--defines ROOMALERT11E-MIB for SNMP agent extension of Room Alert 11E
 | 
						|
--Contents:	Global Registration Module
 | 
						|
--		Room Alert OIDs - Enterprise 20916
 | 
						|
--Version:	1.1.3 
 | 
						|
--Date:		9 January 2014
 | 
						|
--Developed By: AVTECH Software, Inc.
 | 
						|
 | 
						|
--
 | 
						|
--Copyright (c) 2014 AVTECH Software, Inc.
 | 
						|
--
 | 
						|
 | 
						|
ROOMALERT11E-MIB DEFINITIONS ::= BEGIN
 | 
						|
 | 
						|
 | 
						|
IMPORTS
 | 
						|
	enterprises, IpAddress, Counter, TimeTicks
 | 
						|
		FROM RFC1155-SMI
 | 
						|
	OBJECT-TYPE
 | 
						|
		FROM RFC-1212
 | 
						|
	TRAP-TYPE 
 | 
						|
		FROM RFC-1215;
 | 
						|
 | 
						|
 | 
						|
avtech      OBJECT IDENTIFIER ::= { enterprises 20916 }
 | 
						|
products      OBJECT IDENTIFIER ::= { avtech 1 }
 | 
						|
roomalert11E      OBJECT IDENTIFIER ::= { products 3 }
 | 
						|
sensors       OBJECT IDENTIFIER ::= { roomalert11E 1 }
 | 
						|
traps	      OBJECT IDENTIFIER ::= { roomalert11E 2 }
 | 
						|
thresholds    OBJECT IDENTIFIER ::= { roomalert11E 3 }
 | 
						|
channel1   OBJECT IDENTIFIER ::= { sensors 1 }
 | 
						|
channel2   OBJECT IDENTIFIER ::= { sensors 2 }
 | 
						|
channel3   OBJECT IDENTIFIER ::= { sensors 3 }
 | 
						|
channel4   OBJECT IDENTIFIER ::= { sensors 4 }
 | 
						|
channels   OBJECT IDENTIFIER ::= { thresholds 1 }
 | 
						|
channels1   OBJECT IDENTIFIER ::= { channels 1 }
 | 
						|
channels2   OBJECT IDENTIFIER ::= { channels 2 }
 | 
						|
channels3   OBJECT IDENTIFIER ::= { channels 3 }
 | 
						|
channels4   OBJECT IDENTIFIER ::= { channels 4 }
 | 
						|
 
