 -- MIB version: 1.1.115
 | 
						|
 | 
						|
 -- MIB release note
 | 
						|
 --        |    date     | MIB version |  author      |    note
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 02/11/2015  | 1.1.116     |  Zack Huang  |   Syntax modification of POP modes
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 12/02/2014  | 1.1.115     |  Zack Huang  |   Wording modification
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 10/22/2014  | 1.1.114     |  HC Sun      |   Add get/set function for new POP feature
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 07/28/2014  | 1.1.113     |  Zack Huang  |   Modify and unify responses of empty and not-support measurement values
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 10/31/2013  | 1.1.112     |  Zack Huang  |   updated mib to pass smilint level 3
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 10/03/2013  | 1.1.111     |  Jenny Teng  |   updated mib to pass smilint level 3
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 08/09/2013  | 1.1.110     |  Jenny Teng  |   Add outlet init mode
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 07/17/2013  | 1.1.109     |  Zack Huang  |   Add CAP Priority Settings
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 07/05/2013  | 1.1.108     |  Jenny Teng  |   Add Description and change some Syntax of oids
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 05/23/2013  | 1.1.107     |  Carter Wu   |   Change "usrEnable" order from 40 to 47 in "UsrListEntry"
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 05/21/2013  | 1.1.106     |  Carter Wu   |   Hide CAP function
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 05/14/2013  | 1.1.105     |  Carter Wu   |   Modify Power Threshold Description
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 05/07/2013  | 1.1.104     |  Carter Wu   |   Add CAP Function OID
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 04/26/2013  | 1.1.103     |  Zack Huang  |   Add Door Sensor Type OID
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 04/24/2013  | 1.1.102     |  Zack Huang  |   Modify Status Description of Door Sensor
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 02/20/2013  | 1.1.101     |  Zack Huang  |
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 02/17/2012  |             |  Jenny Teng  |
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 --        | 03/29/2010  |             |  Zack Yang   |   Initiative Version
 | 
						|
 -- --------------------------------------------------------------------------------------------------------------------------
 | 
						|
 | 
						|
 -- ATEN International Co., Ltd.
 | 
						|
 -- This file defines the mib struct of Management in PE series
 | 
						|
 -- We attach this mib node on enterprises.aten.atenProducts.overip.poweroverip.pe subtree
 | 
						|
 | 
						|
 -- RENAMED TO AVOID CONFLICTS
 | 
						|
ATEN-PE-CFG-STR DEFINITIONS ::= BEGIN
 | 
						|
 | 
						|
    IMPORTS
 | 
						|
        enterprises, IpAddress, Gauge, TimeTicks     FROM RFC1155-SMI
 | 
						|
        enterprises									FROM RFC1155-SMI
 | 
						|
		DisplayString                                FROM RFC1213-MIB
 | 
						|
		OBJECT-TYPE                                  FROM RFC-1212
 | 
						|
		TRAP-TYPE                                    FROM RFC-1215
 | 
						|
		MODULE-IDENTITY,
 | 
						|
		NOTIFICATION-TYPE							 FROM SNMPv2-SMI
 | 
						|
				KeyChange				      		FROM SNMP-USER-BASED-SM-MIB
 | 
						|
		TEXTUAL-CONVENTION			      			FROM SNMPv2-TC;
 | 
						|
 | 
						|
 | 
						|
 | 
						|
    aten MODULE-IDENTITY
 | 
						|
        LAST-UPDATED "201310311110Z"
 | 
						|
        ORGANIZATION "ATEN"
 | 
						|
        CONTACT-INFO "Aten, Inc."
 | 
						|
        DESCRIPTION
 | 
						|
                "ATEN PE MIB"
 | 
						|
        REVISION "201310311110Z"
 | 
						|
        DESCRIPTION
 | 
						|
                "updated mib to pass smilint level 3"
 | 
						|
        ::= { enterprises 21317 }
 | 
						|
 | 
						|
 | 
						|
 atenProducts OBJECT IDENTIFIER ::= { aten 1 }
 | 
						|
 overip    	OBJECT IDENTIFIER ::= { atenProducts 3 }
 | 
						|
 poweroverip		OBJECT IDENTIFIER ::= { overip 2}
 | 
						|
 pe			OBJECT IDENTIFIER ::= {poweroverip 2}
 | 
						|
 userManagement                   	                OBJECT IDENTIFIER ::=  { pe 1 }
 | 
						|
	control                                             OBJECT IDENTIFIER ::=  { pe 2 }
 | 
						|
	device												OBJECT IDENTIFIER ::=  { control 1 }
 | 
						|
	   doorSensor                                       OBJECT IDENTIFIER ::=  { device 16 }
 | 
						|
	   pop                                              OBJECT IDENTIFIER ::=  { device 17 }
 | 
						|
	   cap												OBJECT IDENTIFIER ::=  { device 18 }
 | 
						|
	outlet												OBJECT IDENTIFIER ::=  { control 2 }
 | 
						|
	bank                                                OBJECT IDENTIFIER ::=  { control 3 }
 | 
						|
deviceManagement									OBJECT IDENTIFIER ::=  { pe 3 }
 | 
						|
	config												OBJECT IDENTIFIER ::=  { deviceManagement 4 }
 | 
						|
		dashBoard											OBJECT IDENTIFIER ::=  { config 4 }
 | 
						|
		servicePorts										OBJECT IDENTIFIER ::=  { config 5 }
 | 
						|
		ipv4config											OBJECT IDENTIFIER ::=  { config 6 }
 | 
						|
		eventNotification									OBJECT IDENTIFIER ::=  { config 7 }
 | 
						|
			devicesnmp												OBJECT IDENTIFIER ::=  { eventNotification 1 }
 | 
						|
			syslog												OBJECT IDENTIFIER ::=  { eventNotification 2 }
 | 
						|
			smtp												OBJECT IDENTIFIER ::=  { eventNotification 3 }
 | 
						|
			configurationNotification							OBJECT IDENTIFIER ::=  { eventNotification 9 }
 | 
						|
 | 
						|
 | 
						|
		dateTime											OBJECT IDENTIFIER ::=  { config 8 }
 | 
						|
			timeZone											OBJECT IDENTIFIER ::=  { dateTime 1 }
 | 
						|
			manualInput											OBJECT IDENTIFIER ::=  { dateTime 2 }
 | 
						|
			networkTime											OBJECT IDENTIFIER ::=  { dateTime 3 }
 | 
						|
 | 
						|
	devicesecurity											OBJECT IDENTIFIER ::=  { deviceManagement 5 }
 | 
						|
		loginFailures										OBJECT IDENTIFIER ::=  { devicesecurity 1 }
 | 
						|
		workingMode											OBJECT IDENTIFIER ::=  { devicesecurity 2 }
 | 
						|
		accountPolicy 										OBJECT IDENTIFIER ::=  { devicesecurity 3 }
 | 
						|
		loginRestriction									OBJECT IDENTIFIER ::=  { devicesecurity 4 }
 | 
						|
			ipFilter											OBJECT IDENTIFIER ::=  { loginRestriction 2 }
 | 
						|
			macFilter											OBJECT IDENTIFIER ::=  { loginRestriction 3 }
 | 
						|
		authentication										OBJECT IDENTIFIER ::=  { devicesecurity 5 }
 | 
						|
			radius												OBJECT IDENTIFIER ::=  { authentication 1 }
 | 
						|
--CPM		               								OBJECT IDENTIFIER ::=  { pe 7 }
 | 
						|
--	CPMDevice                                              OBJECT IDENTIFIER ::=  { CPM 9 }
 | 
						|
--    Sensor												OBJECT IDENTIFIER ::=  { CPM 10 }
 | 
						|
--	EnergySensor											OBJECT IDENTIFIER ::=  { CPM 11 }
 | 
						|
 | 
						|
 | 
						|
--SNMPv3UsmAuthPrivProtocol ::=  TEXTUAL-CONVENTION
 | 
						|
--    STATUS  current
 | 
						|
--    DESCRIPTION
 | 
						|
--		"This textual convention enumerates the authentication and privledge
 | 
						|
--		protocol for USM configuration.
 | 
						|
--        "
 | 
						|
--       SYNTAX    INTEGER
 | 
						|
-- 			{
 | 
						|
--				hmacMD5Auth(2),
 | 
						|
--				hmacSHAAuth(3)
 | 
						|
--				desPrivProtocol(5),
 | 
						|
--				aesPrivProtocol(6)
 | 
						|
--			}
 | 
						|
 | 
						|
-- Device Control
 | 
						|
modelName OBJECT-TYPE
 | 
						|
	SYNTAX DisplayString
 | 
						|
	MAX-ACCESS read-only
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Indicate PE device model name."
 | 
						|
	::= { device 1 }
 | 
						|
 | 
						|
deviceName OBJECT-TYPE
 | 
						|
	SYNTAX DisplayString
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"The name of PE device.
 | 
						|
		string length: 1~39
 | 
						|
		NOTE: Input string as /empty to set this object to NULL.
 | 
						|
		"
 | 
						|
	::= { device 2 }
 | 
						|
 | 
						|
deviceValueTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF DeviceValueEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Device value table. This table displays device's current, voltage, power and
 | 
						|
		 power dissipation.
 | 
						|
		"
 | 
						|
    ::= { device 3 }
 | 
						|
 | 
						|
deviceValueEntry OBJECT-TYPE
 | 
						|
    SYNTAX DeviceValueEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Single deviceValue entry containing device info."
 | 
						|
    INDEX { deviceValueIndex }
 | 
						|
     ::= { deviceValueTable 1 }
 | 
						|
 | 
						|
DeviceValueEntry ::=
 | 
						|
    SEQUENCE {
 | 
						|
        deviceValueIndex
 | 
						|
            INTEGER,
 | 
						|
        deviceCurrent
 | 
						|
            DisplayString,
 | 
						|
        deviceVoltage
 | 
						|
            DisplayString,
 | 
						|
		devicePower
 | 
						|
            DisplayString,
 | 
						|
		devicePowerDissipation
 | 
						|
            DisplayString,
 | 
						|
        inputMaxVoltage
 | 
						|
        	INTEGER,
 | 
						|
        inputMaxCurrent
 | 
						|
        	INTEGER,
 | 
						|
        powerCapacity
 | 
						|
        	INTEGER,
 | 
						|
        devicePowerFactor
 | 
						|
          	DisplayString
 | 
						|
    }
 | 
						|
 | 
						|
deviceValueIndex  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1)
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Index of deviceValue."
 | 
						|
    ::= { deviceValueEntry 1 }
 | 
						|
deviceCurrent  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Device electric current value.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { deviceValueEntry 2 }
 | 
						|
deviceVoltage  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Device voltage value.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { deviceValueEntry 3 }
 | 
						|
devicePower  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Device power value.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { deviceValueEntry 4 }
 | 
						|
 | 
						|
devicePowerDissipation  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Device power dissipation value.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { deviceValueEntry 5 }
 | 
						|
 | 
						|
inputMaxVoltage  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Device input Voltage value. unit:(V)
 | 
						|
        If the device does not support this OID, we show value 0.
 | 
						|
        "
 | 
						|
    ::= { deviceValueEntry 6 }
 | 
						|
 | 
						|
inputMaxCurrent  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Device input Current value. unit:(A)
 | 
						|
        If the device does not support this OID, we show value 0."
 | 
						|
    ::= { deviceValueEntry 7 }
 | 
						|
 | 
						|
powerCapacity  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Device power Capacity value.unit:(VA)
 | 
						|
        If the device does not support this OID, we show value 0."
 | 
						|
    ::= { deviceValueEntry 8 }
 | 
						|
 | 
						|
devicePowerFactor  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Device power Factor value.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { deviceValueEntry 9 }
 | 
						|
 | 
						|
sensorValueTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF SensorValueEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Device's sensor value table. This table displays sensor's temperature, humidity and
 | 
						|
		 pressure.
 | 
						|
		"
 | 
						|
    ::= { device 4 }
 | 
						|
 | 
						|
sensorValueEntry OBJECT-TYPE
 | 
						|
    SYNTAX SensorValueEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Single device's sensor value entry containing device info."
 | 
						|
    INDEX { sensorValueIndex }
 | 
						|
     ::= { sensorValueTable 1 }
 | 
						|
 | 
						|
SensorValueEntry ::=
 | 
						|
    SEQUENCE {
 | 
						|
    		sensorValueIndex
 | 
						|
    			INTEGER,
 | 
						|
		sensorTemperature
 | 
						|
            		DisplayString,
 | 
						|
		sensorHumidity
 | 
						|
			DisplayString,
 | 
						|
		sensorPressure
 | 
						|
			DisplayString,
 | 
						|
		sensorProperty
 | 
						|
			INTEGER
 | 
						|
    }
 | 
						|
 | 
						|
sensorValueIndex  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..6)
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Index of sensor number."
 | 
						|
    ::= { sensorValueEntry 1 }
 | 
						|
sensorTemperature  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Sensor's Temperature value.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { sensorValueEntry 2 }
 | 
						|
sensorHumidity  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Sensor's Humidity value.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { sensorValueEntry 3 }
 | 
						|
sensorPressure  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Sensor's Pressure value.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { sensorValueEntry 4 }
 | 
						|
 | 
						|
sensorProperty  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { intake(1), exhaust(2), floor(3) }
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Sensor's Property."
 | 
						|
    ::= { sensorValueEntry 5 }
 | 
						|
 | 
						|
deviceOutletStatusTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF DeviceOutletStatusEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Device outlet status value table."
 | 
						|
    ::= { device 5 }
 | 
						|
 | 
						|
deviceOutletStatusEntry OBJECT-TYPE
 | 
						|
    SYNTAX DeviceOutletStatusEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Single deviceOutletStatus entry containing device info."
 | 
						|
    INDEX { deviceOutletStatusIndex }
 | 
						|
     ::= { deviceOutletStatusTable 1 }
 | 
						|
 | 
						|
DeviceOutletStatusEntry ::=
 | 
						|
    SEQUENCE {
 | 
						|
        deviceOutletStatusIndex
 | 
						|
            INTEGER,
 | 
						|
	displayOutletStatus
 | 
						|
            INTEGER
 | 
						|
        --deviceOutletControl
 | 
						|
            --INTEGER,
 | 
						|
        --deviceOutletReboot
 | 
						|
        --	INTEGER
 | 
						|
 | 
						|
    }
 | 
						|
 | 
						|
deviceOutletStatusIndex  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..30)
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Index of deviceOutletStatus"
 | 
						|
    ::= { deviceOutletStatusEntry 1 }
 | 
						|
displayOutletStatus OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), fault(4), noauth(5), not-support(6), pop(7) }
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display outlet status."
 | 
						|
    ::= { deviceOutletStatusEntry 2 }
 | 
						|
 | 
						|
 | 
						|
deviceConfigTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF DeviceConfigEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Device configuration table"
 | 
						|
    ::= { device 6 }
 | 
						|
 | 
						|
deviceConfigEntry OBJECT-TYPE
 | 
						|
    SYNTAX DeviceConfigEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Single deviceConfig entry containing device info."
 | 
						|
    INDEX { deviceConfigIndex }
 | 
						|
     ::= { deviceConfigTable 1 }
 | 
						|
 | 
						|
DeviceConfigEntry ::=
 | 
						|
    SEQUENCE {
 | 
						|
        deviceConfigIndex
 | 
						|
            INTEGER,
 | 
						|
        deviceMinCurMT
 | 
						|
            INTEGER,
 | 
						|
        deviceMaxCurMT
 | 
						|
            INTEGER,
 | 
						|
 | 
						|
		deviceMinVolMT
 | 
						|
            INTEGER,
 | 
						|
        deviceMaxVolMT
 | 
						|
            INTEGER,
 | 
						|
		deviceMinPMT
 | 
						|
            INTEGER,
 | 
						|
        deviceMaxPMT
 | 
						|
            INTEGER,
 | 
						|
 | 
						|
		--deviceMinPDMT
 | 
						|
            --INTEGER,
 | 
						|
        deviceMaxPDMT
 | 
						|
            INTEGER
 | 
						|
        --deviceCurFlu
 | 
						|
        --    INTEGER,
 | 
						|
        --deviceVolFlu
 | 
						|
        --    INTEGER,
 | 
						|
        --devicePFlu
 | 
						|
        --    INTEGER
 | 
						|
		--devicePDFlu
 | 
						|
            --INTEGER
 | 
						|
    }
 | 
						|
 | 
						|
deviceConfigIndex  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1)
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Index of deviceConfig"
 | 
						|
    ::= { deviceConfigEntry 1 }
 | 
						|
deviceMinCurMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set device minimum electric current measurement threshold.
 | 
						|
        Example: range 0.0~32.0 represents 0~320.
