mibs/MIBS/dantherm/DANTHERM-COOLING-MIB
2023-12-05 12:25:34 +01:00

2777 lines
75 KiB
Plaintext

-- MIB for Dantherm Cooling Controllers
DANTHERM-COOLING-MIB DEFINITIONS ::= BEGIN
IMPORTS
OBJECT-TYPE
FROM RFC-1212
enterprises
FROM RFC1155-SMI;
--
-- Product and Data group Definitions
danthermCooling OBJECT IDENTIFIER ::= { enterprises 46651 }
--
-- Product CC3000 Controller Definitions
controllerCC3000 OBJECT IDENTIFIER ::= { danthermCooling 1 }
systemStatus OBJECT IDENTIFIER ::= { controllerCC3000 1 }
highlevelControl OBJECT IDENTIFIER ::= { controllerCC3000 2 }
fan1Config OBJECT IDENTIFIER ::= { controllerCC3000 3 }
fan2Config OBJECT IDENTIFIER ::= { controllerCC3000 4 }
damper1Config OBJECT IDENTIFIER ::= { controllerCC3000 5 }
damper2Config OBJECT IDENTIFIER ::= { controllerCC3000 6 }
aircon1Config OBJECT IDENTIFIER ::= { controllerCC3000 7 }
aircon2Config OBJECT IDENTIFIER ::= { controllerCC3000 8 }
heaterConfig OBJECT IDENTIFIER ::= { controllerCC3000 9 }
humidityConfig OBJECT IDENTIFIER ::= { controllerCC3000 10 }
systemConfig OBJECT IDENTIFIER ::= { controllerCC3000 11 }
alarmConfig OBJECT IDENTIFIER ::= { controllerCC3000 12 }
nightModeConfig OBJECT IDENTIFIER ::= { controllerCC3000 13 }
networkConfig OBJECT IDENTIFIER ::= { controllerCC3000 14 }
trapError OBJECT IDENTIFIER ::= { controllerCC3000 15 }
-- Product CCxx Controller Definitions
--controllerCCxx OBJECT IDENTIFIER ::= { danthermCooling x }
--
-- Controller-CC3000 : systemStatus
onBoardTempr OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Controller On-Board temperature in Degree Celcius "
::= { systemStatus 1 }
roomTempr OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Room Sensor or Zone 1 Sensor temperature in Degree Celcius"
::= { systemStatus 2 }
hotSpotTempr OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Hot Spot Sensor or Zone 2 Sensor temperature in Degree Celcius"
::= { systemStatus 3 }
outdoor1Tempr OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Ambient Sensor 1 or Zone 1 Ambient Sensor. temperature in Degree Celcius"
::= { systemStatus 4 }
outdoor2Tempr OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Ambient Sensor 2 or Zone 2 Ambient Sensor. temperature in Degree Celcius"
::= { systemStatus 5 }
shelterTempr OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Shelter Temperature. Valid for Single-Zone solution"
::= { systemStatus 6 }
outdoorCombinedTempr OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Cobined minimum Outdoor Temeperature. Valid for Single-Zone solution"
::= { systemStatus 7 }
fan1RPM OBJECT-TYPE
SYNTAX INTEGER(0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fan 1 Rotation Per Minute"
::= { systemStatus 8 }
fan2RPM OBJECT-TYPE
SYNTAX INTEGER(0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fan 2 Rotation Per Minute"
::= { systemStatus 9 }
fan1SpeedPercentage OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fan 1 Speed in Percentage of Maximum Speed. Also represents Duty-Cycle of FAn Signal "
::= { systemStatus 10 }
fan2SpeedPercentage OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fan 2 Speed in Percentage of Maximum Speed. Also represents Duty-Cycle of FAn Signal "
::= { systemStatus 11 }
damper1Position OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Damper 1 Shutter Open Percentage. 0% - Damper Closed. 100% - Damper completely open"
::= { systemStatus 12 }
damper2Position OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Damper 2 Shutter Open Percentage. 0% - Damper Closed. 100% - Damper completely open"
::= { systemStatus 13 }
humidity OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Internal or external humidity in Rh%"
::= { systemStatus 14 }
dewpoint OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Internal or external DewPoint based on Humidity; in Degree Celcius"
::= { systemStatus 15 }
atmosphericPressure OBJECT-TYPE
SYNTAX INTEGER(0..10000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Atmospheric pressure or Pressure of installed enclosure in KiloPascal"
::= { systemStatus 16 }
flowPressure OBJECT-TYPE
SYNTAX INTEGER(-1000..1000)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Filter flow Pressure in Pascal"
::= { systemStatus 17 }
fan1Status OBJECT-TYPE
SYNTAX INTEGER(0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fan 1 operation status. 0 - Off; 1 - On -; 2 - Emergency/Boost "
::= { systemStatus 18 }
fan2Status OBJECT-TYPE
SYNTAX INTEGER(0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Fan 2 operation status. 0 - Off; 1 - On -; 2 - Emergency/Boost "
::= { systemStatus 19 }
damper1Status OBJECT-TYPE
SYNTAX INTEGER(0..3)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Damper 1 operation status. 0 - Closed; 1 - Open; 2 - Dynamic or Temperature Compensation; 2 - Emergency/Boost "
::= { systemStatus 20 }
damper2Status OBJECT-TYPE
SYNTAX INTEGER(0..3)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Damper 2 Shutter Open Percentage. 0 - Closed; 1 - Open; 2 - Dynamic or Temperature Compensation; 2 - Emergency/Boost "
::= { systemStatus 21 }
aircond1Status OBJECT-TYPE
SYNTAX INTEGER(0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Airconditioner 1 operation status. 0 - Off; 1 - Restart timeout; 2 - On "
::= { systemStatus 22 }
aircond2Status OBJECT-TYPE
SYNTAX INTEGER(0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Airconditioner 2 operation status. 0 - Off; 1 - Restart timeout; 2 - On "
::= { systemStatus 23 }
heaterStatus OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"heater operation status. 0 - Off; 1 - On "
::= { systemStatus 24 }
shelter1Status OBJECT-TYPE
SYNTAX INTEGER(0..6)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Shelter Status in Single-Zone mode or Zone 1 Status in Dual-Zone mode respectively.