 | 
						|
-- Room Alert 11E MIB
 | 
						|
-- Parameters 
 | 
						|
 | 
						|
sensor1-1 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..1)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for internal switch sensor 1 (0 = OPEN, 1 = CLOSED)."
 | 
						|
::= { channel1 1 }
 | 
						|
 | 
						|
sensor1-2 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..1)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for internal switch sensor 2 (0 = OPEN, 1 = CLOSED)."
 | 
						|
::= { channel1 2 }
 | 
						|
 | 
						|
sensor1-3 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..1)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for internal switch sensor 3 (0 = OPEN, 1 = CLOSED)."
 | 
						|
::= { channel1 3 }
 | 
						|
 | 
						|
sensor1-4 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..1)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for internal switch sensor 4 (0 = OPEN, 1 = CLOSED)."
 | 
						|
::= { channel1 4 }
 | 
						|
 | 
						|
sensor1-5 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..1)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for internal switch sensor 5 (0 = OPEN, 1 = CLOSED)."
 | 
						|
::= { channel1 5 }
 | 
						|
 | 
						|
sensor1-6 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..1)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for internal switch sensor 6 (0 = OPEN, 1 = CLOSED)."
 | 
						|
::= { channel1 6 }
 | 
						|
 | 
						|
sensor1-7 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..1)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for internal switch sensor 7 (0 = OPEN, 1 = CLOSED)."
 | 
						|
::= { channel1 7 }
 | 
						|
 | 
						|
sensor1-8 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..1)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for internal switch sensor 8 (0 = OPEN, 1 = CLOSED)."
 | 
						|
::= { channel1 8 }
 | 
						|
 | 
						|
switch-label-1 OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION "The label for switch sensor 1"
 | 
						|
::= { channel1 9 }
 | 
						|
 | 
						|
switch-label-2 OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION "The label for switch sensor 2"
 | 
						|
::= { channel1 10 }
 | 
						|
 | 
						|
switch-label-3 OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION "The label for switch sensor 3"
 | 
						|
::= { channel1 11 }
 | 
						|
 | 
						|
switch-label-4 OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION "The label for switch sensor 4"
 | 
						|
::= { channel1 12 }
 | 
						|
 | 
						|
switch-label-5 OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION "The label for switch sensor 5"
 | 
						|
::= { channel1 13 }
 | 
						|
 | 
						|
switch-label-6 OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION "The label for switch sensor 6"
 | 
						|
::= { channel1 14 }
 | 
						|
 | 
						|
switch-label-7 OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION "The label for switch sensor 7"
 | 
						|
::= { channel1 15 }
 | 
						|
 | 
						|
switch-label-8 OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION "The label for switch sensor 8"
 | 
						|
::= { channel1 16 }
 | 
						|
 | 
						|
sensor2-1 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 2-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
 | 
						|
::= { channel2 1 }
 | 
						|
 | 
						|
sensor2-2 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 2-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
 | 
						|
::= { channel2 2 }
 | 
						|
 | 
						|
sensor2-3 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 2-3. If temp/humidity sensor is connected, value will be current %RH."
 | 
						|
::= { channel2 3 }
 | 
						|
 | 
						|
sensor2-4 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 2-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
 | 
						|
::= { channel2 4 }
 | 
						|
 | 
						|
sensor2-5 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 2-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
 | 
						|
::= { channel2 5 }
 | 
						|
 | 
						|
sensor2-6-label OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION "The label of this sensor"
 | 
						|
::= { channel2 6}
 | 
						|
 | 
						|
sensor3-1 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 3-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
 | 
						|
::= { channel3 1 }
 | 
						|
 | 
						|
sensor3-2 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 3-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
 | 
						|
::= { channel3 2 }
 | 
						|
 | 
						|
sensor3-3 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 3-3. If temp/humidity sensor is connected, value will be current %RH."
 | 
						|
::= { channel3 3 }
 | 
						|
 | 
						|
sensor3-4 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 3-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
 | 
						|
::= { channel3 4 }
 | 
						|
 | 
						|
sensor3-5 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 3-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
 | 
						|
::= { channel3 5 }
 | 
						|
 | 
						|
sensor3-6-label OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION "The label of this sensor"
 | 
						|
::= { channel3 6}
 | 
						|
 | 
						|
sensor4-1 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 4-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius."
 | 
						|
::= { channel4 1 }
 | 
						|
 | 
						|
sensor4-2 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 4-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit."
 | 
						|
::= { channel4 2 }
 | 
						|
 | 
						|
sensor4-3 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 4-3. If temp/humidity sensor is connected, value will be current %RH."
 | 
						|
::= { channel4 3 }
 | 
						|
 | 
						|
sensor4-4 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 4-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit."
 | 
						|
::= { channel4 4 }
 | 
						|
 | 
						|
sensor4-5 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"The reading for sensor 4-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius."
 | 
						|
::= { channel4 5 }
 | 
						|
 | 
						|
sensor4-6-label OBJECT-TYPE
 | 
						|
	SYNTAX		OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION "The label of this sensor"
 | 
						|
::= { channel4 6}
 | 
						|
 | 
						|
alarm1 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..255)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Alarm for sensor channel 1. The binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
 | 
						|
::= { traps 1 }
 | 
						|
	
 | 
						|
alarm2 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..255)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Alarm for sensor channel 2. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
 | 
						|
::= { traps 2 }
 | 
						|
	
 | 
						|
alarm3 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..255)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Alarm for sensor channel 3. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
 | 
						|
::= { traps 3 }
 | 
						|
	
 | 
						|
alarm4 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..255)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Alarm for sensor channel 4. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2 = low temp alarm, 3 = humidity alarm. If a Switch Sensor Expansion box is connected, the binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = sensor ok, 1 = sensor in alarm state). For example, if switch sensors 1 and 4 are in alarm state, the value displayed will be 9, which equals 00001001 in binary."
 | 
						|
::= { traps 4 }	
 | 
						|
	
 | 
						|
alarmMessage1 OBJECT-TYPE
 | 
						|
	SYNTAX  	OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Alarm Message from sensor channel 1 (Internal)"
 | 
						|
::= { traps 5 }	
 | 
						|
	