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { deviceConfigEntry 2 }
 | 
						|
deviceMaxCurMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set device maximum electric current measurement threshold.
 | 
						|
        Example: range 0.0~32.0 represents 0~320
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { deviceConfigEntry 3 }
 | 
						|
 | 
						|
deviceMinVolMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (900..2600 | -3000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set device minimum voltage measurement threshold.
 | 
						|
        Exapmple: range 90.0~260.0 represents 900~2600
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { deviceConfigEntry 4 }
 | 
						|
 | 
						|
deviceMaxVolMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (900..2600 | -3000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set device maximum voltage measurement threshold.
 | 
						|
        Example: range 90.0~260.0 represents 900~2600
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { deviceConfigEntry 5 }
 | 
						|
 | 
						|
deviceMinPMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (0..99999 | -3000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set device minimum power measurement threshold.
 | 
						|
        Example: range 0.0 ~ 9999.9 represents 0~99999
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { deviceConfigEntry 6 }
 | 
						|
 | 
						|
deviceMaxPMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (0..99999 | -3000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set device maximum power measurement threshold.
 | 
						|
        Example: range 0.0 ~ 9999.9 represents 0~99999
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { deviceConfigEntry 7 }
 | 
						|
 | 
						|
--deviceCurFlu  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display device electric current fluctuation threshold.
 | 
						|
    --    Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
 | 
						|
    --    When this value is -3000,it indicate this is NULL.
 | 
						|
    --    When set this value to -3000, indicate set this object as NULL.
 | 
						|
    --    NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
	--	 "
 | 
						|
    --::= { deviceConfigEntry 9 }
 | 
						|
 | 
						|
--deviceVolFlu  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display device voltage fluctuation threshold.
 | 
						|
    --    Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
 | 
						|
    --    When this value is -3000,it indicate this is NULL.
 | 
						|
    --    When set this value to -3000, indicate set this object as NULL.
 | 
						|
    --    NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
    --    "
 | 
						|
    --::= { deviceConfigEntry 10 }
 | 
						|
 | 
						|
--devicePFlu  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display device power fluctuation threshold.
 | 
						|
    --    Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
 | 
						|
    --    When this value is -3000,it indicate this is NULL.
 | 
						|
    --    When set this value to -3000, indicate set this object as NULL.
 | 
						|
    --    NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
    --    "
 | 
						|
    --::= { deviceConfigEntry 11 }
 | 
						|
 | 
						|
--deviceMinPDMT  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER (0..2000)
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display or set device minimum power dissipation measurement threshold."
 | 
						|
    --::= { deviceConfigEntry 8 }
 | 
						|
deviceMaxPDMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (0..999990 | -3000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set device maximum power dissipation measurement threshold.
 | 
						|
        Example: range 0.0 ~ 99999.0 represents 0~999990
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { deviceConfigEntry 8 }
 | 
						|
--devicePDFlu  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER (0..2000)
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
     --   "Display device power dissipation fluctuation threshold."
 | 
						|
    --::= { deviceConfigEntry 13 }
 | 
						|
 | 
						|
 | 
						|
deviceSensorTresholdTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF DeviceSensorTresholdEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Device environment value table"
 | 
						|
    ::= { device 7 }
 | 
						|
 | 
						|
deviceSensorTresholdEntry OBJECT-TYPE
 | 
						|
    SYNTAX DeviceSensorTresholdEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Device's sensor Environment entry containing sensor info."
 | 
						|
    INDEX { deviceSensorTresholdIndex }
 | 
						|
     ::= { deviceSensorTresholdTable 1 }
 | 
						|
 | 
						|
DeviceSensorTresholdEntry ::=
 | 
						|
    SEQUENCE {
 | 
						|
        deviceSensorTresholdIndex
 | 
						|
            INTEGER,
 | 
						|
        sensorMinTempMT
 | 
						|
            INTEGER,
 | 
						|
        sensorMaxTempMT
 | 
						|
            INTEGER,
 | 
						|
 | 
						|
		sensorMinHumMT
 | 
						|
            INTEGER,
 | 
						|
		sensorMaxHumMT
 | 
						|
            INTEGER,
 | 
						|
		sensorMinPressMT
 | 
						|
            INTEGER,
 | 
						|
        sensorMaxPressMT
 | 
						|
            INTEGER
 | 
						|
        --sensorTempFlu
 | 
						|
            --INTEGER,
 | 
						|
        --sensorHumFlu
 | 
						|
			--INTEGER,
 | 
						|
		--sensorPressFlu
 | 
						|
            --INTEGER
 | 
						|
    }
 | 
						|
 | 
						|
deviceSensorTresholdIndex  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..6)
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Index of sensor number"
 | 
						|
    ::= { deviceSensorTresholdEntry 1 }
 | 
						|
 | 
						|
sensorMinTempMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (-200..600 | -3000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set sensor minimum temperature measurement threshold.
 | 
						|
        Example: range -20.0 ~ 60.0 represents -200~600
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { deviceSensorTresholdEntry 2 }
 | 
						|
sensorMaxTempMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (-200..600 | -3000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set sensor maximum temperature measurement threshold.
 | 
						|
        Example: range -20.0 ~ 60.0 represents -200~600
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { deviceSensorTresholdEntry 3 }
 | 
						|
 | 
						|
sensorMinHumMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (150..950 | -3000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set sensor minimum humidity measurement threshold.
 | 
						|
        Example: range 15.0 ~ 95.0 represents 150~950
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { deviceSensorTresholdEntry 4 }
 | 
						|
sensorMaxHumMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (150..950 | -3000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set sensor maximum humidity measurement threshold.
 | 
						|
        Example: range 15.0 ~ 95.0 represents 150~950
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { deviceSensorTresholdEntry 5 }
 | 
						|
 | 
						|
sensorMinPressMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (-2500..2500 | -3000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set sensor minimum pressure measurement threshold.
 | 
						|
        Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { deviceSensorTresholdEntry 6 }
 | 
						|
 | 
						|
sensorMaxPressMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (-2500..2500 | -3000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set sensor maximum pressure measurement threshold.
 | 
						|
        Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { deviceSensorTresholdEntry 7 }
 | 
						|
 | 
						|
--sensorTempFlu  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display sensor temperature fluctuation threshold.
 | 
						|
    --    Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
 | 
						|
    --    When this value is -3000,it indicate this is NULL.
 | 
						|
    --    When set this value to -3000, indicate set this object as NULL.
 | 
						|
    --    NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
    --    "
 | 
						|
    --::= { deviceEnvironmentEntry 8 }
 | 
						|
 | 
						|
--sensorHumFlu  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display sensor humidity fluctuation threshold.
 | 
						|
    --    Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
 | 
						|
    --    When this value is -3000,it indicate this is NULL.
 | 
						|
    --    When set this value to -3000, indicate set this object as NULL.
 | 
						|
    --    NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
    --    "
 | 
						|
    --::= { deviceEnvironmentEntry 9 }
 | 
						|
 | 
						|
 | 
						|
--sensorPressFlu  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display sensor pressure fluctuation threshold.
 | 
						|
    --    Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
 | 
						|
    --    When this value is -3000,it indicate this is NULL.
 | 
						|
    --    When set this value to -3000, indicate set this object as NULL.
 | 
						|
    --    NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
    --    "
 | 
						|
    --::= { deviceEnvironmentEntry 10 }
 | 
						|
 | 
						|
deviceOutletControl OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), nostatus(3), not-support(4) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " This function is used for all outlet ports control.
 | 
						|
          Set off(1) to turn off for all outlet ports.
 | 
						|
          Set on(2) to turn on for all outlet ports.
 | 
						|
          Get this object always return nostatus(3), because there is no device status.
 | 
						|
 | 
						|
        "
 | 
						|
    ::= { device 8 }
 | 
						|
 | 
						|
deviceOutletReboot OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2), not-support(4)  }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " This function is used for all outlet ports to reboot.
 | 
						|
          Only when outlet status is ON can do outlet reboot action to all ports.
 | 
						|
          Set yes(2) to reboot all outlet ports.
 | 
						|
          Get this object always return no(1).
 | 
						|
		"
 | 
						|
    ::= { device 9 }
 | 
						|
 | 
						|
switchable OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2), mix(3)}
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " Outlet is switchable or not."
 | 
						|
    ::= { device 10 }
 | 
						|
 | 
						|
perportreading OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " Outlet is per-port reading or not."
 | 
						|
    ::= { device 11 }
 | 
						|
 | 
						|
sensornumber OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " Sensor number."
 | 
						|
    ::= { device 12 }
 | 
						|
 | 
						|
outletnumber OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " Outlet number."
 | 
						|
    ::= { device 13 }
 | 
						|
 | 
						|
banknumber OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " Bank number."
 | 
						|
    ::= { device 14 }
 | 
						|
 | 
						|
--chainnumber OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER
 | 
						|
    --MAX-ACCESS read-only
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    " The slave device number."
 | 
						|
    --::= { device 15 }
 | 
						|
 | 
						|
doorSensorStatus OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { close(0), open(1), not-attached(2), not-support(4) }
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " Display door sensor status.
 | 
						|
      	  close(0) represents door close.
 | 
						|
	  open(1) represents door open.
 | 
						|
	  not-attached(2) represents door sensor don't attach to device."
 | 
						|
    ::= { doorSensor 1 }
 | 
						|
 | 
						|
doorSensorType OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { notinstalled(0), photo(1), inductiveproximity(2), reed(3) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Door Sensor Type Selection"
 | 
						|
    ::= { doorSensor 2 }
 | 
						|
--
 | 
						|
-- pop
 | 
						|
enablePOPmode OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER {no(1), yes(2)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " Enable/Disable POP mode."
 | 
						|
    ::= { pop 1 }
 | 
						|
 | 
						|
popThreshold OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " (-1)means default value same as Bank Max Current 16 A.
 | 
						|
 | 
						|
          Example: range 0.0~32.0 represents 0~320
 | 
						|
          You can define the POP threshold or set as default(-1) value."
 | 
						|
    ::= { pop 2 }
 | 
						|
 | 
						|
enableOutletPOPmode OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER {no(1), yes(2), not-support(3)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " Enable/Disable Outlet POP mode."
 | 
						|
    ::= { pop 3 }
 | 
						|
 | 
						|
enableLIFOPOPmode OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER {no(1), yes(2), not-support(3)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " Enable/Disable LIFO POP mode."
 | 
						|
    ::= { pop 4 }
 | 
						|
 | 
						|
enablePriorityPOPmode OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER {no(1), yes(2), not-support(3)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " Enable/Disable Priority POP mode."
 | 
						|
    ::= { pop 5 }
 | 
						|
 | 
						|
-- CAP
 | 
						|
enableCAPmode OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER {no(1), yes(2)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " Enable/Disable CAP mode."
 | 
						|
    ::= { cap 1 }
 | 
						|
 | 
						|
outletCAPTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF OutletCAPEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Outlet CAP table"
 | 
						|
    ::= { cap 2 }
 | 
						|
 | 
						|
outletCAPEntry OBJECT-TYPE
 | 
						|
    SYNTAX OutletCAPEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Outlet CAP entry containing CAP info."
 | 
						|
    INDEX { outletCAPIndex }
 | 
						|
     ::= { outletCAPTable 1 }
 | 
						|
 | 
						|
OutletCAPEntry ::=
 | 
						|
    SEQUENCE {
 | 
						|
        outletCAPIndex
 | 
						|
            INTEGER,
 | 
						|
        outletCAPPriority
 | 
						|
            INTEGER
 | 
						|
    }
 | 
						|
 | 
						|
outletCAPIndex  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..40)
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Index of outlet's CAP configuration"
 | 
						|
    ::= { outletCAPEntry 1 }
 | 
						|
 | 
						|
outletCAPPriority  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (0..99)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the CAP Priority of outlet.
 | 
						|
		Priority 0 means this outlet does not support this OID."
 | 
						|
    ::= { outletCAPEntry 2 }
 | 
						|
-- ontlet control init mode
 | 
						|
 | 
						|
outletInitMode OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER {no-delaytime(1), delaytime(2), not-support(3)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "choose outlet init mode you want."
 | 
						|
    ::= { device 19 }
 | 
						|
 | 
						|
 | 
						|
 | 
						|
-- integer value
 | 
						|
 | 
						|
--deviceIntegerValueTable OBJECT-TYPE
 | 
						|
--    SYNTAX SEQUENCE OF DeviceIntegerValueEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device value table. This table displays device's current, voltage, power and
 | 
						|
--		 power dissipation.
 | 
						|
--		"
 | 
						|
--    ::= { device 99 }
 | 
						|
 | 
						|
--deviceIntegerValueEntry OBJECT-TYPE
 | 
						|
--    SYNTAX DeviceIntegerValueEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Single deviceValue entry containing device info."
 | 
						|
--    INDEX { deviceIntegerValueIndex }
 | 
						|
--     ::= { deviceIntegerValueTable 1 }
 | 
						|
 | 
						|
--DeviceIntegerValueEntry ::=
 | 
						|
--    SEQUENCE {
 | 
						|
--        deviceIntegerValueIndex
 | 
						|
--            INTEGER,
 | 
						|
--        deviceIntegerCurrent
 | 
						|
--            INTEGER,
 | 
						|
--        deviceIntegerVoltage
 | 
						|
--            INTEGER,
 | 
						|
--		deviceIntegerPower
 | 
						|
--            INTEGER,
 | 
						|
--		deviceIntegerPowerDissipation
 | 
						|
--            INTEGER
 | 
						|
        --inputMaxVoltage
 | 
						|
        --	INTEGER,
 | 
						|
        --inputMaxCurrent
 | 
						|
        --	INTEGER,
 | 
						|
        --powerCapacity
 | 
						|
        --	INTEGER
 | 
						|
        --devicePowerFactor
 | 
						|
        --  INTEGER
 | 
						|
--    }
 | 
						|
 | 
						|
--deviceIntegerValueIndex  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (1)
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Index of deviceValue."
 | 
						|
--    ::= { deviceIntegerValueEntry 1 }
 | 
						|
 | 
						|
--deviceIntegerCurrent  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device electric current value.
 | 
						|
--         This value indicates that 1,000 times.
 | 
						|
--        "
 | 
						|
--    ::= { deviceIntegerValueEntry 2 }
 | 
						|
 | 
						|
--deviceIntegerVoltage  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device voltage value.
 | 
						|
--        This value indicates that 1,000 times
 | 
						|
--        "
 | 
						|
--    ::= { deviceIntegerValueEntry 3 }
 | 
						|
 | 
						|
--deviceIntegerPower  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device power value.
 | 
						|
--        This value indicates that 1,000 times.
 | 
						|
--        "
 | 
						|
--    ::= { deviceIntegerValueEntry 4 }
 | 
						|
 | 
						|
--deviceIntegerPowerDissipation  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device power dissipation value.
 | 
						|
--        This value indicates that 1,000 times
 | 
						|
--        "
 | 
						|
--    ::= { deviceIntegerValueEntry 5 }
 | 
						|
 | 
						|
--inputMaxVoltage  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device input Voltage value. unit:(V)"
 | 
						|
--    ::= { deviceValueEntry 6 }
 | 
						|
 | 
						|
--inputMaxCurrent  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device input Current value. unit:(A)"
 | 
						|
--    ::= { deviceValueEntry 7 }
 | 
						|
 | 
						|
--powerCapacity  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device power Capacity value.unit:(VA)"
 | 
						|
--    ::= { deviceValueEntry 8 }
 | 
						|
 | 
						|
--devicePowerFactor  OBJECT-TYPE
 | 
						|
--    SYNTAX DisplayString
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device power Factor value."
 | 
						|
--    ::= { deviceValueEntry 9 }
 | 
						|
--
 | 
						|
 | 
						|
--sensorIntegerValueTable OBJECT-TYPE
 | 
						|
--    SYNTAX SEQUENCE OF SensorIntegerValueEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device's sensor value table. This table displays sensor's temperature, humidity and
 | 
						|
--		 pressure.
 | 
						|
--		"
 | 
						|
--    ::= { device 100 }
 | 
						|
 | 
						|
--sensorIntegerValueEntry OBJECT-TYPE
 | 
						|
--    SYNTAX SensorIntegerValueEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Single device's sensor value entry containing device info."
 | 
						|
--    INDEX { sensorIntegerValueIndex }
 | 
						|
--     ::= { sensorIntegerValueTable 1 }
 | 
						|
 | 
						|
--SensorIntegerValueEntry ::=
 | 
						|
--    SEQUENCE {
 | 
						|
--    		sensorIntegerValueIndex
 | 
						|
--    			INTEGER,
 | 
						|
--			sensorIntegerTemperature
 | 
						|
--            	INTEGER,
 | 
						|
--			sensorIntegerHumidity
 | 
						|
--				INTEGER,
 | 
						|
--			sensorIntegerPressure
 | 
						|
--				INTEGER
 | 
						|
		--sensorIntegerProperty
 | 
						|
		--	INTEGER
 | 
						|
--    }
 | 
						|
 | 
						|
--sensorIntegerValueIndex  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (1..6)
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Index of sensor number."
 | 
						|
--    ::= { sensorIntegerValueEntry 1 }
 | 
						|
 | 
						|
--sensorIntegerTemperature  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Sensor's Temperature value.
 | 
						|
--        This value indicates that 1,000 times.
 | 
						|
--        Value -300000 represents empty value."
 | 
						|
--    ::= { sensorIntegerValueEntry 2 }
 | 
						|
 | 
						|
--sensorIntegerHumidity  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Sensor's Humidity value.
 | 
						|
--        This value indicates that 1,000 times.
 | 
						|
--        Value -300000 represents empty value."
 | 
						|
--    ::= { sensorIntegerValueEntry 3 }
 | 
						|
 | 
						|
--sensorIntegerPressure  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Sensor's Pressure value.
 | 
						|
--        This value indicates that 1,000 times.
 | 
						|
--        Value -300000 represents empty value."
 | 
						|
--    ::= { sensorIntegerValueEntry 4 }
 | 
						|
 | 
						|
--sensorIntegerProperty  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER { intake(1), exhaust(2), floor(3) }
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Sensor's Property."
 | 
						|
--    ::= { sensorIntegerValueEntry 5 }
 | 
						|
 | 
						|
-- Device Control End
 | 
						|
 | 
						|
-- Outlet Control
 | 
						|
outletValueTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF OutletValueEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display total outlet value table"
 | 
						|
    ::= { outlet 1 }
 | 
						|
 | 
						|
outletValueEntry OBJECT-TYPE
 | 
						|
    SYNTAX OutletValueEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Single outletValue entry containing outlet info."
 | 
						|
    INDEX { outletValueIndex }
 | 
						|
     ::= { outletValueTable 1 }
 | 
						|
 | 
						|
OutletValueEntry ::=
 | 
						|
    SEQUENCE {
 | 
						|
        outletValueIndex
 | 
						|
            INTEGER,
 | 
						|
        outletCurrent
 | 
						|
            DisplayString,
 | 
						|
        outletVoltage
 | 
						|
            DisplayString,
 | 
						|
		outletPower
 | 
						|
            DisplayString,
 | 
						|
		outletPowerDissipation
 | 
						|
            DisplayString,
 | 
						|
        outletMaxCurrent
 | 
						|
        	INTEGER,
 | 
						|
        outletPowerFactor
 | 
						|
        	DisplayString
 | 
						|
    }
 | 
						|
 | 
						|
outletValueIndex  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..30)
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Index of outlet number"
 | 
						|
    ::= { outletValueEntry 1 }
 | 
						|
outletCurrent  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Outlet electric current value.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { outletValueEntry 2 }
 | 
						|
outletVoltage  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Outlet voltage value.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { outletValueEntry 3 }
 | 
						|
outletPower  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Outlet power value.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { outletValueEntry 4 }
 | 
						|
outletPowerDissipation  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Outlet power dissipation value.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { outletValueEntry 5 }
 | 
						|
 | 
						|
outletMaxCurrent  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Outlet Max Current value. unit: (A).
 | 
						|
        If the device does not support this OID, we show value 0.
