6472 lines
146 KiB
Plaintext
6472 lines
146 KiB
Plaintext
VERTIV-V5-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
|
|
DisplayString, TruthValue, MacAddress FROM SNMPv2-TC
|
|
SnmpAdminString FROM SNMP-FRAMEWORK-MIB
|
|
MODULE-IDENTITY, OBJECT-TYPE, enterprises, Integer32,
|
|
Gauge32, NOTIFICATION-TYPE, OBJECT-IDENTITY FROM SNMPv2-SMI
|
|
sysName FROM SNMPv2-MIB;
|
|
|
|
vertiv MODULE-IDENTITY
|
|
LAST-UPDATED "202001070000Z"
|
|
ORGANIZATION "Vertiv"
|
|
CONTACT-INFO "support@geistglobal.com"
|
|
DESCRIPTION
|
|
"The MIB for Vertiv products"
|
|
|
|
REVISION "202001070000Z"
|
|
DESCRIPTION
|
|
"Updates for VRC spec change"
|
|
|
|
REVISION "201909300000Z"
|
|
DESCRIPTION
|
|
"Added hostname, alarm/warning count, and manufacturer to deviceInfo"
|
|
|
|
REVISION "201909120000Z"
|
|
DESCRIPTION
|
|
"Added SN-2D door switch sensor"
|
|
|
|
REVISION "201908300000Z"
|
|
DESCRIPTION
|
|
"Removed current min, max, and peak fields from pdu phase, line,
|
|
breaker, and outlet tables
|
|
Removed voltage min, max, and peak fields from pdu phase, line,
|
|
breaker, and outlet tables
|
|
Removed minmax reset value from pduOutletMeterReset
|
|
Added balance field to pdu phase table"
|
|
|
|
REVISION "201906060000Z"
|
|
DESCRIPTION
|
|
"Updated pduOutletSwitchControl description"
|
|
|
|
REVISION "201905070000Z"
|
|
DESCRIPTION
|
|
"Changed productMacAddress type to MacAddress"
|
|
|
|
REVISION "201904300000Z"
|
|
DESCRIPTION
|
|
"Added remote humidity-only sensor"
|
|
|
|
REVISION "201903070000Z"
|
|
DESCRIPTION
|
|
"Added VRC support"
|
|
|
|
REVISION "201801190000Z"
|
|
DESCRIPTION
|
|
"Modified pduOutletSwitchTable to support outlet actions with delays"
|
|
|
|
REVISION "201709190000Z"
|
|
DESCRIPTION
|
|
"Changed SYNTAX of objects, with a UTF-8 encoded string value, to
|
|
SnmpAdminString"
|
|
|
|
REVISION "201708100000Z"
|
|
DESCRIPTION
|
|
"Added pduBreakerCurrentPeak, pduLineCurrentPeak,
|
|
pduOutletMeterCurrentPeak, pduPhaseVoltagePeak, and
|
|
pduPhaseCurrentPeak
|
|
Updated object descriptions, indicating which fields are not supported
|
|
on all platforms"
|
|
|
|
REVISION "201705100000Z"
|
|
DESCRIPTION
|
|
"Added trapObj group with trap payload objects
|
|
Added additional payload objects to trap definitions"
|
|
|
|
REVISION "201704050000Z"
|
|
DESCRIPTION
|
|
"Added productPlatform to deviceInfo group
|
|
Added product identity entries"
|
|
|
|
REVISION "201606300000Z"
|
|
DESCRIPTION
|
|
"Raven version"
|
|
|
|
REVISION "201209110000Z"
|
|
DESCRIPTION
|
|
"Original version"
|
|
::= { enterprises 21239 }
|
|
|
|
v5 OBJECT IDENTIFIER ::= { vertiv 5 }
|
|
|
|
imd OBJECT IDENTIFIER ::= { v5 2 }
|
|
|
|
--###########################################################################################--
|
|
--deviceInfo--
|
|
--###########################################################################################--
|
|
|
|
deviceInfo OBJECT IDENTIFIER ::= { imd 1 }
|
|
|
|
productTitle OBJECT-TYPE
|
|
SYNTAX SnmpAdminString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Product name"
|
|
::= { deviceInfo 1 }
|
|
|
|
productVersion OBJECT-TYPE
|
|
SYNTAX SnmpAdminString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Product version"
|
|
::= { deviceInfo 2 }
|
|
|
|
productFriendlyName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-assigned name"
|
|
::= { deviceInfo 3 }
|
|
|
|
productMacAddress OBJECT-TYPE
|
|
SYNTAX MacAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Product's unique MAC address"
|
|
::= { deviceInfo 4 }
|
|
|
|
deviceCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..16)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total number of devices on unit"
|
|
::= { deviceInfo 6 }
|
|
|
|
temperatureUnits OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
fahrenheit(0),
|
|
celsius(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current units for temperature/dewpoint values:
|
|
0 = Degrees Fahrenheit
|
|
1 = Degrees Celsius"
|
|
::= { deviceInfo 7 }
|
|
|
|
productModelNumber OBJECT-TYPE
|
|
SYNTAX SnmpAdminString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Product model number (factory-assigned)"
|
|
::= { deviceInfo 8 }
|
|
|
|
productPartNumber OBJECT-TYPE
|
|
SYNTAX SnmpAdminString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Product part number (factory-assigned)"
|
|
::= { deviceInfo 9 }
|
|
|
|
productSerialNumber OBJECT-TYPE
|
|
SYNTAX SnmpAdminString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Product serial number (factory-assigned)"
|
|
::= { deviceInfo 10 }
|
|
|
|
productPlatform OBJECT-TYPE
|
|
SYNTAX SnmpAdminString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Product platform"
|
|
::= { deviceInfo 11 }
|
|
|
|
productHostname OBJECT-TYPE
|
|
SYNTAX SnmpAdminString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Product hostname"
|
|
::= { deviceInfo 12 }
|
|
|
|
productAlarmCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of alarms currently tripped"
|
|
::= { deviceInfo 13 }
|
|
|
|
productWarnCount OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of warnings currently tripped"
|
|
::= { deviceInfo 14 }
|
|
|
|
productManufacturer OBJECT-TYPE
|
|
SYNTAX SnmpAdminString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Product manufacturer"
|
|
::= { deviceInfo 15 }
|
|
|
|
--###########################################################################################--
|
|
--pdu--
|
|
--###########################################################################################--
|
|
|
|
pdu OBJECT IDENTIFIER ::= { imd 3 }
|
|
|
|
--###########################################################################################--
|
|
--pduMainTable--
|
|
--###########################################################################################--
|
|
|
|
pduMainTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduMainEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU general information"
|
|
::= { pdu 1 }
|
|
|
|
pduMainEntry OBJECT-TYPE
|
|
SYNTAX PduMainEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the pduMainTable table: each entry contains an index
|
|
and other sensor details"
|
|
INDEX { pduMainIndex }
|
|
::= { pduMainTable 1 }
|
|
|
|
PduMainEntry ::= SEQUENCE {
|
|
pduMainIndex Integer32,
|
|
pduMainSerial DisplayString,
|
|
pduMainName SnmpAdminString,
|
|
pduMainLabel SnmpAdminString,
|
|
pduMainAvail Gauge32,
|
|
pduMeterType INTEGER,
|
|
pduTotalName SnmpAdminString,
|
|
pduTotalLabel SnmpAdminString,
|
|
pduTotalRealPower Gauge32,
|
|
pduTotalApparentPower Gauge32,
|
|
pduTotalPowerFactor Gauge32,
|
|
pduTotalEnergy Gauge32
|
|
}
|
|
|
|
pduMainIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table entry index value"
|
|
::= { pduMainEntry 1 }
|
|
|
|
pduMainSerial OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number"
|
|
::= { pduMainEntry 2 }
|
|
|
|
pduMainName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU name (factory-assigned)"
|
|
::= { pduMainEntry 3 }
|
|
|
|
pduMainLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU label (user-defined)"
|
|
::= { pduMainEntry 4 }
|
|
|
|
pduMainAvail OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device availability:
|
|
0 = Unavailable
|
|
1 = Available
|
|
2 = Partially Unavailable"
|
|
::= { pduMainEntry 5 }
|
|
|
|
pduMeterType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
wye(0),
|
|
delta(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current meter type:
|
|
0 = Wye
|
|
1 = Delta"
|
|
::= { pduMainEntry 6 }
|
|
|
|
pduTotalName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total name (factory-assigned)"
|
|
::= { pduMainEntry 7 }
|
|
|
|
pduTotalLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total label (user-defined)"
|
|
::= { pduMainEntry 8 }
|
|
|
|
pduTotalRealPower OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9999)
|
|
UNITS "watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU total real power"
|
|
::= { pduMainEntry 9 }
|
|
|
|
pduTotalApparentPower OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9999)
|
|
UNITS "volt-amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU total apparent power"
|
|
::= { pduMainEntry 10 }
|
|
|
|
pduTotalPowerFactor OBJECT-TYPE
|
|
SYNTAX Gauge32(0..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU total power factor"
|
|
::= { pduMainEntry 11 }
|
|
|
|
pduTotalEnergy OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9999000)
|
|
UNITS "watt-hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU total accumulated energy in watt-hours"
|
|
::= { pduMainEntry 12 }
|
|
|
|
--###########################################################################################--
|
|
--pduPhaseTable--
|
|
--###########################################################################################--
|
|
|
|
pduPhaseTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduPhaseEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU phases information"
|
|
::= { pdu 2 }
|
|
|
|
pduPhaseEntry OBJECT-TYPE
|
|
SYNTAX PduPhaseEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the pduPhaseTable table: each entry contains an index
|
|
and other sensor details"
|
|
INDEX { pduPhaseIndex }
|
|
::= { pduPhaseTable 1 }
|
|
|
|
PduPhaseEntry ::= SEQUENCE {
|
|
pduPhaseIndex Integer32,
|
|
pduPhaseName SnmpAdminString,
|
|
pduPhaseLabel SnmpAdminString,
|
|
pduPhaseVoltage Gauge32,
|
|
pduPhaseCurrent Gauge32,
|
|
pduPhaseRealPower Gauge32,
|
|
pduPhaseApparentPower Gauge32,
|
|
pduPhasePowerFactor Gauge32,
|
|
pduPhaseEnergy Gauge32,
|
|
pduPhaseBalance Gauge32,
|
|
pduPhaseCurrentCrestFactor Gauge32
|
|
}
|
|
|
|
pduPhaseIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table entry index value"
|
|
::= { pduPhaseEntry 1 }
|
|
|
|
pduPhaseName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU phase name (factory-assigned)"
|
|
::= { pduPhaseEntry 2 }
|
|
|
|
pduPhaseLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU phase label (user-defined)"
|
|
::= { pduPhaseEntry 3 }
|
|
|
|
pduPhaseVoltage OBJECT-TYPE
|
|
SYNTAX Gauge32(0..3100)
|
|
UNITS "decivolts (rms)"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU phase voltage in tenths of a volt"
|
|
::= { pduPhaseEntry 4 }
|
|
|
|
pduPhaseCurrent OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9900)
|
|
UNITS "centiamps (rms)"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU phase current reading in hundredths of an amp"
|
|
::= { pduPhaseEntry 8 }
|
|
|
|
pduPhaseRealPower OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9999)
|
|
UNITS "watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Real power for phase in watts"
|
|
::= { pduPhaseEntry 12 }
|
|
|
|
pduPhaseApparentPower OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9999)
|
|
UNITS "volt-amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Apparent power for phase in volt-amps"
|
|
::= { pduPhaseEntry 13 }
|
|
|
|
pduPhasePowerFactor OBJECT-TYPE
|
|
SYNTAX Gauge32(0..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power factor for phase"
|
|
::= { pduPhaseEntry 14 }
|
|
|
|
pduPhaseEnergy OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9999000)
|
|
UNITS "watt-hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated energy for phase in watt-hours"
|
|
::= { pduPhaseEntry 15 }
|
|
|
|
pduPhaseBalance OBJECT-TYPE
|
|
SYNTAX Gauge32(0..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Phase balance as percent"
|
|
::= { pduPhaseEntry 17 }
|
|
|
|
pduPhaseCurrentCrestFactor OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9999)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current crest factor for phase, in hundredths"
|
|
::= { pduPhaseEntry 19 }
|
|
|
|
--###########################################################################################--
|
|
--pduBreakerTable--
|
|
--###########################################################################################--
|
|
|
|
pduBreakerTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduBreakerEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU breaker information"
|
|
::= { pdu 3 }
|
|
|
|
pduBreakerEntry OBJECT-TYPE
|
|
SYNTAX PduBreakerEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the pduBreakerTable table: each entry contains an index
|
|
and other sensor details"
|
|
INDEX { pduBreakerIndex }
|
|
::= { pduBreakerTable 1 }
|
|
|
|
PduBreakerEntry ::= SEQUENCE {
|
|
pduBreakerIndex Integer32,
|
|
pduBreakerName SnmpAdminString,
|
|
pduBreakerLabel SnmpAdminString,
|
|
pduBreakerCurrent Gauge32,
|
|
pduBreakerVoltage Gauge32,
|
|
pduBreakerRealPower Gauge32,
|
|
pduBreakerApparentPower Gauge32,
|
|
pduBreakerPowerFactor Gauge32,
|
|
pduBreakerEnergy Gauge32
|
|
}
|
|
|
|
pduBreakerIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table entry index value"
|
|
::= { pduBreakerEntry 1 }
|
|
|
|
pduBreakerName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU breaker name (factory-assigned)"
|
|
::= { pduBreakerEntry 2 }
|
|
|
|
pduBreakerLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU breaker label (user-defined)"
|
|
::= { pduBreakerEntry 3 }
|
|
|
|
pduBreakerCurrent OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9900)
|
|
UNITS "centiamps (rms)"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU breaker current reading in hundredths of an amp"
|
|
::= { pduBreakerEntry 4 }
|
|
|
|
pduBreakerVoltage OBJECT-TYPE
|
|
SYNTAX Gauge32(0..3100)
|
|
UNITS "decivolts (rms)"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU breaker voltage in tenths of a volt. This object may not exist on
|
|
all platforms, due to hardware differences."
|
|
::= { pduBreakerEntry 8 }
|
|
|
|
pduBreakerRealPower OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9999)
|
|
UNITS "watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Real power for breaker in watts. This object may not exist on all
|
|
platforms, due to hardware differences."
|
|
::= { pduBreakerEntry 12 }
|
|
|
|
pduBreakerApparentPower OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9999)
|
|
UNITS "volt-amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Apparent power for breaker in volt-amps. This object may not exist on
|
|
all platforms, due to hardware differences."
|
|
::= { pduBreakerEntry 13 }
|
|
|
|
pduBreakerPowerFactor OBJECT-TYPE
|
|
SYNTAX Gauge32(0..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power factor for breaker. This object may not exist on all platforms,
|
|
due to hardware differences."
|
|
::= { pduBreakerEntry 14 }
|
|
|
|
pduBreakerEnergy OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9999000)
|
|
UNITS "watt-hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated energy for breaker in watt-hours. This object may not
|
|
exist on all platforms, due to hardware differences."
|
|
::= { pduBreakerEntry 15 }
|
|
|
|
--###########################################################################################--
|
|
--pduLineTable--
|
|
--###########################################################################################--
|
|
|
|
pduLineTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduLineEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU line current information"
|
|
::= { pdu 4 }
|
|
|
|
pduLineEntry OBJECT-TYPE
|
|
SYNTAX PduLineEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the pduLineTable table: each entry contains an index
|
|
and other sensor details"
|
|
INDEX { pduLineIndex }
|
|
::= { pduLineTable 1 }
|
|
|
|
PduLineEntry ::= SEQUENCE {
|
|
pduLineIndex Integer32,
|
|
pduLineName SnmpAdminString,
|
|
pduLineLabel SnmpAdminString,
|
|
pduLineCurrent Gauge32
|
|
}
|
|
|
|
pduLineIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table entry index value"
|
|
::= { pduLineEntry 1 }
|
|
|
|
pduLineName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU line name (factory-assigned)"
|
|
::= { pduLineEntry 2 }
|
|
|
|
pduLineLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU line label (user-defined)"
|
|
::= { pduLineEntry 3 }
|
|
|
|
pduLineCurrent OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9900)
|
|
UNITS "centiamps (rms)"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU line current reading in hundredths of an amp"
|
|
::= { pduLineEntry 4 }
|
|
|
|
--###########################################################################################--
|
|
--pduOutletSwitchTable--
|
|
--###########################################################################################--
|
|
|
|
pduOutletSwitchTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduOutletSwitchEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data, config and control for outlets with switching"
|
|
::= { pdu 5 }
|
|
|
|
pduOutletSwitchEntry OBJECT-TYPE
|
|
SYNTAX PduOutletSwitchEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the pduOutletSwitchTable table: each entry contains an index
|
|
and other sensor details"
|
|
INDEX { pduOutletSwitchIndex }
|
|
::= { pduOutletSwitchTable 1 }
|
|
|
|
PduOutletSwitchEntry ::= SEQUENCE {
|
|
pduOutletSwitchIndex Integer32,
|
|
pduOutletSwitchName SnmpAdminString,
|
|
pduOutletSwitchLabel SnmpAdminString,
|
|
pduOutletSwitchState INTEGER,
|
|
pduOutletSwitchRelayFailure TruthValue,
|
|
pduOutletSwitchControl INTEGER,
|
|
pduOutletSwitchTimeToAction Integer32,
|
|
pduOutletSwitchOnDelay Integer32,
|
|
pduOutletSwitchOffDelay Integer32,
|
|
pduOutletSwitchRebootDelay Integer32,
|
|
pduOutletSwitchRebootHoldDelay Integer32,
|
|
pduOutletSwitchPoaAction INTEGER,
|
|
pduOutletSwitchPoaDelay Integer32
|
|
}
|
|
|
|
pduOutletSwitchIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table entry index value"
|
|
::= { pduOutletSwitchEntry 1 }
|
|
|
|
pduOutletSwitchName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU outlet name (factory-assigned)"
|
|
::= { pduOutletSwitchEntry 2 }
|
|
|
|
pduOutletSwitchLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU outlet label (user-defined)"
|
|
::= { pduOutletSwitchEntry 3 }
|
|
|
|
pduOutletSwitchState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2),
|
|
on2off(3),
|
|
off2on(4),
|
|
rebootOn(5),
|
|
rebootOff(6),
|
|
unavailable(7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Switch state of the outlet:
|
|
1 = Outlet is on
|
|
2 = Outlet is off
|
|
3 = Outlet is on, but will turn off after a delay
|
|
4 = Outlet is off, but will turn on after a delay
|
|
5 = Starting reboot cycle, outlet is on, but will go to the
|
|
rebootOff(6) state after a delay
|
|
6 = Rebooting, outlet is off, but it will turn on after a delay
|
|
7 = Cannot get outlet state"
|
|
::= { pduOutletSwitchEntry 4 }
|
|
|
|
pduOutletSwitchRelayFailure OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Tells if the outlet relay has failed. In normal operation, the value
|
|
will be false(2)."
