ALGPOWER-v2-MIB DEFINITIONS ::= BEGIN
|
||
|
IMPORTS
|
||
|
DisplayString FROM RFC1213-MIB
|
||
|
OBJECT-TYPE FROM RFC-1212
|
||
|
enterprises FROM RFC1155-SMI;
|
||
|
|
||
|
algcom OBJECT IDENTIFIER ::= { enterprises 49136 }
|
||
|
upsObjects OBJECT IDENTIFIER ::= { algcom 1 }
|
||
|
output OBJECT IDENTIFIER ::= { upsObjects 1 }
|
||
|
battery OBJECT IDENTIFIER ::= { upsObjects 2 }
|
||
|
input OBJECT IDENTIFIER ::= { upsObjects 3 }
|
||
|
temperature OBJECT IDENTIFIER ::= { upsObjects 4 }
|
||
|
watchdog OBJECT IDENTIFIER ::= { upsObjects 5 }
|
||
|
supply OBJECT IDENTIFIER ::= { upsObjects 6 }
|
||
|
installation OBJECT IDENTIFIER ::= { upsObjects 7 }
|
||
|
bat-tst OBJECT IDENTIFIER ::= { upsObjects 8 }
|
||
|
|
||
|
|
||
|
outputVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Numeric value of instantaneous output voltage from
|
||
|
the source in tenths of a volt. To get the value
|
||
|
actual in volt should be divided by 10.
|
||
|
|
||
|
Example:
|
||
|
Read value 241, actual value 24.1V."
|
||
|
::= { output 1 }
|
||
|
|
||
|
outputCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Numeric value of current output of converter AC/DC.
|
||
|
Real value reading in milli ampere.
|
||
|
|
||
|
Example:
|
||
|
Read value 1087, Actual value 1.087 milli ampere
|
||
|
or 1.087A.
|
||
|
If the output is '0' the AC/DC is off and the output
|
||
|
for the equipments is provide from batteries"
|
||
|
::= { output 2 }
|
||
|
|
||
|
oidNotUsed0 OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"OID not used."
|
||
|
::= { output 3 }
|
||
|
|
||
|
oidNotUsed1 OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"OID not used."
|
||
|
::= { output 4 }
|
||
|
|
||
|
|
||
|
batteryVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Numeric value of instantaneous voltage of battery bank.
|
||
|
To get the actual value in volt must be divided by 10.
|
||
|
|
||
|
Example:
|
||
|
Read value 240, actual value 24.0V."
|
||
|
::= { battery 1 }
|
||
|
|
||
|
batteryCurrent OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Numeric value of current in Battery bank. Real
|
||
|
value reading in milli ampere.
|
||
|
If the value is negative the Battery bank is provide
|
||
|
energy for the output.
|
||
|
If the value is positive the Battery bank is under
|
||
|
charger
|
||
|
|
||
|
Example:
|
||
|
Read value -2230, Actual value 2,230 ampere and the
|
||
|
battery bank is provide this current.
|
||
|
Read value 3000, Actual value 3.000 milli ampere and
|
||
|
the battery bank is absorve this current."
|
||
|
::= { battery 2 }
|
||
|
|
||
|
chargerStatus OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Show the status of battery charger:
|
||
|
0 - The battery is not connected in DC UPS;
|
||
|
1 - The battery is voltage incompatible with DC UPS;
|
||
|
2 - The DC UPS is in nobreak mode;
|
||
|
3 - The charger of Battery is in Bulk stage;
|
||
|
4 - The charger of Battery is Absorption stage;
|
||
|
5 - The charger of Battery is Float stage;
|
||
|
6 - The Battery will be disconnected in 30s due to
|
||
|
low voltage and the DC-UPS output will be
|
||
|
turned off.
|
||
|
7 - The Battery is under test"
|
||
|
::= { battery 3 }
|
||
|
|
||
|
|
||
|
alarmOnBattery OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Shows the operation mode of DC-UPS:
|
||
|
|
||
|
0 - The DC-UPS output is provide by AC energy.