 | 
						|
        "
 | 
						|
    ::= { outletValueEntry 6 }
 | 
						|
 | 
						|
outletPowerFactor  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Outlet Power Factor value.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { outletValueEntry 7 }
 | 
						|
 | 
						|
outlet1Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 1 status. Can't set pending status."
 | 
						|
    ::= { outlet 2 }
 | 
						|
 | 
						|
outlet2Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 2 status. Can't set pending status."
 | 
						|
    ::= { outlet 3 }
 | 
						|
outlet3Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 3 status. Can't set pending status."
 | 
						|
    ::= { outlet 4 }
 | 
						|
outlet4Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 4 status. Can't set pending status."
 | 
						|
    ::= { outlet 5 }
 | 
						|
outlet5Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 5 status. Can't set pending status."
 | 
						|
    ::= { outlet 6 }
 | 
						|
outlet6Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 6 status. Can't set pending status."
 | 
						|
    ::= { outlet 7 }
 | 
						|
outlet7Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 7 status. Can't set pending status."
 | 
						|
    ::= { outlet 8 }
 | 
						|
outlet8Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 8 status. Can't set pending status."
 | 
						|
    ::= { outlet 9 }
 | 
						|
 | 
						|
outlet9Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 9 status. Can't set pending status."
 | 
						|
    ::= { outlet 11 }
 | 
						|
 | 
						|
outlet10Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 10 status. Can't set pending status."
 | 
						|
    ::= { outlet 12 }
 | 
						|
 | 
						|
outlet11Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 11 status. Can't set pending status."
 | 
						|
    ::= { outlet 13 }
 | 
						|
 | 
						|
outlet12Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 12 status. Can't set pending status."
 | 
						|
    ::= { outlet 14 }
 | 
						|
 | 
						|
outlet13Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 13 status. Can't set pending status."
 | 
						|
    ::= { outlet 15 }
 | 
						|
 | 
						|
outlet14Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 14 status. Can't set pending status."
 | 
						|
    ::= { outlet 16 }
 | 
						|
 | 
						|
outlet15Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 15 status. Can't set pending status."
 | 
						|
    ::= { outlet 17 }
 | 
						|
 | 
						|
outlet16Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 16 status. Can't set pending status."
 | 
						|
    ::= { outlet 18 }
 | 
						|
 | 
						|
outlet17Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 17 status. Can't set pending status."
 | 
						|
    ::= { outlet 19 }
 | 
						|
 | 
						|
outlet18Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 18 status. Can't set pending status."
 | 
						|
    ::= { outlet 20 }
 | 
						|
 | 
						|
outlet19Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 19 status. Can't set pending status."
 | 
						|
    ::= { outlet 21 }
 | 
						|
 | 
						|
outlet20Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 20 status. Can't set pending status."
 | 
						|
    ::= { outlet 22 }
 | 
						|
 | 
						|
outlet21Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 21 status. Can't set pending status."
 | 
						|
    ::= { outlet 23 }
 | 
						|
 | 
						|
outlet22Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 22 status. Can't set pending status."
 | 
						|
    ::= { outlet 24 }
 | 
						|
 | 
						|
outlet23Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 23 status. Can't set pending status."
 | 
						|
    ::= { outlet 25 }
 | 
						|
 | 
						|
outlet24Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 24 status. Can't set pending status."
 | 
						|
    ::= { outlet 26 }
 | 
						|
 | 
						|
outlet25Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 25 status. Can't set pending status."
 | 
						|
    ::= { outlet 27 }
 | 
						|
 | 
						|
outlet26Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 26 status. Can't set pending status."
 | 
						|
    ::= { outlet 28 }
 | 
						|
 | 
						|
outlet27Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 27 status. Can't set pending status."
 | 
						|
    ::= { outlet 29 }
 | 
						|
 | 
						|
outlet28Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 28 status. Can't set pending status."
 | 
						|
    ::= { outlet 30 }
 | 
						|
 | 
						|
outlet29Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 29 status. Can't set pending status."
 | 
						|
    ::= { outlet 31 }
 | 
						|
 | 
						|
outlet30Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 30 status. Can't set pending status."
 | 
						|
    ::= { outlet 32 }
 | 
						|
 | 
						|
outlet31Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 31 status. Can't set pending status."
 | 
						|
    ::= { outlet 33 }
 | 
						|
 | 
						|
outlet32Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 32 status. Can't set pending status."
 | 
						|
    ::= { outlet 34 }
 | 
						|
 | 
						|
outlet33Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 33 status. Can't set pending status."
 | 
						|
    ::= { outlet 35 }
 | 
						|
 | 
						|
 | 
						|
outlet34Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 34 status. Can't set pending status."
 | 
						|
    ::= { outlet 36 }
 | 
						|
 | 
						|
outlet35Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 35 status. Can't set pending status."
 | 
						|
    ::= { outlet 37 }
 | 
						|
 | 
						|
outlet36Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 36 status. Can't set pending status."
 | 
						|
    ::= { outlet 38 }
 | 
						|
 | 
						|
outlet37Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 37 status. Can't set pending status."
 | 
						|
    ::= { outlet 39 }
 | 
						|
 | 
						|
outlet38Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 38 status. Can't set pending status."
 | 
						|
    ::= { outlet 40 }
 | 
						|
 | 
						|
outlet39Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 39 status. Can't set pending status."
 | 
						|
    ::= { outlet 41 }
 | 
						|
 | 
						|
outlet40Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 40 status. Can't set pending status."
 | 
						|
    ::= { outlet 42 }
 | 
						|
 | 
						|
outlet41Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 41 status. Can't set pending status."
 | 
						|
    ::= { outlet 43 }
 | 
						|
 | 
						|
outlet42Status OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display and control outlet 42 status. Can't set pending status."
 | 
						|
    ::= { outlet 44 }
 | 
						|
 | 
						|
--
 | 
						|
 | 
						|
outletSwitchableTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF OutletSwitchableEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "
 | 
						|
		"
 | 
						|
    ::= { outlet 70 }
 | 
						|
 | 
						|
outletSwitchableEntry OBJECT-TYPE
 | 
						|
    SYNTAX OutletSwitchableEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        ""
 | 
						|
    INDEX { outletSwitchableIndex }
 | 
						|
     ::= { outletSwitchableTable 1 }
 | 
						|
 | 
						|
 OutletSwitchableEntry ::=
 | 
						|
    SEQUENCE {
 | 
						|
        outletSwitchableIndex
 | 
						|
            INTEGER,
 | 
						|
        outletSwitchable
 | 
						|
            INTEGER
 | 
						|
 | 
						|
    }
 | 
						|
 | 
						|
outletSwitchableIndex  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..30)
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Index of outlet number.
 | 
						|
        "
 | 
						|
    ::= { outletSwitchableEntry 1 }
 | 
						|
 | 
						|
outletSwitchable  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER {no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "
 | 
						|
        "
 | 
						|
    ::= { outletSwitchableEntry 2 }
 | 
						|
 | 
						|
 | 
						|
--outlet integer value
 | 
						|
 | 
						|
--outletIntegerValueTable OBJECT-TYPE
 | 
						|
--    SYNTAX SEQUENCE OF OutletIntegerValueEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display total outlet value table"
 | 
						|
--    ::= { outlet 99 }
 | 
						|
 | 
						|
--outletIntegerValueEntry OBJECT-TYPE
 | 
						|
--    SYNTAX OutletIntegerValueEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Single outletValue entry containing outlet info."
 | 
						|
--    INDEX { outletIntegerValueIndex }
 | 
						|
--     ::= { outletIntegerValueTable 1 }
 | 
						|
 | 
						|
--OutletIntegerValueEntry ::=
 | 
						|
--    SEQUENCE {
 | 
						|
--        outletIntegerValueIndex
 | 
						|
--            INTEGER,
 | 
						|
--        outletIntegerCurrent
 | 
						|
--            INTEGER,
 | 
						|
--        outletIntegerVoltage
 | 
						|
--            INTEGER,
 | 
						|
--		outletIntegerPower
 | 
						|
--            INTEGER,
 | 
						|
--		outletIntegerPowerDissipation
 | 
						|
--            INTEGER
 | 
						|
--         }
 | 
						|
 | 
						|
--outletIntegerValueIndex  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (1..30)
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Index of outlet number.
 | 
						|
--        "
 | 
						|
--    ::= { outletIntegerValueEntry 1 }
 | 
						|
 | 
						|
--outletIntegerCurrent  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Outlet electric current value.
 | 
						|
--        This value indicates that 1,000 times.
 | 
						|
--        "
 | 
						|
--    ::= { outletIntegerValueEntry 2 }
 | 
						|
 | 
						|
--outletIntegerVoltage  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Outlet voltage value.
 | 
						|
--        This value indicates that 1,000 times.
 | 
						|
--        "
 | 
						|
--    ::= { outletIntegerValueEntry 3 }
 | 
						|
 | 
						|
--outletIntegerPower  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Outlet power value.
 | 
						|
--        This value indicates that 1,000 times."
 | 
						|
--    ::= { outletIntegerValueEntry 4 }
 | 
						|
 | 
						|
--outletIntegerPowerDissipation  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Outlet power dissipation value.
 | 
						|
--        This value indicates that 1,000 times."
 | 
						|
--    ::= { outletIntegerValueEntry 5 }
 | 
						|
 | 
						|
 | 
						|
 | 
						|
 | 
						|
 | 
						|
outletConfigTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF OutletConfigEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Outlet configuration table"
 | 
						|
    ::= { outlet 10 }
 | 
						|
 | 
						|
outletConfigEntry OBJECT-TYPE
 | 
						|
    SYNTAX OutletConfigEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Outlet Config entry containing outlet info."
 | 
						|
    INDEX { outletConfigIndex }
 | 
						|
     ::= { outletConfigTable 1 }
 | 
						|
 | 
						|
OutletConfigEntry ::=
 | 
						|
    SEQUENCE {
 | 
						|
        outletConfigIndex
 | 
						|
            INTEGER,
 | 
						|
		outletName
 | 
						|
            DisplayString,
 | 
						|
        outletConfirmation
 | 
						|
            INTEGER,
 | 
						|
        outletOnDelayTime
 | 
						|
            INTEGER,
 | 
						|
		outletOffDelayTime
 | 
						|
            INTEGER,
 | 
						|
		outletShutdownMethod
 | 
						|
            INTEGER,
 | 
						|
        outletMAC
 | 
						|
            DisplayString,
 | 
						|
		outletMinCurMT
 | 
						|
            INTEGER,
 | 
						|
		outletMaxCurMT
 | 
						|
            INTEGER,
 | 
						|
 | 
						|
        outletMinVolMT
 | 
						|
            INTEGER,
 | 
						|
		outletMaxVolMT
 | 
						|
            INTEGER,
 | 
						|
 | 
						|
		outletMinPMT
 | 
						|
            INTEGER,
 | 
						|
        outletMaxPMT
 | 
						|
            INTEGER,
 | 
						|
		--outletMinPDMT
 | 
						|
            --INTEGER,
 | 
						|
        outletMaxPDMT
 | 
						|
            INTEGER
 | 
						|
        --outletCurFlu
 | 
						|
            --INTEGER,
 | 
						|
        --outletVolFlu
 | 
						|
            --INTEGER,
 | 
						|
        --outletPFlu
 | 
						|
            --INTEGER
 | 
						|
        --outletPDFlu
 | 
						|
            --INTEGER
 | 
						|
    }
 | 
						|
 | 
						|
outletConfigIndex  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..30)
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Index of outlet number"
 | 
						|
    ::= { outletConfigEntry 1 }
 | 
						|
outletName  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the name of outlet.
 | 
						|
        If the device does not support this OID, we show n/a.
 | 
						|
        string length: 0~15
 | 
						|
        NOTE: Input string as /empty to set this object to NULL.
 | 
						|
        "
 | 
						|
    ::= { outletConfigEntry 2 }
 | 
						|
outletConfirmation  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) , noauth(3), not-support(4)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the confirmation of outlet."
 | 
						|
    ::= { outletConfigEntry 3 }
 | 
						|
outletOnDelayTime  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (0..999 | -1)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the ON delay time of outlet.
 | 
						|
        When this model does not support the OID, we show value -1. "
 | 
						|
    ::= { outletConfigEntry 4 }
 | 
						|
outletOffDelayTime  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (0..999 | -1)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the OFF delay time of outlet.
 | 
						|
        When this model does not support the OID, we show value -1. "
 | 
						|
    ::= { outletConfigEntry 5 }
 | 
						|
outletShutdownMethod  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { kill-the-power(1), wake-on-lan(2), after-ac-back(3), not-support(4)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the shutdown mehtod of outlet."
 | 
						|
    ::= { outletConfigEntry 6 }
 | 
						|
outletMAC  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the MAC address of ShutdownMethod.
 | 
						|
        If the device does not support this OID, we show n/a.
 | 
						|
        string length: 12
 | 
						|
        "
 | 
						|
    ::= { outletConfigEntry 7 }
 | 
						|
outletMinCurMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the outlet minimum electric current measurment threshold.
 | 
						|
         Example: range 0.0 ~16.0 rerpresnts 0~160
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { outletConfigEntry 8 }
 | 
						|
outletMaxCurMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the outlet maximum electric current measurment threshold.
 | 
						|
         Example: range 0.0 ~16.0 represents 0~160
 | 
						|
         NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { outletConfigEntry 9 }
 | 
						|
 | 
						|
outletMinVolMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (900..2600 | -3000 | -2000000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the outlet minimum voltage measurment threshold.
 | 
						|
        Example: range 90.0 ~260.0 represents 900~2600
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { outletConfigEntry 10 }
 | 
						|
outletMaxVolMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (900..2600 | -3000 | -2000000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the outlet maximum voltage measurment threshold.
 | 
						|
        Example: range 90.0 ~260.0 represents 900~2600
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { outletConfigEntry 11 }
 | 
						|
 | 
						|
outletMinPMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (0..99999 | -3000 | -2000000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the outlet minimum power measurment threshold.
 | 
						|
        Example: range 0.0 ~ 9999.9 represents 0~99999
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { outletConfigEntry 12 }
 | 
						|
outletMaxPMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (0..99999 | -3000 | -2000000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the outlet maximum power measurment threshold.
 | 
						|
        Example: range 0.0 ~ 9999.9 represents 0~99999
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { outletConfigEntry 13 }
 | 
						|
 | 
						|
--outletMinPDMT  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER (0..100)
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display or set the outlet minimum power dissipation measurment threshold ."
 | 
						|
    --::= { outletConfigEntry 14 }
 | 
						|
outletMaxPDMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (0..999990 | -3000 | -2000000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the outlet maximum power dissipation measurment threshold.
 | 
						|
        Example: range 0.0 ~ 99999.0 represents 0~999990
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { outletConfigEntry 14 }
 | 
						|
 | 
						|
--outletCurFlu  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display the outlet electric current fluctuation threshold.
 | 
						|
    --    Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
 | 
						|
    --    When this value is -3000,it indicate this is NULL.
 | 
						|
    --    When set this value to -3000, indicate set this object as NULL.
 | 
						|
    --    NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
    --    "
 | 
						|
    --::= { outletConfigEntry 15 }
 | 
						|
 | 
						|
--outletVolFlu  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display the outlet voltage fluctuation threshold.
 | 
						|
    --    Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
 | 
						|
    --    When this value is -3000,it indicate this is NULL.
 | 
						|
    --    When set this value to -3000, indicate set this object as NULL.
 | 
						|
    --    NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
    --    "
 | 
						|
    --::= { outletConfigEntry 16 }
 | 
						|
--outletPFlu  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display the outlet power fluctuation threshold.
 | 
						|
    --    Fluctuation Range = (MaxThreshold-MinThreshold)/2 x10
 | 
						|
    --    When this value is -3000,it indicate this is NULL.
 | 
						|
    --    When set this value to -3000, indicate set this object as NULL.
 | 
						|
    --    NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
    --    "
 | 
						|
    --::= { outletConfigEntry 17 }
 | 
						|
 | 
						|
--outletPDFlu  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER (0..100)
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display the outlet power dissipation fluctuation threshold ."
 | 
						|
    --::= { outletConfigEntry 19 }
 | 
						|
 | 
						|
-- Outlet Control End
 | 
						|
-- Bank control
 | 
						|
breakerStatusTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF BreakerStatusEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display total bank value table"
 | 
						|
    ::= { bank 1 }
 | 
						|
 | 
						|
breakerStatusEntry OBJECT-TYPE
 | 
						|
    SYNTAX BreakerStatusEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Single bankValue entry containing bank info."
 | 
						|
    INDEX { breakerStatusIndex }
 | 
						|
     ::= { breakerStatusTable 1 }
 | 
						|
 | 
						|
BreakerStatusEntry ::=
 | 
						|
    SEQUENCE {
 | 
						|
        breakerStatusIndex
 | 
						|
            INTEGER,
 | 
						|
        breakerStatus
 | 
						|
            INTEGER
 | 
						|
            }
 | 
						|
 | 
						|
breakerStatusIndex  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..30)
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Index of breaker number."
 | 
						|
    ::= { breakerStatusEntry 1 }
 | 
						|
 | 
						|
breakerStatus  OBJECT-TYPE
 | 
						|
   SYNTAX INTEGER { off(1), on(2), not-support(3)}
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Breaker status."
 | 
						|
    ::= { breakerStatusEntry 2 }
 | 
						|
 | 
						|
 | 
						|
bankValueTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF BankValueEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display total bank value table"
 | 
						|
    ::= { bank 2 }
 | 
						|
 | 
						|
bankValueEntry OBJECT-TYPE
 | 
						|
    SYNTAX BankValueEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Single bankValue entry containing bank info."
 | 
						|
    INDEX { bankValueIndex }
 | 
						|
     ::= { bankValueTable 1 }
 | 
						|
 | 
						|
BankValueEntry ::=
 | 
						|
    SEQUENCE {
 | 
						|
        bankValueIndex
 | 
						|
            INTEGER,
 | 
						|
        bankCurrent
 | 
						|
            DisplayString,
 | 
						|
        bankVoltage
 | 
						|
            DisplayString,
 | 
						|
		bankPower
 | 
						|
            DisplayString,
 | 
						|
		bankPowerDissipation
 | 
						|
            DisplayString,
 | 
						|
        bankMaxCurrent
 | 
						|
        	INTEGER,
 | 
						|
        bankAttachStatus
 | 
						|
        	INTEGER,
 | 
						|
        bankPowerFactor
 | 
						|
        	DisplayString
 | 
						|
    }
 | 
						|
 | 
						|
bankValueIndex  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..30)
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Index of bank number"
 | 
						|
    ::= { bankValueEntry 1 }
 | 
						|
bankCurrent  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Bank electric current value.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { bankValueEntry 2 }
 | 
						|
bankVoltage  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Bank voltage value.
