-- Toshiba MIB
-- MIB for Toshiba G9000 Uninterruptible Power Supply
--
--{iso(1) org(3) dod(6) internet(1) private(4) enterprises(1)
-- toshiba(186) equ(1) equups(19) ticups(2) rmti4 (5) upsG9000-G2020(1)}
--=============================================================================
TIC-RMTI4-G9000-G2020-MIB DEFINITIONS ::= BEGIN
--=============================================================================
-- Update : September 28, 2016
-- By : Edwin Rubio, Toshiba International Corp.
-- Revised: renamed MIB file from upsG9000 to upsG9000-G2020
--=============================================================================
-- Update : May 28, 2015
-- By : Edwin Rubio, Toshiba International Corp.
-- Revised: Added in description warning for upsTrapBatteryLow, upsTrapBatteryLowClear and upsAlarmBatteryLow.
-- : Added in description warning for upsTrapBatteryDepleted, upsTrapBatteryDepletedClear and upsAlarmBatteryDepleted.
-- : Added in description warning for upsTrapAsyncOperation, upsTrapAsyncOperationClear and upsAlarmAsyncOperation.
-- : Added in description warning for upsTrapRemotEyeCommError, upsTrapRemotEyeCommErrorClear and upsAlarmRemotEyeCommError.
-- : Added in description warning for upsTrapOnBypass, upsTrapOnBypassClear and upsAlarmOnBypass.
-- : Added in description info for upsTrapPowerFailure, upsTrapPowerFailureClear, and upsAlarmPowerFailure
--=============================================================================
-- Update : March 19, 2015
-- By : Edwin Rubio, Toshiba International Corp.
-- Revised: renamed upsConfigInputRatedFrequency to upsConfigRatedInputFrequency
-- : Added upsAlarmUserDefinedOverload
-- : Added upsConfigUserDefinedOverloadSetPoint
-- : Added upsTrapUserDefinedOverload
-- : Added upsTrapUserDefinedOverloadClear
--=============================================================================
-- Update : February 3, 2015
-- By : Edwin Rubio, Toshiba International Corp.
-- Revised: renamed upsConfigInputRatedFrequency to upsConfigRatedInputFrequency
--=============================================================================
-- Update : January 30, 2015
-- By : Edwin Rubio, Toshiba International Corp.
-- Revised: Changed Access Level for upsConfigBatteryInstallationDate to R/W
-- : Changed Access Level for upsConfigPassword to R/W
--=============================================================================
-- Update: November 13, 2014
-- By : Edwin Rubio, Toshiba International Corp.
-- Revised: Changed upsOutputCurrentPhaseA units to "RMS Amps"
-- : Changed upsOutputCurrentPhaseB units to "RMS Amps"
-- : Changed upsOutputCurrentPhaseC units to "RMS Amps"
--=============================================================================
-- Update : October 29, 2014
-- By : Edwin Rubio, Toshiba International Corp.
-- Revised: Changed upsInputCurrentPhaseA units to "0.1 RMS Amps"
-- : Changed upsInputCurrentPhaseB units to "0.1 RMS Amps"
-- : Changed upsInputCurrentPhaseC units to "0.1 RMS Amps"
-- : Changed upsOutputCurrentPhaseA units to "0.1 RMS Amps"
-- : Changed upsOutputCurrentPhaseB units to "0.1 RMS Amps"
-- : Changed upsOutputCurrentPhaseC units to "0.1 RMS Amps"
--=============================================================================
-- Update : June 18, 2014
-- By : Edwin Rubio, Toshiba International Corp.
-- Revised: Changed upsInputCurrentPhaseA units to "RMS Amps"
-- : Changed upsInputCurrentPhaseB units to "RMS Amps"
-- : Changed upsInputCurrentPhaseC units to "RMS Amps"
-- : Changed upsOutputCurrentPhaseA units to "RMS Amps"
-- : Changed upsOutputCurrentPhaseB units to "RMS Amps"
-- : Changed upsOutputCurrentPhaseC units to "RMS Amps"
--=============================================================================
-- Update : January 13, 2014
-- By : Edwin Rubio, Toshiba International Corp.
