PM8ECCMIB DEFINITIONS ::= BEGIN
|
|||
|
IMPORTS
|
|||
|
enterprises
|
|||
|
FROM RFC1155-SMI
|
|||
|
OBJECT-TYPE
|
|||
|
FROM RFC-1212
|
|||
|
TRAP-TYPE
|
|||
|
FROM RFC-1215;
|
|||
|
|
|||
|
AlarmType ::= INTEGER {
|
|||
|
overValue( 10 ),
|
|||
|
overPower( 11 ),
|
|||
|
overReversePower( 12 ),
|
|||
|
underValue( 20 ),
|
|||
|
underPower( 21 ),
|
|||
|
phaseRotationReversal( 51 ),
|
|||
|
phaseLossVoltage( 52 ),
|
|||
|
phaseLossCurrent( 53 ),
|
|||
|
powerFactorLeading( 54 ),
|
|||
|
powerFactorLagging( 55 ),
|
|||
|
digitalInputOFFtoON( 60 ),
|
|||
|
digitalInputONtoOFF( 61 ),
|
|||
|
unaryEvent( 70 ),
|
|||
|
voltageOrCurrentSwell( 80 ),
|
|||
|
voltageOrCurrentSag( 90 ),
|
|||
|
combinatorialAND( 100 ),
|
|||
|
combinatorialNAND( 101 ),
|
|||
|
combinatorialOR( 102 ),
|
|||
|
combinatorialNOR( 103 ),
|
|||
|
combinatorialXOR( 104 ),
|
|||
|
combinatorialNOT( 105 ),
|
|||
|
diagnostic( 1280 )
|
|||
|
}
|
|||
|
|
|||
|
IOPointType ::= INTEGER {
|
|||
|
digitalInput( 1 ),
|
|||
|
digitalOutput( 2 ),
|
|||
|
analogInput( 3 ),
|
|||
|
analogOutput( 4 )
|
|||
|
}
|
|||
|
|
|||
|
IOPointLabel ::= OCTET STRING (SIZE(0..16))
|
|||
|
|
|||
|
AlarmLabel ::= OCTET STRING (SIZE(0..16))
|
|||
|
|
|||
|
|
|||
|
|
|||
|
schneiderElectric OBJECT IDENTIFIER ::= { enterprises 3833 }
|
|||
|
|
|||
|
transparentFactoryEthernet OBJECT IDENTIFIER ::= { schneiderElectric 1 }
|
|||
|
|
|||
|
equipmentProfile OBJECT IDENTIFIER ::= { transparentFactoryEthernet 7 }
|
|||
|
|
|||
|
tfProducts OBJECT IDENTIFIER ::= { equipmentProfile 255 }
|
|||
|
|
|||
|
ecc OBJECT IDENTIFIER ::= { tfProducts 15 }
|
|||
|
|
|||
|
pm8ecc OBJECT IDENTIFIER ::= { ecc 1 }
|
|||
|
|
|||
|
metering OBJECT IDENTIFIER ::= { pm8ecc 1 }
|
|||
|
|
|||
|
systemWiringTypeTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF SystemWiringTypeEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "The wiring system type of the host meter."
|
|||
|
::= { metering 1 }
|
|||
|
|
|||
|
systemWiringTypeEntry OBJECT-TYPE
|
|||
|
SYNTAX SystemWiringTypeEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter System Wiring Type"
|
|||
|
INDEX {
|
|||
|
swtIndex
|
|||
|
}
|
|||
|
::= { systemWiringTypeTable 1 }
|
|||
|
|
|||
|
SystemWiringTypeEntry ::= SEQUENCE {
|
|||
|
swtIndex
|
|||
|
INTEGER,
|
|||
|
swtWiringType
|
|||
|
INTEGER
|
|||
|
}
|
|||
|
|
|||
|
swtIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "System Wiring Type Table Index"
|
|||
|
::= { systemWiringTypeEntry 1 }
|
|||
|
|
|||
|
swtWiringType OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (10 | 11 | 12 | 30 | 31 | 32 | 40 | 42 | 44)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Single Phase Line to Neutral 2 Wire 1CT 1PT is
|
|||
|
'10' Single Phase Line to Line 2 Wire 1CT 1PT
|
|||
|
is '11' Single Phase 3-Wire 3 wire 2CT 2PT is
|
|||
|
'12' Three Phase 3 Wire 2CT 2PT is '30' Three
|
|||
|
Phase 3 Wire 3CT 2PT is '31' Three Phase 3 Wire
|
|||
|
1CT 2PT is '32' Three Phase 4 Wire 3CT 3PT is
|
|||
|
'40' Three Phase 4 Wire 3CT 2PT is '42' Three
|
|||
|
Phase 4 Wire 1CT 3PT is '44'"
|
|||
|
::= { systemWiringTypeEntry 2 }
|
|||
|
|
|||
|
loadCurrentTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF LoadCurrentEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Load Current Table"
|
|||
|
::= { metering 2 }
|
|||
|
|
|||
|
loadCurrentEntry OBJECT-TYPE
|
|||
|
SYNTAX LoadCurrentEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Load Current Table"
|
|||
|
INDEX {
|
|||
|
lcIndex
|
|||
|
}
|
|||
|
::= { loadCurrentTable 1 }
|
|||
|
|
|||
|
LoadCurrentEntry ::= SEQUENCE {
|
|||
|
lcIndex
|
|||
|
INTEGER,
|
|||
|
lcIa
|
|||
|
OCTET STRING,
|
|||
|
lcIb
|
|||
|
OCTET STRING,
|
|||
|
lcIc
|
|||
|
OCTET STRING,
|
|||
|
lcIAvg
|
|||
|
OCTET STRING
|
|||
|
}
|
|||
|
|
|||
|
lcIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Load Current Table Index"
|
|||
|
::= { loadCurrentEntry 1 }
|
|||
|
|
|||
|
lcIa OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Load Current Phase A Units = A (Amps)"
|
|||
|
::= { loadCurrentEntry 2 }
|
|||
|
|
|||
|
lcIb OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Load Current Phase B Units = A (Amps)"
|
|||
|
::= { loadCurrentEntry 3 }
|
|||
|
|
|||
|
lcIc OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Load Current Phase C Units = A (Amps)"
|
|||
|
::= { loadCurrentEntry 4 }
|
|||
|
|
|||
|
lcIAvg OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Load Current 3 Phase Average Units
|
|||
|
= A (Amps)"
|
|||
|
::= { loadCurrentEntry 5 }
|
|||
|
|
|||
|
powerTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF PowerEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Power Table"
|
|||
|
::= { metering 3 }
|
|||
|
|
|||
|
powerEntry OBJECT-TYPE
|
|||
|
SYNTAX PowerEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Power Table"
|
|||
|
INDEX {
|
|||
|
pIndex
|
|||
|
}
|
|||
|
::= { powerTable 1 }
|
|||
|
|
|||
|
PowerEntry ::= SEQUENCE {
|
|||
|
pIndex
|
|||
|
INTEGER,
|
|||
|
pReal
|
|||
|
OCTET STRING,
|
|||
|
pReactive
|
|||
|
OCTET STRING,
|
|||
|
pApparent
|
|||
|
OCTET STRING
|
|||
|
}
|
|||
|
|
|||
|
pIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Power Table Index"
|
|||
|
::= { powerEntry 1 }
|
|||
|
|
|||
|
pReal OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Real Power Units = kW"
|
|||
|
::= { powerEntry 2 }
|
|||
|
|
|||
|
pReactive OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Reactive Power Units = kVAR"
|
|||
|
::= { powerEntry 3 }
|
|||
|
|
|||
|
pApparent OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Apparent Power Units = kVA"
|
|||
|
::= { powerEntry 4 }
|
|||
|
|
|||
|
powerFactorTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF PowerFactorEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Power Factor Table"
|
|||
|
::= { metering 4 }
|
|||
|
|
|||
|
powerFactorEntry OBJECT-TYPE
|
|||
|
SYNTAX PowerFactorEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Power Factor Table"
|
|||
|
INDEX {
|
|||
|
pfIndex
|
|||
|
}
|
|||
|
::= { powerFactorTable 1 }
|
|||
|
|
|||
|
PowerFactorEntry ::= SEQUENCE {
|
|||
|
pfIndex
|
|||
|
INTEGER,
|
|||
|
pfPowerFactorTotal
|
|||
|
OCTET STRING,
|
|||
|
pfPowerFactorDescription
|
|||
|
OCTET STRING
|
|||
|
}
|
|||
|
|
|||
|
pfIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Power Factor Table Index"
|
|||
|
::= { powerFactorEntry 1 }
|
|||
|
|
|||
|
pfPowerFactorTotal OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter 3 Phase Total Power Factor"
|
|||
|
::= { powerFactorEntry 2 }
|
|||
|
|
|||
|
pfPowerFactorDescription OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Describes the current power factor Lead/Lag for
|
|||
|
IEEE mode Cap/Ind for IEC mode"
|
|||
|
::= { powerFactorEntry 3 }
|
|||
|
|
|||
|
voltageTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF VoltageEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Voltage Table"
|
|||
|
::= { metering 5 }
|
|||
|
|
|||
|
voltageEntry OBJECT-TYPE
|
|||
|
SYNTAX VoltageEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Voltage Table"
|
|||
|
INDEX {
|
|||
|
vIndex
|
|||
|
}
|
|||
|
::= { voltageTable 1 }
|
|||
|
|
|||
|
VoltageEntry ::= SEQUENCE {
|
|||
|
vIndex
|
|||
|
INTEGER,
|
|||
|
vVab
|
|||
|
OCTET STRING,
|
|||
|
vVbc
|
|||
|
OCTET STRING,
|
|||
|
vVca
|
|||
|
OCTET STRING,
|
|||
|
vVllAvg
|
|||
|
OCTET STRING,
|
|||
|
vVan
|
|||
|
OCTET STRING,
|
|||
|
vVbn
|
|||
|
OCTET STRING,
|
|||
|
vVcn
|
|||
|
OCTET STRING,
|
|||
|
vVlnAvg
|
|||
|
OCTET STRING
|
|||
|
}
|
|||
|
|
|||
|
vIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Voltage Table Index"
|
|||
|
::= { voltageEntry 1 }
|
|||
|
|
|||
|
vVab OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Voltage Line A to Line B Units = V
|
|||
|
(Volts)"
|
|||
|
::= { voltageEntry 2 }
|
|||
|
|
|||
|
vVbc OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Voltage Line B to Line C Units = V
|
|||
|
(Volts)"
|
|||
|
::= { voltageEntry 3 }
|
|||
|
|
|||
|
vVca OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Voltage Line C to Line A Units = V
|
|||
|
(Volts)"
|
|||
|
::= { voltageEntry 4 }
|
|||
|
|
|||
|
vVllAvg OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Voltage Line to Line Average Voltage
|
|||
|
Units = V (Volts)"
|
|||
|
::= { voltageEntry 5 }
|
|||
|
|
|||
|
vVan OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Voltage Line A to Neutral Units = V
|
|||
|
(Volts)"
|
|||
|
::= { voltageEntry 6 }
|
|||
|
|
|||
|
vVbn OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Voltage Line B to Neutral Units = V
|
|||
|
(Volts)"
|
|||
|
::= { voltageEntry 7 }
|
|||
|
|
|||
|
vVcn OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Voltage Line C to Neutral Units = V
|
|||
|
(Volts)"
|
|||
|
::= { voltageEntry 8 }
|
|||
|
|
|||
|
vVlnAvg OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Voltage Line to Neutral 3 Phase Average
|
|||
|
Units = V (Volts)"
|
|||
|
::= { voltageEntry 9 }
|
|||
|
|
|||
|
frequencyTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF FrequencyEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Frequency Table"
