-- MIB for Dantherm Cooling Controllers
|
|
DANTHERM-COOLING-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
enterprises
|
|
FROM RFC1155-SMI;
|
|
|
|
--
|
|
-- Product and Data group Definitions
|
|
danthermCooling OBJECT IDENTIFIER ::= { enterprises 46651 }
|
|
|
|
--
|
|
-- Product CC3000 Controller Definitions
|
|
|
|
controllerCC3000 OBJECT IDENTIFIER ::= { danthermCooling 1 }
|
|
systemStatus OBJECT IDENTIFIER ::= { controllerCC3000 1 }
|
|
highlevelControl OBJECT IDENTIFIER ::= { controllerCC3000 2 }
|
|
fan1Config OBJECT IDENTIFIER ::= { controllerCC3000 3 }
|
|
fan2Config OBJECT IDENTIFIER ::= { controllerCC3000 4 }
|
|
damper1Config OBJECT IDENTIFIER ::= { controllerCC3000 5 }
|
|
damper2Config OBJECT IDENTIFIER ::= { controllerCC3000 6 }
|
|
aircon1Config OBJECT IDENTIFIER ::= { controllerCC3000 7 }
|
|
aircon2Config OBJECT IDENTIFIER ::= { controllerCC3000 8 }
|
|
heaterConfig OBJECT IDENTIFIER ::= { controllerCC3000 9 }
|
|
humidityConfig OBJECT IDENTIFIER ::= { controllerCC3000 10 }
|
|
systemConfig OBJECT IDENTIFIER ::= { controllerCC3000 11 }
|
|
alarmConfig OBJECT IDENTIFIER ::= { controllerCC3000 12 }
|
|
nightModeConfig OBJECT IDENTIFIER ::= { controllerCC3000 13 }
|
|
networkConfig OBJECT IDENTIFIER ::= { controllerCC3000 14 }
|
|
trapError OBJECT IDENTIFIER ::= { controllerCC3000 15 }
|
|
|
|
-- Product CCxx Controller Definitions
|
|
--controllerCCxx OBJECT IDENTIFIER ::= { danthermCooling x }
|
|
|
|
--
|
|
-- Controller-CC3000 : systemStatus
|
|
onBoardTempr OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Controller On-Board temperature in Degree Celcius "
|
|
::= { systemStatus 1 }
|
|
|
|
roomTempr OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Room Sensor or Zone 1 Sensor temperature in Degree Celcius"
|
|
::= { systemStatus 2 }
|
|
|
|
hotSpotTempr OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Hot Spot Sensor or Zone 2 Sensor temperature in Degree Celcius"
|
|
::= { systemStatus 3 }
|
|
|
|
outdoor1Tempr OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Ambient Sensor 1 or Zone 1 Ambient Sensor. temperature in Degree Celcius"
|
|
::= { systemStatus 4 }
|
|
|
|
outdoor2Tempr OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Ambient Sensor 2 or Zone 2 Ambient Sensor. temperature in Degree Celcius"
|
|
::= { systemStatus 5 }
|
|
|
|
shelterTempr OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Shelter Temperature. Valid for Single-Zone solution"
|
|
::= { systemStatus 6 }
|
|
|
|
outdoorCombinedTempr OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Cobined minimum Outdoor Temeperature. Valid for Single-Zone solution"
|
|
::= { systemStatus 7 }
|
|
|
|
fan1RPM OBJECT-TYPE
|
|
SYNTAX INTEGER(0..10000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Fan 1 Rotation Per Minute"
|
|
::= { systemStatus 8 }
|
|
|
|
fan2RPM OBJECT-TYPE
|
|
SYNTAX INTEGER(0..10000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Fan 2 Rotation Per Minute"
|
|
::= { systemStatus 9 }
|
|
|
|
fan1SpeedPercentage OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Fan 1 Speed in Percentage of Maximum Speed. Also represents Duty-Cycle of FAn Signal "
|
|
::= { systemStatus 10 }
|
|
|
|
fan2SpeedPercentage OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Fan 2 Speed in Percentage of Maximum Speed. Also represents Duty-Cycle of FAn Signal "
|
|
::= { systemStatus 11 }
|
|
|
|
|
|
damper1Position OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Damper 1 Shutter Open Percentage. 0% - Damper Closed. 100% - Damper completely open"
|
|
::= { systemStatus 12 }
|
|
|
|
damper2Position OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Damper 2 Shutter Open Percentage. 0% - Damper Closed. 100% - Damper completely open"
|
|
::= { systemStatus 13 }
|
|
|
|
humidity OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Internal or external humidity in Rh%"
|
|
::= { systemStatus 14 }
|
|
|
|
dewpoint OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Internal or external DewPoint based on Humidity; in Degree Celcius"
|
|
::= { systemStatus 15 }
|
|
|
|
atmosphericPressure OBJECT-TYPE
|
|
SYNTAX INTEGER(0..10000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Atmospheric pressure or Pressure of installed enclosure in KiloPascal"
|
|
::= { systemStatus 16 }
|
|
|
|
flowPressure OBJECT-TYPE
|
|
SYNTAX INTEGER(-1000..1000)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Filter flow Pressure in Pascal"
|
|
::= { systemStatus 17 }
|
|
|
|
fan1Status OBJECT-TYPE
|
|
SYNTAX INTEGER(0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Fan 1 operation status. 0 - Off; 1 - On -; 2 - Emergency/Boost "
|
|
::= { systemStatus 18 }
|
|
|
|
fan2Status OBJECT-TYPE
|
|
SYNTAX INTEGER(0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Fan 2 operation status. 0 - Off; 1 - On -; 2 - Emergency/Boost "
|
|
::= { systemStatus 19 }
|
|
|
|
damper1Status OBJECT-TYPE
|
|
SYNTAX INTEGER(0..3)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Damper 1 operation status. 0 - Closed; 1 - Open; 2 - Dynamic or Temperature Compensation; 2 - Emergency/Boost "
|
|
::= { systemStatus 20 }
|
|
|
|
damper2Status OBJECT-TYPE
|
|
SYNTAX INTEGER(0..3)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Damper 2 Shutter Open Percentage. 0 - Closed; 1 - Open; 2 - Dynamic or Temperature Compensation; 2 - Emergency/Boost "
|
|
::= { systemStatus 21 }
|
|
|
|
aircond1Status OBJECT-TYPE
|
|
SYNTAX INTEGER(0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Airconditioner 1 operation status. 0 - Off; 1 - Restart timeout; 2 - On "
|
|
::= { systemStatus 22 }
|
|
|
|
aircond2Status OBJECT-TYPE
|
|
SYNTAX INTEGER(0..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Airconditioner 2 operation status. 0 - Off; 1 - Restart timeout; 2 - On "
|
|
::= { systemStatus 23 }
|
|
|
|
heaterStatus OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"heater operation status. 0 - Off; 1 - On "
|
|
::= { systemStatus 24 }
|
|
|
|
shelter1Status OBJECT-TYPE
|
|
SYNTAX INTEGER(0..6)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Shelter Status in Single-Zone mode or Zone 1 Status in Dual-Zone mode respectively.
|
|
0 - Inactive or None State
|
|
1 - Heating State
|
|
2 - Re-Cycling State
|
|
3 - Free Cooling State
|
|
4 - Active or Aircon Coolign State
|
|
5 - Emergency State
|
|
6 - Intermediate state( strategy transistion) "
|
|
::= { systemStatus 25 }
|
|
|
|
shelter2Status OBJECT-TYPE
|
|
SYNTAX INTEGER(0..6)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Shelter Status in Dual-Zone mode or Zone 2 Status.
|
|
0 - Inactive or None State
|
|
1 - Heating State
|
|
2 - Re-Cycling State
|
|
3 - Free Cooling State
|
|
4 - Active or Aircon Coolign State
|
|
5 - Emergency State
|
|
6 - Intermediate state( strategy transistion) "
|
|
::= { systemStatus 26 }
|
|
|
|
shelter1Mode OBJECT-TYPE
|
|
SYNTAX INTEGER(0..3)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Shelter Run time mode in Single-Zone mode or Zone 1 Status in Dual-Zone mode respectively.