 | 
						|
        We put this OID to write access type for user to set the reference voltage on EC1000 model.
 | 
						|
        And the setting should be the numbers. You can set 0 to clear the setting.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { bankValueEntry 3 }
 | 
						|
 | 
						|
bankPower  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Bank power value.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { bankValueEntry 4 }
 | 
						|
 | 
						|
bankPowerDissipation  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Bank power dissipation value.
 | 
						|
        If this measurement value is not available, it returns: N/A.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { bankValueEntry 5 }
 | 
						|
 | 
						|
 | 
						|
bankMaxCurrent  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "The Bank Max Current value. unit: (A)
 | 
						|
        EC1000:0A~320A
 | 
						|
        "
 | 
						|
    ::= { bankValueEntry 6 }
 | 
						|
 | 
						|
bankAttachStatus  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { noattached(1), attached(2), error(3), noexisted(4) }
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "The status of Energy sensor Bank attached status."
 | 
						|
    ::= { bankValueEntry 7 }
 | 
						|
 | 
						|
bankPowerFactor  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Bank Power Factor value.
 | 
						|
        If the device does not support this OID, it returns: not-support."
 | 
						|
    ::= { bankValueEntry 8 }
 | 
						|
 | 
						|
bankConfigTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF BankConfigEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Bank configuration table"
 | 
						|
    ::= { bank 3 }
 | 
						|
 | 
						|
bankConfigEntry OBJECT-TYPE
 | 
						|
    SYNTAX BankConfigEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Bank Config entry containing Bank info."
 | 
						|
    INDEX { bankConfigIndex }
 | 
						|
     ::= { bankConfigTable 1 }
 | 
						|
 | 
						|
BankConfigEntry ::=
 | 
						|
    SEQUENCE {
 | 
						|
        bankConfigIndex
 | 
						|
            INTEGER,
 | 
						|
		bankName
 | 
						|
            DisplayString,
 | 
						|
		bankMinCurMT
 | 
						|
            INTEGER,
 | 
						|
		bankMaxCurMT
 | 
						|
            INTEGER,
 | 
						|
 | 
						|
        bankMinVolMT
 | 
						|
            INTEGER,
 | 
						|
		bankMaxVolMT
 | 
						|
            INTEGER,
 | 
						|
 | 
						|
		bankMinPMT
 | 
						|
            INTEGER,
 | 
						|
        bankMaxPMT
 | 
						|
            INTEGER,
 | 
						|
		--outletMinPDMT
 | 
						|
            --INTEGER,
 | 
						|
        bankMaxPDMT
 | 
						|
            INTEGER
 | 
						|
        --outletCurFlu
 | 
						|
            --INTEGER,
 | 
						|
        --outletVolFlu
 | 
						|
            --INTEGER,
 | 
						|
        --outletPFlu
 | 
						|
            --INTEGER
 | 
						|
        --outletPDFlu
 | 
						|
            --INTEGER
 | 
						|
    }
 | 
						|
 | 
						|
bankConfigIndex  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..30)
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Index of bank number"
 | 
						|
    ::= { bankConfigEntry 1 }
 | 
						|
 | 
						|
bankName  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the name of bank.
 | 
						|
        When this model does not support the OID, we show n/a.
 | 
						|
        string length: 0~15
 | 
						|
        NOTE: Input string as /empty to set this object to NULL.
 | 
						|
        "
 | 
						|
    ::= { bankConfigEntry 2 }
 | 
						|
 | 
						|
 | 
						|
bankMinCurMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the outlet minimum electric current measurment threshold.
 | 
						|
        Example: range 0.0 ~16.0 rerpresnts 0~160
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { bankConfigEntry 3 }
 | 
						|
 | 
						|
bankMaxCurMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the outlet maximum electric current measurment threshold.
 | 
						|
        Example: range 0.0 ~16.0 represents 0~160
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { bankConfigEntry 4}
 | 
						|
 | 
						|
bankMinVolMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (900..2600 | -3000 | -2000000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the outlet minimum voltage measurment threshold.
 | 
						|
        Example: range 90.0 ~260.0 represents 900~2600
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { bankConfigEntry 5 }
 | 
						|
bankMaxVolMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (900..2600 | -3000 | -2000000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the outlet maximum voltage measurment threshold.
 | 
						|
        Example: range 90.0 ~260.0 represents 900~2600
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { bankConfigEntry 6 }
 | 
						|
 | 
						|
bankMinPMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (0..99999| -3000 | -2000000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the outlet minimum power measurment threshold.
 | 
						|
        Example: range 0.0 ~ 9999.9 represents 0~99999
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { bankConfigEntry 7 }
 | 
						|
bankMaxPMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (0..99999 | -3000 | -2000000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the outlet maximum power measurment threshold.
 | 
						|
        Example: range 0.0 ~ 9999.9 represents 0~99999
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { bankConfigEntry 8 }
 | 
						|
 | 
						|
--outletMinPDMT  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER (0..100)
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display or set the outlet minimum power dissipation measurment threshold ."
 | 
						|
    --::= { outletConfigEntry 14 }
 | 
						|
 | 
						|
bankMaxPDMT  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (0..999990 | -3000 | -2000000)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the outlet maximum power dissipation measurment threshold.
 | 
						|
        Example: range 0.0 ~ 99999.0 represents 0~999990
 | 
						|
        NOTICE: Minimum threshold should be smaller than maximum threshold.
 | 
						|
        Empty value: -3000.
 | 
						|
        If the device does not support this OID, it returns value -2000000."
 | 
						|
    ::= { bankConfigEntry 9 }
 | 
						|
 | 
						|
 | 
						|
bankControlTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF BankControlEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Bank Control table"
 | 
						|
    ::= { bank 4 }
 | 
						|
 | 
						|
bankControlEntry OBJECT-TYPE
 | 
						|
    SYNTAX BankControlEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Bank control entry."
 | 
						|
    INDEX { bankControlIndex }
 | 
						|
     ::= { bankControlTable 1 }
 | 
						|
 | 
						|
BankControlEntry ::=
 | 
						|
    SEQUENCE {
 | 
						|
        bankControlIndex
 | 
						|
            INTEGER,
 | 
						|
		bankControlStatus
 | 
						|
            INTEGER
 | 
						|
    }
 | 
						|
 | 
						|
bankControlIndex  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..4)
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Index of bank number"
 | 
						|
    ::= { bankControlEntry 1 }
 | 
						|
 | 
						|
bankControlStatus  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER {off(1), on(2), reboot(3), nostatus(4), not-support(5)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " This function is used for outlet control of bank.
 | 
						|
          Set off(1) to turn off for outlet control of bank.
 | 
						|
          Set on(2) to turn on for all outlet control of bank.
 | 
						|
          Set reboot(3) to turn on for outlet control of bank.
 | 
						|
          Get this object always return nostatus(3), because there is no bank status.
 | 
						|
        "
 | 
						|
    ::= { bankControlEntry 2 }
 | 
						|
 | 
						|
-- Bank control End
 | 
						|
 | 
						|
 | 
						|
--bankIntegerValueTable OBJECT-TYPE
 | 
						|
--    SYNTAX SEQUENCE OF BankIntegerValueEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display total bank value table"
 | 
						|
--    ::= { bank 99 }
 | 
						|
 | 
						|
--bankIntegerValueEntry OBJECT-TYPE
 | 
						|
--    SYNTAX BankIntegerValueEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Single bankValue entry containing bank info."
 | 
						|
--    INDEX { bankIntegerValueIndex }
 | 
						|
--     ::= { bankIntegerValueTable 1 }
 | 
						|
 | 
						|
--BankIntegerValueEntry ::=
 | 
						|
--    SEQUENCE {
 | 
						|
--        bankIntegerValueIndex
 | 
						|
--            INTEGER,
 | 
						|
--        bankIntegerCurrent
 | 
						|
--            INTEGER,
 | 
						|
--        bankIntegerVoltage
 | 
						|
--            INTEGER,
 | 
						|
--		bankIntegerPower
 | 
						|
--            INTEGER,
 | 
						|
--		bankIntegerPowerDissipation
 | 
						|
--            INTEGER
 | 
						|
        --bankIntegerMaxCurrent
 | 
						|
        --	INTEGER,
 | 
						|
        --bankIntegerAttachStatus
 | 
						|
        --	INTEGER,
 | 
						|
        --bankIntegerPowerFactor
 | 
						|
        	--INTEGER
 | 
						|
--    }
 | 
						|
 | 
						|
--bankIntegerValueIndex  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (1..30)
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Index of bank number.
 | 
						|
--        "
 | 
						|
--    ::= { bankIntegerValueEntry 1 }
 | 
						|
 | 
						|
--bankIntegerCurrent  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Bank electric current value.
 | 
						|
--        This value indicates that 1,000 times."
 | 
						|
--    ::= { bankIntegerValueEntry 2 }
 | 
						|
--bankIntegerVoltage  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Bank voltage value.
 | 
						|
--        This value indicates that 1,000 times."
 | 
						|
--    ::= { bankIntegerValueEntry 3 }
 | 
						|
 | 
						|
--bankIntegerPower  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Bank power value.
 | 
						|
--        This value indicates that 1,000 times."
 | 
						|
--    ::= { bankIntegerValueEntry 4 }
 | 
						|
 | 
						|
--bankIntegerPowerDissipation  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Bank power dissipation value.
 | 
						|
--        This value indicates that 1,000 times."
 | 
						|
--    ::= { bankIntegerValueEntry 5 }
 | 
						|
 | 
						|
 | 
						|
--bankMaxCurrent  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "The Bank Max Current value. unit: (A)
 | 
						|
--        EC1000:0A~320A
 | 
						|
--        "
 | 
						|
--    ::= { bankValueEntry 6 }
 | 
						|
 | 
						|
--bankAttachStatus  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER { noattached(1), attached(2), error(3) }
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "The status of Energy sensor Bank attached status."
 | 
						|
--    ::= { bankValueEntry 7 }
 | 
						|
 | 
						|
--bankPowerFactor  OBJECT-TYPE
 | 
						|
--    SYNTAX DisplayString
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Bank Power Factor value"
 | 
						|
--    ::= { bankValueEntry 8 }
 | 
						|
 | 
						|
 | 
						|
 | 
						|
-- Device Management
 | 
						|
deviceMAC OBJECT-TYPE
 | 
						|
	SYNTAX DisplayString
 | 
						|
	MAX-ACCESS read-only
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display device MAC address."
 | 
						|
	::= { config 1 }
 | 
						|
 | 
						|
deviceIPv4 OBJECT-TYPE
 | 
						|
	SYNTAX IpAddress
 | 
						|
	MAX-ACCESS read-only
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display device IP address."
 | 
						|
	::= { config 2 }
 | 
						|
 | 
						|
deviceFWversion OBJECT-TYPE
 | 
						|
	SYNTAX DisplayString
 | 
						|
	MAX-ACCESS read-only
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display device FW version."
 | 
						|
	::= { config 3 }
 | 
						|
 | 
						|
-- dashboard settings
 | 
						|
dashboardRow OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER	(1..26)
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set device's dashboard row number."
 | 
						|
	::= { dashBoard 1 }
 | 
						|
 | 
						|
dashboardColumn OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER	(1..26)
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set device's dashboard column number."
 | 
						|
	::= { dashBoard 2 }
 | 
						|
 | 
						|
dashboardRackName OBJECT-TYPE
 | 
						|
	SYNTAX DisplayString
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set device's dashboard rack name.
 | 
						|
		string length: 1~32
 | 
						|
		NOTE: Input string as /empty to set this object to NULL.
 | 
						|
		"
 | 
						|
	::= { dashBoard 3 }
 | 
						|
 | 
						|
httpPort OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER	(1..65535)
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set the HTTP port of PE device."
 | 
						|
	::= { servicePorts 1 }
 | 
						|
 | 
						|
httpsPort OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER	(1..65535)
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set the HTTPs port of PE device."
 | 
						|
	::= { servicePorts 2 }
 | 
						|
 | 
						|
httpsOnlyEnable OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER	{yes(1), no(2) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Enable to use Webpage HTTPs only or disable to use Webpage HTTP/HTTPs"
 | 
						|
	::= { servicePorts 3 }
 | 
						|
 | 
						|
 | 
						|
 | 
						|
staticIPEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set IPv4 address automatically or not"
 | 
						|
    ::= { ipv4config 1 }
 | 
						|
fixedIPv4  OBJECT-TYPE
 | 
						|
    SYNTAX IpAddress
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set fixed IPv4 address"
 | 
						|
    ::= { ipv4config 2 }
 | 
						|
subnetMask  OBJECT-TYPE
 | 
						|
    SYNTAX IpAddress
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set subnet mask address"
 | 
						|
    ::= { ipv4config 3 }
 | 
						|
gateway  OBJECT-TYPE
 | 
						|
    SYNTAX IpAddress
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set gateway address"
 | 
						|
    ::= { ipv4config 4 }
 | 
						|
staticDNSEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set DNS address automatically or not"
 | 
						|
    ::= { ipv4config 5 }
 | 
						|
dnsPreferIPv4  OBJECT-TYPE
 | 
						|
    SYNTAX IpAddress
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set prefer DNS address"
 | 
						|
    ::= { ipv4config 6 }
 | 
						|
dnsAlternateIPv4  OBJECT-TYPE
 | 
						|
    SYNTAX IpAddress
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set alternate DNS address"
 | 
						|
    ::= { ipv4config 7 }
 | 
						|
 | 
						|
trapEnabled OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Indicates if this trap entry is enabled or not.
 | 
						|
        You should set the username/auth-password/priv-password first, when choosing snmpv3.
 | 
						|
		You should set the community string first, when choosing snmpv1/v2c."
 | 
						|
    ::= { devicesnmp 1 }
 | 
						|
 | 
						|
trapVersion OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { v1(1), v2c(2), v3(3)}
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " Choose SNMP Trap version to send trap.
 | 
						|
	You should set the username/auth-password/priv-password first, when choosing snmpv3.
 | 
						|
	You should set the community string first, when choosing snmpv1/v2c."
 | 
						|
    ::= { devicesnmp 2 }
 | 
						|
 | 
						|
snmpTrapTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF SnmpTrapEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "PE SNMP agent trap setup table. If users want to use trap,
 | 
						|
		they must set enable trap, ip and community first."
 | 
						|
    ::= { devicesnmp 3 }
 | 
						|
 | 
						|
snmpTrapEntry OBJECT-TYPE
 | 
						|
    SYNTAX SnmpTrapEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Single trap entry containing trap receiver info."
 | 
						|
    INDEX { trapReceiverNumber }
 | 
						|
     ::= { snmpTrapTable 1 }
 | 
						|
 | 
						|
SnmpTrapEntry ::=
 | 
						|
    SEQUENCE {
 | 
						|
        trapReceiverNumber
 | 
						|
            INTEGER,
 | 
						|
        --trapEnabled
 | 
						|
            --INTEGER,
 | 
						|
        trapReceiverIPAddress
 | 
						|
            IpAddress,
 | 
						|
        --trapCommunity
 | 
						|
            --DisplayString,
 | 
						|
		trapPort
 | 
						|
			INTEGER,
 | 
						|
		trapCommunity
 | 
						|
			DisplayString,
 | 
						|
		trapUsername
 | 
						|
			DisplayString,
 | 
						|
		trapAuthpassword
 | 
						|
			DisplayString,
 | 
						|
		trapPrivpassword
 | 
						|
		    DisplayString
 | 
						|
    }
 | 
						|
 | 
						|
trapReceiverNumber  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..2)
 | 
						|
    MAX-ACCESS read-only
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Index of trap receiver"
 | 
						|
    ::= { snmpTrapEntry 1 }
 | 
						|
 | 
						|
 | 
						|
 | 
						|
trapReceiverIPAddress OBJECT-TYPE
 | 
						|
    SYNTAX  IpAddress
 | 
						|
    MAX-ACCESS  read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Trap receiver IP address"
 | 
						|
    ::= { snmpTrapEntry 2 }
 | 
						|
 | 
						|
 | 
						|
trapPort OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER (1..65535)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "NMS trap port to be used by agent to send trap"
 | 
						|
    ::= { snmpTrapEntry 3 }
 | 
						|
 | 
						|
trapCommunity OBJECT-TYPE
 | 
						|
    SYNTAX  DisplayString (SIZE (0..20))
 | 
						|
    MAX-ACCESS  read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "If use SNMPv1/v2c to receive trap should set this Community string.
 | 
						|
        MAX string length: 20
 | 
						|
        NOTE: Input string as /empty to set this object to NULL.
 | 
						|
        "
 | 
						|
    ::= { snmpTrapEntry 4 }
 | 
						|
trapUsername OBJECT-TYPE
 | 
						|
    SYNTAX  DisplayString (SIZE (0..20))
 | 
						|
    MAX-ACCESS  read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "If use SNMPv3 to receive trap should set this string.
 | 
						|
        NOTE: Input string as /empty to set this object to NULL.
 | 
						|
        MAX string length: 20
 | 
						|
        "
 | 
						|
    ::= { snmpTrapEntry 5 }
 | 
						|
trapAuthpassword OBJECT-TYPE
 | 
						|
    SYNTAX  DisplayString (SIZE (8..20))
 | 
						|
    MAX-ACCESS  read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "If use SNMPv3 to receive trap should set this string.
 | 
						|
        MAX string length: 20
 | 
						|
        NOTE: Input string as /empty to set this object to NULL.
 | 
						|
        "
 | 
						|
    ::= { snmpTrapEntry 6 }
 | 
						|
trapPrivpassword OBJECT-TYPE
 | 
						|
    SYNTAX  DisplayString (SIZE (8..20))
 | 
						|
    MAX-ACCESS  read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "If use SNMPv3 to receive trap should set this string.
 | 
						|
        MAX string length: 20
 | 
						|
        NOTE: Input string as /empty to set this object to NULL.