|
||
|
1 - The DC-UPS output is provide by Battery"
|
||
|
::= { input 1 }
|
||
|
|
||
|
acFail OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm that alert about AC outages in the last 10
|
||
|
minutes:
|
||
|
|
||
|
0 - DC-UPS in normal operation.
|
||
|
1 - Occur a AC fail in the last 10 minutes."
|
||
|
::= { input 2 }
|
||
|
|
||
|
batteryCharging OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Show the status of charging Battery:
|
||
|
|
||
|
1 - The battery is on charging.
|
||
|
0 - The battery is on discharging."
|
||
|
::= { input 3 }
|
||
|
|
||
|
batteryDischarging OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Show the status of discharging Battery:
|
||
|
|
||
|
1 - The battery is on discharging.
|
||
|
0 - The battery is on charging."
|
||
|
::= { input 4 }
|
||
|
|
||
|
overheat OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm that alert about overtemperature of DC-UPS
|
||
|
|
||
|
1 - The DC-UPS is in condition of overtemperature.
|
||
|
0 - The DC-UPS is in normal condition."
|
||
|
::= { input 5 }
|
||
|
|
||
|
overload OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm that alert about overload of DC-UPS
|
||
|
|
||
|
1 - The DC-UPS is in condition of overload.
|
||
|
0 - The DC-UPS is in normal condition."
|
||
|
::= { input 6 }
|
||
|
|
||
|
fanAfail OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm that alert about fail in internal FAN A
|
||
|
|
||
|
1 - Internal FAN with fail.
|
||
|
0 - Internal FAN ok"
|
||
|
::= { input 7 }
|
||
|
|
||
|
fanBfail OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm that alert about fail in internal FAN B
|
||
|
|
||
|
1 - Internal FAN with fail.
|
||
|
0 - Internal FAN ok"
|
||
|
::= { input 8 }
|
||
|
|
||
|
oidNotUsed2 OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"OID not used."
|
||
|
::= { input 9 }
|
||
|
|
||
|
oidNotUsed3 OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"OID not used."
|
||
|
::= { input 10 }
|
||
|
|
||
|
upTime OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION "System Up time in hours"
|
||
|
::= {input 11}
|
||
|
|
||
|
|
||
|
innerTemperature OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Show the internal temperature of power supply.
|
||
|
Uses the unit degree Celsius.
|
||
|
|
||
|
Example
|
||
|
Read value: 25, temperature is 25degC."
|
||
|
::= { temperature 1 }
|
||
|
|
||
|
outerTemperature OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Show the temperature of external sensor (cable that
|
||
|
comes with power supply).
|
||
|
Uses the unit degree Celsius.
|
||
|
|
||
|
Example
|
||
|
Read value: 25, temperature is 25degC."
|
||
|
::= { temperature 2 }
|
||
|
|
||
|
heatSinkTemperature OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Show the temperature of sensor in the heatsink of
|
||
|
power supply use the unit degree Celsius.
|
||
|
|
||
|
Example
|
||
|
Read value: 25, temperature is 25degC."
|
||
|
::= { temperature 3 }
|
||
|
|
||
|
|
||
|
watchdogPing1 OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm indicating the action of watchdog 1
|
||
|
programmed in the last 10 minutes. The watchdog
|
||
|
acts on the output by turning it off when not
|
||
|
receive response from IP ping command
|
||
|
configured.
|
||
|
|
||
|
1 - The watchdog 1 acted on the output the last 10
|
||
|
minutes.
|
||
|
0 - The Watchdog 1 has not acted in the last 10
|
||
|
minutes."
|
||
|
::= { watchdog 1 }
|
||
|
|
||
|
watchdogPing2 OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm indicating the action of watchdog 2
|
||
|
programmed in the last 10 minutes. The watchdog
|
||
|
acts on the output by turning it off when not
|
||
|
receive response from IP ping command
|
||
|
configured.
|
||
|
|
||
|
1 - The watchdog 2 acted on the output the last 10
|
||
|
minutes.
