mibs/MIBS/avtech/ROOMALERT11E-MIB
2023-12-05 12:25:34 +01:00

694 lines
21 KiB
Plaintext

--
--defines ROOMALERT11E-MIB for SNMP agent extension of Room Alert 11E
--Contents: Global Registration Module
-- Room Alert OIDs - Enterprise 20916
--Version: 1.1.3
--Date: 9 January 2014
--Developed By: AVTECH Software, Inc.
--
--Copyright (c) 2014 AVTECH Software, Inc.
--
ROOMALERT11E-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress, Counter, TimeTicks
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
TRAP-TYPE
FROM RFC-1215;
avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
products OBJECT IDENTIFIER ::= { avtech 1 }
roomalert11E OBJECT IDENTIFIER ::= { products 3 }
sensors OBJECT IDENTIFIER ::= { roomalert11E 1 }
traps OBJECT IDENTIFIER ::= { roomalert11E 2 }
thresholds OBJECT IDENTIFIER ::= { roomalert11E 3 }
channel1 OBJECT IDENTIFIER ::= { sensors 1 }
channel2 OBJECT IDENTIFIER ::= { sensors 2 }
channel3 OBJECT IDENTIFIER ::= { sensors 3 }
channel4 OBJECT IDENTIFIER ::= { sensors 4 }
channels OBJECT IDENTIFIER ::= { thresholds 1 }
channels1 OBJECT IDENTIFIER ::= { channels 1 }
channels2 OBJECT IDENTIFIER ::= { channels 2 }
channels3 OBJECT IDENTIFIER ::= { channels 3 }
channels4 OBJECT IDENTIFIER ::= { channels 4 }
-- Room Alert 11E MIB
-- Parameters
sensor1-1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for internal switch sensor 1 (0 = OPEN, 1 = CLOSED)."
::= { channel1 1 }
sensor1-2 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for internal switch sensor 2 (0 = OPEN, 1 = CLOSED)."
::= { channel1 2 }
sensor1-3 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for internal switch sensor 3 (0 = OPEN, 1 = CLOSED)."
::= { channel1 3 }
sensor1-4 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for internal switch sensor 4 (0 = OPEN, 1 = CLOSED)."
::= { channel1 4 }
sensor1-5 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for internal switch sensor 5 (0 = OPEN, 1 = CLOSED)."
::= { channel1 5 }
sensor1-6 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for internal switch sensor 6 (0 = OPEN, 1 = CLOSED)."
::= { channel1 6 }
sensor1-7 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for internal switch sensor 7 (0 = OPEN, 1 = CLOSED)."
::= { channel1 7 }
sensor1-8 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for internal switch sensor 8 (0 = OPEN, 1 = CLOSED)."
::= { channel1 8 }
switch-label-1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label for switch sensor 1"
::= { channel1 9 }
switch-label-2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label for switch sensor 2"
::= { channel1 10 }
switch-label-3 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label for switch sensor 3"
::= { channel1 11 }
switch-label-4 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label for switch sensor 4"
::= { channel1 12 }
switch-label-5 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label for switch sensor 5"
::= { channel1 13 }
switch-label-6 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label for switch sensor 6"
::= { channel1 14 }
switch-label-7 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label for switch sensor 7"
::= { channel1 15 }
switch-label-8 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label for switch sensor 8"
::= { channel1 16 }
sensor2-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 2-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
::= { channel2 1 }
sensor2-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 2-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
::= { channel2 2 }
sensor2-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 2-3. If temp/humidity sensor is connected, value will be current %RH."
::= { channel2 3 }
sensor2-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 2-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
::= { channel2 4 }
sensor2-5 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 2-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
::= { channel2 5 }
sensor2-6-label OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label of this sensor"
::= { channel2 6}
sensor3-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 3-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
::= { channel3 1 }
sensor3-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 3-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
::= { channel3 2 }
sensor3-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 3-3. If temp/humidity sensor is connected, value will be current %RH."
::= { channel3 3 }
sensor3-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 3-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
::= { channel3 4 }
sensor3-5 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 3-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
::= { channel3 5 }
sensor3-6-label OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label of this sensor"
::= { channel3 6}
sensor4-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 4-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
::= { channel4 1 }
sensor4-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 4-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
::= { channel4 2 }
sensor4-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 4-3. If temp/humidity sensor is connected, value will be current %RH."