0 - Inactive or None State
1 - Heating State
2 - Re-Cycling State
3 - Free Cooling State
4 - Active or Aircon Coolign State
5 - Emergency State
6 - Intermediate state( strategy transistion) "
::= { systemStatus 25 }
shelter2Status OBJECT-TYPE
SYNTAX INTEGER(0..6)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Shelter Status in Dual-Zone mode or Zone 2 Status.
0 - Inactive or None State
1 - Heating State
2 - Re-Cycling State
3 - Free Cooling State
4 - Active or Aircon Coolign State
5 - Emergency State
6 - Intermediate state( strategy transistion) "
::= { systemStatus 26 }
shelter1Mode OBJECT-TYPE
SYNTAX INTEGER(0..3)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Shelter Run time mode in Single-Zone mode or Zone 1 Status in Dual-Zone mode respectively.
0 - Free Cooling Mode
1 - Standard Mode
2 - Power Save Mode
3 - Air conditioner Mode "
::= { systemStatus 27 }
shelter2Mode OBJECT-TYPE
SYNTAX INTEGER(0..3)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Shelter Run time mode in Dual-Zone mode or Zone 2 Status.
0 - Free Cooling Mode
1 - Standard Mode
2 - Power Save Mode
3 - Air conditioner Mode "
::= { systemStatus 28 }
shelter1Setpoint OBJECT-TYPE
SYNTAX INTEGER(-41..80)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Shelter run time Cooling Set point in Single-Zone mode or Zone 1 Status in Dual-Zone mode respectively.
Cooling setpoint can be offset by following functions
RH function
Night mode
Digital inputs "
::= { systemStatus 29 }
shelter2Setpoint OBJECT-TYPE
SYNTAX INTEGER(-41..80)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Shelter run time Cooling Set point in Dual-Zone mode or Zone 2 Status.
Cooling setpoint can be offset by following functions
RH function
Night mode
Digital inputs "
::= { systemStatus 30 }
errorStatus OBJECT-TYPE
SYNTAX INTEGER(0..33554432)
ACCESS read-only
STATUS mandatory
DESCRIPTION
" controller internal error status. Binary
bit position - alarm drive state: 0 - inactive , 1 - active
0 - voltage low
1 - voltage high
2 - tempr low
3 - tempr limit 1
4 - tempr limit 2
5 - tempr limit 3
6 - humid. low
7 - humid. high
8 - fltr pressure 1
9 - fltr pressure 2
10 - fan 1
11 - fan 2
12 - onboard sens
13 - room sens
14 - hotspot sens
15 - ambient 1 sens
16 - ambient 2 sens
17 - dig 1 i/p
18 - dig 2 i/p
19 - dig 3 i/p
20 - filter i/p 1
21 - filter i/p 2
22 - network
23 - int storage
24 - sd card "
::= { systemStatus 31 }
maskedErrorStatus OBJECT-TYPE
SYNTAX INTEGER(0..33554432)
ACCESS read-only
STATUS mandatory
DESCRIPTION
" Controller Output Error status. Binary
Bit Position - Alarm Drive State: 0 - Inactive , 1 - Active
0 - Voltage Low
1 - Voltage High
2 - Tempr Low
3 - Tempr Limit 1
4 - Tempr Limit 2
5 - Tempr Limit 3
6 - Humid. Low
7 - Humid. High
8 - Fltr Pressure 1
9 - Fltr Pressure 2
10 - Fan 1
11 - Fan 2
12 - Onboard Sens
13 - Room Sens
14 - Hotspot Sens
15 - Ambient 1 Sens
16 - Ambient 2 Sens
17 - Dig 1 I/P
18 - Dig 2 I/P
19 - Dig 3 I/P
20 - Filter I/P 1
21 - Filter I/P 2
22 - Network
23 - Int storage
24 - SD Card "
::= { systemStatus 32 }
voltage OBJECT-TYPE
SYNTAX INTEGER(0..80)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"System Voltage in DC. "
::= { systemStatus 33 }
digitalInputStatus OBJECT-TYPE
SYNTAX INTEGER(0..16)
ACCESS read-only
STATUS mandatory
DESCRIPTION
" Controller Alarm Drive Status. Binary
Bit Position - Digital Input State: 0 - Inactive , 1 - Active
0 - DIG 1 I/P
1 - DIG 2 I/P
2 - DIG 3 I/P
3 - FILTER GUARD DIGI 1 I/P
4 - FILTER GUARD DIGI 2 I/P "
::= { systemStatus 34 }
alarmDriveStatus OBJECT-TYPE
SYNTAX INTEGER(0..1024)
ACCESS read-only
STATUS mandatory
DESCRIPTION
" Controller Alarm Drive Status. Binary
Bit Position - Alarm Drive State: 0 - Inactive , 1 - Active
0 - ALARM 1
1 - ALARM 2
2 - ALARM 3
3 - ALARM 4
4 - ALARM 5
5 - ALARM 6
6 - ALARM 7
7 - ALARM 8
8 - ALARM 9
9 - ALARM 10"
::= { systemStatus 35 }
fan1OpertdurHour OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Fan 1 operation duration - Hour "
::= { systemStatus 36 }
fan1OpertdurMin OBJECT-TYPE
SYNTAX INTEGER(0..59)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Fan 1 operation duration - Minute "
::= { systemStatus 37 }
fan2OpertdurHour OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Fan 2 operation duration - Hour "
::= { systemStatus 38 }
fan2OpertdurMin OBJECT-TYPE
SYNTAX INTEGER(0..59)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Fan 2 operation duration - Minute "
::= { systemStatus 39 }
aircon1OpertdurHour OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Airconditioner 1 operation duration - Hour "
::= { systemStatus 40 }
aircon1OpertdurMin OBJECT-TYPE
SYNTAX INTEGER(0..59)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Airconditioner 1 operation duration - Minute "
::= { systemStatus 41 }
aircon2OpertdurHour OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Airconditioner 2 operation duration - Hour "
::= { systemStatus 42 }
aircon2OpertdurMin OBJECT-TYPE
SYNTAX INTEGER(0..59)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Airconditioner 2 operation duration - Minute "
::= { systemStatus 43 }
heaterOpertdurHour OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Heater operation duration - Hour "
::= { systemStatus 44 }
heaterOpertdurMin OBJECT-TYPE
SYNTAX INTEGER(0..59)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Heater operation duration - Minute "
::= { systemStatus 45 }
ccSN OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "CC3000 Controller serial number "
::= { systemStatus 46 }
fanbox1SN OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "Free cooling FanBox unit 1 serial number "
::= { systemStatus 47 }
fanbox2SN OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "Free cooling FanBox unit 2 serial number "
::= { systemStatus 48 }
aircond1SN OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "Aicodnitioner unit 1 serial number "
::= { systemStatus 49 }
aircond2SN OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "Aicodnitioner unit 2 serial number "
::= { systemStatus 50 }
fwVersion OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION "CC3000 Firmware version "
::= { systemStatus 51 }
--
-- Controller-CC3000 : highlevelControl
coolSetpointZone1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Cooling Setpoint Zone/Shelter 1 "
::= { highlevelControl 1 }
coolSetpointZone2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Cooling Setpoint Zone/Shelter 2 "
::= { highlevelControl 2 }
heaterSetpoint OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Heater Setpoint "
::= { highlevelControl 3 }
backupConfig OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Configuration Backup to Internal memory and SD card. 0 - No change, 1 - Backup "
::= { highlevelControl 4 }
restoreConfig OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Configuration restore from Internal memory. 0 - No change, 1 - Restore "
