompCfgJumpFreq1 OBJECT-TYPE
SYNTAX Integer32(0..1000)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor jump frequency 1 in tenths of a percent"
::= { vrcCompCfgEntry 17 }
vrcCompCfgJumpFreq2 OBJECT-TYPE
SYNTAX Integer32(0..1000)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor jump frequency 2 in tenths of a percent"
::= { vrcCompCfgEntry 18 }
vrcCompCfgJumpFreq3 OBJECT-TYPE
SYNTAX Integer32(0..1000)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor jump frequency 3 in tenths of a percent"
::= { vrcCompCfgEntry 19 }
vrcCompCfgJumpFreq4 OBJECT-TYPE
SYNTAX Integer32(0..1000)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor jump frequency 4 in tenths of a percent"
::= { vrcCompCfgEntry 20 }
vrcCompCfgJumpFreq5 OBJECT-TYPE
SYNTAX Integer32(0..1000)
UNITS "0.1%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor jump frequency 5 in tenths of a percent"
::= { vrcCompCfgEntry 21 }
vrcCompCfgTempP OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor temperature P in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The settable range is determined
by the current temperature units.
Celsius: 10 to 150
Fahrenheit: 18 to 269"
::= { vrcCompCfgEntry 22 }
vrcCompCfgTempI OBJECT-TYPE
SYNTAX Integer32(0..900)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor temperature I in seconds"
::= { vrcCompCfgEntry 23 }
vrcCompCfgTempD OBJECT-TYPE
SYNTAX Integer32(0..900)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor temperature D in seconds"
::= { vrcCompCfgEntry 24 }
vrcCompCfgDriverFaultAlmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor driver fault alarm control:
2 = suspend
3 = open"
::= { vrcCompCfgEntry 25 }
vrcCompCfgDriverCommFailAlmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor driver communication failure alarm control:
2 = suspend
3 = open"
::= { vrcCompCfgEntry 26 }
vrcCompCfgFaultLockAlmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Compressor fault lock alarm control:
2 = suspend
3 = open"
::= { vrcCompCfgEntry 27 }
--###########################################################################################--
--vrcReturnPtTable--
--###########################################################################################--
vrcReturnPtTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcReturnPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table that contains VRC return status"
::= { vrc 10 }
vrcReturnPtEntry OBJECT-TYPE
SYNTAX VrcReturnPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcReturnPtTable: each entry represents return data for a
VRC"
INDEX { vrcReturnPtIndex }
::= { vrcReturnPtTable 1 }
VrcReturnPtEntry ::= SEQUENCE {
vrcReturnPtIndex Integer32,
vrcReturnPtName SnmpAdminString,
vrcReturnPtTemp Integer32,
vrcReturnPtHighTempAlarm TruthValue,
vrcReturnPtTempSensorFailAlarm TruthValue
}
vrcReturnPtIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcReturnPtEntry 1 }
vrcReturnPtName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Return name (factory-assigned)"
::= { vrcReturnPtEntry 2 }
vrcReturnPtTemp OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Return temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120"
::= { vrcReturnPtEntry 3 }
vrcReturnPtHighTempAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Return high temperature alarm state"
::= { vrcReturnPtEntry 4 }
vrcReturnPtTempSensorFailAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Return temperature sensor failure alarm state"
::= { vrcReturnPtEntry 5 }
--###########################################################################################--
--vrcReturnCfgTable--
--###########################################################################################--
vrcReturnCfgTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcReturnCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table used for VRC return configuration"
::= { vrc 11 }
vrcReturnCfgEntry OBJECT-TYPE
SYNTAX VrcReturnCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcReturnCfgTable: each entry contains config fields for
VRC return"
INDEX { vrcReturnCfgIndex }
::= { vrcReturnCfgTable 1 }
VrcReturnCfgEntry ::= SEQUENCE {
vrcReturnCfgIndex Integer32,
vrcReturnCfgOilCycle Integer32,
vrcReturnCfgOilRunCapacity Integer32,
vrcReturnCfgOilRunTime Integer32,
vrcReturnCfgTempCalValue Integer32,
vrcReturnCfgTempSetting Integer32,
vrcReturnCfgHighTempAlarmValue Integer32,
vrcReturnCfgHighTempAlarmCtrl INTEGER,
vrcReturnCfgTempSensFailAlmCtrl INTEGER
}
vrcReturnCfgIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcReturnCfgEntry 1 }
vrcReturnCfgOilCycle OBJECT-TYPE
SYNTAX Integer32(5..50)
UNITS "decihours"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Return oil cycle in tenths of an hour"
::= { vrcReturnCfgEntry 2 }
vrcReturnCfgOilRunCapacity OBJECT-TYPE
SYNTAX Integer32(50..100)
UNITS "%"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Return Oil run capacity (percent)"
::= { vrcReturnCfgEntry 3 }
vrcReturnCfgOilRunTime OBJECT-TYPE
SYNTAX Integer32(0..10)
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Return oil run time in minutes"
::= { vrcReturnCfgEntry 4 }
vrcReturnCfgTempCalValue OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Return temperature calibration value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: -100 to 100
Fahrenheit: -179 to 179"
::= { vrcReturnCfgEntry 5 }
vrcReturnCfgTempSetting OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Return temperature setting in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The settable range is determined
by the current temperature units.