|
|||
|
::= { metering 6 }
|
|||
|
|
|||
|
frequencyEntry OBJECT-TYPE
|
|||
|
SYNTAX FrequencyEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Frequency Table"
|
|||
|
INDEX {
|
|||
|
fIndex
|
|||
|
}
|
|||
|
::= { frequencyTable 1 }
|
|||
|
|
|||
|
FrequencyEntry ::= SEQUENCE {
|
|||
|
fIndex
|
|||
|
INTEGER,
|
|||
|
fFrequency
|
|||
|
OCTET STRING
|
|||
|
}
|
|||
|
|
|||
|
fIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Frequency Table Index"
|
|||
|
::= { frequencyEntry 1 }
|
|||
|
|
|||
|
fFrequency OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Frequency Units = Hz"
|
|||
|
::= { frequencyEntry 2 }
|
|||
|
|
|||
|
currentDemandTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF CurrentDemandEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Current Demand Table"
|
|||
|
::= { metering 7 }
|
|||
|
|
|||
|
currentDemandEntry OBJECT-TYPE
|
|||
|
SYNTAX CurrentDemandEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Current Demand Table"
|
|||
|
INDEX {
|
|||
|
cdPhase,
|
|||
|
cdIndex
|
|||
|
}
|
|||
|
::= { currentDemandTable 1 }
|
|||
|
|
|||
|
CurrentDemandEntry ::= SEQUENCE {
|
|||
|
cdIndex
|
|||
|
INTEGER,
|
|||
|
cdPhase
|
|||
|
OCTET STRING,
|
|||
|
cdPresentCurrentDemand
|
|||
|
OCTET STRING,
|
|||
|
cdPeakCurrentDemand
|
|||
|
OCTET STRING,
|
|||
|
cdLastCurrentDemand
|
|||
|
OCTET STRING,
|
|||
|
cdPeakDateTime
|
|||
|
OCTET STRING,
|
|||
|
cdResetDateTime
|
|||
|
OCTET STRING,
|
|||
|
cdPhaseEnum
|
|||
|
INTEGER
|
|||
|
}
|
|||
|
|
|||
|
cdIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Demand Current Table Index"
|
|||
|
::= { currentDemandEntry 1 }
|
|||
|
|
|||
|
cdPhase OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(2))
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Current Demand Phase Name"
|
|||
|
::= { currentDemandEntry 2 }
|
|||
|
|
|||
|
cdPresentCurrentDemand OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Present Demand Current Units = A (Amps)"
|
|||
|
::= { currentDemandEntry 3 }
|
|||
|
|
|||
|
cdPeakCurrentDemand OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Peak Current Demand Units = A (Amps)"
|
|||
|
::= { currentDemandEntry 4 }
|
|||
|
|
|||
|
cdLastCurrentDemand OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Current Demand Last Interval Units
|
|||
|
= A (Amps)"
|
|||
|
::= { currentDemandEntry 5 }
|
|||
|
|
|||
|
cdPeakDateTime OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Peak Current Demand Date and Time"
|
|||
|
::= { currentDemandEntry 6 }
|
|||
|
|
|||
|
cdResetDateTime OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Date and Time of Demand Current Reset"
|
|||
|
::= { currentDemandEntry 7 }
|
|||
|
|
|||
|
cdPhaseEnum OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
currentPhaseA( 1 ),
|
|||
|
currentPhaseB( 2 ),
|
|||
|
currentPhaseC( 3 )
|
|||
|
}
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Current Demand Phase"
|
|||
|
::= { currentDemandEntry 8 }
|
|||
|
|
|||
|
powerDemandTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF PowerDemandEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Power Demand"
|
|||
|
::= { metering 8 }
|
|||
|
|
|||
|
powerDemandEntry OBJECT-TYPE
|
|||
|
SYNTAX PowerDemandEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Power Demand Table"
|
|||
|
INDEX {
|
|||
|
pdComponent,
|
|||
|
pdIndex
|
|||
|
}
|
|||
|
::= { powerDemandTable 1 }
|
|||
|
|
|||
|
PowerDemandEntry ::= SEQUENCE {
|
|||
|
pdIndex
|
|||
|
INTEGER,
|
|||
|
pdComponent
|
|||
|
OCTET STRING,
|
|||
|
pdPresentPowerDemand
|
|||
|
OCTET STRING,
|
|||
|
pdPeakPowerDemand
|
|||
|
OCTET STRING,
|
|||
|
pdLastPowerDemand
|
|||
|
OCTET STRING,
|
|||
|
pdPeakDateTime
|
|||
|
OCTET STRING,
|
|||
|
pdResetDateTime
|
|||
|
OCTET STRING,
|
|||
|
pdComponentEnum
|
|||
|
INTEGER
|
|||
|
}
|
|||
|
|
|||
|
pdIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Power Demand Table Index"
|
|||
|
::= { powerDemandEntry 1 }
|
|||
|
|
|||
|
pdComponent OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(4..8))
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Power Demand Component Units: Real
|
|||
|
= kW Reacitve = kVAR Apparent = kVA"
|
|||
|
::= { powerDemandEntry 2 }
|
|||
|
|
|||
|
pdPresentPowerDemand OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Present Demand Power"
|
|||
|
::= { powerDemandEntry 3 }
|
|||
|
|
|||
|
pdPeakPowerDemand OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Peak Power Demand"
|
|||
|
::= { powerDemandEntry 4 }
|
|||
|
|
|||
|