::= { channel4 3 }
sensor4-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 4-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
::= { channel4 4 }
sensor4-5 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "The reading for sensor 4-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
::= { channel4 5 }
sensor4-6-label OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "The label of this sensor"
::= { channel4 6}
alarm1 OBJECT-TYPE
SYNTAX INTEGER(0..255)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm for sensor channel 1. The binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
::= { traps 1 }
alarm2 OBJECT-TYPE
SYNTAX INTEGER(0..255)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm for sensor channel 2. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
::= { traps 2 }
alarm3 OBJECT-TYPE
SYNTAX INTEGER(0..255)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm for sensor channel 3. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
::= { traps 3 }
alarm4 OBJECT-TYPE
SYNTAX INTEGER(0..255)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm for sensor channel 4. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
::= { traps 4 }
alarmMessage1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm Message from sensor channel 1 (Internal)"
::= { traps 5 }
alarmMessage2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm Message from sensor channel 2 (External)"
::= { traps 6 }
alarmMessage3 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm Message from sensor channel 3 (External)"
::= { traps 7 }
alarmMessage4 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm Message from sensor channel 4 (External)"
::= { traps 8 }
threshold1-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 1 defined for Channel 1"
::= { channels1 1 }
threshold1-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 2 defined for Channel 1"
::= { channels1 2 }
threshold1-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 3 defined for Channel 1"
::= { channels1 3 }
threshold1-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 4 defined for Channel 1"
::= { channels1 4 }
threshold1-5 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 5 defined for Channel 1"
::= { channels1 5 }
threshold1-6 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 6 defined for Channel 1"
::= { channels1 6 }
threshold1-7 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 7 defined for Channel 1"
::= { channels1 7 }
threshold1-8 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 8 defined for Channel 1"
::= { channels1 8 }
threshold2-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 1 defined for Channel 2"
::= { channels2 1 }
threshold2-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 2 defined for Channel 2"
::= { channels2 2 }
threshold2-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 3 defined for Channel 2"
::= { channels2 3 }
threshold2-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 4 defined for Channel 2"
::= { channels2 4 }
threshold3-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 1 defined for Channel 3"
::= { channels3 1 }
threshold3-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 2 defined for Channel 3"
::= { channels3 2 }
threshold3-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 3 defined for Channel 3"
::= { channels3 3 }
threshold3-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 4 defined for Channel 3"
::= { channels3 4 }
threshold4-1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 1 defined for Channel 4"
::= { channels4 1 }
threshold4-2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 2 defined for Channel 4"
::= { channels4 2 }
threshold4-3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 3 defined for Channel 4"
::= { channels4 3 }
threshold4-4 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Threshold 4 defined for Channel 4"
::= { channels4 4 }
-- ROOMALERT11E TRAPS
tempAlarm1-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage2, sensor2-1, sensor2-2, sensor2-1 }
DESCRIPTION "A tempAlarm1 trap signifies that the current
temperature on external sensor 1 is outside the
defined high or low threshold."
::= 1
room-alert-11E-SNMP-trap TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1,alarmMessage2,alarmMessage3,alarmMessage4 }
DESCRIPTION "A Room Alert 11E SNMP Trap indicates that an alarm
condition has occurred on the sensor inidcated
by the alarmMessage variable."
::= 2
tempAlarm2-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-1 }
DESCRIPTION "A tempAlarm2 trap signifies that the current
temperature on external sensor 2 is outside the
defined high or low threshold."
::= 3
tempClear2-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-1 }
DESCRIPTION "A tempClear2 trap signifies that the current
temperature on external sensor 2 has returned to
a normal condition and is within the defined
high or low threshold."
::= 4
tempAlarm3-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-1 }
DESCRIPTION "A tempAlarm3 trap signifies that the current
temperature on external sensor 3 is outside the
defined high or low threshold."
::= 5
tempClear3-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-1 }
DESCRIPTION "A tempClear3 trap signifies that the current
temperature on external sensor 3 has returned to
a normal condition and is within the defined
high or low threshold."
::= 6
humidityAlarm1-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage2, sensor2-1, sensor2-2, sensor2-3 }
DESCRIPTION "A humidityAlarm1 trap signifies that the current
humidity on external sensor 1 is outside the
defined high or low threshold."