Celsius: 250 to 350
Fahrenheit: 770 to 949"
::= { vrcReturnCfgEntry 6 }
vrcReturnCfgHighTempAlarmValue OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Return high temperature alarm value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: 300 to 450
Fahrenheit: 860 to 1129"
::= { vrcReturnCfgEntry 7 }
vrcReturnCfgHighTempAlarmCtrl OBJECT-TYPE
SYNTAX INTEGER {
close(1),
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Return high temperature alarm control:
1 = close
2 = suspend
3 = open"
::= { vrcReturnCfgEntry 8 }
vrcReturnCfgTempSensFailAlmCtrl OBJECT-TYPE
SYNTAX INTEGER {
close(1),
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Return temperature sensor failure alarm control:
1 = close
2 = suspend
3 = open"
::= { vrcReturnCfgEntry 9 }
--###########################################################################################--
--vrcSupplyPtTable--
--###########################################################################################--
vrcSupplyPtTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcSupplyPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table that contains VRC supply status"
::= { vrc 12 }
vrcSupplyPtEntry OBJECT-TYPE
SYNTAX VrcSupplyPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcSupplyPtTable: each entry represents supply data for a
VRC"
INDEX { vrcSupplyPtIndex }
::= { vrcSupplyPtTable 1 }
VrcSupplyPtEntry ::= SEQUENCE {
vrcSupplyPtIndex Integer32,
vrcSupplyPtName SnmpAdminString,
vrcSupplyPtTemp Integer32,
vrcSupplyPtLowTempAlarm TruthValue,
vrcSupplyPtHighTempAlarm TruthValue,
vrcSupplyPtTempSensorFailAlarm TruthValue
}
vrcSupplyPtIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcSupplyPtEntry 1 }
vrcSupplyPtName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Supply name (factory-assigned)"
::= { vrcSupplyPtEntry 2 }
vrcSupplyPtTemp OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Supply temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120"
::= { vrcSupplyPtEntry 3 }
vrcSupplyPtLowTempAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Supply low temperature alarm state"
::= { vrcSupplyPtEntry 4 }
vrcSupplyPtHighTempAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Supply high temperature alarm state"
::= { vrcSupplyPtEntry 5 }
vrcSupplyPtTempSensorFailAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Supply temperature sensor failure alarm state"
::= { vrcSupplyPtEntry 6 }
--###########################################################################################--
--vrcSupplyCfgTable--
--###########################################################################################--
vrcSupplyCfgTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcSupplyCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table used for VRC supply configuration"
::= { vrc 13 }
vrcSupplyCfgEntry OBJECT-TYPE
SYNTAX VrcSupplyCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcSupplyCfgTable: each entry contains config fields for
a VRC supply"
INDEX { vrcSupplyCfgIndex }
::= { vrcSupplyCfgTable 1 }
VrcSupplyCfgEntry ::= SEQUENCE {
vrcSupplyCfgIndex Integer32,
vrcSupplyCfgTempCalValue Integer32,
vrcSupplyCfgTempSetting Integer32,
vrcSupplyCfgLowTempAlarmValue Integer32,
vrcSupplyCfgHighTempAlarmValue Integer32,
vrcSupplyCfgLowTempAlmCtrl INTEGER,
vrcSupplyCfgHighTempAlmCtrl INTEGER,
vrcSupplyCfgTempSensFailAlmCtrl INTEGER
}
vrcSupplyCfgIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcSupplyCfgEntry 1 }
vrcSupplyCfgTempCalValue OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Supply temperature calibration value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: -100 to 100
Fahrenheit: -179 to 179"
::= { vrcSupplyCfgEntry 2 }
vrcSupplyCfgTempSetting OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Supply temperature setting in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The settable range is determined
by the current temperature units.
Celsius: 130 to 280
Fahrenheit: 554 to 823"
::= { vrcSupplyCfgEntry 3 }
vrcSupplyCfgLowTempAlarmValue OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Supply low temperature alarm value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: 50 to 200
Fahrenheit: 410 to 679"
::= { vrcSupplyCfgEntry 4 }
vrcSupplyCfgHighTempAlarmValue OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Supply high temperature alarm value in tenths of a degree. Units are
given by temperatureUnits field in deviceInfo. The settable range is
determined by the current temperature units.
Celsius: 200 to 350
Fahrenheit: 680 to 949"
::= { vrcSupplyCfgEntry 5 }
vrcSupplyCfgLowTempAlmCtrl OBJECT-TYPE
SYNTAX INTEGER {
close(1),
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Supply low temperature alarm control:
1 = close
2 = suspend
3 = open"
::= { vrcSupplyCfgEntry 6 }
vrcSupplyCfgHighTempAlmCtrl OBJECT-TYPE
SYNTAX INTEGER {
close(1),
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Supply high temperature alarm control:
1 = close
2 = suspend
3 = open"
::= { vrcSupplyCfgEntry 7 }
vrcSupplyCfgTempSensFailAlmCtrl OBJECT-TYPE
SYNTAX INTEGER {
close(1),
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Supply temperature sensor failure alarm control:
1 = close
2 = suspend
3 = open"
::= { vrcSupplyCfgEntry 8 }
--###########################################################################################--
--vrcPowerPtTable--
--###########################################################################################--
vrcPowerPtTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcPowerPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table that contains VRC power status"
::= { vrc 14 }
vrcPowerPtEntry OBJECT-TYPE
SYNTAX VrcPowerPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcPowerPtTable: each entry represents power data for a
VRC"
INDEX { vrcPowerPtIndex }
::= { vrcPowerPtTable 1 }
VrcPowerPtEntry ::= SEQUENCE {
vrcPowerPtIndex Integer32,
vrcPowerPtName SnmpAdminString,
vrcPowerPtVoltage Integer32,
vrcPowerPtFrequency Integer32,
vrcPowerPtLowVoltageAlarm TruthValue,
vrcPowerPtHighVoltageAlarm TruthValue,
vrcPowerPtLossOfPhasePowerAlarm TruthValue,
vrcPowerPtLossOfPowerAlarm TruthValue,
vrcPowerPtFrequencyErrorAlarm TruthValue
}
vrcPowerPtIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcPowerPtEntry 1 }
vrcPowerPtName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power name (factory-assigned)"
::= { vrcPowerPtEntry 2 }
vrcPowerPtVoltage OBJECT-TYPE
SYNTAX Integer32(-32768..32767)
UNITS "decivolts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power voltage measurement in tenths of a volt"
::= { vrcPowerPtEntry 3 }
vrcPowerPtFrequency OBJECT-TYPE
SYNTAX Integer32(-32768..32767)
UNITS "decihertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power frequency measurement in tenths of hertz"
::= { vrcPowerPtEntry 4 }
vrcPowerPtLowVoltageAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power low voltage alarm state"
::= { vrcPowerPtEntry 5 }
vrcPowerPtHighVoltageAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power high voltage alarm state"
::= { vrcPowerPtEntry 6 }
vrcPowerPtLossOfPhasePowerAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Phase power loss alarm state"
::= { vrcPowerPtEntry 7 }
vrcPowerPtLossOfPowerAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power loss alarm state"
::= { vrcPowerPtEntry 8 }
vrcPowerPtFrequencyErrorAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Power frequency error alarm state"
::= { vrcPowerPtEntry 9 }
--###########################################################################################--
--vrcPowerCfgTable--
--###########################################################################################--
vrcPowerCfgTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcPowerCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table used for VRC power configuration"
::= { vrc 15 }
vrcPowerCfgEntry OBJECT-TYPE
SYNTAX VrcPowerCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcPowerCfgTable: each entry contains config fields for
VRC power"
INDEX { vrcPowerCfgIndex }
::= { vrcPowerCfgTable 1 }
VrcPowerCfgEntry ::= SEQUENCE {
vrcPowerCfgIndex Integer32,
vrcPowerCfgLowVoltageSetting Integer32,
vrcPowerCfgHighVoltageSetting Integer32,
vrcPowerCfgLowVoltageAlarmCtrl INTEGER,
vrcPowerCfgHighVoltageAlarmCtrl INTEGER,
vrcPowerCfgLossOfPowerAlarmCtrl INTEGER,
