Initial commit
This commit is contained in:
257
MIBS/avtech/ROOMALERT4E-MIB
Normal file
257
MIBS/avtech/ROOMALERT4E-MIB
Normal file
@ -0,0 +1,257 @@
|
||||
--
|
||||
--defines ROOMALERT4E-MIB for SNMP agent extension of Room Alert 4E
|
||||
--Contents: Global Registration Module
|
||||
-- Room Alert OIDs - Enterprise 20916
|
||||
--Version: 4.2.4
|
||||
--Date: 15 February 2019
|
||||
--Developed By: AVTECH Software, Inc.
|
||||
|
||||
--
|
||||
--Copyright (c) 2019 AVTECH Software, Inc.
|
||||
--
|
||||
|
||||
ROOMALERT4E-MIB DEFINITIONS ::= BEGIN
|
||||
|
||||
|
||||
IMPORTS
|
||||
enterprises, IpAddress, Counter, TimeTicks
|
||||
FROM RFC1155-SMI
|
||||
OBJECT-TYPE
|
||||
FROM RFC-1212
|
||||
TRAP-TYPE
|
||||
FROM RFC-1215;
|
||||
|
||||
|
||||
avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
|
||||
products OBJECT IDENTIFIER ::= { avtech 1 }
|
||||
roomalert4E OBJECT IDENTIFIER ::= { products 6 }
|
||||
sensors OBJECT IDENTIFIER ::= { roomalert4E 1 }
|
||||
signaltower OBJECT IDENTIFIER ::= { roomalert4E 2 }
|
||||
traps OBJECT IDENTIFIER ::= { roomalert4E 3 }
|
||||
internal OBJECT IDENTIFIER ::= { sensors 1 }
|
||||
temperature OBJECT IDENTIFIER ::= { internal 1 }
|
||||
label OBJECT IDENTIFIER ::= { internal 2 }
|
||||
digital OBJECT IDENTIFIER ::= { sensors 2 }
|
||||
digital-sen1 OBJECT IDENTIFIER ::= { digital 1 }
|
||||
digital-sen2 OBJECT IDENTIFIER ::= { digital 2 }
|
||||
switch OBJECT IDENTIFIER ::= { sensors 3 }
|
||||
|
||||
|
||||
-- Room Alert 4E MIB
|
||||
-- Parameters
|
||||
|
||||
|
||||
internal-tempf OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The internal temperature reading in Fahrenheit."
|
||||
::= { temperature 1 }
|
||||
|
||||
internal-tempc OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The internal temperature reading in Celsius."
|
||||
::= { temperature 2 }
|
||||
|
||||
internal-label OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label of this sensor"
|
||||
::= { label 1 }
|
||||
|
||||
digital-sen1-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
|
||||
::= { digital-sen1 1 }
|
||||
|
||||
digital-sen1-2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
|
||||
::= { digital-sen1 2 }
|
||||
|
||||
digital-sen1-3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
|
||||
::= { digital-sen1 3 }
|
||||
|
||||
digital-sen1-4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
|
||||
::= { digital-sen1 4 }
|
||||
|
||||
digital-sen1-5 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
|
||||
::= { digital-sen1 5 }
|
||||
|
||||
digital-sen1-6 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
|
||||
::= { digital-sen1 6 }
|
||||
|
||||
digital-sen1-7 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
|
||||
::= { digital-sen1 7 }
|
||||
|
||||
digital-sen1-label OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label of this sensor"
|
||||
::= {digital-sen1 8}
|
||||
|
||||
digital-sen2-1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
|
||||
::= { digital-sen2 1 }
|
||||
|
||||
digital-sen2-2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
|
||||
::= { digital-sen2 2 }
|
||||
|
||||
digital-sen2-3 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
|
||||
::= { digital-sen2 3 }
|
||||
|
||||
digital-sen2-4 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
|
||||
::= { digital-sen2 4 }
|
||||
|
||||
digital-sen2-5 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
|
||||
::= { digital-sen2 5 }
|
||||
|
||||
digital-sen2-6 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
|
||||
::= { digital-sen2 6 }
|
||||
|
||||
digital-sen2-7 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..65535)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
|
||||
::= { digital-sen2 7 }
|
||||
|
||||
digital-sen2-label OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label of this sensor"
|
||||
::= {digital-sen2 8}
|
||||
|
||||
switch-sen1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The reading for the switch sensor 1 (0 = OPEN, 1 = CLOSED)."
|
||||
::= { switch 1 }
|
||||
|
||||
switch-label OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The label for the switch sensor"
|
||||
::= { switch 2 }
|
||||
|
||||
red-led OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of this Light Tower element (0 = OFF, 1 = ON)."
|
||||
::= { signaltower 1 }
|
||||
|
||||
amber-led OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of this Light Tower element (0 = OFF, 1 = ON)."
|
||||
::= { signaltower 2 }
|
||||
|
||||
green-led OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of this Light Tower element (0 = OFF, 1 = ON)."
|
||||
::= { signaltower 3 }
|
||||
|
||||
blue-led OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of this Light Tower element (0 = OFF, 1 = ON)."
|
||||
::= { signaltower 4 }
|
||||
|
||||
white-led OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of this Light Tower element (0 = OFF, 1 = ON)."
|
||||
::= { signaltower 5 }
|
||||
|
||||
alarm1 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of this Light Tower element (0 = OFF, 1 = ON)."
|
||||
::= { signaltower 6 }
|
||||
|
||||
alarm2 OBJECT-TYPE
|
||||
SYNTAX INTEGER(0..1)
|
||||
ACCESS read-write
|
||||
STATUS mandatory
|
||||
DESCRIPTION "The status of this Light Tower element (0 = OFF, 1 = ON)."
|
||||
::= { signaltower 7 }
|
||||
|
||||
alarmmessage OBJECT-TYPE
|
||||
SYNTAX OCTET STRING
|
||||
ACCESS read-only
|
||||
STATUS mandatory
|
||||
DESCRIPTION "Last Alarm Message"
|
||||
::= { traps 1 }
|
||||
|
||||
|
||||
-- roomalert4E TRAPS
|
||||
|
||||
room-alert-4e-snmp-trap TRAP-TYPE
|
||||
ENTERPRISE roomalert4E
|
||||
VARIABLES { alarmmessage }
|
||||
DESCRIPTION "A room-alert-4e-snmp-trap indicates that an alarm
|
||||
condition has occurred on the sensor indicated
|
||||
by the alarmmessage variable."
|
||||
::= 2
|
||||
END
|
Reference in New Issue
Block a user