|
||
|
0 - The Watchdog 2 has not acted in the last 10
|
||
|
minutes."
|
||
|
::= { watchdog 2 }
|
||
|
|
||
|
watchdogPing3 OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm indicating the action of watchdog 3
|
||
|
programmed in the last 10 minutes. The watchdog
|
||
|
acts on the output by turning it off when not
|
||
|
receive response from IP ping command
|
||
|
configured.
|
||
|
|
||
|
1 - The watchdog 3 acted on the output the last 10
|
||
|
minutes.
|
||
|
0 - The Watchdog 3 has not acted in the last 10
|
||
|
minutes."
|
||
|
::= { watchdog 3 }
|
||
|
|
||
|
watchdogPing4 OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm indicating the action of watchdog 4
|
||
|
programmed in the last 10 minutes. The watchdog
|
||
|
acts on the output by turning it off when not
|
||
|
receive response from IP ping command
|
||
|
configured.
|
||
|
|
||
|
1 - The watchdog 4 acted on the output the last 10
|
||
|
minutes.
|
||
|
0 - The Watchdog 4 has not acted in the last 10
|
||
|
minutes."
|
||
|
::= { watchdog 4 }
|
||
|
|
||
|
watchdogPing5 OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm indicating the action of watchdog 5
|
||
|
programmed in the last 10 minutes. The watchdog
|
||
|
acts on the output by turning it off when not
|
||
|
receive response from IP ping command
|
||
|
configured.
|
||
|
|
||
|
1 - The watchdog 5 acted on the output the last 10
|
||
|
minutes.
|
||
|
0 - The Watchdog 5 has not acted in the last 10
|
||
|
minutes."
|
||
|
::= { watchdog 5 }
|
||
|
|
||
|
watchdogPing6 OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm indicating the action of watchdog 6
|
||
|
programmed in the last 10 minutes. The watchdog
|
||
|
acts on the output by turning it off when not
|
||
|
receive response from IP ping command
|
||
|
configured.
|
||
|
|
||
|
1 - The watchdog 6 acted on the output the last 10
|
||
|
minutes.
|
||
|
0 - The Watchdog 6 has not acted in the last 10
|
||
|
minutes."
|
||
|
::= { watchdog 6 }
|
||
|
|
||
|
watchdogPing7 OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm indicating the action of watchdog 7
|
||
|
programmed in the last 10 minutes. The watchdog
|
||
|
acts on the output by turning it off when not
|
||
|
receive response from IP ping command
|
||
|
configured.
|
||
|
|
||
|
1 - The watchdog 7 acted on the output the last 10
|
||
|
minutes.
|
||
|
0 - The Watchdog 7 has not acted in the last 10
|
||
|
minutes."
|
||
|
::= { watchdog 7 }
|
||
|
|
||
|
watchdogPing8 OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm indicating the action of watchdog 8
|
||
|
programmed in the last 10 minutes. The watchdog
|
||
|
acts on the output by turning it off when not
|
||
|
receive response from IP ping command
|
||
|
configured.
|
||
|
|
||
|
1 - The watchdog 8 acted on the output the last 10
|
||
|
minutes.
|
||
|
0 - The Watchdog 8 has not acted in the last 10
|
||
|
minutes."
|
||
|
::= { watchdog 8 }
|
||
|
|
||
|
watchdogPing9 OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm indicating the action of watchdog 9
|
||
|
programmed in the last 10 minutes. The watchdog
|
||
|
acts on the output by turning it off when not
|
||
|
receive response from IP ping command
|
||
|
configured.
|
||
|
|
||
|
1 - The watchdog 9 acted on the output the last 10
|
||
|
minutes.
|
||
|
0 - The Watchdog 9 has not acted in the last 10
|
||
|
minutes."
|
||
|
::= { watchdog 9 }
|
||
|
|
||
|
watchdogPing10 OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"Alarm indicating the action of watchdog 10
|
||
|
programmed in the last 10 minutes. The watchdog
|
||
|
acts on the output by turning it off when not
|
||
|
receive response from IP ping command
|
||
|
configured.