 | 
						|
        "
 | 
						|
    ::= { snmpTrapEntry 7 }
 | 
						|
 | 
						|
 | 
						|
--privacypassword OBJECT-TYPE
 | 
						|
--    SYNTAX  DisplayString
 | 
						|
--    MAX-ACCESS  read-write
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "SNMPv3 privacy password to be used by agent to send trap
 | 
						|
--        string length: 8~20
 | 
						|
--        "
 | 
						|
--    ::= { devicesnmp 4 }
 | 
						|
 | 
						|
--engineID OBJECT-TYPE
 | 
						|
--	SYNTAX DisplayString
 | 
						|
--	MAX-ACCESS read-only
 | 
						|
--	STATUS current
 | 
						|
--	DESCRIPTION
 | 
						|
--		"EngineID"
 | 
						|
--	::= { devicesnmp 5 }
 | 
						|
--engineBoot OBJECT-TYPE
 | 
						|
--	SYNTAX INTEGER
 | 
						|
--	MAX-ACCESS read-only
 | 
						|
--	STATUS current
 | 
						|
--	DESCRIPTION
 | 
						|
--		"EngineBoot"
 | 
						|
--	::= { devicesnmp 6 }
 | 
						|
--engineTime OBJECT-TYPE
 | 
						|
--	SYNTAX INTEGER
 | 
						|
--	MAX-ACCESS read-only
 | 
						|
--	STATUS current
 | 
						|
--	DESCRIPTION
 | 
						|
--		"EngineTime"
 | 
						|
--	::= { devicesnmp 7 }
 | 
						|
--engineMaxMSG OBJECT-TYPE
 | 
						|
--	SYNTAX INTEGER
 | 
						|
--	MAX-ACCESS read-only
 | 
						|
--	STATUS current
 | 
						|
--	DESCRIPTION
 | 
						|
--		"EngineMaxMSG"
 | 
						|
--	::= { devicesnmp 8 }
 | 
						|
sysLogServerEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set syslog server address automatically or not"
 | 
						|
    ::= { syslog 1 }
 | 
						|
sysLogServerIPv4  OBJECT-TYPE
 | 
						|
    SYNTAX IpAddress
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set syslog server address"
 | 
						|
    ::= { syslog 2 }
 | 
						|
sysLogServerPort  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..65535)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set syslog server port"
 | 
						|
    ::= { syslog 3 }
 | 
						|
 | 
						|
smtpServerEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set SMTP server enable status."
 | 
						|
    ::= { smtp 1 }
 | 
						|
smtpServerName  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set a SMTP server name.
 | 
						|
        NOTE: Input string as /empty to set this object to NULL.
 | 
						|
        "
 | 
						|
    ::= { smtp 2 }
 | 
						|
smtpAuthEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set authentication of SMTP server."
 | 
						|
    ::= { smtp 3 }
 | 
						|
smtpAccountName  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set a user's name of SMTP server.
 | 
						|
        NOTE: Input string as /empty to set this object to NULL.
 | 
						|
        "
 | 
						|
    ::= { smtp 4 }
 | 
						|
smtpAccountPwd  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set a user's password of SMTP server.
 | 
						|
        NOTE: Input string as /empty to set this object to NULL.
 | 
						|
        "
 | 
						|
    ::= { smtp 5 }
 | 
						|
smtpMailFrom  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set a mail of SMTP server.
 | 
						|
        NOTE: Input string as /empty to set this object to NULL.
 | 
						|
        "
 | 
						|
    ::= { smtp 6 }
 | 
						|
smtpMailTo  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set a mail of SMTP server.
 | 
						|
        NOTE: Input string as /empty to set this object to NULL.
 | 
						|
        "
 | 
						|
    ::= { smtp 7 }
 | 
						|
--
 | 
						|
 | 
						|
configurationNotifyEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        " "
 | 
						|
    ::= { configurationNotification 1 }
 | 
						|
 | 
						|
configurationNotifyTrapMSG NOTIFICATION-TYPE
 | 
						|
    STATUS  current
 | 
						|
    --OBJECTS { customTrapMSG }
 | 
						|
    DESCRIPTION " "
 | 
						|
        ::= { configurationNotification 2 }
 | 
						|
 | 
						|
 | 
						|
--
 | 
						|
timeZoneSetting  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set the time zone of PE device.
 | 
						|
		 (0) [GMT-12:00] Eniwetok Kwajalein
 | 
						|
         (1) [GMT-11:00] Midway Island Samoa
 | 
						|
         (2) [GMT-10:00] Hawaii
 | 
						|
         (3) [GMT-09:00] Alaska
 | 
						|
         (4) [GMT-08:00] Pacific Time (US & Canada); Tijuana
 | 
						|
         (5) [GMT-07:00] Mountain Time (US & Canada)
 | 
						|
         (6) [GMT-07:00] Arizona
 | 
						|
         (7) [GMT-06:00] Central Time (US & Canada)
 | 
						|
         (8) [GMT-06:00] Mexico City
 | 
						|
         (9) [GMT-06:00] Saskatchewan
 | 
						|
         (10)[GMT-06:00] Central America
 | 
						|
         (11)[GMT-05:00] Eastern Time (US & Canada)
 | 
						|
         (12)[GMT-05:00] Indiana (East)
 | 
						|
         (13)[GMT-05:00] Bogota Lima Quito
 | 
						|
         (14)[GMT-04:00] Atlantic Time (Canada)
 | 
						|
         (15)[GMT-04:00] Caracas La Paz
 | 
						|
         (16)[GMT-04:00] Santiago
 | 
						|
         (17)[GMT-03:30] Newfoundland
 | 
						|
         (18)[GMT-03:00] Buenos Aires Georgetown
 | 
						|
         (19)[GMT-03:00] Brasilia
 | 
						|
         (20)[GMT-03:00] Greenland
 | 
						|
         (21)[GMT-02:00] Mid-Atlantic
 | 
						|
         (22)[GMT-01:00] Azores
 | 
						|
         (23)[GMT-01:00] Cape Verde Is
 | 
						|
         (24)[GMT]       Casablanca Monrovia
 | 
						|
         (25)[GMT]       Greenwich Mean Time: Dublin Edinburgh Lisbon London
 | 
						|
         (26)[GMT+01:00] Amsterdam Copenhagen Madrid Paris Vilnius
 | 
						|
         (27)[GMT+01:00] West Central Africa
 | 
						|
         (28)[GMT+01:00] Belgrade Sarajevo Skopje Sofija Zagreb
 | 
						|
         (29)[GMT+01:00] Bratislava Budapest Ljubljana Prague Warsaw
 | 
						|
         (30)[GMT+01:00] Brussels Berlin Bern Rome Stockholm Vienna
 | 
						|
         (31)[GMT+02:00] Cairo
 | 
						|
         (32)[GMT+02:00] Harare Pretoria
 | 
						|
         (33)[GMT+02:00] Jerusalem
 | 
						|
         (34)[GMT+02:00] Bucharest
 | 
						|
         (35)[GMT+02:00] Helsinki Riga Tallinn
 | 
						|
         (36)[GMT+02:00] Athens Istanbul Minsk
 | 
						|
         (37)[GMT+03:00] Kuwait Riyadh
 | 
						|
         (38)[GMT+03:00] Nairobi
 | 
						|
         (39)[GMT+03:00] Baghdad
 | 
						|
         (40)[GMT+03:00] Moscow St. Petersburg Volgograd
 | 
						|
         (41)[GMT+03:30] Tehran
 | 
						|
         (42)[GMT+04:00] Abu Dhabi Muscat
 | 
						|
         (43)[GMT+04:00] Baku Tbilisi Yerevan
 | 
						|
         (44)[GMT+04:30] Kabul
 | 
						|
         (45)[GMT+05:00] Islamabad Karachi Tashkent
 | 
						|
         (46)[GMT+05:00] Ekaterinburg
 | 
						|
         (47)[GMT+05:30] Calcutta Chennai Mumbai New Delhi
 | 
						|
         (48)[GMT+05:45] Kathmandu
 | 
						|
         (49)[GMT+06:00] Astana Dhaka
 | 
						|
         (50)[GMT+06:00] Sri Jayawardenepura
 | 
						|
         (51)[GMT+06:00] Almaty Novosibirsk
 | 
						|
         (52)[GMT+06:30] Rangoon
 | 
						|
         (53)[GMT+07:00] Bangkok Hanoi Jakarta
 | 
						|
         (54)[GMT+07:00] Krasnoyarsk
 | 
						|
         (55)[GMT+08:00] Beijing Chongqing Hong Kong Urumqi
 | 
						|
         (56)[GMT+08:00] Perth
 | 
						|
         (57)[GMT+08:00] Kuala Lumpur Singapore
 | 
						|
         (58)[GMT+08:00] Taipei
 | 
						|
         (59)[GMT+08:00] Irkutsk Ulaan Bataar
 | 
						|
         (60)[GMT+09:00] Osaka Sapporo Tokyo
 | 
						|
         (61)[GMT+09:00] Seoul
 | 
						|
         (62)[GMT+09:00] Yakutsk
 | 
						|
         (63)[GMT+09:30] Darwin
 | 
						|
         (64)[GMT+09:30] Adelaide
 | 
						|
         (65)[GMT+10:00] Canberra Melbourne Sydney
 | 
						|
         (66)[GMT+10:00] Brisbane
 | 
						|
         (67)[GMT+10:00] Guam Port Moresby
 | 
						|
         (68)[GMT+10:00] Hobart
 | 
						|
         (69)[GMT+10:00] Vladivostok
 | 
						|
         (70)[GMT+11:00] Magadan Solomon Is New Caledonia
 | 
						|
         (71)[GMT+12:00] Fiji Kamchatka Marshall Is.
 | 
						|
         (72)[GMT+12:00] Auckland Wellington
 | 
						|
         (73)[GMT+13:00] Nuku'alofa
 | 
						|
		"
 | 
						|
    ::= { timeZone 1 }
 | 
						|
 | 
						|
dstEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set daylight savings time ."
 | 
						|
    ::= { timeZone 2 }
 | 
						|
 | 
						|
dateSetting  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set date in a manual way.(This is Greenwich Mean Time, GMT)
 | 
						|
         string length: 10
 | 
						|
		 This value format must match the following form:
 | 
						|
		 YYYY-MM-DD
 | 
						|
		 ex. 2011-01-01
 | 
						|
		 Note: range of year: 2000-2099
 | 
						|
		 	   range of month: 01-12
 | 
						|
		 	   range of day: 01-31
 | 
						|
		"
 | 
						|
    ::= { manualInput 1 }
 | 
						|
 | 
						|
timeSetting  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set time in a manual way.(This is Greenwich Mean Time, GMT)
 | 
						|
         string length: 8
 | 
						|
		 This value format must match the following form:
 | 
						|
		 HH:MM:SS
 | 
						|
		 ex. 02:02:02
 | 
						|
		 Note: range of hour: 00-24
 | 
						|
		 	   range of minute: 00-60
 | 
						|
		 	   range of second: 00-60
 | 
						|
 | 
						|
		"
 | 
						|
    ::= { manualInput 2 }
 | 
						|
 | 
						|
--syncWithPC  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
--    MAX-ACCESS read-write
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display or set date time useing sync PC way."
 | 
						|
--    ::= { manualInput 3 }
 | 
						|
 | 
						|
autoAdjustEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set date time useing auto adjustment way."
 | 
						|
    ::= { networkTime 1 }
 | 
						|
 | 
						|
preferNTP  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
       "Display or set prefer NTP server.
 | 
						|
        AU | ntp1.cs.mu.OZ.AU(0),
 | 
						|
	AU | ntp0.cs.mu.OZ.AU(1),
 | 
						|
	BE | ntp2.oma.be(2),
 | 
						|
	BE | ntp1.oma.be(3),
 | 
						|
	BR | ntps1.pads.ufrj.br(4),
 | 
						|
	CH | swisstime.ethz.ch(5),
 | 
						|
	CL | ntp.shoa.cl(6),
 | 
						|
	CZ | ntp.nic.cz(7),
 | 
						|
	DE | ntp.stairweb.de(8),
 | 
						|
	DE | ntps1-0.cs.tu-berlin.de(9),
 | 
						|
	DE | ptbtime1.ptb.de(10),
 | 
						|
	DE | ntp1.fau.de(11),
 | 
						|
	DE | ptbtime2.ptb.de(12),
 | 
						|
	DE | time1.one4vision.de(13),
 | 
						|
	DE | rustime01.rus.uni-stuttgart.de(14),
 | 
						|
	DE | ntp.probe-networks.de(15),
 | 
						|
	DE | ntp2.fau.de(16),
 | 
						|
	ES | hora.roa.es(17),
 | 
						|
	HK | stdtime.gov.hk(18),
 | 
						|
	IE | ntp-galway.hea.net(19),
 | 
						|
	IT | ntp1.inrim.it(20),
 | 
						|
	IT | ntp2.inrim.it(21),
 | 
						|
	JP | clock.tl.fukuoka-u.ac.jp(22),
 | 
						|
	JP | ntp.nict.jp(23),
 | 
						|
	JP | clock.nc.fukuoka-u.ac.jp(24),
 | 
						|
	KR | ntp.xbsd.kr(25),
 | 
						|
	MX | cronos.cenam.mx(26),
 | 
						|
	NL | ntp0.nl.uu.net(27),
 | 
						|
	NL | ntp1.nl.uu.net(28),
 | 
						|
	NL | ntp.remco.org(29),
 | 
						|
	NL | ntp0.nl.net(30),
 | 
						|
	PL | vega.cbk.poznan.pl(31),
 | 
						|
	PL | ntp.ntp-servers.com(32),
 | 
						|
	RO | ntp3.usv.ro(33),
 | 
						|
	RO | ntp2.usv.ro(34),
 | 
						|
	RU | ntp1.vniiftri.ru; ntp1.imvp.ru(35),
 | 
						|
	RU | ntp2.vniiftri.ru; ntp2.imvp.ru(36),
 | 
						|
	SE | ntp1.mmo.netnod.se(37),
 | 
						|
	SE | ntp1.sth.netnod.se(38),
 | 
						|
	SE | ntp2.mmo.netnod.se(39),
 | 
						|
	SE | ntp2.sth.netnod.se(40),
 | 
						|
	SE | time2.stupi.se(41),
 | 
						|
	SE | ntp1.sp.se(42),
 | 
						|
	SE | timehost.lysator.liu.se(43),
 | 
						|
	SI | ntp.mostovna.com(44),
 | 
						|
	US CA | timekeeper.isi.edu(45),
 | 
						|
	US CA | clock.sjc.he.net(46),
 | 
						|
	US CA | nist1.symmetricom.com(47),
 | 
						|
	US CA | clock.via.net(48),
 | 
						|
	US CA | nist1.aol-ca.truetime.com(49),
 | 
						|
	US CA | clock.isc.org(50),
 | 
						|
	US CA | clepsydra.dec.com(51),
 | 
						|
	US CA | gps.layer42.net(52),
 | 
						|
	US CA | time.no-such-agency.net(53),
 | 
						|
	US CA | nist1-sj.WiTime.net(54),
 | 
						|
	US CA | clock.fmt.he.net(55),
 | 
						|
	US CO | time-b.timefreq.bldrdoc.gov(56),
 | 
						|
	US CO | time-a.timefreq.bldrdoc.gov(57),
 | 
						|
	US CO | utcnist.colorado.edu(58),
 | 
						|
	US CO | time-c.timefreq.bldrdoc.gov(59),
 | 
						|
	US DE | rackety.udel.edu(60),
 | 
						|
	US DE | mizbeaver.udel.edu(61),
 | 
						|
	US GA | nist1.columbiacountyga.gov(62),
 | 
						|
	US IL | ntp.your.org(63),
 | 
						|
	US MA | bonehed.lcs.mit.edu(64),
 | 
						|
	US MA | time.keneli.org(65),
 | 
						|
	US MA | ntp0.broad.mit.edu(66),
 | 
						|
	US MD | time-a.nist.gov(67),
 | 
						|
	US MD | time-b.nist.gov(68),
 | 
						|
	US MI | nist.netservicesgroup.com(69),
 | 
						|
	US NY | nist1-ny.WiTime.net(70),
 | 
						|
	US NY | clock.nyc.he.net(71),
 | 
						|
	US UT | time.xmission.com(72),
 | 
						|
	US VA | nist1-dc.WiTime.net(73),
 | 
						|
	US VA | nist1.aol-va.truetime.com(74),
 | 
						|
	US WA | time-nw.nist.gov(75),
 | 
						|
	FR | utp.univ-lyon1.fr(76),
 | 
						|
	FR | ntp-sop.inria.fr(77),
 | 
						|
	FR | ntp.tuxfamily.net(78),
 | 
						|
	UK | bear.zoo.bt.co.uk(79)
 | 
						|
	"
 | 
						|
    ::= { networkTime 2 }
 | 
						|
 | 
						|
preferServerIPenable  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Enable or disable prefer custom server IP."
 | 
						|
    ::= { networkTime 3 }
 | 
						|
 | 
						|
preferNTPIp  OBJECT-TYPE
 | 
						|
    SYNTAX IpAddress
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set prefer NTP server IP."
 | 
						|
    ::= { networkTime 4 }
 | 
						|
 | 
						|
alternateNtpEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set date time using alternate NTP server."
 | 
						|
    ::= { networkTime 5 }
 | 
						|
 | 
						|
alternateNtp  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set alternative NTP server.