::= { highlevelControl 5 }
systemReset OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Colling System reset or restart. 0 - No change, 1 - Restart "
::= { highlevelControl 6 }
year OBJECT-TYPE
SYNTAX INTEGER(2015..2099)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Calender - Year "
::= { highlevelControl 7 }
month OBJECT-TYPE
SYNTAX INTEGER(1..12)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Calender - Month "
::= { highlevelControl 8 }
date OBJECT-TYPE
SYNTAX INTEGER(1..31)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Calender - Date "
::= { highlevelControl 9 }
hour OBJECT-TYPE
SYNTAX INTEGER(0..23)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Clock - Hour "
::= { highlevelControl 10 }
minute OBJECT-TYPE
SYNTAX INTEGER(0..59)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Clock - Minute "
::= { highlevelControl 11 }
--
-- Controller-CC3000 : fan1Config
saveReloadConff1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
::= { fan1Config 1 }
offTemprf1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Fan OFF temperature "
::= { fan1Config 2 }
idleOnTemprf1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Fan Idle Speed On temperature "
::= { fan1Config 3 }
idleEntryTemprf1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Idle entry temperature "
::= { fan1Config 4 }
midPoint1Temprf1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Mid point 1 entry temperature "
::= { fan1Config 5 }
setPointTemprf1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Set Point temperature "
::= { fan1Config 6 }
midPoint2Temprf1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Mid point 2 entry temperature "
::= { fan1Config 7 }
highSpeedTemprf1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "high Speed entry temperature "
::= { fan1Config 8 }
extendHighSpeedEntryTemprf1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Extended high Speed entry temperature "
::= { fan1Config 9 }
extendHighSpeedExitTemprf1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Extended high Speed exit temperature "
::= { fan1Config 10 }
boostEntryTemprf1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Boost Speed entry temperature "
::= { fan1Config 11 }
boostExitTemprf1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Boost Speed entry temperature "
::= { fan1Config 12 }
idleRPMf1 OBJECT-TYPE
SYNTAX INTEGER(0..9999)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Idle speed RPM "
::= { fan1Config 13 }
midPointRPMf1 OBJECT-TYPE
SYNTAX INTEGER(0..9999)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Midpoint Speed RPM "
::= { fan1Config 14 }
highSpeedRPMf1 OBJECT-TYPE
SYNTAX INTEGER(0..9999)
ACCESS read-write
STATUS mandatory
DESCRIPTION "high Speed RPM "
::= { fan1Config 15 }
extendHighSpeedRPMf1 OBJECT-TYPE
SYNTAX INTEGER(0..9999)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Extended high Speed RPM "
::= { fan1Config 16 }
idleDutyCyclef1 OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Idle Speed Duty Cycle "
::= { fan1Config 17 }
midDutyCyclef1 OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Midpoint speed Duty Cycle "
::= { fan1Config 18 }
highSpeedDutyCyclef1 OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION "high speed Duty Cycle "
::= { fan1Config 19 }
extendHighSpeedDutyCyclef1 OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Extended high speed Duty Cycle "
::= { fan1Config 20 }
boostDutyCyclef1 OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Boost speed Duty Cycle "
::= { fan1Config 21 }
deadBandRPMf1 OBJECT-TYPE
SYNTAX INTEGER(0..1000)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Dead band RPM "
::= { fan1Config 22 }
overrideDigi1f1 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
::= { fan1Config 23 }
overrideDigi2f1 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
::= { fan1Config 24 }
overrideDigi3f1 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
::= { fan1Config 25 }
overrideSensorfailf1 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
::= { fan1Config 26 }
sensorSelectf1 OBJECT-TYPE
SYNTAX INTEGER(0..5)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature "
::= { fan1Config 27 }
tachoPulseperrotationf1 OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Number of Tacho pulses per cycle rotation for given fan "
::= { fan1Config 28 }
closedLoopenablef1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Closed Loop control enable or disable for given Fan. 0 - Enable. 1 - Disable "
::= { fan1Config 29 }
controlTypef1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - 0-10V DC control. 1 - PWM control "
::= { fan1Config 30 }
enablef1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - Disable Fan control. 1 - Enabel fan control "
::= { fan1Config 31 }
--
-- Controller-CC3000 : fan2Config
saveReloadConff2 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
::= { fan2Config 1 }
offTemprf2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Fan OFF temperature "
::= { fan2Config 2 }
idleOnTemprf2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Fan Idle Speed On temperature "
::= { fan2Config 3 }
idleEntryTemprf2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Idle entry temperature "
::= { fan2Config 4 }
midPoint1Temprf2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Mid point 1 entry temperature "
::= { fan2Config 5 }
setPointTemprf2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Set Point temperature "
::= { fan2Config 6 }
midPoint2Temprf2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Mid point 2 entry temperature "
::= { fan2Config 7 }
highSpeedTemprf2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "high Speed entry temperature "
::= { fan2Config 8 }
extendHighSpeedEntryTemprf2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Extended high Speed entry temperature "
::= { fan2Config 9 }
extendHighSpeedExitTemprf2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Extended high Speed exit temperature "
::= { fan2Config 10 }
boostEntryTemprf2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Boost Speed entry temperature "
::= { fan2Config 11 }
boostExitTemprf2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Boost Speed entry temperature "
::= { fan2Config 12 }
idleRPMf2 OBJECT-TYPE
SYNTAX INTEGER(0..9999)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Idle speed RPM "
::= { fan2Config 13 }
midPointRPMf2 OBJECT-TYPE
SYNTAX INTEGER(0..9999)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Midpoint Speed RPM "
::= { fan2Config 14 }
highSpeedRPMf2 OBJECT-TYPE
SYNTAX INTEGER(0..9999)
ACCESS read-write
STATUS mandatory
DESCRIPTION "high Speed RPM "
::= { fan2Config 15 }
extendHighSpeedRPMf2 OBJECT-TYPE
SYNTAX INTEGER(0..9999)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Extended high Speed RPM "
