-- AT-ENVMON.MIB, Allied Telesis enterprise MIB: Environment Monitoring
|
|
--
|
|
-- Copied from ATR-ENVMON.MIB of pre 2.9.1 release
|
|
--
|
|
-- Copyright (c) 2006 by Allied Telesis, Inc.
|
|
-- All rights reserved.
|
|
--
|
|
-- ============================================================================
|
|
|
|
AT-ENVMON-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY,
|
|
OBJECT-TYPE,
|
|
NOTIFICATION-TYPE,
|
|
Unsigned32,
|
|
enterprises
|
|
FROM SNMPv2-SMI
|
|
|
|
TruthValue,
|
|
TEXTUAL-CONVENTION
|
|
FROM SNMPv2-TC
|
|
|
|
ifIndex
|
|
FROM IF-MIB
|
|
|
|
DisplayStringUnsized
|
|
FROM AT-SMI-MIB
|
|
|
|
sysinfo
|
|
FROM AT-SYSINFO-MIB
|
|
;
|
|
|
|
envMon MODULE-IDENTITY
|
|
LAST-UPDATED "200603070000Z"
|
|
ORGANIZATION "Allied Telesis, Inc"
|
|
CONTACT-INFO
|
|
"http://www.alliedtelesis.com"
|
|
DESCRIPTION
|
|
"The AT Environment Monitoring MIB for managing and
|
|
reporting data relating to voltage rails, fan speeds,
|
|
temperature sensors and power supply units."
|
|
|
|
REVISION "200603070000Z"
|
|
DESCRIPTION
|
|
"Initial Revision"
|
|
::= { sysinfo 10 }
|
|
|
|
-- Textual Conventions
|
|
|
|
EnvMonPsbSensorType ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the type of a Power Supply Bay Device sensor."
|
|
SYNTAX INTEGER {
|
|
psbSensorTypeInvalid (0),
|
|
fanSpeedDiscrete (1),
|
|
temperatureDiscrete (2),
|
|
voltageDiscrete (3) }
|
|
|
|
-- This section of the MIB contains new generic environment monitoring
|
|
-- data. It relates to temperature, fanspeed, voltage and power supply
|
|
-- bay device monitors.
|
|
|
|
-- ---------------------------------------------------------- --
|
|
-- The Environment Monitoring Fan Table
|
|
-- ---------------------------------------------------------- --
|
|
|
|
envMonFanTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF EnvMonFanEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of fans installed in the device that have their
|
|
fan speeds monitored by environment monitoring hardware."
|
|
::= { envMon 1 }
|
|
|
|
envMonFanEntry OBJECT-TYPE
|
|
SYNTAX EnvMonFanEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The description, current speed, lower threshold speed and
|
|
current status of a fan."
|
|
INDEX { envMonFanBoardIndex, envMonFanIndex }
|
|
::= { envMonFanTable 1 }
|
|
|
|
EnvMonFanEntry ::=
|
|
SEQUENCE {
|
|
envMonFanBoardIndex
|
|
Unsigned32,
|
|
envMonFanIndex
|
|
Unsigned32,
|
|
envMonFanDescription
|
|
DisplayStringUnsized,
|
|
envMonFanCurrentSpeed
|
|
Unsigned32,
|
|
envMonFanLowerThreshold
|
|
Unsigned32,
|
|
envMonFanAlarm
|
|
TruthValue
|
|
}
|
|
|
|
envMonFanBoardIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the board hosting this fan in the board table."
|
|
::= { envMonFanEntry 1 }
|
|
|
|
envMonFanIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The numeric identifier of this fan within the context of its host board."
|
|
::= { envMonFanEntry 2 }
|
|
|
|
envMonFanDescription OBJECT-TYPE
|
|
SYNTAX DisplayStringUnsized (SIZE (0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The text description of this fan."
|
|
::= { envMonFanEntry 3 }
|
|
|
|
envMonFanCurrentSpeed OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current speed of this fan in revolutions per
|
|
minute."
|
|
::= { envMonFanEntry 4 }
|
|
|
|
envMonFanLowerThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum acceptable speed of the fan (in revolutions
|
|
per minute)."
|
|
::= { envMonFanEntry 5 }
|
|
|
|
envMonFanAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An indication of whether this fan is currently in an
|
|
alarm condition. A value of TRUE indicates that its
|
|
current speed is too low, FALSE indicates that the
|
|
current speed is acceptable."
|
|
::= { envMonFanEntry 6 }
|
|
|
|
-- ---------------------------------------------------------- --
|
|
-- The Environment Monitoring Voltage Table
|
|
-- ---------------------------------------------------------- --
|
|
|
|
envMonVoltageTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF EnvMonVoltageEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of voltage rails in the device that are
|
|
monitored by environment monitoring hardware."
