mibs/MIBS/comet/T3610-MIB

527 lines
13 KiB
Plaintext
Raw Normal View History

2023-12-05 12:25:34 +01:00
----------------------------------------------------------------------
-- MIB table for T3610
--
-- v3.0 for firmware 1-5-7-2, 2016-04-11
-----------------------------------------------------------------------
T3610-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
TRAP-TYPE
FROM RFC-1215;
DisplayString ::= OCTET STRING
comet OBJECT IDENTIFIER ::= { enterprises 22626 }
products OBJECT IDENTIFIER ::= { comet 1 }
t3610 OBJECT IDENTIFIER ::= { products 2 }
values OBJECT IDENTIFIER ::= { t3610 1 }
global OBJECT IDENTIFIER ::= { t3610 2 }
valuesInt OBJECT IDENTIFIER ::= { t3610 3 }
settings OBJECT IDENTIFIER ::= { t3610 4 }
traps OBJECT IDENTIFIER ::= { t3610 5 }
tables OBJECT IDENTIFIER ::= { t3610 6 }
-----------------------------------------------------------------------
-- Measured values - String
-----------------------------------------------------------------------
temp OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature"
::= { values 1 }
hum OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Relative humidity"
::= { values 2 }
compVal OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value"
::= { values 3 }
tempAlarm OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm on Temperature; none, high, low"
::= { values 5 }
humAlarm OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm on Relative humidity; none, high, low"
::= { values 6 }
compValAlarm OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm on Computed value; none, high, low"
::= { values 7 }
tempUnit OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Unit"
::= { values 9 }
humUnit OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Relative humidity Unit"
::= { values 10 }
compValUnit OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value Unit"
::= { values 11 }
tempMin OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Minimal temperature"
::= { values 13 }
humMin OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Minimal relative humidity"
::= { values 14 }
compValMin OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Minimal computed value"
::= { values 15 }
tempMax OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Maximal temperature"
::= { values 17 }
humMax OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Maximal relative humidity"
::= { values 18 }
compValMax OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Maximal computed value"
::= { values 19 }
-----------------------------------------------------------------------
-- Device informations
-----------------------------------------------------------------------
sensorName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..68))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Device name"
::= { global 1 }
serialNumber OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..16))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Serial number"
::= { global 2 }
deviceType OBJECT-TYPE
SYNTAX INTEGER (0..65534)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Device type"
::= { global 3 }
-----------------------------------------------------------------------
-- Measured values - Integer
-----------------------------------------------------------------------
tempInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature (value*10)"
::= { valuesInt 1 }
humInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Relative humidity (value*10)"
::= { valuesInt 2 }
compValInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value (value*10)"
::= { valuesInt 3 }
tempAlarmInt OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm on Temperature; 0 - No, 1 - High, 2 - Low"
::= { valuesInt 5 }
humAlarmInt OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm on Relative humidity; 0 - No, 1 - High, 2 - Low"
::= { valuesInt 6 }
compValAlarmInt OBJECT-TYPE
SYNTAX INTEGER (0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm on Computed value; 0 - No, 1 - High, 2 - Low"
::= { valuesInt 7 }
-----------------------------------------------------------------------
-- Alarm settings
-----------------------------------------------------------------------
tempLowInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Limit Low (value*10)"
::= { settings 1 }
tempHighInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Limit High (value*10)"
::= { settings 2 }
humLowInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Humidity Limit Low (value*10)"
::= { settings 3 }
humHighInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Humidity Limit High (value*10)"
::= { settings 4 }
compValLowInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value Limit Low (value*10)"
::= { settings 5 }
compValHighInt OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value Limit High (value*10)"
::= { settings 6 }
tempDelayInt OBJECT-TYPE
SYNTAX INTEGER (0..4500)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature alaram delay [sec]"
::= { settings 7 }
humDelayInt OBJECT-TYPE
SYNTAX INTEGER (0..4500)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Humidity alaram delay [sec]"
