694 lines
21 KiB
Plaintext
694 lines
21 KiB
Plaintext
--
|
|
--defines ROOMALERT11E-MIB for SNMP agent extension of Room Alert 11E
|
|
--Contents: Global Registration Module
|
|
-- Room Alert OIDs - Enterprise 20916
|
|
--Version: 1.1.3
|
|
--Date: 9 January 2014
|
|
--Developed By: AVTECH Software, Inc.
|
|
|
|
--
|
|
--Copyright (c) 2014 AVTECH Software, Inc.
|
|
--
|
|
|
|
ROOMALERT11E-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
IMPORTS
|
|
enterprises, IpAddress, Counter, TimeTicks
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
|
|
avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
|
|
products OBJECT IDENTIFIER ::= { avtech 1 }
|
|
roomalert11E OBJECT IDENTIFIER ::= { products 3 }
|
|
sensors OBJECT IDENTIFIER ::= { roomalert11E 1 }
|
|
traps OBJECT IDENTIFIER ::= { roomalert11E 2 }
|
|
thresholds OBJECT IDENTIFIER ::= { roomalert11E 3 }
|
|
channel1 OBJECT IDENTIFIER ::= { sensors 1 }
|
|
channel2 OBJECT IDENTIFIER ::= { sensors 2 }
|
|
channel3 OBJECT IDENTIFIER ::= { sensors 3 }
|
|
channel4 OBJECT IDENTIFIER ::= { sensors 4 }
|
|
channels OBJECT IDENTIFIER ::= { thresholds 1 }
|
|
channels1 OBJECT IDENTIFIER ::= { channels 1 }
|
|
channels2 OBJECT IDENTIFIER ::= { channels 2 }
|
|
channels3 OBJECT IDENTIFIER ::= { channels 3 }
|
|
channels4 OBJECT IDENTIFIER ::= { channels 4 }
|
|
|
|
-- Room Alert 11E MIB
|
|
-- Parameters
|
|
|
|
sensor1-1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for internal switch sensor 1 (0 = OPEN, 1 = CLOSED)."
|
|
::= { channel1 1 }
|
|
|
|
sensor1-2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for internal switch sensor 2 (0 = OPEN, 1 = CLOSED)."
|
|
::= { channel1 2 }
|
|
|
|
sensor1-3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for internal switch sensor 3 (0 = OPEN, 1 = CLOSED)."
|
|
::= { channel1 3 }
|
|
|
|
sensor1-4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for internal switch sensor 4 (0 = OPEN, 1 = CLOSED)."
|
|
::= { channel1 4 }
|
|
|
|
sensor1-5 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for internal switch sensor 5 (0 = OPEN, 1 = CLOSED)."
|
|
::= { channel1 5 }
|
|
|
|
sensor1-6 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for internal switch sensor 6 (0 = OPEN, 1 = CLOSED)."
|
|
::= { channel1 6 }
|
|
|
|
sensor1-7 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for internal switch sensor 7 (0 = OPEN, 1 = CLOSED)."
|
|
::= { channel1 7 }
|
|
|
|
sensor1-8 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for internal switch sensor 8 (0 = OPEN, 1 = CLOSED)."
|
|
::= { channel1 8 }
|
|
|
|
switch-label-1 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label for switch sensor 1"
|
|
::= { channel1 9 }
|
|
|
|
switch-label-2 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label for switch sensor 2"
|
|
::= { channel1 10 }
|
|
|
|
switch-label-3 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label for switch sensor 3"
|
|
::= { channel1 11 }
|
|
|
|
switch-label-4 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label for switch sensor 4"
|
|
::= { channel1 12 }
|
|
|
|
switch-label-5 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label for switch sensor 5"
|
|
::= { channel1 13 }
|
|
|
|
switch-label-6 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label for switch sensor 6"
|
|
::= { channel1 14 }
|
|
|
|
switch-label-7 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label for switch sensor 7"
|
|
::= { channel1 15 }
|
|
|
|
switch-label-8 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label for switch sensor 8"
|
|
::= { channel1 16 }
|
|
|
|
sensor2-1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 2-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
|
|
::= { channel2 1 }
|
|
|
|
sensor2-2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 2-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
|
|
::= { channel2 2 }
|
|
|
|
sensor2-3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 2-3. If temp/humidity sensor is connected, value will be current %RH."