|
|
::= { pduOutletSwitchEntry 5 }
|
|
|
|
pduOutletSwitchControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
cancel(1),
|
|
on(2),
|
|
onAfterDelay(3),
|
|
off(4),
|
|
offAfterDelay(5),
|
|
reboot(6),
|
|
rebootAfterDelay(7),
|
|
none(8)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Used for manual control of the outlet. If the outlet is in manual
|
|
mode, this field can be set to one of the following values:
|
|
1 = Cancel pending operation
|
|
2 = Turn outlet on
|
|
3 = After delay (pduOutletSwitchOnDelay), turn outlet on
|
|
4 = Turn outlet off
|
|
5 = After delay (pduOutletSwitchOffDelay), turn outlet off
|
|
6 = Reboot: turn off, delay (pduOutletSwitchRebootHoldDelay), turn
|
|
outlet back on
|
|
7 = After delay (pduOutletSwitchRebootDelay), reboot outlet
|
|
When not in manual mode, setting this field will give an
|
|
inconsistentValue error. Returns none(8) for all get requests."
|
|
::= { pduOutletSwitchEntry 6 }
|
|
|
|
pduOutletSwitchTimeToAction OBJECT-TYPE
|
|
SYNTAX Integer32(0..600)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Seconds until an outlet state change. The value of
|
|
pduOutletSwitchState tells what state the outlet will be set, after
|
|
the delay."
|
|
::= { pduOutletSwitchEntry 7 }
|
|
|
|
pduOutletSwitchOnDelay OBJECT-TYPE
|
|
SYNTAX Integer32(0..600)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Seconds to wait before powering on the outlet, during onAfterDelay(3)
|
|
operation. Changing this value has no effect on pending actions."
|
|
::= { pduOutletSwitchEntry 8 }
|
|
|
|
pduOutletSwitchOffDelay OBJECT-TYPE
|
|
SYNTAX Integer32(0..600)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Seconds to wait before powering off the outlet, during
|
|
offAfterDelay(5) operation. Changing this value has no effect on
|
|
pending actions."
|
|
::= { pduOutletSwitchEntry 9 }
|
|
|
|
pduOutletSwitchRebootDelay OBJECT-TYPE
|
|
SYNTAX Integer32(0..600)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Seconds to wait before powering off the outlet, during
|
|
rebootAfterDelay(7) operation. Changing this value has no effect on
|
|
pending actions. See pduOutletSwitchControl for more info."
|
|
::= { pduOutletSwitchEntry 10 }
|
|
|
|
pduOutletSwitchRebootHoldDelay OBJECT-TYPE
|
|
SYNTAX Integer32(0..600)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Seconds to hold the outlet off, before powering on the outlet, during
|
|
rebootAfterDelay(7) operation. Changing this value has no effect on
|
|
pending actions. See pduOutletSwitchControl for more info."
|
|
::= { pduOutletSwitchEntry 11 }
|
|
|
|
pduOutletSwitchPoaAction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2),
|
|
last(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The outlet is set to this state during power-up. The action can be
|
|
have one the following values:
|
|
1 = Outlet will be turned on
|
|
2 = Outlet will stay off
|
|
3 = Outlet will be set to last known state"
|
|
::= { pduOutletSwitchEntry 12 }
|
|
|
|
pduOutletSwitchPoaDelay OBJECT-TYPE
|
|
SYNTAX Integer32(0..600)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Seconds to wait before setting the outlet to the
|
|
pduOutletSwitchPoaAction state. The delay starts at power-up."
|
|
::= { pduOutletSwitchEntry 13 }
|
|
|
|
--###########################################################################################--
|
|
--pduOutletMeterTable--
|
|
--###########################################################################################--
|
|
|
|
pduOutletMeterTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduOutletMeterEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Metering data for outlets that support this feature"
|
|
::= { pdu 6 }
|
|
|
|
pduOutletMeterEntry OBJECT-TYPE
|
|
SYNTAX PduOutletMeterEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the pduOutletMeterTable table: each entry contains an index
|
|
and other sensor details"
|
|
INDEX { pduOutletMeterIndex }
|
|
::= { pduOutletMeterTable 1 }
|
|
|
|
PduOutletMeterEntry ::= SEQUENCE {
|
|
pduOutletMeterIndex Integer32,
|
|
pduOutletMeterName SnmpAdminString,
|
|
pduOutletMeterLabel SnmpAdminString,
|
|
pduOutletMeterVoltage Gauge32,
|
|
pduOutletMeterCurrent Gauge32,
|
|
pduOutletMeterRealPower Gauge32,
|
|
pduOutletMeterApparentPower Gauge32,
|
|
pduOutletMeterPowerFactor Gauge32,
|
|
pduOutletMeterEnergy Gauge32,
|
|
pduOutletMeterReset INTEGER,
|
|
pduOutletCurrentCrestFactor Gauge32
|
|
}
|
|
|
|
pduOutletMeterIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table entry index value"
|
|
::= { pduOutletMeterEntry 1 }
|
|
|
|
pduOutletMeterName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU outlet name (factory-assigned)"
|
|
::= { pduOutletMeterEntry 2 }
|
|
|
|
pduOutletMeterLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU outlet label (user-defined)"
|
|
::= { pduOutletMeterEntry 3 }
|
|
|
|
pduOutletMeterVoltage OBJECT-TYPE
|
|
SYNTAX Gauge32(0..3100)
|
|
UNITS "decivolts (rms)"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU outlet voltage in tenths of a volt"
|
|
::= { pduOutletMeterEntry 4 }
|
|
|
|
pduOutletMeterCurrent OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9900)
|
|
UNITS "centiamps (rms)"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU outlet current reading in hundredths of an amp"
|
|
::= { pduOutletMeterEntry 8 }
|
|
|
|
pduOutletMeterRealPower OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9999)
|
|
UNITS "watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Real power for outlet in watts"
|
|
::= { pduOutletMeterEntry 12 }
|
|
|
|
pduOutletMeterApparentPower OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9999)
|
|
UNITS "volt-amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Apparent power for outlet in volt-amps"
|
|
::= { pduOutletMeterEntry 13 }
|
|
|
|
pduOutletMeterPowerFactor OBJECT-TYPE
|
|
SYNTAX Gauge32(0..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power factor for outlet"
|
|
::= { pduOutletMeterEntry 14 }
|
|
|
|
pduOutletMeterEnergy OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9999000)
|
|
UNITS "watt-hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Accumulated energy for outlet in watt-hours"
|
|
::= { pduOutletMeterEntry 15 }
|
|
|
|
pduOutletMeterReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
resetEnergy(1),
|
|
none(8)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Used to reset energy. If read, the value is none(8). It can be set to
|
|
resetEnergy(1), which sets outlet energy to 0"
|
|
::= { pduOutletMeterEntry 16 }
|
|
|
|
pduOutletCurrentCrestFactor OBJECT-TYPE
|
|
SYNTAX Gauge32(0..9999)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Current crest factor for outlet, in hundredths"
|
|
::= { pduOutletMeterEntry 19 }
|
|
|
|
--###########################################################################################--
|
|
--tempSensorTable--
|
|
--###########################################################################################--
|
|
|
|
tempSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TempSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote Temperature (RT) sensor"
|
|
::= { imd 4 }
|
|
|
|
tempSensorEntry OBJECT-TYPE
|
|
SYNTAX TempSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the tempSensorTable table: each entry contains an index
|
|
and other sensor details"
|
|
INDEX { tempSensorIndex }
|
|
::= { tempSensorTable 1 }
|
|
|
|
TempSensorEntry ::= SEQUENCE {
|
|
tempSensorIndex Integer32,
|
|
tempSensorSerial DisplayString,
|
|
tempSensorLabel SnmpAdminString,
|
|
tempSensorAvail Gauge32,
|
|
tempSensorTemp Integer32
|
|
}
|
|
|
|
tempSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table entry index value"
|
|
::= { tempSensorEntry 1 }
|
|
|
|
tempSensorSerial OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number"
|
|
::= { tempSensorEntry 2 }
|
|
|
|
tempSensorLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined label"
|
|
::= { tempSensorEntry 3 }
|
|
|
|
tempSensorAvail OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device availability:
|
|
0 = Unavailable
|
|
1 = Available
|
|
2 = Partially Unavailable"
|
|
::= { tempSensorEntry 4 }
|
|
|
|
tempSensorTemp OBJECT-TYPE
|
|
SYNTAX Integer32(-400..2540)
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature in tenths of a degree. Units are given by temperatureUnits
|
|
field in deviceInfo."
|
|
::= { tempSensorEntry 5 }
|
|
|
|
--###########################################################################################--
|
|
--airFlowSensorTable--
|
|
--###########################################################################################--
|
|
|
|
airFlowSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AirFlowSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor"
|
|
::= { imd 5 }
|
|
|
|
airFlowSensorEntry OBJECT-TYPE
|
|
SYNTAX AirFlowSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the airFlowSensorTable table: each entry contains an index
|
|
and other sensor details"
|
|
INDEX { airFlowSensorIndex }
|
|
::= { airFlowSensorTable 1 }
|
|
|
|
AirFlowSensorEntry ::= SEQUENCE {
|
|
airFlowSensorIndex Integer32,
|
|
airFlowSensorSerial DisplayString,
|
|
airFlowSensorLabel SnmpAdminString,
|
|
airFlowSensorAvail Gauge32,
|
|
airFlowSensorTemp Integer32,
|
|
airFlowSensorFlow Integer32,
|
|
airFlowSensorHumidity Integer32,
|
|
airFlowSensorDewPoint Integer32
|
|
}
|
|
|
|
airFlowSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table entry index value"
|
|
::= { airFlowSensorEntry 1 }
|
|
|
|
airFlowSensorSerial OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number"
|
|
::= { airFlowSensorEntry 2 }
|
|
|
|
airFlowSensorLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined label"
|
|
::= { airFlowSensorEntry 3 }
|
|
|
|
airFlowSensorAvail OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device availability:
|
|
0 = Unavailable
|
|
1 = Available
|
|
2 = Partially Unavailable"
|
|
::= { airFlowSensorEntry 4 }
|
|
|
|
airFlowSensorTemp OBJECT-TYPE
|
|
SYNTAX Integer32(-400..2540)
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature reading in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo."
|
|
::= { airFlowSensorEntry 5 }
|
|
|
|
airFlowSensorFlow OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Airflow reading. Still air will be less than 20, while rushing air
|
|
will be around 100."
|
|
::= { airFlowSensorEntry 6 }
|
|
|
|
airFlowSensorHumidity OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity reading"
|
|
::= { airFlowSensorEntry 7 }
|
|
|
|
airFlowSensorDewPoint OBJECT-TYPE
|
|
SYNTAX Integer32(-400..2540)
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Dewpoint reading in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo."
|
|
::= { airFlowSensorEntry 8 }
|
|
|
|
--###########################################################################################--
|
|
--t3hdSensorTable--
|
|
--###########################################################################################--
|
|
|
|
t3hdSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF T3hdSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote Temperature x 3, Humidity and Dewpoint Sensor"
|
|
::= { imd 8 }
|
|
|
|
t3hdSensorEntry OBJECT-TYPE
|
|
SYNTAX T3hdSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the t3hdSensorTable table: each entry contains an index
|
|
and other sensor details"
|
|
INDEX { t3hdSensorIndex }
|
|
::= { t3hdSensorTable 1 }
|
|
|
|
T3hdSensorEntry ::= SEQUENCE {
|
|
t3hdSensorIndex Integer32,
|
|
t3hdSensorSerial DisplayString,
|
|
t3hdSensorLabel SnmpAdminString,
|
|
t3hdSensorAvail Gauge32,
|
|
t3hdSensorIntLabel SnmpAdminString,
|
|
t3hdSensorIntTemp Integer32,
|
|
t3hdSensorIntHumidity Integer32,
|
|
t3hdSensorIntDewPoint Integer32,
|
|
t3hdSensorExtAAvail Gauge32,
|
|
t3hdSensorExtALabel SnmpAdminString,
|
|
t3hdSensorExtATemp Integer32,
|
|
t3hdSensorExtBAvail Gauge32,
|
|
t3hdSensorExtBLabel SnmpAdminString,
|
|
t3hdSensorExtBTemp Integer32
|
|
}
|
|
|
|
t3hdSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table entry index value"
|
|
::= { t3hdSensorEntry 1 }
|
|
|
|
t3hdSensorSerial OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number"
|
|
::= { t3hdSensorEntry 2 }
|
|
|
|
t3hdSensorLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined label"
|
|
::= { t3hdSensorEntry 3 }
|
|
|
|
t3hdSensorAvail OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device availability:
|
|
0 = Unavailable
|
|
1 = Available
|
|
2 = Partially Unavailable"
|
|
::= { t3hdSensorEntry 4 }
|
|
|
|
t3hdSensorIntLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Internal label (user-defined)"
|
|
::= { t3hdSensorEntry 5 }
|
|
|
|
t3hdSensorIntTemp OBJECT-TYPE
|
|
SYNTAX Integer32(-400..2540)
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Internal temperature in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo."
|
|
::= { t3hdSensorEntry 6 }
|
|
|
|
t3hdSensorIntHumidity OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Internal humidity"
|
|
::= { t3hdSensorEntry 7 }
|
|
|
|
t3hdSensorIntDewPoint OBJECT-TYPE
|
|
SYNTAX Integer32(-400..2540)
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Internal dewpoint in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo."
|
|
::= { t3hdSensorEntry 8 }
|
|
|
|
t3hdSensorExtAAvail OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External A status:
|
|
0 = Unavailable
|
|
1 = Available"
|
|
::= { t3hdSensorEntry 9 }
|
|
|
|
t3hdSensorExtALabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External A label (user-defined)"
|
|
::= { t3hdSensorEntry 10 }
|
|
|
|
t3hdSensorExtATemp OBJECT-TYPE
|
|
SYNTAX Integer32(-400..2540)
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External A temperature in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo."
|
|
::= { t3hdSensorEntry 11 }
|
|
|
|
t3hdSensorExtBAvail OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External B status:
|
|
0 = Unavailable
|
|
1 = Available"
|
|
::= { t3hdSensorEntry 12 }
|
|
|
|
t3hdSensorExtBLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External B label (user-defined)"
|
|
::= { t3hdSensorEntry 13 }
|
|
|
|
t3hdSensorExtBTemp OBJECT-TYPE
|
|
SYNTAX Integer32(-400..2540)
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External B temperature in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo."
|
|
::= { t3hdSensorEntry 14 }
|
|
|
|
--###########################################################################################--
|
|
--thdSensorTable--
|
|
--###########################################################################################--
|
|
|
|
thdSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF ThdSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote Temperature, Humidity, and Dewpoint (THD) Sensor"
|
|
::= { imd 9 }
|
|
|
|
thdSensorEntry OBJECT-TYPE
|
|
SYNTAX ThdSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the thdSensorTable table: each entry contains an index
|
|
and other sensor details"
|
|
INDEX { thdSensorIndex }
|
|
::= { thdSensorTable 1 }
|
|
|
|
ThdSensorEntry ::= SEQUENCE {
|
|
thdSensorIndex Integer32,
|
|
thdSensorSerial DisplayString,
|
|
thdSensorLabel SnmpAdminString,
|
|
thdSensorAvail Gauge32,
|
|
thdSensorTemp Integer32,
|
|
thdSensorHumidity Integer32,
|
|
thdSensorDewPoint Integer32
|
|
}
|
|
|
|
thdSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table entry index value"
|
|
::= { thdSensorEntry 1 }
|
|
|
|
thdSensorSerial OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number"
|
|
::= { thdSensorEntry 2 }
|
|
|
|
thdSensorLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined label"
|
|
::= { thdSensorEntry 3 }
|
|
|
|
thdSensorAvail OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device availability:
|
|
0 = Unavailable
|
|
1 = Available
|
|
2 = Partially Unavailable"
|
|
::= { thdSensorEntry 4 }
|
|
|
|
thdSensorTemp OBJECT-TYPE
|
|
SYNTAX Integer32(-400..2540)
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature value in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo."