pdLastPowerDemand OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Power Demand Last Interval"
|
|||
|
::= { powerDemandEntry 5 }
|
|||
|
|
|||
|
pdPeakDateTime OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Peak Power Demand Date and Time"
|
|||
|
::= { powerDemandEntry 6 }
|
|||
|
|
|||
|
pdResetDateTime OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Date and Time of Power Demand Reset"
|
|||
|
::= { powerDemandEntry 7 }
|
|||
|
|
|||
|
pdComponentEnum OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
realPower( 1 ),
|
|||
|
reactivePower( 2 ),
|
|||
|
apparentPower( 3 )
|
|||
|
}
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Power Demand Component"
|
|||
|
::= { powerDemandEntry 8 }
|
|||
|
|
|||
|
energyTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF EnergyEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Energy Table"
|
|||
|
::= { metering 9 }
|
|||
|
|
|||
|
energyEntry OBJECT-TYPE
|
|||
|
SYNTAX EnergyEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Energy Table"
|
|||
|
INDEX {
|
|||
|
eIndex
|
|||
|
}
|
|||
|
::= { energyTable 1 }
|
|||
|
|
|||
|
EnergyEntry ::= SEQUENCE {
|
|||
|
eIndex
|
|||
|
INTEGER,
|
|||
|
eRealEnergy
|
|||
|
OCTET STRING,
|
|||
|
eDateTimeRealEnergyReset
|
|||
|
OCTET STRING,
|
|||
|
eReactiveEnergy
|
|||
|
OCTET STRING,
|
|||
|
eDateTimeReactiveEnergyReset
|
|||
|
OCTET STRING,
|
|||
|
eApparentEnergy
|
|||
|
OCTET STRING,
|
|||
|
eDateTimeApparentEnergyReset
|
|||
|
OCTET STRING
|
|||
|
}
|
|||
|
|
|||
|
eIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Energy Table Index"
|
|||
|
::= { energyEntry 1 }
|
|||
|
|
|||
|
eRealEnergy OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Real Energy Units = Wh"
|
|||
|
::= { energyEntry 2 }
|
|||
|
|
|||
|
eDateTimeRealEnergyReset OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Date and Time Real Energy Accumulation
|
|||
|
was reset"
|
|||
|
::= { energyEntry 3 }
|
|||
|
|
|||
|
eReactiveEnergy OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Reactive Energy Units = VARh"
|
|||
|
::= { energyEntry 4 }
|
|||
|
|
|||
|
eDateTimeReactiveEnergyReset OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Date and Time Reative Energy Accumulation
|
|||
|
was reset"
|
|||
|
::= { energyEntry 5 }
|
|||
|
|
|||
|
eApparentEnergy OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Apparent Energy Units = VAh"
|
|||
|
::= { energyEntry 6 }
|
|||
|
|
|||
|
eDateTimeApparentEnergyReset OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Date and Time Reactive Energy Accumulation
|
|||
|
was reset"
|
|||
|
::= { energyEntry 7 }
|
|||
|
|
|||
|
alarms OBJECT IDENTIFIER ::= { pm8ecc 2 }
|
|||
|
|
|||
|
alarmConfigurationTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF AlarmConfigurationEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Displays the current configuration of the Host
|
|||
|
Meter On-board alarms"
|
|||
|
::= { alarms 1 }
|
|||
|
|
|||
|
alarmConfigurationEntry OBJECT-TYPE
|
|||
|
SYNTAX AlarmConfigurationEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Contains configuration information for the Host
|
|||
|
Meter On-board Alarms"
|
|||
|
INDEX {
|
|||
|
acIndex,
|
|||
|
acPosition
|
|||
|
}
|
|||
|
::= { alarmConfigurationTable 1 }
|
|||
|
|
|||
|
AlarmConfigurationEntry ::= SEQUENCE {
|
|||
|
acIndex
|
|||
|
INTEGER,
|
|||
|
acPosition
|
|||
|
INTEGER,
|
|||
|
acAlarmLabel
|
|||
|
AlarmLabel,
|
|||
|
acEnabled
|
|||
|
INTEGER,
|
|||
|
acStatus
|
|||
|
INTEGER,
|
|||
|
acCounter
|
|||
|
INTEGER,
|
|||
|
acPriority
|
|||
|
INTEGER,
|
|||
|
acType
|
|||
|
AlarmType,
|
|||
|
acAlarmList1
|
|||
|
INTEGER,
|
|||
|
acAlarmList2
|
|||
|
INTEGER,
|
|||
|
acAlarmList3
|
|||
|
INTEGER,
|
|||
|
acAlarmList4
|
|||
|
INTEGER
|
|||
|
}
|
|||
|
|
|||
|
acIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Alarm Configuration Table Index"
|
|||
|
::= { alarmConfigurationEntry 1 }
|
|||
|
|
|||
|
acPosition OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..74)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Indicates the position of the alarm. 1 - 74"
|
|||
|
::= { alarmConfigurationEntry 2 }
|
|||
|
|
|||
|
acAlarmLabel OBJECT-TYPE
|
|||
|
SYNTAX AlarmLabel
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "The name of the alarm (user configurable)"
|
|||
|
::= { alarmConfigurationEntry 3 }
|
|||
|
|
|||
|
acEnabled OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (0 | 255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Indicates whether the alarm is enabled or not.