::= { fan2Config 16 }
idleDutyCyclef2 OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Idle Speed Duty Cycle "
::= { fan2Config 17 }
midDutyCyclef2 OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Midpoint speed Duty Cycle "
::= { fan2Config 18 }
highSpeedDutyCyclef2 OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION "high speed Duty Cycle "
::= { fan2Config 19 }
extendHighSpeedDutyCyclef2 OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Extended high speed Duty Cycle "
::= { fan2Config 20 }
boostDutyCyclef2 OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Boost speed Duty Cycle "
::= { fan2Config 21 }
deadBandRPMf2 OBJECT-TYPE
SYNTAX INTEGER(0..1000)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Dead band RPM "
::= { fan2Config 22 }
overrideDigi1f2 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
::= { fan2Config 23 }
overrideDigi2f2 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
::= { fan2Config 24 }
overrideDigi3f2 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
::= { fan2Config 25 }
overrideSensorfailf2 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. "
::= { fan2Config 26 }
sensorSelectf2 OBJECT-TYPE
SYNTAX INTEGER(0..5)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature "
::= { fan2Config 27 }
tachoPulseperrotationf2 OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Number of Tacho pulses per cycle rotation for given fan "
::= { fan2Config 28 }
closedLoopenablef2 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Closed Loop control enable or disable for given Fan. 0 - Enable. 1 - Disable "
::= { fan2Config 29 }
controlTypef2 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - 0-10V DC control. 1 - PWM control"
::= { fan2Config 30 }
enablef2 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - Disable Fan control. 1 - Enabel fan control "
::= { fan2Config 31 }
--
-- Controller-CC3000 : damper1Config
saveReloadConfd1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
::= { damper1Config 1 }
lowercloseTemprd1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Damper lower closing temperature "
::= { damper1Config 2 }
setPointd1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Damper opening temperature "
::= { damper1Config 3 }
upperOpentempd1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Damper upper opening temperature "
::= { damper1Config 4 }
upperClosetempd1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Damper upper closing temperature "
::= { damper1Config 5 }
emgncyClosetempd1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Damper emergency closing temperature "
::= { damper1Config 6 }
emgncyopentempd1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Damper emergency open temperature "
::= { damper1Config 7 }
overrideDigi1d1 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
::= { damper1Config 8 }
overrideDigi2d1 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
::= { damper1Config 9 }
overrideDigi3d1 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
::= { damper1Config 10 }
overrideSensorFaild1 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
::= { damper1Config 11 }
sensSelectd1 OBJECT-TYPE
SYNTAX INTEGER(0..5)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature "
::= { damper1Config 12 }
runDurationd1 OBJECT-TYPE
SYNTAX INTEGER(30..300)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Damper Run time in minutes "
::= { damper1Config 13 }
enabled1 OBJECT-TYPE
SYNTAX INTEGER(0..2)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Disable. 1 - ONOFF. 2 - Dynamic "
::= { damper1Config 14 }
--
--Controller-CC3000 : damper2Config
saveReloadConfd2 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
::= { damper2Config 1 }
lowercloseTemprd2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Damper lower closing temperature "
::= { damper2Config 2 }
setPointd2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Damper opening temperature "
::= { damper2Config 3 }
upperOpentempd2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Damper upper opening temperature "
::= { damper2Config 4 }
upperClosetempd2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Damper upper closing temperature "
::= { damper2Config 5 }
emgncyClosetempd2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Damper emergency closing temperature "
::= { damper2Config 6 }
emgncyopentempd2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Damper emergency open temperature "
::= { damper2Config 7 }
overrideDigi1d2 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
::= { damper2Config 8 }
overrideDigi2d2 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
::= { damper2Config 9 }
overrideDigi3d2 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
::= { damper2Config 10 }
overrideSensorFaild2 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Damper close. 1 - Damper open. 120 - No action on Over ride. "
::= { damper2Config 11 }
sensSelectd2 OBJECT-TYPE
SYNTAX INTEGER(0..5)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature "
::= { damper2Config 12 }
runDurationd2 OBJECT-TYPE
SYNTAX INTEGER(30..300)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Damper Run time in minutes "
::= { damper2Config 13 }
enabled2 OBJECT-TYPE
SYNTAX INTEGER(0..2)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Disable. 1 - ONOFF. 2 - Dynamic "
::= { damper2Config 14 }
--
-- Controller-CC3000 : AC-1-Config
saveReloadConfac1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
::= { aircon1Config 1 }
oNTemprac1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Air Conditioner ON temperature "
::= { aircon1Config 2 }
oFFTemprac1 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Air Conditioner OFF temperature "
::= { aircon1Config 3 }
overrideDigi1ac1 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride. "
::= { aircon1Config 4 }
overrideDigi2ac1 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride. "
::= { aircon1Config 5 }
overrideDigi3ac1 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride "
::= { aircon1Config 6 }
overrideSensorFailac1 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride "
::= { aircon1Config 7 }
sensSelectac1 OBJECT-TYPE
SYNTAX INTEGER(0..5)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature "
::= { aircon1Config 8 }
minimumRunDurationac1 OBJECT-TYPE
SYNTAX INTEGER(60..3600)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Minimum AC Run time in seconds "
::= { aircon1Config 9 }
restartTimeoutac1 OBJECT-TYPE
SYNTAX INTEGER(60..3600)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Restart timer in seconds "
::= { aircon1Config 10 }
enableac1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Disable. 1 - Enable. "
::= { aircon1Config 11 }
--
-- Controller-CC3000 : aircon2Config