-- Revised:
-- : upsBattery 14: upsBatteryInstalledDate SYNTAX DisplayString from size 8 to 10
-- : upsIdent 4: upsIdentName changed to upsIdentSysName
-- : upsInput 1: upsInputNumLines changed to upsInputNumOfPhases
-- : upsInput 5: upsInputLLVoltagePercentAB added to MIB
-- : upsInput 6: upsInputLLVoltagePercentBC added to MIB
-- : upsInput 7: upsInputLLVoltagePercentCA added to MIB
-- : upsInput 16: upsInputRatedLLVoltage added to MIB
-- : upsOutput 2: upsOutputNumLines changed to upsOutputNumOfPhases
-- : upsOutput 6: upsOutputPhaseCurrentA changed to upsOutputCurrentPhaseA
-- : upsOutput 7: upsOutputPhaseCurrentB changed to upsOutputCurrentPhaseB
-- : upsOutput 8: upsOutputPhaseCurrentC changed to upsOutputCurrentPhaseC
-- : upsOutput 13: upsOutputActivePower changed to upsOutputTotalAcitvePower
-- : upsOutput 14: upsOutputActivePowerPercent changed to upsOutputTotalActivePowerPercent
-- : upsOutput 16: upsOutputRatedActivePower added to MIB
-- : upsOutput 17: upsOutputApparentPower changed to upsOutputRatedApparentPower
-- : upsOutput 18: upsOutputRatedLLVoltage added to MIB
-- : upsBypass 1: upsBypassNumLines changed to upsBypassNumOfPhases
-- : upsBattery 2: upsSecondsOnBattery changed to upsElapsedTimeOnBatteryPower
-- : upsBattery 3: upsEstimatedMinutesRemaining changed to upsEstimatedBatteryRuntime
-- : upsBattery 6: upsBatteryEstimatedChargeRemaining changed to upsBatteryEstimatedCharge
-- : upsBattery 10: upsBatteryInSeries added to MIB
-- : upsBattery 11: upsBatteryNumStrings added to MIB
-- : upsBattery 12: upsBatteryRatedAmpereHour added to MIB
-- : upsBattery 14: upsBatteryInstalledDate changed to upsBatteryInstallationDate
-- : upsWellKnownAlarms 1/upsTrap 1 & 2: upsAlarmFaultStatus changed to upsAlarmFault
-- : upsWellKnownAlarms 3/upsTrap 5 & 6: upsAlarmLowBattery changed to upsAlarmBatteryLow
-- : upsWellKnownAlarms 4/upsTrap 7 7 & 8: upsAlarmDepletedBattery changed to upsAlarmBatteryDepleted
-- : upsAlarmInputVoltageAbnormal removed from MIB
-- : upsAlarmOutputBad removed from MIB
-- : upsWellKnownAlarms 8/upsTrap 15 & 16: upsAlarmPowerFailure added to MIB
-- : upsWellKnownAlarms 11/upsTrap 21 & 22: upsAlarmUpsOutputOff changed to upsAlarmOutputOff
-- : upsAlarmRE4UPSCommError removed from MIB
-- : upsAlarmInverterSynchronous removed from MIB
-- : upsWellKnownAlarms 12/upsTrap 23 & 24: upsAlarmAsyncOperation added to MIB
-- : upsWellKnownAlarms 13/upsTrap 25 & 26: upsAlarmDCOverCurrent changed to upsAlarmDCBusOverCurrent
-- : upsWellKnownAlarms 14/upsTrap 27 & 28: upsAlarmDCOverVoltage changed to upsAlarmDCBusOverVoltage
-- : upsWellKnownAlarms 15/upsTrap 29 & 30: upsAlarmDCUnderVoltage changed to upsAlarmDCBusUnderVoltage
-- : upsWellKnownAlarms 16/upsTrap 31 & 32: upsAlarmDCUnbalanced changed to upsAlarmDCBusImbalance
-- : upsWellKnownAlarms 20/upsTrap 39 & 40: upsAlarmOutputOverCurrent changed to upsAlarmInverterOvercurrent
-- : upsWellKnownAlarms 21/upsTrap 41 & 42: upsAlarmRemotEyeCommError added to MIB
-- : upsConfig 2: upsConfigUPSSoftwareVersion changed to upsConfigUPSFirmwareVersion
-- : upsConfig 3: upsConfigInputNumLines changed to upsConfigInputNumOfPhases
-- : upsConfig 4: upsConfigInputFreq changed to upsConfigRatedInputFrequency
-- : upsConfig 5: upsConfigInputVoltage changed to upsConfigRatedInputLLVoltage
-- : upsConfig 6: upsConfigInputPF changed to upsConfigRatedInputPowerFactor
-- : upsConfig 7: upsConfigOutputNumLines changed to upsConfigOutputNumOfPhases
-- : upsConfig 8: upsConfigOutputFreq changed to upsConfigRatedOutputFrequency
-- : upsConfig 9: upsConfigOutputVoltage changed to upsConfigRatedOutputLLVoltage
-- : upsConfig 10: upsConfigOutputVA changed to upsConfigRatedOutputApperentPower
-- : upsConfig 11: upsConfigOutputActivePower changed to upsConfigRatedOuputActivePower
-- : upsConfig 12: upsConfigOutputPF changed to upsConfigRatedOutputPowerFactor
-- : upsConfig 13: upsConfigBypassNumOfPhases added to MIB