 | 
						|
        AU | ntp1.cs.mu.OZ.AU(0),
 | 
						|
	AU | ntp0.cs.mu.OZ.AU(1),
 | 
						|
	BE | ntp2.oma.be(2),
 | 
						|
	BE | ntp1.oma.be(3),
 | 
						|
	BR | ntps1.pads.ufrj.br(4),
 | 
						|
	CH | swisstime.ethz.ch(5),
 | 
						|
	CL | ntp.shoa.cl(6),
 | 
						|
	CZ | ntp.nic.cz(7),
 | 
						|
	DE | ntp.stairweb.de(8),
 | 
						|
	DE | ntps1-0.cs.tu-berlin.de(9),
 | 
						|
	DE | ptbtime1.ptb.de(10),
 | 
						|
	DE | ntp1.fau.de(11),
 | 
						|
	DE | ptbtime2.ptb.de(12),
 | 
						|
	DE | time1.one4vision.de(13),
 | 
						|
	DE | rustime01.rus.uni-stuttgart.de(14),
 | 
						|
	DE | ntp.probe-networks.de(15),
 | 
						|
	DE | ntp2.fau.de(16),
 | 
						|
	ES | hora.roa.es(17),
 | 
						|
	HK | stdtime.gov.hk(18),
 | 
						|
	IE | ntp-galway.hea.net(19),
 | 
						|
	IT | ntp1.inrim.it(20),
 | 
						|
	IT | ntp2.inrim.it(21),
 | 
						|
	JP | clock.tl.fukuoka-u.ac.jp(22),
 | 
						|
	JP | ntp.nict.jp(23),
 | 
						|
	JP | clock.nc.fukuoka-u.ac.jp(24),
 | 
						|
	KR | ntp.xbsd.kr(25),
 | 
						|
	MX | cronos.cenam.mx(26),
 | 
						|
	NL | ntp0.nl.uu.net(27),
 | 
						|
	NL | ntp1.nl.uu.net(28),
 | 
						|
	NL | ntp.remco.org(29),
 | 
						|
	NL | ntp0.nl.net(30),
 | 
						|
	PL | vega.cbk.poznan.pl(31),
 | 
						|
	PL | ntp.ntp-servers.com(32),
 | 
						|
	RO | ntp3.usv.ro(33),
 | 
						|
	RO | ntp2.usv.ro(34),
 | 
						|
	RU | ntp1.vniiftri.ru; ntp1.imvp.ru(35),
 | 
						|
	RU | ntp2.vniiftri.ru; ntp2.imvp.ru(36),
 | 
						|
	SE | ntp1.mmo.netnod.se(37),
 | 
						|
	SE | ntp1.sth.netnod.se(38),
 | 
						|
	SE | ntp2.mmo.netnod.se(39),
 | 
						|
	SE | ntp2.sth.netnod.se(40),
 | 
						|
	SE | time2.stupi.se(41),
 | 
						|
	SE | ntp1.sp.se(42),
 | 
						|
	SE | timehost.lysator.liu.se(43),
 | 
						|
	SI | ntp.mostovna.com(44),
 | 
						|
	US CA | timekeeper.isi.edu(45),
 | 
						|
	US CA | clock.sjc.he.net(46),
 | 
						|
	US CA | nist1.symmetricom.com(47),
 | 
						|
	US CA | clock.via.net(48),
 | 
						|
	US CA | nist1.aol-ca.truetime.com(49),
 | 
						|
	US CA | clock.isc.org(50),
 | 
						|
	US CA | clepsydra.dec.com(51),
 | 
						|
	US CA | gps.layer42.net(52),
 | 
						|
	US CA | time.no-such-agency.net(53),
 | 
						|
	US CA | nist1-sj.WiTime.net(54),
 | 
						|
	US CA | clock.fmt.he.net(55),
 | 
						|
	US CO | time-b.timefreq.bldrdoc.gov(56),
 | 
						|
	US CO | time-a.timefreq.bldrdoc.gov(57),
 | 
						|
	US CO | utcnist.colorado.edu(58),
 | 
						|
	US CO | time-c.timefreq.bldrdoc.gov(59),
 | 
						|
	US DE | rackety.udel.edu(60),
 | 
						|
	US DE | mizbeaver.udel.edu(61),
 | 
						|
	US GA | nist1.columbiacountyga.gov(62),
 | 
						|
	US IL | ntp.your.org(63),
 | 
						|
	US MA | bonehed.lcs.mit.edu(64),
 | 
						|
	US MA | time.keneli.org(65),
 | 
						|
	US MA | ntp0.broad.mit.edu(66),
 | 
						|
	US MD | time-a.nist.gov(67),
 | 
						|
	US MD | time-b.nist.gov(68),
 | 
						|
	US MI | nist.netservicesgroup.com(69),
 | 
						|
	US NY | nist1-ny.WiTime.net(70),
 | 
						|
	US NY | clock.nyc.he.net(71),
 | 
						|
	US UT | time.xmission.com(72),
 | 
						|
	US VA | nist1-dc.WiTime.net(73),
 | 
						|
	US VA | nist1.aol-va.truetime.com(74),
 | 
						|
	US WA | time-nw.nist.gov(75),
 | 
						|
	FR | utp.univ-lyon1.fr(76),
 | 
						|
	FR | ntp-sop.inria.fr(77),
 | 
						|
	FR | ntp.tuxfamily.net(78),
 | 
						|
	UK | bear.zoo.bt.co.uk(79)
 | 
						|
        "
 | 
						|
    ::= { networkTime 6 }
 | 
						|
 | 
						|
alternateServerIPenable  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Enable or disable alternate custom server IP."
 | 
						|
    ::= { networkTime 7 }
 | 
						|
 | 
						|
alternateNtpIp  OBJECT-TYPE
 | 
						|
    SYNTAX IpAddress
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set alternative NTP server IP."
 | 
						|
    ::= { networkTime 8 }
 | 
						|
 | 
						|
adjustTimeEveryDays  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set frequency of adjustment in days."
 | 
						|
	::= { networkTime 9 }
 | 
						|
 | 
						|
--adjustTimeNow  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Adjust time using NTP server."
 | 
						|
	--::= { networkTime 8 }
 | 
						|
 | 
						|
loginAllowTimes  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..99)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set time of login faliure."
 | 
						|
	::= { loginFailures 1 }
 | 
						|
 | 
						|
loginTimeOut  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..240)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set login time out."
 | 
						|
	::= { loginFailures 2 }
 | 
						|
 | 
						|
icmpEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set status of ICMP."
 | 
						|
	::= { workingMode 1 }
 | 
						|
 | 
						|
--multiUserEnabled  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display or set status of multi-user operation."
 | 
						|
	--::= { workingMode 2 }
 | 
						|
 | 
						|
--browserEnabled  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display or set status of browser."
 | 
						|
	--::= { workingMode 3 }
 | 
						|
 | 
						|
minUserNameLen  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..16)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set minimum length of user name."
 | 
						|
	::= { accountPolicy 1 }
 | 
						|
 | 
						|
minUserPwdLen  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER (1..16)
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set minimum length of user password.
 | 
						|
        "
 | 
						|
	::= { accountPolicy 2 }
 | 
						|
 | 
						|
upperCaseEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set one upper case rule in user password."
 | 
						|
	::= { accountPolicy 3 }
 | 
						|
 | 
						|
lowerCaseEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set one lower case rule in user password."
 | 
						|
	::= { accountPolicy 4 }
 | 
						|
 | 
						|
numberEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set one number rule in user password."
 | 
						|
	::= { accountPolicy 5 }
 | 
						|
 | 
						|
disableDuplicateLogin  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set status of disabled duplicate login rule."
 | 
						|
	::= { accountPolicy 6 }
 | 
						|
 | 
						|
loginString  OBJECT-TYPE
 | 
						|
    SYNTAX DisplayString
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set a login string.
 | 
						|
        string length: 0~32
 | 
						|
        NOTE: Input string as /empty to set this object to NULL.
 | 
						|
        "
 | 
						|
	::= { loginRestriction 1 }
 | 
						|
 | 
						|
ipFilterEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set status of ip filter."
 | 
						|
	::= { ipFilter 1 }
 | 
						|
 | 
						|
ipFilterRule  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { include(1), exclude(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set status of ip filter rule."
 | 
						|
	::= { ipFilter 2 }
 | 
						|
 | 
						|
ipFilterTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF IpFilterEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "A list of restricted ip."
 | 
						|
    ::= { ipFilter 3 }
 | 
						|
 | 
						|
ipFilterEntry OBJECT-TYPE
 | 
						|
	SYNTAX IpFilterEntry
 | 
						|
	MAX-ACCESS not-accessible
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Status and parameter values for a PE's restricted IP."
 | 
						|
	INDEX { ipFilterIndex }
 | 
						|
	::= { ipFilterTable 1 }
 | 
						|
 | 
						|
IpFilterEntry ::=
 | 
						|
	SEQUENCE {
 | 
						|
		ipFilterIndex
 | 
						|
			INTEGER,
 | 
						|
		ipFilterFrom
 | 
						|
			IpAddress,
 | 
						|
		ipFilterTo
 | 
						|
		    IpAddress
 | 
						|
	}
 | 
						|
 | 
						|
ipFilterIndex OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER (1..5)
 | 
						|
	MAX-ACCESS read-only
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"The value of index for the ip filter.
 | 
						|
		"
 | 
						|
	::= { ipFilterEntry 1 }
 | 
						|
 | 
						|
ipFilterFrom OBJECT-TYPE
 | 
						|
	SYNTAX IpAddress
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"A set of restricted ip.
 | 
						|
		 ex. 192.168.0.1
 | 
						|
 | 
						|
		 Note: Users must follow in order to set the ip address.
 | 
						|
		 Note: To clear the settings to set the ip 0.0.0.0
 | 
						|
		"
 | 
						|
	::= { ipFilterEntry 2 }
 | 
						|
 | 
						|
ipFilterTo OBJECT-TYPE
 | 
						|
	SYNTAX IpAddress
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"A set of restricted ip.
 | 
						|
		 ex. 192.168.0.255
 | 
						|
 | 
						|
		 Note: Users must follow in order to set the ip address.
 | 
						|
		 Note: To clear the settings to set the ip 0.0.0.0
 | 
						|
		"
 | 
						|
	::= { ipFilterEntry 3 }
 | 
						|
 | 
						|
macFilterEnabled  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set status of mac filter."
 | 
						|
	::= { macFilter 1 }
 | 
						|
 | 
						|
macFilterRule  OBJECT-TYPE
 | 
						|
    SYNTAX INTEGER { include(1), exclude(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "Display or set status of mac filter rule."
 | 
						|
	::= { macFilter 2 }
 | 
						|
 | 
						|
macFilterTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF MacFilterEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "A list of restricted mac."
 | 
						|
    ::= { macFilter 3 }
 | 
						|
 | 
						|
macFilterEntry OBJECT-TYPE
 | 
						|
	SYNTAX MacFilterEntry
 | 
						|
	MAX-ACCESS not-accessible
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Status and parameter values for a PE's restricted MAC."
 | 
						|
	INDEX { macFilterIndex }
 | 
						|
	::= { macFilterTable 1 }
 | 
						|
 | 
						|
MacFilterEntry ::=
 | 
						|
	SEQUENCE {
 | 
						|
		macFilterIndex
 | 
						|
			INTEGER,
 | 
						|
		macFilterSet
 | 
						|
			DisplayString
 | 
						|
	}
 | 
						|
 | 
						|
macFilterIndex OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER (1..5)
 | 
						|
	MAX-ACCESS read-only
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"The value of index for the mac filter.
 | 
						|
		"
 | 
						|
	::= { macFilterEntry 1 }
 | 
						|
 | 
						|
macFilterSet OBJECT-TYPE
 | 
						|
	SYNTAX DisplayString
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"A set of restricted mac.
 | 
						|
		 string length: 12
 | 
						|
		 ex. 004854655511
 | 
						|
 | 
						|
		 Note: Users must follow in order to set the MAC address.
 | 
						|
		 Note: To clear the settings to set the MAC 000000000000
 | 
						|
		"
 | 
						|
	::= { macFilterEntry 2 }
 | 
						|
 | 
						|
--LocalAuth  OBJECT-TYPE
 | 
						|
	--SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
	--MAX-ACCESS read-write
 | 
						|
	--STATUS current
 | 
						|
	--DESCRIPTION
 | 
						|
	--	"Display or set status of disable local authentication."
 | 
						|
	--::= { authentication 1 }
 | 
						|
 | 
						|
radiusEnabled  OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set status of RADIUS server."
 | 
						|
	::= { radius 1 }
 | 
						|
 | 
						|
preferRadiusIp  OBJECT-TYPE
 | 
						|
	SYNTAX IpAddress
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set prefer RADIUS server IP."
 | 
						|
	::= { radius 2 }
 | 
						|
 | 
						|
preferRadiusPort  OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER (1..65535)
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set prefer RADIUS server port."
 | 
						|
	::= { radius 3 }
 | 
						|
 | 
						|
alternateRadiusIp  OBJECT-TYPE
 | 
						|
	SYNTAX IpAddress
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set alternative RADIUS server IP."
 | 
						|
	::= { radius 4 }
 | 
						|
 | 
						|
alternateRadiusPort  OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER (1..65535)
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set alternative RADIUS server port."
 | 
						|
	::= { radius 5 }
 | 
						|
 | 
						|
radiusTimeOut  OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER (1..60)
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set time out of authentication using RADIUS server.
 | 
						|
		 The unit is sec.
 | 
						|
		"
 | 
						|
	::= { radius 6 }
 | 
						|
 | 
						|
radiusRetry  OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER (0..10)
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set retry times of authentication using RADIUS server."
 | 
						|
	::= { radius 7 }
 | 
						|
 | 
						|
radiusSecret  OBJECT-TYPE
 | 
						|
	SYNTAX DisplayString
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set shared secret of RADIUS server.
 | 
						|
		 string length: 6~15
 | 
						|
		 At least 6 characters.
 | 
						|
		 NOTE: Input string as /empty to set this object to NULL.
 | 
						|
		"
 | 
						|
	::= { radius 8 }
 | 
						|
 | 
						|
-- Device Management End
 | 
						|
 | 
						|
-- User Management
 | 
						|
usrListTable OBJECT-TYPE
 | 
						|
    SYNTAX SEQUENCE OF UsrListEntry
 | 
						|
    MAX-ACCESS not-accessible
 | 
						|
    STATUS current
 | 
						|
    DESCRIPTION
 | 
						|
        "A list of user. The number of user is
 | 
						|
            given by the value of usrcfgNumber."
 | 
						|
    ::= { userManagement 1 }
 | 
						|
 | 
						|
usrListEntry OBJECT-TYPE
 | 
						|
	SYNTAX UsrListEntry
 | 
						|
	MAX-ACCESS not-accessible
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Status and parameter values for a pe8208 user."
 | 
						|
	INDEX { usrIndex }
 | 
						|
	::= { usrListTable 1 }
 | 
						|
 | 
						|
UsrListEntry ::=
 | 
						|
	SEQUENCE {
 | 
						|
		usrIndex
 | 
						|
			INTEGER,
 | 
						|
		usrType
 | 
						|
			INTEGER,
 | 
						|
		usrName
 | 
						|
			DisplayString,
 | 
						|
		usrPassword
 | 
						|
			DisplayString,
 | 
						|
		usrPort1Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort2Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort3Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort4Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort5Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort6Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort7Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort8Auth
 | 
						|
			INTEGER,
 | 
						|
 | 
						|
		usrPort9Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort10Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort11Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort12Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort13Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort14Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort15Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort16Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort17Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort18Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort19Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort20Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort21Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort22Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort23Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort24Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort25Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort26Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort27Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort28Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort29Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort30Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort31Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort32Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort33Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort34Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort35Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort36Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort37Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort38Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort39Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort40Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort41Auth
 | 
						|
			INTEGER,
 | 
						|
		usrPort42Auth
 | 
						|
			INTEGER,
 | 
						|
		usrEnable
 | 
						|
			INTEGER
 | 
						|
	}
 | 
						|
 | 
						|
usrIndex OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER (1..9)
 | 
						|
	MAX-ACCESS read-only
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"The value of usrIndex for the user. We have 1 administrator and 8 users.
 | 
						|
		 The index 9 will be the administrator.
 | 
						|
		"
 | 
						|
	::= { usrListEntry 1 }
 | 
						|
 | 
						|
usrType OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { administrator(1), user(2)}
 | 
						|
	MAX-ACCESS read-only
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"The user's type."
 | 
						|
	::= { usrListEntry 2 }
 | 
						|
 | 
						|
usrName OBJECT-TYPE
 | 
						|
   SYNTAX  DisplayString (SIZE (1..16))
 | 
						|
   MAX-ACCESS  read-write
 | 
						|
   STATUS  current
 | 
						|
   DESCRIPTION
 | 
						|
		   "A textual string containing name of the user.
 | 
						|
		   string length: 1~16
 | 
						|
		   "
 | 
						|
	::= { usrListEntry 3 }
 | 
						|
 | 
						|
usrPassword OBJECT-TYPE
 | 
						|
   SYNTAX  DisplayString (SIZE (1..16))
 | 
						|
   MAX-ACCESS  read-write
 | 
						|
   STATUS  current
 | 
						|
   DESCRIPTION
 | 
						|
		   "A textual string containing password of the user.
 | 
						|
		   string length: 1~16
 | 
						|
		   "
 | 
						|
	::= { usrListEntry 4 }
 | 
						|
 | 
						|
usrPort1Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 1 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 5 }
 | 
						|
usrPort2Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 2 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 6 }
 | 
						|
usrPort3Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 3 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 7 }
 | 
						|
usrPort4Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 4 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 8 }
 | 
						|
usrPort5Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 5 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 9 }
 | 
						|
usrPort6Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Dispaly or set this user's outlet 6 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 10 }
 | 
						|
usrPort7Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 7 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 11 }
 | 
						|
usrPort8Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 8 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 12 }
 | 
						|
usrEnable OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), enable(2) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user is enable or not"
 | 
						|
	::= { usrListEntry 47 }
 | 
						|
 | 
						|
usrPort9Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 9 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 13 }
 | 
						|
 | 
						|
usrPort10Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 10 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 14 }
 | 
						|
 | 
						|
usrPort11Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 11 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 15 }
 | 
						|
 | 
						|
usrPort12Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 12 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 16 }
 | 
						|
 | 
						|
usrPort13Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 13 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 17 }
 | 
						|
 | 
						|
 | 
						|
usrPort14Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 14 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 18 }
 | 
						|
 | 
						|
usrPort15Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 15 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 19 }
 | 
						|
 | 
						|
usrPort16Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 16 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 20 }
 | 
						|
 | 
						|
usrPort17Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 17 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 21 }
 | 
						|
 | 
						|
usrPort18Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 18 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 22 }
 | 
						|
 | 
						|
usrPort19Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 19 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 23 }
 | 
						|
 | 
						|
usrPort20Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 20 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 24 }
 | 
						|
 | 
						|
usrPort21Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 21 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 25 }
 | 
						|
 | 
						|
usrPort22Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 22 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 26 }
 | 
						|
 | 
						|
usrPort23Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 23 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 27 }
 | 
						|
 | 
						|
usrPort24Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 24 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 28 }
 | 
						|
 | 
						|
usrPort25Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 25 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 29 }
 | 
						|
 | 
						|
usrPort26Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 26 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 30 }
 | 
						|
 | 
						|
usrPort27Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 27 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 31 }
 | 
						|
usrPort28Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 28 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 32 }
 | 
						|
 | 
						|
usrPort29Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 29 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 33 }
 | 
						|
 | 
						|
usrPort30Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 30 authority.