saveReloadConfac2 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
::= { aircon2Config 1 }
onTemprac2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Air Conditioner ON temperature "
::= { aircon2Config 2 }
offTemprac2 OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Air Conditioner OFF temperature "
::= { aircon2Config 3 }
overrideDigi1ac2 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride. "
::= { aircon2Config 4 }
overrideDigi2ac2 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride. "
::= { aircon2Config 5 }
overrideDigi3ac2 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride "
::= { aircon2Config 6 }
overrideSensorFailac2 OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - AC OFF. 1 - AC ON. 120 - No action on Over ride "
::= { aircon2Config 7 }
sensSelectac2 OBJECT-TYPE
SYNTAX INTEGER(0..5)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature "
::= { aircon2Config 8 }
minimumRunDurationac2 OBJECT-TYPE
SYNTAX INTEGER(60..3600)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Minimum AC Run time in seconds "
::= { aircon2Config 9 }
restartTimeoutac2 OBJECT-TYPE
SYNTAX INTEGER(60..3600)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Restart timer in seconds "
::= { aircon2Config 10 }
enableac2 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Disable. 1 - Enable. "
::= { aircon2Config 11 }
--
-- Controller-CC3000 : heaterConfig
saveReloadConfhtr OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
::= { heaterConfig 1 }
onTemprhtr OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Heater ON temperature "
::= { heaterConfig 2 }
offTemprhtr OBJECT-TYPE
SYNTAX INTEGER(-41..101)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Heater OFF temperature "
::= { heaterConfig 3 }
overrideDigi1htr OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride. "
::= { heaterConfig 4 }
overrideDigi2htr OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride. "
::= { heaterConfig 5 }
overrideDigi3htr OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride "
::= { heaterConfig 6 }
overrideSensorFailhtr OBJECT-TYPE
SYNTAX INTEGER(0..120)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride "
::= { heaterConfig 7 }
sensSelecthtr OBJECT-TYPE
SYNTAX INTEGER(0..5)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature "
::= { heaterConfig 8 }
enablehtr OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Disable. 1 - Enable. "
::= { heaterConfig 9 }
--
-- Controller-CC3000 : humidityConfig
saveReloadConfhum OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
::= { humidityConfig 1 }
rhEntryhum OBJECT-TYPE
SYNTAX INTEGER(40..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Humidity function entry value "
::= { humidityConfig 2 }
rhExithum OBJECT-TYPE
SYNTAX INTEGER(40..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Humidity function exit value "
::= { humidityConfig 3 }
coolingmodehum OBJECT-TYPE
SYNTAX INTEGER(0..3)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Freecooling. 1 - Standard. 2 - Power save. 3 - Aircon. "
::= { humidityConfig 4 }
temprsetpoffsethum OBJECT-TYPE
SYNTAX INTEGER(-10..10)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Cooling setpoint offset "
::= { humidityConfig 5 }
rhSensPositionhum OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Indoor. 1 - Outdoor "
::= { humidityConfig 6 }
enablehum OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Disable. 1 - Enable. "
::= { humidityConfig 7 }
--
-- Controller-CC3000 : systemConfig
saveReloadConfsysc OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
::= { systemConfig 1 }
vdcLowEntrysys OBJECT-TYPE
SYNTAX INTEGER(18..60)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Low voltage shut down entry "
::= { systemConfig 2 }
vdcLowExitsys OBJECT-TYPE
SYNTAX INTEGER(18..60)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Low voltage shut down exit "
::= { systemConfig 3 }
vdcHighEntrysys OBJECT-TYPE
SYNTAX INTEGER(18..60)
ACCESS read-write
STATUS mandatory
DESCRIPTION " High voltage shut down entry "
::= { systemConfig 4 }
vdcHighExitsys OBJECT-TYPE
SYNTAX INTEGER(18..60)
ACCESS read-write
STATUS mandatory
DESCRIPTION " High voltage shut down exit "
::= { systemConfig 5 }
temprLowlimitsys OBJECT-TYPE
SYNTAX INTEGER(-40..80)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Low temperature alarm limit "
::= { systemConfig 6 }
temprHighlimit1sys OBJECT-TYPE
SYNTAX INTEGER(-40..80)
ACCESS read-write
STATUS mandatory
DESCRIPTION " High temperature alarm limit 1 "
::= { systemConfig 7 }
temprHighlimit2sys OBJECT-TYPE
SYNTAX INTEGER(-40..80)
ACCESS read-write
STATUS mandatory
DESCRIPTION " High temperature alarm limit 2 "
::= { systemConfig 8 }
temprHighlimit3sys OBJECT-TYPE
SYNTAX INTEGER(-40..80)
ACCESS read-write
STATUS mandatory
DESCRIPTION " High temperature alarm limit 3 "
::= { systemConfig 9 }
temprlimithyssys OBJECT-TYPE
SYNTAX INTEGER(-20..20)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Temperature alarm limit hysteresis "
::= { systemConfig 10 }
rhLowlimitsys OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Humidity alarm low limit %RH "
::= { systemConfig 11 }
rhHighlimitsys OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Humidity alarm High limit %RH "
::= { systemConfig 12 }
flowpresslimit1sys OBJECT-TYPE
SYNTAX INTEGER(60..400)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Flow pressure limit 1 Pa "
::= { systemConfig 13 }
flowpresslimit2sys OBJECT-TYPE
SYNTAX INTEGER(60..400)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Flow pressure limit 2 Pa "
::= { systemConfig 14 }
flowpresshyssys OBJECT-TYPE
SYNTAX INTEGER(0..400)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Flow pressure limit hysteresis Pa "
::= { systemConfig 15 }
coolingzonessys OBJECT-TYPE
SYNTAX INTEGER(1..2)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 1 - One cooling zone, 2 - Two cooling zones "
::= { systemConfig 16 }
coolingModesys OBJECT-TYPE
SYNTAX INTEGER(0..3)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - FC, 1 - Std, 2 - Ps, 3 - Acon "
::= { systemConfig 17 }
negCoolingDeltaOverridesys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - Disable, 1 - Enable "
::= { systemConfig 18 }
negCoolingDeltaHyssys OBJECT-TYPE
SYNTAX INTEGER(-10..10)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Negative cooling delta hysteresis "
::= { systemConfig 19 }
coolingDeltatempsys OBJECT-TYPE
SYNTAX INTEGER(-10..10)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Cooling delta temperature "
::= { systemConfig 20 }
shelterTemprsys OBJECT-TYPE
SYNTAX INTEGER(0..2)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - RA, 1 - HS, 2 - Both "
::= { systemConfig 21 }
acleadlagsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - Disable, 1 - Enable "
::= { systemConfig 22 }
coolingModeXzonesys OBJECT-TYPE