-- : upsConfig 16: upsConfigNumBattSeries changed to upsConfigBatteryInSeries
-- : upsConfig 17: upsConfigNumBattStrings changed to upsConfigBatterNumStrings
-- : upsConfig 18: upsConfig1BattVoltage changed to upsConfigRatedBatteryVoltage
-- : upsConfig 19: upsConfigBatteryRatedAmpereHour changed to upsConfigRatedBatteryAmpereHour
-- : upsConfig 20: upsConfigBattModel changed to upsConfigBatteryModel
-- : upsConfig 21: upsConfigBattRatedHoldingTime changed to upsConfigBatteryRatedBackupTime
-- : upsConfig 22: upsConfigBatteryInstalledDate changed to upsConfigBatteryInstallationDate
-- : upsConfig 23: upsConfigSysName added to MIB
-- : upsConfig 24: upsConfigAttachedDevices added to MIB
-- : upsConfig 25: upsConfigPassword added to MIB
-- : upsTrap 1 & 2: upsTrapFaultStatus changed to upsTrapFault
-- : upsTrap 5 & 6: upsTrapBatteryLowVoltage changed to upsTrapBatteryLow
-- : upsTrap 7 & 8: upsTrapDepletedBattery changed to upsTrapBatteryDepleted
-- : upsTrap 15 & 16: upsTrapPowerFailure added to MIB
-- : upsTrap 19 & 20: upsTrapOnBypass added to MIB
-- : upsTrap 21 & 22: upsTrapUpsOutputOff changed to upsTrapOutputOff
-- : upsTrapInverterSynchronous removed from MIB
-- : upsTrap 23 & 24: upsTrapAsyncOperation added to MIB
-- : upsTrap 25 & 26: upsTrapDCOvercurrent changed to upsTrapsDCBusOverCurrent
-- : upsTrap 27 & 28: upsTrapDCOvervoltage changed to upsTrapDCBusOverVoltage
-- : upsTrap 29 & 30: upsTrapDCUndervoltage changed to upsTrapDCBusUnderVoltage
-- : upsTrap 31 & 32: upsTrapDCUnbalance changed to upsTrapDCBusImbalance
-- : upsTrap 33 & 34: upsTrapOutputUndervoltage changed to upsTrapOutputUnderVoltage
-- : upsTrap 35 & 36: upsTrapOutputOvervoltage changed to upsTrapOutputOverVoltage
-- : upsTrap 41 & 42: upsTrapRemotEyeCommError added to MIB
-- : upsTrapOutputBad removed from MIB
-- : upsTrapBypassSourceSupply removed from MIB
-- : upsTrapInputVoltageAbnormal removed from MIB
--=============================================================================
-- Update : December 22, 2013
-- By : Tiffany Tye, Toshiba International Corp.
-- Revised:upsOutputCurrentPercentA, B & C syntax change from nonnegativeinteger to Integer (1..200)
-- : upsBatteryInstalledDate SYNTAX DisplayString from size 8 to 10
-- : Remove EMD Alarm and Traps
-- : upsConfigBatteryInstalledDate SYNTAX DisplayString from size 8 to 10 upsConfigBatteryInstalledDate Add unit
-- : Remove TrapRE4UPSComm & TrapLoginError
-- : Change upsBatteryRatedHoldingTime to upsBatteryRatedBackupTime
--=============================================================================
-- Update: July 30, 2013
-- By : Edwin Rubio, Toshiba International Corp.
-- For : G9000 First Draft MIB for RemotEye 4
--==============================================================================
IMPORTS
DisplayString, TimeStamp, TimeInterval, TestAndIncr, AutonomousType
FROM SNMPv2-TC
enterprises
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
TRAP-TYPE
FROM RFC-1215;
PositiveInteger ::= INTEGER (0..2147483647)
NonNegativeInteger ::= INTEGER (0..2147483647)
toshiba OBJECT IDENTIFIER ::= { enterprises 186 }
equ OBJECT IDENTIFIER ::= { toshiba 1 }
equUPS OBJECT IDENTIFIER ::= { equ 19 }
ticUPS OBJECT IDENTIFIER ::= { equUPS 2 }
rmti4 OBJECT IDENTIFIER ::= { ticUPS 5 }
upsG9000-G2020 OBJECT IDENTIFIER ::= { rmti4 1 }
upsIdent OBJECT IDENTIFIER ::= { upsG9000-G2020 1 }
upsInput OBJECT IDENTIFIER ::= { upsG9000-G2020 2 }
upsOutput OBJECT IDENTIFIER ::= { upsG9000-G2020 3 }
upsBypass OBJECT IDENTIFIER ::= { upsG9000-G2020 4 }
upsBattery OBJECT IDENTIFIER ::= { upsG9000-G2020 5 }
upsAlarm OBJECT IDENTIFIER ::= { upsG9000-G2020 6 }
upsConfig OBJECT IDENTIFIER ::= { upsG9000-G2020 7 }
upsTime OBJECT IDENTIFIER ::= { upsG9000-G2020 8 }
upsTrap OBJECT IDENTIFIER ::= { upsG9000-G2020 9 }
-- ===========================================================================
-- upsIdentification Group 1
-- Device Identification group
-- All objects in this group are set at device initialization and remain static.