|
|
0 - Free Cooling Mode
|
|
1 - Standard Mode
|
|
2 - Power Save Mode
|
|
3 - Air conditioner Mode "
|
|
::= { systemStatus 27 }
|
|
|
|
shelter2Mode OBJECT-TYPE
|
|
SYNTAX INTEGER(0..3)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Shelter Run time mode in Dual-Zone mode or Zone 2 Status.
|
|
0 - Free Cooling Mode
|
|
1 - Standard Mode
|
|
2 - Power Save Mode
|
|
3 - Air conditioner Mode "
|
|
::= { systemStatus 28 }
|
|
|
|
shelter1Setpoint OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..80)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Shelter run time Cooling Set point in Single-Zone mode or Zone 1 Status in Dual-Zone mode respectively.
|
|
Cooling setpoint can be offset by following functions
|
|
RH function
|
|
Night mode
|
|
Digital inputs "
|
|
::= { systemStatus 29 }
|
|
|
|
shelter2Setpoint OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..80)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Shelter run time Cooling Set point in Dual-Zone mode or Zone 2 Status.
|
|
Cooling setpoint can be offset by following functions
|
|
RH function
|
|
Night mode
|
|
Digital inputs "
|
|
::= { systemStatus 30 }
|
|
|
|
errorStatus OBJECT-TYPE
|
|
SYNTAX INTEGER(0..33554432)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" controller internal error status. Binary
|
|
bit position - alarm drive state: 0 - inactive , 1 - active
|
|
0 - voltage low
|
|
1 - voltage high
|
|
2 - tempr low
|
|
3 - tempr limit 1
|
|
4 - tempr limit 2
|
|
5 - tempr limit 3
|
|
6 - humid. low
|
|
7 - humid. high
|
|
8 - fltr pressure 1
|
|
9 - fltr pressure 2
|
|
10 - fan 1
|
|
11 - fan 2
|
|
12 - onboard sens
|
|
13 - room sens
|
|
14 - hotspot sens
|
|
15 - ambient 1 sens
|
|
16 - ambient 2 sens
|
|
17 - dig 1 i/p
|
|
18 - dig 2 i/p
|
|
19 - dig 3 i/p
|
|
20 - filter i/p 1
|
|
21 - filter i/p 2
|
|
22 - network
|
|
23 - int storage
|
|
24 - sd card "
|
|
::= { systemStatus 31 }
|
|
|
|
maskedErrorStatus OBJECT-TYPE
|
|
SYNTAX INTEGER(0..33554432)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Controller Output Error status. Binary
|
|
Bit Position - Alarm Drive State: 0 - Inactive , 1 - Active
|
|
0 - Voltage Low
|
|
1 - Voltage High
|
|
2 - Tempr Low
|
|
3 - Tempr Limit 1
|
|
4 - Tempr Limit 2
|
|
5 - Tempr Limit 3
|
|
6 - Humid. Low
|
|
7 - Humid. High
|
|
8 - Fltr Pressure 1
|
|
9 - Fltr Pressure 2
|
|
10 - Fan 1
|
|
11 - Fan 2
|
|
12 - Onboard Sens
|
|
13 - Room Sens
|
|
14 - Hotspot Sens
|
|
15 - Ambient 1 Sens
|
|
16 - Ambient 2 Sens
|
|
17 - Dig 1 I/P
|
|
18 - Dig 2 I/P
|
|
19 - Dig 3 I/P
|
|
20 - Filter I/P 1
|
|
21 - Filter I/P 2
|
|
22 - Network
|
|
23 - Int storage
|
|
24 - SD Card "
|
|
::= { systemStatus 32 }
|
|
|
|
voltage OBJECT-TYPE
|
|
SYNTAX INTEGER(0..80)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"System Voltage in DC. "
|
|
::= { systemStatus 33 }
|
|
|
|
digitalInputStatus OBJECT-TYPE
|
|
SYNTAX INTEGER(0..16)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Controller Alarm Drive Status. Binary
|
|
Bit Position - Digital Input State: 0 - Inactive , 1 - Active
|
|
0 - DIG 1 I/P
|
|
1 - DIG 2 I/P
|
|
2 - DIG 3 I/P
|
|
3 - FILTER GUARD DIGI 1 I/P
|
|
4 - FILTER GUARD DIGI 2 I/P "
|
|
::= { systemStatus 34 }
|
|
|
|
alarmDriveStatus OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1024)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Controller Alarm Drive Status. Binary
|
|
Bit Position - Alarm Drive State: 0 - Inactive , 1 - Active
|
|
0 - ALARM 1
|
|
1 - ALARM 2
|
|
2 - ALARM 3
|
|
3 - ALARM 4
|
|
4 - ALARM 5
|
|
5 - ALARM 6
|
|
6 - ALARM 7
|
|
7 - ALARM 8
|
|
8 - ALARM 9
|
|
9 - ALARM 10"
|
|
::= { systemStatus 35 }
|
|
|
|
|
|
fan1OpertdurHour OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Fan 1 operation duration - Hour "
|
|
::= { systemStatus 36 }
|
|
|
|
fan1OpertdurMin OBJECT-TYPE
|
|
SYNTAX INTEGER(0..59)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Fan 1 operation duration - Minute "
|
|
::= { systemStatus 37 }
|
|
|
|
fan2OpertdurHour OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Fan 2 operation duration - Hour "
|
|
::= { systemStatus 38 }
|
|
|
|
fan2OpertdurMin OBJECT-TYPE
|
|
SYNTAX INTEGER(0..59)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Fan 2 operation duration - Minute "
|
|
::= { systemStatus 39 }
|
|
|
|
|
|
aircon1OpertdurHour OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Airconditioner 1 operation duration - Hour "
|
|
::= { systemStatus 40 }
|
|
|
|
aircon1OpertdurMin OBJECT-TYPE
|
|
SYNTAX INTEGER(0..59)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Airconditioner 1 operation duration - Minute "
|
|
::= { systemStatus 41 }
|
|
|
|
aircon2OpertdurHour OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Airconditioner 2 operation duration - Hour "
|
|
::= { systemStatus 42 }
|
|
|
|
aircon2OpertdurMin OBJECT-TYPE
|
|
SYNTAX INTEGER(0..59)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Airconditioner 2 operation duration - Minute "
|
|
::= { systemStatus 43 }
|
|
|
|
heaterOpertdurHour OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Heater operation duration - Hour "
|
|
::= { systemStatus 44 }
|
|
|
|
heaterOpertdurMin OBJECT-TYPE
|
|
SYNTAX INTEGER(0..59)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Heater operation duration - Minute "
|
|
::= { systemStatus 45 }
|
|
|
|
|
|
ccSN OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "CC3000 Controller serial number "
|
|
::= { systemStatus 46 }
|
|
|
|
|
|
fanbox1SN OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Free cooling FanBox unit 1 serial number "
|
|
::= { systemStatus 47 }
|
|
|
|
fanbox2SN OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Free cooling FanBox unit 2 serial number "
|
|
::= { systemStatus 48 }
|
|
|
|
aircond1SN OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Aicodnitioner unit 1 serial number "
|
|
::= { systemStatus 49 }
|
|
|
|
aircond2SN OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Aicodnitioner unit 2 serial number "
|
|
::= { systemStatus 50 }
|
|
|
|
fwVersion OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "CC3000 Firmware version "
|
|
::= { systemStatus 51 }
|
|
|
|
|
|
--
|
|
-- Controller-CC3000 : highlevelControl
|
|
|
|
coolSetpointZone1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Cooling Setpoint Zone/Shelter 1 "
|
|
::= { highlevelControl 1 }
|
|
|
|
coolSetpointZone2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Cooling Setpoint Zone/Shelter 2 "
|
|
::= { highlevelControl 2 }
|
|
|
|
heaterSetpoint OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Heater Setpoint "
|
|
::= { highlevelControl 3 }
|
|
|
|
backupConfig OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Configuration Backup to Internal memory and SD card. 0 - No change, 1 - Backup "
|
|
::= { highlevelControl 4 }
|
|
|
|
restoreConfig OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Configuration restore from Internal memory. 0 - No change, 1 - Restore "
|
|
::= { highlevelControl 5 }
|
|
|
|
systemReset OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Colling System reset or restart. 0 - No change, 1 - Restart "
|
|
::= { highlevelControl 6 }
|
|
|
|
|
|
year OBJECT-TYPE
|
|
SYNTAX INTEGER(2015..2099)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Calender - Year "
|
|
::= { highlevelControl 7 }
|
|
|
|
month OBJECT-TYPE
|
|
SYNTAX INTEGER(1..12)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Calender - Month "
|
|
::= { highlevelControl 8 }
|
|
|
|
date OBJECT-TYPE
|
|
SYNTAX INTEGER(1..31)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Calender - Date "
|
|