::= 7
humidityClear1-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage2, sensor2-1, sensor2-2, sensor2-3 }
DESCRIPTION "A humidityClear1 trap signifies that the current
humidity on external sensor 1 has returned to
a normal condition and is within the defined
high or low threshold."
::= 8
humidityAlarm2-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-3 }
DESCRIPTION "A humidityAlarm2 trap signifies that the current
humidity on external sensor 2 is outside the
defined high or low threshold."
::= 9
humidityClear2-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage3, sensor3-1, sensor3-2, sensor3-3 }
DESCRIPTION "A humidityClear2 trap signifies that the current
humidity on external sensor 2 has returned to
a normal condition and is within the defined
high or low threshold."
::= 10
humidityAlarm3-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-3 }
DESCRIPTION "A humidityAlarm3 trap signifies that the current
humidity on external sensor 3 is outside the
defined high or low threshold."
::= 11
humidityClear3-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage4, sensor4-1, sensor4-2, sensor4-3 }
DESCRIPTION "A humidityClear3 trap signifies that the current
humidity on external sensor 3 has returned to
a normal condition and is within the defined
high or low threshold."
::= 12
switchAlarm1-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-1, sensor1-1, sensor1-1 }
DESCRIPTION "A switchAlarm1 trap signifies that switch sensor 1
is in an alarm state."
::= 13
switchClear1-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-1, sensor1-1, sensor1-1 }
DESCRIPTION "A switchClear1 trap signifies that the switch sensor 1
has returned to a normal state."
::= 14
switchAlarm2-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-2, sensor1-2, sensor1-2 }
DESCRIPTION "A switchAlarm2 trap signifies that switch sensor 2
is in an alarm state."
::= 15
switchClear2-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-2, sensor1-2, sensor1-2 }
DESCRIPTION "A switchClear2 trap signifies that the switch sensor 2
has returned to a normal state."
::= 16
switchAlarm3-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-3, sensor1-3, sensor1-3 }
DESCRIPTION "A switchAlarm1 trap signifies that switch sensor 1
is in an alarm state."
::= 17
switchClear3-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-3, sensor1-3, sensor1-3 }
DESCRIPTION "A switchClear3 trap signifies that the switch sensor 3
has returned to a normal state."
::= 18
switchAlarm4-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-4, sensor1-4, sensor1-4 }
DESCRIPTION "A switchAlarm4 trap signifies that switch sensor 4
is in an alarm state."
::= 19
switchClear4-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-4, sensor1-4, sensor1-4 }
DESCRIPTION "A switchClear4 trap signifies that the switch sensor 4
has returned to a normal state."
::= 20
switchAlarm5-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-5, sensor1-5, sensor1-5 }
DESCRIPTION "A switchAlarm5 trap signifies that switch sensor 5
is in an alarm state."
::= 21
switchClear5-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-5, sensor1-5, sensor1-5 }
DESCRIPTION "A switchClear5 trap signifies that the switch sensor 5
has returned to a normal state."
::= 22
switchAlarm6-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-6, sensor1-6, sensor1-6 }
DESCRIPTION "A switchAlarm6 trap signifies that switch sensor 6
is in an alarm state."
::= 23
switchClear6-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-6, sensor1-6, sensor1-6 }
DESCRIPTION "A switchClear6 trap signifies that the switch sensor 6
has returned to a normal state."
::= 24
switchAlarm7-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-7, sensor1-7, sensor1-7 }
DESCRIPTION "A switchAlarm7 trap signifies that switch sensor 7
is in an alarm state."
::= 25
switchClear7-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-7, sensor1-7, sensor1-7 }
DESCRIPTION "A switchClear7 trap signifies that the switch sensor 7
has returned to a normal state."
::= 26
switchAlarm8-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-8, sensor1-8, sensor1-8 }
DESCRIPTION "A switchAlarm8 trap signifies that switch sensor 8
is in an alarm state."
::= 27
switchClear8-11e TRAP-TYPE
ENTERPRISE roomalert11E
VARIABLES { alarmMessage1, sensor1-8, sensor1-8, sensor1-8 }
DESCRIPTION "A switchClear8 trap signifies that the switch sensor 8
has returned to a normal state."
::= 28
END