|
|
::= { thdSensorEntry 5 }
|
|
|
|
thdSensorHumidity OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity value"
|
|
::= { thdSensorEntry 6 }
|
|
|
|
thdSensorDewPoint OBJECT-TYPE
|
|
SYNTAX Integer32(-400..2540)
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Dewpoint value in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo."
|
|
::= { thdSensorEntry 7 }
|
|
|
|
--###########################################################################################--
|
|
--a2dSensorTable--
|
|
--###########################################################################################--
|
|
|
|
a2dSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF A2dSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Analog measurement (A2D) sensor (voltage, current, or dry-contact)"
|
|
::= { imd 11 }
|
|
|
|
a2dSensorEntry OBJECT-TYPE
|
|
SYNTAX A2dSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the a2dSensorTable table: each entry contains an index
|
|
and other sensor details"
|
|
INDEX { a2dSensorIndex }
|
|
::= { a2dSensorTable 1 }
|
|
|
|
A2dSensorEntry ::= SEQUENCE {
|
|
a2dSensorIndex Integer32,
|
|
a2dSensorSerial DisplayString,
|
|
a2dSensorLabel SnmpAdminString,
|
|
a2dSensorAvail Gauge32,
|
|
a2dSensorValue Integer32,
|
|
a2dSensorDisplayValue SnmpAdminString,
|
|
a2dSensorMode INTEGER,
|
|
a2dSensorUnits SnmpAdminString,
|
|
a2dSensorMin Integer32,
|
|
a2dSensorMax Integer32,
|
|
a2dSensorLowLabel SnmpAdminString,
|
|
a2dSensorHighLabel SnmpAdminString,
|
|
a2dSensorAnalogLabel SnmpAdminString
|
|
}
|
|
|
|
a2dSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table entry index value"
|
|
::= { a2dSensorEntry 1 }
|
|
|
|
a2dSensorSerial OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number"
|
|
::= { a2dSensorEntry 2 }
|
|
|
|
a2dSensorLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined label"
|
|
::= { a2dSensorEntry 3 }
|
|
|
|
a2dSensorAvail OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device availability:
|
|
0 = Unavailable
|
|
1 = Available
|
|
2 = Partially Unavailable"
|
|
::= { a2dSensorEntry 4 }
|
|
|
|
a2dSensorValue OBJECT-TYPE
|
|
SYNTAX Integer32(-1000000..1000000)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Analog measurement value, within either a user-defined or preset
|
|
range, depending on a2dSensorMode."
|
|
::= { a2dSensorEntry 5 }
|
|
|
|
a2dSensorDisplayValue OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"For current/voltage modes, the analog value is given as a string. In
|
|
binary modes, the value is either a2dSensorLowLabel or
|
|
a2dSensorHighLabel, based on a2dSensorValue."
|
|
::= { a2dSensorEntry 6 }
|
|
|
|
a2dSensorMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
door(1),
|
|
powerFailure(2),
|
|
flood(3),
|
|
wscLeak(4),
|
|
wscFault(5),
|
|
smoke(6),
|
|
ivsNegGnd(7),
|
|
ivsPosGnd(8),
|
|
customVoltage(9),
|
|
customBinary(10),
|
|
customCurrent(11)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Binary modes have two states represented by the values 0 (low) or 1
|
|
(high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel.
|
|
Current and voltage modes provide a scaled value from a2dSensorMin to
|
|
a2dSensorMax.
|
|
Analog modes:
|
|
1 = Door (binary)
|
|
2 = Power failure (binary)
|
|
3 = Flood (binary)
|
|
4 = Water-sensing cable leak (binary)
|
|
5 = Water-sensing cable fault (binary)
|
|
6 = Smoke alarm (binary)
|
|
7 = Isolated voltage negative ground (voltage)
|
|
8 = Isolated voltage positive ground (voltage)
|
|
9 = Custom voltage (voltage)
|
|
10 = Custom binary (binary)
|
|
11 = Custom current (current)"
|
|
::= { a2dSensorEntry 7 }
|
|
|
|
a2dSensorUnits OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..7))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The units for the analog value. If a2dSensorMode is customVoltage(9)
|
|
or customCurrent(11), then this field has a user-defined value.
|
|
Otherwise, the value is fixed, based on mode."
|
|
::= { a2dSensorEntry 8 }
|
|
|
|
a2dSensorMin OBJECT-TYPE
|
|
SYNTAX Integer32(-1000000..1000000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum analog value, given as an integer. The analog measurement is
|
|
scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is
|
|
customVoltage(9) or customCurrent(11), then this field has a user-
|
|
defined value. Otherwise, the value is fixed, based on mode."
|
|
::= { a2dSensorEntry 9 }
|
|
|
|
a2dSensorMax OBJECT-TYPE
|
|
SYNTAX Integer32(-1000000..1000000)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum analog value, given as an integer. The analog measurement is
|
|
scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is
|
|
customVoltage(9) or customCurrent(11), then this field has a user-
|
|
defined value. Otherwise, the value is fixed, based on mode."
|
|
::= { a2dSensorEntry 10 }
|
|
|
|
a2dSensorLowLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Label for 0 (low) binary value. This field is only applicable if
|
|
a2dSensorMode is one of the binary modes. If a2dSensorMode is
|
|
customBinary(10), then this field is user-defined. Otherwise, it has a
|
|
pre-defined value based on the mode."
|
|
::= { a2dSensorEntry 11 }
|
|
|
|
a2dSensorHighLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Label for 1 (high) binary value. The field is only applicable if
|
|
a2dSensorMode is one of the binary modes. If a2dSensorMode is
|
|
customBinary(10), then this field is user-defined. Otherwise, it has a
|
|
pre-defined value based on the mode."
|
|
::= { a2dSensorEntry 12 }
|
|
|
|
a2dSensorAnalogLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Label for the analog measurement"
|
|
::= { a2dSensorEntry 13 }
|
|
|
|
--###########################################################################################--
|
|
--humiditySensorTable--
|
|
--###########################################################################################--
|
|
|
|
humiditySensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF HumiditySensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote humidity sensor"
|
|
::= { imd 12 }
|
|
|
|
humiditySensorEntry OBJECT-TYPE
|
|
SYNTAX HumiditySensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the humiditySensorTable table: each entry contains an index
|
|
and other sensor details"
|
|
INDEX { humiditySensorIndex }
|
|
::= { humiditySensorTable 1 }
|
|
|
|
HumiditySensorEntry ::= SEQUENCE {
|
|
humiditySensorIndex Integer32,
|
|
humiditySensorSerial DisplayString,
|
|
humiditySensorLabel SnmpAdminString,
|
|
humiditySensorAvail Gauge32,
|
|
humiditySensorValue Integer32
|
|
}
|
|
|
|
humiditySensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table entry index value"
|
|
::= { humiditySensorEntry 1 }
|
|
|
|
humiditySensorSerial OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number"
|
|
::= { humiditySensorEntry 2 }
|
|
|
|
humiditySensorLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined label"
|
|
::= { humiditySensorEntry 3 }
|
|
|
|
humiditySensorAvail OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device availability:
|
|
0 = Unavailable
|
|
1 = Available
|
|
2 = Partially Unavailable"
|
|
::= { humiditySensorEntry 4 }
|
|
|
|
humiditySensorValue OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity value"
|
|
::= { humiditySensorEntry 5 }
|
|
|
|
--###########################################################################################--
|
|
--sn2dSensorTable--
|
|
--###########################################################################################--
|
|
|
|
sn2dSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF Sn2dSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"2 Door Switch Sensor (SN-2D)"
|
|
::= { imd 13 }
|
|
|
|
sn2dSensorEntry OBJECT-TYPE
|
|
SYNTAX Sn2dSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the sn2dSensorTable table: each entry contains an index
|
|
and other sensor details"
|
|
INDEX { sn2dSensorIndex }
|
|
::= { sn2dSensorTable 1 }
|
|
|
|
Sn2dSensorEntry ::= SEQUENCE {
|
|
sn2dSensorIndex Integer32,
|
|
sn2dSensorSerial DisplayString,
|
|
sn2dSensorLabel SnmpAdminString,
|
|
sn2dSensorAvail Gauge32,
|
|
sn2dSensorDoor1Label SnmpAdminString,
|
|
sn2dSensorDoor1State INTEGER,
|
|
sn2dSensorDoor1DisplayState SnmpAdminString,
|
|
sn2dSensorDoor2Label SnmpAdminString,
|
|
sn2dSensorDoor2State INTEGER,
|
|
sn2dSensorDoor2DisplayState SnmpAdminString
|
|
}
|
|
|
|
sn2dSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table entry index value"
|
|
::= { sn2dSensorEntry 1 }
|
|
|
|
sn2dSensorSerial OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number"
|
|
::= { sn2dSensorEntry 2 }
|
|
|
|
sn2dSensorLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined label"
|
|
::= { sn2dSensorEntry 3 }
|
|
|
|
sn2dSensorAvail OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device availability:
|
|
0 = Unavailable
|
|
1 = Available
|
|
2 = Partially Unavailable"
|
|
::= { sn2dSensorEntry 4 }
|
|
|
|
sn2dSensorDoor1Label OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Door switch 1 label"
|
|
::= { sn2dSensorEntry 5 }
|
|
|
|
sn2dSensorDoor1State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
open(1),
|
|
closed(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Door switch 1 state:
|
|
1 = open
|
|
2 = closed"
|
|
::= { sn2dSensorEntry 6 }
|
|
|
|
sn2dSensorDoor1DisplayState OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Door switch 1 state given as a string"
|
|
::= { sn2dSensorEntry 7 }
|
|
|
|
sn2dSensorDoor2Label OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Door switch 2 label"
|
|
::= { sn2dSensorEntry 8 }
|
|
|
|
sn2dSensorDoor2State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
open(1),
|
|
closed(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Door switch 2 state:
|
|
1 = open
|
|
2 = closed"
|
|
::= { sn2dSensorEntry 9 }
|
|
|
|
sn2dSensorDoor2DisplayState OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Door switch 2 state given as a string"
|
|
::= { sn2dSensorEntry 10 }
|
|
|
|
--###########################################################################################--
|
|
--cooling--
|
|
--###########################################################################################--
|
|
|
|
cooling OBJECT IDENTIFIER ::= { imd 30 }
|
|
|
|
--###########################################################################################--
|
|
--vrc--
|
|
--###########################################################################################--
|
|
|
|
vrc OBJECT IDENTIFIER ::= { cooling 1 }
|
|
|
|
--###########################################################################################--
|
|
--vrcMainTable--
|
|
--###########################################################################################--
|
|
|
|
vrcMainTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcMainEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table that contains general VRC information"
|
|
::= { vrc 1 }
|
|
|
|
vrcMainEntry OBJECT-TYPE
|
|
SYNTAX VrcMainEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcMainTable: each entry represents a VRC device"
|
|
INDEX { vrcMainIndex }
|
|
::= { vrcMainTable 1 }
|
|
|
|
VrcMainEntry ::= SEQUENCE {
|
|
vrcMainIndex Integer32,
|
|
vrcMainSerial DisplayString,
|
|
vrcMainName SnmpAdminString,
|
|
vrcMainLabel SnmpAdminString,
|
|
vrcMainAvail Gauge32
|
|
}
|
|
|
|
vrcMainIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcMainEntry 1 }
|
|
|
|
vrcMainSerial OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number"
|
|
::= { vrcMainEntry 2 }
|
|
|
|
vrcMainName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"VRC name (factory-assigned)"
|
|
::= { vrcMainEntry 3 }
|
|
|
|
vrcMainLabel OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (0..25))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"VRC label (user-defined)"
|
|
::= { vrcMainEntry 4 }
|
|
|
|
vrcMainAvail OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device availability:
|
|
0 = Unavailable
|
|
1 = Available
|
|
2 = Partially Unavailable"
|
|
::= { vrcMainEntry 5 }
|
|
|
|
--###########################################################################################--
|
|
--vrcMainPtTable--
|
|
--###########################################################################################--
|
|
|
|
vrcMainPtTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcMainPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table that contains general VRC status"
|
|
::= { vrc 2 }
|
|
|
|
vrcMainPtEntry OBJECT-TYPE
|
|
SYNTAX VrcMainPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcMainPtTable: each entry contains status data for a VRC
|
|
device"
|
|
INDEX { vrcMainPtIndex }
|
|
::= { vrcMainPtTable 1 }
|
|
|
|
VrcMainPtEntry ::= SEQUENCE {
|
|
vrcMainPtIndex Integer32,
|
|
vrcMainPtRunState INTEGER,
|
|
vrcMainPtEevOpened Integer32,
|
|
vrcMainPtAlarmNumbers Integer32,
|
|
vrcMainPtHistoryAlarmNumbers Integer32,
|
|
vrcMainPtHpAbnRecordCnt Integer32,
|
|
vrcMainPtMonitorBaudrate INTEGER,
|
|
vrcMainPtMonitorAddress Integer32,
|
|
vrcMainPtLp TruthValue,
|
|
vrcMainPtFilterMaintRemind TruthValue,
|
|
vrcMainPtCoolingFlag TruthValue,
|
|
vrcMainPtFirstOnFlag TruthValue,
|
|
vrcMainPtNewAlarmFlag TruthValue,
|
|
vrcMainPtComAlarmOutState TruthValue,
|
|
vrcMainPtHighWaterInput TruthValue,
|
|
vrcMainPtHighWaterAlarm TruthValue,
|
|
vrcMainPtWaterUnderFloorAlarm TruthValue,
|
|
vrcMainPtSwShutDownStatus TruthValue,
|
|
vrcMainPtRemoteShutdown TruthValue,
|
|
vrcMainPtRemoteShutDownFlag TruthValue,
|
|
vrcMainPtRemoteShutDownAlarm TruthValue,
|
|
vrcMainPtHmiShutDownFlag TruthValue,
|
|
vrcMainPtLpAlarm TruthValue,
|
|
vrcMainPtHpAlarm TruthValue,
|
|
vrcMainPtLpFreqAlarm TruthValue,
|
|
vrcMainPtHpFreqAlarm TruthValue,
|
|
vrcMainPtLpSensorFailAlarm TruthValue,
|
|
vrcMainPtHpSensorFailAlarm TruthValue,
|
|
vrcMainPtEevCommFailAlarm TruthValue
|
|
}
|
|
|
|
vrcMainPtIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcMainPtEntry 1 }
|
|
|
|
vrcMainPtRunState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"VRC run state:
|
|
1 = on
|
|
2 = off"
|
|
::= { vrcMainPtEntry 2 }
|
|
|
|
vrcMainPtEevOpened OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Eev opened value (percent)"
|
|
::= { vrcMainPtEntry 3 }
|
|
|
|
vrcMainPtAlarmNumbers OBJECT-TYPE
|
|
SYNTAX Integer32(-32768..32767)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alarm numbers value"
|
|
::= { vrcMainPtEntry 4 }
|
|
|
|
vrcMainPtHistoryAlarmNumbers OBJECT-TYPE
|
|
SYNTAX Integer32(-32768..32767)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"History alarm numbers value"
|
|
::= { vrcMainPtEntry 5 }
|
|
|
|
vrcMainPtHpAbnRecordCnt OBJECT-TYPE
|
|
SYNTAX Integer32(-32768..32767)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Hp Abnormal record count"
|
|
::= { vrcMainPtEntry 6 }
|
|
|
|
vrcMainPtMonitorBaudrate OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
error(1),
|
|
baud1200(2),
|
|
baud2400(3),
|
|
baud4800(4),
|
|
baud9600(5),
|
|
baud19200(6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Monitor baud rate:
|
|
1 = error
|
|
2 = 1200
|
|
3 = 2400
|
|
4 = 4800
|
|
5 = 9600
|
|
6 = 19200"
|
|
::= { vrcMainPtEntry 7 }
|
|
|
|
vrcMainPtMonitorAddress OBJECT-TYPE
|
|
SYNTAX Integer32(1..247)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Monitor address"
|
|
::= { vrcMainPtEntry 8 }
|
|
|
|
vrcMainPtLp OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lp status"
|
|
::= { vrcMainPtEntry 9 }
|
|
|
|
vrcMainPtFilterMaintRemind OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Filter maintenance reminder status"
|
|
::= { vrcMainPtEntry 10 }
|
|
|
|
vrcMainPtCoolingFlag OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Cooling flag"
|
|
::= { vrcMainPtEntry 11 }
|
|
|
|
vrcMainPtFirstOnFlag OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"First on flag"
|
|
::= { vrcMainPtEntry 12 }
|
|
|
|
vrcMainPtNewAlarmFlag OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"New alarm flag"
|
|
::= { vrcMainPtEntry 13 }
|
|
|
|
vrcMainPtComAlarmOutState OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Common alarm output state"
|
|