vrcPowerCfgFreqErrorAlarmCtrl INTEGER
}
vrcPowerCfgIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcPowerCfgEntry 1 }
vrcPowerCfgLowVoltageSetting OBJECT-TYPE
SYNTAX Integer32(100..230)
UNITS "volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Power low voltage setting in volts"
::= { vrcPowerCfgEntry 2 }
vrcPowerCfgHighVoltageSetting OBJECT-TYPE
SYNTAX Integer32(100..300)
UNITS "volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Power high voltage setting in volts"
::= { vrcPowerCfgEntry 3 }
vrcPowerCfgLowVoltageAlarmCtrl OBJECT-TYPE
SYNTAX INTEGER {
close(1),
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Power low voltage alarm control:
1 = close
2 = suspend
3 = open"
::= { vrcPowerCfgEntry 4 }
vrcPowerCfgHighVoltageAlarmCtrl OBJECT-TYPE
SYNTAX INTEGER {
close(1),
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Power high voltage alarm control:
1 = close
2 = suspend
3 = open"
::= { vrcPowerCfgEntry 5 }
vrcPowerCfgLossOfPowerAlarmCtrl OBJECT-TYPE
SYNTAX INTEGER {
close(1),
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Power loss alarm control:
1 = close
2 = suspend
3 = open"
::= { vrcPowerCfgEntry 6 }
vrcPowerCfgFreqErrorAlarmCtrl OBJECT-TYPE
SYNTAX INTEGER {
close(1),
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Power frequency error alarm control:
1 = close
2 = suspend
3 = open"
::= { vrcPowerCfgEntry 7 }
--###########################################################################################--
--vrcOutdoorPtTable--
--###########################################################################################--
vrcOutdoorPtTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcOutdoorPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table that contains VRC outdoor status"
::= { vrc 16 }
vrcOutdoorPtEntry OBJECT-TYPE
SYNTAX VrcOutdoorPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcOutdoorPtTable: each entry represents data for a VRC
outdoor"
INDEX { vrcOutdoorPtIndex }
::= { vrcOutdoorPtTable 1 }
VrcOutdoorPtEntry ::= SEQUENCE {
vrcOutdoorPtIndex Integer32,
vrcOutdoorPtName SnmpAdminString,
vrcOutdoorPtTemp Integer32
}
vrcOutdoorPtIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcOutdoorPtEntry 1 }
vrcOutdoorPtName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Outdoor name (factory-assigned)"
::= { vrcOutdoorPtEntry 2 }
vrcOutdoorPtTemp OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Outdoor temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120"
::= { vrcOutdoorPtEntry 3 }
--###########################################################################################--
--vrcDischPtTable--
--###########################################################################################--
vrcDischPtTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcDischPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table that contains VRC discharge status"
::= { vrc 18 }
vrcDischPtEntry OBJECT-TYPE
SYNTAX VrcDischPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcDischPtTable: each entry represents discharge data for
a VRC"
INDEX { vrcDischPtIndex }
::= { vrcDischPtTable 1 }
VrcDischPtEntry ::= SEQUENCE {
vrcDischPtIndex Integer32,
vrcDischPtName SnmpAdminString,
vrcDischPtTemp Integer32,
vrcDischPtPressure Integer32,
vrcDischPtHighTempAlarm TruthValue,
vrcDischPtHighTempFreqAlarm TruthValue,
vrcDischPtTempSensorFailAlarm TruthValue
}
vrcDischPtIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcDischPtEntry 1 }
vrcDischPtName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Discharge name (factory-assigned)"
::= { vrcDischPtEntry 2 }
vrcDischPtTemp OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Discharge temperature value in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1560
Fahrenheit: -400 to 3128"
::= { vrcDischPtEntry 3 }
vrcDischPtPressure OBJECT-TYPE
SYNTAX Integer32(0..460)
UNITS "decibars"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Discharge air pressure value in tenths of a bar"
::= { vrcDischPtEntry 4 }
vrcDischPtHighTempAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Discharge high temperature alarm state"
::= { vrcDischPtEntry 5 }
vrcDischPtHighTempFreqAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Discharge high temperature frequently alarm state"
::= { vrcDischPtEntry 6 }
vrcDischPtTempSensorFailAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Discharge temperature sensor failure alarm state"
::= { vrcDischPtEntry 7 }
--###########################################################################################--
--vrcDischCfgTable--
--###########################################################################################--
vrcDischCfgTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcDischCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table used for VRC discharge configuration"
::= { vrc 19 }
vrcDischCfgEntry OBJECT-TYPE
SYNTAX VrcDischCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcDischCfgTable: each entry contains config fields for
VRC discharge"
INDEX { vrcDischCfgIndex }
::= { vrcDischCfgTable 1 }
VrcDischCfgEntry ::= SEQUENCE {
vrcDischCfgIndex Integer32,
vrcDischCfgTempCalValue Integer32,
vrcDischCfgPressCalValue Integer32,
vrcDischCfgHighTempAlmCtrl INTEGER,
vrcDischCfgHighTempFreqAlmCtrl INTEGER,
vrcDischCfgTempSensFailAlmCtrl INTEGER
}
vrcDischCfgIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcDischCfgEntry 1 }
vrcDischCfgTempCalValue OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Discharge temperature calibration value in tenths of a degree. Units
are given by temperatureUnits field in deviceInfo. The settable range
is determined by the current temperature units.
Celsius: -100 to 100
Fahrenheit: -179 to 179"
::= { vrcDischCfgEntry 2 }
vrcDischCfgPressCalValue OBJECT-TYPE
SYNTAX Integer32(-100..100)
UNITS "decibars"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Discharge pressure calibration value in tenths of a bar"
::= { vrcDischCfgEntry 3 }
vrcDischCfgHighTempAlmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Discharge high temperature alarm control:
2 = suspend
3 = open"
::= { vrcDischCfgEntry 4 }
vrcDischCfgHighTempFreqAlmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Discharge high temperature frequenctly alarm control:
2 = suspend
3 = open"
::= { vrcDischCfgEntry 5 }
vrcDischCfgTempSensFailAlmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Discharge temperature sensor failure alarm control:
2 = suspend
3 = open"
::= { vrcDischCfgEntry 6 }
--###########################################################################################--
--vrcSuctPtTable--
--###########################################################################################--
vrcSuctPtTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcSuctPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table that contains VRC suction status"
::= { vrc 20 }
vrcSuctPtEntry OBJECT-TYPE
SYNTAX VrcSuctPtEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcSuctPtTable: each entry represents suction data for a
VRC"
INDEX { vrcSuctPtIndex }
::= { vrcSuctPtTable 1 }
VrcSuctPtEntry ::= SEQUENCE {
vrcSuctPtIndex Integer32,
vrcSuctPtName SnmpAdminString,
vrcSuctPtTemp Integer32,
vrcSuctPtPressure Integer32,
vrcSuctPtSuperHeatTemp Integer32,
vrcSuctPtTempSensorFailAlarm TruthValue
}
vrcSuctPtIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcSuctPtEntry 1 }
vrcSuctPtName OBJECT-TYPE
SYNTAX SnmpAdminString(SIZE (1..25))
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Suction name (factory-assigned)"
::= { vrcSuctPtEntry 2 }
vrcSuctPtTemp OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Suction temperature in tenths of a degree. Units are given by
temperatureUnits field in deviceInfo. The range is determined by the
current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120"
::= { vrcSuctPtEntry 3 }
vrcSuctPtPressure OBJECT-TYPE
SYNTAX Integer32(0..173)
UNITS "decibars"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Suction air pressure in tenths of a bar"
::= { vrcSuctPtEntry 4 }
vrcSuctPtSuperHeatTemp OBJECT-TYPE
SYNTAX Integer32
UNITS "decidegrees"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Suction super heat temperature in tenths of a degree. Units are given
by temperatureUnits field in deviceInfo. The range is determined by
the current temperature units.