--===========================================================================
upsIdentManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The name of the UPS manufacturer."
::= { upsIdent 1 }
upsIdentTypeform OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..127))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The UPS Model designation."
::= { upsIdent 2 }
upsIdentUPSFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The UPS firmware version."
::= { upsIdent 3 }
upsIdentSysName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A string identifying the UPS. This object is
set by the administrator."
::= { upsIdent 4 }
upsIdentAttachedDevices OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..63))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A string identifying the devices attached to the
output(s) of the UPS. This object is set by
the administrator."
::= { upsIdent 5 }
--===========================================================================
-- upsInput Group 2
--
-- Input group.
-- ===========================================================================
upsInputNumOfPhases OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of input lines. This data is used by upsInputNumLines."
::= { upsInput 1 }
upsInputLLVoltageAB OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The input line to line voltage for AB in RMS volts."
::= { upsInput 2 }
upsInputLLVoltageBC OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The input line to line voltage for BC in RMS volts."
::= { upsInput 3 }
upsInputLLVoltageCA OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The input line to line voltage for CA in RMS volts."
::= { upsInput 4 }
upsInputLLVoltagePercentAB OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Percentage"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The input line to line voltage percent for AB."
::= { upsInput 5 }
upsInputLLVoltagePercentBC OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Percentage"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The input line to line voltage percent for BC."
::= { upsInput 6 }
upsInputLLVoltagePercentCA OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Percentage"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The input line to line voltage percent for CA."
::= { upsInput 7 }
upsInputCurrentPhaseA OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 RMS Amps"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The input phase current for Phase A."
::= { upsInput 8 }
upsInputCurrentPhaseB OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 RMS Amps"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The input phase current unit for Phase B."
::= { upsInput 9 }
upsInputCurrentPhaseC OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 RMS Amps"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The input phase current unit for Phase C."
::= { upsInput 10 }
upsInputFrequency OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Hertz"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The input frequency unit 0.1 Hertz."
::= { upsInput 11 }
upsInputActivePowerA OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Watts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The magnitude of the present input true power for phase A."
::= { upsInput 12 }
upsInputActivePowerB OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Watts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The magnitude of the present input true power for phase B."
::= { upsInput 13 }
upsInputActivePowerC OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Watts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The magnitude of the present input true power for phase C."
::= { upsInput 14 }
upsInputTotalActivePower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Watts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The magnitude of the total input true power."
::= { upsInput 15 }
upsInputRatedLLVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The input line to line rated voltage in RMS volts."
::= { upsInput 16 }
-- ===========================================================================
-- upsOutput Group 3
--
-- Output group
-- ===========================================================================
upsOutputSource OBJECT-TYPE
SYNTAX INTEGER {
other(1),
none(2),
normal(3),
bypass(4),
battery(5)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker."
::= { upsOutput 1 }
upsOutputNumOfPhases OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of output lines utilized in this device."
::= { upsOutput 2 }
upsOutputLLVoltageAB OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output line to line voltage for AB in RMS volts."
::= { upsOutput 3 }
upsOutputLLVoltageBC OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output line to line voltage for BC in RMS volts."
::= { upsOutput 4 }
upsOutputLLVoltageCA OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output line to line voltage for CA in RMS volts."
::= { upsOutput 5 }
upsOutputCurrentPhaseA OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Amps"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Output phase current for phase A in amps."
::= { upsOutput 6 }
upsOutputCurrentPhaseB OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Amps"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Output phase current for phase B in amps."
::= { upsOutput 7 }
upsOutputCurrentPhaseC OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Amps"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Output phase current for phase C in amps."
::= { upsOutput 8 }
upsOutputFrequency OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Hertz"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Output Frequency for phase A in 1/10 of HZ."
::= { upsOutput 9 }
upsOutputCurrentPercentA OBJECT-TYPE
SYNTAX INTEGER
UNITS "PERCENT"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output current for phase A in percent."
::= { upsOutput 10 }
upsOutputCurrentPercentB OBJECT-TYPE
SYNTAX INTEGER
UNITS "PERCENT"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output current for phase B in percent."
::= { upsOutput 11 }
upsOutputCurrentPercentC OBJECT-TYPE
SYNTAX INTEGER
UNITS "PERCENT"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output current for phase C in percent."
::= { upsOutput 12 }
upsOutputTotalActivePower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "kWatts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output active power."
::= { upsOutput 13 }
upsOutputTotalActivePowerPercent OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "percentage"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output active power in percent."
::= { upsOutput 14 }
upsOutputPowerFactor OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.01"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The UPS output power factor."