|
|
::= { channel2 3 }
|
|
|
|
sensor2-4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 2-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
|
|
::= { channel2 4 }
|
|
|
|
sensor2-5 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 2-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
|
|
::= { channel2 5 }
|
|
|
|
sensor2-6-label OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label of this sensor"
|
|
::= { channel2 6}
|
|
|
|
sensor3-1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 3-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
|
|
::= { channel3 1 }
|
|
|
|
sensor3-2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 3-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
|
|
::= { channel3 2 }
|
|
|
|
sensor3-3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 3-3. If temp/humidity sensor is connected, value will be current %RH."
|
|
::= { channel3 3 }
|
|
|
|
sensor3-4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 3-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
|
|
::= { channel3 4 }
|
|
|
|
sensor3-5 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 3-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
|
|
::= { channel3 5 }
|
|
|
|
sensor3-6-label OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label of this sensor"
|
|
::= { channel3 6}
|
|
|
|
sensor4-1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 4-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
|
|
::= { channel4 1 }
|
|
|
|
sensor4-2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 4-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
|
|
::= { channel4 2 }
|
|
|
|
sensor4-3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 4-3. If temp/humidity sensor is connected, value will be current %RH."
|
|
::= { channel4 3 }
|
|
|
|
sensor4-4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 4-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
|
|
::= { channel4 4 }
|
|
|
|
sensor4-5 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The reading for sensor 4-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
|
|
::= { channel4 5 }
|
|
|
|
sensor4-6-label OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The label of this sensor"
|
|
::= { channel4 6}
|
|
|
|
alarm1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm for sensor channel 1. The binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
|
|
::= { traps 1 }
|
|
|
|
alarm2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm for sensor channel 2. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
|
|
::= { traps 2 }
|
|
|
|
alarm3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm for sensor channel 3. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
|
|
::= { traps 3 }
|
|
|
|
alarm4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm for sensor channel 4. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
|
|
::= { traps 4 }
|
|
|
|
alarmMessage1 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm Message from sensor channel 1 (Internal)"
|
|
::= { traps 5 }
|
|
|
|
alarmMessage2 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm Message from sensor channel 2 (External)"
|
|
::= { traps 6 }
|
|
|
|
alarmMessage3 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm Message from sensor channel 3 (External)"
|
|
::= { traps 7 }
|
|
|
|
alarmMessage4 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm Message from sensor channel 4 (External)"
|
|
::= { traps 8 }
|
|
|
|
threshold1-1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 1 defined for Channel 1"
|
|
::= { channels1 1 }
|
|
|
|
threshold1-2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 2 defined for Channel 1"
|
|
::= { channels1 2 }
|
|
|
|
threshold1-3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 3 defined for Channel 1"
|
|
::= { channels1 3 }
|
|
|
|
threshold1-4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 4 defined for Channel 1"
|
|
::= { channels1 4 }
|
|
|
|
threshold1-5 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 5 defined for Channel 1"
|
|
::= { channels1 5 }
|
|
|
|
threshold1-6 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 6 defined for Channel 1"
|
|
::= { channels1 6 }
|
|
|
|
threshold1-7 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 7 defined for Channel 1"
|
|
::= { channels1 7 }
|
|
|
|
threshold1-8 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 8 defined for Channel 1"
|
|
::= { channels1 8 }
|
|
|
|
threshold2-1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 1 defined for Channel 2"
|
|
::= { channels2 1 }
|
|
|
|
threshold2-2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 2 defined for Channel 2"
|
|
::= { channels2 2 }
|
|
|
|
threshold2-3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 3 defined for Channel 2"
|
|
::= { channels2 3 }
|
|
|
|
threshold2-4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 4 defined for Channel 2"
|
|
::= { channels2 4 }
|
|
|
|
threshold3-1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 1 defined for Channel 3"
|
|
::= { channels3 1 }
|
|
|
|
threshold3-2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 2 defined for Channel 3"
|
|
::= { channels3 2 }
|
|
|
|
threshold3-3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 3 defined for Channel 3"
|
|
::= { channels3 3 }
|
|
|
|
threshold3-4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 4 defined for Channel 3"
|
|
::= { channels3 4 }
|
|
|
|
threshold4-1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 1 defined for Channel 4"
|
|
::= { channels4 1 }
|
|
|
|
threshold4-2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 2 defined for Channel 4"
|
|
::= { channels4 2 }
|
|
|
|
threshold4-3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 3 defined for Channel 4"
|
|
::= { channels4 3 }
|
|
|
|
threshold4-4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Threshold 4 defined for Channel 4"
|
|
::= { channels4 4 }
|
|
|
|
|
|
-- ROOMALERT11E TRAPS
|
|
|
|
tempAlarm1-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage2, sensor2-1, sensor2-2, sensor2-1 }
|
|
DESCRIPTION "A tempAlarm1 trap signifies that the current
|
|
temperature on external sensor 1 is outside the
|
|
defined high or low threshold."
