--defines ROOMALERT11E-MIB for SNMP agent extension of Room Alert 11E
|
||||
--Contents: Global Registration Module
|
||||
-- Room Alert OIDs - Enterprise 20916
|
||||
--Version: 1.1.3
|
||||
--Date: 9 January 2014
|
||||
--Developed By: AVTECH Software, Inc.
|
||||
|
||||
--
|
||||
--Copyright (c) 2014 AVTECH Software, Inc.
|
||||
--
|
||||
|
||||
ROOMALERT11E-MIB DEFINITIONS ::= BEGIN
|
||||
|
||||
|
||||
IMPORTS
|
||||
enterprises, IpAddress, Counter, TimeTicks
|
||||
FROM RFC1155-SMI
|
||||
OBJECT-TYPE
|
||||
FROM RFC-1212
|
||||
TRAP-TYPE
|
||||
FROM RFC-1215;
|
||||
|
||||
|
||||
avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
|
||||
products OBJECT IDENTIFIER ::= { avtech 1 }
|
||||
roomalert11E OBJECT IDENTIFIER ::= { products 3 }
|
||||
sensors OBJECT IDENTIFIER ::= { roomalert11E 1 }
|
||||
traps OBJECT IDENTIFIER ::= { roomalert11E 2 }
|
||||
thresholds OBJECT IDENTIFIER ::= { roomalert11E 3 }
|
||||
channel1 OBJECT IDENTIFIER ::= { sensors 1 }
|
||||
channel2 OBJECT IDENTIFIER ::= { sensors 2 }
|
||||
channel3 OBJECT IDENTIFIER ::= { sensors 3 }
|
||||
channel4 OBJECT IDENTIFIER ::= { sensors 4 }
|
||||
channels OBJECT IDENTIFIER ::= { thresholds 1 }
|
||||
channels1 OBJECT IDENTIFIER ::= { channels 1 }
|
||||
channels2 OBJECT IDENTIFIER ::= { channels 2 }
|
||||
channels3 OBJECT IDENTIFIER ::= { channels 3 }
|
||||
channels4 OBJECT IDENTIFIER ::= { channels 4 }
|
||||
|
||||
-- Room Alert 11E MIB
|
||||
-- Parameters
|
||||
|
||||
sensor1-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for internal switch sensor 1 (0 = OPEN, 1 = CLOSED)."
|
||||
::= { channel1 1 }
|
||||
|
||||
sensor1-2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for internal switch sensor 2 (0 = OPEN, 1 = CLOSED)."
|
||||
::= { channel1 2 }
|
||||
|
||||
sensor1-3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for internal switch sensor 3 (0 = OPEN, 1 = CLOSED)."
|
||||
::= { channel1 3 }
|
||||
|
||||
sensor1-4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for internal switch sensor 4 (0 = OPEN, 1 = CLOSED)."
|
||||
::= { channel1 4 }
|
||||
|
||||
sensor1-5 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for internal switch sensor 5 (0 = OPEN, 1 = CLOSED)."
|
||||
::= { channel1 5 }
|
||||
|
||||
sensor1-6 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for internal switch sensor 6 (0 = OPEN, 1 = CLOSED)."
|
||||
::= { channel1 6 }
|
||||
|
||||
sensor1-7 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for internal switch sensor 7 (0 = OPEN, 1 = CLOSED)."
|
||||
::= { channel1 7 }
|
||||
|
||||
sensor1-8 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for internal switch sensor 8 (0 = OPEN, 1 = CLOSED)."
|
||||
::= { channel1 8 }
|
||||
|
||||
switch-label-1 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label for switch sensor 1"
|
||||
::= { channel1 9 }
|
||||
|
||||
switch-label-2 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label for switch sensor 2"
|
||||
::= { channel1 10 }
|
||||
|
||||
switch-label-3 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label for switch sensor 3"
|
||||
::= { channel1 11 }
|
||||
|
||||
switch-label-4 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label for switch sensor 4"
|
||||
::= { channel1 12 }
|
||||
|
||||
switch-label-5 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label for switch sensor 5"
|
||||
::= { channel1 13 }
|
||||
|
||||
switch-label-6 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label for switch sensor 6"
|
||||
::= { channel1 14 }
|
||||
|
||||
switch-label-7 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label for switch sensor 7"
|
||||
::= { channel1 15 }
|
||||
|
||||
switch-label-8 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label for switch sensor 8"
|
||||
::= { channel1 16 }
|
||||
|
||||
sensor2-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 2-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
|
||||
::= { channel2 1 }
|
||||
|
||||
sensor2-2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 2-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
|
||||
::= { channel2 2 }
|
||||
|
||||
sensor2-3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 2-3. If temp/humidity sensor is connected, value will be current %RH."