|
|
::= { envMon 2 }
|
|
|
|
envMonVoltageEntry OBJECT-TYPE
|
|
SYNTAX EnvMonVoltageEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The description, current value, upper & lower threshold
|
|
settings and current status of a voltage rail."
|
|
INDEX { envMonVoltageBoardIndex, envMonVoltageIndex }
|
|
::= { envMonVoltageTable 1 }
|
|
|
|
EnvMonVoltageEntry ::=
|
|
SEQUENCE {
|
|
envMonVoltageBoardIndex
|
|
Unsigned32,
|
|
envMonVoltageIndex
|
|
Unsigned32,
|
|
envMonVoltageDescription
|
|
DisplayStringUnsized,
|
|
envMonVoltageCurrent
|
|
INTEGER,
|
|
envMonVoltageUpperThreshold
|
|
INTEGER,
|
|
envMonVoltageLowerThreshold
|
|
INTEGER,
|
|
envMonVoltageAlarm
|
|
TruthValue
|
|
}
|
|
|
|
envMonVoltageBoardIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the board hosting this voltage sensor in the board table."
|
|
::= { envMonVoltageEntry 1 }
|
|
|
|
envMonVoltageIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The numeric identifier of this voltage rail within the context of its host board."
|
|
::= { envMonVoltageEntry 2 }
|
|
|
|
envMonVoltageDescription OBJECT-TYPE
|
|
SYNTAX DisplayStringUnsized (SIZE (0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The text description of this voltage rail."
|
|
::= { envMonVoltageEntry 3 }
|
|
|
|
envMonVoltageCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current reading of this voltage rail in millivolts."
|
|
::= { envMonVoltageEntry 4 }
|
|
|
|
envMonVoltageUpperThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum acceptable reading of this voltage rail in millivolts."
|
|
::= { envMonVoltageEntry 5 }
|
|
|
|
envMonVoltageLowerThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum acceptable reading of this voltage rail in millivolts."
|
|
::= { envMonVoltageEntry 6 }
|
|
|
|
envMonVoltageAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An indication of whether this voltage rail is currently
|
|
in an alarm condition. A value of TRUE indicates that
|
|
its current reading is outside its threshold range,
|
|
FALSE indicates that the current reading is acceptable."
|
|
::= { envMonVoltageEntry 7 }
|
|
|
|
|
|
-- ---------------------------------------------------------- --
|
|
-- The Environment Monitoring Temperature Table
|
|
-- ---------------------------------------------------------- --
|
|
|
|
envMonTemperatureTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF EnvMonTemperatureEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of temperature sensors in the device that are
|
|
monitored by environment monitoring hardware."
|
|
::= { envMon 3 }
|
|
|
|
envMonTemperatureEntry OBJECT-TYPE
|
|
SYNTAX EnvMonTemperatureEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The description, current value, upper threshold setting
|
|
and current status of a temperature sensor."
|
|
INDEX { envMonTemperatureBoardIndex, envMonTemperatureIndex }
|
|
::= { envMonTemperatureTable 1 }
|
|
|
|
EnvMonTemperatureEntry ::=
|
|
SEQUENCE {
|
|
envMonTemperatureBoardIndex
|
|
Unsigned32,
|
|
envMonTemperatureIndex
|
|
Unsigned32,
|
|
envMonTemperatureDescription
|
|
DisplayStringUnsized,
|
|
envMonTemperatureCurrent
|
|
INTEGER,
|
|
envMonTemperatureUpperThreshold
|
|
INTEGER,
|
|
envMonTemperatureAlarm
|
|
TruthValue
|
|
}
|
|
|
|
envMonTemperatureBoardIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the board hosting this temperature sensor in the board table."
|
|
::= { envMonTemperatureEntry 1 }
|
|
|
|
envMonTemperatureIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The numeric identifier of this temperature sensor within the context of its host board."
|
|
::= { envMonTemperatureEntry 2 }
|
|
|
|
envMonTemperatureDescription OBJECT-TYPE
|
|
SYNTAX DisplayStringUnsized (SIZE (0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The text description of this temperature sensor."
|
|
::= { envMonTemperatureEntry 3 }
|
|
|
|
envMonTemperatureCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current reading of this temperature sensor in tenths of a degree Celcius."
|
|
::= { envMonTemperatureEntry 4 }
|
|
|
|
envMonTemperatureUpperThreshold OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum acceptable reading of this temperature
|
|
sensor in tenths of a degree Celcius."