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 34 }
 | 
						|
 | 
						|
usrPort31Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 31 authority
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 35 }
 | 
						|
 | 
						|
usrPort32Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 32 authority
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 36 }
 | 
						|
 | 
						|
usrPort33Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 33 authority
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 37 }
 | 
						|
 | 
						|
usrPort34Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 34 authority
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 38 }
 | 
						|
 | 
						|
usrPort35Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 35 authority
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 39 }
 | 
						|
 | 
						|
usrPort36Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 36 authority
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 40 }
 | 
						|
 | 
						|
usrPort37Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 37 authority
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 41 }
 | 
						|
 | 
						|
usrPort38Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 38 authority
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 42 }
 | 
						|
 | 
						|
usrPort39Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 39 authority
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 43 }
 | 
						|
 | 
						|
usrPort40Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 40 authority
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 44 }
 | 
						|
 | 
						|
usrPort41Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 41 authority
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 45 }
 | 
						|
 | 
						|
usrPort42Auth OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { disable(1), view(2), modify(3), not-support(4) }
 | 
						|
	MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION
 | 
						|
		"Display or set this user's outlet 42 authority
 | 
						|
		Port in the pe of series represents outlet.
 | 
						|
		Port in the Energy monitor of series represents a bank or a pdu."
 | 
						|
	::= { usrListEntry 46 }
 | 
						|
 | 
						|
-- User Management End
 | 
						|
 | 
						|
-- SNMPv3 USM Settings
 | 
						|
--snmpv3UsmUserTable     OBJECT-TYPE
 | 
						|
--    SYNTAX       SEQUENCE OF Snmpv3UsmUserEntry
 | 
						|
--    MAX-ACCESS   not-accessible
 | 
						|
--    STATUS       current
 | 
						|
--   DESCRIPTION "This table is used to configure PE SNMPv3 USM.
 | 
						|
--			     To get the SNMPv3 access, One need to configure security
 | 
						|
--		         name,authentication,auth password,priv protocol and priv
 | 
						|
--                 password.
 | 
						|
--		        "
 | 
						|
--    ::= { snmp 2 }
 | 
						|
 | 
						|
--snmpv3UsmUserEntry     OBJECT-TYPE
 | 
						|
--    SYNTAX       	Snmpv3UsmUserEntry
 | 
						|
--    MAX-ACCESS      	not-accessible
 | 
						|
--    STATUS       	current
 | 
						|
--    DESCRIPTION 	"A user configured for the User-based
 | 
						|
--                 		Security Model.
 | 
						|
--                		"
 | 
						|
--    INDEX       { usmIndex }
 | 
						|
--    ::= { snmpv3UsmUserTable 1 }
 | 
						|
 | 
						|
--Snmpv3UsmUserEntry   ::= SEQUENCE {
 | 
						|
--	usmIndex		INTEGER,
 | 
						|
--	usmSecurityName	SnmpAdminString,
 | 
						|
--    smAuthProtocol  SNMPv3UsmAuthPrivProtocol,
 | 
						|
--    usmPrivPassword	SnmpAdminString
 | 
						|
--    }
 | 
						|
 | 
						|
--usmIndex	  	OBJECT-TYPE
 | 
						|
--    SYNTAX 		INTEGER (1)
 | 
						|
--   MAX-ACCESS   not-accessible
 | 
						|
--    STATUS       current
 | 
						|
--    DESCRIPTION  "Usm configuration index. "
 | 
						|
--    ::= { snmpv3UsmUserEntry 1 }
 | 
						|
 | 
						|
 | 
						|
--usmSecurityName  OBJECT-TYPE
 | 
						|
--    SYNTAX       SnmpAdminString
 | 
						|
--    MAX-ACCESS   read-only
 | 
						|
--   STATUS       current
 | 
						|
--    DESCRIPTION "A human readable string representing the user in
 | 
						|
--                 Security Model independent format.
 | 
						|
 | 
						|
--                The default transformation of the User-based Security
 | 
						|
--                 Model dependent security ID to the securityName and
 | 
						|
--                 vice versa is the identity function so that the
 | 
						|
--                 securityName is the same as the userName.
 | 
						|
--                "
 | 
						|
--    ::= { snmpv3UsmUserEntry 2 }
 | 
						|
 | 
						|
 | 
						|
--usmKeyAlgorithm OBJECT-TYPE
 | 
						|
--    SYNTAX       SNMPv3UsmAuthPrivProtocol
 | 
						|
--    MAX-ACCESS   read-only
 | 
						|
--    STATUS       current
 | 
						|
--    DESCRIPTION  "
 | 
						|
--		     If usmAuthProtocol == HMACMD5Auth , supports MD5 AuthKey and PrivKey
 | 
						|
--		     If usmAuthProtocol == HMACSHAAuth, supports SHA AuthKey and PrivKey
 | 
						|
--                "
 | 
						|
--    ::= { snmpv3UsmUserEntry 3 }
 | 
						|
 | 
						|
--usmPrivProtocol OBJECT-TYPE
 | 
						|
--    SYNTAX       SNMPv3UsmAuthPrivProtocol
 | 
						|
--    MAX-ACCESS   read-only
 | 
						|
 --   STATUS       current
 | 
						|
 --   DESCRIPTION " A privacy protocol to provide encryption and decryption
 | 
						|
--			SNMPv3 pdu.
 | 
						|
 --               "
 | 
						|
 --   ::= { snmpv3UsmUserEntry 4 }
 | 
						|
 | 
						|
--usmPrivPassword OBJECT-TYPE
 | 
						|
--    SYNTAX   SnmpAdminString
 | 
						|
--    MAX-ACCESS   read-only
 | 
						|
--    STATUS       current
 | 
						|
--    DESCRIPTION "An user's privacy password, Associated protocol
 | 
						|
--			and a secret key is used to establish a connection
 | 
						|
--			for the snmp agent and manager commnucation.
 | 
						|
--                "
 | 
						|
--   ::= { snmpv3UsmUserEntry 4 }
 | 
						|
 | 
						|
 | 
						|
-- SNMPv3 Target MIB
 | 
						|
 | 
						|
--snmpv3TargetTable OBJECT-TYPE
 | 
						|
--       SYNTAX      SEQUENCE OF Snmpv3TargetEntry
 | 
						|
--       MAX-ACCESS      not-accessible
 | 
						|
--       STATUS      current
 | 
						|
--       DESCRIPTION
 | 
						|
 --          "A table of SNMP target information to be used
 | 
						|
 --           in the generation of SNMP trap messages."
 | 
						|
 --      ::= { snmp 3 }
 | 
						|
 | 
						|
--snmpv3TargetEntry OBJECT-TYPE
 | 
						|
--       SYNTAX      Snmpv3TargetEntry
 | 
						|
--       MAX-ACCESS      not-accessible
 | 
						|
--       STATUS      current
 | 
						|
--       DESCRIPTION
 | 
						|
--           "A set of SNMP target information.
 | 
						|
--           "
 | 
						|
--       INDEX { snmpv3TargetIndex }
 | 
						|
--       ::= { snmpv3TargetTable 1 }
 | 
						|
 | 
						|
--Snmpv3TargetEntry ::= SEQUENCE {
 | 
						|
--       snmpv3TargetIndex          INTEGER,
 | 
						|
--       snmpv3TargetMPModel        SnmpMessageProcessingModel,
 | 
						|
--       snmpv3TargetSecurityModel  SnmpSecurityModel,
 | 
						|
 --      snmpv3TargetSecurityName   SnmpAdminString
 | 
						|
--}
 | 
						|
--snmpv3TargetIndex OBJECT-TYPE
 | 
						|
 --      SYNTAX      INTEGER(1)
 | 
						|
 --      MAX-ACCESS  	 not-accessible
 | 
						|
 --      STATUS      current
 | 
						|
 --      DESCRIPTION
 | 
						|
 --          "The locally arbitrary, but unique identifier associated
 | 
						|
 --           with this snmpv3TargetEntry."
 | 
						|
 --      ::= { snmpv3TargetEntry 1 }
 | 
						|
 | 
						|
--snmpv3TargetMPModel OBJECT-TYPE
 | 
						|
 --      SYNTAX      SnmpMessageProcessingModel
 | 
						|
 --      MAX-ACCESS      read-only
 | 
						|
 --      STATUS      current
 | 
						|
 --      DESCRIPTION
 | 
						|
 --          "The Message Processing Model to be used when generating
 | 
						|
 --           SNMP messages using this entry."
 | 
						|
 --      ::= { snmpv3TargetEntry 2 }
 | 
						|
 | 
						|
--snmpv3TargetSecurityModel OBJECT-TYPE
 | 
						|
 --      SYNTAX      SnmpSecurityModel (1..2147483647)
 | 
						|
 --      MAX-ACCESS      read-only
 | 
						|
 --     STATUS      current
 | 
						|
  --     DESCRIPTION
 | 
						|
  --         "The Security Model to be used when generating SNMP
 | 
						|
  --           messages using this entry.  An implementation may
 | 
						|
  --           choose to return an inconsistentValue error if an
 | 
						|
  --           attempt is made to set this variable to a value
 | 
						|
  --           for a security model which the implementation does
 | 
						|
  --           not support."
 | 
						|
  --     ::= { snmpv3TargetEntry 3 }
 | 
						|
 | 
						|
--snmpv3TargetSecurityName OBJECT-TYPE
 | 
						|
 --      SYNTAX      SnmpAdminString
 | 
						|
  --     MAX-ACCESS      read-only
 | 
						|
  --     STATUS      current
 | 
						|
  --     DESCRIPTION
 | 
						|
 --          "The securityName which identifies the Principal on
 | 
						|
 --           whose behalf SNMP messages will be generated using
 | 
						|
 --          this entry."
 | 
						|
  --     ::= { snmpv3TargetEntry 4 }
 | 
						|
 | 
						|
--snmpv3TargetSecurityLevel OBJECT-TYPE
 | 
						|
 --      SYNTAX      SnmpSecurityLevel
 | 
						|
  --     MAX-ACCESS      read-only
 | 
						|
  --     STATUS      current
 | 
						|
  --     DESCRIPTION
 | 
						|
  --         "The Level of Security to be used when generating
 | 
						|
  --          SNMP messages using this entry."
 | 
						|
   --    ::= { snmpv3TargetEntry 5 }
 | 
						|
 | 
						|
-- Custom Trap Message
 | 
						|
 | 
						|
customTrapMSG NOTIFICATION-TYPE
 | 
						|
    STATUS  current
 | 
						|
    --OBJECTS { customTrapMSG }
 | 
						|
    DESCRIPTION "Display custom trap message."
 | 
						|
        ::= { pe 5 }
 | 
						|
 | 
						|
rebootDevice OBJECT-TYPE
 | 
						|
	SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    MAX-ACCESS read-write
 | 
						|
	STATUS current
 | 
						|
	DESCRIPTION "Reboot PE Device"
 | 
						|
        ::= { pe 6 }
 | 
						|
-- CPM
 | 
						|
--modelName OBJECT-TYPE
 | 
						|
--	SYNTAX DisplayString
 | 
						|
--	MAX-ACCESS read-only
 | 
						|
--	STATUS current
 | 
						|
--	DESCRIPTION
 | 
						|
--		"Indicate CPM device model name."
 | 
						|
--	::= { CPM 1 }
 | 
						|
 | 
						|
--cpmName OBJECT-TYPE
 | 
						|
--	SYNTAX DisplayString
 | 
						|
--	MAX-ACCESS read-write
 | 
						|
--	STATUS current
 | 
						|
--	DESCRIPTION
 | 
						|
--		"The name of CPM device.
 | 
						|
--		string length: 1~39
 | 
						|
--		NOTE: Input string as /empty to set this object to NULL.
 | 
						|
--		"
 | 
						|
--	::= { CPM 2 }
 | 
						|
 | 
						|
--cpmswitchable OBJECT-TYPE
 | 
						|
--   SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        " Switchable or not. "
 | 
						|
--    ::= { CPM 3 }
 | 
						|
 | 
						|
--cpmPDUreading OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        " CPM is per-PDU reading or not."
 | 
						|
--    ::= { CPM 4 }
 | 
						|
 | 
						|
--cpmSensornumber OBJECT-TYPE
 | 
						|
--   SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        " CPM's Sensor number."
 | 
						|
--    ::= { CPM 5 }
 | 
						|
 | 
						|
--cpmOutletnumber OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        " CPM's Outlet number."
 | 
						|
--    ::= { CPM 6 }
 | 
						|
 | 
						|
--cpmbreaker OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER { off(1), on(2) }
 | 
						|
    --MAX-ACCESS read-only
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "CPM's breaker status."
 | 
						|
    --::= { CPM 7 }
 | 
						|
 | 
						|
-- Device
 | 
						|
--cpmdeviceValueTable OBJECT-TYPE
 | 
						|
--    SYNTAX SEQUENCE OF cpmDeviceValueEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device value table. This table displays device's current.
 | 
						|
--		"
 | 
						|
--    ::= { CPMDevice 1 }
 | 
						|
 | 
						|
--cpmdeviceValueEntry OBJECT-TYPE
 | 
						|
--    SYNTAX cpmDeviceValueEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Single deviceValue entry containing device info."
 | 
						|
--    INDEX { cpmdeviceValueIndex }
 | 
						|
--     ::= { cpmdeviceValueTable 1 }
 | 
						|
 | 
						|
--cpmDeviceValueEntry ::=
 | 
						|
--    SEQUENCE {
 | 
						|
--        cpmdeviceValueIndex
 | 
						|
--            INTEGER,
 | 
						|
--        cpmdeviceCurrent
 | 
						|
--            DisplayString,
 | 
						|
        --cpmdeviceVoltage
 | 
						|
        --    DisplayString,
 | 
						|
		--cpmdevicePower
 | 
						|
        --    DisplayString,
 | 
						|
		--cpmdevicePowerDissipation
 | 
						|
        --    DisplayString,
 | 
						|
        --cpminputMaxVoltage
 | 
						|
        --	INTEGER,
 | 
						|
--        cpminputMaxCurrent
 | 
						|
--        	INTEGER
 | 
						|
        --cpmpowerCapacity
 | 
						|
        --	INTEGER
 | 
						|
 | 
						|
--    }
 | 
						|
 | 
						|
--cpmdeviceValueIndex  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (1)
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Index of device Value."
 | 
						|
--    ::= { cpmdeviceValueEntry 1 }
 | 
						|
 | 
						|
--cpmdeviceCurrent  OBJECT-TYPE
 | 
						|
--    SYNTAX DisplayString
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device electric current value.
 | 
						|
--        "
 | 
						|
--    ::= { cpmdeviceValueEntry 2 }
 | 
						|
 | 
						|
--cpmdeviceVoltage  OBJECT-TYPE
 | 
						|
--    SYNTAX DisplayString
 | 
						|
--   MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device voltage value."
 | 
						|
--    ::= { cpmdeviceValueEntry 3 }
 | 
						|
--cpmdevicePower  OBJECT-TYPE
 | 
						|
--    SYNTAX DisplayString
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device power value."
 | 
						|
--    ::= { cpmdeviceValueEntry 4 }
 | 
						|
 | 
						|
--cpmdevicePowerDissipation  OBJECT-TYPE
 | 
						|
--    SYNTAX DisplayString
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device power dissipation value."
 | 
						|
--    ::= { cpmdeviceValueEntry 5 }
 | 
						|
 | 
						|
--cpminputMaxVoltage  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device input Voltage value. unit:(V)"
 | 
						|
--    ::= { cpmdeviceValueEntry 6 }
 | 
						|
 | 
						|
--cpminputMaxCurrent  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device input Current value. unit:(A)"
 | 
						|
--    ::= { cpmdeviceValueEntry 7 }
 | 
						|
 | 
						|
--cpmpowerCapacity  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device power Capacity value.unit:(VA)"
 | 
						|
--    ::= { cpmdeviceValueEntry 8 }
 | 
						|
 | 
						|
--cpmdeviceConfigTable OBJECT-TYPE
 | 
						|
--    SYNTAX SEQUENCE OF cpmDeviceConfigEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Device configuration table"
 | 
						|
--    ::= { CPMDevice 2 }
 | 
						|
 | 
						|
--cpmdeviceConfigEntry OBJECT-TYPE
 | 
						|
--    SYNTAX cpmDeviceConfigEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Single deviceConfig entry containing device info."
 | 
						|
--    INDEX { cpmdeviceConfigIndex }
 | 
						|
--     ::= { cpmdeviceConfigTable 1 }
 | 
						|
 | 
						|
--cpmDeviceConfigEntry ::=
 | 
						|
--    SEQUENCE {
 | 
						|
--        cpmdeviceConfigIndex
 | 
						|
--            INTEGER,
 | 
						|
        --cpmdeviceMinCurMT
 | 
						|
        --    INTEGER,
 | 
						|
--        cpmdeviceMaxCurMT
 | 
						|
--            INTEGER
 | 
						|
		--cpmdeviceMinVolMT
 | 
						|
        --    INTEGER,
 | 
						|
        --cpmdeviceMaxVolMT
 | 
						|
        --    INTEGER,
 | 
						|
--    }
 | 
						|
 | 
						|
--cpmdeviceConfigIndex  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (1)
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Index of deviceConfig"
 | 
						|
--    ::= { cpmdeviceConfigEntry 1 }
 | 
						|
 | 
						|
--cpmdeviceMinCurMT  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-write
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display or set device minimum electric current measurement threshold.
 | 
						|
--        When this value is -3000,it indicate this is NULL.
 | 
						|
--        When set this value to -3000, indicate set this object as NULL.
 | 
						|
--        range:0.0~32.0 represents:0~320
 | 
						|
--        NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
--        "
 | 
						|
--    ::= { cpmdeviceConfigEntry 2 }
 | 
						|
 | 
						|
--cpmdeviceMaxCurMT  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-write
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display or set device maximum electric current measurement threshold.
 | 
						|
--        When this value is -3000,it indicate this is NULL.
 | 
						|
--        When set this value to -3000, indicate set this object as NULL.
