128 lines
4.7 KiB
Plaintext
128 lines
4.7 KiB
Plaintext
--
|
|
--defines TEMPAGER3E-MIB for SNMP agent extension of TemPageR 3E
|
|
--Contents: Global Registration Module
|
|
-- TemPageR OIDs - Enterprise 20916
|
|
--Version: 1.0.0
|
|
--Date: 30 July 2008
|
|
--Developed By: AVTECH Software, Inc.
|
|
|
|
--
|
|
--Copyright (c) 2008 AVTECH Software, Inc.
|
|
--
|
|
|
|
TEMPAGER3E-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
IMPORTS
|
|
enterprises, IpAddress, Counter, TimeTicks
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
|
|
avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
|
|
products OBJECT IDENTIFIER ::= { avtech 1 }
|
|
TEMPAGER3E OBJECT IDENTIFIER ::= { products 7 }
|
|
sensors OBJECT IDENTIFIER ::= { TEMPAGER3E 1 }
|
|
traps OBJECT IDENTIFIER ::= { TEMPAGER3E 2 }
|
|
internal OBJECT IDENTIFIER ::= { sensors 1 }
|
|
temperature OBJECT IDENTIFIER ::= { internal 1 }
|
|
digital OBJECT IDENTIFIER ::= { sensors 2 }
|
|
digital-sen1 OBJECT IDENTIFIER ::= { digital 1 }
|
|
digital-sen2 OBJECT IDENTIFIER ::= { digital 2 }
|
|
|
|
|
|
-- TemPageR 3E MIB
|
|
-- Parameters
|
|
|
|
internal-tempc OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The internal temperature reading in Celsius. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value."
|
|
::= { temperature 1 }
|
|
|
|
internal-tempf OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The internal temperature reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value."
|
|
::= { temperature 2 }
|
|
|
|
digital-sen1-1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage."
|
|
::= { digital-sen1 1 }
|
|
|
|
digital-sen1-2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts."
|
|
::= { digital-sen1 2 }
|
|
|
|
digital-sen1-3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts."
|
|
::= { digital-sen1 3 }
|
|
|
|
digital-sen1-4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts."
|
|
::= { digital-sen1 4 }
|
|
|
|
digital-sen2-1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage."
|
|
::= { digital-sen2 1 }
|
|
|
|
digital-sen2-2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts."
|
|
::= { digital-sen2 2 }
|
|
|
|
digital-sen2-3 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts."
|
|
::= { digital-sen2 3 }
|
|
|
|
digital-sen2-4 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts."
|
|
::= { digital-sen2 4 }
|
|
|
|
alarmmessage OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Last Alarm Message"
|
|
::= { traps 1 }
|
|
|
|
|
|
-- TEMPAGER3E TRAPS
|
|
|
|
tempager3e-snmp-trap TRAP-TYPE
|
|
ENTERPRISE TEMPAGER3E
|
|
VARIABLES { alarmmessage }
|
|
DESCRIPTION "A tempager3e-snmp-trap indicates that an alarm
|
|
condition has occurred on the sensor indicated
|
|
by the alarmmessage variable."
|
|
::= 2
|
|
END
|