::= { vrcMainPtEntry 14 }
|
|
|
|
vrcMainPtHighWaterInput OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High water input"
|
|
::= { vrcMainPtEntry 15 }
|
|
|
|
vrcMainPtHighWaterAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High water alarm status"
|
|
::= { vrcMainPtEntry 16 }
|
|
|
|
vrcMainPtWaterUnderFloorAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water under floor alarm status"
|
|
::= { vrcMainPtEntry 17 }
|
|
|
|
vrcMainPtSwShutDownStatus OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Software shutdown status"
|
|
::= { vrcMainPtEntry 18 }
|
|
|
|
vrcMainPtRemoteShutdown OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote shutdown status"
|
|
::= { vrcMainPtEntry 19 }
|
|
|
|
vrcMainPtRemoteShutDownFlag OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote shutdown flag"
|
|
::= { vrcMainPtEntry 20 }
|
|
|
|
vrcMainPtRemoteShutDownAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote shutdown alarm status"
|
|
::= { vrcMainPtEntry 21 }
|
|
|
|
vrcMainPtHmiShutDownFlag OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Hmi shutdown flag"
|
|
::= { vrcMainPtEntry 22 }
|
|
|
|
vrcMainPtLpAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Low pressure alarm status"
|
|
::= { vrcMainPtEntry 23 }
|
|
|
|
vrcMainPtHpAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High pressure alarm status"
|
|
::= { vrcMainPtEntry 24 }
|
|
|
|
vrcMainPtLpFreqAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Low pressure frequently alarm status"
|
|
::= { vrcMainPtEntry 25 }
|
|
|
|
vrcMainPtHpFreqAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High pressure frequently alarm status"
|
|
::= { vrcMainPtEntry 26 }
|
|
|
|
vrcMainPtLpSensorFailAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Low pressure sensor failure alarm status"
|
|
::= { vrcMainPtEntry 27 }
|
|
|
|
vrcMainPtHpSensorFailAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High pressure sensor failure alarm status"
|
|
::= { vrcMainPtEntry 28 }
|
|
|
|
vrcMainPtEevCommFailAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Eev communication failure alarm status"
|
|
::= { vrcMainPtEntry 29 }
|
|
|
|
--###########################################################################################--
|
|
--vrcMainCfgTable--
|
|
--###########################################################################################--
|
|
|
|
vrcMainCfgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcMainCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table that contains general VRC configuration"
|
|
::= { vrc 3 }
|
|
|
|
vrcMainCfgEntry OBJECT-TYPE
|
|
SYNTAX VrcMainCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcMainCfgTable: each entry contains general config
|
|
fields for a VRC device"
|
|
INDEX { vrcMainCfgIndex }
|
|
::= { vrcMainCfgTable 1 }
|
|
|
|
VrcMainCfgEntry ::= SEQUENCE {
|
|
vrcMainCfgIndex Integer32,
|
|
vrcMainCfgModelSelect INTEGER,
|
|
vrcMainCfgSystemTimeYear Integer32,
|
|
vrcMainCfgSystemTimeMonth Integer32,
|
|
vrcMainCfgSystemTimeDay Integer32,
|
|
vrcMainCfgSystemTimeHour Integer32,
|
|
vrcMainCfgSystemTimeMin Integer32,
|
|
vrcMainCfgSystemTimeSec Integer32,
|
|
vrcMainCfgEevShtSettingMin Integer32,
|
|
vrcMainCfgEevShtSettingMax Integer32,
|
|
vrcMainCfgEevValveCloseSht Integer32,
|
|
vrcMainCfgEevMopPressSetting Integer32,
|
|
vrcMainCfgLpdt Integer32,
|
|
vrcMainCfgDeadBand Integer32,
|
|
vrcMainCfgOnOffSwitch TruthValue,
|
|
vrcMainCfgVacuumState TruthValue,
|
|
vrcMainCfgControlMode INTEGER,
|
|
vrcMainCfgManualRunEnable TruthValue,
|
|
vrcMainCfgRemShutdownInput TruthValue,
|
|
vrcMainCfgMonitorShutDownFlag TruthValue,
|
|
vrcMainCfgFirstOnPassword Integer32,
|
|
vrcMainCfgFilterMaintSetting TruthValue,
|
|
vrcMainCfgFilterMaintRemindTime Integer32,
|
|
vrcMainCfgFilterMaintRemindCtrl INTEGER,
|
|
vrcMainCfgCommonAlarmOutputDir TruthValue,
|
|
vrcMainCfgHpAbnAlarmSetting Integer32,
|
|
vrcMainCfgLpAlarmCtrl INTEGER,
|
|
vrcMainCfgHpAlarmCtrl INTEGER,
|
|
vrcMainCfgLpFreqAlarmCtrl INTEGER,
|
|
vrcMainCfgHpFreqAlarmCtrl INTEGER,
|
|
vrcMainCfgLpSensorFailAlarmCtrl INTEGER,
|
|
vrcMainCfgHpSensorFailAlarmCtrl INTEGER,
|
|
vrcMainCfgHighWaterAlarmCtrl INTEGER,
|
|
vrcMainCfgRemShutdownAlarmCtrl INTEGER,
|
|
vrcMainCfgEevCommFailAlarmCtrl INTEGER
|
|
}
|
|
|
|
vrcMainCfgIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcMainCfgEntry 1 }
|
|
|
|
vrcMainCfgModelSelect OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
tmLoc(1),
|
|
r035Ap(2),
|
|
r035Ak(3),
|
|
scLoc(4),
|
|
zeroULoc(5),
|
|
r035Ep(6),
|
|
r035Ek(7)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Model Selection:
|
|
1 = TMM-Local 220V 50/60HZ
|
|
2 = TMM-Global 208/230V 50/60HZ
|
|
3 = TMM-Global 120V 50/60HZ
|
|
4 = SC 220V 50/60HZ
|
|
5 = 0U 220V 50/60HZ
|
|
6 = SS 208/230V 50/60HZ
|
|
7 = SS 120V 50/60HZ"
|
|
::= { vrcMainCfgEntry 2 }
|
|
|
|
vrcMainCfgSystemTimeYear OBJECT-TYPE
|
|
SYNTAX Integer32(2000..2099)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System time - year"
|
|
::= { vrcMainCfgEntry 3 }
|
|
|
|
vrcMainCfgSystemTimeMonth OBJECT-TYPE
|
|
SYNTAX Integer32(1..12)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System time - month"
|
|
::= { vrcMainCfgEntry 4 }
|
|
|
|
vrcMainCfgSystemTimeDay OBJECT-TYPE
|
|
SYNTAX Integer32(1..31)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System time - day"
|
|
::= { vrcMainCfgEntry 5 }
|
|
|
|
vrcMainCfgSystemTimeHour OBJECT-TYPE
|
|
SYNTAX Integer32(0..23)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System time - hour"
|
|
::= { vrcMainCfgEntry 6 }
|
|
|
|
vrcMainCfgSystemTimeMin OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System time - minutes"
|
|
::= { vrcMainCfgEntry 7 }
|
|
|
|
vrcMainCfgSystemTimeSec OBJECT-TYPE
|
|
SYNTAX Integer32(0..59)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System time - seconds"
|
|
::= { vrcMainCfgEntry 8 }
|
|
|
|
vrcMainCfgEevShtSettingMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min Eev sht in tenths of a degree. Units are given by temperatureUnits
|
|
field in deviceInfo. The settable range is determined by the current
|
|
temperature units.
|
|
Celsius: 50 to 200
|
|
Fahrenheit: 90 to 359"
|
|
::= { vrcMainCfgEntry 9 }
|
|
|
|
vrcMainCfgEevShtSettingMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max Eev sht in tenths of a degree. Units are given by temperatureUnits
|
|
field in deviceInfo. The settable range is determined by the current
|
|
temperature units.
|
|
Celsius: 50 to 200
|
|
Fahrenheit: 90 to 359"
|
|
::= { vrcMainCfgEntry 10 }
|
|
|
|
vrcMainCfgEevValveCloseSht OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Eev valve close sht in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo. The settable range is determined
|
|
by the current temperature units.
|
|
Celsius: 0 to 100
|
|
Fahrenheit: 0 to 179"
|
|
::= { vrcMainCfgEntry 11 }
|
|
|
|
vrcMainCfgEevMopPressSetting OBJECT-TYPE
|
|
SYNTAX Integer32(0..200)
|
|
UNITS "decibars"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Eev mop pressure setting in tenths of a bar."
|
|
::= { vrcMainCfgEntry 12 }
|
|
|
|
vrcMainCfgLpdt OBJECT-TYPE
|
|
SYNTAX Integer32(30..600)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Low pressure dt in seconds"
|
|
::= { vrcMainCfgEntry 13 }
|
|
|
|
vrcMainCfgDeadBand OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Dead band in tenths of a degree. Units are given by temperatureUnits
|
|
field in deviceInfo. The settable range is determined by the current
|
|
temperature units.
|
|
Celsius: 0 to 20
|
|
Fahrenheit: 0 to 35"
|
|
::= { vrcMainCfgEntry 14 }
|
|
|
|
vrcMainCfgOnOffSwitch OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"On-off switch"
|
|
::= { vrcMainCfgEntry 15 }
|
|
|
|
vrcMainCfgVacuumState OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Vacuum state"
|
|
::= { vrcMainCfgEntry 16 }
|
|
|
|
vrcMainCfgControlMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
supply(1),
|
|
return(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Control mode:
|
|
1 = supply
|
|
2 = return"
|
|
::= { vrcMainCfgEntry 17 }
|
|
|
|
vrcMainCfgManualRunEnable OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Manual run enable"
|
|
::= { vrcMainCfgEntry 18 }
|
|
|
|
vrcMainCfgRemShutdownInput OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote shutdown input"
|
|
::= { vrcMainCfgEntry 19 }
|
|
|
|
vrcMainCfgMonitorShutDownFlag OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Monitor shutdown flag"
|
|
::= { vrcMainCfgEntry 20 }
|
|
|
|
vrcMainCfgFirstOnPassword OBJECT-TYPE
|
|
SYNTAX Integer32(-32768..32767)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"First on password value"
|
|
::= { vrcMainCfgEntry 21 }
|
|
|
|
vrcMainCfgFilterMaintSetting OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Filter maintenance setting"
|
|
::= { vrcMainCfgEntry 22 }
|
|
|
|
vrcMainCfgFilterMaintRemindTime OBJECT-TYPE
|
|
SYNTAX Integer32(30..360)
|
|
UNITS "days"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time between filter maintenance reminders in days"
|
|
::= { vrcMainCfgEntry 23 }
|
|
|
|
vrcMainCfgFilterMaintRemindCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
close(1),
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Filter maintenance reminder:
|
|
1 = close
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcMainCfgEntry 24 }
|
|
|
|
vrcMainCfgCommonAlarmOutputDir OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Common alarm output direction"
|
|
::= { vrcMainCfgEntry 25 }
|
|
|
|
vrcMainCfgHpAbnAlarmSetting OBJECT-TYPE
|
|
SYNTAX Integer32(300..360)
|
|
UNITS "decibars"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Abnormal high pressure alarm value in tenths of a bar"
|
|
::= { vrcMainCfgEntry 26 }
|
|
|
|
vrcMainCfgLpAlarmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Low pressure alarm control:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcMainCfgEntry 27 }
|
|
|
|
vrcMainCfgHpAlarmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High pressure alarm control:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcMainCfgEntry 28 }
|
|
|
|
vrcMainCfgLpFreqAlarmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Low pressure frequently alarm control:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcMainCfgEntry 29 }
|
|
|
|
vrcMainCfgHpFreqAlarmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High pressure frequently alarm control:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcMainCfgEntry 30 }
|
|
|
|
vrcMainCfgLpSensorFailAlarmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Low pressure sensor failure alarm control:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcMainCfgEntry 31 }
|
|
|
|
vrcMainCfgHpSensorFailAlarmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High pressure sensor failure alarm control:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcMainCfgEntry 32 }
|
|
|
|
vrcMainCfgHighWaterAlarmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
close(1),
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High water alarm control:
|
|
1 = close
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcMainCfgEntry 33 }
|
|
|
|
vrcMainCfgRemShutdownAlarmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote shutdown alarm control:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcMainCfgEntry 34 }
|
|
|
|
vrcMainCfgEevCommFailAlarmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Eev communication failure alarm:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcMainCfgEntry 35 }
|
|
|
|
--###########################################################################################--
|
|
--vrcOutFanPtTable--
|
|
--###########################################################################################--
|
|
|
|
vrcOutFanPtTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcOutFanPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table that contains VRC out-fan status"
|
|
::= { vrc 4 }
|
|
|
|
vrcOutFanPtEntry OBJECT-TYPE
|
|
SYNTAX VrcOutFanPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcOutFanPtTable: each entry represents data for a VRC
|
|
out-fan"
|
|
INDEX { vrcOutFanPtIndex }
|
|
::= { vrcOutFanPtTable 1 }
|
|
|
|
VrcOutFanPtEntry ::= SEQUENCE {
|
|
vrcOutFanPtIndex Integer32,
|
|
vrcOutFanPtName SnmpAdminString,
|
|
vrcOutFanPtSpeed Integer32
|
|
}
|
|
|
|
vrcOutFanPtIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcOutFanPtEntry 1 }
|
|
|
|
vrcOutFanPtName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Out-fan name (factory-assigned)"
|
|
::= { vrcOutFanPtEntry 2 }
|
|
|
|
vrcOutFanPtSpeed OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fan speed (percent)"
|
|
::= { vrcOutFanPtEntry 3 }
|
|
|
|
--###########################################################################################--
|
|
--vrcOutFanCfgTable--
|
|
--###########################################################################################--
|
|
|
|
vrcOutFanCfgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcOutFanCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table used for VRC out-fan configuration"
|
|
::= { vrc 5 }
|
|
|
|
vrcOutFanCfgEntry OBJECT-TYPE
|
|
SYNTAX VrcOutFanCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcOutFanCfgTable: each entry contains config fields for
|
|
a VRC out-fan"
|
|
INDEX { vrcOutFanCfgIndex }
|
|
::= { vrcOutFanCfgTable 1 }
|
|
|
|
VrcOutFanCfgEntry ::= SEQUENCE {
|
|
vrcOutFanCfgIndex Integer32,
|
|
vrcOutFanCfgStartPress Integer32,
|
|
vrcOutFanCfgPressSetting Integer32,
|
|
vrcOutFanCfgMinPowerVoltage Integer32,
|
|
vrcOutFanCfgMaxPowerVoltage Integer32,
|
|
vrcOutFanCfgSpeed Integer32
|
|
}
|
|
|
|
vrcOutFanCfgIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcOutFanCfgEntry 1 }
|
|
|
|
vrcOutFanCfgStartPress OBJECT-TYPE
|
|
SYNTAX Integer32(190..250)
|
|
UNITS "decibars"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Out-fan start pressure in tenths of a bar"
|
|
::= { vrcOutFanCfgEntry 2 }
|
|
|
|
vrcOutFanCfgPressSetting OBJECT-TYPE
|
|
SYNTAX Integer32(50..80)
|
|
UNITS "decibars"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Out-fan pressure setting in tenths of a bar"
|
|
::= { vrcOutFanCfgEntry 3 }
|
|
|
|
vrcOutFanCfgMinPowerVoltage OBJECT-TYPE
|
|
SYNTAX Integer32(30..50)
|
|
UNITS "%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min out-fan voltage (percent)"
|
|
::= { vrcOutFanCfgEntry 4 }
|
|
|
|
vrcOutFanCfgMaxPowerVoltage OBJECT-TYPE
|
|
SYNTAX Integer32(60..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max out-fan voltage (percent)"
|
|
::= { vrcOutFanCfgEntry 5 }
|
|
|
|
vrcOutFanCfgSpeed OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Out-fan speed (percent)"
|
|
::= { vrcOutFanCfgEntry 6 }
|
|
|
|
--###########################################################################################--
|
|
--vrcInFanPtTable--
|
|
--###########################################################################################--
|
|
|
|
vrcInFanPtTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcInFanPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table that contains VRC in-fan status"
|
|
::= { vrc 6 }
|
|
|
|
vrcInFanPtEntry OBJECT-TYPE
|
|
SYNTAX VrcInFanPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcInFanPtTable: each entry represents data for a VRC in-
|
|
fan"
|
|
INDEX { vrcInFanPtIndex }
|
|
::= { vrcInFanPtTable 1 }
|
|
|
|
VrcInFanPtEntry ::= SEQUENCE {
|
|
vrcInFanPtIndex Integer32,
|
|
vrcInFanPtName SnmpAdminString,
|
|
vrcInFanPtRunTimeHours Integer32,
|
|
vrcInFanPtStartStopCount Integer32
|
|
}
|
|
|
|
vrcInFanPtIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcInFanPtEntry 1 }
|
|
|
|
vrcInFanPtName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan name (factory-assigned)"
|
|
::= { vrcInFanPtEntry 2 }
|
|
|
|
vrcInFanPtRunTimeHours OBJECT-TYPE
|
|
SYNTAX Integer32(-32768..32767)
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan run time in hours"
|
|
::= { vrcInFanPtEntry 3 }
|
|
|
|
vrcInFanPtStartStopCount OBJECT-TYPE
|
|
SYNTAX Integer32(-32768..32767)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan start/stop count"