 | 
						|
--        Example: range 0.0~32.0 represents: 0~320
 | 
						|
 | 
						|
--        NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
--       "
 | 
						|
--    ::= { cpmdeviceConfigEntry 3 }
 | 
						|
 | 
						|
--cpmdeviceMinVolMT  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (900..2600 | -3000)
 | 
						|
--    MAX-ACCESS read-write
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display or set device minimum voltage measurement threshold.
 | 
						|
--        range:90.0~260.0 represents:900~2600
 | 
						|
--        When this value is -3000,it indicate this is NULL.
 | 
						|
--        When set this value to -3000, indicate set this object as NULL.
 | 
						|
--        NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
--        "
 | 
						|
--    ::= { cpmdeviceConfigEntry 4 }
 | 
						|
 | 
						|
--cpmdeviceMaxVolMT  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (900..2600 | -3000)
 | 
						|
--    MAX-ACCESS read-write
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display or set device maximum voltage measurement threshold.
 | 
						|
--        range:90.0~260.0 represents:900~2600
 | 
						|
--        When this value is -3000,it indicate this is NULL.
 | 
						|
--        When set this value to -3000, indicate set this object as NULL.
 | 
						|
--        NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
--       "
 | 
						|
--    ::= { cpmdeviceConfigEntry 5 }
 | 
						|
 | 
						|
 | 
						|
 | 
						|
-- Sensor
 | 
						|
--cpmSensorValueTable OBJECT-TYPE
 | 
						|
--    SYNTAX SEQUENCE OF cpmSensorValueEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "CPM's sensor value table. This table displays sensor's temperature, humidity and
 | 
						|
--		 pressure.
 | 
						|
--		"
 | 
						|
--    ::= { Sensor 1 }
 | 
						|
 | 
						|
--cpmSensorValueEntry OBJECT-TYPE
 | 
						|
--    SYNTAX cpmSensorValueEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "CPM's sensor value entry containing Sensor info."
 | 
						|
--    INDEX { cpmSensorValueIndex }
 | 
						|
--     ::= { cpmSensorValueTable 1 }
 | 
						|
 | 
						|
--cpmSensorValueEntry ::=
 | 
						|
--   SEQUENCE {
 | 
						|
--    	cpmSensorValueIndex
 | 
						|
--    		INTEGER,
 | 
						|
--		cpmSensorTemperature
 | 
						|
--            DisplayString,
 | 
						|
--		cpmSensorHumidity
 | 
						|
--			DisplayString,
 | 
						|
--		cpmSensorPressure
 | 
						|
--			DisplayString,
 | 
						|
--		cpmSensorProperty
 | 
						|
--			INTEGER
 | 
						|
--    }
 | 
						|
 | 
						|
--cpmSensorValueIndex  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (1..4)
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Index of CPM's Sensor number."
 | 
						|
--    ::= { cpmSensorValueEntry 1 }
 | 
						|
 | 
						|
--cpmSensorTemperature  OBJECT-TYPE
 | 
						|
--    SYNTAX DisplayString
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "CPM's Sensor Temperature value."
 | 
						|
--    ::= { cpmSensorValueEntry 2 }
 | 
						|
 | 
						|
--cpmSensorHumidity  OBJECT-TYPE
 | 
						|
--    SYNTAX DisplayString
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "CPM's Sensor Humidity value."
 | 
						|
--    ::= { cpmSensorValueEntry 3 }
 | 
						|
 | 
						|
--cpmSensorPressure  OBJECT-TYPE
 | 
						|
--    SYNTAX DisplayString
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "CPM's Sensor Pressure value."
 | 
						|
--    ::= { cpmSensorValueEntry 4 }
 | 
						|
 | 
						|
--cpmSensorProperty  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER { intake(1), exhaust(2) }
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "CPM's Sensor Property."
 | 
						|
--    ::= { cpmSensorValueEntry 5 }
 | 
						|
 | 
						|
--cpmSensorThresholdTable OBJECT-TYPE
 | 
						|
--    SYNTAX SEQUENCE OF cpmSensorThresholdEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "CPM's Sensor value table"
 | 
						|
--    ::= { Sensor 2 }
 | 
						|
 | 
						|
--cpmSensorThresholdEntry OBJECT-TYPE
 | 
						|
--    SYNTAX cpmSensorThresholdEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--   DESCRIPTION
 | 
						|
--        "CPM's sensor threshold entry containing sensor info."
 | 
						|
--    INDEX { cpmSensorThresholdIndex }
 | 
						|
--     ::= { cpmSensorThresholdTable 1 }
 | 
						|
 | 
						|
--cpmSensorThresholdEntry ::=
 | 
						|
--    SEQUENCE {
 | 
						|
--        cpmSensorThresholdIndex
 | 
						|
--            INTEGER,
 | 
						|
--        cpmsensorMinTempMT
 | 
						|
--            INTEGER,
 | 
						|
--        cpmsensorMaxTempMT
 | 
						|
--            INTEGER,
 | 
						|
 | 
						|
--		cpmsensorMinHumMT
 | 
						|
--            INTEGER,
 | 
						|
--		cpmsensorMaxHumMT
 | 
						|
--            INTEGER,
 | 
						|
--		cpmsensorMinPressMT
 | 
						|
--            INTEGER,
 | 
						|
--        cpmsensorMaxPressMT
 | 
						|
--            INTEGER
 | 
						|
        --sensorTempFlu
 | 
						|
            --INTEGER,
 | 
						|
        --sensorHumFlu
 | 
						|
			--INTEGER,
 | 
						|
		--sensorPressFlu
 | 
						|
            --INTEGER
 | 
						|
--    }
 | 
						|
 | 
						|
--cpmSensorThresholdIndex  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (1..4)
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Index of CPM's sensor number"
 | 
						|
--    ::= { cpmSensorThresholdEntry 1 }
 | 
						|
 | 
						|
--cpmsensorMinTempMT  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (-200..600 | -3000)
 | 
						|
--    MAX-ACCESS read-write
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display or set sensor minimum temperature measurement threshold.
 | 
						|
--        Example: range 0.0 ~ 60.0 represents 0~600
 | 
						|
--        When this value is -3000,it indicate this is NULL.
 | 
						|
--        When set this value to -3000, indicate set this object as NULL.
 | 
						|
 | 
						|
--        NOTICE:Minimum threshold should be setted smaller than Maxima threshold.
 | 
						|
--        "
 | 
						|
--    ::= { cpmSensorThresholdEntry 2 }
 | 
						|
 | 
						|
--cpmsensorMaxTempMT  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (-200..600 | -3000)
 | 
						|
--    MAX-ACCESS read-write
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display or set sensor maximum temperature measurement threshold.
 | 
						|
--        Example: range 0.0 ~ 60.0 represents 0~600
 | 
						|
--        When this value is -3000,it indicate this is NULL.
 | 
						|
--        When set this value to -3000, indicate set this object as NULL.
 | 
						|
 | 
						|
--        NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
--        "
 | 
						|
--    ::= { cpmSensorThresholdEntry 3 }
 | 
						|
 | 
						|
--cpmsensorMinHumMT  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (150..950 | -3000)
 | 
						|
--    MAX-ACCESS read-write
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display or set sensor minimum humidity measurement threshold.
 | 
						|
--        Example: range 15.0 ~ 95.0 represents 150~950
 | 
						|
--        When this value is -3000,it indicate this is NULL.
 | 
						|
--        When set this value to -3000, indicate set this object as NULL.
 | 
						|
 | 
						|
--        NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
--        "
 | 
						|
--    ::= { cpmSensorThresholdEntry 4 }
 | 
						|
--cpmsensorMaxHumMT  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (150..950 | -3000)
 | 
						|
--    MAX-ACCESS read-write
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display or set sensor maximum humidity measurement threshold.
 | 
						|
--        Example: range 15.0 ~ 95.0 represents 150~950
 | 
						|
--        When this value is -3000,it indicate this is NULL.
 | 
						|
--        When set this value to -3000, indicate set this object as NULL.
 | 
						|
 | 
						|
--        NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
--        "
 | 
						|
--    ::= { cpmSensorThresholdEntry 5 }
 | 
						|
 | 
						|
--cpmsensorMinPressMT  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (-2500..2500 | -3000)
 | 
						|
--    MAX-ACCESS read-write
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display or set sensor minimum pressure measurement threshold.
 | 
						|
--        Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
 | 
						|
--        When this value is -3000,it indicate this is NULL.
 | 
						|
--        When set this value to -3000, indicate set this object as NULL.
 | 
						|
 | 
						|
--        NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
--        "
 | 
						|
--    ::= { cpmSensorThresholdEntry 6 }
 | 
						|
 | 
						|
--cpmsensorMaxPressMT  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (-2500..2500 | -3000)
 | 
						|
--   MAX-ACCESS read-write
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display or set sensor maximum pressure measurement threshold.
 | 
						|
--        Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
 | 
						|
--        When this value is -3000,it indicate this is NULL.
 | 
						|
--        When set this value to -3000, indicate set this object as NULL.
 | 
						|
 | 
						|
--        NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
--        "
 | 
						|
--    ::= { cpmSensorThresholdEntry 7 }
 | 
						|
 | 
						|
 | 
						|
-- pdu
 | 
						|
 | 
						|
--cpmPDUValueTable OBJECT-TYPE
 | 
						|
--    SYNTAX SEQUENCE OF cpmPDUValueEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display the PDU's current value of CPM"
 | 
						|
--    ::= { EnergySensor 1 }
 | 
						|
 | 
						|
--cpmPDUValueEntry OBJECT-TYPE
 | 
						|
--    SYNTAX cpmPDUValueEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "CPM's monitor pdu Value entry containing outlet info."
 | 
						|
--    INDEX { cpmPDUValueIndex }
 | 
						|
--     ::= { cpmPDUValueTable 1 }
 | 
						|
 | 
						|
--cpmPDUValueEntry ::=
 | 
						|
--    SEQUENCE {
 | 
						|
--        cpmPDUValueIndex
 | 
						|
--            INTEGER,
 | 
						|
--        cpmPDUCurrent
 | 
						|
--           DisplayString,
 | 
						|
        --cpmPDUVoltage
 | 
						|
        --    DisplayString,
 | 
						|
		--cpmPDUPower
 | 
						|
        --    DisplayString,
 | 
						|
		--cpmPDUPowerDissipation
 | 
						|
        --    DisplayString,
 | 
						|
--        cpmPDUMaxCurrent
 | 
						|
--        	INTEGER
 | 
						|
--    }
 | 
						|
 | 
						|
--cpmPDUValueIndex  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (1..4)
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Index of PDU number"
 | 
						|
--    ::= { cpmPDUValueEntry 1 }
 | 
						|
 | 
						|
--cpmPDUCurrent  OBJECT-TYPE
 | 
						|
--    SYNTAX DisplayString
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "CPM's monitor PDU electric current value"
 | 
						|
--    ::= { cpmPDUValueEntry 2 }
 | 
						|
 | 
						|
--cpmPDUVoltage  OBJECT-TYPE
 | 
						|
    --SYNTAX DisplayString
 | 
						|
    --MAX-ACCESS read-only
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "CPM's monitor PDU voltage value"
 | 
						|
    --::= { cpmPDUValueEntry 3 }
 | 
						|
 | 
						|
--cpmPDUPower  OBJECT-TYPE
 | 
						|
    --SYNTAX DisplayString
 | 
						|
    --MAX-ACCESS read-only
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "CPM's monitor PDU power value"
 | 
						|
    --::= { cpmPDUValueEntry 4 }
 | 
						|
 | 
						|
--cpmPDUPowerDissipation  OBJECT-TYPE
 | 
						|
    --SYNTAX DisplayString
 | 
						|
    --MAX-ACCESS read-only
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "CPM's monitor PDU power dissipation value"
 | 
						|
    --::= { cpmPDUValueEntry 5 }
 | 
						|
 | 
						|
--cpmPDUMaxCurrent  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "CPM's monitor PDU Max Current value. unit: (A)"
 | 
						|
--    ::= { cpmPDUValueEntry 6 }
 | 
						|
 | 
						|
--cpmBankStatus  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER { noattached(1), attached(2) }
 | 
						|
--    MAX-ACCESS read-only
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "The status CPM device Bank status."
 | 
						|
--    ::= { cpmPDUValueEntry 7 }
 | 
						|
 | 
						|
 | 
						|
--cpmPDUConfigTable OBJECT-TYPE
 | 
						|
--    SYNTAX SEQUENCE OF cpmPDUConfigEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "CPM's monitor PDU configuration table"
 | 
						|
--    ::= { EnergySensor 2 }
 | 
						|
 | 
						|
--cpmPDUConfigEntry OBJECT-TYPE
 | 
						|
--    SYNTAX cpmPDUConfigEntry
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "CPM's monitor PDU config entry containing PDU info."
 | 
						|
--    INDEX { cpmPDUConfigIndex }
 | 
						|
--     ::= { cpmPDUConfigTable 1 }
 | 
						|
 | 
						|
--cpmPDUConfigEntry ::=
 | 
						|
--    SEQUENCE {
 | 
						|
--        cpmPDUConfigIndex
 | 
						|
--            INTEGER,
 | 
						|
--		cpmPDUName
 | 
						|
--            DisplayString,
 | 
						|
        --cpmPDUConfirmation
 | 
						|
        --    INTEGER,
 | 
						|
        --cpmPDUOnDelayTime
 | 
						|
        --    INTEGER,
 | 
						|
		--cpmPDUOffDelayTime
 | 
						|
        --    INTEGER,
 | 
						|
		--cpmPDUShutdownMethod
 | 
						|
        --    INTEGER,
 | 
						|
        --cpmPDUMAC
 | 
						|
        --    DisplayString,
 | 
						|
		--cpmPDUMinCurMT
 | 
						|
        --    INTEGER,
 | 
						|
--		cpmPDUMaxCurMT
 | 
						|
--           INTEGER
 | 
						|
 | 
						|
        --cpmPDUMinVolMT
 | 
						|
        --    INTEGER,
 | 
						|
		--cpmPDUMaxVolMT
 | 
						|
        --    INTEGER,
 | 
						|
 | 
						|
 | 
						|
--    }
 | 
						|
 | 
						|
--cpmPDUConfigIndex  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER (1..4)
 | 
						|
--    MAX-ACCESS not-accessible
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Index of PDU number"
 | 
						|
--    ::= { cpmPDUConfigEntry 1 }
 | 
						|
 | 
						|
--cpmPDUName  OBJECT-TYPE
 | 
						|
--    SYNTAX DisplayString
 | 
						|
--    MAX-ACCESS read-write
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display or set the name of pdu.
 | 
						|
--        string length: 0~15
 | 
						|
--        NOTE: Input string as /empty to set this object to NULL.
 | 
						|
--        "
 | 
						|
--    ::= { cpmPDUConfigEntry 2 }
 | 
						|
 | 
						|
--cpmPDUConfirmation  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER { no(1), yes(2) }
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display or set the confirmation of outlet."
 | 
						|
    --::= { cpmPDUConfigEntry 3 }
 | 
						|
 | 
						|
--cpmPDUOnDelayTime  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER (0..999)
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display or set the ON delay time of outlet."
 | 
						|
    --::= { cpmPDUConfigEntry 4 }
 | 
						|
 | 
						|
--cpmPDUOffDelayTime  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER (0..999)
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display or set the OFF delay time of outlet."
 | 
						|
    --::= { cpmPDUConfigEntry 5 }
 | 
						|
 | 
						|
--cpmPDUShutdownMethod  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER { kill-the-power(1), wake-on-lan(2), after-ac-back(3) }
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display or set the shutdown mehtod of outlet."
 | 
						|
    --::= { cpmPDUConfigEntry 6 }
 | 
						|
 | 
						|
--cpmPDUMAC  OBJECT-TYPE
 | 
						|
    --SYNTAX DisplayString
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display or set the MAC address of ShutdownMethod.
 | 
						|
    --    string length: 12
 | 
						|
    --    "
 | 
						|
    --::= { cpmPDUConfigEntry 7 }
 | 
						|
 | 
						|
--cpmPDUMinCurMT  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-write
 | 
						|
--    STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display or set the PDU minimum electric current measurment threshold.
 | 
						|
--         Range:0.0 ~16.0 rerpresnts 0~160
 | 
						|
--         When this value is -3000,it indicate this is NULL.
 | 
						|
--         When set this value to -3000, indicate set this object as NULL.
 | 
						|
--
 | 
						|
--         NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
--        "
 | 
						|
--    ::= { cpmPDUConfigEntry 3 }
 | 
						|
 | 
						|
--cpmPDUMaxCurMT  OBJECT-TYPE
 | 
						|
--    SYNTAX INTEGER
 | 
						|
--    MAX-ACCESS read-write
 | 
						|
--   STATUS current
 | 
						|
--    DESCRIPTION
 | 
						|
--        "Display or set the PDU maximum electric current measurment threshold.
 | 
						|
--         Example: range 0.0 ~16.0 represents 0~160
 | 
						|
--        When this value is -3000,it indicate this is NULL.
 | 
						|
--         When set this value to -3000, indicate set this object as NULL.
 | 
						|
 | 
						|
--         NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
--        "
 | 
						|
--    ::= { cpmPDUConfigEntry 4 }
 | 
						|
 | 
						|
--cpmPDUMinVolMT  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER (900..2600)
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display or set the outlet minimum voltage measurment threshold.
 | 
						|
    --    Range:90.0 ~260.0 represents 900~2600
 | 
						|
    --    When this value is -3000,it indicate this is NULL.
 | 
						|
    --    When set this value to -3000, indicate set this object as NULL.
 | 
						|
    --    NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
    --    "
 | 
						|
    --::= { cpmPDUConfigEntry 10 }
 | 
						|
 | 
						|
--cpmPDUMaxVolMT  OBJECT-TYPE
 | 
						|
    --SYNTAX INTEGER (900..2600)
 | 
						|
    --MAX-ACCESS read-write
 | 
						|
    --STATUS current
 | 
						|
    --DESCRIPTION
 | 
						|
    --    "Display or set the outlet maximum voltage measurment threshold.
 | 
						|
    --    Range:90.0 ~260.0 represents 900~2600
 | 
						|
    --    When this value is -3000,it indicate this is NULL.
 | 
						|
    --    When set this value to -3000, indicate set this object as NULL.
 | 
						|
    --    NOTICE:Minimum threshold should be setted smaller than Maxima threshold
 | 
						|
    --    "
 | 
						|
    --::= { cpmPDUConfigEntry 11 }
 | 
						|
 | 
						|
 | 
						|
END
 |