SYNTAX INTEGER(0..3)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - FC, 1 - Std, 2 - Ps, 3 - Acon "
::= { systemConfig 23 }
negCoolingDeltaOverrideXzonesys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - Disable, 1 - Enable "
::= { systemConfig 24 }
negCoolingDeltaHysXzonesys OBJECT-TYPE
SYNTAX INTEGER(-10..10)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Negative cooling delta hysteresis "
::= { systemConfig 25 }
coolingDeltatempXzonesys OBJECT-TYPE
SYNTAX INTEGER(-10..10)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Cooling delta temperature "
::= { systemConfig 26 }
fan1Zonesys OBJECT-TYPE
SYNTAX INTEGER(1..2)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 1 - Fan 1 for Zone 1, 2 - Fan 1 for zone 2 "
::= { systemConfig 27 }
fan2Zonesys OBJECT-TYPE
SYNTAX INTEGER(1..2)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 1 - Fan 2 for Zone 1, 2 - Fan 2 for zone 2 "
::= { systemConfig 28 }
ac1Zonesys OBJECT-TYPE
SYNTAX INTEGER(1..2)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 1 - AC 1 for Zone 1, 2 - AC 1 for zone 2 "
::= { systemConfig 29 }
ac2Zonesys OBJECT-TYPE
SYNTAX INTEGER(1..2)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 1 - AC 2 for Zone 1, 2 - AC 2 for zone 2 "
::= { systemConfig 30 }
damper1Zonesys OBJECT-TYPE
SYNTAX INTEGER(1..2)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 1 - Damper 1 for Zone 1, 2 - Damper 1 for zone 2 "
::= { systemConfig 31 }
damper2Zonesys OBJECT-TYPE
SYNTAX INTEGER(1..2)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 1 - Damper 2 for Zone 1, 2 - Damper 2 for zone 2 "
::= { systemConfig 32 }
heaterZonesys OBJECT-TYPE
SYNTAX INTEGER(1..2)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 1 - Heater for Zone 1, 2 - Heater for zone 2 "
::= { systemConfig 33 }
statusLogsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - Disable, 1 - Enable "
::= { systemConfig 34 }
logintervalsys OBJECT-TYPE
SYNTAX INTEGER(1..60)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Log interval in minutes "
::= { systemConfig 35 }
alarm1NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 36 }
alarm2NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 37 }
alarm3NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 38 }
alarm4NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 39 }
alarm5NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 40 }
alarm6NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 41 }
alarm7NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 42 }
alarm8NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 43 }
alarm9NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 44 }
alarm10NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 45 }
alarm1Delaysys OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Alarm output delay in seconds "
::= { systemConfig 46 }
alarm2Delaysys OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Alarm output delay in seconds "
::= { systemConfig 47 }
alarm3Delaysys OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Alarm output delay in seconds "
::= { systemConfig 48 }
alarm4Delaysys OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Alarm output delay in seconds "
::= { systemConfig 49 }
alarm5Delaysys OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Alarm output delay in seconds "
::= { systemConfig 50 }
alarm6Delaysys OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Alarm output delay in seconds "
::= { systemConfig 51 }
alarm7Delaysys OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Alarm output delay in seconds "
::= { systemConfig 52 }
alarm8Delaysys OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Alarm output delay in seconds "
::= { systemConfig 53 }
alarm9Delaysys OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Alarm output delay in seconds "
::= { systemConfig 54 }
alarm10Delaysys OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Alarm output delay in seconds "
::= { systemConfig 55 }
ac1NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 56 }
ac2NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 57 }
dig1NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 58 }
dig2NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 59 }
dig3NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 60 }
dig2funcoverridesys OBJECT-TYPE
SYNTAX INTEGER(0..2)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - Override, 1 - setpoint offset, 2 - mode X "
::= { systemConfig 61 }
dig3funcoverridesys OBJECT-TYPE
SYNTAX INTEGER(0..2)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - Override, 1 - setpoint offset, 2 - mode X "
::= { systemConfig 62 }
dig2offsetsys OBJECT-TYPE
SYNTAX INTEGER(-10..10)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Cooling setpoint offset "
::= { systemConfig 63 }
dig3offsetsys OBJECT-TYPE
SYNTAX INTEGER(-10..10)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Cooling setpoint offset "
::= { systemConfig 64 }
dig2trigModesys OBJECT-TYPE
SYNTAX INTEGER(0..3)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - FC, 1 - Std, 2 - Ps, 3 - Acon "
::= { systemConfig 65 }
dig3TrigModesys OBJECT-TYPE
SYNTAX INTEGER(0..3)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - FC, 1 - Std, 2 - Ps, 3 - Acon"
::= { systemConfig 66 }
filterGuard1NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 67 }
filterGuard2NONCsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - NO, 1 - NC "
::= { systemConfig 68 }
temprUnitsCFsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - Celcius, 1 - Fahrenheit "
::= { systemConfig 69 }
languageEnglishsys OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION " 0 - Disable, 1 - Enable "
::= { systemConfig 70 }
--
-- Controller-CC3000 : alarmConfig
saveReloadConfAlm OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Alarm Mapping reloaded "
::= { alarmConfig 1 }
alarm1mask OBJECT-TYPE
SYNTAX INTEGER(0..33554432)
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Alarm drive 1 Mask [Can have multiple Alarm Errors].
Bit Position - Value - Alarm Drive State: 0 - Unselect, 1 - Select
1 - 1 - Voltage Low
2 - 2 - Voltage High
3 - 4 - Tempr Low
4 - 8 - Tempr Limit 1
5 - 16 - Tempr Limit 2
6 - 32 - Tempr Limit 3
7 - 64 - Humid. Low
8 - 128 - Humid. High
9 - 256 - Fltr Pressure 1
10 - 512 - Fltr Pressure 2
11 - 1024 - Fan 1
12 - 2048 - Fan 2
13 - 4096 - Onboard Sens
14 - 8192 - Room Sens
15 - 16384 - Hotspot Sens
16 - 32768 - Ambient 1 Sens
17 - 65536 - Ambient 2 Sens
18 - 131072 - Dig 1 I/P
19 - 262144 - Dig 2 I/P
20 - 524288 - Dig 3 I/P
21 - 1048576 - Filter I/P 1
22 - 2097152 - Filter I/P 2
23 - 4194304 - Network
24 - 8388608 - Int storage
25 - 16777216 - SD Card "
::= { alarmConfig 2 }
alarm2mask OBJECT-TYPE
SYNTAX INTEGER(0..33554432)
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Alarm drive 2 Mask [Can have multiple Alarm Errors].