Celsius: -400 to 1000
Fahrenheit: -400 to 2120"
::= { vrcSuctPtEntry 5 }
vrcSuctPtTempSensorFailAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Suction temperature sensor failure alarm state"
::= { vrcSuctPtEntry 6 }
--###########################################################################################--
--vrcSuctCfgTable--
--###########################################################################################--
vrcSuctCfgTable OBJECT-TYPE
SYNTAX SEQUENCE OF VrcSuctCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Table used for VRC suction configuration"
::= { vrc 21 }
vrcSuctCfgEntry OBJECT-TYPE
SYNTAX VrcSuctCfgEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Entry in the vrcSuctCfgTable: each entry contains config fields for
VRC suction"
INDEX { vrcSuctCfgIndex }
::= { vrcSuctCfgTable 1 }
VrcSuctCfgEntry ::= SEQUENCE {
vrcSuctCfgIndex Integer32,
vrcSuctCfgPressCalValue Integer32,
vrcSuctCfgTempSensFailAlmCtrl INTEGER
}
vrcSuctCfgIndex OBJECT-TYPE
SYNTAX Integer32(1..100)
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Unique id for each entry in the table"
::= { vrcSuctCfgEntry 1 }
vrcSuctCfgPressCalValue OBJECT-TYPE
SYNTAX Integer32(-100..100)
UNITS "decibars"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Suction pressure calibration value in tenths of a bar"
::= { vrcSuctCfgEntry 2 }
vrcSuctCfgTempSensFailAlmCtrl OBJECT-TYPE
SYNTAX INTEGER {
suspend(2),
open(3)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Suction temperature sensor failure alarm control:
2 = suspend
3 = open"
::= { vrcSuctCfgEntry 3 }
--###########################################################################################--
--Notifications--
--###########################################################################################--
trap OBJECT IDENTIFIER ::= { imd 32767 }
trapPrefix OBJECT IDENTIFIER ::= { trap 0 }
trapObj OBJECT IDENTIFIER ::= { trap 1 }
trapSeverity OBJECT-TYPE
SYNTAX INTEGER {
none(0),
warning(1),
alarm(2)
}
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Indicates the severity of the trap:
0 = None
1 = Warning
2 = Alarm"
::= { trapObj 1 }
trapThreshType OBJECT-TYPE
SYNTAX INTEGER {
low(1),
high(2)
}
MAX-ACCESS accessible-for-notify
STATUS current
DESCRIPTION
"Only sent for threshold alarms. Identifies the threshold type:
1 = Low
2 = High"
::= { trapObj 2 }
internalTestNOTIFY NOTIFICATION-TYPE
STATUS current
DESCRIPTION "Test SNMP Trap"
::= { trapPrefix 10101 }
--#####deviceInfo#####--
--#####pdu#####--
--#####pduMainTable#####--
pduMainAvailNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduMainAvail,
trapSeverity,
sysName,
pduMainLabel
}
STATUS current
DESCRIPTION "PDU availability trap"
::= { trapPrefix 10305 }
pduMainAvailCLEAR NOTIFICATION-TYPE
OBJECTS {
pduMainAvail,
trapSeverity,
sysName,
pduMainLabel
}
STATUS current
DESCRIPTION "PDU availability clear trap"
::= { trapPrefix 20305 }
pduTotalRealPowerNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduTotalRealPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduTotalLabel
}
STATUS current
DESCRIPTION "PDU total real power trap"
::= { trapPrefix 10309 }
pduTotalRealPowerCLEAR NOTIFICATION-TYPE
OBJECTS {
pduTotalRealPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduTotalLabel
}
STATUS current
DESCRIPTION "PDU total real power clear trap"
::= { trapPrefix 20309 }
pduTotalApparentPowerNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduTotalApparentPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduTotalLabel
}
STATUS current
DESCRIPTION "PDU total apparent power trap"
::= { trapPrefix 10310 }
pduTotalApparentPowerCLEAR NOTIFICATION-TYPE
OBJECTS {
pduTotalApparentPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduTotalLabel
}
STATUS current
DESCRIPTION "PDU total apparent power clear trap"
::= { trapPrefix 20310 }
pduTotalPowerFactorNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduTotalPowerFactor,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduTotalLabel
}
STATUS current
DESCRIPTION "PDU total power factor trap"
::= { trapPrefix 10311 }
pduTotalPowerFactorCLEAR NOTIFICATION-TYPE
OBJECTS {
pduTotalPowerFactor,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduTotalLabel
}
STATUS current
DESCRIPTION "PDU total power factor clear trap"
::= { trapPrefix 20311 }
pduTotalEnergyNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduTotalEnergy,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduTotalLabel
}
STATUS current
DESCRIPTION "PDU total energy trap"
::= { trapPrefix 10312 }
pduTotalEnergyCLEAR NOTIFICATION-TYPE
OBJECTS {
pduTotalEnergy,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduTotalLabel
}
STATUS current
DESCRIPTION "PDU total energy clear trap"
::= { trapPrefix 20312 }
--#####pduPhaseTable#####--
pduPhaseVoltageNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduPhaseVoltage,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase voltage trap"
::= { trapPrefix 10324 }
pduPhaseVoltageCLEAR NOTIFICATION-TYPE
OBJECTS {
pduPhaseVoltage,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase voltage clear trap"
::= { trapPrefix 20324 }
pduPhaseCurrentNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduPhaseCurrent,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase current trap"
::= { trapPrefix 10328 }
pduPhaseCurrentCLEAR NOTIFICATION-TYPE
OBJECTS {
pduPhaseCurrent,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase current clear trap"
::= { trapPrefix 20328 }
pduPhaseRealPowerNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduPhaseRealPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase real power trap"
::= { trapPrefix 10332 }
pduPhaseRealPowerCLEAR NOTIFICATION-TYPE
OBJECTS {
pduPhaseRealPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase real power clear trap"
::= { trapPrefix 20332 }
pduPhaseApparentPowerNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduPhaseApparentPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase apparent power trap"
::= { trapPrefix 10333 }
pduPhaseApparentPowerCLEAR NOTIFICATION-TYPE
OBJECTS {
pduPhaseApparentPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase apparent power clear trap"
::= { trapPrefix 20333 }
pduPhasePowerFactorNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduPhasePowerFactor,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase power factor trap"
::= { trapPrefix 10334 }
pduPhasePowerFactorCLEAR NOTIFICATION-TYPE
OBJECTS {
pduPhasePowerFactor,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase power factor clear trap"
::= { trapPrefix 20334 }
pduPhaseEnergyNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduPhaseEnergy,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase energy trap"
::= { trapPrefix 10335 }
pduPhaseEnergyCLEAR NOTIFICATION-TYPE
OBJECTS {
pduPhaseEnergy,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase energy clear trap"
::= { trapPrefix 20335 }
pduPhaseBalanceNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduPhaseBalance,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase balance trap"
::= { trapPrefix 10337 }
pduPhaseBalanceCLEAR NOTIFICATION-TYPE
OBJECTS {
pduPhaseBalance,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase balance clear trap"
::= { trapPrefix 20337 }
pduPhaseCurrentCrestFactorNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduPhaseCurrentCrestFactor,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase current crest factor trap"
::= { trapPrefix 10339 }
pduPhaseCurrentCrestFactorCLEAR NOTIFICATION-TYPE
OBJECTS {
pduPhaseCurrentCrestFactor,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduPhaseLabel
}
STATUS current
DESCRIPTION "PDU phase current crest factor clear trap"
::= { trapPrefix 20339 }
--#####pduBreakerTable#####--
pduBreakerCurrentNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduBreakerCurrent,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduBreakerLabel
}
STATUS current
DESCRIPTION "PDU breaker current trap"
::= { trapPrefix 10354 }
pduBreakerCurrentCLEAR NOTIFICATION-TYPE
OBJECTS {
pduBreakerCurrent,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduBreakerLabel
}
STATUS current
DESCRIPTION "PDU breaker current clear trap"
::= { trapPrefix 20354 }
pduBreakerVoltageNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduBreakerVoltage,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduBreakerLabel
}
STATUS current
DESCRIPTION "PDU breaker voltage trap"
::= { trapPrefix 10358 }
pduBreakerVoltageCLEAR NOTIFICATION-TYPE
OBJECTS {
pduBreakerVoltage,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduBreakerLabel
}
STATUS current
DESCRIPTION "PDU breaker voltage clear trap"
::= { trapPrefix 20358 }
pduBreakerRealPowerNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduBreakerRealPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduBreakerLabel
}
STATUS current
DESCRIPTION "PDU breaker real power trap"
::= { trapPrefix 10362 }
pduBreakerRealPowerCLEAR NOTIFICATION-TYPE
OBJECTS {
pduBreakerRealPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduBreakerLabel
}
STATUS current
DESCRIPTION "PDU breaker real power clear trap"
::= { trapPrefix 20362 }
pduBreakerApparentPowerNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduBreakerApparentPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduBreakerLabel
}
STATUS current
DESCRIPTION "PDU breaker apparent power trap"
::= { trapPrefix 10363 }
pduBreakerApparentPowerCLEAR NOTIFICATION-TYPE
OBJECTS {
pduBreakerApparentPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduBreakerLabel
}
STATUS current
DESCRIPTION "PDU breaker apparent power clear trap"
::= { trapPrefix 20363 }
pduBreakerPowerFactorNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduBreakerPowerFactor,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduBreakerLabel
}
STATUS current
DESCRIPTION "PDU breaker power factor trap"
::= { trapPrefix 10364 }
pduBreakerPowerFactorCLEAR NOTIFICATION-TYPE
OBJECTS {
pduBreakerPowerFactor,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduBreakerLabel
}
STATUS current
DESCRIPTION "PDU breaker power factor clear trap"
::= { trapPrefix 20364 }
pduBreakerEnergyNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduBreakerEnergy,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduBreakerLabel
}
STATUS current
DESCRIPTION "PDU breaker energy trap"
::= { trapPrefix 10365 }
pduBreakerEnergyCLEAR NOTIFICATION-TYPE
OBJECTS {
pduBreakerEnergy,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduBreakerLabel
}
STATUS current
DESCRIPTION "PDU breaker energy clear trap"
::= { trapPrefix 20365 }
--#####pduLineTable#####--
pduLineCurrentNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduLineCurrent,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduLineLabel
}
STATUS current
DESCRIPTION "PDU line current trap"
::= { trapPrefix 10374 }
pduLineCurrentCLEAR NOTIFICATION-TYPE
OBJECTS {
pduLineCurrent,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduLineLabel
}
STATUS current
DESCRIPTION "PDU line current clear trap"
::= { trapPrefix 20374 }
--#####pduOutletSwitchTable#####--
--#####pduOutletMeterTable#####--
pduOutletMeterVoltageNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduOutletMeterVoltage,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduOutletMeterLabel
}
STATUS current
DESCRIPTION "PDU outlet voltage trap"
::= { trapPrefix 10385 }
pduOutletMeterVoltageCLEAR NOTIFICATION-TYPE
OBJECTS {
pduOutletMeterVoltage,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduOutletMeterLabel
}
STATUS current
DESCRIPTION "PDU outlet voltage clear trap"
::= { trapPrefix 20385 }
pduOutletMeterCurrentNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduOutletMeterCurrent,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduOutletMeterLabel
}
STATUS current
DESCRIPTION "PDU outlet current trap"
::= { trapPrefix 10389 }
pduOutletMeterCurrentCLEAR NOTIFICATION-TYPE
OBJECTS {
pduOutletMeterCurrent,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduOutletMeterLabel
}
STATUS current
DESCRIPTION "PDU outlet current clear trap"
::= { trapPrefix 20389 }
pduOutletMeterRealPowerNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduOutletMeterRealPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduOutletMeterLabel
}
STATUS current
DESCRIPTION "PDU outlet real power trap"
::= { trapPrefix 10393 }
pduOutletMeterRealPowerCLEAR NOTIFICATION-TYPE
OBJECTS {
pduOutletMeterRealPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduOutletMeterLabel
}
STATUS current
DESCRIPTION "PDU outlet real power clear trap"
::= { trapPrefix 20393 }
pduOutletMeterApparentPowerNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduOutletMeterApparentPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduOutletMeterLabel
}
STATUS current
DESCRIPTION "PDU outlet apparent power trap"
::= { trapPrefix 10394 }
pduOutletMeterApparentPowerCLEAR NOTIFICATION-TYPE
OBJECTS {
pduOutletMeterApparentPower,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduOutletMeterLabel
}
STATUS current
DESCRIPTION "PDU outlet apparent power clear trap"
::= { trapPrefix 20394 }
pduOutletMeterPowerFactorNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduOutletMeterPowerFactor,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduOutletMeterLabel
}
STATUS current
DESCRIPTION "PDU outlet power factor trap"
::= { trapPrefix 10395 }
pduOutletMeterPowerFactorCLEAR NOTIFICATION-TYPE
OBJECTS {
pduOutletMeterPowerFactor,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduOutletMeterLabel
}
STATUS current
DESCRIPTION "PDU outlet power factor clear trap"
::= { trapPrefix 20395 }
pduOutletMeterEnergyNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduOutletMeterEnergy,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduOutletMeterLabel
}
STATUS current
DESCRIPTION "PDU outlet energy trap"
::= { trapPrefix 10396 }
pduOutletMeterEnergyCLEAR NOTIFICATION-TYPE
OBJECTS {
pduOutletMeterEnergy,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduOutletMeterLabel
}
STATUS current
DESCRIPTION "PDU outlet energy clear trap"
::= { trapPrefix 20396 }
pduOutletCurrentCrestFactorNOTIFY NOTIFICATION-TYPE
OBJECTS {
pduOutletCurrentCrestFactor,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduOutletMeterLabel
}
STATUS current
DESCRIPTION "PDU outlet current crest factor trap"
::= { trapPrefix 10400 }
pduOutletCurrentCrestFactorCLEAR NOTIFICATION-TYPE
OBJECTS {
pduOutletCurrentCrestFactor,
trapThreshType,
trapSeverity,
sysName,
pduMainLabel,
pduOutletMeterLabel
}
STATUS current
DESCRIPTION "PDU outlet current crest factor clear trap"
::= { trapPrefix 20400 }
--#####tempSensorTable#####--
tempSensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS {
tempSensorAvail,
trapSeverity,
sysName,
tempSensorLabel
}
STATUS current
DESCRIPTION "RT availability trap"
::= { trapPrefix 10404 }
tempSensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS {
tempSensorAvail,
trapSeverity,
sysName,
tempSensorLabel
}
STATUS current
DESCRIPTION "RT availability clear trap"
::= { trapPrefix 20404 }
tempSensorTempNOTIFY NOTIFICATION-TYPE
OBJECTS {
tempSensorTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
tempSensorLabel
}
STATUS current
DESCRIPTION "RT temperature trap"
::= { trapPrefix 10405 }
tempSensorTempCLEAR NOTIFICATION-TYPE
OBJECTS {
tempSensorTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
tempSensorLabel
}
STATUS current
DESCRIPTION "RT temperature clear trap"
::= { trapPrefix 20405 }
--#####airFlowSensorTable#####--
airFlowSensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS {
airFlowSensorAvail,
trapSeverity,
sysName,
airFlowSensorLabel
}
STATUS current
DESCRIPTION "AFHT3 availability trap"
::= { trapPrefix 10504 }
airFlowSensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS {
airFlowSensorAvail,
trapSeverity,
sysName,
airFlowSensorLabel
}
STATUS current
DESCRIPTION "AFHT3 availability clear trap"
::= { trapPrefix 20504 }
airFlowSensorTempNOTIFY NOTIFICATION-TYPE
OBJECTS {
airFlowSensorTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
airFlowSensorLabel
}
STATUS current
DESCRIPTION "AFHT3 temperature trap"
::= { trapPrefix 10505 }
airFlowSensorTempCLEAR NOTIFICATION-TYPE
OBJECTS {
airFlowSensorTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
airFlowSensorLabel
}
STATUS current
DESCRIPTION "AFHT3 temperature clear trap"
::= { trapPrefix 20505 }
airFlowSensorFlowNOTIFY NOTIFICATION-TYPE
OBJECTS {
airFlowSensorFlow,
trapThreshType,
trapSeverity,
sysName,
airFlowSensorLabel
}
STATUS current
DESCRIPTION "AFHT3 airflow trap"
::= { trapPrefix 10506 }
airFlowSensorFlowCLEAR NOTIFICATION-TYPE
OBJECTS {
airFlowSensorFlow,
trapThreshType,
trapSeverity,
sysName,
airFlowSensorLabel
}
STATUS current
DESCRIPTION "AFHT3 airflow clear trap"
::= { trapPrefix 20506 }
airFlowSensorHumidityNOTIFY NOTIFICATION-TYPE
OBJECTS {
airFlowSensorHumidity,
trapThreshType,
trapSeverity,
sysName,
airFlowSensorLabel
}
STATUS current
DESCRIPTION "AFHT3 humidity trap"
::= { trapPrefix 10507 }
airFlowSensorHumidityCLEAR NOTIFICATION-TYPE
OBJECTS {
airFlowSensorHumidity,
trapThreshType,
trapSeverity,
sysName,
airFlowSensorLabel
}
STATUS current
DESCRIPTION "AFHT3 humidity clear trap"
::= { trapPrefix 20507 }
airFlowSensorDewPointNOTIFY NOTIFICATION-TYPE
OBJECTS {
airFlowSensorDewPoint,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
airFlowSensorLabel
}
STATUS current
DESCRIPTION "AFHT3 dewpoint trap"
::= { trapPrefix 10508 }
airFlowSensorDewPointCLEAR NOTIFICATION-TYPE
OBJECTS {
airFlowSensorDewPoint,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
airFlowSensorLabel
}
STATUS current
DESCRIPTION "AFHT3 dewpoint clear trap"
::= { trapPrefix 20508 }
--#####t3hdSensorTable#####--
t3hdSensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS {
t3hdSensorAvail,
trapSeverity,
sysName,
t3hdSensorLabel
}
STATUS current
DESCRIPTION "T3HD availability trap"
::= { trapPrefix 10804 }
t3hdSensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS {
t3hdSensorAvail,
trapSeverity,
sysName,
t3hdSensorLabel
}
STATUS current
DESCRIPTION "T3HD availability clear trap"
::= { trapPrefix 20804 }
t3hdSensorIntTempNOTIFY NOTIFICATION-TYPE
OBJECTS {
t3hdSensorIntTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
t3hdSensorLabel,
t3hdSensorIntLabel
}
STATUS current
DESCRIPTION "T3HD Internal temperature trap"
::= { trapPrefix 10806 }
t3hdSensorIntTempCLEAR NOTIFICATION-TYPE
OBJECTS {
t3hdSensorIntTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
t3hdSensorLabel,
t3hdSensorIntLabel
}
STATUS current
DESCRIPTION "T3HD Internal temperature clear trap"
::= { trapPrefix 20806 }