|
|||
|
0 = Disabled 255 = Enabled"
|
|||
|
::= { alarmConfigurationEntry 4 }
|
|||
|
|
|||
|
acStatus OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (0..1)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Indicates whether the alarm is active. 0 = Inactive
|
|||
|
1 = Active"
|
|||
|
::= { alarmConfigurationEntry 5 }
|
|||
|
|
|||
|
acCounter OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (0..32767)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Indicates the number of times the alarm has been
|
|||
|
activated. Note: This counter resets at 32767"
|
|||
|
::= { alarmConfigurationEntry 6 }
|
|||
|
|
|||
|
acPriority OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (0..3)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "The priority of the alarm. 0 = No Priority 1 =
|
|||
|
Low Priority 2 = Medium Priority 3 = High Priority"
|
|||
|
::= { alarmConfigurationEntry 7 }
|
|||
|
|
|||
|
acType OBJECT-TYPE
|
|||
|
SYNTAX AlarmType
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Indicates the type of the alarm."
|
|||
|
::= { alarmConfigurationEntry 8 }
|
|||
|
|
|||
|
acAlarmList1 OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Used for combinatorial type alarms - The position
|
|||
|
of the first alarm that is used to evaluate the
|
|||
|
alarm state."
|
|||
|
::= { alarmConfigurationEntry 9 }
|
|||
|
|
|||
|
acAlarmList2 OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Used for combinatorial type alarms - The position
|
|||
|
of the second alarm that is used to evaluate
|
|||
|
the alarm state."
|
|||
|
::= { alarmConfigurationEntry 10 }
|
|||
|
|
|||
|
acAlarmList3 OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Used for combinatorial type alarms - The position
|
|||
|
of the third alarm that is used to evaluate the
|
|||
|
alarm state."
|
|||
|
::= { alarmConfigurationEntry 11 }
|
|||
|
|
|||
|
acAlarmList4 OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Used for combinatorial type alarms - The position
|
|||
|
of the fourth alarm that is used to evaluate
|
|||
|
the alarm state."
|
|||
|
::= { alarmConfigurationEntry 12 }
|
|||
|
|
|||
|
alarmSummaryBitmapsTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF AlarmSummaryBitmapsEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Indicates the state of the Host Meter On-Board
|
|||
|
Alarms"
|
|||
|
::= { alarms 2 }
|
|||
|
|
|||
|
alarmSummaryBitmapsEntry OBJECT-TYPE
|
|||
|
SYNTAX AlarmSummaryBitmapsEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Indicates the status of the Host Meter On-Board
|
|||
|
Alarms"
|
|||
|
INDEX {
|
|||
|
alSumIndex
|
|||
|
}
|
|||
|
::= { alarmSummaryBitmapsTable 1 }
|
|||
|
|
|||
|
AlarmSummaryBitmapsEntry ::= SEQUENCE {
|
|||
|
alSumIndex
|
|||
|
INTEGER,
|
|||
|
alSumAlarms1to16
|
|||
|
OCTET STRING,
|
|||
|
alSumAlarms17to32
|
|||
|
OCTET STRING,
|
|||
|
alSumAlarms33to48
|
|||
|
OCTET STRING,
|
|||
|
alSumAlarms49to64
|
|||
|
OCTET STRING,
|
|||
|
alSumAlarms65to74
|
|||
|
OCTET STRING
|
|||
|
}
|
|||
|
|
|||
|
alSumIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Alarm Summary Bitmap Table Index"
|
|||
|
::= { alarmSummaryBitmapsEntry 1 }
|
|||
|
|
|||
|
alSumAlarms1to16 OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(16))
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Indicates the status of Alarms 1 - 16 (16-bits,
|
|||
|
bit-0 = Alarm 1)"
|
|||
|
::= { alarmSummaryBitmapsEntry 2 }
|
|||
|
|
|||
|
alSumAlarms17to32 OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(16))
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Indicates the status of Alarms 17 - 32 (16-bits,
|
|||
|
bit-0 = Alarm 17)"
|
|||
|
::= { alarmSummaryBitmapsEntry 3 }
|
|||
|
|
|||
|
alSumAlarms33to48 OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(16))
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Indicates the status of Alarms 33 - 48 (16-bits,
|
|||
|
bit-0 = Alarm 33)"
|
|||
|
::= { alarmSummaryBitmapsEntry 4 }
|
|||
|
|
|||
|
alSumAlarms49to64 OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(16))