::= { settings 8 }
compValDelayInt OBJECT-TYPE
SYNTAX INTEGER (0..4500)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value alaram delay [sec]"
::= { settings 9 }
tempHystInt OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature hysteresis (value*10)"
::= { settings 10 }
humHystInt OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Humidity hysteresis (value*10)"
::= { settings 11 }
compValHystInt OBJECT-TYPE
SYNTAX INTEGER (0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value hysteresis (value*10)"
::= { settings 12 }
-----------------------------------------------------------------------
-- Trap message
-----------------------------------------------------------------------
messageString OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION "Message giving more detailed information on alarms"
::= { traps 1 }
-----------------------------------------------------------------------
-- Tables
-----------------------------------------------------------------------
historyTable OBJECT-TYPE
SYNTAX SEQUENCE OF HistoryEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION "Table of the history values"
::= { tables 1 }
historyEntry OBJECT-TYPE
SYNTAX HistoryEntry
ACCESS not-accessible
STATUS optional
DESCRIPTION "History values entries"
INDEX { histTemp }
::= { historyTable 1 }
HistoryEntry ::=
SEQUENCE {
histTemp
INTEGER,
histHum
INTEGER,
histCompVal
INTEGER
}
histTemp OBJECT-TYPE
SYNTAX INTEGER(-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature reading"
::= { historyEntry 1 }
histHum OBJECT-TYPE
SYNTAX INTEGER(-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Humidity reading"
::= { historyEntry 2 }
histCompVal OBJECT-TYPE
SYNTAX INTEGER (-5000..20000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Computed value reading"
::= { historyEntry 3 }
-----------------------------------------------------------------------
-- Traps definition
-----------------------------------------------------------------------
trapTest TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"Testing trap, testing trap by TSensor software"
::= 0
trapNTPError TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"Error on time synchronisation via NTP"
::= 1
trapEmailErrLogin TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SMTP error - unknown server"
::= 2
trapEmailErrAuth TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SMTP error - authentication error"
::= 3
trapEmailErrSome TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SMTP error - error during communication with server, unexpected return code"
::= 4
trapEmailErrSocket TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SMTP error - socket error, server is not available"
::= 5
trapEmailErrDNS TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SMTP error - DNS error"
::= 6
trapSOAPErrFile TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SOAP error - file SOAP not found"
::= 7
trapSOAPErrDNS TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SOAP error - DNS error"
::= 8
trapSOAPErrSocket TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SOAP error - socket error, server is not available"
::= 9
trapSOAPErrDelivery TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString }
DESCRIPTION
"SOAP error - delivery error, wrong return code from server"
::= 10
trapTempHighAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
DESCRIPTION
"Trap for high alarm on temperature"
::= 11
trapHumHighAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, hum, humAlarmInt }
DESCRIPTION
"Trap for high alarm on relative humidity"
::= 12
trapCompValHighAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, compVal, compValAlarmInt }
DESCRIPTION
"Trap for high alarm on computed value"
::= 13
trapTempLowAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
DESCRIPTION
"Trap for low alarm on temperature"
::= 21
trapHumLowAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, hum, humAlarmInt }
DESCRIPTION
"Trap for low alarm on relative humidity"
::= 22
trapCompValLowAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, compVal, compValAlarmInt }
DESCRIPTION
"Trap for low alarm on computed value"
::= 23
trapTempClrAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
DESCRIPTION
"Trap for clearing alarm on temperature"
::= 31
trapHumClrAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, hum, humAlarmInt }
DESCRIPTION
"Trap for clearing alarm on relative humidity"
::= 32
trapCompValClrAlarm TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, compVal, compValAlarmInt }
DESCRIPTION
"Trap for clearing alarm on computed value"
::= 33
trapTempError TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, temp, tempAlarmInt }
DESCRIPTION
"Trap for error on temperature"
::= 41
trapHumError TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, hum, humAlarmInt }
DESCRIPTION
"Trap for error on relative humidity"
::= 42
trapCompValError TRAP-TYPE
ENTERPRISE comet
VARIABLES { sensorName, messageString, compVal, compValAlarmInt }
DESCRIPTION
"Trap for error on computed value"
::= 43
END