::= { highlevelControl 9 }
|
|
|
|
hour OBJECT-TYPE
|
|
SYNTAX INTEGER(0..23)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Clock - Hour "
|
|
::= { highlevelControl 10 }
|
|
|
|
minute OBJECT-TYPE
|
|
SYNTAX INTEGER(0..59)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Clock - Minute "
|
|
::= { highlevelControl 11 }
|
|
|
|
--
|
|
-- Controller-CC3000 : fan1Config
|
|
|
|
saveReloadConff1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
|
|
::= { fan1Config 1 }
|
|
|
|
offTemprf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Fan OFF temperature "
|
|
::= { fan1Config 2 }
|
|
|
|
idleOnTemprf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Fan Idle Speed On temperature "
|
|
::= { fan1Config 3 }
|
|
idleEntryTemprf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Idle entry temperature "
|
|
::= { fan1Config 4 }
|
|
|
|
midPoint1Temprf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Mid point 1 entry temperature "
|
|
::= { fan1Config 5 }
|
|
|
|
setPointTemprf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Set Point temperature "
|
|
::= { fan1Config 6 }
|
|
|
|
midPoint2Temprf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Mid point 2 entry temperature "
|
|
::= { fan1Config 7 }
|
|
|
|
highSpeedTemprf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "high Speed entry temperature "
|
|
::= { fan1Config 8 }
|
|
|
|
extendHighSpeedEntryTemprf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Extended high Speed entry temperature "
|
|
::= { fan1Config 9 }
|
|
|
|
extendHighSpeedExitTemprf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Extended high Speed exit temperature "
|
|
::= { fan1Config 10 }
|
|
|
|
boostEntryTemprf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Boost Speed entry temperature "
|
|
::= { fan1Config 11 }
|
|
|
|
boostExitTemprf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Boost Speed entry temperature "
|
|
::= { fan1Config 12 }
|
|
|
|
idleRPMf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..9999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Idle speed RPM "
|
|
::= { fan1Config 13 }
|
|
|
|
midPointRPMf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..9999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Midpoint Speed RPM "
|
|
::= { fan1Config 14 }
|
|
|
|
highSpeedRPMf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..9999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "high Speed RPM "
|
|
::= { fan1Config 15 }
|
|
|
|
extendHighSpeedRPMf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..9999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Extended high Speed RPM "
|
|
::= { fan1Config 16 }
|
|
|
|
idleDutyCyclef1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Idle Speed Duty Cycle "
|
|
::= { fan1Config 17 }
|
|
|
|
midDutyCyclef1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Midpoint speed Duty Cycle "
|
|
::= { fan1Config 18 }
|
|
|
|
highSpeedDutyCyclef1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "high speed Duty Cycle "
|
|
::= { fan1Config 19 }
|
|
|
|
extendHighSpeedDutyCyclef1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Extended high speed Duty Cycle "
|
|
::= { fan1Config 20 }
|
|
|
|
boostDutyCyclef1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Boost speed Duty Cycle "
|
|
::= { fan1Config 21 }
|
|
|
|
deadBandRPMf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1000)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Dead band RPM "
|
|
::= { fan1Config 22 }
|
|
|
|
overrideDigi1f1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
|
|
::= { fan1Config 23 }
|
|
|
|
overrideDigi2f1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
|
|
::= { fan1Config 24 }
|
|
|
|
overrideDigi3f1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
|
|
::= { fan1Config 25 }
|
|
|
|
overrideSensorfailf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
|
|
::= { fan1Config 26 }
|
|
|
|
sensorSelectf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..5)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature "
|
|
::= { fan1Config 27 }
|
|
|
|
tachoPulseperrotationf1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Number of Tacho pulses per cycle rotation for given fan "
|
|
::= { fan1Config 28 }
|
|
|
|
closedLoopenablef1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Closed Loop control enable or disable for given Fan. 0 - Enable. 1 - Disable "
|
|
::= { fan1Config 29 }
|
|
|
|
controlTypef1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - 0-10V DC control. 1 - PWM control "
|
|
::= { fan1Config 30 }
|
|
|
|
enablef1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - Disable Fan control. 1 - Enabel fan control "
|
|
::= { fan1Config 31 }
|
|
|
|
--
|
|
-- Controller-CC3000 : fan2Config
|
|
|
|
saveReloadConff2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
|
|
::= { fan2Config 1 }
|
|
|
|
offTemprf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Fan OFF temperature "
|
|
::= { fan2Config 2 }
|
|
|
|
idleOnTemprf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Fan Idle Speed On temperature "
|
|
::= { fan2Config 3 }
|
|
|
|
idleEntryTemprf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Idle entry temperature "
|
|
::= { fan2Config 4 }
|
|
|
|
midPoint1Temprf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Mid point 1 entry temperature "
|
|
::= { fan2Config 5 }
|
|
|
|
setPointTemprf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Set Point temperature "
|
|
::= { fan2Config 6 }
|
|
|
|
midPoint2Temprf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Mid point 2 entry temperature "
|
|
::= { fan2Config 7 }
|
|
|
|
highSpeedTemprf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "high Speed entry temperature "
|
|
::= { fan2Config 8 }
|
|
|
|
extendHighSpeedEntryTemprf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Extended high Speed entry temperature "
|
|
::= { fan2Config 9 }
|
|
|
|
extendHighSpeedExitTemprf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Extended high Speed exit temperature "
|
|
::= { fan2Config 10 }
|
|
|
|
boostEntryTemprf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Boost Speed entry temperature "
|
|
::= { fan2Config 11 }
|
|
|
|
boostExitTemprf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Boost Speed entry temperature "
|
|
::= { fan2Config 12 }
|
|
|
|
idleRPMf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..9999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Idle speed RPM "
|
|
::= { fan2Config 13 }
|
|
|
|
midPointRPMf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..9999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Midpoint Speed RPM "
|
|
::= { fan2Config 14 }
|
|
|
|
highSpeedRPMf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..9999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "high Speed RPM "
|
|
::= { fan2Config 15 }
|
|
|
|
extendHighSpeedRPMf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..9999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Extended high Speed RPM "
|
|
::= { fan2Config 16 }
|
|
|
|
idleDutyCyclef2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Idle Speed Duty Cycle "
|
|
::= { fan2Config 17 }
|
|
|
|
midDutyCyclef2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Midpoint speed Duty Cycle "
|
|
::= { fan2Config 18 }
|
|
|
|
highSpeedDutyCyclef2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "high speed Duty Cycle "
|
|
::= { fan2Config 19 }
|
|
|
|
extendHighSpeedDutyCyclef2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Extended high speed Duty Cycle "
|
|
::= { fan2Config 20 }