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Indicates the status of Alarms 49 - 64 (16-bits,
|
|||
|
bit-0 = Alarm 49)"
|
|||
|
::= { alarmSummaryBitmapsEntry 5 }
|
|||
|
|
|||
|
alSumAlarms65to74 OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(16))
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Indicates the status of Alarms 65 - 74 (16-bits,
|
|||
|
bit-0 = Alarm 65, bit-9 = Alarm 74)"
|
|||
|
::= { alarmSummaryBitmapsEntry 6 }
|
|||
|
|
|||
|
alarmCountersTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF AlarmCountersEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter On-Board Alarm Counters"
|
|||
|
::= { alarms 3 }
|
|||
|
|
|||
|
alarmCountersEntry OBJECT-TYPE
|
|||
|
SYNTAX AlarmCountersEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter On-Board Alarm Counters"
|
|||
|
INDEX {
|
|||
|
alCntAlarmPosition,
|
|||
|
alCntIndex
|
|||
|
}
|
|||
|
::= { alarmCountersTable 1 }
|
|||
|
|
|||
|
AlarmCountersEntry ::= SEQUENCE {
|
|||
|
alCntIndex
|
|||
|
INTEGER,
|
|||
|
alCntAlarmPosition
|
|||
|
INTEGER,
|
|||
|
alCntCount
|
|||
|
INTEGER
|
|||
|
}
|
|||
|
|
|||
|
alCntIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Alarm Counters Table Index"
|
|||
|
::= { alarmCountersEntry 1 }
|
|||
|
|
|||
|
alCntAlarmPosition OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..74)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "The Host Meter Alarm Position"
|
|||
|
::= { alarmCountersEntry 2 }
|
|||
|
|
|||
|
alCntCount OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (0..65535)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "The number of times the Host Meter On-Board alarm
|
|||
|
has transitioned from an inactive state to an
|
|||
|
active state"
|
|||
|
::= { alarmCountersEntry 3 }
|
|||
|
|
|||
|
io OBJECT IDENTIFIER ::= { pm8ecc 3 }
|
|||
|
|
|||
|
ioOptionIDTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF IoOptionIDEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "I/O Option Module Installed on the Host Meter"
|
|||
|
::= { io 1 }
|
|||
|
|
|||
|
ioOptionIDEntry OBJECT-TYPE
|
|||
|
SYNTAX IoOptionIDEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "I/O Option Card Installed On-board the Host Meter"
|
|||
|
INDEX {
|
|||
|
ioIDIndex
|
|||
|
}
|
|||
|
::= { ioOptionIDTable 1 }
|
|||
|
|
|||
|
IoOptionIDEntry ::= SEQUENCE {
|
|||
|
ioIDIndex
|
|||
|
INTEGER,
|
|||
|
ioIDInstalledOptionSlot1
|
|||
|
INTEGER,
|
|||
|
ioIDInstalledOptionSlot2
|
|||
|
INTEGER
|
|||
|
}
|
|||
|
|
|||
|
ioIDIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "I/O Installed Option ID Table Index"
|
|||
|
::= { ioOptionIDEntry 1 }
|
|||
|
|
|||
|
ioIDInstalledOptionSlot1 OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
unused( 1 ),
|
|||
|
io-22( 2 ),
|
|||
|
io-26( 3 ),
|
|||
|
io-2222( 4 )
|
|||
|
}
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "0 = Not Installed 1 = Unused 2 = IO22 3 = IO26
|
|||
|
4 = IO 2222"
|
|||
|
::= { ioOptionIDEntry 2 }
|
|||
|
|
|||
|
ioIDInstalledOptionSlot2 OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
unused( 1 ),
|
|||
|
io-22( 2 ),
|
|||
|
io-26( 3 ),
|
|||
|
io-2222( 4 )
|
|||
|
}
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "0 = Not Installed 1 = Unused 2 = IO22 3 = IO26
|
|||
|
4 = IO 2222"
|
|||
|
::= { ioOptionIDEntry 3 }
|
|||
|
|
|||
|
ioConfigurationTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF IoConfigurationEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Displays the current I/O configuration for each
|
|||
|
I/O point"
|
|||
|
::= { io 2 }
|
|||
|
|
|||
|
ioConfigurationEntry OBJECT-TYPE
|
|||
|
SYNTAX IoConfigurationEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Contains configuration information for the Host
|
|||
|
Meter On-board I/O"
|
|||
|
INDEX {
|
|||
|
iocIndex,
|
|||
|
iocPointNumber
|
|||
|
}
|
|||
|
::= { ioConfigurationTable 1 }
|
|||
|
|
|||
|
IoConfigurationEntry ::= SEQUENCE {
|
|||
|
iocIndex
|
|||
|
INTEGER,
|
|||
|
iocPointNumber
|
|||
|
INTEGER,
