--defines ROOMALERT12E-MIB for SNMP agent extension of Room Alert 12E
 | 
						|
--Contents:     Global Registration Module
 | 
						|
--              Room Alert OIDs - Enterprise 20916
 | 
						|
--Version:      3.3.0
 | 
						|
--Date:         28 May 2021
 | 
						|
--Developed By: AVTECH Software, Inc.
 | 
						|
 | 
						|
--
 | 
						|
--Copyright (c) 2021 AVTECH Software, Inc.
 | 
						|
--
 | 
						|
 | 
						|
ROOMALERT12E-MIB DEFINITIONS ::= BEGIN
 | 
						|
 | 
						|
 | 
						|
IMPORTS
 | 
						|
        enterprises, IpAddress, Counter, TimeTicks
 | 
						|
                FROM RFC1155-SMI
 | 
						|
        OBJECT-TYPE
 | 
						|
                FROM RFC-1212
 | 
						|
        TRAP-TYPE
 | 
						|
                FROM RFC-1215;
 | 
						|
 | 
						|
 | 
						|
avtech                  OBJECT IDENTIFIER ::= { enterprises 20916 }
 | 
						|
products                OBJECT IDENTIFIER ::= { avtech 1 }
 | 
						|
roomalert12E    OBJECT IDENTIFIER ::= { products 10 }
 | 
						|
sensors                 OBJECT IDENTIFIER ::= { roomalert12E 1 }
 | 
						|
lightTower              OBJECT IDENTIFIER ::= { roomalert12E 2 }
 | 
						|
internal-sen    OBJECT IDENTIFIER ::= { sensors  1 }
 | 
						|
digital-sen1    OBJECT IDENTIFIER ::= { sensors  2 }
 | 
						|
digital-sen2    OBJECT IDENTIFIER ::= { sensors  3 }
 | 
						|
digital-sen3    OBJECT IDENTIFIER ::= { sensors  4 }
 | 
						|
switch1                 OBJECT IDENTIFIER ::= { sensors  5 }
 | 
						|
switch2                 OBJECT IDENTIFIER ::= { sensors  6 }
 | 
						|
switch3                 OBJECT IDENTIFIER ::= { sensors  7 }
 | 
						|
switch4                 OBJECT IDENTIFIER ::= { sensors  8 }
 | 
						|
analog                  OBJECT IDENTIFIER ::= { sensors  9 }
 | 
						|
relay                   OBJECT IDENTIFIER ::= { sensors 10 }
 | 
						|
traps                   OBJECT IDENTIFIER ::= { roomalert12E 3 }
 | 
						|
 | 
						|
-- Room Alert 12E MIB
 | 
						|
-- Parameters
 | 
						|
 | 
						|
 | 
						|
 | 
						|
 | 
						|
internal-sen-1 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "This value represents the current internal temperature in Celsius"
 | 
						|
::= { internal-sen 1 }
 | 
						|
 | 
						|
internal-sen-2 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "This value represents the current internal temperature in Fahrenheit."
 | 
						|
::= { internal-sen 2 }
 | 
						|
 | 
						|
internal-sen-3 OBJECT-TYPE
 | 
						|
        SYNTAX          OCTET STRING
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The internal sensor's label"
 | 
						|
::= { internal-sen 3 }
 | 
						|
 | 
						|
analog-1 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The current status of the Room Alert 12E analog input (0-5VDC)."
 | 
						|
::= { analog 1 }
 | 
						|
 | 
						|
analog-2 OBJECT-TYPE
 | 
						|
        SYNTAX          OCTET STRING
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The analog sensor's label."
 | 
						|
::= { analog 2 }
 | 
						|
 | 
						|
analog-3 OBJECT-TYPE
 | 
						|
        SYNTAX          OCTET STRING
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The current status of the Room Alert 12E analog input (user-defined scale)."
 | 
						|
::= { analog 3 }
 | 
						|
 | 
						|
relay-1 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..1)
 | 
						|
        ACCESS          read-write
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The current status of the Room Alert 12E relay output."
 | 
						|
::= { relay 1 }
 | 
						|
 | 
						|
relay-2 OBJECT-TYPE
 | 
						|
        SYNTAX          OCTET STRING
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION "The relay output's label."