 | 
						|
alarmMessage2 OBJECT-TYPE
 | 
						|
	SYNTAX  	OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Alarm Message from sensor channel 2 (External)"
 | 
						|
::= { traps 6 }	
 | 
						|
	
 | 
						|
alarmMessage3 OBJECT-TYPE
 | 
						|
	SYNTAX  	OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Alarm Message from sensor channel 3 (External)"
 | 
						|
::= { traps 7 }	
 | 
						|
	
 | 
						|
alarmMessage4 OBJECT-TYPE
 | 
						|
	SYNTAX  	OCTET STRING
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Alarm Message from sensor channel 4 (External)"
 | 
						|
::= { traps 8 }	
 | 
						|
	
 | 
						|
threshold1-1 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 1 defined for Channel 1"
 | 
						|
::= { channels1 1 }		
 | 
						|
	
 | 
						|
threshold1-2 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 2 defined for Channel 1"
 | 
						|
::= { channels1 2 }
 | 
						|
	
 | 
						|
threshold1-3 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 3 defined for Channel 1"
 | 
						|
::= { channels1 3 }		
 | 
						|
	
 | 
						|
threshold1-4 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 4 defined for Channel 1"
 | 
						|
::= { channels1 4 }
 | 
						|
	
 | 
						|
threshold1-5 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 5 defined for Channel 1"
 | 
						|
::= { channels1 5 }
 | 
						|
	
 | 
						|
threshold1-6 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 6 defined for Channel 1"
 | 
						|
::= { channels1 6 }
 | 
						|
	
 | 
						|
threshold1-7 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 7 defined for Channel 1"
 | 
						|
::= { channels1 7 }
 | 
						|
	
 | 
						|
threshold1-8 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 8 defined for Channel 1"
 | 
						|
::= { channels1 8 }
 | 
						|
	
 | 
						|
threshold2-1 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 1 defined for Channel 2"
 | 
						|
::= { channels2 1 }		
 | 
						|
	
 | 
						|
threshold2-2 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 2 defined for Channel 2"
 | 
						|
::= { channels2 2 }
 | 
						|
	
 | 
						|
threshold2-3 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 3 defined for Channel 2"
 | 
						|
::= { channels2 3 }		
 | 
						|
	
 | 
						|
threshold2-4 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 4 defined for Channel 2"
 | 
						|
::= { channels2 4 }
 | 
						|
	
 | 
						|
threshold3-1 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 1 defined for Channel 3"
 | 
						|
::= { channels3 1 }		
 | 
						|
	
 | 
						|
threshold3-2 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 2 defined for Channel 3"
 | 
						|
::= { channels3 2 }
 | 
						|
	
 | 
						|
threshold3-3 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 3 defined for Channel 3"
 | 
						|
::= { channels3 3 }		
 | 
						|
	
 | 
						|
threshold3-4 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 4 defined for Channel 3"
 | 
						|
::= { channels3 4 }
 | 
						|
	
 | 
						|
threshold4-1 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 1 defined for Channel 4"
 | 
						|
::= { channels4 1 }		
 | 
						|
	
 | 
						|
threshold4-2 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 2 defined for Channel 4"
 | 
						|
::= { channels4 2 }
 | 
						|
	
 | 
						|
threshold4-3 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 3 defined for Channel 4"
 | 
						|
::= { channels4 3 }		
 | 
						|
	
 | 
						|
threshold4-4 OBJECT-TYPE
 | 
						|
	SYNTAX  	INTEGER(0..65535)
 | 
						|
	ACCESS		read-only
 | 
						|
	STATUS		mandatory
 | 
						|
	DESCRIPTION	"Threshold 4 defined for Channel 4"
 | 
						|
::= { channels4 4 }
 | 
						|
	
 | 
						|
	
 | 
						|
-- ROOMALERT11E TRAPS
 | 
						|
 | 
						|
tempAlarm1-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage2, sensor2-1, sensor2-2, sensor2-1 }
 | 
						|
	DESCRIPTION	"A tempAlarm1 trap signifies that the current
 | 
						|
			temperature on external sensor 1 is outside the 
 | 
						|
			defined high or low threshold."
 | 
						|
::= 1
 | 
						|
	