::= { upsOutput 15 }
upsOutputRatedActivePower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Watts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output rated active power for the UPS."
::= { upsOutput 16 }
upsOutputRatedApparentPower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "VA"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output rated apparent power for the UPS."
::= { upsOutput 17 }
upsOutputRatedLLVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output rated line to line voltage for the UPS."
::= { upsOutput 18 }
-- ===========================================================================
-- upsBypass Group 4
-- ===========================================================================
upsBypassNumOfPhases OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of bypass lines utilized."
::= { upsBypass 1 }
upsBypassLLVoltageAB OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Bypass line to line voltage for AB in RMS volts."
::= { upsBypass 2 }
upsBypassLLVoltageBC OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Bypass line to line voltage for BC in RMS volts."
::= { upsBypass 3 }
upsBypassLLVoltageCA OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Bypass line to line voltage for CA in RMS volts."
::= { upsBypass 4 }
upsBypassFrequency OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Hertz"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The Bypass frequency in 0.1 Hertz."
::= { upsBypass 5 }
--===========================================================================
-- upsBattery Group 5
--
-- The Battery group.
-- ===========================================================================
upsBatteryStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
batteryNormal(2),
batteryLow(3),
batteryDepleted(4),
batteryDischarging(5),
batteryFailure(6)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run time sufficient to handle the load. A value of batteryLow indicates the battery level is low. Continued operation in battery mode will deplate batteries. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output). A value of batteryDischarging indicates UPS system is in Battery power. "
::= { upsBattery 1 }
upsElapsedTimeOnBatteryPower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "seconds"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"If the unit is on battery power, the elapsed time
since the UPS on battery power, or the
time since the network management subsystem was last
restarted, whichever is less. Zero shall be returned
if the unit is not on battery power."
::= { upsBattery 2 }
upsEstimatedBatteryRuntime OBJECT-TYPE
SYNTAX PositiveInteger
UNITS "minutes"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An estimate of the time to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off."
::= { upsBattery 3 }
upsBatteryVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Volt DC"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The battery voltage DC."
::= { upsBattery 4 }
upsBatteryVoltagePercent OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "percentage"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Battery voltage in percent."
::= { upsBattery 5 }
upsBatteryEstimatedCharge OBJECT-TYPE
SYNTAX INTEGER(0..100)
UNITS "percentage"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An estimate of the charge to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off."
::= { upsBattery 6 }
upsBatteryDischargeCurrent OBJECT-TYPE
SYNTAX Integer32
UNITS "percentage"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The present battery discharge Current in percent."
::= { upsBattery 7 }
upsBatteryChargeCurrent OBJECT-TYPE
SYNTAX Integer32
UNITS "percentage"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The present battery charge Current in percent."
::= { upsBattery 8 }
upsBatteryModel OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Battery manufacturer."
::= { upsBattery 9 }
upsBatteryInSeries OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Battery rated holding time in minutes."
::= { upsBattery 10 }
upsBatteryNumStrings OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Battery rated holding time in minutes."
::= { upsBattery 11 }
upsBatteryRatedAmpereHour OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Ampere Hour"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Battery rated holding time in minutes."
::= { upsBattery 12 }
upsBatteryRatedBackupTime OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..8))
UNITS "minutes"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The Battery rated holding time in minutes."
::= { upsBattery 13 }
upsBatteryInstallationDate OBJECT-TYPE
SYNTAX DisplayString (SIZE(10))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The battery install date."
::= { upsBattery 14 }
-- ===========================================================================
-- upsAlarm Group 6
-- ===========================================================================
upsAlarmsPresent OBJECT-TYPE
SYNTAX Gauge32
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The present number of active alarm conditions."
::= { upsAlarm 1 }
upsAlarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsAlarmEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains. The agent creates the first row with
upsAlarmId equal to 1, and increments the value of
upsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of upsAlarmId would otherwise be
exceeded. Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
upsAlarmId might have wrapped.
Alarms are named by an OBJECT IDENTIFIER,
upsAlarmDescr, to allow a single table to
reflect well known alarms plus alarms defined by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device. No
two rows will have the same value of upsAlarmDescr,
since alarms define conditions. In order to meet this
requirement, care should be taken in the definition of
alarm conditions to insure that a system cannot enter
the same condition multiple times simultaneously.
The number of rows in the table at any given time is
reflected by the value of upsAlarmsPresent."
::= { upsAlarm 2 }
upsAlarmEntry OBJECT-TYPE
SYNTAX UpsAlarmEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"An entry containing information applicable to a
particular alarm."
INDEX { upsAlarmId }
::= { upsAlarmTable 1 }
UpsAlarmEntry ::=
SEQUENCE {
upsAlarmId PositiveInteger,
upsAlarmDescr AutonomousType,
upsAlarmTime TimeStamp
}
-- ===========================================================================
-- upsAlarmTable/upsAlarmEntry/upsAlarmId
-- ===========================================================================
upsAlarmId OBJECT-TYPE
SYNTAX PositiveInteger
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A unique identifier for an alarm condition. This
value must remain constant."