|
||||
::= { channel2 3 }
|
||||
|
||||
sensor2-4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 2-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
|
||||
::= { channel2 4 }
|
||||
|
||||
sensor2-5 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 2-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
|
||||
::= { channel2 5 }
|
||||
|
||||
sensor2-6-label OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label of this sensor"
|
||||
::= { channel2 6}
|
||||
|
||||
sensor3-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 3-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
|
||||
::= { channel3 1 }
|
||||
|
||||
sensor3-2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 3-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
|
||||
::= { channel3 2 }
|
||||
|
||||
sensor3-3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 3-3. If temp/humidity sensor is connected, value will be current %RH."
|
||||
::= { channel3 3 }
|
||||
|
||||
sensor3-4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 3-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
|
||||
::= { channel3 4 }
|
||||
|
||||
sensor3-5 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 3-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
|
||||
::= { channel3 5 }
|
||||
|
||||
sensor3-6-label OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label of this sensor"
|
||||
::= { channel3 6}
|
||||
|
||||
sensor4-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 4-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
|
||||
::= { channel4 1 }
|
||||
|
||||
sensor4-2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 4-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
|
||||
::= { channel4 2 }
|
||||
|
||||
sensor4-3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 4-3. If temp/humidity sensor is connected, value will be current %RH."
|
||||
::= { channel4 3 }
|
||||
|
||||
sensor4-4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 4-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
|
||||
::= { channel4 4 }
|
||||
|
||||
sensor4-5 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for sensor 4-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
|
||||
::= { channel4 5 }
|
||||
|
||||
sensor4-6-label OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label of this sensor"
|
||||
::= { channel4 6}
|
||||
|
||||
alarm1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..255)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm for sensor channel 1. The binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
|
||||
::= { traps 1 }
|
||||
|
||||
alarm2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..255)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm for sensor channel 2. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
|
||||
::= { traps 2 }
|
||||
|
||||
alarm3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..255)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm for sensor channel 3. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
|
||||
::= { traps 3 }
|
||||
|
||||
alarm4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..255)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm for sensor channel 4. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
|
||||
::= { traps 4 }
|
||||
|
||||
alarmMessage1 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm Message from sensor channel 1 (Internal)"
|
||||
::= { traps 5 }
|
||||
|
||||
alarmMessage2 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm Message from sensor channel 2 (External)"
|
||||
::= { traps 6 }
|
||||
|
||||
alarmMessage3 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm Message from sensor channel 3 (External)"
|
||||
::= { traps 7 }
|
||||
|
||||
alarmMessage4 OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Alarm Message from sensor channel 4 (External)"
|
||||
::= { traps 8 }
|
||||
|
||||
threshold1-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 1 defined for Channel 1"
|
||||
::= { channels1 1 }
|
||||
|
||||
threshold1-2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 2 defined for Channel 1"
|
||||
::= { channels1 2 }
|
||||
|
||||
threshold1-3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 3 defined for Channel 1"
|
||||
::= { channels1 3 }
|
||||
|
||||
threshold1-4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 4 defined for Channel 1"
|
||||
::= { channels1 4 }
|
||||
|
||||
threshold1-5 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 5 defined for Channel 1"
|
||||
::= { channels1 5 }
|
||||
|
||||
threshold1-6 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 6 defined for Channel 1"
|
||||
::= { channels1 6 }
|
||||
|
||||
threshold1-7 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 7 defined for Channel 1"
|
||||
::= { channels1 7 }
|
||||
|
||||