|
|
::= { envMonTemperatureEntry 5 }
|
|
|
|
envMonTemperatureAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An indication of whether this temperature sensor is
|
|
currently in an alarm condition. A value of TRUE indicates
|
|
that its current reading is outside its threshold range,
|
|
FALSE indicates that the current reading is acceptable."
|
|
::= { envMonTemperatureEntry 6 }
|
|
|
|
|
|
-- ---------------------------------------------------------- --
|
|
-- The Environment Monitoring Power Supply Bay Device Table
|
|
-- ---------------------------------------------------------- --
|
|
|
|
envMonPsbObjects OBJECT IDENTIFIER ::= { envMon 4 }
|
|
|
|
envMonPsbTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF EnvMonPsbEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table showing power supply bays in the system and info
|
|
on any devices that are present."
|
|
::= { envMonPsbObjects 1 }
|
|
|
|
envMonPsbEntry OBJECT-TYPE
|
|
SYNTAX EnvMonPsbEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The description and current status of a power supply
|
|
bay device."
|
|
INDEX { envMonPsbHostBoardIndex, envMonPsbHostSlotIndex }
|
|
::= { envMonPsbTable 1 }
|
|
|
|
EnvMonPsbEntry ::=
|
|
SEQUENCE {
|
|
envMonPsbHostBoardIndex
|
|
Unsigned32,
|
|
envMonPsbHostSlotIndex
|
|
Unsigned32,
|
|
envMonPsbHeldBoardIndex
|
|
Unsigned32,
|
|
envMonPsbHeldBoardId
|
|
OBJECT IDENTIFIER,
|
|
envMonPsbDescription
|
|
DisplayStringUnsized
|
|
}
|
|
|
|
envMonPsbHostBoardIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the board hosting this PSB in the board table."
|
|
::= { envMonPsbEntry 1 }
|
|
|
|
envMonPsbHostSlotIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of this PSB slot within the context of its host board.
|
|
This index is fixed for each slot, on each type of board."
|
|
::= { envMonPsbEntry 2 }
|
|
|
|
envMonPsbHeldBoardIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of a board installed in this power supply bay.
|
|
This value corresponds to envMonPsbSensorBoardIndex for
|
|
each sensor on this board. A value of 0 indicates that a
|
|
board is is either not present or not supported."
|
|
::= { envMonPsbEntry 3 }
|
|
|
|
envMonPsbHeldBoardId OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of board installed in this power supply bay. The
|
|
values of this object are taken from the pprXxx object IDs
|
|
under the boards sub-tree in the parent MIB. A value of 0
|
|
indicates that a board is is either not present or not
|
|
supported."
|
|
::= { envMonPsbEntry 4 }
|
|
|
|
envMonPsbDescription OBJECT-TYPE
|
|
SYNTAX DisplayStringUnsized (SIZE (0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The text description of this power supply bay."
|
|
::= { envMonPsbEntry 5 }
|
|
|
|
envMonPsbSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF EnvMonPsbSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of environment monitoring sensors on installed
|
|
power supply bay devices."
|
|
::= { envMonPsbObjects 2 }
|
|
|
|
envMonPsbSensorEntry OBJECT-TYPE
|
|
SYNTAX EnvMonPsbSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The description and current status of a power supply
|
|
bay device."
|
|
INDEX { envMonPsbSensorBoardIndex, envMonPsbSensorIndex }
|
|
::= { envMonPsbSensorTable 1 }
|
|
|
|
EnvMonPsbSensorEntry ::=
|
|
SEQUENCE {
|
|
envMonPsbSensorBoardIndex
|
|
Unsigned32,
|
|
envMonPsbSensorIndex
|
|
Unsigned32,
|
|
envMonPsbSensorType
|
|
EnvMonPsbSensorType,
|
|
envMonPsbSensorDescription
|
|
DisplayStringUnsized,
|
|
envMonPsbSensorAlarm
|
|
TruthValue
|
|
}
|
|
|
|
envMonPsbSensorBoardIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the board hosting this sensor in the board table."
|
|
::= { envMonPsbSensorEntry 1 }
|
|
|
|
envMonPsbSensorIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of this power supply bay environmental sensor, within the
|
|
context of its host board."
|
|
::= { envMonPsbSensorEntry 2 }
|
|
|
|
envMonPsbSensorType OBJECT-TYPE
|
|
SYNTAX EnvMonPsbSensorType
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the type of environmental variable this sensor detects."
|
|
::= { envMonPsbSensorEntry 3 }
|
|
|
|
envMonPsbSensorDescription OBJECT-TYPE
|
|
SYNTAX DisplayStringUnsized (SIZE (0..30))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The text description of this power supply bay environmental sensor."