|
|
|
|
boostDutyCyclef2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Boost speed Duty Cycle "
|
|
::= { fan2Config 21 }
|
|
|
|
deadBandRPMf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1000)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Dead band RPM "
|
|
::= { fan2Config 22 }
|
|
|
|
overrideDigi1f2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
|
|
::= { fan2Config 23 }
|
|
|
|
overrideDigi2f2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
|
|
::= { fan2Config 24 }
|
|
|
|
overrideDigi3f2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
|
|
::= { fan2Config 25 }
|
|
|
|
overrideSensorfailf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
|
|
::= { fan2Config 26 }
|
|
|
|
sensorSelectf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..5)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature "
|
|
::= { fan2Config 27 }
|
|
|
|
tachoPulseperrotationf2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Number of Tacho pulses per cycle rotation for given fan "
|
|
::= { fan2Config 28 }
|
|
|
|
closedLoopenablef2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Closed Loop control enable or disable for given Fan. 0 - Enable. 1 - Disable "
|
|
::= { fan2Config 29 }
|
|
|
|
controlTypef2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - 0-10V DC control. 1 - PWM control"
|
|
::= { fan2Config 30 }
|
|
|
|
enablef2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - Disable Fan control. 1 - Enabel fan control "
|
|
::= { fan2Config 31 }
|
|
|
|
--
|
|
-- Controller-CC3000 : damper1Config
|
|
|
|
saveReloadConfd1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
|
|
::= { damper1Config 1 }
|
|
|
|
|
|
lowercloseTemprd1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Damper lower closing temperature "
|
|
::= { damper1Config 2 }
|
|
|
|
setPointd1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Damper opening temperature "
|
|
::= { damper1Config 3 }
|
|
|
|
|
|
upperOpentempd1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Damper upper opening temperature "
|
|
::= { damper1Config 4 }
|
|
|
|
upperClosetempd1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Damper upper closing temperature "
|
|
::= { damper1Config 5 }
|
|
|
|
|
|
emgncyClosetempd1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Damper emergency closing temperature "
|
|
::= { damper1Config 6 }
|
|
|
|
|
|
emgncyopentempd1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Damper emergency open temperature "
|
|
::= { damper1Config 7 }
|
|
|
|
|
|
overrideDigi1d1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
|
|
::= { damper1Config 8 }
|
|
|
|
|
|
overrideDigi2d1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
|
|
::= { damper1Config 9 }
|
|
|
|
|
|
overrideDigi3d1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
|
|
::= { damper1Config 10 }
|
|
|
|
|
|
overrideSensorFaild1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
|
|
::= { damper1Config 11 }
|
|
|
|
|
|
sensSelectd1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..5)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature "
|
|
::= { damper1Config 12 }
|
|
|
|
|
|
runDurationd1 OBJECT-TYPE
|
|
SYNTAX INTEGER(30..300)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Damper Run time in minutes "
|
|
::= { damper1Config 13 }
|
|
|
|
|
|
enabled1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..2)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Disable. 1 - ONOFF. 2 - Dynamic "
|
|
::= { damper1Config 14 }
|
|
|
|
|
|
--
|
|
--Controller-CC3000 : damper2Config
|
|
|
|
saveReloadConfd2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
|
|
::= { damper2Config 1 }
|
|
|
|
|
|
lowercloseTemprd2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Damper lower closing temperature "
|
|
::= { damper2Config 2 }
|
|
|
|
setPointd2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Damper opening temperature "
|
|
::= { damper2Config 3 }
|
|
|
|
|
|
upperOpentempd2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Damper upper opening temperature "
|
|
::= { damper2Config 4 }
|
|
|
|
upperClosetempd2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Damper upper closing temperature "
|
|
::= { damper2Config 5 }
|
|
|
|
|
|
emgncyClosetempd2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Damper emergency closing temperature "
|
|
::= { damper2Config 6 }
|
|
|
|
|
|
emgncyopentempd2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Damper emergency open temperature "
|
|
::= { damper2Config 7 }
|
|
|
|
|
|
|
|
overrideDigi1d2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
|
|
::= { damper2Config 8 }
|
|
|
|
|
|
overrideDigi2d2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
|
|
::= { damper2Config 9 }
|
|
|
|
|
|
overrideDigi3d2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
|
|
::= { damper2Config 10 }
|
|
|
|
|
|
overrideSensorFaild2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
|
|
::= { damper2Config 11 }
|
|
|
|
|
|
sensSelectd2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..5)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature "
|
|
::= { damper2Config 12 }
|
|
|
|
|
|
runDurationd2 OBJECT-TYPE
|
|
SYNTAX INTEGER(30..300)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Damper Run time in minutes "
|
|
::= { damper2Config 13 }
|
|
|
|
|
|
enabled2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..2)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Disable. 1 - ONOFF. 2 - Dynamic "
|
|
::= { damper2Config 14 }
|
|
|
|
|
|
--
|
|
-- Controller-CC3000 : AC-1-Config
|
|
|
|
saveReloadConfac1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
|
|
::= { aircon1Config 1 }
|
|
|
|
|
|
oNTemprac1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Air Conditioner ON temperature "
|
|
::= { aircon1Config 2 }
|
|
|
|
|
|
oFFTemprac1 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Air Conditioner OFF temperature "
|
|
::= { aircon1Config 3 }
|
|
|
|
|
|
|
|
overrideDigi1ac1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride. "
|
|
::= { aircon1Config 4 }
|
|
|
|
|
|
overrideDigi2ac1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride. "
|
|
::= { aircon1Config 5 }
|
|
|
|
|
|
overrideDigi3ac1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride "
|
|
::= { aircon1Config 6 }
|
|
|
|
|
|
overrideSensorFailac1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride "
|
|
::= { aircon1Config 7 }
|
|
|
|
|
|
|
|
sensSelectac1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..5)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature "
|
|
::= { aircon1Config 8 }
|
|
|
|
|
|
|
|
minimumRunDurationac1 OBJECT-TYPE
|
|
SYNTAX INTEGER(60..3600)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Minimum AC Run time in seconds "
|
|
::= { aircon1Config 9 }
|
|
|
|
|
|
restartTimeoutac1 OBJECT-TYPE
|
|
SYNTAX INTEGER(60..3600)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Restart timer in seconds "
|
|
::= { aircon1Config 10 }
|
|
|
|
|
|
|
|
enableac1 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Disable. 1 - Enable. "
|
|
::= { aircon1Config 11 }
|
|
|
|
|
|
--
|
|
-- Controller-CC3000 : aircon2Config
|
|
|
|
saveReloadConfac2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
|
|
::= { aircon2Config 1 }
|
|
|
|
|
|
onTemprac2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Air Conditioner ON temperature "
|
|
::= { aircon2Config 2 }
|
|
|
|
|
|
offTemprac2 OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Air Conditioner OFF temperature "
|
|
::= { aircon2Config 3 }
|
|
|
|
|
|
|
|