t3hdSensorIntHumidityNOTIFY NOTIFICATION-TYPE
OBJECTS {
t3hdSensorIntHumidity,
trapThreshType,
trapSeverity,
sysName,
t3hdSensorLabel,
t3hdSensorIntLabel
}
STATUS current
DESCRIPTION "T3HD Internal humidity trap"
::= { trapPrefix 10807 }
t3hdSensorIntHumidityCLEAR NOTIFICATION-TYPE
OBJECTS {
t3hdSensorIntHumidity,
trapThreshType,
trapSeverity,
sysName,
t3hdSensorLabel,
t3hdSensorIntLabel
}
STATUS current
DESCRIPTION "T3HD Internal humidity clear trap"
::= { trapPrefix 20807 }
t3hdSensorIntDewPointNOTIFY NOTIFICATION-TYPE
OBJECTS {
t3hdSensorIntDewPoint,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
t3hdSensorLabel,
t3hdSensorIntLabel
}
STATUS current
DESCRIPTION "T3HD Internal dewpoint trap"
::= { trapPrefix 10808 }
t3hdSensorIntDewPointCLEAR NOTIFICATION-TYPE
OBJECTS {
t3hdSensorIntDewPoint,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
t3hdSensorLabel,
t3hdSensorIntLabel
}
STATUS current
DESCRIPTION "T3HD Internal dewpoint clear trap"
::= { trapPrefix 20808 }
t3hdSensorExtATempNOTIFY NOTIFICATION-TYPE
OBJECTS {
t3hdSensorExtATemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
t3hdSensorLabel,
t3hdSensorExtALabel
}
STATUS current
DESCRIPTION "T3HD External A temperature trap"
::= { trapPrefix 10811 }
t3hdSensorExtATempCLEAR NOTIFICATION-TYPE
OBJECTS {
t3hdSensorExtATemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
t3hdSensorLabel,
t3hdSensorExtALabel
}
STATUS current
DESCRIPTION "T3HD External A temperature clear trap"
::= { trapPrefix 20811 }
t3hdSensorExtBTempNOTIFY NOTIFICATION-TYPE
OBJECTS {
t3hdSensorExtBTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
t3hdSensorLabel,
t3hdSensorExtBLabel
}
STATUS current
DESCRIPTION "T3HD External B temperature trap"
::= { trapPrefix 10814 }
t3hdSensorExtBTempCLEAR NOTIFICATION-TYPE
OBJECTS {
t3hdSensorExtBTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
t3hdSensorLabel,
t3hdSensorExtBLabel
}
STATUS current
DESCRIPTION "T3HD External B temperature clear trap"
::= { trapPrefix 20814 }
--#####thdSensorTable#####--
thdSensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS {
thdSensorAvail,
trapSeverity,
sysName,
thdSensorLabel
}
STATUS current
DESCRIPTION "THD availability trap"
::= { trapPrefix 10904 }
thdSensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS {
thdSensorAvail,
trapSeverity,
sysName,
thdSensorLabel
}
STATUS current
DESCRIPTION "THD availability clear trap"
::= { trapPrefix 20904 }
thdSensorTempNOTIFY NOTIFICATION-TYPE
OBJECTS {
thdSensorTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
thdSensorLabel
}
STATUS current
DESCRIPTION "THD temperature trap"
::= { trapPrefix 10905 }
thdSensorTempCLEAR NOTIFICATION-TYPE
OBJECTS {
thdSensorTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
thdSensorLabel
}
STATUS current
DESCRIPTION "THD temperature clear trap"
::= { trapPrefix 20905 }
thdSensorHumidityNOTIFY NOTIFICATION-TYPE
OBJECTS {
thdSensorHumidity,
trapThreshType,
trapSeverity,
sysName,
thdSensorLabel
}
STATUS current
DESCRIPTION "THD humidity trap"
::= { trapPrefix 10906 }
thdSensorHumidityCLEAR NOTIFICATION-TYPE
OBJECTS {
thdSensorHumidity,
trapThreshType,
trapSeverity,
sysName,
thdSensorLabel
}
STATUS current
DESCRIPTION "THD humidity clear trap"
::= { trapPrefix 20906 }
thdSensorDewPointNOTIFY NOTIFICATION-TYPE
OBJECTS {
thdSensorDewPoint,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
thdSensorLabel
}
STATUS current
DESCRIPTION "THD dewpoint trap"
::= { trapPrefix 10907 }
thdSensorDewPointCLEAR NOTIFICATION-TYPE
OBJECTS {
thdSensorDewPoint,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
thdSensorLabel
}
STATUS current
DESCRIPTION "THD dewpoint clear trap"
::= { trapPrefix 20907 }
--#####a2dSensorTable#####--
a2dSensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS {
a2dSensorAvail,
trapSeverity,
sysName,
a2dSensorLabel
}
STATUS current
DESCRIPTION "A2D availability trap"
::= { trapPrefix 11104 }
a2dSensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS {
a2dSensorAvail,
trapSeverity,
sysName,
a2dSensorLabel
}
STATUS current
DESCRIPTION "A2D availability clear trap"
::= { trapPrefix 21104 }
a2dSensorValueNOTIFY NOTIFICATION-TYPE
OBJECTS {
a2dSensorValue,
trapThreshType,
trapSeverity,
sysName,
a2dSensorLabel,
a2dSensorAnalogLabel,
a2dSensorDisplayValue
}
STATUS current
DESCRIPTION "A2D measurement trap"
::= { trapPrefix 11105 }
a2dSensorValueCLEAR NOTIFICATION-TYPE
OBJECTS {
a2dSensorValue,
trapThreshType,
trapSeverity,
sysName,
a2dSensorLabel,
a2dSensorAnalogLabel,
a2dSensorDisplayValue
}
STATUS current
DESCRIPTION "A2D measurement clear trap"
::= { trapPrefix 21105 }
--#####humiditySensorTable#####--
humiditySensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS {
humiditySensorAvail,
trapSeverity,
sysName,
humiditySensorLabel
}
STATUS current
DESCRIPTION "Remote humidity availability trap"
::= { trapPrefix 11204 }
humiditySensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS {
humiditySensorAvail,
trapSeverity,
sysName,
humiditySensorLabel
}
STATUS current
DESCRIPTION "Remote humidity availability clear trap"
::= { trapPrefix 21204 }
humiditySensorValueNOTIFY NOTIFICATION-TYPE
OBJECTS {
humiditySensorValue,
trapThreshType,
trapSeverity,
sysName,
humiditySensorLabel
}
STATUS current
DESCRIPTION "Remote humidity value trap"
::= { trapPrefix 11205 }
humiditySensorValueCLEAR NOTIFICATION-TYPE
OBJECTS {
humiditySensorValue,
trapThreshType,
trapSeverity,
sysName,
humiditySensorLabel
}
STATUS current
DESCRIPTION "Remote humidity value clear trap"
::= { trapPrefix 21205 }
--#####sn2dSensorTable#####--
sn2dSensorAvailNOTIFY NOTIFICATION-TYPE
OBJECTS {
sn2dSensorAvail,
trapSeverity,
sysName,
sn2dSensorLabel
}
STATUS current
DESCRIPTION "SN-2D availability trap"
::= { trapPrefix 11304 }
sn2dSensorAvailCLEAR NOTIFICATION-TYPE
OBJECTS {
sn2dSensorAvail,
trapSeverity,
sysName,
sn2dSensorLabel
}
STATUS current
DESCRIPTION "SN-2D availability clear trap"
::= { trapPrefix 21304 }
sn2dSensorDoor1StateNOTIFY NOTIFICATION-TYPE
OBJECTS {
sn2dSensorDoor1State,
trapThreshType,
trapSeverity,
sysName,
sn2dSensorLabel,
sn2dSensorDoor1Label,
sn2dSensorDoor1DisplayState
}
STATUS current
DESCRIPTION "SN-2D Door switch 1 state trap"
::= { trapPrefix 11306 }