 | 
						|
::= { relay 2 }
 | 
						|
 | 
						|
digital-sen1-1 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
 | 
						|
::= { digital-sen1 1 }
 | 
						|
 | 
						|
digital-sen1-2 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
 | 
						|
::= { digital-sen1 2 }
 | 
						|
 | 
						|
digital-sen1-3 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
 | 
						|
::= { digital-sen1 3 }
 | 
						|
 | 
						|
digital-sen1-4 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
 | 
						|
::= { digital-sen1 4 }
 | 
						|
 | 
						|
digital-sen1-5 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
 | 
						|
::= { digital-sen1 5 }
 | 
						|
 | 
						|
digital-sen1-6 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
 | 
						|
::= { digital-sen1 6 }
 | 
						|
 | 
						|
digital-sen1-7 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
 | 
						|
::= { digital-sen1 7 }
 | 
						|
 | 
						|
digital-sen1-8 OBJECT-TYPE
 | 
						|
        SYNTAX          OCTET STRING
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The sensor's label"
 | 
						|
::= { digital-sen1 8 }
 | 
						|
 | 
						|
digital-sen2-1 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
 | 
						|
::= { digital-sen2 1 }
 | 
						|
 | 
						|
digital-sen2-2 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
 | 
						|
::= { digital-sen2 2 }
 | 
						|
 | 
						|
digital-sen2-3 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
 | 
						|
::= { digital-sen2 3 }
 | 
						|
 | 
						|
digital-sen2-4 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
 | 
						|
::= { digital-sen2 4 }
 | 
						|
 | 
						|
digital-sen2-5 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
 | 
						|
::= { digital-sen2 5 }
 | 
						|
 | 
						|
digital-sen2-6 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
 | 
						|
::= { digital-sen2 6 }
 | 
						|
 | 
						|
digital-sen2-7 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
 | 
						|
::= { digital-sen2 7 }
 | 
						|
 | 
						|
digital-sen2-8 OBJECT-TYPE
 | 
						|
        SYNTAX          OCTET STRING
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The sensor's label"
 | 
						|
::= { digital-sen2 8 }
 | 
						|
 | 
						|
digital-sen3-1 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Celsius."
 | 
						|
::= { digital-sen3 1 }
 | 
						|
 | 
						|
digital-sen3-2 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temperature, Temp/Humidity, Temp/Analog, or Temp/Active Power sensor, this value represents the current temperature in Fahrenheit."
 | 
						|
::= { digital-sen3 2 }
 | 
						|
 | 
						|
digital-sen3-3 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Temp/Analog sensor, this value represents the current Voltage reading. If this is a Temp/Active Power sensor, this value represents the current power state (1=Power Detected, 0=No Power Detected)."
 | 
						|
::= { digital-sen3 3 }
 | 
						|
 | 
						|
digital-sen3-4 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Temp/Analog sensor, this value represents the current custom reading."
 | 
						|
::= { digital-sen3 4 }
 | 
						|
 | 
						|
digital-sen3-5 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
 | 
						|
::= { digital-sen3 5 }
 | 
						|
 | 
						|
digital-sen3-6 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Celsius."
 | 
						|
::= { digital-sen3 6 }
 | 
						|
 | 
						|
digital-sen3-7 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..65535)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "If this sensor is a Temp/Humidity sensor, this value represents the current dew point in Fahrenheit."
 | 
						|
::= { digital-sen3 7 }
 | 
						|
 | 
						|
digital-sen3-8 OBJECT-TYPE
 | 
						|
        SYNTAX          OCTET STRING
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The sensor's label"
 | 
						|
::= { digital-sen3 8 }
 | 
						|
 | 
						|
switch-sen1-1 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..1)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED)."
 | 
						|
::= { switch1 1 }
 | 
						|
 | 
						|
switch-sen1-2 OBJECT-TYPE
 | 
						|
        SYNTAX          OCTET STRING
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The label for switch sensor 1."
 | 
						|
::= { switch1 2 }
 | 
						|
 | 
						|
switch-sen2 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..1)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The reading for switch sensor 2 (0 = OPEN, 1 = CLOSED)."