|
|
::= 1
|
|
|
|
room-alert-11E-SNMP-trap TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1,alarmMessage2,alarmMessage3,alarmMessage4 }
|
|
DESCRIPTION "A Room Alert 11E SNMP Trap indicates that an alarm
|
|
condition has occurred on the sensor inidcated
|
|
by the alarmMessage variable."
|
|
::= 2
|
|
|
|
tempAlarm2-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-1 }
|
|
DESCRIPTION "A tempAlarm2 trap signifies that the current
|
|
temperature on external sensor 2 is outside the
|
|
defined high or low threshold."
|
|
::= 3
|
|
|
|
tempClear2-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-1 }
|
|
DESCRIPTION "A tempClear2 trap signifies that the current
|
|
temperature on external sensor 2 has returned to
|
|
a normal condition and is within the defined
|
|
high or low threshold."
|
|
::= 4
|
|
|
|
tempAlarm3-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-1 }
|
|
DESCRIPTION "A tempAlarm3 trap signifies that the current
|
|
temperature on external sensor 3 is outside the
|
|
defined high or low threshold."
|
|
::= 5
|
|
|
|
tempClear3-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-1 }
|
|
DESCRIPTION "A tempClear3 trap signifies that the current
|
|
temperature on external sensor 3 has returned to
|
|
a normal condition and is within the defined
|
|
high or low threshold."
|
|
::= 6
|
|
|
|
humidityAlarm1-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage2, sensor2-1, sensor2-2, sensor2-3 }
|
|
DESCRIPTION "A humidityAlarm1 trap signifies that the current
|
|
humidity on external sensor 1 is outside the
|
|
defined high or low threshold."
|
|
::= 7
|
|
|
|
humidityClear1-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage2, sensor2-1, sensor2-2, sensor2-3 }
|
|
DESCRIPTION "A humidityClear1 trap signifies that the current
|
|
humidity on external sensor 1 has returned to
|
|
a normal condition and is within the defined
|
|
high or low threshold."
|
|
::= 8
|
|
|
|
humidityAlarm2-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-3 }
|
|
DESCRIPTION "A humidityAlarm2 trap signifies that the current
|
|
humidity on external sensor 2 is outside the
|
|
defined high or low threshold."
|
|
::= 9
|
|
|
|
humidityClear2-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-3 }
|
|
DESCRIPTION "A humidityClear2 trap signifies that the current
|
|
humidity on external sensor 2 has returned to
|
|
a normal condition and is within the defined
|
|
high or low threshold."
|
|
::= 10
|
|
|
|
humidityAlarm3-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-3 }
|
|
DESCRIPTION "A humidityAlarm3 trap signifies that the current
|
|
humidity on external sensor 3 is outside the
|
|
defined high or low threshold."