|
|
::= { vrcInFanPtEntry 4 }
|
|
|
|
--###########################################################################################--
|
|
--vrcInFanCfgTable--
|
|
--###########################################################################################--
|
|
|
|
vrcInFanCfgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcInFanCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table used for VRC in-fan configuration"
|
|
::= { vrc 7 }
|
|
|
|
vrcInFanCfgEntry OBJECT-TYPE
|
|
SYNTAX VrcInFanCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcInFanCfgTable: each entry contains config fields for a
|
|
VRC in-fan"
|
|
INDEX { vrcInFanCfgIndex }
|
|
::= { vrcInFanCfgTable 1 }
|
|
|
|
VrcInFanCfgEntry ::= SEQUENCE {
|
|
vrcInFanCfgIndex Integer32,
|
|
vrcInFanCfgOutputStatus TruthValue,
|
|
vrcInFanCfgLowSpeedStep Integer32,
|
|
vrcInFanCfgHighSpeedStep Integer32,
|
|
vrcInFanCfgMinSpeed Integer32,
|
|
vrcInFanCfgStandardSpeed Integer32,
|
|
vrcInFanCfgMinCfc Integer32,
|
|
vrcInFanCfgStandardCfc Integer32,
|
|
vrcInFanCfgStartDelay Integer32,
|
|
vrcInFanCfgStopDelay Integer32,
|
|
vrcInFanCfgReduceSpeedDelay Integer32,
|
|
vrcInFanCfgJumpBand1 Integer32,
|
|
vrcInFanCfgJumpBand2 Integer32,
|
|
vrcInFanCfgJumpBand3 Integer32,
|
|
vrcInFanCfgJumpBand4 Integer32,
|
|
vrcInFanCfgJumpBand5 Integer32,
|
|
vrcInFanCfgJumpFreq1 Integer32,
|
|
vrcInFanCfgJumpFreq2 Integer32,
|
|
vrcInFanCfgJumpFreq3 Integer32,
|
|
vrcInFanCfgJumpFreq4 Integer32,
|
|
vrcInFanCfgJumpFreq5 Integer32,
|
|
vrcInFanCfgTempP Integer32,
|
|
vrcInFanCfgTempI Integer32,
|
|
vrcInFanCfgTempD Integer32
|
|
}
|
|
|
|
vrcInFanCfgIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcInFanCfgEntry 1 }
|
|
|
|
vrcInFanCfgOutputStatus OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan output status"
|
|
::= { vrcInFanCfgEntry 2 }
|
|
|
|
vrcInFanCfgLowSpeedStep OBJECT-TYPE
|
|
SYNTAX Integer32(1..20)
|
|
UNITS "0.1%/s"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan low speed step in tenths of a percent per second"
|
|
::= { vrcInFanCfgEntry 3 }
|
|
|
|
vrcInFanCfgHighSpeedStep OBJECT-TYPE
|
|
SYNTAX Integer32(1..50)
|
|
UNITS "0.1%/s"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan high speed step in tenths of a percent per second"
|
|
::= { vrcInFanCfgEntry 4 }
|
|
|
|
vrcInFanCfgMinSpeed OBJECT-TYPE
|
|
SYNTAX Integer32(30..80)
|
|
UNITS "%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min in-fan speed (percent)"
|
|
::= { vrcInFanCfgEntry 5 }
|
|
|
|
vrcInFanCfgStandardSpeed OBJECT-TYPE
|
|
SYNTAX Integer32(80..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Standard in-fan speed (percent)"
|
|
::= { vrcInFanCfgEntry 6 }
|
|
|
|
vrcInFanCfgMinCfc OBJECT-TYPE
|
|
SYNTAX Integer32(0..30)
|
|
UNITS "%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min in-fan cfc (percent)"
|
|
::= { vrcInFanCfgEntry 7 }
|
|
|
|
vrcInFanCfgStandardCfc OBJECT-TYPE
|
|
SYNTAX Integer32(85..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Standard in-fan cfc (percent)"
|
|
::= { vrcInFanCfgEntry 8 }
|
|
|
|
vrcInFanCfgStartDelay OBJECT-TYPE
|
|
SYNTAX Integer32(10..600)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan start delay in seconds"
|
|
::= { vrcInFanCfgEntry 9 }
|
|
|
|
vrcInFanCfgStopDelay OBJECT-TYPE
|
|
SYNTAX Integer32(10..300)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan stop delay in seconds"
|
|
::= { vrcInFanCfgEntry 10 }
|
|
|
|
vrcInFanCfgReduceSpeedDelay OBJECT-TYPE
|
|
SYNTAX Integer32(0..300)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan reduce speed delay in seconds"
|
|
::= { vrcInFanCfgEntry 11 }
|
|
|
|
vrcInFanCfgJumpBand1 OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan jump band 1 in tenths of a percent"
|
|
::= { vrcInFanCfgEntry 12 }
|
|
|
|
vrcInFanCfgJumpBand2 OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan jump band 2 in tenths of a percent"
|
|
::= { vrcInFanCfgEntry 13 }
|
|
|
|
vrcInFanCfgJumpBand3 OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan jump band 3 in tenths of a percent"
|
|
::= { vrcInFanCfgEntry 14 }
|
|
|
|
vrcInFanCfgJumpBand4 OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan jump band 4 in tenths of a percent"
|
|
::= { vrcInFanCfgEntry 15 }
|
|
|
|
vrcInFanCfgJumpBand5 OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan jump band 5 in tenths of a percent"
|
|
::= { vrcInFanCfgEntry 16 }
|
|
|
|
vrcInFanCfgJumpFreq1 OBJECT-TYPE
|
|
SYNTAX Integer32(0..1000)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan jump frequency 1 in tenths of a percent"
|
|
::= { vrcInFanCfgEntry 17 }
|
|
|
|
vrcInFanCfgJumpFreq2 OBJECT-TYPE
|
|
SYNTAX Integer32(0..1000)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan jump frequency 2 in tenths of a percent"
|
|
::= { vrcInFanCfgEntry 18 }
|
|
|
|
vrcInFanCfgJumpFreq3 OBJECT-TYPE
|
|
SYNTAX Integer32(0..1000)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan jump frequency 3 in tenths of a percent"
|
|
::= { vrcInFanCfgEntry 19 }
|
|
|
|
vrcInFanCfgJumpFreq4 OBJECT-TYPE
|
|
SYNTAX Integer32(0..1000)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan jump frequency 4 in tenths of a percent"
|
|
::= { vrcInFanCfgEntry 20 }
|
|
|
|
vrcInFanCfgJumpFreq5 OBJECT-TYPE
|
|
SYNTAX Integer32(0..1000)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan jump frequency 5 in tenths of a percent"
|
|
::= { vrcInFanCfgEntry 21 }
|
|
|
|
vrcInFanCfgTempP OBJECT-TYPE
|
|
SYNTAX Integer32(10..150)
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan temperature P in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo."
|
|
::= { vrcInFanCfgEntry 22 }
|
|
|
|
vrcInFanCfgTempI OBJECT-TYPE
|
|
SYNTAX Integer32(0..900)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan temperature I in seconds"
|
|
::= { vrcInFanCfgEntry 23 }
|
|
|
|
vrcInFanCfgTempD OBJECT-TYPE
|
|
SYNTAX Integer32(0..900)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"In-fan temperature D in seconds"
|
|
::= { vrcInFanCfgEntry 24 }
|
|
|
|
--###########################################################################################--
|
|
--vrcCompPtTable--
|
|
--###########################################################################################--
|
|
|
|
vrcCompPtTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcCompPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table that contains VRC compressor status"
|
|
::= { vrc 8 }
|
|
|
|
vrcCompPtEntry OBJECT-TYPE
|
|
SYNTAX VrcCompPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcCompPtTable: each entry represents data for a VRC
|
|
compressor"
|
|
INDEX { vrcCompPtIndex }
|
|
::= { vrcCompPtTable 1 }
|
|
|
|
VrcCompPtEntry ::= SEQUENCE {
|
|
vrcCompPtIndex Integer32,
|
|
vrcCompPtName SnmpAdminString,
|
|
vrcCompPtCapacity Integer32,
|
|
vrcCompPtRunTimeHours Integer32,
|
|
vrcCompPtStartStopCount Integer32,
|
|
vrcCompPtDriverFaultU00 TruthValue,
|
|
vrcCompPtDriverFaultU01 TruthValue,
|
|
vrcCompPtDriverFaultU02 TruthValue,
|
|
vrcCompPtDriverFaultU03 TruthValue,
|
|
vrcCompPtDriverFaultU04 TruthValue,
|
|
vrcCompPtDriverFaultU05 TruthValue,
|
|
vrcCompPtDriverFaultU06 TruthValue,
|
|
vrcCompPtDriverFaultU07 TruthValue,
|
|
vrcCompPtDriverFaultU08 TruthValue,
|
|
vrcCompPtDriverFaultU09 TruthValue,
|
|
vrcCompPtDriverFaultU10 TruthValue,
|
|
vrcCompPtDriverFaultU11 TruthValue,
|
|
vrcCompPtDriverFaultU12 TruthValue,
|
|
vrcCompPtDriverFaultU13 TruthValue,
|
|
vrcCompPtDriverFaultU14 TruthValue,
|
|
vrcCompPtDriverFaultU15 TruthValue,
|
|
vrcCompPtDriverCommFailAlarm TruthValue,
|
|
vrcCompPtFaultLockAlarm TruthValue
|
|
}
|
|
|
|
vrcCompPtIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcCompPtEntry 1 }
|
|
|
|
vrcCompPtName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor name (factory-assigned)"
|
|
::= { vrcCompPtEntry 2 }
|
|
|
|
vrcCompPtCapacity OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor capacity value (percent)"
|
|
::= { vrcCompPtEntry 3 }
|
|
|
|
vrcCompPtRunTimeHours OBJECT-TYPE
|
|
SYNTAX Integer32(-32768..32767)
|
|
UNITS "hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor run time in hours"
|
|
::= { vrcCompPtEntry 4 }
|
|
|
|
vrcCompPtStartStopCount OBJECT-TYPE
|
|
SYNTAX Integer32(-32768..32767)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor start/stop count"
|
|
::= { vrcCompPtEntry 5 }
|
|
|
|
vrcCompPtDriverFaultU00 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U00 state"
|
|
::= { vrcCompPtEntry 6 }
|
|
|
|
vrcCompPtDriverFaultU01 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U01 state"
|
|
::= { vrcCompPtEntry 7 }
|
|
|
|
vrcCompPtDriverFaultU02 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U02 state"
|
|
::= { vrcCompPtEntry 8 }
|
|
|
|
vrcCompPtDriverFaultU03 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U03 state"
|
|
::= { vrcCompPtEntry 9 }
|
|
|
|
vrcCompPtDriverFaultU04 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U04 state"
|
|
::= { vrcCompPtEntry 10 }
|
|
|
|
vrcCompPtDriverFaultU05 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U05 state"
|
|
::= { vrcCompPtEntry 11 }
|
|
|
|
vrcCompPtDriverFaultU06 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U06 state"
|
|
::= { vrcCompPtEntry 12 }
|
|
|
|
vrcCompPtDriverFaultU07 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U07 state"
|
|
::= { vrcCompPtEntry 13 }
|
|
|
|
vrcCompPtDriverFaultU08 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U08 state"
|
|
::= { vrcCompPtEntry 14 }
|
|
|
|
vrcCompPtDriverFaultU09 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U09 state"
|
|
::= { vrcCompPtEntry 15 }
|
|
|
|
vrcCompPtDriverFaultU10 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U10 state"
|
|
::= { vrcCompPtEntry 16 }
|
|
|
|
vrcCompPtDriverFaultU11 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U11 state"
|
|
::= { vrcCompPtEntry 17 }
|
|
|
|
vrcCompPtDriverFaultU12 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U12 state"
|
|
::= { vrcCompPtEntry 18 }
|
|
|
|
vrcCompPtDriverFaultU13 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U13 state"
|
|
::= { vrcCompPtEntry 19 }
|
|
|
|
vrcCompPtDriverFaultU14 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U14 state"
|
|
::= { vrcCompPtEntry 20 }
|
|
|
|
vrcCompPtDriverFaultU15 OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm U15 state"
|
|
::= { vrcCompPtEntry 21 }
|
|
|
|
vrcCompPtDriverCommFailAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver communication failure alarm state"
|
|
::= { vrcCompPtEntry 22 }
|
|
|
|
vrcCompPtFaultLockAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor fault lock alarm state"
|
|
::= { vrcCompPtEntry 23 }
|
|
|
|
--###########################################################################################--
|
|
--vrcCompCfgTable--
|
|
--###########################################################################################--
|
|
|
|
vrcCompCfgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcCompCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table used for VRC compressor configuration"
|
|
::= { vrc 9 }
|
|
|
|
vrcCompCfgEntry OBJECT-TYPE
|
|
SYNTAX VrcCompCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcCompCfgTable: each entry contains config fields for a
|
|
VRC compressor"
|
|
INDEX { vrcCompCfgIndex }
|
|
::= { vrcCompCfgTable 1 }
|
|
|
|
VrcCompCfgEntry ::= SEQUENCE {
|
|
vrcCompCfgIndex Integer32,
|
|
vrcCompCfgOutputStatus TruthValue,
|
|
vrcCompCfgOutputDeadBand Integer32,
|
|
vrcCompCfgCapacityOutputValue Integer32,
|
|
vrcCompCfgMinCapacity Integer32,
|
|
vrcCompCfgStartCapacity Integer32,
|
|
vrcCompCfgStandardCapacity Integer32,
|
|
vrcCompCfgStartCfc Integer32,
|
|
vrcCompCfgStopCfc Integer32,
|
|
vrcCompCfgMinRunTime Integer32,
|
|
vrcCompCfgMinStopTime Integer32,
|
|
vrcCompCfgJumpBand1 Integer32,
|
|
vrcCompCfgJumpBand2 Integer32,
|
|
vrcCompCfgJumpBand3 Integer32,
|
|
vrcCompCfgJumpBand4 Integer32,
|
|
vrcCompCfgJumpBand5 Integer32,
|
|
vrcCompCfgJumpFreq1 Integer32,
|
|
vrcCompCfgJumpFreq2 Integer32,
|
|
vrcCompCfgJumpFreq3 Integer32,
|
|
vrcCompCfgJumpFreq4 Integer32,
|
|
vrcCompCfgJumpFreq5 Integer32,
|
|
vrcCompCfgTempP Integer32,
|
|
vrcCompCfgTempI Integer32,
|
|
vrcCompCfgTempD Integer32,
|
|
vrcCompCfgDriverFaultAlmCtrl INTEGER,
|
|
vrcCompCfgDriverCommFailAlmCtrl INTEGER,
|
|
vrcCompCfgFaultLockAlmCtrl INTEGER
|
|
}
|
|
|
|
vrcCompCfgIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcCompCfgEntry 1 }
|
|
|
|
vrcCompCfgOutputStatus OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor output status"
|
|
::= { vrcCompCfgEntry 2 }
|
|
|
|
vrcCompCfgOutputDeadBand OBJECT-TYPE
|
|
SYNTAX Integer32(0..50)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor output dead band in tenths of a percent"
|
|
::= { vrcCompCfgEntry 3 }
|
|
|
|
vrcCompCfgCapacityOutputValue OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor capacity output (percent)"
|
|
::= { vrcCompCfgEntry 4 }
|
|
|
|
vrcCompCfgMinCapacity OBJECT-TYPE
|
|
SYNTAX Integer32(15..50)
|
|
UNITS "%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor min capacity (percent)"
|
|
::= { vrcCompCfgEntry 5 }
|
|
|
|
vrcCompCfgStartCapacity OBJECT-TYPE
|
|
SYNTAX Integer32(40..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor start capacity (percent)"
|
|
::= { vrcCompCfgEntry 6 }
|
|
|
|
vrcCompCfgStandardCapacity OBJECT-TYPE
|
|
SYNTAX Integer32(80..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor standard capacity (percent)"
|
|
::= { vrcCompCfgEntry 7 }
|
|
|
|
vrcCompCfgStartCfc OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor start cfc (percent)"
|
|
::= { vrcCompCfgEntry 8 }
|
|
|
|
vrcCompCfgStopCfc OBJECT-TYPE
|
|
SYNTAX Integer32(-200..-50)
|
|
UNITS "%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor stop cfc (percent)"
|
|
::= { vrcCompCfgEntry 9 }
|
|
|
|
vrcCompCfgMinRunTime OBJECT-TYPE
|
|
SYNTAX Integer32(0..30)
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor min run time in minutes"
|
|
::= { vrcCompCfgEntry 10 }
|
|
|
|
vrcCompCfgMinStopTime OBJECT-TYPE
|
|
SYNTAX Integer32(0..10)
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor min stop time in minutes"
|
|
::= { vrcCompCfgEntry 11 }
|
|
|
|
vrcCompCfgJumpBand1 OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor jump band 1 in tenths of a percent"
|
|
::= { vrcCompCfgEntry 12 }
|
|
|
|
vrcCompCfgJumpBand2 OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor jump band 2 in tenths of a percent"
|
|
::= { vrcCompCfgEntry 13 }
|
|
|
|
vrcCompCfgJumpBand3 OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor jump band 3 in tenths of a percent"
|
|
::= { vrcCompCfgEntry 14 }
|
|
|
|
vrcCompCfgJumpBand4 OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor jump band 4 in tenths of a percent"
|
|
::= { vrcCompCfgEntry 15 }
|
|
|
|
vrcCompCfgJumpBand5 OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor jump band 5 in tenths of a percent"
|
|
::= { vrcCompCfgEntry 16 }
|
|
|
|
vrcCompCfgJumpFreq1 OBJECT-TYPE
|
|
SYNTAX Integer32(0..1000)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor jump frequency 1 in tenths of a percent"
|
|
::= { vrcCompCfgEntry 17 }
|
|
|
|
vrcCompCfgJumpFreq2 OBJECT-TYPE
|
|
SYNTAX Integer32(0..1000)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor jump frequency 2 in tenths of a percent"
|
|
::= { vrcCompCfgEntry 18 }
|
|
|
|
vrcCompCfgJumpFreq3 OBJECT-TYPE
|
|
SYNTAX Integer32(0..1000)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor jump frequency 3 in tenths of a percent"
|
|
::= { vrcCompCfgEntry 19 }
|
|
|
|
vrcCompCfgJumpFreq4 OBJECT-TYPE
|
|
SYNTAX Integer32(0..1000)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor jump frequency 4 in tenths of a percent"
|
|
::= { vrcCompCfgEntry 20 }
|
|
|
|
vrcCompCfgJumpFreq5 OBJECT-TYPE
|
|
SYNTAX Integer32(0..1000)
|
|
UNITS "0.1%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor jump frequency 5 in tenths of a percent"
|
|
::= { vrcCompCfgEntry 21 }
|
|
|
|
vrcCompCfgTempP OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor temperature P in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo. The settable range is determined
|
|
by the current temperature units.