::= { upsAlarmEntry 1 }
upsAlarmDescr OBJECT-TYPE
SYNTAX AutonomousType
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A reference to an alarm description object. The
object referenced should not be accessible, but rather
be used to provide a unique description of the alarm
condition."
::= { upsAlarmEntry 2 }
-- ===========================================================================
-- .../upsAlarmTime
-- ===========================================================================
upsAlarmTime OBJECT-TYPE
SYNTAX TimeStamp
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of sysUpTime when the alarm condition was
detected. If the alarm condition was detected at the
time of agent startup and presumably existed before
agent startup, the value of upsAlarmTime shall equal 0."
::= { upsAlarmEntry 3 }
upsWellKnownAlarms OBJECT IDENTIFIER ::= { upsAlarm 3 }
upsAlarmFault OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fault: A UPS fault/Alarm condition exists."
::= { upsWellKnownAlarms 1 }
upsAlarmOnBattery OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Info: The UPS is on Battery mode; it is supplying output power from its batteries."
::= { upsWellKnownAlarms 2 }
upsAlarmBatteryLow OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Warning: The battery level is low. It has dropped to less than 90% of its nominal value. Continued operation in Battery Mode will deplete Batteries and result in UPS output shut down. Reduce critical load to increase battery runtime."
::= { upsWellKnownAlarms 3 }
upsAlarmBatteryDepleted OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Warning: UPS contains depleted batteries, it will be unable to support critical loads. Shut down excess equipment to reduce Load."
::= { upsWellKnownAlarms 4 }
upsAlarmBatteryOverheat OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fault: Detection of over temperature at the batteries."
::= { upsWellKnownAlarms 5 }
upsAlarmBatteryVoltageAbnormal OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fault: Battery voltage is abnormality."
::= { upsWellKnownAlarms 6 }
upsAlarmUPSOverheat OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fault: The UPS is overheating (warning is given when the internal temperature reaches and exceeds 50?C rise @ 40?C ambient). Check to see if the ambient temperature is abnormally high (40?C or more). If so, turn on air conditioning. Also, check ventilation fan at the back of the UPS for operation or obstructions. Otherwise, shut down the UPS and contact your Toshiba authorized service center."
::= { upsWellKnownAlarms 7 }
upsAlarmPowerFailure OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Info: Power Failure."
::= { upsWellKnownAlarms 8 }
upsAlarmUPSOverload OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fault: The UPS is overloaded. UPS will switch to bypass operation or shut down if no action is taken. Shut down excess equipment to reduce Load."
::= { upsWellKnownAlarms 9 }
upsAlarmUserDefinedOverloadWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Warning: The inverter output load % is greater than the user defined overload set point (default: 110%)."
::= { upsWellKnownAlarms 10 }
upsAlarmOnBypass OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Warning: The UPS is in Stop (Bypass) mode."
::= { upsWellKnownAlarms 11 }
upsAlarmOutputOff OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Info: The UPS output is off."
::= { upsWellKnownAlarms 12 }
upsAlarmAsyncOperation OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Warning: Async Operation"
::= { upsWellKnownAlarms 13 }
upsAlarmDCBusOverCurrent OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fault: UPS is reporting a DC bus overcurrent condition. Contact your Toshiba authorized service center for examination of a DCOC fault."
::= { upsWellKnownAlarms 14 }
upsAlarmDCBusOverVoltage OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fault: UPS is reporting a DC bus overvoltage condition. Contact your Toshiba authorized service center for examination of a DCOV fault."
::= { upsWellKnownAlarms 15 }
upsAlarmDCBusUnderVoltage OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fault: UPS is reporting a DC bus undervoltage condition. Contact your
Toshiba authorized service center for examination of a DCUV fault."
::= { upsWellKnownAlarms 16 }
upsAlarmDCBusImbalanced OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fault: The DC imbalanced alarm detection."
::= { upsWellKnownAlarms 17 }
upsAlarmOutputUnderVoltage OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fault: UPS is reporting an output undervoltage condition. Contact your Toshiba authorized service center for examination of a INVUV fault."
::= { upsWellKnownAlarms 18 }
upsAlarmOutputOverVoltage OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fault: UPS is reporting an output overvoltage condition. Contact your
Toshiba authorized service center for examination of a INVOV fault."
::= { upsWellKnownAlarms 19 }
upsAlarmInverterOverload OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fault: Short time over-current has been detected."
::= { upsWellKnownAlarms 20 }
upsAlarmInverterOvercurrent OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fault: Detection of inverter overcurrent."
::= { upsWellKnownAlarms 21 }
upsAlarmRemotEyeCommError OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Warning: Communication error between the RemotEye 4 and the UPS."