|
|||
|
iocLabel
|
|||
|
IOPointLabel,
|
|||
|
iocStateOrValue
|
|||
|
OCTET STRING,
|
|||
|
iocPointType
|
|||
|
IOPointType,
|
|||
|
iocMode
|
|||
|
INTEGER,
|
|||
|
iocType
|
|||
|
INTEGER,
|
|||
|
iocCount
|
|||
|
OCTET STRING
|
|||
|
}
|
|||
|
|
|||
|
iocIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "I/O Configuration Table Index"
|
|||
|
::= { ioConfigurationEntry 1 }
|
|||
|
|
|||
|
iocPointNumber OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..18)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "The point number for this I/O Point"
|
|||
|
::= { ioConfigurationEntry 2 }
|
|||
|
|
|||
|
iocLabel OBJECT-TYPE
|
|||
|
SYNTAX IOPointLabel
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "The name of the I/O Point (user configurable)"
|
|||
|
::= { ioConfigurationEntry 3 }
|
|||
|
|
|||
|
iocStateOrValue OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Displays the current value for the I/O Point Digial
|
|||
|
I/O: 1 = Active or 0 = Inactive
|
|||
|
|
|||
|
Analog I/O: Scaled input/output value"
|
|||
|
::= { ioConfigurationEntry 4 }
|
|||
|
|
|||
|
iocPointType OBJECT-TYPE
|
|||
|
SYNTAX IOPointType
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "The type of I/O at this point"
|
|||
|
::= { ioConfigurationEntry 5 }
|
|||
|
|
|||
|
iocMode OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (0..9)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "For Digital Inputs and Outputs this object is
|
|||
|
always 0 indicating <20>Discrete<74>.
|
|||
|
|
|||
|
For Analog Inputs and Outputs this object indicates
|
|||
|
the range of analog I/O values (used without
|
|||
|
units) 0 = 0 <20> 1 1 = 0 <20> 5 2 = 0 <20> 10 3 = 0 <20>
|
|||
|
20 4 = 1 <20> 5 5 = 4 <20> 20 6 = -5 <20> 5 7 = -10 <20>
|
|||
|
10 8 = -100 <20> 100 9 = User defined (values default
|
|||
|
to 0)"
|
|||
|
::= { ioConfigurationEntry 6 }
|
|||
|
|
|||
|
iocType OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "For Digital Inputs this object indicates input
|
|||
|
type 1 = Unused 2 = AC/DC
|
|||
|
|
|||
|
For Digital Outputs this object indicates output
|
|||
|
type 1 = solid state relay 2 = electromechanical
|
|||
|
relay
|
|||
|
|
|||
|
For Analog Inputs and Outputs this object indicates
|
|||
|
the digital resolution of the I/O hardware. 0
|
|||
|
= 8-Bit, unipolar 1 = 10-Bit, unipolar 2 = 12-Bit,
|
|||
|
unipolar 3 = 14-Bit, unipolar 4 = 16-Bit, unipolar
|
|||
|
5 = 16-Bit, bipolar with sign 6 = reserved 7
|
|||
|
= reserved 8 = Resolution for IO2222 Voltage
|
|||
|
range 0 - 4000 9 = Resolution for IO2222 Current
|
|||
|
range 800 - 4000"
|
|||
|
::= { ioConfigurationEntry 7 }
|
|||
|
|
|||
|
iocCount OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(8))
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Number of times digital I/O point has transitioned
|
|||
|
from OFF to ON"
|
|||
|
::= { ioConfigurationEntry 8 }
|
|||
|
|
|||
|
ioStatusBitmapsTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF IoStatusBitmapsEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter I/O Status Bitmaps"
|
|||
|
::= { io 3 }
|
|||
|
|
|||
|
ioStatusBitmapsEntry OBJECT-TYPE
|
|||
|
SYNTAX IoStatusBitmapsEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter On-Board I/O Status Bitmaps"
|
|||
|
INDEX {
|
|||
|
ioStatIndex
|
|||
|
}
|
|||
|
::= { ioStatusBitmapsTable 1 }
|
|||
|
|
|||
|
IoStatusBitmapsEntry ::= SEQUENCE {
|
|||
|
ioStatIndex
|
|||
|
INTEGER,
|
|||
|
ioStatSummaryBitmap
|
|||
|
OCTET STRING
|
|||
|
}
|
|||
|
|
|||
|
ioStatIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "I/O Summary Bitmaps Table Index"
|
|||
|
::= { ioStatusBitmapsEntry 1 }
|
|||
|
|
|||
|
ioStatSummaryBitmap OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING (SIZE(18))
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Indicates the Status of the Host Meter I/O Points
|
|||
|
Bit-0 = I/O Point 1 Bit-1 = I/O Point 2 ... Bit-17
|
|||
|
= I/O Point 18"
|
|||
|
::= { ioStatusBitmapsEntry 2 }
|
|||
|
|
|||
|
meterSystem OBJECT IDENTIFIER ::= { pm8ecc 4 }