 | 
						|
::= { switch2 1 }
 | 
						|
 | 
						|
switch-sen2-2 OBJECT-TYPE
 | 
						|
        SYNTAX          OCTET STRING
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The label for switch sensor 2."
 | 
						|
::= { switch2 2 }
 | 
						|
 | 
						|
switch-sen3 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..1)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The reading for switch sensor 3 (0 = OPEN, 1 = CLOSED)."
 | 
						|
::= { switch3 1 }
 | 
						|
 | 
						|
switch-sen3-2 OBJECT-TYPE
 | 
						|
        SYNTAX          OCTET STRING
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The label for switch sensor 3."
 | 
						|
::= { switch3 2 }
 | 
						|
 | 
						|
switch-sen4 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..1)
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The reading for switch sensor 4 (0 = OPEN, 1 = CLOSED)."
 | 
						|
::= { switch4 1 }
 | 
						|
 | 
						|
switch-sen4-2 OBJECT-TYPE
 | 
						|
        SYNTAX          OCTET STRING
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The label for switch sensor 4."
 | 
						|
::= { switch4 2 }
 | 
						|
 | 
						|
alarmmessage OBJECT-TYPE
 | 
						|
        SYNTAX          OCTET STRING
 | 
						|
        ACCESS          read-only
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "Last Alarm Message"
 | 
						|
::= { traps 1 }
 | 
						|
 | 
						|
 | 
						|
-- Light Tower
 | 
						|
 | 
						|
lightTower-RE OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..1)
 | 
						|
        ACCESS          read-write
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The status of the red LED on the Light Tower."
 | 
						|
::= { lightTower 1 }
 | 
						|
 | 
						|
lightTower-OR OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..1)
 | 
						|
        ACCESS          read-write
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The status of the orange LED on the Light Tower."
 | 
						|
::= { lightTower 2 }
 | 
						|
 | 
						|
lightTower-GR OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..1)
 | 
						|
        ACCESS          read-write
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The status of the green LED on the Light Tower."
 | 
						|
::= { lightTower 3 }
 | 
						|
 | 
						|
lightTower-WH OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..1)
 | 
						|
        ACCESS          read-write
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The status of the white LED on the Light Tower."
 | 
						|
::= { lightTower 4 }
 | 
						|
 | 
						|
lightTower-BL OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..1)
 | 
						|
        ACCESS          read-write
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The status of the blue LED on the Light Tower."
 | 
						|
::= { lightTower 5 }
 | 
						|
 | 
						|
lightTower-A1 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..1)
 | 
						|
        ACCESS          read-write
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The status of the 1st audio alarm on the Light Tower."
 | 
						|
::= { lightTower 6 }
 | 
						|
 | 
						|
lightTower-A2 OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..1)
 | 
						|
        ACCESS          read-write
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The status of the 2nd audio alarm on the Light Tower."
 | 
						|
::= { lightTower 7 }
 | 
						|
 | 
						|
lightTower-RL OBJECT-TYPE
 | 
						|
        SYNTAX          INTEGER(0..1)
 | 
						|
        ACCESS          read-write
 | 
						|
        STATUS          mandatory
 | 
						|
        DESCRIPTION     "The status of the LTA's on-board relay output"
 | 
						|
::= { lightTower 8 }
 | 
						|
 | 
						|
 | 
						|
-- ROOMALERT12E TRAPS
 | 
						|
 | 
						|
tempalarm1-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A tempalarm1 trap signifies that the current
 | 
						|
                        temperature on external sensor 1 is outside the
 | 
						|
                        defined high or low threshold."
 | 
						|
::= 1
 | 
						|
 | 
						|
room-alert-12E-snmp-trap TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A room-alert-12E-snmp-trap indicates that an alarm
 | 
						|
                        condition has occurred on the sensor inidcated
 | 
						|
                        by the alarmMessage variable."
 | 
						|
::= 2
 | 
						|
 | 
						|
tempalarm2-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A tempalarm2 trap signifies that the current
 | 
						|
                        temperature on external sensor 2 is outside the
 | 
						|
                        defined high or low threshold."