overrideDigi1ac2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride. "
|
|
::= { aircon2Config 4 }
|
|
|
|
|
|
overrideDigi2ac2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride. "
|
|
::= { aircon2Config 5 }
|
|
|
|
|
|
overrideDigi3ac2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride "
|
|
::= { aircon2Config 6 }
|
|
|
|
|
|
overrideSensorFailac2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride "
|
|
::= { aircon2Config 7 }
|
|
|
|
|
|
|
|
sensSelectac2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..5)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature "
|
|
::= { aircon2Config 8 }
|
|
|
|
|
|
|
|
minimumRunDurationac2 OBJECT-TYPE
|
|
SYNTAX INTEGER(60..3600)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Minimum AC Run time in seconds "
|
|
::= { aircon2Config 9 }
|
|
|
|
|
|
restartTimeoutac2 OBJECT-TYPE
|
|
SYNTAX INTEGER(60..3600)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Restart timer in seconds "
|
|
::= { aircon2Config 10 }
|
|
|
|
|
|
enableac2 OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Disable. 1 - Enable. "
|
|
::= { aircon2Config 11 }
|
|
|
|
--
|
|
-- Controller-CC3000 : heaterConfig
|
|
|
|
saveReloadConfhtr OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
|
|
::= { heaterConfig 1 }
|
|
|
|
|
|
onTemprhtr OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Heater ON temperature "
|
|
::= { heaterConfig 2 }
|
|
|
|
|
|
offTemprhtr OBJECT-TYPE
|
|
SYNTAX INTEGER(-41..101)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Heater OFF temperature "
|
|
::= { heaterConfig 3 }
|
|
|
|
|
|
|
|
overrideDigi1htr OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride. "
|
|
::= { heaterConfig 4 }
|
|
|
|
|
|
overrideDigi2htr OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride. "
|
|
::= { heaterConfig 5 }
|
|
|
|
|
|
overrideDigi3htr OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride "
|
|
::= { heaterConfig 6 }
|
|
|
|
|
|
overrideSensorFailhtr OBJECT-TYPE
|
|
SYNTAX INTEGER(0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride "
|
|
::= { heaterConfig 7 }
|
|
|
|
|
|
|
|
sensSelecthtr OBJECT-TYPE
|
|
SYNTAX INTEGER(0..5)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature "
|
|
::= { heaterConfig 8 }
|
|
|
|
|
|
|
|
|
|
enablehtr OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Disable. 1 - Enable. "
|
|
::= { heaterConfig 9 }
|
|
|
|
|
|
--
|
|
-- Controller-CC3000 : humidityConfig
|
|
|
|
saveReloadConfhum OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
|
|
::= { humidityConfig 1 }
|
|
|
|
|
|
rhEntryhum OBJECT-TYPE
|
|
SYNTAX INTEGER(40..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Humidity function entry value "
|
|
::= { humidityConfig 2 }
|
|
|
|
|
|
rhExithum OBJECT-TYPE
|
|
SYNTAX INTEGER(40..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Humidity function exit value "
|
|
::= { humidityConfig 3 }
|
|
|
|
|
|
|
|
coolingmodehum OBJECT-TYPE
|
|
SYNTAX INTEGER(0..3)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Freecooling. 1 - Standard. 2 - Power save. 3 - Aircon. "
|
|
::= { humidityConfig 4 }
|
|
|
|
|
|
temprsetpoffsethum OBJECT-TYPE
|
|
SYNTAX INTEGER(-10..10)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Cooling setpoint offset "
|
|
::= { humidityConfig 5 }
|
|
|
|
|
|
rhSensPositionhum OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Indoor. 1 - Outdoor "
|
|
::= { humidityConfig 6 }
|
|
|
|
|
|
enablehum OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Disable. 1 - Enable. "
|
|
::= { humidityConfig 7 }
|
|
|
|
|
|
--
|
|
-- Controller-CC3000 : systemConfig
|
|
|
|
saveReloadConfsysc OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
|
|
::= { systemConfig 1 }
|
|
|
|
|
|
vdcLowEntrysys OBJECT-TYPE
|
|
SYNTAX INTEGER(18..60)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Low voltage shut down entry "
|
|
::= { systemConfig 2 }
|
|
|
|
|
|
vdcLowExitsys OBJECT-TYPE
|
|
SYNTAX INTEGER(18..60)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Low voltage shut down exit "
|
|
::= { systemConfig 3 }
|
|
|
|
vdcHighEntrysys OBJECT-TYPE
|
|
SYNTAX INTEGER(18..60)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " High voltage shut down entry "
|
|
::= { systemConfig 4 }
|
|
|
|
|
|
vdcHighExitsys OBJECT-TYPE
|
|
SYNTAX INTEGER(18..60)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " High voltage shut down exit "
|
|
::= { systemConfig 5 }
|
|
|
|
|
|
temprLowlimitsys OBJECT-TYPE
|
|
SYNTAX INTEGER(-40..80)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Low temperature alarm limit "
|
|
::= { systemConfig 6 }
|
|
|
|
|
|
temprHighlimit1sys OBJECT-TYPE
|
|
SYNTAX INTEGER(-40..80)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " High temperature alarm limit 1 "
|
|
::= { systemConfig 7 }
|
|
|
|
|
|
temprHighlimit2sys OBJECT-TYPE
|
|
SYNTAX INTEGER(-40..80)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " High temperature alarm limit 2 "
|
|
::= { systemConfig 8 }
|
|
|
|
|
|
temprHighlimit3sys OBJECT-TYPE
|
|
SYNTAX INTEGER(-40..80)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " High temperature alarm limit 3 "
|
|
::= { systemConfig 9 }
|
|
|
|
|
|
temprlimithyssys OBJECT-TYPE
|
|
SYNTAX INTEGER(-20..20)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Temperature alarm limit hysteresis "
|
|
::= { systemConfig 10 }
|
|
|
|
|
|
rhLowlimitsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Humidity alarm low limit %RH "
|
|
::= { systemConfig 11 }
|
|
|
|
|
|
|
|
rhHighlimitsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Humidity alarm High limit %RH "
|
|
::= { systemConfig 12 }
|
|
|
|
|
|
flowpresslimit1sys OBJECT-TYPE
|
|
SYNTAX INTEGER(60..400)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Flow pressure limit 1 Pa "
|
|
::= { systemConfig 13 }
|
|
|
|
|
|
flowpresslimit2sys OBJECT-TYPE
|
|
SYNTAX INTEGER(60..400)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Flow pressure limit 2 Pa "
|
|
::= { systemConfig 14 }
|
|
|
|
|
|
flowpresshyssys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..400)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Flow pressure limit hysteresis Pa "
|
|
::= { systemConfig 15 }
|
|
|
|
|
|
coolingzonessys OBJECT-TYPE
|
|
SYNTAX INTEGER(1..2)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 1 - One cooling zone, 2 - Two cooling zones "
|
|
::= { systemConfig 16 }
|
|
|
|
|
|
coolingModesys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..3)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - FC, 1 - Std, 2 - Ps, 3 - Acon "
|
|
::= { systemConfig 17 }
|
|
|
|
|
|
negCoolingDeltaOverridesys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - Disable, 1 - Enable "
|
|
::= { systemConfig 18 }
|
|
|
|
|
|
negCoolingDeltaHyssys OBJECT-TYPE
|
|
SYNTAX INTEGER(-10..10)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Negative cooling delta hysteresis "
|
|
::= { systemConfig 19 }
|
|
|
|
|
|
coolingDeltatempsys OBJECT-TYPE
|
|
SYNTAX INTEGER(-10..10)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Cooling delta temperature "
|
|
::= { systemConfig 20 }
|
|
|
|
|
|
shelterTemprsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..2)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - RA, 1 - HS, 2 - Both "
|
|
::= { systemConfig 21 }
|
|
|
|
|
|
acleadlagsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - Disable, 1 - Enable "
|
|
::= { systemConfig 22 }
|
|
|
|
|
|
coolingModeXzonesys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..3)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - FC, 1 - Std, 2 - Ps, 3 - Acon "
|
|
::= { systemConfig 23 }
|
|
|
|
|
|