::= { upsWellKnownAlarms 22 }
-- ===========================================================================
-- upsConfig Group 7
-- Config data
-- 1) All 'upsConfig' data is to be stored in NV-RAM inside the agent device.
-- 2) All 'upsConfig' data is to be checked at each agent startup
-- 3) If initial values present at startup, replace with default values
-- unless specified otherwise.
-- ===========================================================================
upsConfigModelIDString OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"UPS Model ID string. This string contains codes for the UPS series,input voltage, output voltage, output VA, and addition option."
::= { upsConfig 1 }
upsConfigUPSFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The G9000 software version."
::= { upsConfig 2 }
upsConfigInputNumOfPhases OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of input lines. This data is used by upsInputNumLines."
::= { upsConfig 3 }
upsConfigRatedInputFrequency OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Hertz"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The nominal input frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the request must be rejected and the agent
shall respond with an appropriate error message, i.e.,
badValue for SNMPv1, or inconsistentValue for SNMPv2."
::= { upsConfig 4 }
upsConfigRatedInputLLVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The magnitude of the nominal input voltage. On those
systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not supported, the request must be
rejected and the agent shall respond with an
appropriate error message, i.e., badValue for SNMPv1,
or inconsistentValue for SNMPv2."
::= { upsConfig 5 }
upsConfigRatedInputPowerFactor OBJECT-TYPE
SYNTAX PositiveInteger
UNITS "0.01"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"UNITS are in hundredths. For 0.95 = 95."
::= { upsConfig 6 }
upsConfigOutputNumOfPhases OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Number of output lines. This data is used by upsOutputNumLines."
::= { upsConfig 7 }
upsConfigRatedOutputFrequency OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.1 Hertz"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The nominal output frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the request must be rejected and the agent
shall respond with an appropriate error message, i.e.,
bad Value for SNMPv1, or inconsistent Value for SNMPv2."
::= { upsConfig 8 }
upsConfigRatedOutputLLVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "RMS Volts"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The magnitude of the nominal output voltage. On
those systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not supported, the request must be
rejected and the agent shall respond with an
appropriate error message, i.e., bad Value for SNMPv1,
or inconsistent Value for SNMPv2."
::= { upsConfig 9 }
upsConfigRatedOutputApperentPower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Volt-Amps"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The magnitude of the nominal Volt-Amp rating."
::= { upsConfig 10 }
upsConfigRatedOutputActivePower OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "KWatts"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The magnitude of the nominal true power rating."
::= { upsConfig 11 }
upsConfigRatedOutputPowerFactor OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "0.01"
ACCESS read-only
STATUS mandatory
DESCRIPTION
"UNITS are in hundredths. For 0.70 = 70."
::= { upsConfig 12 }
upsConfigBypassNumOfPhases OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of bypass lines utilized."
::= { upsConfig 13 }
upsConfigLowVoltageTransferPoint OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "percentage"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The minimum input line voltage allowed before the UPS
system transfers to battery backup."
::= { upsConfig 14 }
upsConfigHighVoltageTransferPoint OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "percentage"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The maximum line voltage allowed before the UPS
system transfers to battery backup."
::= { upsConfig 15 }
upsConfigBatteryInSeries OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The number of batteries in each string connected in series."
::= { upsConfig 16 }
upsConfigBatteryNumStrings OBJECT-TYPE
SYNTAX NonNegativeInteger
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The number of parallel battery strings."
::= { upsConfig 17 }
upsConfigRatedBatteryVoltage OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "Volts DC"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Rated voltage of a single battery."
::= { upsConfig 18 }
upsConfigRatedBatteryAmpereHour OBJECT-TYPE
SYNTAX INTEGER
UNITS "Ahr"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The rated battery in ampere hour."
::= { upsConfig 19 }
upsConfigBatteryModel OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The manufacturer of the battery."
::= { upsConfig 20 }
upsConfigBatteryRatedBackupTime OBJECT-TYPE
SYNTAX NonNegativeInteger
UNITS "minutes"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The rated duration batteries can hold when unit is in backup mode with full load."
::= { upsConfig 21 }
upsConfigUserDefinedOverloadSetPoint OBJECT-TYPE
SYNTAX INTEGER
UNITS "%"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The maximum output load % defined by the user."
::= { upsConfig 22 }
upsConfigBatteryInstallationDate OBJECT-TYPE
SYNTAX DisplayString (SIZE(10))
UNITS "mm/dd/yyyy"
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The battery install date."
::= { upsConfig 23 }
upsConfigSysName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A string identifying the UPS. This object is
set by the administrator."
::= { upsConfig 24 }
upsConfigAttachedDevices OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A string identifying the devices attached to the
output(s) of the UPS. This object is set by
the administrator."
::= { upsConfig 25 }
upsConfigPassword OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Password."