|
||
|
|
||
|
1 - The watchdog 10 acted on the output the last 10
|
||
|
minutes.
|
||
|
0 - The Watchdog 10 has not acted in the last 10
|
||
|
minutes."
|
||
|
::= { watchdog 10 }
|
||
|
|
||
|
|
||
|
supplyVoltage OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The supply AC voltage decivolt [dV]
|
||
|
Numeric value of instantaneous input voltage.
|
||
|
An optional sensor is required to read this value.
|
||
|
To get the actual value in volt it should be
|
||
|
divided by 10.
|
||
|
|
||
|
Example:
|
||
|
Read value 2410, actual value 241 Vac."
|
||
|
::= {supply 1}
|
||
|
|
||
|
|
||
|
popName OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (30))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION "PoP name"
|
||
|
::= {installation 1}
|
||
|
|
||
|
facilityAddr OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (40))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION "Facility address"
|
||
|
::= {installation 2}
|
||
|
|
||
|
facilityCity OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (30))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION "Facility city"
|
||
|
::= {installation 3}
|
||
|
|
||
|
instDate OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (10))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION "Installation date"
|
||
|
::= {installation 4}
|
||
|
|
||
|
batCapacity OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION "Battery capacity"
|
||
|
::= {installation 5}
|
||
|
|
||
|
batBrand OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (30))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION "Battery brand"
|
||
|
::= {installation 6}
|
||
|
|
||
|
batInstDate OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (10))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION "Battery installation date"
|
||
|
::= {installation 7}
|
||
|
|
||
|
respPers OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (50))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION "Responsible person"
|
||
|
::= {installation 8}
|
||
|
|
||
|
btst-date OBJECT-TYPE
|
||
|
SYNTAX DisplayString (SIZE (10))
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION "Battery test execution date (dd/mm/yyyy)"
|
||
|
::= {bat-tst 1}
|
||
|
|
||
|
btst-status OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION "Battery test status
|
||
|
0 - NEVER DONE
|
||
|
1 - Passed
|
||
|
2 - Running
|
||
|
3 - Aborted
|
||
|
4 - Failed"
|
||
|
::= {bat-tst 2}
|
||
|
|
||
|
btst-duration OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION "Programmed test duration in minutes
|
||
|
* 999 - Perform the test until battery is fully discharged"
|
||
|
::= {bat-tst 3}
|
||
|
|
||
|
btst-elapsed OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION "Elapsed time in current\last battery test"
|
||
|
::= {bat-tst 4}
|
||
|
|
||
|
btst-volt-i OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The battery initial voltage [dV]
|
||
|
Numeric value of battery voltage when starting the battery test.
|
||
|
|
||
|
Example:
|
||
|
Read value 241, actual value 24.1 V."
|
||
|
::= {bat-tst 5}
|
||
|
|
||
|
btst-amp-i OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The battery initial cuurent [mA]
|
||
|
Numeric value of battery current when starting the battery test.
|
||
|
|
||
|
Example:
|
||
|
Read value 1522, actual value 1.55 A."
|
||
|
::= {bat-tst 6}
|
||
|
|
||
|
btst-volt-f OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The battery final voltage [dV]
|
||
|
Numeric value of battery voltage when the battery test is done.
|
||
|
|
||
|
Example:
|
||
|
Read value 225, actual value 22.5 V."
|
||
|
::= {bat-tst 7}
|
||
|
|
||
|
btst-amp-f OBJECT-TYPE
|
||
|
SYNTAX INTEGER
|
||
|
ACCESS read-only
|
||
|
STATUS mandatory
|
||
|
DESCRIPTION
|
||
|
"The battery initial cuurent [mA]
|
||
|
Numeric value of battery current when the battery test is done.
|
||
|
|
||
|
Example:
|
||
|
Read value 1485, actual value 1.48 A."
|
||
|
::= {bat-tst 8}
|
||
|
|
||
|
END
|