Bit Position - Value - Alarm Drive State: 0 - Unselect, 1 - Select
1 - 1 - Voltage Low
2 - 2 - Voltage High
3 - 4 - Tempr Low
4 - 8 - Tempr Limit 1
5 - 16 - Tempr Limit 2
6 - 32 - Tempr Limit 3
7 - 64 - Humid. Low
8 - 128 - Humid. High
9 - 256 - Fltr Pressure 1
10 - 512 - Fltr Pressure 2
11 - 1024 - Fan 1
12 - 2048 - Fan 2
13 - 4096 - Onboard Sens
14 - 8192 - Room Sens
15 - 16384 - Hotspot Sens
16 - 32768 - Ambient 1 Sens
17 - 65536 - Ambient 2 Sens
18 - 131072 - Dig 1 I/P
19 - 262144 - Dig 2 I/P
20 - 524288 - Dig 3 I/P
21 - 1048576 - Filter I/P 1
22 - 2097152 - Filter I/P 2
23 - 4194304 - Network
24 - 8388608 - Int storage
25 - 16777216 - SD Card "
::= { alarmConfig 3 }
alarm3mask OBJECT-TYPE
SYNTAX INTEGER(0..25)
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Alarm drive 3 Select [Single Alarm Error].
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
1 - Voltage Low
2 - Voltage High
3 - Tempr Low
4 - Tempr Limit 1
5 - Tempr Limit 2
6 - Tempr Limit 3
7 - Humid. Low
8 - Humid. High
9 - Fltr Pressure 1
10 - Fltr Pressure 2
11 - Fan 1
12 - Fan 2
13 - Onboard Sens
14 - Room Sens
15 - Hotspot Sens
16 - Ambient 1 Sens
17 - Ambient 2 Sens
18 - Dig 1 I/P
19 - Dig 2 I/P
20 - Dig 3 I/P
21 - Filter I/P 1
22 - Filter I/P 2
23 - Network
24 - Int storage
25 - SD Card "
::= { alarmConfig 4 }
alarm4mask OBJECT-TYPE
SYNTAX INTEGER(0..25)
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Alarm drive 4 Select [Single Alarm Error].
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
1 - Voltage Low
2 - Voltage High
3 - Tempr Low
4 - Tempr Limit 1
5 - Tempr Limit 2
6 - Tempr Limit 3
7 - Humid. Low
8 - Humid. High
9 - Fltr Pressure 1
10 - Fltr Pressure 2
11 - Fan 1
12 - Fan 2
13 - Onboard Sens
14 - Room Sens
15 - Hotspot Sens
16 - Ambient 1 Sens
17 - Ambient 2 Sens
18 - Dig 1 I/P
19 - Dig 2 I/P
20 - Dig 3 I/P
21 - Filter I/P 1
22 - Filter I/P 2
23 - Network
24 - Int storage
25 - SD Card "
::= { alarmConfig 5 }
alarm5mask OBJECT-TYPE
SYNTAX INTEGER(0..25)
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Alarm drive 5 Select [Single Alarm Error].
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
1 - Voltage Low
2 - Voltage High
3 - Tempr Low
4 - Tempr Limit 1
5 - Tempr Limit 2
6 - Tempr Limit 3
7 - Humid. Low
8 - Humid. High
9 - Fltr Pressure 1
10 - Fltr Pressure 2
11 - Fan 1
12 - Fan 2
13 - Onboard Sens
14 - Room Sens
15 - Hotspot Sens
16 - Ambient 1 Sens
17 - Ambient 2 Sens
18 - Dig 1 I/P
19 - Dig 2 I/P
20 - Dig 3 I/P
21 - Filter I/P 1
22 - Filter I/P 2
23 - Network
24 - Int storage
25 - SD Card "
::= { alarmConfig 6 }
alarm6mask OBJECT-TYPE
SYNTAX INTEGER(0..25)
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Alarm drive 6 Select [Single Alarm Error].
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
1 - Voltage Low
2 - Voltage High
3 - Tempr Low
4 - Tempr Limit 1
5 - Tempr Limit 2
6 - Tempr Limit 3
7 - Humid. Low
8 - Humid. High
9 - Fltr Pressure 1
10 - Fltr Pressure 2
11 - Fan 1
12 - Fan 2
13 - Onboard Sens
14 - Room Sens
15 - Hotspot Sens
16 - Ambient 1 Sens
17 - Ambient 2 Sens
18 - Dig 1 I/P
19 - Dig 2 I/P
20 - Dig 3 I/P
21 - Filter I/P 1
22 - Filter I/P 2
23 - Network
24 - Int storage
25 - SD Card "
::= { alarmConfig 7 }
alarm7mask OBJECT-TYPE
SYNTAX INTEGER(0..25)
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Alarm drive 7 Select [Single Alarm Error].
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
1 - Voltage Low
2 - Voltage High
3 - Tempr Low
4 - Tempr Limit 1
5 - Tempr Limit 2
6 - Tempr Limit 3
7 - Humid. Low
8 - Humid. High
9 - Fltr Pressure 1
10 - Fltr Pressure 2
11 - Fan 1
12 - Fan 2
13 - Onboard Sens
14 - Room Sens
15 - Hotspot Sens
16 - Ambient 1 Sens
17 - Ambient 2 Sens
18 - Dig 1 I/P
19 - Dig 2 I/P
20 - Dig 3 I/P
21 - Filter I/P 1
22 - Filter I/P 2
23 - Network
24 - Int storage
25 - SD Card "
::= { alarmConfig 8 }
alarm8mask OBJECT-TYPE
SYNTAX INTEGER(0..25)
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Alarm drive 8 Select [Single Alarm Error].
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
1 - Voltage Low
2 - Voltage High
3 - Tempr Low
4 - Tempr Limit 1
5 - Tempr Limit 2
6 - Tempr Limit 3
7 - Humid. Low
8 - Humid. High
9 - Fltr Pressure 1
10 - Fltr Pressure 2
11 - Fan 1
12 - Fan 2
13 - Onboard Sens
14 - Room Sens
15 - Hotspot Sens
16 - Ambient 1 Sens
17 - Ambient 2 Sens
18 - Dig 1 I/P
19 - Dig 2 I/P
20 - Dig 3 I/P
21 - Filter I/P 1
22 - Filter I/P 2
23 - Network
24 - Int storage
25 - SD Card "
::= { alarmConfig 9 }
alarm9mask OBJECT-TYPE
SYNTAX INTEGER(0..25)
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Alarm drive 9 Select [Single Alarm Error].