 | 
						|
room-alert-11E-SNMP-trap TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1,alarmMessage2,alarmMessage3,alarmMessage4 }
 | 
						|
	DESCRIPTION	"A Room Alert 11E SNMP Trap indicates that an alarm
 | 
						|
			condition has occurred on the sensor inidcated
 | 
						|
			by the alarmMessage variable."
 | 
						|
::= 2	
 | 
						|
	
 | 
						|
tempAlarm2-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage3, sensor3-1, sensor3-2, sensor3-1 }
 | 
						|
	DESCRIPTION	"A tempAlarm2 trap signifies that the current
 | 
						|
			temperature on external sensor 2 is outside the 
 | 
						|
			defined high or low threshold."
 | 
						|
::= 3
 | 
						|
	
 | 
						|
tempClear2-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage3, sensor3-1, sensor3-2, sensor3-1 }
 | 
						|
	DESCRIPTION	"A tempClear2 trap signifies that the current
 | 
						|
			temperature on external sensor 2 has returned to
 | 
						|
			a normal condition and is within the defined 
 | 
						|
			high or low threshold."
 | 
						|
::= 4	
 | 
						|
 | 
						|
tempAlarm3-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage4, sensor4-1, sensor4-2, sensor4-1 }
 | 
						|
	DESCRIPTION	"A tempAlarm3 trap signifies that the current
 | 
						|
			temperature on external sensor 3 is outside the 
 | 
						|
			defined high or low threshold."
 | 
						|
::= 5
 | 
						|
	
 | 
						|
tempClear3-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage4, sensor4-1, sensor4-2, sensor4-1 }
 | 
						|
	DESCRIPTION	"A tempClear3 trap signifies that the current
 | 
						|
			temperature on external sensor 3 has returned to
 | 
						|
			a normal condition and is within the defined 
 | 
						|
			high or low threshold."
 | 
						|
::= 6
 | 
						|
	
 | 
						|
humidityAlarm1-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage2, sensor2-1, sensor2-2, sensor2-3 }
 | 
						|
	DESCRIPTION	"A humidityAlarm1 trap signifies that the current
 | 
						|
			humidity on external sensor 1 is outside the 
 | 
						|
			defined high or low threshold."
 | 
						|
::= 7
 | 
						|
	
 | 
						|
humidityClear1-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage2, sensor2-1, sensor2-2, sensor2-3 }
 | 
						|
	DESCRIPTION	"A humidityClear1 trap signifies that the current
 | 
						|
			humidity on external sensor 1 has returned to
 | 
						|
			a normal condition and is within the defined 
 | 
						|
			high or low threshold."
 | 
						|
::= 8	
 | 
						|
	
 | 
						|
humidityAlarm2-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage3, sensor3-1, sensor3-2, sensor3-3 }
 | 
						|
	DESCRIPTION	"A humidityAlarm2 trap signifies that the current
 | 
						|
			humidity on external sensor 2 is outside the 
 | 
						|
			defined high or low threshold."
 | 
						|
::= 9
 | 
						|
	
 | 
						|
humidityClear2-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage3, sensor3-1, sensor3-2, sensor3-3 }
 | 
						|
	DESCRIPTION	"A humidityClear2 trap signifies that the current
 | 
						|
			humidity on external sensor 2 has returned to
 | 
						|
			a normal condition and is within the defined 
 | 
						|
			high or low threshold."
 | 
						|
::= 10	
 | 
						|
 | 
						|
humidityAlarm3-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage4, sensor4-1, sensor4-2, sensor4-3 }
 | 
						|
	DESCRIPTION	"A humidityAlarm3 trap signifies that the current
 | 
						|
			humidity on external sensor 3 is outside the 
 | 
						|
			defined high or low threshold."
 | 
						|
::= 11
 | 
						|
	
 | 
						|
humidityClear3-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage4, sensor4-1, sensor4-2, sensor4-3 }
 | 
						|
	DESCRIPTION	"A humidityClear3 trap signifies that the current
 | 
						|
			humidity on external sensor 3 has returned to
 | 
						|
			a normal condition and is within the defined 
 | 
						|
			high or low threshold."
 | 
						|
::= 12	
 | 
						|
	
 | 
						|
switchAlarm1-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-1, sensor1-1, sensor1-1 }
 | 
						|
	DESCRIPTION	"A switchAlarm1 trap signifies that switch sensor 1
 | 
						|
			is in an alarm state."
 | 
						|
::= 13
 | 
						|
	