|
|
Celsius: 10 to 150
|
|
Fahrenheit: 18 to 269"
|
|
::= { vrcCompCfgEntry 22 }
|
|
|
|
vrcCompCfgTempI OBJECT-TYPE
|
|
SYNTAX Integer32(0..900)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor temperature I in seconds"
|
|
::= { vrcCompCfgEntry 23 }
|
|
|
|
vrcCompCfgTempD OBJECT-TYPE
|
|
SYNTAX Integer32(0..900)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor temperature D in seconds"
|
|
::= { vrcCompCfgEntry 24 }
|
|
|
|
vrcCompCfgDriverFaultAlmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver fault alarm control:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcCompCfgEntry 25 }
|
|
|
|
vrcCompCfgDriverCommFailAlmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor driver communication failure alarm control:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcCompCfgEntry 26 }
|
|
|
|
vrcCompCfgFaultLockAlmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor fault lock alarm control:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcCompCfgEntry 27 }
|
|
|
|
--###########################################################################################--
|
|
--vrcReturnPtTable--
|
|
--###########################################################################################--
|
|
|
|
vrcReturnPtTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcReturnPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table that contains VRC return status"
|
|
::= { vrc 10 }
|
|
|
|
vrcReturnPtEntry OBJECT-TYPE
|
|
SYNTAX VrcReturnPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcReturnPtTable: each entry represents return data for a
|
|
VRC"
|
|
INDEX { vrcReturnPtIndex }
|
|
::= { vrcReturnPtTable 1 }
|
|
|
|
VrcReturnPtEntry ::= SEQUENCE {
|
|
vrcReturnPtIndex Integer32,
|
|
vrcReturnPtName SnmpAdminString,
|
|
vrcReturnPtTemp Integer32,
|
|
vrcReturnPtHighTempAlarm TruthValue,
|
|
vrcReturnPtTempSensorFailAlarm TruthValue
|
|
}
|
|
|
|
vrcReturnPtIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcReturnPtEntry 1 }
|
|
|
|
vrcReturnPtName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return name (factory-assigned)"
|
|
::= { vrcReturnPtEntry 2 }
|
|
|
|
vrcReturnPtTemp OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return temperature value in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo. The range is determined by the
|
|
current temperature units.
|
|
Celsius: -400 to 1000
|
|
Fahrenheit: -400 to 2120"
|
|
::= { vrcReturnPtEntry 3 }
|
|
|
|
vrcReturnPtHighTempAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return high temperature alarm state"
|
|
::= { vrcReturnPtEntry 4 }
|
|
|
|
vrcReturnPtTempSensorFailAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return temperature sensor failure alarm state"
|
|
::= { vrcReturnPtEntry 5 }
|
|
|
|
--###########################################################################################--
|
|
--vrcReturnCfgTable--
|
|
--###########################################################################################--
|
|
|
|
vrcReturnCfgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcReturnCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table used for VRC return configuration"
|
|
::= { vrc 11 }
|
|
|
|
vrcReturnCfgEntry OBJECT-TYPE
|
|
SYNTAX VrcReturnCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcReturnCfgTable: each entry contains config fields for
|
|
VRC return"
|
|
INDEX { vrcReturnCfgIndex }
|
|
::= { vrcReturnCfgTable 1 }
|
|
|
|
VrcReturnCfgEntry ::= SEQUENCE {
|
|
vrcReturnCfgIndex Integer32,
|
|
vrcReturnCfgOilCycle Integer32,
|
|
vrcReturnCfgOilRunCapacity Integer32,
|
|
vrcReturnCfgOilRunTime Integer32,
|
|
vrcReturnCfgTempCalValue Integer32,
|
|
vrcReturnCfgTempSetting Integer32,
|
|
vrcReturnCfgHighTempAlarmValue Integer32,
|
|
vrcReturnCfgHighTempAlarmCtrl INTEGER,
|
|
vrcReturnCfgTempSensFailAlmCtrl INTEGER
|
|
}
|
|
|
|
vrcReturnCfgIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcReturnCfgEntry 1 }
|
|
|
|
vrcReturnCfgOilCycle OBJECT-TYPE
|
|
SYNTAX Integer32(5..50)
|
|
UNITS "decihours"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return oil cycle in tenths of an hour"
|
|
::= { vrcReturnCfgEntry 2 }
|
|
|
|
vrcReturnCfgOilRunCapacity OBJECT-TYPE
|
|
SYNTAX Integer32(50..100)
|
|
UNITS "%"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return Oil run capacity (percent)"
|
|
::= { vrcReturnCfgEntry 3 }
|
|
|
|
vrcReturnCfgOilRunTime OBJECT-TYPE
|
|
SYNTAX Integer32(0..10)
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return oil run time in minutes"
|
|
::= { vrcReturnCfgEntry 4 }
|
|
|
|
vrcReturnCfgTempCalValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return temperature calibration value in tenths of a degree. Units are
|
|
given by temperatureUnits field in deviceInfo. The settable range is
|
|
determined by the current temperature units.
|
|
Celsius: -100 to 100
|
|
Fahrenheit: -179 to 179"
|
|
::= { vrcReturnCfgEntry 5 }
|
|
|
|
vrcReturnCfgTempSetting OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return temperature setting in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo. The settable range is determined
|
|
by the current temperature units.
|
|
Celsius: 250 to 350
|
|
Fahrenheit: 770 to 949"
|
|
::= { vrcReturnCfgEntry 6 }
|
|
|
|
vrcReturnCfgHighTempAlarmValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return high temperature alarm value in tenths of a degree. Units are
|
|
given by temperatureUnits field in deviceInfo. The settable range is
|
|
determined by the current temperature units.
|
|
Celsius: 300 to 450
|
|
Fahrenheit: 860 to 1129"
|
|
::= { vrcReturnCfgEntry 7 }
|
|
|
|
vrcReturnCfgHighTempAlarmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
close(1),
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return high temperature alarm control:
|
|
1 = close
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcReturnCfgEntry 8 }
|
|
|
|
vrcReturnCfgTempSensFailAlmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
close(1),
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return temperature sensor failure alarm control:
|
|
1 = close
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcReturnCfgEntry 9 }
|
|
|
|
--###########################################################################################--
|
|
--vrcSupplyPtTable--
|
|
--###########################################################################################--
|
|
|
|
vrcSupplyPtTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcSupplyPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table that contains VRC supply status"
|
|
::= { vrc 12 }
|
|
|
|
vrcSupplyPtEntry OBJECT-TYPE
|
|
SYNTAX VrcSupplyPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcSupplyPtTable: each entry represents supply data for a
|
|
VRC"
|
|
INDEX { vrcSupplyPtIndex }
|
|
::= { vrcSupplyPtTable 1 }
|
|
|
|
VrcSupplyPtEntry ::= SEQUENCE {
|
|
vrcSupplyPtIndex Integer32,
|
|
vrcSupplyPtName SnmpAdminString,
|
|
vrcSupplyPtTemp Integer32,
|
|
vrcSupplyPtLowTempAlarm TruthValue,
|
|
vrcSupplyPtHighTempAlarm TruthValue,
|
|
vrcSupplyPtTempSensorFailAlarm TruthValue
|
|
}
|
|
|
|
vrcSupplyPtIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcSupplyPtEntry 1 }
|
|
|
|
vrcSupplyPtName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply name (factory-assigned)"
|
|
::= { vrcSupplyPtEntry 2 }
|
|
|
|
vrcSupplyPtTemp OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply temperature value in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo. The range is determined by the
|
|
current temperature units.
|
|
Celsius: -400 to 1000
|
|
Fahrenheit: -400 to 2120"
|
|
::= { vrcSupplyPtEntry 3 }
|
|
|
|
vrcSupplyPtLowTempAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply low temperature alarm state"
|
|
::= { vrcSupplyPtEntry 4 }
|
|
|
|
vrcSupplyPtHighTempAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply high temperature alarm state"
|
|
::= { vrcSupplyPtEntry 5 }
|
|
|
|
vrcSupplyPtTempSensorFailAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply temperature sensor failure alarm state"
|
|
::= { vrcSupplyPtEntry 6 }
|
|
|
|
--###########################################################################################--
|
|
--vrcSupplyCfgTable--
|
|
--###########################################################################################--
|
|
|
|
vrcSupplyCfgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcSupplyCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table used for VRC supply configuration"
|
|
::= { vrc 13 }
|
|
|
|
vrcSupplyCfgEntry OBJECT-TYPE
|
|
SYNTAX VrcSupplyCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcSupplyCfgTable: each entry contains config fields for
|
|
a VRC supply"
|
|
INDEX { vrcSupplyCfgIndex }
|
|
::= { vrcSupplyCfgTable 1 }
|
|
|
|
VrcSupplyCfgEntry ::= SEQUENCE {
|
|
vrcSupplyCfgIndex Integer32,
|
|
vrcSupplyCfgTempCalValue Integer32,
|
|
vrcSupplyCfgTempSetting Integer32,
|
|
vrcSupplyCfgLowTempAlarmValue Integer32,
|
|
vrcSupplyCfgHighTempAlarmValue Integer32,
|
|
vrcSupplyCfgLowTempAlmCtrl INTEGER,
|
|
vrcSupplyCfgHighTempAlmCtrl INTEGER,
|
|
vrcSupplyCfgTempSensFailAlmCtrl INTEGER
|
|
}
|
|
|
|
vrcSupplyCfgIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcSupplyCfgEntry 1 }
|
|
|
|
vrcSupplyCfgTempCalValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply temperature calibration value in tenths of a degree. Units are
|
|
given by temperatureUnits field in deviceInfo. The settable range is
|
|
determined by the current temperature units.
|
|
Celsius: -100 to 100
|
|
Fahrenheit: -179 to 179"
|
|
::= { vrcSupplyCfgEntry 2 }
|
|
|
|
vrcSupplyCfgTempSetting OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply temperature setting in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo. The settable range is determined
|
|
by the current temperature units.
|
|
Celsius: 130 to 280
|
|
Fahrenheit: 554 to 823"
|
|
::= { vrcSupplyCfgEntry 3 }
|
|
|
|
vrcSupplyCfgLowTempAlarmValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply low temperature alarm value in tenths of a degree. Units are
|
|
given by temperatureUnits field in deviceInfo. The settable range is
|
|
determined by the current temperature units.
|
|
Celsius: 50 to 200
|
|
Fahrenheit: 410 to 679"
|
|
::= { vrcSupplyCfgEntry 4 }
|
|
|
|
vrcSupplyCfgHighTempAlarmValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply high temperature alarm value in tenths of a degree. Units are
|
|
given by temperatureUnits field in deviceInfo. The settable range is
|
|
determined by the current temperature units.
|
|
Celsius: 200 to 350
|
|
Fahrenheit: 680 to 949"
|
|
::= { vrcSupplyCfgEntry 5 }
|
|
|
|
vrcSupplyCfgLowTempAlmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
close(1),
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply low temperature alarm control:
|
|
1 = close
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcSupplyCfgEntry 6 }
|
|
|
|
vrcSupplyCfgHighTempAlmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
close(1),
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply high temperature alarm control:
|
|
1 = close
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcSupplyCfgEntry 7 }
|
|
|
|
vrcSupplyCfgTempSensFailAlmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
close(1),
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply temperature sensor failure alarm control:
|
|
1 = close
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcSupplyCfgEntry 8 }
|
|
|
|
--###########################################################################################--
|
|
--vrcPowerPtTable--
|
|
--###########################################################################################--
|
|
|
|
vrcPowerPtTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcPowerPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table that contains VRC power status"
|
|
::= { vrc 14 }
|
|
|
|
vrcPowerPtEntry OBJECT-TYPE
|
|
SYNTAX VrcPowerPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcPowerPtTable: each entry represents power data for a
|
|
VRC"
|
|
INDEX { vrcPowerPtIndex }
|
|
::= { vrcPowerPtTable 1 }
|
|
|
|
VrcPowerPtEntry ::= SEQUENCE {
|
|
vrcPowerPtIndex Integer32,
|
|
vrcPowerPtName SnmpAdminString,
|
|
vrcPowerPtVoltage Integer32,
|
|
vrcPowerPtFrequency Integer32,
|
|
vrcPowerPtLowVoltageAlarm TruthValue,
|
|
vrcPowerPtHighVoltageAlarm TruthValue,
|
|
vrcPowerPtLossOfPhasePowerAlarm TruthValue,
|
|
vrcPowerPtLossOfPowerAlarm TruthValue,
|
|
vrcPowerPtFrequencyErrorAlarm TruthValue
|
|
}
|
|
|
|
vrcPowerPtIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcPowerPtEntry 1 }
|
|
|
|
vrcPowerPtName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power name (factory-assigned)"
|
|
::= { vrcPowerPtEntry 2 }
|
|
|
|
vrcPowerPtVoltage OBJECT-TYPE
|
|
SYNTAX Integer32(-32768..32767)
|
|
UNITS "decivolts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power voltage measurement in tenths of a volt"
|
|
::= { vrcPowerPtEntry 3 }
|
|
|
|
vrcPowerPtFrequency OBJECT-TYPE
|
|
SYNTAX Integer32(-32768..32767)
|
|
UNITS "decihertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power frequency measurement in tenths of hertz"
|
|
::= { vrcPowerPtEntry 4 }
|
|
|
|
vrcPowerPtLowVoltageAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power low voltage alarm state"
|
|
::= { vrcPowerPtEntry 5 }
|
|
|
|
vrcPowerPtHighVoltageAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power high voltage alarm state"
|
|
::= { vrcPowerPtEntry 6 }
|
|
|
|
vrcPowerPtLossOfPhasePowerAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Phase power loss alarm state"
|
|
::= { vrcPowerPtEntry 7 }
|
|
|
|
vrcPowerPtLossOfPowerAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power loss alarm state"
|
|
::= { vrcPowerPtEntry 8 }
|
|
|
|
vrcPowerPtFrequencyErrorAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power frequency error alarm state"
|
|
::= { vrcPowerPtEntry 9 }
|
|
|
|
--###########################################################################################--
|
|
--vrcPowerCfgTable--
|
|
--###########################################################################################--
|
|
|
|
vrcPowerCfgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcPowerCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table used for VRC power configuration"
|
|
::= { vrc 15 }
|
|
|
|
vrcPowerCfgEntry OBJECT-TYPE
|
|
SYNTAX VrcPowerCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcPowerCfgTable: each entry contains config fields for
|
|
VRC power"
|
|
INDEX { vrcPowerCfgIndex }
|
|
::= { vrcPowerCfgTable 1 }
|
|
|
|
VrcPowerCfgEntry ::= SEQUENCE {
|
|
vrcPowerCfgIndex Integer32,
|
|
vrcPowerCfgLowVoltageSetting Integer32,
|
|
vrcPowerCfgHighVoltageSetting Integer32,
|
|
vrcPowerCfgLowVoltageAlarmCtrl INTEGER,
|
|
vrcPowerCfgHighVoltageAlarmCtrl INTEGER,
|
|
vrcPowerCfgLossOfPowerAlarmCtrl INTEGER,
|
|
vrcPowerCfgFreqErrorAlarmCtrl INTEGER
|
|
}
|
|
|
|
vrcPowerCfgIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcPowerCfgEntry 1 }
|
|
|
|
vrcPowerCfgLowVoltageSetting OBJECT-TYPE
|
|
SYNTAX Integer32(100..230)
|
|
UNITS "volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power low voltage setting in volts"
|
|
::= { vrcPowerCfgEntry 2 }
|
|
|
|
vrcPowerCfgHighVoltageSetting OBJECT-TYPE
|
|
SYNTAX Integer32(100..300)
|
|
UNITS "volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power high voltage setting in volts"
|
|
::= { vrcPowerCfgEntry 3 }
|
|
|
|
vrcPowerCfgLowVoltageAlarmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
close(1),
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power low voltage alarm control:
|
|
1 = close
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcPowerCfgEntry 4 }
|
|
|
|
vrcPowerCfgHighVoltageAlarmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
close(1),
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power high voltage alarm control:
|
|
1 = close
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcPowerCfgEntry 5 }
|
|
|
|
vrcPowerCfgLossOfPowerAlarmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
close(1),
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power loss alarm control:
|
|
1 = close
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcPowerCfgEntry 6 }
|
|
|
|
vrcPowerCfgFreqErrorAlarmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
close(1),
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power frequency error alarm control:
|
|
1 = close
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcPowerCfgEntry 7 }
|
|
|
|
--###########################################################################################--
|
|
--vrcOutdoorPtTable--
|
|
--###########################################################################################--
|
|
|
|
vrcOutdoorPtTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcOutdoorPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table that contains VRC outdoor status"
|
|
::= { vrc 16 }
|
|
|
|
vrcOutdoorPtEntry OBJECT-TYPE
|
|
SYNTAX VrcOutdoorPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcOutdoorPtTable: each entry represents data for a VRC
|
|
outdoor"
|
|
INDEX { vrcOutdoorPtIndex }
|
|
::= { vrcOutdoorPtTable 1 }
|
|
|
|
VrcOutdoorPtEntry ::= SEQUENCE {
|
|
vrcOutdoorPtIndex Integer32,
|
|
vrcOutdoorPtName SnmpAdminString,
|
|
vrcOutdoorPtTemp Integer32
|
|
}
|
|
|
|
vrcOutdoorPtIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcOutdoorPtEntry 1 }
|
|
|
|
vrcOutdoorPtName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outdoor name (factory-assigned)"
|
|
::= { vrcOutdoorPtEntry 2 }
|
|
|
|
vrcOutdoorPtTemp OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outdoor temperature value in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo. The range is determined by the
|
|
current temperature units.