|
|||
|
|
|||
|
meterIdentificationTable OBJECT-TYPE
|
|||
|
SYNTAX SEQUENCE OF MeterIdentificationEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Identification"
|
|||
|
::= { meterSystem 1 }
|
|||
|
|
|||
|
meterIdentificationEntry OBJECT-TYPE
|
|||
|
SYNTAX MeterIdentificationEntry
|
|||
|
ACCESS not-accessible
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Identification"
|
|||
|
INDEX {
|
|||
|
midIndex
|
|||
|
}
|
|||
|
::= { meterIdentificationTable 1 }
|
|||
|
|
|||
|
MeterIdentificationEntry ::= SEQUENCE {
|
|||
|
midIndex
|
|||
|
INTEGER,
|
|||
|
midSerialNumber
|
|||
|
INTEGER,
|
|||
|
midFirmwareVersion
|
|||
|
OCTET STRING,
|
|||
|
midModelNumber
|
|||
|
OCTET STRING,
|
|||
|
midDeviceName
|
|||
|
OCTET STRING
|
|||
|
}
|
|||
|
|
|||
|
midIndex OBJECT-TYPE
|
|||
|
SYNTAX INTEGER (1..255)
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Meter Identification Table Index"
|
|||
|
::= { meterIdentificationEntry 1 }
|
|||
|
|
|||
|
midSerialNumber OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host meter 32 bit Serial Number"
|
|||
|
::= { meterIdentificationEntry 2 }
|
|||
|
|
|||
|
midFirmwareVersion OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Firmware Version"
|
|||
|
::= { meterIdentificationEntry 3 }
|
|||
|
|
|||
|
midModelNumber OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Model Number"
|
|||
|
::= { meterIdentificationEntry 4 }
|
|||
|
|
|||
|
midDeviceName OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "Host Meter Label plus Nameplate"
|
|||
|
::= { meterIdentificationEntry 5 }
|
|||
|
|
|||
|
trapVariables OBJECT IDENTIFIER ::= { pm8ecc 5 }
|
|||
|
|
|||
|
alarmDateAndTime OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "The Date and Time of the alarm state change."
|
|||
|
::= { trapVariables 1 }
|
|||
|
|
|||
|
alarmLabel OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "The Descriptive Label given to the alarm"
|
|||
|
::= { trapVariables 2 }
|
|||
|
|
|||
|
alarmState OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "The state of the Alarm - pickup, dropout, unary,
|
|||
|
diagnostic"
|
|||
|
::= { trapVariables 3 }
|
|||
|
|
|||
|
alarmValue OBJECT-TYPE
|
|||
|
SYNTAX INTEGER
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "The value of the alarm when it changed state."
|
|||
|
::= { trapVariables 4 }
|
|||
|
|
|||
|
alarmPriority OBJECT-TYPE
|
|||
|
SYNTAX INTEGER {
|
|||
|
highPriority( 1 ),
|
|||
|
mediumPriority( 2 ),
|
|||
|
lowPriority( 3 )
|
|||
|
}
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "The priority defined for the alarm."
|
|||
|
::= { trapVariables 5 }
|
|||
|
|
|||
|
mibVersion OBJECT-TYPE
|
|||
|
SYNTAX OCTET STRING
|
|||
|
ACCESS read-only
|
|||
|
STATUS mandatory
|
|||
|
DESCRIPTION "This is the current version of the MIB"
|
|||
|
::= { pm8ecc 6 }
|
|||
|
|
|||
|
|
|||
|
pm8OnBoardAlarmP1 TRAP-TYPE
|
|||
|
ENTERPRISE pm8ecc
|
|||
|
VARIABLES {
|
|||
|
alarmDateAndTime,
|
|||
|
alarmLabel,
|
|||
|
alarmState,
|
|||
|
alarmValue,
|
|||
|
alarmPriority
|
|||
|
}
|
|||
|
DESCRIPTION "Indicates the Host Meter On-Board Alarm system has
|
|||
|
detected a state change of an enabled alarm with a
|
|||
|
priority of 1"
|
|||
|
::= 1
|
|||
|
|
|||
|
pm8OnBoardAlarmP2 TRAP-TYPE
|
|||
|
ENTERPRISE pm8ecc
|
|||
|
VARIABLES {
|
|||
|
alarmDateAndTime,
|
|||
|
alarmLabel,
|
|||
|
alarmState,
|
|||
|
alarmValue,
|
|||
|
alarmPriority
|
|||
|
}
|
|||
|
DESCRIPTION "Indicates the Host Meter On-Board Alarm system has
|
|||
|
detected a state change of an enabled alarm with a
|
|||
|
priority of 2"
|
|||
|
::= 2
|
|||
|
|
|||
|
pm8OnBoardAlarmP3 TRAP-TYPE
|
|||
|
ENTERPRISE pm8ecc
|
|||
|
VARIABLES {
|
|||
|
alarmDateAndTime,
|
|||
|
alarmLabel,
|
|||
|
alarmState,
|
|||
|
alarmValue,
|
|||
|
alarmPriority
|
|||
|
}
|
|||
|
DESCRIPTION "Indicates the Host Meter On-Board Alarm system has
|
|||
|
detected a state change of an enabled alarm with a
|
|||
|
priority of 3"
|
|||
|
::= 3
|
|||
|
|
|||
|
|
|||
|
END
|
|||
|
|