negCoolingDeltaOverrideXzonesys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - Disable, 1 - Enable "
|
|
::= { systemConfig 24 }
|
|
|
|
|
|
negCoolingDeltaHysXzonesys OBJECT-TYPE
|
|
SYNTAX INTEGER(-10..10)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Negative cooling delta hysteresis "
|
|
::= { systemConfig 25 }
|
|
|
|
|
|
coolingDeltatempXzonesys OBJECT-TYPE
|
|
SYNTAX INTEGER(-10..10)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Cooling delta temperature "
|
|
::= { systemConfig 26 }
|
|
|
|
|
|
fan1Zonesys OBJECT-TYPE
|
|
SYNTAX INTEGER(1..2)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 1 - Fan 1 for Zone 1, 2 - Fan 1 for zone 2 "
|
|
::= { systemConfig 27 }
|
|
|
|
|
|
fan2Zonesys OBJECT-TYPE
|
|
SYNTAX INTEGER(1..2)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 1 - Fan 2 for Zone 1, 2 - Fan 2 for zone 2 "
|
|
::= { systemConfig 28 }
|
|
|
|
|
|
ac1Zonesys OBJECT-TYPE
|
|
SYNTAX INTEGER(1..2)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 1 - AC 1 for Zone 1, 2 - AC 1 for zone 2 "
|
|
::= { systemConfig 29 }
|
|
|
|
ac2Zonesys OBJECT-TYPE
|
|
SYNTAX INTEGER(1..2)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 1 - AC 2 for Zone 1, 2 - AC 2 for zone 2 "
|
|
::= { systemConfig 30 }
|
|
|
|
|
|
damper1Zonesys OBJECT-TYPE
|
|
SYNTAX INTEGER(1..2)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 1 - Damper 1 for Zone 1, 2 - Damper 1 for zone 2 "
|
|
::= { systemConfig 31 }
|
|
|
|
damper2Zonesys OBJECT-TYPE
|
|
SYNTAX INTEGER(1..2)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 1 - Damper 2 for Zone 1, 2 - Damper 2 for zone 2 "
|
|
::= { systemConfig 32 }
|
|
|
|
|
|
|
|
heaterZonesys OBJECT-TYPE
|
|
SYNTAX INTEGER(1..2)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 1 - Heater for Zone 1, 2 - Heater for zone 2 "
|
|
::= { systemConfig 33 }
|
|
|
|
|
|
statusLogsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - Disable, 1 - Enable "
|
|
::= { systemConfig 34 }
|
|
|
|
|
|
|
|
logintervalsys OBJECT-TYPE
|
|
SYNTAX INTEGER(1..60)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Log interval in minutes "
|
|
::= { systemConfig 35 }
|
|
|
|
|
|
alarm1NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 36 }
|
|
|
|
|
|
alarm2NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 37 }
|
|
|
|
alarm3NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 38 }
|
|
|
|
alarm4NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 39 }
|
|
|
|
alarm5NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 40 }
|
|
|
|
alarm6NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 41 }
|
|
|
|
alarm7NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 42 }
|
|
|
|
alarm8NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 43 }
|
|
|
|
alarm9NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 44 }
|
|
|
|
alarm10NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 45 }
|
|
|
|
alarm1Delaysys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Alarm output delay in seconds "
|
|
::= { systemConfig 46 }
|
|
|
|
|
|
alarm2Delaysys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Alarm output delay in seconds "
|
|
::= { systemConfig 47 }
|
|
|
|
alarm3Delaysys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Alarm output delay in seconds "
|
|
::= { systemConfig 48 }
|
|
|
|
alarm4Delaysys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Alarm output delay in seconds "
|
|
::= { systemConfig 49 }
|
|
|
|
alarm5Delaysys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Alarm output delay in seconds "
|
|
::= { systemConfig 50 }
|
|
|
|
alarm6Delaysys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Alarm output delay in seconds "
|
|
::= { systemConfig 51 }
|
|
|
|
alarm7Delaysys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Alarm output delay in seconds "
|
|
::= { systemConfig 52 }
|
|
|
|
alarm8Delaysys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Alarm output delay in seconds "
|
|
::= { systemConfig 53 }
|
|
|
|
alarm9Delaysys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Alarm output delay in seconds "
|
|
::= { systemConfig 54 }
|
|
|
|
alarm10Delaysys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Alarm output delay in seconds "
|
|
::= { systemConfig 55 }
|
|
|
|
|
|
ac1NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 56 }
|
|
|
|
|
|
ac2NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 57 }
|
|
|
|
|
|
|
|
dig1NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 58 }
|
|
|
|
dig2NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 59 }
|
|
|
|
dig3NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 60 }
|
|
|
|
|
|
dig2funcoverridesys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..2)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - Override, 1 - setpoint offset, 2 - mode X "
|
|
::= { systemConfig 61 }
|
|
|
|
|
|
dig3funcoverridesys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..2)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - Override, 1 - setpoint offset, 2 - mode X "
|
|
::= { systemConfig 62 }
|
|
|
|
|
|
|
|
dig2offsetsys OBJECT-TYPE
|
|
SYNTAX INTEGER(-10..10)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Cooling setpoint offset "
|
|
::= { systemConfig 63 }
|
|
|
|
|
|
dig3offsetsys OBJECT-TYPE
|
|
SYNTAX INTEGER(-10..10)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Cooling setpoint offset "
|
|
::= { systemConfig 64 }
|
|
|
|
|
|
dig2trigModesys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..3)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - FC, 1 - Std, 2 - Ps, 3 - Acon "
|
|
::= { systemConfig 65 }
|
|
|
|
|
|
dig3TrigModesys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..3)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - FC, 1 - Std, 2 - Ps, 3 - Acon"
|
|
::= { systemConfig 66 }
|
|
|
|
|
|
|
|
filterGuard1NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 67 }
|
|
|
|
|
|
filterGuard2NONCsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - NO, 1 - NC "
|
|
::= { systemConfig 68 }
|
|
|
|
temprUnitsCFsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - Celcius, 1 - Fahrenheit "
|
|
::= { systemConfig 69 }
|
|
|
|
|
|
languageEnglishsys OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " 0 - Disable, 1 - Enable "
|
|
::= { systemConfig 70 }
|
|
|
|
|
|
|
|
|
|
--
|
|
-- Controller-CC3000 : alarmConfig
|
|
|
|
saveReloadConfAlm OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Alarm Mapping reloaded "
|
|
::= { alarmConfig 1 }
|
|
|
|
alarm1mask OBJECT-TYPE
|
|
SYNTAX INTEGER(0..33554432)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Alarm drive 1 Mask [Can have multiple Alarm Errors].
|
|
Bit Position - Value - Alarm Drive State: 0 - Unselect, 1 - Select
|
|
1 - 1 - Voltage Low
|
|
2 - 2 - Voltage High
|
|
3 - 4 - Tempr Low
|
|
4 - 8 - Tempr Limit 1
|
|
5 - 16 - Tempr Limit 2
|
|
6 - 32 - Tempr Limit 3
|
|
7 - 64 - Humid. Low
|
|
8 - 128 - Humid. High
|
|
9 - 256 - Fltr Pressure 1
|
|
10 - 512 - Fltr Pressure 2
|
|
11 - 1024 - Fan 1
|
|
12 - 2048 - Fan 2
|
|
13 - 4096 - Onboard Sens
|
|
14 - 8192 - Room Sens
|
|
15 - 16384 - Hotspot Sens
|
|
16 - 32768 - Ambient 1 Sens
|
|
17 - 65536 - Ambient 2 Sens
|
|
18 - 131072 - Dig 1 I/P
|
|
19 - 262144 - Dig 2 I/P
|
|
20 - 524288 - Dig 3 I/P
|
|
21 - 1048576 - Filter I/P 1
|
|
22 - 2097152 - Filter I/P 2
|
|
23 - 4194304 - Network
|
|
24 - 8388608 - Int storage
|
|
25 - 16777216 - SD Card "
|
|
::= { alarmConfig 2 }
|
|
|
|
|
|
alarm2mask OBJECT-TYPE
|
|
SYNTAX INTEGER(0..33554432)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Alarm drive 2 Mask [Can have multiple Alarm Errors].