|
|
Celsius: -400 to 1000
|
|
Fahrenheit: -400 to 2120"
|
|
::= { vrcOutdoorPtEntry 3 }
|
|
|
|
--###########################################################################################--
|
|
--vrcDischPtTable--
|
|
--###########################################################################################--
|
|
|
|
vrcDischPtTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcDischPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table that contains VRC discharge status"
|
|
::= { vrc 18 }
|
|
|
|
vrcDischPtEntry OBJECT-TYPE
|
|
SYNTAX VrcDischPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcDischPtTable: each entry represents discharge data for
|
|
a VRC"
|
|
INDEX { vrcDischPtIndex }
|
|
::= { vrcDischPtTable 1 }
|
|
|
|
VrcDischPtEntry ::= SEQUENCE {
|
|
vrcDischPtIndex Integer32,
|
|
vrcDischPtName SnmpAdminString,
|
|
vrcDischPtTemp Integer32,
|
|
vrcDischPtPressure Integer32,
|
|
vrcDischPtHighTempAlarm TruthValue,
|
|
vrcDischPtHighTempFreqAlarm TruthValue,
|
|
vrcDischPtTempSensorFailAlarm TruthValue
|
|
}
|
|
|
|
vrcDischPtIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcDischPtEntry 1 }
|
|
|
|
vrcDischPtName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Discharge name (factory-assigned)"
|
|
::= { vrcDischPtEntry 2 }
|
|
|
|
vrcDischPtTemp OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Discharge temperature value in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo. The range is determined by the
|
|
current temperature units.
|
|
Celsius: -400 to 1560
|
|
Fahrenheit: -400 to 3128"
|
|
::= { vrcDischPtEntry 3 }
|
|
|
|
vrcDischPtPressure OBJECT-TYPE
|
|
SYNTAX Integer32(0..460)
|
|
UNITS "decibars"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Discharge air pressure value in tenths of a bar"
|
|
::= { vrcDischPtEntry 4 }
|
|
|
|
vrcDischPtHighTempAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Discharge high temperature alarm state"
|
|
::= { vrcDischPtEntry 5 }
|
|
|
|
vrcDischPtHighTempFreqAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Discharge high temperature frequently alarm state"
|
|
::= { vrcDischPtEntry 6 }
|
|
|
|
vrcDischPtTempSensorFailAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Discharge temperature sensor failure alarm state"
|
|
::= { vrcDischPtEntry 7 }
|
|
|
|
--###########################################################################################--
|
|
--vrcDischCfgTable--
|
|
--###########################################################################################--
|
|
|
|
vrcDischCfgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcDischCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table used for VRC discharge configuration"
|
|
::= { vrc 19 }
|
|
|
|
vrcDischCfgEntry OBJECT-TYPE
|
|
SYNTAX VrcDischCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcDischCfgTable: each entry contains config fields for
|
|
VRC discharge"
|
|
INDEX { vrcDischCfgIndex }
|
|
::= { vrcDischCfgTable 1 }
|
|
|
|
VrcDischCfgEntry ::= SEQUENCE {
|
|
vrcDischCfgIndex Integer32,
|
|
vrcDischCfgTempCalValue Integer32,
|
|
vrcDischCfgPressCalValue Integer32,
|
|
vrcDischCfgHighTempAlmCtrl INTEGER,
|
|
vrcDischCfgHighTempFreqAlmCtrl INTEGER,
|
|
vrcDischCfgTempSensFailAlmCtrl INTEGER
|
|
}
|
|
|
|
vrcDischCfgIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcDischCfgEntry 1 }
|
|
|
|
vrcDischCfgTempCalValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Discharge temperature calibration value in tenths of a degree. Units
|
|
are given by temperatureUnits field in deviceInfo. The settable range
|
|
is determined by the current temperature units.
|
|
Celsius: -100 to 100
|
|
Fahrenheit: -179 to 179"
|
|
::= { vrcDischCfgEntry 2 }
|
|
|
|
vrcDischCfgPressCalValue OBJECT-TYPE
|
|
SYNTAX Integer32(-100..100)
|
|
UNITS "decibars"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Discharge pressure calibration value in tenths of a bar"
|
|
::= { vrcDischCfgEntry 3 }
|
|
|
|
vrcDischCfgHighTempAlmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Discharge high temperature alarm control:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcDischCfgEntry 4 }
|
|
|
|
vrcDischCfgHighTempFreqAlmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Discharge high temperature frequenctly alarm control:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcDischCfgEntry 5 }
|
|
|
|
vrcDischCfgTempSensFailAlmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Discharge temperature sensor failure alarm control:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcDischCfgEntry 6 }
|
|
|
|
--###########################################################################################--
|
|
--vrcSuctPtTable--
|
|
--###########################################################################################--
|
|
|
|
vrcSuctPtTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcSuctPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table that contains VRC suction status"
|
|
::= { vrc 20 }
|
|
|
|
vrcSuctPtEntry OBJECT-TYPE
|
|
SYNTAX VrcSuctPtEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcSuctPtTable: each entry represents suction data for a
|
|
VRC"
|
|
INDEX { vrcSuctPtIndex }
|
|
::= { vrcSuctPtTable 1 }
|
|
|
|
VrcSuctPtEntry ::= SEQUENCE {
|
|
vrcSuctPtIndex Integer32,
|
|
vrcSuctPtName SnmpAdminString,
|
|
vrcSuctPtTemp Integer32,
|
|
vrcSuctPtPressure Integer32,
|
|
vrcSuctPtSuperHeatTemp Integer32,
|
|
vrcSuctPtTempSensorFailAlarm TruthValue
|
|
}
|
|
|
|
vrcSuctPtIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcSuctPtEntry 1 }
|
|
|
|
vrcSuctPtName OBJECT-TYPE
|
|
SYNTAX SnmpAdminString(SIZE (1..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Suction name (factory-assigned)"
|
|
::= { vrcSuctPtEntry 2 }
|
|
|
|
vrcSuctPtTemp OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Suction temperature in tenths of a degree. Units are given by
|
|
temperatureUnits field in deviceInfo. The range is determined by the
|
|
current temperature units.
|
|
Celsius: -400 to 1000
|
|
Fahrenheit: -400 to 2120"
|
|
::= { vrcSuctPtEntry 3 }
|
|
|
|
vrcSuctPtPressure OBJECT-TYPE
|
|
SYNTAX Integer32(0..173)
|
|
UNITS "decibars"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Suction air pressure in tenths of a bar"
|
|
::= { vrcSuctPtEntry 4 }
|
|
|
|
vrcSuctPtSuperHeatTemp OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "decidegrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Suction super heat temperature in tenths of a degree. Units are given
|
|
by temperatureUnits field in deviceInfo. The range is determined by
|
|
the current temperature units.
|
|
Celsius: -400 to 1000
|
|
Fahrenheit: -400 to 2120"
|
|
::= { vrcSuctPtEntry 5 }
|
|
|
|
vrcSuctPtTempSensorFailAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Suction temperature sensor failure alarm state"
|
|
::= { vrcSuctPtEntry 6 }
|
|
|
|
--###########################################################################################--
|
|
--vrcSuctCfgTable--
|
|
--###########################################################################################--
|
|
|
|
vrcSuctCfgTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VrcSuctCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table used for VRC suction configuration"
|
|
::= { vrc 21 }
|
|
|
|
vrcSuctCfgEntry OBJECT-TYPE
|
|
SYNTAX VrcSuctCfgEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Entry in the vrcSuctCfgTable: each entry contains config fields for
|
|
VRC suction"
|
|
INDEX { vrcSuctCfgIndex }
|
|
::= { vrcSuctCfgTable 1 }
|
|
|
|
VrcSuctCfgEntry ::= SEQUENCE {
|
|
vrcSuctCfgIndex Integer32,
|
|
vrcSuctCfgPressCalValue Integer32,
|
|
vrcSuctCfgTempSensFailAlmCtrl INTEGER
|
|
}
|
|
|
|
vrcSuctCfgIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique id for each entry in the table"
|
|
::= { vrcSuctCfgEntry 1 }
|
|
|
|
vrcSuctCfgPressCalValue OBJECT-TYPE
|
|
SYNTAX Integer32(-100..100)
|
|
UNITS "decibars"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Suction pressure calibration value in tenths of a bar"
|
|
::= { vrcSuctCfgEntry 2 }
|
|
|
|
vrcSuctCfgTempSensFailAlmCtrl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
suspend(2),
|
|
open(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Suction temperature sensor failure alarm control:
|
|
2 = suspend
|
|
3 = open"
|
|
::= { vrcSuctCfgEntry 3 }
|
|
|
|
--###########################################################################################--
|
|
--Notifications--
|
|
--###########################################################################################--
|
|
|
|
trap OBJECT IDENTIFIER ::= { imd 32767 }
|
|
|
|
trapPrefix OBJECT IDENTIFIER ::= { trap 0 }
|
|
|
|
trapObj OBJECT IDENTIFIER ::= { trap 1 }
|
|
|
|
|
|
trapSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(0),
|
|
warning(1),
|
|
alarm(2)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the severity of the trap:
|
|
0 = None
|
|
1 = Warning
|
|
2 = Alarm"
|
|
::= { trapObj 1 }
|
|
|
|
trapThreshType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
low(1),
|
|
high(2)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Only sent for threshold alarms. Identifies the threshold type:
|
|
1 = Low
|
|
2 = High"
|
|
::= { trapObj 2 }
|
|
|
|
internalTestNOTIFY NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION "Test SNMP Trap"
|
|
::= { trapPrefix 10101 }
|
|
|
|
--#####deviceInfo#####--
|
|
|
|
--#####pdu#####--
|
|
|
|
--#####pduMainTable#####--
|
|
|
|
pduMainAvailNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduMainAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU availability trap"
|
|
::= { trapPrefix 10305 }
|
|
|
|
pduMainAvailCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduMainAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU availability clear trap"
|
|
::= { trapPrefix 20305 }
|
|
|
|
pduTotalRealPowerNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduTotalRealPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduTotalLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU total real power trap"
|
|
::= { trapPrefix 10309 }
|
|
|
|
pduTotalRealPowerCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduTotalRealPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduTotalLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU total real power clear trap"
|
|
::= { trapPrefix 20309 }
|
|
|
|
pduTotalApparentPowerNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduTotalApparentPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduTotalLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU total apparent power trap"
|
|
::= { trapPrefix 10310 }
|
|
|
|
pduTotalApparentPowerCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduTotalApparentPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduTotalLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU total apparent power clear trap"
|
|
::= { trapPrefix 20310 }
|
|
|
|
pduTotalPowerFactorNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduTotalPowerFactor,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduTotalLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU total power factor trap"
|
|
::= { trapPrefix 10311 }
|
|
|
|
pduTotalPowerFactorCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduTotalPowerFactor,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduTotalLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU total power factor clear trap"
|
|
::= { trapPrefix 20311 }
|
|
|
|
pduTotalEnergyNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduTotalEnergy,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduTotalLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU total energy trap"
|
|
::= { trapPrefix 10312 }
|
|
|
|
pduTotalEnergyCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduTotalEnergy,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduTotalLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU total energy clear trap"
|
|
::= { trapPrefix 20312 }
|
|
|
|
--#####pduPhaseTable#####--
|
|
|
|
pduPhaseVoltageNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhaseVoltage,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase voltage trap"
|
|
::= { trapPrefix 10324 }
|
|
|
|
pduPhaseVoltageCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhaseVoltage,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase voltage clear trap"
|
|
::= { trapPrefix 20324 }
|
|
|
|
pduPhaseCurrentNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhaseCurrent,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase current trap"
|
|
::= { trapPrefix 10328 }
|
|
|
|
pduPhaseCurrentCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhaseCurrent,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase current clear trap"
|
|
::= { trapPrefix 20328 }
|
|
|
|
pduPhaseRealPowerNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhaseRealPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase real power trap"
|
|
::= { trapPrefix 10332 }
|
|
|
|
pduPhaseRealPowerCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhaseRealPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase real power clear trap"
|
|
::= { trapPrefix 20332 }
|
|
|
|
pduPhaseApparentPowerNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhaseApparentPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase apparent power trap"
|
|
::= { trapPrefix 10333 }
|
|
|
|
pduPhaseApparentPowerCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhaseApparentPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase apparent power clear trap"
|
|
::= { trapPrefix 20333 }
|
|
|
|
pduPhasePowerFactorNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhasePowerFactor,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase power factor trap"
|
|
::= { trapPrefix 10334 }
|
|
|
|
pduPhasePowerFactorCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhasePowerFactor,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase power factor clear trap"
|
|
::= { trapPrefix 20334 }
|
|
|
|
pduPhaseEnergyNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhaseEnergy,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase energy trap"
|
|
::= { trapPrefix 10335 }
|
|
|
|
pduPhaseEnergyCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhaseEnergy,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase energy clear trap"
|
|
::= { trapPrefix 20335 }
|
|
|
|
pduPhaseBalanceNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhaseBalance,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase balance trap"
|
|
::= { trapPrefix 10337 }
|
|
|
|
pduPhaseBalanceCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhaseBalance,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase balance clear trap"
|
|
::= { trapPrefix 20337 }
|
|
|
|
pduPhaseCurrentCrestFactorNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhaseCurrentCrestFactor,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase current crest factor trap"
|
|
::= { trapPrefix 10339 }
|
|
|
|
pduPhaseCurrentCrestFactorCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduPhaseCurrentCrestFactor,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduPhaseLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU phase current crest factor clear trap"
|
|
::= { trapPrefix 20339 }
|
|
|
|
--#####pduBreakerTable#####--
|
|
|
|
pduBreakerCurrentNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduBreakerCurrent,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduBreakerLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU breaker current trap"
|
|
::= { trapPrefix 10354 }
|
|
|
|
pduBreakerCurrentCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduBreakerCurrent,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduBreakerLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU breaker current clear trap"
|
|
::= { trapPrefix 20354 }
|
|
|
|
pduBreakerVoltageNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduBreakerVoltage,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduBreakerLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU breaker voltage trap"
|
|
::= { trapPrefix 10358 }
|
|
|
|
pduBreakerVoltageCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduBreakerVoltage,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduBreakerLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU breaker voltage clear trap"
|
|
::= { trapPrefix 20358 }
|
|
|
|
pduBreakerRealPowerNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduBreakerRealPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduBreakerLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU breaker real power trap"
|
|
::= { trapPrefix 10362 }
|
|
|
|
pduBreakerRealPowerCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduBreakerRealPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduBreakerLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU breaker real power clear trap"
|
|
::= { trapPrefix 20362 }
|
|
|
|
pduBreakerApparentPowerNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduBreakerApparentPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduBreakerLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU breaker apparent power trap"
|
|
::= { trapPrefix 10363 }
|
|
|
|
pduBreakerApparentPowerCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduBreakerApparentPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduBreakerLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU breaker apparent power clear trap"
|
|
::= { trapPrefix 20363 }
|
|
|
|
pduBreakerPowerFactorNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduBreakerPowerFactor,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduBreakerLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU breaker power factor trap"
|
|
::= { trapPrefix 10364 }
|
|
|
|
pduBreakerPowerFactorCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduBreakerPowerFactor,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduBreakerLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU breaker power factor clear trap"
|
|
::= { trapPrefix 20364 }
|
|
|
|
pduBreakerEnergyNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduBreakerEnergy,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduBreakerLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU breaker energy trap"
|
|
::= { trapPrefix 10365 }
|
|
|
|
pduBreakerEnergyCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduBreakerEnergy,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduBreakerLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU breaker energy clear trap"
|
|
::= { trapPrefix 20365 }
|
|
|
|
--#####pduLineTable#####--
|
|
|
|
pduLineCurrentNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduLineCurrent,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduLineLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU line current trap"
|
|
::= { trapPrefix 10374 }
|
|
|
|
pduLineCurrentCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduLineCurrent,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduLineLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU line current clear trap"
|
|
::= { trapPrefix 20374 }
|
|
|
|
--#####pduOutletSwitchTable#####--
|
|
|
|
--#####pduOutletMeterTable#####--
|
|
|
|
pduOutletMeterVoltageNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduOutletMeterVoltage,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduOutletMeterLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU outlet voltage trap"
|
|
::= { trapPrefix 10385 }
|
|
|
|
pduOutletMeterVoltageCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduOutletMeterVoltage,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduOutletMeterLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU outlet voltage clear trap"
|
|
::= { trapPrefix 20385 }
|
|
|
|
pduOutletMeterCurrentNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduOutletMeterCurrent,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduOutletMeterLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU outlet current trap"
|
|
::= { trapPrefix 10389 }
|
|
|
|
pduOutletMeterCurrentCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduOutletMeterCurrent,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduOutletMeterLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU outlet current clear trap"
|
|
::= { trapPrefix 20389 }
|
|
|
|
pduOutletMeterRealPowerNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduOutletMeterRealPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduOutletMeterLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU outlet real power trap"
|
|
::= { trapPrefix 10393 }
|
|
|
|
pduOutletMeterRealPowerCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduOutletMeterRealPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduOutletMeterLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU outlet real power clear trap"
|
|
::= { trapPrefix 20393 }
|
|
|
|
pduOutletMeterApparentPowerNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduOutletMeterApparentPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduOutletMeterLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU outlet apparent power trap"
|
|
::= { trapPrefix 10394 }
|
|
|
|
pduOutletMeterApparentPowerCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduOutletMeterApparentPower,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduOutletMeterLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU outlet apparent power clear trap"
|
|
::= { trapPrefix 20394 }
|
|
|
|
pduOutletMeterPowerFactorNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduOutletMeterPowerFactor,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduOutletMeterLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU outlet power factor trap"
|
|