|
|
::= 11
|
|
|
|
humidityClear3-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-3 }
|
|
DESCRIPTION "A humidityClear3 trap signifies that the current
|
|
humidity on external sensor 3 has returned to
|
|
a normal condition and is within the defined
|
|
high or low threshold."
|
|
::= 12
|
|
|
|
switchAlarm1-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-1, sensor1-1, sensor1-1 }
|
|
DESCRIPTION "A switchAlarm1 trap signifies that switch sensor 1
|
|
is in an alarm state."
|
|
::= 13
|
|
|
|
switchClear1-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-1, sensor1-1, sensor1-1 }
|
|
DESCRIPTION "A switchClear1 trap signifies that the switch sensor 1
|
|
has returned to a normal state."
|
|
::= 14
|
|
|
|
switchAlarm2-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-2, sensor1-2, sensor1-2 }
|
|
DESCRIPTION "A switchAlarm2 trap signifies that switch sensor 2
|
|
is in an alarm state."
|
|
::= 15
|
|
|
|
switchClear2-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-2, sensor1-2, sensor1-2 }
|
|
DESCRIPTION "A switchClear2 trap signifies that the switch sensor 2
|
|
has returned to a normal state."
|
|
::= 16
|
|
|
|
switchAlarm3-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-3, sensor1-3, sensor1-3 }
|
|
DESCRIPTION "A switchAlarm1 trap signifies that switch sensor 1
|
|
is in an alarm state."
|
|
::= 17
|
|
|
|
switchClear3-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-3, sensor1-3, sensor1-3 }
|
|
DESCRIPTION "A switchClear3 trap signifies that the switch sensor 3
|
|
has returned to a normal state."
|
|
::= 18
|
|
|
|
switchAlarm4-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-4, sensor1-4, sensor1-4 }
|
|
DESCRIPTION "A switchAlarm4 trap signifies that switch sensor 4
|
|
is in an alarm state."
|
|
::= 19
|
|
|
|
switchClear4-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-4, sensor1-4, sensor1-4 }
|
|
DESCRIPTION "A switchClear4 trap signifies that the switch sensor 4
|
|
has returned to a normal state."
|
|
::= 20
|
|
|
|
switchAlarm5-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-5, sensor1-5, sensor1-5 }
|
|
DESCRIPTION "A switchAlarm5 trap signifies that switch sensor 5
|
|
is in an alarm state."
|
|
::= 21
|
|
|
|
switchClear5-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-5, sensor1-5, sensor1-5 }
|
|
DESCRIPTION "A switchClear5 trap signifies that the switch sensor 5
|
|
has returned to a normal state."
|
|
::= 22
|
|
|
|
switchAlarm6-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-6, sensor1-6, sensor1-6 }
|
|
DESCRIPTION "A switchAlarm6 trap signifies that switch sensor 6
|
|
is in an alarm state."
|
|
::= 23
|
|
|
|
switchClear6-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-6, sensor1-6, sensor1-6 }
|
|
DESCRIPTION "A switchClear6 trap signifies that the switch sensor 6
|
|
has returned to a normal state."
|
|
::= 24
|
|
|
|
switchAlarm7-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-7, sensor1-7, sensor1-7 }
|
|
DESCRIPTION "A switchAlarm7 trap signifies that switch sensor 7
|
|
is in an alarm state."
|
|
::= 25
|
|
|
|
switchClear7-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-7, sensor1-7, sensor1-7 }
|
|
DESCRIPTION "A switchClear7 trap signifies that the switch sensor 7
|
|
has returned to a normal state."
|
|
::= 26
|
|
|
|
switchAlarm8-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-8, sensor1-8, sensor1-8 }
|
|
DESCRIPTION "A switchAlarm8 trap signifies that switch sensor 8
|
|
is in an alarm state."
|
|
::= 27
|
|
|
|
switchClear8-11e TRAP-TYPE
|
|
ENTERPRISE roomalert11E
|
|
VARIABLES { alarmMessage1, sensor1-8, sensor1-8, sensor1-8 }
|
|
DESCRIPTION "A switchClear8 trap signifies that the switch sensor 8
|
|
has returned to a normal state."
|
|
::= 28
|
|
END
|