|
|
Bit Position - Value - Alarm Drive State: 0 - Unselect, 1 - Select
|
|
1 - 1 - Voltage Low
|
|
2 - 2 - Voltage High
|
|
3 - 4 - Tempr Low
|
|
4 - 8 - Tempr Limit 1
|
|
5 - 16 - Tempr Limit 2
|
|
6 - 32 - Tempr Limit 3
|
|
7 - 64 - Humid. Low
|
|
8 - 128 - Humid. High
|
|
9 - 256 - Fltr Pressure 1
|
|
10 - 512 - Fltr Pressure 2
|
|
11 - 1024 - Fan 1
|
|
12 - 2048 - Fan 2
|
|
13 - 4096 - Onboard Sens
|
|
14 - 8192 - Room Sens
|
|
15 - 16384 - Hotspot Sens
|
|
16 - 32768 - Ambient 1 Sens
|
|
17 - 65536 - Ambient 2 Sens
|
|
18 - 131072 - Dig 1 I/P
|
|
19 - 262144 - Dig 2 I/P
|
|
20 - 524288 - Dig 3 I/P
|
|
21 - 1048576 - Filter I/P 1
|
|
22 - 2097152 - Filter I/P 2
|
|
23 - 4194304 - Network
|
|
24 - 8388608 - Int storage
|
|
25 - 16777216 - SD Card "
|
|
::= { alarmConfig 3 }
|
|
|
|
alarm3mask OBJECT-TYPE
|
|
SYNTAX INTEGER(0..25)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Alarm drive 3 Select [Single Alarm Error].
|
|
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
|
|
1 - Voltage Low
|
|
2 - Voltage High
|
|
3 - Tempr Low
|
|
4 - Tempr Limit 1
|
|
5 - Tempr Limit 2
|
|
6 - Tempr Limit 3
|
|
7 - Humid. Low
|
|
8 - Humid. High
|
|
9 - Fltr Pressure 1
|
|
10 - Fltr Pressure 2
|
|
11 - Fan 1
|
|
12 - Fan 2
|
|
13 - Onboard Sens
|
|
14 - Room Sens
|
|
15 - Hotspot Sens
|
|
16 - Ambient 1 Sens
|
|
17 - Ambient 2 Sens
|
|
18 - Dig 1 I/P
|
|
19 - Dig 2 I/P
|
|
20 - Dig 3 I/P
|
|
21 - Filter I/P 1
|
|
22 - Filter I/P 2
|
|
23 - Network
|
|
24 - Int storage
|
|
25 - SD Card "
|
|
::= { alarmConfig 4 }
|
|
|
|
alarm4mask OBJECT-TYPE
|
|
SYNTAX INTEGER(0..25)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Alarm drive 4 Select [Single Alarm Error].
|
|
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
|
|
1 - Voltage Low
|
|
2 - Voltage High
|
|
3 - Tempr Low
|
|
4 - Tempr Limit 1
|
|
5 - Tempr Limit 2
|
|
6 - Tempr Limit 3
|
|
7 - Humid. Low
|
|
8 - Humid. High
|
|
9 - Fltr Pressure 1
|
|
10 - Fltr Pressure 2
|
|
11 - Fan 1
|
|
12 - Fan 2
|
|
13 - Onboard Sens
|
|
14 - Room Sens
|
|
15 - Hotspot Sens
|
|
16 - Ambient 1 Sens
|
|
17 - Ambient 2 Sens
|
|
18 - Dig 1 I/P
|
|
19 - Dig 2 I/P
|
|
20 - Dig 3 I/P
|
|
21 - Filter I/P 1
|
|
22 - Filter I/P 2
|
|
23 - Network
|
|
24 - Int storage
|
|
25 - SD Card "
|
|
::= { alarmConfig 5 }
|
|
|
|
alarm5mask OBJECT-TYPE
|
|
SYNTAX INTEGER(0..25)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Alarm drive 5 Select [Single Alarm Error].
|
|
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
|
|
1 - Voltage Low
|
|
2 - Voltage High
|
|
3 - Tempr Low
|
|
4 - Tempr Limit 1
|
|
5 - Tempr Limit 2
|
|
6 - Tempr Limit 3
|
|
7 - Humid. Low
|
|
8 - Humid. High
|
|
9 - Fltr Pressure 1
|
|
10 - Fltr Pressure 2
|
|
11 - Fan 1
|
|
12 - Fan 2
|
|
13 - Onboard Sens
|
|
14 - Room Sens
|
|
15 - Hotspot Sens
|
|
16 - Ambient 1 Sens
|
|
17 - Ambient 2 Sens
|
|
18 - Dig 1 I/P
|
|
19 - Dig 2 I/P
|
|
20 - Dig 3 I/P
|
|
21 - Filter I/P 1
|
|
22 - Filter I/P 2
|
|
23 - Network
|
|
24 - Int storage
|
|
25 - SD Card "
|
|
::= { alarmConfig 6 }
|
|
|
|
alarm6mask OBJECT-TYPE
|
|
SYNTAX INTEGER(0..25)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Alarm drive 6 Select [Single Alarm Error].
|
|
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
|
|
1 - Voltage Low
|
|
2 - Voltage High
|
|
3 - Tempr Low
|
|
4 - Tempr Limit 1
|
|
5 - Tempr Limit 2
|
|
6 - Tempr Limit 3
|
|
7 - Humid. Low
|
|
8 - Humid. High
|
|
9 - Fltr Pressure 1
|
|
10 - Fltr Pressure 2
|
|
11 - Fan 1
|
|
12 - Fan 2
|
|
13 - Onboard Sens
|
|
14 - Room Sens
|
|
15 - Hotspot Sens
|
|
16 - Ambient 1 Sens
|
|
17 - Ambient 2 Sens
|
|
18 - Dig 1 I/P
|
|
19 - Dig 2 I/P
|
|
20 - Dig 3 I/P
|
|
21 - Filter I/P 1
|
|
22 - Filter I/P 2
|
|
23 - Network
|
|
24 - Int storage
|
|
25 - SD Card "
|
|
::= { alarmConfig 7 }
|
|
|
|
alarm7mask OBJECT-TYPE
|
|
SYNTAX INTEGER(0..25)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Alarm drive 7 Select [Single Alarm Error].
|
|
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
|
|
1 - Voltage Low
|
|
2 - Voltage High
|
|
3 - Tempr Low
|
|
4 - Tempr Limit 1
|
|
5 - Tempr Limit 2
|
|
6 - Tempr Limit 3
|
|
7 - Humid. Low
|
|
8 - Humid. High
|
|
9 - Fltr Pressure 1
|
|
10 - Fltr Pressure 2
|
|
11 - Fan 1
|
|
12 - Fan 2
|
|
13 - Onboard Sens
|
|
14 - Room Sens
|
|
15 - Hotspot Sens
|
|
16 - Ambient 1 Sens
|
|
17 - Ambient 2 Sens
|
|
18 - Dig 1 I/P
|
|
19 - Dig 2 I/P
|
|
20 - Dig 3 I/P
|
|
21 - Filter I/P 1
|
|
22 - Filter I/P 2
|
|
23 - Network
|
|
24 - Int storage
|
|
25 - SD Card "
|
|
::= { alarmConfig 8 }
|
|
|
|
alarm8mask OBJECT-TYPE
|
|
SYNTAX INTEGER(0..25)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Alarm drive 8 Select [Single Alarm Error].
|
|
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
|
|
1 - Voltage Low
|
|
2 - Voltage High
|
|
3 - Tempr Low
|
|
4 - Tempr Limit 1
|
|
5 - Tempr Limit 2
|
|
6 - Tempr Limit 3
|
|
7 - Humid. Low
|
|
8 - Humid. High
|
|
9 - Fltr Pressure 1
|
|
10 - Fltr Pressure 2
|
|
11 - Fan 1
|
|
12 - Fan 2
|
|
13 - Onboard Sens
|
|
14 - Room Sens
|
|
15 - Hotspot Sens
|
|
16 - Ambient 1 Sens
|
|
17 - Ambient 2 Sens
|
|
18 - Dig 1 I/P
|
|
19 - Dig 2 I/P
|
|
20 - Dig 3 I/P
|
|
21 - Filter I/P 1
|
|
22 - Filter I/P 2
|
|
23 - Network
|
|
24 - Int storage
|
|
25 - SD Card "
|
|
::= { alarmConfig 9 }
|
|
|
|
alarm9mask OBJECT-TYPE
|
|
SYNTAX INTEGER(0..25)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Alarm drive 9 Select [Single Alarm Error].