sn2dSensorDoor1StateCLEAR NOTIFICATION-TYPE
OBJECTS {
sn2dSensorDoor1State,
trapThreshType,
trapSeverity,
sysName,
sn2dSensorLabel,
sn2dSensorDoor1Label,
sn2dSensorDoor1DisplayState
}
STATUS current
DESCRIPTION "SN-2D Door switch 1 state clear trap"
::= { trapPrefix 21306 }
sn2dSensorDoor2StateNOTIFY NOTIFICATION-TYPE
OBJECTS {
sn2dSensorDoor2State,
trapThreshType,
trapSeverity,
sysName,
sn2dSensorLabel,
sn2dSensorDoor2Label,
sn2dSensorDoor2DisplayState
}
STATUS current
DESCRIPTION "SN-2D Door switch 2 state trap"
::= { trapPrefix 11309 }
sn2dSensorDoor2StateCLEAR NOTIFICATION-TYPE
OBJECTS {
sn2dSensorDoor2State,
trapThreshType,
trapSeverity,
sysName,
sn2dSensorLabel,
sn2dSensorDoor2Label,
sn2dSensorDoor2DisplayState
}
STATUS current
DESCRIPTION "SN-2D Door switch 2 state clear trap"
::= { trapPrefix 21309 }
--#####cooling#####--
--#####vrc#####--
--#####vrcMainTable#####--
vrcMainAvailNOTIFY NOTIFICATION-TYPE
OBJECTS {
vrcMainAvail,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC availability trap"
::= { trapPrefix 13001 }
vrcMainAvailCLEAR NOTIFICATION-TYPE
OBJECTS {
vrcMainAvail,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC availability clear trap"
::= { trapPrefix 23001 }
--#####vrcMainPtTable#####--
--#####vrcMainCfgTable#####--
--#####vrcOutFanPtTable#####--
vrcOutFanPtSpeedNOTIFY NOTIFICATION-TYPE
OBJECTS {
vrcOutFanPtSpeed,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC out-fan speed trap"
::= { trapPrefix 13002 }
vrcOutFanPtSpeedCLEAR NOTIFICATION-TYPE
OBJECTS {
vrcOutFanPtSpeed,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC out-fan speed clear trap"
::= { trapPrefix 23002 }
--#####vrcOutFanCfgTable#####--
--#####vrcInFanPtTable#####--
--#####vrcInFanCfgTable#####--
--#####vrcCompPtTable#####--
vrcCompPtCapacityNOTIFY NOTIFICATION-TYPE
OBJECTS {
vrcCompPtCapacity,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC compressor capacity trap"
::= { trapPrefix 13003 }
vrcCompPtCapacityCLEAR NOTIFICATION-TYPE
OBJECTS {
vrcCompPtCapacity,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC compressor capacity clear trap"
::= { trapPrefix 23003 }
--#####vrcCompCfgTable#####--
--#####vrcReturnPtTable#####--
vrcReturnPtTempNOTIFY NOTIFICATION-TYPE
OBJECTS {
vrcReturnPtTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC return temperature trap"
::= { trapPrefix 13004 }
vrcReturnPtTempCLEAR NOTIFICATION-TYPE
OBJECTS {
vrcReturnPtTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC return temperature clear trap"
::= { trapPrefix 23004 }
--#####vrcReturnCfgTable#####--
--#####vrcSupplyPtTable#####--
vrcSupplyPtTempNOTIFY NOTIFICATION-TYPE
OBJECTS {
vrcSupplyPtTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC supply temperature trap"
::= { trapPrefix 13005 }
vrcSupplyPtTempCLEAR NOTIFICATION-TYPE
OBJECTS {
vrcSupplyPtTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC supply temperature clear trap"
::= { trapPrefix 23005 }
--#####vrcSupplyCfgTable#####--
--#####vrcPowerPtTable#####--
vrcPowerPtVoltageNOTIFY NOTIFICATION-TYPE
OBJECTS {
vrcPowerPtVoltage,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC power voltage trap"
::= { trapPrefix 13006 }
vrcPowerPtVoltageCLEAR NOTIFICATION-TYPE
OBJECTS {
vrcPowerPtVoltage,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC power voltage clear trap"
::= { trapPrefix 23006 }
vrcPowerPtFrequencyNOTIFY NOTIFICATION-TYPE
OBJECTS {
vrcPowerPtFrequency,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC power frequency trap"
::= { trapPrefix 13007 }
vrcPowerPtFrequencyCLEAR NOTIFICATION-TYPE
OBJECTS {
vrcPowerPtFrequency,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC power frequency clear trap"
::= { trapPrefix 23007 }
--#####vrcPowerCfgTable#####--
--#####vrcOutdoorPtTable#####--
vrcOutdoorPtTempNOTIFY NOTIFICATION-TYPE
OBJECTS {
vrcOutdoorPtTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC outdoor temperature trap"
::= { trapPrefix 13008 }
vrcOutdoorPtTempCLEAR NOTIFICATION-TYPE
OBJECTS {
vrcOutdoorPtTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC outdoor temperature clear trap"
::= { trapPrefix 23008 }
--#####vrcDischPtTable#####--
vrcDischPtTempNOTIFY NOTIFICATION-TYPE
OBJECTS {
vrcDischPtTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC discharge temperature trap"
::= { trapPrefix 13009 }
vrcDischPtTempCLEAR NOTIFICATION-TYPE
OBJECTS {
vrcDischPtTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC discharge temperature clear trap"
::= { trapPrefix 23009 }
vrcDischPtPressureNOTIFY NOTIFICATION-TYPE
OBJECTS {
vrcDischPtPressure,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC discharge pressure trap"
::= { trapPrefix 13010 }
vrcDischPtPressureCLEAR NOTIFICATION-TYPE
OBJECTS {
vrcDischPtPressure,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC discharge pressure clear trap"
::= { trapPrefix 23010 }
--#####vrcDischCfgTable#####--
--#####vrcSuctPtTable#####--
vrcSuctPtTempNOTIFY NOTIFICATION-TYPE
OBJECTS {
vrcSuctPtTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC suction temperature trap"
::= { trapPrefix 13011 }
vrcSuctPtTempCLEAR NOTIFICATION-TYPE
OBJECTS {
vrcSuctPtTemp,
temperatureUnits,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC suction temperature clear trap"
::= { trapPrefix 23011 }
vrcSuctPtPressureNOTIFY NOTIFICATION-TYPE
OBJECTS {
vrcSuctPtPressure,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC suction pressure trap"
::= { trapPrefix 13012 }
vrcSuctPtPressureCLEAR NOTIFICATION-TYPE
OBJECTS {
vrcSuctPtPressure,
trapThreshType,
trapSeverity,
sysName,
vrcMainLabel
}
STATUS current
DESCRIPTION "VRC suction pressure clear trap"
::= { trapPrefix 23012 }
--#####vrcSuctCfgTable#####--
--###########################################################################################--
--common group--
--###########################################################################################--
common OBJECT IDENTIFIER ::= { vertiv 42 }
identity OBJECT IDENTIFIER ::= { common 1 }
i03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Value given for sysObjectID on IMD3 units"
::= { identity 53 }
r05 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Value given for sysObjectID on R-Series units"
::= { identity 15 }
END