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
1 - Voltage Low
2 - Voltage High
3 - Tempr Low
4 - Tempr Limit 1
5 - Tempr Limit 2
6 - Tempr Limit 3
7 - Humid. Low
8 - Humid. High
9 - Fltr Pressure 1
10 - Fltr Pressure 2
11 - Fan 1
12 - Fan 2
13 - Onboard Sens
14 - Room Sens
15 - Hotspot Sens
16 - Ambient 1 Sens
17 - Ambient 2 Sens
18 - Dig 1 I/P
19 - Dig 2 I/P
20 - Dig 3 I/P
21 - Filter I/P 1
22 - Filter I/P 2
23 - Network
24 - Int storage
25 - SD Card "
::= { alarmConfig 10 }
alarm10mask OBJECT-TYPE
SYNTAX INTEGER(0..25)
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Alarm drive 10 Select [Single Alarm Error].
Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select
1 - Voltage Low
2 - Voltage High
3 - Tempr Low
4 - Tempr Limit 1
5 - Tempr Limit 2
6 - Tempr Limit 3
7 - Humid. Low
8 - Humid. High
9 - Fltr Pressure 1
10 - Fltr Pressure 2
11 - Fan 1
12 - Fan 2
13 - Onboard Sens
14 - Room Sens
15 - Hotspot Sens
16 - Ambient 1 Sens
17 - Ambient 2 Sens
18 - Dig 1 I/P
19 - Dig 2 I/P
20 - Dig 3 I/P
21 - Filter I/P 1
22 - Filter I/P 2
23 - Network
24 - Int storage
25 - SD Card "
::= { alarmConfig 11 }
--
-- Controller-CC3000 : nightModeConfig
saveReloadConfNm OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
::= { nightModeConfig 1 }
starttimeHournm OBJECT-TYPE
SYNTAX INTEGER(0..24)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Night Mode Start time hour "
::= { nightModeConfig 2 }
startTimeMinutesnm OBJECT-TYPE
SYNTAX INTEGER(0..59)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Night Mode Start time minutes "
::= { nightModeConfig 3 }
endTimeHournm OBJECT-TYPE
SYNTAX INTEGER(0..24)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Night Mode End time hour "
::= { nightModeConfig 4 }
endTimeMinutesnm OBJECT-TYPE
SYNTAX INTEGER(0..59)
ACCESS read-write
STATUS mandatory
DESCRIPTION " Night Mode End time minutes "
::= { nightModeConfig 5 }
fanMaxRPMnm OBJECT-TYPE
SYNTAX INTEGER(0..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION " % of max fan speed "
::= { nightModeConfig 6 }
setPointOffsetnm OBJECT-TYPE
SYNTAX INTEGER(-10..10)
ACCESS read-write
STATUS mandatory
DESCRIPTION "Cooling setpoint offset "
::= { nightModeConfig 7 }
coolingModenm OBJECT-TYPE
SYNTAX INTEGER(0..3)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Freecooling. 1 - Standard. 2 - Power save. 3 - Aircon. "
::= { nightModeConfig 8 }
enablenm OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Disable. 1 - Enable. "
::= { nightModeConfig 9 }
--
-- Controller-CC3000 : networkConfig
saveReloadConfNW OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Discard modifications, 1 - Save Modifications. Configuration reloaded "
::= { networkConfig 1 }
dhcpenable OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-write
STATUS mandatory
DESCRIPTION "0 - Static IP, 1 - Dynamic IP "
::= { networkConfig 2 }
ipaddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "System IP Address"
::= { networkConfig 3 }
subnetmask OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "Sub-net Mask "
::= { networkConfig 4 }
gatewayIPaddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "Default Gateway IP Address"
::= { networkConfig 5 }
ntpIPaddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "DNS IP Address"
::= { networkConfig 6 }
snmpPort OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION "SNMP Agent Port"
::= { networkConfig 7 }
trapServer1IPaddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "SNMP TRAP manager 1 IP address"
::= { networkConfig 8 }
trapServer1port OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION "SNMP TRAP manager 1 Port Number"
::= { networkConfig 9 }
trapServer2IPaddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "SNMP TRAP manager 2 IP address"
::= { networkConfig 10 }
trapServer2port OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION "SNMP TRAP manager 2 Port Number"
::= { networkConfig 11 }
trapServer3IPaddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "SNMP TRAP manager 3 IP address"
::= { networkConfig 12 }
trapServer3port OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION "SNMP TRAP manager 3 Port Number"
::= { networkConfig 13 }
snmpCommunity OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "SNMP Read/write Community string"
::= { networkConfig 14 }
hostName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "System Netwrok Host name"
::= { networkConfig 15 }
--
-- Controller-CC3000 : trapError
errorNumber OBJECT-TYPE
SYNTAX INTEGER {
VoltageLow (1),
VoltageHigh (2),
TemprLow (3),
TemprLimit1 (4),
TemprLimit2 (5),
TemprLimit3 (6),
HumidLow (7),
HumidHigh (8),
FltrPressure1 (9),
FltPressure2 (10),
Fan1 (11),
Fan2 (12),
OnboardSens (13),
RoomSens (14),
HotspotSens (15),
Ambient1Sens (16),
Ambient2Sens (17),
Dig1IP (18),
Dig2IP (19),
Dig3IP (20),
FilterIP1 (21),
FilterIP2 (22),
Network (23),
Intstorage (24),
SDCard (25) }
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
" Error Number corresponding to CC3000 controller Error."
::= { trapError 1 }
status OBJECT-TYPE
SYNTAX INTEGER { ALARMset (1), ALARMclear (0) }
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
" Error Status Active/SET or Inactive/CLEAR."
::= { trapError 2 }
value OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
" Value Corresponding to Error Occurance Instance."
::= { trapError 3 }
info OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
" Description of Current Error."
::= { trapError 4 }
cc3000Trap TRAP-TYPE
ENTERPRISE danthermCooling
VARIABLES {hostName, errorNumber, status, value, info }
DESCRIPTION "Trap From CC300 Controller. Contains TRAP information "
REFERENCE "None"
::= 1
END