threshold1-8 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 8 defined for Channel 1"
|
||||
::= { channels1 8 }
|
||||
|
||||
threshold2-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 1 defined for Channel 2"
|
||||
::= { channels2 1 }
|
||||
|
||||
threshold2-2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 2 defined for Channel 2"
|
||||
::= { channels2 2 }
|
||||
|
||||
threshold2-3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 3 defined for Channel 2"
|
||||
::= { channels2 3 }
|
||||
|
||||
threshold2-4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 4 defined for Channel 2"
|
||||
::= { channels2 4 }
|
||||
|
||||
threshold3-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 1 defined for Channel 3"
|
||||
::= { channels3 1 }
|
||||
|
||||
threshold3-2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 2 defined for Channel 3"
|
||||
::= { channels3 2 }
|
||||
|
||||
threshold3-3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 3 defined for Channel 3"
|
||||
::= { channels3 3 }
|
||||
|
||||
threshold3-4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 4 defined for Channel 3"
|
||||
::= { channels3 4 }
|
||||
|
||||
threshold4-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 1 defined for Channel 4"
|
||||
::= { channels4 1 }
|
||||
|
||||
threshold4-2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 2 defined for Channel 4"
|
||||
::= { channels4 2 }
|
||||
|
||||
threshold4-3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 3 defined for Channel 4"
|
||||
::= { channels4 3 }
|
||||
|
||||
threshold4-4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Threshold 4 defined for Channel 4"
|
||||
::= { channels4 4 }
|
||||
|
||||
|
||||
-- ROOMALERT11E TRAPS
|
||||
|
||||
tempAlarm1-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage2, sensor2-1, sensor2-2, sensor2-1 }
|
||||
DESCRIPTION "A tempAlarm1 trap signifies that the current
|
||||
temperature on external sensor 1 is outside the
|
||||
defined high or low threshold."
|
||||
::= 1
|
||||
|
||||
room-alert-11E-SNMP-trap TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1,alarmMessage2,alarmMessage3,alarmMessage4 }
|
||||
DESCRIPTION "A Room Alert 11E SNMP Trap indicates that an alarm
|
||||
condition has occurred on the sensor inidcated
|
||||
by the alarmMessage variable."
|
||||
::= 2
|
||||
|
||||
tempAlarm2-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-1 }
|
||||
DESCRIPTION "A tempAlarm2 trap signifies that the current
|
||||
temperature on external sensor 2 is outside the
|
||||
defined high or low threshold."
|
||||
::= 3
|
||||
|
||||
tempClear2-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-1 }
|
||||
DESCRIPTION "A tempClear2 trap signifies that the current
|
||||
temperature on external sensor 2 has returned to
|
||||
a normal condition and is within the defined
|
||||
high or low threshold."
|
||||
::= 4
|
||||
|
||||
tempAlarm3-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-1 }
|
||||
DESCRIPTION "A tempAlarm3 trap signifies that the current
|
||||
temperature on external sensor 3 is outside the
|
||||
defined high or low threshold."
|
||||
::= 5
|
||||
|
||||
tempClear3-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-1 }
|
||||
DESCRIPTION "A tempClear3 trap signifies that the current
|
||||
temperature on external sensor 3 has returned to
|
||||
a normal condition and is within the defined
|
||||
high or low threshold."
|
||||
::= 6
|
||||
|
||||
humidityAlarm1-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage2, sensor2-1, sensor2-2, sensor2-3 }
|
||||
DESCRIPTION "A humidityAlarm1 trap signifies that the current
|
||||
humidity on external sensor 1 is outside the
|
||||
defined high or low threshold."
|
||||
::= 7
|
||||
|
||||
humidityClear1-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage2, sensor2-1, sensor2-2, sensor2-3 }
|
||||
DESCRIPTION "A humidityClear1 trap signifies that the current
|
||||
humidity on external sensor 1 has returned to
|
||||
a normal condition and is within the defined
|
||||
high or low threshold."
|
||||
::= 8
|
||||
|
||||
humidityAlarm2-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-3 }
|
||||
DESCRIPTION "A humidityAlarm2 trap signifies that the current
|
||||
humidity on external sensor 2 is outside the
|
||||
defined high or low threshold."
|
||||
::= 9
|
||||
|
||||
humidityClear2-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-3 }
|
||||
DESCRIPTION "A humidityClear2 trap signifies that the current
|
||||
humidity on external sensor 2 has returned to
|
||||
a normal condition and is within the defined
|
||||
high or low threshold."
|
||||
::= 10
|
||||
|
||||
humidityAlarm3-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-3 }
|
||||
DESCRIPTION "A humidityAlarm3 trap signifies that the current
|
||||
humidity on external sensor 3 is outside the
|
||||
defined high or low threshold."