 | 
						|
::= 3
 | 
						|
 | 
						|
tempclear2-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A tempclear2 trap signifies that the current
 | 
						|
                        temperature on external sensor 2 has returned to
 | 
						|
                        a normal condition and is within the defined
 | 
						|
                        high or low threshold."
 | 
						|
::= 4
 | 
						|
 | 
						|
tempalarm3-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A tempalarm3 trap signifies that the current
 | 
						|
                        temperature on external sensor 3 is outside the
 | 
						|
                        defined high or low threshold."
 | 
						|
::= 5
 | 
						|
 | 
						|
tempclear3-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A tempclear3 trap signifies that the current
 | 
						|
                        temperature on external sensor 3 has returned to
 | 
						|
                        a normal condition and is within the defined
 | 
						|
                        high or low threshold."
 | 
						|
::= 6
 | 
						|
 | 
						|
humidityalarm1-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A humidityalarm1 trap signifies that the current
 | 
						|
                        humidity on external sensor 1 is outside the
 | 
						|
                        defined high or low threshold."
 | 
						|
::= 7
 | 
						|
 | 
						|
humidityclear1-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A humidityclear1 trap signifies that the current
 | 
						|
                        humidity on external sensor 1 has returned to
 | 
						|
                        a normal condition and is within the defined
 | 
						|
                        high or low threshold."
 | 
						|
::= 8
 | 
						|
 | 
						|
humidityalarm2-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A humidityalarm2 trap signifies that the current
 | 
						|
                        humidity on external sensor 2 is outside the
 | 
						|
                        defined high or low threshold."
 | 
						|
::= 9
 | 
						|
 | 
						|
humidityclear2-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A humidityclear2 trap signifies that the current
 | 
						|
                        humidity on external sensor 2 has returned to
 | 
						|
                        a normal condition and is within the defined
 | 
						|
                        high or low threshold."
 | 
						|
::= 10
 | 
						|
 | 
						|
humidityalarm3-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A humidityalarm3 trap signifies that the current
 | 
						|
                        humidity on external sensor 3 is outside the
 | 
						|
                        defined high or low threshold."
 | 
						|
::= 11
 | 
						|
 | 
						|
humidityclear3-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A humidityclear3 trap signifies that the current
 | 
						|
                        humidity on external sensor 3 has returned to
 | 
						|
                        a normal condition and is within the defined
 | 
						|
                        high or low threshold."
 | 
						|
::= 12
 | 
						|
 | 
						|
switchalarm1-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A switchalarm1 trap signifies that switch sensor 1
 | 
						|
                        is in an alarm state."
 | 
						|
::= 13
 | 
						|
 | 
						|
switchclear1-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A switchclear1 trap signifies that the switch sensor 1
 | 
						|
                        has returned to a normal state."
 | 
						|
::= 14
 | 
						|
 | 
						|
switchalarm2-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A switchalarm2 trap signifies that switch sensor 2
 | 
						|
                        is in an alarm state."
 | 
						|
::= 15
 | 
						|
 | 
						|
switchclear2-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A switchclear2 trap signifies that the switch sensor 2
 | 
						|
                        has returned to a normal state."
 | 
						|
::= 16
 | 
						|
 | 
						|
switchalarm3-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A switchalarm3 trap signifies that switch sensor 3
 | 
						|
                        is in an alarm state."
 | 
						|
::= 17
 | 
						|
 | 
						|
switchclear3-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A switchclear3 trap signifies that the switch sensor 3
 | 
						|
                        has returned to a normal state."
 | 
						|
::= 18
 | 
						|
 | 
						|
switchalarm4-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A switchalarm4 trap signifies that switch sensor 4
 | 
						|
                        is in an alarm state."
 | 
						|
::= 19
 | 
						|
 | 
						|
switchclear4-12E TRAP-TYPE
 | 
						|
        ENTERPRISE      roomalert12E
 | 
						|
        VARIABLES       { alarmmessage }
 | 
						|
        DESCRIPTION     "A switchclear4 trap signifies that the switch sensor 4
 | 
						|
                        has returned to a normal state."
 | 
						|
::= 20
 | 
						|
END |