|
|
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
|
|
1 - Voltage Low
|
|
2 - Voltage High
|
|
3 - Tempr Low
|
|
4 - Tempr Limit 1
|
|
5 - Tempr Limit 2
|
|
6 - Tempr Limit 3
|
|
7 - Humid. Low
|
|
8 - Humid. High
|
|
9 - Fltr Pressure 1
|
|
10 - Fltr Pressure 2
|
|
11 - Fan 1
|
|
12 - Fan 2
|
|
13 - Onboard Sens
|
|
14 - Room Sens
|
|
15 - Hotspot Sens
|
|
16 - Ambient 1 Sens
|
|
17 - Ambient 2 Sens
|
|
18 - Dig 1 I/P
|
|
19 - Dig 2 I/P
|
|
20 - Dig 3 I/P
|
|
21 - Filter I/P 1
|
|
22 - Filter I/P 2
|
|
23 - Network
|
|
24 - Int storage
|
|
25 - SD Card "
|
|
::= { alarmConfig 10 }
|
|
|
|
alarm10mask OBJECT-TYPE
|
|
SYNTAX INTEGER(0..25)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Alarm drive 10 Select [Single Alarm Error].
|
|
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
|
|
1 - Voltage Low
|
|
2 - Voltage High
|
|
3 - Tempr Low
|
|
4 - Tempr Limit 1
|
|
5 - Tempr Limit 2
|
|
6 - Tempr Limit 3
|
|
7 - Humid. Low
|
|
8 - Humid. High
|
|
9 - Fltr Pressure 1
|
|
10 - Fltr Pressure 2
|
|
11 - Fan 1
|
|
12 - Fan 2
|
|
13 - Onboard Sens
|
|
14 - Room Sens
|
|
15 - Hotspot Sens
|
|
16 - Ambient 1 Sens
|
|
17 - Ambient 2 Sens
|
|
18 - Dig 1 I/P
|
|
19 - Dig 2 I/P
|
|
20 - Dig 3 I/P
|
|
21 - Filter I/P 1
|
|
22 - Filter I/P 2
|
|
23 - Network
|
|
24 - Int storage
|
|
25 - SD Card "
|
|
::= { alarmConfig 11 }
|
|
|
|
|
|
|
|
--
|
|
-- Controller-CC3000 : nightModeConfig
|
|
|
|
saveReloadConfNm OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
|
|
::= { nightModeConfig 1 }
|
|
|
|
|
|
starttimeHournm OBJECT-TYPE
|
|
SYNTAX INTEGER(0..24)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Night Mode Start time hour "
|
|
::= { nightModeConfig 2 }
|
|
|
|
|
|
startTimeMinutesnm OBJECT-TYPE
|
|
SYNTAX INTEGER(0..59)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Night Mode Start time minutes "
|
|
::= { nightModeConfig 3 }
|
|
|
|
|
|
|
|
endTimeHournm OBJECT-TYPE
|
|
SYNTAX INTEGER(0..24)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Night Mode End time hour "
|
|
::= { nightModeConfig 4 }
|
|
|
|
|
|
endTimeMinutesnm OBJECT-TYPE
|
|
SYNTAX INTEGER(0..59)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " Night Mode End time minutes "
|
|
::= { nightModeConfig 5 }
|
|
|
|
|
|
fanMaxRPMnm OBJECT-TYPE
|
|
SYNTAX INTEGER(0..100)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION " % of max fan speed "
|
|
::= { nightModeConfig 6 }
|
|
|
|
|
|
setPointOffsetnm OBJECT-TYPE
|
|
SYNTAX INTEGER(-10..10)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Cooling setpoint offset "
|
|
::= { nightModeConfig 7 }
|
|
|
|
|
|
|
|
coolingModenm OBJECT-TYPE
|
|
SYNTAX INTEGER(0..3)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Freecooling. 1 - Standard. 2 - Power save. 3 - Aircon. "
|
|
::= { nightModeConfig 8 }
|
|
|
|
|
|
enablenm OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Disable. 1 - Enable. "
|
|
::= { nightModeConfig 9 }
|
|
|
|
|
|
--
|
|
-- Controller-CC3000 : networkConfig
|
|
|
|
saveReloadConfNW OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
|
|
::= { networkConfig 1 }
|
|
|
|
dhcpenable OBJECT-TYPE
|
|
SYNTAX INTEGER(0..1)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "0 - Static IP, 1 - Dynamic IP "
|
|
::= { networkConfig 2 }
|
|
|
|
ipaddr OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "System IP Address"
|
|
::= { networkConfig 3 }
|
|
|
|
subnetmask OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Sub-net Mask "
|
|
::= { networkConfig 4 }
|
|
|
|
gatewayIPaddr OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Default Gateway IP Address"
|
|
::= { networkConfig 5 }
|
|
|
|
ntpIPaddr OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "DNS IP Address"
|
|
::= { networkConfig 6 }
|
|
|
|
snmpPort OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "SNMP Agent Port"
|
|
::= { networkConfig 7 }
|
|
|
|
trapServer1IPaddr OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "SNMP TRAP manager 1 IP address"
|
|
::= { networkConfig 8 }
|
|
|
|
trapServer1port OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "SNMP TRAP manager 1 Port Number"
|
|
::= { networkConfig 9 }
|
|
|
|
trapServer2IPaddr OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "SNMP TRAP manager 2 IP address"
|
|
::= { networkConfig 10 }
|
|
|
|
trapServer2port OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "SNMP TRAP manager 2 Port Number"
|
|
::= { networkConfig 11 }
|
|
|
|
trapServer3IPaddr OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "SNMP TRAP manager 3 IP address"
|
|
::= { networkConfig 12 }
|
|
|
|
trapServer3port OBJECT-TYPE
|
|
SYNTAX INTEGER(0..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "SNMP TRAP manager 3 Port Number"
|
|
::= { networkConfig 13 }
|
|
|
|
snmpCommunity OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "SNMP Read/write Community string"
|
|
::= { networkConfig 14 }
|
|
|
|
hostName OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "System Netwrok Host name"
|
|
::= { networkConfig 15 }
|
|
|
|
--
|
|
-- Controller-CC3000 : trapError
|
|
|
|
errorNumber OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
VoltageLow (1),
|
|
VoltageHigh (2),
|
|
TemprLow (3),
|
|
TemprLimit1 (4),
|
|
TemprLimit2 (5),
|
|
TemprLimit3 (6),
|
|
HumidLow (7),
|
|
HumidHigh (8),
|
|
FltrPressure1 (9),
|
|
FltPressure2 (10),
|
|
Fan1 (11),
|
|
Fan2 (12),
|
|
OnboardSens (13),
|
|
RoomSens (14),
|
|
HotspotSens (15),
|
|
Ambient1Sens (16),
|
|
Ambient2Sens (17),
|
|
Dig1IP (18),
|
|
Dig2IP (19),
|
|
Dig3IP (20),
|
|
FilterIP1 (21),
|
|
FilterIP2 (22),
|
|
Network (23),
|
|
Intstorage (24),
|
|
SDCard (25) }
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Error Number corresponding to CC3000 controller Error."
|
|
::= { trapError 1 }
|
|
|
|
status OBJECT-TYPE
|
|
SYNTAX INTEGER { ALARMset (1), ALARMclear (0) }
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Error Status Active/SET or Inactive/CLEAR."
|
|
::= { trapError 2 }
|
|
|
|
value OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Value Corresponding to Error Occurance Instance."
|
|
::= { trapError 3 }
|
|
|
|
info OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Description of Current Error."
|
|
::= { trapError 4 }
|
|
|
|
|
|
cc3000Trap TRAP-TYPE
|
|
ENTERPRISE danthermCooling
|
|
VARIABLES {hostName, errorNumber, status, value, info }
|
|
DESCRIPTION "Trap From CC300 Controller. Contains TRAP information "
|
|
REFERENCE "None"
|
|
::= 1
|
|
|
|
|
|
|
|
END
|
|
|