::= { trapPrefix 10395 }
|
|
|
|
pduOutletMeterPowerFactorCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduOutletMeterPowerFactor,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduOutletMeterLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU outlet power factor clear trap"
|
|
::= { trapPrefix 20395 }
|
|
|
|
pduOutletMeterEnergyNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduOutletMeterEnergy,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduOutletMeterLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU outlet energy trap"
|
|
::= { trapPrefix 10396 }
|
|
|
|
pduOutletMeterEnergyCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduOutletMeterEnergy,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduOutletMeterLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU outlet energy clear trap"
|
|
::= { trapPrefix 20396 }
|
|
|
|
pduOutletCurrentCrestFactorNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduOutletCurrentCrestFactor,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduOutletMeterLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU outlet current crest factor trap"
|
|
::= { trapPrefix 10400 }
|
|
|
|
pduOutletCurrentCrestFactorCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
pduOutletCurrentCrestFactor,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
pduMainLabel,
|
|
pduOutletMeterLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "PDU outlet current crest factor clear trap"
|
|
::= { trapPrefix 20400 }
|
|
|
|
--#####tempSensorTable#####--
|
|
|
|
tempSensorAvailNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
tempSensorAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
tempSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "RT availability trap"
|
|
::= { trapPrefix 10404 }
|
|
|
|
tempSensorAvailCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
tempSensorAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
tempSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "RT availability clear trap"
|
|
::= { trapPrefix 20404 }
|
|
|
|
tempSensorTempNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
tempSensorTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
tempSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "RT temperature trap"
|
|
::= { trapPrefix 10405 }
|
|
|
|
tempSensorTempCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
tempSensorTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
tempSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "RT temperature clear trap"
|
|
::= { trapPrefix 20405 }
|
|
|
|
--#####airFlowSensorTable#####--
|
|
|
|
airFlowSensorAvailNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
airFlowSensorAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
airFlowSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "AFHT3 availability trap"
|
|
::= { trapPrefix 10504 }
|
|
|
|
airFlowSensorAvailCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
airFlowSensorAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
airFlowSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "AFHT3 availability clear trap"
|
|
::= { trapPrefix 20504 }
|
|
|
|
airFlowSensorTempNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
airFlowSensorTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
airFlowSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "AFHT3 temperature trap"
|
|
::= { trapPrefix 10505 }
|
|
|
|
airFlowSensorTempCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
airFlowSensorTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
airFlowSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "AFHT3 temperature clear trap"
|
|
::= { trapPrefix 20505 }
|
|
|
|
airFlowSensorFlowNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
airFlowSensorFlow,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
airFlowSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "AFHT3 airflow trap"
|
|
::= { trapPrefix 10506 }
|
|
|
|
airFlowSensorFlowCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
airFlowSensorFlow,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
airFlowSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "AFHT3 airflow clear trap"
|
|
::= { trapPrefix 20506 }
|
|
|
|
airFlowSensorHumidityNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
airFlowSensorHumidity,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
airFlowSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "AFHT3 humidity trap"
|
|
::= { trapPrefix 10507 }
|
|
|
|
airFlowSensorHumidityCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
airFlowSensorHumidity,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
airFlowSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "AFHT3 humidity clear trap"
|
|
::= { trapPrefix 20507 }
|
|
|
|
airFlowSensorDewPointNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
airFlowSensorDewPoint,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
airFlowSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "AFHT3 dewpoint trap"
|
|
::= { trapPrefix 10508 }
|
|
|
|
airFlowSensorDewPointCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
airFlowSensorDewPoint,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
airFlowSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "AFHT3 dewpoint clear trap"
|
|
::= { trapPrefix 20508 }
|
|
|
|
--#####t3hdSensorTable#####--
|
|
|
|
t3hdSensorAvailNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
t3hdSensorAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
t3hdSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "T3HD availability trap"
|
|
::= { trapPrefix 10804 }
|
|
|
|
t3hdSensorAvailCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
t3hdSensorAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
t3hdSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "T3HD availability clear trap"
|
|
::= { trapPrefix 20804 }
|
|
|
|
t3hdSensorIntTempNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
t3hdSensorIntTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
t3hdSensorLabel,
|
|
t3hdSensorIntLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "T3HD Internal temperature trap"
|
|
::= { trapPrefix 10806 }
|
|
|
|
t3hdSensorIntTempCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
t3hdSensorIntTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
t3hdSensorLabel,
|
|
t3hdSensorIntLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "T3HD Internal temperature clear trap"
|
|
::= { trapPrefix 20806 }
|
|
|
|
t3hdSensorIntHumidityNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
t3hdSensorIntHumidity,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
t3hdSensorLabel,
|
|
t3hdSensorIntLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "T3HD Internal humidity trap"
|
|
::= { trapPrefix 10807 }
|
|
|
|
t3hdSensorIntHumidityCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
t3hdSensorIntHumidity,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
t3hdSensorLabel,
|
|
t3hdSensorIntLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "T3HD Internal humidity clear trap"
|
|
::= { trapPrefix 20807 }
|
|
|
|
t3hdSensorIntDewPointNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
t3hdSensorIntDewPoint,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
t3hdSensorLabel,
|
|
t3hdSensorIntLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "T3HD Internal dewpoint trap"
|
|
::= { trapPrefix 10808 }
|
|
|
|
t3hdSensorIntDewPointCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
t3hdSensorIntDewPoint,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
t3hdSensorLabel,
|
|
t3hdSensorIntLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "T3HD Internal dewpoint clear trap"
|
|
::= { trapPrefix 20808 }
|
|
|
|
t3hdSensorExtATempNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
t3hdSensorExtATemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
t3hdSensorLabel,
|
|
t3hdSensorExtALabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "T3HD External A temperature trap"
|
|
::= { trapPrefix 10811 }
|
|
|
|
t3hdSensorExtATempCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
t3hdSensorExtATemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
t3hdSensorLabel,
|
|
t3hdSensorExtALabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "T3HD External A temperature clear trap"
|
|
::= { trapPrefix 20811 }
|
|
|
|
t3hdSensorExtBTempNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
t3hdSensorExtBTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
t3hdSensorLabel,
|
|
t3hdSensorExtBLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "T3HD External B temperature trap"
|
|
::= { trapPrefix 10814 }
|
|
|
|
t3hdSensorExtBTempCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
t3hdSensorExtBTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
t3hdSensorLabel,
|
|
t3hdSensorExtBLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "T3HD External B temperature clear trap"
|
|
::= { trapPrefix 20814 }
|
|
|
|
--#####thdSensorTable#####--
|
|
|
|
thdSensorAvailNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
thdSensorAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
thdSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "THD availability trap"
|
|
::= { trapPrefix 10904 }
|
|
|
|
thdSensorAvailCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
thdSensorAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
thdSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "THD availability clear trap"
|
|
::= { trapPrefix 20904 }
|
|
|
|
thdSensorTempNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
thdSensorTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
thdSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "THD temperature trap"
|
|
::= { trapPrefix 10905 }
|
|
|
|
thdSensorTempCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
thdSensorTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
thdSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "THD temperature clear trap"
|
|
::= { trapPrefix 20905 }
|
|
|
|
thdSensorHumidityNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
thdSensorHumidity,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
thdSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "THD humidity trap"
|
|
::= { trapPrefix 10906 }
|
|
|
|
thdSensorHumidityCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
thdSensorHumidity,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
thdSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "THD humidity clear trap"
|
|
::= { trapPrefix 20906 }
|
|
|
|
thdSensorDewPointNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
thdSensorDewPoint,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
thdSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "THD dewpoint trap"
|
|
::= { trapPrefix 10907 }
|
|
|
|
thdSensorDewPointCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
thdSensorDewPoint,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
thdSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "THD dewpoint clear trap"
|
|
::= { trapPrefix 20907 }
|
|
|
|
--#####a2dSensorTable#####--
|
|
|
|
a2dSensorAvailNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
a2dSensorAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
a2dSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A2D availability trap"
|
|
::= { trapPrefix 11104 }
|
|
|
|
a2dSensorAvailCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
a2dSensorAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
a2dSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A2D availability clear trap"
|
|
::= { trapPrefix 21104 }
|
|
|
|
a2dSensorValueNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
a2dSensorValue,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
a2dSensorLabel,
|
|
a2dSensorAnalogLabel,
|
|
a2dSensorDisplayValue
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A2D measurement trap"
|
|
::= { trapPrefix 11105 }
|
|
|
|
a2dSensorValueCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
a2dSensorValue,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
a2dSensorLabel,
|
|
a2dSensorAnalogLabel,
|
|
a2dSensorDisplayValue
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "A2D measurement clear trap"
|
|
::= { trapPrefix 21105 }
|
|
|
|
--#####humiditySensorTable#####--
|
|
|
|
humiditySensorAvailNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
humiditySensorAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
humiditySensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "Remote humidity availability trap"
|
|
::= { trapPrefix 11204 }
|
|
|
|
humiditySensorAvailCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
humiditySensorAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
humiditySensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "Remote humidity availability clear trap"
|
|
::= { trapPrefix 21204 }
|
|
|
|
humiditySensorValueNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
humiditySensorValue,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
humiditySensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "Remote humidity value trap"
|
|
::= { trapPrefix 11205 }
|
|
|
|
humiditySensorValueCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
humiditySensorValue,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
humiditySensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "Remote humidity value clear trap"
|
|
::= { trapPrefix 21205 }
|
|
|
|
--#####sn2dSensorTable#####--
|
|
|
|
sn2dSensorAvailNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
sn2dSensorAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
sn2dSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "SN-2D availability trap"
|
|
::= { trapPrefix 11304 }
|
|
|
|
sn2dSensorAvailCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
sn2dSensorAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
sn2dSensorLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "SN-2D availability clear trap"
|
|
::= { trapPrefix 21304 }
|
|
|
|
sn2dSensorDoor1StateNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
sn2dSensorDoor1State,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
sn2dSensorLabel,
|
|
sn2dSensorDoor1Label,
|
|
sn2dSensorDoor1DisplayState
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "SN-2D Door switch 1 state trap"
|
|
::= { trapPrefix 11306 }
|
|
|
|
sn2dSensorDoor1StateCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
sn2dSensorDoor1State,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
sn2dSensorLabel,
|
|
sn2dSensorDoor1Label,
|
|
sn2dSensorDoor1DisplayState
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "SN-2D Door switch 1 state clear trap"
|
|
::= { trapPrefix 21306 }
|
|
|
|
sn2dSensorDoor2StateNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
sn2dSensorDoor2State,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
sn2dSensorLabel,
|
|
sn2dSensorDoor2Label,
|
|
sn2dSensorDoor2DisplayState
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "SN-2D Door switch 2 state trap"
|
|
::= { trapPrefix 11309 }
|
|
|
|
sn2dSensorDoor2StateCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
sn2dSensorDoor2State,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
sn2dSensorLabel,
|
|
sn2dSensorDoor2Label,
|
|
sn2dSensorDoor2DisplayState
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "SN-2D Door switch 2 state clear trap"
|
|
::= { trapPrefix 21309 }
|
|
|
|
--#####cooling#####--
|
|
|
|
--#####vrc#####--
|
|
|
|
--#####vrcMainTable#####--
|
|
|
|
vrcMainAvailNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcMainAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC availability trap"
|
|
::= { trapPrefix 13001 }
|
|
|
|
vrcMainAvailCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcMainAvail,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC availability clear trap"
|
|
::= { trapPrefix 23001 }
|
|
|
|
--#####vrcMainPtTable#####--
|
|
|
|
--#####vrcMainCfgTable#####--
|
|
|
|
--#####vrcOutFanPtTable#####--
|
|
|
|
vrcOutFanPtSpeedNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcOutFanPtSpeed,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC out-fan speed trap"
|
|
::= { trapPrefix 13002 }
|
|
|
|
vrcOutFanPtSpeedCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcOutFanPtSpeed,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC out-fan speed clear trap"
|
|
::= { trapPrefix 23002 }
|
|
|
|
--#####vrcOutFanCfgTable#####--
|
|
|
|
--#####vrcInFanPtTable#####--
|
|
|
|
--#####vrcInFanCfgTable#####--
|
|
|
|
--#####vrcCompPtTable#####--
|
|
|
|
vrcCompPtCapacityNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcCompPtCapacity,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC compressor capacity trap"
|
|
::= { trapPrefix 13003 }
|
|
|
|
vrcCompPtCapacityCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcCompPtCapacity,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC compressor capacity clear trap"
|
|
::= { trapPrefix 23003 }
|
|
|
|
--#####vrcCompCfgTable#####--
|
|
|
|
--#####vrcReturnPtTable#####--
|
|
|
|
vrcReturnPtTempNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcReturnPtTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC return temperature trap"
|
|
::= { trapPrefix 13004 }
|
|
|
|
vrcReturnPtTempCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcReturnPtTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC return temperature clear trap"
|
|
::= { trapPrefix 23004 }
|
|
|
|
--#####vrcReturnCfgTable#####--
|
|
|
|
--#####vrcSupplyPtTable#####--
|
|
|
|
vrcSupplyPtTempNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcSupplyPtTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC supply temperature trap"
|
|
::= { trapPrefix 13005 }
|
|
|
|
vrcSupplyPtTempCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcSupplyPtTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC supply temperature clear trap"
|
|
::= { trapPrefix 23005 }
|
|
|
|
--#####vrcSupplyCfgTable#####--
|
|
|
|
--#####vrcPowerPtTable#####--
|
|
|
|
vrcPowerPtVoltageNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcPowerPtVoltage,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC power voltage trap"
|
|
::= { trapPrefix 13006 }
|
|
|
|
vrcPowerPtVoltageCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcPowerPtVoltage,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC power voltage clear trap"
|
|
::= { trapPrefix 23006 }
|
|
|
|
vrcPowerPtFrequencyNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcPowerPtFrequency,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC power frequency trap"
|
|
::= { trapPrefix 13007 }
|
|
|
|
vrcPowerPtFrequencyCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcPowerPtFrequency,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC power frequency clear trap"
|
|
::= { trapPrefix 23007 }
|
|
|
|
--#####vrcPowerCfgTable#####--
|
|
|
|
--#####vrcOutdoorPtTable#####--
|
|
|
|
vrcOutdoorPtTempNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcOutdoorPtTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC outdoor temperature trap"
|
|
::= { trapPrefix 13008 }
|
|
|
|
vrcOutdoorPtTempCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcOutdoorPtTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC outdoor temperature clear trap"
|
|
::= { trapPrefix 23008 }
|
|
|
|
--#####vrcDischPtTable#####--
|
|
|
|
vrcDischPtTempNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcDischPtTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC discharge temperature trap"
|
|
::= { trapPrefix 13009 }
|
|
|
|
vrcDischPtTempCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcDischPtTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC discharge temperature clear trap"
|
|
::= { trapPrefix 23009 }
|
|
|
|
vrcDischPtPressureNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcDischPtPressure,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC discharge pressure trap"
|
|
::= { trapPrefix 13010 }
|
|
|
|
vrcDischPtPressureCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcDischPtPressure,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC discharge pressure clear trap"
|
|
::= { trapPrefix 23010 }
|
|
|
|
--#####vrcDischCfgTable#####--
|
|
|
|
--#####vrcSuctPtTable#####--
|
|
|
|
vrcSuctPtTempNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcSuctPtTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC suction temperature trap"
|
|
::= { trapPrefix 13011 }
|
|
|
|
vrcSuctPtTempCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcSuctPtTemp,
|
|
temperatureUnits,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC suction temperature clear trap"
|
|
::= { trapPrefix 23011 }
|
|
|
|
vrcSuctPtPressureNOTIFY NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcSuctPtPressure,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC suction pressure trap"
|
|
::= { trapPrefix 13012 }
|
|
|
|
vrcSuctPtPressureCLEAR NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
vrcSuctPtPressure,
|
|
trapThreshType,
|
|
trapSeverity,
|
|
sysName,
|
|
vrcMainLabel
|
|
}
|
|
STATUS current
|
|
DESCRIPTION "VRC suction pressure clear trap"
|
|
::= { trapPrefix 23012 }
|
|
|
|
--#####vrcSuctCfgTable#####--
|
|
|
|
--###########################################################################################--
|
|
--common group--
|
|
--###########################################################################################--
|
|
|
|
common OBJECT IDENTIFIER ::= { vertiv 42 }
|
|
|
|
identity OBJECT IDENTIFIER ::= { common 1 }
|
|
|
|
i03 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value given for sysObjectID on IMD3 units"
|
|
::= { identity 53 }
|
|
|
|
r05 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value given for sysObjectID on R-Series units"
|
|
::= { identity 15 }
|
|
|
|
END
|