|
|
::= { envMonPsbSensorEntry 4 }
|
|
|
|
envMonPsbSensorAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An indication of whether this environmental sensor is currently
|
|
in an alarm condition. A value of TRUE indicates that
|
|
the device is in a failure condition, FALSE indicates
|
|
that the device is functioning normally."
|
|
::= { envMonPsbSensorEntry 5 }
|
|
|
|
|
|
-- ---------------------------------------------------------- --
|
|
-- The Environment Monitoring SNMP Trap Objects
|
|
-- ---------------------------------------------------------- --
|
|
|
|
envMonTraps OBJECT IDENTIFIER ::= { envMon 5 }
|
|
|
|
envMonFanAlarmSetEvent NOTIFICATION-TYPE
|
|
OBJECTS { envMonFanBoardIndex,
|
|
envMonFanIndex,
|
|
envMonFanDescription,
|
|
envMonFanLowerThreshold,
|
|
envMonFanCurrentSpeed }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Triggered when the monitored speed of a fan
|
|
drops below its lower threshold."
|
|
::= { envMonTraps 1 }
|
|
|
|
envMonFanAlarmClearedEvent NOTIFICATION-TYPE
|
|
OBJECTS { envMonFanBoardIndex,
|
|
envMonFanIndex,
|
|
envMonFanDescription,
|
|
envMonFanLowerThreshold,
|
|
envMonFanCurrentSpeed }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Triggered when the monitored speed of a fan
|
|
returns to an acceptable value, the fan
|
|
having previously been in an alarm condition."
|
|
::= { envMonTraps 2 }
|
|
|
|
envMonVoltAlarmSetEvent NOTIFICATION-TYPE
|
|
OBJECTS { envMonVoltageBoardIndex,
|
|
envMonVoltageIndex,
|
|
envMonVoltageDescription,
|
|
envMonVoltageUpperThreshold,
|
|
envMonVoltageLowerThreshold,
|
|
envMonVoltageCurrent }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Triggered when the voltage of a monitored
|
|
voltage rail, goes out of tolerance by
|
|
either dropping below its lower threshold,
|
|
or exceeding its upper threshold."
|
|
::= { envMonTraps 3 }
|
|
|
|
envMonVoltAlarmClearedEvent NOTIFICATION-TYPE
|
|
OBJECTS { envMonVoltageBoardIndex,
|
|
envMonVoltageIndex,
|
|
envMonVoltageDescription,
|
|
envMonVoltageUpperThreshold,
|
|
envMonVoltageLowerThreshold,
|
|
envMonVoltageCurrent }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Triggered when the voltage of a monitored
|
|
voltage rail returns to an acceptable value,
|
|
having previously been in an alarm condition."
|
|
::= { envMonTraps 4 }
|
|
|
|
envMonTempAlarmSetEvent NOTIFICATION-TYPE
|
|
OBJECTS { envMonTemperatureBoardIndex,
|
|
envMonTemperatureIndex,
|
|
envMonTemperatureDescription,
|
|
envMonTemperatureUpperThreshold,
|
|
envMonTemperatureCurrent }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Triggered when a monitored temperature
|
|
exceeds its upper threshold."
|
|
::= { envMonTraps 5 }
|
|
|
|
envMonTempAlarmClearedEvent NOTIFICATION-TYPE
|
|
OBJECTS { envMonTemperatureBoardIndex,
|
|
envMonTemperatureIndex,
|
|
envMonTemperatureDescription,
|
|
envMonTemperatureUpperThreshold,
|
|
envMonTemperatureCurrent }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Triggered when a monitored temperature
|
|
returns to an acceptable value, having
|
|
previously been in an alarm condition."
|
|
::= { envMonTraps 6 }
|
|
|
|
envMonPsbAlarmSetEvent NOTIFICATION-TYPE
|
|
OBJECTS { envMonPsbSensorBoardIndex,
|
|
envMonPsbSensorIndex,
|
|
envMonPsbSensorType,
|
|
envMonPsbSensorDescription }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Triggered when a monitored parameter of
|
|
a power supply bay device goes out of
|
|
tolerance."
|
|
::= { envMonTraps 7 }
|
|
|
|
envMonPsbAlarmClearedEvent NOTIFICATION-TYPE
|
|
OBJECTS { envMonPsbSensorBoardIndex,
|
|
envMonPsbSensorIndex,
|
|
envMonPsbSensorType,
|
|
envMonPsbSensorDescription }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Triggered when a monitored parameter of
|
|
a power supply bay device returns to an
|
|
acceptable value, having previously been
|
|
in an alarm condition."
|
|
::= { envMonTraps 8 }
|
|
|
|
END
|