 | 
						|
switchClear1-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-1, sensor1-1, sensor1-1 }
 | 
						|
	DESCRIPTION	"A switchClear1 trap signifies that the switch sensor 1
 | 
						|
			has returned to a normal state."
 | 
						|
::= 14	
 | 
						|
	
 | 
						|
switchAlarm2-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-2, sensor1-2, sensor1-2 }
 | 
						|
	DESCRIPTION	"A switchAlarm2 trap signifies that switch sensor 2
 | 
						|
			is in an alarm state."
 | 
						|
::= 15
 | 
						|
	
 | 
						|
switchClear2-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-2, sensor1-2, sensor1-2 }
 | 
						|
	DESCRIPTION	"A switchClear2 trap signifies that the switch sensor 2
 | 
						|
			has returned to a normal state."
 | 
						|
::= 16	
 | 
						|
	
 | 
						|
switchAlarm3-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-3, sensor1-3, sensor1-3 }
 | 
						|
	DESCRIPTION	"A switchAlarm1 trap signifies that switch sensor 1
 | 
						|
			is in an alarm state."
 | 
						|
::= 17
 | 
						|
	
 | 
						|
switchClear3-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-3, sensor1-3, sensor1-3 }
 | 
						|
	DESCRIPTION	"A switchClear3 trap signifies that the switch sensor 3
 | 
						|
			has returned to a normal state."
 | 
						|
::= 18	
 | 
						|
	
 | 
						|
switchAlarm4-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-4, sensor1-4, sensor1-4 }
 | 
						|
	DESCRIPTION	"A switchAlarm4 trap signifies that switch sensor 4
 | 
						|
			is in an alarm state."
 | 
						|
::= 19
 | 
						|
	
 | 
						|
switchClear4-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-4, sensor1-4, sensor1-4 }
 | 
						|
	DESCRIPTION	"A switchClear4 trap signifies that the switch sensor 4
 | 
						|
			has returned to a normal state."
 | 
						|
::= 20	
 | 
						|
	
 | 
						|
switchAlarm5-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-5, sensor1-5, sensor1-5 }
 | 
						|
	DESCRIPTION	"A switchAlarm5 trap signifies that switch sensor 5
 | 
						|
			is in an alarm state."
 | 
						|
::= 21
 | 
						|
	
 | 
						|
switchClear5-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-5, sensor1-5, sensor1-5 }
 | 
						|
	DESCRIPTION	"A switchClear5 trap signifies that the switch sensor 5
 | 
						|
			has returned to a normal state."
 | 
						|
::= 22	
 | 
						|
	
 | 
						|
switchAlarm6-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-6, sensor1-6, sensor1-6 }
 | 
						|
	DESCRIPTION	"A switchAlarm6 trap signifies that switch sensor 6
 | 
						|
			is in an alarm state."
 | 
						|
::= 23
 | 
						|
	
 | 
						|
switchClear6-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-6, sensor1-6, sensor1-6 }
 | 
						|
	DESCRIPTION	"A switchClear6 trap signifies that the switch sensor 6
 | 
						|
			has returned to a normal state."
 | 
						|
::= 24	
 | 
						|
	
 | 
						|
switchAlarm7-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-7, sensor1-7, sensor1-7 }
 | 
						|
	DESCRIPTION	"A switchAlarm7 trap signifies that switch sensor 7
 | 
						|
			is in an alarm state."
 | 
						|
::= 25
 | 
						|
	
 | 
						|
switchClear7-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-7, sensor1-7, sensor1-7 }
 | 
						|
	DESCRIPTION	"A switchClear7 trap signifies that the switch sensor 7
 | 
						|
			has returned to a normal state."
 | 
						|
::= 26	
 | 
						|
	
 | 
						|
switchAlarm8-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-8, sensor1-8, sensor1-8 }
 | 
						|
	DESCRIPTION	"A switchAlarm8 trap signifies that switch sensor 8
 | 
						|
			is in an alarm state."
 | 
						|
::= 27
 | 
						|
	
 | 
						|
switchClear8-11e TRAP-TYPE
 | 
						|
	ENTERPRISE	roomalert11E
 | 
						|
	VARIABLES	{ alarmMessage1, sensor1-8, sensor1-8, sensor1-8 }
 | 
						|
	DESCRIPTION	"A switchClear8 trap signifies that the switch sensor 8
 | 
						|
			has returned to a normal state."
 | 
						|
::= 28		
 | 
						|
END
 |