|
||||
::= 11
|
||||
|
||||
humidityClear3-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-3 }
|
||||
DESCRIPTION "A humidityClear3 trap signifies that the current
|
||||
humidity on external sensor 3 has returned to
|
||||
a normal condition and is within the defined
|
||||
high or low threshold."
|
||||
::= 12
|
||||
|
||||
switchAlarm1-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-1, sensor1-1, sensor1-1 }
|
||||
DESCRIPTION "A switchAlarm1 trap signifies that switch sensor 1
|
||||
is in an alarm state."
|
||||
::= 13
|
||||
|
||||
switchClear1-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-1, sensor1-1, sensor1-1 }
|
||||
DESCRIPTION "A switchClear1 trap signifies that the switch sensor 1
|
||||
has returned to a normal state."
|
||||
::= 14
|
||||
|
||||
switchAlarm2-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-2, sensor1-2, sensor1-2 }
|
||||
DESCRIPTION "A switchAlarm2 trap signifies that switch sensor 2
|
||||
is in an alarm state."
|
||||
::= 15
|
||||
|
||||
switchClear2-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-2, sensor1-2, sensor1-2 }
|
||||
DESCRIPTION "A switchClear2 trap signifies that the switch sensor 2
|
||||
has returned to a normal state."
|
||||
::= 16
|
||||
|
||||
switchAlarm3-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-3, sensor1-3, sensor1-3 }
|
||||
DESCRIPTION "A switchAlarm1 trap signifies that switch sensor 1
|
||||
is in an alarm state."
|
||||
::= 17
|
||||
|
||||
switchClear3-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-3, sensor1-3, sensor1-3 }
|
||||
DESCRIPTION "A switchClear3 trap signifies that the switch sensor 3
|
||||
has returned to a normal state."
|
||||
::= 18
|
||||
|
||||
switchAlarm4-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-4, sensor1-4, sensor1-4 }
|
||||
DESCRIPTION "A switchAlarm4 trap signifies that switch sensor 4
|
||||
is in an alarm state."
|
||||
::= 19
|
||||
|
||||
switchClear4-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-4, sensor1-4, sensor1-4 }
|
||||
DESCRIPTION "A switchClear4 trap signifies that the switch sensor 4
|
||||
has returned to a normal state."
|
||||
::= 20
|
||||
|
||||
switchAlarm5-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-5, sensor1-5, sensor1-5 }
|
||||
DESCRIPTION "A switchAlarm5 trap signifies that switch sensor 5
|
||||
is in an alarm state."
|
||||
::= 21
|
||||
|
||||
switchClear5-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-5, sensor1-5, sensor1-5 }
|
||||
DESCRIPTION "A switchClear5 trap signifies that the switch sensor 5
|
||||
has returned to a normal state."
|
||||
::= 22
|
||||
|
||||
switchAlarm6-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-6, sensor1-6, sensor1-6 }
|
||||
DESCRIPTION "A switchAlarm6 trap signifies that switch sensor 6
|
||||
is in an alarm state."
|
||||
::= 23
|
||||
|
||||
switchClear6-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-6, sensor1-6, sensor1-6 }
|
||||
DESCRIPTION "A switchClear6 trap signifies that the switch sensor 6
|
||||
has returned to a normal state."
|
||||
::= 24
|
||||
|
||||
switchAlarm7-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-7, sensor1-7, sensor1-7 }
|
||||
DESCRIPTION "A switchAlarm7 trap signifies that switch sensor 7
|
||||
is in an alarm state."
|
||||
::= 25
|
||||
|
||||
switchClear7-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-7, sensor1-7, sensor1-7 }
|
||||
DESCRIPTION "A switchClear7 trap signifies that the switch sensor 7
|
||||
has returned to a normal state."
|
||||
::= 26
|
||||
|
||||
switchAlarm8-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-8, sensor1-8, sensor1-8 }
|
||||
DESCRIPTION "A switchAlarm8 trap signifies that switch sensor 8
|
||||
is in an alarm state."
|
||||
::= 27
|
||||
|
||||
switchClear8-11e TRAP-TYPE
|
||||
ENTERPRISE roomalert11E
|
||||
VARIABLES { alarmMessage1, sensor1-8, sensor1-8, sensor1-8 }
|
||||
DESCRIPTION "A switchClear8 trap signifies that the switch sensor 8
|
||||
has returned to a normal state."
|
||||
::= 28
|
||||
END
|