::= { upsConfig 26 }
-- ===========================================================================
-- upsTime Group 8
--
-- Time group
-- ===========================================================================
upsTimeRealDate OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Present date: year-month-date-day of the week."
::= { upsTime 1 }
upsTimeRealTime OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Present time (military format): hour-minute-second. For example,2:00pm would be 14:00:00."
::= { upsTime 2 }
--
--=======================================================================
-- upsTraps Group 9
--
-- Traps group
--
--=======================================================================
upsTrapFault TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Alarm: One or more fault/status alarm(s) reported."
::= 1
upsTrapFaultClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Alarm Clear: One or more fault/status reported."
::= 2
upsTrapOnBattery TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Info: The UPS is on Battery Mode."
::= 3
upsTrapOnBatteryClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Info Clear: The UPS is on Battery Mode."
::= 4
upsTrapBatteryLow TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Warning: Battery Low Voltage."
::= 5
upsTrapBatteryLowClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Warning Clear: Battery Low Voltage."
::= 6
upsTrapBatteryDepleted TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Warning: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load."
::= 7
upsTrapBatteryDepletedClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Warning Clear: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load.."
::= 8
upsTrapBatteryOverheat TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault: Battery Overheat."
::= 9
upsTrapBatteryOverheatClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault Clear: Battery Overheat."
::= 10
upsTrapBatteryVoltageAbnormal TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault: Battery Voltage Abnormal. Contact your Toshiba authorized service center for examination."
::= 11
upsTrapBatteryVoltageAbnormalClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault Clear: Battery Voltage Abnormal. Contact your Toshiba authorized service center for examination."
::= 12
upsTrapUPSOverheat TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination."
::= 13
upsTrapUPSOverheatClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault Clear: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination."
::= 14
upsTrapPowerFailure TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Info: Power Failure."
::= 15
upsTrapPowerFailureClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Info Clear: PowerFailure."
::= 16
upsTrapUPSOverload TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault: UPS Overload (OL), the output load exceeds the rated current. Decrease load."
::= 17
upsTrapUPSOverloadClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault Clear: UPS Overload (OL), the output load exceeds the rated current. Decrease load."
::= 18
upsTrapUserDefinedOverloadWarning TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Warning: The inverter output load % is greater than the user defined overload set point (default: 110%)."
::= 19
upsTrapUserDefinedOverloadWarningClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Warning Clear: The inverter output load % is greater than the user defined overload set point (default: 110%)."
::= 20
upsTrapOnBypass TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Warning:On Bypass."
::= 21
upsTrapOnBypassClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Warning Clear: On Bypass."
::= 22
upsTrapOutputOff TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Info: The UPS output is off."
::= 23
upsTrapOutputOffClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Info Clear: The UPS output is off."
::= 24
upsTrapAsyncOperation TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Warning: Inverter Synchronous."
::= 25
upsTrapAsyncOperationClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Warning Clear: Inverter Synchronous."
::= 26
upsTrapDCBusOverCurrent TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination."
::= 27
upsTrapDCBusOverCurrentClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault Clear: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination."
::= 28
upsTrapDCBusOverVoltage TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination."
::= 29
upsTrapDCBusOverVoltageClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault Clear: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination."
::= 30
upsTrapDCBusUnderVoltage TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination."
::= 31
upsTrapDCBusUnderVoltageClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault Clear: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination."
::= 32
upsTrapDCBusImbalance TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault: DC Unbalance. Contact your Toshiba authorized service center for examination."
::= 33
upsTrapDCBusImbalanceClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault Clear: DC Unbalance. Contact your Toshiba authorized service center for examination."
::= 34
upsTrapOutputUnderVoltage TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault: Output Undervoltage. Contact your Toshiba authorized service center for examination."
::= 35
upsTrapOutputUnderVoltageClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault Clear: Output Undervoltage. Contact your Toshiba authorized service center for examination."
::= 36
upsTrapOutputOverVoltage TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination."
::= 37
upsTrapOutputOverVoltageClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault Clear: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination."
::= 38
upsTrapInverterOverload TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load."
::= 39
upsTrapInverterOverloadClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault Clear: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load."
::= 40
upsTrapInverterOvercurrent TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault: Inverter Overcurrent. Contact your Toshiba authorized service center for examination."
::= 41
upsTrapInverterOvercurrentClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Fault Clear: Inverter Overcurrent. Contact your Toshiba authorized service center for examination."
::= 42
upsTrapRemotEyeCommError TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Warning: RemotEye UPS communication error."
::= 43
upsTrapRemotEyeCommErrorClear TRAP-TYPE
ENTERPRISE upsG9000-G2020
DESCRIPTION
"Warning Clear:RemotEye UPS communication error."
::= 44
END